Prolog
Power Quality Pioneering
Brian St. Pierre
Regional Business Development Manager
(517) 294-0087
bstpierre@ra.rockwell.com
Copyright © 2012 Rockwell Automation, Inc. All rights reserved.
Who …………and ………What:
SoftSwitching Technologies / RA
 A technical Innovator in the Power
Quality Field
 Founded in 1995 through University of
Wisconsin
 Manufacturing Facility and offices located
in Middleton, WI
 Acquired by Rockwell Automation on
March 12th, 2012
 Part of the Industrial Components
Business at Rockwell
Power Quality Monitoring
Notification + Reporting
Power Quality Mitigation
Eliminate Downtime
Protect Investment
3
“…the hottest
new
technology
comes from
startup
SoftSwitching
Technologies”
Copyright © 2012 Rockwell Automation, Inc. All rights reserved.
SoftSwitching’s / RA’s Product Line
4
1-50 A
Single Phase
25-200 A
3 Phase
400-2400 A
3 Phase
I-Sense Monitor
Copyright © 2012 Rockwell Automation, Inc. All rights reserved.
Food and Beverage
Aseptic Packaging
Dry Extrusion
Bakeries
Batch Processing
Automotive
Robots
Test
CNC Machining
Positioning Equipment
Semiconductor
Lithography
Process Tools
Facilities
Ovens
Healthcare
Imaging Equipment
Non Invasive
Generator Test Ride Through
Other
Pharmaceutical
Pulp and Paper
Oil and Gas
Plastics
Rule #1: All Factories Experience Voltage Sags
Rule #2: The DySC Will Make
- Any Component
- Any Machine
- Any Process
- Any Plant
On Average Break 10-14 Fewer Times Per Year
Key Applications and Industries
Copyright © 2012 Rockwell Automation, Inc. All rights reserved.
Revealing Power Quality as a
“Process Variable”
Copyright © 2012 Rockwell Automation, Inc. All rights reserved.
Power from Two Perspectives —
What is the difference?
 Power/Energy Management:
 Providing solutions that enable a customer to optimize the
consumption of energy in their plant or at a specific process.
 Power Quality Management:
 Providing solutions that eliminate “unscheduled downtime”
caused by both external and internal power quality
events/conditions that can impact the profitability of a plant or a
specific process.
 Both solutions have similar aspects or parts:
 Power Monitoring, Data organization or analysis through a tool or
software, *System optimization
 *Very different remediation solutions (Solving a different problem)
 Today we’ll focus on how Power Quality acts as a Process Variable!
7
Copyright © 2012 Rockwell Automation, Inc. All rights reserved.
The Consumer is Responsible for
Power Quality
 Utility cannot provide perfect power quality and are not
required to. (e.g., Wisconsin PSC 113.0703)
 Customers having equipment or operations that are sensitive to such voltage
fluctuations … may find it necessary to install, at their own expense, power
conditioning equipment or other modifications …
 Job is to “Keep the lights on.”
 Goals of Utility
 Deliver maximum energy through the existing infrastructure
 Maintain +/-10% (on average) voltage at service entrance
 Minimize outages longer than 2-5 minutes
 60.00 Hz, when averaged over 24 hours
 Keep large industrial customers satisfied
 Minimize large customers disrupting neighbors’ power quality
8
Copyright © 2012 Rockwell Automation, Inc. All rights reserved.
I-Grid (Monitoring the Power Grid with I-Sense)
 One pin per postal code
 Over 3000 I-Sense monitors active in the USA today
Copyright © 2012 Rockwell Automation, Inc. All rights reserved.
Healthcare’s i-Grid Network
(Today there are approximately 750 active sites)
Copyright © 2012 Rockwell Automation, Inc. All rights reserved.
The Story / “Background Basics”
FrequencyofOccurrence
Typical Incident Cost
$ $$ $$$ $$$$
LowVeryLowMediumHigh
Notching (Constant) Interruption (0.5 cycles – >1 hr)
Swell (0.5 cycles – 60s)
Noise (Constant)
Harmonics (Constant)
Transient (<50 ns – 5 ms)
Unbalance (Fluctuating)
Undervoltage (>1 minute)
Overvoltage (>1 minute)
Sag (0.5 cycles – 60s) EPRI (Electrical Power
Research Institute)
• Monitored 300 sites for 2+ years.
• 1993 study: 92% of all events were
voltage sags under 2 seconds
• 1995 study: 96% of all events were
voltage sags less than 2 seconds
Grid
Related
Facility
Related
11
Copyright © 2012 Rockwell Automation, Inc. All rights reserved.
Measuring Power Quality --
Voltage Sag (Dip) Characterization
 Sag - RMS voltage reduction between 1/2 cycle - 60 sec
 Magnitude and Duration
12
-1
-0.5
0
0.5
1
0 1 2 3 4 5 6 7 8
Duration: 4 Cycles
Magnitude: 60% Remaining
Copyright © 2012 Rockwell Automation, Inc. All rights reserved.
0.0
0.2
0.4
0.6
0.8
1.0
1 10 100 1000
Duration (ms)
Magnitude(perunit)
90%
Tracking Voltage Sag Events
13
Copyright © 2012 Rockwell Automation, Inc. All rights reserved.
Electrical Design Standards used in NA
(Sags Captured at High-Tech Mfg. Sites)
 Very few outages, still
many sags!
 1000 sag events from
15 Semi plants
 Avg. 5.4 events below
CBEMA per year…with
transmission-level
service!
 SEMI F47
source: International SEMATECH & EPRI, 1999
Copyright © 2012 Rockwell Automation, Inc. All rights reserved.
Plant Wall
480V Bus
1
2
3
Machine B
Machine C
PLC
Input
Output
Error Light
Intermittent Failure
Program Loss
Mis-feeds / Jams
Damaged Equipment
Downtime
XfrmrXfrmr
SensorsRelays Counters
Control
Feedback
Analog
Inputs
Digital
Inputs
My Machine or process just
went down but not others,
Why Not?
What broke?
What do I need to do?
Machine A
Typical Dilemma
Typical Manufacturing Plant Electrical and Controls Environment
Copyright © 2012 Rockwell Automation, Inc. All rights reserved.
The correlation between unscheduled
downtime and extreme weather is clear
Copyright © 2012 Rockwell Automation, Inc. All rights reserved.
Others like Drunk’n Utility Poles and wayward Construction
Cranes may not be visible on the way to work
Roughly ~60% of Power Quality
Problems are caused by Weather…
Copyright © 2012 Rockwell Automation, Inc. All rights reserved.
Equipment Failures
Copyright © 2012 Rockwell Automation, Inc. All rights reserved.
Or the much more common--Squirrels on Holiday
cause similar problems: Downtime and Damage.
Copyright © 2012 Rockwell Automation, Inc. All rights reserved.
And rare, but well-meaning Misguided Reindeer
Copyright © 2012 Rockwell Automation, Inc. All rights reserved.
Cuban Tree Frog chasing the “Corona”
21
Copyright © 2012 Rockwell Automation, Inc. All rights reserved.
Downstream of Switch: Outage
Upstream of Switch: Voltage Sag
How the Grid Works
230kV
Transmission
69kV
Transmission
13kV
Distribution
A
B
C
S
S
S
S
S
S
S
S
S
S
S
S
S
S S SS
S S S
S S
S
Up to 200 Miles
The Grid Self Heals within 2 seconds or
Trucks have to be sent out
Copyright © 2012 Rockwell Automation, Inc. All rights reserved.
-35%
-70%
-25%
The depth of your
Sag depends on
the distance you
are from the event
When Lightning Strikes, Squirrels Fry, or the
grid Shorts: You feel it
Copyright © 2012 Rockwell Automation, Inc. All rights reserved.
Past Year on Three Separate
Electrical Feeds in Durham NC
Copyright © 2012 Rockwell Automation, Inc. All rights reserved.
19 of 29 (63%) Events fell below the CBEMA curve
CBEMA
Curve
Copyright © 2012 Rockwell Automation, Inc. All rights reserved.
Confirmation and Corroboration
Copyright © 2012 Rockwell Automation, Inc. All rights reserved.
Friday May 31, 2013 Sag to 30%, (~10 Cycles)
Copyright © 2012 Rockwell Automation, Inc. All rights reserved.
Past Year in Lumberton NC
Copyright © 2012 Rockwell Automation, Inc. All rights reserved.
3 of 10 (30%) Events fell below the CBEMA curve
CBEMA
Curve
Copyright © 2012 Rockwell Automation, Inc. All rights reserved.
Past Year in New Bern NC
Copyright © 2012 Rockwell Automation, Inc. All rights reserved.
3 of 12 (25%) Events fell below the CBEMA curve
CBEMA
Curve
Copyright © 2012 Rockwell Automation, Inc. All rights reserved.
Past Year in Chapel Hill NC
Copyright © 2012 Rockwell Automation, Inc. All rights reserved.
3 of 10 (30%) Events fell below the CBEMA curve
CBEMA
Curve
Copyright © 2012 Rockwell Automation, Inc. All rights reserved.
Past 3 Months in Greensboro NC
Copyright © 2012 Rockwell Automation, Inc. All rights reserved.
3 of 3 (100%) Events fell below the CBEMA curve
CBEMA
Curve
Copyright © 2012 Rockwell Automation, Inc. All rights reserved.
Confirmation and Corroboration
Copyright © 2012 Rockwell Automation, Inc. All rights reserved.
Monday Feb 3, 2013 Sag to 58%, (~2.5 Cycles)
37
Copyright © 2012 Rockwell Automation, Inc. All rights reserved.
May 2011 to May 2012 in
Burlington NC
Copyright © 2012 Rockwell Automation, Inc. All rights reserved.
