PROFIBUS
Commissioning
and
Maintenance
Presented by :-
Richard
Needham
Hi-Port Controls
Agenda
Topic 1
Topic 2
Topic 3
2
PROFIBUS Commissioning and Maintenance : Richard Needham - November 2016
PROFIBUS Commissioning & Maintenance
Introduction
PROFIBUS DP essentials
Typical faults which may occur
Important preparations for fault-finding
Tools and expertise needed to tackle problems
Expected PROFIBUS network quality / performance
Examples of typical analyser screen images
Preventive maintenance
What to do when the fault alarm rings!
Commissioning issues
Use test Master in place of operational PLC
Check cable connections & waveforms
Confirm slave address settings
Get slaves into data exchange : run test data
Connect PLC and confirm overall performance
High speed serial network
Bi-directional digital communications
Multi-drop cable array linking Masters & Slaves
Transferring both plant values and control signals
What is a PROFIBUS DP Network?
Master
Slave
1
Slave
2
Slave
3
Slave
4
This is called a Network Segment
3
The Master shown above is usually a semi-autonomous network
controller within a PLC, using shared memory or similar for passing
data between the two. Each is likely to operate at different cycle times
PROFIBUS Commissioning and Maintenance : Richard Needham - November 2016
3
Bi-directional digital communications
……but with only one device transmitting at any time…
…as directed by the Master which separately addresses each
slave, one a time, then awaits reply from that device
PROFIBUS resilience is partly derived from the fact that the
Master can cope with occasionally illegal (corrupted) or missing
replies – then asking for a second or subsequent attempt
Only when a device totally fails to reply, will it be indicated as lost
to the PLC which may then stop the operational program, but
generally the Master will continue it’s cyclic scanning of all slaves,
using a special Sync message addressed to the known missing
device in the expectation that it may be able to come back online
later
What is a PROFIBUS DP Network?
4PROFIBUS Commissioning and Maintenance : Richard Needham - November 2016
4
Typical faults which may occur
Failure of expected replies from one or more slaves is the most
common fault symptom
This is most likely to be due to connection network damage
One of the more common causes of connection damage is poor
installation work undertaken when the system was first built
Such poor workmanship may not become apparent or impact on
system reliability for several years, but might then gradually start
to reduce the overall communications quality until eventually
causing failure
Following photos show typical and frequently seen problems!
5
PROFIBUS Commissioning and Maintenance : Richard Needham - November 2016
PROFIBUS cable installation problems
6
PROFIBUS Commissioning and Maintenance : Richard Needham - November 2016
Wrong plug used Cable sheath not secured
Cable screen not earthed properly Poor cable preparation
Correct strip tool should be used!
What to do first when faults are noted
After seeing that a device or devices are no longer
communicating reliably, or at all, one should first check for
power supply to each, then look for cable breaks or wiring
damage and check for corrupted waveforms
To see which devices are still connected, the
communication reliability and waveform quality one needs
a PROFIBUS Analyser Tool
…..and test point(s) on the network to which it may be
attached!
7
PROFIBUS Commissioning and Maintenance : Richard Needham - November 2016
Preparations for fault-finding
Needless to say, one also needs to know how to use any
available tools effectively and have reasonable
appreciation of PROFIBUS wiring and protocol basics!
Accurate network ‘as built’ drawings will be helpful – these
might also usefully include geographic information about
locations of each device within the site, where appropriate
(particularly in multi-level buildings or distributed networks)
And hopefully a historical bench mark report against which
you can compare currently measured performance
8
PROFIBUS Commissioning and Maintenance : Richard Needham - November 2016
Test Points for PROFIBUS Analyser connection
We need at least one test point in each network segment
This will allow electrical waveform, voltage and full
message analysis
With usual 9-pin PROFIBUS connectors you will need (at
least) one with a rear PG test socket, as in following slide
9
PROFIBUS Commissioning and Maintenance : Richard Needham - November 2016
Master
Slave
1
Slave
2
Slave
3
Slave
4
Test point here
9-pin PROFIBUS DP network plug
Plug for network
cable
connection to
Slave or Master
Optional female
PG rear test
connector
10PROFIBUS Commissioning and Maintenance : Richard Needham - November 2016
8
Test Points for PROFIBUS Analyser connection
M S S S s
Repeater
s s
Segment 1 – up to 32 devices
11
Test Point 1
Test Point 2
Segment 2 – up to 32 more
The left hand test point will allow a connected analyser to see messages to
and from all devices, but will only faithfully show waveforms and voltages for
devices on segment 1
Although waveforms from devices in segment 2 will be ‘visible’ at Test Point 1,
these can actually show only the waveforms and voltages from the repeater
circuits – hence Test Point 2 is needed to see true values from segment 2
devices!
PROFIBUS Commissioning and Maintenance : Richard Needham - November 2016
9
PROFIBUS Analyser Tools
PROFIBUS Analyser Tools are available from a number of
different suppliers
But for this presentation we will show use of the Procentec
ProfiTrace tool. Broadly similar features are provided in
tools from other manufacturers
12
PROFIBUS Commissioning and Maintenance : Richard Needham - November 2016
ProfiTrace is supplied as
a suite of computer
programs, with the test
computer connected to a
PROFIBUS network with
USB cable onto a small
ProfiCore Ultra adapter
and a short Tap Lead, as
in adjacent picture and
following slides
Connecting test kit to test point….
13
PROFIBUS Commissioning and Maintenance : Richard Needham - November 2016
…..then start test software, and here check device
driver voltages 14
PROFIBUS Commissioning and Maintenance : Richard Needham - November 2016
PROFIBUS Analyser connection issues
It is vital that any test equipment connected to an
operational PROFIBUS network does not interfere with
normal operations of that network
Hence use of very short connection links and high input
impedance to the attached test device
Some analysers include local front panel display to allow
performance inspection without need for separate
computer. This can be useful, but will add to the device
size and weight loading on the test point connector
ProfiTrace uses a very small, lightweight adapter, with
scope for long USB cable to computer location
15
PROFIBUS Commissioning and Maintenance : Richard Needham - November 2016
What do we want to see on the network?
Network operating speed : bit rate ?
Details of devices connected : their addresses and type ?
What do the waveforms look like : noise, spikes, ringing ?
Is the Idle Voltage correct for 2 terminators ?
Are all connected device driver voltages OK ?
Check failure statistics for lost, repeats and syncs ?
A good network should show 1 volt idle voltage, square
waveforms and no message repeats (or losts / syncs)
Following slides show typical ProfiTrace images
16
PROFIBUS Commissioning and Maintenance : Richard Needham - November 2016
Initial ProfiTrace Live List display
Typical Live List view after
connection to running
network
Network speed
displayed here
Slave with address 66
- here in normal data
exchange
Master with
address shown
as red number
17
Slave with extended
diagnostic errors
PROFIBUS Commissioning and Maintenance : Richard Needham - November 2016
