21, rue d’Artois, F-75008 PARIS CIGRE US National Committee
http://www.cigre.org 2019 Grid of the Future Symposium
Enhanced Protection Modeling Approach for Power System Transient Stability
Studies Using Individual Phase and Sequence Voltages
S. D. RAO, J. J. SANCHEZ-GASCA, S. ACHILLES
GE Energy Consulting
USA
SUMMARY
Accurate protection modelling in power system transient stability studies is required to ensure that
reliable conclusions are drawn from such analyses. Typically, protection models available in transient
stability programs use only positive sequence quantities such as the positive sequence voltages,
currents, etc. to trigger any preventive/corrective actions such as tripping of generators, load-shedding,
etc. However, with the increasing penetration of inverter-based resources, these models could prove to
be inadequate in some scenarios. The work reported in this paper uses improved modelling practices
for protection elements in transient stability studies using sequence/individual phase quantities. This
approach does not necessarily require additional data from users and incurs only minimal incremental
computational costs. In addition to using the sequence voltages/currents or individual phase
voltages/currents for more accurate representation of protection systems, simply monitoring these
quantities can also provide useful additional information about the system. Additionally, having access
to these quantities could be useful in more accurate modelling of inverter-based resources such as the
ability to model converter controls’ protective functions, controls that actively suppress the negative
sequence current produced by the inverter, and other such controls that use or control the negative
sequence or zero sequence current injections.
In the absence of negative sequence and zero sequence network data, some typical assumptions
based on engineering judgement are used to approximate this data. Once the data is available for all
three sequence networks, the RMS sequence voltages (and currents) can be easily computed in the
time-frame when an unbalanced fault is applied during a dynamic simulation. Since the network is
assumed to be balanced before an unbalanced fault is applied and after it is cleared, the non-positive
sequence voltages and currents in those time-frames are zero and all three phase voltages have equal
magnitudes. Using this feature, two protection models widely used in dynamic simulation studies that
are present in all commercial transient stability programs are modified in this work to use the
lowest/highest individual phase voltage instead of positive sequence voltage to trigger trip signals.
Even though the proposed models/techniques would have an impact in the relatively short time frame
when an unbalanced fault is on in the system, it could have a significant impact on studies involving
delayed clearing of faults. While it is not practical to model entire interconnection-wide base cases in a
detailed three-phase domain for all transient stability studies, the proposed approach is aimed at trying
to achieve a middle ground, such that more information about the system behaviour is obtained and
protection systems are more realistically represented in RMS studies. These models are incorporated
into a commercial positive sequence dynamic simulation engine GE-PSLF. Case studies using these
models in two Western Electricity Coordinating Council (WECC) cases and a 9-bus case are
discussed. With the framework to compute sequence/phase voltages/currents in place, the approach
can be easily extended to models other than those mentioned in this paper. The possible future uses of
such modelling capabilities for improved modelling of inverter controls etc. are also discussed.
2
KEYWORDS
Protection modelling, Dynamics studies, Sequence voltages, unbalanced faults, phase voltage-based
tripping.
3
INTRODUCTION
One of the recent topics of research focus in the power system industry has been understanding the
behaviour of protection relaying elements or inverter protective functions in the grid under increasing
penetration levels of inverter-based resources (IBRs), and ensuring reliable fault detection for such
scenarios [1] - [7]. Inverter-based resources restrict their fault current contribution to be close to their
rated current injection (typically less than 1.5 pu), which makes fault detection difficult [3], [5].
Additionally, some controls in modern converters are designed to inject very limited negative
sequence currents under faulted conditions as compared to traditional machines [5]. Hence the fault
detection techniques used in protection systems in emerging grids could also be different than
traditional protection systems. For example, the negative sequence voltage generated by inverters to
negate that seen at the terminals such that the negative sequence current injected by the inverter is
zero, is proposed to be used to detect unbalanced faults in [4]. Zero-sequence based protection is
proposed to be used in [5] to detect unbalanced faults in cases where the load unbalance is not very
high, while the zero-sequence current magnitude on the high-side of the step-up transformer along
with under-voltage detection is proposed to be used in [6]. An elaborate fault detection methodology
using phase as well as sequence voltages has been proposed and tested on a hardware-in-the-loop
setup in [1].
For typical dynamics studies, the network is assumed to be balanced before and after any
unbalanced disturbances are cleared. Consequently, these studies typically involve the representation
of positive-sequence networks and models only. Hence the state-of-the-art protection models in
transient stability studies, such as those used for generator protection, load shedding, etc., also use
only positive sequence voltages and currents to trigger tripping actions. However, since a vast majority
of the faults seen on the system are unbalanced, monitoring/using only positive sequence quantities
can be inadequate in some situations, especially for studies involving delayed clearing of the faults.
The changing fault response of the system with several utility scale renewable energy resources as
well as distributed energy resources using converter technologies, could render some of the traditional
dynamic models inadequate in terms of sufficiently capturing controller actions that could have a
noticeable effect on the post-fault system behaviour, which could in turn lead to misleading
conclusions drawn from the results of such simulations. The voltages of the un-faulted phases in the
vicinity of the fault may reach very high levels, likewise the faulted phase voltages may reach very
low levels causing high phase currents. These severe conditions may persist for a duration sufficiently
long to trigger tripping actions by the protection elements or protective functions in IBR controllers.
Likewise, there may be some protection elements utilizing the negative sequence voltages/currents,
and if standard positive sequence protection models are used for dynamic simulations, one could fail
to predict the loss of some units.
In this work, the sequence voltages are computed using the positive-, negative- and zero-sequence
networks during the timeframe that an unbalanced fault is on in the system. Since the network
admittance matrices are built and factorized only when there is a network change, the additional
computational expense of such capabilities is not significant. For the Western Electricity Coordinating
Council (WECC) cases used in this work, the execution time needed on average is similar to that when
only positive sequence quantities are computed. Next, the “der_a” model (described in detail in [9])
meant to represent distributed energy resources in bulk system studies is modified to use the
lowest/highest phase voltage in the voltage cut-out logic that is meant to capture momentary cessation.
Similarly, one of the most widely used generator protection models in dynamics studies, “lhvrt” that is
meant to model the protection for generators against low/high voltages, is modified. In the modified
version of the model trip signals are triggered based on the lowest/highest individual phase voltage
instead of the positive sequence voltage. A meter model is also implemented as a part of this work, to
monitor the sequence voltages or individual phase voltages at the buses/areas/zones of interest. Case
studies are presented using WECC cases to demonstrate the advantages of such modelling. Other
applications of such modelling techniques such as more detailed converter models are also discussed.
4
SEQUENCE NETWORK ASSUMPTIONS
One of the challenges in obtaining all sequence/phase quantities is that often the zero-sequence
and negative-sequence network data are not mapped to the positive sequence network data used in
dynamic simulations. Since the zero sequence and negative sequence representations of the system are
necessary for the computation of these sequence/per-phase voltages and currents, if this data is not
readily available some standard engineering assumptions are employed to approximate the negative
sequence and zero sequence network data using the available positive-sequence data. These are
standard assumptions made in typical short circuit analysis studies and are listed in this section. The
negative sequence impedances for generators are assumed to be equal to their respective positive
sequence impedances. Generators are assumed to be open-circuited for zero sequence networks as
most generator step-up (GSU) transformers are connected in delta on the generator side. All
transformer connections are assumed to be wye-grounded except on the generator-side for GSUs
which are assumed to be in delta. The negative sequence and zero sequence transformer impedances
are assumed to be equal to the positive sequence impedances. For transmission lines, the negative
sequence impedances are assumed to be equal to the positive sequence impedances and the zero-
sequence impedances are assumed to be thrice the positive sequence impedances. The zero-sequence
charging shunt admittances for transmission lines are assumed to be half that of the positive sequence
charging shunt admittances while the negative sequence charging shunt admittances are assumed to be
equal to the positive sequence charging shunt admittances. Loads and shunts are assumed to be
constant admittance in the negative sequence network with the same admittance as they would have in
positive sequence, while they are assumed to be open circuited in the zero-sequence network. In the
duration that an unbalanced fault is applied, the source of unbalance is assumed to be only at the
faulted location (i.e. loads and the rest of the network are still assumed to be balanced). The sequence
network interconnections for single-line-ground (SLG) faults, line-line (LL) faults, and line-line-
ground (LLG) faults are standard, as available in several references and shown in Figure 1 [8]. With
the positive, negative, and zero sequence current injections at the faulted location known, the sequence
voltages and currents throughout the network can easily be computed. The sequence voltages/currents
can then be used to obtain the phase A, B, C voltages/currents using the standard transformation
matrix [10]. For a 9-bus simplified representation of the western interconnection [11], the phase A, B,
C, and positive sequence voltages for an SLG bus fault at bus 6 are shown in Figure 2. The negative
sequence voltage seen at the terminals of a photovoltaic (PV) plant in a full WECC case for an SLG
fault is shown in Figure 3.
Figure 1 Network interconnections for unbalanced faults [8]
SLG fault LL fault LLG fault
5
Figure 2 Individual phase voltages for a single-line-ground fault at bus 6
Figure 3 Negative sequence voltage (pu) seen at the terminal of the PV units in WECC case
CASE STUDIES
In this section, some examples will be shown to demonstrate the modified models. The der_a is
the latest WECC-approved model to represent an aggregation of DERs including utility-scale DER
(U-DER) as well as retail-scale DERs (R-DER) along a feeder [9]. The model has also been recently
included as a component in the composite load model (cmpldw). One of the salient features of this
model is its capability to capture momentary cessation and tripping of these resources on high/low
voltages. This voltage cut-out block uses the positive-sequence voltage to send either trip signals or
reduced current signals as shown in Figure 4. The output of this block vmult is multiplied with the
current command signal to obtain the actual current injection into the network. The signal vmult tracks
the black line defined by the points (vl0,0), (vl1,1),(vh1,1), and (vh0,0) unless the following conditions
occur:
• If the voltage stays below vl1 for a duration greater than tvl1, vmult will follow the path of the red
line when the voltage recovers. Vmin is the lowest voltage (greater than vl0) during a simulation
after timer tvl1 expires.
6
• If the voltage stays above vh1 for a duration greater than tvh1, vmult will follow the path of the
red line when the voltage recovers. Vmax is the highest voltage (lesser than vh0) during a
simulation after timer tvh1 expires.
