Air cycle refrigeration systems use air as their refrigerant, compressing it and expanding it
to create heating and cooling capacity.Heat flows in direction of decreasing temperature
i.e. From high temperature to low temperature regions.
But the reverse process (i.e. heat transfer from low to high temperature) cannot occur by
itself (Claussius Definition of Second Law). This process requires a special device called
Refrigerator.
The Carnot cycle is used to convert the heat into the mechanical work
whereas the reverse Carnot cycle is used to absorb the heat from the
system and rejects to the surroundings to maintain the system cool.
Carnot Refrigeration cycle is a totally reversible cycle which consists of
two reversible isothermal processes and two isentropic processes.A
refrigerator or heat pump that operates on the reversed Carnot cycle is
called a Carnot refrigerator or a Carnot heat pump.
12/28/2021 2
Suhail Bhatia
The term heat pump is usually reserved for a device that can heat
a house in winter by using an electric motor that does work W to
take heat Qcold from the outside at low temperature and delivers
heat Qhot to the warmer inside of the house.
The operating principle of refrigerators, air conditioners, and heat
pumps is the same, and it is just the reverse of a heat engine.
In general, a heat pump is a device that transfers heat energy from
a heat source to a ā€œheat sink,ā€ but in this case, the transfer occurs in the
opposite direction of spontaneous heat transfer by absorbing heat from
a cold space and releasing it to a warmer one.
12/28/2021 3
Suhail Bhatia
12/28/2021
4 Suhail Bhatia
We know that;
COP of Refrigerator = Heat absorbed / work supplied
= Heat absorbed / (Heat rejected ā€“ Heat absorbed)
= T2 (Sb-Sa) / [T1(Sb-Sa) ā€“ T2(Sb-Sa)
= T2 / (T1-T2)
Therefore, COP of Carnot Refrigerator is :
where TH is the source temperature and TL is the sink
temperature where heat is rejected (i.e., lake, ambient air,
etc.).
12/28/2021
5 Suhail Bhatia
Brayton cycle is a thermodynamic cycle that describes the
operation of certain heat engines that have air or some other
gas as their working fluid.
A Brayton Refrigeration cycle that is driven in the reverse
direction is known as the reverse Brayton cycle. Its purpose is
to move heat from the colder to the hotter body rather than
produce work.
This cycle is also known as the gas refrigeration cycle or the
Bell Coleman cycle. This type of cycle is widely used in jet
aircraft for air conditioning systems using air from the engine
compressors. It is also widely used in the LNG industry.
12/28/2021
6 Suhail Bhatia
In compliance with the second law of thermodynamics, heat cannot
spontaneously flow from cold system to hot system without external
work being performed on the system. Heat can flow from colder to the
hotter body, but only when forced by external work. This is exactly
what refrigerators and heat pumps accomplish. These are driven
by electric motors requiring work from their surroundings to
operate. One of the possible cycles is a reverse Brayton cycle,
which is similar to the ordinary Brayton cycle, but it is driven in
reverse via net work input. 12/28/2021
7 Suhail Bhatia
Aircraft air refrigeration systems are required due to heat transfer
from many external and internal heat sources (like solar radiation
and avionics) which increase the cabin air temperature. With the
technological developments in high-speed passenger and jet
aircrafts, the air refrigeration systems are proving to be most
efficient, compact and simple.
Despite outside temperature is low refrigeration is required in inside
the occupant cabin because :
1. large internal heat is generated due to occupant and equipment
inside the cabin.
2.Heat generation due to skin friction caused by the fast moving
aircraft.
3. At high altitude, the outside pressure will be sub-automatic.
4.Solar radiation.
For low speed aircraft flying at low altitudes, cooling system may not
be required, however, for high speed aircraft flying at high altitude, a
cooling system is must. 12/28/2021
8 Suhail Bhatia
Various types of aircraft air refrigeration
systems used these days are:
ā€¢Simple air cooling system
ā€¢Simple air evaporative cooling system
ā€¢Boot strap air cooling system
ā€¢Boot strap air evaporative cooling system
ā€¢Reduced ambient air cooling system
ā€¢Regenerative air cooling system.
12/28/2021
9 Suhail Bhatia
Ambient air gets rammed before the main compressor.
The air required for refrigeration system is then bled off from
this compressor.
It is then sent to the heat exchanger where this high pressure
and high temperature air is cooled using ram air.
Air is further cooled in the cooling turbine due to its expansion.
The turbine work drives the cooling fan which draws ram air
through the heat exchanger.
The cooled air from turbine is then sent to the aircraft cabin.
12/28/2021
10 Suhail Bhatia
12/28/2021
11 Suhail Bhatia
12/28/2021
12 Suhail Bhatia
12/28/2021
13 Suhail Bhatia
Process 1-2= Isentropic ramming of air,
Process 2-3i= Isentropic compression in main compressor,
Process 2-3= Actual compression in main compressor,
Process 3-4= Constant pressure heat rejection in heat exchanger,
Process 4-5i= Isentropic expansion in cooling turbine,
Process 4-5= Actual expansion in cooling turbine,
Process 5-6= Constant pressure heat addition in cabin
12/28/2021
14 Suhail Bhatia
If a Q tonnes of refrigeration is the Cooling load in the cabin then the air
required for the refrigeration purpose,
Power required for the refrigerating system,
And C O.P. of the refrigerating system
The initial mass of evaporant (Me) required to be carried for the given
flight time is given by
where Qe = Heat to be removed in evaporation in kJ/min, and Hfg =
Latent heat of vaporisation of evaporant in kJ/kg
12/28/2021
15 Suhail Bhatia
Problems on aircraft cooling systems - Simple Refrigeration Cycle
Example
A simple air cooled system is used for an aeroplane having a load of 10
tones. The atmospheric pressure and temperature are 0.9 bar and 10Ā°C
respectively. The pressure increases to 1.013 bar due to ramming. The
temperature of the air is reduced by 50Ā°C in the heat exchanger. The
pressure in the cabin is 1.01 bar and the temperature of air leaving the
cabin is 25Ā°C. Determine :
1 Power required to take the load of cooling in the cabin; and
2. C.O.P. of the system.
Assume that all the expansions and compressions are isentropic. The
pressure of the compressed air is 3.5 bar.
Solution
Given :
Q=10TR; p1=0.9bar; T1=10Ā°C=10+273=283K;
p2=1.013bar; p5=p6=1.01bar;
T6=25Ā°C=25+273=298K; p3=3.5bar take Ī» = 1.4
12/28/2021
16 Suhail Bhatia
1. Power required taking the load of cooling in the cabin
First of all, let us find the mass of air (mama) required for the
refrigeration purpose. Since the compressions and expansions are
isentropic, therefore the various processes on the T-s diagram are as
shown in diagram below
Let
T2 = Temperature of air at the end of ramming or entering the main
compressor,
T3 = Temperature of air leaving the main compressor after isentropic
compression,
T4 = Temperature of air leaving the heat exchanger, and
T5 = Temperature of air leaving the cooling turbine
12/28/2021
17 Suhail Bhatia
12/28/2021
18 Suhail Bhatia
12/28/2021
19 Suhail Bhatia
It is similar to the simple cooling system except that the addition of an
evaporator between the beat exchanger and cooling turbine. The
evaporator provides an additional cooling effect through evaporation of
a refrigerant such as water. At high altitudes, the evaporative cooling
may be obtained by using alcohol or ammonia. The water, alcohol and
ammonia have different refrigerating effects at different altitudes. At
20000 metres height for example, water boils at 400 C, alcohol at 90 C
and ammonia at - 70Ā° C.
The T-s diagram for simple air cycle evaporative cooling system is
shown below:
12/28/2021
20 Suhail Bhatia
If a Q tonnes of refrigeration is the Cooling load in the cabin then the air
required for the refrigeration purpose,
Power required for the refrigerating system,
And C O.P. of the refrigerating system
The initial mass of evaporant (Me) required to be carried for the given
flight time is given by
where Qe = Heat to be removed in evaporation in kJ/min, and Hfg =
Latent heat of vaporisation of evaporant in kJ/kg
12/28/2021
21 Suhail Bhatia
Problem on simple air evaporative cooling system
Example