17 of 447 (4%) Events fell below the CBEMA curve
CBEMA
Curve
Copyright © 2012 Rockwell Automation, Inc. All rights reserved.
Where are the Applications?
The Plant Floor!
There is More Micro-processing
Power on the Factory Floor Than
in the Average IT Room
Most Factory Automation
is Left Unprotected
And Can Represent as Much as 30%
Of A Plant’s Unplanned Downtime
Copyright © 2012 Rockwell Automation, Inc. All rights reserved.
DEMO
How does this affect your equipment?
Copyright © 2012 Rockwell Automation, Inc. All rights reserved.
EPRI’s IEC Relay Profile
Failure
Zone
EPRI - Electrical Power Research Institute
Copyright © 2012 Rockwell Automation, Inc. All rights reserved.
Variable Speed Drive Profile
Failure
Zone
EPRI - Electrical Power Research Institute
Copyright © 2012 Rockwell Automation, Inc. All rights reserved.
PLC Profile
Failure
Zone
EPRI - Electrical Power Research Institute
Copyright © 2012 Rockwell Automation, Inc. All rights reserved.
Industrial PC Profile
Failure
Zone
EPRI - Electrical Power Research Institute
Copyright © 2012 Rockwell Automation, Inc. All rights reserved.
480V Bus
1
2
3
Machine B
Machine C
PLC
Input
Output
Error Light
Intermittent Failure
Program Loss
Misfeeds / Jams
Damaged Equipment
XfrmrXfrmr
SensorsRelays Counters
Control
Feedback
Analog
Inputs
Digital
Inputs
Machine A
Power Analysis With I-Sense / I-Grid
Install I-Sense At Spare Breaker
on 480V Bus. Connect to E-Net or
analog Phone Line.
View Data at www.igrid.com
Copyright © 2012 Rockwell Automation, Inc. All rights reserved.
Durham NC Area 2013/14 PQ Report
Protecting a the “Average” PLC and not protecting any relays will still
result in downtime of a typical control system
“Dots” below and to right of curve
represent events that will cause
profiled devices to “trip”
UPS Times Out
(5 Minutes)
Actual Data
Recorded by I-Grid
Monitoring System
Data Taken
From a Monitor
In the Durham NC
Area Over 12 Month
Period During 2012/13
1 Events over 1 second.
Average Relay Tolerance
Average PLC Tolerance
Source: IEEE Std 1346-1998
No Over Voltage Or Surges During 2012/13 at Monitored Sites
The Average Site in Durham
Experienced 17 Voltage Sags Severe
Enough to Impact Production During
2012/13
Copyright © 2012 Rockwell Automation, Inc. All rights reserved.
Burlington NC Area in past (2011 -2012)
Protecting a the “Average” PLC and not protecting any relays will still
result in downtime of a typical control system
“Dots” below and to right of curve
represent events that will cause
profiled devices to “trip”
UPS Times Out
(5 Minutes)
Actual Data
Recorded by I-Grid
Monitoring System
Data Taken
From a Monitor
In the Burlington NC
Area Over 12 Month
Period During 1022/12
No Events over 1 second.
Average Relay Tolerance
Average PLC Tolerance
Source: IEEE Std 1346-1998
No Over Voltage Or Surges During 2013/14 at Monitored Sites
The Average Site in Burtlington
Experienced 17 Voltage Sags Severe
Enough to Impact Production During
the past 6 months of 2011/12
Copyright © 2012 Rockwell Automation, Inc. All rights reserved.
Voltage Sags Damage Equipment
 When voltage returns, high current inrush can occur because
the Soft-charge ckt. is bypassed
 RF Amplifiers; Gradient Amplifiers; Low Voltage Power
Supplies and Variable Frequency Drives, subjected to
repeated hits—Over Time Causes Failure.
Typical Rectifier Circuit diagram:
fuse
Line impedance
Soft-charge ckt. DC Loads
Big cap.
filter
Diode Rectifier
Copyright © 2012 Rockwell Automation, Inc. All rights reserved.
How Voltage Sags Damage Equipment
5
Example: Inrush current measured for 1kVA electronic load
Note the scale change necessary to get the sagged results on the same page!
Normal inrush Inrush after Sag
• Peak inrush 50A
• Soft-charge
circuit bypassed
• Peak inrush 10A
• Soft-charge
circuit is active
Volts
Amps
10
0
20
Volts
Amps
40
0
50
Copyright © 2012 Rockwell Automation, Inc. All rights reserved.
480V Bus
1
2
3
Machine B
Machine C
PLC
Input
Output
Error Light
Intermittent Failure
Program Loss
Misfeeds / Jams
Damaged Equipment
XfrmrXfrmr
SensorsRelays Counters
Control
Feedback
Analog
Inputs
Digital
Inputs
Voltage Sags Cause
Erroneous Data to PLC or
Control System Resulting in
Intermittent System Failures
That are Commonly
Misdiagnosed by Operators
And Maintenance Personnel
Machine A
Root Cause Established
Single Phase Fault
On Grid Causes One
Phase In Plant to Drop
For Several Cycles
Local Voltage Sags
Impact Plant Production 10 – 20 Times Per year
And Are Almost Impossible to Detect Without
An Event Capture Monitoring System
Copyright © 2012 Rockwell Automation, Inc. All rights reserved.
Power DSP – constantly monitors incoming power, system integrity and load
Static Switch – is closed, sending power directly to the load. The switch has an overall
efficiency rating in excess of 99%.
Power Matrix – is idle
Double Conversion Power Core (dCPC) – is idle
Auto By-Pass – is idle
Normal Operation - The DySC monitors PQ continuously, while the power
electronics are in standby 99.999% of the time; making the DySC the most
energy efficient PQ device on the market.
Power
Matrix
Double Conversion
Power Core
Static
Switch
Auto
By-Pass
Utility
Load
DySC
Power DSP
Rectifier Inverter
The Solutions:
UPS, Flywheel or DySC
Copyright © 2012 Rockwell Automation, Inc. All rights reserved.
Sag Correction Solution Envelope
CVT
Protection
On-Line UPS
Protection
Stand-by UPS
ProtectionDySC Protection
53
53
Copyright © 2012 Rockwell Automation, Inc. All rights reserved.
Power DSP – detects the leading edge of a voltage sag, immediately routing power thru the
Power Matrix and dCPC and continuously corrects to insure true sinusoidal output
Static Switch – is open
Power Matrix– pulls power additional from the grid
Double Conversion Power Core (dCPC) – rectifies and inverts to recreate a true sinusoidal
Output (tSR)
Auto By-Pass – is idle
Voltage Sag - Most medical facilities experience 20 - 30 deep voltage sags
each year; lasting typically less than a 1/2 second. Given the short duration
of the actual voltage sag means the DySC power electronics run less than 30
seconds per year. The DySC is an extremely reliable machine.
Double Conversion
Power Core
Static
Switch
Auto
By-Pass
Utility
Load
DySC
Power DSP
Inverter
Power
Matrix Rectifier
DySC is “On” in under 2 milliseconds
Copyright © 2012 Rockwell Automation, Inc. All rights reserved.
DEMO
How does this protect your equipment?
Copyright © 2012 Rockwell Automation, Inc. All rights reserved.
One Year of data after installation of the DySC
Copyright © 2012 Rockwell Automation, Inc. All rights reserved.
A 6 channel I-Sense:
The Event and the DySC correction
3 phase Sag to 10% remaining
.860 Seconds long
Corrected by 100 Amp HC DySC
Site located on
the Florida Coast
3 years of flawless
performance
Copyright © 2012 Rockwell Automation, Inc. All rights reserved.
UPS Product Offering
58
Copyright © 2012 Rockwell Automation, Inc. All rights reserved.
DySC® (Dynamic Sag Corrector)
 DySC® (pronounced “Disk”) is an adaptive power supply that optimizes the remaining
power during a sag by using patented inverter technology to compensate for the sag
thereby maintaining an uninterrupted flow of optimal power to the load thus maximizing
uptime, minimizing inventory loss and reducing maintenance costs
MiniDySC® (single-phase; 0.25-12 kVA) ProDySC® (3-phase; 9-167 kVA) MegaDySC® (3-phase; 263-2000 kVA)
 Up to 5 seconds of ride through
 U.S. and International voltages available
 Scalable solution
59
Copyright © 2012 Rockwell Automation, Inc. All rights reserved.
Energy Consumption Comparison
GT DySC; A “GREEN” Solution: >99% efficient
and no Batteries!
92 kVA HC GT DySC
24”D x 41”W x 78”H
Copyright © 2012 Rockwell Automation, Inc. All rights reserved.
Food and Beverage
Aseptic Packaging
Dry Extrusion
Bakeries
Batch Processing
Automotive
Robots
Test
CNC Machining
Positioning Equipment
Semiconductor
Lithography
Process Tools
Facilities
Ovens
Healthcare
Imaging Equipment
Non Invasive
Generator Test Ride Through
Other
Pharmaceutical
Pulp and Paper
Oil and Gas
Plastics
Rule #1: All Factories Experience Voltage Sags
Rule #2: The DySC Will Make
- Any Component
- Any Machine
- Any Process
- Any Plant
On Average Break 10-14 Fewer Times Per Year
Key Applications and Industries
Copyright © 2012 Rockwell Automation, Inc. All rights reserved.
www.rockwellautomation.com
Follow ROKAutomation on Facebook & Twitter.
Connect with us on LinkedIn.
Thank you for your attention. Questions?

