132/11 KV SUBSTATION
INDEX
• Introduction
• Classified of substation
• Single line diagram
• Lighting arrester
• Capacitor voltage transformer(CVT)
• Current transformer
• Potential transformer
• Circuit breaker
INDEX
• Relay
• Bus
• Transformer
• Working
• Control panel
• Battery
• Isolator
INTRODUCTION
• The present-day electrical power system is A.C.
i.e. electric power is generated, transmitted and
distributed in the form of alternating current.
• It is delivered to the consumers through a large
network of transmission and distribution.
• At many places in the line of the power system, it
may be desirable and necessary to change some
characteristic (e.g. voltage, A.C. to D.C., frequency,
Power factor etc.) of electric supply.
• This is accomplished by suitable apparatus
called sub-station. For example, generation
voltage (11KV or 6.6KV) at the power station is
stepped up to high voltage (say132KV or
220KV) for transmission of electric power.
• The assembly of apparatus (e.g. transformer
etc.) used for this purpose is the sub-station.
• Similarly, near the consumer’s localities, the
voltage may have to be stepped down to
utilization level.
• This job is again accomplished by a suitable
apparatus called ‘substation’.
TYPE OF SUBSTATION
There are several ways of classifying sub-stations.
However, the two most important way is used to make
substation.
According To The Requirements:- A sub-station
may be called upon to change voltage level or improve
power factor or convert A.C. power into D.C. power etc.
According to the service requirement, sub-stations
may be classified into:
1. Transformer sub-stations
2. Switching sub-stations
3. Converting sub-stations
4. Industrial sub-stations
According To The Constructional Features
• A sub-station has many components (e.g.
circuit breakers, switches, fuses, instruments
etc.) which must be housed properly to ensure
continuous and reliable service. According to
constructional features, the sub-stations are
classified as
1.Indoor sub-station
2.Outdoor sub-station
3.Underground sub-station
SINGLE LINE DIAGRAM
LIGHTENING ARRESTOR
• Lightening arresters are the instruments that are used
in the incoming feeders so that to prevent the high
voltage entering the main station. This high voltage is
very dangerous to the instruments used in the
substation. Even the instruments are very costly, so to
prevent any damage lightening arresters are used. The
lightening arresters do not let the lightening to fall on
the station. If some lightening occurs the arrestors pull
the lightening and ground it to the earth. In any
substation the main important is of protection which is
firstly done by these lightening arrestors. The
lightening arresters are grounded to the earth so that it
can pull the lightening to the ground.
FIGURE OF L.A
(i) Surge Diverter
(ii)Characteristics of The Non Linear Resister Lightning Arrester
WORKING OF L.A.
• Under normal operation, the lightning arrester is off the line
i.e. it conducts no current to earth or the gap is non-conducting.
• On the occurrence of over voltage, the air insulation across the gap
breaks down and an arc is formed providing a low resistance path for
the surge to the ground. In this way, the excess charge on the line due
to the surge is harmlessly conducted through the arrester to the
ground instead of being sent back over the line.
• It is worthwhile to mention the function of non-linear resistor in the
operation of arrester. As the gap sparks over due to over voltage, the
arc would be a short circuit on the power system and may cause
power-follow current in the arrester. Since the characteristic of the
resistor is to offer low resistance to high voltage (or current), it gives
the effect of short circuit. After the surge is over, the resistor offers
high resistance to make the gap non conducting.
CPPACITOR VOLTAGE TRANSFORMER
• A capacitor voltage transformer (CVT) is a transformer
used in power systems to step-down extra high voltage
signals and provide low voltage signals either for
measurement or to operate a protective relay.
• These are high pass Filters (carrier frequency 50KHZ to
500 KHZ) pass carrier frequency to carrier panels and
power frequency parameters to switch yard.
• In its most basic form the device consists of three
parts: two capacitors across which the voltage signal is
split, an inductive element used to tune the device and
a transformer used to isolate and further step down
the voltage.
FIGURE OF C.V.T
Circuit Diagram of C.V.T Capacitor Voltage Transformer
WORKING OF C.V.T
• The device has at least four terminals, a high-voltage
terminal for connection to the high voltage signal, a
ground terminal and at least one set of secondary
terminals for connection to the instrumentation or
protective relay. CVTs are typically single-phase devices
used for measuring voltages in excess of one hundred
KV where the use of voltage transformers would be
uneconomical. In practice the first capacitor, C1, is
often replaced by a stack of capacitors connected in
series. This results in a large voltage drop across the
stack of capacitors, that replaced the first capacitor and
a comparatively small voltage drop across the second
capacitor, C2, and hence the secondary terminals.
WAP TRAP
• Wave trap is an instrument using for trapping of
the wave.
• The function of this wave trap is that it traps the
unwanted waves. Its shape is like a drum.
• It is connected to the main incoming feeder so
that it can trap the waves which may be
dangerous to the instruments in the substation.
• Generally it is used to exclude unwanted
frequency components, such as noise or other
interference, of a wave.
• Line trap also is known as Wave trap.
• What it does is trapping the high frequency
communication signals sent on the line from
the remote substation and diverting them .
• The telecom/ tele protection panel in the
substation control room through coupling
capacitor.
CURRENT TRANSFORMER
• Current transformer is a
current measuring device
used to measure the currents
in high voltage lines directly
by stepping down the
currents to measurable
values by means of
electromagnetic circuit.
WORKING PRINCIPLE OF C.T
• The basic principle induced in designing of current transformers is-
• Primary ampere turns = Secondary ampere turns
• Ip Np = Is Ns
• Where, Ip - Primary current
• Np – Primary Winding Turns
• Is - Secondary Current; Ns – Secondary Winding Turn
• Ampere turns plays very important role in designing current
