HARMONIC MITIGATION FOR POWER QUALITY IMPROVEMENT
Jeel Contractor1
, P.N.Kapil 2
, Bhavin Shah3
1
M.Tech (PEMD) ,EE , Nirma University, Ahmedabad, India
2
Assistant Professor, EE , Nirma University, Ahmedabad, India
3
Director, PQS Electrolink (I) Pvt. Ltd. , Ahmedabad, India
Abstract
In every industries non-linear load such as single-phase diode rectifier, converters, inverters, low voltage power supplies, SMPS,
personal computers etc are exists. In every three-phase system the lowest and significant order of harmonic will be 5th
harmonic
after the fundamental. This harmonics incurs losses in the form of heat dissipation and also contribute to eddy currents and core
losses. This extra heat have significant impact in reducing the operating life of electrical instrument especially transformer
insulation. This paper provides information on harmonic mitigation techniques for power quality improvement.
Keywords: Harmonics, power quality, harmonic mitigation, De-tuned filter
--------------------------------------------------------------------***------------------------------------------------------------------
1. INTRODUCTION
In the recent time, there exist many different non-linear loads
in the different kinds of industries. Due to the non-linearity of
the loads it injects harmonics in the system and deteriorate
the power factor of the entire system. The first solution is
often possible by phase-shifting of the transformers and/or
the control of converter bridges or by the use of switching
devices with turn-off capability. External harmonic
compensation can be achieved by means of filters [1]. The
harmonic components have large current magnitudes. The
harmonics generated will be divided into three types that is
positive sequence harmonics, negative-sequence harmonics
and zero-sequence harmonics. The positive-sequence
harmonics current are the current harmonic components such
as 7th
, 13th
, 19th
and negative-sequence harmonics current
such as 5th
, 11th
, 17th
that is excessive in phase line which
increase the THD (Total Harmonic Distortion) of the system.
While, zero-sequence harmonics current that is triplen
harmonics such as 3th
, 9th
, 15th
will flows through the neutral
wire and may cause overheating on that wire.
2. HARMONICS
Harmonic frequencies are integral multiples of the
fundamental supply frequency, i.e. for a fundamental of 50
Hz, the third harmonic would be 150 Hz and the fifth
harmonic would be 250 Hz.
2.1 Types of Equipment that Generate Harmonics[2]
In the industries there are two types of loads. (1) Linear (2)
Non-linear. Linear loads will absorb the power linearly. And
the current waveforms are also sinusoidal. Whereas nonlinear
loads will absorb power in non-linear fashion and the current
waveform is not sinusoidal but it is distorted. Harmonic load
currents are generated by all non-linear loads. These include:
Single phase loads, e.g. Switched mode power supplies
(SMPS), Electronic fluorescent lighting ballasts , Small
uninterruptable power supplies (UPS) units.
Fig. 1 Harmonic spectrum of a personal computer
Fig. 2 harmonic spectrum of a typical six-pulse Bridge
IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308
_______________________________________________________________________________________
Volume: 04 Issue: 05 | May-2015, Available @ http://www.ijret.org 6
2.2 Harmonic Problems within the Installation
There are several common problem areas caused by
harmonics :
Problems caused by harmonic currents
1. Overloading of neutrals.
2. Overheating of transformers
3. Nuisance tripping of circuit breakers.
4. Over-stressing of power factor correction capacitors.
5.Skin effect
Problems caused by harmonic voltages
1. Voltage distortion.
2. Induction motors
3. Zero-crossing noise
2.3 Effect of Harmonics
 Tripping of circuit breakers and fuses
 Overloading / decrease of life time of transformer
 Overloading of transformer
 Losses in distribution equipment
 Excessive currents in the neutral conductor
 Measurements error in the metering system
2.4 Harmonic Mitigation Techniques
Table 1: HMTs and their main features [3][7]
HMT Main Features
Phase
multiplication
Effective to reduce low order
harmonics as long as there is a
balanced load
Passive filters
Improve power factor, reduce
high-frequency harmonics, large
size. If tuning reactors are not
used, instability may occurs due to
parallel resonance with the source
inductance. Performance depends
on the source impedance which is
usually not known accurately and
can vary with system changes.
Not appropriate for
cycloconverters.
Active filters
Improved power factor. Output
current can be controlled. Provide
stable operation against ac source
impedance variations, and fast
response irrespective of the order
and magnitude of the harmonics.
Appropriate for cycloconverter.
Initial and running costs are
usually higher than passive filters
Harmonic
Injection
Takes care of uncharacteristic
harmonics.
System impedance is no part of the
design criteria, may give rise to
low-order harmonics.
HMT with
PWM
Capable of obtaining harmonic
reduction of less than 1% of the
fundamental. Programmable to
eliminate specific harmonics.
3. POWER QUALITY ANALYSIS
The first step in solving harmonic related problems is to
perform an analysis to determine the specific needs of your
electrical distribution system. To determine capacitor and
filter requirements, it is necessary to establish the impedance
of the supply network and the value of each harmonic
current. Capacitor, reactor and filter bank equipment are then
specified under very detailed and stringent computer analysis
to meet your needs.
Analysis is carried out at Rashtriya Metal Industries Ltd.,
sarigan GIDC, Vapi. It is basically Metal Industry. Here
loads are generally AC and DC – small and medium sized
drives and normal lighting load. The transformer
specifications are 3.15MVA, 11/0.433 KV, 400Amp.
3.1 Readings
Graph of power factor, Voltage THD and Current THD of
main incomer are shown in below figures.
IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308
_______________________________________________________________________________________
Volume: 04 Issue: 05 | May-2015, Available @ http://www.ijret.org 7
Fig. 3 Power factor
Fig. 4 Voltage THD per phase
Fig. 5 Current THD per phase
IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308
_______________________________________________________________________________________
Volume: 04 Issue: 05 | May-2015, Available @ http://www.ijret.org 8
The Fig 3 shows the power factor at 135KVAR panel. And it
