Electric Equipment
Leader in Electrics & Automation
Prime-MEC
LS HRC Power Fuseswww.dienhathe.xyz
www.dienhathe.vn
3.6 7.2 24
56� 85� 90� 45� 70� 89� 47� 85� 85�
6.5 7.2 7.3 5.2 6.0 7.3 5.1 7.2 7.2
0.07 ~ 0.15
�Test current : 40kA �Basis : 63A
�I peak : Let through current(under the short circuit test)
Rated voltage(kV)
Initiation of
arcing(degree)
Ipeak(kA)
Power Factor
Current without
Power Fuse
(40kA ms)
Ipeak
Let through current
Below 0.5 Cycle
1
www.dienhathe.xyz
www.dienhathe.vn
2
Features
�The LS HRC Power Fuses belong to the PRIME MEC series.
It interrupts high currents before the first loop of fault
current has reached its natural peak value and therefore cuts
down the required withstand capacity of the associated
equipment on the electric system.
�Though small in size, it has a high breaking capacity and
its enclosed type is suitable for use inside of the panel board.
�PRIME MEC fuses are equipped with striker pins for trip
indicators as well as for operating the related load break switches.
�Link type fuse holder enables easy maintenance and high stability when replacing the fuses.
�With Fuse Checker, checking the conditions of a fuse in the panel board or by telecommunication is possible.(Optional)
Applied standards
�IEC 282-1, DIN 43625, BS 2692, KSC 4612
Applications
�Transformer protection
- To protect against short circuit current in the secondary part of
a transformer and fault current in the transformer circuit.
�Condenser protection
- To protect against fault current in the condenser circuit.
�Motor protection
- To protect against fault current in the motor circuit
�Cable protection
- Fault current protection secures the cable
www.dienhathe.xyz
www.dienhathe.vn
3
LS HRC Power Fuses
Ratings
5
10
20
30
40
50
63
75
100
125
160
200
160
200
5
10
16
20
25
30
40
50
63
75
100
125
160
200
LFL-3/6G-5B
LFL-3/6G-10B
LFL-3/6G-20B
LFL-3/6G-30B
LFL-3/6G-40B
LFL-3/6G-50B
LFL-3/6G-60B
LFL-3/6G-75B
LFL-3/6G-100B
LFL-3/6G-125B
LFL-3G-160B
LFL-3G-200B
LFL-6G-160B
LFL-6G-200B
LFL-20G-5B
LFL-20G-10B
LFL-20G-16B
LFL-20G-20B
LFL-20G-25B
LFL-20G-30B
LFL-20G-40B
LFL-20G-50B
LFL-20G-60B
LFL-20G-75C
LFL-20G-100C
LFL-20G-125B
LFL-20G-160B
LFL-20G-200B
LFH-6G-D1HB
LFH-20G-D2HB
LFH-20G-D2HC
LFH-6G-D2HB
3.6/7.2
3.6
7.2
24
7.2 60
12524
40
40
25
100
200
200
5In
5In
6In
192 55 1
192 77 2
292 77 2.8
442
442
442
537
87
87
5.1
5.5
55
77
2
4.2
Note) 1. Application site : Indoor use
2. Refer to the column "B" in the table for inside diameters of Hook rings
3. Models highlighted can be applied to 3.6 or 7.2kV
Type
Rated
voltage
(kV)
Rated
current
(A)
Breaking
current
(kA, rms)
Minimum
breaking
current (A)
Dimensions Weight
(kg)
Type
Rated
voltage
(kV)
Rated
current
(A)
Insulation
level
(BIL, kV)A B
Fuse link Fuse holder
www.dienhathe.xyz
www.dienhathe.vn
4
Conditions of selection
Basic conditions for selecting the Power Fuses
�The rated current of a Power Fuse should be higher than sum of the total rated current of
the electric equipment on the circuit.
�Back-up protection with electric equipment on the circuit.
- Set the operating characteristics of the Power Fuses to satisfy the over-current characteristics of the protected loads on the circuit. Also,
set the occurred calories, by the l2
t operation, to be smaller than the short-circuit intensity of the electric equipment and circuit.
- When using the Power Fuses for backup usage with other protective equipment, set the operating times of the protective equipment
below the minimum breaking current to be faster than those of the Power Fuses.
�The inrush current of a transformer is selected assuming that the current is 10 time that of the full-load transformer current in 0.1sec.
�The rated current of the Power Fuses is selected to continuously flow at 1.5time of the transformer rated current.
�Power Fuses for proteting against short-circuit in the secondary part of a transformer are selected assuming that the current is 25times that of
the transformer rated current in 2seconds.
Circuit Transformer Circuit Transformer Circuit Transformer
Phase voltage capacity Applied fuses voltage capacity Applied fuses voltage capacity Applied fuses
(kV) (kVA) (kV) (kVA) (kV) (kVA)
4~8 LFL-3/6G-5B 8~16 LFL-3/6G-5B 20~43 LFL-20G-5B
6~13 LFL-3/6G-10B 13~25 LFL-3/6G-10B 43~90 LFL-20G-10B
- - - - 87~180 LFL-20G-16B
15~31 LFL-3/6G-20B 30~62 LFL-3/6G-20B 99~206 LFL-20G-20B
- - - - 130~269 LFL-20G-25B
21~42 LFL-3/6G-30B 40~84 LFL-3/6G-30B 149~310 LFL-20G-30B
40~82 LFL-3/6G-40B 80~165 LFL-3/6G-40B 267~557 LFL-20G-40B
1фф 3.3 49~102 LFL-3/6G-50B 6.6 98~204 LFL-3/6G-50B 22.9 345~719 LFL-20G-50B
66~137 LFL-3/6G-60B 132~275 LFL-3/6G-60B 430~897 LFL-20G-60B
68~165 LFL-3/6G-75B 134~330 LFL-3/6G-75B 580~1145 LFL-20G-75B
128~220 LFL-3/6G-100B 256~440 LFL-3/6G-100B 923~1527 LFL-20G-100B
151~275 LFL-3/6G-125B 302~550 LFL-3/6G-125B 1364~1908 LFL-20G-125B
211~352 LFL-3/6G-160B 425~704 LFL-3/6G-160B 2125~2443 LFL-20G-160B
265~4402 LFL-3/6G-200B 437~880 LFL-3/6G-200B 2650~3050 LFL-20G-200B
6.7~14 LFL-3/6G-5B 13~28 LFL-3/6G-5B 36~75 LFL-20G-5B
11~22 LFL-3/6G-10B 21~44 LFL-3/6G-10B 75~157 LFL-20G-10B
- - - - 151~313 LFL-20G-16B
25~53 LFL-3/6G-20B 51~107 LFL-3/6G-20B 172~358 LFL-20G-20B
- - - - 224~466 LFL-20G-25B
35~73 LFL-3/6G-30B 70~145 LFL-3/6G-30B 258~538 LFL-20G-30B
69~143 LFL-3/6G-40B 137~286 LFL-3/6G-40B 464~965 LFL-20G-40B
3фф 3.3
85~77 LFL-3/6G-50B
6.6
170~354 LFL-3/6G-50B
22.9
598~1246 LFL-20G-50B
114~238 LFL-3/6G-60B 229~476 LFL-3/6G-60B 745~1554 LFL-20G-60B
117~285 LFL-3/6G-75B 233~571 LFL-3/6G-75B 1000~1983 LFL-20G-75B
222~381 LFL-3/6G-100B 443~762 LFL-3/6G-100B 1600~2645 LFL-20G-100B
261~476 LFL-3/6G-125B 522~952 LFL-3/6G-125B 2362~3304 LFL-20G-125B
365~610 LFL-3G-160B 735~1220 LFL-6G-160B 3680~4232 LFL-20G-160B
459~762 LFL-3G-200B 755~1520 LFL-6G-200B 4593~5287 LFL-20G-200B
For transformer protection
Selecting
conditions
Note) 1. Models highlighted can be applied to 3.6 or 7.2kV
www.dienhathe.xyz
www.dienhathe.vn
5
LS HRC Power Fuses
Conditions of selection
For condenser protection
For motor protection
�Under the short-circuit condition, the power fuse
breaks the circuit in high speed. Therefore, with
relatively high rated current, the Power Fuse
protects small size cables.
�Selected to protect from above 10 times of the
short-circuit current.
Circuit Transformer Circuit Condenser Circuit Condenser
Phase voltage capacity Applied fuses voltage capacity Applied fuses voltage capacity Applied fuses
(kV) (kVA) (kV) (kVA) (kV) (kVA)
~9.8 LFL-3/6G-5B ~19 LFL-3/6G-5B ~46 LFL-20G-5B
9.8~12 LFL-3/6G-10B 19~24 LFL-3/6G-10B 46~83 LFL-20G-10B
- - - - 64~172 LFL-20G-16B
12~31 LFL-3/6G-20B 24~61 LFL-3/6G-20B 83~203 LFL-20G-20B
- - - - 193~272 LFL-20G-25B
31~46 LFL-3/6G-30B 61~92 LFL-3/6G-30B 203~317 LFL-20G-30B
3фф 3.3 46~64 LFL-3/6G-40B 6.6 92~128 LFL-3/6G-40B 22.9 317~425 LFL-20G-40B
64~81 LFL-3/6G-50B 128~163 LFL-3/6G-50B 425~564 LFL-20G-50B
81~105 LFL-3/6G-60B 163~210 LFL-3/6G-60B 564~710 LFL-20G-60B
105~150 LFL-3/6G-75B 210~300 LFL-3/6G-75B 710~1021 LFL-20G-75B
150~222 LFL-3/6G-100B 300~445 LFL-3/6G-100B 1021~1655 LFL-20G-100B
222~275 LFL-3/6G-125B 445~550 LFL-3/6G-125B 1655~2370 LFL-20G-125B
275~370 LFL-3G-160B 550~742 LFL-6G-160B 2370~3170 LFL-20G-160B
370~500 LFL-3G-200B 742~1000 LFL-6G-200B 3170~4000 LFL-20G-200B
Circuit Circuit
Phase voltage Motor output Applied fuses voltage Motor output Applied fuses
(kV) (kVA) (kV) (kVA)
4.3~7.2 LFL-3/6G-5B 8.7~15 LFL-3/6G-5B
7.2~19 LFL-3/6G-10B 15~25 LFL-3/6G-10B
19~39 LFL-3/6G-20B 25~65 LFL-3/6G-20B
34~64 LFL-3/6G-30B 65~88 LFL-3/6G-30B
64~87 LFL-3/6G-40B 88~183 LFL-3/6G-40B
3фф 3.3
87~109 LFL-3/6G-50B
6.6
183~225 LFL-3/6G-50B
106~149 LFL-3/6G-60B 219~304 LFL-3/6G-60B
139~199 LFL-3/6G-75B 288~407 LFL-3/6G-75B
185~288 LFL-3/6G-100B 377~604 LFL-3/6G-100B
229~344 LFL-3/6G-125B 474~721 LFL-3/6G-125B
268~471 LFL-3G-160B 614~1015 LFL-6G-160B
293~518 LFL-3G-200B 958~1502 LFL-6G-200B
For cable protection
Cable Rated(A)
diameter current of PF
(mm2) (A)
0.8 40
1.6 50
2 75
3.5 100
5.5 150
8 200
22 200
�The starting current of a motor is selected to withstand 5 times of
the full-loads current in 10sec.
Selecting
conditions
�The inrush current of a condenser is selected to withstand 71time of the condenser rated current in 0.002sec.
�The rated current of the Power Fuses is selected to continuously flow at 1.43 times of the condenser rated current.
Selecting
conditions
Note) 1. Models highlighted can be applied to 3.6 or 7.2kV
Note) 1. Models highlighted can be applied to 3.6 or 7.2kV
