SlideShare a Scribd company logo
1 of 90
Download to read offline
2/1
2
Semiconductor Fuses
General Data 2/2 Product overview
LV HRC SITOR
Fuse Links
2/4 Application information
2/13 Rated voltage 500 V AC
2/15 Rated voltage 600 V AC
2/17 Rated voltage 660 V AC
2/19 Rated voltage: 690 V AC/ 700 V DC
2/22 Rated voltage 690 V AC,
operational class gS
2/27 Rated voltage 690 V AC,
operational class gR
2/33 Rated voltage 800 V AC
2/35 Rated voltage 1000 V AC
2/41 Rated voltage 1500 V AC
2/44 Rated voltage 2000 V AC
2/46 Rated voltage 2500 V AC
2/48 Configuration Aids
SITOR Fuse Links for
Special Applications
2/50 For rectifiers in electrolysis systems
2/54 For SITOR thyristor sets
2/57 For railway supply rectifiers
2/59 Configuration Aids
SITOR Cylindrical
Fuse Links
2/60 SITOR cylindrical fuse links
SILIZED Fuse Links 2/73 NEOZED fuse links SILIZED
2/75 DIAZED fuse links SILIZED
2/77 Configuration Aids
Notes on Dimensioning 2/78 Technical explanations
2/86 Specifying the rated current
2/89 Terms
2/90 Characteristic curves
www.dienhathe.xyz
www.dienhathe.vn
Semiconductor Fuses
General Data
Product overview
2/2 Siemens ET B1 T · 2007
■Overview
LV HRC SITOR fuse links
• Rated voltage Un to 2500 V AC, 700 V DC
• Rated current In 16 ... 1000 A
• Operational class: aR, gR, gS
• Sizes 000 to 3
• Range of connection types:
- for mounting in LV HRC fuse bases
- with bolt-on links, mounting dimensions 80 ... 260 mm
- with bolt-on links, with 2 oblong slots
- with M12 screw connection
For rectifiers in electrolysis systems
• Rated voltage Un 600 ... 1000 V AC
• Rated current In 350 ... 1250 A
• Operational class: aR, gR
For SITOR thyristor sets
• Rated voltage Un 800/1000 V AC
• Rated current In 50 ... 710 A
• Operational class: aR, gR
For railway supply rectifiers
• Rated voltage Un 680 V AC
• Rated current In 250/350 A
• Operational class: aR
www.dienhathe.xyz
www.dienhathe.vn
Semiconductor Fuses
General Data
Product overview
2/3Siemens ET B1 T · 2007
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
SITOR cylindrical fuse links
• Rated voltage Un 600/690 V AC, 400/700 V AC
• Rated current In 1 ... 100 A
• Operational class: aR
• Sizes 10 mm x 38 mm, 14 mm x 51 mm and 22 mm x 58 mm
Accessories for SITOR cylindrical fuse links
• Fuse holders/fuse switch disconnectors/fuse disconnectors for cylindrical fuse links 10 x 38, 14 x 51, 22 x 58
• Fuse bases for cylindrical fuse links 10 x 38, 14 x 51, 22 x 58
NEOZED fuse links SILIZED
• Rated voltage Un 400 V AC, 250 V DC
• Rated current In 10 ... 63 A
• Sizes D01 and D02
• Operational class: gR
DIAZED fuse links SILIZED
• Rated voltage Un 500 V AC, 500 V DC
• Rated current In 16 ... 100 A
• Operational class: gR
• Super quick
www.dienhathe.xyz
www.dienhathe.vn
Semiconductor Fuses
LV HRC SITOR Fuse Links
Application information
2/4 Siemens ET B1 T · 2007
■Benefits
Used in conjunction with the new 3NE1 ...–2 fuse range, the 3KL
switch disconnectors with fuses have been awarded UL
approval.
■Application
Characteristics
SITOR fuse links protect converter equipment against
short-circuits.
The power semiconductors used in these devices (diodes,
thyristors, GTOs and others) require high-speed elements for
protection due to their low thermal capacity. SITOR fuse links
(super quick fuse links for semiconductor protection) are ideal
for these types of application.
The following types of short-circuit faults can occur:
• Internal short-circuit:
a faulty semiconductor device causes a short circuit within the
power converter.
• External short-circuit:
a fault in the load causes a short circuit on the output side of the
power converter.
• Shoot-throughs:
In the event of a failure of the chassis converter control system
during inverter operation (commutation failure), the converter con-
nection forms a short-circuit type connection between the DC and
AC power supply system.
Fuse links can be arranged in a number of ways within the converter
connection. A distinction is made between phase fuses in three-
phase current incoming feeders and, if applicable, DC fuses and
arm fuses in the arms of the converter connections (see adjacent
graphs). In the case of center tap connections, fuse links can only
be arranged as phase fuses in three-phase current incoming
feeders.
When using SITOR fuse links of operational class aR, the overload
protection of converter equipment, up to approx. 3.5 times the rated
current of the fuse link, is taken from conventional protective devices
(for example, thermal-delayed overload relays) or, in the case of
controlled power converters, from the current limiter (exception: full
range fuses).
As semiconductor protection, SITOR fuse links of the3NE1 ...-0
series with gS operational class are also suitable for the overload
and short-circuit protection of cables, lines and busbars. All other
dual-function fuses of the SITOR series have a gR characteristic.
Overload protection is ensured as long as the rated current of the SI-
TOR fuse links of the 3NE1 ...-0 series is selected as In ≤Iz
(DIN VDE 0100 Part 430).
The rules of DIN VDE 0100 Part 430 must be applied when rating
short-circuit protection for cables, lines and busbars.
Configuration options
I2_10898
Three-phase bidirectional connection
W3 with phase fuses with arm fuses
I2_10893
I2_10894
( ) ( )
Six-pulse bridge circuit B6 with
phase fuses
Six-pulse bridge circuit B6 with
phase fuses and DC fuse
(reversible connection)
I2_10895
I2_10896
Six-pulse bridge circuit B6 with
phase fuses and DC fuse
(switching for converter)
Six-pulse bridge circuit B6 with
arm fuses
I2_10897
( ) ( )
Six-pulse bridge circuit B6 with arm fuses
(reversible connection)
www.dienhathe.xyz
www.dienhathe.vn
Semiconductor Fuses
LV HRC SITOR Fuse Links
Application information
2/5Siemens ET B1 T · 2007
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
Use in switch disconnectors
When using SITOR semiconductor fuses in 3KL and 3KM switch dis-
connectors with fuses and 3NP fuse switch disconnectors, the rated
current of the fuse must sometimes be reduced due to the higher
power dissipation compared to LV HRC fuses for line protection.
Sometimes when using SITOR semiconductor fuses in switch dis-
connectors, the currents designated can be higher than the rated
currents of the switches. These higher currents only apply when us-
ing SITOR switch disconnectors with semiconductor fuses and can-
not be used when using switch disconnectors with standard LV HRC
fuses. You will find further details in the following selection table.
When using SITOR semiconductor fuses of the 3NC24, 3NC84,
3NE33 and 3NE43 series, the standard switching capacity of the
fuse must not be used as the blades of these fuses (in contrast to
LV HRC fuses) are slit. Occasional switching of currents up to the
rated current of the fuses is permissible.
Due to the mechanical strain on the comparatively long fuse blade,
SITOR semiconductor fuses of the 3NE41 series may only be occa-
sionally switched, and only without load. If only switching without
load is permissible, this must be clearly stated on the switch itself.
The use of SITOR semiconductor fuses > 63 A for overload protec-
tion is not permitted – even if gR fuses are used (exception: 3NE1).
The operational voltage is limited by the rated voltage of the switch
disconnector or the fuse. If switching without load, the limit value is
the rated insulation voltage of the switch disconnector.
The 3NE1 "double protection fuses" can be used as full range fuses
(gS) for semiconductor and line protection.
Due to the dimensions of the SITOR semiconductor fuses, only the
fuses shown in the following selection and ordering data can be
used with 3KL and 3KM switch disconnectors with fuses and 3NP
fuse switch disconnectors.
www.dienhathe.xyz
www.dienhathe.vn
Semiconductor Fuses
LV HRC SITOR Fuse Links
Application information
2/6 Siemens ET B1 T · 2007
Load rating of fuse links with SITOR LV HRC fuse bases
Un = rated voltage
BG = size
In = rated current
WL = varying load factor
Ømin Cu = required conductor cross-section Cu
Imax = maximum permissible current
IWL = maximum permissible current with varying load
SITOR fuse links Ømin Cu LV HRC fuse bases
Order No. Un Operational
class
BG In WL Order No. BG Imax IWL
V AC A mm2
A A
3NC2 4
3NC2 423-3 500 gR 3 150 0.95 70 3NH3 430 3 150 143
3NC2 425-3 500 gR 3 200 0.95 95 3 190 181
3NC2 427-3 500 gR 3 250 0.95 120 3 240 228
3NC2 428-3 500 gR 3 300 0.95 185 3 285 271
3NC2 431-3 500 gR 3 350 0.95 240 3 330 314
3NC2 432-3 500 aR 3 400 0.95 240 3 400 380
3NC8 4
3NC8 423-3 660 gR 3 150 0.85 70 3NH3 430 3 135 115
3NC8 425-3 660 gR 3 200 0.85 95 3 180 153
3NC8 427-3 660 gR 3 250 0.85 120 3 250 213
3NC8 431-3 660 gR 3 350 0.85 240 3 315 268
3NC8 434-3 660 gR 3 500 0.85 2 x 150 3 450 383
3NC8 444-3 600 aR 3 1000 0.95 2 x (60 x 6) 3 800 800
3NE1 0
3NE1 020-2 690 gR 00 80 1.0 25 3NH3 030/
3NH4 030
00 80 80
3NE1 021-0 690 gS 00 100 1.0 35 00 100 100
3NE1 021-2 690 gR 00 100 1.0 35 00 100 100
3NE1 022-0 690 gS 00 125 1.0 50 00 125 125
3NE1 022-2 690 gR 00 125 1.0 50 00 125 125
3NE1 2
3NE1 224-0 690 gS 1 160 1.0 70 3NH3 230/
3NH4 230
1 160 160
3NE1 224-2 690 gR 1 160 1.0 70 1 160 160
3NE1 225-0 690 gS 1 200 1.0 95 1 200 200
3NE1 225-2 690 gR 1 200 1.0 95 1 200 200
3NE1 227-0 690 gS 1 250 1.0 120 1 250 250
3NE1 227-2 690 gR 1 250 1.0 120 1 250 250
3NE1 230-0 690 gS 1 315 1.0 2 x 70 3NH3 330 2 315 315
3NE1 230-2 690 gR 1 315 1.0 2 x 70 2 315 315
3NE1 3
3NE1 331-0 690 gS 2 350 1.0 2 x 95 3NH3 330 2 350 350
3NE1 331-2 690 gR 2 350 1.0 2 x 95 2 350 350
3NE1 332-0 690 gS 2 400 1.0 2 x 95 2 400 400
3NE1 333-0 690 gS 2 450 1.0 2 x 120 3NH3 430 3 450 450
3NE1 333-2 690 gR 2 450 1.0 2 x 120 3 450 450
3NE1 334-0 690 gS 2 500 1.0 2 x 120 3 500 500
3NE1 334-2 690 gR 2 500 1.0 2 x 120 3 500 500
3NE1 4
3NE1 435-0 690 gS 3 560 1.0 2 x 150 3NH3 430 3 560 560
3NE1 435-2 690 gR 3 560 1.0 2 x 150 3 560 560
3NE1 436-0 690 gS 3 630 1.0 2 x 185 3 630 630
3NE1 436-2 690 gR 3 630 1.0 2 x 185 3 630 630
3NE1 437-0 690 gS 3 710 1.0 2 x (40 x 5) 3 710 690
3NE1 437-1 600 gR 3 710 1.0 2 x (40 x 5) 3 690 690
3NE1 437-2 690 gR 3 710 1.0 2 x (40 x 5) 3 710 710
3NE1 438-0 690 gS 3 800 1.0 2 x (50 x 5) 3 800 750
3NE1 438-1 600 gR 3 800 1.0 2 x (50 x 5) 3 750 750
3NE1 438-2 690 gR 3 800 1.0 2 x (50 x 5) 3 800 800
3NE1 447-2 690 gR 3 670 1.0 2 x (40 x 5) 3 670 670
3NE1 448-2 690 gR 3 850 1.0 2 x (40 x 8) 3 850 850
www.dienhathe.xyz
www.dienhathe.vn
Semiconductor Fuses
LV HRC SITOR Fuse Links
Application information
2/7Siemens ET B1 T · 2007
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
Un = rated voltage
BG = size
In = rated current
WL = varying load factor
Ømin Cu = required conductor cross-section Cu
Imax = maximum permissible current
IWL = maximum permissible current with varying load
SITOR fuse links Ømin Cu LV HRC fuse bases
Order No. Un Operational
class
BG In WL Order No. BG Imax IWL
V AC A mm2
A A
3NE1 8
3NE1 813-0 690 gS 000 16 1.0 1.5 3NH3 030/
3NH4 030
00 16 16
3NE1 814-0 690 gS 000 20 1.0 2.5 00 20 20
3NE1 815-0 690 gS 000 25 1.0 4 00 25 25
3NE1 803-0 690 gS 000 35 1.0 6 00 35 35
3NE1 802-0 690 gS 000 40 1.0 10 00 40 40
3NE1 817-0 690 gS 000 50 1.0 10 00 50 50
3NE1 818-0 690 gS 000 63 1.0 16 00 63 63
3NE1 820-0 690 gS 000 80 1.0 25 00 80 80
3NE3
3NE3 221 1000 aR 1 100 0.95 35 3NH3 230/
3NH4 230
1 100 95
3NE3 222 1000 aR 1 125 0.95 50 1 125 119
3NE3 224 1000 aR 1 160 1.0 70 1 160 160
3NE3 225 1000 aR 1 200 1.0 95 1 200 200
3NE3 227 1000 aR 1 250 1.0 120 1 250 250
3NE3 230-0B 1000 aR 1 315 0.95 185 3NH3 330 2 305 290
3NE3 231 1000 aR 1 350 0.95 240 2 335 318
3NE3 232-0B 1000 aR 1 400 0.90 240 2 380 342
3NE3 233 1000 aR 1 450 0.90 2 x 150 2 425 383
3NE3 332-0B 1000 aR 2 400 1.0 240 3NH3 430 3 400 400
3NE3 333 1000 aR 2 450 1.0 2 x 150 3 450 450
3NE3 334-0B 1000 aR 2 500 1.0 2 x 150 3 500 500
3NE3 335 1000 aR 2 560 1.0 2 x 185 3 560 560
3NE3 336 1000 aR 2 630 1.0 2 x 185 3 630 630
3NE3 337-8 900 aR 2 710 1.0 2 x 200 3 680 680
3NE3 338-8 800 aR 2 800 0.95 2 x 200 3 700 665
3NE3 340-8 690 aR 2 900 0.95 2 x 200 3 750 713
3NE4
3NE4 101 1000 gR 0 32 0.85 6 3NH3 120/
3NH4 230
0/1 32 27
3NE4 102 1000 gR 0 40 0.85 10 0/1 40 34
3NE4 117 1000 gR 0 50 0.85 10 0/1 50 43
3NE4 118 1000 aR 0 63 0.85 16 0/1 63 54
3NE4 120 1000 aR 0 80 0.85 25 0/1 80 68
3NE4 121 1000 aR 0 100 0.85 35 0/1 100 85
3NE4 122 1000 aR 0 125 0.85 50 0/1 125 106
3NE4 124 1000 aR 0 160 0.85 70 0/1 160 136
3NE4 327-0B 800 aR 2 250 0.85 120 3NH3 330 2 240 204
3NE4 330-0B 800 aR 2 315 0.85 240 2 300 255
3NE4 333-0B 800 aR 2 450 0.85 2 x (30 x 5) 3NH3 430 3 425 361
3NE4 334-0B 800 aR 2 500 0.85 2 x (30 x 5) 3 475 404
3NE4 337 800 aR 2 710 0.95 2 x (40 x 5) 3 630 599
3NE8
3NE8 015-1 690 gR 00 25 0.95 4 3NH3 030/
3NH4 030
00 25 24
3NE8 003-1 690 gR 00 35 0.95 6 00 35 33
3NE8 017-1 690 gR 00 50 0.90 10 00 50 45
3NE8 018-1 690 gR 00 63 0.95 16 00 63 60
3NE8 020-1 690 aR 00 80 0.95 25 00 80 76
3NE8 021-1 690 aR 00 100 0.95 35 3NH3 030/
3NH4 030
00 100 95
3NE8 022-1 690 aR 00 125 0.95 50 00 125 119
3NE8 024-1 690 aR 00 160 0.95 70 00 160 152
www.dienhathe.xyz
www.dienhathe.vn
Semiconductor Fuses
LV HRC SITOR Fuse Links
Application information
2/8 Siemens ET B1 T · 2007
Load rating of fuse links with SITOR 3NP LV HRC fuse switch disconnectors
Un = rated voltage
BG = size
In = rated current
WL = varying load factor
Ømin Cu = required conductor cross-section Cu
Imax = maximum permissible current
IWL = maximum permissible current with varying load
SITOR fuse links Ø min
Cu
3NP LV HRC fuse switch disconnectors
Add-on units Busbar devices
Order No. Un BG In WL Order No. BG Imax IWL Order No. BG Imax IWL Order No. BG Imax IWL Order No. BG Imax IWL
V AC A mm2
A A A A
3NC2 4
3NC2 423-3 500 3 150 0.95 70 3NP54 3 145 125 3NP44 70 3 140 120 3NP44 76 3 140 120 -- -- -- --
3NC2 425-3 500 3 200 0.95 95 3 180 165 3 175 160 3 175 160 -- -- --
3NC2 427-3 500 3 250 0.95 120 3 225 205 3 220 200 3 215 195 -- -- --
3NC2 428-3 500 3 300 0.95 185 3 255 240 3 250 235 3 245 230 -- -- --
3NC2 431-3 500 3 350 0.95 240 3 330 295 3 320 290 3 315 285 -- -- --
3NC2 432-3 500 3 400 0.95 240 3 400 380 3 370 370 3 360 360 -- -- --
3NC8 4
3NC8 423-3 660 3 150 0.85 70 3NP54 3 135 125 3NP44 70 3 120 120 3NP44 76 3 120 120 -- -- -- --
3NC8 425-3 660 3 200 0.85 95 3 180 165 3 160 160 3 155 155 -- -- --
3NC8 427-3 660 3 250 0.85 120 3 225 205 3 200 200 3 195 195 -- -- --
3NC8 431-3 660 3 350 0.85 240 3 300 275 3 270 270 3 260 260 -- -- --
3NC8 434-3 660 3 500 0.85 2 x 150 3 425 400 3 385 385 3 375 375 -- -- --
3NC8 444-3 600 3 1000 0.95 2 x
(60 x 6)
3NP54 3 800 800 -- -- -- -- 3NP44 76 3 400 400 -- -- -- --
3NE1 02
3NE1 020-2 690 00 80 1.0 25 3NP50 00 80 80 3NP40 70 00 80 80 3NP40 76 00 80 80 -- -- -- --
3NE1 021-0 690 00 100 1.0 35 00 100 100 00 100 100 00 100 100 -- -- --
3NE1 021-2 690 00 100 1.0 35 00 98 101 00 98 98 00 98 98 -- -- --
3NE1 022-0 690 00 125 1.0 125 00 125 125 00 125 125 00 125 125 -- -- --
3NE1 022-2 690 00 125 1.0 125 00 125 125 00 120 120 00 120 120 -- -- --
3NE1 2
3NE1 224-0 690 1 160 1.0 70 3NP52/
3NP42
1 160 160 3NP53/
3NP43
2 160 160 3NP42 76 1 160 160 3NP43 76 2 160 160
3NE1 224-2 690 1 160 1.0 70 1 160 160 2 160 160 1 160 160 2 160 160
3NE1 225-0 690 1 200 1.0 95 1 200 200 2 200 200 1 200 200 2 200 200
3NE1 225-2 690 1 200 1.0 95 1 200/
190
200/
190
2 200 200 1 190 190 2 200 200
3NE1 227-0 690 1 250 1.0 120 1 250 250 2 250 250 1 250 250 2 250 250
3NE1 227-2 690 1 250 1.0 120 1 250/
235
250/
235
2 250 250 1 235 235 2 250 250
3NE1 230-0 690 1 315 1.0 2x 70 3NP53/
3NP43
2 315 315 -- -- -- -- 3NP4376 2 315 315 -- -- -- --
3NE1 230-2 690 1 315 1.0 2x 70 3NP53 2 315 315 3NP43 70 2 315 315 2 315 315 -- -- --
3NE1 3
3NE1 331-0 690 2 350 1.0 2x 95 3NP53/
3NP43
2 350 350 3NP54/
3NP44
3 350 350 3NP43 76 2 350 350 3NP44 76 3 350 350
3NE1 331-2 690 2 350 1.0 2x 95 2 350 350 3 350 350 2 350 350 3 350 350
3NE1 332-0 690 2 400 1.0 2x 95 2 400 400 3 400 400 2 400 400 3 400 400
3NE1 333-0 690 2 450 1.0 2x 120 3NP54/
3NP44
3 450 450 -- -- -- -- 3NP44 76 3 450 450 -- -- -- --
3NE1 333-2 690 2 450 1.0 2x 120 3NP54 3 450 450 3NP44 70 3 425 425 3 425 425 -- -- --
3NE1 334-0 690 2 500 1.0 2x 120 3NP54/
3NP44
3 500 500 -- 3 480 480 -- -- --
3NE1 334-2 690 2 500 1.0 2x 120 3NP54 3 500 500 3NP44 70 3 465 465 3 450 450 -- -- --
3NE1 4
3NE1 435-0 690 3 560 1.0 2x 150 3NP54/
3NP44
3 560 560 -- -- -- -- 3NP44 76 3 510 510 -- -- -- --
3NE1 435-2 690 3 560 1.0 2x 150 3NP54 3 560 560 3NP44 70 3 540 540 3 500 500 -- -- --
3NE1 436-0 690 3 630 1.0 2x 185 3 630 630 3 620 620 3 535 535 -- -- --
3NE1 436-2 690 3 630 1.0 2x 185 3 625 625 3 600 600 3 520 520 -- -- --
3NE1 437-0 690 3 710 1.0 2x
(40x5)
3 710 710 3 690 650 3 600 600 -- -- --
3NE1 437-1 600 3 710 1.0 2x
(40x5)
3 690 690 3 670 630 3 570 570 -- -- --
3NE1 437-2 690 3 710 1.0 2x
(40x5)
3 685 685 -- -- -- -- 3 540 540 -- -- --
3NE1 438-0 690 3 800 1.0 2x
(50x5)