More Related Content

What's hot

Power quality disturbances
Power quality disturbancesPower quality disturbances
Power quality disturbancesManasKumarPatro
 
Power Quality and Monitoring
Power Quality and MonitoringPower Quality and Monitoring
Power Quality and Monitoringash08031996
 
Practical Power System Harmonics, Earthing and Power Quality - Problems and S...
Practical Power System Harmonics, Earthing and Power Quality - Problems and S...Practical Power System Harmonics, Earthing and Power Quality - Problems and S...
Practical Power System Harmonics, Earthing and Power Quality - Problems and S...Living Online
 
POWER QUALITY IMPROVEMENT
POWER QUALITY IMPROVEMENTPOWER QUALITY IMPROVEMENT
POWER QUALITY IMPROVEMENTUday Wankar
 
Power Quality Issues _Literature Survey
Power Quality Issues _Literature SurveyPower Quality Issues _Literature Survey
Power Quality Issues _Literature SurveyKetan Bhavsar
 
Power quality (IV-EEE)
Power quality (IV-EEE)Power quality (IV-EEE)
Power quality (IV-EEE)betasam
 
Power Quality Monitoring System Projects Research Topics
Power Quality Monitoring System Projects Research TopicsPower Quality Monitoring System Projects Research Topics
Power Quality Monitoring System Projects Research TopicsMatlab Simulation
 
Power Quality Issues
Power Quality IssuesPower Quality Issues
Power Quality Issuesmaneesh001
 
Overview of power quality problems ppt
Overview of power quality problems pptOverview of power quality problems ppt
Overview of power quality problems pptMitesh Karmur
 
Power quality issues in POWER SYSTEMS
Power quality issues in POWER SYSTEMSPower quality issues in POWER SYSTEMS
Power quality issues in POWER SYSTEMSCharan Sai Jc
 
Power Quality Basics_Complex Compatibility_Aclara
Power Quality Basics_Complex Compatibility_AclaraPower Quality Basics_Complex Compatibility_Aclara
Power Quality Basics_Complex Compatibility_AclaraAclara
 
Power quality &amp; demand side management
Power quality &amp; demand side managementPower quality &amp; demand side management
Power quality &amp; demand side managementMark Anthony Enoy
 

What's hot (20)

Power Quality Standards
Power Quality StandardsPower Quality Standards
Power Quality Standards
 
Power quality
Power qualityPower quality
Power quality
 
Power quality disturbances
Power quality disturbancesPower quality disturbances
Power quality disturbances
 
Power Quality and Monitoring
Power Quality and MonitoringPower Quality and Monitoring
Power Quality and Monitoring
 
Power quality
Power  qualityPower  quality
Power quality
 
Practical Power System Harmonics, Earthing and Power Quality - Problems and S...
Practical Power System Harmonics, Earthing and Power Quality - Problems and S...Practical Power System Harmonics, Earthing and Power Quality - Problems and S...
Practical Power System Harmonics, Earthing and Power Quality - Problems and S...
 
POWER QUALITY IMPROVEMENT
POWER QUALITY IMPROVEMENTPOWER QUALITY IMPROVEMENT
POWER QUALITY IMPROVEMENT
 
Power Quality Issues _Literature Survey
Power Quality Issues _Literature SurveyPower Quality Issues _Literature Survey
Power Quality Issues _Literature Survey
 
Power quality (IV-EEE)
Power quality (IV-EEE)Power quality (IV-EEE)
Power quality (IV-EEE)
 
Power Quality Monitoring System Projects Research Topics
Power Quality Monitoring System Projects Research TopicsPower Quality Monitoring System Projects Research Topics
Power Quality Monitoring System Projects Research Topics
 
UST Power Quality Basics
UST Power Quality BasicsUST Power Quality Basics
UST Power Quality Basics
 
Power Quality Issues
Power Quality IssuesPower Quality Issues
Power Quality Issues
 
Overview of power quality problems ppt
Overview of power quality problems pptOverview of power quality problems ppt
Overview of power quality problems ppt
 
Ieee power quality distribution systems
Ieee power quality distribution systemsIeee power quality distribution systems
Ieee power quality distribution systems
 
Power Quality
Power QualityPower Quality
Power Quality
 
Power quality issues in POWER SYSTEMS
Power quality issues in POWER SYSTEMSPower quality issues in POWER SYSTEMS
Power quality issues in POWER SYSTEMS
 
Power Quality Basics_Complex Compatibility_Aclara
Power Quality Basics_Complex Compatibility_AclaraPower Quality Basics_Complex Compatibility_Aclara
Power Quality Basics_Complex Compatibility_Aclara
 
An Overview of Power Quality
An Overview of Power QualityAn Overview of Power Quality
An Overview of Power Quality
 
Power quality &amp; demand side management
Power quality &amp; demand side managementPower quality &amp; demand side management
Power quality &amp; demand side management
 
Power quality 5
Power quality 5Power quality 5
Power quality 5
 

Similar to Revealing power quality as a process variable - Carotek Process Solutions Summit

What is Power Quality?
What is Power Quality?What is Power Quality?
What is Power Quality?svergin
 
Stacey_Resume_October_2016
Stacey_Resume_October_2016Stacey_Resume_October_2016
Stacey_Resume_October_2016Stacey Martin
 
Introduction relay
Introduction relayIntroduction relay
Introduction relayK R Vaghela
 
Grid Software solutions smart grids
Grid Software solutions smart gridsGrid Software solutions smart grids
Grid Software solutions smart gridsalexa842003
 
Trans Block Show
Trans Block ShowTrans Block Show
Trans Block Showmjsmith9
 
Maintenance and Test Equipment Cyber Security
Maintenance and Test Equipment Cyber Security Maintenance and Test Equipment Cyber Security
Maintenance and Test Equipment Cyber Security Michael Toecker
 
Novel Cost-effective Technique for Continued Operation of Electrical Equipmen...
Novel Cost-effective Technique for Continued Operation of Electrical Equipmen...Novel Cost-effective Technique for Continued Operation of Electrical Equipmen...
Novel Cost-effective Technique for Continued Operation of Electrical Equipmen...CSCJournals
 
gskresume_2015
gskresume_2015gskresume_2015
gskresume_2015Gary Katz
 
safety_critical_applications_and_customer_concerns
safety_critical_applications_and_customer_concernssafety_critical_applications_and_customer_concerns
safety_critical_applications_and_customer_concernsRufino Olay III
 
Modeling Analysis& Solution of Power Quality Problems Using DVR & DSTATCOM
Modeling Analysis& Solution of Power Quality Problems Using DVR & DSTATCOMModeling Analysis& Solution of Power Quality Problems Using DVR & DSTATCOM
Modeling Analysis& Solution of Power Quality Problems Using DVR & DSTATCOMijsrd.com
 
Catalog ls susol mc_leaflet_e_0901_dienhathe.vn
Catalog ls susol mc_leaflet_e_0901_dienhathe.vnCatalog ls susol mc_leaflet_e_0901_dienhathe.vn
Catalog ls susol mc_leaflet_e_0901_dienhathe.vnDien Ha The
 
Catalog ls susol mc_leaflet_e_0901
Catalog ls susol mc_leaflet_e_0901Catalog ls susol mc_leaflet_e_0901
Catalog ls susol mc_leaflet_e_0901Dien Ha The
 
Wind turbine condition monitoring sqi rev
Wind turbine condition monitoring sqi revWind turbine condition monitoring sqi rev
Wind turbine condition monitoring sqi revSpectra Quest Inc
 

Similar to Revealing power quality as a process variable - Carotek Process Solutions Summit (20)

Moise.pdf
Moise.pdfMoise.pdf
Moise.pdf
 
What is Power Quality?
What is Power Quality?What is Power Quality?
What is Power Quality?
 