www.dienhathe.xyz
www.dienhathe.vn
6
Characteristics curves
1000
800
600
400
200
100
80
60
40
20
10
8
6
4
2
1
0.8
0.6
0.4
0.2
0.1
0.08
0.06
0.04
0.02
0.01
125A
100A
75A
50A
63A
40A
30A
20A
10A
5A
0.02
0.04
0.06
0.08
0.1
0.2
0.4
0.6
0.8
1
2
4
6
8
10
20
40
100
Cut-offcurrent(peakvalue:kA)→→
Prospective breaking current(rms : kA) →→
1000
800
600
400
200
100
80
60
40
20
10
8
6
4
2
1
0.8
0.6
0.4
0.2
0.1
0.08
0.06
0.04
0.02
0.01
2
4
6
8
10
20
40
60
80
100
200
400
600
800
1000
2000
4000
5A
10A
20A
30A
40A
50A
125A
100A
75A
63A
Operatingtime(sec)→→
Prospective rated current(rms : A) →→
1000
800
600
400
200
100
80
60
40
20
10
8
6
4
2
1
0.8
0.6
0.4
0.2
0.1
0.08
0.06
0.04
0.02
0.01
200A
160A
0.02
0.04
0.06
0.08
0.1
0.2
0.4
0.6
0.8
1
2
4
6
8
10
20
40
100
Cut-offcurrent(peakvalue:kA)→→
Prospective breaking current(rms : kA) →→
1000
800
600
400
200
100
80
60
40
20
10
8
6
4
2
1
0.8
0.6
0.4
0.2
0.1
0.08
0.06
0.04
0.02
0.01
2
4
6
8
10
20
40
60
80
100
200
400
600
800
1000
2000
4000
200A
160A
Operatingtime(sec)→→
Prospective rated current(rms : A) →→
3.6/7.2kV Cut-off characteristics 3.6/7.2kV Pre-arcing time-
current characteristics
3.6kV Cut-off characteristics 3.6kV Pre-arcing time-
current characteristics
www.dienhathe.xyz
www.dienhathe.vn
7
Characteristics curves
LS HRC Power Fuses
1000
800
600
400
200
100
80
60
40
20
10
8
6
4
2
1
0.8
0.6
0.4
0.2
0.1
0.08
0.06
0.04
0.02
0.01
0.02
0.04
0.06
0.08
0.1
0.2
0.4
0.6
0.8
1
2
4
6
8
10
20
40
100
200A
160A
Cut-offcurrent(peakvalue:kA)→→
Prospective breaking current(rms : kA) →→
1000
800
600
400
200
100
80
60
40
20
10
8
6
4
2
1
0.8
0.6
0.4
0.2
0.1
0.08
0.06
0.04
0.02
0.01
2
4
6
8
10
20
40
60
80
100
200
400
600
800
1000
2000
4000
6000
8000
10000
200A
160A
Operatingtime(sec)→→
Prospective rated current(rms : A) →→
7.2kV Cut-off characteristics 7.2kV Pre-arcing time-
current characteristics
Cut-offcurrent(peakvalue:kA)→→
Prospective breaking current(rms : kA) →→
1000
800
600
400
200
100
80
60
40
20
10
8
6
4
2
1
0.8
0.6
0.4
0.2
0.1
0.08
0.06
0.04
0.02
0.01
2
4
6
8
10
20
40
60
80
100
200
400
600
800
1000
2000
4000
8000
6000
10000
Operatingtime(sec)→→
Prospective rated current(rms : A) →→
24kV Cut-off characteristics 24kV Pre-arcing time-
current characteristics
www.dienhathe.xyz
www.dienhathe.vn
8
Fuse holder dimensions
Indoor use Power Fuse holder
LFH-6G-D1HB Type
Indoor use Power Fuse holder
LFH-6G-D2HB Type
Fuse size(A) B C
ф 55 242.3 376
ф 77 253.3 380
C (Peak height in open condition)
Fuse checker
ф12.5(Hold)
Mounting hold
Earth hole
Hook Ring
Fuse checker
ф12.5(Hold)
Mounting hole
Earth hole
Below1
456.5 (Peak height in open condition)
Hook Ring
www.dienhathe.xyz
www.dienhathe.vn
Rated Rated Circuit Insulation Dimensions(mm)
PH Holder type voltage current voltage level Applied fuse
(kV) (A) (kV) (BIL, kV) A B C D E F G
3.3 45 421 250 376 323 477 97 130 LFL-3/6G-5B, 10B, 20B, 30B, 40B, 50B
3.3 45 421 254 380 334 477 97 130 LFL-3/6G-60B, 75B, 100B
LFH-6G-D1HB 7.2 100
6.6 60 421 250 376 349 503 123 158 LFL-3/6G-5B, 10B, 20B, 30B, 40B, 50B
6.6 60 421 254 380 360 503 123 158 LFL-3/6G-60B, 75B, 100B
LFH-6G-D2HB 7.2 200
3.3 45 521 254 457 334 564 97 130 LFL-3/6G-125B, LFL-3G-160B, 200B
6.6 60 521 254 457 360 590 123 158 LFL-3/6G-125B, LFL-6G-160B, 200B
671 363 688 586 934 - 260 LFL-20G-5B, 10B, 16B, 20B
LFH-20G-D2HB
24 200 22.9 125
671 374 692 597 957 - 260 LFL-20G-25B, 30B, 40B, 50B, 60B
671 379 695 602 957 - 260 LFL-20G-75C, 100C 125B, 160B
LFH-6G-D2HB 766 379 768 602 957 - 260 LFL-20G-200B
9
LS HRC Power Fuses
Fuse holder dimensions
Indoor use Power Fuse holder
LFH20-D2HB(C) Type
C (Peak height in open condition)
Fuse checker
ф12.5(Hold)
Mounting hold
Earth hole
Below1
Hook Ring
Power Fuse holder
Panel Conductor Panel
Fuse size(A) B C
ф 55 362.3 687.5
ф 77 373.3 691.6
ф 87 378.3 695(768)
Note) Dimension in ( ) is for LFH-20G-D2HC
D: Minimum insulation
distance in opening
E: Minimum insulation
distance in closing
www.dienhathe.xyz
www.dienhathe.vn
Operatingweight(kgf)→→
Operating distance(mm) →→
Operating characteristics of the Power Fuses
The characteristics of the Power Fuses are native and fixed. Therefore
it can not be regulated like a circuit breaker or over-load relay. When
ordering, please select the Power Fuses with proper current and
operating characteristics by considering its usage and circuit condition.
Breaking a small current.
Power Fuses are not adequate to protect small current. So, the
manufacturer specifies and guarantees the minimum breaking current
by regulation.
1) Select the rated current of the Power Fuse, which does not
operate below the minimum breaking current.
2) Protect the current below the minimum value by use of other
protective equipment.
10
Striker operating characteristics & Ordering information
Striker operating characteristics
P/F Link
P/F Holder
Types of P/F Link & P/F Holder
Model name General use Revision No.Rated voltage
3/6 3.6/7.2kV
3 3.6kV
6 7.2kV
20 24kV
Rated current
5 5A
10 10A
16 16A
20 20A
25 25A
30 30A
40 40A
50 50A
60 63A
75 75A
100 100A
125 125A
160 160A
200 200A
Model name General use Indoor use
LFL 6 G
LFH 6 G D 1H B 1 5
50 B
Rated voltage
3/6 3.6/7.2kV
20 24kV
Rated current
1H 100A
2H 200A
Fuse Checker
0 Without
1 With
Hook Ring
5 ∅ 55
7 ∅ 77
8 ∅ 87
Revision No.
B -
C 200A(24kV)
www.dienhathe.xyz
www.dienhathe.vn
www.lsis.biz
�� For your safety, please read user's manual thoroughly before operating.
�� Contact the nearest authorized service facility for examination, repair, or adjustment.
�� Please contact a qualified service technician when you need maintenance.
Do not disassemble or repair by yourself!
�� Any maintenance and inspection shall be performed by the personnel having expertise concerned.Safety Instructions
Leader in Electrics & Automation
Specifications in this catalog are subject to change without notice due to
continuous product development and improvement.
�� HEAD OFFICE
Yonsei Jaedan Severance Bldg., 84-11, Namdaemunno 5ga,
Jung-gu, Seoul, 100-753, Korea
Tel. (82-2)2034-4870
Fax. (82-2)2034-4713
�� CHEONG-JU PLANT
Cheong-Ju Plant #1, Song Jung Dong, Hung Duk Ku,
Cheong Ju, 361-720, Korea
2008. 01 LS HRC Power Fuses(E) 2003. 08/(03) 2008. 01 Printed in Korea STAFF
��LS Industrial Systems (Middle East) FZE ����Dubai, U.A.E.
Address: P.O.Box-114216, API World Tower, 303B, Sheikhe Zayed Road, Dubai, U.A.E.
Tel: 971-4-332-8289 Fax: 971-4-332-9444 e-mail: hwyim@lsis.biz
��Dalian LS Industrial Systems Co., Ltd. ����Dalian, China
Address: No.15, Liaohexi 3-Road, Economic and Technical Development zone, Dalian 116600, China
Tel: 86-411-8273-7777 Fax: 86-411-8730-7560 e-mail: lixk@lsis.com.cn
��LS Industrial Systems (Wuxi) Co., Ltd. ����Wuxi, china
Address: 102-A , National High & New Tech Industrial Development Area, Wuxi, Jiangsu,214028, P.R.China
Tel: 86-510-8534-6666 Fax: 86-510-522-4078 e-mail: xuhg@lsis.com.cn
��LS-VINA Industrial Systems Co., Ltd. ����Hanoi, Vietnam
Address: Nguyen Khe - Dong Anh - Ha Noi - Viet Nam
Tel: 84-4-882-0222 Fax: 84-4-882-0220 e-mail: srjo@lsisvina.com
��LS Industrial Systems Tokyo Office ����Tokyo, Japan
Address: 16FL, Higashi-Kan, Akasaka Twin Tower 17-22, 2-chome, Akasaka, Minato-ku Tokyo 107-8470, Japan
Tel: 81-3-3582-9128 Fax: 81-3-3582-2667 e-mail: jschuna@lsis.biz
��LS Industrial Systems Shanghai Office ����Shanghai, China
Address: Room E-G, 12th Floor Huamin Empire Plaza, No.726, West Yan'an Road Shanghai 200050, P.R. China
Tel: 86-21-5237-9977 (609) Fax: 89-21-5237-7191 e-mail: jinhk@lsis.com.cn
��LS Industrial Systems Beijing Office ����Beijing, China
Address: B-Tower 17FL.Beijing Global Trade Center B/D. No.36, BeiSanHuanDong-Lu, DongCheng-District,
Beijing 100013, P.R. China
Tel: 86-10-5825-6025,7 Fax: 86-10-5825-6026 e-mail: cuixiaorong@lsis.com.cn
��LS Industrial Systems Guangzhou Office ����Guangzhou, China
Address: Room 1403,14F,New Poly Tower,2 Zhongshan Liu Road,Guangzhou, P.R. China
Tel: 86-20-8326-6764 Fax: 86-20-8326-6287 e-mail: linsz@lsis.com.cn
��LS Industrial Systems Chengdu Office ����Chengdu, China
Address: 12Floor, Guodong Buiding, No52 Jindun Road Chengdu, 610041, P.R. China
Tel: 86-28-8612-9151 Fax: 86-28-8612-9236 e-mail: yangcf@lsis.com.cn
��LS Industrial Systems Qingdao Office ����Qingdao, China
Address: 7B40,Haixin Guangchang Shenye Building B, No.9, Shandong Road Qingdao 26600, P.R. China
Tel: 86-532-8501-6568 Fax: 86-532-583-3793 e-mail: lirj@lsis.com.cn
�� Global Network
ⓒ 2003.8 LS Industrial Systems Co.,Ltd. All rights reserved.
www.dienhathe.xyz
www.dienhathe.vn