3 800 800 3NP44 70 3 750 700 3 640 630 -- -- --
3NE1 438-1 600 3 800 1.0 2x
(50x5)
3 750 750 3 710 630 3 600 600 -- -- --
3NE1 438-2 690 3 800 1.0 2x
(50x5)
3 770 770 -- -- -- -- 3 580 580 -- -- --
3NE1 447-2 690 3 670 1.0 2x
(40x5)
3 655 655 -- -- -- 3 530 530 -- -- --
3NE1 448-2 690 3 850 1.0 2x
(40x8)
3 820 820 -- -- -- 3 630 630 -- -- --
www.dienhathe.xyz
www.dienhathe.vn
Semiconductor Fuses
LV HRC SITOR Fuse Links
Application information
2/9Siemens ET B1 T · 2007
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
Un = rated voltage
BG = size
In = rated current
WL = varying load factor
Ømin Cu = required conductor cross-section Cu
Imax = maximum permissible current
IWL = maximum permissible current with varying load
SITOR fuse links Ø min
Cu
3NP LV HRC fuse switch disconnectors
Add-on units Busbar devices
Order No. Un BG In WL Order No. BG Imax IWL Order No. BG Imax IWL Order No. BG Imax IWL Order No. BG Imax IWL
V AC A mm2
A A A A
3NE1 8
3NE1 813-0 690 000 16 1.0 1.5 3NP35/
3NP40 10
000 16 16 3NP50/
3NP40 70
00 16 16 3NP40 15/
3NP40 16
000 16 16 3NP40 75/
3NP40 76
00 16 16
3NE1 814-0 690 000 20 1.0 2.5 000 20 20 00 20 20 000 20 20 00 20 20
3NE1 815-0 690 000 25 1.0 4 000 25 25 00 25 25 000 25 25 00 25 25
3NE1 803-0 690 000 35 1.0 6 000 35 35 00 35 35 000 35 35 00 35 35
3NE1 802-0 690 000 40 1.0 10 000 40 40 00 40 40 000 40 40 00 40 40
3NE1 817-0 690 000 50 1.0 10 000 50 50 00 50 50 000 50 50 00 50 50
3NE1 818-0 690 000 63 1.0 16 000 63 63 00 63 63 000 63 63 00 63 63
3NE1 820-0 690 000 80 1.0 25 000 80 80 00 80 80 000 80 80 00 80 80
3NE3
3NE3 221 1000 1 100 0.95 35 3NP52/
3NP42
1 95 90 3NP53/
3NP43
2 100 95 3NP42 76 1 95 90 3NP43 76 2 100 95
3NE3 222 1000 1 125 0.95 50 1 110 110 2 120 114 1 115 109 2 125 119
3NE3 224 1000 1 160 1.0 70 1 140 140 2 150 150 1 150 150 2 160 160
3NE3 225 1000 1 200 1.0 95 1 175 175 2 190 190 1 185 185 2 200 200
3NE3 227 1000 1 250 1.0 120 1 210 210 2 230 230 1 225 225 2 250 250
3NE3 230-0B 1000 1 315 0.95 185 3NP53 2 285 280 3NP43 70 2 270 270 3NP43 76 2 285 285 -- -- -- --
3NE3 231 1000 1 350 0.95 240 2 310 300 2 290 290 2 310 310 -- -- --
3NE3 232-0B 1000 1 400 0.90 240 2 330 320 2 310 310 2 330 330 -- -- --
3NE3 233 1000 1 450 0.90 2x 150 2 360 340 2 330 330 2 360 360 -- -- --
3NE3 332-0B 1000 2 400 1.0 240 3NP54 3 360 345 3NP44 70 3 345 345 3NP44 76 3 340 340 -- -- -- --
3NE3 333 1000 2 450 1.0 2x 150 3 400 385 3 385 385 3 370 370 -- -- --
3NE3 334-0B 1000 2 500 1.0 2x 150 3 450 450 3 430 430 3 410 410 -- -- --
3NE3 335 1000 2 560 1.0 2x 185 3 510 510 3 490 490 3 450 450 -- -- --
3NE3 336 1000 2 630 1.0 2x 185 3 580 580 3 560 560 3 500 500 -- -- --
3NE3 337-8 900 2 710 1.0 2x 200 3 630 630 3 590 590 3 510 510 -- -- --
3NE3 338-8 800 2 800 0.95 2x 200 3 630 630 3 605 605 3 520 520 -- -- --
3NE3 340-8 690 2 900 0.95 2x 200 3 630 630 3 630 630 3 530 530 -- -- --
3NE4
3NE4 101 1000 0 32 0.85 6 3NP52 1 32 27 3NP42 70 1 32 27 3NP42 76 1 32 27 -- -- -- --
3NE4 102 1000 0 40 0.85 10 1 40 34 1 38 32 1 38 32 -- -- --
3NE4 117 1000 0 50 0.85 10 1 50 43 1 45 40 1 45 40 -- -- --
3NE4 118 1000 0 63 0.85 16 1 63 54 1 59 50 1 59 50 -- -- --
3NE4 120 1000 0 80 0.85 25 1 80 68 1 76 65 1 76 65 -- -- --
3NE4 121 1000 0 100 0.85 35 1 95 81 1 90 78 1 90 78 -- -- --
3NE4 122 1000 0 125 0.85 50 1 120 102 1 115 98 1 115 98 -- -- --
3NE4 124 1000 0 160 0.85 70 1 150 128 1 144 125 1 144 125 -- -- --
3NE4 327-0B 800 2 250 0.85 120 3NP53/
3NP54
2/3 210/
220
205/
210
3NP44 70 3 205 200 3NP44 76 3 235 210 -- -- -- --
3NE4 330-0B 800 2 315 0.85 240 2/3 270/
285
255/
265
3 260 250 3 280 260 -- -- --
3NE4 333-0B 800 2 450 0.85 2x
(30x5)
2/3 400/
420
370/
380
3 375 360 3 390 370 -- -- --
3NE4 334-0B 800 2 500 0.85 2x
(30x5)
3NP54 3 450 400 3NP44 70 3 410 395 3NP44 76 3 415 400 -- -- -- --
3NE4 337 800 2 710 0.95 2x
(40x5)
3 600 570 3 540 540 3 480 480 -- -- --
3NE8
3NE8 015-1 690 00 25 0.95 4 3NP40 70/
3NP50
00 25 24 -- -- -- -- 3NP40 75/
3NP40 76
00 25 24 -- -- -- --
3NE8 003-1 690 00 35 0.95 6 00 33 31 -- -- -- 00 33 31 -- -- --
3NE8 017-1 690 00 50 0.90 10 00 45 41 -- -- -- 00 45 41 -- -- --
3NE8 018-1 690 00 63 0.95 16 00 54 51 -- -- -- 00 53 50 -- -- --
3NE8 020-1 690 00 80 0.95 25 00 68 65 -- -- -- 00 68 65 -- -- --
3NE8 021-1 690 00 100 0.95 35 3NP50/
3NP40 70
00 89 85 -- -- -- -- 3NP40 75/
3NP40 76
00 85 81 -- -- -- --
3NE8 022-1 690 00 125 0.95 50 00 106 101 -- -- -- 00 100 95 -- -- --
3NE8 024-1 690 00 160 0.95 70 00 130 124 -- -- -- 00 125 120 -- -- --
www.dienhathe.xyz
www.dienhathe.vn
Semiconductor Fuses
LV HRC SITOR Fuse Links
Application information
2/10 Siemens ET B1 T · 2007
Load rating of fuse links with SITOR 3KL/3KM LV HRC fuse switch disconnectors
Un = rated voltage
BG = size
In = rated current
WL = varying load factor
Ømin Cu = required conductor cross-section Cu
Imax = maximum permissible current
IWL = maximum permissible current with varying load
SITOR fuse links Ø min
Cu
3KL/3KM switch disconnectors with fuses
3KL add-on devices 3KM busbar devices
Order No. Un BG In WL Order No. BG Imax IWL Order No. BG Imax IWL Order No. BG Imax IWL Order No. BG Imax IWL
V AC A mm2
A A A A
3NC2 4
3NC2 423-3 500 3 150 0.95 70 3KL61 3 145 138 3KL62 3 150 143 -- -- -- -- -- -- -- --
3NC2 425-3 500 3 200 0.95 95 3 180 171 3 190 181 -- -- -- -- -- --
3NC2 427-3 500 3 250 0.95 120 3 225 214 3 240 228 -- -- -- -- -- --
3NC2 428-3 500 3 300 0.95 185 3 255 242 3 270 257 -- -- -- -- -- --
3NC2 431-3 500 3 350 0.95 240 3 330 314 3 345 328 -- -- -- -- -- --
3NC2 432-3 500 3 400 0.95 240 3 400 380 3 400 380 -- -- -- -- -- --
3NC8 4
3NC8 423-3 660 3 150 0.85 70 3KL61 3 135 115 3KL62 3 140 119 -- -- -- -- -- -- -- --
3NC8 425-3 660 3 200 0.85 95 3 180 153 3 190 162 -- -- -- -- -- --
3NC8 427-3 660 3 250 0.85 120 3 225 191 3 240 204 -- -- -- -- -- --
3NC8 431-3 660 3 350 0.85 240 3 300 255 3 315 268 -- -- -- -- -- --
3NC8 434-3 660 3 500 0.85 2 x 150 3 425 361 3 450 383 -- -- -- -- -- --
3NC8 444-3 600 3 1000 0.95 2 x
(60 x 6)
3 800 800 3 630 630 -- -- -- -- -- --
3NE1 0
3NE1 020-2 690 00 80 1.0 25 3KL52 00 80 80 3KL53 00 80 80 3KM52 00 80 80 3KM53 00 80 80
3NE1 021-0 690 00 100 1.0 35 00 100 100 00 100 100 00 100 100 00 100 100
3NE1 021-2 690 00 100 1.0 35 00 100 100 00 100 100 00 100 100 00 100 100
3NE1 022-0 690 00 125 1.0 125 00 125 125 00 125 125 00 125 125 00 125 125
3NE1 022-2 690 00 125 1.0 125 00 125 125 00 125 125 00 125 125 00 125 125
3NE1 2
3NE1 224-0 690 1 160 1.0 70 3KL55 1 160 160 3KL57 2 160 160 3KM55 1 160 160 3KM57 2 160 160
3NE1 224-2 690 1 160 1.0 70 1 160 160 2 160 160 1 160 160 2 160 160
3NE1 225-0 690 1 200 1.0 95 1 200 200 2 200 200 1 200 200 2 200 200
3NE1 225-2 690 1 200 1.0 95 1 200 200 2 200 200 1 200 200 2 200 200
3NE1 227-0 690 1 250 1.0 120 1 250 250 2 250 250 1 250 250 2 250 250
3NE1 227-2 690 1 250 1.0 120 1 245 245 2 250 250 1 245 245 2 250 250
3NE1 230-0 690 1 315 1.0 2x 70 3KL57 2 315 315 -- -- -- -- 3KM57 2 315 315 -- -- -- --
3NE1 230-2 690 1 315 1.0 2x 70 2 280 280 -- -- -- 2 280 280 -- -- --
3NE1 3
3NE1 331-0 690 2 350 1.0 2x 95 3KL57 2 330 330 3KL61 3 350 350 3KM57 2 330 330 -- -- -- --
3NE1 331-2 690 2 350 1.0 2x 95 2 300 300 3 350 350 2 300 300 -- -- --
3NE1 332-0 690 2 400 1.0 2x 95 2 375 375 3 400 400 2 375 375 -- -- --
3NE1 333-0 690 2 450 1.0 2x 120 3KL61 3 450 450 3KL62 3 450 450 2 400 400 -- -- --
3NE1 333-2 690 2 450 1.0 2x 120 3 450 450 3 450 500 2 325 325 -- -- --
3NE1 334-0 690 2 500 1.0 2x 120 3 500 500 3 500 500 2 400 400 -- -- --
3NE1 334-2 690 2 500 1.0 2x 120 3 500 500 3 500 500 2 350 350 -- -- --
3NE1 4
3NE1 435-0 690 3 560 1.0 2x 150 3KL61 3 560 560 3KL62 3 560 560 -- -- -- -- -- -- -- --
3NE1 435-2 690 3 560 1.0 2x 150 3 560 560 3 560 560 -- -- -- -- -- --
3NE1 436-0 690 3 630 1.0 2x 185 3 630 630 3 630 630 -- -- -- -- -- --
3NE1 436-2 690 3 630 1.0 2x 185 3 615 615 3 630 630 -- -- -- -- -- --
3NE1 437-0 690 3 710 1.0 2x
(40x5)
3 630 630 3 710 710 -- -- -- -- -- --
3NE1 437-1 600 3 710 1.0 2x
(40x5)
3 630 630 3 710 710 -- -- -- -- -- --
3NE1 437-2 690 3 710 1.0 2x
(40x5)
3 630 630 3 700 700 -- -- -- -- -- --
3NE1 438-0 690 3 800 1.0 2x
(50x5)
3 630 630 3 800 800 -- -- -- -- -- --
3NE1 438-1 600 3 800 1.0 2x
(50x5)
3 630 630 3 800 800 -- -- -- -- -- --
3NE1 438-2 690 3 800 1.0 2x
(50x5)
3 630 630 3 760 760 -- -- -- -- -- --
3NE1 447-2 690 3 670 1.0 2x
(40x5)
3 630 630 3 670 670 -- -- -- -- -- --
3NE1 448-2 690 3 850 1.0 2x
(40x8)
3 630 630 3 790 790 -- -- -- -- -- --
www.dienhathe.xyz
www.dienhathe.vn
Semiconductor Fuses
LV HRC SITOR Fuse Links
Application information
2/11Siemens ET B1 T · 2007
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
Un = rated voltage
BG = size
In = rated current
WL = varying load factor
Ømin Cu = required conductor cross-section Cu
Imax = maximum permissible current
IWL = maximum permissible current with varying load
SITOR fuse links Ø min
Cu
3KL/3KM switch disconnectors with fuses
3KL... add-on devices 3KM... busbar devices
Order No. Un BG In WL Order No. BG Imax IWL Order No. BG Imax IWL Order No. BG Imax IWL Order No. BG Imax IWL
V AC A mm2
A A A A
3NE1 8
3NE1 813-0 690 000 16 1.0 1.5 3KL50 00 16 16 3KL52 00 16 16 3KM50 00 16 16 3KM52 00 16 16
3NE1 814-0 690 000 20 1.0 2.5 00 20 20 00 20 20 00 20 20 00 20 20
3NE1 815-0 690 000 25 1.0 4 00 25 25 00 25 25 00 25 25 00 25 25
3NE1 803-0 690 000 35 1.0 6 00 35 35 00 35 35 00 35 35 00 35 35
3NE1 802-0 690 000 40 1.0 10 00 40 40 00 40 40 00 40 40 00 40 40
3NE1 817-0 690 000 50 1.0 10 00 50 50 00 50 50 00 50 50 00 50 50
3NE1 818-0 690 000 63 1.0 16 00 63 63 00 63 63 00 63 63 00 63 63
3NE1 820-0 690 000 80 1.0 25 3KL52 00 80 80 -- -- -- -- 3KM52 00 80 80 -- -- -- --
3NE3
3NE3 221 1000 1 100 0.95 35 3KL55 1 90 86 3KL57 2 95 90 3KM55 1 90 86 3KM57 2 95 90
3NE3 222 1000 1 125 0.95 50 1 110 105 2 115 109 1 110 105 2 115 109
3NE3 224 1000 1 160 1.0 70 1 140 140 2 150 150 1 140 140 2 150 150
3NE3 225 1000 1 200 1.0 95 1 175 175 2 180 180 1 175 175 2 180 180
3NE3 227 1000 1 250 1.0 120 1 210 210 2 220 220 1 210 210 2 220 220
3NE3 230-0B 1000 1 315 0.95 185 3KL57 2 240 228 -- -- -- -- 3KM57 2 240 228 -- -- -- --
3NE3 231 1000 1 350 0.95 240 2 265 252 -- -- -- 2 265 252 -- -- --
3NE3 232-0B 1000 1 400 0.90 240 2 290 261 -- -- -- 2 290 261 -- -- --
3NE3 233 1000 1 450 0.90 2x 150 2 320 288 -- -- -- 2 320 288 -- -- --
3NE3 332-0B 1000 2 400 1.0 240 3KL61 3 340 340 3KL62 3 360 360 3KM57 2 290 290 -- -- -- --
3NE3 333 1000 2 450 1.0 2x 150 3 380 380 3 400 400 2 320 320 -- -- --
3NE3 334-0B 1000 2 500 1.0 2x 150 3 440 440 3 470 470 2 360 360 -- -- --
3NE3 335 1000 2 560 1.0 2x 185 3 500 500 3 530 530 2 400 400 -- -- --
3NE3 336 1000 2 630 1.0 2x 185 3 540 540 3 580 580 2 400 400 -- -- --
3NE3 337-8 900 2 710 1.0 2x 200 3 600 600 3 640 640 2 400 400 -- -- --
3NE3 338-8 800 2 800 0.95 2x 200 3 630 630 3 720 680 2 400 400 -- -- --
3NE3 340-8 690 2 900 0.95 2x 200 3 630 630 3 800 750 2 400 400 -- -- --
3NE4
3NE4 101 1000 0 32 0.85 6 3KL55 1 32 27 -- -- -- -- 3KM55 1 32 27 -- -- -- --
3NE4 102 1000 0 40 0.85 10 1 40 34 -- -- -- 1 40 34 -- -- --
3NE4 117 1000 0 50 0.85 10 1 50 43 -- -- -- 1 50 43 -- -- --
3NE4 118 1000 0 63 0.85 16 1 63 54 -- -- -- 1 63 54 -- -- --
3NE4 120 1000 0 80 0.85 25 1 80 68 -- -- -- 1 80 68 -- -- --
3NE4 121 1000 0 100 0.85 35 1 95 81 -- -- -- 1 95 81 -- -- --
3NE4 122 1000 0 125 0.85 50 1 120 102 -- -- -- 1 120 102 -- -- --
3NE4 124 1000 0 160 0.85 70 1 150 128 -- -- -- 1 150 128 -- -- --
3NE4 327-0B 800 2 250 0.85 120 3KL57 2 175 149 3KL61 3 200 170 3KM57 2 175 149 -- -- -- --
3NE4 330-0B 800 2 315 0.85 240 2 230 196 3 260 221 2 230 196 -- -- --
3NE4 333-0B 800 2 450 0.85 2x
(30x5)
2 340 289 3 370 315 2 340 289 -- -- --
3NE4 334-0B 800 2 500 0.85 2x
(30x5)
3KL61 3 425 361 3KL62 3 450 375 2 380 323 -- -- --
3NE4 337 800 2 710 0.95 2x
(40x5)
3 600 570 3 630 600 2 400 400 -- -- --
3NE8 0
3NE8 015-1 690 00 25 0.95 4 3KL50 00 25 24 3KL52 00 25 24 3KM50 00 25 24 3KM52 00 25 24
3NE8 003-1 690 00 35 0.95 6 00 33 31 00 35 33 00 33 31 00 35 33
3NE8 017-1 690 00 50 0.90 10 00 45 41 00 50 45 00 45 41 00 50 45
3NE8 018-1 690 00 63 0.95 16 00 54 51 00 60 57 00 54 51 00 60 57
3NE8 020-1 690 00 80 0.95 25 3KL52 00 68 65 3KL53 00 68 65 3KM52 00 68 65 3KM53 00 68 65
3NE8 021-1 690 00 100 0.95 35 3KL52 00 89 85 3KL53 00 89 85 3KM52 00 89 85 3KM53 00 89 85
3NE8 022-1 690 00 125 0.95 50 00 106 101 00 106 101 00 106 101 00 106 101
3NE8 024-1 690 00 160 0.95 70 00 130 124 00 130 124 00 130 124 00 130 124
www.dienhathe.xyz
www.dienhathe.vn
Semiconductor Fuses
LV HRC SITOR Fuse Links
Application information
2/12 Siemens ET B1 T · 2007
Standards
The SITOR fuse links comply with the following standards:
• IEC 60269-4
• EN 60269-4
If noted in the selection and ordering data and characteristic curves,
the SITOR fuse links also comply with the following standards and
regulations:
• IEC 60269-2-1
DIN VDE 0636-201
(for installation in LV HRC fuse bases according to VDE 0636/201,
as well as in fuse switch disconnectors and switch disconnectors
with fuses)
• u
The following SITOR fuse links and LV HRC fuse bases are also
u recognized:
• CCC
The following SITOR fuse links have the Chinese certification CCC:
3NE1 0..-0
3NE1 8..-0
3NE1 2..-0
3NE3 2..
3NE3 3..
• IEC 60269-4-1
DIN VDE 0636-401
(for screwing onto busbar). SITOR fuse links of size 1 to 3 with
gauge 110 mm are also suitable for installation in LV HRC fuse
bases according to IEC 60269-2-1 and in fuse switch disconnec-
tors and switch disconnectors with fuses.
•
All SITOR fuse links with rated voltage Un ≤1000 V are CE-marked
according to the low-voltage Directive 73/23/EWG. The CE mark-
ing confirms conformance of the products with the requirements of
the directive.
■More information
Environment-friendly recycling
In 1995, seven German manufacturers of LV HRC/HV HRC fuse links
founded a non-profit association.
LV HRC/HV HRC Recycling
The objective is to provide a useful recycling option for used fuse
links and determine an acceptable disposal concept that meets all
the requirements of modern environment protection.
Used fuse links are sorted according to product type and are
accepted back without packaging for recycling, melted down and
the recovered materials are fed back into the material cycle.
According to the regulations, statutes and articles of the association,
any surplus from the recycling process is donated to a
university in order to encourage research in the area of fuse link
technology.
For further information, please visit our Web site at:
http://www.nh-hh-recycling.de
Disclaimer
The products described here were developed as part of an overall
plant or machine to perform safety-related functions. A complete fail-
safe system usually contains sensors, evaluation units, signaling de-
vices and concepts for failsafe disconnection. It is the responsibility
of the manufacturer of a plant or machine to ensure the correct over-
all function. Siemens AG, its branches and affiliated companies
(hereafter "Siemens"), is not in a position to guarantee the function of
an overall plant or machine that was not designed by Siemens.
Siemens can accept no liability for recommendations, either explicit
or implicit, contained in the following description. Furthermore, no
warranty or liability claims above and beyond those provided for in
the Siemens General Terms and Conditions can be derived from the
description.
Caution
Fuses must always be fitted by a qualified technician.
Series Registration number Reference
3NC1 0.., 3NC1 4..
3NC2 2.., 3NE1 ...
3NE3 2.., 3NE3 3..
3NE4 1.., 3NE8 0..-1
3NE8 7..-1
JFHR2 E167357
3NC1 038-., 3NC1 09.
3NC1 49., , 3NC2 29.
IZLT2 E220063
3NH3 030, 3NH3 120
3NH3 230, 3NH3 330
3NH3 430
IZLT2 E171267
NH HH
www.dienhathe.xyz
www.dienhathe.vn
Semiconductor Fuses
LV HRC SITOR Fuse Links
Rated voltage 500 V AC
2/13Siemens ET B1 T · 2007
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
■Technical specifications
1)
Cooling air speed 1 m/s. In the case of natural air cooling,
reduction of 5 %.
■Selection and ordering data
For dimensional drawings, see pages 2/48 and 2/49.
1)
Cladding dimensions and grip lugs according to IEC 60269-2-1;
but blade slotted according to IEC 60269-4-1.
Type 3NC2 423
3NC2 423-3
3NC2 425
3NC2 425-3
3NC2 427
3NC2 427-3
3NC2 428
3NC2 428-3
3NC2 431
3NC2 431-3
3NC2 432
3NC2 432-3
Operational class (IEC 60269) gR aR
Rated voltage Un V AC 500
Rated current In A 1501)
2001)
2501)
3001)
3501)
4001)
Melting I2t value I2ts (tvs = 1 ms) A2
s 7000 13600 21000 28000 53000 83000
Breaking I2t value I2tA at Un A2
s 33000 64000 99000 132000 249000 390000
Temperature rise at In (body center) K 26 25 30 40 35 30
Power dissipation at In W 35 40 50 65 60 50
Varying load factor WL 0.85
Weight approx. kg 0.95
Accessories
Fuse base, 1-pole 3NH3 430
Fuse puller 3NX1 011
Fuse switch disconnectors 3NP54
Switch disconnector with fuses 3KL61 30-1.B0
Size In Operational
class
Order No. Weight
1 unit
approx.
