Pearce Avenue Project
1. _1m _3m _5m _10m0
Lounge
Dining
Media room
Kitchen
Study
Utility room
Vault above
Outside dining
WC
Garage
459.0 6000.0
3431.0
2533.0
838Door838Door
762 Door
2063.0
1647.0
SVP
Open up existing
cavity and align
after inspection
Fan outlet 15L/S
EXCT FAN
AV Cupb'd St.
BBQ client to
confirm
Fireplace to clients
specification
SVP
STAIRCASE:
Timber:Part K
15 Risers =186mm.
Goings = 220mm.
rwp
659.0
4800.0
300.0
1100.0
1400.0
1100.0
900.0
6233.0
1083.0
2500.0
2500.0
300.0
940.0
407.0
100.0
912.0
347.0
900.0
600.0
2043.0
St. St.
600mm x 600mm
Paving slabs
Timber Louvre's -
client to confirm
specification
Bedroom
Bedroom
Bedroom
En-Suite
En-suite
Bedroom
Bathroom
12783.0
1200.0 3044.0 2575.0 875.0 2030.0 2159.0 900.0
11581.0
5666.0
1200.0
4715.0
11581.0
6233.0
1200.0
4148.0
12783.0
450.0 3268.0 1594.0 2159.0 2228.0 2159.0 925.0
Insulated cavity closers to all
proposed doors and windows .
3655.0
4497.0
1800.0
3618.0
3642.0
4910.01900.0
3618.0
3000.0
3641.0
4890.0
2825.0
4448.0
2825.0
2329.0
4293.0
2600.0
2825.0
1200.0
5968.0
1150.0
1171.0
838 Door
838Door
838Door
838 Door
FD30 838
FD30 838
FD30838
838 Door
SVP
SVP
Fan outlet 15L/S
EXCT FAN
Fan outlet
15L/S
EXCT FAN
Towel
Rail
Fan outlet
15L/S
EXCT FAN
SVP
rwp
838 Door
Towel
Rail
838 Door protruding light
box to
electricians
specification
Velux TWF -
Flexible sun
tunnel
WALL LEGEND
BLOCK AND BEAM'
'Periscopic' type vents to manufacturers details
30mm Finish Render
100mm Concrete Block
50mm Cavity
50mm Celotex
100mm Thermalite Turbo block ( to achieve K value of 0.11)
12.5mm plasterboard on 10mm dabs, taped and skimmed
STUD WORK
70mm Metal Studwork
25MM Wool batts internally (minimum thickness 25MM, Minimum
density 10 KG/M3)
15MM Plasterboard to both sides all joints to be taped and skimed.
Smoke detector
Mains powered single station smoke detector units in strict
accordance with BS5446 within hall of house, exact position to be
determined with building inspector on site.
FIRE LEGEND
DRAINAGE.
Rain water pipes
Soil vent pipes
VENTILATION.
Mechanical extract fan ceiling mounted.
SVP
rwp
Heat Detector
VMZ Angle
Profile
38mm Timber
Batten
Breather
Membrane
Breather Membrane
38mm Timber Batten
VMZ Interlocking
Panels
VMZ Fixation Clip
Mesh
Welted Panels VMZinc with
perforated grids
VMZ Profile clip
Mesh
Mastic Sealant
Welted Panels VMZinc with
perforated grids
Soldered clip in VMZINC
BUILDING REGULATIONS
PROPOSED FLOOR PLANS
01202 280638
mail@dotarchitecture.co.uk
www.dotarchitecture.co.uk
as shown
MAY 14
PROPOSED GROUND FLOOR PLAN
SCALE 1:50@A1
23 Pearce Avenue
Poole
BH14 8EG
102631BR
Mr & Mrs. S. Beales
PROPOSED FIRST FLOOR PLAN
SCALE 1:50@A1
G
All drawings to be read in conjunction with
Structural Engineers drawings and calculations
Denotes existing structure
E Amended to clients comments AUG 14
F Amended to clients comments SEP 14
G Amended to clients comments SEP 14
PROPOSED ANGLE DETAIL
SCALE 1:10@A1
PROPOSED WINDOW DETAIL
SCALE 1:10@A1
2. _1m _3m _5m _10m0
rwp
WALL LEGEND
BLOCK AND BEAM'
'Periscopic' type vents to manufacturers details
30mm Finish Render
100mm Concrete Block
50mm Cavity
50mm Celotex
100mm Thermalite Turbo block ( to achieve K value of 0.11)
12.5mm plasterboard on 10mm dabs, taped and skimmed
STUD WORK
70mm Metal Studwork
25MM Wool batts internally (minimum thickness 25MM, Minimum
density 10 KG/M3)
15MM Plasterboard to both sides all joints to be taped and skimed.
Smoke detector
Mains powered single station smoke detector units in strict
accordance with BS5446 within hall of house, exact position to be
determined with building inspector on site.
FIRE LEGEND
DRAINAGE.
