MElec-Ch2 - 1
Chapter 2
Electrical Wiring Practices
and Diagrams
MElec-Ch2 - 2
Overview
• Safety
• Standards
• Wiring Considerations
• Wire Terminations
• Coaxial Cable
• Wiring Installations
• Wiring Diagrams
MElec-Ch2 - 3
Safety
• Lethal Current
• Safety Precautions
MElec-Ch2 - 4
Lethal Current
• Fundamental policy of the USPS is SAFETY
• Human Body
 Resistance – 4 KΩ (moist skin) to 24 KΩ (dry skin)
 Safe current (through chest) – less than 20 milliamps
 E = 120 VAC R = 4 KΩ I = ?
 I = 30 milliamps - NOT SAFE
 Don’t want current through chest cavity (may be lethal)
MElec-Ch2 - 5
Safety Precautions
• Turn circuit off
 Disconnect service cord
 Disconnect negative battery cable
• If must work on live AC circuit
 Need 2nd safety person
• Remove metal jewelry
• Know your boat and its wiring
• Use outlet tester on AC outlets
• Use 3-wire extension cord from GFI outlet
MElec-Ch2 - 6
Standards
• American Boat and Yacht Council (ABYC)
 AC and DC Electrical Systems is E-11
 Minimum standards
• Construction
• Repair
• Marine Dept. of Underwriters Laboratory
 Test and certify commercial products
 Safety, not function
MElec-Ch2 - 7
Wiring Considerations
• Conductors
• Wire Types
• Wire Size
• Wire Insulation
• Wire Color Code
MElec-Ch2 - 8
Conductors
• Connects power sources to power loads
• Characteristics
 Safe
 Dependable
 Efficient (minimal voltage drop)
• Boat environment
 Worse than either house or car
 High humidity
 Vibration
 Corrosive conditions
MElec-Ch2 - 9
Wire Types
• Marine Grade
 Type 3 is recommended
• Stranded copper
 Tinned is preferred
MElec-Ch2 - 10
Wire Size
• 3% voltage drop
 Critical circuits (Nav lights)
 Electronic Equipment
• 10% voltage drop
 Cabin lights
 Motorized Equipment
• Minimum size AWG # 16
MElec-Ch2 - 11
Wire Has Resistance
• Inadvertent Resistors
 Wire too small (min of #16 - properly size using table)
 Bad connections (or corroded connections)
• Clean and tighten battery connectors
• Tighten lug screws and inspect wire to lug connection
 Why do wires get warm / hot?
• Low resistance circuits pass high current (P = I2 x R)
• Wires can account for much of the overall resistance
V
12 VDC
0.1 Ώ
0.1 Ώ
10A What Voltage?
An. 10 VDC
MElec-Ch2 - 12
Wire Size Comparison
#16 top to #10 bottom
#2 top to #10 bottom
MElec-Ch2 - 13
Copper Wire Characteristics
MElec-Ch2 - 14
12- VDC Wire Size Selection
MElec-Ch2 - 15
12 VDC Wire Size Selection
MElec-Ch2 - 16
120 VAC Wire Size Selection
MElec-Ch2 - 17
What Size Wires?
B
MElec-Ch2 - 18
Step 1
What current to Load?
From Table 2-3 – Maximum of 44 feet (for 10A in #16 wire)
P = E * I I = P / E I = 1200/120
I = 10 Amps
From Table 2-1 – For 10A need #16 wire
B
MElec-Ch2 - 19
Step 1 Answers
AMPACITY
10 Amperes
#16 AWG TW
by Table 2-1
for 3% voltage drop
44 feet maximum
by Table 2-3
B
MElec-Ch2 - 20
Step 2
What current to Inverter?
From Table 2-3 – Maximum of 14 feet (for 110A in #1 wire)
Iload = Iout = Iin *0.91 Iin = Iout / 0.91 = 100 / 0.91 = 110 Amps
From Table 2-1 – For 110A need #1 wire
B
Iload = 100 Amps @ 12 V
MElec-Ch2 - 21
Step 2 Answers
AMPACITY
110 Amperes
#1 AWG TW
by Table 1
for 3% voltage drop
14 feet maximum
by Table 2-2A
B
MElec-Ch2 - 22
Wire Insulation
• AC cables must be type UL 1426 BC
 600 volt insulation
 Gasoline and Oil resistant
 Won’t absorb moisture
• DC wires & cables must be Marine Grade
 600 volt insulation
 Gasoline and Oil resistant
 Won’t absorb moisture
• Color coded wires
MElec-Ch2 - 23
Wire Color Code
Color AC (Hot) AC (Neut) AC (Gnd) DC + DC -
Black X X1
White X
Green (may have a yellow stripe) X
Red X2 X
Yellow X1
Footnotes:
1 – Yellow preferred for DC negative to avoid confusion with AC Hot wire
2 – 2nd hot wire in 220 VAC is Red
MElec-Ch2 - 24
Wire Color Coding
MElec-Ch2 - 25
Wire Terminations
• Crimping
 Special Tool
 Approved Marine Connectors
 Use of Ratcheting Tool
• Solder
• Heat-shrink Tubing
MElec-Ch2 - 26
Wire Terminals
MElec-Ch2 - 27
Ratcheting Crimper
YES
NO
MElec-Ch2 - 28
Ratcheting Tool Use
• First select appropriate connector
• Strip insulation length of stem plus 1/16”
• Insert stripped end all way into terminal
 End should extend 1/16”
• Place terminal in same color slot
 First crimp end of terminal barrel nearest ring
 Then crimp wire end of terminal barrel
• Check the connection with a solid tug
MElec-Ch2 - 29
Soldering
• Terminal connection can’t be only soldered
 Must also be crimped
• Soldering is normally not required
 Crimped connectors are acceptable to ABYC
 If solder, apply only to ring end of terminal
• Solder changes stranded wire into solid
 Stranded wire is flexible
• Use 40% lead / 60% tin, rosin core solder
• Battery lugs may be only soldered
MElec-Ch2 - 30
Heat-Shrink Tubing
Application Steps