PS*/
P. unit
A kg Unit(s)
Rated voltage 500 V AC
with bolt-on links
Mounting dimensions: 110 mm
31)
150 gR 3NC2 423-3 1.063 3
200 gR 3NC2 425-3 1.057 3
250 gR 3NC2 427-3 1.066 3
300 gR 3NC2 428-3 1.078 3
350 aR 3NC2 431-3 1.056 3
400 aR 3NC2 432-3 1.062 3
Special design with 2 oblong slots
3 150 gR 3NC2 423 1.055 3
200 gR 3NC2 425 1.070 3
250 gR 3NC2 427 1.056 3
300 gR 3NC2 428 1.056 3
350 aR 3NC2 431 1.061 3
400 aR 3NC2 432 1.056 1/3
* You can order this quantity or a multiple thereof.
www.dienhathe.xyz
www.dienhathe.vn
Semiconductor Fuses
LV HRC SITOR Fuse Links
Rated voltage 500 V AC
2/14 Siemens ET B1 T · 2007
■Characteristic curves
Series 3NC2 4..
Size: 3
Operational class: gR or aR
Rated voltage: 500 V AC
Rated current: 150 ... 400 A
Time/current characteristics diagram Let-through characteristics (current limitation at 50 Hz)
Correction factor kA for breaking I2
t value Peak arc voltage
2102
10-3
2
4
6
10-2
64 1038 2 64 1048
2
4
6
10-1
2
4
6
100
2
4
6
101
2
4
6
102
2
4
6
103
2
4
6
104
I2_10809
4 0 0 A3 0 0 A2 0 0 A
3 5 0 A2 5 0 A1 5 0 A
vs
p [ A ]
[s]Virtualpre-arcingtime
Prospective short-circuit current
p
c
103 2 64 1048
10
2
4
6
10
I2_10812
4
3
2 64 1058 2
2
4
6
105
[A]
[ A ]
1 5 0 A
2 0 0 A
2 5 0 A
3 0 0 A
3 5 0 A
4 0 0 A
Prospective short-circuit current
Unlimited peak values:
DC component 50 %
DC component 0 %
Let-throughcurrent
0 100 200 300 400 500 600
1
A
w [ V ]Recovery voltage
Correctionfactor
0.8
0.6
0.4
0.2
0 200 400 600 800
400
800
1200
s
w
1400
1000
600
200
0
I2_10811
[ V ]
[V]
Recovery voltage
PeakarcvoltageÛ
www.dienhathe.xyz
www.dienhathe.vn
Semiconductor Fuses
LV HRC SITOR Fuse Links
Rated voltage 600 V AC
2/15Siemens ET B1 T · 2007
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
■Technical specifications
1)
Temperature rise and power dissipation for operation in LV HRC fuse base.
■Selection and ordering data
For dimensional drawings, see pages 2/48 and 2/49.
Type 3NE1 437-1 3NE1 438-1
Operational class (IEC 60269) gR
Rated voltage Un V AC 600
Rated current In A 710 800
Melting I2t value I2ts (tvs = 1 ms) A2
s 321000 437000
Breaking I2t value I2tA at Un A2
s 2460000 3350000
Temperature rise at In (body center)1) K 85 95
Power dissipation at In
1) W 65 72
Varying load factor WL 1.0
Certification according to UL 248-13
Weight approx. kg 0.95
Accessories
Fuse base, 1-pole 3NH3 430
Fuse puller 3NX1 011
Fuse switch disconnectors 3NP54
Switch disconnector with fuses 3KL62 30
Size In Operational
class
Order No. Weight
1 unit
approx.
PS*/
P. unit
A kg Unit(s)
Rated voltage 600 V AC
for mounting in LV HRC fuse bases
3 710 gR 3NE1 437-1 1.120 3
800 gR 3NE1 438-1 1.113 3
* You can order this quantity or a multiple thereof.
www.dienhathe.xyz
www.dienhathe.vn
Semiconductor Fuses
LV HRC SITOR Fuse Links
Rated voltage 600 V AC
2/16 Siemens ET B1 T · 2007
■Characteristic curves
Series 3NE1 437-1, 3NE1 438-1
Size: 3
Operational class: gR
Rated voltage: 600 V AC
Rated current: 710 ... 800 A
Time/current characteristics diagram Let-through characteristics (current limitation at 50 Hz)
Correction factor kA for breaking I2
t value Peak arc voltage
p
vs
2102
10-3
2
4
6
10-2
64 1038 2 64 1048 2 4
2
4
6
10-1
2
4
6
100
2
4
6
101
2
4
6
102
2
4
6
103
2
4
6
104
I2_10835
6 1058
7 1 0 A
8 0 0 A
[ A ]
[s]Virtualpre-arcingtime
Prospective short-circuit current
p
c
103 2 64 1048
10
2
4
6
10
I2_10838
5
4
2 64 1058 2
[A]
[ A ]
7 1 0 A
8 0 0 A
Prospective short-circuit current
Unlimited peak values:
DC component 50 %
DC component 0 %
Let-throughcurrent
0 100 200 300 400 500 600
1
700 800
A
w [ V ]
Correctionfactor
Recovery voltage
0.2
0.4
0.6
0.8
200 400 500 600 700 800100
s
w
300
1400
1200
1000
800
600
400
200
0
[ V ]
[V]
0
Peakarcvoltage
Recovery voltage
Û
www.dienhathe.xyz
www.dienhathe.vn
Semiconductor Fuses
LV HRC SITOR Fuse Links
Rated voltage 660 V AC
2/17Siemens ET B1 T · 2007
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
■Technical specifications
1)
Cooling air speed 1 m/s. In the case of natural air cooling,
reduction of 5 %.
■Selection and ordering data
For dimensional drawings, see pages 2/48 and 2/49.
1)
Cladding dimensions and grip lugs according to IEC 60269-2-1;
but blade slotted according to IEC 602269-4-1.
Type 3NC8 423
3NC8 423-3
3NC8 425
3NC8 425-3
3NC8 427
3NC8 427-3
3NC8 431
3NC8 431-3
3NC8 434
3NC8 434-3
3NC8 444-3
Operational class (IEC 60269) gR aR
Rated voltage Un V AC 660 600
Rated current In A 1501)
2001)
250 3501)
5001)
10001)
Melting I2t value I2ts (tvs = 1 ms) A2
s 1100 2400 4400 11000 28000 400000
Breaking I2t value I2tA at Un A2
s 17600 38400 70400 176000 448000 2480000
Temperature rise at In (body center) K 33 46 95 65 75 110
Power dissipation at In W 40 55 72 95 130 140
Varying load factor WL 0.85 0.9
Weight approx. kg 0.95
Accessories
Fuse base, 1-pole 3NH3 430 –
Fuse puller 3NX1 011
Fuse switch disconnectors 3NP54 –
Switch disconnector with fuses 3KL61 30-1AB0 –
Size In Opera-
tional class
Order No. Weight
1 unit
approx.
PS*/
P. unit
A kg Unit(s)
Rated voltage 660 V AC
with bolt-on links
Mounting dimensions: 110 mm
31)
150 gR 3NC8 423-3 1.062 3
200 gR 3NC8 425-3 1.063 3
250 gR 3NC8 427-3 1.069 3
350 gR 3NC8 431-3 1.072 3
500 gR 3NC8 434-3 1.069 3
1000 aR 3NC8 444-3 1.085 3
Special design with 2 oblong slots
3 150 gR 3NC8 423 1.044 3
200 gR 3NC8 425 1.060 3
250 gR 3NC8 427 1.074 3
350 gR 3NC8 431 1.065 3
500 gR 3NC8 434 1.095 3
* You can order this quantity or a multiple thereof.
www.dienhathe.xyz
www.dienhathe.vn
Semiconductor Fuses
LV HRC SITOR Fuse Links
Rated voltage 660 V AC
2/18 Siemens ET B1 T · 2007
■Characteristic curves
Series 3NC8 4..
Size: 3
Operational class: gR or aR
Rated voltage: 660 V AC
Rated current: 150 ... 1000 A
Time/current characteristics diagram Let-through characteristics (current limitation at 50 Hz)
Correction factor kA for breaking I2
t value Peak arc voltage
p
vs
2102
10-3
2
4
6
10-2
64 1038 2 64 1048 2 4
2
4
6
10-1
2
4
6
100
2
4
6
101
2
4
6
102
2
4
6
103
2
4
6
104
I2_10821
6 1058
5 0 0 A
3 5 0 A
2 5 0 A
2 0 0 A
1 0 0 0 A
1 5 0 A
[ A ]
[s]Virtualpre-arcingtime
Prospective short-circuit current
102
2 64 108
10
2
4
6
2
4
6
4
c
p [A]
[A]
105
103
3
2 64 108 4
2 64 108 5
2 4
1 5 0 A
I2_10824
2 0 0 A
2 5 0 A
3 0 0 A
3 5 0 A
4 0 0 A
Let-throughcurrent
Prospective short-circuit current
Unlimited peak values:
DC component 50 %
DC component 0 %
0 100 200 300 400 500 600
1
700 800
A
w
1 0 0 0 A
1 5 0 . . . 5 0 0 A
[ V ]
Correctionfactor
Recovery voltage
0.2
0.4
0.6
0.8
0 200 400 600 800
400
800
1200
s
w
1400
1000
600
200
0
I2_10823
1 0 0 0 A
1 5 0 . . . 5 0 0 A
[ V ]
[V]
Recovery voltage
PeakarcvoltageÛ
www.dienhathe.xyz
www.dienhathe.vn
Semiconductor Fuses
LV HRC SITOR Fuse Links
Rated voltage 690 V AC/700 V DC
2/19Siemens ET B1 T · 2007
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
■Technical specifications
■Selection and ordering data
For dimensional drawings, see pages 2/48 and 2/49.
Type 3NE8 714-1 3NE8 715-1 3NE8 701-1 3NE8 702-1 3NE8 717-1 3NE8 718-1
Operational class (IEC 60269) gR aR
Rated voltage Un V 690 V AC/700 V DC
Rated current In A 20 25 32 40 50 63
Melting I2t value I2ts (tvs = 1 ms) A2
s 12 19 40 69 115 215
Breaking I2t value I2tA at Un A2
s 83 140 285 490 815 1550
Temperature rise at In (body center) K 40 45 55 60 70
Power dissipation at In W 7 9 10 12 15 16
Varying load factor WL 0.9 0.95
Certification according to UL 248-13
Weight approx. kg 0.13
Type 3NE8 720-1 3NE8 721-1 3NE8 722-1 3NE8 724-1 3NE8 725-1 3NE8 727-1 3NE8 731-1
Operational class (IEC 60269) aR
Rated voltage Un V 690 V AC/700 V DC
Rated current In A 80 100 125 160 200 250 315
Melting I2
t value I2
ts (tvs = 1 ms) A2
s 380 695 1250 2350 4200 7750 12000
Breaking I2
t value I2
tA at Un A2
s 2700 4950 9100 17000 30000 55000 85500
Temperature rise at In (body center) K 80 75 80 100 120 125 150
Power dissipation at In W 18 19 23 31 36 42 54
Varying load factor WL 0.9 0.95 0.9 0.85
Certification according to UL 248-13
Weight approx. kg 0.13
Size In Operational
class
Order No. Weight
1 unit
approx.
PS*/
P. unit
A kg Unit(s)
Rated voltage 690 V AC/700 V DC
with bolt-on links
Mounting dimensions: 80 mm
000 20 gR 3NE8 714-1 0.130 10
25 gR 3NE8 715-1 0.130 10
32 gR 3NE8 701-1 0.131 10
40 gR 3NE8 702-1 0.131 10
50 gR 3NE8 717-1 0.132 10
63 aR 3NE8 718-1 0.132 10
80 aR 3NE8 720-1 0.131 10
100 aR 3NE8 721-1 0.130 10
125 aR 3NE8 722-1 0.131 10
160 aR 3NE8 724-1 0.132 10
200 aR 3NE8 725-1 0.130 10
250 aR 3NE8 727-1 0.133 10
315 aR 3NE8 731-1 0.134 10
* You can order this quantity or a multiple thereof.
www.dienhathe.xyz
www.dienhathe.vn
Semiconductor Fuses
LV HRC SITOR Fuse Links
Rated voltage 690 V AC/700 V DC
2/20 Siemens ET B1 T · 2007
■Characteristic curves
Series 3NE8 71.-1, 3NE8 70.-1
Size: 000
Operational class: gR or aR
Rated voltage: AC 690 V/ 700 V DC
Rated current: 20 ... 63 A
Time/current characteristics diagram Let-through characteristics (current limitation at 50 Hz)
Correction factor kA for breaking I2
t value Peak arc voltage
2101
10-3
2
4
6
10-2
64 1028 2 64 1038
2
4
6
10-1
2
4
6
100
2
4
6
101
2
4
6
102
2
4
6
103
2
4
6
104
I2_10813
5 0 A3 2 A2 0 A
6 3 A4 0 A2 5 A
vs
p [ A ]
[s]Virtualpre-arcingtime
Prospective short-circuit current
102
2 64 108
10
2
4
6
2
4
6
3
c
p [A]
[A]
104
102
3
2 64 108 4
2 64 108 5
2 4
2 0 A
I2_10816
2 5 A
3 2 A
4 0 A
5 0 A
6 3 A
Let-throughcurrent
Prospective short-circuit current
Unlimited peak values:
DC component 50 %
DC component 0 %
0 100 200 300 400 500 600
1
700 800
A
w [ V ]
Correctionfactor
Recovery voltage
0.2
0.4
0.6
0.8
200 400 500 600 700 800100
s
w
300
1400
1200
1000
800
600
400
200
0
[ V ]
[V]
0
ÛPeakarcvoltage
ADA94-5004a-v
Recovery voltage
www.dienhathe.xyz
www.dienhathe.vn
Semiconductor Fuses
LV HRC SITOR Fuse Links
Rated voltage 690 V AC/700 V DC
2/21Siemens ET B1 T · 2007
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
Series 3NE8 72.-1, 3NE8 731-1
Size: 000
Operational class: aR
Rated voltage: 690 V AC/ 700 V DC
Rated current: 80 ... 315 A
Time/current characteristics diagram Let-through characteristics (current limitation at 50 Hz)
Correction factor kA for breaking I2
t value Peak arc voltage
2101
10-3
2
4
6
10-2
64 1028 2 64 1038 2 4
2
4
6
10-1
2
4
6
100
2
4
6
101
2
4
6
102
2
4
6
103
2
4
6
104
I2_10817
6 1048
2 5 0 A
2 0 0 A
1 6 0 A
1 2 5 A
1 0 0 A
8 0 A
3 1 5 A
vs
p [ A ]
[s]Virtualpre-arcingtime
Prospective short-circuit current
10
2
4
6
2
4
6
4
c[A]
105
103
I2_10820
6
8 0 A
1 0 0 A
1 2 5 A
1 6 0 A
2 0 0 A
2 5 0 A
3 1 5 A
102
2 64 108 3
2 64 108 4
2 64 108 5
2 4
p [A]
Let-throughcurrent
Prospective short-circuit current
Unlimited peak values:
DC component 50 %
DC component 0 %
0 100 200 300 400 500 600
1
700 800
A
w [ V ]
Correctionfactor
ADA94-5003a-v
Recovery voltage
0.2
0.4
0.6
0.8
200 400 500 600 700 800100
s
w
300
1400
1200
1000
800
600
400
200
0
[ V ]
[V]
0
ÛPeakarcvoltage
Recovery voltage
www.dienhathe.xyz
www.dienhathe.vn
Semiconductor Fuses
LV HRC SITOR Fuse Links
Rated voltage 690 V AC,
operational class gS
2/22 Siemens ET B1 T · 2007
■Technical specifications
1)
Temperature rise and power dissipation for operation in LV HRC fuse base.
Type 3NE1 813-0 3NE1 814-0 3NE1 815-0 3NE1 803-0 3NE1 802-0 3NE1 817-0 3NE1 818-0 3NE1 820-0
Operational class (IEC 60269) gS
Rated voltage Un V AC 690
Rated current In A 16 20 25 35 40 50 63 80
Melting I2t value I2ts (tvs = 1 ms) A2
s 18 41 74 166 295 461 903 1843
Breaking I2t value I2tA at Un A2
s 200 430 780 1700 3000 4400 9000 18000
Temperature rise at In (body center)1) K 25 30 35 30 35 40
Power dissipation at In
1) W 3.0 3.5 4.0 5.0 6.0 7.0 8.0
Varying load factor WL 1.0
Certification according to UL 248-13
Weight approx. kg 0.13
Accessories
Fuse base, 1-pole 3NH3 030
3-pole 3NH4 030
Fuse puller 3NX1 011
Fuse switch disconnectors 3NP40/3NP50
Switch disconnector with fuses 3KL50 30-1.B00
3KM50 30-1.B00
3KL52 30-
1.B00
3KM52 30-
1.B00
Type 3NE1 021-0 3NE1 022-0 3NE1 224-0 3NE1 225-0 3NE1 227-0 3NE1 230-0
Operational class (IEC 60269) gS
Rated voltage Un V AC 690
Rated current In A 100 125 160 200 250 315
Melting I2
t value I2
ts (tvs = 1 ms) A2
s 3100 6000 7400 14500 29500 46100
Breaking I2
t value I2
tA at Un A2
s 33000 63000 60000 100000 200000 310000
Temperature rise at In (body center)1)
K 36 40 60 65 75 80
Power dissipation at In
1) W 10 11 24 27 30 38
Varying load factor WL 1.0
Certification according to UL 248-13
Weight approx. kg 0.20 0.55
Accessories
Fuse base, 1-pole 3NH3 030 3NH3 230 3NH3 330
3-pole 3NH4 030 3NH4 230 3NH4 330
Fuse puller 3NX1 011
Fuse switch disconnectors 3NP40
3NP50
3NP42
3NP52
3NP53
Switch disconnector with fuses 3KL52 30-1.B00
3KM52 30-1.B00
3KL55 30-1.B00
3KM55 30-1.B00
3KL57 30-1.B00
3KM57 30-1.B00
Type 3NE1 331-0 3NE1 332-0 3NE1 333-0 3NE1 334-0 3NE1 435-0 3NE1 436-0 3NE1 437-0 3NE1 438-0
Operational class (IEC 60269) gS
Rated voltage Un V AC 690
Rated current In A 350 400 450 500 560 630 710 800
Melting I2
t value I2
ts (tvs = 1 ms) A2
s 58000 84000 104000 149000 215000 293000 437000 723000
Breaking I2
t value I2
tA at Un A2
s 430000 590000 750000 950000 1700000 2350000 3400000 5000000
Temperature rise at In (body center)1)
K 75 85 90 65 70 68 70
Power dissipation at In
1)
W 42 45 53 56 50 55 60 59
Varying load factor WL 1.0
Certification according to UL 248-13
Weight approx. kg 0.7 0.95
Accessories
Fuse base, 1-pole 3NH3 330 3NH3 430
Fuse puller 3NX1 011
Fuse switch disconnectors 3NP53 3NP54
Switch disconnector with fuses 3KL57 30-1.B00
3KM57 30-1.B00
3KL61 30-1AB0 3KL62
www.dienhathe.xyz
www.dienhathe.vn
Semiconductor Fuses
LV HRC SITOR Fuse Links
Rated voltage 690 V AC,
operational class gS
2/23Siemens ET B1 T · 2007
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
■Selection and ordering data
For dimensional drawings, see pages 2/48 and 2/49.
Size In Operational
class
Order No. Weight
1 unit
approx.
PS*/
P. unit
A kg Unit(s)
Rated voltage 690 V AC
for mounting in LV HRC fuse bases
000 16 gS 3NE1 813-0 0.127 3
20 gS 3NE1 814-0 0.128 3
25 gS 3NE1 815-0 0.127 3
35 gS 3NE1 803-0 0.128 3
40 gS 3NE1 802-0 0.127 3
50 gS 3NE1 817-0 0.128 3
63 gS 3NE1 818-0 0.128 3
80 gS 3NE1 820-0 0.129 3
00 100 gS 3NE1 021-0 0.202 3
125 gS 3NE1 022-0 0.202 3
1 160 gS 3NE1 224-0 0.580 3
200 gS 3NE1 225-0 0.582 3
250 gS 3NE1 227-0 0.580 3
315 gS 3NE1 230-0 0.581 3
2 350 gS 3NE1 331-0 0.766 3
400 gS 3NE1 332-0 0.743 3
450 gS 3NE1 333-0 0.760 3
500 gS 3NE1 334-0 0.766 3
3 560 gS 3NE1 435-0 1.111 3
630 gS 3NE1 436-0 1.114 3
710 gS 3NE1 437-0 1.117 3
800 gS 3NE1 438-0 1.124 3
* You can order this quantity or a multiple thereof.
www.dienhathe.xyz
www.dienhathe.vn
Semiconductor Fuses
LV HRC SITOR Fuse Links
Rated voltage 690 V AC,
operational class gS
2/24 Siemens ET B1 T · 2007
■Characteristic curves
Series 3NE1 8..-0
Size: 000
Operational class: gS
Rated voltage: 690 V AC
Rated current: 16 ... 80 A
Time/current characteristics diagram Let-through characteristics (current limitation at 50 Hz)
Correction factor kA for breaking I2
t value Peak arc voltage
p
vs
2101
10-3
2
4
6
10-2
64 1028 2 64 1038 2 4
2
4
6
10-1
2
4
6
100
2
4
6
101
2
4
6
102
2
4
6
103
2
4
6
104
I2_10825
6 1048
4 0 A
3 5 A
2 5 A
2 0 A
1 6 A
5 0 A
6 3 A
8 0 A
[ A ]
[s]Virtualpre-arcingtime
Prospective short-circuit current
102
2 64 108
10
2
4
6
2
4
6
3
c
p [A]
[A]
104
102
3
2 64 108 4
2 64 108 5
2 4
2 0 A
I2_10828
2 5 A
3 2 A
4 0 A
5 0 A
6 3 A
1 6 A
8 0 A
Let-throughcurrent
Prospective short-circuit current
Unlimited peak values:
DC component 50 %
DC component 0 %
0 100 200 300 400 500 600
1
700 800
A
w [ V ]
Correctionfactor
Recovery voltage
0.2
0.4
0.6
0.8
200 400 500 600 700 800100
s
w
300
1400
1200
1000
800
600
400
200
0
[ V ]
[V]
0
ÛPeakarcvoltage
Recovery voltage
www.dienhathe.xyz
www.dienhathe.vn
Semiconductor Fuses
LV HRC SITOR Fuse Links
Rated voltage 690 V AC,
operational class gS
2/25Siemens ET B1 T · 2007
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
Series 3NE1 02.-0, 3NE1 2..-0
Size: 00, 1
Operational class: gS
Rated voltage: 690 V AC
Rated current: 100 ... 315 A
Time/current characteristics diagram Let-through characteristics (current limitation at 50 Hz)
Correction factor kA for breaking I2
t value Peak arc voltage
p
vs
2102
10-3
2
4
6
10-2
64 1038 2 64 1048
2
4
6
10-1
2
4
6
100
2
4
6
101
2
4
6
102
2
4
6
103
2
4
6
104
I2_10829
2 5 0 A
2 0 0 A
1 6 0 A
1 2 5 A
1 0 0 A
3 1 5 A
Virtualpre-arcingtime
Prospective short-circuit current
p
c
103 2 64 1048
10
2
4
6
10
I2_10831
4
3
2 64 1058 2
2
4
6
105
[A]
[ A ]
1 0 0 A
2 0 0 A
2 5 0 A
3 1 5 A
1 2 5 / 1 6 0 A
Prospective short-circuit current
Unlimited peak values:
DC component 50 %
DC component 0 %
Let-throughcurrent
0 100 200 300 400 500 600
1
700 800
A
w
3 N E 1 2 . . - 0
3 N E 1 0 2 . - 0
[ V ]
Correctionfactor
Recovery voltage
0.2
0.4
0.6
0.8
200 400 500 600 700 800100
s
w
300
1400
1200
1000
800
600
400
200
0
[ V ]
[V]
0
ÛPeakarcvoltage
Recovery voltage
www.dienhathe.xyz
www.dienhathe.vn