Simple evaporative air refrigeration system is used for an aeroplane to take 20
tones of refrigeration load. The ambient air conditions are 20Ā°C and 0.9 bar.
The ambient air is rammed isentropically to a pressure of 1bar. The air leaving
the main compressor at pressure 3.5 bar is first cooled in the heat exchanger
having effectiveness of 0.6 and then in the evaporator where its temperature is
reduced by 5Ā°C. The air from the evaporator is passed through the cooling
turbine and then it is supplied to the cabin which is to be maintained at a
temperature of 25Ā°C and at a pressure of 1.05 bar. If the internal efficiency of
the compressor is 80% and that of cooling turbine is 75% determine:
1. Mass of air bled off the main compressor;
2. Power required for the refrigerating system; and
3. C.O.P. of the refrigeration system.
Solution
Given:
Q=20TR; T1=20Ā°C=20+273=293K; p1=0.9bar; p2=1bar;
p3=pā€²3=3.5bar; Ī·H=0.6;
T6=25Ā°C=25+273=298K; p6=1.05bar; Ī·C=80%= 0.8 ;
Ī·T=75%=0.75
12/28/2021
22 Suhail Bhatia
The T-s diagram for the simple evaporative air refrigeration system with
the given conditions is shown below:
12/28/2021
23 Suhail Bhatia
12/28/2021
24 Suhail Bhatia
12/28/2021
25 Suhail Bhatia
12/28/2021
26 Suhail Bhatia
12/28/2021
27 Suhail Bhatia
This boot strap air cooling system has two heat exchangers instead of
one, and a cooling turbine drives a secondary compressor instead of
cooling fan. The air bled from the main compressor is first cooled by the
ram air in the first heat exchanger. This cooled air, after compression in
the secondary compressor, is led to the second heat exchanger where it
is again cooled by the ram air before passing to the cooling turbine. This
type of cooling system is mostly used in transport type aircraft.
The T-s diagram for a boot-strap air cycle cooling system:
12/28/2021
28 Suhail Bhatia
The various processes are as follows:
The process 1-2' represents the isentropic ramming of ambient air from
pressure P1, and temperature T1 to pressure P2 and temperature T2.
The process 1-2' represents the actual ramming process because of
internal friction due to irreversibilities.
The process 2'-3 represents the isentropic compression of air in the
main compressor and the process 2'-3' represents the actual
compression of air because of internal friction due to irreversibilities.
The process 3'-4 represents the cooling by ram air in the first heat
exchanger. The pressure drop in the heat exchanger is neglected.
The process 4.5 represents compression of cooled air, from first heat
exchanger, in the secondary compressor. The process 4-5' represents
the actual compression process because of internal friction due to
irreversibilities.
The process 5'-6 represents the cooling by ram air in the second heat
exchanger. The pressure drop in heat exchanger in neglected.
The process 6-7 represents isentropic expansion of the cooled air in
the cooling turbine upto the cabin pressure. The process 6-7'
represents actual expansion of the cooled air in the cooling turbine.
The process 7'-8 represents the heating of air upto the cabin
12/28/2021
29 Suhail Bhatia
If Q tonnes of refrigeration is the cooling load in the cabin, then the
quantity of air required for the refrigeration purpose will be
Power required for the refrigerating system,
and C.O.P. of the refrigerating system
12/28/2021
30 Suhail Bhatia
Problem on boot strap cooling system
Example
A boot-strap cooling system of 10 TR capacity is used in an aeroplane. The
ambient air temperature and pressure are 20Ā°C and 0.85 bar respectively.
The pressure of air increases from 0.85 bar to 1 bar due to ramming action
of air. "The pressure of air discharged from the main compressor is 3 bar.
The discharge pressure of air from the auxiliary compressor is 4 bar.
The isentropic efficiency of each of the compressor is 80%, while that of
turbine is 85%. 50% of the enthalpy of air discharged from the main
compressor is removed in the first heat exchanger and 30% of the enthalpy
of air discharged from the auxiliary compressor is removed in the second
heat exchanger using rammed air.
Assuming ramming action to be isentropic, the required cabin pressure of
0.9 bar and temperature of the air leaving the cabin not more than 20Ā° C,
find :
1. the power required to operate the system, and
2. the C.O.P. of the system.
Draw the schematic and temperature -entropy diagram of the system.
Take Ī³=1.4 and cp=1 kJ/kg K.
12/28/2021
31 Suhail Bhatia
20Ā°C
12/28/2021
32 Suhail Bhatia
12/28/2021
33 Suhail Bhatia
12/28/2021
34 Suhail Bhatia
12/28/2021
35 Suhail Bhatia
12/28/2021
36 Suhail Bhatia
A boot-strap air cycle evaporative cooling system is shown above. It is
similar to the boot-strap air cycle cooling system except that the addition
of an evaporator between the second heat exchanger and the cooling
turbine. The T-s diagram for a boot-strap air evaporative cooling system:
12/28/2021
37 Suhail Bhatia
The various processes of this cycle are same as a simple boot-strap
system except the process 5''-6 which represents cooling in the
evaporator using any suitable evaporant.
If Q tonnes of refrigeration is the cooling load in the cabin, then the
quantity of air required for the refrigeration purpose will be:
Power required for the refrigeration system is given by:
and C.O.P. of the refrigerating system
Note: Since the temperature of air leaving the cooling turbine in boot-
strap evaporative system is lower than the simple boot-strap system,
therefore mass of air (ma) per tonne of refrigeration will be less in boot-
strap evaporative system.
12/28/2021
38 Suhail Bhatia
12/28/2021
39 Suhail Bhatia
Problem on boot strap evaporative cooling system
Example
The following data refer to a boot strap air cycle evaporative refrigeration system
used for an aeroplane to take 20 tonnes of refrigeration load:
Ambient air temperature = 15Ā°C
Ambient air pressure = 0.8bar
Mach number of the flight = 1.2
Ram efficiency = 90
Pressure of air bled off the main compressor = 4bar
Pressure of air in the secondary compressor = 5bar
Isentropic efficiency of the main compressor = 90
Isentropic efficiency of the secondary compressor = 80
Isentropic efficiency of the cooling turbine = 80
Temperature of air leaving the first heat exchanger =?
Temperature of air leaving the second heat exchange = ?
Temperature of air leaving the evaporator = 100Ā°C
Cabin temperature = 25Ā°C
Cabin pressure = 1bar
Find:
1. Mass of air required to take the cabin load,
2. Power required for the refrigeration system, and
3. C.O.P. of the system. 12/28/2021
40 Suhail Bhatia
Solution
Given:
Q=20 TR ; T1=15Ā°C=15+237=288K; p1=0.8bar; M=1.2; Ī·R=90
p3=pā€²3=p4=4bar; p5=pā€²5=p5ā€=p6=bar; Ī·C1=90; Ī·C2=80
T6=100Ā°C=100+273=373K; T8=25Ā°C=25+273=298K; p8=p7=p7ā€=1bar
The T-s diagram for the boot-strap air cycle evaporative refrigeration system,
with the given conditions, is shown in the figure below:
12/28/2021
41 Suhail Bhatia
12/28/2021
42 Suhail Bhatia
12/28/2021
43 Suhail Bhatia
12/28/2021
44 Suhail Bhatia
12/28/2021
45 Suhail Bhatia
The regenerative air cooling-system is a modification of a simple air
cooling system with the addition of a regenerative heat exchanger. The
high pressure and high temperature air from the main compressor is first
cooled by the ram air in the heat exchanger. This air is further cooled in
the regenerative heat exchanger with a portion of the air bled after
expansion in the cooling turbine.
This type of cooling system is used for supersonic aircrafts and rockets.
12/28/2021
46 Suhail Bhatia
The T-s diagram for the regenerative air cooling system is shown
above. The various processes are as follows:
1. The process 1-2 represents' isentropic ramming of air and
process 1-2' represents actual ramming of air because of internal
friction due to irreversibilities.
2. The process 2'-3 represents isentropic compression of air in the
main compressor and the process 2'-3' represents actual
compression of air because of internal friction due to
irreversibilities.
3. The process 3'-4 represents cooling of compressed air by ram air
in the heat exchanger.
4. The process 4-5 represents cooling of air in the regenerative heat
exchanger.
5. The process 5-6 represents isentropic expansion of air in the
cooling turbine up to the cabin pressure and the process 5-6'
represents actual expansion of air in the cooling turbine.
6. The process 6'-7 represents heating of air upto the cabin