MElec-Ch2 - 31
Coaxial Cable
• Antenna cable
• Radio coax is 50 ohm with PL-259
• Radio cable is cut to length
• Want attenuation under 3 db
• TV cable is 75 ohm with “F” connectors
• GPS cable is not cut to length
 Coil excess in 1-foot loops
MElec-Ch2 - 32
Coaxial Cable Information
MElec-Ch2 - 33
Soldering PL-259 Connector
MElec-Ch2 - 34
Wiring Installation
• Basic Considerations
• Distribution Panel
• Fuses / Circuit Breakers
• Branch Circuits
 Wire
 Outlets
 Switches
• Grounding Systems
• Bonding Systems
MElec-Ch2 - 35
Basic Considerations
• Must have source and return wires
 Return wires to a common point
 May use feeder wire from power panel for:
• engine, helm console, etc.
• Wires above flood level of bilge
 Waterproof if in bilge
• Insulated support every 18”
• Twist DC wires within 1 meter of compass
MElec-Ch2 - 36
Distribution Panel
• Central location of Circuit Breakers / Fuses
 All branch circuits from this location
• AC and DC may be combined in one panel
• All equipment / circuits should go to panel
 Not direct to battery (except bilge pump)
• Noise interference suppression covered in Section 7
MElec-Ch2 - 37
DC / AC Power Panel
Front View
MElec-Ch2 - 38
Inside Power Panel
DC Side
Buss Bars
MElec-Ch2 - 39
Fuses and Circuit Breakers
• Used to protect wiring from over current
 In positive or hot wire
• Newer boats use circuit breakers
 Initially more expensive
• Replace blown fuse with correct rating
• Circuit Breakers should be Marine Grade
 Trip free
 Manual reset
MElec-Ch2 - 40
Branch Circuits - Wires
• Minimum size is 16 AWG
 See Wire Selection Tables
 For AC normally #14 for 15A and #12 for 20A
• Must terminate in closed electrical box
• Of sufficient length
• DC negative returned to DC Panel
 May use several negative feeder terminals
• AC neutrals returned to AC Panel
• Bonding system never used as return wire
MElec-Ch2 - 41
Branch Circuits - Outlets
• 120 VAC outlets must be 3-wire polarized
 Black (hot) to brass or copper colored terminal
• Outlet wires must have crimp terminals
• GFI outlets
 Required on weather deck, head, galley and
machinery spaces
 Good practice for all AC outlets to be GFI
 Trip at 5 milliamps
• Different outlets for AC and DC power
MElec-Ch2 - 42
Outlets and Plugs
DC Outlet
(Receptacle)
DC Plug
120 VAC 120 VAC
12 VDC 120 VAC
15 A Outlet
AC Plug 15 A AC Plug 20 A
GFI 15 A
Outlet
20 A Outlet
MElec-Ch2 - 43
Branch Circuits - Switches
• Modern panels use Circuit Breakers
 Which also double as switches
• Switches / Circuit Breakers
 Must be Marine Grade
 Rated for the voltage and current controlled
 Interrupt the positive (DC) or hot (AC) leg
• Battery Switch
 Designed for high current service
 Not located in engine or fuel-tank compartments
MElec-Ch2 - 44
Grounding System
• Ground is potential of water around boat
 Or potential of earth’s surface
• DC – Ground Battery negative terminal(s)
 Also engine block
 Wire color is Yellow (or Black)
• AC – Transformer center tap on shore
 Also connected to ground rod at transformer
 Wire color is Green and uninterrupted wire
• Isolation transformers and galvanic isolators are
exception and covered in Chapter 4 on AC
• Engine, DC negative & AC ground connected
MElec-Ch2 - 45
Bonding System
• For lightning protection
 More in Chapter 6
• All metal objects should be bonded
 Keeps all metal at zero potential
 Engine blocks
 Battery negative terminals
• Non-current carrying wire
• Through-hull fittings
 ABYC now recommends they be bonded
 Electrically isolated from metal hull
MElec-Ch2 - 46
Bonding Diagram
MElec-Ch2 - 47
Wiring Diagrams
• Elements of a Good Wiring Diagram
 Documents boat’s electrical layout
 Should be kept current
 Used for troubleshooting
• Component Identification
 Physical objects to their symbol
 Wires are color coded
MElec-Ch2 - 48
Wiring Diagram Symbols
Switch, double pole, single throw (DPST)
Switch, single pole, single throw (SPST)
Switch, single pole, double throw (SPDT)
Battery (long line on top is positive)
Wires connected (at dots)
Wires crossing (but NOT connected)
Wire (insulated, metal conductor)
Incandescent Light
Alternate symbol for Light
Circuit Breaker
Fuse
Ground
Male Connector
Female Connector
MElec-Ch2 - 49
Simple DC Wiring Diagram
MElec-Ch2 - 50
Summary
• Circuits should be off when working on them
• Use only marine grade properly sized wires
 Tables will help determine proper wire size
 Minimum wire size is #16 AWG
• Use wire terminations and ratcheting crimper
• DC circuits are 2 dedicated wires
 Waterproof wire connection in bilge
• AC circuits are 3 dedicated wires
 GFCI in galley, head, machine spaces & weather deck
• Separate Grounding & Bonding systems required
• Keep wiring diagram current

