SlideShare a Scribd company logo
1 of 10
Download to read offline
TELKOMNIKA Telecommunication, Computing, Electronics and Control
Vol. 18, No. 5, October 2020, pp. 2708~2717
ISSN: 1693-6930, accredited First Grade by Kemenristekdikti, Decree No: 21/E/KPT/2018
DOI: 10.12928/TELKOMNIKA.v18i5.5632 ๏ฒ 2708
Journal homepage: http://journal.uad.ac.id/index.php/TELKOMNIKA
Accurate harmonic source identification using S-transform
Mohd Hatta Jopri1
, Abdul Rahim Abdullah2
, Rony Karim3
,
Srete Nikolovski4
, Tole Sutikno5
, Mustafa Manap6
1,6
Faculty of Electrical and Electronic Engineering Technology, Universiti Teknikal Malaysia Melaka, Malaysia
2
Faculty of Electrical Engineering, Universiti Teknikal Malaysia Melaka, Malaysia
3
Infineon Technologies AG, Germany
4
Department of Power System, Faculty of Electrical Engineering, University of Osijek, Croatia
5
Deparment of Electrical Engineering, Universitas Ahmad Dahlan, Indonesia
Article Info ABSTRACT
Article history:
Received Jan 15, 2020
Revised Apr 16, 2020
Accepted May 1, 2020
This paper introduces the accurate identification of harmonic sources in
the power distribution system using time-frequency distribution (TFD)
analysis, which is S-transform. The S-transform is a very applicable method
to represent signals parameters in time-frequency representation (TFR) such
as TFR impedance (ZTFR) and the main advantages of S-transform it
can provide better frequency resolution for low frequency components and
also offers better time resolution for high-frequency components.
The identification of multiple harmonic sources are based on the significant
relationship of spectral impedances (ZS) that extracted from the ZTFR, consist
of the fundamental impedance (Z1) and harmonic impedance (Zh). To verify
the accuracy of the proposed method, MATLAB simulations carried out
several unique cases on IEEE 4-bus test feeder cases. It is proven that
the proposed method is superior, with 100% correct identification of harmonic
source location. It is proven that the method is accurate, fast and cost-efficient
to localize harmonic sources in the power distribution system.
Keywords:
Harmonic source identification
Power distribution system
Spectral impedance
S-transform
Time-frequency distribution
This is an open access article under the CC BY-SA license.
Corresponding Author:
Mohd Hatta Jopri,
Faculty of Electrical and Electronic Engineering Technology,
Universiti Teknikal Malaysia Melaka (UTeM),
Hang Tuah Jaya St., 76100 Durian Tunggal, Melaka, Malaysia.
Email: hatta@utem.edu.my
1. INTRODUCTION
As the power quality (PQ) issues caused mainly by harmonics directly affect the overall continuation
of electric transmission and distribution network, the uninterrupted monitoring of electric power systems
(EPSs) has become highly necessary for the utility industry [1, 2]. The harmonic distortion causes several
adverse effects such as overheating of rotational machines, static machines, and currentโ€carrying conductors.
Furthermore, it causes premature breakdown or action of protecting appliances and harmonic resonance
situations on the customers' EPS and metering imprecisions [2, 3].
In EPS, multiple harmonic sources can be found at the utility side, which known as upstream and
downstream when harmonic sources located at the customer side with respect to a measurement point of point
of common coupling (PCC) [4, 5]. Previously, numerous of harmonic source identification can be found in
many kinds of literature. The earliest technique to localize the harmonic sources is utilizing power direction
technique. However, this method used limited harmonic power-based indices, whereas mathematical analysis
has shown the power direction method is not suitable for harmonic source detection [6, 7]. Furthermore, a state
TELKOMNIKA Telecommun Comput El Control ๏ฒ
Accurate harmonic source identification using S-transform (Mohd Hatta Jopri)
2709
estimation method is presented with the accomplishment of least square and Kirchhoff current law [8]. Yet,
a study from [9], explained that the state estimation technique requires numerous measurement devices and
unreasonable setup cost for the large power system. Thus, to overcome the previous constraint, the critical
impedance method is introduced [10, 11]. The main disadvantage of this method is to know the value of source
internal impedances of customer and utility, whereas it is difficult to obtain these parameters without switching
tests [12, 13]. Consequently, a harmonic current vector method is introduced due to solving the previous
method drawback. However, the measurement long-drawn-out and hard to analyze harmonic impedances at
the customer side [14-16].
In the previous studies [17-20], the harmonic source estimation is discussed by applying the Bayesian
estimation and harmonic state estimation (HSE). Unfortunately, this technique involves high computational
complexity and the set-up cost of the distributed measurement system station is very expensive [5, 21, 22].
In real-time, accuracy, fast analysis and low cost are essential. Therefore, the limitation of previous analysis
techniques can be solved by using signal processing techniques such as fast fourier transform (FFT),
spectrogram and S-transform [2].
A harmonic source identification using FFT is introduced to provide fast analysis in determining the
location of harmonic sources in the EPS. The significant relationship of spectral impedance, which are
fundamental and harmonic impedance are used due to identify the harmonic location of the harmonic
source [23, 24]. However, the drawback of the FFT technique, such as the signal information, for instance,
amplitude frequencies and phases, cannot be acquired correctly. This is because of the leakage, aliasing effects,
and picket fence formed by the FFT [25-27]. As a result of the FFT limitation, the spectrogram is presented to
identify the harmonic source location [28]. Conversely, the spectrogram has two main disadvantages. First, its
time-frequency resolution is limited by Heisenbergโ€™s Uncertainty Principle. Secondly, both its energy location
in the time-frequency representation and its resolution can vary with the window selected [29-32].
The S-transform is the advancement of wavelet transform (WT) and short-time fourier transform
(STFT) by its variable window and phase correction, respectively. Similar to WT, it offers an improved time
and frequency representation of a signal. Additionally, the scalable and movable Gaussian window properties
of the ST can be utilized for superior recognition of any power quality events [2, 33-35]. Due to the excellent
features of the S-transform in power quality analysis, it is a necessity to perform an analysis of identifying the
location of the harmonic sources using this technique. In this paper, the S-transform is proposed to identify the
location of the harmonic source in the distribution system with a single-point measurement approach at the point
of common coupling (PCC). S-transform is a technique that uses time-frequency analysis to distinguish the signals
in time and frequency representation (TFR) [36, 37]. The S-transform is proposed because it is able to provide
provides better frequency resolution for low-frequency components and also offers better time resolution for high-
frequency components.
2. PROPOSED METHOD
Harmonic current source type-load is selected as a frequent and widely use of harmonic producing
loads in industrial [38, 39]. A time-frequency analysis which is used in this research is the S-transform. Three
steps are proposed in this method. Firstly, measurement of voltage and current at the PCC. Secondly, these
signals are analyzed using S-transform due to obtain the signal parameters in time-frequency representation
(TFR) plane. Thirdly, the spectral impedance components are extracted from the TFR impedance and
the significant relationship of these components are used in identifying the harmonic source location.
2.1. S-transform
S-transform combines the element of wavelet transform (WT) and the short-time fourier transform
(STFT), which inherits the advantage of WT and STFT in signal processing. In particular, ST employs
a moving and scalable localizing Gaussian window in the transformation process. The Gaussian window is
as shown in (2). Mathematically ST can be defined as [29],
๐‘†๐‘‡(๐œ, ๐‘“) = โˆซ ๐‘ฅ(๐‘ก)
|๐‘“|
โˆš2๐œ‹
๐‘’
โˆ’(๐œโˆ’๐‘ก)2 ๐‘“2
2 ๐‘’โˆ’๐‘—2๐œ‹๐‘“๐‘ก
๐‘‘๐‘ก
โˆž
โˆ’โˆž
(1)
๐‘”(๐‘ก) =
1
๐œŽโˆš2๐œ‹
๐‘’
โˆ’๐‘ก2
2๐œŽ2
(2)
๐œŽ(๐‘“) =
1
|๐‘“|
(3)
where ๐‘ฅ(๐‘ก) is the signal, ๐‘ก is the time, ๐‘“ is the frequency, ๐‘”(๐‘ก) is the scalable Gaussian window, and ๐œŽ(๐‘“) is
a parameter that controls the position of the Gaussian window.
๏ฒ ISSN: 1693-6930
TELKOMNIKA Telecommun Comput El Control, Vol. 18, No. 5, October 2020: 2708 - 2717
2710
2.2. Signal parameters
The parameters of power quality signals are extracted from the TFR to provide the information of
the signal in time.
2.2.1. Instantaneous total non-harmonic distortion
Total harmonic distortion, THD, is used to measure of how much harmonic content in
a waveform [40]. The instantaneous total harmonic distortion of a waveform is defined mathematically as (4),
๐‘‡๐ป๐ท(๐‘ก) =
โˆšโˆ‘ ๐‘‰โ„Ž,๐‘Ÿ๐‘š๐‘ (๐‘ก)2๐ป
โ„Ž=2
๐‘‰1๐‘Ÿ๐‘š๐‘ (๐‘ก)
(4)
where Vh,rms(t) is RMS harmonic voltage and Vh,rms(t) is RMS fundamental voltage. The instantaneous total
harmonic distortion of a waveform is defined mathematically as.
2.2.2. Instantaneous total non-harmonic distortion
Besides harmonic, a signal also contains interharmonic components that are not multiple integers of
the power system frequency [27]. Referring to this as the instantaneous total nonharmonic distortion,
(TnHD(t)), then for this parameter is written as (5).
๐‘‡๐‘›๐ป๐ท(๐‘ก) =
โˆš๐‘‰๐‘Ÿ๐‘š๐‘ (๐‘ก)2โˆ’โˆ‘ ๐‘‰โ„Ž,๐‘Ÿ๐‘š๐‘ (๐‘ก)2๐ป
โ„Ž=0
๐‘‰1๐‘Ÿ๐‘š๐‘ (๐‘ก)
(5)
2.3. Spectral impedance
The spectral impedance (ZS) components are extracted from the TFR impedance (ZTFR). The ZTFR can be
calculated using equation at each harmonic frequency and the values then plotted. The ZTFR is expressed as (6) [13].
๐‘ ๐‘‡๐น๐‘… =
๐‘† ๐‘‰(๐‘ก,๐‘“)
๐‘† ๐ผ(๐‘ก,๐‘“)
(6)
where SV(t,f) is the TFR of voltage and SI(t,f) is the TFR of current. The spectral impedance consists of
a fundamental impedance (Z1), whereas the harmonic impedance (Zh) is a harmonic impedance at the order
number of harmonic.
2.4. Implementation of proposed method
In most recent studies, suggest the execution of the proposed technique can be realized as depicts in
Figure 1 (a) and Figure 1 (b) using IEEE 4-bus test feeders, while the harmonic source is modeled as an
inverter-based load, which is known as harmonic current source type-load [41-43], where N is a linear load,
which is a resistor whereas H is a harmonic source. Besides, four specific cases are considered in this research,
such as [15 , 44, 45]:
- Case 1: No harmonic source in the power network system
- Case 2: Harmonic source at downstream of the PCC
- Case 3: Harmonic sources at upstream and downstream of the PCC
- Case 4: Harmonic source at upstream of the PCC
(a) (b)
Figure 1. (a) Upstream-downstream for case 1, (b) IEEE 4-bus test feeders for case 2, 3 and 4
3. RESULTS AND ANALYSIS
In this section, it is explained the results of the research and at the same time is given
the comprehensive discussion. Results can be presented in figures and tables.
TELKOMNIKA Telecommun Comput El Control ๏ฒ
Accurate harmonic source identification using S-transform (Mohd Hatta Jopri)
2711
3.1. Case 1: No harmonic source in the power network system
The linear load, which is resistive loads, are located upstream and downstream of the PCC. As can be
seen in Figures 2 (a) and (b) show the measured voltage and current signals in the time domain. The peak
voltage is 326.5 V. In contrast, the peak current is 66.5 A, respectively. Besides, Figure 2 (c) shows the THD(t)
and TnHD(t) of voltage and both parameters are zero percent. Meanwhile, Figure 2 (d) presents the THD(t)
and TnHD(t) of current and both parameters are zero percent too. It shows that the voltage and current signal
have neither harmonic nor interharmonic components. Figure 2 (e) shows the ZTFR of the PCC, while
Figure 2 (f) presents the ZS. The most striking result from ZS, it is shown that the Z1 at 50 Hz is of 4.8 ohm and
no harmonic impedances exist. Thus, for case 1, the significant relationship between Z1 and Zh at the condition
of no harmonic source in the power system network, where for harmonic component, h is any positive integer
whereas, for interharmonic, h is any positive non-integer. can be written as:
๐‘1 โ‰  0 ๐‘œโ„Ž๐‘š (7)
๐‘โ„Ž โ‰  0 ๐‘œโ„Ž๐‘š (8)
(a) (b)
(c) (d)
(e) (f)
Figure 2. Case 1; (a) voltage signal in time domain, (b) current signal in time domain,
(c) THD(t) and TnHD(t) of voltage, (d) THD(t) and TnHD(t) of current,
(e) TFR of impedance (ZTFR), (f) spectral impedance component
3.2. Case 2: Harmonic source at downstream of the PCC
For case 2, the harmonic source is located downstream of the PCC. As can be seen in Figure 3 (a) and
Figure 3 (b) show the measured voltage and current signals in the time domain. The peak voltage is 326.5 V.
In contrast, the peak current is 66.5 A, respectively. In addition, Figure 3 (c) shows the THD(t) and TnHD(t)
mean of voltage are 1.51% and 6.05%, respectively. In the meantime, Figure 3 (d) presents the THD(t) and
TnHD(t) mean of current, which are 1.67% and 6.68%, respectively. The values of THD(t) and TnHD(t) show
๏ฒ ISSN: 1693-6930
TELKOMNIKA Telecommun Comput El Control, Vol. 18, No. 5, October 2020: 2708 - 2717
2712
that the voltage and current signals do have harmonic and interharmonic components. Figure 3 (e) shows
the ZTFR of the PCC and the ZS is obtained by extracting the parameters from the ZTFR. Meanwhile, Figure 3 (f)
presents the ZS that consists of the Z1. In contrast the harmonic impedance consists of Z275, Z375, Z600, Z700, Z825
and Z900, respectively. It is crucial to observe the relationship of ZS components due to identify the harmonic
source location in the power system network. Interestingly, as shown in Table 1, the Z1 value at 50 Hz, is
always higher than any Zh. Thus, for case 2, the significant relationship between Z1 and Zh at the condition of
the harmonic source located at downstream of the PCC can be concluded and written as:
๐‘1 โ‰  0 ๐‘œโ„Ž๐‘š (9)
๐‘โ„Ž < ๐‘1 (10)
where for harmonic component, h is any positive integer whereas, for interharmonic, h is any positive
non-integer.
(a) (b)
(c) (d)
(e) (f)
Figure 3. Case 2; (a) voltage signal in time domain, (b) current signal in time domain,
(c) THD(t) and TnHD(t) of voltage, (d) THD(t) and TnHD(t) of current,
(e) TFR of impedance (ZTFR), (f) spectral impedance component
3.3. Case 3: Harmonic sources at upstream and downstream of the PCC
For case 3, the harmonic source is located upstream and downstream of the PCC. As can be seen in
Figures 4 (a) and (b) show the measured voltage and current signals in the time domain. The peak voltage is
TELKOMNIKA Telecommun Comput El Control ๏ฒ
Accurate harmonic source identification using S-transform (Mohd Hatta Jopri)
2713
324.7 V, while the peak current is 44.6 A, respectively. Besides, Figure 4 (c) shows the THD(t) and TnHD(t)
mean of voltage are 1.47% and 6.04%, respectively. In the meantime, Figure 4 (d) presents the THD(t) and
TnHD(t) mean of current, which are 1.91% and 45.18%, respectively. The values of THD(t) and TnHD(t) show
that the voltage and current signals do have harmonic and interharmonic components. Figure 4 (e) shows
the ZTFR of the PCC, while Figure 4 (f) presents the ZS that been extracted from the ZTFR. Furthermore,
Figure 4 (f) shows that the Z1 is 5.36 ohm; in contrast the harmonic impedance consists of Z275, Z375, Z400, Z600,