temperature T7.
12/28/2021
47 Suhail Bhatia
If Q tonnes of refrigeration is the cooling load in the cabin, then the
quantity of air required for the refrigeration purpose will be
For the energy balance of regenerative heat exchanger, we have
where T8 = Temperature of air leaving to atmosphere from the
regenerative heat exchanger.
Power required for the refrigeration system:
and C.O.P. of the refrigerating system:
12/28/2021
48 Suhail Bhatia
Problem on regenerative cooling system
Example
A regenerative air cooling system is used for an airplane to take 20 tonnes of
refrigeration load. The ambient air at pressure 0.8 bar and temperature 10Ā°C is
rammed isentropically till the pressure rises to 1.2 bar. The air bled off the main
compressor at 4.5 bar is, cooled by the ram air in the heat exchanger whose
effectiveness is 60%. The air from the heat exchanger is further cooled to 60Ā°C in
the regenerative heat exchanger with a portion of the air bled after expansion in the
cooling turbine. The cabin is to be maintained at a temperature of 25Ā°C and a
pressure of I bar. If the isentropic efficiencies of the compressor and turbine are
90% and 80% respectively, find:
1. Mass of the air bled from cooling turbine to be used for regenerative cooling;
2. Power required for maintaining the cabin at the required condition; and
3. C. O. P. of the system.
Assume the temperature of air leaving to atmosphere from the regenerative heat
exchanger as 1 00Ā° C.
Solution
Given :
Q=20TR; p1=0.8bar; T1=10Ā°C=10+273=283K; p2=1.2bar;
p3=pāˆ’4=p5=4.5bar; Ī·H=60%=0.6; T5=60Ā°C=60+273=333K;
T7=25Ā°C=25+273=298K; p7=p6=pā€²6=1bar; Ī·c=0.9;
Ī·T=80%=0.8;=0.8;
12/28/2021
49 Suhail Bhatia
The T-s diagram for the regenerative air cooling system with the given
conditions is
12/28/2021
50 Suhail Bhatia
12/28/2021
51 Suhail Bhatia
12/28/2021
52 Suhail Bhatia
12/28/2021
53 Suhail Bhatia
12/28/2021
54 Suhail Bhatia
The reduced ambient air cooling system includes two cooling turbines
and one heat exchanger. The air reduced for the refrigeration initially in
system is bled off from the main compressor.
This high pressure and high temperature air is cooled the heat
exchanger. The air for cooling is taken from the cooling turbine which
lower the high temperature of rammed air.
The cooled air from the heat exchanger is passed through the second
cooling turbine from where the air is supplied to the cabin.
The work of the cooling turbine is used to drive the cooling fan (through
reduction gears) which draws cooling air from the heat exchanger.
The reduced ambient air cooling system is used for very high speed
aircrafts.
12/28/2021
55 Suhail Bhatia
The T-s diagram for the reduced ambient air cycle cooling system is:
12/28/2021
56 Suhail Bhatia
The various processes are as follows:
The process 1-2 represents isentropic ramming of air and the
process 1-2' represents actual ramming of air because of internal
friction due to irreversibilities.
The process 2'-3 represents isentropic compression in the main
compressor and the process 2'-3' represents actual compression
of air, because of internal friction due to irreversibilities.
The process 3'-4 represents cooling of compressed air by ram air
which after passing through the first cooling turbine is led to the
heat exchanger. The pressure drop in the heat exchanger is
neglected.
The process 4-5 represents isentropic expansion of air in the
second cooling turbine upto the cabin pressure. The actual
expansion of air in the second cooling turbine is represented by the
curve 4-5'.
The process 5'-6 represents the heating of air upto the cabin
12/28/2021
57 Suhail Bhatia
If Q tonnes of refrigeration is the cooling load in the cabin, then the
quantity of air required for the refrigeration purpose will be:
Power required for the refrigeration system is given by
and C.O.P. of the system
12/28/2021
58 Suhail Bhatia
Problems on reduced ambient cooling system
Example
The reduced ambient air refrigeration system used for an aircraft consists of two cooling
turbines, one heat exchanger and one air cooling fan. The speed of aircraft is 1500
km/h. The ambient air conditions are 0.8 bar and 10Ā° C. The ram efficiency may be
taken as 90%. The rammed air used for cooling is expanded in the first cooling turbine
and leaves it at a pressure of 0.8 bar.
The air bled from the main compressor at 6 bar is cooled in the heat exchanger and
leaves it at 100Ā° C: The cabin is to be maintained at 20Ā° C and 1 bar. The pressure loss
between the second cooling turbine and cabin is 0.1 bar. If the isentropic efficiency for
the main compressor and both of the cooling turbines are 85% and 80% respectively,
find:
1. mass flow rate of air supplied to cabin to take a cabin load of 10 tonnes of
refrigeration ;
2. quantity of air passing through the heat exchanger if the temperature rise of ram air is
limited to 80 K ;
3. power used to drive the cooling fan; and
4. C.O.P. of the system.
Solution
Given : V=1500 km/h=417m/s ;p2=0.6bar;
T1=10Ā°C=10+273=283K;
Ī·R=90%=0.9; p3=p4=6bar; T4=100Ā°C=100+273=373K;
T6=20Ā°C=20+273=293K; p6=1bar; Ī·C=85%=0.85;
12/28/2021
59 Suhail Bhatia
The T-s diagram for the reduced ambient air refrigeration system with
the given conditions is below:
12/28/2021
60 Suhail Bhatia
Let
Tā€²2T2ā€²=Stagnation temperature of ambient air entering the main compressor,
p2p2=Pressure of air at the end of isentropic ramming, and
pā€²2p2ā€²= Stagnation pressure of air entering the main compressor.
12/28/2021
61 Suhail Bhatia
12/28/2021
62 Suhail Bhatia
T-s diagram of first cooling tube
12/28/2021
63 Suhail Bhatia
12/28/2021
64 Suhail Bhatia
12/28/2021
65 Suhail Bhatia
Comparison of Various Air Cooling Systems used for Aircraft
Dry Air Rated Temperature (DART): The concept of Dry Air Rated
Temperature is used to compare different aircraft refrigeration cycles.
Dry Air Rated Temperature is defined as the temperature of the air at the
exit of the cooling turbine in the absence of moisture condensation. For
condensation not to occur during expansion in the turbine, the dew
point temperature and hence moisture content of the air should be very
low, i.e., the air should be very dry. The aircraft refrigeration systems are
rated based on the mass flow rate of air at the design DART. The
cooling capacity is then given by:
where, m is the mass flow rate of air, T DART and Ti are the dry air
rated temperature and cabin temperature, respectively.
12/28/2021
66 Suhail Bhatia
12/28/2021
67 Suhail Bhatia
The performance curves for the various air cooling systems used for
aircrafts are shown above. These curves show the dry air rated turbine
discharge temperature (DART) against the Mach number. From the figure,
we see that the simple air cooling system gives maximum cooling effect on
the ground surface and decreases as the speed of aircraft increases. The
boot strap system on the other hand, requires the air plane to be in flight so
that the ram air can be used for cooling in the heat exchangers.
One method of overcoming this drawback of boot strap system is to use
part of work derived from turbine to drive a fan which pulls air over the
secondary heat exchanger, thus combining the features of a simple and
boot strap system .As the speed of aircraft increases, the temperature of
ram cooling air rises and the ram air becomes less effective as a coolant in
the heat exchanger. In such cases, a suitable evaporant is used with the
ram air so that the cabin temperature does not rise.
For high speed aircrafts, the boot strap evaporative or regenerative systems
are used because they give lower turbine discharge temperature than the
simple cooling system. In some cases, aeroplanes carry an auxiliary gas-
,turbine for cabin pressurisation and, air conditioning. From the chart, we
see that the turbine. Discharge temperature of the air is variable. Therefore,
in order to maintain the content temperature of simply air to the cabin, it
12/28/2021
68 Suhail Bhatia
Summary:
i. DART increases monotonically with Mach number for all
the systems except the reduced ambient system.
ii. The simple system is adequate at low Mach numbers.
iii. At high Mach numbers either bootstrap system or
regenerative system should be used.
iv. Reduced ambient temperature system is best suited for
very high Mach number, supersonic aircrafts.
12/28/2021
69 Suhail Bhatia
12/28/2021
70 Suhail Bhatia