More Related Content

Similar to 3560357.ppt

Mechanical Design of Overhead Lines
Mechanical Design of Overhead LinesMechanical Design of Overhead Lines
Mechanical Design of Overhead LinesRanjeet Kumar
 
Transmission lines of Electrical powe
Transmission lines of Electrical poweTransmission lines of Electrical powe
Transmission lines of Electrical poweDarya khan
 
Contactor generalizations
Contactor generalizationsContactor generalizations
Contactor generalizationsMichael O'Dell
 
Chapter 1 Introduction to power Electronic Devices.pdf
Chapter 1 Introduction to power Electronic Devices.pdfChapter 1 Introduction to power Electronic Devices.pdf
Chapter 1 Introduction to power Electronic Devices.pdfLiewChiaPing
 
Introduction to PCB Designing Tutorial
Introduction to PCB Designing TutorialIntroduction to PCB Designing Tutorial
Introduction to PCB Designing TutorialMudit Thakkar
 
Contactor generalizations
Contactor generalizationsContactor generalizations
Contactor generalizationsMichael O'Dell
 
Switchgear.pptx
Switchgear.pptxSwitchgear.pptx
Switchgear.pptxsatabdi8
 
Transformer Failure Due to Circuit Breaker Induced Switching Transients
Transformer Failure Due to Circuit Breaker Induced Switching TransientsTransformer Failure Due to Circuit Breaker Induced Switching Transients
Transformer Failure Due to Circuit Breaker Induced Switching Transientsmichaeljmack
 
Contactor generalizations
Contactor generalizationsContactor generalizations
Contactor generalizationsMichael O'Dell
 