15
Oscilloscope waveform and voltage display
Double-click on the
device legends to see
associated waveforms
from each
Horizontal Time
Scale
Vertical Voltage
Scale
Display cursors
Note bit interpretation shown
hereSelected device
address
confirmed here
Check important idle
voltage level is at 1
volt as set by
terminators
18PROFIBUS Commissioning and Maintenance : Richard Needham - November 2016
16
12 Mbps example waveform on large network
19
PROFIBUS Commissioning and Maintenance : Richard Needham - November 2016
More usual waveform shape, but with spikes
20
PROFIBUS Commissioning and Maintenance : Richard Needham - November 2016
Large network bar graph example
21
PROFIBUS Commissioning and Maintenance : Richard Needham - November 2016
This photo shows the individual driver voltages from all connected
devices as seen at test point
Topology Scan : Typical result report
Start the Topology
scan
Total cable
length
Cable length between
devices
22PROFIBUS Commissioning and Maintenance : Richard Needham - November 2016
20
Preventive Maintenance
In addition to fault-finding work, PROFIBUS Analysers, such a
ProfiTrace, should be used on a regular basis to check on
continued performance of all networks, including low level stats
This will not only help to identify any gradually degrading
network performance issues, but may also help to identify
increasing incidents of interference or device weaknesses (as
seen through increasing numbers of message repeats)
When weaknesses are identified, these may be addressed
immediately, or tracked over time to the point where they are felt
to threaten overall network reliability due to increasing numbers
Scans of this nature also help keep staff fluent and familiar with
the test tools (and network documentation) to ensure optimal
effectiveness when a major network failure occurs
23
PROFIBUS Commissioning and Maintenance : Richard Needham - November 2016
High availability network maintenance
Networks which MUST be kept running safely and securely,
including those with personal safety or very high failure
costs may be fitted with automatic 24/7 performance
monitoring and fault reporting kit
For this requirement Procentec provides it’s ComBricks
range of modular repeaters which can be programmed (by
maintainers) to check, log and alert on typical network
performance issues such as redundant power supply
failures, message repeats, lost devices etc. Such reports are
logged to local microSD memory cards, but may also be
sent as email alerts to maintenance staff, then allowing dial-
in access to see both current real-time network status and
recorded information, using a browser program
Broadly equivalent devices are provided by other firms
24
PROFIBUS Commissioning and Maintenance : Richard Needham - November 2016
Location of faults in distributed systems
It is worth mentioning that even with the best tools, fault-
finding in such distributed control or monitoring systems can
be very challenging!
In some cases, fault symptoms may not appear anywhere
near the fault itself
For example, failure of a terminator at the end of a segment
may lead to missing or corrupted messages from devices a
long way back down that segment, cause by reflections
Some faults may also trigger multiple different symptoms,
so it is worth realising that, with a previously reliably
network, any new failure will usually only be caused by 1
fault……….
…unlike when commissioning a new system, where multiple
faults may need to be found and sorted, one by one
25
PROFIBUS Commissioning and Maintenance : Richard Needham - November 2016
Commissioning using ProfiTrace
ProfiTrace can be used in place of a PLC/Master on a new
network to confirm cable integrity, connected device
addresses and operation of these devices
In this case the ProfiCaptain Master software is arranged to
drive the network, scanning and reporting connected devices.
Although connected devices will not (at least initially) here be
operating in the usual Data Exchange, normal waveforms, bar
graphs, topology scan (diagramming) and message statistics
features of ProfiTrace will all work – and the addresses of any
software settable devices may be changed online
26
PROFIBUS Commissioning and Maintenance : Richard Needham - November 2016
ProfiCore
Ultra
Slave
1
Slave
2
Slave
3
Slave
4
Commissioning using ProfiTrace
27
PROFIBUS Commissioning and Maintenance : Richard Needham - November 2016
Step 1 : scan for connected devices,
showing addresses of each using
ProfiCaptain Stop mode. This checks
cables and device address settings
Step 2 : Run Class 2 Scan for device
Identifiers. Name details then taken
from associated GSD files for each
Step 3 : Filter GSD file list to those for these
devices only, select required options for each,
then bring devices online and into full Data
Exchange - may allow test data checks too
Commissioning using ProfiTrace
If GSD files are available for the connected devices,
ProfiCaptain may be used to Scan the network for
identification of all devices, replacing the device addresses
with better details in the Live List (& printable) reports
One may then automatically filter the available GSD file list to
isolate only those for connected devices and so help to quickly
set-up and bring each into full Data Exchange. This may then
allow automatically changing test patterns or fixed data values
to be output to these to help verify operation / setup
These procedures may be applied to individual cabinets or
sections of a network, without final PLC. This can be done
before shipping to site, as part of a factory acceptance test,
then again on-site once all other sections are connected
Once the final PLC is available ProfiTrace may be used to
confirm correct operation of the completed network!
28
PROFIBUS Commissioning and Maintenance : Richard Needham - November 2016
Review and wrap-up
In the above slides I have attempted to highlight some of
the most important issues that need to be considered for
successful PROFIBUS DP network commissioning and
maintenance
This has been a very rapid review of a complex topic and
in no way claims to have covered all aspects. For
example, I have made no reference to PROFIBUS PA or
AS-i networks, which you may also need to understand
For more comprehensive introduction to PROFIBUS you
should look into joining a one day Certified PROFIBUS
Installer Course, which is not only intended for installers,
but also for managers, designers, bidding teams etc –
thereafter a 1 day Commissioning and Maintenance
Course is also available
For further discussions and ProfiTrace demo see our
exhibition stand here today!
29
PROFIBUS Commissioning and Maintenance : Richard Needham - November 2016
Speaker contact details
For further information contact :-
Richard Needham -- Hi-Port Controls
Tel : 02392 552855 Mob : 07739 847277
richard@hiport.co.uk
Website : www.hiport.co.uk
30
PROFIBUS Commissioning and Maintenance : Richard Needham - November 2016
What to do when the fault alarm rings!
Assuming this may be due to a PROFIBUS related issue,
find your test kit and any associated computer that may be
needed to run it!
Before you leave the office, check it works and you know
how to use it! – a few minutes here may well save lots of
embarrassment later
If ProfiTrace is used, connect the ProfiCore Ultra to your
computer and run the self check procedure. This will
confirm that your test software is working, that the
PROFIBUS to USB adapter is working and that you have
the correct licence files in place
It can also provide a useful reminder of how to run the
software before you reach the shop floor!
You’re now ready to go!
31
PROFIBUS Commissioning and Maintenance : Richard Needham - November 2016