More Related Content

What's hot

Vapour compression refrigeration system
Vapour compression refrigeration systemVapour compression refrigeration system
Vapour compression refrigeration systemnaphis ahamad
Ā 
Chapter 5 Fundamentals of Refrigeration
Chapter 5  Fundamentals of RefrigerationChapter 5  Fundamentals of Refrigeration
Chapter 5 Fundamentals of RefrigerationANIKET SURYAWANSHI
Ā 
Basics of Refrigerartion
Basics of RefrigerartionBasics of Refrigerartion
Basics of RefrigerartionKonal Singh
Ā 
Refrigeration and Air conditioning
Refrigeration and Air conditioningRefrigeration and Air conditioning
Refrigeration and Air conditioningSLA1987
Ā 
Vapour Absorption Refrigeration System
Vapour Absorption Refrigeration SystemVapour Absorption Refrigeration System
Vapour Absorption Refrigeration SystemDeep Dalsania
Ā 
Simple Vapour Compression Refrigeration System
Simple Vapour Compression Refrigeration SystemSimple Vapour Compression Refrigeration System
Simple Vapour Compression Refrigeration SystemDarshan Panchal
Ā 
vapour compression refrigeration system
vapour compression refrigeration systemvapour compression refrigeration system
vapour compression refrigeration systemAbhishek Choksi
Ā 
refrigerator and Air Condition
refrigerator and Air Conditionrefrigerator and Air Condition
refrigerator and Air ConditionShowhanur Rahman
Ā 
Introduction to refrigeration systems
Introduction to refrigeration systemsIntroduction to refrigeration systems
Introduction to refrigeration systemsVishu Sharma
Ā 
Aircraft refrigeration system
Aircraft refrigeration systemAircraft refrigeration system
Aircraft refrigeration systemAnkur Sachdeva
Ā 
Applications of Refrigeration and Air Conditioning & Refrigerants
Applications of Refrigeration and Air Conditioning & RefrigerantsApplications of Refrigeration and Air Conditioning & Refrigerants
Applications of Refrigeration and Air Conditioning & RefrigerantsNITIN AHER
Ā 
Aircraft refrigeration system (air cooling system)
Aircraft refrigeration system (air cooling system)Aircraft refrigeration system (air cooling system)
Aircraft refrigeration system (air cooling system)Ripuranjan Singh
Ā 
Application of refrigeration and air conditioning
Application of refrigeration and air conditioningApplication of refrigeration and air conditioning
Application of refrigeration and air conditioningRavindra Kolhe
Ā 
Effect of compressor suction pressure in Vapor Compression Refrigeration Syst...
Effect of compressor suction pressure in Vapor Compression Refrigeration Syst...Effect of compressor suction pressure in Vapor Compression Refrigeration Syst...
Effect of compressor suction pressure in Vapor Compression Refrigeration Syst...Sharath Kumar
Ā 
Application of refrigeration and air conditioning PWI
Application of refrigeration and air conditioning PWIApplication of refrigeration and air conditioning PWI
Application of refrigeration and air conditioning PWIPurushottam Ingle
Ā 
Introduction to Refrigeration and Air Conditioning
Introduction to Refrigeration and Air ConditioningIntroduction to Refrigeration and Air Conditioning
Introduction to Refrigeration and Air ConditioningMechanicalstudents.com
Ā 
Refrigeration vtu atd notes pdf download
Refrigeration vtu atd notes pdf downloadRefrigeration vtu atd notes pdf download
Refrigeration vtu atd notes pdf downloadkiran555555
Ā 
Economiser & air preheater
Economiser & air preheaterEconomiser & air preheater
Economiser & air preheaterdishti7
Ā 

What's hot (20)

Vapour compression refrigeration system
Vapour compression refrigeration systemVapour compression refrigeration system
Vapour compression refrigeration system
Ā 
Refrigeration systems
Refrigeration systemsRefrigeration systems
Refrigeration systems
Ā 
Chapter 5 Fundamentals of Refrigeration
Chapter 5  Fundamentals of RefrigerationChapter 5  Fundamentals of Refrigeration
Chapter 5 Fundamentals of Refrigeration
Ā 
Basics of Refrigerartion
Basics of RefrigerartionBasics of Refrigerartion
Basics of Refrigerartion
Ā 
Refrigeration and Air conditioning
Refrigeration and Air conditioningRefrigeration and Air conditioning
Refrigeration and Air conditioning
Ā 
Vapour Absorption Refrigeration System
Vapour Absorption Refrigeration SystemVapour Absorption Refrigeration System
Vapour Absorption Refrigeration System
Ā 
Simple Vapour Compression Refrigeration System
Simple Vapour Compression Refrigeration SystemSimple Vapour Compression Refrigeration System
Simple Vapour Compression Refrigeration System
Ā 
vapour compression refrigeration system
vapour compression refrigeration systemvapour compression refrigeration system
vapour compression refrigeration system
Ā 
refrigerator and Air Condition
refrigerator and Air Conditionrefrigerator and Air Condition
refrigerator and Air Condition
Ā 
Introduction to refrigeration systems
Introduction to refrigeration systemsIntroduction to refrigeration systems
Introduction to refrigeration systems
Ā 
Aircraft refrigeration system
Aircraft refrigeration systemAircraft refrigeration system
Aircraft refrigeration system
Ā 
Applications of Refrigeration and Air Conditioning & Refrigerants
Applications of Refrigeration and Air Conditioning & RefrigerantsApplications of Refrigeration and Air Conditioning & Refrigerants
Applications of Refrigeration and Air Conditioning & Refrigerants
Ā 
Aircraft refrigeration system (air cooling system)
Aircraft refrigeration system (air cooling system)Aircraft refrigeration system (air cooling system)
Aircraft refrigeration system (air cooling system)
Ā 
Application of refrigeration and air conditioning
Application of refrigeration and air conditioningApplication of refrigeration and air conditioning
Application of refrigeration and air conditioning
Ā 
Effect of compressor suction pressure in Vapor Compression Refrigeration Syst...
Effect of compressor suction pressure in Vapor Compression Refrigeration Syst...Effect of compressor suction pressure in Vapor Compression Refrigeration Syst...
Effect of compressor suction pressure in Vapor Compression Refrigeration Syst...
Ā 
Application of refrigeration and air conditioning PWI
Application of refrigeration and air conditioning PWIApplication of refrigeration and air conditioning PWI
Application of refrigeration and air conditioning PWI
Ā 
Referigeration
ReferigerationReferigeration
Referigeration
Ā 
Introduction to Refrigeration and Air Conditioning
Introduction to Refrigeration and Air ConditioningIntroduction to Refrigeration and Air Conditioning
Introduction to Refrigeration and Air Conditioning
Ā 
Refrigeration vtu atd notes pdf download
Refrigeration vtu atd notes pdf downloadRefrigeration vtu atd notes pdf download
Refrigeration vtu atd notes pdf download
Ā 
Economiser & air preheater
Economiser & air preheaterEconomiser & air preheater
Economiser & air preheater
Ā 

Similar to Air refrigeration systems

Refrigeration Engineering Lecture notes
Refrigeration Engineering Lecture notesRefrigeration Engineering Lecture notes
Refrigeration Engineering Lecture notesFellowBuddy.com
Ā 
Refrigeration Engineering Lecture Notes
Refrigeration Engineering Lecture NotesRefrigeration Engineering Lecture Notes
Refrigeration Engineering Lecture NotesFellowBuddy.com
Ā 
Refrigeration and air conditioning
Refrigeration and air conditioningRefrigeration and air conditioning
Refrigeration and air conditioningEagle .
Ā 
Refrigeration and Air Conditioning
Refrigeration and Air ConditioningRefrigeration and Air Conditioning
Refrigeration and Air Conditioningdineshucer
Ā 
Chapter_11.ppt RAC REFRIGERATOR.ppt
Chapter_11.ppt RAC REFRIGERATOR.pptChapter_11.ppt RAC REFRIGERATOR.ppt
Chapter_11.ppt RAC REFRIGERATOR.pptGeoffreyMichael1
Ā 
Boot-strap air cooling system
Boot-strap air cooling systemBoot-strap air cooling system
Boot-strap air cooling systemAjeetSaini3
Ā 
5022-RAC MODULE-1.pdf
5022-RAC MODULE-1.pdf5022-RAC MODULE-1.pdf
5022-RAC MODULE-1.pdfAthulUdayan2
Ā 
Introduction to Air Refrigeration for 3/4 B.Tech
Introduction to Air Refrigeration for 3/4 B.TechIntroduction to Air Refrigeration for 3/4 B.Tech
Introduction to Air Refrigeration for 3/4 B.Techmaheshchindanu5783
Ā 
Basics of refrigeration_lect_1
Basics of refrigeration_lect_1Basics of refrigeration_lect_1
Basics of refrigeration_lect_127273737
Ā 
Refrigeration system
Refrigeration system Refrigeration system
Refrigeration system Sagar Joshi
Ā 
ENERGY AUDIT presentationin power system .pptx
ENERGY AUDIT presentationin power system .pptxENERGY AUDIT presentationin power system .pptx
ENERGY AUDIT presentationin power system .pptxReshevSharma
Ā 
Welcome to International Journal of Engineering Research and Development (IJERD)
Welcome to International Journal of Engineering Research and Development (IJERD)Welcome to International Journal of Engineering Research and Development (IJERD)
Welcome to International Journal of Engineering Research and Development (IJERD)IJERD Editor
Ā 
Cooling of mine air by chilled water system (final)
Cooling of mine air by chilled water system (final)Cooling of mine air by chilled water system (final)
Cooling of mine air by chilled water system (final)Safdar Ali
Ā 
Refrigeration and air conditioning (full note)
Refrigeration and air conditioning (full note)Refrigeration and air conditioning (full note)
Refrigeration and air conditioning (full note)shone john
Ā 
Air-Cycle refrigeration.pdf
Air-Cycle refrigeration.pdfAir-Cycle refrigeration.pdf
Air-Cycle refrigeration.pdfEssaYimer
Ā 
Hvac systems
Hvac systemsHvac systems
Hvac systemsHusain Baqer
Ā 
DOC-20231017-WA0003..pptx
DOC-20231017-WA0003..pptxDOC-20231017-WA0003..pptx
DOC-20231017-WA0003..pptxKarthik029CSK
Ā 