Concept of energy transmission & distribution
Concept of energy transmission & distribution Concept of energy transmission & distribution
Concept of energy transmission & distribution ZunAib Ali
 
Design of Electrical Installation of Buildings.ppt
Design of Electrical Installation of Buildings.pptDesign of Electrical Installation of Buildings.ppt
Design of Electrical Installation of Buildings.pptSameeraShaman
 
High_Low_Impedance_BusBar_Protection.ppt
High_Low_Impedance_BusBar_Protection.pptHigh_Low_Impedance_BusBar_Protection.ppt
High_Low_Impedance_BusBar_Protection.pptThien Phan Bản
 
21955068-High-Low-Impedance-BusBar-Protection.ppt
21955068-High-Low-Impedance-BusBar-Protection.ppt21955068-High-Low-Impedance-BusBar-Protection.ppt
21955068-High-Low-Impedance-BusBar-Protection.pptThien Phan Bản
 
Electrical-Symbol-magnetic-ContactorsRelays.ppt
Electrical-Symbol-magnetic-ContactorsRelays.pptElectrical-Symbol-magnetic-ContactorsRelays.ppt
Electrical-Symbol-magnetic-ContactorsRelays.pptNotROYALgaming
 
Webinar 03 electrical installation of pv system
Webinar 03 electrical installation of pv system Webinar 03 electrical installation of pv system
Webinar 03 electrical installation of pv system solpowerpeople
 

Similar to 3560357.ppt (20)

Mechanical Design of Overhead Lines
Mechanical Design of Overhead LinesMechanical Design of Overhead Lines
Mechanical Design of Overhead Lines
 
Transmission lines of Electrical powe
Transmission lines of Electrical poweTransmission lines of Electrical powe
Transmission lines of Electrical powe
 
Contactor generalizations
Contactor generalizationsContactor generalizations
Contactor generalizations
 
Chapter 1 Introduction to power Electronic Devices.pdf
Chapter 1 Introduction to power Electronic Devices.pdfChapter 1 Introduction to power Electronic Devices.pdf
Chapter 1 Introduction to power Electronic Devices.pdf
 
Introduction to PCB Designing Tutorial
Introduction to PCB Designing TutorialIntroduction to PCB Designing Tutorial
Introduction to PCB Designing Tutorial
 
2008 Electrical & Data
2008 Electrical & Data2008 Electrical & Data
2008 Electrical & Data
 
Contactor generalizations
Contactor generalizationsContactor generalizations
Contactor generalizations
 
Switchgear.pptx
Switchgear.pptxSwitchgear.pptx
Switchgear.pptx
 
Residential wiring PPT.pptx
Residential wiring PPT.pptxResidential wiring PPT.pptx
Residential wiring PPT.pptx
 
Transformer Failure Due to Circuit Breaker Induced Switching Transients
Transformer Failure Due to Circuit Breaker Induced Switching TransientsTransformer Failure Due to Circuit Breaker Induced Switching Transients
Transformer Failure Due to Circuit Breaker Induced Switching Transients
 
Contactor generalizations
Contactor generalizationsContactor generalizations
Contactor generalizations
 
Concept of energy transmission & distribution
Concept of energy transmission & distribution Concept of energy transmission & distribution
Concept of energy transmission & distribution
 
Design of Electrical Installation of Buildings.ppt
Design of Electrical Installation of Buildings.pptDesign of Electrical Installation of Buildings.ppt
Design of Electrical Installation of Buildings.ppt
 
High_Low_Impedance_BusBar_Protection.ppt
High_Low_Impedance_BusBar_Protection.pptHigh_Low_Impedance_BusBar_Protection.ppt
High_Low_Impedance_BusBar_Protection.ppt
 
21955068-High-Low-Impedance-BusBar-Protection.ppt
21955068-High-Low-Impedance-BusBar-Protection.ppt21955068-High-Low-Impedance-BusBar-Protection.ppt
21955068-High-Low-Impedance-BusBar-Protection.ppt
 
Grounding and Bonding
Grounding and BondingGrounding and Bonding
Grounding and Bonding
 
Electrical-Symbol-magnetic-ContactorsRelays.ppt
Electrical-Symbol-magnetic-ContactorsRelays.pptElectrical-Symbol-magnetic-ContactorsRelays.ppt
Electrical-Symbol-magnetic-ContactorsRelays.ppt
 