is almost -0.47 and at some point it differ very high. As we
know as per IEEE standards power factor must be between
0.90 and 0.95. But in this case power factor is quite less than
0.90 that means the reactive power drawn from supply is very
high and it needs to be reduced.[4]
4. SIMULATIONS
The simulation is done by considering a System of Rastriya
metal Industries pvt. Ltd.
The simulation is carried out using MATLAB/Simulink. In
this case the rectifier is used as a nonlinear load and the load
connected to RL load of 1000KW.
Block Diagram of the system shown in figure 6
Fig. 6 Block diagram of the system
MATLAB simulation is show in fig 7.
Fig. 7 Simulation of system (MATLAB/Simulink)
Fig. 8 Voltage and Current Waveform of the system
The power factor of the system is 0.76 , voltage THD is
16.32% and current THD is 11.16% .
Now simulate the same system with de-tuned filter and
improve the power factor of system and reduced the
harmonics.
The block diagram of the system with de-tuned filter is
shown in fig 9 and MATLAB simulation shown in fig 10.
IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308
_______________________________________________________________________________________
Volume: 04 Issue: 05 | May-2015, Available @ http://www.ijret.org 9
Fig. 9 Block diagram of the system with de-tuned filter
After implementation of de-tuned filter power factor is 0.98 ,
voltage THD is 3.09% and current THD is 3.70%
Fig. 10 Simulation of system with de-tuned filter (MATLAB/Simulink)
Fig. 11 Voltage and Current Waveform of the system with
de-tuned filter
5. HARDWARE IMPLEMENTATION
From power quality analysis and MATLAB simulation we
decide to make hybrid type power factor correction system
and for that APP capacitor(50 KVAr) , 14% reactor and
Thyristor switch modules are used.
IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308
_______________________________________________________________________________________
Volume: 04 Issue: 05 | May-2015, Available @ http://www.ijret.org 10
Fig. 12 Capacitors installed in panel
Fig. 13 TSM installed in panel
Fig. 14 Reactors installed in panel
After the implementation of all components in panel, panel
installed at the industry and then again power quality analysis
take place.
Now power factor improve to 0.86, voltage THD is 7.09%
and current THD is 8.07%
Fig. 15 power factor
Fig. 16 Voltage THD per phase
IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308
_______________________________________________________________________________________
Volume: 04 Issue: 05 | May-2015, Available @ http://www.ijret.org 11
Fig. 17 Current THD per phase
6. COMPARISON
Now, comparison of actual system without de-tuned filter
implementation, simulation of the system of the same
industry and final result after de-tuned filter implementation
is carried out.
Table I shows the Comparison of the actual system without
de-tuned filter implementation, simulation of the system of
the same industry and final result after de-tuned filter
implementation .
Table 2: Comparison
Actual System
P.F -0.47
Voltage THD
14.32
%
Current THD
16.78
%
Simulation
(With de-tuned
filter)
P.F 0.98
Voltage THD 3.09 %
Current THD 3.70 %
Final Result
(After panel
implementation )
P.F 0.86
Voltage THD 7.09 %
Current THD 8.07 %
7. CONCLUSION
From table II it can be seen that using de-tuned filter of
appropriate ratings, harmonics can decrease to very good
extent. Harmonics are reduced using Fixed capacitor, 14%
Reactors and TSM and so Among the all harmonics
mitigation techniques (Table I) passive filters technique is
very conventional and it is proved.
ACKNOWLEDGMENTS
The authors wish to express their sincere thanks to the PQS
Electrolink (I) pvt. ltd, Ahmedabad and Nirma university
and Rashtriya Metal Industries Ltd., sarigan GIDC, Vapi for
their cooperation in this work
REFERENCES
[1] Mauricio Areses Hirofumi Akagi, Edson Hirokazu
Watanabe. Instantaneous power theory and
applications to power conditioning. IEEE press,
(Chaper 3 and Chapter 4).
[2] Harmonics – Causes and effects. , David chapman ,
power quality management , Asia power quality
initiative
[3] Harmonic mitigation techniques for the improvement
of power quality of adjustable speed drives (ASDs)
Domijan, A. ; IEEE 5 19- 1992. Recommended
Practices and Requirements for Harmonic Control in
Electric Power Systems.
[4] M. Mohseni M. A. Zamani. Damped-type double
tuned filters design for hvdc systems. IEEE
Transactions on Power Electronics, Vol.9,No.3, May
1994
[5] MALCOLM CAMERON., Trends in power factor
correction with harmonic filtering.
[6] Power factor correction and harmonic filtering in
electrical plants. Technical Application Papers, ABB
[7] H. Fujita and H. Akagi. Design strategy for the
combined system of shunt passive and series active
filters. IEEE Transactions on Power Electronics,
Vol.5,No.3,June 1991.
[8] Wenjun Wu Jie Li Xiangqian Tong, JunyiXue.
Approach of optimal tuning frequency in single tuned
harmonic filter. Inter National Conference On Power
Engineering.
[9] David E. Rice,"Adjustable Speed Drive and power
Rectifier Harmonics – Their Effects on power
Systemm components."IEEE Trans on Ind Appl. Vol.
IA-22,No.1,Jan/Feb.1986
IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308
_______________________________________________________________________________________
Volume: 04 Issue: 05 | May-2015, Available @ http://www.ijret.org 12
BIOGRAPHIES
Jeel Contractor received the B.E. degree in
Electrical Engineering from C. K.
Pithawalla College of Engineering &
Technology, Surat, Gujarat, India, in 2013.
He is pursuing M.Tech in Electrical
engineering with specialization in Power
Electronics, machines and drives from Nirma university,
Ahmedabad,India
P. N. Kapil received the B.E. degree in
Electrical Engineering from Sankalchand
Patel College of Engineering, Visnagar,
Gujarat , India, in 2007, and the M.Tech.
degree in electrical engineering with
specialization in Power Apparatus and
Systems from Institute of Technology, Nirma University. He
has been a member of the Faculty at the Nirma Institute of
Technology, Ahmedabad, India.
Bhavin V. Shah has done graduation in
Electrical Engineering from L.D College
of Engineering, Ahmedabad, Gujarat,
India, in 1991. Started his career as
quality control engineer in distribution
transformer company, has spent more than
two decades in power quality field with companies like
SIEMENS & EPCOS. He provides solutions for Power factor
correction and harmonic filtering solutions for industries.
Currently, he is Technical Director of PQS Electrolink (I)
Pvt. Ltd, Ahmedabad.

