International Journal of Power Electronics and Drive System (IJPEDS)
Vol. 7, No. 4, December 2016, pp. 1172~1180
ISSN: 2088-8694, DOI: 10.11591/ijpeds.v7i4.pp1172-1180  1172
Journal homepage: http://iaesjournal.com/online/index.php/IJPEDS
Inter-Area Oscillation Damping using an STATCOM Based
Hybrid Shunt Compensation Scheme
Vahid Farzam, Ahad Mokhtarpour
Department of Electrical and Electronic Engineering, Tabriz Branch, Islamic Azad University Tabriz, Iran
Article Info ABSTRACT
Article history:
Received May 31, 2016
Revised Nov 5, 2016
Accepted Nov 17, 2016
FACTS devices are one of the latest technologies which have been used to
improve power system dynamic and stability during recent years. However,
widespread adoption of this technology has been hampered by high cost
and reliability concerns. In this paper an economical phase imbalanced shunt
reactive compensation concept has been introduced and its ability for power
system dynamic enhancement and inter-area oscillation damping are
investigated. A hybrid phase imbalanced scheme is a shunt capacitive
compensation scheme, where two phases are compensated by fixed shunt
capacitor (C) and the third phase is compensated by a Static Synchronous
Compensator (STATCOM) in shunt with a fixed capacitor (CC). The power
system dynamic stability enhancement would be achieved by adding
a conventional Wide Area Damping Controller (WADC) to the main control
loop of the single phase STATCOM. Two different control methodologies
are proposed: a non-optimized conventional damping controller
and a conventional damping controller with optomised parameters that are
added to the main control loop of the unbalanced compensator in order to
damp the inter area oscillations. The proposed arrangement would, certainly,
be economically attractive when compared with a full three-phase
STATCOM. The proposed scheme is prosperously applied in a 13-bus
six-machine test system and various case studies are conducted to
demonstrate its ability in damping inter-area oscillations and power system
dynamic enhancement.
Keyword:
Compensator (STATCOM)
Inter-area oscillations
Power system stability
Shunt compensation
Static synchronous
Copyright © 2016 Institute of Advanced Engineering and Science.
All rights reserved.
Corresponding Author:
Ahad Mokhtarpour,
Department of Electrical and Electronic Engineering, Tabriz Branch,
Islamic Azad University Tabriz, University Road, Tabriz Township, East Azarbayjan Country, Iran.
Email:a.mokhtarpour@iaut.ac.ir
1. INTRODUCTION
Low frequency inter-area oscillations have been observed when large power systems are
interconnected by relatively weak tie lines. These oscillations may sustain and grow to cause system
separation if no sufficient damping is available [1]-[2]. Traditional power system stabilizers (PSSs) have
been widely studied to solve the problem [3]. However, PSSs suffers a trouble of being liable to cause
considerable variations in the voltage profile and they may even result in leading power factor operation and
losing system stability under severe disturbances, especially those three phase faults which may happen at the
generator terminals. In recent years, the fast progress in the field of power electronics had opened new
opportunities for the application of the Flexible AC Transmission Systems (FACTS) devices as one of the
most effective ways to improve power system operation controllability and power transfer limits [4]-[5].
Through the modulation of bus voltage, phase shift between buses, and transmission line reactance, FACTS
devices can cause a substantial increase in power transfer limits during steady-state. Because of the extremely
fast control action associated with FACTS device operations, they have been very promising candidates for
utilization in power system damping enhancement. It is well known that utilizing a feedback auxiliary
IJPEDS ISSN: 2088-8694 
Inter-Area Oscillation Damping using an STATCOM Based Hybrid Shunt … (Vahid Farzam)
1173
control, in addition to the FACTS device main control, can greatly improve system damping [6]-[8] and can
also improve system voltage profile, which is advantageous over PSSs. Besides many merits which are
provided with FACTS devices, they are suffering from high initial costs, device complexity and low
reliability of these devices which means if a single point of failure occurs in a system, the system will be
entirely shut down. These barriers have convinced the researchers to search out for a solution and, in the
literature some new structures and systems have been introduced [9]-[15]. In [9]-[12] the Distributed FACTS
(D-FACTS) technology has been introduced. This newly born technology points a way to a novel approach
for achieving the power flow control, voltage stability, system oscillation damping and whole system
reliability.
The distributed nature of the suggested system makes it possible to achieve fine granularity in the
system rating. Moreover, it is possible to expand the system with the growing demand. This gives a salient
benefit in planning the system, which allows the planner to have control on available transfer capacity
(ATC). It is done in a way that the growing needs in power transfer (equal to 2% for every year) are satisfied
by installing new D-FACTS modules in the line for 10 years; this is done in order to meet project growth
needs without having to invest all the capital at the start of the project implementation or in [13]-[15] two
economical phase imbalanced series compensation concept has been introduced and their ability for power
system dynamic enhancement and inter-area oscillation damping have been investigated where the series
capacitive compensation in one phase is created using a single-phase TCSC (Scheme I) or a single-phase
SSSC (Scheme II) in series with a fixed capacitor, and the other two phases are compensated by fixed series
capacitors. The TCSC and SSSC controls are initially set such that their equivalent compensations at the
power frequency combined with the fixed capacitor yield a resultant compensation equal to the other two
phases. These two schemes would, definitely, be economically attractive when compared with a full
three-phase TCSC or SSSC, which have been used/proposed for power oscillations damping. Furthermore,
reducing the number of thyristor valves and VSC to one third will also have a positive impact on equipment
reliability.
The main contribution of this paper is introducing an economical phase imbalanced shunt capacitive
compensation concept and investigating its ability for power system dynamic enhancement
and inter-area oscillation damping. A shunt hybrid phase imbalanced scheme is a shunt capacitive
compensation scheme, where two phases are compensated by fixed shunt capacitor (C) and the third phase is
compensated by a single phase Static Synchronous Compensator (STATCOM) in shunt with a fixed
capacitor (CC). Certainly the proposed arrangement would, certainly, be economically attractive when
compared with a full three-phase STATCOM. The power system dynamic stability enhancement would be
achieved by adding an auxiliary damping controller to the main control loop of the single phase STATCOM.
In designing damping controller, the feedback signals could either comprise wide-area information through
utilization of PMUs dispersed over the network or be limited to merely local data captured at the line’s
sending end. Since this paper concentrates on the inter-area phenomenon on which is inherently a global
issue, wide area signals are used for the damping controller input signal [16]-[17]. To optimize the
parameters of the designed Wide Area Damping Controller (WADC) the Particle Swarm Optimization (PSO)
method is utilized. The PSO is a population based stochastic optimization algorithm, prompted by social
behavior of bird flocking or fish schooling [18]-[19]. In order to assess the capability of the PSO based
damping controller in oscillations suppression, a nonoptimized conventional damping controller is also
designed and enhanced to the main control loopof the unbalanced STATCOM to suppress the
oscillations.Finally the proposed approach is prosperously applied in a 16-bus six-machine test system
and various case studies are conducted to demonstrate the potential of the proposed approach.
2. PHASE IMBALANCED SHUNT COMPENSATION SCHEME
The STATCOM is a well-known shunt connected FACTS controller based on voltage source
converter (VSC). As illustrated in Figure 1, a typical STATCOM is realized with a three-phase VSC, a dc
link capacitor and an interfacing transformer. Also a filtering stage (not shown) is considered at the output of
the VSC for alleviating the harmonic pollution in the injected voltage [4].
The STATCOM is capable of generating or absorbing reactive power. By varying the amplitude of
the produced output voltages, the reactive power exchange between the converter and the ac system can be
controlled; hence, it gives the opportunity to control some specific parameters (e.g. voltage) of an electric
power system. To address in more details, the STATCOM main task is to control the voltage dynamically.
However, it is commonly expected to yield some ancillary duties such as power oscillation damping,
transient stability enhancement, voltage flicker control and so forth. Figure 1 also displays the main control
system of the single phase STATCOM considered here. From this figure it can be seen that the control
system requires three input signals including ac system bus voltage, V, converter output current oi and the
 ISSN: 2088-8694
IJPEDS Vol. 7, No. 4, December 2016 : 1172 – 1180
1174
bus reference voltage RefV . As illustrated, voltage Voperates a phase-locked loop (PLL) which determines
the basic synchronizing signal, angle . The reactive component of the output current oQI is extracted
and compared to the produced reactive current reference, QRefI . Ultimately the obtained error signal is
utilized to provide angle , which determines the necessary phase shift between the output voltages of the
converter and the ac system voltage. In the sequel when  is calculated, the dc link capacitor is charged or
discharged to the dc voltage level required [4].
A phase imbalanced STATCOM is a shunt compensation scheme, where two phases are
compensated by fixed shunt capacitor (C) and the third phase is compensated by a single phase STATCOM
paralleled with a fixed capacitor ( CC ) as shown on Figure 2. The phase imbalance of proposed Scheme can
be explained mathematically as follows. At the power frequency, the reactive power for phases a, b and c are
given by:
cba QQQ  (1)
STATCOMCcc QQQ  (2)
During any other frequency, Fe
STATCOMSTATCOMCcc QQQQ  (3)
The first terms in (2) and (3) are different because of the difference in frequency. The third term
in (3) represents the change in effective reactive power of the single phase STATCOM due to the action of
the STATCOM supplementary damping controller that has been added to yhe main control loop of
STATCOM to inter area oscillation mitigation. As said on section 1 this scheme would, definitely, be
economically attractive when compared with a full three-phase STATCOM. This paper introduces this
economical scheme and evaluates the effectiveness of the scheme in damping oscillations. Time domain
simulations were conducted on a benchmark network using the Matlab.
Figure 1. STATCOM Control system
CCQ
aQ
CCCC
bQ CQ
STATCOMQ
STATCOM
Figure 2. Schematic Diagrams of the Hybrid Shunt Compensation Schemes
C
activeRe
current
computer
PLL
oi
oQI
Error
Amplifier
 
