Get your motor running
WHITE PAPER SERIES
Part 3: Motor starting solutions
White Paper Series www.aucom.com 1
James Archer
Business Development
Contact me via j.archer@aucom.com
New Zealand
123 Wrights Road, PO Box 80208,
Christchurch 8440, New Zealand
T +64 3 338 8280 F +64 3 338 8104
China
203-1 JH Plaza, 2008 Huqingping Road,
Shanghai 201702, China
T +86 21 5877 5178 F +86 21 5877 6378
Germany
Borsigstraße 6, 48324 Sendenhorst, Germany
T +49 2526 93880 140 F +49 2526 93880 100
Middle East
10th Floor, Swiss Tower, Jumeirah Lakes Towers,
Dubai, UAE
T +971 4279 8349 F +971 4279 8399
North America
2528 Lovi Road, Building 2-2A,
Freedom, PA 15042, USA
T 855 928 2666 (855 9 AUCOM NA), +1 724 987 4952
F +1 724 510 3005
https://my.aucom.com
For more information and your local contact visit www.aucom.com
The starting function of motors is often misunderstood, impacting motor
performance and compromising energy efficiency.
We’re delivering a series of technical white papers to provide an introduction to the
theory of starting motors, based on the work of electronics design expert Mark
Empson, one of AuCom’s founders in 1978.
There’s more information on our website, or you can follow us on Twitter
@softstarters. You can also talk to your local distributor of AuCom products.
A directory is available at www.aucom.com.
Thanks for reading.
White Paper Series www.aucom.com 2
Table of contents
Full voltage starting - DOL starters	 4
Reduced voltage starting	 5
Primary resistance starters	 7
Auto-transformer starters	 8
Star-delta starters	 9
Solid state soft starters	 10
Summary	 11
White Paper Series www.aucom.com 3
There are many misconceptions about motor starting. It is often believed that the
start current of a motor under full voltage conditions depends on the driven load,
but this is totally incorrect.
Motor starting
The start current of the motor depends on the
motor design, rotor speed and stator voltage
from zero speed until full speed is reached.
The load only influences the time taken for the
motor to reach full speed. The current/speed
curve of the motor is independent of
all external influences other than
stator voltage.
The motor will always initially draw locked
rotor current (LRC) when started direct-on-
line (DOL). The current will stay at LRC as the
motor begins to accelerate, and fall as the
motor approaches full speed.
For many induction motors the current does
not fall significantly until the motor speed is
over 90%.
Starting an unloaded motor DOL is just as
severe on the supply as starting a fully loaded
motor, except that the overload is for a shorter
time. NB: Some clamp type ammeters with
slow response times do not show the true
start current.
White Paper Series www.aucom.com 4
FULL VOLTAGE STARTING:
DOL STARTERS
The simplest form of motor starter is the
full voltage direct-on-line (DOL) or
across-the-line starter, consisting of an
isolation contactor and motor overload
protection device. In some industries DOL
starters are used extensively. However in
many situations full voltage starting is not
permitted by the power authority due to
the high starting currents and the voltage
disturbances they cause.
The DOL starter causes a current transition
from zero to LRC at the instant of contactor
closure. This current typically ranges from
600% to 900% FLC. The result is a voltage
transient induced in the supply by the fast
rising current transient, and a voltage
deflection of six to nine times that expected
under full load conditions.
6 x FLC
10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
Start
Current
Start
Torque
5 x FLC
4 x FLC
3 x FLC
2 x FLC
FLC
Rotor Speed
Contactor MotorThermal overload
M
Thermal
overload
Run contactor
and start
resistors
Full voltage starting also causes a torque
transient from zero to locked rotor torque
(LRT) at the instant of contactor closure. The
instantaneous torque application results
in a severe mechanical shock to the motor
drive system and the machine. The damage
from the torque transient is more severe
than the damage from the maximum torque
amplitude.
White Paper Series www.aucom.com 5
REDUCED VOLTAGE STARTING
Full voltage starting of induction motors results in maximum start torque,
maximum start current and minimum start time. Electromechanical reduced
voltage starting reduces start current and start torque, and increases start time.
Three traditional methods of reduced voltage
starting are commonly used:
-- Primary resistance starting
-- Auto-transformer starting
-- Star-delta starting
Reduced voltage starting is used extensively
and in many areas is mandatory. The use of
reduced voltage starting has been promoted
as a means of reducing power supply voltage
disturbances resulting from motor starting.
In reality the benefits are marginal due to the
misapplication of reduced voltage starters.
Many installations would suffer fewer
disturbances if a full voltage starter replaced
the poorly applied reduced voltage starting
system.
The reduced voltage starter must be able
to accelerate the motor to almost full speed
before stepping to full voltage. A step to full
voltage at much less than rated motor speed
will result in a current step that can be very
close to LRC.
Switching to full voltage at 80% speed results
in a current of typically 75% LRC, or 500%
FLC. At 50% speed, the current would be
90% LRC. The maximum current will be
significantly reduced only if the changeover
occurs at a rotor speed of 90% or more.
The speed of the motor at changeover
depends on the torque of the motor at the
reduced voltage, and the speed/torque curve
of the load. If the time in the reduced voltage
is too short, the motor may not have time to
accelerate to the speed where the available
torque equals the load torque, resulting in a
premature transition to full voltage.
The two controllable parameters which
determine the reduced voltage starter’s
performance are therefore start time and
start voltage. If either of these parameters
is not correctly set, then the reduced voltage
starter is of limited advantage.
The transition from the reduced voltage to full
voltage can be open transition switching or
closed transition switching.
White Paper Series www.aucom.com 6
Open transition switching occurs when the
starter goes through an open circuit stage
in the switching sequence. There are three
stages:
1.	 Connect to the reduced voltage
2.	 Disconnect from the reduced voltage 		
(open circuit)
3.	 Connect to the full voltage
Open transition starting causes severe
current and torque transients which can
be far more detrimental to the supply and
the mechanical equipment than full voltage
starting. When the motor is spinning and then
disconnected from the supply, it acts as a
generator with an output voltage which may
be the same amplitude as the supply.
The frequency of the voltage generated by
the motor depends on the motor speed.
The voltage generated by the motor during
the open transition decays to zero slowly
and at the time of reclose there can still
be significant voltage present at the motor
terminals. As the frequency of the voltage
generated by the motor will always be less
than the supply frequency there will invariably
be an instantaneous voltage difference
between the motor terminals and the supply.
The voltage generated by the motor at the
instant of reclose may be equal to the supply
voltage but exactly out of phase. This equates
to reclosing with twice the supply voltage on
the motor. The result is a current transient
of 200% LRC and a torque transient of 400%
LRT. The transients associated with open
transition starters are responsible for many
of the supply disturbances and mechanical
breakdowns experienced in industry.
The closed transition starter does not have
an open circuit step in changing from the
reduced voltage to the full voltage. During the
transition period the starter provides bridging
impedance between the supply and motor to
eliminate the open circuit.
White Paper Series www.aucom.com 7
PRIMARY RESISTANCE STARTERS
The motor current is equal to the line current
and the starting torque is reduced by the
square of the current reduction ratio. The
current reduction depends on the ratio of the
motor impedance to the sum of the added
primary resistance and motor impedance.
As the motor accelerates, the stator
impedance increases, resulting in increasing
stator voltage with speed. Once the motor
is up to full speed, the resistors are bridged
by a second contactor to supply full voltage
to the motor.
The initial start voltage is determined by the
value of the resistors used. If the resistors
are too high in value, there will be insufficient
torque to accelerate the motor to full speed.
In this case, the step to full voltage will result
in a high current and high torque step.
The reduced voltage start time is controlled
by a preset timer which must be correctly set
for the application. If the time is too short,
the motor will not have achieved full speed
before the resistors are bridged. If the time
is too long, the excessive start time results
in unnecessary motor and resistor heating.
Several stages of resistance can be used and
bridged in steps to control the current and
torque more accurately, and so minimise the
magnitude of the current and torque steps.
Primary resistance starters dissipate a lot of
energy during start due to the high current
through the resistors, and the high voltage
across the resistors. The resistors may be
wound, cast or liquid resistors. For extended
times or frequent starts, the resistors are
physically large and must be well ventilated.
Primary resistance starters are closed
transition starters, so they are not subject
to reclose transients.
Start