transformers.
• Current transformers must be connected in series only.
• Current transformer has less no of turns in primary and more no of
turns in secondary.
• The secondary current is directly proportional to primary current.
POTENTIAL TRANSFORMER
• An instrument transformer in which the
secondary voltage.
• in normal conditions of use ,it is substantially
proportional to the primary voltage and differs
in phase from it by an angle.
• which is approximately zero for an appropriate
direction of the connections.
WORKING OF P.T
• The basic principle involved in the designing of Voltage Transformer
is-
• Voltage Ratio = Turns Ratio
• VP / VS = NP / NS
• Thus NS VP = NP VS
• As heavy primary voltages will be reduced to low secondary
voltages.
• it will have more turns in the primary & less turns in the secondary.
• It must always be connected in parallel only.
• Even if we connect it directly from high voltage to earth, it is not
going to be a short circuit as its primary winding has very high
resistance. Its core is a set of assembled laminations.
FIGURE OF P.T
Potential Transformer
Line Diagram of VT.
CIRCUIT BREAKER
• The circuit breakers are used to break the
circuit if any fault occurs in any of the
instrument.
• These circuit breaker breaks for a fault which
can damage other instrument in the station.
• For any unwanted fault over the station we
need to break the line current.
• This is only done automatically by the circuit
breaker.
CIRCUIT BREAKER TYPE
The present trend is up to 33KV, VCBs are
preferred and beyond 33KV, SF6 gas
circuit breakers are preferred.
There are mainly two types of circuit breakers
used for any substations. They are
(a) SF6 circuit breakers,
(b) Vacuum circuit breakers.
SF6 CIRCUIT BREAKER
• Sulphur hexafluoride (SF6) is an inert, heavy gas having
good dielectric and arc extinguishing properties.
• The dielectric strength of the gas increases with
pressure and is more than the dielectric strength of oil
at 3 kg/cm2.
• SF6 is now being widely used in electrical
• equipment like high voltage metal enclosed cables;
high voltage metal clad switchgear, capacitors, circuit
breakers, current transformers, bushings, etc.
• The gas is liquefied at certain low temperature,
liquidification temperature increases with the pressure.
PROPERTY OF SF6
Some of the properties of SF6 are,
• Very high dielectric strength
• High thermal and chemical inertia
• Superior arc extinguishing
• capability
• Low decomposition by arcing
BUS
• The bus is a line in which the incoming feeders come into
and get into the instruments for further step up or step
down.
• The first bus is used for putting the incoming feeders in la
• single line.
• There may be double line in the bus so that if any fault
occurs in the one the other can still have the current and
the supply will not stop.
• The two lines in the bus are separated by a little distance by
a conductor having a connector between them.
• This is so that one can work at a time and the other works
only if the first is having any fault.
TRANSFORMER
• Transformers come in a range of sizes from a thumbnail-sized
coupling transformer.
• hidden inside a stage microphone to huge units weighing
hundreds of tons used to interconnect portions of national
power grids.
• All operate with the same basic principles, although the range
of designs is wide.
• While new technologies have eliminated the need for
transformers in some electronic circuits, transformers are still
found in nearly all electronic devices designed for household
("mains") voltage.
• Transformers are essential for high voltage power
transmission, which makes long distance transmission
economically practical .
BASIC PRINCIPLE OF TRANSFORMER
• The transformer is based on two principles:
• firstly, that an electric current can produce a
magnetic field (electromagnetism) and secondly
that a changing magnetic field within a coil of
wire induces a voltage across the ends of the coil
(electromagnetic induction).
• Changing the current in the primary coil changes
the magnetic flux that is developed.
• The changing magnetic flux induces a voltage in
the secondary coil.
Induction law
which states that, where VS is the
instantaneous voltage, NS is the number
of turns in the secondary coil and Φ equals the
magnetic flux through one turn of the coil.
If the turns of the coil are oriented
perpendicular to the magnetic field lines, the
flux is the
product of the magnetic field strength and the
area A through which it cuts. The area is
constant, being equal to the cross-sectional
area of the transformer core, whereas the
magnetic
field varies with time according to the
excitation of the primary.
CAPACITOR BANK ATTACHED TO THE
BUS
• The capacitor banks are
• used across the bus so that the
• voltage does not get down till at
• the require place.
• A capacitor bank is used in the
• outgoing bus so that it can
• maintain the
• voltage level same in the
• outgoing feeder.
Capacitor Control Is Usually Done To
Achieve The Following Goals
• Reduce losses due to reactive load current.
• Reduce KVA demand, decrease customer energy
consumption.
• Improve voltage profile, and increase
• revenue.
• Indirectly capacitor control
also results in longer equipment
lifetimes because of reduced
equipment stresses.
TRANSFORMER PROTECTION
• Station Transformer: HG Fuse protection on HV side and fuse protection
on LV side and Vent pipe.
• Power transformers up to 7.5MVA:
• HV side: O/L & Directional E/L protection with highest element in O/L
relays.
• LV side: O/L & E/L protection Buchholz Relay OLTC Buchholz Relay
• Power transformers from 8.0MVA and above: HV side O/L & Directional
E/L
• protection with high set element in O/L relays. LV side O/L & E/L
• protection: differential protection Buchholz Relay OLTC Buchholz Relay
OTI, WTI
• and PRV.
• Power transformers from 31.5MVA and above: Over flux protection & LV
WTI in
addition to protection.
FEEDER PROTECTION
• 33KV feeders: Non directional O/L & E/L
protection with highest and IDMT characteristics.
• 132KV feeders: Main protection: Distance
protection. Back up protection: Directional
• O/L & E/L protection.
• 220KV feeders: Main-1 protection: Distance
protection Main-2protection: Distance
protection, LBB protection, pole discrepancy
Relay.
isolator
• Isolator is a mechanical switch which isolates
a part of circuit from system as when
required. Electrical isolators separate a part of
the system from rest for safe maintenance
works.
THANK
YOU!