oV
Gate
iclog
pattern
Auxiliary
Signal
V
STATCOM
V
dcV
oi
fReQI
fReV
V
oV
Error
Amplifier
Damping
fRe
*
V
IJPEDS ISSN: 2088-8694 
Inter-Area Oscillation Damping using an STATCOM Based Hybrid Shunt … (Vahid Farzam)
1175
3. STUDY SYSTEM
The power system adopted for this study is illustrated in Figure 4 [13]-[14] and [17]. It has
originally 15 buses and six machines in three areas. Although this is a test system, it well serves to illustrate
the concept, which remains the same for large systems. To keep the voltage profile of the system constant,
shunt capacitors are installed at buses 7, 9, and 15. For the nonlinear time domain simulation, generators are
modeled in the d-q-o reference frame and transmission lines are represented in the π model. It is worth
mentioning that the dynamics of generator excitation is also considered in the simulation. The comprehensive
data of the power system are given in the Appendix A. For applying the phase imbalanced shunt compensator
in the system, a single phase STATCOM is installed instead of one phase of shunt capacitor that installed on
bus 7 and the STATCOM contribution in the hybrid compensated phase is 0.5 p.u. of the total reactive
compensation. However, the optimal location of reactive power compensator in practical and large power
systems is vital point and requires comprehensive studies [21].
The power system under study has five distinct oscillatory modes: three local modes and two
inter-area modes which have been obtained by the Eigen value analysis. The inter-area mode 1 is
characterized by having a slightly higher frequency (0.78 Hz) than mode 2 (0.46 Hz). Mode 1 consists of
generators of area 1 swinging against those of area 3. While, mode 2 consists of generators of area 2
oscillating against those of areas 1 and 3 [14]. As a result, in order to mitigate the unstable oscillation modes,
a PSO-based is designed and added to the main control loop of the unbalanced STATCOM.
Figure 4. Three-Area Six-Machine Power System Aggregated with an Unbalanced STATCOM
4. POWER OSCILLATIONS DAMPING CONTROLLER DESIGN
As explained in Section III, the system under study has five distinct modes. These oscillatory modes
are to be damped by an auxiliary damping controller that is added to the main control loop of the unbalanced
STATCOM. Among crucial requirements of implementing auxiliary damping controllers is figuring out its
best location. This task should be done with two major objectives: (i) providing an effective damping of
oscillations and (ii) minimizing the possible interactions between STATCOM reactive power and damping
controllers.
One of the fundamental issues in designing the damping controller is the selection of feedback
signals to achieve the best modal observability and optimal oscillation damping [22]. Any kind of input
signal with sufficient modal observability of inter-area oscillation can be used; amongst are the active power
of tie lines, voltage angle differences between areas, rotor angular speed differences between generators, etc.
Generally, the damping controller input signals can be classified in twofold groups: local signals and wide-
area ones. As a result, two sorts of solutions exist for designing damping controllers: the decentralized
approach based on local signals and the centralized approach exploiting wide-area information. The main
advantage of the former solution comes from the fact that no telecommunication infrastructure is needed. The
expense of this method is that it will suffice to economically and efficiently satisfy the damping requirements
of the present/future heavily stressed networks with credible inter-area oscillation modes. In contrast, the
centralized technique offers more effective outcomes at the expense of having fast communication
infrastructure. Clearly, in a practical environment, selection of either centralized or decentralized solution
depends on a given power system characteristics and its communication facilities. With respect to Figure 4
the power system under study equipped with PMUs, wide area signals used as damping controller input
 ISSN: 2088-8694
IJPEDS Vol. 7, No. 4, December 2016 : 1172 – 1180
1176
signal. Opposite to the conventional measurement devices, PMUs are synchronized respect to each other
through the one pulse per second signals of the global positioning system. This new opportunity realized the
true concept of measuring phase angles which inherently encompass valuable information of the system
stress situation. The huge infrastructure which is in charge for gathering the PMUs’ data in a central
location(s) is referred to as WAMS. Autonomous control including oscillation damping is among advanced
functionalities imagined for WAMS. Clearly, the WAMS potential in feeding WADCs is directly dependent
to the number and location of PMUs deployed in the grid. The PMU placement problem is a broadly
investigated research area and various aspects of this problem have been so far digested in dept [23]-[25].
Intuitively, it can be deduced that for oscillation damping objective a limited number, but geographically
distributed, of PMUs would work sufficiently. The numerical studies presented in the following support this
conclusion.
One of the main advantages of WADCs is its capability in designing multi-band damping
controllers. Each band of the WADC has its own global input signal for damping one of the oscillation
modes. As the system under study has two inter-area modes, a simple two-band classic controller is
considered which is represented in Figure 5. Each controller is a conventional damping controller that is
shown in Figure 6. Band controllers are denoted by WADC1 and WADC2 and the whole unit is recognized
by WADC.
+
WADC1
3113  
WADC2
5115  
++
1W
2W
1SignalDamping
2SignalDamping SignalDamping
Figure 5. The Two-Band WADC Designed for the Three-Area Power System
sT1
sT
w
w
 sT
sT
4
3
1
1


K
max
min
SignalInput 1SignalDamping
sT1
sT1
2
1


Figure 6. The Block Diagram of the Classical Damping Controller
It is apparent that to damp out multi-mode oscillations, two suitable supplementary signals
containing both modes of oscillations are necessary. Any kind of input signal that has a good modal
observability of inter-area oscillation can be used such as the power of tie line interconnecting two areas,
frequency difference between two areas, angle difference of two buses in two areas, etc.
Generally, the PMU firstly receives the sinusoidal waveforms of three-phase voltages and currents,
then converts the sampled digital data to the phasor values, and finally sends the information to the regional
or system control center [26]. Although the PMU computed frequency and its rate of change are based on
local voltage measurements, there are several approaches to calculate the generator speed through local PMU
measurement [27]-[29]. Frequency is a key indicator for the system stability and generation/demand balance.
This parameter or its derivatives such as rotor speeds and their rates of change are usually implemented as the
damping controller feedback signal [11]-[12] and [17]. To this end, high voltage buses associated with G1,
G3 and G5 are assumed to be equipped with PMUs and 3113 -  and 5115 -  are chosen
as global feedback signals. For damping the inter-area mode 1 (0.78 Hz), WADC1 is used whose input is
15 and WADC2 is responsible for damping the oscillation mode 2 (0.46 Hz) with input of 13 . As shown
in Figure 5, the output of WADCs are weighted and summed up to generate the WADC output, which is
)2(*)1(* 21 SignalDampingWSignalDampingWSignalDamping  (4)
IJPEDS ISSN: 2088-8694 
Inter-Area Oscillation Damping using an STATCOM Based Hybrid Shunt … (Vahid Farzam)
1177
W1 and W2 are weighting factors and are chosen inversely proportional to the normalized damping
ratio of their dominant mode obtained from the Prony analysis (W1=1.15, W2=1) [14]. The WADC output is
finally employed for modulating the reactive power loop of the STATCOM (see Figure 1).
It has to be noted that the communication system is thus far assumed to be delay free in the design
process which is not the case in real world observations and the communication latency should be considered
in design procedure. The authors intend to work on this issue in future while many good pioneer research is
available presently [18] and the controller designed in this paper is an ideal WADC without considering
latency in wide area signals. The proposed WADC is implemented in the simulation setup and its parameters
are tuned through the PSO technique. İn the following a quiet explanation about optimisation of WADC
parameters has been presented.
4.1. PSO Algorithm
In the PSO technique, there are some simple entities (particle) which their trajectory in the search
space can be adjusted by dynamically regulating the velocity of each particle. Generally, a predefined
objective function will be defined by the user, and then the best value of the objective function that is
achieved by the ith
particle is expressed as Pbest. Furthermore, the overall best value of the objective function
obtained by the particles at every time step (gbest) is calculated through the algorithm. Then, each particle’s
velocity and position is being updated by [18]-[19]:
))(())(()()1( 2211 tXPrctXPrctwVtV idgdidididid  (5)
)()1()( tcVtXtX ididid 
(6)
Where, Vid is the velocity of the ith
particle, Xidis the position of the ith
particle, Pidand Pgd are Pbest
and gbest, respectively. c1 andc2 are positive constants which are responsible for alternation of the particle
velocity toward Pbest and gbest, r1 and r2are two random constants between 0 and 1 and c is a factor which
can modify the velocity of the particle to adjust the position of each particle in the next iteration. w, inertia
weight, is defined to balance the local and global searches. Hence, the PSO algorithm searches for the
optimal minimum value of the objective function and updates the velocity and particle’s location in each
iteration. The iterative process will be terminated when the stopping criterion is met.
If the parameters of damping controller are properly optimized, the damping of oscillation will be
resulted effectively. For this reason, damping controller parameters will be optimized by the PSO algorithm.
In this study, the objective function to be minimized by PSO is come from the generators rotor speed
deviations. This objective function is an integral of time multiplied by the absolute value of the power
deviation, that is
dtWtJ
simt
13..
0
  (7)
Where, simt is the total simulation time and 13W is the generators rotor speed deviations. The
optimization is subjected to parameter limits, i.e.
maxmin KKK  , max11min1 TTT  , max22min2 TTT  , max33min3 TTT  , max44min4 TTT 
It has to be pointed out that the above parameters are associated with the damping controller
and would be introduced in the next section. Here, the ranges for parameters are as follows. K [0.01-40]
and T1, T2, T3, T4[0.0001-2]. Associated with PSO algorithm, the number of particles, number of iterations,
c1, c2, c, and w are set to 50, 200, 2, 2, 1, and 0.85, respectively and the final values of parameters are
presented in Appendix B.
5. SIMULATION RESULTS
This section demonstrates the capability of the proposed STATCOM based hybrid shunt
compensation scheme in damping inter-area oscillations. As seen on Figure 4, for this propose fixed
capacitor of one phase installed on bus 7 is replaced with an unbalanced. The parameters of the unbalanced
STATCOM are shown in appendix C. For the sake of simulation, it is assumed that in the system shown in
Figure 4, a three-phase to ground fault occurs on bus 8 and lasts for 200 ms. this fault stimulates oscillation
 ISSN: 2088-8694
IJPEDS Vol. 7, No. 4, December 2016 : 1172 – 1180
1178
of the system. Figures 7 and 8 show the rotor speed difference between G1 and G3 and the rotor speed
difference between G1 and G2 as well as their damping behavior in three situations of fixed shunt
compensator and Hybrid shunt compensation with optimized and non-optimised damping controllers. The
inter-area oscillation is measured by rotor speed difference of G1 and G3 and the local oscillation is
measured by rotor speed difference of G1 and G2. As shown in Figures 7 and 8, in the case fix shunt
compensation, the system experiences severe fluctuations with very low damping. However, in the case of
hybrid shunt compensation that in one phase a STATCOMis placed instead of a fixed shunt capacitor, both
supplementary controllers of unbalanced compensation system leads to damping of oscillations but an
effective damping of oscillations after the event of fault is achieved when PSO based damping controlleris
added to main controllers of unbalanced STATCOM. Moreover, in the figure legends, “Fixed” refers to the
system performance with fixed capacitor compensation.
Figures 9 show the tie-line (7–9, line 1) power flow time responses of the test benchmark during
and after disturbance. Comparing the responses of the fixed shunt compensation to the hybrid shunt
compensation scheme in this Figure, the favorable contribution of the proposed hybrid scheme to the
mitigation of the inter-area oscillations is very understandable. As it can be seen from Figures 7 and 9, the
power oscillations damping controller decrease the first swing and effectively damps the subsequent
oscillations.
In Figure 10, the bus voltage, and damping controller output signal of the STATCOM are plotted.
As observed from these figures, unlike the fixed shunt compensation, the hybrid scheme effectively preserves
the system stability after disturbance and damps both inter-area and local oscillations. The results of
simulation obviously show that, in the case of PSO based WADC, the performances of damping controller is
by far better than the case that WADC parameters is achieved by trial and error method. This is because the
parameters of PSO based WADC tuned with an optimization method.
Figure 7. Rotor Speed Difference between G1
and G3, during and After Disturbance
Figure 8. Rotor Speed Difference between G1
and G2, during and After Disturbance
Figure 9. Tie-line power flow time responses during
and after disturbance
(a)
(b)
Figure 10. Performance of Unbalanced STATCOM
during and After Disturbance: (a) STATCOM bus
Voltage and (b) STATCOM Damping Controller
Output Signal
0 5 10 15
-2
0
2
x 10
-3
time (s)
W1-W2(p.u)
Without Damping Controller
With non-optomised Damping Controller
With PSO Based Damping Controller
0 5 10 15
0.9
1
1.1
time (s)
Vstatcom(p.u)
0 5 10 15
-0.2
0
0.2
time (s)
DampingSignal(p.u)
IJPEDS ISSN: 2088-8694 
Inter-Area Oscillation Damping using an STATCOM Based Hybrid Shunt … (Vahid Farzam)
1179
6. CONCLOSION
This work is mainly dedicated to investigate the capability of a new “hybrid” shunt compensation
schemes in damping inter-area oscillations. The presented hybrid shunt compensation schemes is easily
achievable, technically sound, and have an industrial application potential. A six-machine three area power
system is put under investigation in order to verify the proposed scheme capability on inter-area oscillation
damping. The power system dynamic stability enhancement achieved by adding two wide area, damping
controllers. A non-optimized conventional damping controller and a conventional damping controller with optomised
parameters. The PSO algorithm is used to solve optimization problem. Both damping controllers are added to
the main control loop of the proposed shunt compensator. With respect simulation illustrations, it was
observed that as the time goes on, the proposed hybrid compensation equipped with auxiliary damping
controller would damp all inter-area and locally oscillation modes; also the results of simulation showed that,
in the case of PSO based WADC, the performances of damping controller was by far better than the case that
WADC parameters were achieved by trial and error method.Hence, the effective performance of proposed
unbalanced shunt compensation in the system oscillation damping was validated.
Appendix A Power System Data
Generator Data: 900 MVA, 20 kV, ra = 0.0025 p.u., xl= 0.2 p.u., xd = 1.8 p.u., xq = 1.7 p.u., x‫׳‬d = 0.3
p.u., x‫׳‬q = 0.55 p.u., x‫״‬d = -0.25 p.u., x‫״‬q = 0.25 p.u., T‫׳‬
do = 8 s, T‫״‬do = 0.03 s, T‫׳‬qo = 0.4 s, T‫״‬qo = 0.05 s,
H(G1&G2) = 6.5 s, H(G3&G4) = 6.175 s, H (G5) = 5.5 s, H(G6) = 5 s.
Generator Steady State Data: G1: V = 1.04 ∟0o
p.u., G2: P = 700 MW, V = 1.01 p.u., G5: P = 800
MW, V = 1.02 p.u., G6: P = 780 MW, V = 1.01 p.u. Transmission Line Data: r = 0.053 Ω/km, Xseries = 0.53
Ω/km, Yshunt = 5.21 μS/km. Bus 7 load: 1400 + j100-j350, Bus 9 load: 1800 + j100 – j500, Bus 15 load:
1200 + j300 – j220.
Appendix B
Table 1. Parameters of the STATCOM based WADCs
Type K TW T1 T2 T3 T4 min & max
WADC1 9 2 0.012 0.89 1.11 0.011 ±0.2
WADC2 16 2 0.032 1.3 0.014 0.044 ±0.2
Appendix C STATCOM Data
Rated Power = 25 MVA, Rated Voltage = 26 KV, Frequency = 60 Hz, XT(sh) = 0.1 p.u. Switching
Frequency = 15KHz.
REFERENCES
[1] Yu YN. Electric power system dynamics. New York: Academic Press; 1983.
[2] Sauer PW, Pai MA. Power system dynamics and stability. Englewood Cliffs, NJ: Prentice-Hall; 1998.
[3] X. Yang and A. Feliachi, “Stabilization of inter-area oscillation modes through excitation systems”, IEEE Trans.
Power Syst., vol. 9, no. 1, pp.494–502, Feb. 1994.
[4] R.M. Mathur and R.K.Varma, Thyristor-Based FACTS Controllers for Electrical Transmission Systems. New York:
IEEE Press and Wiley.Interscience, Feb. 2002.
[5] N.G. Hingorani, Flexible AC transmission, IEEE Spectrum (1993) 40 45.
[6] E.V. Larson, J.J. Sanchez Gasca, J.H. Chow, “Concepts for design of FACTS controllers to damp power swings”,
IEEE Trans. Power Syst., vol. 10, no. 2, pp948-956, May. 1995.
[7] R. Kunamneni, S. Suman, M. Rambabu, K. Ashok Kumar, "Implementation of phase imbalance scheme for
stabilizing torsional oscillations", International Journal of Electrical and Computer Engineering (IJECE), vol. 4,
no. 5, pp. 697–702, October 2014.
[8] M. Farsadi, A. Ghasemi, B. Ghasemi, " WAMS-Based SSR Damping controller design for FACTS devices and
investigating effects of communication delays", International Journal of Power Electronics and Drive System
(IJPEDS), vol. 6, no. 4, pp. 736–746, December 2015.
[9] D. Divan et al, “A distributed static series compensator system for realizing active power flow control on existing
power lines”, IEEE Trans. Power Delivery, vol. 22, no. 1, pp. 642-649, Jan 2007.
[10] Z. Yuan, S.W.H. de Haan, J.B. Ferreira, and D. Cvoric, “A FACTS Device: Distributed Power-Flow Controller
(DPFC)”, IEEE Trans. Power Electron, vol. 25, no. 10, Oct 2010.
[11] J. Khazaie, M. Mokhtari, M. Khalilian, D. Nazarpour, “Sub-Synchronous Resonance Damping Using Distributed
Static Series Compensator Enhanced with Fuzzy Logic Controller”, Inter Jour of Elect Power and Ener Systems,
vol. 43, no. 1, pp. 80-89, Dec 2012.
 ISSN: 2088-8694
IJPEDS Vol. 7, No. 4, December 2016 : 1172 – 1180
1180
[12] M. Khalilian, M. Mokhtari, S. Golshannavaz, D. Nazarpour, “Distributed Static Series Compensator (DSSC) for
Subsynchronous Resonance Alleviation and Power Oscillation Damping”, Euro. Trans. Electr. Power, vol. 22, no.
5, pp. 589-600, July 2012.
[13] D. Rai, G. Ramakrishna, S.O. Faried, and A. Edris, “Enhancement of power system dynamics using a phase
imbalanced series compensation scheme”, IEEE Trans. Power Syst., vol. 25, no. 2, pp. 966–974, May 2010.
[14] D. Rai, G. Ramakrishna, S.O. Faried, G. Ramakrishna, and A. Edris, “Damping Inter-Area Oscillations Using
Phase Imbalanced Series Compensation Schemes”, IEEE Trans. Power Syst., vol. 26, no. 3, pp. 1756-1761, Aug
2011.
[15] D. Rai, S. O. Faried, G. Ramakrishna, and A. Edris, “Hybrid series compensation scheme capable of damping
subsynchronous resonance”, Proc. Inst. Eng. Technol. Gen., Transm. Distrib, vol. 4, no. 3, pp. 456–466, March
2010.
[16] X. Xie, J. Xiao, C. Lu, and Y. Han, “Wide-area stability control for damping interarea oscillations of
interconnected power systems”, IET Gen. Transm. Distrib., vol. 153, pp. 507–514, Sep. 2006.
[17] M. Mokhtari, F. Aminifar, D. Nazarpour, and S. Golshannavaz, “Widearea power oscillation damping with a Fuzzy
controller compensating the continuous communication delays”, IEEE Trans. Power Syst., vol. 28, no. 2, pp. 1997–
2005, May 2013.
[18] Ho SL, Yang S, Ni G, Lo EWC, Wong HC. A particle swarm optimization basedbmethod for multi objective
design optimizations. IEEE Trans Magnet, 2005; 41(5): 1756–9.
[19] Shayeghi H, Shayanfar HA, Jalilzadeh S, Safari A. Design of output feedback UPFC controllers for damping of
electromechanical oscillations using PSO. Energy Convers Manage, 2009; 50: 2559–61.
[20] T.J.E Miller, Reactive Power Control in Electric System: [M]. New York, Wiley, 1982.
[21] R. Minguez, F. Milano, R. Zarate-Miano, A.J. Conejo, “Optimal Network Placement of SVC Devices”, IEEE
Trans. Power Syst., vol. 22, no. 4, pp. 1851–1860, Nov 2007.
[22] Farsangi MM, Sung YH, Lee KY. Choice of FACTS Device Control Inputs for Damping Inter-area Oscillations.
IEEE Transactions on Power Systems, 2004; 19(2): 1806–1812.
[23] F. Aminifar, M. Fotuhi-Firuzabad, M. Shahidehpour, and A. Khodaei, “Observability enhancement by optimal
PMU placement considering random power system outages”, Energy Syst., vol. 2, pp. 45–65, Mar. 2011.
[24] F. Aminifar, M. Fotuhi-Firuzabad, A. Safdarian, and M. Shahidehpour, “Observability of hybrid AC/DC power
systems with variablecost PMUs”, IEEE Trans. Power Del., to be published.
[25] F. Aminifar, M. Fotuhi-Firuzabad, and A. Safdarian, “Optimal PMU placement based on probabilistic cost/benefit
analysis”, IEEE Trans.Power Syst., vol. 28, no. 1, pp. 566–567, Feb. 2013.
[26] I. Kamwa and R. Grondin, “PMU configuration for system dynamic performance measurement in large, multi-area
power systems”, IEEETrans. Power Syst., vol. 17, no. 2, pp. 385–394, May 2002.
[27] A. G. Phadke, “Synchronized phasormeasurements in power systems”, IEEE Comput. Appl. Power, vol. 6, pp. 10–
15, Apr. 1993.
[28] K. Mei, S.M. Rovnyak, and C.M. Ong, “Clustering-based dynamic event location using wide-area phasor
measurements”, IEEE Trans.Power Syst., vol. 23, no. 2, pp. 673–679, May 2008.
[29] P. Tripathy, S.C. Srivastava, and S.N. Singh, “A divide-by-differencefilter based algorithm for estimation of
generator rotor angle utilizing synchrophasor measurements”, IEEE Trans. Instrum. Meas., vol. 59, pp. 1562–1570,
Jun. 2010.
BIOGRAPHIES OF AUTHORS
Vahid Farzam was born in Tabriz, Iran, September 1992. He received the B.Sc. and the M.Sc.
degrees in electrical engineering from the Islamic Azad University of Tabriz, Tabriz, Iran, in
2013 and 2016, respectively. His research interests arein advanced power electronic, flexible AC
transmission system (FACTS), power quality, renewable energy, wide area measurement system,
and power system dynamics.
Ahad Mokhtarpour was born in Tabriz, Iran, 1979. He received the B.S. degree from University
of Tabriz, Tabriz, Iran, M.S.E. degree from Iran University of Science and Technology, Tehran,
Iran and Ph.D degree from Islamic Azad University, Science and Research Branch, Tehran, Iran
all in Electrical Engineering in 2003, 2005 and 2013, respectively. Currently he is with
Departement of Electrical and Computer Engineering,Tabriz Branch, Islamic Azad University
Tabriz, Iran as an Assistant Professor. His research interests are in the power quality
compensation, FACTS device, distribution network control and reliability.