Current
Start
Torque
CURRENT
TORQUE
2 x FLT
FLT
Rotor Speed
FAN SPEED/TORQUE CURVE
Primary resistance starter designed for
starting current 4 x FLC
6 x FLC
10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
5 x FLC
4 x FLC
3 x FLC
2 x FLC
FLC
CURRENT
TORQUE
2 x FLT
FLT
FAN SPEED/TORQUE CURVE
Primary resistance starter designed for
starting current 3 x FLC
6 x FLC
10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
Start
Current
Start
Torque
5 x FLC
4 x FLC
3 x FLC
2 x FLC
FLC
Rotor Speed
MotorThermal
overload
Run contactor
and start
resistors
Main
contactor
M
The primary resistance starter is one step
beyond the DOL starter. Resistors are
connected in series with each phase, between
the isolation contactor and the motor. The
resistors limit the start current and torque.
White Paper Series www.aucom.com 8
Open transition
Run
contactor
Start
contactor (B)
Start
contactor (A)
3Φ auto-transformer
Motor
M
CURRENT
TORQUE
2 x FLT
FLT
FAN SPEED/TORQUE CURVE
Auto-transformer starter on 50% tap
Start
Current
Start
Torque
Rotor Speed
6 x FLC
10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
5 x FLC
4 x FLC
3 x FLC
2 x FLC
FLC
CURRENT
TORQUE
2 x FLT
FLT
FAN SPEED/TORQUE CURVE
Auto-transformer starter on 66% tap
6 x FLC
10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
Start
Current
Start
Torque
5 x FLC
4 x FLC
3 x FLC
2 x FLC
FLC
Rotor Speed
AUTO-TRANSFORMER STARTERS
The motor current is reduced by the start
voltage reduction, and further reduced by the
transformer action resulting in a line current
less than the actual motor current. The initial
line current is equal to the LRC reduced
by the square of the voltage reduction. A
motor started on the 50% tap of an auto-
transformer will have a line start current of
25% LRC and a start torque
of 25% LRT.
During the motor acceleration period, the
starter may be designed to step through two
or more voltage steps from the initial start
tap to full voltage.
The simplest auto-transformer starters are
single step and often control only two phases.
The initial start voltage is set by tap selection,
and the start time is controlled by one or
more timers.
If the start voltage is too low, or the start time
incorrectly set, the transition to full voltage
will occur with the motor at less than full
speed, resulting in a high current and high
torque step. Auto-transformer starters are
usually rated for infrequent starting duties.
Frequent or extended start rated auto-
transformers are large and expensive due to
the heating in the transformer.
Auto-transformer starters can be
constructed as open transition starters
but usually the Korndorfer closed transition
configuration is used to eliminate the
reclose transients.
Closed transition
Run
contactor
Start
contactor (B)
Start
contactor (A)
3Φ auto-transformer
Motor
M
The auto-transformer starter uses an auto-
transformer to reduce the voltage during the
start period. The transformer has a range of
output voltage taps which can be used to set
the start voltage.
White Paper Series www.aucom.com 9
Main
contactor
Thermal
overload
Delta
contactor
Star
contactor
Motor
FAN SPEED/TORQUE CURVE
CURRENT
TORQUE
2 x FLT
FLT
Start
Current
Start
Torque
Rotor Speed
6 x FLC
10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
5 x FLC
4 x FLC
3 x FLC
2 x FLC
FLC
STAR-DELTA STARTERS
The current and torque in the star
configuration are one third of the full voltage
current and torque when the motor is
connected in delta. The current and torque
for any one motor cannot be controlled to suit
the application. Only two possible choices are
available, star or delta configuration.
If there is insufficient torque available in star
configuration to accelerate the load to full
speed, a high starting torque motor such as
a double cage motor should be used. If the
motor does not reach full speed in star, the
transition from star to delta configuration
will result in a high current and high torque
step, defeating the purpose of reduced
voltage starting.
Most star-delta starters are open transition
starters so the transition from star to
delta results in very high current and
torque transients in addition to the high
step magnitudes. Closed transition star-
delta starters are rarely used due to their
increased complexity and cost. The closed
transition starter reduces the reclose effect
but does not improve the controllability of the
start parameters.
The star-delta starter is the most common
reduced voltage starter used in industry
because of its low cost. The star-delta
starter has traditionally met the requirement
for reduced voltage starting, but in many
installations the advantage of its use is
purely political.
The motor is initially connected in star
configuration and then after a preset time the
motor is disconnected from the supply and
reconnected in delta configuration.
White Paper Series www.aucom.com 10
SOLID STATE SOFT STARTERS
The solid state soft starter uses solid state AC
switches instead of fixed or liquid resistors.
The AC switches are triacs, reverse parallel
connected SCR-diode, or SCR-SCR circuits.
The voltage is controlled by variation of the
conduction angle of the SCRs or triacs.
The triac and SCR-SCR are both symmetric
controllers resulting in odd order harmonic
generation. The asymmetric control of the
SCR-diode AC switch causes even order
harmonic currents to flow in the motor and
supply. The even harmonics are undesirable
for motor control because of the increased
losses and heating induced in the motor and
supply transformers.
The AC switch has a very low power
dissipation compared to traditional primary
resistors and is controllable to give a motor
voltage from zero to full line voltage without
any steps or transients.
Solid state soft starters come in two control
formats:
-- Open loop control
-- Closed loop control
Open loop controllers, like traditional
electromechanical starters, operate following
a preset timed sequence. The most common
open loop system is the timed voltage ramp
where the voltage begins initially at a preset
start voltage and increases to line voltage at a
preset ramp rate.
Closed loop controllers monitor one or
more parameters during the start period
and modify the motor voltage to control the
starting characteristics.
Common closed loop controllers are:
-- Constant current
-- Current ramp
-- Constant acceleration
Solid state soft starters can be designed
to give greater starting duties than most
motors, and because of their linear voltage
control do not cause current or torque steps
or transients. Solid state soft starters are
transition-less.
MotorThermal
overload
AC switchesContactor
M
The solid state soft starter is similar to the
primary resistance starter in that it controls
the voltage applied to the motor by means
of impedance in series with each phase
connected to the motor.
White Paper Series www.aucom.com 11
It is possible to correctly apply and engineer electromechanical reduced voltage
starters so the torque and current magnitudes and transients are reduced to
acceptable levels. However the misapplication of motors and starters often results
in voltage flicker and deflections well in excess of those experienced with DOL
starting techniques.
Incorrectly installed and poorly calibrated electromechanical starters eventually
reach full voltage and DOL start the motor, acting as expensive DOL starters.
Reduced voltage starting is specified in order to reduce the electrical interference
caused by motor starting. It is also used in many applications to reduce the
mechanical damage caused by torque transients and steps. To achieve these
objectives the motor and starter must be correctly selected and commissioned for
optimum performance.
Summary
White Paper Series www.aucom.com 12
Notes
White Paper Series www.aucom.com 13
Notes
White Paper Series www.aucom.com 14
This paper is the third in a series of technical white papers published by AuCom as
an introduction to the theory of starting motors.
Previous papers cover:
- Reduced voltage starting of three phase induction motors
- Differing start torque requirements of machines and motor loads
Subsequent papers discuss the following topics:
- An overview of solid state soft starters
- Variable frequency control
To access these and other published motor control resources please visit our
website at www.aucom.com.
Get your motor running
white paper series
© 2017 AuCom Electronics Ltd. All Rights Reserved. As AuCom is continuously improving its products it reserves the right to modify or change the specification of its
products at any time without notice. The text, diagrams, images and any other literary or artistic works appearing in this document are protected by copyright. Users
may copy some of the material for their personal reference but may not copy or use material for any other purpose without the prior consent of AuCom Electronics
Ltd. AuCom endeavours to ensure that the information contained in this document including images is correct but does not accept any liability for error, omission or
differences with the finished product.
New Zealand
123 Wrights Road, PO Box 80208, Christchurch 8440, New Zealand
T +64 3 338 8280 F +64 3 338 8104
China
203-1 JH Plaza, 2008 Huqingping Road, Shanghai 201702, China
T +86 21 5877 5178 F +86 21 5877 6378
Germany
Borsigstraße 6, 48324 Sendenhorst, Germany
T +49 2526 93880 140 F +49 2526 93880 100
Middle East
10th Floor, Swiss Tower, Jumeirah Lakes Towers, Dubai, UAE
T +971 4279 8349 F +971 4279 8399
North America
2528 Lovi Road, Building 2-2A, Freedom, PA 15042, USA
T 855 928 2666 (855 9 AUCOM NA), +1 724 987 4952 F +1 724 510 3005
https://my.aucom.com
For more information and your local contact visit www.aucom.com