More Related Content

What's hot

Presentation on 132/33 KVSubstation Training
Presentation on 132/33 KVSubstation Training Presentation on 132/33 KVSubstation Training
Presentation on 132/33 KVSubstation Training Sakshi Rastogi
 
Function relay types
Function relay typesFunction relay types
Function relay typesjawaharramaya
 
132kv substation inplant training seminar
132kv substation inplant training seminar132kv substation inplant training seminar
132kv substation inplant training seminarShrikant Bhansali
 
Substations
SubstationsSubstations
Substationsitfakash
 
DISTANCE PROTECTION RELAY
DISTANCE PROTECTION RELAYDISTANCE PROTECTION RELAY
DISTANCE PROTECTION RELAYRaviraj solanki
 
Unit 04 Protection of generators and transformers
Unit  04 Protection of generators and transformers Unit  04 Protection of generators and transformers
Unit 04 Protection of generators and transformers PremanandDesai
 
220 KV Substation Operation & Maintenance
220 KV Substation Operation & Maintenance220 KV Substation Operation & Maintenance
220 KV Substation Operation & MaintenanceHimansu Pradhan
 
Directional over current relay
Directional over current relayDirectional over current relay
Directional over current relayCS V
 
Facts static voltage & phase angle regulators
Facts   static voltage & phase angle regulatorsFacts   static voltage & phase angle regulators
Facts static voltage & phase angle regulatorsSITCOE, Yadrav
 
EE8701 - HVE - Insulation coordination
EE8701 - HVE - Insulation coordinationEE8701 - HVE - Insulation coordination
EE8701 - HVE - Insulation coordinationKarthikeyanK816516
 
132 33kv substation documentation
132 33kv substation documentation132 33kv substation documentation
132 33kv substation documentationRajashekar Gurrala
 
Electrical substation (grid station)
Electrical substation (grid station)Electrical substation (grid station)
Electrical substation (grid station)Sufi Nouman Riaz
 
24620708 feeder-protection (1)
24620708 feeder-protection (1)24620708 feeder-protection (1)
24620708 feeder-protection (1)Adarsh Verma
 
Power System Protection basics
Power System Protection basicsPower System Protection basics
Power System Protection basicsRajan Singh Tanwar
 
Substation presentation by ram
Substation presentation by ramSubstation presentation by ram
Substation presentation by ramGRBabu Naidu
 
substation internship report
substation internship report substation internship report
substation internship report Arun Thapa
 
single phase energy meter.pptx
single phase energy meter.pptxsingle phase energy meter.pptx
single phase energy meter.pptxtadi1padma
 