More Related Content

What's hot

Ocupação de eletrodutos
Ocupação de eletrodutosOcupação de eletrodutos
Ocupação de eletrodutosBeatriz Naufel
 
Industrial Networking - Profibus
Industrial Networking - ProfibusIndustrial Networking - Profibus
Industrial Networking - ProfibusYogesh Kumar
 
Profibus
ProfibusProfibus
ProfibusMrZeroo
 
Tema1 telef 10_11
Tema1 telef 10_11Tema1 telef 10_11
Tema1 telef 10_11jammanel
 
CENTUM VP - 2014 version
CENTUM VP - 2014 versionCENTUM VP - 2014 version
CENTUM VP - 2014 versionYokogawa
 
It's time to modernize your industrial controls with Modicon M580
It's time to modernize your industrial controls with Modicon M580It's time to modernize your industrial controls with Modicon M580
It's time to modernize your industrial controls with Modicon M580Schneider Electric
 
Modicon M580 MUCH MORE then a PLC…the first ePAC!
Modicon M580 MUCH MORE then a PLC…the first ePAC!Modicon M580 MUCH MORE then a PLC…the first ePAC!
Modicon M580 MUCH MORE then a PLC…the first ePAC!Schneider Electric
 
A importância dos meios físicos de transmissão
A importância dos meios físicos de transmissãoA importância dos meios físicos de transmissão
A importância dos meios físicos de transmissãoH P
 
Rede de Computadores - Cabo Coaxial
Rede de Computadores - Cabo CoaxialRede de Computadores - Cabo Coaxial
Rede de Computadores - Cabo CoaxialMarcelo Carvalho
 
3. UTP AND FIBER CABLING.pptx
3. UTP AND FIBER CABLING.pptx3. UTP AND FIBER CABLING.pptx
3. UTP AND FIBER CABLING.pptxChellepia
 

What's hot (20)

NFS-320
NFS-320NFS-320
NFS-320
 
Ocupação de eletrodutos
Ocupação de eletrodutosOcupação de eletrodutos
Ocupação de eletrodutos
 
Redes industriais aula-1
Redes industriais aula-1Redes industriais aula-1
Redes industriais aula-1
 
Profibus and Profinet shield currents - Peter Thomas
Profibus and Profinet shield currents - Peter ThomasProfibus and Profinet shield currents - Peter Thomas
Profibus and Profinet shield currents - Peter Thomas
 
Industrial Networking - Profibus
Industrial Networking - ProfibusIndustrial Networking - Profibus
Industrial Networking - Profibus
 
Profibus Network Issues
Profibus Network IssuesProfibus Network Issues
Profibus Network Issues
 
Profibus
ProfibusProfibus
Profibus
 
Tema1 telef 10_11
Tema1 telef 10_11Tema1 telef 10_11
Tema1 telef 10_11
 
CENTUM VP - 2014 version
CENTUM VP - 2014 versionCENTUM VP - 2014 version
CENTUM VP - 2014 version
 
Redes wireless
Redes wirelessRedes wireless
Redes wireless
 
FIBRA ÓPTICA CABOS
FIBRA ÓPTICA CABOS FIBRA ÓPTICA CABOS
FIBRA ÓPTICA CABOS
 
It's time to modernize your industrial controls with Modicon M580
It's time to modernize your industrial controls with Modicon M580It's time to modernize your industrial controls with Modicon M580
It's time to modernize your industrial controls with Modicon M580
 
Modicon M580 MUCH MORE then a PLC…the first ePAC!
Modicon M580 MUCH MORE then a PLC…the first ePAC!Modicon M580 MUCH MORE then a PLC…the first ePAC!
Modicon M580 MUCH MORE then a PLC…the first ePAC!
 
SLC
SLCSLC
SLC
 
Profibus
ProfibusProfibus
Profibus
 
A importância dos meios físicos de transmissão
A importância dos meios físicos de transmissãoA importância dos meios físicos de transmissão
A importância dos meios físicos de transmissão
 
Practical steps to a successful PROFIBUS project - Richard Needham and Xiu Ji
Practical steps to a successful PROFIBUS project - Richard Needham and Xiu JiPractical steps to a successful PROFIBUS project - Richard Needham and Xiu Ji
Practical steps to a successful PROFIBUS project - Richard Needham and Xiu Ji
 
Rede de Computadores - Cabo Coaxial
Rede de Computadores - Cabo CoaxialRede de Computadores - Cabo Coaxial
Rede de Computadores - Cabo Coaxial
 
3. UTP AND FIBER CABLING.pptx
3. UTP AND FIBER CABLING.pptx3. UTP AND FIBER CABLING.pptx
3. UTP AND FIBER CABLING.pptx
 
Lecture4
Lecture4Lecture4
Lecture4
 

Viewers also liked

A new tool for Clinical Commissioners, HWBs and everyone concerned with commi...
A new tool for Clinical Commissioners, HWBs and everyone concerned with commi...A new tool for Clinical Commissioners, HWBs and everyone concerned with commi...
A new tool for Clinical Commissioners, HWBs and everyone concerned with commi...rightcare
 
Waste Not Want Not
Waste Not Want NotWaste Not Want Not
Waste Not Want Notsflaig
 
Buyer beware
Buyer bewareBuyer beware
Buyer bewaresflaig
 
Start With The End In Mind
Start With The End In MindStart With The End In Mind
Start With The End In MindUptime Institute
 
A Profibus-based Control System for Nuclear Physics Applications - Presentati...
A Profibus-based Control System for Nuclear Physics Applications - Presentati...A Profibus-based Control System for Nuclear Physics Applications - Presentati...
A Profibus-based Control System for Nuclear Physics Applications - Presentati...Cristian Randieri PhD
 
C08 – Updated planning and commissioning guidelines for Profinet - Xaver Sch...
C08 – Updated planning and commissioning guidelines for Profinet -  Xaver Sch...C08 – Updated planning and commissioning guidelines for Profinet -  Xaver Sch...
C08 – Updated planning and commissioning guidelines for Profinet - Xaver Sch...PROFIBUS and PROFINET InternationaI - PI UK
 
Commissioning services for substation and power plants
Commissioning services for substation and power plantsCommissioning services for substation and power plants
Commissioning services for substation and power plantsEvaldas Paliliūnas
 

Viewers also liked (20)

Julie Henderson and Shaun Rowark (NICE): Commissioning in Healthcare show (Ci...
Julie Henderson and Shaun Rowark (NICE): Commissioning in Healthcare show (Ci...Julie Henderson and Shaun Rowark (NICE): Commissioning in Healthcare show (Ci...
Julie Henderson and Shaun Rowark (NICE): Commissioning in Healthcare show (Ci...
 
A new tool for Clinical Commissioners, HWBs and everyone concerned with commi...
A new tool for Clinical Commissioners, HWBs and everyone concerned with commi...A new tool for Clinical Commissioners, HWBs and everyone concerned with commi...
A new tool for Clinical Commissioners, HWBs and everyone concerned with commi...
 