More Related Content

What's hot

Dol starter by kantiakapil
Dol  starter by kantiakapilDol  starter by kantiakapil
Dol starter by kantiakapilKapil Kantia
 
Diwan Annexure Starter panels Presentation Rev-1 Dt16-11-2014
Diwan Annexure Starter panels Presentation Rev-1 Dt16-11-2014Diwan Annexure Starter panels Presentation Rev-1 Dt16-11-2014
Diwan Annexure Starter panels Presentation Rev-1 Dt16-11-2014Sheikh Imran
 
Speed control of Induction motors
Speed control of Induction motorsSpeed control of Induction motors
Speed control of Induction motorsRaghav S
 
Alternating Current Machines Single Phasee
Alternating Current Machines Single PhaseeAlternating Current Machines Single Phasee
Alternating Current Machines Single PhaseeTalia Carbis
 
Speed Control Of Single Phase Induction Motor
Speed Control Of Single Phase Induction MotorSpeed Control Of Single Phase Induction Motor
Speed Control Of Single Phase Induction MotorBhuban Chandra Mohanta
 
Design of a low cost compact size starter for low power water pumps
Design of a low cost compact size starter for low power water pumpsDesign of a low cost compact size starter for low power water pumps
Design of a low cost compact size starter for low power water pumpseSAT Journals
 
Speed control 1 phase i.m. motor by integral ckt
Speed control 1 phase i.m. motor by integral cktSpeed control 1 phase i.m. motor by integral ckt
Speed control 1 phase i.m. motor by integral cktpavankolte
 
Alternating Current Machines 11&12
Alternating Current Machines 11&12Alternating Current Machines 11&12
Alternating Current Machines 11&12Talia Carbis
 
Single Phase Induction Motor
Single Phase Induction MotorSingle Phase Induction Motor
Single Phase Induction Motorprajpurkait
 
Speed control in 3 phase induction motor
Speed control in 3 phase induction motorSpeed control in 3 phase induction motor
Speed control in 3 phase induction motorKakul Gupta
 
Single Phase Induction Motor Speed Control
Single Phase Induction Motor Speed ControlSingle Phase Induction Motor Speed Control
Single Phase Induction Motor Speed ControlEdgefxkits & Solutions
 
kapil dev rawal
kapil dev rawal kapil dev rawal
kapil dev rawal jabi khan
 
SINGLE PHASE INDUCTION MOTOR
SINGLE PHASE INDUCTION MOTORSINGLE PHASE INDUCTION MOTOR
SINGLE PHASE INDUCTION MOTORRiyaRoy60
 
Speed Control of Induction Motor Drive Using Universal Controller
Speed Control of Induction Motor Drive Using Universal ControllerSpeed Control of Induction Motor Drive Using Universal Controller
Speed Control of Induction Motor Drive Using Universal ControllerArif Shahriar
 
Type of Single phase induction Motor
Type of Single phase induction MotorType of Single phase induction Motor
Type of Single phase induction MotorSmit Shah
 
Speed control of Three phase Induction motor using AC voltage regulator
Speed control of Three phase Induction motor using AC voltage regulatorSpeed control of Three phase Induction motor using AC voltage regulator
Speed control of Three phase Induction motor using AC voltage regulatorShivagee Raj
 

What's hot (20)

Dol starter by kantiakapil
Dol  starter by kantiakapilDol  starter by kantiakapil
Dol starter by kantiakapil
 
Project PPT
Project PPTProject PPT
Project PPT
 
Diwan Annexure Starter panels Presentation Rev-1 Dt16-11-2014
Diwan Annexure Starter panels Presentation Rev-1 Dt16-11-2014Diwan Annexure Starter panels Presentation Rev-1 Dt16-11-2014
Diwan Annexure Starter panels Presentation Rev-1 Dt16-11-2014
 
Speed control of Induction motors
Speed control of Induction motorsSpeed control of Induction motors
Speed control of Induction motors
 
Alternating Current Machines Single Phasee
Alternating Current Machines Single PhaseeAlternating Current Machines Single Phasee
Alternating Current Machines Single Phasee
 
Vk
VkVk
Vk
 
Speed Control Of Single Phase Induction Motor
Speed Control Of Single Phase Induction MotorSpeed Control Of Single Phase Induction Motor
Speed Control Of Single Phase Induction Motor
 
Design of a low cost compact size starter for low power water pumps
Design of a low cost compact size starter for low power water pumpsDesign of a low cost compact size starter for low power water pumps
Design of a low cost compact size starter for low power water pumps
 
Speed control 1 phase i.m. motor by integral ckt
Speed control 1 phase i.m. motor by integral cktSpeed control 1 phase i.m. motor by integral ckt
Speed control 1 phase i.m. motor by integral ckt
 
Day 3
Day 3Day 3
Day 3
 
Alternating Current Machines 11&12
Alternating Current Machines 11&12Alternating Current Machines 11&12
Alternating Current Machines 11&12
 