What's hot (20)

Presentation on 132/33 KVSubstation Training
Presentation on 132/33 KVSubstation Training Presentation on 132/33 KVSubstation Training
Presentation on 132/33 KVSubstation Training
 
Function relay types
Function relay typesFunction relay types
Function relay types
 
Pilot protection
Pilot protectionPilot protection
Pilot protection
 
132kv substation inplant training seminar
132kv substation inplant training seminar132kv substation inplant training seminar
132kv substation inplant training seminar
 
Substations
SubstationsSubstations
Substations
 
DISTANCE PROTECTION RELAY
DISTANCE PROTECTION RELAYDISTANCE PROTECTION RELAY
DISTANCE PROTECTION RELAY
 
Unit 04 Protection of generators and transformers
Unit  04 Protection of generators and transformers Unit  04 Protection of generators and transformers
Unit 04 Protection of generators and transformers
 
220 KV Substation Operation & Maintenance
220 KV Substation Operation & Maintenance220 KV Substation Operation & Maintenance
220 KV Substation Operation & Maintenance
 
Directional over current relay
Directional over current relayDirectional over current relay
Directional over current relay
 
Facts static voltage & phase angle regulators
Facts   static voltage & phase angle regulatorsFacts   static voltage & phase angle regulators
Facts static voltage & phase angle regulators
 
132 33kv substation
132 33kv substation132 33kv substation
132 33kv substation
 
EE8701 - HVE - Insulation coordination
EE8701 - HVE - Insulation coordinationEE8701 - HVE - Insulation coordination
EE8701 - HVE - Insulation coordination
 
Types of relay
Types of relayTypes of relay
Types of relay
 
132 33kv substation documentation
132 33kv substation documentation132 33kv substation documentation
132 33kv substation documentation
 
Electrical substation (grid station)
Electrical substation (grid station)Electrical substation (grid station)
Electrical substation (grid station)
 
24620708 feeder-protection (1)
24620708 feeder-protection (1)24620708 feeder-protection (1)
24620708 feeder-protection (1)
 
Power System Protection basics
Power System Protection basicsPower System Protection basics
Power System Protection basics
 
Substation presentation by ram
Substation presentation by ramSubstation presentation by ram
Substation presentation by ram
 
substation internship report
substation internship report substation internship report
substation internship report
 
single phase energy meter.pptx
single phase energy meter.pptxsingle phase energy meter.pptx
single phase energy meter.pptx
 

Viewers also liked

vacuum circuit breakers in flexible ac transmission system
vacuum circuit breakers in flexible ac transmission systemvacuum circuit breakers in flexible ac transmission system
vacuum circuit breakers in flexible ac transmission systemKMEA ENGINEERING COLLEGE
 
Training report of 33/11kv substation Mohamdabad, Tundla
Training report of 33/11kv substation Mohamdabad, TundlaTraining report of 33/11kv substation Mohamdabad, Tundla
Training report of 33/11kv substation Mohamdabad, Tundlashashanksltor
 
Protection of transmission lines(encrypted)
Protection of transmission lines(encrypted)Protection of transmission lines(encrypted)
Protection of transmission lines(encrypted)Rohini Haridas
 
industrial training on 132 kv substation
industrial training on 132 kv substationindustrial training on 132 kv substation
industrial training on 132 kv substationpk130992
 
Transmission Line Towers and details
Transmission Line Towers and detailsTransmission Line Towers and details
Transmission Line Towers and detailsMahesh Sontyal
 

Viewers also liked (6)

vacuum circuit breakers in flexible ac transmission system
vacuum circuit breakers in flexible ac transmission systemvacuum circuit breakers in flexible ac transmission system
vacuum circuit breakers in flexible ac transmission system
 
Training report of 33/11kv substation Mohamdabad, Tundla
Training report of 33/11kv substation Mohamdabad, TundlaTraining report of 33/11kv substation Mohamdabad, Tundla
Training report of 33/11kv substation Mohamdabad, Tundla
 
Protection of transmission lines(encrypted)
Protection of transmission lines(encrypted)Protection of transmission lines(encrypted)
Protection of transmission lines(encrypted)
 
Lightning arresters
Lightning arrestersLightning arresters
Lightning arresters
 
industrial training on 132 kv substation
industrial training on 132 kv substationindustrial training on 132 kv substation
industrial training on 132 kv substation
 
Transmission Line Towers and details
Transmission Line Towers and detailsTransmission Line Towers and details
Transmission Line Towers and details
 

