ECE 740
Synchronous Generators
Construction of synchronous machines
In a synchronous generator, a DC current is
applied to the rotor winding producing a rotor
magnetic field. The rotor is then turned by
external means producing a rotating magnetic
field, which induces a 3-phase voltage within
the stator winding.
• Field windings are the windings
producing the main magnetic field
(rotor windings
• armature windings are the windings
where the main voltage is induced
(stator windings)
Construction of synchronous machines
The rotor of a synchronous machine is a large electromagnet. The
magnetic poles can be either salient (sticking out of rotor surface) or non-
salient construction.
Non-salient-pole rotor: # of poles: 2 or 4. Salient-pole rotor: # of
poles: large number
Rotors are made laminated to reduce eddy current losses.
Construction of synchronous machines
Two common approaches are used to supply a DC current to the field
circuits on the rotating rotor:
1. Supply the DC power from an
external DC source to the rotor by
means of slip rings and brushes;
2. Supply the DC power from a
special DC power source mounted
directly on the shaft of the
machine.
Slip rings are metal rings completely encircling the shaft of a machine but
insulated from it. Graphite-like carbon brushes connected to DC terminals
ride on each slip ring supplying DC voltage to field windings.
Construction of synchronous machines
• On large generators and motors, brushless exciters are used.
• A brushless exciter is a small AC generator whose field
circuits are mounted on the stator and armature circuits are
mounted on the rotor shaft.
• The exciter generator’s 3-phase output is rectified to DC by
a 3-phase rectifier (mounted on the shaft) and fed into the
main DC field circuit.
• It is possible to adjust the field current on the main machine
by controlling the small DC field current of the exciter
generator (located on the stator).
Construction of synchronous machines
To make the excitation of
a generator completely
independent of any
external power source, a
small pilot exciter is often
added to the circuit.
The pilot exciter is an AC
generator with a
permanent magnet
mounted on the rotor
shaft and a 3-phase
winding on the stator
producing the power for
the field circuit of the
exciter.
Construction of synchronous machines
A rotor of large
synchronous
machine with a
brushless exciter
mounted on the
same shaft.
Construction of synchronous machines
Exciter
Rotor pole.
Rotation speed of synchronous generator
By the definition, synchronous generators produce electricity
whose frequency is synchronized with the mechanical rotational
speed.
Where fe is the electrical frequency, Hz;
nm is the rotor speed of the machine, rpm;
p is the number of poles.
• Steam turbines are most efficient when rotating at high speed;
therefore, to generate 60 Hz, they are usually rotating at 3600
rpm (2-pole).
• Water turbines are most efficient when rotating at low speeds
(200-300 rpm); therefore, they usually turn generators with many
poles.
me n
p
f
120

The induced voltage in a 3-phase set of coils
In three coils, each of NC turns, placed around the rotor magnetic field,
the induced in each coil will have the same magnitude and phases
differing by 1200:
 
 
'
'
'
( ) cos
( ) cos 120
( ) cos 240
aa C m m
bb C m m
cc C m m
e t N t
e t N t
e t N t
 
 
 

  
  
Peak voltage:
max C mE N  max 2 CE N f 
RMS voltage:
2
2
2CA CNE Nf f

  
Internal generated voltage of a synchronous
generator
The magnitude of internal generated voltage induced in a given stator is
2A CE N f K   
where K is a constant representing the construction of the machine,  is flux in it
and  is its rotation speed.
Since flux in the
machine depends
on the field current
through it, the
internal generated
voltage is a
function of the
rotor field current.
Magnetization curve (open-circuit characteristic) of a
synchronous machine
Equivalent circuit of a synchronous generator
The internally generated voltage in a single phase of a
synchronous machine EA is not usually the voltage appearing
at its terminals. It equals to the output voltage V only when
there is no armature current in the machine. The reasons
that the armature voltage EA is not equal to the output
voltage V are:
1. Distortion of the air-gap magnetic field caused by the
current flowing in the stator (armature reaction);
2. Self-inductance of the armature coils;
3. Resistance of the armature coils;
Equivalent circuit of a synchronous generator
Armature reaction:
• When the rotor of a
synchronous generator is
spinning, a voltage EA is
induced in its stator.
• When a load is connected,
a current starts flowing
creating a magnetic field in
machine’s stator.
• This stator magnetic field BS
adds to the rotor (main)
magnetic field BR affecting
the total magnetic field and,
therefore, the phase
voltage.
Lagging
load
Equivalent circuit of a synchronous generator
The load current IA will create a stator magnetic field BS, which will
produce the armature reaction voltage Estat. Therefore, the phase voltage
will be
A statV E E  
The net magnetic flux will be
net R SB B B 
Rotor field Stator field
Equivalent circuit of a synchronous generator
Since the armature reaction voltage lags the
current by 90 degrees, it can be modeled by
stat AE jXI 
The phase voltage is then
A AV E jXI  
However, in addition to armature reactance effect, the stator coil
has a self-inductance LA (XA is the corresponding reactance) and
the stator has resistance RA. The phase voltage is thus
A A A A AV E jXI jX I RI    
Equivalent circuit of a synchronous generator
Often, armature reactance and self-
inductance are combined into the
synchronous reactance of the machine:
S AX X X 
A S A AV E jX I RI   
Therefore, the phase voltage is
The equivalent circuit of a 3-phase
synchronous generator is shown.
The adjustable resistor Radj controls
the field current and, therefore, the
rotor magnetic field.
Equivalent circuit of a synchronous generator
A synchronous generator can be Y- or -connected:
The terminal voltage will be
3T TV V for Y V V for       
Equivalent circuit of a synchronous generator
Since – for balanced loads – the three phases of a synchronous
generator are identical except for phase angles, per-phase
equivalent circuits are often used.
Phasor diagram of a synchronous generator
(similar to that of a transformer)
Since the voltages in a synchronous generator are AC voltages, they are
usually expressed as phasors. A vector plot of voltages and currents within
one phase is called a phasor diagram.
A phasor diagram of a synchronous
generator with a unity power factor
(resistive load)
Lagging power factor (inductive load): a
larger than for leading PF internal
generated voltage EA is needed to form
the same phase voltage.
Leading power factor (capacitive load).
The Synchronous generator operating alone
The behavior of a synchronous generator varies greatly under
load depending on the power factor of the load and on
whether the generator is working alone or in parallel with other
synchronous generators.
Although most of the synchronous generators in the world
operate as parts of large power systems, we start our
discussion assuming that the synchronous generator works
alone.
Unless otherwise stated, the speed of the generator is
assumed constant.
The Synchronous generator operating alone
Effects of load changes
A increase in the load is an
increase in the real and/or
reactive power drawn from the
generator.
Assuming the same power factor of the load, a change in load will change
the magnitude of the armature current IA. However, the angle will be the
same (for a constant PF). Thus, the armature reaction voltage jXSIA will be
larger for the increased load. Since the magnitude of the internal
generated voltage is constant
A S AE V jX I 
Armature reaction voltage vector will “move parallel” to its initial position.
The Synchronous generator operating alone
Increase load effect on generators with
Lagging PF
Leading PF
Unity PF
The Synchronous generator operating alone
1. For lagging (inductive) loads, the phase (and terminal) voltage
decreases significantly.
2. For unity power factor (purely resistive) loads, the phase (and
terminal) voltage decreases slightly.
3. For leading (capacitive) loads, the phase (and terminal) voltage rises.
Generally, when a load on a synchronous generator is added, the
following changes can be observed:
Effects of adding loads can be described by the voltage regulation:
100%
nl fl
fl
V V
VR
V