Single Phase Induction Motor
Single Phase Induction MotorSingle Phase Induction Motor
Single Phase Induction Motor
 
Speed control in 3 phase induction motor
Speed control in 3 phase induction motorSpeed control in 3 phase induction motor
Speed control in 3 phase induction motor
 
Single Phase Induction Motor Speed Control
Single Phase Induction Motor Speed ControlSingle Phase Induction Motor Speed Control
Single Phase Induction Motor Speed Control
 
kapil dev rawal
kapil dev rawal kapil dev rawal
kapil dev rawal
 
SINGLE PHASE INDUCTION MOTOR
SINGLE PHASE INDUCTION MOTORSINGLE PHASE INDUCTION MOTOR
SINGLE PHASE INDUCTION MOTOR
 
Single phase im-lecture_10_1
Single phase im-lecture_10_1Single phase im-lecture_10_1
Single phase im-lecture_10_1
 
Speed Control of Induction Motor Drive Using Universal Controller
Speed Control of Induction Motor Drive Using Universal ControllerSpeed Control of Induction Motor Drive Using Universal Controller
Speed Control of Induction Motor Drive Using Universal Controller
 
Type of Single phase induction Motor
Type of Single phase induction MotorType of Single phase induction Motor
Type of Single phase induction Motor
 
Speed control of Three phase Induction motor using AC voltage regulator
Speed control of Three phase Induction motor using AC voltage regulatorSpeed control of Three phase Induction motor using AC voltage regulator
Speed control of Three phase Induction motor using AC voltage regulator
 

Similar to Gymr motor starting_solutions

Motor StarterTypes and Technology of Motor Starter And Its Applications
Motor StarterTypes and Technology of Motor Starter And Its ApplicationsMotor StarterTypes and Technology of Motor Starter And Its Applications
Motor StarterTypes and Technology of Motor Starter And Its Applicationselprocus
 
COMPARATIVE STUDY OF INDUCTION MOTOR STARTERS USING MATLAB SIMULINK
COMPARATIVE STUDY OF INDUCTION MOTOR STARTERS USING MATLAB SIMULINKCOMPARATIVE STUDY OF INDUCTION MOTOR STARTERS USING MATLAB SIMULINK
COMPARATIVE STUDY OF INDUCTION MOTOR STARTERS USING MATLAB SIMULINKIJARIIT
 
International Journal of Computational Engineering Research(IJCER)
International Journal of Computational Engineering Research(IJCER)International Journal of Computational Engineering Research(IJCER)
International Journal of Computational Engineering Research(IJCER)ijceronline
 
Starter of an induction motor
Starter of an induction motor Starter of an induction motor
Starter of an induction motor sbpatel199688
 
Starting of 3-Phase Induction Motors
Starting of 3-Phase Induction MotorsStarting of 3-Phase Induction Motors
Starting of 3-Phase Induction Motorsmorin moli
 
star delta auto starter with forward reverse and motor protection
star delta auto starter with forward reverse and motor protectionstar delta auto starter with forward reverse and motor protection
star delta auto starter with forward reverse and motor protectionBHUPATI PRADHAN
 
Starting Time Calculation for Induction Motor.
Starting Time Calculation for Induction Motor.Starting Time Calculation for Induction Motor.
Starting Time Calculation for Induction Motor.IJERA Editor
 
Minimization of Starting Torque and Inrush Current of Induction Motor by Diff...
Minimization of Starting Torque and Inrush Current of Induction Motor by Diff...Minimization of Starting Torque and Inrush Current of Induction Motor by Diff...
Minimization of Starting Torque and Inrush Current of Induction Motor by Diff...ijtsrd
 
Motor Speed controllers
Motor Speed controllersMotor Speed controllers
Motor Speed controllersHemant Singh
 
Motor Control Centre
Motor Control CentreMotor Control Centre
Motor Control Centresalehkhan
 
Types of starters of 3 phase induction motor
Types of starters of 3 phase induction motorTypes of starters of 3 phase induction motor
Types of starters of 3 phase induction motormpsrekha83
 
Dolstarter 120614095755-phpapp01
Dolstarter 120614095755-phpapp01Dolstarter 120614095755-phpapp01
Dolstarter 120614095755-phpapp01Saleem din Meo
 
Starting method for 3 phase induction motor
Starting method for 3 phase induction motorStarting method for 3 phase induction motor
Starting method for 3 phase induction motorAhmed A.Hassan
 
Starting and speed control of induction motor.ppt
Starting and speed control of induction motor.pptStarting and speed control of induction motor.ppt
Starting and speed control of induction motor.pptdatamboli
 
three phase induction machine starter
three phase induction machine starterthree phase induction machine starter
three phase induction machine starterAditya More
 
Dol and star delta
Dol and star deltaDol and star delta
Dol and star deltaEr Ramgarhia
 
Presentation on starter
Presentation on starterPresentation on starter
Presentation on starteraftab alam
 

Similar to Gymr motor starting_solutions (20)

Motor StarterTypes and Technology of Motor Starter And Its Applications
Motor StarterTypes and Technology of Motor Starter And Its ApplicationsMotor StarterTypes and Technology of Motor Starter And Its Applications
Motor StarterTypes and Technology of Motor Starter And Its Applications
 
COMPARATIVE STUDY OF INDUCTION MOTOR STARTERS USING MATLAB SIMULINK
COMPARATIVE STUDY OF INDUCTION MOTOR STARTERS USING MATLAB SIMULINKCOMPARATIVE STUDY OF INDUCTION MOTOR STARTERS USING MATLAB SIMULINK
COMPARATIVE STUDY OF INDUCTION MOTOR STARTERS USING MATLAB SIMULINK
 
International Journal of Computational Engineering Research(IJCER)
International Journal of Computational Engineering Research(IJCER)International Journal of Computational Engineering Research(IJCER)
International Journal of Computational Engineering Research(IJCER)
 
Starter of an induction motor
Starter of an induction motor Starter of an induction motor
Starter of an induction motor
 
Starting of 3-Phase Induction Motors
Starting of 3-Phase Induction MotorsStarting of 3-Phase Induction Motors
Starting of 3-Phase Induction Motors
 
star delta auto starter with forward reverse and motor protection
star delta auto starter with forward reverse and motor protectionstar delta auto starter with forward reverse and motor protection
star delta auto starter with forward reverse and motor protection
 
Starting Time Calculation for Induction Motor.
Starting Time Calculation for Induction Motor.Starting Time Calculation for Induction Motor.
Starting Time Calculation for Induction Motor.
 
Minimization of Starting Torque and Inrush Current of Induction Motor by Diff...
Minimization of Starting Torque and Inrush Current of Induction Motor by Diff...Minimization of Starting Torque and Inrush Current of Induction Motor by Diff...
Minimization of Starting Torque and Inrush Current of Induction Motor by Diff...
 
