3. • Power motor control centers (PMCC)
• Motor Control Centers (MCC)
• CLOSE DOOR PANELS / HIGH DENSITY
• Power cum Motor control centers
• Intelligent MCC’s
• APFC Panels
• Control Desk
• Soft starter, Drive & Automation Panel
• Feeder Pillars
• DG Synchronizing & Load Sharing Panels
• Crane Control Panels
PRODUCT RANGE
7. SALIENT FEATURES – DRAWOUT TROLLEY
1. FULLY BOLTED TROLLEY WITH MS RIVET
2. TROLLIES ASSEMBLED THRU’ JIGS & FIXTURES
3. RIGID CONSTRUCTION
4. TOTALLY STANDARDIZED HAVING 50mm PITCH
5. TROLLEY SIZES 150,200……….. 700mm
6. LIBERAL SPACING OF COMPONENTS
7. POWER CONTACTS PRECISELY DESIGNED AND AVAILABLE IN 125A, 250A, 400A & 630A
8. HOUSED IN A VERY STEADY MATERIALS MICROLON – 9312
9. CONTROL TERMINALS PLUG IN TYPE RATING FOR 25A, INSULATION LEVEL
8. Important design features
• Main Busbar/Horizontal busbar chamber at the top of cubical
(Busbars at the bottom can also be supplied on request).
• Vertical busbars/droppers chamber behind the equipment
modules.
• Auxiliary Busbar chamber at the top front side in front of main
busbar chamber.
• Equipment modules or withdrawable Trolleys.
• Cable alley covering full height of each MCC cubicle for
termination of power and control cables.
The MCCs are available in SINGLE FRONT and DOUBLE FRONT
or BACK to BACK execution to meet any specific requirement.
Therefore, Flexi module provide complete solution for modern
industrial applications and power distribution.
MOTOR CONTROL CENTER
12. All units combined and in function
Movable contacting module with mechanical-
interlocking for Test- Disconnected- and Operate-
position
Rotating contacting bolts get
under pressure with the VBS and
cable- module installed in
opposite in the cubicle. Spring
loaded contacting- forces are kept
and neutralized within the IDS
solution itself.
Contacting-module VBS and cable-module together
form up an arc-fault-free-zone
13. Sample for a completed drawer-set
with all the necessary equipment.
The drawer is only a simple metal
sheet, combined with the contacting-
module it forms up a drawer unit at
highest level of safety and functionality
FUNCTIONAL UNITS
18. Installment of the bus-bar-module into the EST-
Wall
Bus-bar-module:
existing of rear- and front-part
rear part is installed by push and drop, no tools are
required
19. Removable shutters close the vertical bus-section
Automatic-shutter for each drawer with connecting-windows.
Installment of the bottom-plate for drawer-
compartment
21. Drawer-units might have fixed plate at the front or individual doors. This is in hand of IDS-partner.
Picture right shows cable compartment with profi-bus-line and vertical control-bus-bar up to 6-poles. This is in
hand of IDS partner how to realize control-wiring.
75mm Pitch
Video
Test Position
Service Position
Rack Out
32. CONFIGURATION
1.Set up density of quantity of drawers:
a.Using full-size drawers of a height of
75mm only.
b.Using fractional drawers:
i.4 drawers in one row minimum 150mm
height
ii.3 drawers in one row minimum 150 mm
height
iii.2 drawers in one row minimum 150 mm
height
36. INDEX
1. Standard Distribution Board Dimensions
2. Standard Distribution Board Construction Details
3. Standard MCC Panel Dimensions
4. Standard MCC Construction Details
5. Standard PCC Panel Dimensions
6. Standard Power Control Center (PCC) Construction Details
7. Constructional features – Cost effectiveness – Variation with existing
design
8. Costing pattern
50. Feeder Dimension – Fixed Starter
STANDARD FEEDER DIMENSION
STARTERS - DOL with MPCB/
MCCB / SDFU
Rating Contactor Switch Feeder Size
Upto 5.5KW 26A 32A 200
7.5- 11KW 30A 63A 250
15-22KW with Ammeter and 3 CT 50A 100A 350
30-45KW with Ammeter and 3 CT 95A 125A 400
55-80 kW with Ammeter and 3 CT 140A 200A 600
90-110kW 225A 250A 800
STARTERS - Star Delta with MPCB/
MCCB / SDFU
Rating Contactor Switch Feeder Size
Upto 5.5KW 25A 32A 300
7.5- 11KW 25A 32A 300
15-22KW with Ammeter and 3 CT 25A 63A 350
30-45KW with Ammeter and 3 CT 70A 100A 450
55-80 kW with Ammeter and 3 CT 95A 160A 500
90-110kW 110A 200A 700
125-150KW 185A 250A 900
160-225KW 265A 400A 900
250-300KW 550A 630A 1200
51. Feeder Dimension – Capacitor
CAPACITOR FEEDER
Rating CAP
Upto 25KVAR 250
> 25KVAR < 50KVAR 350
50KVAR < 75KVAR 500
>75KVAR < 100KVAR 600
Max Cap Banks per Vertical
Normal With Reactor
300 200
ABOVE 100KVAR IN EVERTY VERTICAL PROVIDE MINIMUM 9" EX FAN
AND BELOW 6" EX FAN