More Related Content

What's hot

Transistion from TVSS to SPD
Transistion from TVSS to SPDTransistion from TVSS to SPD
Transistion from TVSS to SPDmichaeljmack
 
Fire Pumps, Controllers & Associated Electrical Distribution Aspects
Fire Pumps, Controllers & Associated Electrical Distribution AspectsFire Pumps, Controllers & Associated Electrical Distribution Aspects
Fire Pumps, Controllers & Associated Electrical Distribution AspectsJames S Nasby
 
Siemens MV GIS Switchgear
Siemens MV GIS SwitchgearSiemens MV GIS Switchgear
Siemens MV GIS Switchgearmichaeljmack
 
High Voltage Gas Insulted Switchgear (GIS) Field Testing According to IEEE C3...
High Voltage Gas Insulted Switchgear (GIS) Field Testing According to IEEE C3...High Voltage Gas Insulted Switchgear (GIS) Field Testing According to IEEE C3...
High Voltage Gas Insulted Switchgear (GIS) Field Testing According to IEEE C3...Ali Sepehri
 
European Regulation N 548/14 on power transformers
European Regulation N 548/14 on power transformersEuropean Regulation N 548/14 on power transformers
European Regulation N 548/14 on power transformersLeonardo ENERGY
 
High Voltage Gas Insulated Substation (GIS) Routine Tests According to IEEE C...
High Voltage Gas Insulated Substation (GIS) Routine Tests According to IEEE C...High Voltage Gas Insulated Substation (GIS) Routine Tests According to IEEE C...
High Voltage Gas Insulated Substation (GIS) Routine Tests According to IEEE C...Ali Sepehri
 
Vacuum Circuit Breakers Testing Methods
Vacuum Circuit Breakers Testing MethodsVacuum Circuit Breakers Testing Methods
Vacuum Circuit Breakers Testing MethodsAli Sepehri
 
Power transformer manufacturing process and testing
Power transformer manufacturing process and testingPower transformer manufacturing process and testing
Power transformer manufacturing process and testingSai Kumar
 
Gelbyson Christie K Series MagAmp Power Supplies
Gelbyson Christie K Series MagAmp Power SuppliesGelbyson Christie K Series MagAmp Power Supplies
Gelbyson Christie K Series MagAmp Power Suppliesgelbyson
 

What's hot (17)

Transistion from TVSS to SPD
Transistion from TVSS to SPDTransistion from TVSS to SPD
Transistion from TVSS to SPD
 