Where Vnl is the no-load voltage of the generator and Vfl is its full-load
voltage.
The Synchronous generator operating alone
• A synchronous generator operating at a lagging power factor has a
fairly large positive voltage regulation.
• A synchronous generator operating at a unity power factor has a small
positive voltage regulation.
• A synchronous generator operating at a leading power factor often has
a negative voltage regulation.
Normally, a constant terminal voltage supplied by a generator is desired.
Since the armature reactance cannot be controlled, an obvious approach
to adjust the terminal voltage is by controlling the internal generated
voltage EA = K. This may be done by changing flux in the machine
while varying the value of the field resistance RF, which is summarized:
1. Decreasing the field resistance increases the field current in the
generator.
2. An increase in the field current increases the flux in the machine.
3. An increased flux leads to the increase in the internal generated voltage.
4. An increase in the internal generated voltage increases the terminal
voltage of the generator.
Power and torque in synchronous generators
A synchronous generator needs to be connected to a prime mover whose
speed is reasonably constant (to ensure constant frequency of the
generated voltage) for various loads.
The applied mechanical power
in app mP  
is partially converted to electricity
3 cosconv ind m A AP E I   
Where  is the angle
between EA and IA.
The power-flow diagram of
a synchronous generator.
Power and torque in synchronous generators
The real and reactive output powers of the synchronous generator are
3 cos 3 cosout T L AP V I V I  
3 sin 3 sinout T L AQ V I V I  
Recall that the power factor angle  is the angle between V and IA and not
the angle between EA and IA.
In real synchronous machines of any size, the armature resistance RA <<
XS and, therefore, the armature resistance can be ignored. Thus, a
simplified phasor diagram indicates that
sin
cos A
A
S
E
I
X

 
Power and torque in synchronous generators
Then the real output power of the synchronous generator can be
approximated as 3 sinA
out
S
V E
P
X
 

We observe that electrical losses are assumed to be zero since the
resistance is neglected. Therefore:
conv outP P
Here  is the power angle of the machine – the angle between V and EA.
This is different from the power factor angle θ
The maximum power can be supplied by the generator when  = 900:
max
3 A
S
V E
P
X