Stacey_Resume_October_2016
Stacey_Resume_October_2016Stacey_Resume_October_2016
Stacey_Resume_October_2016
 
Introduction relay
Introduction relayIntroduction relay
Introduction relay
 
Mukesh_Kumar_(1)
Mukesh_Kumar_(1)Mukesh_Kumar_(1)
Mukesh_Kumar_(1)
 
Grid Software solutions smart grids
Grid Software solutions smart gridsGrid Software solutions smart grids
Grid Software solutions smart grids
 
Trans Block Show
Trans Block ShowTrans Block Show
Trans Block Show
 
Maintenance and Test Equipment Cyber Security
Maintenance and Test Equipment Cyber Security Maintenance and Test Equipment Cyber Security
Maintenance and Test Equipment Cyber Security
 
Novel Cost-effective Technique for Continued Operation of Electrical Equipmen...
Novel Cost-effective Technique for Continued Operation of Electrical Equipmen...Novel Cost-effective Technique for Continued Operation of Electrical Equipmen...
Novel Cost-effective Technique for Continued Operation of Electrical Equipmen...
 
gskresume_2015
gskresume_2015gskresume_2015
gskresume_2015
 
ELOHIM INDUSTRIAL SALES INC
ELOHIM INDUSTRIAL SALES INCELOHIM INDUSTRIAL SALES INC
ELOHIM INDUSTRIAL SALES INC
 
Power-One
Power-OnePower-One
Power-One
 
Susol MCCB_LS.pdf
Susol MCCB_LS.pdfSusol MCCB_LS.pdf
Susol MCCB_LS.pdf
 
safety_critical_applications_and_customer_concerns
safety_critical_applications_and_customer_concernssafety_critical_applications_and_customer_concerns
safety_critical_applications_and_customer_concerns
 
Modeling Analysis& Solution of Power Quality Problems Using DVR & DSTATCOM
Modeling Analysis& Solution of Power Quality Problems Using DVR & DSTATCOMModeling Analysis& Solution of Power Quality Problems Using DVR & DSTATCOM
Modeling Analysis& Solution of Power Quality Problems Using DVR & DSTATCOM
 
Power control investor
Power control investorPower control investor
Power control investor
 
Catalog ls susol mc_leaflet_e_0901_dienhathe.vn
Catalog ls susol mc_leaflet_e_0901_dienhathe.vnCatalog ls susol mc_leaflet_e_0901_dienhathe.vn
Catalog ls susol mc_leaflet_e_0901_dienhathe.vn
 
Catalog ls susol mc_leaflet_e_0901
Catalog ls susol mc_leaflet_e_0901Catalog ls susol mc_leaflet_e_0901
Catalog ls susol mc_leaflet_e_0901
 
Wind turbine condition monitoring sqi rev
Wind turbine condition monitoring sqi revWind turbine condition monitoring sqi rev
Wind turbine condition monitoring sqi rev
 
Thor power green overview 131210
Thor power green overview 131210Thor power green overview 131210
Thor power green overview 131210
 

More from Carotek

Steam System Technology Basics
Steam System Technology BasicsSteam System Technology Basics
Steam System Technology BasicsCarotek
 
E+H - Proof testing level instruments
E+H - Proof testing level instrumentsE+H - Proof testing level instruments
E+H - Proof testing level instrumentsCarotek
 
E+H - inline quality measurement
E+H -  inline quality measurementE+H -  inline quality measurement
E+H - inline quality measurementCarotek
 
E+H - Global Offering for LIfe Sciences
E+H - Global Offering for LIfe SciencesE+H - Global Offering for LIfe Sciences
E+H - Global Offering for LIfe SciencesCarotek
 
E+H brochure - Safe Choice for Food & Beverage
E+H brochure - Safe Choice for Food & Beverage E+H brochure - Safe Choice for Food & Beverage
E+H brochure - Safe Choice for Food & Beverage Carotek
 
E+H - Making accurate PH measurements
E+H - Making accurate PH measurementsE+H - Making accurate PH measurements
E+H - Making accurate PH measurementsCarotek
 
E+H Life Sciences Magazine May 2015
E+H Life Sciences Magazine May 2015E+H Life Sciences Magazine May 2015
E+H Life Sciences Magazine May 2015Carotek
 
E+H-Transmitter sensor matching improves RTD accuracy
E+H-Transmitter sensor matching improves RTD accuracyE+H-Transmitter sensor matching improves RTD accuracy
E+H-Transmitter sensor matching improves RTD accuracyCarotek
 
Whey, Water and CIP Detergent?
Whey, Water and CIP Detergent?Whey, Water and CIP Detergent?
Whey, Water and CIP Detergent?Carotek
 
2013 usa flotronic pumps brochure
2013 usa flotronic pumps brochure 2013 usa flotronic pumps brochure
2013 usa flotronic pumps brochure Carotek
 
Viking motor-speed-pumps
Viking motor-speed-pumpsViking motor-speed-pumps
Viking motor-speed-pumpsCarotek
 
Carotek 2015 Process Solutions Summit brochure
Carotek 2015 Process Solutions Summit brochureCarotek 2015 Process Solutions Summit brochure
Carotek 2015 Process Solutions Summit brochureCarotek
 
Asco 8210 Series RedHat Solenoid Valve
Asco 8210 Series RedHat Solenoid ValveAsco 8210 Series RedHat Solenoid Valve
Asco 8210 Series RedHat Solenoid ValveCarotek
 
Banner Wireless SureCross 45 brochure
Banner Wireless SureCross 45 brochureBanner Wireless SureCross 45 brochure
Banner Wireless SureCross 45 brochureCarotek
 
ASCO Solenoid Valves Catalog
ASCO Solenoid Valves CatalogASCO Solenoid Valves Catalog
ASCO Solenoid Valves CatalogCarotek
 
Hydro vision brochure_acousticflowmeasurement_en
Hydro vision brochure_acousticflowmeasurement_enHydro vision brochure_acousticflowmeasurement_en
Hydro vision brochure_acousticflowmeasurement_enCarotek
 
CIP vs COP - Hygienic Pumps and Meeting Government Regulations - Carotek Proc...
CIP vs COP - Hygienic Pumps and Meeting Government Regulations - Carotek Proc...CIP vs COP - Hygienic Pumps and Meeting Government Regulations - Carotek Proc...
CIP vs COP - Hygienic Pumps and Meeting Government Regulations - Carotek Proc...Carotek
 
Internet of Things - structured approach to the physical plant network - Rock...
Internet of Things - structured approach to the physical plant network - Rock...Internet of Things - structured approach to the physical plant network - Rock...
Internet of Things - structured approach to the physical plant network - Rock...Carotek
 
Peerless Pump Prevent Vibration - Carotek Process Solutions Summit
Peerless Pump Prevent Vibration - Carotek Process Solutions SummitPeerless Pump Prevent Vibration - Carotek Process Solutions Summit
Peerless Pump Prevent Vibration - Carotek Process Solutions SummitCarotek
 
City of Asheboro Carotek Process Solutions Summit presentation
City of Asheboro Carotek Process Solutions Summit presentationCity of Asheboro Carotek Process Solutions Summit presentation
City of Asheboro Carotek Process Solutions Summit presentationCarotek
 

More from Carotek (20)

Steam System Technology Basics
Steam System Technology BasicsSteam System Technology Basics
Steam System Technology Basics
 
E+H - Proof testing level instruments
E+H - Proof testing level instrumentsE+H - Proof testing level instruments
E+H - Proof testing level instruments
 
E+H - inline quality measurement
E+H -  inline quality measurementE+H -  inline quality measurement
E+H - inline quality measurement
 
E+H - Global Offering for LIfe Sciences
E+H - Global Offering for LIfe SciencesE+H - Global Offering for LIfe Sciences
E+H - Global Offering for LIfe Sciences
 
E+H brochure - Safe Choice for Food & Beverage
E+H brochure - Safe Choice for Food & Beverage E+H brochure - Safe Choice for Food & Beverage
E+H brochure - Safe Choice for Food & Beverage
 
E+H - Making accurate PH measurements
E+H - Making accurate PH measurementsE+H - Making accurate PH measurements
E+H - Making accurate PH measurements
 
E+H Life Sciences Magazine May 2015
E+H Life Sciences Magazine May 2015E+H Life Sciences Magazine May 2015
E+H Life Sciences Magazine May 2015
 
E+H-Transmitter sensor matching improves RTD accuracy
E+H-Transmitter sensor matching improves RTD accuracyE+H-Transmitter sensor matching improves RTD accuracy
E+H-Transmitter sensor matching improves RTD accuracy
 
Whey, Water and CIP Detergent?
Whey, Water and CIP Detergent?Whey, Water and CIP Detergent?
Whey, Water and CIP Detergent?
 