Waste Not Want Not
Waste Not Want NotWaste Not Want Not
Waste Not Want Not
 
Buyer beware
Buyer bewareBuyer beware
Buyer beware
 
Start With The End In Mind
Start With The End In MindStart With The End In Mind
Start With The End In Mind
 
Factory automation seminar introduction and PROFIBUS & PROFINET update mark...
Factory automation seminar introduction and PROFIBUS & PROFINET update   mark...Factory automation seminar introduction and PROFIBUS & PROFINET update   mark...
Factory automation seminar introduction and PROFIBUS & PROFINET update mark...
 
Profibus commissioning and maintenance - Richard Needham - oct 2015
Profibus commissioning and maintenance  - Richard Needham - oct 2015Profibus commissioning and maintenance  - Richard Needham - oct 2015
Profibus commissioning and maintenance - Richard Needham - oct 2015
 
C05 The specification and use of Profibus networks in the UK water industry...
C05   The specification and use of Profibus networks in the UK water industry...C05   The specification and use of Profibus networks in the UK water industry...
C05 The specification and use of Profibus networks in the UK water industry...
 
5.3 profibus dp0
5.3 profibus dp05.3 profibus dp0
5.3 profibus dp0
 
Profibus in the Water Industry - Roger Marlow
Profibus in the Water Industry - Roger MarlowProfibus in the Water Industry - Roger Marlow
Profibus in the Water Industry - Roger Marlow
 
Introduction to Profibus and Profinet for Process Industry - Mark Freeman
Introduction to Profibus and Profinet for Process Industry - Mark FreemanIntroduction to Profibus and Profinet for Process Industry - Mark Freeman
Introduction to Profibus and Profinet for Process Industry - Mark Freeman
 
Practical steps to a successful PROFIBUS project - Xiu Ji of the UK's PICC
Practical steps to a successful PROFIBUS project - Xiu Ji of the UK's PICCPractical steps to a successful PROFIBUS project - Xiu Ji of the UK's PICC
Practical steps to a successful PROFIBUS project - Xiu Ji of the UK's PICC
 
A Profibus-based Control System for Nuclear Physics Applications - Presentati...
A Profibus-based Control System for Nuclear Physics Applications - Presentati...A Profibus-based Control System for Nuclear Physics Applications - Presentati...
A Profibus-based Control System for Nuclear Physics Applications - Presentati...
 
W03 Profibus diagnostics & monitoring - Andy Verwer, VTC and Dave Tomlin, H...
W03   Profibus diagnostics & monitoring - Andy Verwer, VTC and Dave Tomlin, H...W03   Profibus diagnostics & monitoring - Andy Verwer, VTC and Dave Tomlin, H...
W03 Profibus diagnostics & monitoring - Andy Verwer, VTC and Dave Tomlin, H...
 
C13 – Profibus and Profinet network design - Andy Verwer, VTC
C13 – Profibus and Profinet network design -  Andy Verwer, VTCC13 – Profibus and Profinet network design -  Andy Verwer, VTC
C13 – Profibus and Profinet network design - Andy Verwer, VTC
 
C08 – Updated planning and commissioning guidelines for Profinet - Xaver Sch...
C08 – Updated planning and commissioning guidelines for Profinet -  Xaver Sch...C08 – Updated planning and commissioning guidelines for Profinet -  Xaver Sch...
C08 – Updated planning and commissioning guidelines for Profinet - Xaver Sch...
 
Getting started with Profibus Tester 4
Getting started with Profibus Tester 4Getting started with Profibus Tester 4
Getting started with Profibus Tester 4
 
Commissioning services for substation and power plants
Commissioning services for substation and power plantsCommissioning services for substation and power plants
Commissioning services for substation and power plants
 
Profibus system engineering and monitoring - Andy Verwer
Profibus system engineering and monitoring - Andy VerwerProfibus system engineering and monitoring - Andy Verwer
Profibus system engineering and monitoring - Andy Verwer
 
C6 profibus system design, andy verwer
C6 profibus system design, andy verwerC6 profibus system design, andy verwer
C6 profibus system design, andy verwer
 

Similar to Profibus commissioning and maintenance - Richard Needham

Best Practice in PROFIBUS Diagnostics
Best Practice in PROFIBUS DiagnosticsBest Practice in PROFIBUS Diagnostics
Best Practice in PROFIBUS DiagnosticsBernd Kremer
 
Getting Started With Pb T4 Comment Lan
Getting Started With Pb T4 Comment LanGetting Started With Pb T4 Comment Lan
Getting Started With Pb T4 Comment Lanfrank8040
 
Www ccnav5 net_ccna_3_v5_0_scaling_networks_final_exam_2013
Www ccnav5 net_ccna_3_v5_0_scaling_networks_final_exam_2013Www ccnav5 net_ccna_3_v5_0_scaling_networks_final_exam_2013
Www ccnav5 net_ccna_3_v5_0_scaling_networks_final_exam_2013Đồng Quốc Vương
 
POLYMER MODIFIED AND NEAT BITUMINOUS MIXES USING WARM MIX ASPHALT FOR PAVING ...
POLYMER MODIFIED AND NEAT BITUMINOUS MIXES USING WARM MIX ASPHALT FOR PAVING ...POLYMER MODIFIED AND NEAT BITUMINOUS MIXES USING WARM MIX ASPHALT FOR PAVING ...
POLYMER MODIFIED AND NEAT BITUMINOUS MIXES USING WARM MIX ASPHALT FOR PAVING ...AnilKumar109331
 
Thesis_presentation ctm tk sha.ppt
Thesis_presentation ctm tk sha.pptThesis_presentation ctm tk sha.ppt
Thesis_presentation ctm tk sha.pptKavitaChhajed
 
Thesis_presentation.ppt
Thesis_presentation.pptThesis_presentation.ppt
Thesis_presentation.pptMohdIshaq24
 
Thesis presentation of college iit ppt.ppt
Thesis presentation of college iit ppt.pptThesis presentation of college iit ppt.ppt
Thesis presentation of college iit ppt.pptAmanJohnTudu
 
Thesis_presentation.ppt
Thesis_presentation.pptThesis_presentation.ppt
Thesis_presentation.pptNishant Kumar
 
IEEE 802.11s - Wireless Mesh Network
IEEE 802.11s - Wireless Mesh NetworkIEEE 802.11s - Wireless Mesh Network
IEEE 802.11s - Wireless Mesh NetworkArunabh Mishra
 
Peering 101 - ABQNOG1 - May2023
Peering 101 - ABQNOG1 - May2023Peering 101 - ABQNOG1 - May2023
Peering 101 - ABQNOG1 - May2023Chris Grundemann
 

Similar to Profibus commissioning and maintenance - Richard Needham (20)

Profibus commissioning and maintenance - Richard Needham
Profibus commissioning and maintenance - Richard NeedhamProfibus commissioning and maintenance - Richard Needham
Profibus commissioning and maintenance - Richard Needham
 