Webinar 03 electrical installation of pv system
Webinar 03 electrical installation of pv system Webinar 03 electrical installation of pv system
Webinar 03 electrical installation of pv system
 
Contactor hoangphuongjsc.com
Contactor   hoangphuongjsc.comContactor   hoangphuongjsc.com
Contactor hoangphuongjsc.com
 
L03.1 l aa tv philips
L03.1 l aa tv philipsL03.1 l aa tv philips
L03.1 l aa tv philips
 

Recently uploaded

Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations120cr0395
 
Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxupamatechverse
 
MANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTING
MANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTINGMANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTING
MANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTINGSIVASHANKAR N
 
Introduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxIntroduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxupamatechverse
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escortsranjana rawat
 
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Christo Ananth
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...Call Girls in Nagpur High Profile
 
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Bookingdharasingh5698
 
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordAsst.prof M.Gokilavani
 
UNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular ConduitsUNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular Conduitsrknatarajan
 
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSMANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSSIVASHANKAR N
 
UNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its PerformanceUNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its Performancesivaprakash250
 
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Dr.Costas Sachpazis
 
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxpranjaldaimarysona
 
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 

Recently uploaded (20)

Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations
 
Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptx
 
MANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTING
MANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTINGMANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTING
MANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTING
 
Introduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxIntroduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptx
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
 
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
 
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
 
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
 
UNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular ConduitsUNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular Conduits
 
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSMANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
 
UNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its PerformanceUNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its Performance
 