2013 usa flotronic pumps brochure
2013 usa flotronic pumps brochure 2013 usa flotronic pumps brochure
2013 usa flotronic pumps brochure
 
Viking motor-speed-pumps
Viking motor-speed-pumpsViking motor-speed-pumps
Viking motor-speed-pumps
 
Carotek 2015 Process Solutions Summit brochure
Carotek 2015 Process Solutions Summit brochureCarotek 2015 Process Solutions Summit brochure
Carotek 2015 Process Solutions Summit brochure
 
Asco 8210 Series RedHat Solenoid Valve
Asco 8210 Series RedHat Solenoid ValveAsco 8210 Series RedHat Solenoid Valve
Asco 8210 Series RedHat Solenoid Valve
 
Banner Wireless SureCross 45 brochure
Banner Wireless SureCross 45 brochureBanner Wireless SureCross 45 brochure
Banner Wireless SureCross 45 brochure
 
ASCO Solenoid Valves Catalog
ASCO Solenoid Valves CatalogASCO Solenoid Valves Catalog
ASCO Solenoid Valves Catalog
 
Hydro vision brochure_acousticflowmeasurement_en
Hydro vision brochure_acousticflowmeasurement_enHydro vision brochure_acousticflowmeasurement_en
Hydro vision brochure_acousticflowmeasurement_en
 
CIP vs COP - Hygienic Pumps and Meeting Government Regulations - Carotek Proc...
CIP vs COP - Hygienic Pumps and Meeting Government Regulations - Carotek Proc...CIP vs COP - Hygienic Pumps and Meeting Government Regulations - Carotek Proc...
CIP vs COP - Hygienic Pumps and Meeting Government Regulations - Carotek Proc...
 
Internet of Things - structured approach to the physical plant network - Rock...
Internet of Things - structured approach to the physical plant network - Rock...Internet of Things - structured approach to the physical plant network - Rock...
Internet of Things - structured approach to the physical plant network - Rock...
 
Peerless Pump Prevent Vibration - Carotek Process Solutions Summit
Peerless Pump Prevent Vibration - Carotek Process Solutions SummitPeerless Pump Prevent Vibration - Carotek Process Solutions Summit
Peerless Pump Prevent Vibration - Carotek Process Solutions Summit
 
City of Asheboro Carotek Process Solutions Summit presentation
City of Asheboro Carotek Process Solutions Summit presentationCity of Asheboro Carotek Process Solutions Summit presentation
City of Asheboro Carotek Process Solutions Summit presentation
 

Recently uploaded

A DAY IN THE LIFE OF A SALESMAN / WOMAN
A DAY IN THE LIFE OF A  SALESMAN / WOMANA DAY IN THE LIFE OF A  SALESMAN / WOMAN
A DAY IN THE LIFE OF A SALESMAN / WOMANIlamathiKannappan
 
Lucknow 💋 Escorts in Lucknow - 450+ Call Girl Cash Payment 8923113531 Neha Th...
Lucknow 💋 Escorts in Lucknow - 450+ Call Girl Cash Payment 8923113531 Neha Th...Lucknow 💋 Escorts in Lucknow - 450+ Call Girl Cash Payment 8923113531 Neha Th...
Lucknow 💋 Escorts in Lucknow - 450+ Call Girl Cash Payment 8923113531 Neha Th...anilsa9823
 
Creating Low-Code Loan Applications using the Trisotech Mortgage Feature Set
Creating Low-Code Loan Applications using the Trisotech Mortgage Feature SetCreating Low-Code Loan Applications using the Trisotech Mortgage Feature Set
Creating Low-Code Loan Applications using the Trisotech Mortgage Feature SetDenis Gagné
 
Yaroslav Rozhankivskyy: Три складові і три передумови максимальної продуктивн...
Yaroslav Rozhankivskyy: Три складові і три передумови максимальної продуктивн...Yaroslav Rozhankivskyy: Три складові і три передумови максимальної продуктивн...
Yaroslav Rozhankivskyy: Три складові і три передумови максимальної продуктивн...Lviv Startup Club
 
Sales & Marketing Alignment: How to Synergize for Success
Sales & Marketing Alignment: How to Synergize for SuccessSales & Marketing Alignment: How to Synergize for Success
Sales & Marketing Alignment: How to Synergize for SuccessAggregage
 
Eni 2024 1Q Results - 24.04.24 business.
Eni 2024 1Q Results - 24.04.24 business.Eni 2024 1Q Results - 24.04.24 business.
Eni 2024 1Q Results - 24.04.24 business.Eni
 
Call Girls In Panjim North Goa 9971646499 Genuine Service
Call Girls In Panjim North Goa 9971646499 Genuine ServiceCall Girls In Panjim North Goa 9971646499 Genuine Service
Call Girls In Panjim North Goa 9971646499 Genuine Serviceritikaroy0888
 
Monthly Social Media Update April 2024 pptx.pptx
Monthly Social Media Update April 2024 pptx.pptxMonthly Social Media Update April 2024 pptx.pptx
Monthly Social Media Update April 2024 pptx.pptxAndy Lambert
 
Monte Carlo simulation : Simulation using MCSM
Monte Carlo simulation : Simulation using MCSMMonte Carlo simulation : Simulation using MCSM
Monte Carlo simulation : Simulation using MCSMRavindra Nath Shukla
 
VIP Call Girls In Saharaganj ( Lucknow ) 🔝 8923113531 🔝 Cash Payment (COD) 👒
VIP Call Girls In Saharaganj ( Lucknow  ) 🔝 8923113531 🔝  Cash Payment (COD) 👒VIP Call Girls In Saharaganj ( Lucknow  ) 🔝 8923113531 🔝  Cash Payment (COD) 👒
VIP Call Girls In Saharaganj ( Lucknow ) 🔝 8923113531 🔝 Cash Payment (COD) 👒anilsa9823
 
Regression analysis: Simple Linear Regression Multiple Linear Regression
Regression analysis:  Simple Linear Regression Multiple Linear RegressionRegression analysis:  Simple Linear Regression Multiple Linear Regression
Regression analysis: Simple Linear Regression Multiple Linear RegressionRavindra Nath Shukla
 
VIP Call Girl Jamshedpur Aashi 8250192130 Independent Escort Service Jamshedpur
VIP Call Girl Jamshedpur Aashi 8250192130 Independent Escort Service JamshedpurVIP Call Girl Jamshedpur Aashi 8250192130 Independent Escort Service Jamshedpur
VIP Call Girl Jamshedpur Aashi 8250192130 Independent Escort Service JamshedpurSuhani Kapoor
 
Best VIP Call Girls Noida Sector 40 Call Me: 8448380779
Best VIP Call Girls Noida Sector 40 Call Me: 8448380779Best VIP Call Girls Noida Sector 40 Call Me: 8448380779
Best VIP Call Girls Noida Sector 40 Call Me: 8448380779Delhi Call girls
 
Call Girls Pune Just Call 9907093804 Top Class Call Girl Service Available
Call Girls Pune Just Call 9907093804 Top Class Call Girl Service AvailableCall Girls Pune Just Call 9907093804 Top Class Call Girl Service Available
Call Girls Pune Just Call 9907093804 Top Class Call Girl Service AvailableDipal Arora
 
GD Birla and his contribution in management
GD Birla and his contribution in managementGD Birla and his contribution in management
GD Birla and his contribution in managementchhavia330
 
RE Capital's Visionary Leadership under Newman Leech
RE Capital's Visionary Leadership under Newman LeechRE Capital's Visionary Leadership under Newman Leech
RE Capital's Visionary Leadership under Newman LeechNewman George Leech
 