More Related Content

What's hot

C121738
C121738C121738
C121738irjes
 
International Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentInternational Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentIJERD Editor
 
WAMS-Based SSR Damping Controller Design for FACTS Devices and Investigating ...
WAMS-Based SSR Damping Controller Design for FACTS Devices and Investigating ...WAMS-Based SSR Damping Controller Design for FACTS Devices and Investigating ...
WAMS-Based SSR Damping Controller Design for FACTS Devices and Investigating ...IJPEDS-IAES
 
Optimal placement of dstatcom in an indian power system for load and
Optimal placement of dstatcom in an indian power system for load andOptimal placement of dstatcom in an indian power system for load and
Optimal placement of dstatcom in an indian power system for load andIAEME Publication
 
IRJET-Identification of Weak Bus using Load Variation
IRJET-Identification of Weak Bus using Load VariationIRJET-Identification of Weak Bus using Load Variation
IRJET-Identification of Weak Bus using Load VariationIRJET Journal
 
Voltage Stabilization of a Wind Turbine with STATCOM Using Intelligent Contro...
Voltage Stabilization of a Wind Turbine with STATCOM Using Intelligent Contro...Voltage Stabilization of a Wind Turbine with STATCOM Using Intelligent Contro...
Voltage Stabilization of a Wind Turbine with STATCOM Using Intelligent Contro...ijeei-iaes
 
A Matlab/Simulink Model for the control scheme utilized to improve power qual...
A Matlab/Simulink Model for the control scheme utilized to improve power qual...A Matlab/Simulink Model for the control scheme utilized to improve power qual...
A Matlab/Simulink Model for the control scheme utilized to improve power qual...AM Publications
 
Wind-Turbine Asynchronous Generator Synchronous Condenser with Excitation in ...
Wind-Turbine Asynchronous Generator Synchronous Condenser with Excitation in ...Wind-Turbine Asynchronous Generator Synchronous Condenser with Excitation in ...
Wind-Turbine Asynchronous Generator Synchronous Condenser with Excitation in ...IJMTST Journal
 
Aircraft Electrical Power Generation & Distribution System Units Through an A...
Aircraft Electrical Power Generation & Distribution System Units Through an A...Aircraft Electrical Power Generation & Distribution System Units Through an A...
Aircraft Electrical Power Generation & Distribution System Units Through an A...IJMTST Journal
 
Optimal Placement of DG for Loss Reduction and Voltage Sag Mitigation in Radi...
Optimal Placement of DG for Loss Reduction and Voltage Sag Mitigation in Radi...Optimal Placement of DG for Loss Reduction and Voltage Sag Mitigation in Radi...
Optimal Placement of DG for Loss Reduction and Voltage Sag Mitigation in Radi...IDES Editor
 
Optimal Placement of FACTS Controller
Optimal Placement of FACTS ControllerOptimal Placement of FACTS Controller
Optimal Placement of FACTS ControllerDivyang soni
 
Modeling of BESS for Blackstart System Restoration Studies
Modeling of BESS for Blackstart System Restoration StudiesModeling of BESS for Blackstart System Restoration Studies
Modeling of BESS for Blackstart System Restoration StudiesPower System Operation
 
Power Quality Improvement in Power System using UPFC
Power Quality Improvement in Power System using UPFCPower Quality Improvement in Power System using UPFC
Power Quality Improvement in Power System using UPFCijtsrd
 
Improvement of Power Quality in PMSG Based Wind Integrated System using FACTS...
Improvement of Power Quality in PMSG Based Wind Integrated System using FACTS...Improvement of Power Quality in PMSG Based Wind Integrated System using FACTS...
Improvement of Power Quality in PMSG Based Wind Integrated System using FACTS...IRJET Journal
 

What's hot (20)

Selection the optimum place of FACTS devices using fuzzy control system
Selection the optimum place of FACTS devices using fuzzy control systemSelection the optimum place of FACTS devices using fuzzy control system
Selection the optimum place of FACTS devices using fuzzy control system
 
C1081826
C1081826C1081826
C1081826
 
C121738
C121738C121738
C121738
 
International Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentInternational Journal of Engineering Research and Development
International Journal of Engineering Research and Development
 
[IJET V2I5P4] Authors: Rachana Chavan, Rakesh Singh Lodhi
[IJET V2I5P4] Authors: Rachana Chavan, Rakesh Singh Lodhi[IJET V2I5P4] Authors: Rachana Chavan, Rakesh Singh Lodhi
[IJET V2I5P4] Authors: Rachana Chavan, Rakesh Singh Lodhi
 
WAMS-Based SSR Damping Controller Design for FACTS Devices and Investigating ...
WAMS-Based SSR Damping Controller Design for FACTS Devices and Investigating ...WAMS-Based SSR Damping Controller Design for FACTS Devices and Investigating ...
WAMS-Based SSR Damping Controller Design for FACTS Devices and Investigating ...
 