Generator P-f Curve
• All generators are driven by a prime mover, such as a
steam, gas, water, wind turbines, diesel engines, etc.
• Regardless the power source, most of prime movers tend to
slow down with increasing the load.
• The speed drop (SD) of a prime mover is defined as:
• Most prime movers have a speed drop from 2% to 4%.
Most governors have a mechanism to adjust the turbine’s
no-load speed (set-point adjustment).
Generator P-f Curve
Generator Q-V Curve
• A similar relationship can be derived for the reactive power Q and
terminal voltage VT.
– When supplying a lagging load to a synchronous generator, its
terminal voltage decreases.
– When adding a leading load to a synchronous generator, its terminal
voltage increases.
• Both the frequency-power and terminal voltage vs. reactive
power characteristics are important for parallel operations of
generators.
Example
A generator with no-load frequency of 61.0 Hz and a slope of 1 MW/Hz is
connected to Load 1 consuming 1 MW of real power at 0.8 PF lagging.
Load 2 (that to be connected to the generator) consumes a real power of
0.8 MW at 0.707 PF lagging.
1. Find the operating frequency of the system before the switch is
closed. (ans. 60 Hz)
2. Find the operating frequency of the system after the switch is closed.
(ans. 59.2 Hz)
3. What action could an operator take to restore the system frequency
to 60 Hz after both loads are connected to the generator? (ans.
increase the governor no-load set point by 0.8 Hz)
Generator Operating Alone
• When a generator is operating alone,
– The real and reactive powers generated are the
amounts demanded by the load.
– The governor of the generator controls the
operating frequency of the circuit.
– The field current controls the terminal voltage of
the circuit.
Generators connected in parallel
• Most of synchronous generators are operating in parallel
with other synchronous generators to supply power to the
same power system.
• Obvious advantages of this arrangement are:
– Several generators can supply a bigger load;
– A failure of a single generator does not result in a total
power loss to the load, thus increasing reliability of the
power system;
– Individual generators may be removed from the power
system for maintenance without shutting down the load;
– A single generator not operating at near full load might
be quite inefficient. While having several generators in
parallel, it is possible to turn off some, and operate the
rest at near full-load condition.
Conditions required for paralleling generators
• Closing the switch arbitrarily can cause severe damage. If
voltages are not the same (magnitude, frequency, phase,
sequence) in both lines, a very large current will flow when the
switch is closed.
• To avoid this, the following conditions must be met:
– The rms line voltages of the two generators must be equal.
– The two generators must have the same phase sequence.
– The phase angles of two “a” phases must be equal.
– The frequency of the oncoming generator must be slightly higher
than the frequency of the running system.
Steps for paralleling generators (3-light bulb method)
1. Adjust the field current of the oncoming generator to make its terminal
voltage equal to the line voltage of the system (use a voltmeter).
2. Compare the phase sequences of the oncoming generator and the
running system by examining the three light bulbs. If all three bulbs get
bright and dark together, both generators have the same phase
sequences. If not, two of the conductors must be altered.
3. The frequency of the oncoming generator is adjusted to be slightly
higher than the system’s frequency.
4. When all three lights go out, the voltage across them is zero and,
therefore, machines are in phase. This is the time to close the switch.
Synchronizing a generator with the utility grid
• When a synchronous generator is added to a power system, that
system is so large that one additional generator does not cause
observable changes to the system.
• An infinite bus is a power system that is so large that its voltage
and frequency do not vary regardless of how much real and
reactive power is drawn from or supplied to it (i.e., the power-
frequency and reactive power-voltage characteristics are
horizontal:
Synchronizing a generator with the utility grid
• Consider adding a generator to an
infinite bus supplying a load.
• The frequency and terminal
voltage of all machines must be
the same.
• Therefore, their power-frequency
and reactive power-voltage
characteristics can be plotted
with a common vertical axis.
Synchronizing a generator with the utility grid
Parallel operation with the utility grid
• If an attempt is made to
increase the speed of the
generator after it is connected
to the infinite bus, the system
frequency cannot change and
the power supplied by the
generator increases.
• Note an increase in power
(with Vt and EA staying
constant), results in an
increase in the power angle δ.
Parallel operation with the utility grid
• By adjusting the field current of the machine, it is
possible to make it to make the generator supply or
consume reactive power Q.
• When the generator is operating in parallel to an
infinite bus:
– The frequency and terminal voltage of the generator
are controlled by the system to which it is connected.
– The governor set points of the generator control the
real power supplied by the generator to the system.
– The generator’s field current controls the reactive
power supplied by the generator to the system.
Parallel operation of generators of similar size
• Unlike the case of an infinite bus,
the slope of the frequency-power
curve of G1 is of the same order of
magnitude as that of G2.
• The power-frequency diagram
right after G2 is connected to the
system is shown to the right.
• As indicated previously, in order for
G2 to come in as a generator, its
frequency should be slightly higher
than that of G1.
Parallel operation of generators of similar size
• Note that the sum of the real and
reactive powers supplied by the two
generators must equal the real and
reactive powers demanded by the load:
• If the speed of G2 is increased, its
power-frequency diagram shifts
upwards. This will in turn
– increase the real power supplied by G2
– reduce the real power supplied by G1
– increase the system frequency.
– To bring the frequency down, the speed
of G2 must be reduced.
Example
Two generators are set to supply the same load. G1 has a no-load
frequency of 61.5 Hz and a slope sp1 of 1 MW/Hz. G2 has a no-load
frequency of 61.0 Hz and a slope sp2 of 1 MW/Hz. The two generators are
supplying a real load of 2.5 MW at 0.8 PF lagging.
a) System frequency? Ans. 60 Hz
b) Power generated by G1 and G2? Ans. 1.5 MW and 1 MW
c) An additional load of 1 MW is added, find the system frequency and the
generator powers? Ans. 59.5 Hz, 2 MW, and 1.5 MW
d) Repeat c) after the no-load frequency of G2 is increased by 0.5 Hz? Ans. 59.75
Hz, 1.75 MW and 1.75 MW.
Parallel operation of generators of similar size
• Similarly, an increase in the field
current of G1 will result in
– An increase of the reactive power
supplied G1,
– A reduction of the reactive power
supplied G2.
– An Increase of the system terminal
voltage.
– To bring the voltage down, the field
current of G1 must be reduced.
Synchronous Generator Rating
• The purpose of ratings is to protect the machine from damage.
Typical ratings of synchronous machines are voltage, speed,
apparent power (kVA), power factor, field current and service
factor.
– The rated frequency of a synchronous machine depends on the
power system to which it is connected. Once the operation
frequency is determined, only one rotational speed in possible for
the given number of poles.
– For a given design, the rated voltage is limited by the flux that is
capped by the field current. The rated voltage is also limited by
the windings insulation breakdown limit.
– The maximum acceptable armature current sets the apparent
power rating for a generator. The power factor of the armature
current is irrelevant for heating the armature windings.
Synchronous Generator Real and Reactive Power
}cos{
sin
sin
cos
ti
d
t
i
d
t
at
at
VE
X
V
Q
E
X
V
P
IVQ
IVP








Generator Loading Capability Diagram
Generator Loading Capability
Generator Loading Capability Curve
Static Load Models
• ZIP model:
• Exponential model:
• Frequency dependent model:

More Related Content

What's hot

measurement of high voltage and high currents
 measurement of high voltage and high currents  measurement of high voltage and high currents
measurement of high voltage and high currents mukund mukund.m
 
ELECTRICAL POWER SYSTEM - II. symmetrical three phase faults. PREPARED BY : J...
ELECTRICAL POWER SYSTEM - II. symmetrical three phase faults. PREPARED BY : J...ELECTRICAL POWER SYSTEM - II. symmetrical three phase faults. PREPARED BY : J...
ELECTRICAL POWER SYSTEM - II. symmetrical three phase faults. PREPARED BY : J...Jobin Abraham
 
Synchronous machines
Synchronous machinesSynchronous machines
Synchronous machinesmichaeljmack
 
Protection of three phase synchronous generator
Protection of three phase synchronous generatorProtection of three phase synchronous generator
Protection of three phase synchronous generatorMohammad Abdullah
 
V and inverted v curves of synchronous motor
V and inverted v curves of synchronous motorV and inverted v curves of synchronous motor
V and inverted v curves of synchronous motorkarthi1017
 
3 phase of induction motor 2015 16
3 phase of induction motor 2015 163 phase of induction motor 2015 16
3 phase of induction motor 2015 16Rajputm123
 
EXCITATION SYSTEM.ppt
EXCITATION SYSTEM.pptEXCITATION SYSTEM.ppt
EXCITATION SYSTEM.pptvishal laddha
 
Doubly fed-induction-generator
Doubly fed-induction-generatorDoubly fed-induction-generator
Doubly fed-induction-generatorHarshad Karmarkar
 
Electromechanical energy conversion
Electromechanical energy conversionElectromechanical energy conversion
Electromechanical energy conversionMohammed Waris Senan
 
Power electronic converter in wind turbine
Power electronic converter in wind turbinePower electronic converter in wind turbine
Power electronic converter in wind turbineSonuKumarBairwa
 
EE8701-High Voltage Engineering (1).pptx
EE8701-High Voltage Engineering (1).pptxEE8701-High Voltage Engineering (1).pptx
EE8701-High Voltage Engineering (1).pptxsai karthick
 
Working of synchronous machine, Construction of synchronous machine, Types o...
Working of synchronous machine, Construction of synchronous machine, Types  o...Working of synchronous machine, Construction of synchronous machine, Types  o...
Working of synchronous machine, Construction of synchronous machine, Types o...Self-employed
 
Basic Law related to Electrical Engineering
Basic Law related to Electrical Engineering Basic Law related to Electrical Engineering
Basic Law related to Electrical Engineering Vinay Vishwakarma
 
Induction generator and synchronous induction motor
Induction generator and synchronous induction motor Induction generator and synchronous induction motor
Induction generator and synchronous induction motor Pavithran Selvam
 

What's hot (20)

measurement of high voltage and high currents
 measurement of high voltage and high currents  measurement of high voltage and high currents
measurement of high voltage and high currents
 
ELECTRICAL POWER SYSTEM - II. symmetrical three phase faults. PREPARED BY : J...
ELECTRICAL POWER SYSTEM - II. symmetrical three phase faults. PREPARED BY : J...ELECTRICAL POWER SYSTEM - II. symmetrical three phase faults. PREPARED BY : J...
ELECTRICAL POWER SYSTEM - II. symmetrical three phase faults. PREPARED BY : J...
 
