TRANSFORMER PROTECTION
Transformers
• Transformers are the major power system components which are used at
various voltage levels with the capacity varying from 1kVA to >600 MVA.
• Transformers are widely used devices to transfer power from one circuit to
another circuit magnetically with out physical coupling.
• Any damage to this component results in complete loss of power to one
system.
• The transformer should be protected from the faults to avoid break down of
the transformer which may lead to major interruption in power
transformation.
• To protect it from the fault the typical faults in the fault should be known.
Possible Transformer Faults
Transformer
Faults
Internal Faults
(Winding faults)
Phase to Phase
fault
Phase to earth
fault
Inter-turn fault
External Faults
(Through faults)
Transformer Internal Faults
•Breakdown of the insulating oil.
•Insulation failure of winding.
•Over heat generated in the coils
due to failure of insulation etc.
Transformer External Faults
High Voltage Disturbance in Power Transformer are of two kinds
1.Transient Surge Voltage
•Arcing ground if neutral point is isolated.
•Switching operation of different electrical equipment.
•Atmospheric Lightening Impulse.
2. Power Frequency Over Voltage
As we know that, voltage V = 4.44Φ.f.N ⇒ V ∝ Φ, increased voltage causes
proportionate increase in the working flux. This therefore causes, increased in iron loss
and dis-proportionately large increase in magnetizing current. The increase flux is
diverted from the transformer core to other steel structural parts of the transformer.
Core bolts which normally carry little flux, may be subjected to a large component
of flux diverted from saturated region of the core alongside. Under such condition, the
bolt may be rapidly heated up and destroys their own insulation as well as winding
insulation.
Transformer External Faults Contd…
Protection against lighting surges lighting arrester can be provided.
Transformer Types
There are different kinds of transformers such as
•Two winding or three winding power transformer,
•Auto transformer,
•regulating transformers,
•Earthing transformer,
•Rectifier transformers etc.
Different transformers demand different schemes of transformer
protection depending upon their importance, winding connections, earthing
methods and mode of operation etc.
•It is common practice to provide Buchholz relay protection to all 500 kVA and
above transformers.
•While for all small size distribution transformers, only high voltage fuses are
used as main protective device.
• For all larger rated and important distribution transformers, over current
protection along with restricted earth fault protectionis applied.
•Differential protection should be provided in the transformers rated above 5
MVA
Typical Protections in Transformer
Typically transformer protections are classified as two types.
1) Main protections
2) backup protections.
Main protections:
These are immediate fault clearance protections which
acts instantaneously to clear the faults in the transformer.
Differential protection
Over current protection
Back up protection:
These protections will acts as a back up to the main
protections i.e. if the main protection fails corresponding back up
protection will act and safe guard the device from fault.
Over voltage
Volts/hertz
Negative phase sequence relay
Differential Protection
•Generally Differential protection is provided in the electrical
power transformer rated more than 5MVA. The Differential Protection of
Transformer has many advantages over other schemes of protection.
•The faults occur in the transformer inside the insulating oil can be detected
by Buchholz relay. But if any fault occurs in the transformer but not in oil then it
can not be detected by Buchholz relay.
•Any flash over at the bushings are not adequately covered by Buchholz relay.
•Differential relays can detect such type of faults. Moreover Buchholz relay is
provided in transformer for detecting any internal fault in the transformer but
Differential Protection scheme detects the same in more faster way.
•The differential relays normally response to those faults which occur inside the
differential protection zone of transformer.
Differential Protection Contd…
Basic Considerations for Transformer Differential
Protection:
• Line Current Transformer Primary Ratings
•Current Transformer Connections
•The neutrals of C.T star and power transformer stars
are grounded.
•Selection of C.T and Power transformer tapings.
Differential Protection Contd…
Line Current Transformer Primary Ratings
Consider a two winding, 11kV/132kV, 30MVA Power Transformer.
The rated line current on the 11kV side of the Transformer is:
Irated = MVA / Line Voltage
= 30000000 / (11000)(sqrt 3)
= 1574.59A
Thus, choose a CT with a primary rating of 1600/1.
The line current on the 132kV side of the Transformer is:
Irated = 30000000 / (132000)(sqrt 3)
= 131.22A
Thus choose a CT with a primary rating of 200/1.
Notice that in both cases, the current that the Bias Coils in the relay is
1A at both ends. Any deviation of this 1A will causes an imbalance within the
relay, which will consequently cause protection to operate and isolate the
Transformer.
Differential Protection Contd…
Current Transformer Connections
Merz-Price Protection for Star-Delta
Transformer
Merz-Price Protection for Star-Delta
Transformer Contd…
Merz-Price Protection for Star-Star
Transformer
BUCHHOLZ RELAY
•Buchholz relay is a type of oil and gas actuated protection relay
universally used on all oil immersed transformers having rating more
than 500 kVA.
• Buchholz relay is not provided in transformer having rating below
500 kVA from the point of view of economic considerations.
Why Buchholz relay is used in transformers?
Buchholz relay is used for the protection of transformers from the faults occurring inside the
transformer. Short circuit faults such as inter turn faults, incipient winding faults, and core faults may
occur due to the impulse breakdown of the insulating oil or simply the transformer oil. Buchholz relay
will sense such faults and closes the alarm circuit.
Working principle
Buchholz relay relies on the fact that an electrical fault inside the transformer tank is accompanied by
the generation of gas and if the fault is high enough it will be accompanied by a surge of oil from the
tank to the conservator
Whenever a fault occurs inside the transformer, the oil in the transformer tank gets overheated and
gases are generated. The generation of the gases depends mainly on the intensity of fault produced.
The heat generated during the fault will be high enough to decompose the transformer oil and the
gases produced can be used to detect the winding faults. This is the basic principle behind the working
of the Buchholz relay.
Construction
Buchholz relay can be used in the transformers having the conservators only. It is placed in the pipe
connecting the conservator and the transformer tank. It consists of an oil filled chamber. Two hinged
floats, one at the top of the chamber and the other at the bottom of the chamber which accompanies
a mercury switch each is present in the oil filled chamber. The mercury switch on the upper float is
connected to an external alarm circuit and the mercury switch on the lower is connected to an
external trip circuit.
Buchholz Relay Contd..
Buchholz Relay Contd..
Buchholz relay is employed for the following types faults,
• Core bolt insulation failure
• Local-overheating
• Entrance of air into the oil
• Less of oil due to leakage
• Short circuited lamination due to burns.
Buchholz Relay Contd..
Advantages of Buchholz relay
• The advantage of using a Buchholtz relay is that they indicate incipient faults.
For example, It indicates the faults between turns or heating of core which
enables us to take the transformer out of service before severe damage
occurs.
• Buchholtz relay gives an alarm when the oil level reduces below a certain
level due to leakage of oil from transformer.
• Buchholtz relay gives an audible warning which informs the operator that
there is some fault in the transformer.
• Type of insulation failure of the transformer can also be detected by testing
the gas.
Buchholz Relay Contd..
Limitation of Buchholz relay
1. This type of relay can be used only for transformers with conservators.
2. The relay does not operate when the faults are above the oil level.
3. Buchholz relay does not protect the cables associated with the transformers
below. A separate protection has to be employed for the cables.
4. Due to economic considerations, this relay is not employed for transformers
above 500 kVA.
5. Setting of the mercury switch cannot be too sensitive, otherwise there can be a
false operation due to vibrations,earthquakes. mechanical shocks to the pipe.
6. The operation of this new is unsatisfactory due to slow operating time. (Nearly
0.2 to 0.1 seconds).
Buchholz Relay Contd..
transformerprotection-180102061059.pdf