Transformers
TransformersTransformers
Transformers
 
Fire Pumps, Controllers & Associated Electrical Distribution Aspects
Fire Pumps, Controllers & Associated Electrical Distribution AspectsFire Pumps, Controllers & Associated Electrical Distribution Aspects
Fire Pumps, Controllers & Associated Electrical Distribution Aspects
 
18824156
1882415618824156
18824156
 
ROCKWELL Transformers
ROCKWELL TransformersROCKWELL Transformers
ROCKWELL Transformers
 
Siemens MV GIS Switchgear
Siemens MV GIS SwitchgearSiemens MV GIS Switchgear
Siemens MV GIS Switchgear
 
RPS-SF6LBS-PKE
RPS-SF6LBS-PKERPS-SF6LBS-PKE
RPS-SF6LBS-PKE
 
Code questions
Code questionsCode questions
Code questions
 
Dog Conductor
Dog ConductorDog Conductor
Dog Conductor
 
KYN28 12kV Medium voltage metal clad switchgear
KYN28 12kV Medium voltage metal clad switchgearKYN28 12kV Medium voltage metal clad switchgear
KYN28 12kV Medium voltage metal clad switchgear
 
Standing type outdoor full sf6 gas insualted ring main unit
Standing type outdoor full sf6 gas insualted ring main unitStanding type outdoor full sf6 gas insualted ring main unit
Standing type outdoor full sf6 gas insualted ring main unit
 
High Voltage Gas Insulted Switchgear (GIS) Field Testing According to IEEE C3...
High Voltage Gas Insulted Switchgear (GIS) Field Testing According to IEEE C3...High Voltage Gas Insulted Switchgear (GIS) Field Testing According to IEEE C3...
High Voltage Gas Insulted Switchgear (GIS) Field Testing According to IEEE C3...
 
European Regulation N 548/14 on power transformers
European Regulation N 548/14 on power transformersEuropean Regulation N 548/14 on power transformers
European Regulation N 548/14 on power transformers
 
High Voltage Gas Insulated Substation (GIS) Routine Tests According to IEEE C...
High Voltage Gas Insulated Substation (GIS) Routine Tests According to IEEE C...High Voltage Gas Insulated Substation (GIS) Routine Tests According to IEEE C...
High Voltage Gas Insulated Substation (GIS) Routine Tests According to IEEE C...
 
Vacuum Circuit Breakers Testing Methods
Vacuum Circuit Breakers Testing MethodsVacuum Circuit Breakers Testing Methods
Vacuum Circuit Breakers Testing Methods
 
Power transformer manufacturing process and testing
Power transformer manufacturing process and testingPower transformer manufacturing process and testing
Power transformer manufacturing process and testing
 
Gelbyson Christie K Series MagAmp Power Supplies
Gelbyson Christie K Series MagAmp Power SuppliesGelbyson Christie K Series MagAmp Power Supplies
Gelbyson Christie K Series MagAmp Power Supplies
 

Similar to Ls catalog thiet bi dien pf e_dienhathe.vn

Elastimold - Cable Connectors, Joints, Terminations Catalogue
Elastimold - Cable Connectors, Joints, Terminations CatalogueElastimold - Cable Connectors, Joints, Terminations Catalogue
Elastimold - Cable Connectors, Joints, Terminations CatalogueThorne & Derrick International
 
sqd-app-guide-2-25c.pdf
sqd-app-guide-2-25c.pdfsqd-app-guide-2-25c.pdf
sqd-app-guide-2-25c.pdfNafir Anas
 
Iskra Low Voltage Switchgear
Iskra Low Voltage SwitchgearIskra Low Voltage Switchgear
Iskra Low Voltage SwitchgearMinka Grdesic
 
Dienhathe.com semiconductor fuses
Dienhathe.com semiconductor fusesDienhathe.com semiconductor fuses
Dienhathe.com semiconductor fusesDien Ha The
 
SMC LET Primary Injection Test Sets
SMC LET Primary Injection Test SetsSMC LET Primary Injection Test Sets
SMC LET Primary Injection Test SetsErika Herbozo
 
Weg low-voltage-switch-control-gear-50019086-brochure-english
Weg low-voltage-switch-control-gear-50019086-brochure-englishWeg low-voltage-switch-control-gear-50019086-brochure-english
Weg low-voltage-switch-control-gear-50019086-brochure-englishDaniel García
 
Cable sizing to withstand short-circuit current - Example
Cable sizing to withstand short-circuit current - ExampleCable sizing to withstand short-circuit current - Example
Cable sizing to withstand short-circuit current - ExampleLeonardo ENERGY
 
M. standard-stock-materials-for-33k v-system
M. standard-stock-materials-for-33k v-systemM. standard-stock-materials-for-33k v-system
M. standard-stock-materials-for-33k v-systemRamesh Meti
 
Cataloge ge 2.industrial components_dienhathe.com-1_record_plus
Cataloge ge 2.industrial components_dienhathe.com-1_record_plusCataloge ge 2.industrial components_dienhathe.com-1_record_plus
Cataloge ge 2.industrial components_dienhathe.com-1_record_plusDien Ha The
 
Cataloge ge 2.industrial components-1_record_plus
Cataloge ge 2.industrial components-1_record_plusCataloge ge 2.industrial components-1_record_plus
Cataloge ge 2.industrial components-1_record_plusDien Ha The
 

Similar to Ls catalog thiet bi dien pf e_dienhathe.vn (20)

Gis91
Gis91Gis91
Gis91
 
Lc1 d
Lc1 dLc1 d
Lc1 d
 
Elastimold - Cable Connectors, Joints, Terminations Catalogue
Elastimold - Cable Connectors, Joints, Terminations CatalogueElastimold - Cable Connectors, Joints, Terminations Catalogue
Elastimold - Cable Connectors, Joints, Terminations Catalogue
 
sqd-app-guide-2-25c.pdf
sqd-app-guide-2-25c.pdfsqd-app-guide-2-25c.pdf
sqd-app-guide-2-25c.pdf
 
Iskra Low Voltage Switchgear
Iskra Low Voltage SwitchgearIskra Low Voltage Switchgear
Iskra Low Voltage Switchgear
 
Quick Guide to Suitable Welding Consumables Low temperature steel.pdf
Quick Guide to Suitable Welding Consumables Low temperature steel.pdfQuick Guide to Suitable Welding Consumables Low temperature steel.pdf
Quick Guide to Suitable Welding Consumables Low temperature steel.pdf
 
Dienhathe.com semiconductor fuses
Dienhathe.com semiconductor fusesDienhathe.com semiconductor fuses
Dienhathe.com semiconductor fuses
 
SMC LET Primary Injection Test Sets
SMC LET Primary Injection Test SetsSMC LET Primary Injection Test Sets
SMC LET Primary Injection Test Sets
 
Thông số MCB LS
Thông số MCB LSThông số MCB LS
Thông số MCB LS
 
Easy pacttvs catalogues lc1e
Easy pacttvs catalogues lc1eEasy pacttvs catalogues lc1e
Easy pacttvs catalogues lc1e
 
Rc2 tm
Rc2 tmRc2 tm
Rc2 tm
 
Weg low-voltage-switch-control-gear-50019086-brochure-english
Weg low-voltage-switch-control-gear-50019086-brochure-englishWeg low-voltage-switch-control-gear-50019086-brochure-english
Weg low-voltage-switch-control-gear-50019086-brochure-english
 
Cable sizing to withstand short-circuit current - Example
Cable sizing to withstand short-circuit current - ExampleCable sizing to withstand short-circuit current - Example
Cable sizing to withstand short-circuit current - Example
 
Renewable energy
Renewable energyRenewable energy
Renewable energy
 
Renewable energy
Renewable energyRenewable energy
Renewable energy
 
M. standard-stock-materials-for-33k v-system
M. standard-stock-materials-for-33k v-systemM. standard-stock-materials-for-33k v-system
M. standard-stock-materials-for-33k v-system
 
Thông số kĩ thuật siemens-semiconductor fuses
Thông số kĩ thuật siemens-semiconductor fusesThông số kĩ thuật siemens-semiconductor fuses
Thông số kĩ thuật siemens-semiconductor fuses
 
Lawson - Low Voltage Fuse Links
Lawson - Low Voltage Fuse Links Lawson - Low Voltage Fuse Links
Lawson - Low Voltage Fuse Links
 
Cataloge ge 2.industrial components_dienhathe.com-1_record_plus
Cataloge ge 2.industrial components_dienhathe.com-1_record_plusCataloge ge 2.industrial components_dienhathe.com-1_record_plus
Cataloge ge 2.industrial components_dienhathe.com-1_record_plus
 