SYNCHRONOUS MACHINES
SYNCHRONOUS MACHINESSYNCHRONOUS MACHINES
SYNCHRONOUS MACHINES
 
Synchronous machines
Synchronous machinesSynchronous machines
Synchronous machines
 
Protection of three phase synchronous generator
Protection of three phase synchronous generatorProtection of three phase synchronous generator
Protection of three phase synchronous generator
 
Synchronous machine
Synchronous machineSynchronous machine
Synchronous machine
 
V and inverted v curves of synchronous motor
V and inverted v curves of synchronous motorV and inverted v curves of synchronous motor
V and inverted v curves of synchronous motor
 
3 phase of induction motor 2015 16
3 phase of induction motor 2015 163 phase of induction motor 2015 16
3 phase of induction motor 2015 16
 
EXCITATION SYSTEM.ppt
EXCITATION SYSTEM.pptEXCITATION SYSTEM.ppt
EXCITATION SYSTEM.ppt
 
Doubly fed-induction-generator
Doubly fed-induction-generatorDoubly fed-induction-generator
Doubly fed-induction-generator
 
Streamer theory
Streamer theoryStreamer theory
Streamer theory
 
Electromechanical energy conversion
Electromechanical energy conversionElectromechanical energy conversion
Electromechanical energy conversion
 
Wind physics
Wind physicsWind physics
Wind physics
 
Power electronic converter in wind turbine
Power electronic converter in wind turbinePower electronic converter in wind turbine
Power electronic converter in wind turbine
 
EE8701-High Voltage Engineering (1).pptx
EE8701-High Voltage Engineering (1).pptxEE8701-High Voltage Engineering (1).pptx
EE8701-High Voltage Engineering (1).pptx
 
Working of synchronous machine, Construction of synchronous machine, Types o...
Working of synchronous machine, Construction of synchronous machine, Types  o...Working of synchronous machine, Construction of synchronous machine, Types  o...
Working of synchronous machine, Construction of synchronous machine, Types o...
 
Synchronous generator
Synchronous generatorSynchronous generator
Synchronous generator
 
EXCITATION SYSTEMS
EXCITATION SYSTEMSEXCITATION SYSTEMS
EXCITATION SYSTEMS
 
Basic Law related to Electrical Engineering
Basic Law related to Electrical Engineering Basic Law related to Electrical Engineering
Basic Law related to Electrical Engineering
 
Induction generator and synchronous induction motor
Induction generator and synchronous induction motor Induction generator and synchronous induction motor
Induction generator and synchronous induction motor
 

Similar to synchronous generators

Synchronous Generator.pdf
Synchronous Generator.pdfSynchronous Generator.pdf
Synchronous Generator.pdfasmasharab1
 
1337683699.3104Lecture 07 - Synchronous machines.ppt
1337683699.3104Lecture 07 - Synchronous machines.ppt1337683699.3104Lecture 07 - Synchronous machines.ppt
1337683699.3104Lecture 07 - Synchronous machines.pptgulie
 
Presentation on Synchronous Machine.pptx
Presentation on Synchronous Machine.pptxPresentation on Synchronous Machine.pptx
Presentation on Synchronous Machine.pptxMaharAliHamzaHansla
 
Electrical Power Systems Synchronous Generator
Electrical Power Systems Synchronous GeneratorElectrical Power Systems Synchronous Generator
Electrical Power Systems Synchronous GeneratorMubarek Kurt
 
Lectures synchronous machines(1)
Lectures synchronous machines(1)Lectures synchronous machines(1)
Lectures synchronous machines(1)Leela Marigowda
 
Synchronous generator
Synchronous generatorSynchronous generator
Synchronous generatorPrasant Kumar
 
4 the dc generator
4 the dc generator4 the dc generator
4 the dc generatorAngelic Sher
 
Synchronous generator construction
Synchronous generator constructionSynchronous generator construction
Synchronous generator constructionAnilKumarJain19
 
DC_Machines_week_4.ppt
DC_Machines_week_4.pptDC_Machines_week_4.ppt
DC_Machines_week_4.pptkiran93845
 
Chapter 1 - Experiment 1 slides.pptx
Chapter 1 - Experiment 1 slides.pptxChapter 1 - Experiment 1 slides.pptx
Chapter 1 - Experiment 1 slides.pptxasmasharab1
 
POWER SYSTEM ANALYSIS-3
POWER SYSTEM ANALYSIS-3POWER SYSTEM ANALYSIS-3
POWER SYSTEM ANALYSIS-3M Ugur Kebir
 
Synchmachi.ppt
Synchmachi.pptSynchmachi.ppt
Synchmachi.pptAskUdaipur
 

Similar to synchronous generators (20)

Synchronous Generator.pdf
Synchronous Generator.pdfSynchronous Generator.pdf
Synchronous Generator.pdf
 
Lecture 07 synchronous machines
Lecture 07   synchronous machinesLecture 07   synchronous machines
Lecture 07 synchronous machines
 
1337683699.3104Lecture 07 - Synchronous machines.ppt
1337683699.3104Lecture 07 - Synchronous machines.ppt1337683699.3104Lecture 07 - Synchronous machines.ppt
1337683699.3104Lecture 07 - Synchronous machines.ppt
 
16888242.ppt
16888242.ppt16888242.ppt
16888242.ppt
 
Presentation on Synchronous Machine.pptx
Presentation on Synchronous Machine.pptxPresentation on Synchronous Machine.pptx
Presentation on Synchronous Machine.pptx
 
Chapter 5
Chapter 5Chapter 5
Chapter 5
 
Electrical Power Systems Synchronous Generator
Electrical Power Systems Synchronous GeneratorElectrical Power Systems Synchronous Generator
Electrical Power Systems Synchronous Generator
 
Lectures synchronous machines(1)
Lectures synchronous machines(1)Lectures synchronous machines(1)
Lectures synchronous machines(1)
 
Synchronous generator
Synchronous generatorSynchronous generator
Synchronous generator
 
EMEC-II, unit 1
EMEC-II, unit 1EMEC-II, unit 1
EMEC-II, unit 1
 
4 the dc generator
4 the dc generator4 the dc generator
4 the dc generator
 
DC_Machines.ppt
DC_Machines.pptDC_Machines.ppt
DC_Machines.ppt
 
Synchronous generator construction
Synchronous generator constructionSynchronous generator construction
Synchronous generator construction
 