More Related Content

Similar to transformerprotection-180102061059.pdf

transformer protection
transformer protection transformer protection
transformer protection jason adidela
 
Transformer protection
Transformer protectionTransformer protection
Transformer protectionjawaharramaya
 
Generator and Transformer Protection (PART 2)
Generator and Transformer Protection (PART 2)Generator and Transformer Protection (PART 2)
Generator and Transformer Protection (PART 2)Dr. Rohit Babu
 
Transformer design and protection
Transformer design and protectionTransformer design and protection
Transformer design and protectionashwin fcc
 
Relay and switchgear protection
Relay and switchgear protectionRelay and switchgear protection
Relay and switchgear protectionBinit Das
 
Presentation on KESCO sub-station, kanpur
Presentation on KESCO sub-station, kanpurPresentation on KESCO sub-station, kanpur
Presentation on KESCO sub-station, kanpurShubham Sachan
 
Switchgear and protection engineering Lecture 02.pptx
Switchgear and protection engineering Lecture 02.pptxSwitchgear and protection engineering Lecture 02.pptx
Switchgear and protection engineering Lecture 02.pptxLoitaFredy
 
transformerdesignandprotection-130408132534-phpapp02.ppt
transformerdesignandprotection-130408132534-phpapp02.ppttransformerdesignandprotection-130408132534-phpapp02.ppt
transformerdesignandprotection-130408132534-phpapp02.pptThien Phan Bản
 
Power Transformer Protection
Power Transformer ProtectionPower Transformer Protection
Power Transformer ProtectionAng Sovann
 