Optimal placement of dstatcom in an indian power system for load and
Optimal placement of dstatcom in an indian power system for load andOptimal placement of dstatcom in an indian power system for load and
Optimal placement of dstatcom in an indian power system for load and
 
IRJET-Identification of Weak Bus using Load Variation
IRJET-Identification of Weak Bus using Load VariationIRJET-Identification of Weak Bus using Load Variation
IRJET-Identification of Weak Bus using Load Variation
 
Voltage Stabilization of a Wind Turbine with STATCOM Using Intelligent Contro...
Voltage Stabilization of a Wind Turbine with STATCOM Using Intelligent Contro...Voltage Stabilization of a Wind Turbine with STATCOM Using Intelligent Contro...
Voltage Stabilization of a Wind Turbine with STATCOM Using Intelligent Contro...
 
Gy3512171221
Gy3512171221Gy3512171221
Gy3512171221
 
A Matlab/Simulink Model for the control scheme utilized to improve power qual...
A Matlab/Simulink Model for the control scheme utilized to improve power qual...A Matlab/Simulink Model for the control scheme utilized to improve power qual...
A Matlab/Simulink Model for the control scheme utilized to improve power qual...
 
Wind-Turbine Asynchronous Generator Synchronous Condenser with Excitation in ...
Wind-Turbine Asynchronous Generator Synchronous Condenser with Excitation in ...Wind-Turbine Asynchronous Generator Synchronous Condenser with Excitation in ...
Wind-Turbine Asynchronous Generator Synchronous Condenser with Excitation in ...
 
Aircraft Electrical Power Generation & Distribution System Units Through an A...
Aircraft Electrical Power Generation & Distribution System Units Through an A...Aircraft Electrical Power Generation & Distribution System Units Through an A...
Aircraft Electrical Power Generation & Distribution System Units Through an A...
 
Optimal Placement of DG for Loss Reduction and Voltage Sag Mitigation in Radi...
Optimal Placement of DG for Loss Reduction and Voltage Sag Mitigation in Radi...Optimal Placement of DG for Loss Reduction and Voltage Sag Mitigation in Radi...
Optimal Placement of DG for Loss Reduction and Voltage Sag Mitigation in Radi...
 
Optimal Placement of FACTS Controller
Optimal Placement of FACTS ControllerOptimal Placement of FACTS Controller
Optimal Placement of FACTS Controller
 
Modeling of BESS for Blackstart System Restoration Studies
Modeling of BESS for Blackstart System Restoration StudiesModeling of BESS for Blackstart System Restoration Studies
Modeling of BESS for Blackstart System Restoration Studies
 
Power Quality Improvement in Power System using UPFC
Power Quality Improvement in Power System using UPFCPower Quality Improvement in Power System using UPFC
Power Quality Improvement in Power System using UPFC
 
26 k. subramanian
26 k. subramanian26 k. subramanian
26 k. subramanian
 
Improvement of Power Quality in PMSG Based Wind Integrated System using FACTS...
Improvement of Power Quality in PMSG Based Wind Integrated System using FACTS...Improvement of Power Quality in PMSG Based Wind Integrated System using FACTS...
Improvement of Power Quality in PMSG Based Wind Integrated System using FACTS...
 
D1072535
D1072535D1072535
D1072535
 

Similar to Inter-Area Oscillation Damping using an STATCOM Based Hybrid Shunt Compensation Scheme

Ga based optimal facts controller for maximizing loadability with stability c...
Ga based optimal facts controller for maximizing loadability with stability c...Ga based optimal facts controller for maximizing loadability with stability c...
Ga based optimal facts controller for maximizing loadability with stability c...IAEME Publication
 
International Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentInternational Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentIJERD Editor
 
Impact of hybrid FACTS devices on the stability of the Kenyan power system
Impact of hybrid FACTS devices on the stability of the Kenyan power system Impact of hybrid FACTS devices on the stability of the Kenyan power system
Impact of hybrid FACTS devices on the stability of the Kenyan power system IJECEIAES
 
Application of Multilevel Voltage-Source-Converter in FACTS Devices for Power...
Application of Multilevel Voltage-Source-Converter in FACTS Devices for Power...Application of Multilevel Voltage-Source-Converter in FACTS Devices for Power...
Application of Multilevel Voltage-Source-Converter in FACTS Devices for Power...IJMER
 
Voltage profile Improvement Using Static Synchronous Compensator STATCOM
Voltage profile Improvement Using Static Synchronous Compensator STATCOMVoltage profile Improvement Using Static Synchronous Compensator STATCOM
Voltage profile Improvement Using Static Synchronous Compensator STATCOMINFOGAIN PUBLICATION
 
International Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentInternational Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentIJERD Editor
 
Enhancement of voltage stability using static synchronous series compensator
Enhancement of voltage stability using static synchronous series compensatorEnhancement of voltage stability using static synchronous series compensator
Enhancement of voltage stability using static synchronous series compensatorIAEME Publication
 
A Review on Optimization of Coordinated Control Plan for PSS and STATCOM Devi...
A Review on Optimization of Coordinated Control Plan for PSS and STATCOM Devi...A Review on Optimization of Coordinated Control Plan for PSS and STATCOM Devi...
A Review on Optimization of Coordinated Control Plan for PSS and STATCOM Devi...ijtsrd
 
Comparison of Shunt Facts Devices for the Improvement of Transient Stability ...
Comparison of Shunt Facts Devices for the Improvement of Transient Stability ...Comparison of Shunt Facts Devices for the Improvement of Transient Stability ...
Comparison of Shunt Facts Devices for the Improvement of Transient Stability ...IJSRD
 
Efficacy of Facts in Power Oscillation Damping and Renewable Integration
Efficacy of Facts in Power Oscillation Damping and Renewable IntegrationEfficacy of Facts in Power Oscillation Damping and Renewable Integration
Efficacy of Facts in Power Oscillation Damping and Renewable IntegrationIOSRJEEE
 
International Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentInternational Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentIJERD Editor
 
Improvement of Power System Oscillation by using Coordinated Control Plan for...
Improvement of Power System Oscillation by using Coordinated Control Plan for...Improvement of Power System Oscillation by using Coordinated Control Plan for...
Improvement of Power System Oscillation by using Coordinated Control Plan for...ijtsrd
 
Voltage Compensation in Wind Power System using STATCOM Controlled by Soft Co...
Voltage Compensation in Wind Power System using STATCOM Controlled by Soft Co...Voltage Compensation in Wind Power System using STATCOM Controlled by Soft Co...
Voltage Compensation in Wind Power System using STATCOM Controlled by Soft Co...IJECEIAES
 
F021201048053
F021201048053F021201048053
F021201048053theijes
 
USING SSSC & STATCOM --IMPROVE TRANSIENT STABILITY--P & Q OSICALLATIONS
USING SSSC & STATCOM --IMPROVE TRANSIENT STABILITY--P & Q OSICALLATIONSUSING SSSC & STATCOM --IMPROVE TRANSIENT STABILITY--P & Q OSICALLATIONS
USING SSSC & STATCOM --IMPROVE TRANSIENT STABILITY--P & Q OSICALLATIONSIJSRD
 
Location of Shunt FACTS Devices for First-Swing Stability Enhancement in Inte...
Location of Shunt FACTS Devices for First-Swing Stability Enhancement in Inte...Location of Shunt FACTS Devices for First-Swing Stability Enhancement in Inte...
Location of Shunt FACTS Devices for First-Swing Stability Enhancement in Inte...Editor IJMTER
 
Phase Measurement Units based FACT’s Devices for the Improvement of Power Sys...
Phase Measurement Units based FACT’s Devices for the Improvement of Power Sys...Phase Measurement Units based FACT’s Devices for the Improvement of Power Sys...
Phase Measurement Units based FACT’s Devices for the Improvement of Power Sys...IJECEIAES
 

Similar to Inter-Area Oscillation Damping using an STATCOM Based Hybrid Shunt Compensation Scheme (20)

EEE 33rd 971 & 975
EEE 33rd 971 & 975EEE 33rd 971 & 975
EEE 33rd 971 & 975
 
Ga based optimal facts controller for maximizing loadability with stability c...
Ga based optimal facts controller for maximizing loadability with stability c...Ga based optimal facts controller for maximizing loadability with stability c...
Ga based optimal facts controller for maximizing loadability with stability c...
 
International Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentInternational Journal of Engineering Research and Development
International Journal of Engineering Research and Development
 
Multi-Objective Evolutionary Programming for Static VAR Compensator (SVC) in ...
Multi-Objective Evolutionary Programming for Static VAR Compensator (SVC) in ...Multi-Objective Evolutionary Programming for Static VAR Compensator (SVC) in ...
Multi-Objective Evolutionary Programming for Static VAR Compensator (SVC) in ...
 
Impact of hybrid FACTS devices on the stability of the Kenyan power system
Impact of hybrid FACTS devices on the stability of the Kenyan power system Impact of hybrid FACTS devices on the stability of the Kenyan power system
Impact of hybrid FACTS devices on the stability of the Kenyan power system
 
Application of Multilevel Voltage-Source-Converter in FACTS Devices for Power...
Application of Multilevel Voltage-Source-Converter in FACTS Devices for Power...Application of Multilevel Voltage-Source-Converter in FACTS Devices for Power...
Application of Multilevel Voltage-Source-Converter in FACTS Devices for Power...
 
Voltage profile Improvement Using Static Synchronous Compensator STATCOM
Voltage profile Improvement Using Static Synchronous Compensator STATCOMVoltage profile Improvement Using Static Synchronous Compensator STATCOM
Voltage profile Improvement Using Static Synchronous Compensator STATCOM
 
International Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentInternational Journal of Engineering Research and Development
International Journal of Engineering Research and Development
 
Enhancement of voltage stability using static synchronous series compensator
Enhancement of voltage stability using static synchronous series compensatorEnhancement of voltage stability using static synchronous series compensator
Enhancement of voltage stability using static synchronous series compensator
 
Effect of Carrier Frequency in Grid Inter Connected Wind System With SSFC Con...
Effect of Carrier Frequency in Grid Inter Connected Wind System With SSFC Con...Effect of Carrier Frequency in Grid Inter Connected Wind System With SSFC Con...
Effect of Carrier Frequency in Grid Inter Connected Wind System With SSFC Con...
 
A Review on Optimization of Coordinated Control Plan for PSS and STATCOM Devi...
A Review on Optimization of Coordinated Control Plan for PSS and STATCOM Devi...A Review on Optimization of Coordinated Control Plan for PSS and STATCOM Devi...
A Review on Optimization of Coordinated Control Plan for PSS and STATCOM Devi...
 
Comparison of Shunt Facts Devices for the Improvement of Transient Stability ...
Comparison of Shunt Facts Devices for the Improvement of Transient Stability ...Comparison of Shunt Facts Devices for the Improvement of Transient Stability ...
Comparison of Shunt Facts Devices for the Improvement of Transient Stability ...
 