PROFIBUS commissioning and maintenance - Richard Needham
PROFIBUS commissioning and maintenance - Richard NeedhamPROFIBUS commissioning and maintenance - Richard Needham
PROFIBUS commissioning and maintenance - Richard Needham
 
Profibus system engineering and monitoring - Andy Verwer and Peter Thomas
Profibus system engineering and monitoring - Andy Verwer and Peter ThomasProfibus system engineering and monitoring - Andy Verwer and Peter Thomas
Profibus system engineering and monitoring - Andy Verwer and Peter Thomas
 
8. PROFINET network commissioning and testing - Peter Thomas
8. PROFINET network commissioning and testing - Peter Thomas8. PROFINET network commissioning and testing - Peter Thomas
8. PROFINET network commissioning and testing - Peter Thomas
 
PROFIBUS monitoring and maintenance - Dave Tomlin
PROFIBUS monitoring and maintenance - Dave TomlinPROFIBUS monitoring and maintenance - Dave Tomlin
PROFIBUS monitoring and maintenance - Dave Tomlin
 
Best Practice in PROFIBUS Diagnostics
Best Practice in PROFIBUS DiagnosticsBest Practice in PROFIBUS Diagnostics
Best Practice in PROFIBUS Diagnostics
 
PROFINET implementation and testing - Dave Tomlin, Hitex and Andy Morse, AJM
PROFINET implementation and testing - Dave Tomlin, Hitex and Andy Morse, AJMPROFINET implementation and testing - Dave Tomlin, Hitex and Andy Morse, AJM
PROFINET implementation and testing - Dave Tomlin, Hitex and Andy Morse, AJM
 
Getting Started With Pb T4 Comment Lan
Getting Started With Pb T4 Comment LanGetting Started With Pb T4 Comment Lan
Getting Started With Pb T4 Comment Lan
 
PI UK Seminar (Nov 2021) - PROFINET Implementation and Testing
PI UK Seminar (Nov 2021) - PROFINET Implementation and TestingPI UK Seminar (Nov 2021) - PROFINET Implementation and Testing
PI UK Seminar (Nov 2021) - PROFINET Implementation and Testing
 
Novarum wlan
Novarum wlanNovarum wlan
Novarum wlan
 
PROFIBUS maintenance & monitoring in Factory Automation - Andy Verwer & Dave...
PROFIBUS maintenance & monitoring in  Factory Automation - Andy Verwer & Dave...PROFIBUS maintenance & monitoring in  Factory Automation - Andy Verwer & Dave...
PROFIBUS maintenance & monitoring in Factory Automation - Andy Verwer & Dave...
 
Www ccnav5 net_ccna_3_v5_0_scaling_networks_final_exam_2013
Www ccnav5 net_ccna_3_v5_0_scaling_networks_final_exam_2013Www ccnav5 net_ccna_3_v5_0_scaling_networks_final_exam_2013
Www ccnav5 net_ccna_3_v5_0_scaling_networks_final_exam_2013
 
Profinet implementation and testing - Dave Tomlin and Xing Ye
Profinet implementation and testing - Dave Tomlin and Xing YeProfinet implementation and testing - Dave Tomlin and Xing Ye
Profinet implementation and testing - Dave Tomlin and Xing Ye
 
POLYMER MODIFIED AND NEAT BITUMINOUS MIXES USING WARM MIX ASPHALT FOR PAVING ...
POLYMER MODIFIED AND NEAT BITUMINOUS MIXES USING WARM MIX ASPHALT FOR PAVING ...POLYMER MODIFIED AND NEAT BITUMINOUS MIXES USING WARM MIX ASPHALT FOR PAVING ...
POLYMER MODIFIED AND NEAT BITUMINOUS MIXES USING WARM MIX ASPHALT FOR PAVING ...
 
Thesis_presentation ctm tk sha.ppt
Thesis_presentation ctm tk sha.pptThesis_presentation ctm tk sha.ppt
Thesis_presentation ctm tk sha.ppt
 
Thesis_presentation.ppt
Thesis_presentation.pptThesis_presentation.ppt
Thesis_presentation.ppt
 
Thesis presentation of college iit ppt.ppt
Thesis presentation of college iit ppt.pptThesis presentation of college iit ppt.ppt
Thesis presentation of college iit ppt.ppt
 
Thesis_presentation.ppt
Thesis_presentation.pptThesis_presentation.ppt
Thesis_presentation.ppt
 
IEEE 802.11s - Wireless Mesh Network
IEEE 802.11s - Wireless Mesh NetworkIEEE 802.11s - Wireless Mesh Network
IEEE 802.11s - Wireless Mesh Network
 
Peering 101 - ABQNOG1 - May2023
Peering 101 - ABQNOG1 - May2023Peering 101 - ABQNOG1 - May2023
Peering 101 - ABQNOG1 - May2023
 

More from PROFIBUS and PROFINET InternationaI - PI UK

More from PROFIBUS and PROFINET InternationaI - PI UK (20)

11. PI_Ford_Dunton_IOLINK_Safety.pdf
11. PI_Ford_Dunton_IOLINK_Safety.pdf11. PI_Ford_Dunton_IOLINK_Safety.pdf
11. PI_Ford_Dunton_IOLINK_Safety.pdf
 
7. Ford_Dunton_TSN_CRM.pdf
7. Ford_Dunton_TSN_CRM.pdf7. Ford_Dunton_TSN_CRM.pdf
7. Ford_Dunton_TSN_CRM.pdf
 
6. SRCI Profibus International v2.pdf
6. SRCI Profibus International v2.pdf6. SRCI Profibus International v2.pdf
6. SRCI Profibus International v2.pdf
 
13. CEMA - AUTOMOTIVE.pdf
13. CEMA - AUTOMOTIVE.pdf13. CEMA - AUTOMOTIVE.pdf
13. CEMA - AUTOMOTIVE.pdf
 
12. PI_OPC_UK.pdf
12. PI_OPC_UK.pdf12. PI_OPC_UK.pdf
12. PI_OPC_UK.pdf
 
4. APL PI Presentation 2023.pdf
4. APL PI Presentation 2023.pdf4. APL PI Presentation 2023.pdf
4. APL PI Presentation 2023.pdf
 
10. PI_Dunton - OT Security.pdf
10. PI_Dunton - OT Security.pdf10. PI_Dunton - OT Security.pdf
10. PI_Dunton - OT Security.pdf
 
9. PA DIM presentation.pdf
9. PA DIM presentation.pdf9. PA DIM presentation.pdf
9. PA DIM presentation.pdf
 
3. Ford Dunton Mark Freeman.pdf
3. Ford Dunton Mark Freeman.pdf3. Ford Dunton Mark Freeman.pdf
3. Ford Dunton Mark Freeman.pdf
 
2. Ford_Dunton_Introductions_CRM.pdf
2. Ford_Dunton_Introductions_CRM.pdf2. Ford_Dunton_Introductions_CRM.pdf
2. Ford_Dunton_Introductions_CRM.pdf
 