BPMI TRANSFORMER PROTECTION.pptx.pdf
BPMI TRANSFORMER PROTECTION.pptx.pdfBPMI TRANSFORMER PROTECTION.pptx.pdf
BPMI TRANSFORMER PROTECTION.pptx.pdfssuser2e69dc
 
Substation_equipment_ (1).pptx
Substation_equipment_ (1).pptxSubstation_equipment_ (1).pptx
Substation_equipment_ (1).pptxSatish Pydimarla
 
Unit 04 Protection of generators and transformers
Unit  04 Protection of generators and transformers Unit  04 Protection of generators and transformers
Unit 04 Protection of generators and transformers PremanandDesai
 
High Tension Current Transformer in Pune
High Tension Current Transformer in PuneHigh Tension Current Transformer in Pune
High Tension Current Transformer in Punebizproto26
 
BUCHHOLZ RELAY TESTING KIT
BUCHHOLZ RELAY TESTING KITBUCHHOLZ RELAY TESTING KIT
BUCHHOLZ RELAY TESTING KITIRJET Journal
 
Presentation training
Presentation trainingPresentation training
Presentation trainingSrajan Raj
 

Similar to transformerprotection-180102061059.pdf (20)

transformer protection
transformer protection transformer protection
transformer protection
 
Transformer protection
Transformer protectionTransformer protection
Transformer protection
 
UNIT 3.pptx
UNIT 3.pptxUNIT 3.pptx
UNIT 3.pptx
 
1.Transformer.pptx
1.Transformer.pptx1.Transformer.pptx
1.Transformer.pptx
 
Generator and Transformer Protection (PART 2)
Generator and Transformer Protection (PART 2)Generator and Transformer Protection (PART 2)
Generator and Transformer Protection (PART 2)
 
Transformer design and protection
Transformer design and protectionTransformer design and protection
Transformer design and protection
 
Relay and switchgear protection
Relay and switchgear protectionRelay and switchgear protection
Relay and switchgear protection
 
TRANSFORMER
TRANSFORMERTRANSFORMER
TRANSFORMER
 
Presentation on KESCO sub-station, kanpur
Presentation on KESCO sub-station, kanpurPresentation on KESCO sub-station, kanpur
Presentation on KESCO sub-station, kanpur
 
Switchgear and protection engineering Lecture 02.pptx
Switchgear and protection engineering Lecture 02.pptxSwitchgear and protection engineering Lecture 02.pptx
Switchgear and protection engineering Lecture 02.pptx
 
transformerdesignandprotection-130408132534-phpapp02.ppt
transformerdesignandprotection-130408132534-phpapp02.ppttransformerdesignandprotection-130408132534-phpapp02.ppt
transformerdesignandprotection-130408132534-phpapp02.ppt
 
Power Transformer Protection
Power Transformer ProtectionPower Transformer Protection
Power Transformer Protection
 
BPMI TRANSFORMER PROTECTION.pptx.pdf
BPMI TRANSFORMER PROTECTION.pptx.pdfBPMI TRANSFORMER PROTECTION.pptx.pdf
BPMI TRANSFORMER PROTECTION.pptx.pdf
 
Power system protection
Power system protectionPower system protection
Power system protection
 
Substation_equipment_ (1).pptx
Substation_equipment_ (1).pptxSubstation_equipment_ (1).pptx
Substation_equipment_ (1).pptx
 
Unit 04 Protection of generators and transformers
Unit  04 Protection of generators and transformers Unit  04 Protection of generators and transformers
Unit 04 Protection of generators and transformers
 
High Tension Current Transformer in Pune
High Tension Current Transformer in PuneHigh Tension Current Transformer in Pune
High Tension Current Transformer in Pune
 
transformer protection
transformer protectiontransformer protection
transformer protection
 
BUCHHOLZ RELAY TESTING KIT
BUCHHOLZ RELAY TESTING KITBUCHHOLZ RELAY TESTING KIT
BUCHHOLZ RELAY TESTING KIT
 
Presentation training
Presentation trainingPresentation training
Presentation training
 

More from Satish Pydimarla

Testing_of_transformers_adjusted.ppt
Testing_of_transformers_adjusted.pptTesting_of_transformers_adjusted.ppt
Testing_of_transformers_adjusted.pptSatish Pydimarla
 
Zaragoza Factory_Our product_ EN.ppt
Zaragoza Factory_Our product_ EN.pptZaragoza Factory_Our product_ EN.ppt
Zaragoza Factory_Our product_ EN.pptSatish Pydimarla
 
