SlideShare a Scribd company logo
1 of 9
Download to read offline
International Journal of Power Electronics and Drive System (IJPEDS)
Vol. 11, No. 4, December 2020, pp. 2107~2115
ISSN: 2088-8694, DOI: 10.11591/ijpeds.v11.i4.pp2107-2115  2107
Journal homepage: http://ijpeds.iaescore.com
Transient response improvement of direct current using
supplementary control based on ANFIS for rectifier in HVDC
I Made Ginarsa, Agung Budi Muljono, I Made Ari Nrartha, Sultan
Department of Electrical Engineering, University of Mataram, Indonesia
Article Info ABSTRACT
Article history:
Received Nov 14, 2019
Revised Apr 26, 2020
Accepted Jun 16, 2020
Current control scheme is commonly used in high voltage direct current
(HVDC) to transmit power delivery. This scheme is done by adjusting trigger
angle to regulate direct current (DC) in thyristor devices. The adaptive neuro-
fuzzy inference system (ANFIS) control is widely applied for start and fault
operation. But, solution for transient response of DC current in HVDC
system is not clearly studied before. In this paper, supplementary control
(SC) based on ANFIS is proposed to improve the transient response of the
current. The SC control is designed by learning-processes and SC parameters
are obtained by data-training automatically. For current reference at 1.05 pu
and up-ramp at 20 pu/s, maximum overshoot is achieved at 5.12% and 7.72%
for the SC and proportional integral controller (PIC), respectively. When the
up-ramp is increased to 28 pu/s, the maximum overshoot is achieved at
10.01% for the SC. While, the peak overshoot for the PIC is 14.28%.
Keywords:
Firing angle
HVDC
Response improvement
Supplementary control
Up-ramp
This is an open access article under the CC BY-SA license.
Corresponding Author:
I Made Ginarsa,
Department of Electrical Engineering,
University of Mataram,
Jln. Majapahit No. 62, Mataram 63125 NTB, Indonesia.
Email: kadekgin@unram.ac.id
1. INTRODUCTION
Indonesia is an archipelago country that consists of main-islands such as: Sumatera, Java, Sulawesi,
Kalimantan, Nusa Tenggara, Maluku and Papua. Most of the main-island electrical power systems are
independent and separate from each other. Application of high voltage alternating current (HVAC) through
long distance submarine power cable (SPC) is difficult to be built because the SPC has very high line-
charging, high reactive power losses and stability problems [1]. While, high voltage direct current (HVDC)
system is very promising to overcome these problems and to be implemented in Indonesia especially for long
distance HVDC using SPC. Pre-analysis of Java-Sumatra HVDC transmission has been conducted to realize
the HVDC application in Indonesia power system inter-connection [2, 3].
The HVDC transmission is applied to transmit bulk electric power through transmission line over a
long distance using overhead conductors or SPC [4]. The HVDC technology has several advantages
compared to competing HVAC technology such as: Power plant can be located far from consumer, not need
reactive power compensation in long distance HVDC transmission, can be inter-connected to HVAC for
difference frequencies, to transmit more capacity of power delivery [5, 6]. Also, development and operation
costs of the HVDC are cheaper than the HVAC for long-distance transmission and friendly for
environment [7]. A HVDC-link connected to a HVAC will prevent fault and oscillation propagate to
neighbor the HVAC. Moreover, the HVDC is able to improve stability of inter-connected HVAC by
modulating power in response to small/large disturbances [8], line commutated converter (LCC)-HVDC links
are applied to enhance stability of permanent magnet synchronous generator offshore wind turbine [9] and
 ISSN: 2088-8694
Int J Pow Elec & Dri Syst, Vol. 11, No. 4, December 2020 : 2107 – 2115
2108
large-scale integration of wind, solar and marine-current generation [10] fed to multi-machine
power systems (PS).
To help the HVDC in operation and control managements, a comprehensive small-signal model of a
LCC-voltage source converter (VSC) HVDC-link and their eigen-analysis of the model are built and impact
of parameter to system damping is studied. The DC-current control parameters of LCC, DC-voltage control
parameters of VSC DC-side capacitor of VSC and smoothing reactor of LCC have large effect to the
damping oscillatory mode of power systems. Also, larger PI gain of the VSC, and smaller PI gain of the LCC
are able to improve damping of the dominant mode [11]. A model for hybrid multi-in-feed HVDC (H-MIDC)
link and its controller are developed to simulate small-signal model. The H-MIDC link is located close in a
common receiving AC grid. The dynamic performances of H-MIDC are improved using optimized
parameters control [12]. Analysis of HVDC-line with off-shore resources and storage devices is done using
optimal power flow strategy [13]. Some differential equation sets are designed to develop HVDC in average-
value model to simplify the HVDC model without including switching-device mechanism and neglected high
frequency [14], and this model is applied to power system analysis [15]. Dynamic properties in both AC/DC
of HVDC-link are presented on frequency-domain model. This model is used to control and stability analysis
of overall power systems, that Part I describes fixed-commutation overlap method [16] and Part II explains
the model upgraded by varying-overlap angle [17].
However, HVDC control has non-linear characteristics include several properties in
converter/inverter devices, transformer saturation and presence of filters in AC/DC-side and harmonic
generation. The non-linear characteristics make the regulation of HVDC are complicated and challenged in
PS and power electronic fields. Predictive control is proposed to improve PS stability [18]. Control parameter
is optimized to improve the HVDC performance using electromagnetic transient analysis program [19]. The
HVDC control is simplified by building a novel space-vector pulse width modulation (SVPWM) [20] and
simplification of SVPWM 3-dimension control is applied to regulate 3-phase 4-leg of inverters [21].
Artificial intelligent application is very attractive research and it is implemented in some fields such
as: Genetic algorithm to optimize robustness and efficiency of micro-grid DC solar-system structures [22],
firefly algorithm to optimize PID parameter of automatic generation control in multi-area [23]. Grey wolf
optimizer (GWO) is used to optimize power flow wind farm integrated to PS [24], to optimize power
allocation to realize plug-and-play capability of micro-grid system [25], to minimize operating cost and
active power loss by optimizing reactive power generation [26] and to estimate input-output parameters of
thermal plant [27]. The GWO is also applied on power system stabilizer to damp local oscillation in multi-
machine [28] and inter-area oscillation in wide-area [29]. While, development of neural control is done
in [30] to improve stability of power transmission and in [31] to help dispatcher in decision making on
mapping of PS fault instantaneously. Fuzzy control is developed to design of wind-PV combined-generator
model [32], to regulate induction motor speed combined by proportional-integral control [33], and fuzzy
type-2 to control permanent magnet synchronous machine through digital-signal processing [34]. The neural
network-fuzzy model is applied to advance direct power control for grid-connected to distributed
generator [35]. An adaptive neuro-fuzzy inference system (ANFIS) has been designed to regulate
converter [36] and inverter [37] of HVDC-line, and to control voltage collapse in PS [38]. Also, the ANFIS
scheme is used to control, detect fault, and protect [39, 40] of HVDC, and to protect HVDC-light from AC
fault [41]. Moreover, combination of ANFIS and fuzzy type-2 has been used to maintain large-scale
PS stability [42].
Transient responses of voltage/current are very important in PS and power electronic researches
because these responses should be constrained to protect the systems and devices from over-voltage/current
on its operation. To improve transient response, some control schemes are proposed such as: ANFIS
algorithm based on additional PID-loop to improve transient voltage response in PS [43], feed-forward
compensation method [44], feed-forward capacitor [45], triangular wave generator through to adjust its
slope [46] for DC-DC converters and feed-forward compensation model for DC-AC converter based on
space vector-pulse width modulation [47]. However, research topic of transient responses improvement in
HVDC using ANFIS control scheme has not been clearly discussed. This remaining paper is organized as
follows: Design of supplementary control based on ANFIS model is described in Section 2. Results and
discussion are explained in Section 3. And, finally conclusion is summarized in Section 4.
2. DESIGN OF SUPPLEMENTARY CONTROL BASED ON ANFIS MODEL
Supplementary control (SC) is proposed in thyristor-based rectifier of HVDC system to help the PI
regulator to reduce transient direct current response, especially when the up-ramp value was higher (such as:
20 pu/s or more). Where, the SC is defined by PI control plus ANFIS-based control. The HVDC and its
control blocks are taken from [48] and controller of the system is shown in Figure 1(a). While, current
Int J Pow Elec & Dri Syst ISSN: 2088-8694 
Transient response improvement of direct current using supplementary control based … (I.M. Ginarsa)
2109
reference pattern of HVDC at start-up is illustrated in Figure 1(b). The ANFIS-based controller is built by
ANFIS model [49]. Block diagram of SC is depicted in Figure 2.
The ANFIS controller of SC is developed by training process. Inputs data of training process are
current error (Ierr), its derivative (dIerr) and additional trigger angle from the supplementary control (AlphaSC,
αSC). Where, the current error was obtained by difference of direct current (Id) and reference current (Iref). In
the training process, the (Ierr; dIerr) and (AlphaSC, αSC) were formed into 5,000 input-output matrix data. The
training process was done in off-line session. Result of the training process was a SC controller based on
ANFIS model as shown in Figure 3. The ANFIS structure and pattern of input-output control are shown in
Figures 4(a) and (b), respectively. Furthermore, the ANFIS model is embedded to fuzzy controller in
Simulink [50] model as described in Figure 3. Next, the SC performance is evaluated in Section 3.
(a) (b)
Figure 1. Control scheme for HVDC transmission system,