PI UK Seminar (Nov 2021) - Online Certified Training Courses
PI UK Seminar (Nov 2021) - Online Certified Training CoursesPI UK Seminar (Nov 2021) - Online Certified Training Courses
PI UK Seminar (Nov 2021) - Online Certified Training Courses
 
PI UK Seminar (Nov 2021) - PROFINET Design Basics
PI UK Seminar (Nov 2021) - PROFINET Design BasicsPI UK Seminar (Nov 2021) - PROFINET Design Basics
PI UK Seminar (Nov 2021) - PROFINET Design Basics
 
PI UK Seminar (Nov 2021) - PROFINET Gateways
PI UK Seminar (Nov 2021) - PROFINET GatewaysPI UK Seminar (Nov 2021) - PROFINET Gateways
PI UK Seminar (Nov 2021) - PROFINET Gateways
 
PI UK Seminar (Nov 2021) - PROFIBUS and PROFINET Device Configuration
PI UK Seminar (Nov 2021) - PROFIBUS and PROFINET Device ConfigurationPI UK Seminar (Nov 2021) - PROFIBUS and PROFINET Device Configuration
PI UK Seminar (Nov 2021) - PROFIBUS and PROFINET Device Configuration
 
PI UK Seminar (Nov 2021) - PROFINET of Things
PI UK Seminar (Nov 2021) - PROFINET of ThingsPI UK Seminar (Nov 2021) - PROFINET of Things
PI UK Seminar (Nov 2021) - PROFINET of Things
 
PI UK Seminar (Nov 2021) - Update on APL
PI UK Seminar (Nov 2021) - Update on APLPI UK Seminar (Nov 2021) - Update on APL
PI UK Seminar (Nov 2021) - Update on APL
 
PROFINET to PROFIBUS gateways - Peter Thomas - 03 june 2020
PROFINET to PROFIBUS gateways - Peter Thomas - 03 june 2020PROFINET to PROFIBUS gateways - Peter Thomas - 03 june 2020
PROFINET to PROFIBUS gateways - Peter Thomas - 03 june 2020
 
PROFIBUS lightning surge protection - Peter Thomas, CSL - 10 june 2020
PROFIBUS lightning surge protection -  Peter Thomas, CSL - 10 june 2020 PROFIBUS lightning surge protection -  Peter Thomas, CSL - 10 june 2020
PROFIBUS lightning surge protection - Peter Thomas, CSL - 10 june 2020
 
PROFINET network diagnostics and support - May 2020 - Peter Thomas
PROFINET network diagnostics and support - May 2020 - Peter ThomasPROFINET network diagnostics and support - May 2020 - Peter Thomas
PROFINET network diagnostics and support - May 2020 - Peter Thomas
 
Profinet network design webinar - Peter Thomas may 2020 - v1.0
Profinet network design webinar - Peter Thomas   may 2020 - v1.0Profinet network design webinar - Peter Thomas   may 2020 - v1.0
Profinet network design webinar - Peter Thomas may 2020 - v1.0
 

Recently uploaded

EduAI - E learning Platform integrated with AI
EduAI - E learning Platform integrated with AIEduAI - E learning Platform integrated with AI
EduAI - E learning Platform integrated with AIkoyaldeepu123
 
Sachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective IntroductionSachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective IntroductionDr.Costas Sachpazis
 
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ
 
Effects of rheological properties on mixing
Effects of rheological properties on mixingEffects of rheological properties on mixing
Effects of rheological properties on mixingviprabot1
 
DATA ANALYTICS PPT definition usage example
DATA ANALYTICS PPT definition usage exampleDATA ANALYTICS PPT definition usage example
DATA ANALYTICS PPT definition usage examplePragyanshuParadkar1
 
An experimental study in using natural admixture as an alternative for chemic...
An experimental study in using natural admixture as an alternative for chemic...An experimental study in using natural admixture as an alternative for chemic...
An experimental study in using natural admixture as an alternative for chemic...Chandu841456
 
main PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidmain PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidNikhilNagaraju
 
IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024Mark Billinghurst
 
Electronically Controlled suspensions system .pdf
Electronically Controlled suspensions system .pdfElectronically Controlled suspensions system .pdf
Electronically Controlled suspensions system .pdfme23b1001
 
What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxWhat are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxwendy cai
 
Internship report on mechanical engineering
Internship report on mechanical engineeringInternship report on mechanical engineering
Internship report on mechanical engineeringmalavadedarshan25
 
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdfCCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdfAsst.prof M.Gokilavani
 
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...srsj9000
 
CCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdf
CCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdfCCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdf
CCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdfAsst.prof M.Gokilavani
 
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube ExchangerStudy on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube ExchangerAnamika Sarkar
 
Risk Assessment For Installation of Drainage Pipes.pdf
Risk Assessment For Installation of Drainage Pipes.pdfRisk Assessment For Installation of Drainage Pipes.pdf
Risk Assessment For Installation of Drainage Pipes.pdfROCENODodongVILLACER
 
pipeline in computer architecture design
pipeline in computer architecture  designpipeline in computer architecture  design
pipeline in computer architecture designssuser87fa0c1
 
Oxy acetylene welding presentation note.
Oxy acetylene welding presentation note.Oxy acetylene welding presentation note.
Oxy acetylene welding presentation note.eptoze12
 

Recently uploaded (20)

EduAI - E learning Platform integrated with AI
EduAI - E learning Platform integrated with AIEduAI - E learning Platform integrated with AI
EduAI - E learning Platform integrated with AI
 
Sachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective IntroductionSachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
 
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
 
Effects of rheological properties on mixing
Effects of rheological properties on mixingEffects of rheological properties on mixing
Effects of rheological properties on mixing
 
DATA ANALYTICS PPT definition usage example
DATA ANALYTICS PPT definition usage exampleDATA ANALYTICS PPT definition usage example
DATA ANALYTICS PPT definition usage example
 
An experimental study in using natural admixture as an alternative for chemic...
An experimental study in using natural admixture as an alternative for chemic...An experimental study in using natural admixture as an alternative for chemic...
An experimental study in using natural admixture as an alternative for chemic...
 
main PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidmain PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfid
 
IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024
 
POWER SYSTEMS-1 Complete notes examples
POWER SYSTEMS-1 Complete notes  examplesPOWER SYSTEMS-1 Complete notes  examples
POWER SYSTEMS-1 Complete notes examples
 
Electronically Controlled suspensions system .pdf
Electronically Controlled suspensions system .pdfElectronically Controlled suspensions system .pdf
Electronically Controlled suspensions system .pdf
 
What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxWhat are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptx
 
Internship report on mechanical engineering
Internship report on mechanical engineeringInternship report on mechanical engineering
Internship report on mechanical engineering
 
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdfCCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
 
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
 
CCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdf
CCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdfCCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdf
CCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdf
 
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube ExchangerStudy on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
 
Risk Assessment For Installation of Drainage Pipes.pdf
Risk Assessment For Installation of Drainage Pipes.pdfRisk Assessment For Installation of Drainage Pipes.pdf
Risk Assessment For Installation of Drainage Pipes.pdf
 
pipeline in computer architecture design
pipeline in computer architecture  designpipeline in computer architecture  design
pipeline in computer architecture design
 
Oxy acetylene welding presentation note.
Oxy acetylene welding presentation note.Oxy acetylene welding presentation note.
Oxy acetylene welding presentation note.
 