DC_Machines_week_4.ppt
DC_Machines_week_4.pptDC_Machines_week_4.ppt
DC_Machines_week_4.ppt
 
5_Synchronous.pdf
5_Synchronous.pdf5_Synchronous.pdf
5_Synchronous.pdf
 
Asm exp.10
Asm exp.10Asm exp.10
Asm exp.10
 
Chapter 1 - Experiment 1 slides.pptx
Chapter 1 - Experiment 1 slides.pptxChapter 1 - Experiment 1 slides.pptx
Chapter 1 - Experiment 1 slides.pptx
 
POWER SYSTEM ANALYSIS-3
POWER SYSTEM ANALYSIS-3POWER SYSTEM ANALYSIS-3
POWER SYSTEM ANALYSIS-3
 
Synchmachi.ppt
Synchmachi.pptSynchmachi.ppt
Synchmachi.ppt
 
Synchmachine
SynchmachineSynchmachine
Synchmachine
 

More from Souvik Dutta

Automatic Power Factor Detection And Correction using Arduino
Automatic Power Factor Detection And Correction using ArduinoAutomatic Power Factor Detection And Correction using Arduino
Automatic Power Factor Detection And Correction using ArduinoSouvik Dutta
 
Generator synchronization
Generator synchronizationGenerator synchronization
Generator synchronizationSouvik Dutta
 
Gate question 2020
Gate question 2020Gate question 2020
Gate question 2020Souvik Dutta
 
Fundamentals of doping
Fundamentals  of dopingFundamentals  of doping
Fundamentals of dopingSouvik Dutta
 
Fundamental elements of-electrical-engineering circuit theory basic stardelta
Fundamental elements of-electrical-engineering circuit theory basic stardeltaFundamental elements of-electrical-engineering circuit theory basic stardelta
Fundamental elements of-electrical-engineering circuit theory basic stardeltaSouvik Dutta
 
Experience feedback steam turbine
Experience feedback steam turbineExperience feedback steam turbine
Experience feedback steam turbineSouvik Dutta
 
Faults on electrical system
Faults on electrical systemFaults on electrical system
Faults on electrical systemSouvik Dutta
 
Engineering symbology-prints-and-drawings-2
Engineering symbology-prints-and-drawings-2Engineering symbology-prints-and-drawings-2
Engineering symbology-prints-and-drawings-2Souvik Dutta
 
Engineering symbology-prints-and-drawings-1
Engineering symbology-prints-and-drawings-1Engineering symbology-prints-and-drawings-1
Engineering symbology-prints-and-drawings-1Souvik Dutta
 
Energy efficient-electric-motor-selection-handbook
Energy efficient-electric-motor-selection-handbookEnergy efficient-electric-motor-selection-handbook
Energy efficient-electric-motor-selection-handbookSouvik Dutta
 
Electrician handbook
Electrician handbookElectrician handbook
Electrician handbookSouvik Dutta
 
Electrical power supply and distribution
Electrical power supply and distributionElectrical power supply and distribution
Electrical power supply and distributionSouvik Dutta
 
Electrical network protection guide schneider electric
Electrical network protection guide schneider electricElectrical network protection guide schneider electric
Electrical network protection guide schneider electricSouvik Dutta
 
Electrical installation handbook part-2
Electrical installation handbook part-2Electrical installation handbook part-2
Electrical installation handbook part-2Souvik Dutta
 
Electrical installation handbook part-1
Electrical installation handbook part-1Electrical installation handbook part-1
Electrical installation handbook part-1Souvik Dutta
 
Electrical engineering formulas
Electrical engineering formulasElectrical engineering formulas
Electrical engineering formulasSouvik Dutta
 
Edc module iid-synch-motor-alternator
Edc module iid-synch-motor-alternatorEdc module iid-synch-motor-alternator
Edc module iid-synch-motor-alternatorSouvik Dutta
 
Earthing of mv and lv distribution lines
Earthing of mv and lv distribution linesEarthing of mv and lv distribution lines
Earthing of mv and lv distribution linesSouvik Dutta
 
Determining correction factor of power cable sizing
Determining correction factor of power cable sizingDetermining correction factor of power cable sizing
Determining correction factor of power cable sizingSouvik Dutta
 
Designing low voltage feeder circuits
Designing low voltage feeder circuitsDesigning low voltage feeder circuits
Designing low voltage feeder circuitsSouvik Dutta
 

More from Souvik Dutta (20)

Automatic Power Factor Detection And Correction using Arduino
Automatic Power Factor Detection And Correction using ArduinoAutomatic Power Factor Detection And Correction using Arduino
Automatic Power Factor Detection And Correction using Arduino
 
Generator synchronization
Generator synchronizationGenerator synchronization
Generator synchronization
 
Gate question 2020
Gate question 2020Gate question 2020
Gate question 2020
 
Fundamentals of doping
Fundamentals  of dopingFundamentals  of doping
Fundamentals of doping
 
Fundamental elements of-electrical-engineering circuit theory basic stardelta
Fundamental elements of-electrical-engineering circuit theory basic stardeltaFundamental elements of-electrical-engineering circuit theory basic stardelta
Fundamental elements of-electrical-engineering circuit theory basic stardelta
 
Experience feedback steam turbine
Experience feedback steam turbineExperience feedback steam turbine
Experience feedback steam turbine
 
Faults on electrical system
Faults on electrical systemFaults on electrical system
Faults on electrical system
 
Engineering symbology-prints-and-drawings-2
Engineering symbology-prints-and-drawings-2Engineering symbology-prints-and-drawings-2
Engineering symbology-prints-and-drawings-2
 
Engineering symbology-prints-and-drawings-1
Engineering symbology-prints-and-drawings-1Engineering symbology-prints-and-drawings-1
Engineering symbology-prints-and-drawings-1
 
Energy efficient-electric-motor-selection-handbook
Energy efficient-electric-motor-selection-handbookEnergy efficient-electric-motor-selection-handbook
Energy efficient-electric-motor-selection-handbook
 
Electrician handbook
Electrician handbookElectrician handbook
Electrician handbook
 
Electrical power supply and distribution
Electrical power supply and distributionElectrical power supply and distribution
Electrical power supply and distribution
 
Electrical network protection guide schneider electric
Electrical network protection guide schneider electricElectrical network protection guide schneider electric
Electrical network protection guide schneider electric
 
Electrical installation handbook part-2
Electrical installation handbook part-2Electrical installation handbook part-2
Electrical installation handbook part-2
 
