H. Saad, Y. Fillion
Abstract - High-frequency responses of HVDC-MMC links are
essential to study because harmonic and resonance phenomena
may impact the AC grid. In this paper, EMT-type simulations are
used to analyze converter station’s frequency response. Several
MMC station and AC network parameters are varied to analyze
their impact. In addition, an EMT-type test case, based on a
recent installed HVDC project, is used to illustrate potential
resonances that can occur between converter stations and AC
networks.
Keywords: EMTP, Harmonic, Resonance, Impedance Analysis,
HVDC, Modular multilevel converter (MMC), Voltage source
converter (VSC)
I. INTRODUCTION
igh Voltage Direct Current (HVDC) systems based on
the Modular Multilevel Converter (MMC) [1] is the
predominant topology used in recent and upcoming HVDC-
VSC projects. For instance, several HVDC-MMC projects are
currently planned or operated by RTE (French TSO), such as
the INELFE, FIL, IFA2, etc.
Harmonic emissions and resonances in a system may reduce
the use of power and damage the insulation of the system
components if they are not limited properly. Furthermore, a
system malfunction may occur if the system has high voltage
or current harmonic amplitudes. The harmonics which
propagate in the AC network and to power electronic
components can cause overheating of equipment and
interferences with communication circuits.
Power electronic converters can cause instabilities and/or
resonances when interacting with other equipment in a power
system. These phenomena can occur in a wide range of
frequencies (up to few kHz). Low and high frequency
resonances have been registered in several power electronics
based projects: in offshore HVDC link high frequency
resonances [2] were noted. Instability with converters of a
photovoltaic plant [3] and in traction applications [4] are
reported. In [5] low frequency oscillations are studied between
power electronic and power system devices. Power electronic
converters inject harmonics in the grid mainly due to
modulation and switching commutations. For a MMC station,
the injected harmonics depend mainly on the number of
H. Saad and Y. Fillion are with Réseau de Transport d'Electricité (RTE),
Paris, France (e-mail: hani.saad@rte-france.com).
Paper submitted to the International Conference on Power Systems
Transients (IPST2017) in Seoul, Republic of Korea June 26-29, 2017
submodules (SMs) per arm and their modulation strategies,
which is specific to the manufacturer and/or project.
In HVDC projects, vendors and utilities perform harmonic
and resonance studies. These studies are conducted in
frequency domain and/or using electromagnetic transient
(EMT) tools. Frequency domain studies are used to assess
system stability [6] and are convenient for simulating a wide
range of configurations and scenarios. To derive the frequency
response of a converter, analytical or small signal approaches
are commonly used. In [7]-[11] an analytical development of a
VSC station is presented. However, during real HVDC and
FACTS projects, the EMT-type model provided by the
manufacturer is often hidden (or black-boxed) due to
intellectual property issue. Therefore, the analytical model
derivation is not possible or not sufficiently accurate. In
addition, model linearization and derivation are challenging
and complex tasks since the MMC includes several variables
and complex control structures. In this paper, the derivation of
the frequency response of a converter station based on a black-
box EMT model, presented in [18], is used. Since this EMT
model includes the detailed representation of the converter
station with its control system, this approach is more practical
than with an analytical model.
This paper is an extended version of [18]. Several test cases
are performed to analyze the impact of MMC station
parameters (as MMC levels, control system, AC filter, etc.) on
the high-frequency response (i.e. harmonics and impedance).
In addition, the generic EMT test case where high frequency
resonances can occur between the AC network and the
converter station presented in [18] is analyzed in this paper.
Parametric sensitivity studies of the AC network is conducted
in order to assess the impact on system stability.
The paper is structured as follows. Section II recalls
harmonics and resonance phenomena. Section III presents the
generic MMC-401-Level station and its control structure.
Section IV illustrates the derivation of the frequency response
based on the EMT-type model. Section V simulation results of
the impact of converter station and ac network parameters are
presented.
II. MMC STATION OVERVIEW
The generic EMT model includes the detailed
representation of the converter station with its control system,
see Figure 1 [5]. The equivalent detailed MMC model where
each SM is represented, (i.e. Model #2 as defined in [13]) is
considered. The control system uses an upper level control
including inner/outer controllers and a lower level control to
Analysis of Harmonics and Resonances in
HVDC-MMC Link Connected to AC grid
H
regulate MMC internal variables: capacitor balancing
algorithm (CBA) to balance SM capacitor voltages in each
arm, modulation to convert the reference voltage to a number
of inserted SMs and circulating current control (CCC) to
regulate converter internal energy. More details can be found
in [17].
+
-
1 2
gate signal
measurements
ref
conv j
v
Lowerlevelcontrol
Outer Control
Inner Control
Upperlevelcontrol
StartPoint
Reactor
CBA and
Modulation
CCC
400 / 320kV
0.12trfL pu=
0.001trfR pu=
0.075armL pu=
PCC j
v
ji
Measurements
filter
640dcV kV=
40 /C kJ MVA=
400N SM=
Figure 1: Generic control structure of MMC station
III. HARMONICS AND RESONANCES
We can distinguish two different high frequency phenomena
that can take place between power electronics and surrounding
AC networks; harmonic emissions and resonances:
• Harmonics emissions are mainly associated with
semiconductor switches and therefore continuously
transmitted by the system which may affect the wave
quality.
• The resonances are mainly related to the control system,
filters, delays, etc. Resonances have usually higher order of
magnitude than harmonics but their time intervals are
shorter since system protection is used to trip network
devices.
Figure 2 illustrates these two different aspects. The voltage
source ( convh
v ) or current source ( convh
i ) represents the
harmonic emissions and the impedance Z(f) (where f stands for
frequency) depends on control loops and physical equipment
which includes system resonances [14]. Since a converter
station with its control system, is a nonlinear system,
equivalent circuit values depend on the set-point operation of
the system and will vary when the converter configuration
changes.
( )Z s convh
v
1convv convv
++
( )Z s
1conviconvh
i
a) Equivalent Thevenin circuit b) Equivalent Norton circuit
Figure 2: Equivalent circuit for frequency response
Determination of Z(f) and convh
i (or convh
v ) is achieved in
two ways: by means of an analytical approach or by EMT
simulations. The analytical approach offers the capability to
use classical modal analysis tools in order to study the
converter behavior [6]. However, analytical models may
become complex depending on the studied system and must be
validated as several approximations are introduced. On the
other hand, the EMT simulations include the detailed models
of the control system and power equipment. The obtained
results are more realistic than with an analytical model,
however simulation time constitutes the main drawback.
This article uses the EMT simulation approach to derive
Norton equivalent values at each harmonic rank h.
IV. FREQUENCY RESPONSE BASED ON EMT SIMULATION
The derivation of the equivalent Norton circuit (Figure 2)
based on time domain EMT simulation is briefly described in
this section. The circuit setup is shown in Figure 3 and the
flow chart computation for each h is depicted in Figure 4. The
converter station is connected to an equivalent AC grid and a
controlled ideal current source injh
i at the PCC. The injected
current injh
i are varied during time domain simulations in
order to compute Z(f) and convh
i (Figure 2.b) [18]. The
amplitude of injh
i should be a fraction of the nominal current of
the system to guarantee a small-signal perturbation and to
avoid any excitation of the control and protection system. The
important feature of this method is that the control system is in