Z700 and Z900, respectively. The characteristic of the spectral impedance, ZS are summarized in Table 2. What is
surprising is that the value of Z1 is always smaller than any harmonic impedances, Zh. It is apparent from
the result that the ZS components can be characterized due to identify the location of the harmonic source.
As a result, for case 3, the significant relationship between Z1 and Zh at the condition of the harmonic source
located downstream of the PCC can be written as:
๐‘1 โ‰  0 ๐‘œโ„Ž๐‘š (11)
๐‘โ„Ž > ๐‘1 (12)
where for harmonic component, h is any positive integer whereas, for interharmonic, h is any positive
non-integer.
(a) (b)
(c) (d)
(e) (f)
Figure 4 Case 3; (a) voltage signal in time domain, (b) current signal in time domain,
(c) THD(t) and TnHD(t) of voltage, (d) THD(t) and TnHD(t) of current,
(e) TFR of impedance (ZTFR), (f) spectral impedance component
๏ฒ ISSN: 1693-6930
TELKOMNIKA Telecommun Comput El Control, Vol. 18, No. 5, October 2020: 2708 - 2717
2714
Table 1. Magnitudes of the spectral impedance for
case 2 using S-transform technique
Spectral Impedance Ohm
Z1 5.36
Z275 3.81
Z375 3.68
Z600 4.19
Z700 4.34
Z825 3.94
Z900 3.68
Table 2. Magnitudes of the spectral impedance for
case 3 using S-transform technique
Spectral Impedance Ohm
Z1 6.5
Z275 12.8
Z375 11.8
Z400 12.3
Z600 12.2
Z700 12.5
Z900 12.9
3.4. Case 4: Harmonic source at upstream of the PCC
In case 4, the harmonic source is located upstream of the PCC. The voltage and current signals in
the time domain are measured at the PCC are shown in Figures 5 (a) and (b). The peak voltage is 324.3 V,
whereas the peak current is 30.65 A and the fundamental frequency is 50 Hz. These signals are used as
the inputs for analyzing harmonic sources using the S-transform technique. It can be seen from the waveforms
that the voltage and current waveforms are distorted because of the harmonic source presents in the network
system. Furthermore, Figure 5 (c) shows the THD(t) and TnHD(t) mean of voltage, which are 1.47%
and 6.04%, respectively. Moreover, Figure 5 (d) shows the THD(t) and TnHD(t) mean of current are 1.5%
and 6.05%, respectively. The values of THD(t) and TnHD(t) show that the voltage and current signals do have
harmonic and interharmonic components. The ZS components are extracted from the ZTFR shown in
Figure 5 (e). As shown in Figure 5 (f), the spectral impedance, ZS, consists of fundamental impedance, Z1 at 50
Hz, whereas the harmonic impedances such as Z275, Z300, Z375, Z400, Z600, Z700, Z900, respectively.
(a) (b)
(c) (d)
(e) (f)
Figure 5. Case 4, (a) Voltage signal in time domain, (b) Current signal in time domain,
(c) THD(t) and TnHD(t) of voltage, (d) THD(t) and TnHD(t) of current,
(e) TFR of impedance (ZTFR), (f) Spectral impedance component
TELKOMNIKA Telecommun Comput El Control ๏ฒ
Accurate harmonic source identification using S-transform (Mohd Hatta Jopri)
2715
The ZS components relationship are the critical driving factor of harmonic source identification and
the values of the components are summarized in Table 3. It can be seen that the Z1 is always the same value as
all harmonic impedances, Zh. Based on the results, it can be concluded that the ZS components can be used to
identify the location of harmonic sources. Hence, for case 4, the significant relationship between Z1 and Zh at
the condition of the harmonic source located at downstream of the PCC can be written as:
๐‘1 โ‰  0 ๐‘œโ„Ž๐‘š (13)
๐‘โ„Ž = ๐‘1 (14)
where for harmonic component, h is any positive integer whereas, for interharmonic, h is any positive
non-integer.
Table 3. Magnitudes of the spectral impedance for case 4 using S-transform technique
Spectral Impedance Ohm
Z1 10.6
Z275 10.6
Z300 10.6
Z375 10.6
Z400 10.6
Z600 10.6
Z700 10.6
Z900 10.6
3.5. Performance of the proposed method
This research provides an exciting opportunity to advance the understanding of harmonic source
identification using the S-transform technique. The main contribution of this analysis is the significant
relationship of the spectral impedance components, ZS such as fundamental impedance, Z1 and harmonic
impedance, Zh in identifying the location of the harmonic source in the network system. The spectral impedance
characteristics are used to identify the location of harmonic sources and the performance of this proposed
method are summarizes in Table 4.
Table 4. Performance of harmonic source identification using spectral impedance components characteristics
Case Upstream side Downstream side Spectral impedance, ZS characteristic % Correct identification
1 N N Z1 โ‰  0 ohm
Zh = 0 ohm
100
2 N H Z1โ‰  0 ohm
Z1 > Zh
100
3 H H Z1 โ‰  0 ohm
Zh > Z1
100
4 N H Z1 โ‰  0 ohm
Zh = Z1
100
4. CONCLUSION
The main concern of this research is to identify the location of harmonic source that connected to
the distribution system utilizing the S-transform technique. The main contribution of this research is
the significant relationship of ZS components that obtained from the S-transform analysis in identifying
the location of harmonic sources. Based on Table 4, the correctness of the proposed method is 100% for each
case and the significant relationship of ZS for identification of harmonic source location are summarized
as follow:
- If Z1 โ‰  0 and Zh = 0, there is no source in the network system.
- If Z1โ‰  0 and Z1 > Zh, there is a harmonic source located at downstream of the PCC.
- If Z1โ‰  0 and Zh > Z1, there are a harmonic sources located at upstream and downstream of the PCC.
- If Z1 โ‰  0 and Z1 = Zh, there is a harmonic source located at upstream of the PCC.
Consequently, considering the results, this method can be used accurately in distinguishing the location of
the harmonic source.
๏ฒ ISSN: 1693-6930
TELKOMNIKA Telecommun Comput El Control, Vol. 18, No. 5, October 2020: 2708 - 2717
2716
ACKNOWLEDGEMENTS
This research is supported by the Advanced Digital Signal Processing Laboratory (ADSP Lab).
Special thanks also to the Faculty of Electrical and Electronic Engineering Technology of Universiti Teknikal
Malaysia Melaka (UTeM), Center for Robotics and Industrial Automation (CeRIA) of UTeM and Ministry of
Higher Education Malaysia (MOHE). Their support is gratefully acknowledged.
REFERENCES
[1] D. D. Ferreira et al., โ€œMethod based on independent component analysis for harmonic extraction from power system
signals,โ€ Electr. Power Syst. Res., vol. 119, pp. 19-24, February 2015.
[2] M. Mishra, โ€œPower quality disturbance detection and classification using signal processing and soft computing
techniques: A comprehensive review,โ€ International Transactions on Electrical Energy Systems, vol. 29, no. 2,
March 2019.
[3] M. Farhoodnea, et al., โ€œAn improved method for determining contribution of utility and customer harmonic
distortions in a power distribution system,โ€ Int. J. Electr. Eng. Informatics, vol. 2, no. 3, pp. 204-215, 2010.
[4] M. Farhoodnea, A. Mohamed, and H. Shareef, โ€œA single point measurement method for evaluating harmonic
contributions of utility and customer in power distribution systems,โ€ Journal of Applied Sciences, vol. 11, no. 2.
pp. 257-265, February 2011.
[5] A. R. Abdullah, et al., โ€œLocalization of multiple harmonic sources for inverter loads utilizing periodogram,โ€
J. Teknol., vol. 8, no. 2, pp. 87-91, January 2016.
[6] W. Xu, โ€œPower direction method cannot be used for harmonic source detection,โ€ 2000 Power Engineering Society
Summer Meeting (Cat. No.00CH37134), vol. 2, pp. 873-876, July 2000.
[7] F. Xu, et al., โ€œStudy on constraints for harmonic source determination using active power direction,โ€ IEEE Trans.
Power Deliv., vol. 33, no. 6, pp. 2683-2692, Dec. 2018.
[8] Y. Liu, et al., โ€œHarmonic source location at the point of common coupling based on the nonlinearity index of load,โ€
2009 Asia-Pacific Power and Energy Engineering Conference, 2009, pp. 1-5, March 2009.
[9] A. R. Abdullah, G. Z. Peng and S. A. Ghani, โ€œA new vector draft method for harmonic source detection at point of
common coupling,โ€ Proc. 2014 IEEE 8th Int. Power Eng. Optim. Conf. PEOCO 2014, pp. 110-114, March 2014.
[10] F. Safargholi, K. Malekian, and W. Schufft, โ€œOn the dominant harmonic source identification-Part II: Application
and interpretation of methods,โ€ IEEE Transaction on Power Delivery, vol. 33, no. 3, pp. 1278-1287, Jun. 2018.
[11] F. Safargholi, K. Malekian, and W. Schufft, โ€œOn the dominant harmonic source identification - Part I: Review of
Methods,โ€ IEEE Trans. Power Deliv., vol. 33, no. 3, pp. 1268-1277, Jun. 2018.
[12] A. R. Abdullah, et al., โ€œLocalization of multiple harmonic sources for inverter loads utilizing periodogram,โ€
J. Telecommun. Electron. Comput. Eng., vol. 8, no. 2, 2016.
[13] A. Abdullah, M. Manap, et al., โ€œAn improved spectrogram to identify multiple harmonic sources in distribution
system with inverter loads,โ€ Proceedings of the International MultiConference of Engineers and Computer
Scientists., vol. II, pp. 0-5, March 2017.
[14] N. Hamzah, et al., โ€œIdentification of harmonic source at the point of common coupling based on voltage indices,โ€
J. Teknol., vol. 43, no. 1, pp. 11-32, Dec. 2005.
[15] A. Abdullah, and M. Manap, โ€œAn improved spectrogram to identify multiple harmonic sources in distribution system
with inverter loads,โ€ Proceedings of the International MultiConference of Engineers and Computer Scientists.,
vol. 7, no. 4, pp. 11591, 2017.
[16] A. Banshwar and A. K. Chandel, โ€œIdentification of harmonic sources using fuzzy logic,โ€ 2010 Jt. Int. Conf. Power
Electron. Drives Energy Syst. 2010 Power India, pp. 1โ€“7, December 2010.
[17] C. Jaipradidtham, โ€œA control of real voltage and harmonic analysis with adaptive static var of electric arc furnace for
power quality improvement by Grey Markov method,โ€ 2016 IEEE 6th Int. Conf. Power Syst. ICPS 2016, no. 1,
March 2016.
[18] T. Zang, et al., โ€œHarmonic source localization approach based on fast kernel entropy optimization ICA and minimum
conditional entropy,โ€ Entropy, vol. 18, no. 6, pp. 214, June 2016.
[19] T. Pfajfar, B. Blaลพiฤ, and I. Papiฤ, โ€œHarmonic contributions evaluation with the harmonic current vector method,โ€
IEEE Transactions on Power Delivery, vol. 23, no. 1, pp. 425-433, January 2008.
[20] A. R. Abdullah, et al., โ€œAn identification of multiple harmonic sources in a distribution system by using
spectrogram,โ€ Bulletin of Electrical. Engineering and Informatics, vol. 7, no. 2, pp. 244-256, June 2018.
[21] P. Supriya and T. N. Padmanabhan Nambiar, โ€œReview of harmonic source identification techniques,โ€ International.
Review. Electrical. Engineering., vol. 7, no. 3, pp. 4525-4531, June 2012.
[22] G. Dโ€™Antona, et al., โ€œHarmonic source estimation in distribution systems,โ€ Appl. Meas. Power Syst. (AMPS), 2010
IEEE Int. Work., vol. 60, no. 10, pp. 1-5, September 2010.
[23] A. R. Abdullah, et al., โ€œA fast localization of multiple harmonic sources for rectifier loads by utilizing periodogram,โ€
Telkomnika (Telecommunication Computer. Electronics. and Control., vol. 15, no. 1, March 2017.
[24] A. Rahim Abdullah, et al., โ€œPerformance evaluation of real power quality disturbances analysis using S-transform,โ€
Appl. Mech. Mater., vol. 752โ€“753, pp. 1343-1348, April 2015.
[25] A. R. Abdullah, et al., โ€œShort-circuit switches fault analysis of voltage source inverter using spectrogram,โ€ Electr.
Mach. Syst. (ICEMS), 2013 Int. Conf., pp. 1808-1813, October 2013.
TELKOMNIKA Telecommun Comput El Control ๏ฒ
Accurate harmonic source identification using S-transform (Mohd Hatta Jopri)
2717
[26] N. A. Abidullah, et al., โ€œReal-time power quality signals monitoring system,โ€ Proceeding - 2013 IEEE Student
Conference on Research and Development, SCOReD 2013, January 2015.
[27] A. Abdullah, et al., โ€œA utilisation of improved gabor transform for harmonic signals detection and classification
analysis,โ€ International. Journal of Electrical and Computer Engineering, vol. 7, no. 1, pp. 21-28, February 2017.
[28] A. R. Abdullah, et al., โ€œAn improved of multiple harmonic sources identification in distribution system with inverter
loads by using spectrogram,โ€ Bull. Electr. Eng. Informatics, vol. 7, no. 2, pp. 244-256, December 2018.
[29] A. R. Abdullah, et al., โ€œAn accurate classification method of harmonic signals in power distribution system
by utilising S-transform,โ€ TELKOMNIKA Telecommunication, Computing, Electronics and Control, vol. 15, no. 1,
pp. 12-20, March 2017.
[30] A. R. Abdullah, et al., โ€œPower quality signals classification system using time-frequency distribution,โ€ Appl. Mech.
Mater., vol. 494-495, pp. 1889-1894, 2014.
[31] A. R. Abdullah, et al., โ€œPerformance verification of power quality signals classification system,โ€ Applied. Mechanics
and. Materials., vol. 753, pp. 1158-1163, April 2015.
[32] A. R. Abdullah, et al., โ€œAn improved detection and classification technique of harmonic signals in power distribution
by utilizing spectrogram,โ€ International Journal Electrical and Computer Engineering, vol. 7, no. 1, pp. 12-20, 2017.
[33] A. G. Miamee, โ€œNonstationary stochastic processes and their applications,โ€ Workshop on Nonstationary Stochastic
Processes and Their Application, pp. 1-298, August 1991.
[34] N. H. T. Ahmad, A. R. Abdullah and N. A. Abidullah, โ€œAnalysis of power quality disturbances using spectrogram
and S-transform,โ€ International Review of Electrical Engineering, vol. 9, no. 3, pp. 611-619, June 2014.
[35] A. R. Abdullah, et al., โ€œA critical review of time-frequency distribution analysis for detection and classification of
harmonic signal in power distribution system,โ€ International Journal Electrical and. Computer Engineering, vol. 8,
no. 6, pp. 4603-4618, December 2018.
[36] N. A. Abidullah, et al., โ€œReal-time power quality signals monitoring system,โ€ Proceeding - 2013 IEEE Student Conf.
Res. Dev. SCOReD 2013, pp. 433-438, December 2013.
[37] N. H. T. Huda, A. R. Abdullah, et al., โ€œPower quality signals detection using S-transform,โ€ Proc. 2013 IEEE 7th Int.
Power Eng. Optim. Conf. PEOCO 2013, pp. 552-557, June 2013.
[38] C.-I. Chen and Y. Chen, โ€œA neural-network-based data-driven nonlinear model on time- and frequency-domain
voltage-current characterization for power-quality study,โ€ IEEE Transaction on Power Delivery, vol. 30, no. 3,
pp. 1577-1584, Jun. 2015.
[39] J. Wu, et al., โ€œIdentification of multiple harmonic sources in cyber-physical energy system using supervised
independent component analysis,โ€ 2014 IEEE International Instrumentation and Measurement Technology
Conference , pp. 496-501, 2014.
[40] M. Manap, et al., โ€œComparison of open and short-circuit switches faults voltage source inverter (VSI) analysis using
time-frequency distributions,โ€ Applied Mechanics and Materials., vol. 752โ€“753, pp. 1164-1169, April 2015.
[41] M. L. Baughman and R. C. Dugan, โ€œIEEE 4 Node Test Feeder,โ€ Inst. Electr. Electron. Eng. Inc, pp. 1-9, 2009.
[42] A. K. Bharati and V. Ajjarapu, โ€œInvestigation of relevant distribution system representation with DG for voltage
stability margin assessment,โ€ IEEE Transaction on Power System, vol, 99, pp. 1-1, Oct. 2019.
[43] M. J. E. Alam, K. M. Muttaqi, and D. Sutanto, โ€œA three-phase power flow approach for integrated 3-wire MV and 4-wire
multigrounded LV networks with rooftop solar PV,โ€ IEEE Trans. Power Syst., vol. 28, no. 2, pp. 1728-1737, 2013.
[44] M. Narimani, S. H. Hosseinian, and B. Vahidi, โ€œA method for harmonic power tracing by using upstream and
downstream distribution matrices,โ€ Electr. Power Components Syst., vol. 47, no. 13, pp. 1169-1179, Aug. 2019.
[45] P. Sinha, S. K. Goswami, and S. Debnath, โ€œHarmonic source identification in distribution system using non-active
power quantities,โ€ Int. J. Power Energy Convers., vol. 8, no. 1, pp. 90-111, January 2017.