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
 

Profibus commissioning and maintenance - Richard Needham

  • 2. Agenda Topic 1 Topic 2 Topic 3 2 PROFIBUS Commissioning and Maintenance : Richard Needham - November 2016 PROFIBUS Commissioning & Maintenance Introduction PROFIBUS DP essentials Typical faults which may occur Important preparations for fault-finding Tools and expertise needed to tackle problems Expected PROFIBUS network quality / performance Examples of typical analyser screen images Preventive maintenance What to do when the fault alarm rings! Commissioning issues Use test Master in place of operational PLC Check cable connections & waveforms Confirm slave address settings Get slaves into data exchange : run test data Connect PLC and confirm overall performance
  • 3. High speed serial network Bi-directional digital communications Multi-drop cable array linking Masters & Slaves Transferring both plant values and control signals What is a PROFIBUS DP Network? Master Slave 1 Slave 2 Slave 3 Slave 4 This is called a Network Segment 3 The Master shown above is usually a semi-autonomous network controller within a PLC, using shared memory or similar for passing data between the two. Each is likely to operate at different cycle times PROFIBUS Commissioning and Maintenance : Richard Needham - November 2016 3
  • 4. Bi-directional digital communications ……but with only one device transmitting at any time… …as directed by the Master which separately addresses each slave, one a time, then awaits reply from that device PROFIBUS resilience is partly derived from the fact that the Master can cope with occasionally illegal (corrupted) or missing replies – then asking for a second or subsequent attempt Only when a device totally fails to reply, will it be indicated as lost to the PLC which may then stop the operational program, but generally the Master will continue it’s cyclic scanning of all slaves, using a special Sync message addressed to the known missing device in the expectation that it may be able to come back online later What is a PROFIBUS DP Network? 4PROFIBUS Commissioning and Maintenance : Richard Needham - November 2016 4
  • 5. Typical faults which may occur Failure of expected replies from one or more slaves is the most common fault symptom This is most likely to be due to connection network damage One of the more common causes of connection damage is poor installation work undertaken when the system was first built Such poor workmanship may not become apparent or impact on system reliability for several years, but might then gradually start to reduce the overall communications quality until eventually causing failure Following photos show typical and frequently seen problems! 5 PROFIBUS Commissioning and Maintenance : Richard Needham - November 2016
  • 6. PROFIBUS cable installation problems 6 PROFIBUS Commissioning and Maintenance : Richard Needham - November 2016 Wrong plug used Cable sheath not secured Cable screen not earthed properly Poor cable preparation Correct strip tool should be used!
  • 7. What to do first when faults are noted After seeing that a device or devices are no longer communicating reliably, or at all, one should first check for power supply to each, then look for cable breaks or wiring damage and check for corrupted waveforms To see which devices are still connected, the communication reliability and waveform quality one needs a PROFIBUS Analyser Tool …..and test point(s) on the network to which it may be attached! 7 PROFIBUS Commissioning and Maintenance : Richard Needham - November 2016
  • 8. Preparations for fault-finding Needless to say, one also needs to know how to use any available tools effectively and have reasonable appreciation of PROFIBUS wiring and protocol basics! Accurate network ‘as built’ drawings will be helpful – these might also usefully include geographic information about locations of each device within the site, where appropriate (particularly in multi-level buildings or distributed networks) And hopefully a historical bench mark report against which you can compare currently measured performance 8 PROFIBUS Commissioning and Maintenance : Richard Needham - November 2016
  • 9. Test Points for PROFIBUS Analyser connection We need at least one test point in each network segment This will allow electrical waveform, voltage and full message analysis With usual 9-pin PROFIBUS connectors you will need (at least) one with a rear PG test socket, as in following slide 9 PROFIBUS Commissioning and Maintenance : Richard Needham - November 2016 Master Slave 1 Slave 2 Slave 3 Slave 4 Test point here
  • 10. 9-pin PROFIBUS DP network plug Plug for network cable connection to Slave or Master Optional female PG rear test connector 10PROFIBUS Commissioning and Maintenance : Richard Needham - November 2016 8
  • 11. Test Points for PROFIBUS Analyser connection M S S S s Repeater s s Segment 1 – up to 32 devices 11 Test Point 1 Test Point 2 Segment 2 – up to 32 more The left hand test point will allow a connected analyser to see messages to and from all devices, but will only faithfully show waveforms and voltages for devices on segment 1 Although waveforms from devices in segment 2 will be ‘visible’ at Test Point 1, these can actually show only the waveforms and voltages from the repeater circuits – hence Test Point 2 is needed to see true values from segment 2 devices! PROFIBUS Commissioning and Maintenance : Richard Needham - November 2016 9
  • 12. PROFIBUS Analyser Tools PROFIBUS Analyser Tools are available from a number of different suppliers But for this presentation we will show use of the Procentec ProfiTrace tool. Broadly similar features are provided in tools from other manufacturers 12 PROFIBUS Commissioning and Maintenance : Richard Needham - November 2016 ProfiTrace is supplied as a suite of computer programs, with the test computer connected to a PROFIBUS network with USB cable onto a small ProfiCore Ultra adapter and a short Tap Lead, as in adjacent picture and following slides
  • 13. Connecting test kit to test point…. 13 PROFIBUS Commissioning and Maintenance : Richard Needham - November 2016
  • 14. …..then start test software, and here check device driver voltages 14 PROFIBUS Commissioning and Maintenance : Richard Needham - November 2016
  • 15. PROFIBUS Analyser connection issues It is vital that any test equipment connected to an operational PROFIBUS network does not interfere with normal operations of that network Hence use of very short connection links and high input impedance to the attached test device Some analysers include local front panel display to allow performance inspection without need for separate computer. This can be useful, but will add to the device size and weight loading on the test point connector ProfiTrace uses a very small, lightweight adapter, with scope for long USB cable to computer location 15 PROFIBUS Commissioning and Maintenance : Richard Needham - November 2016
  • 16. What do we want to see on the network? Network operating speed : bit rate ? Details of devices connected : their addresses and type ? What do the waveforms look like : noise, spikes, ringing ? Is the Idle Voltage correct for 2 terminators ? Are all connected device driver voltages OK ? Check failure statistics for lost, repeats and syncs ? A good network should show 1 volt idle voltage, square waveforms and no message repeats (or losts / syncs) Following slides show typical ProfiTrace images 16 PROFIBUS Commissioning and Maintenance : Richard Needham - November 2016
  • 17. Initial ProfiTrace Live List display Typical Live List view after connection to running network Network speed displayed here Slave with address 66 - here in normal data exchange Master with address shown as red number 17 Slave with extended diagnostic errors PROFIBUS Commissioning and Maintenance : Richard Needham - November 2016 15