Cataloge ge 2.industrial components-1_record_plus
Cataloge ge 2.industrial components-1_record_plusCataloge ge 2.industrial components-1_record_plus
Cataloge ge 2.industrial components-1_record_plus
 

More from Dien Ha The

Vnd feb 2020 price list schneider (1)
Vnd feb 2020 price list schneider (1)Vnd feb 2020 price list schneider (1)
Vnd feb 2020 price list schneider (1)Dien Ha The
 
Resize bientanfuji-dienhathe.com
Resize bientanfuji-dienhathe.comResize bientanfuji-dienhathe.com
Resize bientanfuji-dienhathe.comDien Ha The
 
Fed e-quick-start-up-guide-bientanfuji-dienhathe.com
Fed e-quick-start-up-guide-bientanfuji-dienhathe.comFed e-quick-start-up-guide-bientanfuji-dienhathe.com
Fed e-quick-start-up-guide-bientanfuji-dienhathe.comDien Ha The
 
Fed e-quick-start-manual-bientanfuji-dienhathe.com
Fed e-quick-start-manual-bientanfuji-dienhathe.comFed e-quick-start-manual-bientanfuji-dienhathe.com
Fed e-quick-start-manual-bientanfuji-dienhathe.comDien Ha The
 
Ls bang gia ls ap dung 20 04-2019
Ls bang gia ls ap dung 20 04-2019Ls bang gia ls ap dung 20 04-2019
Ls bang gia ls ap dung 20 04-2019Dien Ha The
 
Mitsubishi graphic operation terminal got2000 series parts library book
Mitsubishi graphic operation terminal got2000 series parts library bookMitsubishi graphic operation terminal got2000 series parts library book
Mitsubishi graphic operation terminal got2000 series parts library bookDien Ha The
 
Mitsubishi inverter fr-a700-instruction-manualbasic-160425031653
Mitsubishi inverter fr-a700-instruction-manualbasic-160425031653Mitsubishi inverter fr-a700-instruction-manualbasic-160425031653
Mitsubishi inverter fr-a700-instruction-manualbasic-160425031653Dien Ha The
 
Mitsubishi graphic operation terminal got2000 series gt2103 new product release
Mitsubishi graphic operation terminal got2000 series gt2103 new product releaseMitsubishi graphic operation terminal got2000 series gt2103 new product release
Mitsubishi graphic operation terminal got2000 series gt2103 new product releaseDien Ha The
 
Mitsubishi graphic operation terminal got2000 series got mobile function quic...
Mitsubishi graphic operation terminal got2000 series got mobile function quic...Mitsubishi graphic operation terminal got2000 series got mobile function quic...
Mitsubishi graphic operation terminal got2000 series got mobile function quic...Dien Ha The
 
Mitsubishi graphic operation terminal got2000 series drive control interactiv...
Mitsubishi graphic operation terminal got2000 series drive control interactiv...Mitsubishi graphic operation terminal got2000 series drive control interactiv...
Mitsubishi graphic operation terminal got2000 series drive control interactiv...Dien Ha The
 
Mitsubishi inverter option catalog
Mitsubishi inverter option catalogMitsubishi inverter option catalog
Mitsubishi inverter option catalogDien Ha The
 
Mitsubishi low voltage ws-v series mccb and elcb
Mitsubishi low voltage ws-v series mccb and elcbMitsubishi low voltage ws-v series mccb and elcb
Mitsubishi low voltage ws-v series mccb and elcbDien Ha The
 
Mitsubishi graphic operation terminal got2000 series (concise)
Mitsubishi graphic operation terminal got2000 series (concise)Mitsubishi graphic operation terminal got2000 series (concise)
Mitsubishi graphic operation terminal got2000 series (concise)Dien Ha The
 
Mitsubishi low voltage ws-v series comparison of previous and new models
Mitsubishi low voltage ws-v series comparison of previous and new modelsMitsubishi low voltage ws-v series comparison of previous and new models
Mitsubishi low voltage ws-v series comparison of previous and new modelsDien Ha The
 
Mitsubishi inverter inverter family
Mitsubishi inverter inverter familyMitsubishi inverter inverter family
Mitsubishi inverter inverter familyDien Ha The
 
Mitsubishi low voltage miniature circuit breakers din series
Mitsubishi low voltage miniature circuit breakers din seriesMitsubishi low voltage miniature circuit breakers din series
Mitsubishi low voltage miniature circuit breakers din seriesDien Ha The
 
Mitsubishi inverter freqrol-hc2 series
Mitsubishi inverter freqrol-hc2 seriesMitsubishi inverter freqrol-hc2 series
Mitsubishi inverter freqrol-hc2 seriesDien Ha The
 
Mitsubishi low voltage mccb and elcb(ws-v series) y0720-version 1-mitsu
Mitsubishi low voltage mccb and elcb(ws-v series) y0720-version 1-mitsuMitsubishi low voltage mccb and elcb(ws-v series) y0720-version 1-mitsu
Mitsubishi low voltage mccb and elcb(ws-v series) y0720-version 1-mitsuDien Ha The
 
Mitsubishi inverter freqrol-f700 pj series
Mitsubishi inverter freqrol-f700 pj seriesMitsubishi inverter freqrol-f700 pj series
Mitsubishi inverter freqrol-f700 pj seriesDien Ha The
 
Mitsubishi inverter catalog-mitsubishi-inverter-option-160426021125
Mitsubishi inverter catalog-mitsubishi-inverter-option-160426021125Mitsubishi inverter catalog-mitsubishi-inverter-option-160426021125
Mitsubishi inverter catalog-mitsubishi-inverter-option-160426021125Dien Ha The
 

More from Dien Ha The (20)

Vnd feb 2020 price list schneider (1)
Vnd feb 2020 price list schneider (1)Vnd feb 2020 price list schneider (1)
Vnd feb 2020 price list schneider (1)
 
Resize bientanfuji-dienhathe.com
Resize bientanfuji-dienhathe.comResize bientanfuji-dienhathe.com
Resize bientanfuji-dienhathe.com
 
Fed e-quick-start-up-guide-bientanfuji-dienhathe.com
Fed e-quick-start-up-guide-bientanfuji-dienhathe.comFed e-quick-start-up-guide-bientanfuji-dienhathe.com
Fed e-quick-start-up-guide-bientanfuji-dienhathe.com
 
Fed e-quick-start-manual-bientanfuji-dienhathe.com
Fed e-quick-start-manual-bientanfuji-dienhathe.comFed e-quick-start-manual-bientanfuji-dienhathe.com
Fed e-quick-start-manual-bientanfuji-dienhathe.com
 
Ls bang gia ls ap dung 20 04-2019
Ls bang gia ls ap dung 20 04-2019Ls bang gia ls ap dung 20 04-2019
Ls bang gia ls ap dung 20 04-2019
 
Mitsubishi graphic operation terminal got2000 series parts library book
Mitsubishi graphic operation terminal got2000 series parts library bookMitsubishi graphic operation terminal got2000 series parts library book
Mitsubishi graphic operation terminal got2000 series parts library book
 
Mitsubishi inverter fr-a700-instruction-manualbasic-160425031653
Mitsubishi inverter fr-a700-instruction-manualbasic-160425031653Mitsubishi inverter fr-a700-instruction-manualbasic-160425031653
Mitsubishi inverter fr-a700-instruction-manualbasic-160425031653
 
Mitsubishi graphic operation terminal got2000 series gt2103 new product release
Mitsubishi graphic operation terminal got2000 series gt2103 new product releaseMitsubishi graphic operation terminal got2000 series gt2103 new product release
Mitsubishi graphic operation terminal got2000 series gt2103 new product release
 
Mitsubishi graphic operation terminal got2000 series got mobile function quic...
Mitsubishi graphic operation terminal got2000 series got mobile function quic...Mitsubishi graphic operation terminal got2000 series got mobile function quic...
Mitsubishi graphic operation terminal got2000 series got mobile function quic...
 
Mitsubishi graphic operation terminal got2000 series drive control interactiv...
Mitsubishi graphic operation terminal got2000 series drive control interactiv...Mitsubishi graphic operation terminal got2000 series drive control interactiv...
Mitsubishi graphic operation terminal got2000 series drive control interactiv...
 