Electrical installation handbook part-1
Electrical installation handbook part-1Electrical installation handbook part-1
Electrical installation handbook part-1
 
Electrical engineering formulas
Electrical engineering formulasElectrical engineering formulas
Electrical engineering formulas
 
Edc module iid-synch-motor-alternator
Edc module iid-synch-motor-alternatorEdc module iid-synch-motor-alternator
Edc module iid-synch-motor-alternator
 
Earthing of mv and lv distribution lines
Earthing of mv and lv distribution linesEarthing of mv and lv distribution lines
Earthing of mv and lv distribution lines
 
Determining correction factor of power cable sizing
Determining correction factor of power cable sizingDetermining correction factor of power cable sizing
Determining correction factor of power cable sizing
 
Designing low voltage feeder circuits
Designing low voltage feeder circuitsDesigning low voltage feeder circuits
Designing low voltage feeder circuits
 

Recently uploaded

Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort serviceGurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort servicejennyeacort
 
Introduction-To-Agricultural-Surveillance-Rover.pptx
Introduction-To-Agricultural-Surveillance-Rover.pptxIntroduction-To-Agricultural-Surveillance-Rover.pptx
Introduction-To-Agricultural-Surveillance-Rover.pptxk795866
 
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxJoão Esperancinha
 
Biology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptxBiology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptxDeepakSakkari2
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxpurnimasatapathy1234
 
Application of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptxApplication of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptx959SahilShah
 
chaitra-1.pptx fake news detection using machine learning
chaitra-1.pptx  fake news detection using machine learningchaitra-1.pptx  fake news detection using machine learning
chaitra-1.pptx fake news detection using machine learningmisbanausheenparvam
 
INFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETE
INFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETEINFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETE
INFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETEroselinkalist12
 
Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...VICTOR MAESTRE RAMIREZ
 
Sachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective IntroductionSachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective IntroductionDr.Costas Sachpazis
 
Internship report on mechanical engineering
Internship report on mechanical engineeringInternship report on mechanical engineering
Internship report on mechanical engineeringmalavadedarshan25
 
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVRajaP95
 
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...srsj9000
 
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdfCCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdfAsst.prof M.Gokilavani
 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...Soham Mondal
 

Recently uploaded (20)

Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort serviceGurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
 
young call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Service
young call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Serviceyoung call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Service
young call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Service
 
Introduction-To-Agricultural-Surveillance-Rover.pptx
Introduction-To-Agricultural-Surveillance-Rover.pptxIntroduction-To-Agricultural-Surveillance-Rover.pptx
Introduction-To-Agricultural-Surveillance-Rover.pptx
 
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
 
young call girls in Green Park🔝 9953056974 🔝 escort Service
young call girls in Green Park🔝 9953056974 🔝 escort Serviceyoung call girls in Green Park🔝 9953056974 🔝 escort Service
young call girls in Green Park🔝 9953056974 🔝 escort Service
 
Biology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptxBiology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptx
 
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptx
 
Application of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptxApplication of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptx
 
chaitra-1.pptx fake news detection using machine learning
chaitra-1.pptx  fake news detection using machine learningchaitra-1.pptx  fake news detection using machine learning
chaitra-1.pptx fake news detection using machine learning
 
INFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETE
INFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETEINFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETE
INFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETE
 
Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...
 
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
 
Sachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective IntroductionSachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
 
Internship report on mechanical engineering
Internship report on mechanical engineeringInternship report on mechanical engineering
Internship report on mechanical engineering
 
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
 
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
 
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdfCCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
 