More Related Content

What's hot

Power quality disturbances
Power quality disturbancesPower quality disturbances
Power quality disturbancesManasKumarPatro
 
Power quality (IV-EEE)
Power quality (IV-EEE)Power quality (IV-EEE)
Power quality (IV-EEE)betasam
 
Power quality issues in POWER SYSTEMS
Power quality issues in POWER SYSTEMSPower quality issues in POWER SYSTEMS
Power quality issues in POWER SYSTEMSCharan Sai Jc
 
Power Quality Issues _Literature Survey
Power Quality Issues _Literature SurveyPower Quality Issues _Literature Survey
Power Quality Issues _Literature SurveyKetan Bhavsar
 
POWER QUALITY IMPROVEMENT
POWER QUALITY IMPROVEMENTPOWER QUALITY IMPROVEMENT
POWER QUALITY IMPROVEMENTUday Wankar
 
Power quality & demand side management
Power quality & demand side managementPower quality & demand side management
Power quality & demand side managementMark Anthony Enoy
 
Power Quality and Monitoring
Power Quality and MonitoringPower Quality and Monitoring
Power Quality and Monitoringash08031996
 
Overview of power quality problems ppt
Overview of power quality problems pptOverview of power quality problems ppt
Overview of power quality problems pptMitesh Karmur
 
UG POWER QUALITY (EE2028) ppt
UG POWER QUALITY (EE2028) pptUG POWER QUALITY (EE2028) ppt
UG POWER QUALITY (EE2028) pptHarris Raj
 
Web based power quality monitoring system
Web based power quality monitoring systemWeb based power quality monitoring system
Web based power quality monitoring systemVikram Purohit
 
Power Quality Issues
Power Quality IssuesPower Quality Issues
Power Quality Issuesmaneesh001
 
Practical Power System Harmonics, Earthing and Power Quality - Problems and S...
Practical Power System Harmonics, Earthing and Power Quality - Problems and S...Practical Power System Harmonics, Earthing and Power Quality - Problems and S...
Practical Power System Harmonics, Earthing and Power Quality - Problems and S...Living Online
 
Voltage sag
Voltage sagVoltage sag
Voltage sagAJAL A J
 

What's hot (20)

Power quality disturbances
Power quality disturbancesPower quality disturbances
Power quality disturbances
 
Power quality (IV-EEE)
Power quality (IV-EEE)Power quality (IV-EEE)
Power quality (IV-EEE)
 
Power quality issues in POWER SYSTEMS
Power quality issues in POWER SYSTEMSPower quality issues in POWER SYSTEMS
Power quality issues in POWER SYSTEMS
 
Power Quality Issues _Literature Survey
Power Quality Issues _Literature SurveyPower Quality Issues _Literature Survey
Power Quality Issues _Literature Survey
 
POWER QUALITY IMPROVEMENT
POWER QUALITY IMPROVEMENTPOWER QUALITY IMPROVEMENT
POWER QUALITY IMPROVEMENT
 
Power Quality Standards
Power Quality StandardsPower Quality Standards
Power Quality Standards
 
Power quality
Power qualityPower quality
Power quality
 
Power quality
Power qualityPower quality
Power quality
 
Power quality 5
Power quality 5Power quality 5
Power quality 5
 
Power quality & demand side management
Power quality & demand side managementPower quality & demand side management
Power quality & demand side management
 
Power Quality and Monitoring
Power Quality and MonitoringPower Quality and Monitoring
Power Quality and Monitoring
 
Overview of power quality problems ppt
Overview of power quality problems pptOverview of power quality problems ppt
Overview of power quality problems ppt
 
UG POWER QUALITY (EE2028) ppt
UG POWER QUALITY (EE2028) pptUG POWER QUALITY (EE2028) ppt
UG POWER QUALITY (EE2028) ppt
 
Power quality 1
Power quality 1Power quality 1
Power quality 1
 
Web based power quality monitoring system
Web based power quality monitoring systemWeb based power quality monitoring system
Web based power quality monitoring system
 
Power Quality
Power QualityPower Quality
Power Quality
 
Power Quality Issues
Power Quality IssuesPower Quality Issues
Power Quality Issues
 
Practical Power System Harmonics, Earthing and Power Quality - Problems and S...
Practical Power System Harmonics, Earthing and Power Quality - Problems and S...Practical Power System Harmonics, Earthing and Power Quality - Problems and S...
Practical Power System Harmonics, Earthing and Power Quality - Problems and S...
 
Voltage sag
Voltage sagVoltage sag
Voltage sag
 
Ppt
PptPpt
Ppt
 

Similar to IJRET: Harmonic Mitigation for Power Quality Improvement

Harmonic Voltage Distortions in Power Systems Due to Non Linear Loads
Harmonic Voltage Distortions in Power Systems Due to Non Linear LoadsHarmonic Voltage Distortions in Power Systems Due to Non Linear Loads
Harmonic Voltage Distortions in Power Systems Due to Non Linear LoadsIJAPEJOURNAL
 
Application of passive harmonic filters to mitigate
Application of passive harmonic filters to mitigateApplication of passive harmonic filters to mitigate
Application of passive harmonic filters to mitigateeSAT Publishing House
 
Application of passive harmonic filters to mitigate source side current harmo...
Application of passive harmonic filters to mitigate source side current harmo...Application of passive harmonic filters to mitigate source side current harmo...
Application of passive harmonic filters to mitigate source side current harmo...eSAT Journals
 
Series Active Power Filter for Power Quality Improvement
Series Active Power Filter for Power Quality ImprovementSeries Active Power Filter for Power Quality Improvement
Series Active Power Filter for Power Quality ImprovementIRJET Journal
 
Improvement of power quality using series active power filter
Improvement of power quality using series active power filterImprovement of power quality using series active power filter
Improvement of power quality using series active power filtereSAT Publishing House
 
Power quality improvement in a weak bus system using facts controller
Power quality improvement in a weak bus system using facts controllerPower quality improvement in a weak bus system using facts controller
Power quality improvement in a weak bus system using facts controllereSAT Journals
 
Mitigation of power quality problem due to starting of induction motor
Mitigation of power quality problem due to starting of induction motorMitigation of power quality problem due to starting of induction motor
Mitigation of power quality problem due to starting of induction motoreSAT Journals
 
Multilevel inverter fed induction motor drives
Multilevel inverter fed induction motor drivesMultilevel inverter fed induction motor drives
Multilevel inverter fed induction motor driveseSAT Journals
 
Harmonic enhancement in microgrid with applications on sensitive loads
Harmonic enhancement in microgrid with applications on sensitive loadsHarmonic enhancement in microgrid with applications on sensitive loads
Harmonic enhancement in microgrid with applications on sensitive loadsIJECEIAES
 