Efficacy of Facts in Power Oscillation Damping and Renewable Integration
Efficacy of Facts in Power Oscillation Damping and Renewable IntegrationEfficacy of Facts in Power Oscillation Damping and Renewable Integration
Efficacy of Facts in Power Oscillation Damping and Renewable Integration
 
International Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentInternational Journal of Engineering Research and Development
International Journal of Engineering Research and Development
 
Improvement of Power System Oscillation by using Coordinated Control Plan for...
Improvement of Power System Oscillation by using Coordinated Control Plan for...Improvement of Power System Oscillation by using Coordinated Control Plan for...
Improvement of Power System Oscillation by using Coordinated Control Plan for...
 
Voltage Compensation in Wind Power System using STATCOM Controlled by Soft Co...
Voltage Compensation in Wind Power System using STATCOM Controlled by Soft Co...Voltage Compensation in Wind Power System using STATCOM Controlled by Soft Co...
Voltage Compensation in Wind Power System using STATCOM Controlled by Soft Co...
 
F021201048053
F021201048053F021201048053
F021201048053
 
USING SSSC & STATCOM --IMPROVE TRANSIENT STABILITY--P & Q OSICALLATIONS
USING SSSC & STATCOM --IMPROVE TRANSIENT STABILITY--P & Q OSICALLATIONSUSING SSSC & STATCOM --IMPROVE TRANSIENT STABILITY--P & Q OSICALLATIONS
USING SSSC & STATCOM --IMPROVE TRANSIENT STABILITY--P & Q OSICALLATIONS
 
Location of Shunt FACTS Devices for First-Swing Stability Enhancement in Inte...
Location of Shunt FACTS Devices for First-Swing Stability Enhancement in Inte...Location of Shunt FACTS Devices for First-Swing Stability Enhancement in Inte...
Location of Shunt FACTS Devices for First-Swing Stability Enhancement in Inte...
 
Phase Measurement Units based FACT’s Devices for the Improvement of Power Sys...
Phase Measurement Units based FACT’s Devices for the Improvement of Power Sys...Phase Measurement Units based FACT’s Devices for the Improvement of Power Sys...
Phase Measurement Units based FACT’s Devices for the Improvement of Power Sys...
 

More from IJPEDS-IAES

Fuzzy Gain-Scheduling Proportional–Integral Control for Improving the Speed B...
Fuzzy Gain-Scheduling Proportional–Integral Control for Improving the Speed B...Fuzzy Gain-Scheduling Proportional–Integral Control for Improving the Speed B...
Fuzzy Gain-Scheduling Proportional–Integral Control for Improving the Speed B...IJPEDS-IAES
 
Advance Technology in Application of Four Leg Inverters to UPQC
Advance Technology in Application of Four Leg Inverters to UPQCAdvance Technology in Application of Four Leg Inverters to UPQC
Advance Technology in Application of Four Leg Inverters to UPQCIJPEDS-IAES
 
Modified SVPWM Algorithm for 3-Level Inverter Fed DTC Induction Motor Drive
Modified SVPWM Algorithm for 3-Level Inverter Fed DTC Induction Motor DriveModified SVPWM Algorithm for 3-Level Inverter Fed DTC Induction Motor Drive
Modified SVPWM Algorithm for 3-Level Inverter Fed DTC Induction Motor DriveIJPEDS-IAES
 
Modelling of a 3-Phase Induction Motor under Open-Phase Fault Using Matlab/Si...
Modelling of a 3-Phase Induction Motor under Open-Phase Fault Using Matlab/Si...Modelling of a 3-Phase Induction Motor under Open-Phase Fault Using Matlab/Si...
Modelling of a 3-Phase Induction Motor under Open-Phase Fault Using Matlab/Si...IJPEDS-IAES
 
Performance Characteristics of Induction Motor with Fiel
Performance Characteristics of Induction Motor with FielPerformance Characteristics of Induction Motor with Fiel
Performance Characteristics of Induction Motor with FielIJPEDS-IAES
 
A Novel Modified Turn-on Angle Control Scheme for Torque- Ripple Reduction in...
A Novel Modified Turn-on Angle Control Scheme for Torque- Ripple Reduction in...A Novel Modified Turn-on Angle Control Scheme for Torque- Ripple Reduction in...
A Novel Modified Turn-on Angle Control Scheme for Torque- Ripple Reduction in...IJPEDS-IAES
 
Modeling and Simulation of Induction Motor based on Finite Element Analysis
Modeling and Simulation of Induction Motor based on Finite Element AnalysisModeling and Simulation of Induction Motor based on Finite Element Analysis
Modeling and Simulation of Induction Motor based on Finite Element AnalysisIJPEDS-IAES
 
Comparative Performance Study for Closed Loop Operation of an Adjustable Spee...
Comparative Performance Study for Closed Loop Operation of an Adjustable Spee...Comparative Performance Study for Closed Loop Operation of an Adjustable Spee...
Comparative Performance Study for Closed Loop Operation of an Adjustable Spee...IJPEDS-IAES
 
Novel Discrete Components Based Speed Controller for Induction Motor
Novel Discrete Components Based Speed Controller for Induction MotorNovel Discrete Components Based Speed Controller for Induction Motor
Novel Discrete Components Based Speed Controller for Induction MotorIJPEDS-IAES
 
Sensorless Control of a Fault Tolerant PMSM Drives in Case of Single-Phase Op...
Sensorless Control of a Fault Tolerant PMSM Drives in Case of Single-Phase Op...Sensorless Control of a Fault Tolerant PMSM Drives in Case of Single-Phase Op...
Sensorless Control of a Fault Tolerant PMSM Drives in Case of Single-Phase Op...IJPEDS-IAES
 
Improved Stator Flux Estimation for Direct Torque Control of Induction Motor ...
Improved Stator Flux Estimation for Direct Torque Control of Induction Motor ...Improved Stator Flux Estimation for Direct Torque Control of Induction Motor ...
Improved Stator Flux Estimation for Direct Torque Control of Induction Motor ...IJPEDS-IAES
 
Minimization of Starting Energy Loss of Three Phase Induction Motors Based on...
Minimization of Starting Energy Loss of Three Phase Induction Motors Based on...Minimization of Starting Energy Loss of Three Phase Induction Motors Based on...
Minimization of Starting Energy Loss of Three Phase Induction Motors Based on...IJPEDS-IAES
 
Hardware Implementation of Solar Based Boost to SEPIC Converter Fed Nine Leve...
Hardware Implementation of Solar Based Boost to SEPIC Converter Fed Nine Leve...Hardware Implementation of Solar Based Boost to SEPIC Converter Fed Nine Leve...
Hardware Implementation of Solar Based Boost to SEPIC Converter Fed Nine Leve...IJPEDS-IAES
 
Transformer Less Voltage Quadrupler Based DC-DC Converter with Coupled Induct...
Transformer Less Voltage Quadrupler Based DC-DC Converter with Coupled Induct...Transformer Less Voltage Quadrupler Based DC-DC Converter with Coupled Induct...
Transformer Less Voltage Quadrupler Based DC-DC Converter with Coupled Induct...IJPEDS-IAES
 
IRAMY Inverter Control for Solar Electric Vehicle
IRAMY Inverter Control for Solar Electric VehicleIRAMY Inverter Control for Solar Electric Vehicle
IRAMY Inverter Control for Solar Electric VehicleIJPEDS-IAES
 
Design and Implementation of Single Phase AC-DC Buck-Boost Converter for Powe...
Design and Implementation of Single Phase AC-DC Buck-Boost Converter for Powe...Design and Implementation of Single Phase AC-DC Buck-Boost Converter for Powe...
Design and Implementation of Single Phase AC-DC Buck-Boost Converter for Powe...IJPEDS-IAES
 
Improvement of Wind farm with PMSG using STATCOM
Improvement of Wind farm with PMSG using STATCOMImprovement of Wind farm with PMSG using STATCOM
Improvement of Wind farm with PMSG using STATCOMIJPEDS-IAES
 
Modeling and Control of a Doubly-Fed Induction Generator for Wind Turbine-Gen...
Modeling and Control of a Doubly-Fed Induction Generator for Wind Turbine-Gen...Modeling and Control of a Doubly-Fed Induction Generator for Wind Turbine-Gen...
Modeling and Control of a Doubly-Fed Induction Generator for Wind Turbine-Gen...IJPEDS-IAES
 
A Review on Design and Development of high Reliable Hybrid Energy Systems wit...
A Review on Design and Development of high Reliable Hybrid Energy Systems wit...A Review on Design and Development of high Reliable Hybrid Energy Systems wit...
A Review on Design and Development of high Reliable Hybrid Energy Systems wit...IJPEDS-IAES
 
Fuzzy Sliding Mode Control for Photovoltaic System
Fuzzy Sliding Mode Control for Photovoltaic SystemFuzzy Sliding Mode Control for Photovoltaic System
Fuzzy Sliding Mode Control for Photovoltaic SystemIJPEDS-IAES
 

More from IJPEDS-IAES (20)

Fuzzy Gain-Scheduling Proportional–Integral Control for Improving the Speed B...
Fuzzy Gain-Scheduling Proportional–Integral Control for Improving the Speed B...Fuzzy Gain-Scheduling Proportional–Integral Control for Improving the Speed B...
Fuzzy Gain-Scheduling Proportional–Integral Control for Improving the Speed B...
 
Advance Technology in Application of Four Leg Inverters to UPQC
Advance Technology in Application of Four Leg Inverters to UPQCAdvance Technology in Application of Four Leg Inverters to UPQC
Advance Technology in Application of Four Leg Inverters to UPQC
 
Modified SVPWM Algorithm for 3-Level Inverter Fed DTC Induction Motor Drive
Modified SVPWM Algorithm for 3-Level Inverter Fed DTC Induction Motor DriveModified SVPWM Algorithm for 3-Level Inverter Fed DTC Induction Motor Drive
Modified SVPWM Algorithm for 3-Level Inverter Fed DTC Induction Motor Drive
 
Modelling of a 3-Phase Induction Motor under Open-Phase Fault Using Matlab/Si...
Modelling of a 3-Phase Induction Motor under Open-Phase Fault Using Matlab/Si...Modelling of a 3-Phase Induction Motor under Open-Phase Fault Using Matlab/Si...
Modelling of a 3-Phase Induction Motor under Open-Phase Fault Using Matlab/Si...
 
Performance Characteristics of Induction Motor with Fiel
Performance Characteristics of Induction Motor with FielPerformance Characteristics of Induction Motor with Fiel
Performance Characteristics of Induction Motor with Fiel
 
A Novel Modified Turn-on Angle Control Scheme for Torque- Ripple Reduction in...
A Novel Modified Turn-on Angle Control Scheme for Torque- Ripple Reduction in...A Novel Modified Turn-on Angle Control Scheme for Torque- Ripple Reduction in...
A Novel Modified Turn-on Angle Control Scheme for Torque- Ripple Reduction in...
 
Modeling and Simulation of Induction Motor based on Finite Element Analysis
Modeling and Simulation of Induction Motor based on Finite Element AnalysisModeling and Simulation of Induction Motor based on Finite Element Analysis
Modeling and Simulation of Induction Motor based on Finite Element Analysis
 
Comparative Performance Study for Closed Loop Operation of an Adjustable Spee...
Comparative Performance Study for Closed Loop Operation of an Adjustable Spee...Comparative Performance Study for Closed Loop Operation of an Adjustable Spee...
Comparative Performance Study for Closed Loop Operation of an Adjustable Spee...
 
Novel Discrete Components Based Speed Controller for Induction Motor
Novel Discrete Components Based Speed Controller for Induction MotorNovel Discrete Components Based Speed Controller for Induction Motor
Novel Discrete Components Based Speed Controller for Induction Motor
 
Sensorless Control of a Fault Tolerant PMSM Drives in Case of Single-Phase Op...
Sensorless Control of a Fault Tolerant PMSM Drives in Case of Single-Phase Op...Sensorless Control of a Fault Tolerant PMSM Drives in Case of Single-Phase Op...
Sensorless Control of a Fault Tolerant PMSM Drives in Case of Single-Phase Op...
 
