1. De expert in de kwaliteit
van elektriciteit
Wij leveren producten en diensten ter optimalisering
van de spannings- en stroomkwaliteit (Power Quality)
4. HyTEPS - Expert in Power Quality
Wat is Flikker
4
1. Spanningsvariatie tussen ± 10 %
2. Meerdere variaties in tijd
3. Frequentie van variatie
5. HyTEPS - Expert in Power Quality
Flikker gaat voornamelijk om gemoedsrust mensen
5
Oog-hersenen respons geeft aanleiding tot de irritatie.
Gevoelig voor:
1. kleur
2. Helderheid
Relatie tussen spanningsvariatie en gevoel van irritatie
Experimenten gebaseerd op mensen
Frequentie wat zichtbaar is: 0.05 Hz – 35 Hz
8.8 Hz is meest storend
6. 20 november 2023 HyTEPS - Expert in Power Quality 6
Use Case – The problem
Metal products fabrication
10kV public grid connection
Continuous spot welding
Repetitive high current peaks
High flicker values (up to 3.5 on 10kV)
Risk of disconnection by grid operator !
7. 20 november 2023 HyTEPS - Expert in Power Quality 7
Use Case – The installation
4x 10/0.4kV transformers
Arc welding lines
Up to 4.2kA peaks
TR1 TR2 TR3 TR4
Welders Welders Welders Welders
8. TR1 TR2 TR3 TR4
Welders Welders Welders Welders
20 november 2023 HyTEPS - Expert in Power Quality 8
Use Case – Measurements
Measured multiple locations
Fast and accurate device
Elspec G4500
1024 samples/sine
Continuous waveform
: Measurement location
4x 10/0.4kV transformers
Arc welding lines
Up to 4.2kA peaks
9. 20 november 2023 HyTEPS - Expert in Power Quality 9
Fast ramp up/down
From 0.35kAp to 6kAp
Use Case – Measurements
10. 20 november 2023 HyTEPS - Expert in Power Quality 10
Use Case – Measurements
up to 6%
100-120 min-1
Pst up to 6.87
11. 20 november 2023 HyTEPS - Expert in Power Quality 11
Use Case – Simulations
Simulations
Technical specs installation
Measurement data
Characteristics Equalizer
12. 20 november 2023 HyTEPS - Expert in Power Quality 12
Use Case – Solution
Elspec Equalizer
Thyristor controller capacitor bank
Fast reactive power compensation <20ms
1500kvar in 15 steps (per transformer)
Implemented in multiple sequences
13. 20 november 2023 HyTEPS - Expert in Power Quality 13
Use Case – Commissioning
14. 20 november 2023 HyTEPS - Expert in Power Quality 14
Use Case – Results
Equalizer reacts within 20ms
Q significantly reduced
is reduced
Equalizer switches ON
Equalizer switches OFF
Q ~ 0
ே ே
Remains almost unchanged Significantly reduced
15. 20 november 2023 HyTEPS - Expert in Power Quality 15
Use Case – Results
Pst Q1 = 1.9
Pst Med = 2.2
Pst Q3 = 2.5
Before:
Pst Q1 = 1.4
Pst Med = 1.6
Pst Q3 = 1.8
After:
16. 20 november 2023 HyTEPS - Expert in Power Quality 16
Use Case – Results
Simulations:
Measurements:
Simulation corresponds to real results
23. HyTEPS - Expert in Power Quality
Allocatie van limieten naar een MV-aansluiting
24
HV
MV
LV
G
G
L
L
L
G
LMV
LHV
LLV
24. De expert in de kwaliteit
van elektriciteit
Wij leveren producten en diensten ter optimalisering
van de spannings- en stroomkwaliteit (Power Quality)