• If the voltage Vt_flt stays below vl0 for more than tvl0 seconds or if it stays above vh0 for more
than tvh0 seconds, then vmult will remain at zero i.e. the DERs are completely trippped.
The frequency trip action of the model is fairly straightforward where if the frequency seen at the
terminals of the DER falls below the parameter fltrp for more than tfl seconds or increases more than
fhtrp for more than tfh seconds, the DERs are entirely tripped.
Vt_flt 1
vl1vl0
0
vh1 vh0
vmult
vl0 vmin vl1 vh1 vh0
1
Vfrac
vmult
Figure 4 Voltage cut-out function in der_a model
However, it is important to note that this model could be used to represent an aggregation of DERs
on all three phases and not all phases see the same voltage for unbalanced faults. Hence in the
proposed “der_a_ph” model, all other aspects are the same as the der_a model, except that the model
uses the highest of the three phase voltages for high-voltage protection and lowest of the three phase
voltages for low-voltage protection. The parameters used for the der_a model are obtained from the
NERC guideline [9], and the parameters pertinent to the momentary cessation/trip settings are
provided in Table 1. Note that in the der_a_ph model used in this section while the entire unit is
tripped on over/under-voltage, since only the DERs on the phases with extreme voltages are tripped it
would be more realistic to trip only a fraction of the net DER output for individual phase violations.
This modified model was used in a small 9-bus system with three generators, one of which was
modelled using der_a_ph. A 10-cycle solid SLG fault was applied one bus away from the DER
terminals i.e. on the high-side of its step-up transformer. The phase A, B, C and positive sequence
voltages are shown in Figure 5. Phase A being assumed to be the faulted phase for SLG faults in
PSLF, phase A voltage is much lower than the other two phases as seen in Figure 5, while the other
two phase voltage magnitudes are higher than the positive sequence voltage which is shown in blue.
As expected, before the unbalanced fault is applied and after it is cleared, all three phase voltage
magnitudes match the positive sequence voltage magnitude. It is seen that the lowest phase voltage
drops below vl1 for more than tvl1 seconds and hence the output of the DER is reduced from 160 MW
to about 60 MW when the fault is applied and remains at that value for about 4 s, as shown in Figure
6. This reduced output causes the frequency to gradually decline, until the fltrp threshold is crossed at
about 2.79s, causing the DER to completely trip on under-frequency at about 4.79s once the timer tfl
times out. The output of the voltage cut-out block, output of the frequency trip block, as well as the
frequency seen at the DER terminal are shown in Figure 7. In the case of der_a model however, since
the positive sequence voltage never decreases below vl1, its output recovers as soon as the fault is
cleared and hence the frequency remains above the trip threshold throughout the simulation causing
the unit to remain online throughout the simulation.
Table 1 Trip/cut-out parameters used for der_a/der_a_ph models
Parameter name Description Value
vl0 Voltage break-point for low
voltage cut-out of the inverter
0.44 p.u.
vl1 Voltage break-point for low
voltage cut-out of the inverter
0.49 p.u.
vh0 Voltage break-point for high 1.20 p.u.
7
voltage cut-out of the inverter
vh1 Voltage break-point for high
voltage cut-out of the inverter
1.15 p.u.
tvl0 Low voltage cut-out timer 0.16 s
tvl1 Low voltage cut-out timer 0.16 s
tvh0 High voltage cut-out timer 0.16 s
tvh1 High voltage cut-out timer 0.16 s
vrfrac Fraction of device that recovers
after voltage returns within vl1
and vh1
0
fltrp Low frequency threshold for
cut-out of the inverter
59.3 Hz
fhtrp High frequency threshold for
cut-out of the inverter
60.5 Hz
tfl Low frequency cut-out of timer 2.0 s
tfh High frequency cut-out of timer 2.0 s
Figure 5 Phase A, B, C and positive sequence voltages at the DER terminal
Phase A
Positive Sequence
Phase B
Phase C
8
Figure 6 DER output : Blue : der_a model, Red : der_a_ph model.
Figure 7 DER output : Blue : vmul (output of voltage cut-out block), Red : fmul (output of the
frequency trip block), Pink : Frequency at the DER terminal bus in Hz.
It is seen that the lowest phase voltage is very close to vl0, hence if the voltage cut-out settings
were to be slightly tighter, the DER would have entirely tripped on under-voltage by the time the fault
cleared. This is shown in Figure 8 where the vl0 and vl1 values are 0.47 pu and 0.52 pu respectively. It
can be seen that the lowest phase voltage drops below vl0 for more than tvl0 seconds, causing the DER
to trip entirely when the der_a_ph model is used, whereas the der_a model output recovers once the
fault is cleared.
9
Figure 8 DER output with vl0=0.47, vl1=0.52 : Blue : der_a model, Red : der_a_ph model.
Similarly, the relay model typically used for representing high/low voltage protection for utility-
scale power plants (thermal as well as renewable plants), lhvrt, is modified to use the highest/lowest
phase voltages instead of the positive-sequence voltage to determine trip signals. The model lhvrt has
the provision of including up to ten voltage trip settings, each with its own fixed-timer setting. The
modified model was used in a WECC case for all instances of lhvrt and a 9-cycle single-line-ground
fault was applied at the high-side bus of the step-up transformer for two PV plants. The lhvrt models
for the protection of these two units had eight trip settings, and the relevant one in this study was a
delta voltage threshold of -0.55 pu with a timer of 0.15 s i.e. if the voltage decreases below 0.45 pu for
more than 0.15 s, the unit is to be tripped in the simulation. The dV signals monitored by the two
versions of the model (using positive sequence voltage vs. lowest phase voltage) are shown in Figure
9. It is seen that while the positive sequence reaches a nadir of approximately 0.55 pu, the lowest
phase voltage reaches a nadir of approximately 0.1 pu. Both units trip on under-voltage based on the
lowest phase voltage when the modified model is used, whereas neither trip when the original model is
used. The real power output of one of the units is shown in Figure 10, where the blue curve is obtained
using the original lhvrt model, while the red curve is obtained using the modified version.
10
Figure 9 Voltage deviations (1-|V|) pu seen by lhvrt : Blue : Positive sequence voltage deviation, Red :
Lowest phase voltage deviation.
Figure 10 Output of one of the PV units: Blue : Original lhvrt model, Red : Modified lhvrt model
using phase voltages.
For a different WECC case, a 10-cycle solid LLG fault is applied at the terminals of a PV plant
generating 155MW. There are four trip settings of the lhvrt model for this unit: delta voltage
thresholds of -0.5 pu and 0.2 pu, both with a timer of 0.16s, -0.12 pu with timer of 2s, 0.1 pu with
timer of 1s. The positive sequence voltage and phase voltage magnitudes at the terminal of the plant
are shown in Figure 11. It is seen that while the positive sequence always remains between 0.5 pu and
1.0 pu, the faulted phase voltages (phases B and C) reach 0 pu, while the highest phase voltage
magnitude for phase A is larger than 1.5 pu. Since both the trip criterion of delta voltage less than -0.5
11
pu and greater than 0.2 pu are satisfied, the unit trips when the modified model is used, while it does
not with the original model, as seen from Figure 12.
Figure 11 Phase A, B, C and positive sequence voltages at the PV terminal for LLG fault
Figure 12 Output of the PV unit for LLG fault: Blue : Original lhvrt model, Red : Modified
lhvrt model using phase voltages.
OTHER APPLICATIONS OF SUCH “PHASE QUANTITY-BASED”/ “SEQUENCE
QUANTITY-BASED” MODELS
Even monitoring the phase and sequence quantities without triggering any protection models using
these quantities can provide very useful information while analysing the results of dynamic
simulations. A major challenge with the modelling of distributed energy resources in positive
sequence models is to appropriately parameterize the trip settings in the models such as the der_a
model, to capture the spread of DERs along a feeder each seeing a different terminal voltage and to
capture the effects of unbalanced faults appropriately. The proposed models using phase voltages for
Phase A
Positive Sequence
Phase B = Phase C
12
modelling the voltage cut-out block representing momentary cessation in der_a_ph can make
considering unbalanced faults easier during parameterization. The negative sequence quantity- and
zero sequence quantity-based protection can also be modelled more accurately with such modelling
approaches. Using the additional signals described, negative sequence current relay operation in
conventional generators could be estimated during prolonged unbalanced conditions, such as a single
line reclosing. The signals could also be used to capture motor contactor opening/closing actions more
accurately. Additionally, these approaches can be easily extended to models other than those
mentioned in this paper. For instance, most inverters have active controls to zero out the negative
sequence voltage at the terminals, such that the negative sequence current at the inverter terminals is
zero [5], [7], which may be modelled using such a capability. Additionally, as more and more loads in
the grid become drive-connected, one could also possibly take advantage the sequence/phase
quantities to capture the behaviour such variable frequency drives more accurately in their models.
CONCLUSIONS
The work presented in this paper explores a more realistic representation of protection elements in
dynamics studies, using phase voltage magnitudes and not just positive sequence voltage magnitudes.
While the quantities are still in the RMS domain, they give a clearer picture of the system behaviour
than using only positive sequence quantities. The sequence and per-phase voltage/current quantities
can be obtained for unbalanced faults using available negative and zero sequence data or some
standard assumptions to set up the sequence data. The additional computations involved for obtaining
these per-phase/sequence voltages are minimal and do not add much to the execution times. Case
studies are shown using modified versions of the der_a model modifying the momentary cessation
portion of the model to use the lowest/highest voltage magnitude instead of the positive sequence
voltage magnitude. Likewise, the lhvrt model was modified to use the lowest/highest phase voltage
magnitude for determining trip signals instead of positive sequence voltage. It is shown using WECC
cases that unbalanced faults can cause sufficiently high/low voltages in individual phases to cause trips
which may not necessarily be seen in the positive sequence voltage based models. Thus, using such
models one can get a more accurate grid response from the simulation. The use of sequence/phase
voltage /current quantities can be easily extended to other models such as capturing advanced controls
of inverters.
13
BIBLIOGRAPHY
[1] Q. Cui, S. Li, K. El-Arroudi and G. Joos, “Multifunction intelligent relay for inverter-based
distributed generation,” 13th International Conference on Development in Power System
Protection 2016 (DPSP), Edinburgh, 2016, pp. 1-6.
[2] J. Keller, B. Kroposki, R. Bravo and S. Robles, “Fault current contribution from single-phase
PV inverters,” 2011 37th IEEE Photovoltaic Specialists Conference, Seattle, WA, 2011, pp.
001822-001826.
[3] A. Mishra, N. C. Nair and N. D. Patel, “Fault current characterisation of single phase inverter
systems,” 2017 IEEE Power & Energy Society General Meeting, Chicago, IL, 2017, pp. 1-5.
[4] K. O. Oureilidis and C. S. Demoulias, “A control strategy for inverter-interfaced microgrids
under symmetrical and asymmetrical faults,” 2013 International Conference on Renewable
Energy Research and Applications (ICRERA), Madrid, 2013, pp. 205-210.
[5] S. Brahma, N. Pragallapati and M. Nagpal, “Protection of Islanded Microgrid Fed by Inverters,”
2018 IEEE Power & Energy Society General Meeting (PESGM), Portland, OR, 2018, pp. 1-5.
[6] T. Alexopoulos, M. Biswal, S. M. Brahma and M. E. Khatib, “Detection of fault using local
measurements at inverter interfaced distributed energy resources,” 2017 IEEE Manchester
PowerTech, Manchester, 2017, pp. 1-6.
[7] T. Neumann, T. Wijnhoven, G. Deconinck and I. Erlich, “Enhanced Dynamic Voltage Control
of Type 4 Wind Turbines During Unbalanced Grid Faults,” in IEEE Transactions on Energy
Conversion, vol. 30, no. 4, pp. 1650-1659, Dec. 2015.
[8] Notes on fault analysis, available at:
https://nptel.ac.in/courses/108107028/module4/lecture8/lecture8.pdf
[9] NERC DER_A paramterization guideline, available at:
https://www.nerc.com/comm/PC_Reliability_Guidelines_DL/Reliability_Guideline-
DER_A_Parameterization_2019-05-20.pdf
[10] C. L. Fortescue, “Method of Symmetrical Co-Ordinates Applied to the Solution of Polyphase
Networks,” in Transactions of the American Institute of Electrical Engineers, vol. XXXVII, no.
2, pp. 1027-1140, July 1918.
[11] P28, “ WSCC 9-bus system” available at: http://www.scribd.com/doc/49081324/26/Western-
System-Coordinating-Council-WSCC-3-Machines-9-Bus-system