3-Phase-Transformer (1).pptx
3-Phase-Transformer (1).pptx3-Phase-Transformer (1).pptx
3-Phase-Transformer (1).pptxSatish Pydimarla
 
Presentation-Kalinga Stadium.pptx
Presentation-Kalinga Stadium.pptxPresentation-Kalinga Stadium.pptx
Presentation-Kalinga Stadium.pptxSatish Pydimarla
 
understandingtransformervectorgroup-180629014651.pptx
understandingtransformervectorgroup-180629014651.pptxunderstandingtransformervectorgroup-180629014651.pptx
understandingtransformervectorgroup-180629014651.pptxSatish Pydimarla
 
transformeronno-load-200825063948.pptx
transformeronno-load-200825063948.pptxtransformeronno-load-200825063948.pptx
transformeronno-load-200825063948.pptxSatish Pydimarla
 
332038674-Vector-Group-of-Transformers.ppt
332038674-Vector-Group-of-Transformers.ppt332038674-Vector-Group-of-Transformers.ppt
332038674-Vector-Group-of-Transformers.pptSatish Pydimarla
 
Parall Operation Transformers
Parall Operation TransformersParall Operation Transformers
Parall Operation TransformersSatish Pydimarla
 
Understanding_lightning_protection.pptx
Understanding_lightning_protection.pptxUnderstanding_lightning_protection.pptx
Understanding_lightning_protection.pptxSatish Pydimarla
 
Construction of HV Transmission Lines etc.pptx
Construction of HV Transmission Lines etc.pptxConstruction of HV Transmission Lines etc.pptx
Construction of HV Transmission Lines etc.pptxSatish Pydimarla
 
high-voltage-dc-transmission-hvdc PKP.pptx
high-voltage-dc-transmission-hvdc PKP.pptxhigh-voltage-dc-transmission-hvdc PKP.pptx
high-voltage-dc-transmission-hvdc PKP.pptxSatish Pydimarla
 

More from Satish Pydimarla (20)

9310091.ppt
9310091.ppt9310091.ppt
9310091.ppt
 
control room.pptx
control room.pptxcontrol room.pptx
control room.pptx
 
Thermovision Test.ppt
Thermovision Test.pptThermovision Test.ppt
Thermovision Test.ppt
 
4143813.ppt
4143813.ppt4143813.ppt
4143813.ppt
 
Transformer_theory.pptx
Transformer_theory.pptxTransformer_theory.pptx
Transformer_theory.pptx
 
Testing_of_transformers_adjusted.ppt
Testing_of_transformers_adjusted.pptTesting_of_transformers_adjusted.ppt
Testing_of_transformers_adjusted.ppt
 
Zaragoza Factory_Our product_ EN.ppt
Zaragoza Factory_Our product_ EN.pptZaragoza Factory_Our product_ EN.ppt
Zaragoza Factory_Our product_ EN.ppt
 
3-Phase-Transformer (1).pptx
3-Phase-Transformer (1).pptx3-Phase-Transformer (1).pptx
3-Phase-Transformer (1).pptx
 
Electrical_Engg_Basic.PPT
Electrical_Engg_Basic.PPTElectrical_Engg_Basic.PPT
Electrical_Engg_Basic.PPT
 
Presentation-Kalinga Stadium.pptx
Presentation-Kalinga Stadium.pptxPresentation-Kalinga Stadium.pptx
Presentation-Kalinga Stadium.pptx
 
understandingtransformervectorgroup-180629014651.pptx
understandingtransformervectorgroup-180629014651.pptxunderstandingtransformervectorgroup-180629014651.pptx
understandingtransformervectorgroup-180629014651.pptx
 
transformeronno-load-200825063948.pptx
transformeronno-load-200825063948.pptxtransformeronno-load-200825063948.pptx
transformeronno-load-200825063948.pptx
 
332038674-Vector-Group-of-Transformers.ppt
332038674-Vector-Group-of-Transformers.ppt332038674-Vector-Group-of-Transformers.ppt
332038674-Vector-Group-of-Transformers.ppt
 
tcee-161003100321.pptx
tcee-161003100321.pptxtcee-161003100321.pptx
tcee-161003100321.pptx
 
Parall Operation Transformers
Parall Operation TransformersParall Operation Transformers
Parall Operation Transformers
 
Understanding_lightning_protection.pptx
Understanding_lightning_protection.pptxUnderstanding_lightning_protection.pptx
Understanding_lightning_protection.pptx
 
Understanding VCB.pptx
Understanding VCB.pptxUnderstanding VCB.pptx
Understanding VCB.pptx
 