Power quality improvement in a weak bus system using
Power quality improvement in a weak bus system usingPower quality improvement in a weak bus system using
Power quality improvement in a weak bus system usingeSAT Publishing House
 
Emc model for modern power electronic systems for
Emc model for modern power electronic systems forEmc model for modern power electronic systems for
Emc model for modern power electronic systems foreSAT Publishing House
 
Emc model for modern power electronic systems for harmonics, losses & emi...
Emc model for modern power electronic systems for harmonics, losses & emi...Emc model for modern power electronic systems for harmonics, losses & emi...
Emc model for modern power electronic systems for harmonics, losses & emi...eSAT Journals
 
Modeling control of automatic voltage regulator with proportional integral de...
Modeling control of automatic voltage regulator with proportional integral de...Modeling control of automatic voltage regulator with proportional integral de...
Modeling control of automatic voltage regulator with proportional integral de...eSAT Journals
 
IRJET-Power Quality Effects on Nonlinear Loads
IRJET-Power Quality Effects on Nonlinear LoadsIRJET-Power Quality Effects on Nonlinear Loads
IRJET-Power Quality Effects on Nonlinear LoadsIRJET Journal
 
Power Quality Improvement in Faulty Conditions using Tuned Harmonic Filters
Power Quality Improvement in Faulty Conditions using Tuned Harmonic FiltersPower Quality Improvement in Faulty Conditions using Tuned Harmonic Filters
Power Quality Improvement in Faulty Conditions using Tuned Harmonic FiltersIOSR Journals
 
A Novel Approach of Harmonic Reduction with Transformer Connected 3-Phase Mul...
A Novel Approach of Harmonic Reduction with Transformer Connected 3-Phase Mul...A Novel Approach of Harmonic Reduction with Transformer Connected 3-Phase Mul...
A Novel Approach of Harmonic Reduction with Transformer Connected 3-Phase Mul...IJMER
 
Design of Smart Filter for Cancellation of Current and Voltage Harmonics in T...
Design of Smart Filter for Cancellation of Current and Voltage Harmonics in T...Design of Smart Filter for Cancellation of Current and Voltage Harmonics in T...
Design of Smart Filter for Cancellation of Current and Voltage Harmonics in T...IRJET Journal
 
An Implementation of a Filter Design Passive LC in Reduce a Current Harmonisa
An Implementation of a Filter Design Passive LC in Reduce a Current Harmonisa An Implementation of a Filter Design Passive LC in Reduce a Current Harmonisa
An Implementation of a Filter Design Passive LC in Reduce a Current Harmonisa Universitas Pembangunan Panca Budi
 
2.Ourside.vip.Power quality improvement using dynamic voltage restorer.pdf
2.Ourside.vip.Power quality improvement using dynamic voltage restorer.pdf2.Ourside.vip.Power quality improvement using dynamic voltage restorer.pdf
2.Ourside.vip.Power quality improvement using dynamic voltage restorer.pdfssuser3793c8
 

Similar to IJRET: Harmonic Mitigation for Power Quality Improvement (20)

Harmonic Voltage Distortions in Power Systems Due to Non Linear Loads
Harmonic Voltage Distortions in Power Systems Due to Non Linear LoadsHarmonic Voltage Distortions in Power Systems Due to Non Linear Loads
Harmonic Voltage Distortions in Power Systems Due to Non Linear Loads
 
Application of passive harmonic filters to mitigate
Application of passive harmonic filters to mitigateApplication of passive harmonic filters to mitigate
Application of passive harmonic filters to mitigate
 
Application of passive harmonic filters to mitigate source side current harmo...
Application of passive harmonic filters to mitigate source side current harmo...Application of passive harmonic filters to mitigate source side current harmo...
Application of passive harmonic filters to mitigate source side current harmo...
 
Series Active Power Filter for Power Quality Improvement
Series Active Power Filter for Power Quality ImprovementSeries Active Power Filter for Power Quality Improvement
Series Active Power Filter for Power Quality Improvement
 
Improvement of power quality using series active power filter
Improvement of power quality using series active power filterImprovement of power quality using series active power filter
Improvement of power quality using series active power filter
 
Power quality improvement in a weak bus system using facts controller
Power quality improvement in a weak bus system using facts controllerPower quality improvement in a weak bus system using facts controller
Power quality improvement in a weak bus system using facts controller
 
Mitigation of power quality problem due to starting of induction motor
Mitigation of power quality problem due to starting of induction motorMitigation of power quality problem due to starting of induction motor
Mitigation of power quality problem due to starting of induction motor
 
J0361059064
J0361059064J0361059064
J0361059064
 
Multilevel inverter fed induction motor drives
Multilevel inverter fed induction motor drivesMultilevel inverter fed induction motor drives
Multilevel inverter fed induction motor drives
 
Harmonic enhancement in microgrid with applications on sensitive loads
Harmonic enhancement in microgrid with applications on sensitive loadsHarmonic enhancement in microgrid with applications on sensitive loads
Harmonic enhancement in microgrid with applications on sensitive loads
 
Power quality improvement in a weak bus system using
Power quality improvement in a weak bus system usingPower quality improvement in a weak bus system using
Power quality improvement in a weak bus system using
 
Emc model for modern power electronic systems for
Emc model for modern power electronic systems forEmc model for modern power electronic systems for
Emc model for modern power electronic systems for
 
Emc model for modern power electronic systems for harmonics, losses & emi...
Emc model for modern power electronic systems for harmonics, losses & emi...Emc model for modern power electronic systems for harmonics, losses & emi...
Emc model for modern power electronic systems for harmonics, losses & emi...
 
Modeling control of automatic voltage regulator with proportional integral de...
Modeling control of automatic voltage regulator with proportional integral de...Modeling control of automatic voltage regulator with proportional integral de...
Modeling control of automatic voltage regulator with proportional integral de...
 
IRJET-Power Quality Effects on Nonlinear Loads
IRJET-Power Quality Effects on Nonlinear LoadsIRJET-Power Quality Effects on Nonlinear Loads
IRJET-Power Quality Effects on Nonlinear Loads
 
Power Quality Improvement in Faulty Conditions using Tuned Harmonic Filters
Power Quality Improvement in Faulty Conditions using Tuned Harmonic FiltersPower Quality Improvement in Faulty Conditions using Tuned Harmonic Filters
Power Quality Improvement in Faulty Conditions using Tuned Harmonic Filters
 
A Novel Approach of Harmonic Reduction with Transformer Connected 3-Phase Mul...
A Novel Approach of Harmonic Reduction with Transformer Connected 3-Phase Mul...A Novel Approach of Harmonic Reduction with Transformer Connected 3-Phase Mul...
A Novel Approach of Harmonic Reduction with Transformer Connected 3-Phase Mul...
 