More Related Content

What's hot

IRJET- Voltage Stability, Loadability and Contingency Analysis with Optimal I...
IRJET- Voltage Stability, Loadability and Contingency Analysis with Optimal I...IRJET- Voltage Stability, Loadability and Contingency Analysis with Optimal I...
IRJET- Voltage Stability, Loadability and Contingency Analysis with Optimal I...IRJET Journal
 
Inter-Area Oscillation Damping using an STATCOM Based Hybrid Shunt Compensati...
Inter-Area Oscillation Damping using an STATCOM Based Hybrid Shunt Compensati...Inter-Area Oscillation Damping using an STATCOM Based Hybrid Shunt Compensati...
Inter-Area Oscillation Damping using an STATCOM Based Hybrid Shunt Compensati...IJPEDS-IAES
 
Open-Switch Fault-Tolerant Control of a Grid-Side Converter in a Wind Power G...
Open-Switch Fault-Tolerant Control of a Grid-Side Converter in a Wind Power G...Open-Switch Fault-Tolerant Control of a Grid-Side Converter in a Wind Power G...
Open-Switch Fault-Tolerant Control of a Grid-Side Converter in a Wind Power G...IJPEDS-IAES
 
Synchronization and Reactive Current Support of PMSG Based Wind Farm during S...
Synchronization and Reactive Current Support of PMSG Based Wind Farm during S...Synchronization and Reactive Current Support of PMSG Based Wind Farm during S...
Synchronization and Reactive Current Support of PMSG Based Wind Farm during S...ijtsrd
 
Welcome to International Journal of Engineering Research and Development (IJERD)
Welcome to International Journal of Engineering Research and Development (IJERD)Welcome to International Journal of Engineering Research and Development (IJERD)
Welcome to International Journal of Engineering Research and Development (IJERD)IJERD Editor
 
2.[6 13]investigation on d-statcom operation for power quality improvement in...
2.[6 13]investigation on d-statcom operation for power quality improvement in...2.[6 13]investigation on d-statcom operation for power quality improvement in...
2.[6 13]investigation on d-statcom operation for power quality improvement in...Alexander Decker
 
Frequency Response Assessment: Parameter Identification of Simplified Governo...
Frequency Response Assessment: Parameter Identification of Simplified Governo...Frequency Response Assessment: Parameter Identification of Simplified Governo...
Frequency Response Assessment: Parameter Identification of Simplified Governo...Power System Operation
 
Using Time Series Analysis to Integrate DA FLISR and CVR Systems
Using Time Series Analysis to Integrate DA FLISR and CVR SystemsUsing Time Series Analysis to Integrate DA FLISR and CVR Systems
Using Time Series Analysis to Integrate DA FLISR and CVR SystemsPower System Operation
 
IRJET- A Comparison of Power Quality Improvement based on Controls of UPQC
IRJET- A Comparison of Power Quality Improvement based on Controls of UPQCIRJET- A Comparison of Power Quality Improvement based on Controls of UPQC
IRJET- A Comparison of Power Quality Improvement based on Controls of UPQCIRJET Journal
 
Low Frequency Oscillations Damping by UPFC with GAPOD and GADC-voltage regulator
Low Frequency Oscillations Damping by UPFC with GAPOD and GADC-voltage regulatorLow Frequency Oscillations Damping by UPFC with GAPOD and GADC-voltage regulator
Low Frequency Oscillations Damping by UPFC with GAPOD and GADC-voltage regulatorIOSR Journals
 
Ga based optimal facts controller for maximizing loadability with stability c...
Ga based optimal facts controller for maximizing loadability with stability c...Ga based optimal facts controller for maximizing loadability with stability c...
Ga based optimal facts controller for maximizing loadability with stability c...IAEME Publication
 
Transient stability analysis of the ieee 9 bus electric power system pgmslm
Transient stability analysis of the ieee 9 bus electric power system pgmslmTransient stability analysis of the ieee 9 bus electric power system pgmslm
Transient stability analysis of the ieee 9 bus electric power system pgmslmHarish PG
 
A Review on Optimization of Coordinated Control Plan for PSS and STATCOM Devi...
A Review on Optimization of Coordinated Control Plan for PSS and STATCOM Devi...A Review on Optimization of Coordinated Control Plan for PSS and STATCOM Devi...
A Review on Optimization of Coordinated Control Plan for PSS and STATCOM Devi...ijtsrd
 

What's hot (19)

IRJET- Voltage Stability, Loadability and Contingency Analysis with Optimal I...
IRJET- Voltage Stability, Loadability and Contingency Analysis with Optimal I...IRJET- Voltage Stability, Loadability and Contingency Analysis with Optimal I...
IRJET- Voltage Stability, Loadability and Contingency Analysis with Optimal I...
 