(a) diagram block of thyristor-based rectifier, (b) current reference (Iref) pattern at up-ramp 20 pu/s
Figure 2. Trigger angle (Alpha) controller using PI regulator
Figure 3. Supplementary controller (SC) to improve transient current response
 ISSN: 2088-8694
Int J Pow Elec & Dri Syst, Vol. 11, No. 4, December 2020 : 2107 – 2115
2110
(a) (b)
Figure 4. Supplementary control (SC) based on ANFIS Sugeno model,
(a) ANFIS structure for SC, (b) pattern of input-output control
3. RESULTS AND DISCUSSION
In this research, simulation was done by using Matlab/Simulink [50] on a PC computer. Which is
specified as follows: Proc. Intel-i5-7400, cache capacity 6,0 MB, Freq. 3.0 GHz, LGA 1151 windows 7
operating system. The SC was tested to regulate firing angle on rectifier-side of HVDC system.
3.1. Improvement of transient response when final value of current reference set at 0.95 pu
In this case, PI controller parameters were set at the default values P=4500; and I = 45 [48]. The
master controller parameters were set as follows. Up-ramp rate was increased at the values of 20, 22, 24, 26
and 28 pu/s. Moreover, the up-ramp time and up-ramp final value were taken at the time of 0.3 s and the
value of 0.95 pu, respectively. The simulation results are described in Figures 5, 6 and listed in Table 1.
Figure 5 and Table 1 show the transient responses of direct current for respective controllers when
the up-ramp rate of current reference was set at 20 pu/s. There are depicted that response parameters for PI
controller (PIC) were as follows: 9.85%, 3.843%, 0.459 s, 0.548 s and 5.953×10−2% for maximum overshoot
(Mp), start-time error (estr), peak time (tp), settling time (ts) and steady-state error (ess), respectively.
Meanwhile, the response parameters that given by SC were as follows: 5.63%, 3.797%, 0.458 s, 0.545 s and
3.233×10−2% for maximum overshoot, start-time error, peak time, settling time and steady-state error,
respectively. Figure 6 and Table 1 illustrate the transient responses when the up-ramp rate of current
reference was increased to 28 pu/s. Responses of the PI controller were as follows: 15.18%, 2.708%, 0.452 s,
0.568 s and 5.651×10−2% for maximum overshoot, start-time error, peak time, settling time and steady-state
error. While, the responses that given by the SC were: 9.77%, 2.856 %, 0.451 s, 0.550 s and 2.564×10−2%
for maximum overshoot, start-time error, peak time, settling time and steady-state error, respectively. The SC
is able to improve the transient response of direct current based on the response parameters are given in
this scenario.
Figure 5. Transient response improvement for direct
current at current reference 0.95 pu.
Figure 6. Transient response for current reference
0.95 and up-ramp 28.0 pu/s.
Int J Pow Elec & Dri Syst ISSN: 2088-8694 
Transient response improvement of direct current using supplementary control based … (I.M. Ginarsa)
2111
Table 1. The performance of SC when final value of current reference at 0.95 pu.
PI control (PIC) Supplementary control (SC)
up-ramp
(pu/s)
Mp
(%)
estr
(%)
tp
(t)
ts
(t)
ess
×10−2
(%)
Mp
(%)
estr
(%)
tp
(t)
ts
(t)
ess
×10−2
(%)
20 9.85 3.843 0.459 0.548 5.953 5.63 3.797 0.458 0.545 3.233
22 11.84 3.446 0.461 0.557 0.669 6.91 3.666 0.454 0.546 2.295
24 13.27 3.156 0.460 0.561 2.054 7.92 3.415 0.453 0.547 4.574
26 14.29 3.157 0.454 0.565 4.209 9.86 3.201 0.453 0.548 4.011
28 15.18 2.708 0.452 0.568 5.651 9.77 2.856 0.451 0.550 2.564
3.2. Performance of SC when the final value of current reference set at 1.0 pu
Furthermore, the final value of current reference was increased to 1.0 pu. The up-ramp rates and up-
ramp time were set as same as the values and time before. The results are depicted in Figures 7, 8 and in
Table 2. From Figure 7 and Table 2 we can see that the maximum overshoot was achieved at the value of
8.96 and 5.73% for the PIC and SC when the up-ramp rate at 20 pu/s, respectively. The start-time error was
at the values of 3.638 and 4.025%. Peak time was at time 0.464 s for the both controllers. The settling time
was achieved at time 0.568 and 0.550 s. The steady-state error was achieved at the values of (3.042 and
0.368)×10−2
% for the PIC and SC, respectively. Figure 7 shows that maximum overshoot of the PI controller
is higher than the supplementary controller.
The Figure 8 and Table 2 shows maximum overshoot was achieved at the value of 14.22 and 9.75%
for the PI controller and supplementary controller when the up-ramp rate at 28 pu/s, respectively. The start-
time error was at the values of 2.451 and 2.627%. Peak time was at time 0.452 and 0.451 s. The settling time
was achieved at time 0.579 and 0.569 s. And, the steady-state error was at the values of (0.202 and
0.374)×10−2
% for the PI controller and supplementary controller, respectively.
It is found that the maximum overshoot of direct current equipped by supplementary controller is
lower than PI controller. Also, settling time of the supplementary controller is shorter than the other. It is
found that the supplementary controller is more effective to reduce peak overshoot of direct current than the
PI controller in this scenario.
Figure 7. Transient response for current reference 1.0 Figure 8. Transient response for current reference
1.0 and up-ramp 28.0 pu/s
Table 2. The performance of supplementary control at current reference = 1.0 pu.
PI control (PIC) Supplementary control (SC)
up-ramp
(pu/s)
Mp
(%)
estr
(%)
tp
(t)
ts
(t)
ess
×10−2
(%)
Mp
(%)
estr
(%)
tp
(t)
ts
(t)
ess
×10−2
(%)
20 8.96 3.638 0.464 0.568 3.042 5.73 4.025 0.464 0.550 0.368
22 10.65 3.326 0.461 0.571 1.264 7.36 3.686 0.459 0.553 1.901
24 12.03 3.036 0.460 0.573 2.154 7.73 3.321 0.453 0.559 0.906
26 13.25 3.036 0.454 0.575 0.380 9.02 2.972 0.453 0.564 0.072
28 14.22 2.451 0.452 0.579 0.202 9.75 2.627 0.451 0.569 0.374
 ISSN: 2088-8694
Int J Pow Elec & Dri Syst, Vol. 11, No. 4, December 2020 : 2107 – 2115
2112
3.3. Improvement of direct current transient response at 1.05 pu
Moreover, the system is tested by increasing the final value of direct current again to 1.05 pu. The
results are described in Figures 9, 10 and Table 3. Table 3 depicts maximum overshoots of direct current
were achieved at the values of 7.72-14.28% for the PIC when the up-ramp rates were taken at 20-28 pu/s,
respectively. Errors at start-time are achieved at the values of 3.63-2.46%. The settling time for the PIC were
at times of 0.571-0.578 s. The steady-state errors were achieved at the values of (3.042-0.202)×10−2
%. Figure
9 shows transient responses of DC current for PI and SC for up-ramp rates at 20 pu/s.
While, the maximum overshoots of direct current were achieved at the values of 5.73-9.75% for the
SC when the up-ramp rates were at 20-28 pu/s. Errors at start-time were at the values of 4.025-2.627%. The
settling times were at times of 0.550-0.569 s. The steady-state errors were achieved at the values of (0.368-
0.374)×10−2
%. Also, transient response of DC current is depicted in Figure 10 for the PIC and SC controller,
respectively, when the up-ramp rate is given at 28 pu/s.
Figure 9. Transient response improvement for
current reference 1.05 pu.
Figure 10. Transient response improvement for
current reference 1.05 pu and up-ramp 28.0 pu/s.
Based on the results, peak overshoot and settling time of SC are lower and shorter than the peak
overshoot and settling of the PIC. On the other hand, the error at start-time and steady state error for all
controllers are small (< 5%) and very small (< 10−2
%), respectively. The SC is more effective to reduce the
transient response of direct current than the PIC for the up-ramp of reference current at 20-28 pu/s.
Table 3. The performance of supplementary control when reference current was set at 1.05 pu.
PI control (PIC) Supplementary control (SC)
up-ramp
(pu/s)
Mp
(%)
estr
(%)
tp
(t)
ts
(t)
ess
×10−2
(%)
Mp
(%)
estr
(%)
tp
(t)
ts
(t)
ess
×10−2
(%)
20 7.72 3.215 0.466 0.571 2.863 5.12 4.343 0.463 0.548 4.844
22 10.12 3.611 0.463 0.573 4.906 5.99 4.302 0.460 0.552 3.787
24 12.34 3.293 0.461 0.575 6.537 6.64 3.518 0.460 0.563 0.967
26 13.38 3.293 0.460 0.579 6.319 8.22 3.220 0.455 0.568 1.936
28 14.28 2.793 0.457 0.580 7.028 10.01 2.992 0.460 0.570 2.735
4. CONCLUSION
Application of SC for HVDC based on ANFIS model is done in this research. The design process of
ANFIS model is also explained before the control applied to the HVDC system. Simulation results of HVDC
with SC are compared to the results from proportional integral control (PIC) to verify the validity of the
proposed controller. The results show that maximum overshoots are achieved at 5.63% and 9.85% for SC and
PIC, when current reference and up-ramp are set at 0.95 pu and 20 pu/s. Moreover, the current reference and
up-ramp are increased to 1.05 pu and 28 pu/s. The maximum overshoots for SC and PIC are achieved at
10.01% and 14.01% and 14.28%, respectively. The proposed control is able to improve the transient response
by reducing the maximum overshoot for all simulations.
Int J Pow Elec & Dri Syst ISSN: 2088-8694 
Transient response improvement of direct current using supplementary control based … (I.M. Ginarsa)
2113
ACKNOWLEDGEMENTS
We appreciate to the Directorate General of Higher Education (DGHE) Republic of Indonesia to
support of this research through decentralization Penelitian Dasar Unggulan Perguruan Tinggi (PDUPT)
scheme 2018-2019 University of Mataram.
REFERENCES
[1] A. Korompili, Q. Wu and H. Zhao, “Review of VSC HVDC connection for offshore wind power integration,”
IJEPES, vol. 59, 2016.
[2] R. Faizal, et al., “Sumatra-Java transmission system modelling and system impact analysis,” Proc. of Conf. on
PowerTech IEEE, Einhoven. pp. 1-6, 2015.
[3] D. Sudarmaji, G.C. Paap and L.v.d. Sluis, “Review of steady state analysis of HVDC interconnection of Java-
Sumatera,” Proc. of Conf. on Elect. Eng. and Informatic, Bandung Indonesia, 2007.
[4] V.K. Sood, “HVDC and FACTS Controllers: Applications of Static Controllers in Power Systems,” Kluwer
Academic Pub, New York USA, 2004.
[5] J. Arillaga, Y.H. Liu and N.R. Watson, “Flexible power transmission: The DC options,” J. Wiley & Sons, 1990.
[6] V.F. Pires, J.Fialho and J.F.Silva, “HVDC transmission system using multilevel power converters based on dual
three-phase two-level inverters,” IJEPES, vol. 65, pp. 191-200, 2015.
[7] R. Rudervall, J.P. Charpentier and R. Sharma, “High voltage direct current (HVDC) transmission systems
technology review paper,” Energy Week 2000, Washington DC, USA, 7-8 March 2014.
[8] C.R. Bayliss, B.J. Hardy, Transmission and Distribution Electrical Engineering, 4th ed., Newnes Elsevier, 2012.