normal operation, therefore, a realistic set point can be
considered [14]. Norton equivalent values change according to
the set point operations.
injh
i
PCCh
v
gridh
i
Equivalent
AC grid
hi
HVDC-MMC link
+
Figure 3: Model setup to derive the equivalent Norton
circuit
Time
domain
+ iinjh
Measure
vPCCh & ih
Compute
iconvh & Zh
Frequency
domain
studies
Figure 4: Block diagram, Norton equivalent computation
The derivation of the Norton equivalent circuit is also
useful for frequency domain studies in power grid systems,
since the computation time is much faster than with the
detailed EMT-model.
It should be highlighted that this approach can be also used
in real-time simulators with hardware-in-the-loop simulation
including the real-physical control system (or replicas). Such
approach can provides faster simulation time and more
realistic results since the real and complete control system is
used.
V. FREQUENCY RESPONSE STUDIES
In this section, the impact of the converter station
parameters on the frequency response is analysed. The test
case used is a point-to-point HVDC-MMC 401-Level link with
a transmission capacity of 1,000 MW. The AC grid is modeled
as an equivalent source with a short-circuit level (SCL) of
20 GVA. Converter station data can be found in Figure 1 and
control data is provided in the Appendix. All model
developments and simulations are performed using the EMTP-
RV software.
A. Harmonic studies
In this sub-section, converter station parameters that impact
the harmonic emissions are considered.
1) Impact of MMC levels
Harmonics emitted from the MMC station are known to be
low in amplitude. In order to show the impact of MMC levels,
the MMC-401-Level is compared with a MMC-11-Level, in
this section. Voltage references, harmonic distorsions (i.e.
convh
i ) and Z(f) are compared in Figure 5. Obviously,
harmonic emissions produced from 11-Level MMC are higher
than those produced by a 401-Level MMC which are
negligible. For such MMC 11-Level, it is expected that an AC
filter will be installed at the converter station in order to limit
those harmonics. Based on Z(f) responses in Figure 5, one can
notice that the impedance is not affected by the MMC levels.
This was expected since control loops are identical (except the
CBA and modulation) between thoses two MMC levels.
0.91 0.915 0.92 0.925 0.93 0.935
0
0.2
0.4
0.6
0.8
1
vPCCa
(pu)
Time (s)
MMC 11L
MMC 401L
100 400 700 1000 1300 1600 1900 2200 2500 2800
0
5
10
15
iconv
(A)
Frequency (Hz)
MMC 11L
MMC 401L
100 400 700 1000 1300 1600 1900 2200 2500 2800
0
500
1000
1500
2000
|Z|(ohm)
Frequency (Hz)
MMC 11L
MMC 401L
Figure 5: Impact of MMC levels
2) CBA impact
In this section, the impact of the CBA over the frequency
response is investigated. The capacitor value and the threshold
activation [15] of the CBA are varied to get the extreme cases:
- CBA #1: threshold is set at 1% and C= 45 kJ/MVA
- CBA #2: threshold is set at 50% and C =25 kJ/MVA
Similar test case as in [18] has been used, however, a MMC
including 401-Level is simulated instead of MMC-11-Level.
Figure 6 shows some of the 400 SMs capacitor voltages of
phase A upper arm, using CBA #1 and CBA #2. It can be
observed that CBA #2 has higher amplitude fluctuation and
higher differences between capacitor voltages.
Figure 7 shows the impact of capacitor fluctuations and
CBA configurations over the frequency response, i.e. Z(f) and
convh
i . It can be observed that these parameters have mainly an
impact on the harmonic injection convh
i rather than on Z(f).
Note that with CBA #2, high harmonic emissions are noticed
at lower frequency (around 250 Hz and 350 Hz). This shows
that CBA and capacitor voltage fluctuations have an impact on
the harmonic emissions. This results shows also the
importance of a detailed EMT model (even for MMC-401
Level) to account for such harmonics.
0.6 0.61 0.62 0.63 0.64 0.65 0.66
0.8
0.9
1
1.1
1.2
vCi(pu)
Time (sec)
a) CBA#1 and C=45 kJ/MVA
0.6 0.61 0.62 0.63 0.64 0.65 0.66
0.8
0.9
1
1.1
1.2
vCi(pu)
Time (sec)
b) CBA#2 and C=25 kJ/MVA
Figure 6: CBA impact, Capacitor voltages of SMs
100 300 500 700 900 1100 1300 1500 1700 1900 2100
0
2
4
6
8
iconv
(A)
Frequency (Hz)
CBA #2
CBA #1
100 400 700 1000 1300 1600 1900 2200 2500 2800
0
500
1000
1500
2000
|Z|(ohm)
Frequency (Hz)
CBA#1
CBA#2
Figure 7: CBA impact, frequency response ( convh
i and Z )
3) CCC impact
To analyze the circulating current control impact, the
reference value of the second harmonic circulating current
control is varied between 0 and 0.1 pu, for CCC #1 and CCC
#2 respectively. Similar test case as in [18] has been used,
however, a MMC including 401-Level is simulated in this
paper, instead of MMC 11-Level. Figure 8 shows the
circulating current variation impact. Figure 9 shows the results
of convh
i and Z(f). Since the frequency response of both CCC
configurations are close, it can be concluded that the
circulating current has a minor impact on the frequency
response from the AC side (as highlighted in [16]).
0.6 0.61 0.62 0.63 0.64 0.65 0.66
-0.5
-0.4
-0.3
-0.2
-0.1
Current(pu)
Time (sec)
CCC #2 CCC #1
Figure 8: CCC impact, circulating current phase A
100 300 500 700 900 1100 1300 1500 1700 1900 2100
0
2
4
6
8
iconv
(A)
Frequency (Hz)
CCC #2
CCC #1
100 400 700 1000 1300 1600 1900 2200 2500 2800
0
500
1000
1500
2000
|Z|(ohm)
Frequency (Hz)
CCC#1
CCC#2
Figure 9: CCC impact, frequency response ( convh
i and Z )
B. Impedance studies
In this section, the impact of control system parameters on
Z(f) is studied.
1) Inner control loop and time delay
Inner control loop dynamic and time delay have an impact
on Z(f). Results and analysis are provided in [18]: The impact
of the inner control is increased when the dynamic response of
the control loop is fast.
2) Impact of AC filter at PCC
Depending on Manufacturers and project specifications, AC
filter equipment can be installed at PCC. To show the impact
of this device over the frequency response, in this section a
low-pass filter is added at PCC to the MMC station model.
Parameters of the low-pass filter are based on [19]. Note, that
in practice, this low-pass filter will be tuned according to
project specification, however, the scope of this section is only
to illustrate the impact of such equipment. Result comparisons
between converter station with and without the installation of
the AC filter is depicted in Figure 10. It can be noticed that the
Z(f) is mainly affected by the AC filter installation for
frequencies above 400 Hz.
100 400 700 1000 1300 1600 1900 2200 2500 2800
0
500
1000
1500
2000
|Z|(ohm)
Frequency (Hz)
with AC filter
without AC filter
100 400 700 1000 1300 1600 1900 2200 2500 2800
-100
-50
0
50
100
∠Z(deg)
Frequency (Hz)
without AC filter
with AC filter
Figure 10: Impact of AC filter at PCC
VI. STABILITY ANALYSIS
In [12] and [18], it has been shown that low-pass filters and
delays in converter station control can lead to negative
resistance in high frequency range. Therefore, this negative
resistance can lead to resonances or instability depending on
the AC network configuration and parameters.
To analyze the stability of a system, the considered circuit
can be represented as a feedback loop system in the small-
signal domain. Therefore, the following Laplace equation can
be deduced [3]:
( )
( ) ( )
1 ( ) / ( )
grid
PCC conv
grid
Z s
i s v s
Z s Z s
=
+
(1)
where ( )gridZ s is the equivalent impedance of the AC grid.
From equ. (1), the system is stable if the expression
( ) / ( )gridZ s Z s is lower than one at each frequency. However,
if the Nyquist criterion is not met, and in addition, the angle
( ) / ( )gridZ s Z s∠ is higher than ±1800
, then the system
becomes unstable or sustained resonances will occur.
Using the EMT time domain simulation, both ( )Z s and
( )gridZ s can be computed, and system stability tools can be
used.
The generic EMT test case where resonances can occur
between the AC network and the converter station presented in
[18] is analyzed in this section. Parametric sensitivity studies
of the AC network is conducted, in order to assess the impact
on system stability. The HVDC-MMC 401 Level link is
connected to an AC network (Figure 11). Network 1 includes:
AC overhead lines, AC breaker “BRK”, shunt compensator of
400 MVar and an equivalent Thevenin source with SCL equal
to 20 GVA. Active power of 1,000 MW is transmitted from
Grid 1 to 2. The outer control strategy considers a DC
voltage/reactive power control on Station 2 and active/reactive