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
 
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptx
 
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
 

3560357.ppt

  • 1. MElec-Ch2 - 1 Chapter 2 Electrical Wiring Practices and Diagrams
  • 2. MElec-Ch2 - 2 Overview • Safety • Standards • Wiring Considerations • Wire Terminations • Coaxial Cable • Wiring Installations • Wiring Diagrams
  • 3. MElec-Ch2 - 3 Safety • Lethal Current • Safety Precautions
  • 4. MElec-Ch2 - 4 Lethal Current • Fundamental policy of the USPS is SAFETY • Human Body  Resistance – 4 KΩ (moist skin) to 24 KΩ (dry skin)  Safe current (through chest) – less than 20 milliamps  E = 120 VAC R = 4 KΩ I = ?  I = 30 milliamps - NOT SAFE  Don’t want current through chest cavity (may be lethal)
  • 5. MElec-Ch2 - 5 Safety Precautions • Turn circuit off  Disconnect service cord  Disconnect negative battery cable • If must work on live AC circuit  Need 2nd safety person • Remove metal jewelry • Know your boat and its wiring • Use outlet tester on AC outlets • Use 3-wire extension cord from GFI outlet
  • 6. MElec-Ch2 - 6 Standards • American Boat and Yacht Council (ABYC)  AC and DC Electrical Systems is E-11  Minimum standards • Construction • Repair • Marine Dept. of Underwriters Laboratory  Test and certify commercial products  Safety, not function
  • 7. MElec-Ch2 - 7 Wiring Considerations • Conductors • Wire Types • Wire Size • Wire Insulation • Wire Color Code
  • 8. MElec-Ch2 - 8 Conductors • Connects power sources to power loads • Characteristics  Safe  Dependable  Efficient (minimal voltage drop) • Boat environment  Worse than either house or car  High humidity  Vibration  Corrosive conditions
  • 9. MElec-Ch2 - 9 Wire Types • Marine Grade  Type 3 is recommended • Stranded copper  Tinned is preferred
  • 10. MElec-Ch2 - 10 Wire Size • 3% voltage drop  Critical circuits (Nav lights)  Electronic Equipment • 10% voltage drop  Cabin lights  Motorized Equipment • Minimum size AWG # 16
  • 11. MElec-Ch2 - 11 Wire Has Resistance • Inadvertent Resistors  Wire too small (min of #16 - properly size using table)  Bad connections (or corroded connections) • Clean and tighten battery connectors • Tighten lug screws and inspect wire to lug connection  Why do wires get warm / hot? • Low resistance circuits pass high current (P = I2 x R) • Wires can account for much of the overall resistance V 12 VDC 0.1 Ώ 0.1 Ώ 10A What Voltage? An. 10 VDC
  • 12. MElec-Ch2 - 12 Wire Size Comparison #16 top to #10 bottom #2 top to #10 bottom
  • 13. MElec-Ch2 - 13 Copper Wire Characteristics
  • 14. MElec-Ch2 - 14 12- VDC Wire Size Selection
  • 15. MElec-Ch2 - 15 12 VDC Wire Size Selection
  • 16. MElec-Ch2 - 16 120 VAC Wire Size Selection
  • 17. MElec-Ch2 - 17 What Size Wires? B
  • 18. MElec-Ch2 - 18 Step 1 What current to Load? From Table 2-3 – Maximum of 44 feet (for 10A in #16 wire) P = E * I I = P / E I = 1200/120 I = 10 Amps From Table 2-1 – For 10A need #16 wire B
  • 19. MElec-Ch2 - 19 Step 1 Answers AMPACITY 10 Amperes #16 AWG TW by Table 2-1 for 3% voltage drop 44 feet maximum by Table 2-3 B
  • 20. MElec-Ch2 - 20 Step 2 What current to Inverter? From Table 2-3 – Maximum of 14 feet (for 110A in #1 wire) Iload = Iout = Iin *0.91 Iin = Iout / 0.91 = 100 / 0.91 = 110 Amps From Table 2-1 – For 110A need #1 wire B Iload = 100 Amps @ 12 V
  • 21. MElec-Ch2 - 21 Step 2 Answers AMPACITY 110 Amperes #1 AWG TW by Table 1 for 3% voltage drop 14 feet maximum by Table 2-2A B
  • 22. MElec-Ch2 - 22 Wire Insulation • AC cables must be type UL 1426 BC  600 volt insulation  Gasoline and Oil resistant  Won’t absorb moisture • DC wires & cables must be Marine Grade  600 volt insulation  Gasoline and Oil resistant  Won’t absorb moisture • Color coded wires
  • 23. MElec-Ch2 - 23 Wire Color Code Color AC (Hot) AC (Neut) AC (Gnd) DC + DC - Black X X1 White X Green (may have a yellow stripe) X Red X2 X Yellow X1 Footnotes: 1 – Yellow preferred for DC negative to avoid confusion with AC Hot wire 2 – 2nd hot wire in 220 VAC is Red
  • 24. MElec-Ch2 - 24 Wire Color Coding
  • 25. MElec-Ch2 - 25 Wire Terminations • Crimping  Special Tool  Approved Marine Connectors  Use of Ratcheting Tool • Solder • Heat-shrink Tubing
  • 26. MElec-Ch2 - 26 Wire Terminals
  • 27. MElec-Ch2 - 27 Ratcheting Crimper YES NO
  • 28. MElec-Ch2 - 28 Ratcheting Tool Use • First select appropriate connector • Strip insulation length of stem plus 1/16” • Insert stripped end all way into terminal  End should extend 1/16” • Place terminal in same color slot  First crimp end of terminal barrel nearest ring  Then crimp wire end of terminal barrel • Check the connection with a solid tug
  • 29. MElec-Ch2 - 29 Soldering • Terminal connection can’t be only soldered  Must also be crimped • Soldering is normally not required  Crimped connectors are acceptable to ABYC  If solder, apply only to ring end of terminal • Solder changes stranded wire into solid  Stranded wire is flexible • Use 40% lead / 60% tin, rosin core solder • Battery lugs may be only soldered