Semiconductor Fuses
LV HRC SITOR Fuse Links
Rated voltage 690 V AC,
operational class gS
2/26 Siemens ET B1 T · 2007
Series 3NE1 33.-0, 3NE1 43.-0
Size: 2, 3
Operational class: gS
Rated voltage: 690 V AC
Rated current: 350 ... 800 A
Time/current characteristics diagram Let-through characteristics (current limitation at 50 Hz)
Correction factor kA for breaking I2t value Peak arc voltage
p
vs
2102
10-3
2
4
6
10-2
64 1038 2 64 1048 2 4
2
4
6
10-1
2
4
6
100
2
4
6
101
2
4
6
102
2
4
6
103
2
4
6
104
I2_10832
6 1058
5 6 0 A
5 0 0 A
4 5 0 A
4 0 0 A
3 5 0 A
6 3 0 A
7 1 0 A
8 0 0 A
[ A ]
[s]Virtualpre-arcingtime
Prospective short-circuit current
p
c
103 2 64 1048
10
2
4
6
10
I2_10834
4
3
2 64 1058 2
2
4
6
105
[A]
[ A ]
3 5 0 A
4 0 0 A
4 5 0 A
5 0 0 A
5 6 0 A
6 3 0 A
7 1 0 A
8 0 0 A
Prospective short-circuit current
Unlimited peak values:
DC component 50 %
DC component 0 %
Let-throughcurrent
0 100 200 300 400 500 600
1
700 800
A
w [ V ]
Correctionfactor
Recovery voltage
0.2
0.4
0.6
0.8
200 400 500 600 700 800100
s
w
300
1400
1200
1000
800
600
400
200
0
[ V ]
[V]
0
ÛPeakarcvoltage
Recovery voltage
www.dienhathe.xyz
www.dienhathe.vn
Semiconductor Fuses
LV HRC SITOR Fuse Links
Rated voltage 690 V AC,
operational class gR
2/27Siemens ET B1 T · 2007
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
■Technical specifications
1) Temperature rise and power dissipation for operation in LV HRC fuse base.
Type 3NE1 020-2 3NE1 021-2 3NE1 022-2 3NE1 224-2 3NE1 225-2 3NE1 227-2 3NE1 230-2
Operational class (IEC 60269) gR
Rated voltage Un V AC 690
Rated current In A 80 100 125 160 200 250 315
Melting I2t value I2ts (tvs = 1 ms) A2
s 780 1490 3115 2650 5645 11520 22580
Breaking I2t value I2tA at Un A2
s 5800 11000 23000 18600 51800 80900 168000
Temperature rise at In (body center)1) K 45 49 55 70 62 70 75
Power dissipation at In
1) W 10.5 11.5 13.5 30 28 35 42
Varying load factor WL 1.0
Certification according to UL 248-13
Weight approx. kg 0.2 0.55
Accessories
Fuse base, 1-pole 3NH3 030 3NH3 230
Fuse puller 3NX1 011
Fuse switch disconnectors 3NP50 3NP52 3NP53
Switch disconnector with fuses 3KL52 3KL55 3KL57
Type 3NE1 331-2 3NE1 333-2 3NE1 334-2
Operational class (IEC 60269) gR
Rated voltage Un V AC 690
Rated current In A 350 450 500
Melting I2
t value I2
ts (tvs = 1 ms) A2
s 29500 46100 66400
Breaking I2
t value I2
tA at Un A2s 177000 276500 398000
Temperature rise at In (body center)1)
K 82 100
Power dissipation at In
1) W 44 62 65
Varying load factor WL 1.0
Certification according to UL 248-13
Weight approx. kg 0.7
Accessories
Fuse base, 1-pole 3NH3 230 3NH3 340
Fuse puller 3NX1 011 3NX1 011
Fuse switch disconnectors 3NP53 3NP54
Switch disconnector with fuses 3KL57 3KL61
Type 3NE1 435-2 3NE1 436-2 3NE1 447-2 3NE1 437-2 3NE1 438-2 3NE1 448-2
Operational class (IEC 60269) gR
Rated voltage Un V AC 690
Rated current In A 560 630 670 710 800 850
Melting I2
t value I2
ts (tvs = 1 ms) A2
s 130000 203000 240000 265000 361000 520000
Breaking I2
t value I2
tA at Un A2
s 890000 1390000 1640000 1818000 2475000 3640000
Temperature rise at In (body center)1)
K 80 82 90 95
Power dissipation at In
1)
W 60 62 65 72 82 76
Varying load factor WL 1.0
Certification according to UL 248-13
Weight approx. kg 1.0
Accessories
Fuse base, 1-pole 3NH3 340
Fuse puller 3NX1 011
Fuse switch disconnectors 3NP54 3NP54
Switch disconnector with fuses 3KL61 3KL62
www.dienhathe.xyz
www.dienhathe.vn
Semiconductor Fuses
LV HRC SITOR Fuse Links
Rated voltage 690 V AC,
operational class gR
2/28 Siemens ET B1 T · 2007
Type 3NE8 015-1 3NE8 003-1 3NE8 017-1 3NE8 018-1 3NE8 020-1 3NE8 021-1 3NE8 022-1 3NE8 024-1
Operational class (IEC 60269) gR aR
Rated voltage Un V AC 690
Rated current In A 25 35 50 63 80 100 125 160
Melting I2
t value I2
ts (tvs = 1 ms) A2
s 30 70 120 260 450 850 1400 2800
Breaking I2t value I2tA at Un A2
s 180 400 700 1400 2400 4200 6500 1300
Temperature rise at In (body center) K 35 45 65 70 80 90 110 130
Power dissipation at In W 7 9 14 16 19 22 28 38
Varying load factor WL 0.95
Certification according to UL 248-13
Weight approx. kg 0.20
Accessories
Fuse base, 1-pole 3NH3 030
3-pole 3NH4 030
Fuse puller 3NX1 011
Fuse switch disconnectors 3NP40
3NP50
Switch disconnector with fuses 3KL50 30-1.B00
3KM50 30-1.B00
3KL52 30-1.B00
3KM52 30-1.B00
www.dienhathe.xyz
www.dienhathe.vn
Semiconductor Fuses
LV HRC SITOR Fuse Links
Rated voltage 690 V AC,
operational class gR
2/29Siemens ET B1 T · 2007
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
■Selection and ordering data
For dimensional drawings, see pages 2/48 and 2/49.
Size In Operational
class
Order No. Weight
1 unit
approx.
PS*/
P. unit
A kg Unit(s)
Rated voltage 690 V AC
for mounting in LV HRC fuse bases
00 80 gR 3NE1 020-2 0.203 3
100 gR 3NE1 021-2 0.203 3
125 gR 3NE1 022-2 0.203 3
1 160 gR 3NE1 224-2 0.613 3
200 gR 3NE1 225-2 0.612 3
250 gR 3NE1 227-2 0.626 3
315 gR 3NE1 230-2 0.615 3
2 350 gR 3NE1 331-2 0.754 3
450 gR 3NE1 333-2 0.768 3
500 gR 3NE1 334-2 0.768 3
3 560 gR 3NE1 435-2 1.149 3
630 gR 3NE1 436-2 1.179 3
670 gR 3NE1 447-2 1.170 3
710 gR 3NE1 437-2 1.153 3
800 gR 3NE1 438-2 1.184 3/1
850 gR 3NE1 448-2 1.207 3
00 25 gR 3NE8 015-1 0.205 3
35 gR 3NE8 003-1 0.204 3
50 gR 3NE8 017-1 0.203 3
63 gR 3NE8 018-1 0.205 3
80 aR 3NE8 020-1 0.203 3
100 aR 3NE8 021-1 0.205 3
125 aR 3NE8 022-1 0.213 3
160 aR 3NE8 024-1 0.207 3
* You can order this quantity or a multiple thereof.
www.dienhathe.xyz
www.dienhathe.vn
Semiconductor Fuses
LV HRC SITOR Fuse Links
Rated voltage 690 V AC,
operational class gR
2/30 Siemens ET B1 T · 2007
■Characteristic curves
Series 3NE1 022-2, 3NE1 2..-2, 3NE1 33.-2
Size: 00, 1
Operational class: gR
Rated voltage: 690 V AC
Rated current: 125 ... 500 A
Time/current characteristics diagram Let-through characteristics (current limitation at 50 Hz)
Correction factor kA for breaking I2
t value Peak arc voltage
10-3
10-2
2
4
6
10-1
2
4
6
100
2
4
6
101
2
4
6
102
2
4
6
103
2
4
6
6
104
2
4
[s]tVS
2 4 6
p
1052 4 6 1042 4 6 103102
I2_1083980 A
100 A
125 A
160 A
200 A
250 A
315 A
350 A
450 A
500 A
VirtualPre-arcingTime
Prospective Short-circuit Current
102 103 104 10 5
103
2
4
6
104
105
2
4
6
2 4 6 2 4 6 2 4 6
p
I2_10842
C
125 A
160 A
100 A
80 A
500 A
450 A
350 A
315 A
250 A
200 A
Prospective Short-Circuit Current
PeakLet-ThroughCurrent
I2_10840
0
0
100 200 300 400 500 600 700 800
1
80 A - 125 A
160 A - 315 A
350 A - 500 A
Recovery voltage
Correctionfactor
0.2
0.4
0.6
0.8
I2_10841
2000
400
800
1200
1600
8002000
0
400 600
160...315 A
80...125 A
350...500 A
Peakarcvoltage
Recovery voltage
www.dienhathe.xyz
www.dienhathe.vn
Semiconductor Fuses
LV HRC SITOR Fuse Links
Rated voltage 690 V AC,
operational class gR
2/31Siemens ET B1 T · 2007
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
Series 3NE1 4..-2
Size: 3
Operational class: gR
Rated voltage: 690 V AC
Rated current: 560 ... 850 A
Time/current characteristics diagram Let-through characteristics (current limitation at 50 Hz)
Correction factor kA for breaking I2t value Peak arc voltage
10-3
10-2
2
4
6
10-1
2
4
6
100
2
4
6
101
2
4
6
102
2
4
6
103
2
4
6
6
104
2
4
[s]tVS
2 4 6
p
1052 4 6 1042 4 6 103102
I2_10843
560 A
630 A
670 A
710 A
800 A
850 A
VirtualPre-arcingTime
Prospective Short-circuit Current
102 103 104 10 5
103
2
4
6
104
105
2
4
6
2 4 6 2 4 6 2 4 6
p
I2_10846
C
850 A
800 A
710 A
670 A
630 A
560 A
Prospective Short-Circuit Current
PeakLet-ThroughCurrent
0
0
100 200 300 400 500 600 700 800
1
I2_10844
Recovery voltage
Correctionfactor
0.2
0.4
0.6
0.8
I2_10845
2000
400
800
1200
1600
8002000
0
400 600
Peakarcvoltage
Recovery voltage
www.dienhathe.xyz
www.dienhathe.vn
Semiconductor Fuses
LV HRC SITOR Fuse Links
Rated voltage 690 V AC,
operational class gR
2/32 Siemens ET B1 T · 2007
Series 3NE8 0..-1
Size: 00
Operational class: gR or aR
Rated voltage: 690 V AC
Rated current: 25 ... 160 A
Time/current characteristics diagram Let-through characteristics (current limitation at 50 Hz)
Correction factor kA for breaking I2
t value Peak arc voltage
p
vs
2101
10-3
2
4
6
10-2
64 1028 2 64 1038 2 4
2
4
6
10-1
2
4
6
100
2
4
6
101
2
4
6
102
2
4
6
103
2
4
6
104
I2_10847
6 1048
1 0 0 A
8 0 A
6 3 A
5 0 A
3 5 A
2 5 A
1 2 5 A
1 6 0 A
[ A ]
[s]Virtualpre-arcingtime
Prospective short-circuit current
102
2 64 108
10
2
4
6
2
4
6
3
c
p [A]
[A]
104
102
3
2 64 108 4
2 64 108 5
2 4
2 5 A
I2_10850
3 5 A
5 0 A
6 3 A
8 0 A
1 0 0 A
1 2 5 A
1 6 0 A
Let-throughcurrent
Prospective short-circuit current
Unlimited peak values:
DC component 50 %
DC component 0 %
0 100 200 300 400 500 600
1
700 800
A
w [ V ]
Correctionfactor
Recovery voltage
0.2
0.4
0.6
0.8
0 200
w
s
2000
1800
1000
800
400
200
400 600 800
I2_10849
600
1200
1400
1600
[ V ]
[V]
0
Peakarcvoltage
Recovery voltage
Û
www.dienhathe.xyz
www.dienhathe.vn
Semiconductor Fuses
LV HRC SITOR Fuse Links
Rated voltage 800 V AC
2/33Siemens ET B1 T · 2007
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
■Technical specifications
■Selection and ordering data
For dimensional drawings, see pages 2/48 and 2/49.
1)
Cladding dimensions and grip lugs according to IEC 60269-2-1;
but blade slotted according to IEC 60269-4-1.
Type 3NE4 327-0B 3NE4 330-0B 3NE4 333-0B 3NE4 334-0B 3NE4 337
Operational class (IEC 60269) aR
Rated voltage Un V AC 800
Rated current In A 250 315 450 500 710
Melting I2
t value I2
ts (tvs = 1 ms) A2
s 3600 7400 29400 42500 142000
Breaking I2
t value I2
tA at Un A2
s 29700 60700 191000 276000 923000
Temperature rise at In (body center) K 175 170 190 195 170
Power dissipation at In W 105 120 140 155
Varying load factor WL 0.85 0.95
Weight approx. kg 0.7
Accessories
Fuse base, 1-pole 3NH3 330 3NH3 430
Fuse puller 3NX1 011
Fuse switch disconnectors 3NP53 3NP54
Switch disconnector with fuses 3KL57 30-1.B00
3KM57 30-1.B00
3KL61 3KL62
Size In Operational
class
Order No. Weight
1 unit
approx.
PS*/
P. unit
A kg Unit(s)
Rated voltage 800 V AC
with bolt-on links
Mounting dimensions: 110 mm
21)
250 aR 3NE4 327-0B 0.753 3
315 aR 3NE4 330-0B 0.760 3
450 aR 3NE4 333-0B 0.760 3
500 aR 3NE4 334-0B 0.754 3
710 aR 3NE4 337 0.771 3
* You can order this quantity or a multiple thereof.
www.dienhathe.xyz
www.dienhathe.vn
Semiconductor Fuses
LV HRC SITOR Fuse Links
Rated voltage 800 V AC
2/34 Siemens ET B1 T · 2007
■Characteristic curves
Series 3NE4 3..-0B, 3NE4 337
Size: 2
Operational class: aR
Rated voltage: 800 V AC
Rated current: 250 ... 710 A
Time/current characteristics diagram Let-through characteristics (current limitation at 50 Hz)
Correction factor kA for breaking I2
t value Peak arc voltage
p
vs
2102
10-3
2
4
6
10-2
64 1038 2 64 1048 2 4
2
4
6
10-1
2
4
6
100
2
4
6
101
2
4
6
102
2
4
6
103
2
4
6
104
I2_10851
6 1058
2 5 0 A
3 1 5 A
4 5 0 A
5 0 0 A
7 1 0 A
[ A ]
[s]Virtualpre-arcingtime
Prospective short-circuit current
p
c
103 2 64 1048
10
2
4
6
10
I2_10854
4
3
2 64 1058 2
2
4
6
105
[A]
[ A ]
7 1 0 A
5 0 0 A
4 5 0 A
3 1 5 A
2 5 0 A
Prospective short-circuit current
Unlimited peak values:
DC component 50 %
DC component 0 %
Let-throughcurrent
0 100 200 300 400 500 600
1
700 800
A
w
4 5 0 A
3 1 5 A
[ V ]
Correctionfactor
ADA94-5003a-v
Recovery voltage
0.2
0.4
0.6
0.8
0 200
w
s
2000
1800
1000
800
400
200
400 600 800
I2_10853
600
1200
1400
1600
1000
[ V ]
[V]
0
Peakarcvoltage
Recovery voltage
Û
www.dienhathe.xyz
www.dienhathe.vn
Semiconductor Fuses
LV HRC SITOR Fuse Links
Rated voltage 1000 V AC
2/35Siemens ET B1 T · 2007
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
■Technical specifications
Type 3NE4 101 3NE4 102 3NE4 117 3NE4 118 3NE4 120 3NE4 121 3NE4 122 3NE4 124
Operational class (IEC 60269) gR aR
Rated voltage Un V AC 1000
Rated current In A 32 40 50 63 80 100 125 160
Melting I2
t value I2
ts (tvs = 1 ms) A2
s 40 75 120 230 450 900 1800 3600
Breaking I2
t value I2
tA at Un A2
s 280 500 800 1500 3000 6000 14000 29000
Temperature rise at In (body center) K 45 50 65 78 82 85 100 120
Power dissipation at In W 12 13 16 20 22 24 30 35
Varying load factor WL 0.9
Certification according to UL 248-13
Weight approx. kg 0.27
Accessories
Fuse base, 1-pole 3NH3 120
3-pole 3NH4 230
Fuse puller 3NX1 011
Fuse switch disconnectors 3NP42, 3NP52
Switch disconnector with fuses 3KL55 30-1.B00
3KM55 30-1.B00
Type 3NE3 221 3NE3 222 3NE3 224 3NE3 225 3NE3 227
Operational class (IEC 60269) aR
Rated voltage Un V AC 1000
Rated current In A 100 125 160 200 250
Melting I2
t value I2
ts (tvs = 1 ms) A2
s 665 1040 1850 4150 6650
Breaking I2
t value I2
tA at Un A2
s 4800 7200 13000 30000 48000
Temperature rise at In (body center) K 65 70 90 80 90
Power dissipation at In W 28 36 42 50
Varying load factor WL 0.95 1.0
Certification according to UL 248-13
Weight approx. kg 0.55
Accessories
Fuse base, 1-pole 3NH3 230
3-pole 3NH4 230
Fuse puller 3NX1 011
Fuse switch disconnectors 3NP42, 3NP52
Switch disconnector with fuses 3KL55 30-1.B00
3KM55 30-1.B00
Type 3NE3 230-0B 3NE3 231 3NE3 232-0B 3NE3 233
Operational class (IEC 60269) aR
Rated voltage Un V AC 1000
Rated current In A 315 350 400 450
Melting I2
t value I2
ts (tvs = 1 ms) A2
s 13400 16600 22600 29500
Breaking I2
t value I2
tA at Un A2
s 80000 100000 135000 175000
Temperature rise at In (body center) K 100 120 140 130
Power dissipation at In W 65 75 85 95
Varying load factor WL 0.95 0.9
Certification according to UL 248-13
Weight approx. kg 0.55
Accessories
Fuse base, 1-pole 3NH3 330
Fuse puller 3NX1 011
Fuse switch disconnectors 3NP53
Switch disconnector with fuses 3KL57 30-1.B00
3KM57 30-1.B00
www.dienhathe.xyz
www.dienhathe.vn
Semiconductor Fuses
LV HRC SITOR Fuse Links
Rated voltage 1000 V AC
2/36 Siemens ET B1 T · 2007
1)
Gauge 140 mm, M12 screw connection.
Type 3NE3 332-0B 3NE3 333 3NE3 334-0B 3NE3 335 3NE3 336 3NE3 337-8 3NE3 338-8 3NE3 340-8
Operational class (IEC 60269) aR
Rated voltage Un V AC 1000 900 800 690
Rated current In A 400 450 500 560 630 710 800 900
Melting I2
t value I2
ts (tvs = 1 ms) A2
s 22600 29500 46100 66400 104000 149000 184000 223000
Breaking I2t value I2tA at Un A2
s 135000 175000 260000 360000 600000 800000 850000 1300000
Temperature rise at In (body center) K 120 125 115 120 110 125 140 160
Power dissipation at In W 85 90 95 100 105 130 165
Varying load factor WL 1.0 0.95
Certification according to UL 248-13
Weight approx. kg 0.7
Accessories
Fuse base, 1-pole 3NH3 430
Fuse puller 3NX1 011
Fuse switch disconnectors 3NP54
Switch disconnector with fuses 3KL61 30-1AB0 3KL62
Type 3NE3 421 3NE3 626 3NE3 430 3NE3 432 3NE3 635
3NE3 635-6
3NE3 434 3NE3 636 3NE3 637
3NE3 637-11)
Operational class (IEC 60269) aR
Rated voltage Un V AC 1000
Rated current In A 100 224 315 400 450 500 630 710
Melting I2
t value I2
ts (tvs = 1 ms) A2
s 1800 7200 29000 48500 65000 116000 170000 260000
Breaking I2
t value I2
tA at Un A2
s 13500 54000 218000 364000 488000 870000 1280000 1950000
Temperature rise at In (body center) K 45 140 120 130 150 120 136 170
Power dissipation at In W 25 85 80 110 95 132 145
Varying load factor WL 1.0
Weight approx. kg 1.15
www.dienhathe.xyz
www.dienhathe.vn
Semiconductor Fuses
LV HRC SITOR Fuse Links
Rated voltage 1000 V AC
2/37Siemens ET B1 T · 2007
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
■Selection and ordering data
For dimensional drawings, see pages 2/48 and 2/49.
1) Cladding dimensions and grip lugs according to IEC 60269-2-1;
but blade slotted according to IEC 60269-4-1.
2) Rated voltage 900 V AC.
3) Rated voltage 800 V AC.
4) Rated voltage 690 V AC.
5) Design according to 3NE6 4.. and 3NE9 4...
Size In Operational
class
Order No. Weight
1 unit
approx.
PS*/
P. unit
A kg Unit(s)
Rated voltage 1000 V AC
for mounting in LV HRC fuse bases
0 32 gR 3NE4 101 0.278 3
40 3NE4 102 0.277 3
50 3NE4 117 0.276 3
63 aR 3NE4 118 0.279 3
80 3NE4 120 0.276 3
100 3NE4 121 0.278 3
125 3NE4 122 0.279 3
160 3NE4 124 0.279 3
with bolt-on links
Mounting dimensions: 110 mm
11)
100 aR 3NE3 221 0.580 3
125 3NE3 222 0.568 3
160 3NE3 224 0.573 3
200 3NE3 225 0.570 3
250 3NE3 227 0.580 3
315 3NE3 230-0B 0.585 3
350 3NE3 231 0.590 3
400 3NE3 232-0B 0.576 3
450 3NE3 233 0.720 3
21)
400 aR 3NE3 332-0B 0.759 3
450 3NE3 333 0.748 3
500 3NE3 334-0B 0.753 3
560 3NE3 335 0.756 3
630 3NE3 336 0.760 3
7102)
3NE3 337-8 0.762 3
8003)
3NE3 338-8 0.764 3
9004)
3NE3 340-8 0.753 3
Mounting dimensions: 130 mm
3 100 aR 3NE3 421 1.200 3
224 3NE3 626 1.300 3
315 3NE3 430 1.241 3
400 3NE3 432 1.247 3
450 3NE3 635 1.179 3
4505)
3NE3 635-6 1.184 3
500 3NE3 434 1.490 3
630 3NE3 636 1.213 3
710 3NE3 637 1.190 3
Mounting dimensions: 140 mm, M12 screw connection
3 710 aR 3NE3 637-1 1.246 3
* You can order this quantity or a multiple thereof.
www.dienhathe.xyz
www.dienhathe.vn
Semiconductor Fuses
LV HRC SITOR Fuse Links
Rated voltage 1000 V AC
2/38 Siemens ET B1 T · 2007
■Characteristic curves
Series 3NE4 1..
Size: 0
Operational class: gR or aR
Rated voltage: 1000 V AC
Rated current: 32 ... 160 A
Time/current characteristics diagram Let-through characteristics (current limitation at 50 Hz)