Improved Stator Flux Estimation for Direct Torque Control of Induction Motor ...
Improved Stator Flux Estimation for Direct Torque Control of Induction Motor ...Improved Stator Flux Estimation for Direct Torque Control of Induction Motor ...
Improved Stator Flux Estimation for Direct Torque Control of Induction Motor ...
 
Minimization of Starting Energy Loss of Three Phase Induction Motors Based on...
Minimization of Starting Energy Loss of Three Phase Induction Motors Based on...Minimization of Starting Energy Loss of Three Phase Induction Motors Based on...
Minimization of Starting Energy Loss of Three Phase Induction Motors Based on...
 
Hardware Implementation of Solar Based Boost to SEPIC Converter Fed Nine Leve...
Hardware Implementation of Solar Based Boost to SEPIC Converter Fed Nine Leve...Hardware Implementation of Solar Based Boost to SEPIC Converter Fed Nine Leve...
Hardware Implementation of Solar Based Boost to SEPIC Converter Fed Nine Leve...
 
Transformer Less Voltage Quadrupler Based DC-DC Converter with Coupled Induct...
Transformer Less Voltage Quadrupler Based DC-DC Converter with Coupled Induct...Transformer Less Voltage Quadrupler Based DC-DC Converter with Coupled Induct...
Transformer Less Voltage Quadrupler Based DC-DC Converter with Coupled Induct...
 
IRAMY Inverter Control for Solar Electric Vehicle
IRAMY Inverter Control for Solar Electric VehicleIRAMY Inverter Control for Solar Electric Vehicle
IRAMY Inverter Control for Solar Electric Vehicle
 
Design and Implementation of Single Phase AC-DC Buck-Boost Converter for Powe...
Design and Implementation of Single Phase AC-DC Buck-Boost Converter for Powe...Design and Implementation of Single Phase AC-DC Buck-Boost Converter for Powe...
Design and Implementation of Single Phase AC-DC Buck-Boost Converter for Powe...
 
Improvement of Wind farm with PMSG using STATCOM
Improvement of Wind farm with PMSG using STATCOMImprovement of Wind farm with PMSG using STATCOM
Improvement of Wind farm with PMSG using STATCOM
 
Modeling and Control of a Doubly-Fed Induction Generator for Wind Turbine-Gen...
Modeling and Control of a Doubly-Fed Induction Generator for Wind Turbine-Gen...Modeling and Control of a Doubly-Fed Induction Generator for Wind Turbine-Gen...
Modeling and Control of a Doubly-Fed Induction Generator for Wind Turbine-Gen...
 
A Review on Design and Development of high Reliable Hybrid Energy Systems wit...
A Review on Design and Development of high Reliable Hybrid Energy Systems wit...A Review on Design and Development of high Reliable Hybrid Energy Systems wit...
A Review on Design and Development of high Reliable Hybrid Energy Systems wit...
 
Fuzzy Sliding Mode Control for Photovoltaic System
Fuzzy Sliding Mode Control for Photovoltaic SystemFuzzy Sliding Mode Control for Photovoltaic System
Fuzzy Sliding Mode Control for Photovoltaic System
 

Recently uploaded

Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024hassan khalil
 
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130Suhani Kapoor
 
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube ExchangerStudy on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube ExchangerAnamika Sarkar
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxAsutosh Ranjan
 
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝soniya singh
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escortsranjana rawat
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingrakeshbaidya232001
 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxpranjaldaimarysona
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...ZTE
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxpurnimasatapathy1234
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
Analog to Digital and Digital to Analog Converter
Analog to Digital and Digital to Analog ConverterAnalog to Digital and Digital to Analog Converter
Analog to Digital and Digital to Analog ConverterAbhinavSharma374939
 
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)Suman Mia
 
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxJoão Esperancinha
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escortsranjana rawat
 
What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxWhat are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxwendy cai
 
Introduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxIntroduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxupamatechverse
 

Recently uploaded (20)

Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024
 
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
 
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube ExchangerStudy on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptx
 
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writing
 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptx
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
 
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptx
 
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptxExploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
 
Analog to Digital and Digital to Analog Converter
Analog to Digital and Digital to Analog ConverterAnalog to Digital and Digital to Analog Converter
Analog to Digital and Digital to Analog Converter
 
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
 
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
 
What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxWhat are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptx
 
Introduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxIntroduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptx
 

Inter-Area Oscillation Damping using an STATCOM Based Hybrid Shunt Compensation Scheme