Design of Smart Filter for Cancellation of Current and Voltage Harmonics in T...
Design of Smart Filter for Cancellation of Current and Voltage Harmonics in T...Design of Smart Filter for Cancellation of Current and Voltage Harmonics in T...
Design of Smart Filter for Cancellation of Current and Voltage Harmonics in T...
 
An Implementation of a Filter Design Passive LC in Reduce a Current Harmonisa
An Implementation of a Filter Design Passive LC in Reduce a Current Harmonisa An Implementation of a Filter Design Passive LC in Reduce a Current Harmonisa
An Implementation of a Filter Design Passive LC in Reduce a Current Harmonisa
 
2.Ourside.vip.Power quality improvement using dynamic voltage restorer.pdf
2.Ourside.vip.Power quality improvement using dynamic voltage restorer.pdf2.Ourside.vip.Power quality improvement using dynamic voltage restorer.pdf
2.Ourside.vip.Power quality improvement using dynamic voltage restorer.pdf
 

More from eSAT Journals

Mechanical properties of hybrid fiber reinforced concrete for pavements
Mechanical properties of hybrid fiber reinforced concrete for pavementsMechanical properties of hybrid fiber reinforced concrete for pavements
Mechanical properties of hybrid fiber reinforced concrete for pavementseSAT Journals
 
Material management in construction – a case study
Material management in construction – a case studyMaterial management in construction – a case study
Material management in construction – a case studyeSAT Journals
 
Managing drought short term strategies in semi arid regions a case study
Managing drought    short term strategies in semi arid regions  a case studyManaging drought    short term strategies in semi arid regions  a case study
Managing drought short term strategies in semi arid regions a case studyeSAT Journals
 
Life cycle cost analysis of overlay for an urban road in bangalore
Life cycle cost analysis of overlay for an urban road in bangaloreLife cycle cost analysis of overlay for an urban road in bangalore
Life cycle cost analysis of overlay for an urban road in bangaloreeSAT Journals
 
Laboratory studies of dense bituminous mixes ii with reclaimed asphalt materials
Laboratory studies of dense bituminous mixes ii with reclaimed asphalt materialsLaboratory studies of dense bituminous mixes ii with reclaimed asphalt materials
Laboratory studies of dense bituminous mixes ii with reclaimed asphalt materialseSAT Journals
 
Laboratory investigation of expansive soil stabilized with natural inorganic ...
Laboratory investigation of expansive soil stabilized with natural inorganic ...Laboratory investigation of expansive soil stabilized with natural inorganic ...
Laboratory investigation of expansive soil stabilized with natural inorganic ...eSAT Journals
 
Influence of reinforcement on the behavior of hollow concrete block masonry p...
Influence of reinforcement on the behavior of hollow concrete block masonry p...Influence of reinforcement on the behavior of hollow concrete block masonry p...
Influence of reinforcement on the behavior of hollow concrete block masonry p...eSAT Journals
 
Influence of compaction energy on soil stabilized with chemical stabilizer
Influence of compaction energy on soil stabilized with chemical stabilizerInfluence of compaction energy on soil stabilized with chemical stabilizer
Influence of compaction energy on soil stabilized with chemical stabilizereSAT Journals
 
Geographical information system (gis) for water resources management
Geographical information system (gis) for water resources managementGeographical information system (gis) for water resources management
Geographical information system (gis) for water resources managementeSAT Journals
 
Forest type mapping of bidar forest division, karnataka using geoinformatics ...
Forest type mapping of bidar forest division, karnataka using geoinformatics ...Forest type mapping of bidar forest division, karnataka using geoinformatics ...
Forest type mapping of bidar forest division, karnataka using geoinformatics ...eSAT Journals
 
Factors influencing compressive strength of geopolymer concrete
Factors influencing compressive strength of geopolymer concreteFactors influencing compressive strength of geopolymer concrete
Factors influencing compressive strength of geopolymer concreteeSAT Journals
 
Experimental investigation on circular hollow steel columns in filled with li...
Experimental investigation on circular hollow steel columns in filled with li...Experimental investigation on circular hollow steel columns in filled with li...
Experimental investigation on circular hollow steel columns in filled with li...eSAT Journals
 
Experimental behavior of circular hsscfrc filled steel tubular columns under ...
Experimental behavior of circular hsscfrc filled steel tubular columns under ...Experimental behavior of circular hsscfrc filled steel tubular columns under ...
Experimental behavior of circular hsscfrc filled steel tubular columns under ...eSAT Journals
 
Evaluation of punching shear in flat slabs
Evaluation of punching shear in flat slabsEvaluation of punching shear in flat slabs
Evaluation of punching shear in flat slabseSAT Journals
 
Evaluation of performance of intake tower dam for recent earthquake in india
Evaluation of performance of intake tower dam for recent earthquake in indiaEvaluation of performance of intake tower dam for recent earthquake in india
Evaluation of performance of intake tower dam for recent earthquake in indiaeSAT Journals
 
Evaluation of operational efficiency of urban road network using travel time ...
Evaluation of operational efficiency of urban road network using travel time ...Evaluation of operational efficiency of urban road network using travel time ...
Evaluation of operational efficiency of urban road network using travel time ...eSAT Journals
 
Estimation of surface runoff in nallur amanikere watershed using scs cn method
Estimation of surface runoff in nallur amanikere watershed using scs cn methodEstimation of surface runoff in nallur amanikere watershed using scs cn method
Estimation of surface runoff in nallur amanikere watershed using scs cn methodeSAT Journals
 
Estimation of morphometric parameters and runoff using rs & gis techniques
Estimation of morphometric parameters and runoff using rs & gis techniquesEstimation of morphometric parameters and runoff using rs & gis techniques
Estimation of morphometric parameters and runoff using rs & gis techniqueseSAT Journals
 
Effect of variation of plastic hinge length on the results of non linear anal...
Effect of variation of plastic hinge length on the results of non linear anal...Effect of variation of plastic hinge length on the results of non linear anal...
Effect of variation of plastic hinge length on the results of non linear anal...eSAT Journals
 