Inter-Area Oscillation Damping using an STATCOM Based Hybrid Shunt Compensati...
Inter-Area Oscillation Damping using an STATCOM Based Hybrid Shunt Compensati...Inter-Area Oscillation Damping using an STATCOM Based Hybrid Shunt Compensati...
Inter-Area Oscillation Damping using an STATCOM Based Hybrid Shunt Compensati...
 
Presentation1
Presentation1Presentation1
Presentation1
 
Open-Switch Fault-Tolerant Control of a Grid-Side Converter in a Wind Power G...
Open-Switch Fault-Tolerant Control of a Grid-Side Converter in a Wind Power G...Open-Switch Fault-Tolerant Control of a Grid-Side Converter in a Wind Power G...
Open-Switch Fault-Tolerant Control of a Grid-Side Converter in a Wind Power G...
 
Synchronization and Reactive Current Support of PMSG Based Wind Farm during S...
Synchronization and Reactive Current Support of PMSG Based Wind Farm during S...Synchronization and Reactive Current Support of PMSG Based Wind Farm during S...
Synchronization and Reactive Current Support of PMSG Based Wind Farm during S...
 
Welcome to International Journal of Engineering Research and Development (IJERD)
Welcome to International Journal of Engineering Research and Development (IJERD)Welcome to International Journal of Engineering Research and Development (IJERD)
Welcome to International Journal of Engineering Research and Development (IJERD)
 
2.[6 13]investigation on d-statcom operation for power quality improvement in...
2.[6 13]investigation on d-statcom operation for power quality improvement in...2.[6 13]investigation on d-statcom operation for power quality improvement in...
2.[6 13]investigation on d-statcom operation for power quality improvement in...
 
Frequency Response Assessment: Parameter Identification of Simplified Governo...
Frequency Response Assessment: Parameter Identification of Simplified Governo...Frequency Response Assessment: Parameter Identification of Simplified Governo...
Frequency Response Assessment: Parameter Identification of Simplified Governo...
 
Using Time Series Analysis to Integrate DA FLISR and CVR Systems
Using Time Series Analysis to Integrate DA FLISR and CVR SystemsUsing Time Series Analysis to Integrate DA FLISR and CVR Systems
Using Time Series Analysis to Integrate DA FLISR and CVR Systems
 
Load flow analysis of radial distribution system
Load flow analysis of radial distribution system Load flow analysis of radial distribution system
Load flow analysis of radial distribution system
 
IRJET- A Comparison of Power Quality Improvement based on Controls of UPQC
IRJET- A Comparison of Power Quality Improvement based on Controls of UPQCIRJET- A Comparison of Power Quality Improvement based on Controls of UPQC
IRJET- A Comparison of Power Quality Improvement based on Controls of UPQC
 
Low Frequency Oscillations Damping by UPFC with GAPOD and GADC-voltage regulator
Low Frequency Oscillations Damping by UPFC with GAPOD and GADC-voltage regulatorLow Frequency Oscillations Damping by UPFC with GAPOD and GADC-voltage regulator
Low Frequency Oscillations Damping by UPFC with GAPOD and GADC-voltage regulator
 
Ga based optimal facts controller for maximizing loadability with stability c...
Ga based optimal facts controller for maximizing loadability with stability c...Ga based optimal facts controller for maximizing loadability with stability c...
Ga based optimal facts controller for maximizing loadability with stability c...
 
Fault location techniques in smart distribution system
Fault location techniques in smart distribution systemFault location techniques in smart distribution system
Fault location techniques in smart distribution system
 
Transient stability analysis of the ieee 9 bus electric power system pgmslm
Transient stability analysis of the ieee 9 bus electric power system pgmslmTransient stability analysis of the ieee 9 bus electric power system pgmslm
Transient stability analysis of the ieee 9 bus electric power system pgmslm
 
A Review on Optimization of Coordinated Control Plan for PSS and STATCOM Devi...
A Review on Optimization of Coordinated Control Plan for PSS and STATCOM Devi...A Review on Optimization of Coordinated Control Plan for PSS and STATCOM Devi...
A Review on Optimization of Coordinated Control Plan for PSS and STATCOM Devi...
 
A Fuzzy Ga Based STATCOM for Power Quality Improvement
A Fuzzy Ga Based STATCOM for Power Quality ImprovementA Fuzzy Ga Based STATCOM for Power Quality Improvement
A Fuzzy Ga Based STATCOM for Power Quality Improvement
 
Basics of facts
Basics of factsBasics of facts
Basics of facts
 
5 1 voss_panasonic_sandia_epri_160509_3
5 1 voss_panasonic_sandia_epri_160509_35 1 voss_panasonic_sandia_epri_160509_3
5 1 voss_panasonic_sandia_epri_160509_3
 

Similar to Enhanced Protection Modeling Approach for Power System Transient Stability Studies Using Individual Phase and Sequence Voltages

A Novel Back Up Wide Area Protection Technique for Power Transmission Grids U...
A Novel Back Up Wide Area Protection Technique for Power Transmission Grids U...A Novel Back Up Wide Area Protection Technique for Power Transmission Grids U...
A Novel Back Up Wide Area Protection Technique for Power Transmission Grids U...Power System Operation
 
IRJET-Identification of Weak Bus using Load Variation
IRJET-Identification of Weak Bus using Load VariationIRJET-Identification of Weak Bus using Load Variation
IRJET-Identification of Weak Bus using Load VariationIRJET Journal
 
Transient Stability Assessment and Enhancement in Power System
Transient Stability Assessment and Enhancement in Power  SystemTransient Stability Assessment and Enhancement in Power  System
Transient Stability Assessment and Enhancement in Power SystemIJMER
 
To Study, Analysis and Implementation of Power Quality Improvement Using DSTA...
To Study, Analysis and Implementation of Power Quality Improvement Using DSTA...To Study, Analysis and Implementation of Power Quality Improvement Using DSTA...
To Study, Analysis and Implementation of Power Quality Improvement Using DSTA...ijtsrd
 
A New Under-Frequency Load Shedding Method Using the Voltage Electrical Dista...
A New Under-Frequency Load Shedding Method Using the Voltage Electrical Dista...A New Under-Frequency Load Shedding Method Using the Voltage Electrical Dista...
A New Under-Frequency Load Shedding Method Using the Voltage Electrical Dista...IJAEMSJORNAL
 
Three Phase Load Flow Analysis on Four Bus System
Three Phase Load Flow Analysis on Four Bus SystemThree Phase Load Flow Analysis on Four Bus System
Three Phase Load Flow Analysis on Four Bus Systempaperpublications3
 
28 16107 paper 088 ijeecs(edit)
28 16107 paper 088 ijeecs(edit)28 16107 paper 088 ijeecs(edit)
28 16107 paper 088 ijeecs(edit)IAESIJEECS
 
Fault diagnosis of a high voltage transmission line using waveform matching a...
Fault diagnosis of a high voltage transmission line using waveform matching a...Fault diagnosis of a high voltage transmission line using waveform matching a...
Fault diagnosis of a high voltage transmission line using waveform matching a...ijsc
 
An Adaptive Virtual Impedance Based Droop Control Scheme for Parallel Inverte...
An Adaptive Virtual Impedance Based Droop Control Scheme for Parallel Inverte...An Adaptive Virtual Impedance Based Droop Control Scheme for Parallel Inverte...
An Adaptive Virtual Impedance Based Droop Control Scheme for Parallel Inverte...IAES-IJPEDS
 
Continuation Power Flow Method based Assessment of Static Voltage Stability c...
Continuation Power Flow Method based Assessment of Static Voltage Stability c...Continuation Power Flow Method based Assessment of Static Voltage Stability c...
Continuation Power Flow Method based Assessment of Static Voltage Stability c...IJERA Editor
 
An accurate technique for supervising distance relays during power swing
An accurate technique for supervising distance relays during  power swingAn accurate technique for supervising distance relays during  power swing
An accurate technique for supervising distance relays during power swingnooriasukmaningtyas
 
Online voltage stability margin assessment
Online voltage stability margin assessmentOnline voltage stability margin assessment
Online voltage stability margin assessmentNaganathan G Sesaiyan
 
International Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentInternational Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentIJERD Editor
 
POWER SYSTEM PROBLEMS IN TEACHING CONTROL THEORY ON SIMULINK
POWER SYSTEM PROBLEMS IN TEACHING CONTROL THEORY ON SIMULINKPOWER SYSTEM PROBLEMS IN TEACHING CONTROL THEORY ON SIMULINK
POWER SYSTEM PROBLEMS IN TEACHING CONTROL THEORY ON SIMULINKijctcm
 
Reliability analysis of pmu using hidden markov model
Reliability analysis of pmu using hidden markov modelReliability analysis of pmu using hidden markov model
Reliability analysis of pmu using hidden markov modelamaresh1234
 