  • 30. MElec-Ch2 - 30 Heat-Shrink Tubing Application Steps
  • 31. MElec-Ch2 - 31 Coaxial Cable • Antenna cable • Radio coax is 50 ohm with PL-259 • Radio cable is cut to length • Want attenuation under 3 db • TV cable is 75 ohm with “F” connectors • GPS cable is not cut to length  Coil excess in 1-foot loops
  • 32. MElec-Ch2 - 32 Coaxial Cable Information
  • 33. MElec-Ch2 - 33 Soldering PL-259 Connector
  • 34. MElec-Ch2 - 34 Wiring Installation • Basic Considerations • Distribution Panel • Fuses / Circuit Breakers • Branch Circuits  Wire  Outlets  Switches • Grounding Systems • Bonding Systems
  • 35. MElec-Ch2 - 35 Basic Considerations • Must have source and return wires  Return wires to a common point  May use feeder wire from power panel for: • engine, helm console, etc. • Wires above flood level of bilge  Waterproof if in bilge • Insulated support every 18” • Twist DC wires within 1 meter of compass
  • 36. MElec-Ch2 - 36 Distribution Panel • Central location of Circuit Breakers / Fuses  All branch circuits from this location • AC and DC may be combined in one panel • All equipment / circuits should go to panel  Not direct to battery (except bilge pump) • Noise interference suppression covered in Section 7
  • 37. MElec-Ch2 - 37 DC / AC Power Panel Front View
  • 38. MElec-Ch2 - 38 Inside Power Panel DC Side Buss Bars
  • 39. MElec-Ch2 - 39 Fuses and Circuit Breakers • Used to protect wiring from over current  In positive or hot wire • Newer boats use circuit breakers  Initially more expensive • Replace blown fuse with correct rating • Circuit Breakers should be Marine Grade  Trip free  Manual reset
  • 40. MElec-Ch2 - 40 Branch Circuits - Wires • Minimum size is 16 AWG  See Wire Selection Tables  For AC normally #14 for 15A and #12 for 20A • Must terminate in closed electrical box • Of sufficient length • DC negative returned to DC Panel  May use several negative feeder terminals • AC neutrals returned to AC Panel • Bonding system never used as return wire
  • 41. MElec-Ch2 - 41 Branch Circuits - Outlets • 120 VAC outlets must be 3-wire polarized  Black (hot) to brass or copper colored terminal • Outlet wires must have crimp terminals • GFI outlets  Required on weather deck, head, galley and machinery spaces  Good practice for all AC outlets to be GFI  Trip at 5 milliamps • Different outlets for AC and DC power
  • 42. MElec-Ch2 - 42 Outlets and Plugs DC Outlet (Receptacle) DC Plug 120 VAC 120 VAC 12 VDC 120 VAC 15 A Outlet AC Plug 15 A AC Plug 20 A GFI 15 A Outlet 20 A Outlet
  • 43. MElec-Ch2 - 43 Branch Circuits - Switches • Modern panels use Circuit Breakers  Which also double as switches • Switches / Circuit Breakers  Must be Marine Grade  Rated for the voltage and current controlled  Interrupt the positive (DC) or hot (AC) leg • Battery Switch  Designed for high current service  Not located in engine or fuel-tank compartments
  • 44. MElec-Ch2 - 44 Grounding System • Ground is potential of water around boat  Or potential of earth’s surface • DC – Ground Battery negative terminal(s)  Also engine block  Wire color is Yellow (or Black) • AC – Transformer center tap on shore  Also connected to ground rod at transformer  Wire color is Green and uninterrupted wire • Isolation transformers and galvanic isolators are exception and covered in Chapter 4 on AC • Engine, DC negative & AC ground connected
  • 45. MElec-Ch2 - 45 Bonding System • For lightning protection  More in Chapter 6 • All metal objects should be bonded  Keeps all metal at zero potential  Engine blocks  Battery negative terminals • Non-current carrying wire • Through-hull fittings  ABYC now recommends they be bonded  Electrically isolated from metal hull
  • 47. MElec-Ch2 - 47 Wiring Diagrams • Elements of a Good Wiring Diagram  Documents boat’s electrical layout  Should be kept current  Used for troubleshooting • Component Identification  Physical objects to their symbol  Wires are color coded
  • 48. MElec-Ch2 - 48 Wiring Diagram Symbols Switch, double pole, single throw (DPST) Switch, single pole, single throw (SPST) Switch, single pole, double throw (SPDT) Battery (long line on top is positive) Wires connected (at dots) Wires crossing (but NOT connected) Wire (insulated, metal conductor) Incandescent Light Alternate symbol for Light Circuit Breaker Fuse Ground Male Connector Female Connector
  • 49. MElec-Ch2 - 49 Simple DC Wiring Diagram
  • 50. MElec-Ch2 - 50 Summary • Circuits should be off when working on them • Use only marine grade properly sized wires  Tables will help determine proper wire size  Minimum wire size is #16 AWG • Use wire terminations and ratcheting crimper • DC circuits are 2 dedicated wires  Waterproof wire connection in bilge • AC circuits are 3 dedicated wires  GFCI in galley, head, machine spaces & weather deck • Separate Grounding & Bonding systems required • Keep wiring diagram current