Motor Speed controllers
Motor Speed controllersMotor Speed controllers
Motor Speed controllers
 
Motor Control Centre
Motor Control CentreMotor Control Centre
Motor Control Centre
 
Mech EE6365 EE lab_manual
Mech EE6365 EE lab_manualMech EE6365 EE lab_manual
Mech EE6365 EE lab_manual
 
Types of starters of 3 phase induction motor
Types of starters of 3 phase induction motorTypes of starters of 3 phase induction motor
Types of starters of 3 phase induction motor
 
Dolstarter 120614095755-phpapp01
Dolstarter 120614095755-phpapp01Dolstarter 120614095755-phpapp01
Dolstarter 120614095755-phpapp01
 
Starting method for 3 phase induction motor
Starting method for 3 phase induction motorStarting method for 3 phase induction motor
Starting method for 3 phase induction motor
 
Starting and speed control of induction motor.ppt
Starting and speed control of induction motor.pptStarting and speed control of induction motor.ppt
Starting and speed control of induction motor.ppt
 
three phase induction machine starter
three phase induction machine starterthree phase induction machine starter
three phase induction machine starter
 
Motor.ppt
Motor.pptMotor.ppt
Motor.ppt
 
MOTOR STARTER
MOTOR STARTERMOTOR STARTER
MOTOR STARTER
 
Dol and star delta
Dol and star deltaDol and star delta
Dol and star delta
 
Presentation on starter
Presentation on starterPresentation on starter
Presentation on starter
 

More from Luis Antonio González Mederos

Da handbook section_3_power_distribution_systems_757959_ena
Da handbook section_3_power_distribution_systems_757959_enaDa handbook section_3_power_distribution_systems_757959_ena
Da handbook section_3_power_distribution_systems_757959_enaLuis Antonio González Mederos
 
Da handbook section_3_power_distribution_systems_757959_ena
Da handbook section_3_power_distribution_systems_757959_enaDa handbook section_3_power_distribution_systems_757959_ena
Da handbook section_3_power_distribution_systems_757959_enaLuis Antonio González Mederos
 
{A1fad7c7 d7c8-4772-8e67-3a934e1341ca} wp027007-en_fin_oct2016
{A1fad7c7 d7c8-4772-8e67-3a934e1341ca} wp027007-en_fin_oct2016{A1fad7c7 d7c8-4772-8e67-3a934e1341ca} wp027007-en_fin_oct2016
{A1fad7c7 d7c8-4772-8e67-3a934e1341ca} wp027007-en_fin_oct2016Luis Antonio González Mederos
 
{76d7e191 801e-4032-8c0f-2e0e374a94fc} short-circuit_current_rating_wp033001_en
{76d7e191 801e-4032-8c0f-2e0e374a94fc} short-circuit_current_rating_wp033001_en{76d7e191 801e-4032-8c0f-2e0e374a94fc} short-circuit_current_rating_wp033001_en
{76d7e191 801e-4032-8c0f-2e0e374a94fc} short-circuit_current_rating_wp033001_enLuis Antonio González Mederos
 
{14dfe281 5214-4c9d-ae78-8fb4fe0a2c62} wp042001en-final_nov2014
{14dfe281 5214-4c9d-ae78-8fb4fe0a2c62} wp042001en-final_nov2014{14dfe281 5214-4c9d-ae78-8fb4fe0a2c62} wp042001en-final_nov2014
{14dfe281 5214-4c9d-ae78-8fb4fe0a2c62} wp042001en-final_nov2014Luis Antonio González Mederos
 
{0db3438a 3954-4fd2-8dea-8af7191aa256} motor-starter_for_usa_and_canada_39200...
{0db3438a 3954-4fd2-8dea-8af7191aa256} motor-starter_for_usa_and_canada_39200...{0db3438a 3954-4fd2-8dea-8af7191aa256} motor-starter_for_usa_and_canada_39200...
{0db3438a 3954-4fd2-8dea-8af7191aa256} motor-starter_for_usa_and_canada_39200...Luis Antonio González Mederos
 
Abb surge arresters product overview 1 hc0075750 ad en
Abb surge arresters   product overview 1 hc0075750 ad enAbb surge arresters   product overview 1 hc0075750 ad en
Abb surge arresters product overview 1 hc0075750 ad enLuis Antonio González Mederos
 

More from Luis Antonio González Mederos (20)

Rej603 pg 1_mdb07217-yn_e_ne
Rej603 pg 1_mdb07217-yn_e_neRej603 pg 1_mdb07217-yn_e_ne
Rej603 pg 1_mdb07217-yn_e_ne
 
Da handbook section_3_power_distribution_systems_757959_ena
Da handbook section_3_power_distribution_systems_757959_enaDa handbook section_3_power_distribution_systems_757959_ena
Da handbook section_3_power_distribution_systems_757959_ena
 
Zone concept broch_756780_lre_na
Zone concept broch_756780_lre_naZone concept broch_756780_lre_na
Zone concept broch_756780_lre_na
 
Substation commissioning1
Substation commissioning1Substation commissioning1
Substation commissioning1
 
Power transformer maintenance
Power transformer maintenancePower transformer maintenance
Power transformer maintenance
 
Da handbook section_3_power_distribution_systems_757959_ena
Da handbook section_3_power_distribution_systems_757959_enaDa handbook section_3_power_distribution_systems_757959_ena
Da handbook section_3_power_distribution_systems_757959_ena
 
E1 a
E1 aE1 a
E1 a
 
Abb white paper_dtc_motor_es_3aua000019548
Abb white paper_dtc_motor_es_3aua000019548Abb white paper_dtc_motor_es_3aua000019548
Abb white paper_dtc_motor_es_3aua000019548
 
Abb white paper_dtc_a4_20150414
Abb white paper_dtc_a4_20150414Abb white paper_dtc_a4_20150414
Abb white paper_dtc_a4_20150414
 
Abb softstartery pstx kat_en15
Abb softstartery pstx kat_en15Abb softstartery pstx kat_en15
Abb softstartery pstx kat_en15
 
{A1fad7c7 d7c8-4772-8e67-3a934e1341ca} wp027007-en_fin_oct2016
{A1fad7c7 d7c8-4772-8e67-3a934e1341ca} wp027007-en_fin_oct2016{A1fad7c7 d7c8-4772-8e67-3a934e1341ca} wp027007-en_fin_oct2016
{A1fad7c7 d7c8-4772-8e67-3a934e1341ca} wp027007-en_fin_oct2016
 
{76d7e191 801e-4032-8c0f-2e0e374a94fc} short-circuit_current_rating_wp033001_en
{76d7e191 801e-4032-8c0f-2e0e374a94fc} short-circuit_current_rating_wp033001_en{76d7e191 801e-4032-8c0f-2e0e374a94fc} short-circuit_current_rating_wp033001_en
{76d7e191 801e-4032-8c0f-2e0e374a94fc} short-circuit_current_rating_wp033001_en
 
{14dfe281 5214-4c9d-ae78-8fb4fe0a2c62} wp042001en-final_nov2014
{14dfe281 5214-4c9d-ae78-8fb4fe0a2c62} wp042001en-final_nov2014{14dfe281 5214-4c9d-ae78-8fb4fe0a2c62} wp042001en-final_nov2014
{14dfe281 5214-4c9d-ae78-8fb4fe0a2c62} wp042001en-final_nov2014
 
{0db3438a 3954-4fd2-8dea-8af7191aa256} motor-starter_for_usa_and_canada_39200...
{0db3438a 3954-4fd2-8dea-8af7191aa256} motor-starter_for_usa_and_canada_39200...{0db3438a 3954-4fd2-8dea-8af7191aa256} motor-starter_for_usa_and_canada_39200...
{0db3438a 3954-4fd2-8dea-8af7191aa256} motor-starter_for_usa_and_canada_39200...
 