Similar to Air refrigeration systems (20)

Refrigeration Engineering Lecture notes
Refrigeration Engineering Lecture notesRefrigeration Engineering Lecture notes
Refrigeration Engineering Lecture notes
Ā 
Refrigeration Engineering Lecture Notes
Refrigeration Engineering Lecture NotesRefrigeration Engineering Lecture Notes
Refrigeration Engineering Lecture Notes
Ā 
CH-3.pptx
CH-3.pptxCH-3.pptx
CH-3.pptx
Ā 
Refrigeration and air conditioning
Refrigeration and air conditioningRefrigeration and air conditioning
Refrigeration and air conditioning
Ā 
Refrigeration and Air Conditioning
Refrigeration and Air ConditioningRefrigeration and Air Conditioning
Refrigeration and Air Conditioning
Ā 
Chapter_11.ppt RAC REFRIGERATOR.ppt
Chapter_11.ppt RAC REFRIGERATOR.pptChapter_11.ppt RAC REFRIGERATOR.ppt
Chapter_11.ppt RAC REFRIGERATOR.ppt
Ā 
refrigeration.pptx
refrigeration.pptxrefrigeration.pptx
refrigeration.pptx
Ā 
Boot-strap air cooling system
Boot-strap air cooling systemBoot-strap air cooling system
Boot-strap air cooling system
Ā 
5022-RAC MODULE-1.pdf
5022-RAC MODULE-1.pdf5022-RAC MODULE-1.pdf
5022-RAC MODULE-1.pdf
Ā 
Refrigeration Senator Libya
Refrigeration  Senator LibyaRefrigeration  Senator Libya
Refrigeration Senator Libya
Ā 
Introduction to Air Refrigeration for 3/4 B.Tech
Introduction to Air Refrigeration for 3/4 B.TechIntroduction to Air Refrigeration for 3/4 B.Tech
Introduction to Air Refrigeration for 3/4 B.Tech
Ā 
Basics of refrigeration_lect_1
Basics of refrigeration_lect_1Basics of refrigeration_lect_1
Basics of refrigeration_lect_1
Ā 
Refrigeration system
Refrigeration system Refrigeration system
Refrigeration system
Ā 
ENERGY AUDIT presentationin power system .pptx
ENERGY AUDIT presentationin power system .pptxENERGY AUDIT presentationin power system .pptx
ENERGY AUDIT presentationin power system .pptx
Ā 
Welcome to International Journal of Engineering Research and Development (IJERD)
Welcome to International Journal of Engineering Research and Development (IJERD)Welcome to International Journal of Engineering Research and Development (IJERD)
Welcome to International Journal of Engineering Research and Development (IJERD)
Ā 
Cooling of mine air by chilled water system (final)
Cooling of mine air by chilled water system (final)Cooling of mine air by chilled water system (final)
Cooling of mine air by chilled water system (final)
Ā 
Refrigeration and air conditioning (full note)
Refrigeration and air conditioning (full note)Refrigeration and air conditioning (full note)
Refrigeration and air conditioning (full note)
Ā 
Air-Cycle refrigeration.pdf
Air-Cycle refrigeration.pdfAir-Cycle refrigeration.pdf
Air-Cycle refrigeration.pdf
Ā 
Hvac systems
Hvac systemsHvac systems
Hvac systems
Ā 
DOC-20231017-WA0003..pptx
DOC-20231017-WA0003..pptxDOC-20231017-WA0003..pptx
DOC-20231017-WA0003..pptx
Ā 

Recently uploaded

Internship report on mechanical engineering
Internship report on mechanical engineeringInternship report on mechanical engineering
Internship report on mechanical engineeringmalavadedarshan25
Ā 
Work Experience-Dalton Park.pptxfvvvvvvv
Work Experience-Dalton Park.pptxfvvvvvvvWork Experience-Dalton Park.pptxfvvvvvvv
Work Experience-Dalton Park.pptxfvvvvvvvLewisJB
Ā 
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...srsj9000
Ā 
Call Girls Narol 7397865700 Independent Call Girls
Call Girls Narol 7397865700 Independent Call GirlsCall Girls Narol 7397865700 Independent Call Girls
Call Girls Narol 7397865700 Independent Call Girlsssuser7cb4ff
Ā 
What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxWhat are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxwendy cai
Ā 
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdfCCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdfAsst.prof M.Gokilavani
Ā 
pipeline in computer architecture design
pipeline in computer architecture  designpipeline in computer architecture  design
pipeline in computer architecture designssuser87fa0c1
Ā 
Electronically Controlled suspensions system .pdf
Electronically Controlled suspensions system .pdfElectronically Controlled suspensions system .pdf
Electronically Controlled suspensions system .pdfme23b1001
Ā 
Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024hassan khalil
Ā 
Artificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptxArtificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptxbritheesh05
Ā 
Effects of rheological properties on mixing
Effects of rheological properties on mixingEffects of rheological properties on mixing
Effects of rheological properties on mixingviprabot1
Ā 
Gurgaon āœ”ļø9711147426āœØCall In girls Gurgaon Sector 51 escort service
Gurgaon āœ”ļø9711147426āœØCall In girls Gurgaon Sector 51 escort serviceGurgaon āœ”ļø9711147426āœØCall In girls Gurgaon Sector 51 escort service
Gurgaon āœ”ļø9711147426āœØCall In girls Gurgaon Sector 51 escort servicejennyeacort
Ā 
Concrete Mix Design - IS 10262-2019 - .pptx
Concrete Mix Design - IS 10262-2019 - .pptxConcrete Mix Design - IS 10262-2019 - .pptx
Concrete Mix Design - IS 10262-2019 - .pptxKartikeyaDwivedi3
Ā 
UNIT III ANALOG ELECTRONICS (BASIC ELECTRONICS)
UNIT III ANALOG ELECTRONICS (BASIC ELECTRONICS)UNIT III ANALOG ELECTRONICS (BASIC ELECTRONICS)
UNIT III ANALOG ELECTRONICS (BASIC ELECTRONICS)Dr SOUNDIRARAJ N
Ā 
Call Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile serviceCall Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile servicerehmti665
Ā 
Application of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptxApplication of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptx959SahilShah
Ā 
main PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidmain PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidNikhilNagaraju
Ā 

Recently uploaded (20)