Mitsubishi inverter option catalog
Mitsubishi inverter option catalogMitsubishi inverter option catalog
Mitsubishi inverter option catalog
 
Mitsubishi low voltage ws-v series mccb and elcb
Mitsubishi low voltage ws-v series mccb and elcbMitsubishi low voltage ws-v series mccb and elcb
Mitsubishi low voltage ws-v series mccb and elcb
 
Mitsubishi graphic operation terminal got2000 series (concise)
Mitsubishi graphic operation terminal got2000 series (concise)Mitsubishi graphic operation terminal got2000 series (concise)
Mitsubishi graphic operation terminal got2000 series (concise)
 
Mitsubishi low voltage ws-v series comparison of previous and new models
Mitsubishi low voltage ws-v series comparison of previous and new modelsMitsubishi low voltage ws-v series comparison of previous and new models
Mitsubishi low voltage ws-v series comparison of previous and new models
 
Mitsubishi inverter inverter family
Mitsubishi inverter inverter familyMitsubishi inverter inverter family
Mitsubishi inverter inverter family
 
Mitsubishi low voltage miniature circuit breakers din series
Mitsubishi low voltage miniature circuit breakers din seriesMitsubishi low voltage miniature circuit breakers din series
Mitsubishi low voltage miniature circuit breakers din series
 
Mitsubishi inverter freqrol-hc2 series
Mitsubishi inverter freqrol-hc2 seriesMitsubishi inverter freqrol-hc2 series
Mitsubishi inverter freqrol-hc2 series
 
Mitsubishi low voltage mccb and elcb(ws-v series) y0720-version 1-mitsu
Mitsubishi low voltage mccb and elcb(ws-v series) y0720-version 1-mitsuMitsubishi low voltage mccb and elcb(ws-v series) y0720-version 1-mitsu
Mitsubishi low voltage mccb and elcb(ws-v series) y0720-version 1-mitsu
 
Mitsubishi inverter freqrol-f700 pj series
Mitsubishi inverter freqrol-f700 pj seriesMitsubishi inverter freqrol-f700 pj series
Mitsubishi inverter freqrol-f700 pj series
 
Mitsubishi inverter catalog-mitsubishi-inverter-option-160426021125
Mitsubishi inverter catalog-mitsubishi-inverter-option-160426021125Mitsubishi inverter catalog-mitsubishi-inverter-option-160426021125
Mitsubishi inverter catalog-mitsubishi-inverter-option-160426021125
 

Recently uploaded

UNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular ConduitsUNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular Conduitsrknatarajan
 
UNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its PerformanceUNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its Performancesivaprakash250
 
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxpurnimasatapathy1234
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130Suhani Kapoor
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingrakeshbaidya232001
 
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Serviceranjana rawat
 
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSKurinjimalarL3
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxAsutosh Ranjan
 
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSHARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSRajkumarAkumalla
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escortsranjana rawat
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escortsranjana rawat
 
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...Call Girls in Nagpur High Profile
 
SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )Tsuyoshi Horigome
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...ranjana rawat
 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Christo Ananth
 
Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxupamatechverse
 

Recently uploaded (20)

Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024
 
UNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular ConduitsUNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular Conduits
 
UNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its PerformanceUNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its Performance
 
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptx
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writing
 
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
 
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
 
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINEDJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptx
 
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSHARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
 