power control on Station 1.
HVDC-MMC link
50km
Overhead line
Network 1
Station 1Station 2
Grid2
Grid1
PCC1
Cshunt
+
+
Figure 11: EMT test case
In the following subsections, the impact of AC network
parameters is elaborated.
A. Impact of AC line length
The impact of the line length parameter on the system
stability is analyzed. AC overhead line length is varied ±10%
from the initial 50km value. Figure 12 shows the EMT
simulation results of the ( ) / ( )gridZ s Z s amplitude and angle.
Line length has mainly an impact on the frequency
resonance value. However, the frequency bandwidth that
exceeds the amplitude of one (threshold that guaranties the
stability) is the same. In addition, the phase margin
( ) / ( )gridZ s Z s∠ is close (and even slightly higher) to -1800
,
which shows that resonances can occur in this specific
frequency range. Indeed, in [18], time domain waveforms
illustrate such resonances.
100 400 700 1000 1300 1600 1900 2200 2500 2800
10
-2
10
0
10
2
|Zgrid
/Z|(ohm)
Frequency (Hz)
ACline=50km
ACline=55km ACline=45km
100 400 700 1000 1300 1600 1900 2200 2500 2800
-180
-140
-100
-60
-20
20
60
100
140
∠(Zgrid
/Z)(degree)
Frequency (Hz)
ACline=45kmACline=55km
ACline=50km
Figure 12: Impact of AC line length
B. Impact of shunt compensator
Shunt capacitors have also an impact on the stability of the
system. In Figure 13, the impact of the capacitor value on
( ) / ( )gridZ s Z s is depicted. Capacitor values of 800MVar,
400MVar, 100MVar and 0MVar are considered. It is noticed
that when no shunt capacitor is included in the system, the
system is stable since the phase margin ( ) / ( )gridZ s Z s∠ is
lower than ±1800
. When the capacitor value increases,
( ) / ( )gridZ s Z s amplitude increases and ( ) / ( )gridZ s Z s∠
tends to -1800
which makes the system unstable.
100 400 700 1000 1300 1600 1900 2200 2500 2800
10
-2
10
0
10
2
|Zgrid
/Z|(ohm)
Frequency (Hz)
100MVar
0MVar
400MVar800MVar
100 400 700 1000 1300 1600 1900 2200 2500 2800
-180
-140
-100
-60
-20
20
60
100
140
∠(Zgrid
/Z)(degree)
Frequency (Hz)
100MVar
0MVar400MVar
800MVar
Figure 13: Impact of Cshunt
C. Impact of short-circuit level
Short-circuit level (SCL) of the Thevenin source (Grid 1) is
varied in this subsection. Figure 14 shows the result of
( ) / ( )gridZ s Z s for three different values: 50, 20 and 5 GVA.
Based on this result, it can be concluded that for high
frequency resonances (>1 kHz), the short circuit level has a
minor impact on the stability of the system.
100 400 700 1000 1300 1600 1900 2200 2500 2800
10
-2
10
0
10
2
|Zgrid
/Z|(ohm)
Frequency (Hz)
SCL=20GVA
SCL=5GVA
SCL=50GVA
100 400 700 1000 1300 1600 1900 2200 2500 2800
-180
-140
-100
-60
-20
20
60
100
140
∠(Zgrid
/Z)(degree)
Frequency (Hz)
SCL=5GVA
SCL=20GVA
SCL=50GVA
Figure 14: Impact of SCL
D. Impact AC lines in parallel
The impact of the number of AC lines connected in parallel
is depicted in Figure 15: one line to three lines in parallel has
been considered. It is noticed, that when the number of AC
lines connected in parallel increases, the stability of the system
increases. In fact, with one AC line is connected, the frequency
range that leads to instability is as large as 100 Hz (1750 to
1850 Hz), however when three AC lines are in parallel, the
frequency range of instabilities tend to zero.
100 400 700 1000 1300 1600 1900 2200 2500 2800
10
-2
10
0
10
2
|Zgrid
/Z|(ohm)
Frequency (Hz)
1 AC line
2 AC lines
3 AC lines
100 400 700 1000 1300 1600 1900 2200 2500 2800
-180
-140
-100
-60
-20
20
60
100
140
∠(Zgrid
/Z)(degree)
Frequency (Hz)
3 AC lines
2 AC lines
1 AC line
Figure 15: Impact of AC lines in parallel
VII. CONCLUSIONS
This paper presents the impact of MMC station parameters
on the frequency response (Z and convh
i ) of the converter on
the AC side. It uses the EMT simulations approach and a
detailed MMC-401 Level model to derive these results.
Several parameters were considered to analyze their impact
on the frequency response: MMC levels, CBA, circulating
current, AC filter installation. Based on the presented results, it
can be concluded that MMC levels and CBA have the main
impact on the harmonic emissions. The circulating current
impact seems negligible on the frequency response at the AC
side. On the other hand, the paper showed that AC filters have
an impact on the impedance Z(f).
Parametric sensitivity studies have been also presented to
shows the impact of the AC network on the stability of the
system: AC line length, shunt capacitor and the number of AC
lines in parallel play a role on the stability of the system.
However, the short circuit level does not seem to affect such
high frequency resonances.
VIII. REFERENCES
[1] A. Lesnicar, and R. Marquardt, “An Innovative Modular Multilevel
Converter Topology Suitable for a Wide Power Range,” in Proc. IEEE
Power Tech. Conference, vol. 3, Bologna, Jun. 2003.
[2] C Buchhagen, C Rauscher, A Menze and J Jung, TenneT, “Borwin1 –
First Experiences with harmonic interactions in converter dominated
grids”, Int’l ETG Congress 2015, Nov. 17-18, 2015, Bonn, Germany,
VDE Conference
[3] J. Sun, "Impedance-Based Stability Criterion for Grid-Connected
Inverters," in IEEE Transactions on Power Electronics, vol. 26, no. 11,
pp. 3075-3078, Nov. 2011
[4] E. Möllerstedt and B. Bernhardsson, “Out of control because of
harmonics—An analysis of the harmonic response of an inverter
locomotive,” IEEE Control Syst. Mag., vol. 20, no. 4, pp. 70–81, Aug.
2000
[5] G. D. Irwin, A. Isaacs and D. Woodford, "Simulation requirements for
analysis and mitigation of SSCI phenomena in wind farms,"
Transmission and Distribution Conference and Exposition (T&D), 2012
IEEE PES, Orlando, FL, 2012, pp. 1-4
[6] R. D. Middlebrook, “Input Filter Considerations in Design and
Application of Switching Regulators,” IEEE Industry Applications
Society Annual Meeting, October 11-14, 1976, Chicago
[7] L. Harnefors, M. Bongiorno and S. Lundberg, "Input-Admittance
Calculation and Shaping for Controlled Voltage-Source Converters," in
IEEE Transactions on Industrial Electronics, vol. 54, no. 6, pp. 3323-
3334, Dec. 2007
[8] M. Cespedes and J. Sun, "Impedance Modeling and Analysis of Grid-
Connected Voltage-Source Converters," in IEEE Transactions on
Power Electronics, vol. 29, no. 3, pp. 1254-1261, March 2014
[9] G. Bergna Diaz, J. A. Suul and S. D'Arco, "Small-signal state-space
modeling of modular multilevel converters for system stability analysis,"
Energy Conversion Congress and Exposition (ECCE), 2015 IEEE,
Montreal, QC, 2015, pp. 5822-5829
[10] H. Saad, J. Mahseredjian, S. Dennetière, S. Nguefeu, “Interactions
studies of HVDC–MMC link embedded in an AC grid,” Electric Power
Systems Research, 11 March 2016
[11] A. Jamshidi Far and D. Jovcic, "Small-Signal Dynamic DQ Model of
Modular Multilevel Converter for System Studies," in IEEE
Transactions on Power Delivery, vol. 31, no. 1, pp. 191-199, Feb. 2016
[12] L. Harnefors, X. Wang, A. G. Yepes and F. Blaabjerg, "Passivity-Based
Stability Assessment of Grid-Connected VSCs—An Overview," in
IEEE Journal of Emerging and Selected Topics in Power Electronics,
vol. 4, no. 1, pp. 116-125, March 2016
[13] H. Saad, S. Dennetière, J. Mahseredjian, et al "Modular Multilevel
Converter Models for Electromagnetic Transients," IEEE Transactions
on Power Delivery, vol. 29, no. 3, pp. 1481-1489, June 2014.
[14] R. D. Middlebrook "Measurement of loop gain in feedback systems†."
International Journal of Electronics Theoretical and Experimental 38.4
(1975): 485-512.
[15] Q. Tu, and Z. Xu, “Impact of Sampling Frequency on Harmonic
Distortion for Modular Multilevel Converter,” IEEE Trans. on Power
Delivery, vol. 26, no. 1, pp. 298-306, Jan. 2011.
[16] S. Rohner, S. Bernet, M. Hiller and R. Sommer, "Analysis and
Simulation of a 6 kV, 6 MVA Modular Multilevel Converter," Industrial
Electronics, 2009. IECON '09. 35th Annual Conference of IEEE, Porto,
2009, pp. 225-230
[17] H. Saad, J. Peralta, S. Dennetière, J. Mahseredjian, J. Jatskevich, J.A.
Martinez et al.., "Dynamic Averaged and Simplified Models for MMC-
Based HVDC Transmission Systems," Power Delivery, IEEE
Transactions on , vol.28, no.3, pp.1723,1730, July 2013
[18] H. Saad; Y. Fillion; S. Deschanvres; Y. Vernay; S. Dennetiere, "On
Resonances and Harmonics in HVDC-MMC Station Connected to AC
grid," in IEEE Transactions on Power Delivery , vol.PP, no.99, pp.1-1
[19] C. Du, “VSC-HVDC for Industrial Power Systems,” Ph.D. Thesis,
Chalmers Univ. of Technology, Göteborg, Sweden, 2007