Correction factor kA for breaking I2
t value Peak arc voltage
p
vs
2101
10-3
2
4
6
10-2
64 1028 2 64 1038 2 4
2
4
6
10-1
2
4
6
100
2
4
6
101
2
4
6
102
2
4
6
103
2
4
6
104
I2_10855
6 1048
1 0 0 A
8 0 A
6 3 A
5 0 A
4 0 A
3 2 A
1 2 5 A
1 6 0 A
[s]
[ A ]
Virtualpre-arcingtime
Prospective short-circuit current
102
2 64 108
10
2
4
6
1 0 0 A
2
4
6
3
1 2 5 A
c
p [A]
[A]
104
102
3
2 64 108 4
2 64 108 5
2 4
3 2 A
I2_10858
4 0 A
5 0 A
1 6 0 A
6 3 A
8 0 A
Let-throughcurrent
Prospective short-circuit current
Unlimited peak values:
DC component 50 %
DC component 0 %
0 200 400 600
1
800 1000
A
w [ V ]
I2_10856
Correctionfactor
0.8
0.6
0.4
0.2
Recovery voltage
0 200 400 600 800 1000 1200
500
1000
1500
2000
2500
0
s
w [ V ]
[V]
I2_10857
Peakarcvoltage
Recovery voltage
Û
www.dienhathe.xyz
www.dienhathe.vn
Semiconductor Fuses
LV HRC SITOR Fuse Links
Rated voltage 1000 V AC
2/39Siemens ET B1 T · 2007
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
Series 3NE3 22.
Size: 1
Operational class: aR
Rated voltage: 1000 V AC
Rated current: 100 ... 225 A
Time/current characteristics diagram Let-through characteristics (current limitation at 50 Hz)
Correction factor kA for breaking I2
t value Peak arc voltage
p
vs
2101
10-3
2
4
6
10-2
64 1028 2 64 1038 2 4
2
4
6
10-1
2
4
6
100
2
4
6
101
2
4
6
102
2
4
6
103
2
4
6
104
I2_10859
6 1048
1 0 0 A
1 2 5 A
1 6 0 A
[s]
[ A ]
2 0 0 A
2 5 0 A
Virtualpre-arcingtime
Prospective short-circuit current
102
2 64 108
10
2
4
6
2
4
6
3
c
p [A]
[A]
104
102
3
2 64 108 4
2 64 108 5
2 4
I2_10862
2
1 0 0 A
1 2 5 A
1 6 0 A
2 0 0 A
2 5 0 A
Let-throughcurrent
Prospective short-circuit current
Unlimited peak values:
DC component 50 %
DC component 0 %
0 200 400 600
1
800 1000
A
w [ V ]
I2_10860
Correctionfactor
0.8
0.6
0.4
0.2
Recovery voltage
0 200 400 600 800 1000 1200
500
1000
1500
2000
2500
0
s
w [ V ]
[V]
I2_10861
ÛPeakarcvoltage
Recovery voltage
www.dienhathe.xyz
www.dienhathe.vn
Semiconductor Fuses
LV HRC SITOR Fuse Links
Rated voltage 1000 V AC
2/40 Siemens ET B1 T · 2007
Series 3NE3 23.
Size: 1
Operational class: aR
Rated voltage: 1000 V AC
Rated current: 315 ... 450 A
Time/current characteristics diagram Let-through characteristics (current limitation at 50 Hz)
Correction factor kA for breaking I2
t value Peak arc voltage
p
vs
2102
10-3
2
4
6
10-2
64 1038 2 64 1048
2
4
6
10-1
2
4
6
100
2
4
6
101
2
4
6
102
2
4
6
103
2
4
6
104
I2_10863
4 5 0 A
[ A ]
4 0 0 A
3 5 0 A
3 0 0 A
[s]Virtualpre-arcingtime
Prospective short-circuit current
p
c
103 2 64 1048
10
2
4
6
10
I2_10864
4
3
2 64 1058 2
2
4
6
105
[A]
[ A ]
3 1 5 A
3 5 0 A
4 0 0 A
4 5 0 A
Prospective short-circuit current
Unlimited peak values:
DC component 50 %
DC component 0 %
Let-throughcurrent
0 200 400 600
1
800 1000
A
w [ V ]
I2_10860
Correctionfactor
0.8
0.6
0.4
0.2
Recovery voltage
0 200 400 600 800 1000 1200
500
1000
1500
2000
2500
0
s
w [ V ]
[V]
I2_10861
ÛPeakarcvoltage
Recovery voltage
www.dienhathe.xyz
www.dienhathe.vn
Semiconductor Fuses
LV HRC SITOR Fuse Links
Rated voltage 1500 V AC
2/41Siemens ET B1 T · 2007
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
■Technical specifications
■Selection and ordering data
For dimensional drawings, see pages 2/48 and 2/49.
1)
M12 screw connection
Type 3NE5 424 3NE5 426 3NE5 430 3NE5 431 3NE5 433
3NE5 433-1
Operational class (IEC 60269) aR
Rated voltage Un V AC 1500
Rated current In A 160 224 315 350 450
Melting I2
t value I2
ts (tvs = 1 ms) A2
s 7200 18400 41500 57000 116000
Breaking I2
t value I2
tA at Un A2
s 54000 138000 311000 428000 870000
Temperature rise at In (body center) K 75 100 125 150 150
Power dissipation at In W 56 80 115 135 145
Varying load factor WL 1.0 0.95
Weight approx. kg 1.95
Type 3NE5 627 3NE5 633 3NE5 643
Operational class (IEC 60269) aR
Rated voltage Un V AC 1500
Rated current In A 250 450 600
Melting I2t value I2ts (tvs = 1 ms) A2
s 11200 78500 260000
Breaking I2
t value I2
tA at Un A2
s 84000 590000 1950000
Temperature rise at In (body center) K 170 160
Power dissipation at In W 130 160 145
Varying load factor WL 1.0
Weight approx. kg 1.6
Size In Operational
class
Order No. Weight
1 unit
approx.
PS*/
P. unit
A kg Unit(s)
Rated voltage 1500 V AC
with bolt-on links
Mounting dimensions: 210 mm
3 160 aR 3NE5 424 1.900 2
224 3NE5 426 1.968 2
315 3NE5 430 2.000 2
350 3NE5 431 1.959 2
450 3NE5 433 2.100 2
4501) 3NE5 433-1 1.961 2
Mounting dimensions: 170 mm
3 250 3NE5 627 1.562 3
450 3NE5 633 1.585 3
600 3NE5 643 1.587 3
* You can order this quantity or a multiple thereof.
www.dienhathe.xyz
www.dienhathe.vn
Semiconductor Fuses
LV HRC SITOR Fuse Links
Rated voltage 1500 V AC
2/42 Siemens ET B1 T · 2007
■Characteristic curves
Series 3NE5 4..
Size: 3
Operational class: aR
Rated voltage: 1500 V AC
Rated current: 160 ... 600 A
Time/current characteristics diagram Let-through characteristics (current limitation at 50 Hz)
Correction factor kA for breaking I2
t value Peak arc voltage
p
vs
2102
10-3
2
4
6
10-2
64 1038 2 64 1048 2 4
2
4
6
10-1
2
4
6
100
2
4
6
101
2
4
6
102
2
4
6
103
2
4
6
104
I2_10872
6 1058
1 6 0 A
2 2 4 A
3 1 5 A
[s]
[ A ]
3 5 0 A
4 5 0 A
Virtualpre-arcingtime
Prospective short-circuit current
p
103 2 64 104
I2_10875
2 64 1058 2
[ A ]
8
1 6 0 A
2 2 4 A
3 1 5 A
3 5 0 A
4 5 0 A
2
4
6
104
3
2
4
10
Prospective short-circuit current
Unlimited peak values:
DC component 50 %
DC component 0 %
Let-throughcurrentc[A]
0 500
1
15001000
w
A
[ V ]
Correctionfactor
0.2
0.4
0.6
0.8
I201_10873
Recovery voltage
0 400 800 1200 1600 2000
800
2400
4000
0
s
w [ V ]
[V]
I2_10874
400
1200
2000
2800
3200
3600
1600
Peakarcvoltage
Recovery voltage
Û
www.dienhathe.xyz
www.dienhathe.vn
Semiconductor Fuses
LV HRC SITOR Fuse Links
Rated voltage 1500 V AC
2/43Siemens ET B1 T · 2007
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
Series 3NE5 6..
Size: 3
Operational class: aR
Rated voltage: 1500 V AC
Rated current: 250 ... 600 A
Time/current characteristics diagram Let-through characteristics (current limitation at 50 Hz)
Correction factor kA for breaking I2
t value Peak arc voltage
p
vs
2102
10-3
2
4
6
10-2
64 1038 2 64 1048 2 4
2
4
6
10-1
2
4
6
100
2
4
6
101
2
4
6
102
2
4
6
103
2
4
6
104
I2_10876
6 1058
[s]
[ A ]
2 5 0 A
4 5 0 A
6 0 0 A
Virtualpre-arcingtime
Prospective short-circuit current
p
103 2 64 104
I2_10877
2 64 1058 2
[ A ]
8
2 5 0 A
4 5 0 A
6 0 0 A
c[A]
10
2
4
6
104
3
2
4
Prospective short-circuit current
Unlimited peak values:
DC component 50 %
DC component 0 %
Let-throughcurrent
0 500
1
15001000
w
A
[ V ]
Correctionfactor
0.2
0.4
0.6
0.8
I201_10873
Recovery voltage
0 400 800 1200 1600 2000
800
2400
4000
0
s
w [ V ]
[V]
I2_10874
400
1200
2000
2800
3200
3600
1600
Peakarcvoltage
Recovery voltage
Û
www.dienhathe.xyz
www.dienhathe.vn
Semiconductor Fuses
LV HRC SITOR Fuse Links
Rated voltage 2000 V AC
2/44 Siemens ET B1 T · 2007
■Technical specifications
1)
M12 screw connection
■Selection and ordering data
For dimensional drawings, see pages 2/48 and 2/49.
1)
M12 screw connection
Type 3NE7 425 3NE7 427 3NE7 431 3NE7 432 3NE7 633
3NE7 633-11)
3NE7 648-11)
3NE7 636
3NE7 636-11)
3NE7 637-11)
Operational class (IEC 60269) aR
Rated voltage Un V AC 2000
Rated current In A 200 250 350 400 450 525 630 710
Melting I2t value I2ts (tvs = 1 ms) A2
s 18400 29000 74000 116000 128000 149000 260000 415000
Breaking I2t value I2tA at Un A2
s 138000 218000 555000 870000 960000 1120000 1950000 3110000
Temperature rise at In (body center) K 85 110 105 130 165 210 200 230
Power dissipation at In W 75 110 120 150 160 210 220 275
Varying load factor WL 1.0
Weight approx. kg 1.95
Size In Operational
class
Order No. Weight
1 unit
approx.
PS*/
P. unit
A kg Unit(s)
Rated voltage 2000 V AC
with bolt-on links
Mounting dimensions: 210 mm
3 200 aR 3NE7 425 2.100 2
250 3NE7 427 1.970 2
350 3NE7 431 1.980 2
400 3NE7 432 1.973 2
450 3NE7 633 1.968 2
4501)
3NE7 633-1 1.983 2
5251)
3NE7 648-1 1.975 2
630 3NE7 636 1.997 2
6301)
3NE7 636-1 2.024 2
7101)
3NE7 637-1 1.997 2
* You can order this quantity or a multiple thereof.
www.dienhathe.xyz
www.dienhathe.vn
Semiconductor Fuses
LV HRC SITOR Fuse Links
Rated voltage 2000 V AC
2/45Siemens ET B1 T · 2007
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
■Characteristic curves
Series 3NE7 4.., 3NE7 6..
Size: 3
Operational class: aR
Rated voltage: 2000 V AC
Rated current: 200 ... 710 A
Time/current characteristics diagram Let-through characteristics (current limitation at 50 Hz)
Correction factor kA for breaking I2
t value Peak arc voltage
p
vs
2102
10-3
2
4
6
10-2
64 1038 2 64 1048 2 4
2
4
6
10-1
2
4
6
100
2
4
6
101
2
4
6
102
2
4
6
103
2
4
6
104
I2_10878
6 1058
[s]
[ A ]
2 0 0 A
2 5 0 A
3 5 0 A
4 0 0 A
4 5 0 A
5 2 5 A
6 3 0 A
7 1 0 A
Virtualpre-arcingtime
Prospective short-circuit current
p
c
103 2 64 1048
10
2
4
6
2 0 0 A
10
I2_10881
4
3
2 64 1058 2
2
4
6
105
2 5 0 A
[A]
[ A ]
3 5 0 A
4 0 0 / 4 5 0 A
5 2 5 A
6 3 0 A
7 1 0 A
Prospective short-circuit current
Unlimited peak values:
DC component 50 %
DC component 0 %
Let-throughcurrent
0 500
1
15001000
w
A
[ V ]
2000
Correctionfactor
0.2
0.4
0.6
0.8
ADA94-5029b
Recovery voltage
0 400 800 1200 1600 2000 2400
800
2400
4000
0
s
w [ V ]
[V]
I2_10880
400
2000
2800
3200
3600
1200
1600
Peakarcvoltage
Recovery voltage
Û
www.dienhathe.xyz
www.dienhathe.vn
Semiconductor Fuses
LV HRC SITOR Fuse Links
Rated voltage 2500 V AC
2/46 Siemens ET B1 T · 2007
■Technical specifications
■Selection and ordering data
For dimensional drawings, see pages 2/48 and 2/49.
1)
M12 screw connection
Type 3NE9 632-1 3NE9 634-1 3NE9 636-1A
Operational class (IEC 60269) aR
Rated voltage Un V AC 2500
Rated current In A 400 500 630
Melting I2
t value I2
ts (tvs = 1 ms) A2
s 81000 170000 385000
Breaking I2
t value I2
tA at Un A2
s 620000 1270000 2800000
Temperature rise at In (body center) K 160 180 198
Power dissipation at In W 205 235 275
Varying load factor WL 1.0
Weight approx. kg 2.5
Size In Operational
class
Order No. Weight
1 unit
approx.
PS*/
P. unit
A kg Unit(s)
Rated voltage 2500 V AC
with bolt-on links
Mounting dimensions: 260 mm
3 4001)
aR 3NE9 632-1 2.542 1
5001)
3NE9 634-1 2.550 1
6301)
3NE9 636-1A 2.557 1
* You can order this quantity or a multiple thereof.
www.dienhathe.xyz
www.dienhathe.vn
Semiconductor Fuses
LV HRC SITOR Fuse Links
Rated voltage 2500 V AC
2/47Siemens ET B1 T · 2007
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
■Characteristic curves
Series 3NE9 63.
Size: 3
Operational class: aR
Rated voltage: 2500 V AC
Rated current: 400 ... 630 A
Time/current characteristics diagram Let-through characteristics (current limitation at 50 Hz)
Correction factor kA for breaking I2
t value Peak arc voltage
p
vs
2102
10-3
2
4
6
10-2
64 1038 2 64 1048 2 4
2
4
6
10-1
2
4
6
100
2
4
6
101
2
4
6
102
2
4
6
103
2
4
6
104
I2_10882
6 1058
[s]
[ A ]
4 0 0 A
5 0 0 A
6 3 0 A
Virtualpre-arcingtime
Prospective short-circuit current
p
c
103 2 64 1048
10
2
4
6
10
I2_10885
4
3
2 64 1058 2
2
4
6
105
[A]
[ A ]
4 0 0 A
5 0 0 A
6 3 0 A
Prospective short-circuit current
Unlimited peak values:
DC component 50 %
DC component 0 %
Let-throughcurrent
0 400 800 1200 1600 2000 2400
1
2800
A
w [ V ]
Correctionfactor
Recovery voltage
0.2
0.4
0.6
0.8
0 500 1000 1500 2000 2500 3000
6000
0
s
w [ V ]
[V]
I2_10884
2000
1000
3000
4000
5000
Peakarcvoltage
Recovery voltage
Û
www.dienhathe.xyz
www.dienhathe.vn
Semiconductor Fuses
LV HRC SITOR Fuse Links
Configuration Aids
2/48 Siemens ET B1 T · 2007
■Dimensional drawings
3NC2 4.., 3NC8 4.. 3NC2 4..-3, 3NC8 4..-3
3NE8 7..-1 3NE1 8..-0 3NE1 02.-0, 3NE1 02.-2, 3NE8 0..-1
3NE1 2..-0, 3NE1 2..-2 3NE1 33.-0, 3NE1 33.-2 3NE1 43.-0, 3NE1 43.-1 3NE1 4..-2
70
60
1814 12
81
10
6
70
108
140
I2 11336
71,5
11,5
18
70
60
12
1814 12
14
81
10
6
70
108
140
71,5
11,5
11,5
I2_11337
8,5
8,5
78
100
54
I2_11343
21
40
6
79,9
50,3
2,3
I2_06713
10
53,3
20
35,8
15
21
40,5
53,8
53
49,4
2,210
I2_06714
6
48
3079
60
35,8
15
10
40,5
52
52
73
66,5
3
I2_06715
25
63,5
6
135
I2_07071
47,5
25
72
60
60
6
10
66,5
3
73
149
70151
I2_06717
10
6
60,4
82,1
68
2,5
73
70
32
73151
I 2 _ 1 2 4 2 7
10
6
6 0 , 4
8 2 , 1
68
2,5
73
7 3
3 2
www.dienhathe.xyz
www.dienhathe.vn
Semiconductor Fuses
LV HRC SITOR Fuse Links
Configuration Aids
2/49Siemens ET B1 T · 2007
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
3NE4 3..-0B, 3NE4 337 3NE4 1..
60
71
48
10
6
60
I2_11338
10,5
14,511,5 12,5
14,511,5 12,5
107,5
141,5
73,5
10,5
10
30
6
15 14
47
65
125
58
I2_06450
3NE3 4.., 3NE3 6.., 3NE3 637-1,
3NE5 4.., 3NE5 433-1, 3NE5 6..,
3NE7 4.., 3NE7 6.., 3NE9 63.-1
Type Dimensions
a b c d
3NE3 4.., 3NE3 6.. 160 128 11.5 91.5
3NE3 635-6 see adjacent drawing
3NE3 637-1 170 138 13 91.5
3NE5 4.., 3NE7 4.., 240 208 11.5 171.5
3NE7 6..
3NE5 433-1, 240 208 13 171.5
3NE7 6..-1
3NE5 6.. 200 168 11.5 131.5
3NE9 63.-1 287 255 13 220
10
6
70
b
a
c
c
70
60
81
14 18 12
14 18 12
d
I2_11339
3NE3 22., 3NE3 23., 3NE3 3..
Type Dimensions
a b c d e f g
3NE3 22., 3NE3 23. 135 31 12.5 40.5 13.5 52 63.5
3NE3 3.. 149 38 19.5 47.5 15 60 72
3NE3 635-6
I2_06473a
10
f
673
a
10,5
c110
b
12,512,5
10,5
d e
f
g
10
70
M10
Æ28
70 96
109
10
81,5
I2_11340
www.dienhathe.xyz
www.dienhathe.vn
Semiconductor Fuses
SITOR Fuse Links for Special Applications
For rectifiers in electrolysis systems
2/50 Siemens ET B1 T · 2007
■Technical specifications
1)
Maximum tightening torque:
- M10 thread (with indicator): 40 Nm
- M10 capped thread: 50 Nm, depth of screw entry ≥ 9 mm
- M24 × 1.5 thread: 60 Nm.
2)
Temperature of water-cooled busbar max. +45 C.
3)
Maximum tightening torque: M10 capped thread: 35 Nm,
depth of screw entry ≥ 9 mm.
4)
Cooling air speed ≥ 2 m/s.
5)
Bottom (cooled) connection max. +60 °C, top connection (M10)
max. +110 °C.
■Selection and ordering data
For dimensional drawings, see page 2/59.
Type 3NC5 5311)
3NC5 8411)
3NC5 8401)
3NC5 8381)
Operational class (IEC 60269) aR
Rated voltage Un V AC 800 1000
Rated current In A 3502)
6302)
6002)
8002)
Melting I2t value I2ts (tvs = 1 ms) A2
s 66000 185000 360000
Breaking I2t value I2tA at Un A2
s 260000 888000 1728000
Temperature rise at In (body center) K 200 110 130
Power dissipation at In W 80 145 150 170
Varying load factor WL 0.9
Weight approx. kg 0.67 1.2 1.4 1.2
Type 3NE9 440-6 3NE9 450 3NE6 437 3NE6 444 3NE9 450-7 3NE6 437-7
Operational class (IEC 60269) gR aR
Rated voltage Un V AC 600 900 600 900
Rated current In
3)
A 850 12504)
7104)
9004)
12505)
7105)
Melting I2
t value I2
ts (tvs = 1 ms) A2
s 400000 100000 400000 100000
Breaking I2
t value I2
tA at Un A2
s 2480000 620000 1920000 2480000 620000
Temperature rise at In (body center) K 74 80 105 110
Power dissipation at In W 85 210 150 170 210 150
Varying load factor WL 1.0 0.9
Weight approx. kg 1.0 1.1 1.0
In Un Opera-
tional
class
Order No. Weight
1 unit
approx.
PS*/
P. unit
A V AC kg Unit(s)
For rectifiers in electrolysis systems
for screwing onto water-cooled busbars
350 800 aR 3NC5 531 0.671 1/3
600 1000 3NC5 840 1.408 3
630 800 3NC5 841 1.185 3
800 1000 3NC5 838 1.196 3
710 900 3NE6 437-7 1.168 3
1250 600 3NE9 450-7 1.245 3
For air-cooled rectifiers in electrolysis systems
710 800 gR 3NE6 437 1.093 3
850 1000 3NE9 440-6 1.082 3
900 1000 aR 3NE6 444 1.175 3
1250 800 3NE9 450 1.114 3
* You can order this quantity or a multiple thereof.
www.dienhathe.xyz
www.dienhathe.vn
Semiconductor Fuses
SITOR Fuse Links for Special Applications
For rectifiers in electrolysis systems
2/51Siemens ET B1 T · 2007
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
■Characteristic curves
Series 3NC5 531, 3NC5 8..
Operational class: aR
Rated voltage: 800 V AC (350 A, 600 A),
1000 V AC (600 A, 800 A)
Rated current: 350 ... 800 A
Time/current characteristics diagram
Correction factor kA for breaking I2t value
Let-through characteristics (current limitation at 50 Hz)
Peak arc voltage
p
vs
2102
10-3
2
4
6
10-2
64 1038 2 64 1048 2 4
2
4
6
10-1
2
4
6
100
2
4
6
101
2
4
6
102
2
4
6
103
2
4
6
104
I2_11432
6 1058
[s]
[A]
8 0 0 A6 3 0 A
3 5 0 A
6 0 0 A
Virtualpre-arcingtime
Prospective short-circuit current
0 200 400 600
1
800 1000
A
w [V]
I2_11434
3 5 0 A
6 3 0 A
6 0 0 A
8 0 0 A
Correctionfactor
0.8
0.6
0.4
0.2
Recovery voltage
c
p [A]
[A]
I2_11433
103
10
2
4
6
2
4
6
4
105
103
105
2 4104
2 64 82 64 8
3 5 0 A
6 0 0 A
6 3 0 A
8 0 0 A
Let-throughcurrent
Prospective short-circuit current
Unlimited peak values:
DC component 50 %
DC component 0 %
0 200 400 600 800 1000 1200
400
1200
1600
2000
0
s
w [ V ]
[V]
I2_11435
200
600
800
1000
1400
1800
6 0 0 A
8 0 0 A
3 5 0 A
6 3 0 A
Peakarcvoltage
Recovery voltage
Û
www.dienhathe.xyz
www.dienhathe.vn
Semiconductor Fuses
SITOR Fuse Links for Special Applications
For rectifiers in electrolysis systems
2/52 Siemens ET B1 T · 2007
Series 3NE6 4.., 3NE9 4..
Operational class: aR, gR
Rated voltage: 600 V AC (1250 A),
800 V AC (710 A, 1250 A,),
900 V AC (710 A)
Rated current: 710 ... 1250 A
Time/current characteristics diagrams
p
vs
2102
10-3
2
4
6
10-2
64 1038 2 64 1048 2 4
2
4
6
10-1
2
4
6