More Related Content

What's hot

40120140505007 2-3-4
40120140505007 2-3-440120140505007 2-3-4
40120140505007 2-3-4IAEME Publication
ย 
Signal-Energy Based Fault Classification of Unbalanced Network using S-Transf...
Signal-Energy Based Fault Classification of Unbalanced Network using S-Transf...Signal-Energy Based Fault Classification of Unbalanced Network using S-Transf...
Signal-Energy Based Fault Classification of Unbalanced Network using S-Transf...idescitation
ย 
The Need for Enhanced Power System Modelling Techniques & Simulation Tools
The Need for Enhanced  Power System  Modelling Techniques  &  Simulation Tools The Need for Enhanced  Power System  Modelling Techniques  &  Simulation Tools
The Need for Enhanced Power System Modelling Techniques & Simulation Tools Power System Operation
ย 
Design and verification of pipelined parallel architecture implementation in ...
Design and verification of pipelined parallel architecture implementation in ...Design and verification of pipelined parallel architecture implementation in ...
Design and verification of pipelined parallel architecture implementation in ...eSAT Publishing House
ย 
Power System Modeling Techniques & Simulation Tools
Power System Modeling Techniques & Simulation ToolsPower System Modeling Techniques & Simulation Tools
Power System Modeling Techniques & Simulation ToolsPower System Operation
ย 
Computer aided-teaching-of-transformers-for-undergraduates
Computer aided-teaching-of-transformers-for-undergraduatesComputer aided-teaching-of-transformers-for-undergraduates
Computer aided-teaching-of-transformers-for-undergraduatesRajesh Kumar
ย 
H04654853
H04654853H04654853
H04654853IOSR-JEN
ย 
Paper Publication 163-143696093856-61
Paper Publication 163-143696093856-61Paper Publication 163-143696093856-61
Paper Publication 163-143696093856-61sayaji nagargoje
ย 
Distributed Power-Flow Controller (DPFC) Simulation
Distributed Power-Flow Controller (DPFC) SimulationDistributed Power-Flow Controller (DPFC) Simulation
Distributed Power-Flow Controller (DPFC) SimulationIJERA Editor
ย 
Wide Area Fault Location for Power Transmission Network using Reactance Based...
Wide Area Fault Location for Power Transmission Network using Reactance Based...Wide Area Fault Location for Power Transmission Network using Reactance Based...
Wide Area Fault Location for Power Transmission Network using Reactance Based...Muhd Hafizi Idris
ย 
Design of CW THz Photonic Transmitter based on Low Pass-Filter and Bow-tie W...
Design of CW THz Photonic Transmitter based on  Low Pass-Filter and Bow-tie W...Design of CW THz Photonic Transmitter based on  Low Pass-Filter and Bow-tie W...
Design of CW THz Photonic Transmitter based on Low Pass-Filter and Bow-tie W...IJECEIAES
ย 
WAVELET- FUZZY BASED MULTI TERMINAL TRANSMISSION SYSTEM PROTECTION SCHEME IN ...
WAVELET- FUZZY BASED MULTI TERMINAL TRANSMISSION SYSTEM PROTECTION SCHEME IN ...WAVELET- FUZZY BASED MULTI TERMINAL TRANSMISSION SYSTEM PROTECTION SCHEME IN ...
WAVELET- FUZZY BASED MULTI TERMINAL TRANSMISSION SYSTEM PROTECTION SCHEME IN ...ijfls
ย 
Adaptive resources assignment in OFDM-based cognitive radio systems
Adaptive resources assignment in OFDM-based cognitive radio systemsAdaptive resources assignment in OFDM-based cognitive radio systems
Adaptive resources assignment in OFDM-based cognitive radio systemsIJECEIAES
ย 

What's hot (18)