CT & PT.pptx
CT & PT.pptxCT & PT.pptx
CT & PT.pptx
 
Construction of HV Transmission Lines etc.pptx
Construction of HV Transmission Lines etc.pptxConstruction of HV Transmission Lines etc.pptx
Construction of HV Transmission Lines etc.pptx
 
high-voltage-dc-transmission-hvdc PKP.pptx
high-voltage-dc-transmission-hvdc PKP.pptxhigh-voltage-dc-transmission-hvdc PKP.pptx
high-voltage-dc-transmission-hvdc PKP.pptx
 

Recently uploaded

Introduction to AI in Higher Education_draft.pptx
Introduction to AI in Higher Education_draft.pptxIntroduction to AI in Higher Education_draft.pptx
Introduction to AI in Higher Education_draft.pptxpboyjonauth
 
Alper Gobel In Media Res Media Component
Alper Gobel In Media Res Media ComponentAlper Gobel In Media Res Media Component
Alper Gobel In Media Res Media ComponentInMediaRes1
 
Crayon Activity Handout For the Crayon A
Crayon Activity Handout For the Crayon ACrayon Activity Handout For the Crayon A
Crayon Activity Handout For the Crayon AUnboundStockton
 
EPANDING THE CONTENT OF AN OUTLINE using notes.pptx
EPANDING THE CONTENT OF AN OUTLINE using notes.pptxEPANDING THE CONTENT OF AN OUTLINE using notes.pptx
EPANDING THE CONTENT OF AN OUTLINE using notes.pptxRaymartEstabillo3
 
“Oh GOSH! Reflecting on Hackteria's Collaborative Practices in a Global Do-It...
“Oh GOSH! Reflecting on Hackteria's Collaborative Practices in a Global Do-It...“Oh GOSH! Reflecting on Hackteria's Collaborative Practices in a Global Do-It...
“Oh GOSH! Reflecting on Hackteria's Collaborative Practices in a Global Do-It...Marc Dusseiller Dusjagr
 
Blooming Together_ Growing a Community Garden Worksheet.docx
Blooming Together_ Growing a Community Garden Worksheet.docxBlooming Together_ Growing a Community Garden Worksheet.docx
Blooming Together_ Growing a Community Garden Worksheet.docxUnboundStockton
 
Proudly South Africa powerpoint Thorisha.pptx
Proudly South Africa powerpoint Thorisha.pptxProudly South Africa powerpoint Thorisha.pptx
Proudly South Africa powerpoint Thorisha.pptxthorishapillay1
 
Meghan Sutherland In Media Res Media Component
Meghan Sutherland In Media Res Media ComponentMeghan Sutherland In Media Res Media Component
Meghan Sutherland In Media Res Media ComponentInMediaRes1
 
What is Model Inheritance in Odoo 17 ERP
What is Model Inheritance in Odoo 17 ERPWhat is Model Inheritance in Odoo 17 ERP
What is Model Inheritance in Odoo 17 ERPCeline George
 
Presiding Officer Training module 2024 lok sabha elections
Presiding Officer Training module 2024 lok sabha electionsPresiding Officer Training module 2024 lok sabha elections
Presiding Officer Training module 2024 lok sabha electionsanshu789521
 
Types of Journalistic Writing Grade 8.pptx
Types of Journalistic Writing Grade 8.pptxTypes of Journalistic Writing Grade 8.pptx
Types of Journalistic Writing Grade 8.pptxEyham Joco
 
AmericanHighSchoolsprezentacijaoskolama.
AmericanHighSchoolsprezentacijaoskolama.AmericanHighSchoolsprezentacijaoskolama.
AmericanHighSchoolsprezentacijaoskolama.arsicmarija21
 
Final demo Grade 9 for demo Plan dessert.pptx
Final demo Grade 9 for demo Plan dessert.pptxFinal demo Grade 9 for demo Plan dessert.pptx
Final demo Grade 9 for demo Plan dessert.pptxAvyJaneVismanos
 
Hierarchy of management that covers different levels of management
Hierarchy of management that covers different levels of managementHierarchy of management that covers different levels of management
Hierarchy of management that covers different levels of managementmkooblal
 
call girls in Kamla Market (DELHI) 🔝 >༒9953330565🔝 genuine Escort Service 🔝✔️✔️
call girls in Kamla Market (DELHI) 🔝 >༒9953330565🔝 genuine Escort Service 🔝✔️✔️call girls in Kamla Market (DELHI) 🔝 >༒9953330565🔝 genuine Escort Service 🔝✔️✔️
call girls in Kamla Market (DELHI) 🔝 >༒9953330565🔝 genuine Escort Service 🔝✔️✔️9953056974 Low Rate Call Girls In Saket, Delhi NCR
 