100
2
4
6
101
2
4
6
102
2
4
6
103
2
4
6
104
I2_11436
6 1058
[s]
[A]
8 5 0 A
7 1 0 A
Virtualpre-arcingtime
Prospective short-circuit current p
vs
2102
10-3
2
4
6
10-2
64 1038 2 64 1048 2 4
2
4
6
10-1
2
4
6
100
2
4
6
101
2
4
6
102
2
4
6
103
2
4
6
104
I2_11437
6 1058
[s]
[A]
1 2 5 0 A
9 0 0 A
Virtualpre-arcingtime
Prospective short-circuit current
www.dienhathe.xyz
www.dienhathe.vn
Semiconductor Fuses
SITOR Fuse Links for Special Applications
For rectifiers in electrolysis systems
2/53Siemens ET B1 T · 2007
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
Series 3NE6 4.., 3NE9 4..
Operational class: aR, gR
Rated voltage: 600 V AC (1250 A),
800 V AC (710 A, 1250 A),
900 V AC (710 A)
Rated current: 710 ... 1250 A
Let-through characteristics (current limitation at 50 Hz)
c
p [A]
[A]
I2_11438
103
10
2
4
6
2
4
6
4
105
103
105
2 4104
2 64 82 64 8
7 1 0 A
8 5 0 / 9 0 0 / 1 2 5 0 A
Let-throughcurrent
Prospective short-circuit current
Unlimited peak values:
DC component 50 %
DC component 0 %
Correction factor kA for breaking I2
t value Peak arc voltage
0 200 400 600
1
800 1000
A
w [V]
I2_11439
9 0 0 A
8 0 0 A
1 2 5 0 A
7 1 0 A
Correctionfactor
0.8
0.6
0.4
0.2
Recovery voltage
0 200 400 600 800 1000 1200
400
1200
1600
2000
0
s
w [ V ]
[V]
I2_11440
200
600
800
1000
1400
1800
8 5 0 A
7 1 0 A
9 0 0 A
1 2 5 0 A
Peakarcvoltage
Recovery voltage
Û
www.dienhathe.xyz
www.dienhathe.vn
Semiconductor Fuses
SITOR Fuse Links for Special Applications
For SITOR thyristor sets
2/54 Siemens ET B1 T · 2007
■Technical specifications
1)
Maximum tightening torque: M10 capped thread: 35 Nm,
depth of screw entry ≥ 9 mm.
2)
Cooling air speed ≥ 0.5 m/s. In the case of natural air cooling,
reduction of 5 %.
■Selection and ordering data
For dimensional drawings, see page 2/59.
Type 3NE4 117-5 3NE4 121-5 3NE4 146-5 3NE3 525-51)
3NE3 535-51)
Operational class (IEC 60269) gR aR
Rated voltage Un V AC 1000 800 1000
Rated current In A 50 100 170 2002)
4502)
Melting I2t value I2ts (tvs = 1 ms) A2
s 135 900 7370 7150 64500
Breaking I2t value I2tA at Un A2
s 1100 7400 60500 44000 395000
Temperature rise at In (body center) K 95 135 142 75 130
Power dissipation at In W 20 35 43 50 90
Varying load factor WL 0.85
Weight approx. kg 0.28 0.7
Type 3NE4 327-6B1)
3NE4 330-6B1)
3NE4 333-6B1)
3NE4 334-6B1)
3NE4 337-61)
Operational class (IEC 60269) aR
Rated voltage Un V AC 800
Rated current In A 250 315 450 500 710
Melting I2
t value I2
ts (tvs = 1 ms) A2
s 3600 7400 29400 42500 142000
Breaking I2
t value I2
tA at Un A2
s 29700 60700 191000 276000 923000
Temperature rise at In (body center) K 175 170 190 195 170
Power dissipation at In W 105 120 140 155
Varying load factor WL 0.85 0.95
Weight approx. kg 0.65
In Un Opera-
tional
class
Order No. Weight
1 unit
approx.
PS*/
P. unit
A V AC kg Unit(s)
For SITOR 6QG10 thyristor sets
200 1000 aR 3NE3 525-5 0.744 3
450 3NE3 535-5 0.746 3
For SITOR 6QG11 thyristor sets
50 1000 gR 3NE4 117-5 0.303 1/3
100 aR 3NE4 121-5 0.309 1/3
170 800 3NE4 146-5 0.311 1/3
For SITOR 6QG12 thyristor sets
250 800 aR 3NE4 327-6B 0.692 3
315 3NE4 330-6B 0.688 3
450 3NE4 333-6B 0.690 3
500 3NE4 334-6B 0.688 3
710 3NE4 337-6 0.689 3
* You can order this quantity or a multiple thereof.
www.dienhathe.xyz
www.dienhathe.vn
Semiconductor Fuses
SITOR Fuse Links for Special Applications
For SITOR thyristor sets
2/55Siemens ET B1 T · 2007
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
■Characteristic curves
Series 3NE3 5.5-5, 3NE4 1..-5
Operational class: aR, gR
Rated voltage: 800 V AC (170 A),
1000 V AC (50 A, 100 A, 200 A, 450 A)
Rated current: 50 ... 450 A
Time/current characteristics diagram
Correction factor kA for breaking I2t value
Let-through characteristics (current limitation at 50 Hz)
Peak arc voltage
p
vs
2101
10-3
2
4
6
10-2
64 1028 2 64 1038 2 4
2
4
6
10-1
2
4
6
100
2
4
6
101
2
4
6
102
2
4
6
103
2
4
6
104
I2_11441
6 1048
[s]
[A]
1 7 0 A
5 0 A 1 0 0 A 2 0 0 A 4 5 0 A
Virtualpre-arcingtime
Prospective short-circuit current
0 200 400 600
1
800 1000
A
w [V]
I2_11443
5 0 / 1 0 0 A
1 7 0 A
2 0 0 / 4 5 0 A
Correctionfactor
0.8
0.6
0.4
0.2
Recovery voltage
102
2 64 108
10
2
4
6
3
c
p [A]
[A]
102
3
2 64 108 4
2 64 108 5
2 4
I2_11442
10
2
4
6
4
2
4
1 0 0 A
2 0 0 A
1 7 0 A
5 0 A
4 5 0 A
Let-throughcurrent
Prospective short-circuit current
Unlimited peak values:
DC component 50 %
DC component 0 %
0 200 400 600 800 1000 1200
400
1200
1600
2000
0
s
w [ V ]
[V]
I2_11444
200
600
800
1000
1400
1800
2 0 0 A
1 7 0 A
ÛPeakarcvoltage
Recovery voltage
www.dienhathe.xyz
www.dienhathe.vn
Semiconductor Fuses
SITOR Fuse Links for Special Applications
For SITOR thyristor sets
2/56 Siemens ET B1 T · 2007
Series 3NE4 3..-6B, 3NE4 337-6
Operational class: aR
Rated voltage: 800 V AC
Rated current: 250 ... 710 A
Time/current characteristics diagram
Correction factor kA for breaking I2
t value
Let-through characteristics (current limitation at 50 Hz)
Peak arc voltage
p
vs
2102
10-3
2
4
6
10-2
64 1038 2 64 1048 2 4
2
4
6
10-1
2
4
6
100
2
4
6
101
2
4
6
102
2
4
6
103
2
4
6
104
I2_11445
6 1058
[s]
[A]
7 1 0 A
5 0 0 A
4 5 0 A
3 1 5 A
2 5 0 A
Virtualpre-arcingtime
Prospective short-circuit current
0 100 200 300 400 500 600
1
700 800
A
w [ V ]
3 1 5 A
4 5 0 A
Correctionfactor
Recovery voltage
0.2
0.4
0.6
0.8
c
p [A]
[A]
I2_11446
103
10
2
4
6
2
4
6
4
105
103
105
2 4104
2 64 82 64 8
2 5 0 A
3 1 5 A
4 5 0 A
5 0 0 A
7 1 0 A
Let-throughcurrent
Prospective short-circuit current
Unlimited peak values:
DC component 50 %
DC component 0 %
0 200 400 600 800 1000 1200
400
1200
1600
2000
0
s
w [ V ]
[V]
I2_11448
200
600
800
1000
1400
1800
Peakarcvoltage
Recovery voltage
Û
www.dienhathe.xyz
www.dienhathe.vn
Semiconductor Fuses
SITOR Fuse Links for Special Applications
For railway supply rectifiers
2/57Siemens ET B1 T · 2007
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
■Technical specifications
■Selection and ordering data
For dimensional drawings, see page 2/59.
Type 3NC7 327-2 3NC7 331-2
Operational class (IEC 60269) aR
Rated voltage Un V AC 680
Rated current In A 250 350
Melting I2t value I2ts (tvs = 1 ms) A2
s 244000 550000
Breaking I2t value I2tA at Un A2
s 635000 1430000
Temperature rise at In (body center) K 45 66
Power dissipation at In W 25 32
Varying load factor WL 0.9
Weight approx. kg 0.7
In Un Opera-
tional
class
Order No. Weight
1 unit
approx.
PS*/
P. unit
A V AC kg Unit(s)
For railway supply rectifiers
250 680 aR 3NC7 327-2 0.725 3
350 3NC7 331-2 0.740 3
* You can order this quantity or a multiple thereof.
www.dienhathe.xyz
www.dienhathe.vn
Semiconductor Fuses
SITOR Fuse Links for Special Applications
For railway supply rectifiers
2/58 Siemens ET B1 T · 2007
■Characteristic curves
Series 3NC7 3..-2
Operational class: aR
Rated voltage: 680 V AC
Rated current: 250 A, 350 A
Time/current characteristics diagram
Correction factor kA for breaking I2
t value
Let-through characteristics (current limitation at 50 Hz)
Peak arc voltage
p
vs
2102
10-3
2
4
6
10-2
64 1038 2 64 1048 2 4
2
4
6
10-1
2
4
6
100
2
4
6
101
2
4
6
102
2
4
6
103
2
4
6
104
I2_11449
6 1058
[s]
[A]
2 5 0 A
3 5 0 A
Virtualpre-arcingtime
Prospective short-circuit current
0 100 200 300 400 500 600
1
700 800
A
w [ V ]
Correctionfactor
Recovery voltage
0.2
0.4
0.6
0.8
c
p [A]
[A]
I2_11450
103
10
2
4
6
2
4
6
4
105
103
105
2 4104
2 64 82 64 8
2 5 0 A
3 5 0 A
Let-throughcurrent
Prospective short-circuit current
Unlimited peak values:
DC component 50 %
DC component 0 %
0 200 400 600 800 1000 1200
400
1200
1600
2000
0
s
w [ V ]
[V]
I2_11452
200
600
800
1000
1400
1800
ÛPeakarcvoltage
Recovery voltage
www.dienhathe.xyz
www.dienhathe.vn
Semiconductor Fuses
SITOR Fuse Links for Special Applications
Configuration Aids
2/59Siemens ET B1 T · 2007
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
■Dimensional drawings
3NC5 531 3NC5 8..
Type Dimensions
a b c
3NC5 838,
3NC5 841
98 88.5 25
3NC5 844 119 109.5 20.5
3NE6 4.., 3NE9 4.., 3NE6 4..-7, 3NE9 4..-7
Type Dimensions
a b
3NE6 437,
3NE9 440-6,
3NE9 450
89 76
3NE6 444 99 86
50
M10
M10
28
50
SW41
91
9
24,5
0,3
I2_11369
73
M10
40
M24
M10
SW41 b
a c
11
I2_11370
10
70
M10
28
70 b
a
10
81,5
I2_11371
70
M10
28
70
100
125
83
10
11
10
81,5
75,5
I2_11372
3NE3 5..-5 3NE4 3..-6B, 3NE4 337-6
3NE4 1..-5 3NC7 3..-2
7755
15
60
73
60
M10
20
10,5
82,5
I2_11373
I2_11374
60
M10
20
60 76
77
15
66
47
52
53
3010
54
57
62
26
40
10,4
I2_11375
12,5
57
68
119
57
30
7 79
10,510,5
I2_11376
www.dienhathe.xyz
www.dienhathe.vn
Semiconductor Fuses
SITOR Cylindrical Fuse Links
SITOR cylindrical fuse links
2/60 Siemens ET B1 T · 2007
■Overview
Load rating of SITOR cylindrical fuses without strikers in
fuse holders/fuse switch disconnectors/fuse disconnectors1)2)
Fuse tongs: 3NC1 000
Load rating of SITOR cylindrical fuses with strikers in
fuse holders/fuse switch disconnectors/fuse disconnectors1)2)
1) Fuse holders according to IEC 60269-3, UL 512,
fuse switch disconnectors (10 x 38, 14 x 51) according to IEC 60947-3,
fuse disconnectors (22 x 58) according to IEC 60947-3
2) The values Imax apply for "stand-alone operation". If several devices
are butt-mounted and/or subject to unfavorable cooling conditions, these
values may be reduced still further.
For SITOR
fuse links
Rated
voltage
Rated
current
Required
conductor
cross-
section
Cylindrical fuse bases Fuse holders/fuse switch disconnectors/
fuse disconnectors1)
1-pole 2-pole 3-pole 1-pole 2-pole 3-pole
In Cu Type Imax Type Imax Type Imax Type Imax Type Imax Type Imax
V AC A mm2
A A A A A A
Size 10 x 38
3NC1 003 600 3 1 3NC1 038-1 3 3NC1 038-2
/
2 ×
3NC1 038-1
3 3NC1 038-3
/
3 ×
3NC1 038-1
3 3NC1 091 3 3NC1 092
/
2 ×
3NC1 091
3 3NC1 093
/
3 ×
3NC1 091
3
3NC1 006 6 1 6 6 6 6 6 6
3NC1 008 8 1 8 8 8 8 8 8
3NC1 010 10 1.5 10 10 10 10 10 10
3NC1 012 12 1.5 12 12 12 12 12 12
3NC1 016 16 2.5 16 16 16 16 16 16
3NC1 020 20 2.5 20 20 20 20 20 20
3NC1 025 25 4 25 24 24 25 25 25
3NC1 032 32 6 32 28 28 30 32 29
Size 14 x 51
3NC1 401 660 1 1 3NC1 451-1 1 – – 3NC1 491 1 3NC1 492
/
2 ×
3NC1 491
1 3NC1 493
/
3 ×
3NC1 491
1
3NC1 402 2 1 2 2 2 2
3NC1 403 3 1 3 3 3 3
3NC1 404 4 1 4 4 4 4
3NC1 405 690 5 1 5 5 5 5
3NC1 406 6 1 6 6 6 6
3NC1 410 10 1.5 10 10 10 10
3NC1 415 15 1.5 15 15 15 15
3NC1 420 20 2.5 20 20 20 20
3NC1 425 25 4 25 25 24 23
3NC1 430 30 6 30 28 27 25
3NC1 432 32 6 32 31 30 30
3NC1 440 40 10 40 38 37 36
3NC1 450 50 10 50 48 46 44
Size 22 x 58
3NC2 220 690 20 2.5 3NC2 258-1 20 – – 3NC2 291 20 3NC2 292
/
2 ×
3NC2 291
20 3NC2 293
/
3 ×
3NC2 291
20
3NC2 225 25 4 25 25 25 25
3NC2 232 32 6 32 32 32 32
3NC2 240 40 10 40 40 39 38
3NC2 250 50 10 50 50 48 46
3NC2 263 63 16 63 60 58 56
3NC2 280 80 25 80 74 71 69
3NC2 200 600 100 35 100 95 90 85
For SITOR
fuse links
Rated voltage Rated current Required conduc-
tor cross-section
Fuse holders/fuse switch disconnectors/fuse disconnectors1)
1-pole 2-pole 3-pole
In Cu Type Imax Type Imax Type Imax
V AC A mm2
A A A
Size 14 x 51
3NC1 410-5 690 10 1.5 3NC1 491 10 3NC1 492/
2 × 3NC1 491-5
10 3NC1 493/
3 × 3NC1 491-5
10
3NC1 415-5 15 1.5 15 15 15
3NC1 420-5 20 2.5 20 20 20
3NC1 425-5 25 4 25 25 25
3NC1 430-5 30 6 30 30 30
3NC1 432-5 32 6 32 32 31
3NC1 440-5 40 10 38 35 34
3NC1 450-5 50 10 48 46 44
Size 22 x 58
3NC2 220-5 690 20 2.5 3NC2 291 20 3NC2 292/
2 × 3NC2 291-5
20 3NC2 293/
3 × 3NC2 291-5
20
3NC2 225-5 25 4 25 25 25
3NC2 232-5 32 6 32 31 30
3NC2 240-5 40 10 40 39 37
3NC2 250-5 50 10 45 43 42
3NC2 263-5 63 16 59 55 52
3NC2 280-5 80 25 71 69 68
3NC2 200-5 600 100 35 94 90 85
www.dienhathe.xyz
www.dienhathe.vn
Semiconductor Fuses
SITOR Cylindrical Fuse Links
SITOR cylindrical fuse links
2/61Siemens ET B1 T · 2007
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
■Technical specifications
Type 3NC1 003 3NC1 006 3NC1 008 3NC1 010 3NC1 012 3NC1 016 3NC1 020 3NC1 025 3NC1 032
Operational class (IEC 60269) aR
Rated voltage Un V 600 V AC/400 V DC
Rated current In A 3 6 8 10 12 16 20 25 32
Melting I2t value I2ts (tvs = 1 ms) A2
s 3 4 6 9 15 25 34 60 95
Breaking I2t value I2tA at Un A2
s 8 20 30 60 110 150 200 250 500
Temperature rise at In (body center) K 30 25 40 50 60 80 90 110
Power dissipation at In W 1.2 1.5 2 2.5 3 3.5 4.8 6 7.5
Weight approx. kg 0.01
Type 3NC1 401 3NC1 402 3NC1 403 3NC1 404 3NC1 405 3NC1 406 3NC1 410
Operational class (IEC 60269) aR
Rated voltage Un V 660 V AC/700 V DC 690 V AC/700 V DC
Rated current In A 1 2 3 4 5 6 10
Melting I2
t value I2
ts (tvs = 1 ms) A2
s – 1.6 – 3.6
Breaking I2
t value I2
tA at Un A2
s 1.2 10 15 25 9 12 20
Temperature rise at In (body center) K 90 30 40 50 20 30 50
Power dissipation at In W 5 3 2.5 3 1.5 1.5 4
Certification according to UL 248-13
Weight approx. kg 0.02
Type 3NC1 415 3NC1 420 3NC1 425 3NC1 430 3NC1 432 3NC1 440 3NC1 450
Operational class (IEC 60269) aR
Rated voltage Un V 690 V AC/700 V DC
Rated current In A 15 20 25 30 32 40 50
Melting I2
t value I2
ts (tvs = 1 ms) A2
s 10 26 44 58 95 110 220
Breaking I2
t value I2
tA at Un A2
s 75 120 250 300 700 900 1800
Temperature rise at In (body center) K 60 70 80 100 110
Power dissipation at In W 5.5 6 7 9 7.6 8 9
Certification according to UL 248-13
Weight approx. kg 0.02
Type 3NC2 220 3NC2 225 3NC2 232 3NC2 240 3NC2 250 3NC2 263 3NC2 280 3NC2 200
Operational class (IEC 60269) aR
Rated voltage Un V 690 V AC/700 V DC 600 V AC/700 V DC
Rated current In A 20 25 32 40 50 63 80 100
Melting I2
t value I2
ts (tvs = 1 ms) A2
s 34 50 80 100 185 310 620 1250
Breaking I2
t value I2
tA at Un A2
s 220 300 450 700 1350 2600 5500 8000
Temperature rise at In (body center) K 40 50 65 80 90 100 110
Power dissipation at In W 4.6 5.6 7 8.5 9.5 11 13.5 16
Certification according to UL 248-13
Weight approx. kg 0.06
www.dienhathe.xyz
www.dienhathe.vn
Semiconductor Fuses
SITOR Cylindrical Fuse Links
SITOR cylindrical fuse links
2/62 Siemens ET B1 T · 2007
1) UL recognized
1)
These devices have been specially developed for the application of SITOR
fuse links with regard to heat tolerance with heat dissipation and are there-
fore not recommended for standard applications.
Type 3NC1 410-5 3NC1 415-5 3NC1 420-5 3NC1 425-5 3NC1 430-5 3NC1 432-5 3NC1 440-5 3NC1 450-5
Operational class (IEC 60269) aR
Rated voltage Un V 690 AC/700 DC1)
Rated current In A 10 15 20 25 30 32 40 50
Melting I2
t value I2
ts (tvs = 1 ms) A2
s 3.6 9 26 47 58 68 84 200
Breaking I2t value I2tA at Un A2
s 90 100 500 400 500 600 900 2000
Temperature rise at In (body center) K 50 60 70 80 80 80 100 110
Power dissipation at In W 4 5.5 6 7 9 7.6 8 9
Certification according to UL 248-13
Weight approx. kg 0.02
Type 3NC2 220-5 3NC2 225-5 3NC2 232-5 3NC2 240-5 3NC2 250-5 3NC2 263-5 3NC2 280-5 3NC2 200-5
Operational class (IEC 60269) aR
Rated voltage Un V 690 AC/700 DC1) 600 AC/700 DC1)
Rated current In A 20 25 32 40 50 63 80 100
Melting I2t value I2ts (tvs = 1 ms) A2
s 19 34 54 68 135 280 600 1100
Breaking I2t value I2tA at Un A2
s 240 350 500 800 1500 3000 6000 8500
Temperature rise at In (body center) K 40 50 65 80 90 100 110 110
Power dissipation at In W 5 6 8 9 9.5 11 13.5 16
Certification according to UL 248-13
Weight approx. kg 0.06
Fuse bases
Sizes 10 x 38 14 x 51 22 x 58
Rated voltage V AC 600 690
V DC 600 690
Rated current In A 32 50 100
Fuse holders/fuse switch disconnectors/
fuse disconnectors
Classifications
• According to IEC 60269-3, UL 512 Fuse holders Fuse holders
• According to IEC 60947-3 Fuse switch disconnectors Fuse disconnectors
Sizes 10 x 38 14 x 51
with and without alarm
switches
22 x 58
with and without alarm
switches
Rated voltage V AC 690
Rated current In A 32 50 100
Max. power dissipation of fuse link1) W 3 (6 mm2)
4.3 (10 mm2)
5 (10 mm2)
6.5 (25 mm2)
9.5 (35 mm2)
11 (50 mm2)
Feeder terminals mm2 1.5 ... 25 1.5 ... 35 4 ... 50
Operational class according to IEC 60947-3 22B/32 A/400 V AC
22B/10 A/690 V AC
22B/50 A/400 V AC
22B/20 A/690 V AC
20B/690 V AC
Rated conditional short-circuit current
• At 400 V kA 50 (32 A gG) 100 (50 A gG) 100 (100 A gG)
80 (80 A gG)
Approvals UUS s
www.dienhathe.xyz
www.dienhathe.vn
Dienhathe.com semiconductor fuses
Dienhathe.com semiconductor fuses
Dienhathe.com semiconductor fuses
Dienhathe.com semiconductor fuses
Dienhathe.com semiconductor fuses
Dienhathe.com semiconductor fuses
Dienhathe.com semiconductor fuses
Dienhathe.com semiconductor fuses
Dienhathe.com semiconductor fuses
Dienhathe.com semiconductor fuses
Dienhathe.com semiconductor fuses
Dienhathe.com semiconductor fuses
Dienhathe.com semiconductor fuses
Dienhathe.com semiconductor fuses
Dienhathe.com semiconductor fuses
Dienhathe.com semiconductor fuses
Dienhathe.com semiconductor fuses
Dienhathe.com semiconductor fuses
Dienhathe.com semiconductor fuses
Dienhathe.com semiconductor fuses
Dienhathe.com semiconductor fuses
Dienhathe.com semiconductor fuses
Dienhathe.com semiconductor fuses
Dienhathe.com semiconductor fuses
Dienhathe.com semiconductor fuses
Dienhathe.com semiconductor fuses
Dienhathe.com semiconductor fuses
Dienhathe.com semiconductor fuses