Similar to 33/11 KV TRANSMISSION LINE

400 kv Heerapura gss ppt by ishan pdf
400 kv Heerapura gss ppt by ishan pdf 400 kv Heerapura gss ppt by ishan pdf
400 kv Heerapura gss ppt by ishan pdf Ishan Khandelwal
 
220kv gss pindwara(sirohi)
220kv gss pindwara(sirohi)220kv gss pindwara(sirohi)
220kv gss pindwara(sirohi)Pankaj Rawal
 
Load Distribution
Load DistributionLoad Distribution
Load DistributionArpit Gupta
 
Design of substation
Design of substationDesign of substation
Design of substationSayanSarkar55
 
Special transformers
Special transformersSpecial transformers
Special transformersPreet_patel
 
presentation on substation layout and BUS bar arrangement.
presentation on substation layout and BUS bar arrangement.presentation on substation layout and BUS bar arrangement.
presentation on substation layout and BUS bar arrangement.Hemendra Kumar Rajput
 
Indian grid system
Indian grid systemIndian grid system
Indian grid systemPRANAY GUPTA
 
Uttar pradesh power corporation limited
Uttar pradesh power corporation limitedUttar pradesh power corporation limited
Uttar pradesh power corporation limitedVSRAGHU
 
Ppt on 400 kv gss raiser Bikaner- Yatendra Parashar
Ppt on 400 kv gss raiser Bikaner- Yatendra ParasharPpt on 400 kv gss raiser Bikaner- Yatendra Parashar
Ppt on 400 kv gss raiser Bikaner- Yatendra ParasharYatendra Parashar
 
ELECTRIC SUB-STATION IN BRIEF
ELECTRIC SUB-STATION IN BRIEFELECTRIC SUB-STATION IN BRIEF
ELECTRIC SUB-STATION IN BRIEFjang041
 
Switchyard final
Switchyard finalSwitchyard final
Switchyard finalHAIDER ALI
 
Substation Training presentation
Substation Training presentationSubstation Training presentation
Substation Training presentationKamal Mittal
 
ALBA MANUFACTURING OF TRANSFORMERS.pptx
ALBA MANUFACTURING OF TRANSFORMERS.pptxALBA MANUFACTURING OF TRANSFORMERS.pptx
ALBA MANUFACTURING OF TRANSFORMERS.pptxsfQyoom
 
Manish Kumar Gangey- 19ESKEE095.pptx
Manish Kumar Gangey- 19ESKEE095.pptxManish Kumar Gangey- 19ESKEE095.pptx
Manish Kumar Gangey- 19ESKEE095.pptxManish Gangwal
 
Electrical Basics-VBR
Electrical Basics-VBRElectrical Basics-VBR
Electrical Basics-VBRVijay Raskar
 

Similar to 33/11 KV TRANSMISSION LINE (20)

400 kv Heerapura gss ppt by ishan pdf
400 kv Heerapura gss ppt by ishan pdf 400 kv Heerapura gss ppt by ishan pdf
400 kv Heerapura gss ppt by ishan pdf
 
220kv gss pindwara(sirohi)
220kv gss pindwara(sirohi)220kv gss pindwara(sirohi)
220kv gss pindwara(sirohi)
 
Load Distribution
Load DistributionLoad Distribution
Load Distribution
 
Design of substation
Design of substationDesign of substation
Design of substation
 
Special transformers
Special transformersSpecial transformers
Special transformers
 
presentation on substation layout and BUS bar arrangement.
presentation on substation layout and BUS bar arrangement.presentation on substation layout and BUS bar arrangement.
presentation on substation layout and BUS bar arrangement.
 
33kv substation
33kv substation33kv substation
33kv substation
 
132 KV GSS CHAMBAL JAIPUR
132 KV GSS CHAMBAL JAIPUR132 KV GSS CHAMBAL JAIPUR
132 KV GSS CHAMBAL JAIPUR
 
Power quality 2
Power quality 2Power quality 2
Power quality 2
 
Indian grid system
Indian grid systemIndian grid system
Indian grid system
 
Uttar pradesh power corporation limited
Uttar pradesh power corporation limitedUttar pradesh power corporation limited
Uttar pradesh power corporation limited
 
Ppt on 400 kv gss raiser Bikaner- Yatendra Parashar
Ppt on 400 kv gss raiser Bikaner- Yatendra ParasharPpt on 400 kv gss raiser Bikaner- Yatendra Parashar
Ppt on 400 kv gss raiser Bikaner- Yatendra Parashar
 
rough.pptx
rough.pptxrough.pptx
rough.pptx
 
ELECTRIC SUB-STATION IN BRIEF
ELECTRIC SUB-STATION IN BRIEFELECTRIC SUB-STATION IN BRIEF
ELECTRIC SUB-STATION IN BRIEF
 
Switchyard final
Switchyard finalSwitchyard final
Switchyard final
 
Substation Training presentation
Substation Training presentationSubstation Training presentation
Substation Training presentation
 