A Time-Frequency Transform Based Fault Detectionand Classificationof STATCOM ...
A Time-Frequency Transform Based Fault Detectionand Classificationof STATCOM ...A Time-Frequency Transform Based Fault Detectionand Classificationof STATCOM ...
A Time-Frequency Transform Based Fault Detectionand Classificationof STATCOM ...
ย 
40120140505007 2-3-4
40120140505007 2-3-440120140505007 2-3-4
40120140505007 2-3-4
ย 
40120140505007 2-3
40120140505007 2-340120140505007 2-3
40120140505007 2-3
ย 
40120140501014
4012014050101440120140501014
40120140501014
ย 
Signal-Energy Based Fault Classification of Unbalanced Network using S-Transf...
Signal-Energy Based Fault Classification of Unbalanced Network using S-Transf...Signal-Energy Based Fault Classification of Unbalanced Network using S-Transf...
Signal-Energy Based Fault Classification of Unbalanced Network using S-Transf...
ย 
E1082935
E1082935E1082935
E1082935
ย 
The Need for Enhanced Power System Modelling Techniques & Simulation Tools
The Need for Enhanced  Power System  Modelling Techniques  &  Simulation Tools The Need for Enhanced  Power System  Modelling Techniques  &  Simulation Tools
The Need for Enhanced Power System Modelling Techniques & Simulation Tools
ย 
Design and verification of pipelined parallel architecture implementation in ...
Design and verification of pipelined parallel architecture implementation in ...Design and verification of pipelined parallel architecture implementation in ...
Design and verification of pipelined parallel architecture implementation in ...
ย 
Power System Modeling Techniques & Simulation Tools
Power System Modeling Techniques & Simulation ToolsPower System Modeling Techniques & Simulation Tools
Power System Modeling Techniques & Simulation Tools
ย 
Computer aided-teaching-of-transformers-for-undergraduates
Computer aided-teaching-of-transformers-for-undergraduatesComputer aided-teaching-of-transformers-for-undergraduates
Computer aided-teaching-of-transformers-for-undergraduates
ย 
H04654853
H04654853H04654853
H04654853
ย 
Paper Publication 163-143696093856-61
Paper Publication 163-143696093856-61Paper Publication 163-143696093856-61
Paper Publication 163-143696093856-61
ย 
Distributed Power-Flow Controller (DPFC) Simulation
Distributed Power-Flow Controller (DPFC) SimulationDistributed Power-Flow Controller (DPFC) Simulation
Distributed Power-Flow Controller (DPFC) Simulation
ย 
Wide Area Fault Location for Power Transmission Network using Reactance Based...
Wide Area Fault Location for Power Transmission Network using Reactance Based...Wide Area Fault Location for Power Transmission Network using Reactance Based...
Wide Area Fault Location for Power Transmission Network using Reactance Based...
ย 
Design of CW THz Photonic Transmitter based on Low Pass-Filter and Bow-tie W...
Design of CW THz Photonic Transmitter based on  Low Pass-Filter and Bow-tie W...Design of CW THz Photonic Transmitter based on  Low Pass-Filter and Bow-tie W...
Design of CW THz Photonic Transmitter based on Low Pass-Filter and Bow-tie W...
ย 
WAVELET- FUZZY BASED MULTI TERMINAL TRANSMISSION SYSTEM PROTECTION SCHEME IN ...
WAVELET- FUZZY BASED MULTI TERMINAL TRANSMISSION SYSTEM PROTECTION SCHEME IN ...WAVELET- FUZZY BASED MULTI TERMINAL TRANSMISSION SYSTEM PROTECTION SCHEME IN ...
WAVELET- FUZZY BASED MULTI TERMINAL TRANSMISSION SYSTEM PROTECTION SCHEME IN ...
ย 
Adaptive resources assignment in OFDM-based cognitive radio systems
Adaptive resources assignment in OFDM-based cognitive radio systemsAdaptive resources assignment in OFDM-based cognitive radio systems
Adaptive resources assignment in OFDM-based cognitive radio systems
ย 
Sub519
Sub519Sub519
Sub519
ย 

Similar to Accurate harmonic source identification using S-transform

An Identification of Multiple Harmonic Sources in a Distribution System by Us...
An Identification of Multiple Harmonic Sources in a Distribution System by Us...An Identification of Multiple Harmonic Sources in a Distribution System by Us...
An Identification of Multiple Harmonic Sources in a Distribution System by Us...journalBEEI
ย 
Differential equation fault location algorithm with harmonic effects in power...
Differential equation fault location algorithm with harmonic effects in power...Differential equation fault location algorithm with harmonic effects in power...
Differential equation fault location algorithm with harmonic effects in power...TELKOMNIKA JOURNAL
ย 
An Improved Detection and Classification Technique of Harmonic Signals in Pow...
An Improved Detection and Classification Technique of Harmonic Signals in Pow...An Improved Detection and Classification Technique of Harmonic Signals in Pow...
An Improved Detection and Classification Technique of Harmonic Signals in Pow...IJECEIAES
ย 
A verification of periodogram technique for harmonic source diagnostic analyt...
A verification of periodogram technique for harmonic source diagnostic analyt...A verification of periodogram technique for harmonic source diagnostic analyt...
A verification of periodogram technique for harmonic source diagnostic analyt...TELKOMNIKA JOURNAL
ย 
An Accurate Classification Method of Harmonic Signals in Power Distribution S...
An Accurate Classification Method of Harmonic Signals in Power Distribution S...An Accurate Classification Method of Harmonic Signals in Power Distribution S...
An Accurate Classification Method of Harmonic Signals in Power Distribution S...TELKOMNIKA JOURNAL
ย 
A Utilisation of Improved Gabor Transform for Harmonic Signals Detection and ...
A Utilisation of Improved Gabor Transform for Harmonic Signals Detection and ...A Utilisation of Improved Gabor Transform for Harmonic Signals Detection and ...
A Utilisation of Improved Gabor Transform for Harmonic Signals Detection and ...IJECEIAES
ย 
A Utilisation of Improved Gabor Transform for Harmonic Signals Detection and ...
A Utilisation of Improved Gabor Transform for Harmonic Signals Detection and ...A Utilisation of Improved Gabor Transform for Harmonic Signals Detection and ...
A Utilisation of Improved Gabor Transform for Harmonic Signals Detection and ...Yayah Zakaria
ย 
An Analysis of Harmonic and Interharmonic Contribution of Electric Arc Furnac...
An Analysis of Harmonic and Interharmonic Contribution of Electric Arc Furnac...An Analysis of Harmonic and Interharmonic Contribution of Electric Arc Furnac...
An Analysis of Harmonic and Interharmonic Contribution of Electric Arc Furnac...IJECEIAES
ย 
Diagnosis of broken bars fault in induction machines using higher order spect...
Diagnosis of broken bars fault in induction machines using higher order spect...Diagnosis of broken bars fault in induction machines using higher order spect...
Diagnosis of broken bars fault in induction machines using higher order spect...ISA Interchange
ย 
A Fast Localization of Multiple Harmonic Sources for Rectifier Loads by Utili...
A Fast Localization of Multiple Harmonic Sources for Rectifier Loads by Utili...A Fast Localization of Multiple Harmonic Sources for Rectifier Loads by Utili...
A Fast Localization of Multiple Harmonic Sources for Rectifier Loads by Utili...TELKOMNIKA JOURNAL
ย 
IRJET- Low Cost Harmonic Measurement using Arduino UNO
IRJET-  	  Low Cost Harmonic Measurement using Arduino UNOIRJET-  	  Low Cost Harmonic Measurement using Arduino UNO
IRJET- Low Cost Harmonic Measurement using Arduino UNOIRJET Journal
ย 
Voltage variations identification using Gabor Transform and rule-based classi...
Voltage variations identification using Gabor Transform and rule-based classi...Voltage variations identification using Gabor Transform and rule-based classi...
Voltage variations identification using Gabor Transform and rule-based classi...IJECEIAES
ย 
A simple faulted phase-based fault distance estimation algorithm for a loop d...
A simple faulted phase-based fault distance estimation algorithm for a loop d...A simple faulted phase-based fault distance estimation algorithm for a loop d...
A simple faulted phase-based fault distance estimation algorithm for a loop d...nooriasukmaningtyas
ย 
A simple faulted phase-based fault distance estimation algorithm for a loop d...
A simple faulted phase-based fault distance estimation algorithm for a loop d...A simple faulted phase-based fault distance estimation algorithm for a loop d...
A simple faulted phase-based fault distance estimation algorithm for a loop d...IJEECSIAES
ย 
International Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentInternational Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentIJERD Editor
ย 
Ri 7
Ri 7Ri 7
Ri 7Tarighat
ย 
Transient Monitoring Function based Fault Classifier for Relaying Applications
Transient Monitoring Function based Fault Classifier for Relaying Applications Transient Monitoring Function based Fault Classifier for Relaying Applications
Transient Monitoring Function based Fault Classifier for Relaying Applications IJECEIAES
ย 
Analysis of harmonics and resonances in hvdc mmc link connected to AC grid
Analysis of harmonics and resonances in hvdc mmc link connected to AC gridAnalysis of harmonics and resonances in hvdc mmc link connected to AC grid
Analysis of harmonics and resonances in hvdc mmc link connected to AC gridBรฉrengรจre VIGNAUX
ย 
WAVELET- FUZZY BASED MULTI TERMINAL TRANSMISSION SYSTEM PROTECTION SCHEME IN ...
WAVELET- FUZZY BASED MULTI TERMINAL TRANSMISSION SYSTEM PROTECTION SCHEME IN ...WAVELET- FUZZY BASED MULTI TERMINAL TRANSMISSION SYSTEM PROTECTION SCHEME IN ...
WAVELET- FUZZY BASED MULTI TERMINAL TRANSMISSION SYSTEM PROTECTION SCHEME IN ...Wireilla
ย 
ESPRIT Method Enhancement for Real-time Wind Turbine Fault Recognition
ESPRIT Method Enhancement for Real-time Wind Turbine Fault RecognitionESPRIT Method Enhancement for Real-time Wind Turbine Fault Recognition
ESPRIT Method Enhancement for Real-time Wind Turbine Fault RecognitionIAES-IJPEDS
ย 

Similar to Accurate harmonic source identification using S-transform (20)