[9] L. Wang and M.S.-N. Thi, “Stability enhancement of a PMSG-based offshore wind farm fed to a multi-machine
system through an LCC-HVDC link,” IEEE Trans. on Pow. Syst., vol. 98, 2013.
[10] L. Wang and M.S.-N. Thi, “Stability enhancement of large-scale integration of wind, solar, and marine-current
power generation fed to an SG-based power system through an LCC-HVDC link,” IEEE Trans. on Sustain. Energy,
vol. 5, no.1, pp. 160-170, 2014.
[11] C. Guo, Z. Yin, C. Zhao and R. Iravani, “Small signal dynamics of hybrid LCC-VSC HVDC system,” IJEPES, vol.
98, pp. 362-372, 2018.
[12] C. Guo, W. Liu, C. Zhao, X. Ni, “Small signal dynamics and control parameter optimization of hybrid multi-infeed
HVDC system,” IJEPES, vol. 98, pp. 409-418, 2018.
[13] M.J. Carrizosa, et al., “Optimal power flow in multi-terminal HVDC grid with offshore wind farm and storage
devices,” IJEPES, vol. 65, pp. 291-298, 2015.
[14] H. Atigechi, et al., “Dynamic average-value model of CIGRE HVDC Benchmark system,” IEEE trans. on Power
Del., vol. 29, no. 5, pp. 2046-2054, 2014.
[15] S. Chinforoosh, et al., “Definitions and applications of dynamic average-value models for analysis of power
systems,” IEEE trans. on Power Del., vol. 25, no. 4, pp. 2655-2669, 2010.
[16] P.F. de Toledo, L. Angquist and A.-P. Nee, “Frequency domain model of an HVDC link with a line-commutated
current-source converter. Part I: Fixed overlap,” IET Gene. Transm. & Distrib., vol. 3, pp. 757-771, 2009.
[17] P.F. de Toledo, L. Angquist and A.-P. Nee, “Frequency domain model of an HVDC link with a line-commutated
current-source converter. Part II: Varying overlap,” IET Gene. Transm. & Distrib., vol. 3, pp. 771-782, 2009.
[18] M. Darabian, A. Jalilvand and A. Azari, “Power system stability enhancement in the presence of renewable energy
and HVDC line based on predictive control strategy,” IJEPES, vol. 80, pp. 363-373, 2016.
[19] X. Zhang, et al., “Optimizing HVDC control parameters in multi-infeed HVDC system based on electromagnetic
transient analysis,” IJEPES, vol. 49, pp. 449-454, 2013.
[20] Z. Yinhai, et al., “A novel SVPWM modulation scheme,” Applied Power Electronics Conference and Exposition
(APEC) 2009, Twenty-Fourth Annual IEEE, pp. 128-131, 2009.
[21] X.S. Li, et al., “Analysis and simplification of three-dimensional space vector PWM for three-phase four-leg
inverters,” IEEE Trans. on Industrial Electronics, vol. 58, pp. 450-464, Feb 2011.
[22] M. D'Antonio, C. Shi, B. Wu and A. Khaligh, “Design and optimization of a solar power conversion system for
space applications,” IEEE Trans. on Industry Appl., vol. 55, no. 3, pp. 2310-2319, 2019.
[23] K. Jagatheesan, B. Anand, S. Samanta, N. Dey, A.S. Ashour and V.E. Balas, “Design of a proportional-integral-
derivative controller for an automatic generation control of multi-area power thermal systems using firefly
algorithm,” IEEE/CAA J. of Auto. Sinica, vol. 6, no. 2, pp. 503-515, 2019.
[24] M. Siavash, C. Pfeifer, A. Rahiminejad, B. Vahidi, “An application of grey wolf optimizer for optimal power flow
of wind integrated power systems,” Int. Conf. on EPE, Cezh Republic, 2017.
[25] J. Zhang, X. Wang, L. Ma, “An optimal power allocation scheme of microgrid using grey wolf optimizer,” IEEE
Access, vol. 7, pp. 137608-137619, 2019.
[26] S. Raj, B. Bhattacharyya, “Reactive power planning by opposition- grey wolf optimization method,” Int Trans.
Electr. Energ. Syst., Wiley, 2018.
[27] O. Zebua, I.M. Ginarsa, I.M.A. Nrartha, “GWO-based estimation of input-output parameters of thermal power
plants,” TELKOMNIKA (Telecommunication Computing Electronics and Control), vol. 18, no. 4, pp. 2235-2244,
2020.
[28] P. Dhanaselvi, S.S. Reddy, R. Kiranmayi, “Optimal tuning of multi-machine power system stabilizer parameter
using grey wolf optimization (GWO) algorithm,” Book Chap. Lect. Note in Elect. Eng., Springer Singapore, vol.
569, 2020.
 ISSN: 2088-8694
Int J Pow Elec & Dri Syst, Vol. 11, No. 4, December 2020 : 2107 – 2115
2114
[29] M.R. Shakarami, L.F. Davoukhani, “Wide-area power system stabilizer design based on grey wolf optimization
algorithm considering the time delay,” EPSR Journal, vol. 133, pp. 149-159, 2016.
[30] B. Abdelkrim, Y. Merzong, “Robust stability power in transmission line with the use of UPFC system and neural
controllers based adaptive control,” International Journal of Power Electronics and Drive System (IJPEDS), vol.
10, no. 3, pp. 1281-1296, 2019.
[31] M.R. Khaldi, “Power systems voltage stability using artificial neural network,” JICPST/IEEE Power India Conf.,
New Delhi India, 12-15 Oct. 2008.
[32] D.M. Atia, et al., “Modeling and control PV-wind hybrid system based on fuzzy logic control technique,”
TELKOMNIKA (Telecommunication Computing Electronics and Control), vol. 10, no. 3, pp. 431-441, 2012.
[33] R. Arulmozhiyal and K. Baskaran, “Implementation of a fuzzy PI controller for speed control of induction motors
using FPGA,” Journal of Power Electronics, vol. 10, pp. 65-71, 2010.
[34] S. Wahsh, Y. Ahmed and E.A. Elzahab, “Implementation of type-2 fuzzy logic controller in PMSM drives using
DSP,” International Journal of Power Electronics and Drive System (IJPEDS), vol. 9, no. 3, pp. 1098-1105, 2018.
[35] M. Jamma, et al., “Advanced direct power control for grid-connected distribution generation system based on fuzzy
logic and artificial neural networks techniques,” International Journal of Power Electronics and Drive System
(IJPEDS), vol. 8, no. 3, pp. 979-989 2017.
[36] I.M. Ginarsa, A.B. Muljono, I.M.A. Nrartha, “Simulation of ANFIS controller to line commutation based on
current source converter high voltage direct current system,” Proc. of CENCON IEEE, Yogya Indonesia, 16-17
Oct., 2019.
[37] I.M. Ginarsa, et al., “ANFIS-based controller to regulate firing angle of inverter in average value model-high
voltage direct current transmission system,” Proc. of ICSGTEIS IEEE, Bali Indonesia, pp. 1-6, 2018.
[38] I.M. Ginarsa, A. Soeprijanto and M.H. Purnomo, “Controlling chaos and voltage collapse using an ANFIS-based
composite controller-static var compensator (CC-SVC) in power systems”, IJEPES, vol. 46, 2013.
[39] N. Bawane, A.G. Kothari and D.P. Kothari, “ANFIS based control and fault detection of HVDC converter,” HAIT
Journal of Science and Engineering B, vol. 2, pp. 673-689, 2006.
[40] M.Z. Hossain, et al., “Performance analysis of a high voltage DC (HVDC) transmission system under steady state
and faulted conditions,” Telkomnika, vol. 8, no. 12, 2014.
[41] M.A. Kumar, N.V. Srikanth, “An adaptive neuro-fuzzy inference system controlled space vector pulse width
modulation based HVDC light transmission system under AC fault conditions, Cent. Eur. J.E., vol. 4, no. 1, 2014.
[42] A.B. Muljono, et al., “Coordination of adaptive neuro-fuzzy inference system (ANFIS) and type-2 fuzzy logic
power system stabilizer (T2FLS) to improve a large-scale power system stability,” International Journal of
Electrical and Computer Engineering (IJECE), vol. 8, no. 1, pp76-86, 2018.
[43] I.M. Ginarsa, et al., “Improvement of transient voltage response using an additional PID-loop on ANFIS-based
composite controller-SVC (CC-SVC) to control chaos and voltage collapse in power systems,” IEEJ trans. on
Power and Energy, vol. 131, no.10, pp. 836-848, 2011.
[44] K. Sato, T. Sato and M. Sonehara, “Transient response improvement of digitally controlled DC-DC converter with
feedforward compensation,” Proc. of INTELEC, Broadbeach Queenland, Australia pp. 609-614, 2017.
[45] B. Butterfield, “Optimizing transient response of internally compensated DC-DC converter with feedforward
capacitor,” Application report, Texas Inst., 2017.
[46] S. Wu, et al., “Transient response improvement of DC-DC buck converter by a slope adjustable triangular wave
generator”, IEICE Trans. on Comm., vol. E98, no.10, pp. 288-295, 2015.
[47] S.-J. Hong, et al., “Improvement of transient state response through feedforward compensation method of AC/DC
power conversion system based on space vector pulse width modulation (SVPWM),” Energies J., vol. 11, 2018.
[48] S. Casario, “Thyristor-based HVDC transmission system: In Matlab demo,” Hydro Quebec, Canada, 2013.
[49] J.-S.R. Jang, C.T. Sun and E. Mizuni, “Neuro-fuzzy and Soft Computing: A Computational Approach to Learning
and Machine Intelligence,” Prentice Hall Int. Inc., USA, 1997.
[50] Matlab, The Mathworks, Inc. 2013.
BIOGRAPHIES OF AUTHORS
I Made Ginarsa was born in Darmasaba, Badung Bali Indonesia 1970. He received in B.Eng,
M.Eng and Ph.D in elect. eng. UNUD (1997), UGM (2001) and ITS (2012). Since 1999 he was
a lecturer at Elect. Eng., University of Mataram. In 2010 he was a member of EPS Lab.,
Kumamoto Univ. His research interests are dynamic and stability, nonlinear dynamic, voltage
stability and artificial intelligent application in power systems. He was an active author, co-
author and invited reviewer on national and international publications.
Int J Pow Elec & Dri Syst ISSN: 2088-8694 
Transient response improvement of direct current using supplementary control based … (I.M. Ginarsa)
2115
Agung B. Muljono, was born in Purwodadi Grobogan Indonesia, 1971. In 1998 he joined
University of Mataram, Indonesia, as a lecturer. His research interests include transmission and
distribution, dynamic and stability, artificial intelligent application, and energy planning and
distributed generation in power systems. He received the B. Eng and M. Eng. in Electrical Eng.
from Malang Institute of Technology (1996) and UGM (2000), respectively. He was an active
author and co-author research papers and served as editorial board in Dielektrika Journal.
I Made Ari Nrartha, was born in Denpasar Bali Indonesia, 1973. He received in B.Eng and
M.Eng in electrical eng. from ITS (1997) and UGM (2001). Since 1999 he was a lecturer at
Electrical Eng., University of Mataram. His research interests are power system dynamic and
stability, transmission and distribution, optimization, power quality and artificial intelligent
application in power systems. He was an active author and co-author research papers in national
and international journal, and served as editorial board in Dielektrika Journal.
S. Sultan, was born in Bulukumba South Sulawesi, Indonesia. He received the B. Eng. and
M.Eng. degrees in Electrical Eng. from Hassanudin University (1995) and UGM (2005),
respectively. In 1997 he was a lecturer in University of Mataram, Indonesia. His research
interests include power system transmission and distribution, power system dynamic and
stability in power systems. He was an active author and co-author research papers in national
and international journal, and served as editor in chief of Dielektrika Journal 2010-2018.