Rain water pipes
Soil vent pipes
VENTILATION.
Mechanical extract fan ceiling mounted.
SVP
rwp
Heat Detector
W05 W06
W04
W06
D02
D01
W01 W02
W03
SL01 SL01
W02
VMZ Continuous
welt piece
Aluminium Fascia
(to clients specification)
VMZ Fixation Clip
VMZINC Interlocking
Panels
38mm Timber Batten
screwed vertically
to Blockwork
75x75mm Batten screwed
onto vertical batten
White painted render
Existing wall make up
Render bead
Sika Sarnafil Sealant
15mm Ply
VMZINC
Interlocking
Panels
VMZ Continuous
welt piece
Aluminium Fascia
(to clients specification)
15mm Ply
38mm Timber Batten
screwed vertically
to Blockwork
Aluminium Trim
Timber Batten
Timber Joists to structural
engineers design
22mm ply sat on timber firings
Single Ply
Membrane
125mm Insulation on
top of rafters.
Insulation to be fixed
by Mechanical fixings
Existing wall make up
BUILDING REGULATIONS
PROPOSED FLOOR PLANS
01202 280638
mail@dotarchitecture.co.uk
www.dotarchitecture.co.uk
as shown
MAY 14
23 Pearce Avenue
Poole
BH14 8EG
103631BR
Mr & Mrs. S. Beales
PROPOSED ROOF PLAN
SCALE 1:50@A1
PROPOSED EAVES DETAIL
SCALE 1:20@A3
SCALE 1:10@A1
E
All drawings to be read in conjunction with
Structural Engineers drawings and calculations
C Amended to clients comments AUG 14
D Amended to clients comments AUG 14
PROPOSED FRONT ELEVATION
SCALE 1:200@A3
SCALE 1:100@A1
PROPOSED SIDE ELEVATION
SCALE 1:200@A3
SCALE 1:100@A1
E Amended to clients comments SEP 14
PROPOSED CLADDED RAIL DETAIL
SCALE 1:10@A1PROPOSED ROOF DETAIL TO GARAGE
SCALE 1:10@A1
3. _1m _3m _5m _10m0
White Render
D04
W07 W08W02
Marley Eternit
Equitone Pictura
Slate Effect Roof
Tile
W10
D05
W11
W09
WINDOWS SCHEDULE
ALL WINDOWS TO COMPLY WITH
BUILDING REGULATIONS APPROVED DOCUMENT.
SAMPLE TO BE SUBMITTED BY CONTRACTOR FOR CLIENT APPROVAL
PRIOR TO ORDERING UNITS.
ALL WINDOWS TO HAVE TRICKLE VENTS AND DOUBLE GLAZED UNITS -
ALL WINDOW SIZES TO BE CONFIRMED ON SITE PRIOR TO ORDERS BEING PLACED
MANUFACTURER - TO BE CONFIRMED BY CONTRACTOR/CLIENT
MAIN CONTRACTOR TO ALLOW PROVISIONAL SUM FOR THE SUPPLY AND
FITTING OF ALL WINDOW IRONMONGERY.
D01
SL01 SL01D02
W01
W02
W03
W04
W05
W05
1200mm x 560mm
W06
W06
1100mm x 560mm
W07
W07
875mm x 1800mm
W08
W08
3044mm x 1800mm
D04 - Sliding
6000mm x 2350mm
W09
D05
W08
900mm x 1400mm
D04
W10
W11
W10
940mm x 600mm
W11
900mm x 1000mm
W07 W08W02
150.0
Breather Membrane
Aluminium Coping
VMZ Fixation Clip
38mm Timber Batten
screwed to Blockwork
200mm Ceiling Joists to
structural engineers design
100mm Dense Concrete Block
Lead Work on
top of
15mm Ply Sheathing
VMZINC Interlocking
Panels
ceiling material
to clients specification
VMZ Continuous
welt piece
Breather Membrane
Timber Fillet
75mm Celotex insulation
(or equivilant)
10kg Dense
sound fibre
quilt
Plasterboard finish
BUILDING REGULATIONS
PROPOSED ELEVATIONS
01202 280638
mail@dotarchitecture.co.uk
www.dotarchitecture.co.uk
as shown
MAY 14
23 Pearce Avenue
Poole
BH14 8EG
104631BR
Mr & Mrs. S. Beales
PROPOSED REAR ELEVATION
SCALE 1:200@A3
SCALE 1:100@A1
PROPOSED SIDE ELEVATION
SCALE 1:100@A1
PROPOSED KEY SECTION
SCALE 1:50@A1
PROPOSED FOUNDATION DETAIL
SCALE 1:10@A1
PROPOSED FLAT ROOF DETAIL
SCALE 1:10@A1
F
PROPOSED INTERMEDIATE FLOOR DETAIL
SCALE 1:10@A1
E Amended to clients comments SEP 14
F Amended to clients comments SEP 14