ALBA MANUFACTURING OF TRANSFORMERS.pptx
ALBA MANUFACTURING OF TRANSFORMERS.pptxALBA MANUFACTURING OF TRANSFORMERS.pptx
ALBA MANUFACTURING OF TRANSFORMERS.pptx
 
Manish Kumar Gangey- 19ESKEE095.pptx
Manish Kumar Gangey- 19ESKEE095.pptxManish Kumar Gangey- 19ESKEE095.pptx
Manish Kumar Gangey- 19ESKEE095.pptx
 
Ashish.pptx
Ashish.pptxAshish.pptx
Ashish.pptx
 
Electrical Basics-VBR
Electrical Basics-VBRElectrical Basics-VBR
Electrical Basics-VBR
 

Recently uploaded

High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escortsranjana rawat
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
KubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlyKubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlysanyuktamishra911
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxAsutosh Ranjan
 
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptx
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptxBSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptx
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptxfenichawla
 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations120cr0395
 
UNIT-III FMM. DIMENSIONAL ANALYSIS
UNIT-III FMM.        DIMENSIONAL ANALYSISUNIT-III FMM.        DIMENSIONAL ANALYSIS
UNIT-III FMM. DIMENSIONAL ANALYSISrknatarajan
 
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Bookingdharasingh5698
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
AKTU Computer Networks notes --- Unit 3.pdf
AKTU Computer Networks notes ---  Unit 3.pdfAKTU Computer Networks notes ---  Unit 3.pdf
AKTU Computer Networks notes --- Unit 3.pdfankushspencer015
 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxpranjaldaimarysona
 
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordAsst.prof M.Gokilavani
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...ranjana rawat
 
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Christo Ananth
 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Dr.Costas Sachpazis
 
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...roncy bisnoi
 
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...ranjana rawat
 

Recently uploaded (20)

High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
 
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
KubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlyKubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghly
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptx
 
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptx
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptxBSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptx
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptx
 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations
 
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINEDJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
 
UNIT-III FMM. DIMENSIONAL ANALYSIS
UNIT-III FMM.        DIMENSIONAL ANALYSISUNIT-III FMM.        DIMENSIONAL ANALYSIS
UNIT-III FMM. DIMENSIONAL ANALYSIS
 
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
 
AKTU Computer Networks notes --- Unit 3.pdf
AKTU Computer Networks notes ---  Unit 3.pdfAKTU Computer Networks notes ---  Unit 3.pdf
AKTU Computer Networks notes --- Unit 3.pdf
 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptx
 