More Related Content

What's hot

Modelling of 25 kV Electric Railway System
Modelling of 25 kV Electric Railway SystemModelling of 25 kV Electric Railway System
Modelling of 25 kV Electric Railway SystemBérengère VIGNAUX
 
Lcl filter design
Lcl filter designLcl filter design
Lcl filter designZunAib Ali
 
Small Signal Modeling Of Controller For Statcom Used In Distribution System F...
Small Signal Modeling Of Controller For Statcom Used In Distribution System F...Small Signal Modeling Of Controller For Statcom Used In Distribution System F...
Small Signal Modeling Of Controller For Statcom Used In Distribution System F...IJERA Editor
 
FAULT DETECTION AND CLASSIFICATION ON TRANSMISSION OVERHEAD LINE USING BPP...
FAULT DETECTION AND CLASSIFICATION ON TRANSMISSION OVERHEAD LINE  USING BPP...FAULT DETECTION AND CLASSIFICATION ON TRANSMISSION OVERHEAD LINE  USING BPP...
FAULT DETECTION AND CLASSIFICATION ON TRANSMISSION OVERHEAD LINE USING BPP...Politeknik Negeri Ujung Pandang
 
Power upgrading of transmission line by combining ac dc transmission
Power upgrading of transmission line by combining ac dc transmissionPower upgrading of transmission line by combining ac dc transmission
Power upgrading of transmission line by combining ac dc transmissionShailesh Senta
 
POWER QUALITY IMPROVEMENT BY SSSC AND STATCOM USING PI CONTROLLER
POWER QUALITY IMPROVEMENT BY SSSC AND STATCOM USING PI CONTROLLERPOWER QUALITY IMPROVEMENT BY SSSC AND STATCOM USING PI CONTROLLER
POWER QUALITY IMPROVEMENT BY SSSC AND STATCOM USING PI CONTROLLERJournal For Research
 
Flexible ac transmission FACTs
Flexible ac transmission FACTsFlexible ac transmission FACTs
Flexible ac transmission FACTsMOHAN RAKIB
 
Tranformerless H6 Grid Tied Inverter For Photovoltaic Generation
Tranformerless H6 Grid Tied Inverter For Photovoltaic GenerationTranformerless H6 Grid Tied Inverter For Photovoltaic Generation
Tranformerless H6 Grid Tied Inverter For Photovoltaic GenerationIJMER
 
Major Project, HVDC Thesis - Saurabh Saxena
Major Project, HVDC Thesis - Saurabh SaxenaMajor Project, HVDC Thesis - Saurabh Saxena
Major Project, HVDC Thesis - Saurabh SaxenaSaurabh Saxena
 
Active Reactive Power Flow Control Using Static Synchronous Series Compensato...
Active Reactive Power Flow Control Using Static Synchronous Series Compensato...Active Reactive Power Flow Control Using Static Synchronous Series Compensato...
Active Reactive Power Flow Control Using Static Synchronous Series Compensato...IOSR Journals
 
Meet sarayni
Meet sarayniMeet sarayni
Meet saraynithavasik
 

What's hot (19)

Modelling of 25 kV Electric Railway System
Modelling of 25 kV Electric Railway SystemModelling of 25 kV Electric Railway System
Modelling of 25 kV Electric Railway System
 
Lcl filter design
Lcl filter designLcl filter design
Lcl filter design
 
K.Sravanthi.
K.Sravanthi.K.Sravanthi.
K.Sravanthi.
 
6 PHASE TRANSMISSION SYSTEM
6 PHASE TRANSMISSION SYSTEM6 PHASE TRANSMISSION SYSTEM
6 PHASE TRANSMISSION SYSTEM
 
Ehv ac transmission line
Ehv ac transmission lineEhv ac transmission line
Ehv ac transmission line
 
Small Signal Modeling Of Controller For Statcom Used In Distribution System F...
Small Signal Modeling Of Controller For Statcom Used In Distribution System F...Small Signal Modeling Of Controller For Statcom Used In Distribution System F...
Small Signal Modeling Of Controller For Statcom Used In Distribution System F...
 
FAULT DETECTION AND CLASSIFICATION ON TRANSMISSION OVERHEAD LINE USING BPP...
FAULT DETECTION AND CLASSIFICATION ON TRANSMISSION OVERHEAD LINE  USING BPP...FAULT DETECTION AND CLASSIFICATION ON TRANSMISSION OVERHEAD LINE  USING BPP...
FAULT DETECTION AND CLASSIFICATION ON TRANSMISSION OVERHEAD LINE USING BPP...
 
Electrical power system
Electrical power system Electrical power system
Electrical power system
 
Power upgrading of transmission line by combining ac dc transmission
Power upgrading of transmission line by combining ac dc transmissionPower upgrading of transmission line by combining ac dc transmission
Power upgrading of transmission line by combining ac dc transmission
 
POWER QUALITY IMPROVEMENT BY SSSC AND STATCOM USING PI CONTROLLER
POWER QUALITY IMPROVEMENT BY SSSC AND STATCOM USING PI CONTROLLERPOWER QUALITY IMPROVEMENT BY SSSC AND STATCOM USING PI CONTROLLER
POWER QUALITY IMPROVEMENT BY SSSC AND STATCOM USING PI CONTROLLER
 
Flexible ac transmission FACTs
Flexible ac transmission FACTsFlexible ac transmission FACTs
Flexible ac transmission FACTs
 
Tranformerless H6 Grid Tied Inverter For Photovoltaic Generation
Tranformerless H6 Grid Tied Inverter For Photovoltaic GenerationTranformerless H6 Grid Tied Inverter For Photovoltaic Generation
Tranformerless H6 Grid Tied Inverter For Photovoltaic Generation
 
Major Project, HVDC Thesis - Saurabh Saxena
Major Project, HVDC Thesis - Saurabh SaxenaMajor Project, HVDC Thesis - Saurabh Saxena
Major Project, HVDC Thesis - Saurabh Saxena
 
Active Reactive Power Flow Control Using Static Synchronous Series Compensato...
Active Reactive Power Flow Control Using Static Synchronous Series Compensato...Active Reactive Power Flow Control Using Static Synchronous Series Compensato...
Active Reactive Power Flow Control Using Static Synchronous Series Compensato...
 
Performance Investigation of a Monopolar HVDC Transmission System Feeding a ...
Performance Investigation of a Monopolar HVDC Transmission  System Feeding a ...Performance Investigation of a Monopolar HVDC Transmission  System Feeding a ...
Performance Investigation of a Monopolar HVDC Transmission System Feeding a ...
 
EHV AC
EHV ACEHV AC
EHV AC
 
Loss minimisation in power system
Loss minimisation in power systemLoss minimisation in power system
Loss minimisation in power system
 
Power system calculations
Power system calculationsPower system calculations
Power system calculations
 
Meet sarayni
Meet sarayniMeet sarayni
Meet sarayni
 

Similar to Analysis of harmonics and resonances in hvdc mmc link connected to AC grid

The Need for Enhanced Power System Modelling Techniques and Simulation Tools
The Need for Enhanced Power System Modelling Techniques and Simulation ToolsThe Need for Enhanced Power System Modelling Techniques and Simulation Tools
The Need for Enhanced Power System Modelling Techniques and Simulation ToolsPower System Operation
 
[9_CV] FCS-Model Predictive Control of Induction Motors feed by MultilLevel C...
[9_CV] FCS-Model Predictive Control of Induction Motors feed by MultilLevel C...[9_CV] FCS-Model Predictive Control of Induction Motors feed by MultilLevel C...
[9_CV] FCS-Model Predictive Control of Induction Motors feed by MultilLevel C...Nam Thanh
 
The Need for Enhanced Power System Modelling Techniques & Simulation Tools
The Need for Enhanced  Power System  Modelling Techniques  &  Simulation Tools The Need for Enhanced  Power System  Modelling Techniques  &  Simulation Tools
The Need for Enhanced Power System Modelling Techniques & Simulation Tools Power System Operation
 
OPTIMAL TORQUE RIPPLE CONTROL OF ASYNCHRONOUS DRIVE USING INTELLIGENT CONTROL...
OPTIMAL TORQUE RIPPLE CONTROL OF ASYNCHRONOUS DRIVE USING INTELLIGENT CONTROL...OPTIMAL TORQUE RIPPLE CONTROL OF ASYNCHRONOUS DRIVE USING INTELLIGENT CONTROL...
OPTIMAL TORQUE RIPPLE CONTROL OF ASYNCHRONOUS DRIVE USING INTELLIGENT CONTROL...elelijjournal
 
Power System Modeling Techniques & Simulation Tools
Power System Modeling Techniques & Simulation ToolsPower System Modeling Techniques & Simulation Tools
Power System Modeling Techniques & Simulation ToolsPower System Operation
 
IRJET- Comparative Study of Common Methods of Frequency Response using MTDC G...
IRJET- Comparative Study of Common Methods of Frequency Response using MTDC G...IRJET- Comparative Study of Common Methods of Frequency Response using MTDC G...
IRJET- Comparative Study of Common Methods of Frequency Response using MTDC G...IRJET Journal
 
[7] a generalized parameter tuning method of proportional resonant controller...
[7] a generalized parameter tuning method of proportional resonant controller...[7] a generalized parameter tuning method of proportional resonant controller...
[7] a generalized parameter tuning method of proportional resonant controller...Ngoc Dinh
 