Abb surge arresters product overview 1 hc0075750 ad en
Abb surge arresters   product overview 1 hc0075750 ad enAbb surge arresters   product overview 1 hc0075750 ad en
Abb surge arresters product overview 1 hc0075750 ad en
 
Abb lv breakers working with trip curves
Abb lv breakers working with trip curvesAbb lv breakers working with trip curves
Abb lv breakers working with trip curves
 
Abb b.g. controlled switching ed4
Abb b.g. controlled switching ed4Abb b.g. controlled switching ed4
Abb b.g. controlled switching ed4
 
Oil testing cat 2003 149-v02
Oil testing cat 2003 149-v02Oil testing cat 2003 149-v02
Oil testing cat 2003 149-v02
 
Motor phase tester_ug_en_v01
Motor phase tester_ug_en_v01Motor phase tester_ug_en_v01
Motor phase tester_ug_en_v01
 
Nafta power catalog_sc_en_v01
Nafta power catalog_sc_en_v01Nafta power catalog_sc_en_v01
Nafta power catalog_sc_en_v01
 

Recently uploaded

Sachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective IntroductionSachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective IntroductionDr.Costas Sachpazis
 
INFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETE
INFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETEINFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETE
INFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETEroselinkalist12
 
main PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidmain PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidNikhilNagaraju
 
Correctly Loading Incremental Data at Scale
Correctly Loading Incremental Data at ScaleCorrectly Loading Incremental Data at Scale
Correctly Loading Incremental Data at ScaleAlluxio, Inc.
 
An experimental study in using natural admixture as an alternative for chemic...
An experimental study in using natural admixture as an alternative for chemic...An experimental study in using natural admixture as an alternative for chemic...
An experimental study in using natural admixture as an alternative for chemic...Chandu841456
 
Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...VICTOR MAESTRE RAMIREZ
 
Application of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptxApplication of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptx959SahilShah
 
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxJoão Esperancinha
 
An introduction to Semiconductor and its types.pptx
An introduction to Semiconductor and its types.pptxAn introduction to Semiconductor and its types.pptx
An introduction to Semiconductor and its types.pptxPurva Nikam
 
Comparative Analysis of Text Summarization Techniques
Comparative Analysis of Text Summarization TechniquesComparative Analysis of Text Summarization Techniques
Comparative Analysis of Text Summarization Techniquesugginaramesh
 
8251 universal synchronous asynchronous receiver transmitter
8251 universal synchronous asynchronous receiver transmitter8251 universal synchronous asynchronous receiver transmitter
8251 universal synchronous asynchronous receiver transmitterShivangiSharma879191
 
CCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdf
CCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdfCCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdf
CCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdfAsst.prof M.Gokilavani
 
Electronically Controlled suspensions system .pdf
Electronically Controlled suspensions system .pdfElectronically Controlled suspensions system .pdf
Electronically Controlled suspensions system .pdfme23b1001
 
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdfCCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdfAsst.prof M.Gokilavani
 
TechTAC® CFD Report Summary: A Comparison of Two Types of Tubing Anchor Catchers
TechTAC® CFD Report Summary: A Comparison of Two Types of Tubing Anchor CatchersTechTAC® CFD Report Summary: A Comparison of Two Types of Tubing Anchor Catchers
TechTAC® CFD Report Summary: A Comparison of Two Types of Tubing Anchor Catcherssdickerson1
 
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdfCCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdfAsst.prof M.Gokilavani
 

Recently uploaded (20)

Sachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective IntroductionSachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
 
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCRCall Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
 
INFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETE
INFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETEINFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETE
INFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETE
 
main PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidmain PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfid
 
Correctly Loading Incremental Data at Scale
Correctly Loading Incremental Data at ScaleCorrectly Loading Incremental Data at Scale
Correctly Loading Incremental Data at Scale
 
An experimental study in using natural admixture as an alternative for chemic...
An experimental study in using natural admixture as an alternative for chemic...An experimental study in using natural admixture as an alternative for chemic...
An experimental study in using natural admixture as an alternative for chemic...
 
Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...
 
Application of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptxApplication of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptx
 
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
 
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptxExploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
 
An introduction to Semiconductor and its types.pptx
An introduction to Semiconductor and its types.pptxAn introduction to Semiconductor and its types.pptx
An introduction to Semiconductor and its types.pptx
 
Comparative Analysis of Text Summarization Techniques
Comparative Analysis of Text Summarization TechniquesComparative Analysis of Text Summarization Techniques
Comparative Analysis of Text Summarization Techniques
 
8251 universal synchronous asynchronous receiver transmitter
8251 universal synchronous asynchronous receiver transmitter8251 universal synchronous asynchronous receiver transmitter
8251 universal synchronous asynchronous receiver transmitter
 
CCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdf
CCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdfCCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdf
CCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdf
 
young call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Service
young call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Serviceyoung call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Service
young call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Service
 
Electronically Controlled suspensions system .pdf
Electronically Controlled suspensions system .pdfElectronically Controlled suspensions system .pdf
Electronically Controlled suspensions system .pdf
 
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
 
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdfCCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
 
TechTAC® CFD Report Summary: A Comparison of Two Types of Tubing Anchor Catchers
TechTAC® CFD Report Summary: A Comparison of Two Types of Tubing Anchor CatchersTechTAC® CFD Report Summary: A Comparison of Two Types of Tubing Anchor Catchers
TechTAC® CFD Report Summary: A Comparison of Two Types of Tubing Anchor Catchers
 
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdfCCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
 