Effect of use of recycled materials on indirect tensile strength of asphalt c...
Effect of use of recycled materials on indirect tensile strength of asphalt c...Effect of use of recycled materials on indirect tensile strength of asphalt c...
Effect of use of recycled materials on indirect tensile strength of asphalt c...eSAT Journals
 

More from eSAT Journals (20)

Mechanical properties of hybrid fiber reinforced concrete for pavements
Mechanical properties of hybrid fiber reinforced concrete for pavementsMechanical properties of hybrid fiber reinforced concrete for pavements
Mechanical properties of hybrid fiber reinforced concrete for pavements
 
Material management in construction – a case study
Material management in construction – a case studyMaterial management in construction – a case study
Material management in construction – a case study
 
Managing drought short term strategies in semi arid regions a case study
Managing drought    short term strategies in semi arid regions  a case studyManaging drought    short term strategies in semi arid regions  a case study
Managing drought short term strategies in semi arid regions a case study
 
Life cycle cost analysis of overlay for an urban road in bangalore
Life cycle cost analysis of overlay for an urban road in bangaloreLife cycle cost analysis of overlay for an urban road in bangalore
Life cycle cost analysis of overlay for an urban road in bangalore
 
Laboratory studies of dense bituminous mixes ii with reclaimed asphalt materials
Laboratory studies of dense bituminous mixes ii with reclaimed asphalt materialsLaboratory studies of dense bituminous mixes ii with reclaimed asphalt materials
Laboratory studies of dense bituminous mixes ii with reclaimed asphalt materials
 
Laboratory investigation of expansive soil stabilized with natural inorganic ...
Laboratory investigation of expansive soil stabilized with natural inorganic ...Laboratory investigation of expansive soil stabilized with natural inorganic ...
Laboratory investigation of expansive soil stabilized with natural inorganic ...
 
Influence of reinforcement on the behavior of hollow concrete block masonry p...
Influence of reinforcement on the behavior of hollow concrete block masonry p...Influence of reinforcement on the behavior of hollow concrete block masonry p...
Influence of reinforcement on the behavior of hollow concrete block masonry p...
 
Influence of compaction energy on soil stabilized with chemical stabilizer
Influence of compaction energy on soil stabilized with chemical stabilizerInfluence of compaction energy on soil stabilized with chemical stabilizer
Influence of compaction energy on soil stabilized with chemical stabilizer
 
Geographical information system (gis) for water resources management
Geographical information system (gis) for water resources managementGeographical information system (gis) for water resources management
Geographical information system (gis) for water resources management
 
Forest type mapping of bidar forest division, karnataka using geoinformatics ...
Forest type mapping of bidar forest division, karnataka using geoinformatics ...Forest type mapping of bidar forest division, karnataka using geoinformatics ...
Forest type mapping of bidar forest division, karnataka using geoinformatics ...
 
Factors influencing compressive strength of geopolymer concrete
Factors influencing compressive strength of geopolymer concreteFactors influencing compressive strength of geopolymer concrete
Factors influencing compressive strength of geopolymer concrete
 
Experimental investigation on circular hollow steel columns in filled with li...
Experimental investigation on circular hollow steel columns in filled with li...Experimental investigation on circular hollow steel columns in filled with li...
Experimental investigation on circular hollow steel columns in filled with li...
 
Experimental behavior of circular hsscfrc filled steel tubular columns under ...
Experimental behavior of circular hsscfrc filled steel tubular columns under ...Experimental behavior of circular hsscfrc filled steel tubular columns under ...
Experimental behavior of circular hsscfrc filled steel tubular columns under ...
 
Evaluation of punching shear in flat slabs
Evaluation of punching shear in flat slabsEvaluation of punching shear in flat slabs
Evaluation of punching shear in flat slabs
 
Evaluation of performance of intake tower dam for recent earthquake in india
Evaluation of performance of intake tower dam for recent earthquake in indiaEvaluation of performance of intake tower dam for recent earthquake in india
Evaluation of performance of intake tower dam for recent earthquake in india
 
Evaluation of operational efficiency of urban road network using travel time ...
Evaluation of operational efficiency of urban road network using travel time ...Evaluation of operational efficiency of urban road network using travel time ...
Evaluation of operational efficiency of urban road network using travel time ...
 
Estimation of surface runoff in nallur amanikere watershed using scs cn method
Estimation of surface runoff in nallur amanikere watershed using scs cn methodEstimation of surface runoff in nallur amanikere watershed using scs cn method
Estimation of surface runoff in nallur amanikere watershed using scs cn method
 
Estimation of morphometric parameters and runoff using rs & gis techniques
Estimation of morphometric parameters and runoff using rs & gis techniquesEstimation of morphometric parameters and runoff using rs & gis techniques
Estimation of morphometric parameters and runoff using rs & gis techniques
 
Effect of variation of plastic hinge length on the results of non linear anal...
Effect of variation of plastic hinge length on the results of non linear anal...Effect of variation of plastic hinge length on the results of non linear anal...
Effect of variation of plastic hinge length on the results of non linear anal...
 
Effect of use of recycled materials on indirect tensile strength of asphalt c...
Effect of use of recycled materials on indirect tensile strength of asphalt c...Effect of use of recycled materials on indirect tensile strength of asphalt c...
Effect of use of recycled materials on indirect tensile strength of asphalt c...
 

Recently uploaded

Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingrakeshbaidya232001
 
Internship report on mechanical engineering
Internship report on mechanical engineeringInternship report on mechanical engineering
Internship report on mechanical engineeringmalavadedarshan25
 
Current Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCLCurrent Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCLDeelipZope
 
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSKurinjimalarL3
 
High Profile Call Girls Nashik Megha 7001305949 Independent Escort Service Na...
High Profile Call Girls Nashik Megha 7001305949 Independent Escort Service Na...High Profile Call Girls Nashik Megha 7001305949 Independent Escort Service Na...
High Profile Call Girls Nashik Megha 7001305949 Independent Escort Service Na...Call Girls in Nagpur High Profile
 
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)Suman Mia
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxpurnimasatapathy1234
 
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINEMANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINESIVASHANKAR N
 
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube ExchangerStudy on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube ExchangerAnamika Sarkar
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024hassan khalil
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxAsutosh Ranjan
 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...Soham Mondal
 
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxJoão Esperancinha
 
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝soniya singh
 

Recently uploaded (20)

Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writing
 
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
 
Internship report on mechanical engineering
Internship report on mechanical engineeringInternship report on mechanical engineering
Internship report on mechanical engineering
 
Current Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCLCurrent Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCL
 
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
 
High Profile Call Girls Nashik Megha 7001305949 Independent Escort Service Na...
High Profile Call Girls Nashik Megha 7001305949 Independent Escort Service Na...High Profile Call Girls Nashik Megha 7001305949 Independent Escort Service Na...
High Profile Call Girls Nashik Megha 7001305949 Independent Escort Service Na...
 
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptxExploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
 
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptx
 
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINEMANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
 
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINEDJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
 
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube ExchangerStudy on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptx
 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
 
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
 
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
 

IJRET: Harmonic Mitigation for Power Quality Improvement

  • 1. IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308 _______________________________________________________________________________________ Volume: 04 Issue: 05 | May-2015, Available @ http://www.ijret.org 5 HARMONIC MITIGATION FOR POWER QUALITY IMPROVEMENT Jeel Contractor1 , P.N.Kapil 2 , Bhavin Shah3 1 M.Tech (PEMD) ,EE , Nirma University, Ahmedabad, India 2 Assistant Professor, EE , Nirma University, Ahmedabad, India 3 Director, PQS Electrolink (I) Pvt. Ltd. , Ahmedabad, India Abstract In every industries non-linear load such as single-phase diode rectifier, converters, inverters, low voltage power supplies, SMPS, personal computers etc are exists. In every three-phase system the lowest and significant order of harmonic will be 5th harmonic after the fundamental. This harmonics incurs losses in the form of heat dissipation and also contribute to eddy currents and core losses. This extra heat have significant impact in reducing the operating life of electrical instrument especially transformer insulation. This paper provides information on harmonic mitigation techniques for power quality improvement. Keywords: Harmonics, power quality, harmonic mitigation, De-tuned filter --------------------------------------------------------------------***------------------------------------------------------------------ 1. INTRODUCTION In the recent time, there exist many different non-linear loads in the different kinds of industries. Due to the non-linearity of the loads it injects harmonics in the system and deteriorate the power factor of the entire system. The first solution is often possible by phase-shifting of the transformers and/or the control of converter bridges or by the use of switching devices with turn-off capability. External harmonic compensation can be achieved by means of filters [1]. The harmonic components have large current magnitudes. The harmonics generated will be divided into three types that is positive sequence harmonics, negative-sequence harmonics and zero-sequence harmonics. The positive-sequence harmonics current are the current harmonic components such as 7th , 13th , 19th and negative-sequence harmonics current such as 5th , 11th , 17th that is excessive in phase line which increase the THD (Total Harmonic Distortion) of the system. While, zero-sequence harmonics current that is triplen harmonics such as 3th , 9th , 15th will flows through the neutral wire and may cause overheating on that wire. 2. HARMONICS Harmonic frequencies are integral multiples of the fundamental supply frequency, i.e. for a fundamental of 50 Hz, the third harmonic would be 150 Hz and the fifth harmonic would be 250 Hz. 2.1 Types of Equipment that Generate Harmonics[2] In the industries there are two types of loads. (1) Linear (2) Non-linear. Linear loads will absorb the power linearly. And the current waveforms are also sinusoidal. Whereas nonlinear loads will absorb power in non-linear fashion and the current waveform is not sinusoidal but it is distorted. Harmonic load currents are generated by all non-linear loads. These include: Single phase loads, e.g. Switched mode power supplies (SMPS), Electronic fluorescent lighting ballasts , Small uninterruptable power supplies (UPS) units. Fig. 1 Harmonic spectrum of a personal computer Fig. 2 harmonic spectrum of a typical six-pulse Bridge
  • 2. IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308 _______________________________________________________________________________________ Volume: 04 Issue: 05 | May-2015, Available @ http://www.ijret.org 6 2.2 Harmonic Problems within the Installation There are several common problem areas caused by harmonics : Problems caused by harmonic currents 1. Overloading of neutrals. 2. Overheating of transformers 3. Nuisance tripping of circuit breakers. 4. Over-stressing of power factor correction capacitors. 5.Skin effect Problems caused by harmonic voltages 1. Voltage distortion. 2. Induction motors 3. Zero-crossing noise 2.3 Effect of Harmonics  Tripping of circuit breakers and fuses  Overloading / decrease of life time of transformer  Overloading of transformer  Losses in distribution equipment  Excessive currents in the neutral conductor  Measurements error in the metering system 2.4 Harmonic Mitigation Techniques Table 1: HMTs and their main features [3][7] HMT Main Features Phase multiplication Effective to reduce low order harmonics as long as there is a balanced load Passive filters Improve power factor, reduce high-frequency harmonics, large size. If tuning reactors are not used, instability may occurs due to parallel resonance with the source inductance. Performance depends on the source impedance which is usually not known accurately and can vary with system changes. Not appropriate for cycloconverters. Active filters Improved power factor. Output current can be controlled. Provide stable operation against ac source impedance variations, and fast response irrespective of the order and magnitude of the harmonics. Appropriate for cycloconverter. Initial and running costs are usually higher than passive filters Harmonic Injection Takes care of uncharacteristic harmonics. System impedance is no part of the design criteria, may give rise to low-order harmonics. HMT with PWM Capable of obtaining harmonic reduction of less than 1% of the fundamental. Programmable to eliminate specific harmonics. 3. POWER QUALITY ANALYSIS The first step in solving harmonic related problems is to perform an analysis to determine the specific needs of your electrical distribution system. To determine capacitor and filter requirements, it is necessary to establish the impedance of the supply network and the value of each harmonic current. Capacitor, reactor and filter bank equipment are then specified under very detailed and stringent computer analysis to meet your needs. Analysis is carried out at Rashtriya Metal Industries Ltd., sarigan GIDC, Vapi. It is basically Metal Industry. Here loads are generally AC and DC – small and medium sized drives and normal lighting load. The transformer specifications are 3.15MVA, 11/0.433 KV, 400Amp. 3.1 Readings Graph of power factor, Voltage THD and Current THD of main incomer are shown in below figures.
  • 3. IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308 _______________________________________________________________________________________ Volume: 04 Issue: 05 | May-2015, Available @ http://www.ijret.org 7 Fig. 3 Power factor Fig. 4 Voltage THD per phase Fig. 5 Current THD per phase
  • 4. IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308 _______________________________________________________________________________________ Volume: 04 Issue: 05 | May-2015, Available @ http://www.ijret.org 8 The Fig 3 shows the power factor at 135KVAR panel. And it is almost -0.47 and at some point it differ very high. As we know as per IEEE standards power factor must be between 0.90 and 0.95. But in this case power factor is quite less than 0.90 that means the reactive power drawn from supply is very high and it needs to be reduced.[4] 4. SIMULATIONS The simulation is done by considering a System of Rastriya metal Industries pvt. Ltd. The simulation is carried out using MATLAB/Simulink. In this case the rectifier is used as a nonlinear load and the load connected to RL load of 1000KW. Block Diagram of the system shown in figure 6 Fig. 6 Block diagram of the system MATLAB simulation is show in fig 7. Fig. 7 Simulation of system (MATLAB/Simulink) Fig. 8 Voltage and Current Waveform of the system The power factor of the system is 0.76 , voltage THD is 16.32% and current THD is 11.16% . Now simulate the same system with de-tuned filter and improve the power factor of system and reduced the harmonics. The block diagram of the system with de-tuned filter is shown in fig 9 and MATLAB simulation shown in fig 10.
  • 5. IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308 _______________________________________________________________________________________ Volume: 04 Issue: 05 | May-2015, Available @ http://www.ijret.org 9 Fig. 9 Block diagram of the system with de-tuned filter After implementation of de-tuned filter power factor is 0.98 , voltage THD is 3.09% and current THD is 3.70% Fig. 10 Simulation of system with de-tuned filter (MATLAB/Simulink) Fig. 11 Voltage and Current Waveform of the system with de-tuned filter 5. HARDWARE IMPLEMENTATION From power quality analysis and MATLAB simulation we decide to make hybrid type power factor correction system and for that APP capacitor(50 KVAr) , 14% reactor and Thyristor switch modules are used.
  • 6. IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308 _______________________________________________________________________________________ Volume: 04 Issue: 05 | May-2015, Available @ http://www.ijret.org 10 Fig. 12 Capacitors installed in panel Fig. 13 TSM installed in panel Fig. 14 Reactors installed in panel After the implementation of all components in panel, panel installed at the industry and then again power quality analysis take place. Now power factor improve to 0.86, voltage THD is 7.09% and current THD is 8.07% Fig. 15 power factor Fig. 16 Voltage THD per phase
  • 7. IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308 _______________________________________________________________________________________ Volume: 04 Issue: 05 | May-2015, Available @ http://www.ijret.org 11 Fig. 17 Current THD per phase 6. COMPARISON Now, comparison of actual system without de-tuned filter implementation, simulation of the system of the same industry and final result after de-tuned filter implementation is carried out. Table I shows the Comparison of the actual system without de-tuned filter implementation, simulation of the system of the same industry and final result after de-tuned filter implementation . Table 2: Comparison Actual System P.F -0.47 Voltage THD 14.32 % Current THD 16.78 % Simulation (With de-tuned filter) P.F 0.98 Voltage THD 3.09 % Current THD 3.70 % Final Result (After panel implementation ) P.F 0.86 Voltage THD 7.09 % Current THD 8.07 % 7. CONCLUSION From table II it can be seen that using de-tuned filter of appropriate ratings, harmonics can decrease to very good extent. Harmonics are reduced using Fixed capacitor, 14% Reactors and TSM and so Among the all harmonics mitigation techniques (Table I) passive filters technique is very conventional and it is proved. ACKNOWLEDGMENTS The authors wish to express their sincere thanks to the PQS Electrolink (I) pvt. ltd, Ahmedabad and Nirma university and Rashtriya Metal Industries Ltd., sarigan GIDC, Vapi for their cooperation in this work REFERENCES [1] Mauricio Areses Hirofumi Akagi, Edson Hirokazu Watanabe. Instantaneous power theory and applications to power conditioning. IEEE press, (Chaper 3 and Chapter 4). [2] Harmonics – Causes and effects. , David chapman , power quality management , Asia power quality initiative [3] Harmonic mitigation techniques for the improvement of power quality of adjustable speed drives (ASDs) Domijan, A. ; IEEE 5 19- 1992. Recommended Practices and Requirements for Harmonic Control in Electric Power Systems. [4] M. Mohseni M. A. Zamani. Damped-type double tuned filters design for hvdc systems. IEEE Transactions on Power Electronics, Vol.9,No.3, May 1994 [5] MALCOLM CAMERON., Trends in power factor correction with harmonic filtering. [6] Power factor correction and harmonic filtering in electrical plants. Technical Application Papers, ABB [7] H. Fujita and H. Akagi. Design strategy for the combined system of shunt passive and series active filters. IEEE Transactions on Power Electronics, Vol.5,No.3,June 1991. [8] Wenjun Wu Jie Li Xiangqian Tong, JunyiXue. Approach of optimal tuning frequency in single tuned harmonic filter. Inter National Conference On Power Engineering. [9] David E. Rice,"Adjustable Speed Drive and power Rectifier Harmonics – Their Effects on power Systemm components."IEEE Trans on Ind Appl. Vol. IA-22,No.1,Jan/Feb.1986
  • 8. IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308 _______________________________________________________________________________________ Volume: 04 Issue: 05 | May-2015, Available @ http://www.ijret.org 12 BIOGRAPHIES Jeel Contractor received the B.E. degree in Electrical Engineering from C. K. Pithawalla College of Engineering & Technology, Surat, Gujarat, India, in 2013. He is pursuing M.Tech in Electrical engineering with specialization in Power Electronics, machines and drives from Nirma university, Ahmedabad,India P. N. Kapil received the B.E. degree in Electrical Engineering from Sankalchand Patel College of Engineering, Visnagar, Gujarat , India, in 2007, and the M.Tech. degree in electrical engineering with specialization in Power Apparatus and Systems from Institute of Technology, Nirma University. He has been a member of the Faculty at the Nirma Institute of Technology, Ahmedabad, India. Bhavin V. Shah has done graduation in Electrical Engineering from L.D College of Engineering, Ahmedabad, Gujarat, India, in 1991. Started his career as quality control engineer in distribution transformer company, has spent more than two decades in power quality field with companies like SIEMENS & EPCOS. He provides solutions for Power factor correction and harmonic filtering solutions for industries. Currently, he is Technical Director of PQS Electrolink (I) Pvt. Ltd, Ahmedabad.