An Identification of Multiple Harmonic Sources in a Distribution System by Us...
An Identification of Multiple Harmonic Sources in a Distribution System by Us...An Identification of Multiple Harmonic Sources in a Distribution System by Us...
An Identification of Multiple Harmonic Sources in a Distribution System by Us...
ย 
Differential equation fault location algorithm with harmonic effects in power...
Differential equation fault location algorithm with harmonic effects in power...Differential equation fault location algorithm with harmonic effects in power...
Differential equation fault location algorithm with harmonic effects in power...
ย 
An Improved Detection and Classification Technique of Harmonic Signals in Pow...
An Improved Detection and Classification Technique of Harmonic Signals in Pow...An Improved Detection and Classification Technique of Harmonic Signals in Pow...
An Improved Detection and Classification Technique of Harmonic Signals in Pow...
ย 
A verification of periodogram technique for harmonic source diagnostic analyt...
A verification of periodogram technique for harmonic source diagnostic analyt...A verification of periodogram technique for harmonic source diagnostic analyt...
A verification of periodogram technique for harmonic source diagnostic analyt...
ย 
An Accurate Classification Method of Harmonic Signals in Power Distribution S...
An Accurate Classification Method of Harmonic Signals in Power Distribution S...An Accurate Classification Method of Harmonic Signals in Power Distribution S...
An Accurate Classification Method of Harmonic Signals in Power Distribution S...
ย 
A Utilisation of Improved Gabor Transform for Harmonic Signals Detection and ...
A Utilisation of Improved Gabor Transform for Harmonic Signals Detection and ...A Utilisation of Improved Gabor Transform for Harmonic Signals Detection and ...
A Utilisation of Improved Gabor Transform for Harmonic Signals Detection and ...
ย 
A Utilisation of Improved Gabor Transform for Harmonic Signals Detection and ...
A Utilisation of Improved Gabor Transform for Harmonic Signals Detection and ...A Utilisation of Improved Gabor Transform for Harmonic Signals Detection and ...
A Utilisation of Improved Gabor Transform for Harmonic Signals Detection and ...
ย 
An Analysis of Harmonic and Interharmonic Contribution of Electric Arc Furnac...
An Analysis of Harmonic and Interharmonic Contribution of Electric Arc Furnac...An Analysis of Harmonic and Interharmonic Contribution of Electric Arc Furnac...
An Analysis of Harmonic and Interharmonic Contribution of Electric Arc Furnac...
ย 
Diagnosis of broken bars fault in induction machines using higher order spect...
Diagnosis of broken bars fault in induction machines using higher order spect...Diagnosis of broken bars fault in induction machines using higher order spect...
Diagnosis of broken bars fault in induction machines using higher order spect...
ย 
A Fast Localization of Multiple Harmonic Sources for Rectifier Loads by Utili...
A Fast Localization of Multiple Harmonic Sources for Rectifier Loads by Utili...A Fast Localization of Multiple Harmonic Sources for Rectifier Loads by Utili...
A Fast Localization of Multiple Harmonic Sources for Rectifier Loads by Utili...
ย 
IRJET- Low Cost Harmonic Measurement using Arduino UNO
IRJET-  	  Low Cost Harmonic Measurement using Arduino UNOIRJET-  	  Low Cost Harmonic Measurement using Arduino UNO
IRJET- Low Cost Harmonic Measurement using Arduino UNO
ย 
Voltage variations identification using Gabor Transform and rule-based classi...
Voltage variations identification using Gabor Transform and rule-based classi...Voltage variations identification using Gabor Transform and rule-based classi...
Voltage variations identification using Gabor Transform and rule-based classi...
ย 
A simple faulted phase-based fault distance estimation algorithm for a loop d...
A simple faulted phase-based fault distance estimation algorithm for a loop d...A simple faulted phase-based fault distance estimation algorithm for a loop d...
A simple faulted phase-based fault distance estimation algorithm for a loop d...
ย 
A simple faulted phase-based fault distance estimation algorithm for a loop d...
A simple faulted phase-based fault distance estimation algorithm for a loop d...A simple faulted phase-based fault distance estimation algorithm for a loop d...
A simple faulted phase-based fault distance estimation algorithm for a loop d...
ย 
International Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentInternational Journal of Engineering Research and Development
International Journal of Engineering Research and Development
ย 
Ri 7
Ri 7Ri 7
Ri 7
ย 
Transient Monitoring Function based Fault Classifier for Relaying Applications
Transient Monitoring Function based Fault Classifier for Relaying Applications Transient Monitoring Function based Fault Classifier for Relaying Applications
Transient Monitoring Function based Fault Classifier for Relaying Applications
ย 
Analysis of harmonics and resonances in hvdc mmc link connected to AC grid
Analysis of harmonics and resonances in hvdc mmc link connected to AC gridAnalysis of harmonics and resonances in hvdc mmc link connected to AC grid
Analysis of harmonics and resonances in hvdc mmc link connected to AC grid
ย 
WAVELET- FUZZY BASED MULTI TERMINAL TRANSMISSION SYSTEM PROTECTION SCHEME IN ...
WAVELET- FUZZY BASED MULTI TERMINAL TRANSMISSION SYSTEM PROTECTION SCHEME IN ...WAVELET- FUZZY BASED MULTI TERMINAL TRANSMISSION SYSTEM PROTECTION SCHEME IN ...
WAVELET- FUZZY BASED MULTI TERMINAL TRANSMISSION SYSTEM PROTECTION SCHEME IN ...
ย 
ESPRIT Method Enhancement for Real-time Wind Turbine Fault Recognition
ESPRIT Method Enhancement for Real-time Wind Turbine Fault RecognitionESPRIT Method Enhancement for Real-time Wind Turbine Fault Recognition
ESPRIT Method Enhancement for Real-time Wind Turbine Fault Recognition
ย 

More from TELKOMNIKA JOURNAL

Amazon products reviews classification based on machine learning, deep learni...
Amazon products reviews classification based on machine learning, deep learni...Amazon products reviews classification based on machine learning, deep learni...
Amazon products reviews classification based on machine learning, deep learni...TELKOMNIKA JOURNAL
ย 
Design, simulation, and analysis of microstrip patch antenna for wireless app...
Design, simulation, and analysis of microstrip patch antenna for wireless app...Design, simulation, and analysis of microstrip patch antenna for wireless app...
Design, simulation, and analysis of microstrip patch antenna for wireless app...TELKOMNIKA JOURNAL
ย 
Design and simulation an optimal enhanced PI controller for congestion avoida...
Design and simulation an optimal enhanced PI controller for congestion avoida...Design and simulation an optimal enhanced PI controller for congestion avoida...
Design and simulation an optimal enhanced PI controller for congestion avoida...TELKOMNIKA JOURNAL
ย 
Improving the detection of intrusion in vehicular ad-hoc networks with modifi...
Improving the detection of intrusion in vehicular ad-hoc networks with modifi...Improving the detection of intrusion in vehicular ad-hoc networks with modifi...
Improving the detection of intrusion in vehicular ad-hoc networks with modifi...TELKOMNIKA JOURNAL
ย 
Conceptual model of internet banking adoption with perceived risk and trust f...
Conceptual model of internet banking adoption with perceived risk and trust f...Conceptual model of internet banking adoption with perceived risk and trust f...
Conceptual model of internet banking adoption with perceived risk and trust f...TELKOMNIKA JOURNAL
ย 
Efficient combined fuzzy logic and LMS algorithm for smart antenna
Efficient combined fuzzy logic and LMS algorithm for smart antennaEfficient combined fuzzy logic and LMS algorithm for smart antenna
Efficient combined fuzzy logic and LMS algorithm for smart antennaTELKOMNIKA JOURNAL
ย 
Design and implementation of a LoRa-based system for warning of forest fire
Design and implementation of a LoRa-based system for warning of forest fireDesign and implementation of a LoRa-based system for warning of forest fire
Design and implementation of a LoRa-based system for warning of forest fireTELKOMNIKA JOURNAL
ย 
Wavelet-based sensing technique in cognitive radio network
Wavelet-based sensing technique in cognitive radio networkWavelet-based sensing technique in cognitive radio network
Wavelet-based sensing technique in cognitive radio networkTELKOMNIKA JOURNAL
ย 
A novel compact dual-band bandstop filter with enhanced rejection bands
A novel compact dual-band bandstop filter with enhanced rejection bandsA novel compact dual-band bandstop filter with enhanced rejection bands
A novel compact dual-band bandstop filter with enhanced rejection bandsTELKOMNIKA JOURNAL
ย 
Deep learning approach to DDoS attack with imbalanced data at the application...
Deep learning approach to DDoS attack with imbalanced data at the application...Deep learning approach to DDoS attack with imbalanced data at the application...
Deep learning approach to DDoS attack with imbalanced data at the application...TELKOMNIKA JOURNAL
ย 
Brief note on match and miss-match uncertainties
Brief note on match and miss-match uncertaintiesBrief note on match and miss-match uncertainties
Brief note on match and miss-match uncertaintiesTELKOMNIKA JOURNAL
ย 
Implementation of FinFET technology based low power 4ร—4 Wallace tree multipli...
Implementation of FinFET technology based low power 4ร—4 Wallace tree multipli...Implementation of FinFET technology based low power 4ร—4 Wallace tree multipli...
Implementation of FinFET technology based low power 4ร—4 Wallace tree multipli...TELKOMNIKA JOURNAL
ย 
Evaluation of the weighted-overlap add model with massive MIMO in a 5G system
Evaluation of the weighted-overlap add model with massive MIMO in a 5G systemEvaluation of the weighted-overlap add model with massive MIMO in a 5G system
Evaluation of the weighted-overlap add model with massive MIMO in a 5G systemTELKOMNIKA JOURNAL
ย 
Reflector antenna design in different frequencies using frequency selective s...
Reflector antenna design in different frequencies using frequency selective s...Reflector antenna design in different frequencies using frequency selective s...
Reflector antenna design in different frequencies using frequency selective s...TELKOMNIKA JOURNAL
ย 
Reagentless iron detection in water based on unclad fiber optical sensor
Reagentless iron detection in water based on unclad fiber optical sensorReagentless iron detection in water based on unclad fiber optical sensor
Reagentless iron detection in water based on unclad fiber optical sensorTELKOMNIKA JOURNAL
ย 
Impact of CuS counter electrode calcination temperature on quantum dot sensit...
Impact of CuS counter electrode calcination temperature on quantum dot sensit...Impact of CuS counter electrode calcination temperature on quantum dot sensit...
Impact of CuS counter electrode calcination temperature on quantum dot sensit...TELKOMNIKA JOURNAL
ย 
A progressive learning for structural tolerance online sequential extreme lea...
A progressive learning for structural tolerance online sequential extreme lea...A progressive learning for structural tolerance online sequential extreme lea...
A progressive learning for structural tolerance online sequential extreme lea...TELKOMNIKA JOURNAL
ย 
Electroencephalography-based brain-computer interface using neural networks
Electroencephalography-based brain-computer interface using neural networksElectroencephalography-based brain-computer interface using neural networks
Electroencephalography-based brain-computer interface using neural networksTELKOMNIKA JOURNAL
ย 
Adaptive segmentation algorithm based on level set model in medical imaging
Adaptive segmentation algorithm based on level set model in medical imagingAdaptive segmentation algorithm based on level set model in medical imaging
Adaptive segmentation algorithm based on level set model in medical imagingTELKOMNIKA JOURNAL
ย 
Automatic channel selection using shuffled frog leaping algorithm for EEG bas...
Automatic channel selection using shuffled frog leaping algorithm for EEG bas...Automatic channel selection using shuffled frog leaping algorithm for EEG bas...
Automatic channel selection using shuffled frog leaping algorithm for EEG bas...TELKOMNIKA JOURNAL
ย 

More from TELKOMNIKA JOURNAL (20)

Amazon products reviews classification based on machine learning, deep learni...
Amazon products reviews classification based on machine learning, deep learni...Amazon products reviews classification based on machine learning, deep learni...
Amazon products reviews classification based on machine learning, deep learni...
ย 
Design, simulation, and analysis of microstrip patch antenna for wireless app...
Design, simulation, and analysis of microstrip patch antenna for wireless app...Design, simulation, and analysis of microstrip patch antenna for wireless app...
Design, simulation, and analysis of microstrip patch antenna for wireless app...
ย 
Design and simulation an optimal enhanced PI controller for congestion avoida...
Design and simulation an optimal enhanced PI controller for congestion avoida...Design and simulation an optimal enhanced PI controller for congestion avoida...
Design and simulation an optimal enhanced PI controller for congestion avoida...
ย 
Improving the detection of intrusion in vehicular ad-hoc networks with modifi...
Improving the detection of intrusion in vehicular ad-hoc networks with modifi...Improving the detection of intrusion in vehicular ad-hoc networks with modifi...
Improving the detection of intrusion in vehicular ad-hoc networks with modifi...
ย 
Conceptual model of internet banking adoption with perceived risk and trust f...
Conceptual model of internet banking adoption with perceived risk and trust f...Conceptual model of internet banking adoption with perceived risk and trust f...
Conceptual model of internet banking adoption with perceived risk and trust f...
ย 
Efficient combined fuzzy logic and LMS algorithm for smart antenna
Efficient combined fuzzy logic and LMS algorithm for smart antennaEfficient combined fuzzy logic and LMS algorithm for smart antenna
Efficient combined fuzzy logic and LMS algorithm for smart antenna
ย 
Design and implementation of a LoRa-based system for warning of forest fire
Design and implementation of a LoRa-based system for warning of forest fireDesign and implementation of a LoRa-based system for warning of forest fire
Design and implementation of a LoRa-based system for warning of forest fire
ย 
Wavelet-based sensing technique in cognitive radio network
Wavelet-based sensing technique in cognitive radio networkWavelet-based sensing technique in cognitive radio network
Wavelet-based sensing technique in cognitive radio network
ย 
A novel compact dual-band bandstop filter with enhanced rejection bands
A novel compact dual-band bandstop filter with enhanced rejection bandsA novel compact dual-band bandstop filter with enhanced rejection bands
A novel compact dual-band bandstop filter with enhanced rejection bands
ย 
Deep learning approach to DDoS attack with imbalanced data at the application...
Deep learning approach to DDoS attack with imbalanced data at the application...Deep learning approach to DDoS attack with imbalanced data at the application...
Deep learning approach to DDoS attack with imbalanced data at the application...
ย 
Brief note on match and miss-match uncertainties
Brief note on match and miss-match uncertaintiesBrief note on match and miss-match uncertainties
Brief note on match and miss-match uncertainties
ย 
Implementation of FinFET technology based low power 4ร—4 Wallace tree multipli...
Implementation of FinFET technology based low power 4ร—4 Wallace tree multipli...Implementation of FinFET technology based low power 4ร—4 Wallace tree multipli...
Implementation of FinFET technology based low power 4ร—4 Wallace tree multipli...
ย 
Evaluation of the weighted-overlap add model with massive MIMO in a 5G system
Evaluation of the weighted-overlap add model with massive MIMO in a 5G systemEvaluation of the weighted-overlap add model with massive MIMO in a 5G system
Evaluation of the weighted-overlap add model with massive MIMO in a 5G system
ย 
Reflector antenna design in different frequencies using frequency selective s...
Reflector antenna design in different frequencies using frequency selective s...Reflector antenna design in different frequencies using frequency selective s...
Reflector antenna design in different frequencies using frequency selective s...
ย 
Reagentless iron detection in water based on unclad fiber optical sensor
Reagentless iron detection in water based on unclad fiber optical sensorReagentless iron detection in water based on unclad fiber optical sensor
Reagentless iron detection in water based on unclad fiber optical sensor
ย 
Impact of CuS counter electrode calcination temperature on quantum dot sensit...
Impact of CuS counter electrode calcination temperature on quantum dot sensit...Impact of CuS counter electrode calcination temperature on quantum dot sensit...
Impact of CuS counter electrode calcination temperature on quantum dot sensit...
ย 
A progressive learning for structural tolerance online sequential extreme lea...
A progressive learning for structural tolerance online sequential extreme lea...A progressive learning for structural tolerance online sequential extreme lea...
A progressive learning for structural tolerance online sequential extreme lea...
ย 
Electroencephalography-based brain-computer interface using neural networks
Electroencephalography-based brain-computer interface using neural networksElectroencephalography-based brain-computer interface using neural networks
Electroencephalography-based brain-computer interface using neural networks
ย 
Adaptive segmentation algorithm based on level set model in medical imaging
Adaptive segmentation algorithm based on level set model in medical imagingAdaptive segmentation algorithm based on level set model in medical imaging
Adaptive segmentation algorithm based on level set model in medical imaging
ย 
Automatic channel selection using shuffled frog leaping algorithm for EEG bas...
Automatic channel selection using shuffled frog leaping algorithm for EEG bas...Automatic channel selection using shuffled frog leaping algorithm for EEG bas...
Automatic channel selection using shuffled frog leaping algorithm for EEG bas...
ย 