Gymr motor starting_solutions

  • 1. Get your motor running WHITE PAPER SERIES Part 3: Motor starting solutions
  • 2. White Paper Series www.aucom.com 1 James Archer Business Development Contact me via j.archer@aucom.com New Zealand 123 Wrights Road, PO Box 80208, Christchurch 8440, New Zealand T +64 3 338 8280 F +64 3 338 8104 China 203-1 JH Plaza, 2008 Huqingping Road, Shanghai 201702, China T +86 21 5877 5178 F +86 21 5877 6378 Germany Borsigstraße 6, 48324 Sendenhorst, Germany T +49 2526 93880 140 F +49 2526 93880 100 Middle East 10th Floor, Swiss Tower, Jumeirah Lakes Towers, Dubai, UAE T +971 4279 8349 F +971 4279 8399 North America 2528 Lovi Road, Building 2-2A, Freedom, PA 15042, USA T 855 928 2666 (855 9 AUCOM NA), +1 724 987 4952 F +1 724 510 3005 https://my.aucom.com For more information and your local contact visit www.aucom.com The starting function of motors is often misunderstood, impacting motor performance and compromising energy efficiency. We’re delivering a series of technical white papers to provide an introduction to the theory of starting motors, based on the work of electronics design expert Mark Empson, one of AuCom’s founders in 1978. There’s more information on our website, or you can follow us on Twitter @softstarters. You can also talk to your local distributor of AuCom products. A directory is available at www.aucom.com. Thanks for reading.
  • 3. White Paper Series www.aucom.com 2 Table of contents Full voltage starting - DOL starters 4 Reduced voltage starting 5 Primary resistance starters 7 Auto-transformer starters 8 Star-delta starters 9 Solid state soft starters 10 Summary 11
  • 4. White Paper Series www.aucom.com 3 There are many misconceptions about motor starting. It is often believed that the start current of a motor under full voltage conditions depends on the driven load, but this is totally incorrect. Motor starting The start current of the motor depends on the motor design, rotor speed and stator voltage from zero speed until full speed is reached. The load only influences the time taken for the motor to reach full speed. The current/speed curve of the motor is independent of all external influences other than stator voltage. The motor will always initially draw locked rotor current (LRC) when started direct-on- line (DOL). The current will stay at LRC as the motor begins to accelerate, and fall as the motor approaches full speed. For many induction motors the current does not fall significantly until the motor speed is over 90%. Starting an unloaded motor DOL is just as severe on the supply as starting a fully loaded motor, except that the overload is for a shorter time. NB: Some clamp type ammeters with slow response times do not show the true start current.
  • 5. White Paper Series www.aucom.com 4 FULL VOLTAGE STARTING: DOL STARTERS The simplest form of motor starter is the full voltage direct-on-line (DOL) or across-the-line starter, consisting of an isolation contactor and motor overload protection device. In some industries DOL starters are used extensively. However in many situations full voltage starting is not permitted by the power authority due to the high starting currents and the voltage disturbances they cause. The DOL starter causes a current transition from zero to LRC at the instant of contactor closure. This current typically ranges from 600% to 900% FLC. The result is a voltage transient induced in the supply by the fast rising current transient, and a voltage deflection of six to nine times that expected under full load conditions. 6 x FLC 10% 20% 30% 40% 50% 60% 70% 80% 90% 100% Start Current Start Torque 5 x FLC 4 x FLC 3 x FLC 2 x FLC FLC Rotor Speed Contactor MotorThermal overload M Thermal overload Run contactor and start resistors Full voltage starting also causes a torque transient from zero to locked rotor torque (LRT) at the instant of contactor closure. The instantaneous torque application results in a severe mechanical shock to the motor drive system and the machine. The damage from the torque transient is more severe than the damage from the maximum torque amplitude.
  • 6. White Paper Series www.aucom.com 5 REDUCED VOLTAGE STARTING Full voltage starting of induction motors results in maximum start torque, maximum start current and minimum start time. Electromechanical reduced voltage starting reduces start current and start torque, and increases start time. Three traditional methods of reduced voltage starting are commonly used: -- Primary resistance starting -- Auto-transformer starting -- Star-delta starting Reduced voltage starting is used extensively and in many areas is mandatory. The use of reduced voltage starting has been promoted as a means of reducing power supply voltage disturbances resulting from motor starting. In reality the benefits are marginal due to the misapplication of reduced voltage starters. Many installations would suffer fewer disturbances if a full voltage starter replaced the poorly applied reduced voltage starting system. The reduced voltage starter must be able to accelerate the motor to almost full speed before stepping to full voltage. A step to full voltage at much less than rated motor speed will result in a current step that can be very close to LRC. Switching to full voltage at 80% speed results in a current of typically 75% LRC, or 500% FLC. At 50% speed, the current would be 90% LRC. The maximum current will be significantly reduced only if the changeover occurs at a rotor speed of 90% or more. The speed of the motor at changeover depends on the torque of the motor at the reduced voltage, and the speed/torque curve of the load. If the time in the reduced voltage is too short, the motor may not have time to accelerate to the speed where the available torque equals the load torque, resulting in a premature transition to full voltage. The two controllable parameters which determine the reduced voltage starter’s performance are therefore start time and start voltage. If either of these parameters is not correctly set, then the reduced voltage starter is of limited advantage. The transition from the reduced voltage to full voltage can be open transition switching or closed transition switching.
  • 7. White Paper Series www.aucom.com 6 Open transition switching occurs when the starter goes through an open circuit stage in the switching sequence. There are three stages: 1. Connect to the reduced voltage 2. Disconnect from the reduced voltage (open circuit) 3. Connect to the full voltage Open transition starting causes severe current and torque transients which can be far more detrimental to the supply and the mechanical equipment than full voltage starting. When the motor is spinning and then disconnected from the supply, it acts as a generator with an output voltage which may be the same amplitude as the supply. The frequency of the voltage generated by the motor depends on the motor speed. The voltage generated by the motor during the open transition decays to zero slowly and at the time of reclose there can still be significant voltage present at the motor terminals. As the frequency of the voltage generated by the motor will always be less than the supply frequency there will invariably be an instantaneous voltage difference between the motor terminals and the supply. The voltage generated by the motor at the instant of reclose may be equal to the supply voltage but exactly out of phase. This equates to reclosing with twice the supply voltage on the motor. The result is a current transient of 200% LRC and a torque transient of 400% LRT. The transients associated with open transition starters are responsible for many of the supply disturbances and mechanical breakdowns experienced in industry. The closed transition starter does not have an open circuit step in changing from the reduced voltage to the full voltage. During the transition period the starter provides bridging impedance between the supply and motor to eliminate the open circuit.
  • 8. White Paper Series www.aucom.com 7 PRIMARY RESISTANCE STARTERS The motor current is equal to the line current and the starting torque is reduced by the square of the current reduction ratio. The current reduction depends on the ratio of the motor impedance to the sum of the added primary resistance and motor impedance. As the motor accelerates, the stator impedance increases, resulting in increasing stator voltage with speed. Once the motor is up to full speed, the resistors are bridged by a second contactor to supply full voltage to the motor. The initial start voltage is determined by the value of the resistors used. If the resistors are too high in value, there will be insufficient torque to accelerate the motor to full speed. In this case, the step to full voltage will result in a high current and high torque step. The reduced voltage start time is controlled by a preset timer which must be correctly set for the application. If the time is too short, the motor will not have achieved full speed before the resistors are bridged. If the time is too long, the excessive start time results in unnecessary motor and resistor heating. Several stages of resistance can be used and bridged in steps to control the current and torque more accurately, and so minimise the magnitude of the current and torque steps. Primary resistance starters dissipate a lot of energy during start due to the high current through the resistors, and the high voltage across the resistors. The resistors may be wound, cast or liquid resistors. For extended times or frequent starts, the resistors are physically large and must be well ventilated. Primary resistance starters are closed transition starters, so they are not subject to reclose transients. Start Current Start Torque CURRENT TORQUE 2 x FLT FLT Rotor Speed FAN SPEED/TORQUE CURVE Primary resistance starter designed for starting current 4 x FLC 6 x FLC 10% 20% 30% 40% 50% 60% 70% 80% 90% 100% 5 x FLC 4 x FLC 3 x FLC 2 x FLC FLC CURRENT TORQUE 2 x FLT FLT FAN SPEED/TORQUE CURVE Primary resistance starter designed for starting current 3 x FLC 6 x FLC 10% 20% 30% 40% 50% 60% 70% 80% 90% 100% Start Current Start Torque 5 x FLC 4 x FLC 3 x FLC 2 x FLC FLC Rotor Speed MotorThermal overload Run contactor and start resistors Main contactor M The primary resistance starter is one step beyond the DOL starter. Resistors are connected in series with each phase, between the isolation contactor and the motor. The resistors limit the start current and torque.