Enzyme, Pharmaceutical Aids, Miscellaneous Last Part of Chapter no 5th.pdf
Enzyme, Pharmaceutical Aids, Miscellaneous Last Part of Chapter no 5th.pdfEnzyme, Pharmaceutical Aids, Miscellaneous Last Part of Chapter no 5th.pdf
Enzyme, Pharmaceutical Aids, Miscellaneous Last Part of Chapter no 5th.pdfSumit Tiwari
 
Historical philosophical, theoretical, and legal foundations of special and i...
Historical philosophical, theoretical, and legal foundations of special and i...Historical philosophical, theoretical, and legal foundations of special and i...
Historical philosophical, theoretical, and legal foundations of special and i...jaredbarbolino94
 

Recently uploaded (20)

Introduction to AI in Higher Education_draft.pptx
Introduction to AI in Higher Education_draft.pptxIntroduction to AI in Higher Education_draft.pptx
Introduction to AI in Higher Education_draft.pptx
 
Alper Gobel In Media Res Media Component
Alper Gobel In Media Res Media ComponentAlper Gobel In Media Res Media Component
Alper Gobel In Media Res Media Component
 
Crayon Activity Handout For the Crayon A
Crayon Activity Handout For the Crayon ACrayon Activity Handout For the Crayon A
Crayon Activity Handout For the Crayon A
 
OS-operating systems- ch04 (Threads) ...
OS-operating systems- ch04 (Threads) ...OS-operating systems- ch04 (Threads) ...
OS-operating systems- ch04 (Threads) ...
 
EPANDING THE CONTENT OF AN OUTLINE using notes.pptx
EPANDING THE CONTENT OF AN OUTLINE using notes.pptxEPANDING THE CONTENT OF AN OUTLINE using notes.pptx
EPANDING THE CONTENT OF AN OUTLINE using notes.pptx
 
“Oh GOSH! Reflecting on Hackteria's Collaborative Practices in a Global Do-It...
“Oh GOSH! Reflecting on Hackteria's Collaborative Practices in a Global Do-It...“Oh GOSH! Reflecting on Hackteria's Collaborative Practices in a Global Do-It...
“Oh GOSH! Reflecting on Hackteria's Collaborative Practices in a Global Do-It...
 
Blooming Together_ Growing a Community Garden Worksheet.docx
Blooming Together_ Growing a Community Garden Worksheet.docxBlooming Together_ Growing a Community Garden Worksheet.docx
Blooming Together_ Growing a Community Garden Worksheet.docx
 
Proudly South Africa powerpoint Thorisha.pptx
Proudly South Africa powerpoint Thorisha.pptxProudly South Africa powerpoint Thorisha.pptx
Proudly South Africa powerpoint Thorisha.pptx
 
Meghan Sutherland In Media Res Media Component
Meghan Sutherland In Media Res Media ComponentMeghan Sutherland In Media Res Media Component
Meghan Sutherland In Media Res Media Component
 
What is Model Inheritance in Odoo 17 ERP
What is Model Inheritance in Odoo 17 ERPWhat is Model Inheritance in Odoo 17 ERP
What is Model Inheritance in Odoo 17 ERP
 
ESSENTIAL of (CS/IT/IS) class 06 (database)
ESSENTIAL of (CS/IT/IS) class 06 (database)ESSENTIAL of (CS/IT/IS) class 06 (database)
ESSENTIAL of (CS/IT/IS) class 06 (database)
 
Presiding Officer Training module 2024 lok sabha elections
Presiding Officer Training module 2024 lok sabha electionsPresiding Officer Training module 2024 lok sabha elections
Presiding Officer Training module 2024 lok sabha elections
 
Types of Journalistic Writing Grade 8.pptx
Types of Journalistic Writing Grade 8.pptxTypes of Journalistic Writing Grade 8.pptx
Types of Journalistic Writing Grade 8.pptx
 
9953330565 Low Rate Call Girls In Rohini Delhi NCR
9953330565 Low Rate Call Girls In Rohini  Delhi NCR9953330565 Low Rate Call Girls In Rohini  Delhi NCR
9953330565 Low Rate Call Girls In Rohini Delhi NCR
 
AmericanHighSchoolsprezentacijaoskolama.
AmericanHighSchoolsprezentacijaoskolama.AmericanHighSchoolsprezentacijaoskolama.
AmericanHighSchoolsprezentacijaoskolama.
 
Final demo Grade 9 for demo Plan dessert.pptx
Final demo Grade 9 for demo Plan dessert.pptxFinal demo Grade 9 for demo Plan dessert.pptx
Final demo Grade 9 for demo Plan dessert.pptx
 
Hierarchy of management that covers different levels of management
Hierarchy of management that covers different levels of managementHierarchy of management that covers different levels of management
Hierarchy of management that covers different levels of management
 
call girls in Kamla Market (DELHI) 🔝 >༒9953330565🔝 genuine Escort Service 🔝✔️✔️
call girls in Kamla Market (DELHI) 🔝 >༒9953330565🔝 genuine Escort Service 🔝✔️✔️call girls in Kamla Market (DELHI) 🔝 >༒9953330565🔝 genuine Escort Service 🔝✔️✔️
call girls in Kamla Market (DELHI) 🔝 >༒9953330565🔝 genuine Escort Service 🔝✔️✔️
 
Enzyme, Pharmaceutical Aids, Miscellaneous Last Part of Chapter no 5th.pdf
Enzyme, Pharmaceutical Aids, Miscellaneous Last Part of Chapter no 5th.pdfEnzyme, Pharmaceutical Aids, Miscellaneous Last Part of Chapter no 5th.pdf
Enzyme, Pharmaceutical Aids, Miscellaneous Last Part of Chapter no 5th.pdf
 
Historical philosophical, theoretical, and legal foundations of special and i...
Historical philosophical, theoretical, and legal foundations of special and i...Historical philosophical, theoretical, and legal foundations of special and i...
Historical philosophical, theoretical, and legal foundations of special and i...
 

transformerprotection-180102061059.pdf

  • 1. Presented by Dr.Selvarasu Ranganathan Assistant Professor School of Electrical Engineering and Computing Adama Science and Technology University, Adama. . TRANSFORMER PROTECTION
  • 2. Transformers • Transformers are the major power system components which are used at various voltage levels with the capacity varying from 1kVA to >600 MVA. • Transformers are widely used devices to transfer power from one circuit to another circuit magnetically with out physical coupling. • Any damage to this component results in complete loss of power to one system. • The transformer should be protected from the faults to avoid break down of the transformer which may lead to major interruption in power transformation. • To protect it from the fault the typical faults in the fault should be known.
  • 3. Possible Transformer Faults Transformer Faults Internal Faults (Winding faults) Phase to Phase fault Phase to earth fault Inter-turn fault External Faults (Through faults)
  • 4. Transformer Internal Faults •Breakdown of the insulating oil. •Insulation failure of winding. •Over heat generated in the coils due to failure of insulation etc.
  • 5. Transformer External Faults High Voltage Disturbance in Power Transformer are of two kinds 1.Transient Surge Voltage •Arcing ground if neutral point is isolated. •Switching operation of different electrical equipment. •Atmospheric Lightening Impulse. 2. Power Frequency Over Voltage As we know that, voltage V = 4.44Φ.f.N ⇒ V ∝ Φ, increased voltage causes proportionate increase in the working flux. This therefore causes, increased in iron loss and dis-proportionately large increase in magnetizing current. The increase flux is diverted from the transformer core to other steel structural parts of the transformer. Core bolts which normally carry little flux, may be subjected to a large component of flux diverted from saturated region of the core alongside. Under such condition, the bolt may be rapidly heated up and destroys their own insulation as well as winding insulation.
  • 6. Transformer External Faults Contd… Protection against lighting surges lighting arrester can be provided.
  • 7. Transformer Types There are different kinds of transformers such as •Two winding or three winding power transformer, •Auto transformer, •regulating transformers, •Earthing transformer, •Rectifier transformers etc. Different transformers demand different schemes of transformer protection depending upon their importance, winding connections, earthing methods and mode of operation etc. •It is common practice to provide Buchholz relay protection to all 500 kVA and above transformers. •While for all small size distribution transformers, only high voltage fuses are used as main protective device. • For all larger rated and important distribution transformers, over current protection along with restricted earth fault protectionis applied. •Differential protection should be provided in the transformers rated above 5 MVA
  • 8. Typical Protections in Transformer Typically transformer protections are classified as two types. 1) Main protections 2) backup protections. Main protections: These are immediate fault clearance protections which acts instantaneously to clear the faults in the transformer. Differential protection Over current protection Back up protection: These protections will acts as a back up to the main protections i.e. if the main protection fails corresponding back up protection will act and safe guard the device from fault. Over voltage Volts/hertz Negative phase sequence relay
  • 9. Differential Protection •Generally Differential protection is provided in the electrical power transformer rated more than 5MVA. The Differential Protection of Transformer has many advantages over other schemes of protection. •The faults occur in the transformer inside the insulating oil can be detected by Buchholz relay. But if any fault occurs in the transformer but not in oil then it can not be detected by Buchholz relay. •Any flash over at the bushings are not adequately covered by Buchholz relay. •Differential relays can detect such type of faults. Moreover Buchholz relay is provided in transformer for detecting any internal fault in the transformer but Differential Protection scheme detects the same in more faster way. •The differential relays normally response to those faults which occur inside the differential protection zone of transformer.
  • 10. Differential Protection Contd… Basic Considerations for Transformer Differential Protection: • Line Current Transformer Primary Ratings •Current Transformer Connections •The neutrals of C.T star and power transformer stars are grounded. •Selection of C.T and Power transformer tapings.
  • 11. Differential Protection Contd… Line Current Transformer Primary Ratings Consider a two winding, 11kV/132kV, 30MVA Power Transformer. The rated line current on the 11kV side of the Transformer is: Irated = MVA / Line Voltage = 30000000 / (11000)(sqrt 3) = 1574.59A Thus, choose a CT with a primary rating of 1600/1. The line current on the 132kV side of the Transformer is: Irated = 30000000 / (132000)(sqrt 3) = 131.22A Thus choose a CT with a primary rating of 200/1. Notice that in both cases, the current that the Bias Coils in the relay is 1A at both ends. Any deviation of this 1A will causes an imbalance within the relay, which will consequently cause protection to operate and isolate the Transformer.
  • 12. Differential Protection Contd… Current Transformer Connections
  • 13. Merz-Price Protection for Star-Delta Transformer
  • 14. Merz-Price Protection for Star-Delta Transformer Contd…
  • 15. Merz-Price Protection for Star-Star Transformer
  • 16. BUCHHOLZ RELAY •Buchholz relay is a type of oil and gas actuated protection relay universally used on all oil immersed transformers having rating more than 500 kVA. • Buchholz relay is not provided in transformer having rating below 500 kVA from the point of view of economic considerations.
  • 17. Why Buchholz relay is used in transformers? Buchholz relay is used for the protection of transformers from the faults occurring inside the transformer. Short circuit faults such as inter turn faults, incipient winding faults, and core faults may occur due to the impulse breakdown of the insulating oil or simply the transformer oil. Buchholz relay will sense such faults and closes the alarm circuit. Working principle Buchholz relay relies on the fact that an electrical fault inside the transformer tank is accompanied by the generation of gas and if the fault is high enough it will be accompanied by a surge of oil from the tank to the conservator Whenever a fault occurs inside the transformer, the oil in the transformer tank gets overheated and gases are generated. The generation of the gases depends mainly on the intensity of fault produced. The heat generated during the fault will be high enough to decompose the transformer oil and the gases produced can be used to detect the winding faults. This is the basic principle behind the working of the Buchholz relay. Construction Buchholz relay can be used in the transformers having the conservators only. It is placed in the pipe connecting the conservator and the transformer tank. It consists of an oil filled chamber. Two hinged floats, one at the top of the chamber and the other at the bottom of the chamber which accompanies a mercury switch each is present in the oil filled chamber. The mercury switch on the upper float is connected to an external alarm circuit and the mercury switch on the lower is connected to an external trip circuit. Buchholz Relay Contd..
  • 19. Buchholz relay is employed for the following types faults, • Core bolt insulation failure • Local-overheating • Entrance of air into the oil • Less of oil due to leakage • Short circuited lamination due to burns. Buchholz Relay Contd..
  • 20. Advantages of Buchholz relay • The advantage of using a Buchholtz relay is that they indicate incipient faults. For example, It indicates the faults between turns or heating of core which enables us to take the transformer out of service before severe damage occurs. • Buchholtz relay gives an alarm when the oil level reduces below a certain level due to leakage of oil from transformer. • Buchholtz relay gives an audible warning which informs the operator that there is some fault in the transformer. • Type of insulation failure of the transformer can also be detected by testing the gas. Buchholz Relay Contd..
  • 21. Limitation of Buchholz relay 1. This type of relay can be used only for transformers with conservators. 2. The relay does not operate when the faults are above the oil level. 3. Buchholz relay does not protect the cables associated with the transformers below. A separate protection has to be employed for the cables. 4. Due to economic considerations, this relay is not employed for transformers above 500 kVA. 5. Setting of the mercury switch cannot be too sensitive, otherwise there can be a false operation due to vibrations,earthquakes. mechanical shocks to the pipe. 6. The operation of this new is unsatisfactory due to slow operating time. (Nearly 0.2 to 0.1 seconds). Buchholz Relay Contd..