Control and Implementation of a Standalone DG-SPV-BES micro-grid System using...
Control and Implementation of a Standalone DG-SPV-BES micro-grid System using...Control and Implementation of a Standalone DG-SPV-BES micro-grid System using...
Control and Implementation of a Standalone DG-SPV-BES micro-grid System using...IRJET Journal
 
Fault Diagnosis of a High Voltage Transmission Line Using Waveform Matching A...
Fault Diagnosis of a High Voltage Transmission Line Using Waveform Matching A...Fault Diagnosis of a High Voltage Transmission Line Using Waveform Matching A...
Fault Diagnosis of a High Voltage Transmission Line Using Waveform Matching A...ijsc
 
Optimal Location of FACTS Device for Power System Security Improvement using ...
Optimal Location of FACTS Device for Power System Security Improvement using ...Optimal Location of FACTS Device for Power System Security Improvement using ...
Optimal Location of FACTS Device for Power System Security Improvement using ...IRJET Journal
 
Short circuit current calculations
Short circuit current calculationsShort circuit current calculations
Short circuit current calculationsRonald Santos
 

Similar to Enhanced Protection Modeling Approach for Power System Transient Stability Studies Using Individual Phase and Sequence Voltages (20)

A Novel Back Up Wide Area Protection Technique for Power Transmission Grids U...
A Novel Back Up Wide Area Protection Technique for Power Transmission Grids U...A Novel Back Up Wide Area Protection Technique for Power Transmission Grids U...
A Novel Back Up Wide Area Protection Technique for Power Transmission Grids U...
 
IRJET-Identification of Weak Bus using Load Variation
IRJET-Identification of Weak Bus using Load VariationIRJET-Identification of Weak Bus using Load Variation
IRJET-Identification of Weak Bus using Load Variation
 
Transient Stability Assessment and Enhancement in Power System
Transient Stability Assessment and Enhancement in Power  SystemTransient Stability Assessment and Enhancement in Power  System
Transient Stability Assessment and Enhancement in Power System
 
To Study, Analysis and Implementation of Power Quality Improvement Using DSTA...
To Study, Analysis and Implementation of Power Quality Improvement Using DSTA...To Study, Analysis and Implementation of Power Quality Improvement Using DSTA...
To Study, Analysis and Implementation of Power Quality Improvement Using DSTA...
 
A New Under-Frequency Load Shedding Method Using the Voltage Electrical Dista...
A New Under-Frequency Load Shedding Method Using the Voltage Electrical Dista...A New Under-Frequency Load Shedding Method Using the Voltage Electrical Dista...
A New Under-Frequency Load Shedding Method Using the Voltage Electrical Dista...
 
Three Phase Load Flow Analysis on Four Bus System
Three Phase Load Flow Analysis on Four Bus SystemThree Phase Load Flow Analysis on Four Bus System
Three Phase Load Flow Analysis on Four Bus System
 
28 16107 paper 088 ijeecs(edit)
28 16107 paper 088 ijeecs(edit)28 16107 paper 088 ijeecs(edit)
28 16107 paper 088 ijeecs(edit)
 
Fault diagnosis of a high voltage transmission line using waveform matching a...
Fault diagnosis of a high voltage transmission line using waveform matching a...Fault diagnosis of a high voltage transmission line using waveform matching a...
Fault diagnosis of a high voltage transmission line using waveform matching a...
 
An Adaptive Virtual Impedance Based Droop Control Scheme for Parallel Inverte...
An Adaptive Virtual Impedance Based Droop Control Scheme for Parallel Inverte...An Adaptive Virtual Impedance Based Droop Control Scheme for Parallel Inverte...
An Adaptive Virtual Impedance Based Droop Control Scheme for Parallel Inverte...
 
Continuation Power Flow Method based Assessment of Static Voltage Stability c...
Continuation Power Flow Method based Assessment of Static Voltage Stability c...Continuation Power Flow Method based Assessment of Static Voltage Stability c...
Continuation Power Flow Method based Assessment of Static Voltage Stability c...
 
An accurate technique for supervising distance relays during power swing
An accurate technique for supervising distance relays during  power swingAn accurate technique for supervising distance relays during  power swing
An accurate technique for supervising distance relays during power swing
 
Online voltage stability margin assessment
Online voltage stability margin assessmentOnline voltage stability margin assessment
Online voltage stability margin assessment
 
International Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentInternational Journal of Engineering Research and Development
International Journal of Engineering Research and Development
 
40220130405009
4022013040500940220130405009
40220130405009
 
POWER SYSTEM PROBLEMS IN TEACHING CONTROL THEORY ON SIMULINK
POWER SYSTEM PROBLEMS IN TEACHING CONTROL THEORY ON SIMULINKPOWER SYSTEM PROBLEMS IN TEACHING CONTROL THEORY ON SIMULINK
POWER SYSTEM PROBLEMS IN TEACHING CONTROL THEORY ON SIMULINK
 
Reliability analysis of pmu using hidden markov model
Reliability analysis of pmu using hidden markov modelReliability analysis of pmu using hidden markov model
Reliability analysis of pmu using hidden markov model
 
Control and Implementation of a Standalone DG-SPV-BES micro-grid System using...
Control and Implementation of a Standalone DG-SPV-BES micro-grid System using...Control and Implementation of a Standalone DG-SPV-BES micro-grid System using...
Control and Implementation of a Standalone DG-SPV-BES micro-grid System using...
 
Fault Diagnosis of a High Voltage Transmission Line Using Waveform Matching A...
Fault Diagnosis of a High Voltage Transmission Line Using Waveform Matching A...Fault Diagnosis of a High Voltage Transmission Line Using Waveform Matching A...
Fault Diagnosis of a High Voltage Transmission Line Using Waveform Matching A...
 
Optimal Location of FACTS Device for Power System Security Improvement using ...
Optimal Location of FACTS Device for Power System Security Improvement using ...Optimal Location of FACTS Device for Power System Security Improvement using ...
Optimal Location of FACTS Device for Power System Security Improvement using ...
 
Short circuit current calculations
Short circuit current calculationsShort circuit current calculations
Short circuit current calculations
 

More from Power System Operation

Thermography test of electrical panels
Thermography test of electrical panelsThermography test of electrical panels
Thermography test of electrical panelsPower System Operation
 
Big Data Analytics for Power Grid Operations
Big Data Analytics for Power Grid OperationsBig Data Analytics for Power Grid Operations
Big Data Analytics for Power Grid OperationsPower System Operation
 
SPS to RAS Special Protection Scheme Remedial Action Scheme
SPS to RAS Special Protection Scheme  Remedial Action SchemeSPS to RAS Special Protection Scheme  Remedial Action Scheme
SPS to RAS Special Protection Scheme Remedial Action SchemePower System Operation
 
SVC PLUS Frequency Stabilizer Frequency and voltage support for dynamic grid...
SVC PLUS Frequency Stabilizer Frequency and voltage support for  dynamic grid...SVC PLUS Frequency Stabilizer Frequency and voltage support for  dynamic grid...
SVC PLUS Frequency Stabilizer Frequency and voltage support for dynamic grid...Power System Operation
 
Principles & Testing Methods Of Earth Ground Resistance
Principles & Testing Methods Of Earth Ground ResistancePrinciples & Testing Methods Of Earth Ground Resistance
Principles & Testing Methods Of Earth Ground ResistancePower System Operation
 
Gas Insulated Switchgear? Gas-Insulated High-Voltage Switchgear (GIS)
Gas Insulated Switchgear?  Gas-Insulated High-Voltage Switchgear (GIS)Gas Insulated Switchgear?  Gas-Insulated High-Voltage Switchgear (GIS)
Gas Insulated Switchgear? Gas-Insulated High-Voltage Switchgear (GIS)Power System Operation
 
Electrical Transmission Tower Types - Design & Parts
Electrical Transmission Tower  Types - Design & PartsElectrical Transmission Tower  Types - Design & Parts
Electrical Transmission Tower Types - Design & PartsPower System Operation
 
Power Quality Trends in the Transition to Carbon-Free Electrical Energy System
Power Quality  Trends in the Transition to  Carbon-Free Electrical Energy SystemPower Quality  Trends in the Transition to  Carbon-Free Electrical Energy System
Power Quality Trends in the Transition to Carbon-Free Electrical Energy SystemPower System Operation
 
SCADA System ? Supervisory Control & Data Acquisition
SCADA System ? Supervisory Control & Data AcquisitionSCADA System ? Supervisory Control & Data Acquisition
SCADA System ? Supervisory Control & Data AcquisitionPower System Operation
 

More from Power System Operation (20)

ENERGY TRANSITION OUTLOOK 2021
ENERGY TRANSITION OUTLOOK  2021ENERGY TRANSITION OUTLOOK  2021
ENERGY TRANSITION OUTLOOK 2021
 
Thermography test of electrical panels
Thermography test of electrical panelsThermography test of electrical panels
Thermography test of electrical panels
 
What does peak shaving mean
What does peak shaving meanWhat does peak shaving mean
What does peak shaving mean
 
What's short circuit level
What's short circuit levelWhat's short circuit level
What's short circuit level
 
Power System Restoration Guide
Power System Restoration Guide  Power System Restoration Guide
Power System Restoration Guide
 
Big Data Analytics for Power Grid Operations
Big Data Analytics for Power Grid OperationsBig Data Analytics for Power Grid Operations
Big Data Analytics for Power Grid Operations
 
SPS to RAS Special Protection Scheme Remedial Action Scheme
SPS to RAS Special Protection Scheme  Remedial Action SchemeSPS to RAS Special Protection Scheme  Remedial Action Scheme
SPS to RAS Special Protection Scheme Remedial Action Scheme
 
Substation Neutral Earthing
Substation Neutral EarthingSubstation Neutral Earthing
Substation Neutral Earthing
 
SVC PLUS Frequency Stabilizer Frequency and voltage support for dynamic grid...
SVC PLUS Frequency Stabilizer Frequency and voltage support for  dynamic grid...SVC PLUS Frequency Stabilizer Frequency and voltage support for  dynamic grid...
SVC PLUS Frequency Stabilizer Frequency and voltage support for dynamic grid...
 