Russian Faridabad Call Girls(Badarpur) : ☎ 8168257667, @4999
Russian Faridabad Call Girls(Badarpur) : ☎ 8168257667, @4999Russian Faridabad Call Girls(Badarpur) : ☎ 8168257667, @4999
Russian Faridabad Call Girls(Badarpur) : ☎ 8168257667, @4999Tina Ji
 
Call Girls In DLf Gurgaon ➥99902@11544 ( Best price)100% Genuine Escort In 24...
Call Girls In DLf Gurgaon ➥99902@11544 ( Best price)100% Genuine Escort In 24...Call Girls In DLf Gurgaon ➥99902@11544 ( Best price)100% Genuine Escort In 24...
Call Girls In DLf Gurgaon ➥99902@11544 ( Best price)100% Genuine Escort In 24...lizamodels9
 

Recently uploaded (20)

A DAY IN THE LIFE OF A SALESMAN / WOMAN
A DAY IN THE LIFE OF A  SALESMAN / WOMANA DAY IN THE LIFE OF A  SALESMAN / WOMAN
A DAY IN THE LIFE OF A SALESMAN / WOMAN
 
Lucknow 💋 Escorts in Lucknow - 450+ Call Girl Cash Payment 8923113531 Neha Th...
Lucknow 💋 Escorts in Lucknow - 450+ Call Girl Cash Payment 8923113531 Neha Th...Lucknow 💋 Escorts in Lucknow - 450+ Call Girl Cash Payment 8923113531 Neha Th...
Lucknow 💋 Escorts in Lucknow - 450+ Call Girl Cash Payment 8923113531 Neha Th...
 
Creating Low-Code Loan Applications using the Trisotech Mortgage Feature Set
Creating Low-Code Loan Applications using the Trisotech Mortgage Feature SetCreating Low-Code Loan Applications using the Trisotech Mortgage Feature Set
Creating Low-Code Loan Applications using the Trisotech Mortgage Feature Set
 
Yaroslav Rozhankivskyy: Три складові і три передумови максимальної продуктивн...
Yaroslav Rozhankivskyy: Три складові і три передумови максимальної продуктивн...Yaroslav Rozhankivskyy: Три складові і три передумови максимальної продуктивн...
Yaroslav Rozhankivskyy: Три складові і три передумови максимальної продуктивн...
 
Sales & Marketing Alignment: How to Synergize for Success
Sales & Marketing Alignment: How to Synergize for SuccessSales & Marketing Alignment: How to Synergize for Success
Sales & Marketing Alignment: How to Synergize for Success
 
Eni 2024 1Q Results - 24.04.24 business.
Eni 2024 1Q Results - 24.04.24 business.Eni 2024 1Q Results - 24.04.24 business.
Eni 2024 1Q Results - 24.04.24 business.
 
Call Girls In Panjim North Goa 9971646499 Genuine Service
Call Girls In Panjim North Goa 9971646499 Genuine ServiceCall Girls In Panjim North Goa 9971646499 Genuine Service
Call Girls In Panjim North Goa 9971646499 Genuine Service
 
Monthly Social Media Update April 2024 pptx.pptx
Monthly Social Media Update April 2024 pptx.pptxMonthly Social Media Update April 2024 pptx.pptx
Monthly Social Media Update April 2024 pptx.pptx
 
Monte Carlo simulation : Simulation using MCSM
Monte Carlo simulation : Simulation using MCSMMonte Carlo simulation : Simulation using MCSM
Monte Carlo simulation : Simulation using MCSM
 
VIP Call Girls In Saharaganj ( Lucknow ) 🔝 8923113531 🔝 Cash Payment (COD) 👒
VIP Call Girls In Saharaganj ( Lucknow  ) 🔝 8923113531 🔝  Cash Payment (COD) 👒VIP Call Girls In Saharaganj ( Lucknow  ) 🔝 8923113531 🔝  Cash Payment (COD) 👒
VIP Call Girls In Saharaganj ( Lucknow ) 🔝 8923113531 🔝 Cash Payment (COD) 👒
 
Regression analysis: Simple Linear Regression Multiple Linear Regression
Regression analysis:  Simple Linear Regression Multiple Linear RegressionRegression analysis:  Simple Linear Regression Multiple Linear Regression
Regression analysis: Simple Linear Regression Multiple Linear Regression
 
VIP Call Girl Jamshedpur Aashi 8250192130 Independent Escort Service Jamshedpur
VIP Call Girl Jamshedpur Aashi 8250192130 Independent Escort Service JamshedpurVIP Call Girl Jamshedpur Aashi 8250192130 Independent Escort Service Jamshedpur
VIP Call Girl Jamshedpur Aashi 8250192130 Independent Escort Service Jamshedpur
 
KestrelPro Flyer Japan IT Week 2024 (English)
KestrelPro Flyer Japan IT Week 2024 (English)KestrelPro Flyer Japan IT Week 2024 (English)
KestrelPro Flyer Japan IT Week 2024 (English)
 
Best VIP Call Girls Noida Sector 40 Call Me: 8448380779
Best VIP Call Girls Noida Sector 40 Call Me: 8448380779Best VIP Call Girls Noida Sector 40 Call Me: 8448380779
Best VIP Call Girls Noida Sector 40 Call Me: 8448380779
 
Call Girls Pune Just Call 9907093804 Top Class Call Girl Service Available
Call Girls Pune Just Call 9907093804 Top Class Call Girl Service AvailableCall Girls Pune Just Call 9907093804 Top Class Call Girl Service Available
Call Girls Pune Just Call 9907093804 Top Class Call Girl Service Available
 
GD Birla and his contribution in management
GD Birla and his contribution in managementGD Birla and his contribution in management
GD Birla and his contribution in management
 
RE Capital's Visionary Leadership under Newman Leech
RE Capital's Visionary Leadership under Newman LeechRE Capital's Visionary Leadership under Newman Leech
RE Capital's Visionary Leadership under Newman Leech
 
Russian Faridabad Call Girls(Badarpur) : ☎ 8168257667, @4999
Russian Faridabad Call Girls(Badarpur) : ☎ 8168257667, @4999Russian Faridabad Call Girls(Badarpur) : ☎ 8168257667, @4999
Russian Faridabad Call Girls(Badarpur) : ☎ 8168257667, @4999
 
Best Practices for Implementing an External Recruiting Partnership
Best Practices for Implementing an External Recruiting PartnershipBest Practices for Implementing an External Recruiting Partnership
Best Practices for Implementing an External Recruiting Partnership
 
Call Girls In DLf Gurgaon ➥99902@11544 ( Best price)100% Genuine Escort In 24...
Call Girls In DLf Gurgaon ➥99902@11544 ( Best price)100% Genuine Escort In 24...Call Girls In DLf Gurgaon ➥99902@11544 ( Best price)100% Genuine Escort In 24...
Call Girls In DLf Gurgaon ➥99902@11544 ( Best price)100% Genuine Escort In 24...
 

Revealing power quality as a process variable - Carotek Process Solutions Summit

  • 1. The presentation that follows was given during Carotek’s Fifth Annual Process Solutions Summit in Charlotte NC September 24 – 25, 2014. Used with Permission.
  • 2. Copyright © 2012 Rockwell Automation, Inc. All rights reserved. Prolog Power Quality Pioneering Brian St. Pierre Regional Business Development Manager (517) 294-0087 bstpierre@ra.rockwell.com
  • 3. Copyright © 2012 Rockwell Automation, Inc. All rights reserved. Who …………and ………What: SoftSwitching Technologies / RA  A technical Innovator in the Power Quality Field  Founded in 1995 through University of Wisconsin  Manufacturing Facility and offices located in Middleton, WI  Acquired by Rockwell Automation on March 12th, 2012  Part of the Industrial Components Business at Rockwell Power Quality Monitoring Notification + Reporting Power Quality Mitigation Eliminate Downtime Protect Investment 3 “…the hottest new technology comes from startup SoftSwitching Technologies”
  • 4. Copyright © 2012 Rockwell Automation, Inc. All rights reserved. SoftSwitching’s / RA’s Product Line 4 1-50 A Single Phase 25-200 A 3 Phase 400-2400 A 3 Phase I-Sense Monitor
  • 5. Copyright © 2012 Rockwell Automation, Inc. All rights reserved. Food and Beverage Aseptic Packaging Dry Extrusion Bakeries Batch Processing Automotive Robots Test CNC Machining Positioning Equipment Semiconductor Lithography Process Tools Facilities Ovens Healthcare Imaging Equipment Non Invasive Generator Test Ride Through Other Pharmaceutical Pulp and Paper Oil and Gas Plastics Rule #1: All Factories Experience Voltage Sags Rule #2: The DySC Will Make - Any Component - Any Machine - Any Process - Any Plant On Average Break 10-14 Fewer Times Per Year Key Applications and Industries
  • 6. Copyright © 2012 Rockwell Automation, Inc. All rights reserved. Revealing Power Quality as a “Process Variable”
  • 7. Copyright © 2012 Rockwell Automation, Inc. All rights reserved. Power from Two Perspectives — What is the difference?  Power/Energy Management:  Providing solutions that enable a customer to optimize the consumption of energy in their plant or at a specific process.  Power Quality Management:  Providing solutions that eliminate “unscheduled downtime” caused by both external and internal power quality events/conditions that can impact the profitability of a plant or a specific process.  Both solutions have similar aspects or parts:  Power Monitoring, Data organization or analysis through a tool or software, *System optimization  *Very different remediation solutions (Solving a different problem)  Today we’ll focus on how Power Quality acts as a Process Variable! 7
  • 8. Copyright © 2012 Rockwell Automation, Inc. All rights reserved. The Consumer is Responsible for Power Quality  Utility cannot provide perfect power quality and are not required to. (e.g., Wisconsin PSC 113.0703)  Customers having equipment or operations that are sensitive to such voltage fluctuations … may find it necessary to install, at their own expense, power conditioning equipment or other modifications …  Job is to “Keep the lights on.”  Goals of Utility  Deliver maximum energy through the existing infrastructure  Maintain +/-10% (on average) voltage at service entrance  Minimize outages longer than 2-5 minutes  60.00 Hz, when averaged over 24 hours  Keep large industrial customers satisfied  Minimize large customers disrupting neighbors’ power quality 8
  • 9. Copyright © 2012 Rockwell Automation, Inc. All rights reserved. I-Grid (Monitoring the Power Grid with I-Sense)  One pin per postal code  Over 3000 I-Sense monitors active in the USA today
  • 10. Copyright © 2012 Rockwell Automation, Inc. All rights reserved. Healthcare’s i-Grid Network (Today there are approximately 750 active sites)
  • 11. Copyright © 2012 Rockwell Automation, Inc. All rights reserved. The Story / “Background Basics” FrequencyofOccurrence Typical Incident Cost $ $$ $$$ $$$$ LowVeryLowMediumHigh Notching (Constant) Interruption (0.5 cycles – >1 hr) Swell (0.5 cycles – 60s) Noise (Constant) Harmonics (Constant) Transient (<50 ns – 5 ms) Unbalance (Fluctuating) Undervoltage (>1 minute) Overvoltage (>1 minute) Sag (0.5 cycles – 60s) EPRI (Electrical Power Research Institute) • Monitored 300 sites for 2+ years. • 1993 study: 92% of all events were voltage sags under 2 seconds • 1995 study: 96% of all events were voltage sags less than 2 seconds Grid Related Facility Related 11
  • 12. Copyright © 2012 Rockwell Automation, Inc. All rights reserved. Measuring Power Quality -- Voltage Sag (Dip) Characterization  Sag - RMS voltage reduction between 1/2 cycle - 60 sec  Magnitude and Duration 12 -1 -0.5 0 0.5 1 0 1 2 3 4 5 6 7 8 Duration: 4 Cycles Magnitude: 60% Remaining
  • 13. Copyright © 2012 Rockwell Automation, Inc. All rights reserved. 0.0 0.2 0.4 0.6 0.8 1.0 1 10 100 1000 Duration (ms) Magnitude(perunit) 90% Tracking Voltage Sag Events 13
  • 14. Copyright © 2012 Rockwell Automation, Inc. All rights reserved. Electrical Design Standards used in NA (Sags Captured at High-Tech Mfg. Sites)  Very few outages, still many sags!  1000 sag events from 15 Semi plants  Avg. 5.4 events below CBEMA per year…with transmission-level service!  SEMI F47 source: International SEMATECH & EPRI, 1999
  • 15. Copyright © 2012 Rockwell Automation, Inc. All rights reserved. Plant Wall 480V Bus 1 2 3 Machine B Machine C PLC Input Output Error Light Intermittent Failure Program Loss Mis-feeds / Jams Damaged Equipment Downtime XfrmrXfrmr SensorsRelays Counters Control Feedback Analog Inputs Digital Inputs My Machine or process just went down but not others, Why Not? What broke? What do I need to do? Machine A Typical Dilemma Typical Manufacturing Plant Electrical and Controls Environment
  • 16. Copyright © 2012 Rockwell Automation, Inc. All rights reserved. The correlation between unscheduled downtime and extreme weather is clear
  • 17. Copyright © 2012 Rockwell Automation, Inc. All rights reserved. Others like Drunk’n Utility Poles and wayward Construction Cranes may not be visible on the way to work Roughly ~60% of Power Quality Problems are caused by Weather…
  • 18. Copyright © 2012 Rockwell Automation, Inc. All rights reserved. Equipment Failures
  • 19. Copyright © 2012 Rockwell Automation, Inc. All rights reserved. Or the much more common--Squirrels on Holiday cause similar problems: Downtime and Damage.
  • 20. Copyright © 2012 Rockwell Automation, Inc. All rights reserved. And rare, but well-meaning Misguided Reindeer
  • 21. Copyright © 2012 Rockwell Automation, Inc. All rights reserved. Cuban Tree Frog chasing the “Corona” 21
  • 22. Copyright © 2012 Rockwell Automation, Inc. All rights reserved. Downstream of Switch: Outage Upstream of Switch: Voltage Sag How the Grid Works 230kV Transmission 69kV Transmission 13kV Distribution A B C S S S S S S S S S S S S S S S SS S S S S S S Up to 200 Miles The Grid Self Heals within 2 seconds or Trucks have to be sent out
  • 23. Copyright © 2012 Rockwell Automation, Inc. All rights reserved. -35% -70% -25% The depth of your Sag depends on the distance you are from the event When Lightning Strikes, Squirrels Fry, or the grid Shorts: You feel it
  • 24. Copyright © 2012 Rockwell Automation, Inc. All rights reserved. Past Year on Three Separate Electrical Feeds in Durham NC
  • 25. Copyright © 2012 Rockwell Automation, Inc. All rights reserved. 19 of 29 (63%) Events fell below the CBEMA curve CBEMA Curve
  • 26. Copyright © 2012 Rockwell Automation, Inc. All rights reserved. Confirmation and Corroboration
  • 27. Copyright © 2012 Rockwell Automation, Inc. All rights reserved. Friday May 31, 2013 Sag to 30%, (~10 Cycles)
  • 28. Copyright © 2012 Rockwell Automation, Inc. All rights reserved. Past Year in Lumberton NC
  • 29. Copyright © 2012 Rockwell Automation, Inc. All rights reserved. 3 of 10 (30%) Events fell below the CBEMA curve CBEMA Curve
  • 30. Copyright © 2012 Rockwell Automation, Inc. All rights reserved. Past Year in New Bern NC
  • 31. Copyright © 2012 Rockwell Automation, Inc. All rights reserved. 3 of 12 (25%) Events fell below the CBEMA curve CBEMA Curve
  • 32. Copyright © 2012 Rockwell Automation, Inc. All rights reserved. Past Year in Chapel Hill NC
  • 33. Copyright © 2012 Rockwell Automation, Inc. All rights reserved. 3 of 10 (30%) Events fell below the CBEMA curve CBEMA Curve
  • 34. Copyright © 2012 Rockwell Automation, Inc. All rights reserved. Past 3 Months in Greensboro NC
  • 35. Copyright © 2012 Rockwell Automation, Inc. All rights reserved. 3 of 3 (100%) Events fell below the CBEMA curve CBEMA Curve
  • 36. Copyright © 2012 Rockwell Automation, Inc. All rights reserved. Confirmation and Corroboration
  • 37. Copyright © 2012 Rockwell Automation, Inc. All rights reserved. Monday Feb 3, 2013 Sag to 58%, (~2.5 Cycles) 37