More Related Content

What's hot

A review on SVC control for power system stability with and without auxiliary...
A review on SVC control for power system stability with and without auxiliary...A review on SVC control for power system stability with and without auxiliary...
A review on SVC control for power system stability with and without auxiliary...journalBEEI
 
Enhanced Crowbar Protection for Fault Ride through Capability of Wind Generat...
Enhanced Crowbar Protection for Fault Ride through Capability of Wind Generat...Enhanced Crowbar Protection for Fault Ride through Capability of Wind Generat...
Enhanced Crowbar Protection for Fault Ride through Capability of Wind Generat...IAES-IJPEDS
 
International Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentInternational Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentIJERD Editor
 
SRF CONTROLLED DVR FOR COMPENSATION OF BALANCED AND UNBALANCED VOLTAGE DISTUR...
SRF CONTROLLED DVR FOR COMPENSATION OF BALANCED AND UNBALANCED VOLTAGE DISTUR...SRF CONTROLLED DVR FOR COMPENSATION OF BALANCED AND UNBALANCED VOLTAGE DISTUR...
SRF CONTROLLED DVR FOR COMPENSATION OF BALANCED AND UNBALANCED VOLTAGE DISTUR...IAEME Publication
 
IRJET- A Review of Power Control Strategies for DFIG based Wind Energy Conver...
IRJET- A Review of Power Control Strategies for DFIG based Wind Energy Conver...IRJET- A Review of Power Control Strategies for DFIG based Wind Energy Conver...
IRJET- A Review of Power Control Strategies for DFIG based Wind Energy Conver...IRJET Journal
 
Analysis of Total Harmonic Distortion (THD) Level of Distribution Network Usi...
Analysis of Total Harmonic Distortion (THD) Level of Distribution Network Usi...Analysis of Total Harmonic Distortion (THD) Level of Distribution Network Usi...
Analysis of Total Harmonic Distortion (THD) Level of Distribution Network Usi...IJERA Editor
 
Influencing Power Flow and Transient Stability by Static Synchronous Series C...
Influencing Power Flow and Transient Stability by Static Synchronous Series C...Influencing Power Flow and Transient Stability by Static Synchronous Series C...
Influencing Power Flow and Transient Stability by Static Synchronous Series C...ijeei-iaes
 
Fault Ride-Through capability of DSTATCOM for Distributed Wind Generation System
Fault Ride-Through capability of DSTATCOM for Distributed Wind Generation SystemFault Ride-Through capability of DSTATCOM for Distributed Wind Generation System
Fault Ride-Through capability of DSTATCOM for Distributed Wind Generation SystemIJPEDS-IAES
 
LOAD SHEDDING DESIGN FOR AN INDUSTRIAL COGENERATION SYSTEM
LOAD SHEDDING DESIGN FOR AN INDUSTRIAL COGENERATION SYSTEMLOAD SHEDDING DESIGN FOR AN INDUSTRIAL COGENERATION SYSTEM
LOAD SHEDDING DESIGN FOR AN INDUSTRIAL COGENERATION SYSTEMELELIJ
 
Power system operation &amp; control( Switching & Controlling System)
Power system operation &amp; control( Switching & Controlling System)Power system operation &amp; control( Switching & Controlling System)
Power system operation &amp; control( Switching & Controlling System)UthsoNandy
 

What's hot (19)

A review on SVC control for power system stability with and without auxiliary...
A review on SVC control for power system stability with and without auxiliary...A review on SVC control for power system stability with and without auxiliary...
A review on SVC control for power system stability with and without auxiliary...
 
Enhanced Crowbar Protection for Fault Ride through Capability of Wind Generat...
Enhanced Crowbar Protection for Fault Ride through Capability of Wind Generat...Enhanced Crowbar Protection for Fault Ride through Capability of Wind Generat...
Enhanced Crowbar Protection for Fault Ride through Capability of Wind Generat...
 
ISLANDING DETECTION TECHNIQUE FOR DISTRIBUTED GENERATION SYSTEM
ISLANDING DETECTION TECHNIQUE FOR DISTRIBUTED GENERATION SYSTEMISLANDING DETECTION TECHNIQUE FOR DISTRIBUTED GENERATION SYSTEM
ISLANDING DETECTION TECHNIQUE FOR DISTRIBUTED GENERATION SYSTEM
 
Maximum power point tracking algorithms for wind energy systems
Maximum power point tracking algorithms for wind energy systemsMaximum power point tracking algorithms for wind energy systems
Maximum power point tracking algorithms for wind energy systems
 
Droop control approach for power sharing in AC microgrid
Droop control approach for power sharing in AC microgrid Droop control approach for power sharing in AC microgrid
Droop control approach for power sharing in AC microgrid
 
International Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentInternational Journal of Engineering Research and Development
International Journal of Engineering Research and Development
 
SRF CONTROLLED DVR FOR COMPENSATION OF BALANCED AND UNBALANCED VOLTAGE DISTUR...
SRF CONTROLLED DVR FOR COMPENSATION OF BALANCED AND UNBALANCED VOLTAGE DISTUR...SRF CONTROLLED DVR FOR COMPENSATION OF BALANCED AND UNBALANCED VOLTAGE DISTUR...
SRF CONTROLLED DVR FOR COMPENSATION OF BALANCED AND UNBALANCED VOLTAGE DISTUR...
 
IRJET- A Review of Power Control Strategies for DFIG based Wind Energy Conver...
IRJET- A Review of Power Control Strategies for DFIG based Wind Energy Conver...IRJET- A Review of Power Control Strategies for DFIG based Wind Energy Conver...
IRJET- A Review of Power Control Strategies for DFIG based Wind Energy Conver...
 
Analysis of Total Harmonic Distortion (THD) Level of Distribution Network Usi...
Analysis of Total Harmonic Distortion (THD) Level of Distribution Network Usi...Analysis of Total Harmonic Distortion (THD) Level of Distribution Network Usi...
Analysis of Total Harmonic Distortion (THD) Level of Distribution Network Usi...
 
Influencing Power Flow and Transient Stability by Static Synchronous Series C...
Influencing Power Flow and Transient Stability by Static Synchronous Series C...Influencing Power Flow and Transient Stability by Static Synchronous Series C...
Influencing Power Flow and Transient Stability by Static Synchronous Series C...
 
Detailed analysis of grid connected and islanded operation modes based on P/U...
Detailed analysis of grid connected and islanded operation modes based on P/U...Detailed analysis of grid connected and islanded operation modes based on P/U...
Detailed analysis of grid connected and islanded operation modes based on P/U...
 
Advanced control strategy of DFIG during symmetrical grid fault
Advanced control strategy of DFIG during symmetrical grid faultAdvanced control strategy of DFIG during symmetrical grid fault
Advanced control strategy of DFIG during symmetrical grid fault
 
Integration of Renewable Distributed Generators in Distribution System
Integration of Renewable Distributed Generators in Distribution System Integration of Renewable Distributed Generators in Distribution System
Integration of Renewable Distributed Generators in Distribution System
 
Resynchronisation or reconnection or transition of microgrid with the utility...
Resynchronisation or reconnection or transition of microgrid with the utility...Resynchronisation or reconnection or transition of microgrid with the utility...
Resynchronisation or reconnection or transition of microgrid with the utility...
 
Fault Ride-Through capability of DSTATCOM for Distributed Wind Generation System
Fault Ride-Through capability of DSTATCOM for Distributed Wind Generation SystemFault Ride-Through capability of DSTATCOM for Distributed Wind Generation System
Fault Ride-Through capability of DSTATCOM for Distributed Wind Generation System
 
LOAD SHEDDING DESIGN FOR AN INDUSTRIAL COGENERATION SYSTEM
LOAD SHEDDING DESIGN FOR AN INDUSTRIAL COGENERATION SYSTEMLOAD SHEDDING DESIGN FOR AN INDUSTRIAL COGENERATION SYSTEM
LOAD SHEDDING DESIGN FOR AN INDUSTRIAL COGENERATION SYSTEM
 
Modular multilevel converter (MMC) based STATCOM with vector control and virt...
Modular multilevel converter (MMC) based STATCOM with vector control and virt...Modular multilevel converter (MMC) based STATCOM with vector control and virt...
Modular multilevel converter (MMC) based STATCOM with vector control and virt...
 
Power system operation &amp; control( Switching & Controlling System)
Power system operation &amp; control( Switching & Controlling System)Power system operation &amp; control( Switching & Controlling System)
Power system operation &amp; control( Switching & Controlling System)
 
Bc35306309
Bc35306309Bc35306309
Bc35306309
 

Similar to Transient response improvement of direct current using supplementary control based on ANFIS for rectifier in HVDC

Transient response mitigation using type-2 fuzzy controller optimized by grey...
Transient response mitigation using type-2 fuzzy controller optimized by grey...Transient response mitigation using type-2 fuzzy controller optimized by grey...
Transient response mitigation using type-2 fuzzy controller optimized by grey...IJECEIAES
 
IRJET- Comparative Study of Common Methods of Frequency Response using MTDC G...
IRJET- Comparative Study of Common Methods of Frequency Response using MTDC G...IRJET- Comparative Study of Common Methods of Frequency Response using MTDC G...
IRJET- Comparative Study of Common Methods of Frequency Response using MTDC G...IRJET Journal
 
Online voltage stability margin assessment
Online voltage stability margin assessmentOnline voltage stability margin assessment
Online voltage stability margin assessmentNaganathan G Sesaiyan
 
Enhanced dynamic performance of grid feeding distributed generation under va...
Enhanced dynamic performance of grid feeding distributed  generation under va...Enhanced dynamic performance of grid feeding distributed  generation under va...
Enhanced dynamic performance of grid feeding distributed generation under va...IJECEIAES
 
Low Voltage Ride-through for Doubly Fed Induction Generator Using Battery-Sto...
Low Voltage Ride-through for Doubly Fed Induction Generator Using Battery-Sto...Low Voltage Ride-through for Doubly Fed Induction Generator Using Battery-Sto...
Low Voltage Ride-through for Doubly Fed Induction Generator Using Battery-Sto...IJPEDS-IAES
 
Power-Sharing of Parallel Inverters in Micro-Grids via Droop control and Virt...
Power-Sharing of Parallel Inverters in Micro-Grids via Droop control and Virt...Power-Sharing of Parallel Inverters in Micro-Grids via Droop control and Virt...
Power-Sharing of Parallel Inverters in Micro-Grids via Droop control and Virt...IRJET Journal
 
Controllers For A VSC-HVDC Link Connected To A Weak AC System
Controllers For A VSC-HVDC Link Connected To A Weak AC SystemControllers For A VSC-HVDC Link Connected To A Weak AC System
Controllers For A VSC-HVDC Link Connected To A Weak AC SystemIOSR Journals
 
IRJET- Improvement of Power System Stability in Wind Turbine by using Facts D...
IRJET- Improvement of Power System Stability in Wind Turbine by using Facts D...IRJET- Improvement of Power System Stability in Wind Turbine by using Facts D...
IRJET- Improvement of Power System Stability in Wind Turbine by using Facts D...IRJET Journal
 
A novel fuzzy based controller to reduce circulating currents in parallel int...
A novel fuzzy based controller to reduce circulating currents in parallel int...A novel fuzzy based controller to reduce circulating currents in parallel int...
A novel fuzzy based controller to reduce circulating currents in parallel int...IJECEIAES
 
Coordination of Adaptive Neuro Fuzzy Inference System (ANFIS) and Type-2 Fuzz...
Coordination of Adaptive Neuro Fuzzy Inference System (ANFIS) and Type-2 Fuzz...Coordination of Adaptive Neuro Fuzzy Inference System (ANFIS) and Type-2 Fuzz...
Coordination of Adaptive Neuro Fuzzy Inference System (ANFIS) and Type-2 Fuzz...IJECEIAES
 
Improved Transient Compensation using PI-SRF Control Scheme Based UHVDC for O...
Improved Transient Compensation using PI-SRF Control Scheme Based UHVDC for O...Improved Transient Compensation using PI-SRF Control Scheme Based UHVDC for O...
Improved Transient Compensation using PI-SRF Control Scheme Based UHVDC for O...IRJET Journal
 
IRJET-Robot Control by using Human Hand Gestures
IRJET-Robot Control by using Human Hand GesturesIRJET-Robot Control by using Human Hand Gestures
IRJET-Robot Control by using Human Hand GesturesIRJET Journal
 
Modeling Optimization Voltage Index Unified Power Flow Controller Equivalent ...
Modeling Optimization Voltage Index Unified Power Flow Controller Equivalent ...Modeling Optimization Voltage Index Unified Power Flow Controller Equivalent ...
Modeling Optimization Voltage Index Unified Power Flow Controller Equivalent ...IJMTST Journal
 
IRJET- Enhancement of Power Flow Capability in Power System using UPFC- A RevieW
IRJET- Enhancement of Power Flow Capability in Power System using UPFC- A RevieWIRJET- Enhancement of Power Flow Capability in Power System using UPFC- A RevieW
IRJET- Enhancement of Power Flow Capability in Power System using UPFC- A RevieWIRJET Journal
 
IRJET- Level of Service & Throughput Maximization at Operational Toll Plazas
IRJET- Level of Service & Throughput Maximization at Operational Toll PlazasIRJET- Level of Service & Throughput Maximization at Operational Toll Plazas
IRJET- Level of Service & Throughput Maximization at Operational Toll PlazasIRJET Journal
 

Similar to Transient response improvement of direct current using supplementary control based on ANFIS for rectifier in HVDC (20)

Transient response mitigation using type-2 fuzzy controller optimized by grey...
Transient response mitigation using type-2 fuzzy controller optimized by grey...Transient response mitigation using type-2 fuzzy controller optimized by grey...
Transient response mitigation using type-2 fuzzy controller optimized by grey...
 