More Related Content

What's hot

Nec and oesc-3
Nec and oesc-3Nec and oesc-3
Nec and oesc-3grantlerc
 
Catalog MCCB & ACB Fuji Electric dòng G-TWIN Mới Nhất 2019
Catalog MCCB & ACB Fuji Electric dòng G-TWIN Mới Nhất 2019Catalog MCCB & ACB Fuji Electric dòng G-TWIN Mới Nhất 2019
Catalog MCCB & ACB Fuji Electric dòng G-TWIN Mới Nhất 2019CTY TNHH HẠO PHƯƠNG
 
Nec and oesc-2
Nec and oesc-2Nec and oesc-2
Nec and oesc-2grantlerc
 
ABB Medium Voltage MV Surge Arresters - AC & DC Surge Arresters & Protection...
ABB Medium Voltage MV Surge Arresters -  AC & DC Surge Arresters & Protection...ABB Medium Voltage MV Surge Arresters -  AC & DC Surge Arresters & Protection...
ABB Medium Voltage MV Surge Arresters - AC & DC Surge Arresters & Protection...Thorne & Derrick International
 
Catalog contactor fuji-electric Mới Nhất - Hạo Phương
Catalog contactor fuji-electric Mới Nhất - Hạo PhươngCatalog contactor fuji-electric Mới Nhất - Hạo Phương
Catalog contactor fuji-electric Mới Nhất - Hạo PhươngCTY TNHH HẠO PHƯƠNG
 
Iwiss Fiber Optic Tools Catalogue 2013
Iwiss Fiber Optic Tools Catalogue 2013Iwiss Fiber Optic Tools Catalogue 2013
Iwiss Fiber Optic Tools Catalogue 2013Iwiss Tools Co.,Ltd
 
Thermon FP Heat Tracing Cable - Spec Sheet
Thermon FP Heat Tracing Cable - Spec SheetThermon FP Heat Tracing Cable - Spec Sheet
Thermon FP Heat Tracing Cable - Spec SheetThorne & Derrick UK
 
Jvc mx g75v-g78v_gt85v_gt88v_gt95v_gt98v
Jvc mx g75v-g78v_gt85v_gt88v_gt95v_gt98vJvc mx g75v-g78v_gt85v_gt88v_gt95v_gt98v
Jvc mx g75v-g78v_gt85v_gt88v_gt95v_gt98vsophon505
 

What's hot (20)

Catalogue Siemens ACB3 WN
Catalogue Siemens ACB3 WNCatalogue Siemens ACB3 WN
Catalogue Siemens ACB3 WN
 
Nec and oesc-3
Nec and oesc-3Nec and oesc-3
Nec and oesc-3
 
Acb1
Acb1Acb1
Acb1
 
Thông số kĩ thuật siemens monitoring devices
Thông số kĩ thuật siemens monitoring devicesThông số kĩ thuật siemens monitoring devices
Thông số kĩ thuật siemens monitoring devices
 
Catalog mcb fuji electric
Catalog mcb fuji electricCatalog mcb fuji electric
Catalog mcb fuji electric
 
Catalog MCCB & ACB Fuji Electric dòng G-TWIN Mới Nhất 2019
Catalog MCCB & ACB Fuji Electric dòng G-TWIN Mới Nhất 2019Catalog MCCB & ACB Fuji Electric dòng G-TWIN Mới Nhất 2019
Catalog MCCB & ACB Fuji Electric dòng G-TWIN Mới Nhất 2019
 
Fmcat l smccb
Fmcat l smccbFmcat l smccb
Fmcat l smccb
 
Thông số kĩ thuật siemens miniature circuit breakers
Thông số kĩ thuật siemens miniature circuit breakersThông số kĩ thuật siemens miniature circuit breakers
Thông số kĩ thuật siemens miniature circuit breakers
 
Nec and oesc-2
Nec and oesc-2Nec and oesc-2
Nec and oesc-2
 
Thông số kĩ thuật siemens MCCB 3VL
Thông số kĩ thuật siemens MCCB 3VLThông số kĩ thuật siemens MCCB 3VL
Thông số kĩ thuật siemens MCCB 3VL
 
Thông số kĩ thuật siemens MCCB 3 VF
Thông số kĩ thuật siemens MCCB 3 VFThông số kĩ thuật siemens MCCB 3 VF
Thông số kĩ thuật siemens MCCB 3 VF
 
ABB Medium Voltage MV Surge Arresters - AC & DC Surge Arresters & Protection...
ABB Medium Voltage MV Surge Arresters -  AC & DC Surge Arresters & Protection...ABB Medium Voltage MV Surge Arresters -  AC & DC Surge Arresters & Protection...
ABB Medium Voltage MV Surge Arresters - AC & DC Surge Arresters & Protection...
 
Catalog contactor fuji-electric Mới Nhất - Hạo Phương
Catalog contactor fuji-electric Mới Nhất - Hạo PhươngCatalog contactor fuji-electric Mới Nhất - Hạo Phương
Catalog contactor fuji-electric Mới Nhất - Hạo Phương
 
JVC AX-V8000
JVC AX-V8000JVC AX-V8000
JVC AX-V8000
 
01 - Contactor - Fuji Electric
 01 - Contactor - Fuji Electric 01 - Contactor - Fuji Electric
01 - Contactor - Fuji Electric
 
Iwiss Fiber Optic Tools Catalogue 2013
Iwiss Fiber Optic Tools Catalogue 2013Iwiss Fiber Optic Tools Catalogue 2013
Iwiss Fiber Optic Tools Catalogue 2013
 
Thermon FP Heat Tracing Cable - Spec Sheet
Thermon FP Heat Tracing Cable - Spec SheetThermon FP Heat Tracing Cable - Spec Sheet
Thermon FP Heat Tracing Cable - Spec Sheet
 
Jvc mx g75v-g78v_gt85v_gt88v_gt95v_gt98v
Jvc mx g75v-g78v_gt85v_gt88v_gt95v_gt98vJvc mx g75v-g78v_gt85v_gt88v_gt95v_gt98v
Jvc mx g75v-g78v_gt85v_gt88v_gt95v_gt98v
 
06 - MCCB & ACB - Fuji Electric
06 - MCCB & ACB - Fuji Electric06 - MCCB & ACB - Fuji Electric
06 - MCCB & ACB - Fuji Electric
 
Uci274 f
Uci274 fUci274 f
Uci274 f
 

Similar to Dienhathe.com semiconductor fuses

02- Manual Motor Starter - Fuji Electric
02- Manual Motor Starter - Fuji Electric02- Manual Motor Starter - Fuji Electric
02- Manual Motor Starter - Fuji ElectricCTY TNHH HẠO PHƯƠNG
 
Catalog hitachi hitachi switch&breaders ctlg eng-dienhathe.org
Catalog hitachi hitachi switch&breaders ctlg eng-dienhathe.orgCatalog hitachi hitachi switch&breaders ctlg eng-dienhathe.org
Catalog hitachi hitachi switch&breaders ctlg eng-dienhathe.orgDien Ha The
 
SIBA Fuses DC Traction Fuses - Rail Industry Fuse Links
SIBA Fuses DC Traction Fuses - Rail Industry Fuse LinksSIBA Fuses DC Traction Fuses - Rail Industry Fuse Links
SIBA Fuses DC Traction Fuses - Rail Industry Fuse LinksThorne & Derrick International
 
Dienhathe.com mcb-5 sy
Dienhathe.com mcb-5 syDienhathe.com mcb-5 sy
Dienhathe.com mcb-5 syDien Ha The
 
Stahl 8264 CUBEx Reversing Starter Motor Starters – ATEX Zone 1 Zone 2 Hazard...
Stahl 8264 CUBEx Reversing Starter Motor Starters – ATEX Zone 1 Zone 2 Hazard...Stahl 8264 CUBEx Reversing Starter Motor Starters – ATEX Zone 1 Zone 2 Hazard...
Stahl 8264 CUBEx Reversing Starter Motor Starters – ATEX Zone 1 Zone 2 Hazard...Thorne & Derrick International
 
Stahl 8264 CUBEx Direct Online (DOL) Motor Starter – ATEX Zone 1 Zone 2 Hazar...
Stahl 8264 CUBEx Direct Online (DOL) Motor Starter – ATEX Zone 1 Zone 2 Hazar...Stahl 8264 CUBEx Direct Online (DOL) Motor Starter – ATEX Zone 1 Zone 2 Hazar...
Stahl 8264 CUBEx Direct Online (DOL) Motor Starter – ATEX Zone 1 Zone 2 Hazar...Thorne & Derrick International
 
Stahl 8264 CUBEx Star Delta Motor Starter – ATEX Zone 1 Zone 2 Hazardous Area
Stahl 8264 CUBEx Star Delta Motor Starter – ATEX Zone 1 Zone 2 Hazardous Area Stahl 8264 CUBEx Star Delta Motor Starter – ATEX Zone 1 Zone 2 Hazardous Area
Stahl 8264 CUBEx Star Delta Motor Starter – ATEX Zone 1 Zone 2 Hazardous Area Thorne & Derrick International
 
Brochure_26-80S-ANSI _SG104309BEN_B04-0914
Brochure_26-80S-ANSI _SG104309BEN_B04-0914Brochure_26-80S-ANSI _SG104309BEN_B04-0914
Brochure_26-80S-ANSI _SG104309BEN_B04-0914Patrick Volluz
 
Stahl 8220 Star Delta Motor Starters – ATEX Zone 1 Zone 2 Hazardous Area
Stahl 8220 Star Delta Motor Starters – ATEX Zone 1 Zone 2 Hazardous Area Stahl 8220 Star Delta Motor Starters – ATEX Zone 1 Zone 2 Hazardous Area
Stahl 8220 Star Delta Motor Starters – ATEX Zone 1 Zone 2 Hazardous Area Thorne & Derrick International
 
Stahl 8220 Star Reversing Starter Motor Starters - ATEX Zone 1 Zone 2 Hazardo...
Stahl 8220 Star Reversing Starter Motor Starters - ATEX Zone 1 Zone 2 Hazardo...Stahl 8220 Star Reversing Starter Motor Starters - ATEX Zone 1 Zone 2 Hazardo...
Stahl 8220 Star Reversing Starter Motor Starters - ATEX Zone 1 Zone 2 Hazardo...Thorne & Derrick International
 
Stahl 8220 Direct On Line (DOL) Motor Starters – ATEX Zone 1 Zone 2 Hazardous...
Stahl 8220 Direct On Line (DOL) Motor Starters – ATEX Zone 1 Zone 2 Hazardous...Stahl 8220 Direct On Line (DOL) Motor Starters – ATEX Zone 1 Zone 2 Hazardous...
Stahl 8220 Direct On Line (DOL) Motor Starters – ATEX Zone 1 Zone 2 Hazardous...Thorne & Derrick International
 

Similar to Dienhathe.com semiconductor fuses (20)

784144_Thyrotronic_gb
784144_Thyrotronic_gb784144_Thyrotronic_gb
784144_Thyrotronic_gb
 
ABB HRC High Voltage Fuse Links
ABB HRC High Voltage Fuse Links ABB HRC High Voltage Fuse Links
ABB HRC High Voltage Fuse Links
 
02- Manual Motor Starter - Fuji Electric
02- Manual Motor Starter - Fuji Electric02- Manual Motor Starter - Fuji Electric
02- Manual Motor Starter - Fuji Electric
 
Catalog hitachi hitachi switch&breaders ctlg eng-dienhathe.org
Catalog hitachi hitachi switch&breaders ctlg eng-dienhathe.orgCatalog hitachi hitachi switch&breaders ctlg eng-dienhathe.org
Catalog hitachi hitachi switch&breaders ctlg eng-dienhathe.org
 
SIBA Fuses DC Traction Fuses - Rail Industry Fuse Links
SIBA Fuses DC Traction Fuses - Rail Industry Fuse LinksSIBA Fuses DC Traction Fuses - Rail Industry Fuse Links
SIBA Fuses DC Traction Fuses - Rail Industry Fuse Links
 
Hci5 f
Hci5 fHci5 f
Hci5 f
 
Lawson - Low Voltage Fuse Links
Lawson - Low Voltage Fuse Links Lawson - Low Voltage Fuse Links
Lawson - Low Voltage Fuse Links
 
Thông số kĩ thuật siemens MCB 5SY
Thông số kĩ thuật siemens MCB 5SYThông số kĩ thuật siemens MCB 5SY
Thông số kĩ thuật siemens MCB 5SY
 
Dienhathe.com mcb-5 sy
Dienhathe.com mcb-5 syDienhathe.com mcb-5 sy
Dienhathe.com mcb-5 sy
 
Hci4 c
Hci4 cHci4 c
Hci4 c
 
Catalog Motor CB Fuji Electric
Catalog Motor CB Fuji ElectricCatalog Motor CB Fuji Electric
Catalog Motor CB Fuji Electric
 
Stahl 8264 CUBEx Reversing Starter Motor Starters – ATEX Zone 1 Zone 2 Hazard...
Stahl 8264 CUBEx Reversing Starter Motor Starters – ATEX Zone 1 Zone 2 Hazard...Stahl 8264 CUBEx Reversing Starter Motor Starters – ATEX Zone 1 Zone 2 Hazard...
Stahl 8264 CUBEx Reversing Starter Motor Starters – ATEX Zone 1 Zone 2 Hazard...
 
Stahl 8264 CUBEx Direct Online (DOL) Motor Starter – ATEX Zone 1 Zone 2 Hazar...
Stahl 8264 CUBEx Direct Online (DOL) Motor Starter – ATEX Zone 1 Zone 2 Hazar...Stahl 8264 CUBEx Direct Online (DOL) Motor Starter – ATEX Zone 1 Zone 2 Hazar...
Stahl 8264 CUBEx Direct Online (DOL) Motor Starter – ATEX Zone 1 Zone 2 Hazar...
 
Stahl 8264 CUBEx Star Delta Motor Starter – ATEX Zone 1 Zone 2 Hazardous Area
Stahl 8264 CUBEx Star Delta Motor Starter – ATEX Zone 1 Zone 2 Hazardous Area Stahl 8264 CUBEx Star Delta Motor Starter – ATEX Zone 1 Zone 2 Hazardous Area
Stahl 8264 CUBEx Star Delta Motor Starter – ATEX Zone 1 Zone 2 Hazardous Area
 
Brochure_26-80S-ANSI _SG104309BEN_B04-0914
Brochure_26-80S-ANSI _SG104309BEN_B04-0914Brochure_26-80S-ANSI _SG104309BEN_B04-0914
Brochure_26-80S-ANSI _SG104309BEN_B04-0914
 
Hci5 d
Hci5 dHci5 d
Hci5 d
 
Stahl 8220 Star Delta Motor Starters – ATEX Zone 1 Zone 2 Hazardous Area
Stahl 8220 Star Delta Motor Starters – ATEX Zone 1 Zone 2 Hazardous Area Stahl 8220 Star Delta Motor Starters – ATEX Zone 1 Zone 2 Hazardous Area
Stahl 8220 Star Delta Motor Starters – ATEX Zone 1 Zone 2 Hazardous Area
 
Stahl 8220 Star Reversing Starter Motor Starters - ATEX Zone 1 Zone 2 Hazardo...
Stahl 8220 Star Reversing Starter Motor Starters - ATEX Zone 1 Zone 2 Hazardo...Stahl 8220 Star Reversing Starter Motor Starters - ATEX Zone 1 Zone 2 Hazardo...
Stahl 8220 Star Reversing Starter Motor Starters - ATEX Zone 1 Zone 2 Hazardo...
 
Stahl 8220 Direct On Line (DOL) Motor Starters – ATEX Zone 1 Zone 2 Hazardous...
Stahl 8220 Direct On Line (DOL) Motor Starters – ATEX Zone 1 Zone 2 Hazardous...Stahl 8220 Direct On Line (DOL) Motor Starters – ATEX Zone 1 Zone 2 Hazardous...
Stahl 8220 Direct On Line (DOL) Motor Starters – ATEX Zone 1 Zone 2 Hazardous...
 
Uci224 e
Uci224 eUci224 e
Uci224 e
 

More from Dien Ha The

Vnd feb 2020 price list schneider (1)
Vnd feb 2020 price list schneider (1)Vnd feb 2020 price list schneider (1)
Vnd feb 2020 price list schneider (1)Dien Ha The
 
Resize bientanfuji-dienhathe.com
Resize bientanfuji-dienhathe.comResize bientanfuji-dienhathe.com
Resize bientanfuji-dienhathe.comDien Ha The
 
Fed e-quick-start-up-guide-bientanfuji-dienhathe.com
Fed e-quick-start-up-guide-bientanfuji-dienhathe.comFed e-quick-start-up-guide-bientanfuji-dienhathe.com
Fed e-quick-start-up-guide-bientanfuji-dienhathe.comDien Ha The
 
Fed e-quick-start-manual-bientanfuji-dienhathe.com
Fed e-quick-start-manual-bientanfuji-dienhathe.comFed e-quick-start-manual-bientanfuji-dienhathe.com
Fed e-quick-start-manual-bientanfuji-dienhathe.comDien Ha The
 
Ls bang gia ls ap dung 20 04-2019
Ls bang gia ls ap dung 20 04-2019Ls bang gia ls ap dung 20 04-2019
Ls bang gia ls ap dung 20 04-2019Dien Ha The
 
Mitsubishi graphic operation terminal got2000 series parts library book
Mitsubishi graphic operation terminal got2000 series parts library bookMitsubishi graphic operation terminal got2000 series parts library book
Mitsubishi graphic operation terminal got2000 series parts library bookDien Ha The
 
Mitsubishi inverter fr-a700-instruction-manualbasic-160425031653
Mitsubishi inverter fr-a700-instruction-manualbasic-160425031653Mitsubishi inverter fr-a700-instruction-manualbasic-160425031653
Mitsubishi inverter fr-a700-instruction-manualbasic-160425031653Dien Ha The
 
Mitsubishi graphic operation terminal got2000 series gt2103 new product release
Mitsubishi graphic operation terminal got2000 series gt2103 new product releaseMitsubishi graphic operation terminal got2000 series gt2103 new product release
Mitsubishi graphic operation terminal got2000 series gt2103 new product releaseDien Ha The
 
Mitsubishi graphic operation terminal got2000 series got mobile function quic...
Mitsubishi graphic operation terminal got2000 series got mobile function quic...Mitsubishi graphic operation terminal got2000 series got mobile function quic...
Mitsubishi graphic operation terminal got2000 series got mobile function quic...Dien Ha The
 
Mitsubishi graphic operation terminal got2000 series drive control interactiv...
Mitsubishi graphic operation terminal got2000 series drive control interactiv...Mitsubishi graphic operation terminal got2000 series drive control interactiv...
Mitsubishi graphic operation terminal got2000 series drive control interactiv...Dien Ha The
 
Mitsubishi inverter option catalog
Mitsubishi inverter option catalogMitsubishi inverter option catalog
Mitsubishi inverter option catalogDien Ha The
 
Mitsubishi low voltage ws-v series mccb and elcb
Mitsubishi low voltage ws-v series mccb and elcbMitsubishi low voltage ws-v series mccb and elcb
Mitsubishi low voltage ws-v series mccb and elcbDien Ha The
 
Mitsubishi graphic operation terminal got2000 series (concise)
Mitsubishi graphic operation terminal got2000 series (concise)Mitsubishi graphic operation terminal got2000 series (concise)
Mitsubishi graphic operation terminal got2000 series (concise)Dien Ha The
 
Mitsubishi low voltage ws-v series comparison of previous and new models
Mitsubishi low voltage ws-v series comparison of previous and new modelsMitsubishi low voltage ws-v series comparison of previous and new models
Mitsubishi low voltage ws-v series comparison of previous and new modelsDien Ha The
 
Mitsubishi inverter inverter family
Mitsubishi inverter inverter familyMitsubishi inverter inverter family
Mitsubishi inverter inverter familyDien Ha The
 