  • 1. International Journal of Power Electronics and Drive System (IJPEDS) Vol. 7, No. 4, December 2016, pp. 1172~1180 ISSN: 2088-8694, DOI: 10.11591/ijpeds.v7i4.pp1172-1180  1172 Journal homepage: http://iaesjournal.com/online/index.php/IJPEDS Inter-Area Oscillation Damping using an STATCOM Based Hybrid Shunt Compensation Scheme Vahid Farzam, Ahad Mokhtarpour Department of Electrical and Electronic Engineering, Tabriz Branch, Islamic Azad University Tabriz, Iran Article Info ABSTRACT Article history: Received May 31, 2016 Revised Nov 5, 2016 Accepted Nov 17, 2016 FACTS devices are one of the latest technologies which have been used to improve power system dynamic and stability during recent years. However, widespread adoption of this technology has been hampered by high cost and reliability concerns. In this paper an economical phase imbalanced shunt reactive compensation concept has been introduced and its ability for power system dynamic enhancement and inter-area oscillation damping are investigated. A hybrid phase imbalanced scheme is a shunt capacitive compensation scheme, where two phases are compensated by fixed shunt capacitor (C) and the third phase is compensated by a Static Synchronous Compensator (STATCOM) in shunt with a fixed capacitor (CC). The power system dynamic stability enhancement would be achieved by adding a conventional Wide Area Damping Controller (WADC) to the main control loop of the single phase STATCOM. Two different control methodologies are proposed: a non-optimized conventional damping controller and a conventional damping controller with optomised parameters that are added to the main control loop of the unbalanced compensator in order to damp the inter area oscillations. The proposed arrangement would, certainly, be economically attractive when compared with a full three-phase STATCOM. The proposed scheme is prosperously applied in a 13-bus six-machine test system and various case studies are conducted to demonstrate its ability in damping inter-area oscillations and power system dynamic enhancement. Keyword: Compensator (STATCOM) Inter-area oscillations Power system stability Shunt compensation Static synchronous Copyright © 2016 Institute of Advanced Engineering and Science. All rights reserved. Corresponding Author: Ahad Mokhtarpour, Department of Electrical and Electronic Engineering, Tabriz Branch, Islamic Azad University Tabriz, University Road, Tabriz Township, East Azarbayjan Country, Iran. Email:a.mokhtarpour@iaut.ac.ir 1. INTRODUCTION Low frequency inter-area oscillations have been observed when large power systems are interconnected by relatively weak tie lines. These oscillations may sustain and grow to cause system separation if no sufficient damping is available [1]-[2]. Traditional power system stabilizers (PSSs) have been widely studied to solve the problem [3]. However, PSSs suffers a trouble of being liable to cause considerable variations in the voltage profile and they may even result in leading power factor operation and losing system stability under severe disturbances, especially those three phase faults which may happen at the generator terminals. In recent years, the fast progress in the field of power electronics had opened new opportunities for the application of the Flexible AC Transmission Systems (FACTS) devices as one of the most effective ways to improve power system operation controllability and power transfer limits [4]-[5]. Through the modulation of bus voltage, phase shift between buses, and transmission line reactance, FACTS devices can cause a substantial increase in power transfer limits during steady-state. Because of the extremely fast control action associated with FACTS device operations, they have been very promising candidates for utilization in power system damping enhancement. It is well known that utilizing a feedback auxiliary
  • 2. IJPEDS ISSN: 2088-8694  Inter-Area Oscillation Damping using an STATCOM Based Hybrid Shunt … (Vahid Farzam) 1173 control, in addition to the FACTS device main control, can greatly improve system damping [6]-[8] and can also improve system voltage profile, which is advantageous over PSSs. Besides many merits which are provided with FACTS devices, they are suffering from high initial costs, device complexity and low reliability of these devices which means if a single point of failure occurs in a system, the system will be entirely shut down. These barriers have convinced the researchers to search out for a solution and, in the literature some new structures and systems have been introduced [9]-[15]. In [9]-[12] the Distributed FACTS (D-FACTS) technology has been introduced. This newly born technology points a way to a novel approach for achieving the power flow control, voltage stability, system oscillation damping and whole system reliability. The distributed nature of the suggested system makes it possible to achieve fine granularity in the system rating. Moreover, it is possible to expand the system with the growing demand. This gives a salient benefit in planning the system, which allows the planner to have control on available transfer capacity (ATC). It is done in a way that the growing needs in power transfer (equal to 2% for every year) are satisfied by installing new D-FACTS modules in the line for 10 years; this is done in order to meet project growth needs without having to invest all the capital at the start of the project implementation or in [13]-[15] two economical phase imbalanced series compensation concept has been introduced and their ability for power system dynamic enhancement and inter-area oscillation damping have been investigated where the series capacitive compensation in one phase is created using a single-phase TCSC (Scheme I) or a single-phase SSSC (Scheme II) in series with a fixed capacitor, and the other two phases are compensated by fixed series capacitors. The TCSC and SSSC controls are initially set such that their equivalent compensations at the power frequency combined with the fixed capacitor yield a resultant compensation equal to the other two phases. These two schemes would, definitely, be economically attractive when compared with a full three-phase TCSC or SSSC, which have been used/proposed for power oscillations damping. Furthermore, reducing the number of thyristor valves and VSC to one third will also have a positive impact on equipment reliability. The main contribution of this paper is introducing an economical phase imbalanced shunt capacitive compensation concept and investigating its ability for power system dynamic enhancement and inter-area oscillation damping. A shunt hybrid phase imbalanced scheme is a shunt capacitive compensation scheme, where two phases are compensated by fixed shunt capacitor (C) and the third phase is compensated by a single phase Static Synchronous Compensator (STATCOM) in shunt with a fixed capacitor (CC). Certainly the proposed arrangement would, certainly, be economically attractive when compared with a full three-phase STATCOM. The power system dynamic stability enhancement would be achieved by adding an auxiliary damping controller to the main control loop of the single phase STATCOM. In designing damping controller, the feedback signals could either comprise wide-area information through utilization of PMUs dispersed over the network or be limited to merely local data captured at the line’s sending end. Since this paper concentrates on the inter-area phenomenon on which is inherently a global issue, wide area signals are used for the damping controller input signal [16]-[17]. To optimize the parameters of the designed Wide Area Damping Controller (WADC) the Particle Swarm Optimization (PSO) method is utilized. The PSO is a population based stochastic optimization algorithm, prompted by social behavior of bird flocking or fish schooling [18]-[19]. In order to assess the capability of the PSO based damping controller in oscillations suppression, a nonoptimized conventional damping controller is also designed and enhanced to the main control loopof the unbalanced STATCOM to suppress the oscillations.Finally the proposed approach is prosperously applied in a 16-bus six-machine test system and various case studies are conducted to demonstrate the potential of the proposed approach. 2. PHASE IMBALANCED SHUNT COMPENSATION SCHEME The STATCOM is a well-known shunt connected FACTS controller based on voltage source converter (VSC). As illustrated in Figure 1, a typical STATCOM is realized with a three-phase VSC, a dc link capacitor and an interfacing transformer. Also a filtering stage (not shown) is considered at the output of the VSC for alleviating the harmonic pollution in the injected voltage [4]. The STATCOM is capable of generating or absorbing reactive power. By varying the amplitude of the produced output voltages, the reactive power exchange between the converter and the ac system can be controlled; hence, it gives the opportunity to control some specific parameters (e.g. voltage) of an electric power system. To address in more details, the STATCOM main task is to control the voltage dynamically. However, it is commonly expected to yield some ancillary duties such as power oscillation damping, transient stability enhancement, voltage flicker control and so forth. Figure 1 also displays the main control system of the single phase STATCOM considered here. From this figure it can be seen that the control system requires three input signals including ac system bus voltage, V, converter output current oi and the
  • 3.  ISSN: 2088-8694 IJPEDS Vol. 7, No. 4, December 2016 : 1172 – 1180 1174 bus reference voltage RefV . As illustrated, voltage Voperates a phase-locked loop (PLL) which determines the basic synchronizing signal, angle . The reactive component of the output current oQI is extracted and compared to the produced reactive current reference, QRefI . Ultimately the obtained error signal is utilized to provide angle , which determines the necessary phase shift between the output voltages of the converter and the ac system voltage. In the sequel when  is calculated, the dc link capacitor is charged or discharged to the dc voltage level required [4]. A phase imbalanced STATCOM is a shunt compensation scheme, where two phases are compensated by fixed shunt capacitor (C) and the third phase is compensated by a single phase STATCOM paralleled with a fixed capacitor ( CC ) as shown on Figure 2. The phase imbalance of proposed Scheme can be explained mathematically as follows. At the power frequency, the reactive power for phases a, b and c are given by: cba QQQ  (1) STATCOMCcc QQQ  (2) During any other frequency, Fe STATCOMSTATCOMCcc QQQQ  (3) The first terms in (2) and (3) are different because of the difference in frequency. The third term in (3) represents the change in effective reactive power of the single phase STATCOM due to the action of the STATCOM supplementary damping controller that has been added to yhe main control loop of STATCOM to inter area oscillation mitigation. As said on section 1 this scheme would, definitely, be economically attractive when compared with a full three-phase STATCOM. This paper introduces this economical scheme and evaluates the effectiveness of the scheme in damping oscillations. Time domain simulations were conducted on a benchmark network using the Matlab. Figure 1. STATCOM Control system CCQ aQ CCCC bQ CQ STATCOMQ STATCOM Figure 2. Schematic Diagrams of the Hybrid Shunt Compensation Schemes C activeRe current computer PLL oi oQI Error Amplifier   oV Gate iclog pattern Auxiliary Signal V STATCOM V dcV oi fReQI fReV V oV Error Amplifier Damping fRe * V
  • 4. IJPEDS ISSN: 2088-8694  Inter-Area Oscillation Damping using an STATCOM Based Hybrid Shunt … (Vahid Farzam) 1175 3. STUDY SYSTEM The power system adopted for this study is illustrated in Figure 4 [13]-[14] and [17]. It has originally 15 buses and six machines in three areas. Although this is a test system, it well serves to illustrate the concept, which remains the same for large systems. To keep the voltage profile of the system constant, shunt capacitors are installed at buses 7, 9, and 15. For the nonlinear time domain simulation, generators are modeled in the d-q-o reference frame and transmission lines are represented in the π model. It is worth mentioning that the dynamics of generator excitation is also considered in the simulation. The comprehensive data of the power system are given in the Appendix A. For applying the phase imbalanced shunt compensator in the system, a single phase STATCOM is installed instead of one phase of shunt capacitor that installed on bus 7 and the STATCOM contribution in the hybrid compensated phase is 0.5 p.u. of the total reactive compensation. However, the optimal location of reactive power compensator in practical and large power systems is vital point and requires comprehensive studies [21]. The power system under study has five distinct oscillatory modes: three local modes and two inter-area modes which have been obtained by the Eigen value analysis. The inter-area mode 1 is characterized by having a slightly higher frequency (0.78 Hz) than mode 2 (0.46 Hz). Mode 1 consists of generators of area 1 swinging against those of area 3. While, mode 2 consists of generators of area 2 oscillating against those of areas 1 and 3 [14]. As a result, in order to mitigate the unstable oscillation modes, a PSO-based is designed and added to the main control loop of the unbalanced STATCOM. Figure 4. Three-Area Six-Machine Power System Aggregated with an Unbalanced STATCOM 4. POWER OSCILLATIONS DAMPING CONTROLLER DESIGN As explained in Section III, the system under study has five distinct modes. These oscillatory modes are to be damped by an auxiliary damping controller that is added to the main control loop of the unbalanced STATCOM. Among crucial requirements of implementing auxiliary damping controllers is figuring out its best location. This task should be done with two major objectives: (i) providing an effective damping of oscillations and (ii) minimizing the possible interactions between STATCOM reactive power and damping controllers. One of the fundamental issues in designing the damping controller is the selection of feedback signals to achieve the best modal observability and optimal oscillation damping [22]. Any kind of input signal with sufficient modal observability of inter-area oscillation can be used; amongst are the active power of tie lines, voltage angle differences between areas, rotor angular speed differences between generators, etc. Generally, the damping controller input signals can be classified in twofold groups: local signals and wide- area ones. As a result, two sorts of solutions exist for designing damping controllers: the decentralized approach based on local signals and the centralized approach exploiting wide-area information. The main advantage of the former solution comes from the fact that no telecommunication infrastructure is needed. The expense of this method is that it will suffice to economically and efficiently satisfy the damping requirements of the present/future heavily stressed networks with credible inter-area oscillation modes. In contrast, the centralized technique offers more effective outcomes at the expense of having fast communication infrastructure. Clearly, in a practical environment, selection of either centralized or decentralized solution depends on a given power system characteristics and its communication facilities. With respect to Figure 4 the power system under study equipped with PMUs, wide area signals used as damping controller input
  • 5.  ISSN: 2088-8694 IJPEDS Vol. 7, No. 4, December 2016 : 1172 – 1180 1176 signal. Opposite to the conventional measurement devices, PMUs are synchronized respect to each other through the one pulse per second signals of the global positioning system. This new opportunity realized the true concept of measuring phase angles which inherently encompass valuable information of the system stress situation. The huge infrastructure which is in charge for gathering the PMUs’ data in a central location(s) is referred to as WAMS. Autonomous control including oscillation damping is among advanced functionalities imagined for WAMS. Clearly, the WAMS potential in feeding WADCs is directly dependent to the number and location of PMUs deployed in the grid. The PMU placement problem is a broadly investigated research area and various aspects of this problem have been so far digested in dept [23]-[25]. Intuitively, it can be deduced that for oscillation damping objective a limited number, but geographically distributed, of PMUs would work sufficiently. The numerical studies presented in the following support this conclusion. One of the main advantages of WADCs is its capability in designing multi-band damping controllers. Each band of the WADC has its own global input signal for damping one of the oscillation modes. As the system under study has two inter-area modes, a simple two-band classic controller is considered which is represented in Figure 5. Each controller is a conventional damping controller that is shown in Figure 6. Band controllers are denoted by WADC1 and WADC2 and the whole unit is recognized by WADC. + WADC1 3113   WADC2 5115   ++ 1W 2W 1SignalDamping 2SignalDamping SignalDamping Figure 5. The Two-Band WADC Designed for the Three-Area Power System sT1 sT w w  sT sT 4 3 1 1   K max min SignalInput 1SignalDamping sT1 sT1 2 1   Figure 6. The Block Diagram of the Classical Damping Controller It is apparent that to damp out multi-mode oscillations, two suitable supplementary signals containing both modes of oscillations are necessary. Any kind of input signal that has a good modal observability of inter-area oscillation can be used such as the power of tie line interconnecting two areas, frequency difference between two areas, angle difference of two buses in two areas, etc. Generally, the PMU firstly receives the sinusoidal waveforms of three-phase voltages and currents, then converts the sampled digital data to the phasor values, and finally sends the information to the regional or system control center [26]. Although the PMU computed frequency and its rate of change are based on local voltage measurements, there are several approaches to calculate the generator speed through local PMU measurement [27]-[29]. Frequency is a key indicator for the system stability and generation/demand balance. This parameter or its derivatives such as rotor speeds and their rates of change are usually implemented as the damping controller feedback signal [11]-[12] and [17]. To this end, high voltage buses associated with G1, G3 and G5 are assumed to be equipped with PMUs and 3113 -  and 5115 -  are chosen as global feedback signals. For damping the inter-area mode 1 (0.78 Hz), WADC1 is used whose input is 15 and WADC2 is responsible for damping the oscillation mode 2 (0.46 Hz) with input of 13 . As shown in Figure 5, the output of WADCs are weighted and summed up to generate the WADC output, which is )2(*)1(* 21 SignalDampingWSignalDampingWSignalDamping  (4)