IRJET- Comparative Study of Common Methods of Frequency Response using MTDC G...
IRJET- Comparative Study of Common Methods of Frequency Response using MTDC G...IRJET- Comparative Study of Common Methods of Frequency Response using MTDC G...
IRJET- Comparative Study of Common Methods of Frequency Response using MTDC G...
 
Performance improvement of decentralized control for bidirectional converters...
Performance improvement of decentralized control for bidirectional converters...Performance improvement of decentralized control for bidirectional converters...
Performance improvement of decentralized control for bidirectional converters...
 
Current control of grid-connected inverter using integral sliding mode contro...
Current control of grid-connected inverter using integral sliding mode contro...Current control of grid-connected inverter using integral sliding mode contro...
Current control of grid-connected inverter using integral sliding mode contro...
 
Online voltage stability margin assessment
Online voltage stability margin assessmentOnline voltage stability margin assessment
Online voltage stability margin assessment
 
Enhanced dynamic performance of grid feeding distributed generation under va...
Enhanced dynamic performance of grid feeding distributed  generation under va...Enhanced dynamic performance of grid feeding distributed  generation under va...
Enhanced dynamic performance of grid feeding distributed generation under va...
 
Low Voltage Ride-through for Doubly Fed Induction Generator Using Battery-Sto...
Low Voltage Ride-through for Doubly Fed Induction Generator Using Battery-Sto...Low Voltage Ride-through for Doubly Fed Induction Generator Using Battery-Sto...
Low Voltage Ride-through for Doubly Fed Induction Generator Using Battery-Sto...
 
Power-Sharing of Parallel Inverters in Micro-Grids via Droop control and Virt...
Power-Sharing of Parallel Inverters in Micro-Grids via Droop control and Virt...Power-Sharing of Parallel Inverters in Micro-Grids via Droop control and Virt...
Power-Sharing of Parallel Inverters in Micro-Grids via Droop control and Virt...
 
Controllers For A VSC-HVDC Link Connected To A Weak AC System
Controllers For A VSC-HVDC Link Connected To A Weak AC SystemControllers For A VSC-HVDC Link Connected To A Weak AC System
Controllers For A VSC-HVDC Link Connected To A Weak AC System
 
D010121832
D010121832D010121832
D010121832
 
Stability analysis of photovoltaic system under grid faults
Stability analysis of photovoltaic system under grid faultsStability analysis of photovoltaic system under grid faults
Stability analysis of photovoltaic system under grid faults
 
IRJET- Improvement of Power System Stability in Wind Turbine by using Facts D...
IRJET- Improvement of Power System Stability in Wind Turbine by using Facts D...IRJET- Improvement of Power System Stability in Wind Turbine by using Facts D...
IRJET- Improvement of Power System Stability in Wind Turbine by using Facts D...
 
A novel fuzzy based controller to reduce circulating currents in parallel int...
A novel fuzzy based controller to reduce circulating currents in parallel int...A novel fuzzy based controller to reduce circulating currents in parallel int...
A novel fuzzy based controller to reduce circulating currents in parallel int...
 
Coordination of Adaptive Neuro Fuzzy Inference System (ANFIS) and Type-2 Fuzz...
Coordination of Adaptive Neuro Fuzzy Inference System (ANFIS) and Type-2 Fuzz...Coordination of Adaptive Neuro Fuzzy Inference System (ANFIS) and Type-2 Fuzz...
Coordination of Adaptive Neuro Fuzzy Inference System (ANFIS) and Type-2 Fuzz...
 
Improved Transient Compensation using PI-SRF Control Scheme Based UHVDC for O...
Improved Transient Compensation using PI-SRF Control Scheme Based UHVDC for O...Improved Transient Compensation using PI-SRF Control Scheme Based UHVDC for O...
Improved Transient Compensation using PI-SRF Control Scheme Based UHVDC for O...
 
IRJET-Robot Control by using Human Hand Gestures
IRJET-Robot Control by using Human Hand GesturesIRJET-Robot Control by using Human Hand Gestures
IRJET-Robot Control by using Human Hand Gestures
 
Modeling Optimization Voltage Index Unified Power Flow Controller Equivalent ...
Modeling Optimization Voltage Index Unified Power Flow Controller Equivalent ...Modeling Optimization Voltage Index Unified Power Flow Controller Equivalent ...
Modeling Optimization Voltage Index Unified Power Flow Controller Equivalent ...
 
J1103035766
J1103035766J1103035766
J1103035766
 
IRJET- Enhancement of Power Flow Capability in Power System using UPFC- A RevieW
IRJET- Enhancement of Power Flow Capability in Power System using UPFC- A RevieWIRJET- Enhancement of Power Flow Capability in Power System using UPFC- A RevieW
IRJET- Enhancement of Power Flow Capability in Power System using UPFC- A RevieW
 
IRJET- Level of Service & Throughput Maximization at Operational Toll Plazas
IRJET- Level of Service & Throughput Maximization at Operational Toll PlazasIRJET- Level of Service & Throughput Maximization at Operational Toll Plazas
IRJET- Level of Service & Throughput Maximization at Operational Toll Plazas
 

More from International Journal of Power Electronics and Drive Systems

More from International Journal of Power Electronics and Drive Systems (20)

Adaptive backstepping controller design based on neural network for PMSM spee...
Adaptive backstepping controller design based on neural network for PMSM spee...Adaptive backstepping controller design based on neural network for PMSM spee...
Adaptive backstepping controller design based on neural network for PMSM spee...
 
Classification and direction discrimination of faults in transmission lines u...
Classification and direction discrimination of faults in transmission lines u...Classification and direction discrimination of faults in transmission lines u...
Classification and direction discrimination of faults in transmission lines u...
 
Integration of artificial neural networks for multi-source energy management ...
Integration of artificial neural networks for multi-source energy management ...Integration of artificial neural networks for multi-source energy management ...
Integration of artificial neural networks for multi-source energy management ...
 
Rotating blade faults classification of a rotor-disk-blade system using artif...
Rotating blade faults classification of a rotor-disk-blade system using artif...Rotating blade faults classification of a rotor-disk-blade system using artif...
Rotating blade faults classification of a rotor-disk-blade system using artif...
 
Artificial bee colony algorithm applied to optimal power flow solution incorp...
Artificial bee colony algorithm applied to optimal power flow solution incorp...Artificial bee colony algorithm applied to optimal power flow solution incorp...
Artificial bee colony algorithm applied to optimal power flow solution incorp...
 
Soft computing and IoT based solar tracker
Soft computing and IoT based solar trackerSoft computing and IoT based solar tracker
Soft computing and IoT based solar tracker
 
Comparison of roughness index for Kitka and Koznica wind farms
Comparison of roughness index for Kitka and Koznica wind farmsComparison of roughness index for Kitka and Koznica wind farms
Comparison of roughness index for Kitka and Koznica wind farms
 
Primary frequency control of large-scale PV-connected multi-machine power sys...
Primary frequency control of large-scale PV-connected multi-machine power sys...Primary frequency control of large-scale PV-connected multi-machine power sys...
Primary frequency control of large-scale PV-connected multi-machine power sys...
 
Performance of solar modules integrated with reflector
Performance of solar modules integrated with reflectorPerformance of solar modules integrated with reflector
Performance of solar modules integrated with reflector
 
Generator and grid side converter control for wind energy conversion system
Generator and grid side converter control for wind energy conversion systemGenerator and grid side converter control for wind energy conversion system
Generator and grid side converter control for wind energy conversion system
 
Wind speed modeling based on measurement data to predict future wind speed wi...
Wind speed modeling based on measurement data to predict future wind speed wi...Wind speed modeling based on measurement data to predict future wind speed wi...
Wind speed modeling based on measurement data to predict future wind speed wi...
 
Comparison of PV panels MPPT techniques applied to solar water pumping system
Comparison of PV panels MPPT techniques applied to solar water pumping systemComparison of PV panels MPPT techniques applied to solar water pumping system
Comparison of PV panels MPPT techniques applied to solar water pumping system
 
Prospect of renewable energy resources in Bangladesh
Prospect of renewable energy resources in BangladeshProspect of renewable energy resources in Bangladesh
Prospect of renewable energy resources in Bangladesh
 
A novel optimization of the particle swarm based maximum power point tracking...
A novel optimization of the particle swarm based maximum power point tracking...A novel optimization of the particle swarm based maximum power point tracking...
A novel optimization of the particle swarm based maximum power point tracking...
 
Voltage stability enhancement for large scale squirrel cage induction generat...
Voltage stability enhancement for large scale squirrel cage induction generat...Voltage stability enhancement for large scale squirrel cage induction generat...
Voltage stability enhancement for large scale squirrel cage induction generat...
 
Electrical and environmental parameters of the performance of polymer solar c...
Electrical and environmental parameters of the performance of polymer solar c...Electrical and environmental parameters of the performance of polymer solar c...
Electrical and environmental parameters of the performance of polymer solar c...
 
Short and open circuit faults study in the PV system inverter
Short and open circuit faults study in the PV system inverterShort and open circuit faults study in the PV system inverter
Short and open circuit faults study in the PV system inverter
 
A modified bridge-type nonsuperconducting fault current limiter for distribut...
A modified bridge-type nonsuperconducting fault current limiter for distribut...A modified bridge-type nonsuperconducting fault current limiter for distribut...
A modified bridge-type nonsuperconducting fault current limiter for distribut...
 
The new approach minimizes harmonics in a single-phase three-level NPC 400 Hz...
The new approach minimizes harmonics in a single-phase three-level NPC 400 Hz...The new approach minimizes harmonics in a single-phase three-level NPC 400 Hz...
The new approach minimizes harmonics in a single-phase three-level NPC 400 Hz...
 