Principles & Testing Methods Of Earth Ground Resistance
Principles & Testing Methods Of Earth Ground ResistancePrinciples & Testing Methods Of Earth Ground Resistance
Principles & Testing Methods Of Earth Ground Resistance
 
Gas Insulated Switchgear? Gas-Insulated High-Voltage Switchgear (GIS)
Gas Insulated Switchgear?  Gas-Insulated High-Voltage Switchgear (GIS)Gas Insulated Switchgear?  Gas-Insulated High-Voltage Switchgear (GIS)
Gas Insulated Switchgear? Gas-Insulated High-Voltage Switchgear (GIS)
 
Electrical Transmission Tower Types - Design & Parts
Electrical Transmission Tower  Types - Design & PartsElectrical Transmission Tower  Types - Design & Parts
Electrical Transmission Tower Types - Design & Parts
 
What is load management
What is load managementWhat is load management
What is load management
 
What does merit order mean
What does merit order meanWhat does merit order mean
What does merit order mean
 
What are Balancing Services ?
What are  Balancing Services ?What are  Balancing Services ?
What are Balancing Services ?
 
Power Quality Trends in the Transition to Carbon-Free Electrical Energy System
Power Quality  Trends in the Transition to  Carbon-Free Electrical Energy SystemPower Quality  Trends in the Transition to  Carbon-Free Electrical Energy System
Power Quality Trends in the Transition to Carbon-Free Electrical Energy System
 
Power Purchase Agreement PPA
Power Purchase Agreement PPA Power Purchase Agreement PPA
Power Purchase Agreement PPA
 
Harmonic study and analysis
Harmonic study and analysisHarmonic study and analysis
Harmonic study and analysis
 
What is leakage current testing
What is leakage current testingWhat is leakage current testing
What is leakage current testing
 
SCADA System ? Supervisory Control & Data Acquisition
SCADA System ? Supervisory Control & Data AcquisitionSCADA System ? Supervisory Control & Data Acquisition
SCADA System ? Supervisory Control & Data Acquisition
 

Recently uploaded

Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)simmis5
 
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Bookingdharasingh5698
 
UNIT-III FMM. DIMENSIONAL ANALYSIS
UNIT-III FMM.        DIMENSIONAL ANALYSISUNIT-III FMM.        DIMENSIONAL ANALYSIS
UNIT-III FMM. DIMENSIONAL ANALYSISrknatarajan
 
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordAsst.prof M.Gokilavani
 
University management System project report..pdf
University management System project report..pdfUniversity management System project report..pdf
University management System project report..pdfKamal Acharya
 
Online banking management system project.pdf
Online banking management system project.pdfOnline banking management system project.pdf
Online banking management system project.pdfKamal Acharya
 
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and workingUNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and workingrknatarajan
 
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptx
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptxBSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptx
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptxfenichawla
 
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Christo Ananth
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Christo Ananth
 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxpranjaldaimarysona
 
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...ranjana rawat
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Dr.Costas Sachpazis
 
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...roncy bisnoi
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingrakeshbaidya232001
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 

Recently uploaded (20)

Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)
 
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
 
UNIT-III FMM. DIMENSIONAL ANALYSIS
UNIT-III FMM.        DIMENSIONAL ANALYSISUNIT-III FMM.        DIMENSIONAL ANALYSIS
UNIT-III FMM. DIMENSIONAL ANALYSIS
 
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
 
University management System project report..pdf
University management System project report..pdfUniversity management System project report..pdf
University management System project report..pdf
 
Online banking management system project.pdf
Online banking management system project.pdfOnline banking management system project.pdf
Online banking management system project.pdf
 
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and workingUNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
 
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptx
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptxBSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptx
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptx
 
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptx
 
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
 
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
 
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writing
 
Roadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and RoutesRoadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and Routes
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
 

Enhanced Protection Modeling Approach for Power System Transient Stability Studies Using Individual Phase and Sequence Voltages