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
 
SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
 
Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptx
 

Ls catalog thiet bi dien pf e_dienhathe.vn

  • 1. Electric Equipment Leader in Electrics & Automation Prime-MEC LS HRC Power Fuseswww.dienhathe.xyz www.dienhathe.vn
  • 2. 3.6 7.2 24 56� 85� 90� 45� 70� 89� 47� 85� 85� 6.5 7.2 7.3 5.2 6.0 7.3 5.1 7.2 7.2 0.07 ~ 0.15 �Test current : 40kA �Basis : 63A �I peak : Let through current(under the short circuit test) Rated voltage(kV) Initiation of arcing(degree) Ipeak(kA) Power Factor Current without Power Fuse (40kA ms) Ipeak Let through current Below 0.5 Cycle 1 www.dienhathe.xyz www.dienhathe.vn
  • 3. 2 Features �The LS HRC Power Fuses belong to the PRIME MEC series. It interrupts high currents before the first loop of fault current has reached its natural peak value and therefore cuts down the required withstand capacity of the associated equipment on the electric system. �Though small in size, it has a high breaking capacity and its enclosed type is suitable for use inside of the panel board. �PRIME MEC fuses are equipped with striker pins for trip indicators as well as for operating the related load break switches. �Link type fuse holder enables easy maintenance and high stability when replacing the fuses. �With Fuse Checker, checking the conditions of a fuse in the panel board or by telecommunication is possible.(Optional) Applied standards �IEC 282-1, DIN 43625, BS 2692, KSC 4612 Applications �Transformer protection - To protect against short circuit current in the secondary part of a transformer and fault current in the transformer circuit. �Condenser protection - To protect against fault current in the condenser circuit. �Motor protection - To protect against fault current in the motor circuit �Cable protection - Fault current protection secures the cable www.dienhathe.xyz www.dienhathe.vn
  • 4. 3 LS HRC Power Fuses Ratings 5 10 20 30 40 50 63 75 100 125 160 200 160 200 5 10 16 20 25 30 40 50 63 75 100 125 160 200 LFL-3/6G-5B LFL-3/6G-10B LFL-3/6G-20B LFL-3/6G-30B LFL-3/6G-40B LFL-3/6G-50B LFL-3/6G-60B LFL-3/6G-75B LFL-3/6G-100B LFL-3/6G-125B LFL-3G-160B LFL-3G-200B LFL-6G-160B LFL-6G-200B LFL-20G-5B LFL-20G-10B LFL-20G-16B LFL-20G-20B LFL-20G-25B LFL-20G-30B LFL-20G-40B LFL-20G-50B LFL-20G-60B LFL-20G-75C LFL-20G-100C LFL-20G-125B LFL-20G-160B LFL-20G-200B LFH-6G-D1HB LFH-20G-D2HB LFH-20G-D2HC LFH-6G-D2HB 3.6/7.2 3.6 7.2 24 7.2 60 12524 40 40 25 100 200 200 5In 5In 6In 192 55 1 192 77 2 292 77 2.8 442 442 442 537 87 87 5.1 5.5 55 77 2 4.2 Note) 1. Application site : Indoor use 2. Refer to the column "B" in the table for inside diameters of Hook rings 3. Models highlighted can be applied to 3.6 or 7.2kV Type Rated voltage (kV) Rated current (A) Breaking current (kA, rms) Minimum breaking current (A) Dimensions Weight (kg) Type Rated voltage (kV) Rated current (A) Insulation level (BIL, kV)A B Fuse link Fuse holder www.dienhathe.xyz www.dienhathe.vn
  • 5. 4 Conditions of selection Basic conditions for selecting the Power Fuses �The rated current of a Power Fuse should be higher than sum of the total rated current of the electric equipment on the circuit. �Back-up protection with electric equipment on the circuit. - Set the operating characteristics of the Power Fuses to satisfy the over-current characteristics of the protected loads on the circuit. Also, set the occurred calories, by the l2 t operation, to be smaller than the short-circuit intensity of the electric equipment and circuit. - When using the Power Fuses for backup usage with other protective equipment, set the operating times of the protective equipment below the minimum breaking current to be faster than those of the Power Fuses. �The inrush current of a transformer is selected assuming that the current is 10 time that of the full-load transformer current in 0.1sec. �The rated current of the Power Fuses is selected to continuously flow at 1.5time of the transformer rated current. �Power Fuses for proteting against short-circuit in the secondary part of a transformer are selected assuming that the current is 25times that of the transformer rated current in 2seconds. Circuit Transformer Circuit Transformer Circuit Transformer Phase voltage capacity Applied fuses voltage capacity Applied fuses voltage capacity Applied fuses (kV) (kVA) (kV) (kVA) (kV) (kVA) 4~8 LFL-3/6G-5B 8~16 LFL-3/6G-5B 20~43 LFL-20G-5B 6~13 LFL-3/6G-10B 13~25 LFL-3/6G-10B 43~90 LFL-20G-10B - - - - 87~180 LFL-20G-16B 15~31 LFL-3/6G-20B 30~62 LFL-3/6G-20B 99~206 LFL-20G-20B - - - - 130~269 LFL-20G-25B 21~42 LFL-3/6G-30B 40~84 LFL-3/6G-30B 149~310 LFL-20G-30B 40~82 LFL-3/6G-40B 80~165 LFL-3/6G-40B 267~557 LFL-20G-40B 1фф 3.3 49~102 LFL-3/6G-50B 6.6 98~204 LFL-3/6G-50B 22.9 345~719 LFL-20G-50B 66~137 LFL-3/6G-60B 132~275 LFL-3/6G-60B 430~897 LFL-20G-60B 68~165 LFL-3/6G-75B 134~330 LFL-3/6G-75B 580~1145 LFL-20G-75B 128~220 LFL-3/6G-100B 256~440 LFL-3/6G-100B 923~1527 LFL-20G-100B 151~275 LFL-3/6G-125B 302~550 LFL-3/6G-125B 1364~1908 LFL-20G-125B 211~352 LFL-3/6G-160B 425~704 LFL-3/6G-160B 2125~2443 LFL-20G-160B 265~4402 LFL-3/6G-200B 437~880 LFL-3/6G-200B 2650~3050 LFL-20G-200B 6.7~14 LFL-3/6G-5B 13~28 LFL-3/6G-5B 36~75 LFL-20G-5B 11~22 LFL-3/6G-10B 21~44 LFL-3/6G-10B 75~157 LFL-20G-10B - - - - 151~313 LFL-20G-16B 25~53 LFL-3/6G-20B 51~107 LFL-3/6G-20B 172~358 LFL-20G-20B - - - - 224~466 LFL-20G-25B 35~73 LFL-3/6G-30B 70~145 LFL-3/6G-30B 258~538 LFL-20G-30B 69~143 LFL-3/6G-40B 137~286 LFL-3/6G-40B 464~965 LFL-20G-40B 3фф 3.3 85~77 LFL-3/6G-50B 6.6 170~354 LFL-3/6G-50B 22.9 598~1246 LFL-20G-50B 114~238 LFL-3/6G-60B 229~476 LFL-3/6G-60B 745~1554 LFL-20G-60B 117~285 LFL-3/6G-75B 233~571 LFL-3/6G-75B 1000~1983 LFL-20G-75B 222~381 LFL-3/6G-100B 443~762 LFL-3/6G-100B 1600~2645 LFL-20G-100B 261~476 LFL-3/6G-125B 522~952 LFL-3/6G-125B 2362~3304 LFL-20G-125B 365~610 LFL-3G-160B 735~1220 LFL-6G-160B 3680~4232 LFL-20G-160B 459~762 LFL-3G-200B 755~1520 LFL-6G-200B 4593~5287 LFL-20G-200B For transformer protection Selecting conditions Note) 1. Models highlighted can be applied to 3.6 or 7.2kV www.dienhathe.xyz www.dienhathe.vn
  • 6. 5 LS HRC Power Fuses Conditions of selection For condenser protection For motor protection �Under the short-circuit condition, the power fuse breaks the circuit in high speed. Therefore, with relatively high rated current, the Power Fuse protects small size cables. �Selected to protect from above 10 times of the short-circuit current. Circuit Transformer Circuit Condenser Circuit Condenser Phase voltage capacity Applied fuses voltage capacity Applied fuses voltage capacity Applied fuses (kV) (kVA) (kV) (kVA) (kV) (kVA) ~9.8 LFL-3/6G-5B ~19 LFL-3/6G-5B ~46 LFL-20G-5B 9.8~12 LFL-3/6G-10B 19~24 LFL-3/6G-10B 46~83 LFL-20G-10B - - - - 64~172 LFL-20G-16B 12~31 LFL-3/6G-20B 24~61 LFL-3/6G-20B 83~203 LFL-20G-20B - - - - 193~272 LFL-20G-25B 31~46 LFL-3/6G-30B 61~92 LFL-3/6G-30B 203~317 LFL-20G-30B 3фф 3.3 46~64 LFL-3/6G-40B 6.6 92~128 LFL-3/6G-40B 22.9 317~425 LFL-20G-40B 64~81 LFL-3/6G-50B 128~163 LFL-3/6G-50B 425~564 LFL-20G-50B 81~105 LFL-3/6G-60B 163~210 LFL-3/6G-60B 564~710 LFL-20G-60B 105~150 LFL-3/6G-75B 210~300 LFL-3/6G-75B 710~1021 LFL-20G-75B 150~222 LFL-3/6G-100B 300~445 LFL-3/6G-100B 1021~1655 LFL-20G-100B 222~275 LFL-3/6G-125B 445~550 LFL-3/6G-125B 1655~2370 LFL-20G-125B 275~370 LFL-3G-160B 550~742 LFL-6G-160B 2370~3170 LFL-20G-160B 370~500 LFL-3G-200B 742~1000 LFL-6G-200B 3170~4000 LFL-20G-200B Circuit Circuit Phase voltage Motor output Applied fuses voltage Motor output Applied fuses (kV) (kVA) (kV) (kVA) 4.3~7.2 LFL-3/6G-5B 8.7~15 LFL-3/6G-5B 7.2~19 LFL-3/6G-10B 15~25 LFL-3/6G-10B 19~39 LFL-3/6G-20B 25~65 LFL-3/6G-20B 34~64 LFL-3/6G-30B 65~88 LFL-3/6G-30B 64~87 LFL-3/6G-40B 88~183 LFL-3/6G-40B 3фф 3.3 87~109 LFL-3/6G-50B 6.6 183~225 LFL-3/6G-50B 106~149 LFL-3/6G-60B 219~304 LFL-3/6G-60B 139~199 LFL-3/6G-75B 288~407 LFL-3/6G-75B 185~288 LFL-3/6G-100B 377~604 LFL-3/6G-100B 229~344 LFL-3/6G-125B 474~721 LFL-3/6G-125B 268~471 LFL-3G-160B 614~1015 LFL-6G-160B 293~518 LFL-3G-200B 958~1502 LFL-6G-200B For cable protection Cable Rated(A) diameter current of PF (mm2) (A) 0.8 40 1.6 50 2 75 3.5 100 5.5 150 8 200 22 200 �The starting current of a motor is selected to withstand 5 times of the full-loads current in 10sec. Selecting conditions �The inrush current of a condenser is selected to withstand 71time of the condenser rated current in 0.002sec. �The rated current of the Power Fuses is selected to continuously flow at 1.43 times of the condenser rated current. Selecting conditions Note) 1. Models highlighted can be applied to 3.6 or 7.2kV Note) 1. Models highlighted can be applied to 3.6 or 7.2kV www.dienhathe.xyz www.dienhathe.vn