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
 

synchronous generators

  • 2. Construction of synchronous machines In a synchronous generator, a DC current is applied to the rotor winding producing a rotor magnetic field. The rotor is then turned by external means producing a rotating magnetic field, which induces a 3-phase voltage within the stator winding. • Field windings are the windings producing the main magnetic field (rotor windings • armature windings are the windings where the main voltage is induced (stator windings)
  • 3. Construction of synchronous machines The rotor of a synchronous machine is a large electromagnet. The magnetic poles can be either salient (sticking out of rotor surface) or non- salient construction. Non-salient-pole rotor: # of poles: 2 or 4. Salient-pole rotor: # of poles: large number Rotors are made laminated to reduce eddy current losses.
  • 4. Construction of synchronous machines Two common approaches are used to supply a DC current to the field circuits on the rotating rotor: 1. Supply the DC power from an external DC source to the rotor by means of slip rings and brushes; 2. Supply the DC power from a special DC power source mounted directly on the shaft of the machine. Slip rings are metal rings completely encircling the shaft of a machine but insulated from it. Graphite-like carbon brushes connected to DC terminals ride on each slip ring supplying DC voltage to field windings.
  • 5. Construction of synchronous machines • On large generators and motors, brushless exciters are used. • A brushless exciter is a small AC generator whose field circuits are mounted on the stator and armature circuits are mounted on the rotor shaft. • The exciter generator’s 3-phase output is rectified to DC by a 3-phase rectifier (mounted on the shaft) and fed into the main DC field circuit. • It is possible to adjust the field current on the main machine by controlling the small DC field current of the exciter generator (located on the stator).
  • 6. Construction of synchronous machines To make the excitation of a generator completely independent of any external power source, a small pilot exciter is often added to the circuit. The pilot exciter is an AC generator with a permanent magnet mounted on the rotor shaft and a 3-phase winding on the stator producing the power for the field circuit of the exciter.
  • 7. Construction of synchronous machines A rotor of large synchronous machine with a brushless exciter mounted on the same shaft.
  • 8. Construction of synchronous machines Exciter Rotor pole.
  • 9. Rotation speed of synchronous generator By the definition, synchronous generators produce electricity whose frequency is synchronized with the mechanical rotational speed. Where fe is the electrical frequency, Hz; nm is the rotor speed of the machine, rpm; p is the number of poles. • Steam turbines are most efficient when rotating at high speed; therefore, to generate 60 Hz, they are usually rotating at 3600 rpm (2-pole). • Water turbines are most efficient when rotating at low speeds (200-300 rpm); therefore, they usually turn generators with many poles. me n p f 120 
  • 10. The induced voltage in a 3-phase set of coils In three coils, each of NC turns, placed around the rotor magnetic field, the induced in each coil will have the same magnitude and phases differing by 1200:     ' ' ' ( ) cos ( ) cos 120 ( ) cos 240 aa C m m bb C m m cc C m m e t N t e t N t e t N t              Peak voltage: max C mE N  max 2 CE N f  RMS voltage: 2 2 2CA CNE Nf f    
  • 11. Internal generated voltage of a synchronous generator The magnitude of internal generated voltage induced in a given stator is 2A CE N f K    where K is a constant representing the construction of the machine,  is flux in it and  is its rotation speed. Since flux in the machine depends on the field current through it, the internal generated voltage is a function of the rotor field current. Magnetization curve (open-circuit characteristic) of a synchronous machine
  • 12. Equivalent circuit of a synchronous generator The internally generated voltage in a single phase of a synchronous machine EA is not usually the voltage appearing at its terminals. It equals to the output voltage V only when there is no armature current in the machine. The reasons that the armature voltage EA is not equal to the output voltage V are: 1. Distortion of the air-gap magnetic field caused by the current flowing in the stator (armature reaction); 2. Self-inductance of the armature coils; 3. Resistance of the armature coils;
  • 13. Equivalent circuit of a synchronous generator Armature reaction: • When the rotor of a synchronous generator is spinning, a voltage EA is induced in its stator. • When a load is connected, a current starts flowing creating a magnetic field in machine’s stator. • This stator magnetic field BS adds to the rotor (main) magnetic field BR affecting the total magnetic field and, therefore, the phase voltage. Lagging load
  • 14. Equivalent circuit of a synchronous generator The load current IA will create a stator magnetic field BS, which will produce the armature reaction voltage Estat. Therefore, the phase voltage will be A statV E E   The net magnetic flux will be net R SB B B  Rotor field Stator field
  • 15. Equivalent circuit of a synchronous generator Since the armature reaction voltage lags the current by 90 degrees, it can be modeled by stat AE jXI  The phase voltage is then A AV E jXI   However, in addition to armature reactance effect, the stator coil has a self-inductance LA (XA is the corresponding reactance) and the stator has resistance RA. The phase voltage is thus A A A A AV E jXI jX I RI    
  • 16. Equivalent circuit of a synchronous generator Often, armature reactance and self- inductance are combined into the synchronous reactance of the machine: S AX X X  A S A AV E jX I RI    Therefore, the phase voltage is The equivalent circuit of a 3-phase synchronous generator is shown. The adjustable resistor Radj controls the field current and, therefore, the rotor magnetic field.
  • 17. Equivalent circuit of a synchronous generator A synchronous generator can be Y- or -connected: The terminal voltage will be 3T TV V for Y V V for       
  • 18. Equivalent circuit of a synchronous generator Since – for balanced loads – the three phases of a synchronous generator are identical except for phase angles, per-phase equivalent circuits are often used.
  • 19. Phasor diagram of a synchronous generator (similar to that of a transformer) Since the voltages in a synchronous generator are AC voltages, they are usually expressed as phasors. A vector plot of voltages and currents within one phase is called a phasor diagram. A phasor diagram of a synchronous generator with a unity power factor (resistive load) Lagging power factor (inductive load): a larger than for leading PF internal generated voltage EA is needed to form the same phase voltage. Leading power factor (capacitive load).
  • 20. The Synchronous generator operating alone The behavior of a synchronous generator varies greatly under load depending on the power factor of the load and on whether the generator is working alone or in parallel with other synchronous generators. Although most of the synchronous generators in the world operate as parts of large power systems, we start our discussion assuming that the synchronous generator works alone. Unless otherwise stated, the speed of the generator is assumed constant.
  • 21. The Synchronous generator operating alone Effects of load changes A increase in the load is an increase in the real and/or reactive power drawn from the generator. Assuming the same power factor of the load, a change in load will change the magnitude of the armature current IA. However, the angle will be the same (for a constant PF). Thus, the armature reaction voltage jXSIA will be larger for the increased load. Since the magnitude of the internal generated voltage is constant A S AE V jX I  Armature reaction voltage vector will “move parallel” to its initial position.
  • 22. The Synchronous generator operating alone Increase load effect on generators with Lagging PF Leading PF Unity PF
  • 23. The Synchronous generator operating alone 1. For lagging (inductive) loads, the phase (and terminal) voltage decreases significantly. 2. For unity power factor (purely resistive) loads, the phase (and terminal) voltage decreases slightly. 3. For leading (capacitive) loads, the phase (and terminal) voltage rises. Generally, when a load on a synchronous generator is added, the following changes can be observed: Effects of adding loads can be described by the voltage regulation: 100% nl fl fl V V VR V   Where Vnl is the no-load voltage of the generator and Vfl is its full-load voltage.
  • 24. The Synchronous generator operating alone • A synchronous generator operating at a lagging power factor has a fairly large positive voltage regulation. • A synchronous generator operating at a unity power factor has a small positive voltage regulation. • A synchronous generator operating at a leading power factor often has a negative voltage regulation. Normally, a constant terminal voltage supplied by a generator is desired. Since the armature reactance cannot be controlled, an obvious approach to adjust the terminal voltage is by controlling the internal generated voltage EA = K. This may be done by changing flux in the machine while varying the value of the field resistance RF, which is summarized: 1. Decreasing the field resistance increases the field current in the generator. 2. An increase in the field current increases the flux in the machine. 3. An increased flux leads to the increase in the internal generated voltage. 4. An increase in the internal generated voltage increases the terminal voltage of the generator.