  • 38. Copyright © 2012 Rockwell Automation, Inc. All rights reserved. May 2011 to May 2012 in Burlington NC
  • 39. Copyright © 2012 Rockwell Automation, Inc. All rights reserved. 17 of 447 (4%) Events fell below the CBEMA curve CBEMA Curve
  • 40. Copyright © 2012 Rockwell Automation, Inc. All rights reserved. Where are the Applications? The Plant Floor! There is More Micro-processing Power on the Factory Floor Than in the Average IT Room Most Factory Automation is Left Unprotected And Can Represent as Much as 30% Of A Plant’s Unplanned Downtime
  • 41. Copyright © 2012 Rockwell Automation, Inc. All rights reserved. DEMO How does this affect your equipment?
  • 42. Copyright © 2012 Rockwell Automation, Inc. All rights reserved. EPRI’s IEC Relay Profile Failure Zone EPRI - Electrical Power Research Institute
  • 43. Copyright © 2012 Rockwell Automation, Inc. All rights reserved. Variable Speed Drive Profile Failure Zone EPRI - Electrical Power Research Institute
  • 44. Copyright © 2012 Rockwell Automation, Inc. All rights reserved. PLC Profile Failure Zone EPRI - Electrical Power Research Institute
  • 45. Copyright © 2012 Rockwell Automation, Inc. All rights reserved. Industrial PC Profile Failure Zone EPRI - Electrical Power Research Institute
  • 46. Copyright © 2012 Rockwell Automation, Inc. All rights reserved. 480V Bus 1 2 3 Machine B Machine C PLC Input Output Error Light Intermittent Failure Program Loss Misfeeds / Jams Damaged Equipment XfrmrXfrmr SensorsRelays Counters Control Feedback Analog Inputs Digital Inputs Machine A Power Analysis With I-Sense / I-Grid Install I-Sense At Spare Breaker on 480V Bus. Connect to E-Net or analog Phone Line. View Data at www.igrid.com
  • 47. Copyright © 2012 Rockwell Automation, Inc. All rights reserved. Durham NC Area 2013/14 PQ Report Protecting a the “Average” PLC and not protecting any relays will still result in downtime of a typical control system “Dots” below and to right of curve represent events that will cause profiled devices to “trip” UPS Times Out (5 Minutes) Actual Data Recorded by I-Grid Monitoring System Data Taken From a Monitor In the Durham NC Area Over 12 Month Period During 2012/13 1 Events over 1 second. Average Relay Tolerance Average PLC Tolerance Source: IEEE Std 1346-1998 No Over Voltage Or Surges During 2012/13 at Monitored Sites The Average Site in Durham Experienced 17 Voltage Sags Severe Enough to Impact Production During 2012/13
  • 48. Copyright © 2012 Rockwell Automation, Inc. All rights reserved. Burlington NC Area in past (2011 -2012) Protecting a the “Average” PLC and not protecting any relays will still result in downtime of a typical control system “Dots” below and to right of curve represent events that will cause profiled devices to “trip” UPS Times Out (5 Minutes) Actual Data Recorded by I-Grid Monitoring System Data Taken From a Monitor In the Burlington NC Area Over 12 Month Period During 1022/12 No Events over 1 second. Average Relay Tolerance Average PLC Tolerance Source: IEEE Std 1346-1998 No Over Voltage Or Surges During 2013/14 at Monitored Sites The Average Site in Burtlington Experienced 17 Voltage Sags Severe Enough to Impact Production During the past 6 months of 2011/12
  • 49. Copyright © 2012 Rockwell Automation, Inc. All rights reserved. Voltage Sags Damage Equipment  When voltage returns, high current inrush can occur because the Soft-charge ckt. is bypassed  RF Amplifiers; Gradient Amplifiers; Low Voltage Power Supplies and Variable Frequency Drives, subjected to repeated hits—Over Time Causes Failure. Typical Rectifier Circuit diagram: fuse Line impedance Soft-charge ckt. DC Loads Big cap. filter Diode Rectifier
  • 50. Copyright © 2012 Rockwell Automation, Inc. All rights reserved. How Voltage Sags Damage Equipment 5 Example: Inrush current measured for 1kVA electronic load Note the scale change necessary to get the sagged results on the same page! Normal inrush Inrush after Sag • Peak inrush 50A • Soft-charge circuit bypassed • Peak inrush 10A • Soft-charge circuit is active Volts Amps 10 0 20 Volts Amps 40 0 50
  • 51. Copyright © 2012 Rockwell Automation, Inc. All rights reserved. 480V Bus 1 2 3 Machine B Machine C PLC Input Output Error Light Intermittent Failure Program Loss Misfeeds / Jams Damaged Equipment XfrmrXfrmr SensorsRelays Counters Control Feedback Analog Inputs Digital Inputs Voltage Sags Cause Erroneous Data to PLC or Control System Resulting in Intermittent System Failures That are Commonly Misdiagnosed by Operators And Maintenance Personnel Machine A Root Cause Established Single Phase Fault On Grid Causes One Phase In Plant to Drop For Several Cycles Local Voltage Sags Impact Plant Production 10 – 20 Times Per year And Are Almost Impossible to Detect Without An Event Capture Monitoring System
  • 52. Copyright © 2012 Rockwell Automation, Inc. All rights reserved. Power DSP – constantly monitors incoming power, system integrity and load Static Switch – is closed, sending power directly to the load. The switch has an overall efficiency rating in excess of 99%. Power Matrix – is idle Double Conversion Power Core (dCPC) – is idle Auto By-Pass – is idle Normal Operation - The DySC monitors PQ continuously, while the power electronics are in standby 99.999% of the time; making the DySC the most energy efficient PQ device on the market. Power Matrix Double Conversion Power Core Static Switch Auto By-Pass Utility Load DySC Power DSP Rectifier Inverter The Solutions: UPS, Flywheel or DySC
  • 53. Copyright © 2012 Rockwell Automation, Inc. All rights reserved. Sag Correction Solution Envelope CVT Protection On-Line UPS Protection Stand-by UPS ProtectionDySC Protection 53 53
  • 54. Copyright © 2012 Rockwell Automation, Inc. All rights reserved. Power DSP – detects the leading edge of a voltage sag, immediately routing power thru the Power Matrix and dCPC and continuously corrects to insure true sinusoidal output Static Switch – is open Power Matrix– pulls power additional from the grid Double Conversion Power Core (dCPC) – rectifies and inverts to recreate a true sinusoidal Output (tSR) Auto By-Pass – is idle Voltage Sag - Most medical facilities experience 20 - 30 deep voltage sags each year; lasting typically less than a 1/2 second. Given the short duration of the actual voltage sag means the DySC power electronics run less than 30 seconds per year. The DySC is an extremely reliable machine. Double Conversion Power Core Static Switch Auto By-Pass Utility Load DySC Power DSP Inverter Power Matrix Rectifier DySC is “On” in under 2 milliseconds
  • 55. Copyright © 2012 Rockwell Automation, Inc. All rights reserved. DEMO How does this protect your equipment?
  • 56. Copyright © 2012 Rockwell Automation, Inc. All rights reserved. One Year of data after installation of the DySC
  • 57. Copyright © 2012 Rockwell Automation, Inc. All rights reserved. A 6 channel I-Sense: The Event and the DySC correction 3 phase Sag to 10% remaining .860 Seconds long Corrected by 100 Amp HC DySC Site located on the Florida Coast 3 years of flawless performance
  • 58. Copyright © 2012 Rockwell Automation, Inc. All rights reserved. UPS Product Offering 58
  • 59. Copyright © 2012 Rockwell Automation, Inc. All rights reserved. DySC® (Dynamic Sag Corrector)  DySC® (pronounced “Disk”) is an adaptive power supply that optimizes the remaining power during a sag by using patented inverter technology to compensate for the sag thereby maintaining an uninterrupted flow of optimal power to the load thus maximizing uptime, minimizing inventory loss and reducing maintenance costs MiniDySC® (single-phase; 0.25-12 kVA) ProDySC® (3-phase; 9-167 kVA) MegaDySC® (3-phase; 263-2000 kVA)  Up to 5 seconds of ride through  U.S. and International voltages available  Scalable solution 59
  • 60. Copyright © 2012 Rockwell Automation, Inc. All rights reserved. Energy Consumption Comparison GT DySC; A “GREEN” Solution: >99% efficient and no Batteries! 92 kVA HC GT DySC 24”D x 41”W x 78”H
  • 61. Copyright © 2012 Rockwell Automation, Inc. All rights reserved. Food and Beverage Aseptic Packaging Dry Extrusion Bakeries Batch Processing Automotive Robots Test CNC Machining Positioning Equipment Semiconductor Lithography Process Tools Facilities Ovens Healthcare Imaging Equipment Non Invasive Generator Test Ride Through Other Pharmaceutical Pulp and Paper Oil and Gas Plastics Rule #1: All Factories Experience Voltage Sags Rule #2: The DySC Will Make - Any Component - Any Machine - Any Process - Any Plant On Average Break 10-14 Fewer Times Per Year Key Applications and Industries
  • 62. Copyright © 2012 Rockwell Automation, Inc. All rights reserved. www.rockwellautomation.com Follow ROKAutomation on Facebook & Twitter. Connect with us on LinkedIn. Thank you for your attention. Questions?