Voltage profile Improvement Using Static Synchronous Compensator STATCOM
Voltage profile Improvement Using Static Synchronous Compensator STATCOMVoltage profile Improvement Using Static Synchronous Compensator STATCOM
Voltage profile Improvement Using Static Synchronous Compensator STATCOMINFOGAIN PUBLICATION
 
Principle and Algorithm of Reactive Power Management for LLC Based Parlled MT...
Principle and Algorithm of Reactive Power Management for LLC Based Parlled MT...Principle and Algorithm of Reactive Power Management for LLC Based Parlled MT...
Principle and Algorithm of Reactive Power Management for LLC Based Parlled MT...Sohan Bin Anwar Siddique
 
An Improved Repetitive Control for Circulating Current Restraining in MMC-MTDC
An Improved Repetitive Control for Circulating Current Restraining in MMC-MTDCAn Improved Repetitive Control for Circulating Current Restraining in MMC-MTDC
An Improved Repetitive Control for Circulating Current Restraining in MMC-MTDCTELKOMNIKA JOURNAL
 
A Review of Analysis and Modeling of Grid Connected Three Phase Multilevel Un...
A Review of Analysis and Modeling of Grid Connected Three Phase Multilevel Un...A Review of Analysis and Modeling of Grid Connected Three Phase Multilevel Un...
A Review of Analysis and Modeling of Grid Connected Three Phase Multilevel Un...IRJET Journal
 
Power Quality Enhancement in Power Distribution System by Using Fuzzy Logic C...
Power Quality Enhancement in Power Distribution System by Using Fuzzy Logic C...Power Quality Enhancement in Power Distribution System by Using Fuzzy Logic C...
Power Quality Enhancement in Power Distribution System by Using Fuzzy Logic C...Dr. Sudhir Kumar Srivastava
 
An Improved Phase Disposition Pulse Width Modulation (PDPWM) For a Modular Mu...
An Improved Phase Disposition Pulse Width Modulation (PDPWM) For a Modular Mu...An Improved Phase Disposition Pulse Width Modulation (PDPWM) For a Modular Mu...
An Improved Phase Disposition Pulse Width Modulation (PDPWM) For a Modular Mu...IOSR Journals
 
Journal jpe 7-3_1299739594
Journal jpe 7-3_1299739594Journal jpe 7-3_1299739594
Journal jpe 7-3_1299739594Venkat Mandadhi
 
Performance Evaluation of Two-Level Photovoltaic Voltage Source Inverter Cons...
Performance Evaluation of Two-Level Photovoltaic Voltage Source Inverter Cons...Performance Evaluation of Two-Level Photovoltaic Voltage Source Inverter Cons...
Performance Evaluation of Two-Level Photovoltaic Voltage Source Inverter Cons...IJERA Editor
 

Similar to Analysis of harmonics and resonances in hvdc mmc link connected to AC grid (20)

The Need for Enhanced Power System Modelling Techniques and Simulation Tools
The Need for Enhanced Power System Modelling Techniques and Simulation ToolsThe Need for Enhanced Power System Modelling Techniques and Simulation Tools
The Need for Enhanced Power System Modelling Techniques and Simulation Tools
 
A Generalized Parameter Tuning Method of Proportional-Resonant Controllers fo...
A Generalized Parameter Tuning Method of Proportional-Resonant Controllers fo...A Generalized Parameter Tuning Method of Proportional-Resonant Controllers fo...
A Generalized Parameter Tuning Method of Proportional-Resonant Controllers fo...
 
www.ijerd.com
www.ijerd.comwww.ijerd.com
www.ijerd.com
 
Finite-Control-Set Predictive Current Control Based Real and Reactive Power C...
Finite-Control-Set Predictive Current Control Based Real and Reactive Power C...Finite-Control-Set Predictive Current Control Based Real and Reactive Power C...
Finite-Control-Set Predictive Current Control Based Real and Reactive Power C...
 
[9_CV] FCS-Model Predictive Control of Induction Motors feed by MultilLevel C...
[9_CV] FCS-Model Predictive Control of Induction Motors feed by MultilLevel C...[9_CV] FCS-Model Predictive Control of Induction Motors feed by MultilLevel C...
[9_CV] FCS-Model Predictive Control of Induction Motors feed by MultilLevel C...
 
The Need for Enhanced Power System Modelling Techniques & Simulation Tools
The Need for Enhanced  Power System  Modelling Techniques  &  Simulation Tools The Need for Enhanced  Power System  Modelling Techniques  &  Simulation Tools
The Need for Enhanced Power System Modelling Techniques & Simulation Tools
 
OPTIMAL TORQUE RIPPLE CONTROL OF ASYNCHRONOUS DRIVE USING INTELLIGENT CONTROL...
OPTIMAL TORQUE RIPPLE CONTROL OF ASYNCHRONOUS DRIVE USING INTELLIGENT CONTROL...OPTIMAL TORQUE RIPPLE CONTROL OF ASYNCHRONOUS DRIVE USING INTELLIGENT CONTROL...
OPTIMAL TORQUE RIPPLE CONTROL OF ASYNCHRONOUS DRIVE USING INTELLIGENT CONTROL...
 
Power System Modeling Techniques & Simulation Tools
Power System Modeling Techniques & Simulation ToolsPower System Modeling Techniques & Simulation Tools
Power System Modeling Techniques & Simulation Tools
 
IRJET- Comparative Study of Common Methods of Frequency Response using MTDC G...
IRJET- Comparative Study of Common Methods of Frequency Response using MTDC G...IRJET- Comparative Study of Common Methods of Frequency Response using MTDC G...
IRJET- Comparative Study of Common Methods of Frequency Response using MTDC G...
 
[7] a generalized parameter tuning method of proportional resonant controller...
[7] a generalized parameter tuning method of proportional resonant controller...[7] a generalized parameter tuning method of proportional resonant controller...
[7] a generalized parameter tuning method of proportional resonant controller...
 
Voltage profile Improvement Using Static Synchronous Compensator STATCOM
Voltage profile Improvement Using Static Synchronous Compensator STATCOMVoltage profile Improvement Using Static Synchronous Compensator STATCOM
Voltage profile Improvement Using Static Synchronous Compensator STATCOM
 
Principle and Algorithm of Reactive Power Management for LLC Based Parlled MT...
Principle and Algorithm of Reactive Power Management for LLC Based Parlled MT...Principle and Algorithm of Reactive Power Management for LLC Based Parlled MT...
Principle and Algorithm of Reactive Power Management for LLC Based Parlled MT...
 
An Improved Repetitive Control for Circulating Current Restraining in MMC-MTDC
An Improved Repetitive Control for Circulating Current Restraining in MMC-MTDCAn Improved Repetitive Control for Circulating Current Restraining in MMC-MTDC
An Improved Repetitive Control for Circulating Current Restraining in MMC-MTDC
 
An efficient predictive current controller with adaptive parameter estimation...
An efficient predictive current controller with adaptive parameter estimation...An efficient predictive current controller with adaptive parameter estimation...
An efficient predictive current controller with adaptive parameter estimation...
 
A Review of Analysis and Modeling of Grid Connected Three Phase Multilevel Un...
A Review of Analysis and Modeling of Grid Connected Three Phase Multilevel Un...A Review of Analysis and Modeling of Grid Connected Three Phase Multilevel Un...
A Review of Analysis and Modeling of Grid Connected Three Phase Multilevel Un...
 
Power Quality Enhancement in Power Distribution System by Using Fuzzy Logic C...
Power Quality Enhancement in Power Distribution System by Using Fuzzy Logic C...Power Quality Enhancement in Power Distribution System by Using Fuzzy Logic C...
Power Quality Enhancement in Power Distribution System by Using Fuzzy Logic C...
 
Review of the Most Applicable Regulator Collections to Control the Parallel A...
Review of the Most Applicable Regulator Collections to Control the Parallel A...Review of the Most Applicable Regulator Collections to Control the Parallel A...
Review of the Most Applicable Regulator Collections to Control the Parallel A...
 
An Improved Phase Disposition Pulse Width Modulation (PDPWM) For a Modular Mu...
An Improved Phase Disposition Pulse Width Modulation (PDPWM) For a Modular Mu...An Improved Phase Disposition Pulse Width Modulation (PDPWM) For a Modular Mu...
An Improved Phase Disposition Pulse Width Modulation (PDPWM) For a Modular Mu...
 
Journal jpe 7-3_1299739594
Journal jpe 7-3_1299739594Journal jpe 7-3_1299739594
Journal jpe 7-3_1299739594
 
Performance Evaluation of Two-Level Photovoltaic Voltage Source Inverter Cons...
Performance Evaluation of Two-Level Photovoltaic Voltage Source Inverter Cons...Performance Evaluation of Two-Level Photovoltaic Voltage Source Inverter Cons...
Performance Evaluation of Two-Level Photovoltaic Voltage Source Inverter Cons...
 