Comparison of electronic load using linear regulator and boost converter
Comparison of electronic load using linear regulator and boost converterComparison of electronic load using linear regulator and boost converter
Comparison of electronic load using linear regulator and boost converter
 

Recently uploaded

Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingrakeshbaidya232001
 
Glass Ceramics: Processing and Properties
Glass Ceramics: Processing and PropertiesGlass Ceramics: Processing and Properties
Glass Ceramics: Processing and PropertiesPrabhanshu Chaturvedi
 
Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)simmis5
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxAsutosh Ranjan
 
Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxupamatechverse
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINEMANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINESIVASHANKAR N
 
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptx
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptxBSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptx
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptxfenichawla
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Dr.Costas Sachpazis
 
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordAsst.prof M.Gokilavani
 
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Call Girls in Nagpur High Profile
 
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Christo Ananth
 
MANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTING
MANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTINGMANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTING
MANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTINGSIVASHANKAR N
 
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Bookingdharasingh5698
 
University management System project report..pdf
University management System project report..pdfUniversity management System project report..pdf
University management System project report..pdfKamal Acharya
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...ranjana rawat
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and workingUNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and workingrknatarajan
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 

Recently uploaded (20)

Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writing
 
Glass Ceramics: Processing and Properties
Glass Ceramics: Processing and PropertiesGlass Ceramics: Processing and Properties
Glass Ceramics: Processing and Properties
 
Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptx
 
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINEDJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
 
Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptx
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
 
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINEMANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
 
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptx
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptxBSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptx
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptx
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
 
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
 
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
 
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
 
MANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTING
MANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTINGMANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTING
MANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTING
 
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
 
University management System project report..pdf
University management System project report..pdfUniversity management System project report..pdf
University management System project report..pdf
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
 
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and workingUNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 

Transient response improvement of direct current using supplementary control based on ANFIS for rectifier in HVDC