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
 
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
 
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
 
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
 
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
 

33/11 KV TRANSMISSION LINE

  • 1.
  • 3. INDEX • Introduction • Classified of substation • Single line diagram • Lighting arrester • Capacitor voltage transformer(CVT) • Current transformer • Potential transformer • Circuit breaker
  • 4. INDEX • Relay • Bus • Transformer • Working • Control panel • Battery • Isolator
  • 5. INTRODUCTION • The present-day electrical power system is A.C. i.e. electric power is generated, transmitted and distributed in the form of alternating current. • It is delivered to the consumers through a large network of transmission and distribution. • At many places in the line of the power system, it may be desirable and necessary to change some characteristic (e.g. voltage, A.C. to D.C., frequency, Power factor etc.) of electric supply.
  • 6. • This is accomplished by suitable apparatus called sub-station. For example, generation voltage (11KV or 6.6KV) at the power station is stepped up to high voltage (say132KV or 220KV) for transmission of electric power. • The assembly of apparatus (e.g. transformer etc.) used for this purpose is the sub-station. • Similarly, near the consumer’s localities, the voltage may have to be stepped down to utilization level. • This job is again accomplished by a suitable apparatus called ‘substation’.
  • 7. TYPE OF SUBSTATION There are several ways of classifying sub-stations. However, the two most important way is used to make substation. According To The Requirements:- A sub-station may be called upon to change voltage level or improve power factor or convert A.C. power into D.C. power etc. According to the service requirement, sub-stations may be classified into: 1. Transformer sub-stations 2. Switching sub-stations 3. Converting sub-stations 4. Industrial sub-stations
  • 8. According To The Constructional Features • A sub-station has many components (e.g. circuit breakers, switches, fuses, instruments etc.) which must be housed properly to ensure continuous and reliable service. According to constructional features, the sub-stations are classified as 1.Indoor sub-station 2.Outdoor sub-station 3.Underground sub-station
  • 10. LIGHTENING ARRESTOR • Lightening arresters are the instruments that are used in the incoming feeders so that to prevent the high voltage entering the main station. This high voltage is very dangerous to the instruments used in the substation. Even the instruments are very costly, so to prevent any damage lightening arresters are used. The lightening arresters do not let the lightening to fall on the station. If some lightening occurs the arrestors pull the lightening and ground it to the earth. In any substation the main important is of protection which is firstly done by these lightening arrestors. The lightening arresters are grounded to the earth so that it can pull the lightening to the ground.
  • 11. FIGURE OF L.A (i) Surge Diverter (ii)Characteristics of The Non Linear Resister Lightning Arrester
  • 12. WORKING OF L.A. • Under normal operation, the lightning arrester is off the line i.e. it conducts no current to earth or the gap is non-conducting. • On the occurrence of over voltage, the air insulation across the gap breaks down and an arc is formed providing a low resistance path for the surge to the ground. In this way, the excess charge on the line due to the surge is harmlessly conducted through the arrester to the ground instead of being sent back over the line. • It is worthwhile to mention the function of non-linear resistor in the operation of arrester. As the gap sparks over due to over voltage, the arc would be a short circuit on the power system and may cause power-follow current in the arrester. Since the characteristic of the resistor is to offer low resistance to high voltage (or current), it gives the effect of short circuit. After the surge is over, the resistor offers high resistance to make the gap non conducting.
  • 13. CPPACITOR VOLTAGE TRANSFORMER • A capacitor voltage transformer (CVT) is a transformer used in power systems to step-down extra high voltage signals and provide low voltage signals either for measurement or to operate a protective relay. • These are high pass Filters (carrier frequency 50KHZ to 500 KHZ) pass carrier frequency to carrier panels and power frequency parameters to switch yard. • In its most basic form the device consists of three parts: two capacitors across which the voltage signal is split, an inductive element used to tune the device and a transformer used to isolate and further step down the voltage.
  • 14. FIGURE OF C.V.T Circuit Diagram of C.V.T Capacitor Voltage Transformer
  • 15. WORKING OF C.V.T • The device has at least four terminals, a high-voltage terminal for connection to the high voltage signal, a ground terminal and at least one set of secondary terminals for connection to the instrumentation or protective relay. CVTs are typically single-phase devices used for measuring voltages in excess of one hundred KV where the use of voltage transformers would be uneconomical. In practice the first capacitor, C1, is often replaced by a stack of capacitors connected in series. This results in a large voltage drop across the stack of capacitors, that replaced the first capacitor and a comparatively small voltage drop across the second capacitor, C2, and hence the secondary terminals.
  • 16. WAP TRAP • Wave trap is an instrument using for trapping of the wave. • The function of this wave trap is that it traps the unwanted waves. Its shape is like a drum. • It is connected to the main incoming feeder so that it can trap the waves which may be dangerous to the instruments in the substation. • Generally it is used to exclude unwanted frequency components, such as noise or other interference, of a wave.
  • 17. • Line trap also is known as Wave trap. • What it does is trapping the high frequency communication signals sent on the line from the remote substation and diverting them . • The telecom/ tele protection panel in the substation control room through coupling capacitor.
  • 18. CURRENT TRANSFORMER • Current transformer is a current measuring device used to measure the currents in high voltage lines directly by stepping down the currents to measurable values by means of electromagnetic circuit.