  • 1. shrutidwarkanath.rao@ge.com 21, rue d’Artois, F-75008 PARIS CIGRE US National Committee http://www.cigre.org 2019 Grid of the Future Symposium Enhanced Protection Modeling Approach for Power System Transient Stability Studies Using Individual Phase and Sequence Voltages S. D. RAO, J. J. SANCHEZ-GASCA, S. ACHILLES GE Energy Consulting USA SUMMARY Accurate protection modelling in power system transient stability studies is required to ensure that reliable conclusions are drawn from such analyses. Typically, protection models available in transient stability programs use only positive sequence quantities such as the positive sequence voltages, currents, etc. to trigger any preventive/corrective actions such as tripping of generators, load-shedding, etc. However, with the increasing penetration of inverter-based resources, these models could prove to be inadequate in some scenarios. The work reported in this paper uses improved modelling practices for protection elements in transient stability studies using sequence/individual phase quantities. This approach does not necessarily require additional data from users and incurs only minimal incremental computational costs. In addition to using the sequence voltages/currents or individual phase voltages/currents for more accurate representation of protection systems, simply monitoring these quantities can also provide useful additional information about the system. Additionally, having access to these quantities could be useful in more accurate modelling of inverter-based resources such as the ability to model converter controls’ protective functions, controls that actively suppress the negative sequence current produced by the inverter, and other such controls that use or control the negative sequence or zero sequence current injections. In the absence of negative sequence and zero sequence network data, some typical assumptions based on engineering judgement are used to approximate this data. Once the data is available for all three sequence networks, the RMS sequence voltages (and currents) can be easily computed in the time-frame when an unbalanced fault is applied during a dynamic simulation. Since the network is assumed to be balanced before an unbalanced fault is applied and after it is cleared, the non-positive sequence voltages and currents in those time-frames are zero and all three phase voltages have equal magnitudes. Using this feature, two protection models widely used in dynamic simulation studies that are present in all commercial transient stability programs are modified in this work to use the lowest/highest individual phase voltage instead of positive sequence voltage to trigger trip signals. Even though the proposed models/techniques would have an impact in the relatively short time frame when an unbalanced fault is on in the system, it could have a significant impact on studies involving delayed clearing of faults. While it is not practical to model entire interconnection-wide base cases in a detailed three-phase domain for all transient stability studies, the proposed approach is aimed at trying to achieve a middle ground, such that more information about the system behaviour is obtained and protection systems are more realistically represented in RMS studies. These models are incorporated into a commercial positive sequence dynamic simulation engine GE-PSLF. Case studies using these models in two Western Electricity Coordinating Council (WECC) cases and a 9-bus case are discussed. With the framework to compute sequence/phase voltages/currents in place, the approach can be easily extended to models other than those mentioned in this paper. The possible future uses of such modelling capabilities for improved modelling of inverter controls etc. are also discussed.
  • 2. 2 KEYWORDS Protection modelling, Dynamics studies, Sequence voltages, unbalanced faults, phase voltage-based tripping.
  • 3. 3 INTRODUCTION One of the recent topics of research focus in the power system industry has been understanding the behaviour of protection relaying elements or inverter protective functions in the grid under increasing penetration levels of inverter-based resources (IBRs), and ensuring reliable fault detection for such scenarios [1] - [7]. Inverter-based resources restrict their fault current contribution to be close to their rated current injection (typically less than 1.5 pu), which makes fault detection difficult [3], [5]. Additionally, some controls in modern converters are designed to inject very limited negative sequence currents under faulted conditions as compared to traditional machines [5]. Hence the fault detection techniques used in protection systems in emerging grids could also be different than traditional protection systems. For example, the negative sequence voltage generated by inverters to negate that seen at the terminals such that the negative sequence current injected by the inverter is zero, is proposed to be used to detect unbalanced faults in [4]. Zero-sequence based protection is proposed to be used in [5] to detect unbalanced faults in cases where the load unbalance is not very high, while the zero-sequence current magnitude on the high-side of the step-up transformer along with under-voltage detection is proposed to be used in [6]. An elaborate fault detection methodology using phase as well as sequence voltages has been proposed and tested on a hardware-in-the-loop setup in [1]. For typical dynamics studies, the network is assumed to be balanced before and after any unbalanced disturbances are cleared. Consequently, these studies typically involve the representation of positive-sequence networks and models only. Hence the state-of-the-art protection models in transient stability studies, such as those used for generator protection, load shedding, etc., also use only positive sequence voltages and currents to trigger tripping actions. However, since a vast majority of the faults seen on the system are unbalanced, monitoring/using only positive sequence quantities can be inadequate in some situations, especially for studies involving delayed clearing of the faults. The changing fault response of the system with several utility scale renewable energy resources as well as distributed energy resources using converter technologies, could render some of the traditional dynamic models inadequate in terms of sufficiently capturing controller actions that could have a noticeable effect on the post-fault system behaviour, which could in turn lead to misleading conclusions drawn from the results of such simulations. The voltages of the un-faulted phases in the vicinity of the fault may reach very high levels, likewise the faulted phase voltages may reach very low levels causing high phase currents. These severe conditions may persist for a duration sufficiently long to trigger tripping actions by the protection elements or protective functions in IBR controllers. Likewise, there may be some protection elements utilizing the negative sequence voltages/currents, and if standard positive sequence protection models are used for dynamic simulations, one could fail to predict the loss of some units. In this work, the sequence voltages are computed using the positive-, negative- and zero-sequence networks during the timeframe that an unbalanced fault is on in the system. Since the network admittance matrices are built and factorized only when there is a network change, the additional computational expense of such capabilities is not significant. For the Western Electricity Coordinating Council (WECC) cases used in this work, the execution time needed on average is similar to that when only positive sequence quantities are computed. Next, the “der_a” model (described in detail in [9]) meant to represent distributed energy resources in bulk system studies is modified to use the lowest/highest phase voltage in the voltage cut-out logic that is meant to capture momentary cessation. Similarly, one of the most widely used generator protection models in dynamics studies, “lhvrt” that is meant to model the protection for generators against low/high voltages, is modified. In the modified version of the model trip signals are triggered based on the lowest/highest individual phase voltage instead of the positive sequence voltage. A meter model is also implemented as a part of this work, to monitor the sequence voltages or individual phase voltages at the buses/areas/zones of interest. Case studies are presented using WECC cases to demonstrate the advantages of such modelling. Other applications of such modelling techniques such as more detailed converter models are also discussed.
  • 4. 4 SEQUENCE NETWORK ASSUMPTIONS One of the challenges in obtaining all sequence/phase quantities is that often the zero-sequence and negative-sequence network data are not mapped to the positive sequence network data used in dynamic simulations. Since the zero sequence and negative sequence representations of the system are necessary for the computation of these sequence/per-phase voltages and currents, if this data is not readily available some standard engineering assumptions are employed to approximate the negative sequence and zero sequence network data using the available positive-sequence data. These are standard assumptions made in typical short circuit analysis studies and are listed in this section. The negative sequence impedances for generators are assumed to be equal to their respective positive sequence impedances. Generators are assumed to be open-circuited for zero sequence networks as most generator step-up (GSU) transformers are connected in delta on the generator side. All transformer connections are assumed to be wye-grounded except on the generator-side for GSUs which are assumed to be in delta. The negative sequence and zero sequence transformer impedances are assumed to be equal to the positive sequence impedances. For transmission lines, the negative sequence impedances are assumed to be equal to the positive sequence impedances and the zero- sequence impedances are assumed to be thrice the positive sequence impedances. The zero-sequence charging shunt admittances for transmission lines are assumed to be half that of the positive sequence charging shunt admittances while the negative sequence charging shunt admittances are assumed to be equal to the positive sequence charging shunt admittances. Loads and shunts are assumed to be constant admittance in the negative sequence network with the same admittance as they would have in positive sequence, while they are assumed to be open circuited in the zero-sequence network. In the duration that an unbalanced fault is applied, the source of unbalance is assumed to be only at the faulted location (i.e. loads and the rest of the network are still assumed to be balanced). The sequence network interconnections for single-line-ground (SLG) faults, line-line (LL) faults, and line-line- ground (LLG) faults are standard, as available in several references and shown in Figure 1 [8]. With the positive, negative, and zero sequence current injections at the faulted location known, the sequence voltages and currents throughout the network can easily be computed. The sequence voltages/currents can then be used to obtain the phase A, B, C voltages/currents using the standard transformation matrix [10]. For a 9-bus simplified representation of the western interconnection [11], the phase A, B, C, and positive sequence voltages for an SLG bus fault at bus 6 are shown in Figure 2. The negative sequence voltage seen at the terminals of a photovoltaic (PV) plant in a full WECC case for an SLG fault is shown in Figure 3. Figure 1 Network interconnections for unbalanced faults [8] SLG fault LL fault LLG fault
  • 5. 5 Figure 2 Individual phase voltages for a single-line-ground fault at bus 6 Figure 3 Negative sequence voltage (pu) seen at the terminal of the PV units in WECC case CASE STUDIES In this section, some examples will be shown to demonstrate the modified models. The der_a is the latest WECC-approved model to represent an aggregation of DERs including utility-scale DER (U-DER) as well as retail-scale DERs (R-DER) along a feeder [9]. The model has also been recently included as a component in the composite load model (cmpldw). One of the salient features of this model is its capability to capture momentary cessation and tripping of these resources on high/low voltages. This voltage cut-out block uses the positive-sequence voltage to send either trip signals or reduced current signals as shown in Figure 4. The output of this block vmult is multiplied with the current command signal to obtain the actual current injection into the network. The signal vmult tracks the black line defined by the points (vl0,0), (vl1,1),(vh1,1), and (vh0,0) unless the following conditions occur: • If the voltage stays below vl1 for a duration greater than tvl1, vmult will follow the path of the red line when the voltage recovers. Vmin is the lowest voltage (greater than vl0) during a simulation after timer tvl1 expires.