  • 1. International Journal of Power Electronics and Drive System (IJPEDS) Vol. 11, No. 4, December 2020, pp. 2107~2115 ISSN: 2088-8694, DOI: 10.11591/ijpeds.v11.i4.pp2107-2115  2107 Journal homepage: http://ijpeds.iaescore.com Transient response improvement of direct current using supplementary control based on ANFIS for rectifier in HVDC I Made Ginarsa, Agung Budi Muljono, I Made Ari Nrartha, Sultan Department of Electrical Engineering, University of Mataram, Indonesia Article Info ABSTRACT Article history: Received Nov 14, 2019 Revised Apr 26, 2020 Accepted Jun 16, 2020 Current control scheme is commonly used in high voltage direct current (HVDC) to transmit power delivery. This scheme is done by adjusting trigger angle to regulate direct current (DC) in thyristor devices. The adaptive neuro- fuzzy inference system (ANFIS) control is widely applied for start and fault operation. But, solution for transient response of DC current in HVDC system is not clearly studied before. In this paper, supplementary control (SC) based on ANFIS is proposed to improve the transient response of the current. The SC control is designed by learning-processes and SC parameters are obtained by data-training automatically. For current reference at 1.05 pu and up-ramp at 20 pu/s, maximum overshoot is achieved at 5.12% and 7.72% for the SC and proportional integral controller (PIC), respectively. When the up-ramp is increased to 28 pu/s, the maximum overshoot is achieved at 10.01% for the SC. While, the peak overshoot for the PIC is 14.28%. Keywords: Firing angle HVDC Response improvement Supplementary control Up-ramp This is an open access article under the CC BY-SA license. Corresponding Author: I Made Ginarsa, Department of Electrical Engineering, University of Mataram, Jln. Majapahit No. 62, Mataram 63125 NTB, Indonesia. Email: kadekgin@unram.ac.id 1. INTRODUCTION Indonesia is an archipelago country that consists of main-islands such as: Sumatera, Java, Sulawesi, Kalimantan, Nusa Tenggara, Maluku and Papua. Most of the main-island electrical power systems are independent and separate from each other. Application of high voltage alternating current (HVAC) through long distance submarine power cable (SPC) is difficult to be built because the SPC has very high line- charging, high reactive power losses and stability problems [1]. While, high voltage direct current (HVDC) system is very promising to overcome these problems and to be implemented in Indonesia especially for long distance HVDC using SPC. Pre-analysis of Java-Sumatra HVDC transmission has been conducted to realize the HVDC application in Indonesia power system inter-connection [2, 3]. The HVDC transmission is applied to transmit bulk electric power through transmission line over a long distance using overhead conductors or SPC [4]. The HVDC technology has several advantages compared to competing HVAC technology such as: Power plant can be located far from consumer, not need reactive power compensation in long distance HVDC transmission, can be inter-connected to HVAC for difference frequencies, to transmit more capacity of power delivery [5, 6]. Also, development and operation costs of the HVDC are cheaper than the HVAC for long-distance transmission and friendly for environment [7]. A HVDC-link connected to a HVAC will prevent fault and oscillation propagate to neighbor the HVAC. Moreover, the HVDC is able to improve stability of inter-connected HVAC by modulating power in response to small/large disturbances [8], line commutated converter (LCC)-HVDC links are applied to enhance stability of permanent magnet synchronous generator offshore wind turbine [9] and
  • 2.  ISSN: 2088-8694 Int J Pow Elec & Dri Syst, Vol. 11, No. 4, December 2020 : 2107 – 2115 2108 large-scale integration of wind, solar and marine-current generation [10] fed to multi-machine power systems (PS). To help the HVDC in operation and control managements, a comprehensive small-signal model of a LCC-voltage source converter (VSC) HVDC-link and their eigen-analysis of the model are built and impact of parameter to system damping is studied. The DC-current control parameters of LCC, DC-voltage control parameters of VSC DC-side capacitor of VSC and smoothing reactor of LCC have large effect to the damping oscillatory mode of power systems. Also, larger PI gain of the VSC, and smaller PI gain of the LCC are able to improve damping of the dominant mode [11]. A model for hybrid multi-in-feed HVDC (H-MIDC) link and its controller are developed to simulate small-signal model. The H-MIDC link is located close in a common receiving AC grid. The dynamic performances of H-MIDC are improved using optimized parameters control [12]. Analysis of HVDC-line with off-shore resources and storage devices is done using optimal power flow strategy [13]. Some differential equation sets are designed to develop HVDC in average- value model to simplify the HVDC model without including switching-device mechanism and neglected high frequency [14], and this model is applied to power system analysis [15]. Dynamic properties in both AC/DC of HVDC-link are presented on frequency-domain model. This model is used to control and stability analysis of overall power systems, that Part I describes fixed-commutation overlap method [16] and Part II explains the model upgraded by varying-overlap angle [17]. However, HVDC control has non-linear characteristics include several properties in converter/inverter devices, transformer saturation and presence of filters in AC/DC-side and harmonic generation. The non-linear characteristics make the regulation of HVDC are complicated and challenged in PS and power electronic fields. Predictive control is proposed to improve PS stability [18]. Control parameter is optimized to improve the HVDC performance using electromagnetic transient analysis program [19]. The HVDC control is simplified by building a novel space-vector pulse width modulation (SVPWM) [20] and simplification of SVPWM 3-dimension control is applied to regulate 3-phase 4-leg of inverters [21]. Artificial intelligent application is very attractive research and it is implemented in some fields such as: Genetic algorithm to optimize robustness and efficiency of micro-grid DC solar-system structures [22], firefly algorithm to optimize PID parameter of automatic generation control in multi-area [23]. Grey wolf optimizer (GWO) is used to optimize power flow wind farm integrated to PS [24], to optimize power allocation to realize plug-and-play capability of micro-grid system [25], to minimize operating cost and active power loss by optimizing reactive power generation [26] and to estimate input-output parameters of thermal plant [27]. The GWO is also applied on power system stabilizer to damp local oscillation in multi- machine [28] and inter-area oscillation in wide-area [29]. While, development of neural control is done in [30] to improve stability of power transmission and in [31] to help dispatcher in decision making on mapping of PS fault instantaneously. Fuzzy control is developed to design of wind-PV combined-generator model [32], to regulate induction motor speed combined by proportional-integral control [33], and fuzzy type-2 to control permanent magnet synchronous machine through digital-signal processing [34]. The neural network-fuzzy model is applied to advance direct power control for grid-connected to distributed generator [35]. An adaptive neuro-fuzzy inference system (ANFIS) has been designed to regulate converter [36] and inverter [37] of HVDC-line, and to control voltage collapse in PS [38]. Also, the ANFIS scheme is used to control, detect fault, and protect [39, 40] of HVDC, and to protect HVDC-light from AC fault [41]. Moreover, combination of ANFIS and fuzzy type-2 has been used to maintain large-scale PS stability [42]. Transient responses of voltage/current are very important in PS and power electronic researches because these responses should be constrained to protect the systems and devices from over-voltage/current on its operation. To improve transient response, some control schemes are proposed such as: ANFIS algorithm based on additional PID-loop to improve transient voltage response in PS [43], feed-forward compensation method [44], feed-forward capacitor [45], triangular wave generator through to adjust its slope [46] for DC-DC converters and feed-forward compensation model for DC-AC converter based on space vector-pulse width modulation [47]. However, research topic of transient responses improvement in HVDC using ANFIS control scheme has not been clearly discussed. This remaining paper is organized as follows: Design of supplementary control based on ANFIS model is described in Section 2. Results and discussion are explained in Section 3. And, finally conclusion is summarized in Section 4. 2. DESIGN OF SUPPLEMENTARY CONTROL BASED ON ANFIS MODEL Supplementary control (SC) is proposed in thyristor-based rectifier of HVDC system to help the PI regulator to reduce transient direct current response, especially when the up-ramp value was higher (such as: 20 pu/s or more). Where, the SC is defined by PI control plus ANFIS-based control. The HVDC and its control blocks are taken from [48] and controller of the system is shown in Figure 1(a). While, current
  • 3. Int J Pow Elec & Dri Syst ISSN: 2088-8694  Transient response improvement of direct current using supplementary control based … (I.M. Ginarsa) 2109 reference pattern of HVDC at start-up is illustrated in Figure 1(b). The ANFIS-based controller is built by ANFIS model [49]. Block diagram of SC is depicted in Figure 2. The ANFIS controller of SC is developed by training process. Inputs data of training process are current error (Ierr), its derivative (dIerr) and additional trigger angle from the supplementary control (AlphaSC, αSC). Where, the current error was obtained by difference of direct current (Id) and reference current (Iref). In the training process, the (Ierr; dIerr) and (AlphaSC, αSC) were formed into 5,000 input-output matrix data. The training process was done in off-line session. Result of the training process was a SC controller based on ANFIS model as shown in Figure 3. The ANFIS structure and pattern of input-output control are shown in Figures 4(a) and (b), respectively. Furthermore, the ANFIS model is embedded to fuzzy controller in Simulink [50] model as described in Figure 3. Next, the SC performance is evaluated in Section 3. (a) (b) Figure 1. Control scheme for HVDC transmission system, (a) diagram block of thyristor-based rectifier, (b) current reference (Iref) pattern at up-ramp 20 pu/s Figure 2. Trigger angle (Alpha) controller using PI regulator Figure 3. Supplementary controller (SC) to improve transient current response
  • 4.  ISSN: 2088-8694 Int J Pow Elec & Dri Syst, Vol. 11, No. 4, December 2020 : 2107 – 2115 2110 (a) (b) Figure 4. Supplementary control (SC) based on ANFIS Sugeno model, (a) ANFIS structure for SC, (b) pattern of input-output control 3. RESULTS AND DISCUSSION In this research, simulation was done by using Matlab/Simulink [50] on a PC computer. Which is specified as follows: Proc. Intel-i5-7400, cache capacity 6,0 MB, Freq. 3.0 GHz, LGA 1151 windows 7 operating system. The SC was tested to regulate firing angle on rectifier-side of HVDC system. 3.1. Improvement of transient response when final value of current reference set at 0.95 pu In this case, PI controller parameters were set at the default values P=4500; and I = 45 [48]. The master controller parameters were set as follows. Up-ramp rate was increased at the values of 20, 22, 24, 26 and 28 pu/s. Moreover, the up-ramp time and up-ramp final value were taken at the time of 0.3 s and the value of 0.95 pu, respectively. The simulation results are described in Figures 5, 6 and listed in Table 1. Figure 5 and Table 1 show the transient responses of direct current for respective controllers when the up-ramp rate of current reference was set at 20 pu/s. There are depicted that response parameters for PI controller (PIC) were as follows: 9.85%, 3.843%, 0.459 s, 0.548 s and 5.953×10−2% for maximum overshoot (Mp), start-time error (estr), peak time (tp), settling time (ts) and steady-state error (ess), respectively. Meanwhile, the response parameters that given by SC were as follows: 5.63%, 3.797%, 0.458 s, 0.545 s and 3.233×10−2% for maximum overshoot, start-time error, peak time, settling time and steady-state error, respectively. Figure 6 and Table 1 illustrate the transient responses when the up-ramp rate of current reference was increased to 28 pu/s. Responses of the PI controller were as follows: 15.18%, 2.708%, 0.452 s, 0.568 s and 5.651×10−2% for maximum overshoot, start-time error, peak time, settling time and steady-state error. While, the responses that given by the SC were: 9.77%, 2.856 %, 0.451 s, 0.550 s and 2.564×10−2% for maximum overshoot, start-time error, peak time, settling time and steady-state error, respectively. The SC is able to improve the transient response of direct current based on the response parameters are given in this scenario. Figure 5. Transient response improvement for direct current at current reference 0.95 pu. Figure 6. Transient response for current reference 0.95 and up-ramp 28.0 pu/s.
  • 5. Int J Pow Elec & Dri Syst ISSN: 2088-8694  Transient response improvement of direct current using supplementary control based … (I.M. Ginarsa) 2111 Table 1. The performance of SC when final value of current reference at 0.95 pu. PI control (PIC) Supplementary control (SC) up-ramp (pu/s) Mp (%) estr (%) tp (t) ts (t) ess ×10−2 (%) Mp (%) estr (%) tp (t) ts (t) ess ×10−2 (%) 20 9.85 3.843 0.459 0.548 5.953 5.63 3.797 0.458 0.545 3.233 22 11.84 3.446 0.461 0.557 0.669 6.91 3.666 0.454 0.546 2.295 24 13.27 3.156 0.460 0.561 2.054 7.92 3.415 0.453 0.547 4.574 26 14.29 3.157 0.454 0.565 4.209 9.86 3.201 0.453 0.548 4.011 28 15.18 2.708 0.452 0.568 5.651 9.77 2.856 0.451 0.550 2.564 3.2. Performance of SC when the final value of current reference set at 1.0 pu Furthermore, the final value of current reference was increased to 1.0 pu. The up-ramp rates and up- ramp time were set as same as the values and time before. The results are depicted in Figures 7, 8 and in Table 2. From Figure 7 and Table 2 we can see that the maximum overshoot was achieved at the value of 8.96 and 5.73% for the PIC and SC when the up-ramp rate at 20 pu/s, respectively. The start-time error was at the values of 3.638 and 4.025%. Peak time was at time 0.464 s for the both controllers. The settling time was achieved at time 0.568 and 0.550 s. The steady-state error was achieved at the values of (3.042 and 0.368)×10−2 % for the PIC and SC, respectively. Figure 7 shows that maximum overshoot of the PI controller is higher than the supplementary controller. The Figure 8 and Table 2 shows maximum overshoot was achieved at the value of 14.22 and 9.75% for the PI controller and supplementary controller when the up-ramp rate at 28 pu/s, respectively. The start- time error was at the values of 2.451 and 2.627%. Peak time was at time 0.452 and 0.451 s. The settling time was achieved at time 0.579 and 0.569 s. And, the steady-state error was at the values of (0.202 and 0.374)×10−2 % for the PI controller and supplementary controller, respectively. It is found that the maximum overshoot of direct current equipped by supplementary controller is lower than PI controller. Also, settling time of the supplementary controller is shorter than the other. It is found that the supplementary controller is more effective to reduce peak overshoot of direct current than the PI controller in this scenario. Figure 7. Transient response for current reference 1.0 Figure 8. Transient response for current reference 1.0 and up-ramp 28.0 pu/s Table 2. The performance of supplementary control at current reference = 1.0 pu. PI control (PIC) Supplementary control (SC) up-ramp (pu/s) Mp (%) estr (%) tp (t) ts (t) ess ×10−2 (%) Mp (%) estr (%) tp (t) ts (t) ess ×10−2 (%) 20 8.96 3.638 0.464 0.568 3.042 5.73 4.025 0.464 0.550 0.368 22 10.65 3.326 0.461 0.571 1.264 7.36 3.686 0.459 0.553 1.901 24 12.03 3.036 0.460 0.573 2.154 7.73 3.321 0.453 0.559 0.906 26 13.25 3.036 0.454 0.575 0.380 9.02 2.972 0.453 0.564 0.072 28 14.22 2.451 0.452 0.579 0.202 9.75 2.627 0.451 0.569 0.374