Recently uploaded

University management System project report..pdf
University management System project report..pdfUniversity management System project report..pdf
University management System project report..pdfKamal Acharya
 
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and workingUNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and workingrknatarajan
 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxpranjaldaimarysona
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingrakeshbaidya232001
 
Introduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxIntroduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxupamatechverse
 
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...ranjana rawat
 
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfKamal Acharya
 
UNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its PerformanceUNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its Performancesivaprakash250
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Dr.Costas Sachpazis
 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Dr.Costas Sachpazis
 
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Christo Ananth
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...ranjana rawat
 
Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxupamatechverse
 
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Bookingdharasingh5698
 
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINEMANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINESIVASHANKAR N
 
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...ranjana rawat
 
Glass Ceramics: Processing and Properties
Glass Ceramics: Processing and PropertiesGlass Ceramics: Processing and Properties
Glass Ceramics: Processing and PropertiesPrabhanshu Chaturvedi
 
MANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTING
MANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTINGMANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTING
MANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTINGSIVASHANKAR N
 
result management system report for college project
result management system report for college projectresult management system report for college project
result management system report for college projectTonystark477637
 

Recently uploaded (20)

University management System project report..pdf
University management System project report..pdfUniversity management System project report..pdf
University management System project report..pdf
 
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and workingUNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptx
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writing
 
Introduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxIntroduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptx
 
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
 
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
 
UNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its PerformanceUNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its Performance
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
 
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
 
Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptx
 
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
 
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINEMANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
 
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
 
Glass Ceramics: Processing and Properties
Glass Ceramics: Processing and PropertiesGlass Ceramics: Processing and Properties
Glass Ceramics: Processing and Properties
 
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINEDJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
 
MANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTING
MANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTINGMANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTING
MANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTING
 
result management system report for college project
result management system report for college projectresult management system report for college project
result management system report for college project
 