  • 19. WORKING PRINCIPLE OF C.T • The basic principle induced in designing of current transformers is- • Primary ampere turns = Secondary ampere turns • Ip Np = Is Ns • Where, Ip - Primary current • Np – Primary Winding Turns • Is - Secondary Current; Ns – Secondary Winding Turn • Ampere turns plays very important role in designing current transformers. • Current transformers must be connected in series only. • Current transformer has less no of turns in primary and more no of turns in secondary. • The secondary current is directly proportional to primary current.
  • 20. POTENTIAL TRANSFORMER • An instrument transformer in which the secondary voltage. • in normal conditions of use ,it is substantially proportional to the primary voltage and differs in phase from it by an angle. • which is approximately zero for an appropriate direction of the connections.
  • 21. WORKING OF P.T • The basic principle involved in the designing of Voltage Transformer is- • Voltage Ratio = Turns Ratio • VP / VS = NP / NS • Thus NS VP = NP VS • As heavy primary voltages will be reduced to low secondary voltages. • it will have more turns in the primary & less turns in the secondary. • It must always be connected in parallel only. • Even if we connect it directly from high voltage to earth, it is not going to be a short circuit as its primary winding has very high resistance. Its core is a set of assembled laminations.
  • 22. FIGURE OF P.T Potential Transformer Line Diagram of VT.
  • 23. CIRCUIT BREAKER • The circuit breakers are used to break the circuit if any fault occurs in any of the instrument. • These circuit breaker breaks for a fault which can damage other instrument in the station. • For any unwanted fault over the station we need to break the line current. • This is only done automatically by the circuit breaker.
  • 24. CIRCUIT BREAKER TYPE The present trend is up to 33KV, VCBs are preferred and beyond 33KV, SF6 gas circuit breakers are preferred. There are mainly two types of circuit breakers used for any substations. They are (a) SF6 circuit breakers, (b) Vacuum circuit breakers.
  • 25. SF6 CIRCUIT BREAKER • Sulphur hexafluoride (SF6) is an inert, heavy gas having good dielectric and arc extinguishing properties. • The dielectric strength of the gas increases with pressure and is more than the dielectric strength of oil at 3 kg/cm2. • SF6 is now being widely used in electrical • equipment like high voltage metal enclosed cables; high voltage metal clad switchgear, capacitors, circuit breakers, current transformers, bushings, etc. • The gas is liquefied at certain low temperature, liquidification temperature increases with the pressure.
  • 26. PROPERTY OF SF6 Some of the properties of SF6 are, • Very high dielectric strength • High thermal and chemical inertia • Superior arc extinguishing • capability • Low decomposition by arcing
  • 27. BUS • The bus is a line in which the incoming feeders come into and get into the instruments for further step up or step down. • The first bus is used for putting the incoming feeders in la • single line. • There may be double line in the bus so that if any fault occurs in the one the other can still have the current and the supply will not stop. • The two lines in the bus are separated by a little distance by a conductor having a connector between them. • This is so that one can work at a time and the other works only if the first is having any fault.
  • 28. TRANSFORMER • Transformers come in a range of sizes from a thumbnail-sized coupling transformer. • hidden inside a stage microphone to huge units weighing hundreds of tons used to interconnect portions of national power grids. • All operate with the same basic principles, although the range of designs is wide. • While new technologies have eliminated the need for transformers in some electronic circuits, transformers are still found in nearly all electronic devices designed for household ("mains") voltage. • Transformers are essential for high voltage power transmission, which makes long distance transmission economically practical .
  • 29. BASIC PRINCIPLE OF TRANSFORMER • The transformer is based on two principles: • firstly, that an electric current can produce a magnetic field (electromagnetism) and secondly that a changing magnetic field within a coil of wire induces a voltage across the ends of the coil (electromagnetic induction). • Changing the current in the primary coil changes the magnetic flux that is developed. • The changing magnetic flux induces a voltage in the secondary coil.
  • 30. Induction law which states that, where VS is the instantaneous voltage, NS is the number of turns in the secondary coil and Φ equals the magnetic flux through one turn of the coil. If the turns of the coil are oriented perpendicular to the magnetic field lines, the flux is the product of the magnetic field strength and the area A through which it cuts. The area is constant, being equal to the cross-sectional area of the transformer core, whereas the magnetic field varies with time according to the excitation of the primary.
  • 31. CAPACITOR BANK ATTACHED TO THE BUS • The capacitor banks are • used across the bus so that the • voltage does not get down till at • the require place. • A capacitor bank is used in the • outgoing bus so that it can • maintain the • voltage level same in the • outgoing feeder.
  • 32. Capacitor Control Is Usually Done To Achieve The Following Goals • Reduce losses due to reactive load current. • Reduce KVA demand, decrease customer energy consumption. • Improve voltage profile, and increase • revenue. • Indirectly capacitor control also results in longer equipment lifetimes because of reduced equipment stresses.
  • 33. TRANSFORMER PROTECTION • Station Transformer: HG Fuse protection on HV side and fuse protection on LV side and Vent pipe. • Power transformers up to 7.5MVA: • HV side: O/L & Directional E/L protection with highest element in O/L relays. • LV side: O/L & E/L protection Buchholz Relay OLTC Buchholz Relay • Power transformers from 8.0MVA and above: HV side O/L & Directional E/L • protection with high set element in O/L relays. LV side O/L & E/L • protection: differential protection Buchholz Relay OLTC Buchholz Relay OTI, WTI • and PRV. • Power transformers from 31.5MVA and above: Over flux protection & LV WTI in addition to protection.
  • 34. FEEDER PROTECTION • 33KV feeders: Non directional O/L & E/L protection with highest and IDMT characteristics. • 132KV feeders: Main protection: Distance protection. Back up protection: Directional • O/L & E/L protection. • 220KV feeders: Main-1 protection: Distance protection Main-2protection: Distance protection, LBB protection, pole discrepancy Relay.
  • 35. isolator • Isolator is a mechanical switch which isolates a part of circuit from system as when required. Electrical isolators separate a part of the system from rest for safe maintenance works.