Internship report on mechanical engineering
Internship report on mechanical engineeringInternship report on mechanical engineering
Internship report on mechanical engineering
Ā 
Work Experience-Dalton Park.pptxfvvvvvvv
Work Experience-Dalton Park.pptxfvvvvvvvWork Experience-Dalton Park.pptxfvvvvvvv
Work Experience-Dalton Park.pptxfvvvvvvv
Ā 
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Ā 
Call Girls Narol 7397865700 Independent Call Girls
Call Girls Narol 7397865700 Independent Call GirlsCall Girls Narol 7397865700 Independent Call Girls
Call Girls Narol 7397865700 Independent Call Girls
Ā 
What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxWhat are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptx
Ā 
POWER SYSTEMS-1 Complete notes examples
POWER SYSTEMS-1 Complete notes  examplesPOWER SYSTEMS-1 Complete notes  examples
POWER SYSTEMS-1 Complete notes examples
Ā 
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdfCCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
Ā 
pipeline in computer architecture design
pipeline in computer architecture  designpipeline in computer architecture  design
pipeline in computer architecture design
Ā 
Electronically Controlled suspensions system .pdf
Electronically Controlled suspensions system .pdfElectronically Controlled suspensions system .pdf
Electronically Controlled suspensions system .pdf
Ā 
young call girls in Rajiv ChowkšŸ” 9953056974 šŸ” Delhi escort Service
young call girls in Rajiv ChowkšŸ” 9953056974 šŸ” Delhi escort Serviceyoung call girls in Rajiv ChowkšŸ” 9953056974 šŸ” Delhi escort Service
young call girls in Rajiv ChowkšŸ” 9953056974 šŸ” Delhi escort Service
Ā 
Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024
Ā 
Artificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptxArtificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptx
Ā 
Effects of rheological properties on mixing
Effects of rheological properties on mixingEffects of rheological properties on mixing
Effects of rheological properties on mixing
Ā 
Gurgaon āœ”ļø9711147426āœØCall In girls Gurgaon Sector 51 escort service
Gurgaon āœ”ļø9711147426āœØCall In girls Gurgaon Sector 51 escort serviceGurgaon āœ”ļø9711147426āœØCall In girls Gurgaon Sector 51 escort service
Gurgaon āœ”ļø9711147426āœØCall In girls Gurgaon Sector 51 escort service
Ā 
Concrete Mix Design - IS 10262-2019 - .pptx
Concrete Mix Design - IS 10262-2019 - .pptxConcrete Mix Design - IS 10262-2019 - .pptx
Concrete Mix Design - IS 10262-2019 - .pptx
Ā 
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
Ā 
UNIT III ANALOG ELECTRONICS (BASIC ELECTRONICS)
UNIT III ANALOG ELECTRONICS (BASIC ELECTRONICS)UNIT III ANALOG ELECTRONICS (BASIC ELECTRONICS)
UNIT III ANALOG ELECTRONICS (BASIC ELECTRONICS)
Ā 
Call Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile serviceCall Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile service
Ā 
Application of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptxApplication of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptx
Ā 
main PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidmain PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfid
Ā 