  • 25. Power and torque in synchronous generators A synchronous generator needs to be connected to a prime mover whose speed is reasonably constant (to ensure constant frequency of the generated voltage) for various loads. The applied mechanical power in app mP   is partially converted to electricity 3 cosconv ind m A AP E I    Where  is the angle between EA and IA. The power-flow diagram of a synchronous generator.
  • 26. Power and torque in synchronous generators The real and reactive output powers of the synchronous generator are 3 cos 3 cosout T L AP V I V I   3 sin 3 sinout T L AQ V I V I   Recall that the power factor angle  is the angle between V and IA and not the angle between EA and IA. In real synchronous machines of any size, the armature resistance RA << XS and, therefore, the armature resistance can be ignored. Thus, a simplified phasor diagram indicates that sin cos A A S E I X   
  • 27. Power and torque in synchronous generators Then the real output power of the synchronous generator can be approximated as 3 sinA out S V E P X    We observe that electrical losses are assumed to be zero since the resistance is neglected. Therefore: conv outP P Here  is the power angle of the machine – the angle between V and EA. This is different from the power factor angle θ The maximum power can be supplied by the generator when  = 900: max 3 A S V E P X  
  • 28. Generator P-f Curve • All generators are driven by a prime mover, such as a steam, gas, water, wind turbines, diesel engines, etc. • Regardless the power source, most of prime movers tend to slow down with increasing the load. • The speed drop (SD) of a prime mover is defined as: • Most prime movers have a speed drop from 2% to 4%. Most governors have a mechanism to adjust the turbine’s no-load speed (set-point adjustment).
  • 30. Generator Q-V Curve • A similar relationship can be derived for the reactive power Q and terminal voltage VT. – When supplying a lagging load to a synchronous generator, its terminal voltage decreases. – When adding a leading load to a synchronous generator, its terminal voltage increases. • Both the frequency-power and terminal voltage vs. reactive power characteristics are important for parallel operations of generators.
  • 31. Example A generator with no-load frequency of 61.0 Hz and a slope of 1 MW/Hz is connected to Load 1 consuming 1 MW of real power at 0.8 PF lagging. Load 2 (that to be connected to the generator) consumes a real power of 0.8 MW at 0.707 PF lagging. 1. Find the operating frequency of the system before the switch is closed. (ans. 60 Hz) 2. Find the operating frequency of the system after the switch is closed. (ans. 59.2 Hz) 3. What action could an operator take to restore the system frequency to 60 Hz after both loads are connected to the generator? (ans. increase the governor no-load set point by 0.8 Hz)
  • 32. Generator Operating Alone • When a generator is operating alone, – The real and reactive powers generated are the amounts demanded by the load. – The governor of the generator controls the operating frequency of the circuit. – The field current controls the terminal voltage of the circuit.
  • 33. Generators connected in parallel • Most of synchronous generators are operating in parallel with other synchronous generators to supply power to the same power system. • Obvious advantages of this arrangement are: – Several generators can supply a bigger load; – A failure of a single generator does not result in a total power loss to the load, thus increasing reliability of the power system; – Individual generators may be removed from the power system for maintenance without shutting down the load; – A single generator not operating at near full load might be quite inefficient. While having several generators in parallel, it is possible to turn off some, and operate the rest at near full-load condition.
  • 34. Conditions required for paralleling generators • Closing the switch arbitrarily can cause severe damage. If voltages are not the same (magnitude, frequency, phase, sequence) in both lines, a very large current will flow when the switch is closed. • To avoid this, the following conditions must be met: – The rms line voltages of the two generators must be equal. – The two generators must have the same phase sequence. – The phase angles of two “a” phases must be equal. – The frequency of the oncoming generator must be slightly higher than the frequency of the running system.
  • 35. Steps for paralleling generators (3-light bulb method) 1. Adjust the field current of the oncoming generator to make its terminal voltage equal to the line voltage of the system (use a voltmeter). 2. Compare the phase sequences of the oncoming generator and the running system by examining the three light bulbs. If all three bulbs get bright and dark together, both generators have the same phase sequences. If not, two of the conductors must be altered. 3. The frequency of the oncoming generator is adjusted to be slightly higher than the system’s frequency. 4. When all three lights go out, the voltage across them is zero and, therefore, machines are in phase. This is the time to close the switch.
  • 36. Synchronizing a generator with the utility grid • When a synchronous generator is added to a power system, that system is so large that one additional generator does not cause observable changes to the system. • An infinite bus is a power system that is so large that its voltage and frequency do not vary regardless of how much real and reactive power is drawn from or supplied to it (i.e., the power- frequency and reactive power-voltage characteristics are horizontal:
  • 37. Synchronizing a generator with the utility grid • Consider adding a generator to an infinite bus supplying a load. • The frequency and terminal voltage of all machines must be the same. • Therefore, their power-frequency and reactive power-voltage characteristics can be plotted with a common vertical axis.
  • 38. Synchronizing a generator with the utility grid
  • 39. Parallel operation with the utility grid • If an attempt is made to increase the speed of the generator after it is connected to the infinite bus, the system frequency cannot change and the power supplied by the generator increases. • Note an increase in power (with Vt and EA staying constant), results in an increase in the power angle δ.
  • 40. Parallel operation with the utility grid • By adjusting the field current of the machine, it is possible to make it to make the generator supply or consume reactive power Q. • When the generator is operating in parallel to an infinite bus: – The frequency and terminal voltage of the generator are controlled by the system to which it is connected. – The governor set points of the generator control the real power supplied by the generator to the system. – The generator’s field current controls the reactive power supplied by the generator to the system.
  • 41. Parallel operation of generators of similar size • Unlike the case of an infinite bus, the slope of the frequency-power curve of G1 is of the same order of magnitude as that of G2. • The power-frequency diagram right after G2 is connected to the system is shown to the right. • As indicated previously, in order for G2 to come in as a generator, its frequency should be slightly higher than that of G1.
  • 42. Parallel operation of generators of similar size • Note that the sum of the real and reactive powers supplied by the two generators must equal the real and reactive powers demanded by the load: • If the speed of G2 is increased, its power-frequency diagram shifts upwards. This will in turn – increase the real power supplied by G2 – reduce the real power supplied by G1 – increase the system frequency. – To bring the frequency down, the speed of G2 must be reduced.
  • 43. Example Two generators are set to supply the same load. G1 has a no-load frequency of 61.5 Hz and a slope sp1 of 1 MW/Hz. G2 has a no-load frequency of 61.0 Hz and a slope sp2 of 1 MW/Hz. The two generators are supplying a real load of 2.5 MW at 0.8 PF lagging. a) System frequency? Ans. 60 Hz b) Power generated by G1 and G2? Ans. 1.5 MW and 1 MW c) An additional load of 1 MW is added, find the system frequency and the generator powers? Ans. 59.5 Hz, 2 MW, and 1.5 MW d) Repeat c) after the no-load frequency of G2 is increased by 0.5 Hz? Ans. 59.75 Hz, 1.75 MW and 1.75 MW.
  • 44. Parallel operation of generators of similar size • Similarly, an increase in the field current of G1 will result in – An increase of the reactive power supplied G1, – A reduction of the reactive power supplied G2. – An Increase of the system terminal voltage. – To bring the voltage down, the field current of G1 must be reduced.
  • 45. Synchronous Generator Rating • The purpose of ratings is to protect the machine from damage. Typical ratings of synchronous machines are voltage, speed, apparent power (kVA), power factor, field current and service factor. – The rated frequency of a synchronous machine depends on the power system to which it is connected. Once the operation frequency is determined, only one rotational speed in possible for the given number of poles. – For a given design, the rated voltage is limited by the flux that is capped by the field current. The rated voltage is also limited by the windings insulation breakdown limit. – The maximum acceptable armature current sets the apparent power rating for a generator. The power factor of the armature current is irrelevant for heating the armature windings.
  • 46. Synchronous Generator Real and Reactive Power }cos{ sin sin cos ti d t i d t at at VE X V Q E X V P IVQ IVP        
  • 50. Static Load Models • ZIP model: • Exponential model: • Frequency dependent model: