1 The Top 5 Most Over-Engineered Building Components
THE TOP 5 MOST
OVER-ENGINEERED
BUILDING COMPONENTS
2 The Top 5 Most Over-Engineered Building Components
INTRODUCTION
When specifying the mechanical and electrical equipment
for a building, it is easy to assume that extra capacity is a
good thing, but it actually can be just as counterproductive
as having undersized installations. In the first place, extra
capacity comes at a higher upfront cost, which makes
the building owner assume unnecessary expenses.
There are also many types of equipment that experience
performance issues when over-engineered, which can
range from low energy efficiency to a diminished service
life. In a few words, oversized systems come with both a
higher price tag and an increased operating cost.
This ebook will provide an overview of the building systems
that are most commonly over-engineered, pointing
out the pitfalls that must be avoided and the negative
consequences that can come from excessive capacity.
3 The Top 5 Most Over-Engineered Building Components
1 AIR DUCTS
Air ducts play a very important role in HVAC systems that use packaged rooftop
units or chillers with air-handling units, and designing duct systems properly is
critical in order to guarantee high performance.
For NYC buildings, duct systems must meet the requirements set forth in:
•	 The NYC Building Code
•	 The NYC Mechanical Code, which dedicates its entire Chapter 6 to duct systems
•	 The ASHRAE Handbook of Fundamentals
•	 The HVAC Duct Construction Standards by SMACNA (Sheet Metal & Air
Conditioning Contractors’ National Association)
Proper duct design is based on controlling two key variables: airspeed
and pressure drop.
When these variables exceed their optimal design range, the duct system becomes
both noisy and inefficient. Ideally, a duct system should be designed for a pressure
drop of 0.08 inches of water per every 100 feet of length, and air velocity should be
kept under 1200 feet per minute.
 Learn which HVAC system is the right system for your building. 
4 The Top 5 Most Over-Engineered Building Components
Both pressure drop and velocity decrease as the cross-sectional area of a
duct becomes larger, but there is an upper limit to how much duct size can be
increased.
•	 The system becomes more expensive for the simple reason that material and labor
costs are higher.
•	 The design process of other building systems may be complicated by the fact that
ducts take up so much space. It may even be necessary to reduce ceiling height,
disrupting the architectural design.
•	 Oversized ducts increase fan power because a larger air volume has to be moved
through the system.
An ideal duct design keeps pressure drop and air speed under design values, while
optimizing the cross-sectional area of ductwork.
5 The Top 5 Most Over-Engineered Building Components
2 BOILERS
Even in buildings where high-efficiency boilers are used, heating is normally one of
the highest energy expenses; this is especially true for New York and other cities to
the northeast of the country, which have cold winters. There are boiler systems for
practically any type of energy input, including fossil fuels such as oil or natural gas,
electricity, or alternative sources such as sunlight and biodiesel.
Given the critical role they play in buildings, as well as the potential negative
consequences that can come from system malfunctioning, the NYC Department
of Buildings has a dedicated Boiler Unit. This unit oversees the installation and
operation of boilers, and runs a yearly inspection cycle for all systems currently in
operation. Boilers are addressed in the NYC Building Code, Mechanical Code, and
Plumbing Code, and the Fuel Gas Code also applies if the boiler is combustion-based.
Redundancy is desirable in boiler systems, but installing two boilers sized for the full
building load each can result in plenty of unused capacity and a high upfront cost.
The best design recommendation is to size each boiler for 60% of the total building
load, which provides a favorable degree of redundancy, as well as an extra 20%
capacity that can be used during initial building warmup.
Avoiding “rules of thumb” is strongly recommended, since they can result in
boiler systems that are two to three times larger than required.
6 The Top 5 Most Over-Engineered Building Components
Boilers could eventually be displaced by variable refrigerant flow (VRF) systems,
which offer a much higher energy efficiency, as well as greater flexibility to meet
varying heating loads. As implied by their name, VRF systems use refrigerant to
deliver or remove heat, and speed is controlled according to the current building load.
THE ADVANTAGES OF VRF SYSTEMS ARE SIGNIFICANT:
•	 They can use heat pumps, which operate in both heating and cooling modes,
displacing both boilers and traditional AC condensers. The latest heat pump
models offer a comparable efficiency to a chiller in cooling mode, and in heating
mode they can provide savings of over 70% compared to a resistance heater.
•	 Heat is transported in refrigerant lines, which are much more compact than water
pipes and air ducts.
•	 VRF systems are modular, which allows them to be expanded incrementally
according to building needs – boilers, chillers, and packaged rooftop units are
limited in this aspect by their fixed capacities.
VRF systems are very popular in Japan, where they were developed, as well as
in Europe. They are relatively new in the US market, but their installed cost is
comparable to that of a traditional chiller-based system.
7 The Top 5 Most Over-Engineered Building Components
3 AIR CONDITIONERS
The performance of air conditioning equipment improves in direct proportion
to how well the unit matches the application. There is a common but erroneous
belief that oversizing the unit is preferable, so that it can cool indoor spaces
faster while reducing the compressor runtime. However, this comes with many
performance issues. Also, even though the compressor runs less time, it also
draws more power than a properly sized unit, so energy savings are minimal or
zero.
Air conditioning systems are addressed in the NYC Building Code and Mechanical
Code. The ASHRAE Handbook of Fundamentals is also a solid reference when
designing any HVAC system.
POOR HUMIDITY CONTROL
An effective air conditioning system doesn’t only remove indoor heat; it also keeps
humidity within a range that is comfortable for human beings. When an AC system
is oversized, it can reach the required indoor temperature within a shorter amount of
time, and then the compressor is turned off – or slowed down in modern units with
variable speed capabilities. The problem when AC units operate like this is that there
is not enough time for them to bring indoor humidity to acceptable levels, and this
results in an indoor environment that is cold but humid, similar to a refrigerator. Other
than causing discomfort, this is a situation that can result in respiratory health issues
among occupants.
8 The Top 5 Most Over-Engineered Building Components
EXCESSIVE COMPRESSOR CYCLING
An oversized AC unit has spare cooling power, so it can bring indoor temperature in
less time than a properly sized system. This means that the unit will tend to operate in
a series of short bursts, which can wear down electrical and mechanical components,
reducing their service life. On the other hand, a properly sized compressor runs for
longer periods but without frequent starts and stops, which is the intended mode of
operation.
When AC installations are compared based on their total ownership cost, considering
both energy and maintenance expenses as well as their service life, a system of
optimal capacity is superior to both undersized and oversized systems.
DISCOMFORT FOR OCCUPANTS
Since an oversized AC unit has excessive cooling power for the application, sitting
right under an air duct opening or in front of an evaporator can be very uncomfortable.
The fans of evaporators are normally sized in proportion to the AC unit, so the air is
both cold and fast-moving, causing a chilling effect.
9 The Top 5 Most Over-Engineered Building Components
4 ELECTRICAL POWER
Plenty of devices and systems used in buildings run on electric power, and
that includes many types of mechanical equipment. When specifying electrical
installations, the same principle used in mechanical systems applies: components
should have just the right capacity for the application, not less and not more.
Electrical installations in New York City are required to comply with the following
codes:
•	 NYC Building Code – in particular, Chapter 27
•	 NYC Electrical Code
•	 NFPA 70: National Electric Code
•	 In the case of emergency and standby power systems, compliance with NFPA 110,
NFPA 111, and the NYC Fuel Gas Code is also required.
OVERSIZED FEEDERS AND BRANCH CIRCUITS
Undersized electrical circuits tend to fail quickly, sometimes within hours, but
oversized circuits have no negative consequences in terms of operation. In fact, an
oversized electrical circuit experiences a lower voltage drop and power loss than a
properly sized circuit. However, this benefit is negligible compared with the project
cost increase that comes with oversized electrical installations.
 Get a free calculation of your electric load. 
10 The Top 5 Most Over-Engineered Building Components
ELECTRIC MOTORS
The case of motors is different from that of conductors, and there are several
negative consequences when they are oversized:
•	 Motor efficiency is reduced under part-load conditions. For a given mechanical
load, a properly specified motor operating near full load will be more efficient than
an oversized motor.
•	 Power factor is also reduced. The oversized motor draws a high reactive current,
which can contribute to power factor charges in the power bill. The extra reactive
current also uses up capacity in transformers, distribution boards, and circuits,
without contributing to the transmission of useful power.
When motors will be subject to part-load conditions frequently, the best option is to
use technologies that allow speed control: Electronically commutated motors (ECMs)
can be used for fractional horsepower applications, and variable frequency drives
(VFDs) with three-phase motors can be deployed for larger loads.
11 The Top 5 Most Over-Engineered Building Components
If the motors in a building will be upgraded, three aspects must be considered to
achieve the best possible results:
•	 Adequate horsepower.
•	 Upgrading to a higher efficiency tier, for example NEMA Premium.
•	 Implementing automation and speed control measures.
In chiller-based air conditioning systems, it is possible to achieve exceptional synergy
if the chiller plant has variable-speed multi-stage compressors, while the associated
water pumps and AHUs use motors with speed control.
12 The Top 5 Most Over-Engineered Building Components
5 SPRINKLER SYSTEMS
A complex building layout normally means that the fire sprinkler system will have a
piping layout of similar complexity, as well as a high sprinkler headcount. When the
teams in charge of architectural design and fire protection design work in isolation,
complex sprinkler systems are a common consequence.
These systems come with many drawbacks:
•	 The upfront cost is increased, both in terms of materials and labor.
•	 Pumps must be sized larger to provide the adequate water pressure and flow rate
for a system with more piping length and a higher sprinkler count.
The following are some design recommendations to optimize sprinkler layouts,
reducing their complexity and upfront cost:
•	 Coordinating fire sprinkler design and architectural design, so that the interference
of ceiling features, such as offsets and soffits, is minimized.
•	 Merging smaller rooms into single areas whenever possible, because each time a
small room is added, the sprinkler count is increased by one.
 Learn more about our sprinkler engineering services. 
13 The Top 5 Most Over-Engineered Building Components
When designing sprinkler systems in New York, it is important to observe the
requirements set for in the following standards and codes:
•	 NYC Building Code – in particular, Chapter 7 (Fire and Smoke Protection Features),
Chapter 9 (Fire Protection Systems) and Appendix Q (Modifications to National
Standards)
•	 NYC Fire Code
•	 NFPA 13 – Standard for the Installation of Sprinkler Systems
•	 NFPA 13D – Standard for the Installation of Sprinkler Systems in One- and Two-
Family Dwellings and Manufactured Homes
•	 NFPA 13R – Standard for the Installation of Sprinkler Systems in Low-Rise
Residential Occupancies
It is important to note that Appendix Q of the Building Code takes precedence over
national standards, introducing modifications that are specific for New York.
14 The Top 5 Most Over-Engineered Building Components
CONCLUDING REMARKS
There are many reasons not to oversize mechanical and electrical building systems.
In most cases, oversized systems are just as problematic as undersized systems, if
not more, causing performance issues and extra maintenance expenses. Even when
there are no performance issues associated with extra capacity, it represents a higher
upfront cost that must be assumed by the building owner.
Hiring professional MEP designers is the best way to ensure all building systems will
be specified optimally according to the application at hand. Meeting applicable codes
and standards is mandatory for a building to be approved, but these documents often
specify just the minimum requirements; with professional design, a project can meet
code requirements while maximizing performance.
15 The Top 5 Most Over-Engineered Building Components
Over-engineering a project drives up construction cost
without any benefit. Get your construction project back on
budget with a free value engineering service.
REQUEST A CONSULTATION
WANT TO LEARN MORE?

More Related Content

What's hot

How Row-based Data Center Cooling Works
How Row-based Data Center Cooling WorksHow Row-based Data Center Cooling Works
How Row-based Data Center Cooling WorksSchneider Electric
 
2015 x472 class 10 - lcca
2015 x472 class 10 - lcca2015 x472 class 10 - lcca
2015 x472 class 10 - lccamichaeljmack
 
Topic 04 chilled beam system note version small
Topic 04 chilled beam system note version smallTopic 04 chilled beam system note version small
Topic 04 chilled beam system note version smallpnnazz
 
Ashrae CRC presentation doas with chilled beam
Ashrae CRC presentation doas with chilled beamAshrae CRC presentation doas with chilled beam
Ashrae CRC presentation doas with chilled beambostjanpeterman
 
Introduction to VRF
Introduction to VRF Introduction to VRF
Introduction to VRF John Chavez
 
The Use of Ceiling Ducted Air Containment in Data Centers
The Use of Ceiling Ducted Air Containment in Data CentersThe Use of Ceiling Ducted Air Containment in Data Centers
The Use of Ceiling Ducted Air Containment in Data CentersSchneider Electric
 
Central heating level 3
Central heating level 3Central heating level 3
Central heating level 3Barry Everard
 
HVAC Control Systems— Get it Right the First Time! (Part 3)
HVAC Control Systems— Get it Right the First Time! (Part 3)HVAC Control Systems— Get it Right the First Time! (Part 3)
HVAC Control Systems— Get it Right the First Time! (Part 3)Dynamix Energy Services
 
VARIABLE REFRIGERANT FLOW(VRF) ppt
VARIABLE REFRIGERANT FLOW(VRF)  pptVARIABLE REFRIGERANT FLOW(VRF)  ppt
VARIABLE REFRIGERANT FLOW(VRF) pptEzhil Raj s
 
Cooling tower, chilling plants ppt
Cooling tower, chilling plants pptCooling tower, chilling plants ppt
Cooling tower, chilling plants pptRajesh Patil
 
engr103_grp06710_finRep (1)
engr103_grp06710_finRep (1)engr103_grp06710_finRep (1)
engr103_grp06710_finRep (1)Austin Omolo
 
Data center cooling infrastructure slide
Data center cooling infrastructure slideData center cooling infrastructure slide
Data center cooling infrastructure slideLivin Jose
 
Acb presentation
Acb presentationAcb presentation
Acb presentationdean129
 
HVAC Systems- A Complete Guide
HVAC Systems- A Complete GuideHVAC Systems- A Complete Guide
HVAC Systems- A Complete GuideFordly
 
Integrating Radiant Cooling Systems for Energy Efficiency
Integrating Radiant Cooling Systems for Energy EfficiencyIntegrating Radiant Cooling Systems for Energy Efficiency
Integrating Radiant Cooling Systems for Energy EfficiencyCenter for Sustainable Energy
 
DADANCO ACTIVE CHILLED BEAMS
DADANCO ACTIVE CHILLED BEAMSDADANCO ACTIVE CHILLED BEAMS
DADANCO ACTIVE CHILLED BEAMSbostjanpeterman
 

What's hot (20)

How Row-based Data Center Cooling Works
How Row-based Data Center Cooling WorksHow Row-based Data Center Cooling Works
How Row-based Data Center Cooling Works
 
2015 x472 class 10 - lcca
2015 x472 class 10 - lcca2015 x472 class 10 - lcca
2015 x472 class 10 - lcca
 
Topic 04 chilled beam system note version small
Topic 04 chilled beam system note version smallTopic 04 chilled beam system note version small
Topic 04 chilled beam system note version small
 
Ashrae CRC presentation doas with chilled beam
Ashrae CRC presentation doas with chilled beamAshrae CRC presentation doas with chilled beam
Ashrae CRC presentation doas with chilled beam
 
Introduction to VRF
Introduction to VRF Introduction to VRF
Introduction to VRF
 
The Use of Ceiling Ducted Air Containment in Data Centers
The Use of Ceiling Ducted Air Containment in Data CentersThe Use of Ceiling Ducted Air Containment in Data Centers
The Use of Ceiling Ducted Air Containment in Data Centers
 
Central heating level 3
Central heating level 3Central heating level 3
Central heating level 3
 
HVAC Control Systems— Get it Right the First Time! (Part 3)
HVAC Control Systems— Get it Right the First Time! (Part 3)HVAC Control Systems— Get it Right the First Time! (Part 3)
HVAC Control Systems— Get it Right the First Time! (Part 3)
 
VARIABLE REFRIGERANT FLOW(VRF) ppt
VARIABLE REFRIGERANT FLOW(VRF)  pptVARIABLE REFRIGERANT FLOW(VRF)  ppt
VARIABLE REFRIGERANT FLOW(VRF) ppt
 
RESNET: HVAC Presentation
RESNET: HVAC PresentationRESNET: HVAC Presentation
RESNET: HVAC Presentation
 
Cooling tower, chilling plants ppt
Cooling tower, chilling plants pptCooling tower, chilling plants ppt
Cooling tower, chilling plants ppt
 
engr103_grp06710_finRep (1)
engr103_grp06710_finRep (1)engr103_grp06710_finRep (1)
engr103_grp06710_finRep (1)
 
HVAC: New chiller requirements
HVAC: New chiller requirementsHVAC: New chiller requirements
HVAC: New chiller requirements
 
Data center cooling infrastructure slide
Data center cooling infrastructure slideData center cooling infrastructure slide
Data center cooling infrastructure slide
 
Acb presentation
Acb presentationAcb presentation
Acb presentation
 
Hvac complete final
Hvac complete finalHvac complete final
Hvac complete final
 
HVAC Systems- A Complete Guide
HVAC Systems- A Complete GuideHVAC Systems- A Complete Guide
HVAC Systems- A Complete Guide
 
HVAC for Data Centers
HVAC for Data CentersHVAC for Data Centers
HVAC for Data Centers
 
Integrating Radiant Cooling Systems for Energy Efficiency
Integrating Radiant Cooling Systems for Energy EfficiencyIntegrating Radiant Cooling Systems for Energy Efficiency
Integrating Radiant Cooling Systems for Energy Efficiency
 
DADANCO ACTIVE CHILLED BEAMS
DADANCO ACTIVE CHILLED BEAMSDADANCO ACTIVE CHILLED BEAMS
DADANCO ACTIVE CHILLED BEAMS
 

Similar to Five Topmost Over-Engineered Building Components

Aircon Saver
Aircon SaverAircon Saver
Aircon Saverselengia
 
B597-EN-D_Gas_Cooling_Primary_Metals.pdf
B597-EN-D_Gas_Cooling_Primary_Metals.pdfB597-EN-D_Gas_Cooling_Primary_Metals.pdf
B597-EN-D_Gas_Cooling_Primary_Metals.pdfssusercf6d0e
 
Comparison between Systems
Comparison between SystemsComparison between Systems
Comparison between SystemsVictor Ashkenazy
 
DOE NREL TEST Report 2014
DOE NREL TEST Report 2014DOE NREL TEST Report 2014
DOE NREL TEST Report 2014Charles Rice
 
Energy Efficient Air Conditioning System
Energy Efficient Air Conditioning SystemEnergy Efficient Air Conditioning System
Energy Efficient Air Conditioning SystemTantish QS, UTM
 
Saving energy with cooling towers
Saving energy with cooling towersSaving energy with cooling towers
Saving energy with cooling towersAbdelrahim Ramadan
 
Turbine Inlet Air Cooling (TIAC) - Case Studies - Economics - Performance - C...
Turbine Inlet Air Cooling (TIAC) - Case Studies - Economics - Performance - C...Turbine Inlet Air Cooling (TIAC) - Case Studies - Economics - Performance - C...
Turbine Inlet Air Cooling (TIAC) - Case Studies - Economics - Performance - C...Salman Haider
 
Mechanical systems
Mechanical systemsMechanical systems
Mechanical systemsSunil Surya
 
2015 Commercial Products LENNOX
2015 Commercial Products LENNOX2015 Commercial Products LENNOX
2015 Commercial Products LENNOXVictor Neugebauer
 
How do i optimize industrial refrigeration system
How do i optimize industrial refrigeration systemHow do i optimize industrial refrigeration system
How do i optimize industrial refrigeration systemAlaquainc
 
Presentation to Corporate-chain business (1)
Presentation to Corporate-chain business (1)Presentation to Corporate-chain business (1)
Presentation to Corporate-chain business (1)Emily Parfet
 
Air conditioning if its not clean - its not green - ACT smart 4th sept 2014
Air conditioning   if its not clean - its not green - ACT smart 4th sept 2014Air conditioning   if its not clean - its not green - ACT smart 4th sept 2014
Air conditioning if its not clean - its not green - ACT smart 4th sept 2014Phil Wilkinson F.AIRAH F.IEAust M.ASHRAE
 
Heatstar Technical Advice paper - 'New 2022 building regulations'
Heatstar Technical Advice paper - 'New 2022 building regulations'Heatstar Technical Advice paper - 'New 2022 building regulations'
Heatstar Technical Advice paper - 'New 2022 building regulations'Heatstar
 
Optimizing the Steam Generation Cycle and Condensate Recovery Process
Optimizing the Steam Generation Cycle and Condensate Recovery ProcessOptimizing the Steam Generation Cycle and Condensate Recovery Process
Optimizing the Steam Generation Cycle and Condensate Recovery ProcessM.S. Jacobs & Associates
 
Optimizing the Steam Generation Cycle and Condensate Recovery Process
Optimizing the Steam Generation Cycle and Condensate Recovery ProcessOptimizing the Steam Generation Cycle and Condensate Recovery Process
Optimizing the Steam Generation Cycle and Condensate Recovery ProcessBelilove Company-Engineers
 
Energy performance in mission critical facilities
Energy performance in mission critical facilitiesEnergy performance in mission critical facilities
Energy performance in mission critical facilitiesAlcides Villarreal Polo
 

Similar to Five Topmost Over-Engineered Building Components (20)

Aircon Saver
Aircon SaverAircon Saver
Aircon Saver
 
B597-EN-D_Gas_Cooling_Primary_Metals.pdf
B597-EN-D_Gas_Cooling_Primary_Metals.pdfB597-EN-D_Gas_Cooling_Primary_Metals.pdf
B597-EN-D_Gas_Cooling_Primary_Metals.pdf
 
Comparison between Systems
Comparison between SystemsComparison between Systems
Comparison between Systems
 
DOE NREL TEST Report 2014
DOE NREL TEST Report 2014DOE NREL TEST Report 2014
DOE NREL TEST Report 2014
 
Energy Efficient Air Conditioning System
Energy Efficient Air Conditioning SystemEnergy Efficient Air Conditioning System
Energy Efficient Air Conditioning System
 
Saving energy with cooling towers
Saving energy with cooling towersSaving energy with cooling towers
Saving energy with cooling towers
 
Datacentre Uk
Datacentre UkDatacentre Uk
Datacentre Uk
 
Turbine Inlet Air Cooling (TIAC) - Case Studies - Economics - Performance - C...
Turbine Inlet Air Cooling (TIAC) - Case Studies - Economics - Performance - C...Turbine Inlet Air Cooling (TIAC) - Case Studies - Economics - Performance - C...
Turbine Inlet Air Cooling (TIAC) - Case Studies - Economics - Performance - C...
 
Mechanical systems
Mechanical systemsMechanical systems
Mechanical systems
 
2015 Commercial Products LENNOX
2015 Commercial Products LENNOX2015 Commercial Products LENNOX
2015 Commercial Products LENNOX
 
How do i optimize industrial refrigeration system
How do i optimize industrial refrigeration systemHow do i optimize industrial refrigeration system
How do i optimize industrial refrigeration system
 
Presentation to Corporate-chain business (1)
Presentation to Corporate-chain business (1)Presentation to Corporate-chain business (1)
Presentation to Corporate-chain business (1)
 
Air conditioning if its not clean - its not green - ACT smart 4th sept 2014
Air conditioning   if its not clean - its not green - ACT smart 4th sept 2014Air conditioning   if its not clean - its not green - ACT smart 4th sept 2014
Air conditioning if its not clean - its not green - ACT smart 4th sept 2014
 
Lennox Raider
Lennox RaiderLennox Raider
Lennox Raider
 
Heatstar Technical Advice paper - 'New 2022 building regulations'
Heatstar Technical Advice paper - 'New 2022 building regulations'Heatstar Technical Advice paper - 'New 2022 building regulations'
Heatstar Technical Advice paper - 'New 2022 building regulations'
 
Optimizing the Steam Generation Cycle and Condensate Recovery Process
Optimizing the Steam Generation Cycle and Condensate Recovery ProcessOptimizing the Steam Generation Cycle and Condensate Recovery Process
Optimizing the Steam Generation Cycle and Condensate Recovery Process
 
Optimizing the Steam Generation Cycle and Condensate Recovery Process
Optimizing the Steam Generation Cycle and Condensate Recovery ProcessOptimizing the Steam Generation Cycle and Condensate Recovery Process
Optimizing the Steam Generation Cycle and Condensate Recovery Process
 
Adm apn045-en 0912
Adm apn045-en 0912Adm apn045-en 0912
Adm apn045-en 0912
 
Energy performance in mission critical facilities
Energy performance in mission critical facilitiesEnergy performance in mission critical facilities
Energy performance in mission critical facilities
 
Data center m&e
Data center  m&eData center  m&e
Data center m&e
 

Recently uploaded

Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingrakeshbaidya232001
 
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).pptssuser5c9d4b1
 
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)Suman Mia
 
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
Internship report on mechanical engineering
Internship report on mechanical engineeringInternship report on mechanical engineering
Internship report on mechanical engineeringmalavadedarshan25
 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...Soham Mondal
 
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSKurinjimalarL3
 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxpranjaldaimarysona
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
Call Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile serviceCall Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile servicerehmti665
 
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVRajaP95
 
GDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentationGDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentationGDSCAESB
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escortsranjana rawat
 
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
Analog to Digital and Digital to Analog Converter
Analog to Digital and Digital to Analog ConverterAnalog to Digital and Digital to Analog Converter
Analog to Digital and Digital to Analog ConverterAbhinavSharma374939
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxAsutosh Ranjan
 

Recently uploaded (20)

Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writing
 
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
 
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
 
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
 
Internship report on mechanical engineering
Internship report on mechanical engineeringInternship report on mechanical engineering
Internship report on mechanical engineering
 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
 
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptx
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
 
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
 
Call Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile serviceCall Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile service
 
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
 
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
 
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptxExploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
 
GDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentationGDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentation
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
 
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
Analog to Digital and Digital to Analog Converter
Analog to Digital and Digital to Analog ConverterAnalog to Digital and Digital to Analog Converter
Analog to Digital and Digital to Analog Converter
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptx
 

Five Topmost Over-Engineered Building Components

  • 1. 1 The Top 5 Most Over-Engineered Building Components THE TOP 5 MOST OVER-ENGINEERED BUILDING COMPONENTS
  • 2. 2 The Top 5 Most Over-Engineered Building Components INTRODUCTION When specifying the mechanical and electrical equipment for a building, it is easy to assume that extra capacity is a good thing, but it actually can be just as counterproductive as having undersized installations. In the first place, extra capacity comes at a higher upfront cost, which makes the building owner assume unnecessary expenses. There are also many types of equipment that experience performance issues when over-engineered, which can range from low energy efficiency to a diminished service life. In a few words, oversized systems come with both a higher price tag and an increased operating cost. This ebook will provide an overview of the building systems that are most commonly over-engineered, pointing out the pitfalls that must be avoided and the negative consequences that can come from excessive capacity.
  • 3. 3 The Top 5 Most Over-Engineered Building Components 1 AIR DUCTS Air ducts play a very important role in HVAC systems that use packaged rooftop units or chillers with air-handling units, and designing duct systems properly is critical in order to guarantee high performance. For NYC buildings, duct systems must meet the requirements set forth in: • The NYC Building Code • The NYC Mechanical Code, which dedicates its entire Chapter 6 to duct systems • The ASHRAE Handbook of Fundamentals • The HVAC Duct Construction Standards by SMACNA (Sheet Metal & Air Conditioning Contractors’ National Association) Proper duct design is based on controlling two key variables: airspeed and pressure drop. When these variables exceed their optimal design range, the duct system becomes both noisy and inefficient. Ideally, a duct system should be designed for a pressure drop of 0.08 inches of water per every 100 feet of length, and air velocity should be kept under 1200 feet per minute.  Learn which HVAC system is the right system for your building. 
  • 4. 4 The Top 5 Most Over-Engineered Building Components Both pressure drop and velocity decrease as the cross-sectional area of a duct becomes larger, but there is an upper limit to how much duct size can be increased. • The system becomes more expensive for the simple reason that material and labor costs are higher. • The design process of other building systems may be complicated by the fact that ducts take up so much space. It may even be necessary to reduce ceiling height, disrupting the architectural design. • Oversized ducts increase fan power because a larger air volume has to be moved through the system. An ideal duct design keeps pressure drop and air speed under design values, while optimizing the cross-sectional area of ductwork.
  • 5. 5 The Top 5 Most Over-Engineered Building Components 2 BOILERS Even in buildings where high-efficiency boilers are used, heating is normally one of the highest energy expenses; this is especially true for New York and other cities to the northeast of the country, which have cold winters. There are boiler systems for practically any type of energy input, including fossil fuels such as oil or natural gas, electricity, or alternative sources such as sunlight and biodiesel. Given the critical role they play in buildings, as well as the potential negative consequences that can come from system malfunctioning, the NYC Department of Buildings has a dedicated Boiler Unit. This unit oversees the installation and operation of boilers, and runs a yearly inspection cycle for all systems currently in operation. Boilers are addressed in the NYC Building Code, Mechanical Code, and Plumbing Code, and the Fuel Gas Code also applies if the boiler is combustion-based. Redundancy is desirable in boiler systems, but installing two boilers sized for the full building load each can result in plenty of unused capacity and a high upfront cost. The best design recommendation is to size each boiler for 60% of the total building load, which provides a favorable degree of redundancy, as well as an extra 20% capacity that can be used during initial building warmup. Avoiding “rules of thumb” is strongly recommended, since they can result in boiler systems that are two to three times larger than required.
  • 6. 6 The Top 5 Most Over-Engineered Building Components Boilers could eventually be displaced by variable refrigerant flow (VRF) systems, which offer a much higher energy efficiency, as well as greater flexibility to meet varying heating loads. As implied by their name, VRF systems use refrigerant to deliver or remove heat, and speed is controlled according to the current building load. THE ADVANTAGES OF VRF SYSTEMS ARE SIGNIFICANT: • They can use heat pumps, which operate in both heating and cooling modes, displacing both boilers and traditional AC condensers. The latest heat pump models offer a comparable efficiency to a chiller in cooling mode, and in heating mode they can provide savings of over 70% compared to a resistance heater. • Heat is transported in refrigerant lines, which are much more compact than water pipes and air ducts. • VRF systems are modular, which allows them to be expanded incrementally according to building needs – boilers, chillers, and packaged rooftop units are limited in this aspect by their fixed capacities. VRF systems are very popular in Japan, where they were developed, as well as in Europe. They are relatively new in the US market, but their installed cost is comparable to that of a traditional chiller-based system.
  • 7. 7 The Top 5 Most Over-Engineered Building Components 3 AIR CONDITIONERS The performance of air conditioning equipment improves in direct proportion to how well the unit matches the application. There is a common but erroneous belief that oversizing the unit is preferable, so that it can cool indoor spaces faster while reducing the compressor runtime. However, this comes with many performance issues. Also, even though the compressor runs less time, it also draws more power than a properly sized unit, so energy savings are minimal or zero. Air conditioning systems are addressed in the NYC Building Code and Mechanical Code. The ASHRAE Handbook of Fundamentals is also a solid reference when designing any HVAC system. POOR HUMIDITY CONTROL An effective air conditioning system doesn’t only remove indoor heat; it also keeps humidity within a range that is comfortable for human beings. When an AC system is oversized, it can reach the required indoor temperature within a shorter amount of time, and then the compressor is turned off – or slowed down in modern units with variable speed capabilities. The problem when AC units operate like this is that there is not enough time for them to bring indoor humidity to acceptable levels, and this results in an indoor environment that is cold but humid, similar to a refrigerator. Other than causing discomfort, this is a situation that can result in respiratory health issues among occupants.