Air refrigeration systems

  • 1.
  • 2. Air cycle refrigeration systems use air as their refrigerant, compressing it and expanding it to create heating and cooling capacity.Heat flows in direction of decreasing temperature i.e. From high temperature to low temperature regions. But the reverse process (i.e. heat transfer from low to high temperature) cannot occur by itself (Claussius Definition of Second Law). This process requires a special device called Refrigerator. The Carnot cycle is used to convert the heat into the mechanical work whereas the reverse Carnot cycle is used to absorb the heat from the system and rejects to the surroundings to maintain the system cool. Carnot Refrigeration cycle is a totally reversible cycle which consists of two reversible isothermal processes and two isentropic processes.A refrigerator or heat pump that operates on the reversed Carnot cycle is called a Carnot refrigerator or a Carnot heat pump. 12/28/2021 2 Suhail Bhatia
  • 3. The term heat pump is usually reserved for a device that can heat a house in winter by using an electric motor that does work W to take heat Qcold from the outside at low temperature and delivers heat Qhot to the warmer inside of the house. The operating principle of refrigerators, air conditioners, and heat pumps is the same, and it is just the reverse of a heat engine. In general, a heat pump is a device that transfers heat energy from a heat source to a ā€œheat sink,ā€ but in this case, the transfer occurs in the opposite direction of spontaneous heat transfer by absorbing heat from a cold space and releasing it to a warmer one. 12/28/2021 3 Suhail Bhatia
  • 5. We know that; COP of Refrigerator = Heat absorbed / work supplied = Heat absorbed / (Heat rejected ā€“ Heat absorbed) = T2 (Sb-Sa) / [T1(Sb-Sa) ā€“ T2(Sb-Sa) = T2 / (T1-T2) Therefore, COP of Carnot Refrigerator is : where TH is the source temperature and TL is the sink temperature where heat is rejected (i.e., lake, ambient air, etc.). 12/28/2021 5 Suhail Bhatia
  • 6. Brayton cycle is a thermodynamic cycle that describes the operation of certain heat engines that have air or some other gas as their working fluid. A Brayton Refrigeration cycle that is driven in the reverse direction is known as the reverse Brayton cycle. Its purpose is to move heat from the colder to the hotter body rather than produce work. This cycle is also known as the gas refrigeration cycle or the Bell Coleman cycle. This type of cycle is widely used in jet aircraft for air conditioning systems using air from the engine compressors. It is also widely used in the LNG industry. 12/28/2021 6 Suhail Bhatia
  • 7. In compliance with the second law of thermodynamics, heat cannot spontaneously flow from cold system to hot system without external work being performed on the system. Heat can flow from colder to the hotter body, but only when forced by external work. This is exactly what refrigerators and heat pumps accomplish. These are driven by electric motors requiring work from their surroundings to operate. One of the possible cycles is a reverse Brayton cycle, which is similar to the ordinary Brayton cycle, but it is driven in reverse via net work input. 12/28/2021 7 Suhail Bhatia
  • 8. Aircraft air refrigeration systems are required due to heat transfer from many external and internal heat sources (like solar radiation and avionics) which increase the cabin air temperature. With the technological developments in high-speed passenger and jet aircrafts, the air refrigeration systems are proving to be most efficient, compact and simple. Despite outside temperature is low refrigeration is required in inside the occupant cabin because : 1. large internal heat is generated due to occupant and equipment inside the cabin. 2.Heat generation due to skin friction caused by the fast moving aircraft. 3. At high altitude, the outside pressure will be sub-automatic. 4.Solar radiation. For low speed aircraft flying at low altitudes, cooling system may not be required, however, for high speed aircraft flying at high altitude, a cooling system is must. 12/28/2021 8 Suhail Bhatia
  • 9. Various types of aircraft air refrigeration systems used these days are: ā€¢Simple air cooling system ā€¢Simple air evaporative cooling system ā€¢Boot strap air cooling system ā€¢Boot strap air evaporative cooling system ā€¢Reduced ambient air cooling system ā€¢Regenerative air cooling system. 12/28/2021 9 Suhail Bhatia
  • 10. Ambient air gets rammed before the main compressor. The air required for refrigeration system is then bled off from this compressor. It is then sent to the heat exchanger where this high pressure and high temperature air is cooled using ram air. Air is further cooled in the cooling turbine due to its expansion. The turbine work drives the cooling fan which draws ram air through the heat exchanger. The cooled air from turbine is then sent to the aircraft cabin. 12/28/2021 10 Suhail Bhatia
  • 14. Process 1-2= Isentropic ramming of air, Process 2-3i= Isentropic compression in main compressor, Process 2-3= Actual compression in main compressor, Process 3-4= Constant pressure heat rejection in heat exchanger, Process 4-5i= Isentropic expansion in cooling turbine, Process 4-5= Actual expansion in cooling turbine, Process 5-6= Constant pressure heat addition in cabin 12/28/2021 14 Suhail Bhatia
  • 15. If a Q tonnes of refrigeration is the Cooling load in the cabin then the air required for the refrigeration purpose, Power required for the refrigerating system, And C O.P. of the refrigerating system The initial mass of evaporant (Me) required to be carried for the given flight time is given by where Qe = Heat to be removed in evaporation in kJ/min, and Hfg = Latent heat of vaporisation of evaporant in kJ/kg 12/28/2021 15 Suhail Bhatia
  • 16. Problems on aircraft cooling systems - Simple Refrigeration Cycle Example A simple air cooled system is used for an aeroplane having a load of 10 tones. The atmospheric pressure and temperature are 0.9 bar and 10Ā°C respectively. The pressure increases to 1.013 bar due to ramming. The temperature of the air is reduced by 50Ā°C in the heat exchanger. The pressure in the cabin is 1.01 bar and the temperature of air leaving the cabin is 25Ā°C. Determine : 1 Power required to take the load of cooling in the cabin; and 2. C.O.P. of the system. Assume that all the expansions and compressions are isentropic. The pressure of the compressed air is 3.5 bar. Solution Given : Q=10TR; p1=0.9bar; T1=10Ā°C=10+273=283K; p2=1.013bar; p5=p6=1.01bar; T6=25Ā°C=25+273=298K; p3=3.5bar take Ī» = 1.4 12/28/2021 16 Suhail Bhatia
  • 17. 1. Power required taking the load of cooling in the cabin First of all, let us find the mass of air (mama) required for the refrigeration purpose. Since the compressions and expansions are isentropic, therefore the various processes on the T-s diagram are as shown in diagram below Let T2 = Temperature of air at the end of ramming or entering the main compressor, T3 = Temperature of air leaving the main compressor after isentropic compression, T4 = Temperature of air leaving the heat exchanger, and T5 = Temperature of air leaving the cooling turbine 12/28/2021 17 Suhail Bhatia
  • 20. It is similar to the simple cooling system except that the addition of an evaporator between the beat exchanger and cooling turbine. The evaporator provides an additional cooling effect through evaporation of a refrigerant such as water. At high altitudes, the evaporative cooling may be obtained by using alcohol or ammonia. The water, alcohol and ammonia have different refrigerating effects at different altitudes. At 20000 metres height for example, water boils at 400 C, alcohol at 90 C and ammonia at - 70Ā° C. The T-s diagram for simple air cycle evaporative cooling system is shown below: 12/28/2021 20 Suhail Bhatia
  • 21. If a Q tonnes of refrigeration is the Cooling load in the cabin then the air required for the refrigeration purpose, Power required for the refrigerating system, And C O.P. of the refrigerating system The initial mass of evaporant (Me) required to be carried for the given flight time is given by where Qe = Heat to be removed in evaporation in kJ/min, and Hfg = Latent heat of vaporisation of evaporant in kJ/kg 12/28/2021 21 Suhail Bhatia
  • 22. Problem on simple air evaporative cooling system Example Simple evaporative air refrigeration system is used for an aeroplane to take 20 tones of refrigeration load. The ambient air conditions are 20Ā°C and 0.9 bar. The ambient air is rammed isentropically to a pressure of 1bar. The air leaving the main compressor at pressure 3.5 bar is first cooled in the heat exchanger having effectiveness of 0.6 and then in the evaporator where its temperature is reduced by 5Ā°C. The air from the evaporator is passed through the cooling turbine and then it is supplied to the cabin which is to be maintained at a temperature of 25Ā°C and at a pressure of 1.05 bar. If the internal efficiency of the compressor is 80% and that of cooling turbine is 75% determine: 1. Mass of air bled off the main compressor; 2. Power required for the refrigerating system; and 3. C.O.P. of the refrigeration system. Solution Given: Q=20TR; T1=20Ā°C=20+273=293K; p1=0.9bar; p2=1bar; p3=pā€²3=3.5bar; Ī·H=0.6; T6=25Ā°C=25+273=298K; p6=1.05bar; Ī·C=80%= 0.8 ; Ī·T=75%=0.75 12/28/2021 22 Suhail Bhatia
  • 23. The T-s diagram for the simple evaporative air refrigeration system with the given conditions is shown below: 12/28/2021 23 Suhail Bhatia
  • 28. This boot strap air cooling system has two heat exchangers instead of one, and a cooling turbine drives a secondary compressor instead of cooling fan. The air bled from the main compressor is first cooled by the ram air in the first heat exchanger. This cooled air, after compression in the secondary compressor, is led to the second heat exchanger where it is again cooled by the ram air before passing to the cooling turbine. This type of cooling system is mostly used in transport type aircraft. The T-s diagram for a boot-strap air cycle cooling system: 12/28/2021 28 Suhail Bhatia
  • 29. The various processes are as follows: The process 1-2' represents the isentropic ramming of ambient air from pressure P1, and temperature T1 to pressure P2 and temperature T2. The process 1-2' represents the actual ramming process because of internal friction due to irreversibilities. The process 2'-3 represents the isentropic compression of air in the main compressor and the process 2'-3' represents the actual compression of air because of internal friction due to irreversibilities. The process 3'-4 represents the cooling by ram air in the first heat exchanger. The pressure drop in the heat exchanger is neglected. The process 4.5 represents compression of cooled air, from first heat exchanger, in the secondary compressor. The process 4-5' represents the actual compression process because of internal friction due to irreversibilities. The process 5'-6 represents the cooling by ram air in the second heat exchanger. The pressure drop in heat exchanger in neglected. The process 6-7 represents isentropic expansion of the cooled air in the cooling turbine upto the cabin pressure. The process 6-7' represents actual expansion of the cooled air in the cooling turbine. The process 7'-8 represents the heating of air upto the cabin 12/28/2021 29 Suhail Bhatia
  • 30. If Q tonnes of refrigeration is the cooling load in the cabin, then the quantity of air required for the refrigeration purpose will be Power required for the refrigerating system, and C.O.P. of the refrigerating system 12/28/2021 30 Suhail Bhatia
  • 31. Problem on boot strap cooling system Example A boot-strap cooling system of 10 TR capacity is used in an aeroplane. The ambient air temperature and pressure are 20Ā°C and 0.85 bar respectively. The pressure of air increases from 0.85 bar to 1 bar due to ramming action of air. "The pressure of air discharged from the main compressor is 3 bar. The discharge pressure of air from the auxiliary compressor is 4 bar. The isentropic efficiency of each of the compressor is 80%, while that of turbine is 85%. 50% of the enthalpy of air discharged from the main compressor is removed in the first heat exchanger and 30% of the enthalpy of air discharged from the auxiliary compressor is removed in the second heat exchanger using rammed air. Assuming ramming action to be isentropic, the required cabin pressure of 0.9 bar and temperature of the air leaving the cabin not more than 20Ā° C, find : 1. the power required to operate the system, and 2. the C.O.P. of the system. Draw the schematic and temperature -entropy diagram of the system. Take Ī³=1.4 and cp=1 kJ/kg K. 12/28/2021 31 Suhail Bhatia