  • 6. IJPEDS ISSN: 2088-8694  Inter-Area Oscillation Damping using an STATCOM Based Hybrid Shunt … (Vahid Farzam) 1177 W1 and W2 are weighting factors and are chosen inversely proportional to the normalized damping ratio of their dominant mode obtained from the Prony analysis (W1=1.15, W2=1) [14]. The WADC output is finally employed for modulating the reactive power loop of the STATCOM (see Figure 1). It has to be noted that the communication system is thus far assumed to be delay free in the design process which is not the case in real world observations and the communication latency should be considered in design procedure. The authors intend to work on this issue in future while many good pioneer research is available presently [18] and the controller designed in this paper is an ideal WADC without considering latency in wide area signals. The proposed WADC is implemented in the simulation setup and its parameters are tuned through the PSO technique. İn the following a quiet explanation about optimisation of WADC parameters has been presented. 4.1. PSO Algorithm In the PSO technique, there are some simple entities (particle) which their trajectory in the search space can be adjusted by dynamically regulating the velocity of each particle. Generally, a predefined objective function will be defined by the user, and then the best value of the objective function that is achieved by the ith particle is expressed as Pbest. Furthermore, the overall best value of the objective function obtained by the particles at every time step (gbest) is calculated through the algorithm. Then, each particle’s velocity and position is being updated by [18]-[19]: ))(())(()()1( 2211 tXPrctXPrctwVtV idgdidididid  (5) )()1()( tcVtXtX ididid  (6) Where, Vid is the velocity of the ith particle, Xidis the position of the ith particle, Pidand Pgd are Pbest and gbest, respectively. c1 andc2 are positive constants which are responsible for alternation of the particle velocity toward Pbest and gbest, r1 and r2are two random constants between 0 and 1 and c is a factor which can modify the velocity of the particle to adjust the position of each particle in the next iteration. w, inertia weight, is defined to balance the local and global searches. Hence, the PSO algorithm searches for the optimal minimum value of the objective function and updates the velocity and particle’s location in each iteration. The iterative process will be terminated when the stopping criterion is met. If the parameters of damping controller are properly optimized, the damping of oscillation will be resulted effectively. For this reason, damping controller parameters will be optimized by the PSO algorithm. In this study, the objective function to be minimized by PSO is come from the generators rotor speed deviations. This objective function is an integral of time multiplied by the absolute value of the power deviation, that is dtWtJ simt 13.. 0   (7) Where, simt is the total simulation time and 13W is the generators rotor speed deviations. The optimization is subjected to parameter limits, i.e. maxmin KKK  , max11min1 TTT  , max22min2 TTT  , max33min3 TTT  , max44min4 TTT  It has to be pointed out that the above parameters are associated with the damping controller and would be introduced in the next section. Here, the ranges for parameters are as follows. K [0.01-40] and T1, T2, T3, T4[0.0001-2]. Associated with PSO algorithm, the number of particles, number of iterations, c1, c2, c, and w are set to 50, 200, 2, 2, 1, and 0.85, respectively and the final values of parameters are presented in Appendix B. 5. SIMULATION RESULTS This section demonstrates the capability of the proposed STATCOM based hybrid shunt compensation scheme in damping inter-area oscillations. As seen on Figure 4, for this propose fixed capacitor of one phase installed on bus 7 is replaced with an unbalanced. The parameters of the unbalanced STATCOM are shown in appendix C. For the sake of simulation, it is assumed that in the system shown in Figure 4, a three-phase to ground fault occurs on bus 8 and lasts for 200 ms. this fault stimulates oscillation
  • 7.  ISSN: 2088-8694 IJPEDS Vol. 7, No. 4, December 2016 : 1172 – 1180 1178 of the system. Figures 7 and 8 show the rotor speed difference between G1 and G3 and the rotor speed difference between G1 and G2 as well as their damping behavior in three situations of fixed shunt compensator and Hybrid shunt compensation with optimized and non-optimised damping controllers. The inter-area oscillation is measured by rotor speed difference of G1 and G3 and the local oscillation is measured by rotor speed difference of G1 and G2. As shown in Figures 7 and 8, in the case fix shunt compensation, the system experiences severe fluctuations with very low damping. However, in the case of hybrid shunt compensation that in one phase a STATCOMis placed instead of a fixed shunt capacitor, both supplementary controllers of unbalanced compensation system leads to damping of oscillations but an effective damping of oscillations after the event of fault is achieved when PSO based damping controlleris added to main controllers of unbalanced STATCOM. Moreover, in the figure legends, “Fixed” refers to the system performance with fixed capacitor compensation. Figures 9 show the tie-line (7–9, line 1) power flow time responses of the test benchmark during and after disturbance. Comparing the responses of the fixed shunt compensation to the hybrid shunt compensation scheme in this Figure, the favorable contribution of the proposed hybrid scheme to the mitigation of the inter-area oscillations is very understandable. As it can be seen from Figures 7 and 9, the power oscillations damping controller decrease the first swing and effectively damps the subsequent oscillations. In Figure 10, the bus voltage, and damping controller output signal of the STATCOM are plotted. As observed from these figures, unlike the fixed shunt compensation, the hybrid scheme effectively preserves the system stability after disturbance and damps both inter-area and local oscillations. The results of simulation obviously show that, in the case of PSO based WADC, the performances of damping controller is by far better than the case that WADC parameters is achieved by trial and error method. This is because the parameters of PSO based WADC tuned with an optimization method. Figure 7. Rotor Speed Difference between G1 and G3, during and After Disturbance Figure 8. Rotor Speed Difference between G1 and G2, during and After Disturbance Figure 9. Tie-line power flow time responses during and after disturbance (a) (b) Figure 10. Performance of Unbalanced STATCOM during and After Disturbance: (a) STATCOM bus Voltage and (b) STATCOM Damping Controller Output Signal 0 5 10 15 -2 0 2 x 10 -3 time (s) W1-W2(p.u) Without Damping Controller With non-optomised Damping Controller With PSO Based Damping Controller 0 5 10 15 0.9 1 1.1 time (s) Vstatcom(p.u) 0 5 10 15 -0.2 0 0.2 time (s) DampingSignal(p.u)
  • 8. IJPEDS ISSN: 2088-8694  Inter-Area Oscillation Damping using an STATCOM Based Hybrid Shunt … (Vahid Farzam) 1179 6. CONCLOSION This work is mainly dedicated to investigate the capability of a new “hybrid” shunt compensation schemes in damping inter-area oscillations. The presented hybrid shunt compensation schemes is easily achievable, technically sound, and have an industrial application potential. A six-machine three area power system is put under investigation in order to verify the proposed scheme capability on inter-area oscillation damping. The power system dynamic stability enhancement achieved by adding two wide area, damping controllers. A non-optimized conventional damping controller and a conventional damping controller with optomised parameters. The PSO algorithm is used to solve optimization problem. Both damping controllers are added to the main control loop of the proposed shunt compensator. With respect simulation illustrations, it was observed that as the time goes on, the proposed hybrid compensation equipped with auxiliary damping controller would damp all inter-area and locally oscillation modes; also the results of simulation showed that, in the case of PSO based WADC, the performances of damping controller was by far better than the case that WADC parameters were achieved by trial and error method.Hence, the effective performance of proposed unbalanced shunt compensation in the system oscillation damping was validated. Appendix A Power System Data Generator Data: 900 MVA, 20 kV, ra = 0.0025 p.u., xl= 0.2 p.u., xd = 1.8 p.u., xq = 1.7 p.u., x‫׳‬d = 0.3 p.u., x‫׳‬q = 0.55 p.u., x‫״‬d = -0.25 p.u., x‫״‬q = 0.25 p.u., T‫׳‬ do = 8 s, T‫״‬do = 0.03 s, T‫׳‬qo = 0.4 s, T‫״‬qo = 0.05 s, H(G1&G2) = 6.5 s, H(G3&G4) = 6.175 s, H (G5) = 5.5 s, H(G6) = 5 s. Generator Steady State Data: G1: V = 1.04 ∟0o p.u., G2: P = 700 MW, V = 1.01 p.u., G5: P = 800 MW, V = 1.02 p.u., G6: P = 780 MW, V = 1.01 p.u. Transmission Line Data: r = 0.053 Ω/km, Xseries = 0.53 Ω/km, Yshunt = 5.21 μS/km. Bus 7 load: 1400 + j100-j350, Bus 9 load: 1800 + j100 – j500, Bus 15 load: 1200 + j300 – j220. Appendix B Table 1. Parameters of the STATCOM based WADCs Type K TW T1 T2 T3 T4 min & max WADC1 9 2 0.012 0.89 1.11 0.011 ±0.2 WADC2 16 2 0.032 1.3 0.014 0.044 ±0.2 Appendix C STATCOM Data Rated Power = 25 MVA, Rated Voltage = 26 KV, Frequency = 60 Hz, XT(sh) = 0.1 p.u. Switching Frequency = 15KHz. REFERENCES [1] Yu YN. Electric power system dynamics. New York: Academic Press; 1983. [2] Sauer PW, Pai MA. Power system dynamics and stability. Englewood Cliffs, NJ: Prentice-Hall; 1998. [3] X. Yang and A. Feliachi, “Stabilization of inter-area oscillation modes through excitation systems”, IEEE Trans. Power Syst., vol. 9, no. 1, pp.494–502, Feb. 1994. [4] R.M. Mathur and R.K.Varma, Thyristor-Based FACTS Controllers for Electrical Transmission Systems. New York: IEEE Press and Wiley.Interscience, Feb. 2002. [5] N.G. Hingorani, Flexible AC transmission, IEEE Spectrum (1993) 40 45. [6] E.V. Larson, J.J. Sanchez Gasca, J.H. Chow, “Concepts for design of FACTS controllers to damp power swings”, IEEE Trans. Power Syst., vol. 10, no. 2, pp948-956, May. 1995. [7] R. Kunamneni, S. Suman, M. Rambabu, K. Ashok Kumar, "Implementation of phase imbalance scheme for stabilizing torsional oscillations", International Journal of Electrical and Computer Engineering (IJECE), vol. 4, no. 5, pp. 697–702, October 2014. [8] M. Farsadi, A. Ghasemi, B. Ghasemi, " WAMS-Based SSR Damping controller design for FACTS devices and investigating effects of communication delays", International Journal of Power Electronics and Drive System (IJPEDS), vol. 6, no. 4, pp. 736–746, December 2015. [9] D. Divan et al, “A distributed static series compensator system for realizing active power flow control on existing power lines”, IEEE Trans. Power Delivery, vol. 22, no. 1, pp. 642-649, Jan 2007. [10] Z. Yuan, S.W.H. de Haan, J.B. Ferreira, and D. Cvoric, “A FACTS Device: Distributed Power-Flow Controller (DPFC)”, IEEE Trans. Power Electron, vol. 25, no. 10, Oct 2010. [11] J. Khazaie, M. Mokhtari, M. Khalilian, D. Nazarpour, “Sub-Synchronous Resonance Damping Using Distributed Static Series Compensator Enhanced with Fuzzy Logic Controller”, Inter Jour of Elect Power and Ener Systems, vol. 43, no. 1, pp. 80-89, Dec 2012.
  • 9.  ISSN: 2088-8694 IJPEDS Vol. 7, No. 4, December 2016 : 1172 – 1180 1180 [12] M. Khalilian, M. Mokhtari, S. Golshannavaz, D. Nazarpour, “Distributed Static Series Compensator (DSSC) for Subsynchronous Resonance Alleviation and Power Oscillation Damping”, Euro. Trans. Electr. Power, vol. 22, no. 5, pp. 589-600, July 2012. [13] D. Rai, G. Ramakrishna, S.O. Faried, and A. Edris, “Enhancement of power system dynamics using a phase imbalanced series compensation scheme”, IEEE Trans. Power Syst., vol. 25, no. 2, pp. 966–974, May 2010. [14] D. Rai, G. Ramakrishna, S.O. Faried, G. Ramakrishna, and A. Edris, “Damping Inter-Area Oscillations Using Phase Imbalanced Series Compensation Schemes”, IEEE Trans. Power Syst., vol. 26, no. 3, pp. 1756-1761, Aug 2011. [15] D. Rai, S. O. Faried, G. Ramakrishna, and A. Edris, “Hybrid series compensation scheme capable of damping subsynchronous resonance”, Proc. Inst. Eng. Technol. Gen., Transm. Distrib, vol. 4, no. 3, pp. 456–466, March 2010. [16] X. Xie, J. Xiao, C. Lu, and Y. Han, “Wide-area stability control for damping interarea oscillations of interconnected power systems”, IET Gen. Transm. Distrib., vol. 153, pp. 507–514, Sep. 2006. [17] M. Mokhtari, F. Aminifar, D. Nazarpour, and S. Golshannavaz, “Widearea power oscillation damping with a Fuzzy controller compensating the continuous communication delays”, IEEE Trans. Power Syst., vol. 28, no. 2, pp. 1997– 2005, May 2013. [18] Ho SL, Yang S, Ni G, Lo EWC, Wong HC. A particle swarm optimization basedbmethod for multi objective design optimizations. IEEE Trans Magnet, 2005; 41(5): 1756–9. [19] Shayeghi H, Shayanfar HA, Jalilzadeh S, Safari A. Design of output feedback UPFC controllers for damping of electromechanical oscillations using PSO. Energy Convers Manage, 2009; 50: 2559–61. [20] T.J.E Miller, Reactive Power Control in Electric System: [M]. New York, Wiley, 1982. [21] R. Minguez, F. Milano, R. Zarate-Miano, A.J. Conejo, “Optimal Network Placement of SVC Devices”, IEEE Trans. Power Syst., vol. 22, no. 4, pp. 1851–1860, Nov 2007. [22] Farsangi MM, Sung YH, Lee KY. Choice of FACTS Device Control Inputs for Damping Inter-area Oscillations. IEEE Transactions on Power Systems, 2004; 19(2): 1806–1812. [23] F. Aminifar, M. Fotuhi-Firuzabad, M. Shahidehpour, and A. Khodaei, “Observability enhancement by optimal PMU placement considering random power system outages”, Energy Syst., vol. 2, pp. 45–65, Mar. 2011. [24] F. Aminifar, M. Fotuhi-Firuzabad, A. Safdarian, and M. Shahidehpour, “Observability of hybrid AC/DC power systems with variablecost PMUs”, IEEE Trans. Power Del., to be published. [25] F. Aminifar, M. Fotuhi-Firuzabad, and A. Safdarian, “Optimal PMU placement based on probabilistic cost/benefit analysis”, IEEE Trans.Power Syst., vol. 28, no. 1, pp. 566–567, Feb. 2013. [26] I. Kamwa and R. Grondin, “PMU configuration for system dynamic performance measurement in large, multi-area power systems”, IEEETrans. Power Syst., vol. 17, no. 2, pp. 385–394, May 2002. [27] A. G. Phadke, “Synchronized phasormeasurements in power systems”, IEEE Comput. Appl. Power, vol. 6, pp. 10– 15, Apr. 1993. [28] K. Mei, S.M. Rovnyak, and C.M. Ong, “Clustering-based dynamic event location using wide-area phasor measurements”, IEEE Trans.Power Syst., vol. 23, no. 2, pp. 673–679, May 2008. [29] P. Tripathy, S.C. Srivastava, and S.N. Singh, “A divide-by-differencefilter based algorithm for estimation of generator rotor angle utilizing synchrophasor measurements”, IEEE Trans. Instrum. Meas., vol. 59, pp. 1562–1570, Jun. 2010. BIOGRAPHIES OF AUTHORS Vahid Farzam was born in Tabriz, Iran, September 1992. He received the B.Sc. and the M.Sc. degrees in electrical engineering from the Islamic Azad University of Tabriz, Tabriz, Iran, in 2013 and 2016, respectively. His research interests arein advanced power electronic, flexible AC transmission system (FACTS), power quality, renewable energy, wide area measurement system, and power system dynamics. Ahad Mokhtarpour was born in Tabriz, Iran, 1979. He received the B.S. degree from University of Tabriz, Tabriz, Iran, M.S.E. degree from Iran University of Science and Technology, Tehran, Iran and Ph.D degree from Islamic Azad University, Science and Research Branch, Tehran, Iran all in Electrical Engineering in 2003, 2005 and 2013, respectively. Currently he is with Departement of Electrical and Computer Engineering,Tabriz Branch, Islamic Azad University Tabriz, Iran as an Assistant Professor. His research interests are in the power quality compensation, FACTS device, distribution network control and reliability.