Recently uploaded

Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxupamatechverse
ย 
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur Escorts
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur EscortsRussian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur Escorts
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
ย 
Introduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxIntroduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxupamatechverse
ย 
Online banking management system project.pdf
Online banking management system project.pdfOnline banking management system project.pdf
Online banking management system project.pdfKamal Acharya
ย 
University management System project report..pdf
University management System project report..pdfUniversity management System project report..pdf
University management System project report..pdfKamal Acharya
ย 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Dr.Costas Sachpazis
ย 
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINEDJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINEslot gacor bisa pakai pulsa
ย 
MANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTING
MANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTINGMANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTING
MANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTINGSIVASHANKAR N
ย 
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Bookingdharasingh5698
ย 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...ranjana rawat
ย 
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfKamal Acharya
ย 
AKTU Computer Networks notes --- Unit 3.pdf
AKTU Computer Networks notes ---  Unit 3.pdfAKTU Computer Networks notes ---  Unit 3.pdf
AKTU Computer Networks notes --- Unit 3.pdfankushspencer015
ย 
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
ย 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...Call Girls in Nagpur High Profile
ย 
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
ย 
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptx
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptxBSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptx
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptxfenichawla
ย 
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
ย 
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINEMANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINESIVASHANKAR N
ย 
UNIT-III FMM. DIMENSIONAL ANALYSIS
UNIT-III FMM.        DIMENSIONAL ANALYSISUNIT-III FMM.        DIMENSIONAL ANALYSIS
UNIT-III FMM. DIMENSIONAL ANALYSISrknatarajan
ย 

Recently uploaded (20)

Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptx
ย 
Roadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and RoutesRoadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and Routes
ย 
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur Escorts
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur EscortsRussian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur Escorts
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur Escorts
ย 
Introduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxIntroduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptx
ย 
Online banking management system project.pdf
Online banking management system project.pdfOnline banking management system project.pdf
Online banking management system project.pdf
ย 
University management System project report..pdf
University management System project report..pdfUniversity management System project report..pdf
University management System project report..pdf
ย 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
ย 
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINEDJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
ย 
MANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTING
MANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTINGMANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTING
MANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTING
ย 
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
ย 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
ย 
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ย 
AKTU Computer Networks notes --- Unit 3.pdf
AKTU Computer Networks notes ---  Unit 3.pdfAKTU Computer Networks notes ---  Unit 3.pdf
AKTU Computer Networks notes --- Unit 3.pdf
ย 
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
ย 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
ย 
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
ย 
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptx
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptxBSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptx
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptx
ย 
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
ย 
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINEMANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
ย 
UNIT-III FMM. DIMENSIONAL ANALYSIS
UNIT-III FMM.        DIMENSIONAL ANALYSISUNIT-III FMM.        DIMENSIONAL ANALYSIS
UNIT-III FMM. DIMENSIONAL ANALYSIS
ย 