  • 37. A boot-strap air cycle evaporative cooling system is shown above. It is similar to the boot-strap air cycle cooling system except that the addition of an evaporator between the second heat exchanger and the cooling turbine. The T-s diagram for a boot-strap air evaporative cooling system: 12/28/2021 37 Suhail Bhatia
  • 38. The various processes of this cycle are same as a simple boot-strap system except the process 5''-6 which represents cooling in the evaporator using any suitable evaporant. If Q tonnes of refrigeration is the cooling load in the cabin, then the quantity of air required for the refrigeration purpose will be: Power required for the refrigeration system is given by: and C.O.P. of the refrigerating system Note: Since the temperature of air leaving the cooling turbine in boot- strap evaporative system is lower than the simple boot-strap system, therefore mass of air (ma) per tonne of refrigeration will be less in boot- strap evaporative system. 12/28/2021 38 Suhail Bhatia
  • 40. Problem on boot strap evaporative cooling system Example The following data refer to a boot strap air cycle evaporative refrigeration system used for an aeroplane to take 20 tonnes of refrigeration load: Ambient air temperature = 15Ā°C Ambient air pressure = 0.8bar Mach number of the flight = 1.2 Ram efficiency = 90 Pressure of air bled off the main compressor = 4bar Pressure of air in the secondary compressor = 5bar Isentropic efficiency of the main compressor = 90 Isentropic efficiency of the secondary compressor = 80 Isentropic efficiency of the cooling turbine = 80 Temperature of air leaving the first heat exchanger =? Temperature of air leaving the second heat exchange = ? Temperature of air leaving the evaporator = 100Ā°C Cabin temperature = 25Ā°C Cabin pressure = 1bar Find: 1. Mass of air required to take the cabin load, 2. Power required for the refrigeration system, and 3. C.O.P. of the system. 12/28/2021 40 Suhail Bhatia
  • 41. Solution Given: Q=20 TR ; T1=15Ā°C=15+237=288K; p1=0.8bar; M=1.2; Ī·R=90 p3=pā€²3=p4=4bar; p5=pā€²5=p5ā€=p6=bar; Ī·C1=90; Ī·C2=80 T6=100Ā°C=100+273=373K; T8=25Ā°C=25+273=298K; p8=p7=p7ā€=1bar The T-s diagram for the boot-strap air cycle evaporative refrigeration system, with the given conditions, is shown in the figure below: 12/28/2021 41 Suhail Bhatia
  • 46. The regenerative air cooling-system is a modification of a simple air cooling system with the addition of a regenerative heat exchanger. The high pressure and high temperature air from the main compressor is first cooled by the ram air in the heat exchanger. This air is further cooled in the regenerative heat exchanger with a portion of the air bled after expansion in the cooling turbine. This type of cooling system is used for supersonic aircrafts and rockets. 12/28/2021 46 Suhail Bhatia
  • 47. The T-s diagram for the regenerative air cooling system is shown above. The various processes are as follows: 1. The process 1-2 represents' isentropic ramming of air and process 1-2' represents actual ramming of air because of internal friction due to irreversibilities. 2. The process 2'-3 represents isentropic compression of air in the main compressor and the process 2'-3' represents actual compression of air because of internal friction due to irreversibilities. 3. The process 3'-4 represents cooling of compressed air by ram air in the heat exchanger. 4. The process 4-5 represents cooling of air in the regenerative heat exchanger. 5. The process 5-6 represents isentropic expansion of air in the cooling turbine up to the cabin pressure and the process 5-6' represents actual expansion of air in the cooling turbine. 6. The process 6'-7 represents heating of air upto the cabin temperature T7. 12/28/2021 47 Suhail Bhatia
  • 48. If Q tonnes of refrigeration is the cooling load in the cabin, then the quantity of air required for the refrigeration purpose will be For the energy balance of regenerative heat exchanger, we have where T8 = Temperature of air leaving to atmosphere from the regenerative heat exchanger. Power required for the refrigeration system: and C.O.P. of the refrigerating system: 12/28/2021 48 Suhail Bhatia
  • 49. Problem on regenerative cooling system Example A regenerative air cooling system is used for an airplane to take 20 tonnes of refrigeration load. The ambient air at pressure 0.8 bar and temperature 10Ā°C is rammed isentropically till the pressure rises to 1.2 bar. The air bled off the main compressor at 4.5 bar is, cooled by the ram air in the heat exchanger whose effectiveness is 60%. The air from the heat exchanger is further cooled to 60Ā°C in the regenerative heat exchanger with a portion of the air bled after expansion in the cooling turbine. The cabin is to be maintained at a temperature of 25Ā°C and a pressure of I bar. If the isentropic efficiencies of the compressor and turbine are 90% and 80% respectively, find: 1. Mass of the air bled from cooling turbine to be used for regenerative cooling; 2. Power required for maintaining the cabin at the required condition; and 3. C. O. P. of the system. Assume the temperature of air leaving to atmosphere from the regenerative heat exchanger as 1 00Ā° C. Solution Given : Q=20TR; p1=0.8bar; T1=10Ā°C=10+273=283K; p2=1.2bar; p3=pāˆ’4=p5=4.5bar; Ī·H=60%=0.6; T5=60Ā°C=60+273=333K; T7=25Ā°C=25+273=298K; p7=p6=pā€²6=1bar; Ī·c=0.9; Ī·T=80%=0.8;=0.8; 12/28/2021 49 Suhail Bhatia
  • 50. The T-s diagram for the regenerative air cooling system with the given conditions is 12/28/2021 50 Suhail Bhatia
  • 55. The reduced ambient air cooling system includes two cooling turbines and one heat exchanger. The air reduced for the refrigeration initially in system is bled off from the main compressor. This high pressure and high temperature air is cooled the heat exchanger. The air for cooling is taken from the cooling turbine which lower the high temperature of rammed air. The cooled air from the heat exchanger is passed through the second cooling turbine from where the air is supplied to the cabin. The work of the cooling turbine is used to drive the cooling fan (through reduction gears) which draws cooling air from the heat exchanger. The reduced ambient air cooling system is used for very high speed aircrafts. 12/28/2021 55 Suhail Bhatia
  • 56. The T-s diagram for the reduced ambient air cycle cooling system is: 12/28/2021 56 Suhail Bhatia
  • 57. The various processes are as follows: The process 1-2 represents isentropic ramming of air and the process 1-2' represents actual ramming of air because of internal friction due to irreversibilities. The process 2'-3 represents isentropic compression in the main compressor and the process 2'-3' represents actual compression of air, because of internal friction due to irreversibilities. The process 3'-4 represents cooling of compressed air by ram air which after passing through the first cooling turbine is led to the heat exchanger. The pressure drop in the heat exchanger is neglected. The process 4-5 represents isentropic expansion of air in the second cooling turbine upto the cabin pressure. The actual expansion of air in the second cooling turbine is represented by the curve 4-5'. The process 5'-6 represents the heating of air upto the cabin 12/28/2021 57 Suhail Bhatia
  • 58. If Q tonnes of refrigeration is the cooling load in the cabin, then the quantity of air required for the refrigeration purpose will be: Power required for the refrigeration system is given by and C.O.P. of the system 12/28/2021 58 Suhail Bhatia
  • 59. Problems on reduced ambient cooling system Example The reduced ambient air refrigeration system used for an aircraft consists of two cooling turbines, one heat exchanger and one air cooling fan. The speed of aircraft is 1500 km/h. The ambient air conditions are 0.8 bar and 10Ā° C. The ram efficiency may be taken as 90%. The rammed air used for cooling is expanded in the first cooling turbine and leaves it at a pressure of 0.8 bar. The air bled from the main compressor at 6 bar is cooled in the heat exchanger and leaves it at 100Ā° C: The cabin is to be maintained at 20Ā° C and 1 bar. The pressure loss between the second cooling turbine and cabin is 0.1 bar. If the isentropic efficiency for the main compressor and both of the cooling turbines are 85% and 80% respectively, find: 1. mass flow rate of air supplied to cabin to take a cabin load of 10 tonnes of refrigeration ; 2. quantity of air passing through the heat exchanger if the temperature rise of ram air is limited to 80 K ; 3. power used to drive the cooling fan; and 4. C.O.P. of the system. Solution Given : V=1500 km/h=417m/s ;p2=0.6bar; T1=10Ā°C=10+273=283K; Ī·R=90%=0.9; p3=p4=6bar; T4=100Ā°C=100+273=373K; T6=20Ā°C=20+273=293K; p6=1bar; Ī·C=85%=0.85; 12/28/2021 59 Suhail Bhatia
  • 60. The T-s diagram for the reduced ambient air refrigeration system with the given conditions is below: 12/28/2021 60 Suhail Bhatia
  • 61. Let Tā€²2T2ā€²=Stagnation temperature of ambient air entering the main compressor, p2p2=Pressure of air at the end of isentropic ramming, and pā€²2p2ā€²= Stagnation pressure of air entering the main compressor. 12/28/2021 61 Suhail Bhatia
  • 63. T-s diagram of first cooling tube 12/28/2021 63 Suhail Bhatia
  • 66. Comparison of Various Air Cooling Systems used for Aircraft Dry Air Rated Temperature (DART): The concept of Dry Air Rated Temperature is used to compare different aircraft refrigeration cycles. Dry Air Rated Temperature is defined as the temperature of the air at the exit of the cooling turbine in the absence of moisture condensation. For condensation not to occur during expansion in the turbine, the dew point temperature and hence moisture content of the air should be very low, i.e., the air should be very dry. The aircraft refrigeration systems are rated based on the mass flow rate of air at the design DART. The cooling capacity is then given by: where, m is the mass flow rate of air, T DART and Ti are the dry air rated temperature and cabin temperature, respectively. 12/28/2021 66 Suhail Bhatia
  • 68. The performance curves for the various air cooling systems used for aircrafts are shown above. These curves show the dry air rated turbine discharge temperature (DART) against the Mach number. From the figure, we see that the simple air cooling system gives maximum cooling effect on the ground surface and decreases as the speed of aircraft increases. The boot strap system on the other hand, requires the air plane to be in flight so that the ram air can be used for cooling in the heat exchangers. One method of overcoming this drawback of boot strap system is to use part of work derived from turbine to drive a fan which pulls air over the secondary heat exchanger, thus combining the features of a simple and boot strap system .As the speed of aircraft increases, the temperature of ram cooling air rises and the ram air becomes less effective as a coolant in the heat exchanger. In such cases, a suitable evaporant is used with the ram air so that the cabin temperature does not rise. For high speed aircrafts, the boot strap evaporative or regenerative systems are used because they give lower turbine discharge temperature than the simple cooling system. In some cases, aeroplanes carry an auxiliary gas- ,turbine for cabin pressurisation and, air conditioning. From the chart, we see that the turbine. Discharge temperature of the air is variable. Therefore, in order to maintain the content temperature of simply air to the cabin, it 12/28/2021 68 Suhail Bhatia
  • 69. Summary: i. DART increases monotonically with Mach number for all the systems except the reduced ambient system. ii. The simple system is adequate at low Mach numbers. iii. At high Mach numbers either bootstrap system or regenerative system should be used. iv. Reduced ambient temperature system is best suited for very high Mach number, supersonic aircrafts. 12/28/2021 69 Suhail Bhatia