Analysis of harmonics and resonances in hvdc mmc link connected to AC grid

  • 1. H. Saad, Y. Fillion Abstract - High-frequency responses of HVDC-MMC links are essential to study because harmonic and resonance phenomena may impact the AC grid. In this paper, EMT-type simulations are used to analyze converter station’s frequency response. Several MMC station and AC network parameters are varied to analyze their impact. In addition, an EMT-type test case, based on a recent installed HVDC project, is used to illustrate potential resonances that can occur between converter stations and AC networks. Keywords: EMTP, Harmonic, Resonance, Impedance Analysis, HVDC, Modular multilevel converter (MMC), Voltage source converter (VSC) I. INTRODUCTION igh Voltage Direct Current (HVDC) systems based on the Modular Multilevel Converter (MMC) [1] is the predominant topology used in recent and upcoming HVDC- VSC projects. For instance, several HVDC-MMC projects are currently planned or operated by RTE (French TSO), such as the INELFE, FIL, IFA2, etc. Harmonic emissions and resonances in a system may reduce the use of power and damage the insulation of the system components if they are not limited properly. Furthermore, a system malfunction may occur if the system has high voltage or current harmonic amplitudes. The harmonics which propagate in the AC network and to power electronic components can cause overheating of equipment and interferences with communication circuits. Power electronic converters can cause instabilities and/or resonances when interacting with other equipment in a power system. These phenomena can occur in a wide range of frequencies (up to few kHz). Low and high frequency resonances have been registered in several power electronics based projects: in offshore HVDC link high frequency resonances [2] were noted. Instability with converters of a photovoltaic plant [3] and in traction applications [4] are reported. In [5] low frequency oscillations are studied between power electronic and power system devices. Power electronic converters inject harmonics in the grid mainly due to modulation and switching commutations. For a MMC station, the injected harmonics depend mainly on the number of H. Saad and Y. Fillion are with Réseau de Transport d'Electricité (RTE), Paris, France (e-mail: hani.saad@rte-france.com). Paper submitted to the International Conference on Power Systems Transients (IPST2017) in Seoul, Republic of Korea June 26-29, 2017 submodules (SMs) per arm and their modulation strategies, which is specific to the manufacturer and/or project. In HVDC projects, vendors and utilities perform harmonic and resonance studies. These studies are conducted in frequency domain and/or using electromagnetic transient (EMT) tools. Frequency domain studies are used to assess system stability [6] and are convenient for simulating a wide range of configurations and scenarios. To derive the frequency response of a converter, analytical or small signal approaches are commonly used. In [7]-[11] an analytical development of a VSC station is presented. However, during real HVDC and FACTS projects, the EMT-type model provided by the manufacturer is often hidden (or black-boxed) due to intellectual property issue. Therefore, the analytical model derivation is not possible or not sufficiently accurate. In addition, model linearization and derivation are challenging and complex tasks since the MMC includes several variables and complex control structures. In this paper, the derivation of the frequency response of a converter station based on a black- box EMT model, presented in [18], is used. Since this EMT model includes the detailed representation of the converter station with its control system, this approach is more practical than with an analytical model. This paper is an extended version of [18]. Several test cases are performed to analyze the impact of MMC station parameters (as MMC levels, control system, AC filter, etc.) on the high-frequency response (i.e. harmonics and impedance). In addition, the generic EMT test case where high frequency resonances can occur between the AC network and the converter station presented in [18] is analyzed in this paper. Parametric sensitivity studies of the AC network is conducted in order to assess the impact on system stability. The paper is structured as follows. Section II recalls harmonics and resonance phenomena. Section III presents the generic MMC-401-Level station and its control structure. Section IV illustrates the derivation of the frequency response based on the EMT-type model. Section V simulation results of the impact of converter station and ac network parameters are presented. II. MMC STATION OVERVIEW The generic EMT model includes the detailed representation of the converter station with its control system, see Figure 1 [5]. The equivalent detailed MMC model where each SM is represented, (i.e. Model #2 as defined in [13]) is considered. The control system uses an upper level control including inner/outer controllers and a lower level control to Analysis of Harmonics and Resonances in HVDC-MMC Link Connected to AC grid H
  • 2. regulate MMC internal variables: capacitor balancing algorithm (CBA) to balance SM capacitor voltages in each arm, modulation to convert the reference voltage to a number of inserted SMs and circulating current control (CCC) to regulate converter internal energy. More details can be found in [17]. + - 1 2 gate signal measurements ref conv j v Lowerlevelcontrol Outer Control Inner Control Upperlevelcontrol StartPoint Reactor CBA and Modulation CCC 400 / 320kV 0.12trfL pu= 0.001trfR pu= 0.075armL pu= PCC j v ji Measurements filter 640dcV kV= 40 /C kJ MVA= 400N SM= Figure 1: Generic control structure of MMC station III. HARMONICS AND RESONANCES We can distinguish two different high frequency phenomena that can take place between power electronics and surrounding AC networks; harmonic emissions and resonances: • Harmonics emissions are mainly associated with semiconductor switches and therefore continuously transmitted by the system which may affect the wave quality. • The resonances are mainly related to the control system, filters, delays, etc. Resonances have usually higher order of magnitude than harmonics but their time intervals are shorter since system protection is used to trip network devices. Figure 2 illustrates these two different aspects. The voltage source ( convh v ) or current source ( convh i ) represents the harmonic emissions and the impedance Z(f) (where f stands for frequency) depends on control loops and physical equipment which includes system resonances [14]. Since a converter station with its control system, is a nonlinear system, equivalent circuit values depend on the set-point operation of the system and will vary when the converter configuration changes. ( )Z s convh v 1convv convv ++ ( )Z s 1conviconvh i a) Equivalent Thevenin circuit b) Equivalent Norton circuit Figure 2: Equivalent circuit for frequency response Determination of Z(f) and convh i (or convh v ) is achieved in two ways: by means of an analytical approach or by EMT simulations. The analytical approach offers the capability to use classical modal analysis tools in order to study the converter behavior [6]. However, analytical models may become complex depending on the studied system and must be validated as several approximations are introduced. On the other hand, the EMT simulations include the detailed models of the control system and power equipment. The obtained results are more realistic than with an analytical model, however simulation time constitutes the main drawback. This article uses the EMT simulation approach to derive Norton equivalent values at each harmonic rank h. IV. FREQUENCY RESPONSE BASED ON EMT SIMULATION The derivation of the equivalent Norton circuit (Figure 2) based on time domain EMT simulation is briefly described in this section. The circuit setup is shown in Figure 3 and the flow chart computation for each h is depicted in Figure 4. The converter station is connected to an equivalent AC grid and a controlled ideal current source injh i at the PCC. The injected current injh i are varied during time domain simulations in order to compute Z(f) and convh i (Figure 2.b) [18]. The amplitude of injh i should be a fraction of the nominal current of the system to guarantee a small-signal perturbation and to avoid any excitation of the control and protection system. The important feature of this method is that the control system is in normal operation, therefore, a realistic set point can be considered [14]. Norton equivalent values change according to the set point operations. injh i PCCh v gridh i Equivalent AC grid hi HVDC-MMC link + Figure 3: Model setup to derive the equivalent Norton circuit Time domain + iinjh Measure vPCCh & ih Compute iconvh & Zh Frequency domain studies Figure 4: Block diagram, Norton equivalent computation The derivation of the Norton equivalent circuit is also useful for frequency domain studies in power grid systems, since the computation time is much faster than with the detailed EMT-model. It should be highlighted that this approach can be also used in real-time simulators with hardware-in-the-loop simulation including the real-physical control system (or replicas). Such approach can provides faster simulation time and more realistic results since the real and complete control system is used. V. FREQUENCY RESPONSE STUDIES In this section, the impact of the converter station parameters on the frequency response is analysed. The test case used is a point-to-point HVDC-MMC 401-Level link with a transmission capacity of 1,000 MW. The AC grid is modeled
  • 3. as an equivalent source with a short-circuit level (SCL) of 20 GVA. Converter station data can be found in Figure 1 and control data is provided in the Appendix. All model developments and simulations are performed using the EMTP- RV software. A. Harmonic studies In this sub-section, converter station parameters that impact the harmonic emissions are considered. 1) Impact of MMC levels Harmonics emitted from the MMC station are known to be low in amplitude. In order to show the impact of MMC levels, the MMC-401-Level is compared with a MMC-11-Level, in this section. Voltage references, harmonic distorsions (i.e. convh i ) and Z(f) are compared in Figure 5. Obviously, harmonic emissions produced from 11-Level MMC are higher than those produced by a 401-Level MMC which are negligible. For such MMC 11-Level, it is expected that an AC filter will be installed at the converter station in order to limit those harmonics. Based on Z(f) responses in Figure 5, one can notice that the impedance is not affected by the MMC levels. This was expected since control loops are identical (except the CBA and modulation) between thoses two MMC levels. 0.91 0.915 0.92 0.925 0.93 0.935 0 0.2 0.4 0.6 0.8 1 vPCCa (pu) Time (s) MMC 11L MMC 401L 100 400 700 1000 1300 1600 1900 2200 2500 2800 0 5 10 15 iconv (A) Frequency (Hz) MMC 11L MMC 401L 100 400 700 1000 1300 1600 1900 2200 2500 2800 0 500 1000 1500 2000 |Z|(ohm) Frequency (Hz) MMC 11L MMC 401L Figure 5: Impact of MMC levels 2) CBA impact In this section, the impact of the CBA over the frequency response is investigated. The capacitor value and the threshold activation [15] of the CBA are varied to get the extreme cases: - CBA #1: threshold is set at 1% and C= 45 kJ/MVA - CBA #2: threshold is set at 50% and C =25 kJ/MVA Similar test case as in [18] has been used, however, a MMC including 401-Level is simulated instead of MMC-11-Level. Figure 6 shows some of the 400 SMs capacitor voltages of phase A upper arm, using CBA #1 and CBA #2. It can be observed that CBA #2 has higher amplitude fluctuation and higher differences between capacitor voltages. Figure 7 shows the impact of capacitor fluctuations and CBA configurations over the frequency response, i.e. Z(f) and convh i . It can be observed that these parameters have mainly an impact on the harmonic injection convh i rather than on Z(f). Note that with CBA #2, high harmonic emissions are noticed at lower frequency (around 250 Hz and 350 Hz). This shows that CBA and capacitor voltage fluctuations have an impact on the harmonic emissions. This results shows also the importance of a detailed EMT model (even for MMC-401 Level) to account for such harmonics. 0.6 0.61 0.62 0.63 0.64 0.65 0.66 0.8 0.9 1 1.1 1.2 vCi(pu) Time (sec) a) CBA#1 and C=45 kJ/MVA 0.6 0.61 0.62 0.63 0.64 0.65 0.66 0.8 0.9 1 1.1 1.2 vCi(pu) Time (sec) b) CBA#2 and C=25 kJ/MVA Figure 6: CBA impact, Capacitor voltages of SMs 100 300 500 700 900 1100 1300 1500 1700 1900 2100 0 2 4 6 8 iconv (A) Frequency (Hz) CBA #2 CBA #1 100 400 700 1000 1300 1600 1900 2200 2500 2800 0 500 1000 1500 2000 |Z|(ohm) Frequency (Hz) CBA#1 CBA#2 Figure 7: CBA impact, frequency response ( convh i and Z ) 3) CCC impact To analyze the circulating current control impact, the reference value of the second harmonic circulating current control is varied between 0 and 0.1 pu, for CCC #1 and CCC #2 respectively. Similar test case as in [18] has been used,