Accurate harmonic source identification using S-transform

  • 1. TELKOMNIKA Telecommunication, Computing, Electronics and Control Vol. 18, No. 5, October 2020, pp. 2708~2717 ISSN: 1693-6930, accredited First Grade by Kemenristekdikti, Decree No: 21/E/KPT/2018 DOI: 10.12928/TELKOMNIKA.v18i5.5632 ๏ฒ 2708 Journal homepage: http://journal.uad.ac.id/index.php/TELKOMNIKA Accurate harmonic source identification using S-transform Mohd Hatta Jopri1 , Abdul Rahim Abdullah2 , Rony Karim3 , Srete Nikolovski4 , Tole Sutikno5 , Mustafa Manap6 1,6 Faculty of Electrical and Electronic Engineering Technology, Universiti Teknikal Malaysia Melaka, Malaysia 2 Faculty of Electrical Engineering, Universiti Teknikal Malaysia Melaka, Malaysia 3 Infineon Technologies AG, Germany 4 Department of Power System, Faculty of Electrical Engineering, University of Osijek, Croatia 5 Deparment of Electrical Engineering, Universitas Ahmad Dahlan, Indonesia Article Info ABSTRACT Article history: Received Jan 15, 2020 Revised Apr 16, 2020 Accepted May 1, 2020 This paper introduces the accurate identification of harmonic sources in the power distribution system using time-frequency distribution (TFD) analysis, which is S-transform. The S-transform is a very applicable method to represent signals parameters in time-frequency representation (TFR) such as TFR impedance (ZTFR) and the main advantages of S-transform it can provide better frequency resolution for low frequency components and also offers better time resolution for high-frequency components. The identification of multiple harmonic sources are based on the significant relationship of spectral impedances (ZS) that extracted from the ZTFR, consist of the fundamental impedance (Z1) and harmonic impedance (Zh). To verify the accuracy of the proposed method, MATLAB simulations carried out several unique cases on IEEE 4-bus test feeder cases. It is proven that the proposed method is superior, with 100% correct identification of harmonic source location. It is proven that the method is accurate, fast and cost-efficient to localize harmonic sources in the power distribution system. Keywords: Harmonic source identification Power distribution system Spectral impedance S-transform Time-frequency distribution This is an open access article under the CC BY-SA license. Corresponding Author: Mohd Hatta Jopri, Faculty of Electrical and Electronic Engineering Technology, Universiti Teknikal Malaysia Melaka (UTeM), Hang Tuah Jaya St., 76100 Durian Tunggal, Melaka, Malaysia. Email: hatta@utem.edu.my 1. INTRODUCTION As the power quality (PQ) issues caused mainly by harmonics directly affect the overall continuation of electric transmission and distribution network, the uninterrupted monitoring of electric power systems (EPSs) has become highly necessary for the utility industry [1, 2]. The harmonic distortion causes several adverse effects such as overheating of rotational machines, static machines, and currentโ€carrying conductors. Furthermore, it causes premature breakdown or action of protecting appliances and harmonic resonance situations on the customers' EPS and metering imprecisions [2, 3]. In EPS, multiple harmonic sources can be found at the utility side, which known as upstream and downstream when harmonic sources located at the customer side with respect to a measurement point of point of common coupling (PCC) [4, 5]. Previously, numerous of harmonic source identification can be found in many kinds of literature. The earliest technique to localize the harmonic sources is utilizing power direction technique. However, this method used limited harmonic power-based indices, whereas mathematical analysis has shown the power direction method is not suitable for harmonic source detection [6, 7]. Furthermore, a state
  • 2. TELKOMNIKA Telecommun Comput El Control ๏ฒ Accurate harmonic source identification using S-transform (Mohd Hatta Jopri) 2709 estimation method is presented with the accomplishment of least square and Kirchhoff current law [8]. Yet, a study from [9], explained that the state estimation technique requires numerous measurement devices and unreasonable setup cost for the large power system. Thus, to overcome the previous constraint, the critical impedance method is introduced [10, 11]. The main disadvantage of this method is to know the value of source internal impedances of customer and utility, whereas it is difficult to obtain these parameters without switching tests [12, 13]. Consequently, a harmonic current vector method is introduced due to solving the previous method drawback. However, the measurement long-drawn-out and hard to analyze harmonic impedances at the customer side [14-16]. In the previous studies [17-20], the harmonic source estimation is discussed by applying the Bayesian estimation and harmonic state estimation (HSE). Unfortunately, this technique involves high computational complexity and the set-up cost of the distributed measurement system station is very expensive [5, 21, 22]. In real-time, accuracy, fast analysis and low cost are essential. Therefore, the limitation of previous analysis techniques can be solved by using signal processing techniques such as fast fourier transform (FFT), spectrogram and S-transform [2]. A harmonic source identification using FFT is introduced to provide fast analysis in determining the location of harmonic sources in the EPS. The significant relationship of spectral impedance, which are fundamental and harmonic impedance are used due to identify the harmonic location of the harmonic source [23, 24]. However, the drawback of the FFT technique, such as the signal information, for instance, amplitude frequencies and phases, cannot be acquired correctly. This is because of the leakage, aliasing effects, and picket fence formed by the FFT [25-27]. As a result of the FFT limitation, the spectrogram is presented to identify the harmonic source location [28]. Conversely, the spectrogram has two main disadvantages. First, its time-frequency resolution is limited by Heisenbergโ€™s Uncertainty Principle. Secondly, both its energy location in the time-frequency representation and its resolution can vary with the window selected [29-32]. The S-transform is the advancement of wavelet transform (WT) and short-time fourier transform (STFT) by its variable window and phase correction, respectively. Similar to WT, it offers an improved time and frequency representation of a signal. Additionally, the scalable and movable Gaussian window properties of the ST can be utilized for superior recognition of any power quality events [2, 33-35]. Due to the excellent features of the S-transform in power quality analysis, it is a necessity to perform an analysis of identifying the location of the harmonic sources using this technique. In this paper, the S-transform is proposed to identify the location of the harmonic source in the distribution system with a single-point measurement approach at the point of common coupling (PCC). S-transform is a technique that uses time-frequency analysis to distinguish the signals in time and frequency representation (TFR) [36, 37]. The S-transform is proposed because it is able to provide provides better frequency resolution for low-frequency components and also offers better time resolution for high- frequency components. 2. PROPOSED METHOD Harmonic current source type-load is selected as a frequent and widely use of harmonic producing loads in industrial [38, 39]. A time-frequency analysis which is used in this research is the S-transform. Three steps are proposed in this method. Firstly, measurement of voltage and current at the PCC. Secondly, these signals are analyzed using S-transform due to obtain the signal parameters in time-frequency representation (TFR) plane. Thirdly, the spectral impedance components are extracted from the TFR impedance and the significant relationship of these components are used in identifying the harmonic source location. 2.1. S-transform S-transform combines the element of wavelet transform (WT) and the short-time fourier transform (STFT), which inherits the advantage of WT and STFT in signal processing. In particular, ST employs a moving and scalable localizing Gaussian window in the transformation process. The Gaussian window is as shown in (2). Mathematically ST can be defined as [29], ๐‘†๐‘‡(๐œ, ๐‘“) = โˆซ ๐‘ฅ(๐‘ก) |๐‘“| โˆš2๐œ‹ ๐‘’ โˆ’(๐œโˆ’๐‘ก)2 ๐‘“2 2 ๐‘’โˆ’๐‘—2๐œ‹๐‘“๐‘ก ๐‘‘๐‘ก โˆž โˆ’โˆž (1) ๐‘”(๐‘ก) = 1 ๐œŽโˆš2๐œ‹ ๐‘’ โˆ’๐‘ก2 2๐œŽ2 (2) ๐œŽ(๐‘“) = 1 |๐‘“| (3) where ๐‘ฅ(๐‘ก) is the signal, ๐‘ก is the time, ๐‘“ is the frequency, ๐‘”(๐‘ก) is the scalable Gaussian window, and ๐œŽ(๐‘“) is a parameter that controls the position of the Gaussian window.
  • 3. ๏ฒ ISSN: 1693-6930 TELKOMNIKA Telecommun Comput El Control, Vol. 18, No. 5, October 2020: 2708 - 2717 2710 2.2. Signal parameters The parameters of power quality signals are extracted from the TFR to provide the information of the signal in time. 2.2.1. Instantaneous total non-harmonic distortion Total harmonic distortion, THD, is used to measure of how much harmonic content in a waveform [40]. The instantaneous total harmonic distortion of a waveform is defined mathematically as (4), ๐‘‡๐ป๐ท(๐‘ก) = โˆšโˆ‘ ๐‘‰โ„Ž,๐‘Ÿ๐‘š๐‘ (๐‘ก)2๐ป โ„Ž=2 ๐‘‰1๐‘Ÿ๐‘š๐‘ (๐‘ก) (4) where Vh,rms(t) is RMS harmonic voltage and Vh,rms(t) is RMS fundamental voltage. The instantaneous total harmonic distortion of a waveform is defined mathematically as. 2.2.2. Instantaneous total non-harmonic distortion Besides harmonic, a signal also contains interharmonic components that are not multiple integers of the power system frequency [27]. Referring to this as the instantaneous total nonharmonic distortion, (TnHD(t)), then for this parameter is written as (5). ๐‘‡๐‘›๐ป๐ท(๐‘ก) = โˆš๐‘‰๐‘Ÿ๐‘š๐‘ (๐‘ก)2โˆ’โˆ‘ ๐‘‰โ„Ž,๐‘Ÿ๐‘š๐‘ (๐‘ก)2๐ป โ„Ž=0 ๐‘‰1๐‘Ÿ๐‘š๐‘ (๐‘ก) (5) 2.3. Spectral impedance The spectral impedance (ZS) components are extracted from the TFR impedance (ZTFR). The ZTFR can be calculated using equation at each harmonic frequency and the values then plotted. The ZTFR is expressed as (6) [13]. ๐‘ ๐‘‡๐น๐‘… = ๐‘† ๐‘‰(๐‘ก,๐‘“) ๐‘† ๐ผ(๐‘ก,๐‘“) (6) where SV(t,f) is the TFR of voltage and SI(t,f) is the TFR of current. The spectral impedance consists of a fundamental impedance (Z1), whereas the harmonic impedance (Zh) is a harmonic impedance at the order number of harmonic. 2.4. Implementation of proposed method In most recent studies, suggest the execution of the proposed technique can be realized as depicts in Figure 1 (a) and Figure 1 (b) using IEEE 4-bus test feeders, while the harmonic source is modeled as an inverter-based load, which is known as harmonic current source type-load [41-43], where N is a linear load, which is a resistor whereas H is a harmonic source. Besides, four specific cases are considered in this research, such as [15 , 44, 45]: - Case 1: No harmonic source in the power network system - Case 2: Harmonic source at downstream of the PCC - Case 3: Harmonic sources at upstream and downstream of the PCC - Case 4: Harmonic source at upstream of the PCC (a) (b) Figure 1. (a) Upstream-downstream for case 1, (b) IEEE 4-bus test feeders for case 2, 3 and 4 3. RESULTS AND ANALYSIS In this section, it is explained the results of the research and at the same time is given the comprehensive discussion. Results can be presented in figures and tables.
  • 4. TELKOMNIKA Telecommun Comput El Control ๏ฒ Accurate harmonic source identification using S-transform (Mohd Hatta Jopri) 2711 3.1. Case 1: No harmonic source in the power network system The linear load, which is resistive loads, are located upstream and downstream of the PCC. As can be seen in Figures 2 (a) and (b) show the measured voltage and current signals in the time domain. The peak voltage is 326.5 V. In contrast, the peak current is 66.5 A, respectively. Besides, Figure 2 (c) shows the THD(t) and TnHD(t) of voltage and both parameters are zero percent. Meanwhile, Figure 2 (d) presents the THD(t) and TnHD(t) of current and both parameters are zero percent too. It shows that the voltage and current signal have neither harmonic nor interharmonic components. Figure 2 (e) shows the ZTFR of the PCC, while Figure 2 (f) presents the ZS. The most striking result from ZS, it is shown that the Z1 at 50 Hz is of 4.8 ohm and no harmonic impedances exist. Thus, for case 1, the significant relationship between Z1 and Zh at the condition of no harmonic source in the power system network, where for harmonic component, h is any positive integer whereas, for interharmonic, h is any positive non-integer. can be written as: ๐‘1 โ‰  0 ๐‘œโ„Ž๐‘š (7) ๐‘โ„Ž โ‰  0 ๐‘œโ„Ž๐‘š (8) (a) (b) (c) (d) (e) (f) Figure 2. Case 1; (a) voltage signal in time domain, (b) current signal in time domain, (c) THD(t) and TnHD(t) of voltage, (d) THD(t) and TnHD(t) of current, (e) TFR of impedance (ZTFR), (f) spectral impedance component 3.2. Case 2: Harmonic source at downstream of the PCC For case 2, the harmonic source is located downstream of the PCC. As can be seen in Figure 3 (a) and Figure 3 (b) show the measured voltage and current signals in the time domain. The peak voltage is 326.5 V. In contrast, the peak current is 66.5 A, respectively. In addition, Figure 3 (c) shows the THD(t) and TnHD(t) mean of voltage are 1.51% and 6.05%, respectively. In the meantime, Figure 3 (d) presents the THD(t) and TnHD(t) mean of current, which are 1.67% and 6.68%, respectively. The values of THD(t) and TnHD(t) show
  • 5. ๏ฒ ISSN: 1693-6930 TELKOMNIKA Telecommun Comput El Control, Vol. 18, No. 5, October 2020: 2708 - 2717 2712 that the voltage and current signals do have harmonic and interharmonic components. Figure 3 (e) shows the ZTFR of the PCC and the ZS is obtained by extracting the parameters from the ZTFR. Meanwhile, Figure 3 (f) presents the ZS that consists of the Z1. In contrast the harmonic impedance consists of Z275, Z375, Z600, Z700, Z825 and Z900, respectively. It is crucial to observe the relationship of ZS components due to identify the harmonic source location in the power system network. Interestingly, as shown in Table 1, the Z1 value at 50 Hz, is always higher than any Zh. Thus, for case 2, the significant relationship between Z1 and Zh at the condition of the harmonic source located at downstream of the PCC can be concluded and written as: ๐‘1 โ‰  0 ๐‘œโ„Ž๐‘š (9) ๐‘โ„Ž < ๐‘1 (10) where for harmonic component, h is any positive integer whereas, for interharmonic, h is any positive non-integer. (a) (b) (c) (d) (e) (f) Figure 3. Case 2; (a) voltage signal in time domain, (b) current signal in time domain, (c) THD(t) and TnHD(t) of voltage, (d) THD(t) and TnHD(t) of current, (e) TFR of impedance (ZTFR), (f) spectral impedance component 3.3. Case 3: Harmonic sources at upstream and downstream of the PCC For case 3, the harmonic source is located upstream and downstream of the PCC. As can be seen in Figures 4 (a) and (b) show the measured voltage and current signals in the time domain. The peak voltage is