  • 6. 6 • If the voltage stays above vh1 for a duration greater than tvh1, vmult will follow the path of the red line when the voltage recovers. Vmax is the highest voltage (lesser than vh0) during a simulation after timer tvh1 expires. • If the voltage Vt_flt stays below vl0 for more than tvl0 seconds or if it stays above vh0 for more than tvh0 seconds, then vmult will remain at zero i.e. the DERs are completely trippped. The frequency trip action of the model is fairly straightforward where if the frequency seen at the terminals of the DER falls below the parameter fltrp for more than tfl seconds or increases more than fhtrp for more than tfh seconds, the DERs are entirely tripped. Vt_flt 1 vl1vl0 0 vh1 vh0 vmult vl0 vmin vl1 vh1 vh0 1 Vfrac vmult Figure 4 Voltage cut-out function in der_a model However, it is important to note that this model could be used to represent an aggregation of DERs on all three phases and not all phases see the same voltage for unbalanced faults. Hence in the proposed “der_a_ph” model, all other aspects are the same as the der_a model, except that the model uses the highest of the three phase voltages for high-voltage protection and lowest of the three phase voltages for low-voltage protection. The parameters used for the der_a model are obtained from the NERC guideline [9], and the parameters pertinent to the momentary cessation/trip settings are provided in Table 1. Note that in the der_a_ph model used in this section while the entire unit is tripped on over/under-voltage, since only the DERs on the phases with extreme voltages are tripped it would be more realistic to trip only a fraction of the net DER output for individual phase violations. This modified model was used in a small 9-bus system with three generators, one of which was modelled using der_a_ph. A 10-cycle solid SLG fault was applied one bus away from the DER terminals i.e. on the high-side of its step-up transformer. The phase A, B, C and positive sequence voltages are shown in Figure 5. Phase A being assumed to be the faulted phase for SLG faults in PSLF, phase A voltage is much lower than the other two phases as seen in Figure 5, while the other two phase voltage magnitudes are higher than the positive sequence voltage which is shown in blue. As expected, before the unbalanced fault is applied and after it is cleared, all three phase voltage magnitudes match the positive sequence voltage magnitude. It is seen that the lowest phase voltage drops below vl1 for more than tvl1 seconds and hence the output of the DER is reduced from 160 MW to about 60 MW when the fault is applied and remains at that value for about 4 s, as shown in Figure 6. This reduced output causes the frequency to gradually decline, until the fltrp threshold is crossed at about 2.79s, causing the DER to completely trip on under-frequency at about 4.79s once the timer tfl times out. The output of the voltage cut-out block, output of the frequency trip block, as well as the frequency seen at the DER terminal are shown in Figure 7. In the case of der_a model however, since the positive sequence voltage never decreases below vl1, its output recovers as soon as the fault is cleared and hence the frequency remains above the trip threshold throughout the simulation causing the unit to remain online throughout the simulation. Table 1 Trip/cut-out parameters used for der_a/der_a_ph models Parameter name Description Value vl0 Voltage break-point for low voltage cut-out of the inverter 0.44 p.u. vl1 Voltage break-point for low voltage cut-out of the inverter 0.49 p.u. vh0 Voltage break-point for high 1.20 p.u.
  • 7. 7 voltage cut-out of the inverter vh1 Voltage break-point for high voltage cut-out of the inverter 1.15 p.u. tvl0 Low voltage cut-out timer 0.16 s tvl1 Low voltage cut-out timer 0.16 s tvh0 High voltage cut-out timer 0.16 s tvh1 High voltage cut-out timer 0.16 s vrfrac Fraction of device that recovers after voltage returns within vl1 and vh1 0 fltrp Low frequency threshold for cut-out of the inverter 59.3 Hz fhtrp High frequency threshold for cut-out of the inverter 60.5 Hz tfl Low frequency cut-out of timer 2.0 s tfh High frequency cut-out of timer 2.0 s Figure 5 Phase A, B, C and positive sequence voltages at the DER terminal Phase A Positive Sequence Phase B Phase C
  • 8. 8 Figure 6 DER output : Blue : der_a model, Red : der_a_ph model. Figure 7 DER output : Blue : vmul (output of voltage cut-out block), Red : fmul (output of the frequency trip block), Pink : Frequency at the DER terminal bus in Hz. It is seen that the lowest phase voltage is very close to vl0, hence if the voltage cut-out settings were to be slightly tighter, the DER would have entirely tripped on under-voltage by the time the fault cleared. This is shown in Figure 8 where the vl0 and vl1 values are 0.47 pu and 0.52 pu respectively. It can be seen that the lowest phase voltage drops below vl0 for more than tvl0 seconds, causing the DER to trip entirely when the der_a_ph model is used, whereas the der_a model output recovers once the fault is cleared.
  • 9. 9 Figure 8 DER output with vl0=0.47, vl1=0.52 : Blue : der_a model, Red : der_a_ph model. Similarly, the relay model typically used for representing high/low voltage protection for utility- scale power plants (thermal as well as renewable plants), lhvrt, is modified to use the highest/lowest phase voltages instead of the positive-sequence voltage to determine trip signals. The model lhvrt has the provision of including up to ten voltage trip settings, each with its own fixed-timer setting. The modified model was used in a WECC case for all instances of lhvrt and a 9-cycle single-line-ground fault was applied at the high-side bus of the step-up transformer for two PV plants. The lhvrt models for the protection of these two units had eight trip settings, and the relevant one in this study was a delta voltage threshold of -0.55 pu with a timer of 0.15 s i.e. if the voltage decreases below 0.45 pu for more than 0.15 s, the unit is to be tripped in the simulation. The dV signals monitored by the two versions of the model (using positive sequence voltage vs. lowest phase voltage) are shown in Figure 9. It is seen that while the positive sequence reaches a nadir of approximately 0.55 pu, the lowest phase voltage reaches a nadir of approximately 0.1 pu. Both units trip on under-voltage based on the lowest phase voltage when the modified model is used, whereas neither trip when the original model is used. The real power output of one of the units is shown in Figure 10, where the blue curve is obtained using the original lhvrt model, while the red curve is obtained using the modified version.
  • 10. 10 Figure 9 Voltage deviations (1-|V|) pu seen by lhvrt : Blue : Positive sequence voltage deviation, Red : Lowest phase voltage deviation. Figure 10 Output of one of the PV units: Blue : Original lhvrt model, Red : Modified lhvrt model using phase voltages. For a different WECC case, a 10-cycle solid LLG fault is applied at the terminals of a PV plant generating 155MW. There are four trip settings of the lhvrt model for this unit: delta voltage thresholds of -0.5 pu and 0.2 pu, both with a timer of 0.16s, -0.12 pu with timer of 2s, 0.1 pu with timer of 1s. The positive sequence voltage and phase voltage magnitudes at the terminal of the plant are shown in Figure 11. It is seen that while the positive sequence always remains between 0.5 pu and 1.0 pu, the faulted phase voltages (phases B and C) reach 0 pu, while the highest phase voltage magnitude for phase A is larger than 1.5 pu. Since both the trip criterion of delta voltage less than -0.5
  • 11. 11 pu and greater than 0.2 pu are satisfied, the unit trips when the modified model is used, while it does not with the original model, as seen from Figure 12. Figure 11 Phase A, B, C and positive sequence voltages at the PV terminal for LLG fault Figure 12 Output of the PV unit for LLG fault: Blue : Original lhvrt model, Red : Modified lhvrt model using phase voltages. OTHER APPLICATIONS OF SUCH “PHASE QUANTITY-BASED”/ “SEQUENCE QUANTITY-BASED” MODELS Even monitoring the phase and sequence quantities without triggering any protection models using these quantities can provide very useful information while analysing the results of dynamic simulations. A major challenge with the modelling of distributed energy resources in positive sequence models is to appropriately parameterize the trip settings in the models such as the der_a model, to capture the spread of DERs along a feeder each seeing a different terminal voltage and to capture the effects of unbalanced faults appropriately. The proposed models using phase voltages for Phase A Positive Sequence Phase B = Phase C
  • 12. 12 modelling the voltage cut-out block representing momentary cessation in der_a_ph can make considering unbalanced faults easier during parameterization. The negative sequence quantity- and zero sequence quantity-based protection can also be modelled more accurately with such modelling approaches. Using the additional signals described, negative sequence current relay operation in conventional generators could be estimated during prolonged unbalanced conditions, such as a single line reclosing. The signals could also be used to capture motor contactor opening/closing actions more accurately. Additionally, these approaches can be easily extended to models other than those mentioned in this paper. For instance, most inverters have active controls to zero out the negative sequence voltage at the terminals, such that the negative sequence current at the inverter terminals is zero [5], [7], which may be modelled using such a capability. Additionally, as more and more loads in the grid become drive-connected, one could also possibly take advantage the sequence/phase quantities to capture the behaviour such variable frequency drives more accurately in their models. CONCLUSIONS The work presented in this paper explores a more realistic representation of protection elements in dynamics studies, using phase voltage magnitudes and not just positive sequence voltage magnitudes. While the quantities are still in the RMS domain, they give a clearer picture of the system behaviour than using only positive sequence quantities. The sequence and per-phase voltage/current quantities can be obtained for unbalanced faults using available negative and zero sequence data or some standard assumptions to set up the sequence data. The additional computations involved for obtaining these per-phase/sequence voltages are minimal and do not add much to the execution times. Case studies are shown using modified versions of the der_a model modifying the momentary cessation portion of the model to use the lowest/highest voltage magnitude instead of the positive sequence voltage magnitude. Likewise, the lhvrt model was modified to use the lowest/highest phase voltage magnitude for determining trip signals instead of positive sequence voltage. It is shown using WECC cases that unbalanced faults can cause sufficiently high/low voltages in individual phases to cause trips which may not necessarily be seen in the positive sequence voltage based models. Thus, using such models one can get a more accurate grid response from the simulation. The use of sequence/phase voltage /current quantities can be easily extended to other models such as capturing advanced controls of inverters.
  • 13. 13 BIBLIOGRAPHY [1] Q. Cui, S. Li, K. El-Arroudi and G. Joos, “Multifunction intelligent relay for inverter-based distributed generation,” 13th International Conference on Development in Power System Protection 2016 (DPSP), Edinburgh, 2016, pp. 1-6. [2] J. Keller, B. Kroposki, R. Bravo and S. Robles, “Fault current contribution from single-phase PV inverters,” 2011 37th IEEE Photovoltaic Specialists Conference, Seattle, WA, 2011, pp. 001822-001826. [3] A. Mishra, N. C. Nair and N. D. Patel, “Fault current characterisation of single phase inverter systems,” 2017 IEEE Power & Energy Society General Meeting, Chicago, IL, 2017, pp. 1-5. [4] K. O. Oureilidis and C. S. Demoulias, “A control strategy for inverter-interfaced microgrids under symmetrical and asymmetrical faults,” 2013 International Conference on Renewable Energy Research and Applications (ICRERA), Madrid, 2013, pp. 205-210. [5] S. Brahma, N. Pragallapati and M. Nagpal, “Protection of Islanded Microgrid Fed by Inverters,” 2018 IEEE Power & Energy Society General Meeting (PESGM), Portland, OR, 2018, pp. 1-5. [6] T. Alexopoulos, M. Biswal, S. M. Brahma and M. E. Khatib, “Detection of fault using local measurements at inverter interfaced distributed energy resources,” 2017 IEEE Manchester PowerTech, Manchester, 2017, pp. 1-6. [7] T. Neumann, T. Wijnhoven, G. Deconinck and I. Erlich, “Enhanced Dynamic Voltage Control of Type 4 Wind Turbines During Unbalanced Grid Faults,” in IEEE Transactions on Energy Conversion, vol. 30, no. 4, pp. 1650-1659, Dec. 2015. [8] Notes on fault analysis, available at: https://nptel.ac.in/courses/108107028/module4/lecture8/lecture8.pdf [9] NERC DER_A paramterization guideline, available at: https://www.nerc.com/comm/PC_Reliability_Guidelines_DL/Reliability_Guideline- DER_A_Parameterization_2019-05-20.pdf [10] C. L. Fortescue, “Method of Symmetrical Co-Ordinates Applied to the Solution of Polyphase Networks,” in Transactions of the American Institute of Electrical Engineers, vol. XXXVII, no. 2, pp. 1027-1140, July 1918. [11] P28, “ WSCC 9-bus system” available at: http://www.scribd.com/doc/49081324/26/Western- System-Coordinating-Council-WSCC-3-Machines-9-Bus-system