  • 9. White Paper Series www.aucom.com 8 Open transition Run contactor Start contactor (B) Start contactor (A) 3Φ auto-transformer Motor M CURRENT TORQUE 2 x FLT FLT FAN SPEED/TORQUE CURVE Auto-transformer starter on 50% tap Start Current Start Torque Rotor Speed 6 x FLC 10% 20% 30% 40% 50% 60% 70% 80% 90% 100% 5 x FLC 4 x FLC 3 x FLC 2 x FLC FLC CURRENT TORQUE 2 x FLT FLT FAN SPEED/TORQUE CURVE Auto-transformer starter on 66% tap 6 x FLC 10% 20% 30% 40% 50% 60% 70% 80% 90% 100% Start Current Start Torque 5 x FLC 4 x FLC 3 x FLC 2 x FLC FLC Rotor Speed AUTO-TRANSFORMER STARTERS The motor current is reduced by the start voltage reduction, and further reduced by the transformer action resulting in a line current less than the actual motor current. The initial line current is equal to the LRC reduced by the square of the voltage reduction. A motor started on the 50% tap of an auto- transformer will have a line start current of 25% LRC and a start torque of 25% LRT. During the motor acceleration period, the starter may be designed to step through two or more voltage steps from the initial start tap to full voltage. The simplest auto-transformer starters are single step and often control only two phases. The initial start voltage is set by tap selection, and the start time is controlled by one or more timers. If the start voltage is too low, or the start time incorrectly set, the transition to full voltage will occur with the motor at less than full speed, resulting in a high current and high torque step. Auto-transformer starters are usually rated for infrequent starting duties. Frequent or extended start rated auto- transformers are large and expensive due to the heating in the transformer. Auto-transformer starters can be constructed as open transition starters but usually the Korndorfer closed transition configuration is used to eliminate the reclose transients. Closed transition Run contactor Start contactor (B) Start contactor (A) 3Φ auto-transformer Motor M The auto-transformer starter uses an auto- transformer to reduce the voltage during the start period. The transformer has a range of output voltage taps which can be used to set the start voltage.
  • 10. White Paper Series www.aucom.com 9 Main contactor Thermal overload Delta contactor Star contactor Motor FAN SPEED/TORQUE CURVE CURRENT TORQUE 2 x FLT FLT Start Current Start Torque Rotor Speed 6 x FLC 10% 20% 30% 40% 50% 60% 70% 80% 90% 100% 5 x FLC 4 x FLC 3 x FLC 2 x FLC FLC STAR-DELTA STARTERS The current and torque in the star configuration are one third of the full voltage current and torque when the motor is connected in delta. The current and torque for any one motor cannot be controlled to suit the application. Only two possible choices are available, star or delta configuration. If there is insufficient torque available in star configuration to accelerate the load to full speed, a high starting torque motor such as a double cage motor should be used. If the motor does not reach full speed in star, the transition from star to delta configuration will result in a high current and high torque step, defeating the purpose of reduced voltage starting. Most star-delta starters are open transition starters so the transition from star to delta results in very high current and torque transients in addition to the high step magnitudes. Closed transition star- delta starters are rarely used due to their increased complexity and cost. The closed transition starter reduces the reclose effect but does not improve the controllability of the start parameters. The star-delta starter is the most common reduced voltage starter used in industry because of its low cost. The star-delta starter has traditionally met the requirement for reduced voltage starting, but in many installations the advantage of its use is purely political. The motor is initially connected in star configuration and then after a preset time the motor is disconnected from the supply and reconnected in delta configuration.
  • 11. White Paper Series www.aucom.com 10 SOLID STATE SOFT STARTERS The solid state soft starter uses solid state AC switches instead of fixed or liquid resistors. The AC switches are triacs, reverse parallel connected SCR-diode, or SCR-SCR circuits. The voltage is controlled by variation of the conduction angle of the SCRs or triacs. The triac and SCR-SCR are both symmetric controllers resulting in odd order harmonic generation. The asymmetric control of the SCR-diode AC switch causes even order harmonic currents to flow in the motor and supply. The even harmonics are undesirable for motor control because of the increased losses and heating induced in the motor and supply transformers. The AC switch has a very low power dissipation compared to traditional primary resistors and is controllable to give a motor voltage from zero to full line voltage without any steps or transients. Solid state soft starters come in two control formats: -- Open loop control -- Closed loop control Open loop controllers, like traditional electromechanical starters, operate following a preset timed sequence. The most common open loop system is the timed voltage ramp where the voltage begins initially at a preset start voltage and increases to line voltage at a preset ramp rate. Closed loop controllers monitor one or more parameters during the start period and modify the motor voltage to control the starting characteristics. Common closed loop controllers are: -- Constant current -- Current ramp -- Constant acceleration Solid state soft starters can be designed to give greater starting duties than most motors, and because of their linear voltage control do not cause current or torque steps or transients. Solid state soft starters are transition-less. MotorThermal overload AC switchesContactor M The solid state soft starter is similar to the primary resistance starter in that it controls the voltage applied to the motor by means of impedance in series with each phase connected to the motor.
  • 12. White Paper Series www.aucom.com 11 It is possible to correctly apply and engineer electromechanical reduced voltage starters so the torque and current magnitudes and transients are reduced to acceptable levels. However the misapplication of motors and starters often results in voltage flicker and deflections well in excess of those experienced with DOL starting techniques. Incorrectly installed and poorly calibrated electromechanical starters eventually reach full voltage and DOL start the motor, acting as expensive DOL starters. Reduced voltage starting is specified in order to reduce the electrical interference caused by motor starting. It is also used in many applications to reduce the mechanical damage caused by torque transients and steps. To achieve these objectives the motor and starter must be correctly selected and commissioned for optimum performance. Summary
  • 13. White Paper Series www.aucom.com 12 Notes
  • 14. White Paper Series www.aucom.com 13 Notes
  • 15. White Paper Series www.aucom.com 14 This paper is the third in a series of technical white papers published by AuCom as an introduction to the theory of starting motors. Previous papers cover: - Reduced voltage starting of three phase induction motors - Differing start torque requirements of machines and motor loads Subsequent papers discuss the following topics: - An overview of solid state soft starters - Variable frequency control To access these and other published motor control resources please visit our website at www.aucom.com. Get your motor running white paper series
  • 16. © 2017 AuCom Electronics Ltd. All Rights Reserved. As AuCom is continuously improving its products it reserves the right to modify or change the specification of its products at any time without notice. The text, diagrams, images and any other literary or artistic works appearing in this document are protected by copyright. Users may copy some of the material for their personal reference but may not copy or use material for any other purpose without the prior consent of AuCom Electronics Ltd. AuCom endeavours to ensure that the information contained in this document including images is correct but does not accept any liability for error, omission or differences with the finished product. New Zealand 123 Wrights Road, PO Box 80208, Christchurch 8440, New Zealand T +64 3 338 8280 F +64 3 338 8104 China 203-1 JH Plaza, 2008 Huqingping Road, Shanghai 201702, China T +86 21 5877 5178 F +86 21 5877 6378 Germany Borsigstraße 6, 48324 Sendenhorst, Germany T +49 2526 93880 140 F +49 2526 93880 100 Middle East 10th Floor, Swiss Tower, Jumeirah Lakes Towers, Dubai, UAE T +971 4279 8349 F +971 4279 8399 North America 2528 Lovi Road, Building 2-2A, Freedom, PA 15042, USA T 855 928 2666 (855 9 AUCOM NA), +1 724 987 4952 F +1 724 510 3005 https://my.aucom.com For more information and your local contact visit www.aucom.com