  • 4. however, a MMC including 401-Level is simulated in this paper, instead of MMC 11-Level. Figure 8 shows the circulating current variation impact. Figure 9 shows the results of convh i and Z(f). Since the frequency response of both CCC configurations are close, it can be concluded that the circulating current has a minor impact on the frequency response from the AC side (as highlighted in [16]). 0.6 0.61 0.62 0.63 0.64 0.65 0.66 -0.5 -0.4 -0.3 -0.2 -0.1 Current(pu) Time (sec) CCC #2 CCC #1 Figure 8: CCC impact, circulating current phase A 100 300 500 700 900 1100 1300 1500 1700 1900 2100 0 2 4 6 8 iconv (A) Frequency (Hz) CCC #2 CCC #1 100 400 700 1000 1300 1600 1900 2200 2500 2800 0 500 1000 1500 2000 |Z|(ohm) Frequency (Hz) CCC#1 CCC#2 Figure 9: CCC impact, frequency response ( convh i and Z ) B. Impedance studies In this section, the impact of control system parameters on Z(f) is studied. 1) Inner control loop and time delay Inner control loop dynamic and time delay have an impact on Z(f). Results and analysis are provided in [18]: The impact of the inner control is increased when the dynamic response of the control loop is fast. 2) Impact of AC filter at PCC Depending on Manufacturers and project specifications, AC filter equipment can be installed at PCC. To show the impact of this device over the frequency response, in this section a low-pass filter is added at PCC to the MMC station model. Parameters of the low-pass filter are based on [19]. Note, that in practice, this low-pass filter will be tuned according to project specification, however, the scope of this section is only to illustrate the impact of such equipment. Result comparisons between converter station with and without the installation of the AC filter is depicted in Figure 10. It can be noticed that the Z(f) is mainly affected by the AC filter installation for frequencies above 400 Hz. 100 400 700 1000 1300 1600 1900 2200 2500 2800 0 500 1000 1500 2000 |Z|(ohm) Frequency (Hz) with AC filter without AC filter 100 400 700 1000 1300 1600 1900 2200 2500 2800 -100 -50 0 50 100 ∠Z(deg) Frequency (Hz) without AC filter with AC filter Figure 10: Impact of AC filter at PCC VI. STABILITY ANALYSIS In [12] and [18], it has been shown that low-pass filters and delays in converter station control can lead to negative resistance in high frequency range. Therefore, this negative resistance can lead to resonances or instability depending on the AC network configuration and parameters. To analyze the stability of a system, the considered circuit can be represented as a feedback loop system in the small- signal domain. Therefore, the following Laplace equation can be deduced [3]: ( ) ( ) ( ) 1 ( ) / ( ) grid PCC conv grid Z s i s v s Z s Z s = + (1) where ( )gridZ s is the equivalent impedance of the AC grid. From equ. (1), the system is stable if the expression ( ) / ( )gridZ s Z s is lower than one at each frequency. However, if the Nyquist criterion is not met, and in addition, the angle ( ) / ( )gridZ s Z s∠ is higher than ±1800 , then the system becomes unstable or sustained resonances will occur. Using the EMT time domain simulation, both ( )Z s and ( )gridZ s can be computed, and system stability tools can be used. The generic EMT test case where resonances can occur between the AC network and the converter station presented in [18] is analyzed in this section. Parametric sensitivity studies of the AC network is conducted, in order to assess the impact on system stability. The HVDC-MMC 401 Level link is connected to an AC network (Figure 11). Network 1 includes: AC overhead lines, AC breaker “BRK”, shunt compensator of 400 MVar and an equivalent Thevenin source with SCL equal to 20 GVA. Active power of 1,000 MW is transmitted from Grid 1 to 2. The outer control strategy considers a DC voltage/reactive power control on Station 2 and active/reactive power control on Station 1.
  • 5. HVDC-MMC link 50km Overhead line Network 1 Station 1Station 2 Grid2 Grid1 PCC1 Cshunt + + Figure 11: EMT test case In the following subsections, the impact of AC network parameters is elaborated. A. Impact of AC line length The impact of the line length parameter on the system stability is analyzed. AC overhead line length is varied ±10% from the initial 50km value. Figure 12 shows the EMT simulation results of the ( ) / ( )gridZ s Z s amplitude and angle. Line length has mainly an impact on the frequency resonance value. However, the frequency bandwidth that exceeds the amplitude of one (threshold that guaranties the stability) is the same. In addition, the phase margin ( ) / ( )gridZ s Z s∠ is close (and even slightly higher) to -1800 , which shows that resonances can occur in this specific frequency range. Indeed, in [18], time domain waveforms illustrate such resonances. 100 400 700 1000 1300 1600 1900 2200 2500 2800 10 -2 10 0 10 2 |Zgrid /Z|(ohm) Frequency (Hz) ACline=50km ACline=55km ACline=45km 100 400 700 1000 1300 1600 1900 2200 2500 2800 -180 -140 -100 -60 -20 20 60 100 140 ∠(Zgrid /Z)(degree) Frequency (Hz) ACline=45kmACline=55km ACline=50km Figure 12: Impact of AC line length B. Impact of shunt compensator Shunt capacitors have also an impact on the stability of the system. In Figure 13, the impact of the capacitor value on ( ) / ( )gridZ s Z s is depicted. Capacitor values of 800MVar, 400MVar, 100MVar and 0MVar are considered. It is noticed that when no shunt capacitor is included in the system, the system is stable since the phase margin ( ) / ( )gridZ s Z s∠ is lower than ±1800 . When the capacitor value increases, ( ) / ( )gridZ s Z s amplitude increases and ( ) / ( )gridZ s Z s∠ tends to -1800 which makes the system unstable. 100 400 700 1000 1300 1600 1900 2200 2500 2800 10 -2 10 0 10 2 |Zgrid /Z|(ohm) Frequency (Hz) 100MVar 0MVar 400MVar800MVar 100 400 700 1000 1300 1600 1900 2200 2500 2800 -180 -140 -100 -60 -20 20 60 100 140 ∠(Zgrid /Z)(degree) Frequency (Hz) 100MVar 0MVar400MVar 800MVar Figure 13: Impact of Cshunt C. Impact of short-circuit level Short-circuit level (SCL) of the Thevenin source (Grid 1) is varied in this subsection. Figure 14 shows the result of ( ) / ( )gridZ s Z s for three different values: 50, 20 and 5 GVA. Based on this result, it can be concluded that for high frequency resonances (>1 kHz), the short circuit level has a minor impact on the stability of the system. 100 400 700 1000 1300 1600 1900 2200 2500 2800 10 -2 10 0 10 2 |Zgrid /Z|(ohm) Frequency (Hz) SCL=20GVA SCL=5GVA SCL=50GVA 100 400 700 1000 1300 1600 1900 2200 2500 2800 -180 -140 -100 -60 -20 20 60 100 140 ∠(Zgrid /Z)(degree) Frequency (Hz) SCL=5GVA SCL=20GVA SCL=50GVA Figure 14: Impact of SCL D. Impact AC lines in parallel The impact of the number of AC lines connected in parallel is depicted in Figure 15: one line to three lines in parallel has been considered. It is noticed, that when the number of AC lines connected in parallel increases, the stability of the system increases. In fact, with one AC line is connected, the frequency range that leads to instability is as large as 100 Hz (1750 to 1850 Hz), however when three AC lines are in parallel, the frequency range of instabilities tend to zero.
  • 6. 100 400 700 1000 1300 1600 1900 2200 2500 2800 10 -2 10 0 10 2 |Zgrid /Z|(ohm) Frequency (Hz) 1 AC line 2 AC lines 3 AC lines 100 400 700 1000 1300 1600 1900 2200 2500 2800 -180 -140 -100 -60 -20 20 60 100 140 ∠(Zgrid /Z)(degree) Frequency (Hz) 3 AC lines 2 AC lines 1 AC line Figure 15: Impact of AC lines in parallel VII. CONCLUSIONS This paper presents the impact of MMC station parameters on the frequency response (Z and convh i ) of the converter on the AC side. It uses the EMT simulations approach and a detailed MMC-401 Level model to derive these results. Several parameters were considered to analyze their impact on the frequency response: MMC levels, CBA, circulating current, AC filter installation. Based on the presented results, it can be concluded that MMC levels and CBA have the main impact on the harmonic emissions. The circulating current impact seems negligible on the frequency response at the AC side. On the other hand, the paper showed that AC filters have an impact on the impedance Z(f). Parametric sensitivity studies have been also presented to shows the impact of the AC network on the stability of the system: AC line length, shunt capacitor and the number of AC lines in parallel play a role on the stability of the system. However, the short circuit level does not seem to affect such high frequency resonances. VIII. REFERENCES [1] A. Lesnicar, and R. Marquardt, “An Innovative Modular Multilevel Converter Topology Suitable for a Wide Power Range,” in Proc. IEEE Power Tech. Conference, vol. 3, Bologna, Jun. 2003. [2] C Buchhagen, C Rauscher, A Menze and J Jung, TenneT, “Borwin1 – First Experiences with harmonic interactions in converter dominated grids”, Int’l ETG Congress 2015, Nov. 17-18, 2015, Bonn, Germany, VDE Conference [3] J. Sun, "Impedance-Based Stability Criterion for Grid-Connected Inverters," in IEEE Transactions on Power Electronics, vol. 26, no. 11, pp. 3075-3078, Nov. 2011 [4] E. Möllerstedt and B. Bernhardsson, “Out of control because of harmonics—An analysis of the harmonic response of an inverter locomotive,” IEEE Control Syst. Mag., vol. 20, no. 4, pp. 70–81, Aug. 2000 [5] G. D. Irwin, A. Isaacs and D. Woodford, "Simulation requirements for analysis and mitigation of SSCI phenomena in wind farms," Transmission and Distribution Conference and Exposition (T&D), 2012 IEEE PES, Orlando, FL, 2012, pp. 1-4 [6] R. D. Middlebrook, “Input Filter Considerations in Design and Application of Switching Regulators,” IEEE Industry Applications Society Annual Meeting, October 11-14, 1976, Chicago [7] L. Harnefors, M. Bongiorno and S. Lundberg, "Input-Admittance Calculation and Shaping for Controlled Voltage-Source Converters," in IEEE Transactions on Industrial Electronics, vol. 54, no. 6, pp. 3323- 3334, Dec. 2007 [8] M. Cespedes and J. Sun, "Impedance Modeling and Analysis of Grid- Connected Voltage-Source Converters," in IEEE Transactions on Power Electronics, vol. 29, no. 3, pp. 1254-1261, March 2014 [9] G. Bergna Diaz, J. A. Suul and S. D'Arco, "Small-signal state-space modeling of modular multilevel converters for system stability analysis," Energy Conversion Congress and Exposition (ECCE), 2015 IEEE, Montreal, QC, 2015, pp. 5822-5829 [10] H. Saad, J. Mahseredjian, S. Dennetière, S. Nguefeu, “Interactions studies of HVDC–MMC link embedded in an AC grid,” Electric Power Systems Research, 11 March 2016 [11] A. Jamshidi Far and D. Jovcic, "Small-Signal Dynamic DQ Model of Modular Multilevel Converter for System Studies," in IEEE Transactions on Power Delivery, vol. 31, no. 1, pp. 191-199, Feb. 2016 [12] L. Harnefors, X. Wang, A. G. Yepes and F. Blaabjerg, "Passivity-Based Stability Assessment of Grid-Connected VSCs—An Overview," in IEEE Journal of Emerging and Selected Topics in Power Electronics, vol. 4, no. 1, pp. 116-125, March 2016 [13] H. Saad, S. Dennetière, J. Mahseredjian, et al "Modular Multilevel Converter Models for Electromagnetic Transients," IEEE Transactions on Power Delivery, vol. 29, no. 3, pp. 1481-1489, June 2014. [14] R. D. Middlebrook "Measurement of loop gain in feedback systems†." International Journal of Electronics Theoretical and Experimental 38.4 (1975): 485-512. [15] Q. Tu, and Z. Xu, “Impact of Sampling Frequency on Harmonic Distortion for Modular Multilevel Converter,” IEEE Trans. on Power Delivery, vol. 26, no. 1, pp. 298-306, Jan. 2011. [16] S. Rohner, S. Bernet, M. Hiller and R. Sommer, "Analysis and Simulation of a 6 kV, 6 MVA Modular Multilevel Converter," Industrial Electronics, 2009. IECON '09. 35th Annual Conference of IEEE, Porto, 2009, pp. 225-230 [17] H. Saad, J. Peralta, S. Dennetière, J. Mahseredjian, J. Jatskevich, J.A. Martinez et al.., "Dynamic Averaged and Simplified Models for MMC- Based HVDC Transmission Systems," Power Delivery, IEEE Transactions on , vol.28, no.3, pp.1723,1730, July 2013 [18] H. Saad; Y. Fillion; S. Deschanvres; Y. Vernay; S. Dennetiere, "On Resonances and Harmonics in HVDC-MMC Station Connected to AC grid," in IEEE Transactions on Power Delivery , vol.PP, no.99, pp.1-1 [19] C. Du, “VSC-HVDC for Industrial Power Systems,” Ph.D. Thesis, Chalmers Univ. of Technology, Göteborg, Sweden, 2007