  • 18. Oscilloscope waveform and voltage display Double-click on the device legends to see associated waveforms from each Horizontal Time Scale Vertical Voltage Scale Display cursors Note bit interpretation shown hereSelected device address confirmed here Check important idle voltage level is at 1 volt as set by terminators 18PROFIBUS Commissioning and Maintenance : Richard Needham - November 2016 16
  • 19. 12 Mbps example waveform on large network 19 PROFIBUS Commissioning and Maintenance : Richard Needham - November 2016
  • 20. More usual waveform shape, but with spikes 20 PROFIBUS Commissioning and Maintenance : Richard Needham - November 2016
  • 21. Large network bar graph example 21 PROFIBUS Commissioning and Maintenance : Richard Needham - November 2016 This photo shows the individual driver voltages from all connected devices as seen at test point
  • 22. Topology Scan : Typical result report Start the Topology scan Total cable length Cable length between devices 22PROFIBUS Commissioning and Maintenance : Richard Needham - November 2016 20
  • 23. Preventive Maintenance In addition to fault-finding work, PROFIBUS Analysers, such a ProfiTrace, should be used on a regular basis to check on continued performance of all networks, including low level stats This will not only help to identify any gradually degrading network performance issues, but may also help to identify increasing incidents of interference or device weaknesses (as seen through increasing numbers of message repeats) When weaknesses are identified, these may be addressed immediately, or tracked over time to the point where they are felt to threaten overall network reliability due to increasing numbers Scans of this nature also help keep staff fluent and familiar with the test tools (and network documentation) to ensure optimal effectiveness when a major network failure occurs 23 PROFIBUS Commissioning and Maintenance : Richard Needham - November 2016
  • 24. High availability network maintenance Networks which MUST be kept running safely and securely, including those with personal safety or very high failure costs may be fitted with automatic 24/7 performance monitoring and fault reporting kit For this requirement Procentec provides it’s ComBricks range of modular repeaters which can be programmed (by maintainers) to check, log and alert on typical network performance issues such as redundant power supply failures, message repeats, lost devices etc. Such reports are logged to local microSD memory cards, but may also be sent as email alerts to maintenance staff, then allowing dial- in access to see both current real-time network status and recorded information, using a browser program Broadly equivalent devices are provided by other firms 24 PROFIBUS Commissioning and Maintenance : Richard Needham - November 2016
  • 25. Location of faults in distributed systems It is worth mentioning that even with the best tools, fault- finding in such distributed control or monitoring systems can be very challenging! In some cases, fault symptoms may not appear anywhere near the fault itself For example, failure of a terminator at the end of a segment may lead to missing or corrupted messages from devices a long way back down that segment, cause by reflections Some faults may also trigger multiple different symptoms, so it is worth realising that, with a previously reliably network, any new failure will usually only be caused by 1 fault………. …unlike when commissioning a new system, where multiple faults may need to be found and sorted, one by one 25 PROFIBUS Commissioning and Maintenance : Richard Needham - November 2016
  • 26. Commissioning using ProfiTrace ProfiTrace can be used in place of a PLC/Master on a new network to confirm cable integrity, connected device addresses and operation of these devices In this case the ProfiCaptain Master software is arranged to drive the network, scanning and reporting connected devices. Although connected devices will not (at least initially) here be operating in the usual Data Exchange, normal waveforms, bar graphs, topology scan (diagramming) and message statistics features of ProfiTrace will all work – and the addresses of any software settable devices may be changed online 26 PROFIBUS Commissioning and Maintenance : Richard Needham - November 2016 ProfiCore Ultra Slave 1 Slave 2 Slave 3 Slave 4
  • 27. Commissioning using ProfiTrace 27 PROFIBUS Commissioning and Maintenance : Richard Needham - November 2016 Step 1 : scan for connected devices, showing addresses of each using ProfiCaptain Stop mode. This checks cables and device address settings Step 2 : Run Class 2 Scan for device Identifiers. Name details then taken from associated GSD files for each Step 3 : Filter GSD file list to those for these devices only, select required options for each, then bring devices online and into full Data Exchange - may allow test data checks too
  • 28. Commissioning using ProfiTrace If GSD files are available for the connected devices, ProfiCaptain may be used to Scan the network for identification of all devices, replacing the device addresses with better details in the Live List (& printable) reports One may then automatically filter the available GSD file list to isolate only those for connected devices and so help to quickly set-up and bring each into full Data Exchange. This may then allow automatically changing test patterns or fixed data values to be output to these to help verify operation / setup These procedures may be applied to individual cabinets or sections of a network, without final PLC. This can be done before shipping to site, as part of a factory acceptance test, then again on-site once all other sections are connected Once the final PLC is available ProfiTrace may be used to confirm correct operation of the completed network! 28 PROFIBUS Commissioning and Maintenance : Richard Needham - November 2016
  • 29. Review and wrap-up In the above slides I have attempted to highlight some of the most important issues that need to be considered for successful PROFIBUS DP network commissioning and maintenance This has been a very rapid review of a complex topic and in no way claims to have covered all aspects. For example, I have made no reference to PROFIBUS PA or AS-i networks, which you may also need to understand For more comprehensive introduction to PROFIBUS you should look into joining a one day Certified PROFIBUS Installer Course, which is not only intended for installers, but also for managers, designers, bidding teams etc – thereafter a 1 day Commissioning and Maintenance Course is also available For further discussions and ProfiTrace demo see our exhibition stand here today! 29 PROFIBUS Commissioning and Maintenance : Richard Needham - November 2016
  • 30. Speaker contact details For further information contact :- Richard Needham -- Hi-Port Controls Tel : 02392 552855 Mob : 07739 847277 richard@hiport.co.uk Website : www.hiport.co.uk 30 PROFIBUS Commissioning and Maintenance : Richard Needham - November 2016
  • 31. What to do when the fault alarm rings! Assuming this may be due to a PROFIBUS related issue, find your test kit and any associated computer that may be needed to run it! Before you leave the office, check it works and you know how to use it! – a few minutes here may well save lots of embarrassment later If ProfiTrace is used, connect the ProfiCore Ultra to your computer and run the self check procedure. This will confirm that your test software is working, that the PROFIBUS to USB adapter is working and that you have the correct licence files in place It can also provide a useful reminder of how to run the software before you reach the shop floor! You’re now ready to go! 31 PROFIBUS Commissioning and Maintenance : Richard Needham - November 2016