  • 6.  ISSN: 2088-8694 Int J Pow Elec & Dri Syst, Vol. 11, No. 4, December 2020 : 2107 – 2115 2112 3.3. Improvement of direct current transient response at 1.05 pu Moreover, the system is tested by increasing the final value of direct current again to 1.05 pu. The results are described in Figures 9, 10 and Table 3. Table 3 depicts maximum overshoots of direct current were achieved at the values of 7.72-14.28% for the PIC when the up-ramp rates were taken at 20-28 pu/s, respectively. Errors at start-time are achieved at the values of 3.63-2.46%. The settling time for the PIC were at times of 0.571-0.578 s. The steady-state errors were achieved at the values of (3.042-0.202)×10−2 %. Figure 9 shows transient responses of DC current for PI and SC for up-ramp rates at 20 pu/s. While, the maximum overshoots of direct current were achieved at the values of 5.73-9.75% for the SC when the up-ramp rates were at 20-28 pu/s. Errors at start-time were at the values of 4.025-2.627%. The settling times were at times of 0.550-0.569 s. The steady-state errors were achieved at the values of (0.368- 0.374)×10−2 %. Also, transient response of DC current is depicted in Figure 10 for the PIC and SC controller, respectively, when the up-ramp rate is given at 28 pu/s. Figure 9. Transient response improvement for current reference 1.05 pu. Figure 10. Transient response improvement for current reference 1.05 pu and up-ramp 28.0 pu/s. Based on the results, peak overshoot and settling time of SC are lower and shorter than the peak overshoot and settling of the PIC. On the other hand, the error at start-time and steady state error for all controllers are small (< 5%) and very small (< 10−2 %), respectively. The SC is more effective to reduce the transient response of direct current than the PIC for the up-ramp of reference current at 20-28 pu/s. Table 3. The performance of supplementary control when reference current was set at 1.05 pu. PI control (PIC) Supplementary control (SC) up-ramp (pu/s) Mp (%) estr (%) tp (t) ts (t) ess ×10−2 (%) Mp (%) estr (%) tp (t) ts (t) ess ×10−2 (%) 20 7.72 3.215 0.466 0.571 2.863 5.12 4.343 0.463 0.548 4.844 22 10.12 3.611 0.463 0.573 4.906 5.99 4.302 0.460 0.552 3.787 24 12.34 3.293 0.461 0.575 6.537 6.64 3.518 0.460 0.563 0.967 26 13.38 3.293 0.460 0.579 6.319 8.22 3.220 0.455 0.568 1.936 28 14.28 2.793 0.457 0.580 7.028 10.01 2.992 0.460 0.570 2.735 4. CONCLUSION Application of SC for HVDC based on ANFIS model is done in this research. The design process of ANFIS model is also explained before the control applied to the HVDC system. Simulation results of HVDC with SC are compared to the results from proportional integral control (PIC) to verify the validity of the proposed controller. The results show that maximum overshoots are achieved at 5.63% and 9.85% for SC and PIC, when current reference and up-ramp are set at 0.95 pu and 20 pu/s. Moreover, the current reference and up-ramp are increased to 1.05 pu and 28 pu/s. The maximum overshoots for SC and PIC are achieved at 10.01% and 14.01% and 14.28%, respectively. The proposed control is able to improve the transient response by reducing the maximum overshoot for all simulations.
  • 7. Int J Pow Elec & Dri Syst ISSN: 2088-8694  Transient response improvement of direct current using supplementary control based … (I.M. Ginarsa) 2113 ACKNOWLEDGEMENTS We appreciate to the Directorate General of Higher Education (DGHE) Republic of Indonesia to support of this research through decentralization Penelitian Dasar Unggulan Perguruan Tinggi (PDUPT) scheme 2018-2019 University of Mataram. REFERENCES [1] A. Korompili, Q. Wu and H. Zhao, “Review of VSC HVDC connection for offshore wind power integration,” IJEPES, vol. 59, 2016. [2] R. Faizal, et al., “Sumatra-Java transmission system modelling and system impact analysis,” Proc. of Conf. on PowerTech IEEE, Einhoven. pp. 1-6, 2015. [3] D. Sudarmaji, G.C. Paap and L.v.d. Sluis, “Review of steady state analysis of HVDC interconnection of Java- Sumatera,” Proc. of Conf. on Elect. Eng. and Informatic, Bandung Indonesia, 2007. [4] V.K. Sood, “HVDC and FACTS Controllers: Applications of Static Controllers in Power Systems,” Kluwer Academic Pub, New York USA, 2004. [5] J. Arillaga, Y.H. Liu and N.R. Watson, “Flexible power transmission: The DC options,” J. Wiley & Sons, 1990. [6] V.F. Pires, J.Fialho and J.F.Silva, “HVDC transmission system using multilevel power converters based on dual three-phase two-level inverters,” IJEPES, vol. 65, pp. 191-200, 2015. [7] R. Rudervall, J.P. Charpentier and R. Sharma, “High voltage direct current (HVDC) transmission systems technology review paper,” Energy Week 2000, Washington DC, USA, 7-8 March 2014. [8] C.R. Bayliss, B.J. Hardy, Transmission and Distribution Electrical Engineering, 4th ed., Newnes Elsevier, 2012. [9] L. Wang and M.S.-N. Thi, “Stability enhancement of a PMSG-based offshore wind farm fed to a multi-machine system through an LCC-HVDC link,” IEEE Trans. on Pow. Syst., vol. 98, 2013. [10] L. Wang and M.S.-N. Thi, “Stability enhancement of large-scale integration of wind, solar, and marine-current power generation fed to an SG-based power system through an LCC-HVDC link,” IEEE Trans. on Sustain. Energy, vol. 5, no.1, pp. 160-170, 2014. [11] C. Guo, Z. Yin, C. Zhao and R. Iravani, “Small signal dynamics of hybrid LCC-VSC HVDC system,” IJEPES, vol. 98, pp. 362-372, 2018. [12] C. Guo, W. Liu, C. Zhao, X. Ni, “Small signal dynamics and control parameter optimization of hybrid multi-infeed HVDC system,” IJEPES, vol. 98, pp. 409-418, 2018. [13] M.J. Carrizosa, et al., “Optimal power flow in multi-terminal HVDC grid with offshore wind farm and storage devices,” IJEPES, vol. 65, pp. 291-298, 2015. [14] H. Atigechi, et al., “Dynamic average-value model of CIGRE HVDC Benchmark system,” IEEE trans. on Power Del., vol. 29, no. 5, pp. 2046-2054, 2014. [15] S. Chinforoosh, et al., “Definitions and applications of dynamic average-value models for analysis of power systems,” IEEE trans. on Power Del., vol. 25, no. 4, pp. 2655-2669, 2010. [16] P.F. de Toledo, L. Angquist and A.-P. Nee, “Frequency domain model of an HVDC link with a line-commutated current-source converter. Part I: Fixed overlap,” IET Gene. Transm. & Distrib., vol. 3, pp. 757-771, 2009. [17] P.F. de Toledo, L. Angquist and A.-P. Nee, “Frequency domain model of an HVDC link with a line-commutated current-source converter. Part II: Varying overlap,” IET Gene. Transm. & Distrib., vol. 3, pp. 771-782, 2009. [18] M. Darabian, A. Jalilvand and A. Azari, “Power system stability enhancement in the presence of renewable energy and HVDC line based on predictive control strategy,” IJEPES, vol. 80, pp. 363-373, 2016. [19] X. Zhang, et al., “Optimizing HVDC control parameters in multi-infeed HVDC system based on electromagnetic transient analysis,” IJEPES, vol. 49, pp. 449-454, 2013. [20] Z. Yinhai, et al., “A novel SVPWM modulation scheme,” Applied Power Electronics Conference and Exposition (APEC) 2009, Twenty-Fourth Annual IEEE, pp. 128-131, 2009. [21] X.S. Li, et al., “Analysis and simplification of three-dimensional space vector PWM for three-phase four-leg inverters,” IEEE Trans. on Industrial Electronics, vol. 58, pp. 450-464, Feb 2011. [22] M. D'Antonio, C. Shi, B. Wu and A. Khaligh, “Design and optimization of a solar power conversion system for space applications,” IEEE Trans. on Industry Appl., vol. 55, no. 3, pp. 2310-2319, 2019. [23] K. Jagatheesan, B. Anand, S. Samanta, N. Dey, A.S. Ashour and V.E. Balas, “Design of a proportional-integral- derivative controller for an automatic generation control of multi-area power thermal systems using firefly algorithm,” IEEE/CAA J. of Auto. Sinica, vol. 6, no. 2, pp. 503-515, 2019. [24] M. Siavash, C. Pfeifer, A. Rahiminejad, B. Vahidi, “An application of grey wolf optimizer for optimal power flow of wind integrated power systems,” Int. Conf. on EPE, Cezh Republic, 2017. [25] J. Zhang, X. Wang, L. Ma, “An optimal power allocation scheme of microgrid using grey wolf optimizer,” IEEE Access, vol. 7, pp. 137608-137619, 2019. [26] S. Raj, B. Bhattacharyya, “Reactive power planning by opposition- grey wolf optimization method,” Int Trans. Electr. Energ. Syst., Wiley, 2018. [27] O. Zebua, I.M. Ginarsa, I.M.A. Nrartha, “GWO-based estimation of input-output parameters of thermal power plants,” TELKOMNIKA (Telecommunication Computing Electronics and Control), vol. 18, no. 4, pp. 2235-2244, 2020. [28] P. Dhanaselvi, S.S. Reddy, R. Kiranmayi, “Optimal tuning of multi-machine power system stabilizer parameter using grey wolf optimization (GWO) algorithm,” Book Chap. Lect. Note in Elect. Eng., Springer Singapore, vol. 569, 2020.
  • 8.  ISSN: 2088-8694 Int J Pow Elec & Dri Syst, Vol. 11, No. 4, December 2020 : 2107 – 2115 2114 [29] M.R. Shakarami, L.F. Davoukhani, “Wide-area power system stabilizer design based on grey wolf optimization algorithm considering the time delay,” EPSR Journal, vol. 133, pp. 149-159, 2016. [30] B. Abdelkrim, Y. Merzong, “Robust stability power in transmission line with the use of UPFC system and neural controllers based adaptive control,” International Journal of Power Electronics and Drive System (IJPEDS), vol. 10, no. 3, pp. 1281-1296, 2019. [31] M.R. Khaldi, “Power systems voltage stability using artificial neural network,” JICPST/IEEE Power India Conf., New Delhi India, 12-15 Oct. 2008. [32] D.M. Atia, et al., “Modeling and control PV-wind hybrid system based on fuzzy logic control technique,” TELKOMNIKA (Telecommunication Computing Electronics and Control), vol. 10, no. 3, pp. 431-441, 2012. [33] R. Arulmozhiyal and K. Baskaran, “Implementation of a fuzzy PI controller for speed control of induction motors using FPGA,” Journal of Power Electronics, vol. 10, pp. 65-71, 2010. [34] S. Wahsh, Y. Ahmed and E.A. Elzahab, “Implementation of type-2 fuzzy logic controller in PMSM drives using DSP,” International Journal of Power Electronics and Drive System (IJPEDS), vol. 9, no. 3, pp. 1098-1105, 2018. [35] M. Jamma, et al., “Advanced direct power control for grid-connected distribution generation system based on fuzzy logic and artificial neural networks techniques,” International Journal of Power Electronics and Drive System (IJPEDS), vol. 8, no. 3, pp. 979-989 2017. [36] I.M. Ginarsa, A.B. Muljono, I.M.A. Nrartha, “Simulation of ANFIS controller to line commutation based on current source converter high voltage direct current system,” Proc. of CENCON IEEE, Yogya Indonesia, 16-17 Oct., 2019. [37] I.M. Ginarsa, et al., “ANFIS-based controller to regulate firing angle of inverter in average value model-high voltage direct current transmission system,” Proc. of ICSGTEIS IEEE, Bali Indonesia, pp. 1-6, 2018. [38] I.M. Ginarsa, A. Soeprijanto and M.H. Purnomo, “Controlling chaos and voltage collapse using an ANFIS-based composite controller-static var compensator (CC-SVC) in power systems”, IJEPES, vol. 46, 2013. [39] N. Bawane, A.G. Kothari and D.P. Kothari, “ANFIS based control and fault detection of HVDC converter,” HAIT Journal of Science and Engineering B, vol. 2, pp. 673-689, 2006. [40] M.Z. Hossain, et al., “Performance analysis of a high voltage DC (HVDC) transmission system under steady state and faulted conditions,” Telkomnika, vol. 8, no. 12, 2014. [41] M.A. Kumar, N.V. Srikanth, “An adaptive neuro-fuzzy inference system controlled space vector pulse width modulation based HVDC light transmission system under AC fault conditions, Cent. Eur. J.E., vol. 4, no. 1, 2014. [42] A.B. Muljono, et al., “Coordination of adaptive neuro-fuzzy inference system (ANFIS) and type-2 fuzzy logic power system stabilizer (T2FLS) to improve a large-scale power system stability,” International Journal of Electrical and Computer Engineering (IJECE), vol. 8, no. 1, pp76-86, 2018. [43] I.M. Ginarsa, et al., “Improvement of transient voltage response using an additional PID-loop on ANFIS-based composite controller-SVC (CC-SVC) to control chaos and voltage collapse in power systems,” IEEJ trans. on Power and Energy, vol. 131, no.10, pp. 836-848, 2011. [44] K. Sato, T. Sato and M. Sonehara, “Transient response improvement of digitally controlled DC-DC converter with feedforward compensation,” Proc. of INTELEC, Broadbeach Queenland, Australia pp. 609-614, 2017. [45] B. Butterfield, “Optimizing transient response of internally compensated DC-DC converter with feedforward capacitor,” Application report, Texas Inst., 2017. [46] S. Wu, et al., “Transient response improvement of DC-DC buck converter by a slope adjustable triangular wave generator”, IEICE Trans. on Comm., vol. E98, no.10, pp. 288-295, 2015. [47] S.-J. Hong, et al., “Improvement of transient state response through feedforward compensation method of AC/DC power conversion system based on space vector pulse width modulation (SVPWM),” Energies J., vol. 11, 2018. [48] S. Casario, “Thyristor-based HVDC transmission system: In Matlab demo,” Hydro Quebec, Canada, 2013. [49] J.-S.R. Jang, C.T. Sun and E. Mizuni, “Neuro-fuzzy and Soft Computing: A Computational Approach to Learning and Machine Intelligence,” Prentice Hall Int. Inc., USA, 1997. [50] Matlab, The Mathworks, Inc. 2013. BIOGRAPHIES OF AUTHORS I Made Ginarsa was born in Darmasaba, Badung Bali Indonesia 1970. He received in B.Eng, M.Eng and Ph.D in elect. eng. UNUD (1997), UGM (2001) and ITS (2012). Since 1999 he was a lecturer at Elect. Eng., University of Mataram. In 2010 he was a member of EPS Lab., Kumamoto Univ. His research interests are dynamic and stability, nonlinear dynamic, voltage stability and artificial intelligent application in power systems. He was an active author, co- author and invited reviewer on national and international publications.
  • 9. Int J Pow Elec & Dri Syst ISSN: 2088-8694  Transient response improvement of direct current using supplementary control based … (I.M. Ginarsa) 2115 Agung B. Muljono, was born in Purwodadi Grobogan Indonesia, 1971. In 1998 he joined University of Mataram, Indonesia, as a lecturer. His research interests include transmission and distribution, dynamic and stability, artificial intelligent application, and energy planning and distributed generation in power systems. He received the B. Eng and M. Eng. in Electrical Eng. from Malang Institute of Technology (1996) and UGM (2000), respectively. He was an active author and co-author research papers and served as editorial board in Dielektrika Journal. I Made Ari Nrartha, was born in Denpasar Bali Indonesia, 1973. He received in B.Eng and M.Eng in electrical eng. from ITS (1997) and UGM (2001). Since 1999 he was a lecturer at Electrical Eng., University of Mataram. His research interests are power system dynamic and stability, transmission and distribution, optimization, power quality and artificial intelligent application in power systems. He was an active author and co-author research papers in national and international journal, and served as editorial board in Dielektrika Journal. S. Sultan, was born in Bulukumba South Sulawesi, Indonesia. He received the B. Eng. and M.Eng. degrees in Electrical Eng. from Hassanudin University (1995) and UGM (2005), respectively. In 1997 he was a lecturer in University of Mataram, Indonesia. His research interests include power system transmission and distribution, power system dynamic and stability in power systems. He was an active author and co-author research papers in national and international journal, and served as editor in chief of Dielektrika Journal 2010-2018.