  • 6. TELKOMNIKA Telecommun Comput El Control ๏ฒ Accurate harmonic source identification using S-transform (Mohd Hatta Jopri) 2713 324.7 V, while the peak current is 44.6 A, respectively. Besides, Figure 4 (c) shows the THD(t) and TnHD(t) mean of voltage are 1.47% and 6.04%, respectively. In the meantime, Figure 4 (d) presents the THD(t) and TnHD(t) mean of current, which are 1.91% and 45.18%, respectively. The values of THD(t) and TnHD(t) show that the voltage and current signals do have harmonic and interharmonic components. Figure 4 (e) shows the ZTFR of the PCC, while Figure 4 (f) presents the ZS that been extracted from the ZTFR. Furthermore, Figure 4 (f) shows that the Z1 is 5.36 ohm; in contrast the harmonic impedance consists of Z275, Z375, Z400, Z600, Z700 and Z900, respectively. The characteristic of the spectral impedance, ZS are summarized in Table 2. What is surprising is that the value of Z1 is always smaller than any harmonic impedances, Zh. It is apparent from the result that the ZS components can be characterized due to identify the location of the harmonic source. As a result, for case 3, the significant relationship between Z1 and Zh at the condition of the harmonic source located downstream of the PCC can be written as: ๐‘1 โ‰  0 ๐‘œโ„Ž๐‘š (11) ๐‘โ„Ž > ๐‘1 (12) where for harmonic component, h is any positive integer whereas, for interharmonic, h is any positive non-integer. (a) (b) (c) (d) (e) (f) Figure 4 Case 3; (a) voltage signal in time domain, (b) current signal in time domain, (c) THD(t) and TnHD(t) of voltage, (d) THD(t) and TnHD(t) of current, (e) TFR of impedance (ZTFR), (f) spectral impedance component
  • 7. ๏ฒ ISSN: 1693-6930 TELKOMNIKA Telecommun Comput El Control, Vol. 18, No. 5, October 2020: 2708 - 2717 2714 Table 1. Magnitudes of the spectral impedance for case 2 using S-transform technique Spectral Impedance Ohm Z1 5.36 Z275 3.81 Z375 3.68 Z600 4.19 Z700 4.34 Z825 3.94 Z900 3.68 Table 2. Magnitudes of the spectral impedance for case 3 using S-transform technique Spectral Impedance Ohm Z1 6.5 Z275 12.8 Z375 11.8 Z400 12.3 Z600 12.2 Z700 12.5 Z900 12.9 3.4. Case 4: Harmonic source at upstream of the PCC In case 4, the harmonic source is located upstream of the PCC. The voltage and current signals in the time domain are measured at the PCC are shown in Figures 5 (a) and (b). The peak voltage is 324.3 V, whereas the peak current is 30.65 A and the fundamental frequency is 50 Hz. These signals are used as the inputs for analyzing harmonic sources using the S-transform technique. It can be seen from the waveforms that the voltage and current waveforms are distorted because of the harmonic source presents in the network system. Furthermore, Figure 5 (c) shows the THD(t) and TnHD(t) mean of voltage, which are 1.47% and 6.04%, respectively. Moreover, Figure 5 (d) shows the THD(t) and TnHD(t) mean of current are 1.5% and 6.05%, respectively. The values of THD(t) and TnHD(t) show that the voltage and current signals do have harmonic and interharmonic components. The ZS components are extracted from the ZTFR shown in Figure 5 (e). As shown in Figure 5 (f), the spectral impedance, ZS, consists of fundamental impedance, Z1 at 50 Hz, whereas the harmonic impedances such as Z275, Z300, Z375, Z400, Z600, Z700, Z900, respectively. (a) (b) (c) (d) (e) (f) Figure 5. Case 4, (a) Voltage signal in time domain, (b) Current signal in time domain, (c) THD(t) and TnHD(t) of voltage, (d) THD(t) and TnHD(t) of current, (e) TFR of impedance (ZTFR), (f) Spectral impedance component
  • 8. TELKOMNIKA Telecommun Comput El Control ๏ฒ Accurate harmonic source identification using S-transform (Mohd Hatta Jopri) 2715 The ZS components relationship are the critical driving factor of harmonic source identification and the values of the components are summarized in Table 3. It can be seen that the Z1 is always the same value as all harmonic impedances, Zh. Based on the results, it can be concluded that the ZS components can be used to identify the location of harmonic sources. Hence, for case 4, the significant relationship between Z1 and Zh at the condition of the harmonic source located at downstream of the PCC can be written as: ๐‘1 โ‰  0 ๐‘œโ„Ž๐‘š (13) ๐‘โ„Ž = ๐‘1 (14) where for harmonic component, h is any positive integer whereas, for interharmonic, h is any positive non-integer. Table 3. Magnitudes of the spectral impedance for case 4 using S-transform technique Spectral Impedance Ohm Z1 10.6 Z275 10.6 Z300 10.6 Z375 10.6 Z400 10.6 Z600 10.6 Z700 10.6 Z900 10.6 3.5. Performance of the proposed method This research provides an exciting opportunity to advance the understanding of harmonic source identification using the S-transform technique. The main contribution of this analysis is the significant relationship of the spectral impedance components, ZS such as fundamental impedance, Z1 and harmonic impedance, Zh in identifying the location of the harmonic source in the network system. The spectral impedance characteristics are used to identify the location of harmonic sources and the performance of this proposed method are summarizes in Table 4. Table 4. Performance of harmonic source identification using spectral impedance components characteristics Case Upstream side Downstream side Spectral impedance, ZS characteristic % Correct identification 1 N N Z1 โ‰  0 ohm Zh = 0 ohm 100 2 N H Z1โ‰  0 ohm Z1 > Zh 100 3 H H Z1 โ‰  0 ohm Zh > Z1 100 4 N H Z1 โ‰  0 ohm Zh = Z1 100 4. CONCLUSION The main concern of this research is to identify the location of harmonic source that connected to the distribution system utilizing the S-transform technique. The main contribution of this research is the significant relationship of ZS components that obtained from the S-transform analysis in identifying the location of harmonic sources. Based on Table 4, the correctness of the proposed method is 100% for each case and the significant relationship of ZS for identification of harmonic source location are summarized as follow: - If Z1 โ‰  0 and Zh = 0, there is no source in the network system. - If Z1โ‰  0 and Z1 > Zh, there is a harmonic source located at downstream of the PCC. - If Z1โ‰  0 and Zh > Z1, there are a harmonic sources located at upstream and downstream of the PCC. - If Z1 โ‰  0 and Z1 = Zh, there is a harmonic source located at upstream of the PCC. Consequently, considering the results, this method can be used accurately in distinguishing the location of the harmonic source.
  • 9. ๏ฒ ISSN: 1693-6930 TELKOMNIKA Telecommun Comput El Control, Vol. 18, No. 5, October 2020: 2708 - 2717 2716 ACKNOWLEDGEMENTS This research is supported by the Advanced Digital Signal Processing Laboratory (ADSP Lab). Special thanks also to the Faculty of Electrical and Electronic Engineering Technology of Universiti Teknikal Malaysia Melaka (UTeM), Center for Robotics and Industrial Automation (CeRIA) of UTeM and Ministry of Higher Education Malaysia (MOHE). Their support is gratefully acknowledged. REFERENCES [1] D. D. Ferreira et al., โ€œMethod based on independent component analysis for harmonic extraction from power system signals,โ€ Electr. Power Syst. Res., vol. 119, pp. 19-24, February 2015. [2] M. Mishra, โ€œPower quality disturbance detection and classification using signal processing and soft computing techniques: A comprehensive review,โ€ International Transactions on Electrical Energy Systems, vol. 29, no. 2, March 2019. [3] M. Farhoodnea, et al., โ€œAn improved method for determining contribution of utility and customer harmonic distortions in a power distribution system,โ€ Int. J. Electr. Eng. Informatics, vol. 2, no. 3, pp. 204-215, 2010. [4] M. Farhoodnea, A. Mohamed, and H. Shareef, โ€œA single point measurement method for evaluating harmonic contributions of utility and customer in power distribution systems,โ€ Journal of Applied Sciences, vol. 11, no. 2. pp. 257-265, February 2011. [5] A. R. Abdullah, et al., โ€œLocalization of multiple harmonic sources for inverter loads utilizing periodogram,โ€ J. Teknol., vol. 8, no. 2, pp. 87-91, January 2016. [6] W. Xu, โ€œPower direction method cannot be used for harmonic source detection,โ€ 2000 Power Engineering Society Summer Meeting (Cat. No.00CH37134), vol. 2, pp. 873-876, July 2000. [7] F. Xu, et al., โ€œStudy on constraints for harmonic source determination using active power direction,โ€ IEEE Trans. Power Deliv., vol. 33, no. 6, pp. 2683-2692, Dec. 2018. [8] Y. Liu, et al., โ€œHarmonic source location at the point of common coupling based on the nonlinearity index of load,โ€ 2009 Asia-Pacific Power and Energy Engineering Conference, 2009, pp. 1-5, March 2009. [9] A. R. Abdullah, G. Z. Peng and S. A. Ghani, โ€œA new vector draft method for harmonic source detection at point of common coupling,โ€ Proc. 2014 IEEE 8th Int. Power Eng. Optim. Conf. PEOCO 2014, pp. 110-114, March 2014. [10] F. Safargholi, K. Malekian, and W. Schufft, โ€œOn the dominant harmonic source identification-Part II: Application and interpretation of methods,โ€ IEEE Transaction on Power Delivery, vol. 33, no. 3, pp. 1278-1287, Jun. 2018. [11] F. Safargholi, K. Malekian, and W. Schufft, โ€œOn the dominant harmonic source identification - Part I: Review of Methods,โ€ IEEE Trans. Power Deliv., vol. 33, no. 3, pp. 1268-1277, Jun. 2018. [12] A. R. Abdullah, et al., โ€œLocalization of multiple harmonic sources for inverter loads utilizing periodogram,โ€ J. Telecommun. Electron. Comput. Eng., vol. 8, no. 2, 2016. [13] A. Abdullah, M. Manap, et al., โ€œAn improved spectrogram to identify multiple harmonic sources in distribution system with inverter loads,โ€ Proceedings of the International MultiConference of Engineers and Computer Scientists., vol. II, pp. 0-5, March 2017. [14] N. Hamzah, et al., โ€œIdentification of harmonic source at the point of common coupling based on voltage indices,โ€ J. Teknol., vol. 43, no. 1, pp. 11-32, Dec. 2005. [15] A. Abdullah, and M. Manap, โ€œAn improved spectrogram to identify multiple harmonic sources in distribution system with inverter loads,โ€ Proceedings of the International MultiConference of Engineers and Computer Scientists., vol. 7, no. 4, pp. 11591, 2017. [16] A. Banshwar and A. K. Chandel, โ€œIdentification of harmonic sources using fuzzy logic,โ€ 2010 Jt. Int. Conf. Power Electron. Drives Energy Syst. 2010 Power India, pp. 1โ€“7, December 2010. [17] C. Jaipradidtham, โ€œA control of real voltage and harmonic analysis with adaptive static var of electric arc furnace for power quality improvement by Grey Markov method,โ€ 2016 IEEE 6th Int. Conf. Power Syst. ICPS 2016, no. 1, March 2016. [18] T. Zang, et al., โ€œHarmonic source localization approach based on fast kernel entropy optimization ICA and minimum conditional entropy,โ€ Entropy, vol. 18, no. 6, pp. 214, June 2016. [19] T. Pfajfar, B. Blaลพiฤ, and I. Papiฤ, โ€œHarmonic contributions evaluation with the harmonic current vector method,โ€ IEEE Transactions on Power Delivery, vol. 23, no. 1, pp. 425-433, January 2008. [20] A. R. Abdullah, et al., โ€œAn identification of multiple harmonic sources in a distribution system by using spectrogram,โ€ Bulletin of Electrical. Engineering and Informatics, vol. 7, no. 2, pp. 244-256, June 2018. [21] P. Supriya and T. N. Padmanabhan Nambiar, โ€œReview of harmonic source identification techniques,โ€ International. Review. Electrical. Engineering., vol. 7, no. 3, pp. 4525-4531, June 2012. [22] G. Dโ€™Antona, et al., โ€œHarmonic source estimation in distribution systems,โ€ Appl. Meas. Power Syst. (AMPS), 2010 IEEE Int. Work., vol. 60, no. 10, pp. 1-5, September 2010. [23] A. R. Abdullah, et al., โ€œA fast localization of multiple harmonic sources for rectifier loads by utilizing periodogram,โ€ Telkomnika (Telecommunication Computer. Electronics. and Control., vol. 15, no. 1, March 2017. [24] A. Rahim Abdullah, et al., โ€œPerformance evaluation of real power quality disturbances analysis using S-transform,โ€ Appl. Mech. Mater., vol. 752โ€“753, pp. 1343-1348, April 2015. [25] A. R. Abdullah, et al., โ€œShort-circuit switches fault analysis of voltage source inverter using spectrogram,โ€ Electr. Mach. Syst. (ICEMS), 2013 Int. Conf., pp. 1808-1813, October 2013.
  • 10. TELKOMNIKA Telecommun Comput El Control ๏ฒ Accurate harmonic source identification using S-transform (Mohd Hatta Jopri) 2717 [26] N. A. Abidullah, et al., โ€œReal-time power quality signals monitoring system,โ€ Proceeding - 2013 IEEE Student Conference on Research and Development, SCOReD 2013, January 2015. [27] A. Abdullah, et al., โ€œA utilisation of improved gabor transform for harmonic signals detection and classification analysis,โ€ International. Journal of Electrical and Computer Engineering, vol. 7, no. 1, pp. 21-28, February 2017. [28] A. R. Abdullah, et al., โ€œAn improved of multiple harmonic sources identification in distribution system with inverter loads by using spectrogram,โ€ Bull. Electr. Eng. Informatics, vol. 7, no. 2, pp. 244-256, December 2018. [29] A. R. Abdullah, et al., โ€œAn accurate classification method of harmonic signals in power distribution system by utilising S-transform,โ€ TELKOMNIKA Telecommunication, Computing, Electronics and Control, vol. 15, no. 1, pp. 12-20, March 2017. [30] A. R. Abdullah, et al., โ€œPower quality signals classification system using time-frequency distribution,โ€ Appl. Mech. Mater., vol. 494-495, pp. 1889-1894, 2014. [31] A. R. Abdullah, et al., โ€œPerformance verification of power quality signals classification system,โ€ Applied. Mechanics and. Materials., vol. 753, pp. 1158-1163, April 2015. [32] A. R. Abdullah, et al., โ€œAn improved detection and classification technique of harmonic signals in power distribution by utilizing spectrogram,โ€ International Journal Electrical and Computer Engineering, vol. 7, no. 1, pp. 12-20, 2017. [33] A. G. Miamee, โ€œNonstationary stochastic processes and their applications,โ€ Workshop on Nonstationary Stochastic Processes and Their Application, pp. 1-298, August 1991. [34] N. H. T. Ahmad, A. R. Abdullah and N. A. Abidullah, โ€œAnalysis of power quality disturbances using spectrogram and S-transform,โ€ International Review of Electrical Engineering, vol. 9, no. 3, pp. 611-619, June 2014. [35] A. R. Abdullah, et al., โ€œA critical review of time-frequency distribution analysis for detection and classification of harmonic signal in power distribution system,โ€ International Journal Electrical and. Computer Engineering, vol. 8, no. 6, pp. 4603-4618, December 2018. [36] N. A. Abidullah, et al., โ€œReal-time power quality signals monitoring system,โ€ Proceeding - 2013 IEEE Student Conf. Res. Dev. SCOReD 2013, pp. 433-438, December 2013. [37] N. H. T. Huda, A. R. Abdullah, et al., โ€œPower quality signals detection using S-transform,โ€ Proc. 2013 IEEE 7th Int. Power Eng. Optim. Conf. PEOCO 2013, pp. 552-557, June 2013. [38] C.-I. Chen and Y. Chen, โ€œA neural-network-based data-driven nonlinear model on time- and frequency-domain voltage-current characterization for power-quality study,โ€ IEEE Transaction on Power Delivery, vol. 30, no. 3, pp. 1577-1584, Jun. 2015. [39] J. Wu, et al., โ€œIdentification of multiple harmonic sources in cyber-physical energy system using supervised independent component analysis,โ€ 2014 IEEE International Instrumentation and Measurement Technology Conference , pp. 496-501, 2014. [40] M. Manap, et al., โ€œComparison of open and short-circuit switches faults voltage source inverter (VSI) analysis using time-frequency distributions,โ€ Applied Mechanics and Materials., vol. 752โ€“753, pp. 1164-1169, April 2015. [41] M. L. Baughman and R. C. Dugan, โ€œIEEE 4 Node Test Feeder,โ€ Inst. Electr. Electron. Eng. Inc, pp. 1-9, 2009. [42] A. K. Bharati and V. Ajjarapu, โ€œInvestigation of relevant distribution system representation with DG for voltage stability margin assessment,โ€ IEEE Transaction on Power System, vol, 99, pp. 1-1, Oct. 2019. [43] M. J. E. Alam, K. M. Muttaqi, and D. Sutanto, โ€œA three-phase power flow approach for integrated 3-wire MV and 4-wire multigrounded LV networks with rooftop solar PV,โ€ IEEE Trans. Power Syst., vol. 28, no. 2, pp. 1728-1737, 2013. [44] M. Narimani, S. H. Hosseinian, and B. Vahidi, โ€œA method for harmonic power tracing by using upstream and downstream distribution matrices,โ€ Electr. Power Components Syst., vol. 47, no. 13, pp. 1169-1179, Aug. 2019. [45] P. Sinha, S. K. Goswami, and S. Debnath, โ€œHarmonic source identification in distribution system using non-active power quantities,โ€ Int. J. Power Energy Convers., vol. 8, no. 1, pp. 90-111, January 2017.