  • 7. 6 Characteristics curves 1000 800 600 400 200 100 80 60 40 20 10 8 6 4 2 1 0.8 0.6 0.4 0.2 0.1 0.08 0.06 0.04 0.02 0.01 125A 100A 75A 50A 63A 40A 30A 20A 10A 5A 0.02 0.04 0.06 0.08 0.1 0.2 0.4 0.6 0.8 1 2 4 6 8 10 20 40 100 Cut-offcurrent(peakvalue:kA)→→ Prospective breaking current(rms : kA) →→ 1000 800 600 400 200 100 80 60 40 20 10 8 6 4 2 1 0.8 0.6 0.4 0.2 0.1 0.08 0.06 0.04 0.02 0.01 2 4 6 8 10 20 40 60 80 100 200 400 600 800 1000 2000 4000 5A 10A 20A 30A 40A 50A 125A 100A 75A 63A Operatingtime(sec)→→ Prospective rated current(rms : A) →→ 1000 800 600 400 200 100 80 60 40 20 10 8 6 4 2 1 0.8 0.6 0.4 0.2 0.1 0.08 0.06 0.04 0.02 0.01 200A 160A 0.02 0.04 0.06 0.08 0.1 0.2 0.4 0.6 0.8 1 2 4 6 8 10 20 40 100 Cut-offcurrent(peakvalue:kA)→→ Prospective breaking current(rms : kA) →→ 1000 800 600 400 200 100 80 60 40 20 10 8 6 4 2 1 0.8 0.6 0.4 0.2 0.1 0.08 0.06 0.04 0.02 0.01 2 4 6 8 10 20 40 60 80 100 200 400 600 800 1000 2000 4000 200A 160A Operatingtime(sec)→→ Prospective rated current(rms : A) →→ 3.6/7.2kV Cut-off characteristics 3.6/7.2kV Pre-arcing time- current characteristics 3.6kV Cut-off characteristics 3.6kV Pre-arcing time- current characteristics www.dienhathe.xyz www.dienhathe.vn
  • 8. 7 Characteristics curves LS HRC Power Fuses 1000 800 600 400 200 100 80 60 40 20 10 8 6 4 2 1 0.8 0.6 0.4 0.2 0.1 0.08 0.06 0.04 0.02 0.01 0.02 0.04 0.06 0.08 0.1 0.2 0.4 0.6 0.8 1 2 4 6 8 10 20 40 100 200A 160A Cut-offcurrent(peakvalue:kA)→→ Prospective breaking current(rms : kA) →→ 1000 800 600 400 200 100 80 60 40 20 10 8 6 4 2 1 0.8 0.6 0.4 0.2 0.1 0.08 0.06 0.04 0.02 0.01 2 4 6 8 10 20 40 60 80 100 200 400 600 800 1000 2000 4000 6000 8000 10000 200A 160A Operatingtime(sec)→→ Prospective rated current(rms : A) →→ 7.2kV Cut-off characteristics 7.2kV Pre-arcing time- current characteristics Cut-offcurrent(peakvalue:kA)→→ Prospective breaking current(rms : kA) →→ 1000 800 600 400 200 100 80 60 40 20 10 8 6 4 2 1 0.8 0.6 0.4 0.2 0.1 0.08 0.06 0.04 0.02 0.01 2 4 6 8 10 20 40 60 80 100 200 400 600 800 1000 2000 4000 8000 6000 10000 Operatingtime(sec)→→ Prospective rated current(rms : A) →→ 24kV Cut-off characteristics 24kV Pre-arcing time- current characteristics www.dienhathe.xyz www.dienhathe.vn
  • 9. 8 Fuse holder dimensions Indoor use Power Fuse holder LFH-6G-D1HB Type Indoor use Power Fuse holder LFH-6G-D2HB Type Fuse size(A) B C ф 55 242.3 376 ф 77 253.3 380 C (Peak height in open condition) Fuse checker ф12.5(Hold) Mounting hold Earth hole Hook Ring Fuse checker ф12.5(Hold) Mounting hole Earth hole Below1 456.5 (Peak height in open condition) Hook Ring www.dienhathe.xyz www.dienhathe.vn
  • 10. Rated Rated Circuit Insulation Dimensions(mm) PH Holder type voltage current voltage level Applied fuse (kV) (A) (kV) (BIL, kV) A B C D E F G 3.3 45 421 250 376 323 477 97 130 LFL-3/6G-5B, 10B, 20B, 30B, 40B, 50B 3.3 45 421 254 380 334 477 97 130 LFL-3/6G-60B, 75B, 100B LFH-6G-D1HB 7.2 100 6.6 60 421 250 376 349 503 123 158 LFL-3/6G-5B, 10B, 20B, 30B, 40B, 50B 6.6 60 421 254 380 360 503 123 158 LFL-3/6G-60B, 75B, 100B LFH-6G-D2HB 7.2 200 3.3 45 521 254 457 334 564 97 130 LFL-3/6G-125B, LFL-3G-160B, 200B 6.6 60 521 254 457 360 590 123 158 LFL-3/6G-125B, LFL-6G-160B, 200B 671 363 688 586 934 - 260 LFL-20G-5B, 10B, 16B, 20B LFH-20G-D2HB 24 200 22.9 125 671 374 692 597 957 - 260 LFL-20G-25B, 30B, 40B, 50B, 60B 671 379 695 602 957 - 260 LFL-20G-75C, 100C 125B, 160B LFH-6G-D2HB 766 379 768 602 957 - 260 LFL-20G-200B 9 LS HRC Power Fuses Fuse holder dimensions Indoor use Power Fuse holder LFH20-D2HB(C) Type C (Peak height in open condition) Fuse checker ф12.5(Hold) Mounting hold Earth hole Below1 Hook Ring Power Fuse holder Panel Conductor Panel Fuse size(A) B C ф 55 362.3 687.5 ф 77 373.3 691.6 ф 87 378.3 695(768) Note) Dimension in ( ) is for LFH-20G-D2HC D: Minimum insulation distance in opening E: Minimum insulation distance in closing www.dienhathe.xyz www.dienhathe.vn
  • 11. Operatingweight(kgf)→→ Operating distance(mm) →→ Operating characteristics of the Power Fuses The characteristics of the Power Fuses are native and fixed. Therefore it can not be regulated like a circuit breaker or over-load relay. When ordering, please select the Power Fuses with proper current and operating characteristics by considering its usage and circuit condition. Breaking a small current. Power Fuses are not adequate to protect small current. So, the manufacturer specifies and guarantees the minimum breaking current by regulation. 1) Select the rated current of the Power Fuse, which does not operate below the minimum breaking current. 2) Protect the current below the minimum value by use of other protective equipment. 10 Striker operating characteristics & Ordering information Striker operating characteristics P/F Link P/F Holder Types of P/F Link & P/F Holder Model name General use Revision No.Rated voltage 3/6 3.6/7.2kV 3 3.6kV 6 7.2kV 20 24kV Rated current 5 5A 10 10A 16 16A 20 20A 25 25A 30 30A 40 40A 50 50A 60 63A 75 75A 100 100A 125 125A 160 160A 200 200A Model name General use Indoor use LFL 6 G LFH 6 G D 1H B 1 5 50 B Rated voltage 3/6 3.6/7.2kV 20 24kV Rated current 1H 100A 2H 200A Fuse Checker 0 Without 1 With Hook Ring 5 ∅ 55 7 ∅ 77 8 ∅ 87 Revision No. B - C 200A(24kV) www.dienhathe.xyz www.dienhathe.vn
  • 12. www.lsis.biz �� For your safety, please read user's manual thoroughly before operating. �� Contact the nearest authorized service facility for examination, repair, or adjustment. �� Please contact a qualified service technician when you need maintenance. Do not disassemble or repair by yourself! �� Any maintenance and inspection shall be performed by the personnel having expertise concerned.Safety Instructions Leader in Electrics & Automation Specifications in this catalog are subject to change without notice due to continuous product development and improvement. �� HEAD OFFICE Yonsei Jaedan Severance Bldg., 84-11, Namdaemunno 5ga, Jung-gu, Seoul, 100-753, Korea Tel. (82-2)2034-4870 Fax. (82-2)2034-4713 �� CHEONG-JU PLANT Cheong-Ju Plant #1, Song Jung Dong, Hung Duk Ku, Cheong Ju, 361-720, Korea 2008. 01 LS HRC Power Fuses(E) 2003. 08/(03) 2008. 01 Printed in Korea STAFF ��LS Industrial Systems (Middle East) FZE ����Dubai, U.A.E. Address: P.O.Box-114216, API World Tower, 303B, Sheikhe Zayed Road, Dubai, U.A.E. Tel: 971-4-332-8289 Fax: 971-4-332-9444 e-mail: hwyim@lsis.biz ��Dalian LS Industrial Systems Co., Ltd. ����Dalian, China Address: No.15, Liaohexi 3-Road, Economic and Technical Development zone, Dalian 116600, China Tel: 86-411-8273-7777 Fax: 86-411-8730-7560 e-mail: lixk@lsis.com.cn ��LS Industrial Systems (Wuxi) Co., Ltd. ����Wuxi, china Address: 102-A , National High & New Tech Industrial Development Area, Wuxi, Jiangsu,214028, P.R.China Tel: 86-510-8534-6666 Fax: 86-510-522-4078 e-mail: xuhg@lsis.com.cn ��LS-VINA Industrial Systems Co., Ltd. ����Hanoi, Vietnam Address: Nguyen Khe - Dong Anh - Ha Noi - Viet Nam Tel: 84-4-882-0222 Fax: 84-4-882-0220 e-mail: srjo@lsisvina.com ��LS Industrial Systems Tokyo Office ����Tokyo, Japan Address: 16FL, Higashi-Kan, Akasaka Twin Tower 17-22, 2-chome, Akasaka, Minato-ku Tokyo 107-8470, Japan Tel: 81-3-3582-9128 Fax: 81-3-3582-2667 e-mail: jschuna@lsis.biz ��LS Industrial Systems Shanghai Office ����Shanghai, China Address: Room E-G, 12th Floor Huamin Empire Plaza, No.726, West Yan'an Road Shanghai 200050, P.R. China Tel: 86-21-5237-9977 (609) Fax: 89-21-5237-7191 e-mail: jinhk@lsis.com.cn ��LS Industrial Systems Beijing Office ����Beijing, China Address: B-Tower 17FL.Beijing Global Trade Center B/D. No.36, BeiSanHuanDong-Lu, DongCheng-District, Beijing 100013, P.R. China Tel: 86-10-5825-6025,7 Fax: 86-10-5825-6026 e-mail: cuixiaorong@lsis.com.cn ��LS Industrial Systems Guangzhou Office ����Guangzhou, China Address: Room 1403,14F,New Poly Tower,2 Zhongshan Liu Road,Guangzhou, P.R. China Tel: 86-20-8326-6764 Fax: 86-20-8326-6287 e-mail: linsz@lsis.com.cn ��LS Industrial Systems Chengdu Office ����Chengdu, China Address: 12Floor, Guodong Buiding, No52 Jindun Road Chengdu, 610041, P.R. China Tel: 86-28-8612-9151 Fax: 86-28-8612-9236 e-mail: yangcf@lsis.com.cn ��LS Industrial Systems Qingdao Office ����Qingdao, China Address: 7B40,Haixin Guangchang Shenye Building B, No.9, Shandong Road Qingdao 26600, P.R. China Tel: 86-532-8501-6568 Fax: 86-532-583-3793 e-mail: lirj@lsis.com.cn �� Global Network ⓒ 2003.8 LS Industrial Systems Co.,Ltd. All rights reserved. www.dienhathe.xyz www.dienhathe.vn