  • 8. 8 The Top 5 Most Over-Engineered Building Components EXCESSIVE COMPRESSOR CYCLING An oversized AC unit has spare cooling power, so it can bring indoor temperature in less time than a properly sized system. This means that the unit will tend to operate in a series of short bursts, which can wear down electrical and mechanical components, reducing their service life. On the other hand, a properly sized compressor runs for longer periods but without frequent starts and stops, which is the intended mode of operation. When AC installations are compared based on their total ownership cost, considering both energy and maintenance expenses as well as their service life, a system of optimal capacity is superior to both undersized and oversized systems. DISCOMFORT FOR OCCUPANTS Since an oversized AC unit has excessive cooling power for the application, sitting right under an air duct opening or in front of an evaporator can be very uncomfortable. The fans of evaporators are normally sized in proportion to the AC unit, so the air is both cold and fast-moving, causing a chilling effect.
  • 9. 9 The Top 5 Most Over-Engineered Building Components 4 ELECTRICAL POWER Plenty of devices and systems used in buildings run on electric power, and that includes many types of mechanical equipment. When specifying electrical installations, the same principle used in mechanical systems applies: components should have just the right capacity for the application, not less and not more. Electrical installations in New York City are required to comply with the following codes: • NYC Building Code – in particular, Chapter 27 • NYC Electrical Code • NFPA 70: National Electric Code • In the case of emergency and standby power systems, compliance with NFPA 110, NFPA 111, and the NYC Fuel Gas Code is also required. OVERSIZED FEEDERS AND BRANCH CIRCUITS Undersized electrical circuits tend to fail quickly, sometimes within hours, but oversized circuits have no negative consequences in terms of operation. In fact, an oversized electrical circuit experiences a lower voltage drop and power loss than a properly sized circuit. However, this benefit is negligible compared with the project cost increase that comes with oversized electrical installations.  Get a free calculation of your electric load. 
  • 10. 10 The Top 5 Most Over-Engineered Building Components ELECTRIC MOTORS The case of motors is different from that of conductors, and there are several negative consequences when they are oversized: • Motor efficiency is reduced under part-load conditions. For a given mechanical load, a properly specified motor operating near full load will be more efficient than an oversized motor. • Power factor is also reduced. The oversized motor draws a high reactive current, which can contribute to power factor charges in the power bill. The extra reactive current also uses up capacity in transformers, distribution boards, and circuits, without contributing to the transmission of useful power. When motors will be subject to part-load conditions frequently, the best option is to use technologies that allow speed control: Electronically commutated motors (ECMs) can be used for fractional horsepower applications, and variable frequency drives (VFDs) with three-phase motors can be deployed for larger loads.
  • 11. 11 The Top 5 Most Over-Engineered Building Components If the motors in a building will be upgraded, three aspects must be considered to achieve the best possible results: • Adequate horsepower. • Upgrading to a higher efficiency tier, for example NEMA Premium. • Implementing automation and speed control measures. In chiller-based air conditioning systems, it is possible to achieve exceptional synergy if the chiller plant has variable-speed multi-stage compressors, while the associated water pumps and AHUs use motors with speed control.
  • 12. 12 The Top 5 Most Over-Engineered Building Components 5 SPRINKLER SYSTEMS A complex building layout normally means that the fire sprinkler system will have a piping layout of similar complexity, as well as a high sprinkler headcount. When the teams in charge of architectural design and fire protection design work in isolation, complex sprinkler systems are a common consequence. These systems come with many drawbacks: • The upfront cost is increased, both in terms of materials and labor. • Pumps must be sized larger to provide the adequate water pressure and flow rate for a system with more piping length and a higher sprinkler count. The following are some design recommendations to optimize sprinkler layouts, reducing their complexity and upfront cost: • Coordinating fire sprinkler design and architectural design, so that the interference of ceiling features, such as offsets and soffits, is minimized. • Merging smaller rooms into single areas whenever possible, because each time a small room is added, the sprinkler count is increased by one.  Learn more about our sprinkler engineering services. 
  • 13. 13 The Top 5 Most Over-Engineered Building Components When designing sprinkler systems in New York, it is important to observe the requirements set for in the following standards and codes: • NYC Building Code – in particular, Chapter 7 (Fire and Smoke Protection Features), Chapter 9 (Fire Protection Systems) and Appendix Q (Modifications to National Standards) • NYC Fire Code • NFPA 13 – Standard for the Installation of Sprinkler Systems • NFPA 13D – Standard for the Installation of Sprinkler Systems in One- and Two- Family Dwellings and Manufactured Homes • NFPA 13R – Standard for the Installation of Sprinkler Systems in Low-Rise Residential Occupancies It is important to note that Appendix Q of the Building Code takes precedence over national standards, introducing modifications that are specific for New York.
  • 14. 14 The Top 5 Most Over-Engineered Building Components CONCLUDING REMARKS There are many reasons not to oversize mechanical and electrical building systems. In most cases, oversized systems are just as problematic as undersized systems, if not more, causing performance issues and extra maintenance expenses. Even when there are no performance issues associated with extra capacity, it represents a higher upfront cost that must be assumed by the building owner. Hiring professional MEP designers is the best way to ensure all building systems will be specified optimally according to the application at hand. Meeting applicable codes and standards is mandatory for a building to be approved, but these documents often specify just the minimum requirements; with professional design, a project can meet code requirements while maximizing performance.
  • 15. 15 The Top 5 Most Over-Engineered Building Components Over-engineering a project drives up construction cost without any benefit. Get your construction project back on budget with a free value engineering service. REQUEST A CONSULTATION WANT TO LEARN MORE?