Mitsubishi low voltage miniature circuit breakers din series
Mitsubishi low voltage miniature circuit breakers din seriesMitsubishi low voltage miniature circuit breakers din series
Mitsubishi low voltage miniature circuit breakers din seriesDien Ha The
 
Mitsubishi inverter freqrol-hc2 series
Mitsubishi inverter freqrol-hc2 seriesMitsubishi inverter freqrol-hc2 series
Mitsubishi inverter freqrol-hc2 seriesDien Ha The
 
Mitsubishi low voltage mccb and elcb(ws-v series) y0720-version 1-mitsu
Mitsubishi low voltage mccb and elcb(ws-v series) y0720-version 1-mitsuMitsubishi low voltage mccb and elcb(ws-v series) y0720-version 1-mitsu
Mitsubishi low voltage mccb and elcb(ws-v series) y0720-version 1-mitsuDien Ha The
 
Mitsubishi inverter freqrol-f700 pj series
Mitsubishi inverter freqrol-f700 pj seriesMitsubishi inverter freqrol-f700 pj series
Mitsubishi inverter freqrol-f700 pj seriesDien Ha The
 
Mitsubishi inverter catalog-mitsubishi-inverter-option-160426021125
Mitsubishi inverter catalog-mitsubishi-inverter-option-160426021125Mitsubishi inverter catalog-mitsubishi-inverter-option-160426021125
Mitsubishi inverter catalog-mitsubishi-inverter-option-160426021125Dien Ha The
 

More from Dien Ha The (20)

Vnd feb 2020 price list schneider (1)
Vnd feb 2020 price list schneider (1)Vnd feb 2020 price list schneider (1)
Vnd feb 2020 price list schneider (1)
 
Resize bientanfuji-dienhathe.com
Resize bientanfuji-dienhathe.comResize bientanfuji-dienhathe.com
Resize bientanfuji-dienhathe.com
 
Fed e-quick-start-up-guide-bientanfuji-dienhathe.com
Fed e-quick-start-up-guide-bientanfuji-dienhathe.comFed e-quick-start-up-guide-bientanfuji-dienhathe.com
Fed e-quick-start-up-guide-bientanfuji-dienhathe.com
 
Fed e-quick-start-manual-bientanfuji-dienhathe.com
Fed e-quick-start-manual-bientanfuji-dienhathe.comFed e-quick-start-manual-bientanfuji-dienhathe.com
Fed e-quick-start-manual-bientanfuji-dienhathe.com
 
Ls bang gia ls ap dung 20 04-2019
Ls bang gia ls ap dung 20 04-2019Ls bang gia ls ap dung 20 04-2019
Ls bang gia ls ap dung 20 04-2019
 
Mitsubishi graphic operation terminal got2000 series parts library book
Mitsubishi graphic operation terminal got2000 series parts library bookMitsubishi graphic operation terminal got2000 series parts library book
Mitsubishi graphic operation terminal got2000 series parts library book
 
Mitsubishi inverter fr-a700-instruction-manualbasic-160425031653
Mitsubishi inverter fr-a700-instruction-manualbasic-160425031653Mitsubishi inverter fr-a700-instruction-manualbasic-160425031653
Mitsubishi inverter fr-a700-instruction-manualbasic-160425031653
 
Mitsubishi graphic operation terminal got2000 series gt2103 new product release
Mitsubishi graphic operation terminal got2000 series gt2103 new product releaseMitsubishi graphic operation terminal got2000 series gt2103 new product release
Mitsubishi graphic operation terminal got2000 series gt2103 new product release
 
Mitsubishi graphic operation terminal got2000 series got mobile function quic...
Mitsubishi graphic operation terminal got2000 series got mobile function quic...Mitsubishi graphic operation terminal got2000 series got mobile function quic...
Mitsubishi graphic operation terminal got2000 series got mobile function quic...
 
Mitsubishi graphic operation terminal got2000 series drive control interactiv...
Mitsubishi graphic operation terminal got2000 series drive control interactiv...Mitsubishi graphic operation terminal got2000 series drive control interactiv...
Mitsubishi graphic operation terminal got2000 series drive control interactiv...
 
Mitsubishi inverter option catalog
Mitsubishi inverter option catalogMitsubishi inverter option catalog
Mitsubishi inverter option catalog
 
Mitsubishi low voltage ws-v series mccb and elcb
Mitsubishi low voltage ws-v series mccb and elcbMitsubishi low voltage ws-v series mccb and elcb
Mitsubishi low voltage ws-v series mccb and elcb
 
Mitsubishi graphic operation terminal got2000 series (concise)
Mitsubishi graphic operation terminal got2000 series (concise)Mitsubishi graphic operation terminal got2000 series (concise)
Mitsubishi graphic operation terminal got2000 series (concise)
 
Mitsubishi low voltage ws-v series comparison of previous and new models
Mitsubishi low voltage ws-v series comparison of previous and new modelsMitsubishi low voltage ws-v series comparison of previous and new models
Mitsubishi low voltage ws-v series comparison of previous and new models
 
Mitsubishi inverter inverter family
Mitsubishi inverter inverter familyMitsubishi inverter inverter family
Mitsubishi inverter inverter family
 
Mitsubishi low voltage miniature circuit breakers din series
Mitsubishi low voltage miniature circuit breakers din seriesMitsubishi low voltage miniature circuit breakers din series
Mitsubishi low voltage miniature circuit breakers din series
 
Mitsubishi inverter freqrol-hc2 series
Mitsubishi inverter freqrol-hc2 seriesMitsubishi inverter freqrol-hc2 series
Mitsubishi inverter freqrol-hc2 series
 
Mitsubishi low voltage mccb and elcb(ws-v series) y0720-version 1-mitsu
Mitsubishi low voltage mccb and elcb(ws-v series) y0720-version 1-mitsuMitsubishi low voltage mccb and elcb(ws-v series) y0720-version 1-mitsu
Mitsubishi low voltage mccb and elcb(ws-v series) y0720-version 1-mitsu
 
Mitsubishi inverter freqrol-f700 pj series
Mitsubishi inverter freqrol-f700 pj seriesMitsubishi inverter freqrol-f700 pj series
Mitsubishi inverter freqrol-f700 pj series
 
Mitsubishi inverter catalog-mitsubishi-inverter-option-160426021125
Mitsubishi inverter catalog-mitsubishi-inverter-option-160426021125Mitsubishi inverter catalog-mitsubishi-inverter-option-160426021125
Mitsubishi inverter catalog-mitsubishi-inverter-option-160426021125
 

Recently uploaded

HARMONY IN THE HUMAN BEING - Unit-II UHV-2
HARMONY IN THE HUMAN BEING - Unit-II UHV-2HARMONY IN THE HUMAN BEING - Unit-II UHV-2
HARMONY IN THE HUMAN BEING - Unit-II UHV-2RajaP95
 
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVRajaP95
 
microprocessor 8085 and its interfacing
microprocessor 8085  and its interfacingmicroprocessor 8085  and its interfacing
microprocessor 8085 and its interfacingjaychoudhary37
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escortsranjana rawat
 
Oxy acetylene welding presentation note.
Oxy acetylene welding presentation note.Oxy acetylene welding presentation note.
Oxy acetylene welding presentation note.eptoze12
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
Sachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective IntroductionSachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective IntroductionDr.Costas Sachpazis
 
Current Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCLCurrent Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCLDeelipZope
 
SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )Tsuyoshi Horigome
 
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130Suhani Kapoor
 
Heart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptxHeart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptxPoojaBan
 
Call Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile serviceCall Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile servicerehmti665
 
Application of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptxApplication of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptx959SahilShah
 
power system scada applications and uses
power system scada applications and usespower system scada applications and uses
power system scada applications and usesDevarapalliHaritha
 
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...ZTE
 
chaitra-1.pptx fake news detection using machine learning
chaitra-1.pptx  fake news detection using machine learningchaitra-1.pptx  fake news detection using machine learning
chaitra-1.pptx fake news detection using machine learningmisbanausheenparvam
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Dr.Costas Sachpazis
 

Recently uploaded (20)

HARMONY IN THE HUMAN BEING - Unit-II UHV-2
HARMONY IN THE HUMAN BEING - Unit-II UHV-2HARMONY IN THE HUMAN BEING - Unit-II UHV-2
HARMONY IN THE HUMAN BEING - Unit-II UHV-2
 
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
 
young call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Service
young call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Serviceyoung call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Service
young call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Service
 
microprocessor 8085 and its interfacing
microprocessor 8085  and its interfacingmicroprocessor 8085  and its interfacing
microprocessor 8085 and its interfacing
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
 
Oxy acetylene welding presentation note.
Oxy acetylene welding presentation note.Oxy acetylene welding presentation note.
Oxy acetylene welding presentation note.
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
 
Sachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective IntroductionSachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
 
Current Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCLCurrent Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCL
 
SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )
 
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
 
Heart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptxHeart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptx
 
Call Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile serviceCall Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile service
 
Application of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptxApplication of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptx
 
power system scada applications and uses
power system scada applications and usespower system scada applications and uses
power system scada applications and uses
 
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
 
chaitra-1.pptx fake news detection using machine learning
chaitra-1.pptx  fake news detection using machine learningchaitra-1.pptx  fake news detection using machine learning
chaitra-1.pptx fake news detection using machine learning
 
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
 

Dienhathe.com semiconductor fuses

  • 1. 2/1 2 Semiconductor Fuses General Data 2/2 Product overview LV HRC SITOR Fuse Links 2/4 Application information 2/13 Rated voltage 500 V AC 2/15 Rated voltage 600 V AC 2/17 Rated voltage 660 V AC 2/19 Rated voltage: 690 V AC/ 700 V DC 2/22 Rated voltage 690 V AC, operational class gS 2/27 Rated voltage 690 V AC, operational class gR 2/33 Rated voltage 800 V AC 2/35 Rated voltage 1000 V AC 2/41 Rated voltage 1500 V AC 2/44 Rated voltage 2000 V AC 2/46 Rated voltage 2500 V AC 2/48 Configuration Aids SITOR Fuse Links for Special Applications 2/50 For rectifiers in electrolysis systems 2/54 For SITOR thyristor sets 2/57 For railway supply rectifiers 2/59 Configuration Aids SITOR Cylindrical Fuse Links 2/60 SITOR cylindrical fuse links SILIZED Fuse Links 2/73 NEOZED fuse links SILIZED 2/75 DIAZED fuse links SILIZED 2/77 Configuration Aids Notes on Dimensioning 2/78 Technical explanations 2/86 Specifying the rated current 2/89 Terms 2/90 Characteristic curves www.dienhathe.xyz www.dienhathe.vn
  • 2. Semiconductor Fuses General Data Product overview 2/2 Siemens ET B1 T · 2007 ■Overview LV HRC SITOR fuse links • Rated voltage Un to 2500 V AC, 700 V DC • Rated current In 16 ... 1000 A • Operational class: aR, gR, gS • Sizes 000 to 3 • Range of connection types: - for mounting in LV HRC fuse bases - with bolt-on links, mounting dimensions 80 ... 260 mm - with bolt-on links, with 2 oblong slots - with M12 screw connection For rectifiers in electrolysis systems • Rated voltage Un 600 ... 1000 V AC • Rated current In 350 ... 1250 A • Operational class: aR, gR For SITOR thyristor sets • Rated voltage Un 800/1000 V AC • Rated current In 50 ... 710 A • Operational class: aR, gR For railway supply rectifiers • Rated voltage Un 680 V AC • Rated current In 250/350 A • Operational class: aR www.dienhathe.xyz www.dienhathe.vn
  • 3. Semiconductor Fuses General Data Product overview 2/3Siemens ET B1 T · 2007 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 SITOR cylindrical fuse links • Rated voltage Un 600/690 V AC, 400/700 V AC • Rated current In 1 ... 100 A • Operational class: aR • Sizes 10 mm x 38 mm, 14 mm x 51 mm and 22 mm x 58 mm Accessories for SITOR cylindrical fuse links • Fuse holders/fuse switch disconnectors/fuse disconnectors for cylindrical fuse links 10 x 38, 14 x 51, 22 x 58 • Fuse bases for cylindrical fuse links 10 x 38, 14 x 51, 22 x 58 NEOZED fuse links SILIZED • Rated voltage Un 400 V AC, 250 V DC • Rated current In 10 ... 63 A • Sizes D01 and D02 • Operational class: gR DIAZED fuse links SILIZED • Rated voltage Un 500 V AC, 500 V DC • Rated current In 16 ... 100 A • Operational class: gR • Super quick www.dienhathe.xyz www.dienhathe.vn
  • 4. Semiconductor Fuses LV HRC SITOR Fuse Links Application information 2/4 Siemens ET B1 T · 2007 ■Benefits Used in conjunction with the new 3NE1 ...–2 fuse range, the 3KL switch disconnectors with fuses have been awarded UL approval. ■Application Characteristics SITOR fuse links protect converter equipment against short-circuits. The power semiconductors used in these devices (diodes, thyristors, GTOs and others) require high-speed elements for protection due to their low thermal capacity. SITOR fuse links (super quick fuse links for semiconductor protection) are ideal for these types of application. The following types of short-circuit faults can occur: • Internal short-circuit: a faulty semiconductor device causes a short circuit within the power converter. • External short-circuit: a fault in the load causes a short circuit on the output side of the power converter. • Shoot-throughs: In the event of a failure of the chassis converter control system during inverter operation (commutation failure), the converter con- nection forms a short-circuit type connection between the DC and AC power supply system. Fuse links can be arranged in a number of ways within the converter connection. A distinction is made between phase fuses in three- phase current incoming feeders and, if applicable, DC fuses and arm fuses in the arms of the converter connections (see adjacent graphs). In the case of center tap connections, fuse links can only be arranged as phase fuses in three-phase current incoming feeders. When using SITOR fuse links of operational class aR, the overload protection of converter equipment, up to approx. 3.5 times the rated current of the fuse link, is taken from conventional protective devices (for example, thermal-delayed overload relays) or, in the case of controlled power converters, from the current limiter (exception: full range fuses). As semiconductor protection, SITOR fuse links of the3NE1 ...-0 series with gS operational class are also suitable for the overload and short-circuit protection of cables, lines and busbars. All other dual-function fuses of the SITOR series have a gR characteristic. Overload protection is ensured as long as the rated current of the SI- TOR fuse links of the 3NE1 ...-0 series is selected as In ≤Iz (DIN VDE 0100 Part 430). The rules of DIN VDE 0100 Part 430 must be applied when rating short-circuit protection for cables, lines and busbars. Configuration options I2_10898 Three-phase bidirectional connection W3 with phase fuses with arm fuses I2_10893 I2_10894 ( ) ( ) Six-pulse bridge circuit B6 with phase fuses Six-pulse bridge circuit B6 with phase fuses and DC fuse (reversible connection) I2_10895 I2_10896 Six-pulse bridge circuit B6 with phase fuses and DC fuse (switching for converter) Six-pulse bridge circuit B6 with arm fuses I2_10897 ( ) ( ) Six-pulse bridge circuit B6 with arm fuses (reversible connection) www.dienhathe.xyz www.dienhathe.vn
  • 5. Semiconductor Fuses LV HRC SITOR Fuse Links Application information 2/5Siemens ET B1 T · 2007 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 Use in switch disconnectors When using SITOR semiconductor fuses in 3KL and 3KM switch dis- connectors with fuses and 3NP fuse switch disconnectors, the rated current of the fuse must sometimes be reduced due to the higher power dissipation compared to LV HRC fuses for line protection. Sometimes when using SITOR semiconductor fuses in switch dis- connectors, the currents designated can be higher than the rated currents of the switches. These higher currents only apply when us- ing SITOR switch disconnectors with semiconductor fuses and can- not be used when using switch disconnectors with standard LV HRC fuses. You will find further details in the following selection table. When using SITOR semiconductor fuses of the 3NC24, 3NC84, 3NE33 and 3NE43 series, the standard switching capacity of the fuse must not be used as the blades of these fuses (in contrast to LV HRC fuses) are slit. Occasional switching of currents up to the rated current of the fuses is permissible. Due to the mechanical strain on the comparatively long fuse blade, SITOR semiconductor fuses of the 3NE41 series may only be occa- sionally switched, and only without load. If only switching without load is permissible, this must be clearly stated on the switch itself. The use of SITOR semiconductor fuses > 63 A for overload protec- tion is not permitted – even if gR fuses are used (exception: 3NE1). The operational voltage is limited by the rated voltage of the switch disconnector or the fuse. If switching without load, the limit value is the rated insulation voltage of the switch disconnector. The 3NE1 "double protection fuses" can be used as full range fuses (gS) for semiconductor and line protection. Due to the dimensions of the SITOR semiconductor fuses, only the fuses shown in the following selection and ordering data can be used with 3KL and 3KM switch disconnectors with fuses and 3NP fuse switch disconnectors. www.dienhathe.xyz www.dienhathe.vn
  • 6. Semiconductor Fuses LV HRC SITOR Fuse Links Application information 2/6 Siemens ET B1 T · 2007 Load rating of fuse links with SITOR LV HRC fuse bases Un = rated voltage BG = size In = rated current WL = varying load factor Ømin Cu = required conductor cross-section Cu Imax = maximum permissible current IWL = maximum permissible current with varying load SITOR fuse links Ømin Cu LV HRC fuse bases Order No. Un Operational class BG In WL Order No. BG Imax IWL V AC A mm2 A A 3NC2 4 3NC2 423-3 500 gR 3 150 0.95 70 3NH3 430 3 150 143 3NC2 425-3 500 gR 3 200 0.95 95 3 190 181 3NC2 427-3 500 gR 3 250 0.95 120 3 240 228 3NC2 428-3 500 gR 3 300 0.95 185 3 285 271 3NC2 431-3 500 gR 3 350 0.95 240 3 330 314 3NC2 432-3 500 aR 3 400 0.95 240 3 400 380 3NC8 4 3NC8 423-3 660 gR 3 150 0.85 70 3NH3 430 3 135 115 3NC8 425-3 660 gR 3 200 0.85 95 3 180 153 3NC8 427-3 660 gR 3 250 0.85 120 3 250 213 3NC8 431-3 660 gR 3 350 0.85 240 3 315 268 3NC8 434-3 660 gR 3 500 0.85 2 x 150 3 450 383 3NC8 444-3 600 aR 3 1000 0.95 2 x (60 x 6) 3 800 800 3NE1 0 3NE1 020-2 690 gR 00 80 1.0 25 3NH3 030/ 3NH4 030 00 80 80 3NE1 021-0 690 gS 00 100 1.0 35 00 100 100 3NE1 021-2 690 gR 00 100 1.0 35 00 100 100 3NE1 022-0 690 gS 00 125 1.0 50 00 125 125 3NE1 022-2 690 gR 00 125 1.0 50 00 125 125 3NE1 2 3NE1 224-0 690 gS 1 160 1.0 70 3NH3 230/ 3NH4 230 1 160 160 3NE1 224-2 690 gR 1 160 1.0 70 1 160 160 3NE1 225-0 690 gS 1 200 1.0 95 1 200 200 3NE1 225-2 690 gR 1 200 1.0 95 1 200 200 3NE1 227-0 690 gS 1 250 1.0 120 1 250 250 3NE1 227-2 690 gR 1 250 1.0 120 1 250 250 3NE1 230-0 690 gS 1 315 1.0 2 x 70 3NH3 330 2 315 315 3NE1 230-2 690 gR 1 315 1.0 2 x 70 2 315 315 3NE1 3 3NE1 331-0 690 gS 2 350 1.0 2 x 95 3NH3 330 2 350 350 3NE1 331-2 690 gR 2 350 1.0 2 x 95 2 350 350 3NE1 332-0 690 gS 2 400 1.0 2 x 95 2 400 400 3NE1 333-0 690 gS 2 450 1.0 2 x 120 3NH3 430 3 450 450 3NE1 333-2 690 gR 2 450 1.0 2 x 120 3 450 450 3NE1 334-0 690 gS 2 500 1.0 2 x 120 3 500 500 3NE1 334-2 690 gR 2 500 1.0 2 x 120 3 500 500 3NE1 4 3NE1 435-0 690 gS 3 560 1.0 2 x 150 3NH3 430 3 560 560 3NE1 435-2 690 gR 3 560 1.0 2 x 150 3 560 560 3NE1 436-0 690 gS 3 630 1.0 2 x 185 3 630 630 3NE1 436-2 690 gR 3 630 1.0 2 x 185 3 630 630 3NE1 437-0 690 gS 3 710 1.0 2 x (40 x 5) 3 710 690 3NE1 437-1 600 gR 3 710 1.0 2 x (40 x 5) 3 690 690 3NE1 437-2 690 gR 3 710 1.0 2 x (40 x 5) 3 710 710 3NE1 438-0 690 gS 3 800 1.0 2 x (50 x 5) 3 800 750 3NE1 438-1 600 gR 3 800 1.0 2 x (50 x 5) 3 750 750 3NE1 438-2 690 gR 3 800 1.0 2 x (50 x 5) 3 800 800 3NE1 447-2 690 gR 3 670 1.0 2 x (40 x 5) 3 670 670 3NE1 448-2 690 gR 3 850 1.0 2 x (40 x 8) 3 850 850 www.dienhathe.xyz www.dienhathe.vn
  • 7. Semiconductor Fuses LV HRC SITOR Fuse Links Application information 2/7Siemens ET B1 T · 2007 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 Un = rated voltage BG = size In = rated current WL = varying load factor Ømin Cu = required conductor cross-section Cu Imax = maximum permissible current IWL = maximum permissible current with varying load SITOR fuse links Ømin Cu LV HRC fuse bases Order No. Un Operational class BG In WL Order No. BG Imax IWL V AC A mm2 A A 3NE1 8 3NE1 813-0 690 gS 000 16 1.0 1.5 3NH3 030/ 3NH4 030 00 16 16 3NE1 814-0 690 gS 000 20 1.0 2.5 00 20 20 3NE1 815-0 690 gS 000 25 1.0 4 00 25 25 3NE1 803-0 690 gS 000 35 1.0 6 00 35 35 3NE1 802-0 690 gS 000 40 1.0 10 00 40 40 3NE1 817-0 690 gS 000 50 1.0 10 00 50 50 3NE1 818-0 690 gS 000 63 1.0 16 00 63 63 3NE1 820-0 690 gS 000 80 1.0 25 00 80 80 3NE3 3NE3 221 1000 aR 1 100 0.95 35 3NH3 230/ 3NH4 230 1 100 95 3NE3 222 1000 aR 1 125 0.95 50 1 125 119 3NE3 224 1000 aR 1 160 1.0 70 1 160 160 3NE3 225 1000 aR 1 200 1.0 95 1 200 200 3NE3 227 1000 aR 1 250 1.0 120 1 250 250 3NE3 230-0B 1000 aR 1 315 0.95 185 3NH3 330 2 305 290 3NE3 231 1000 aR 1 350 0.95 240 2 335 318 3NE3 232-0B 1000 aR 1 400 0.90 240 2 380 342 3NE3 233 1000 aR 1 450 0.90 2 x 150 2 425 383 3NE3 332-0B 1000 aR 2 400 1.0 240 3NH3 430 3 400 400 3NE3 333 1000 aR 2 450 1.0 2 x 150 3 450 450 3NE3 334-0B 1000 aR 2 500 1.0 2 x 150 3 500 500 3NE3 335 1000 aR 2 560 1.0 2 x 185 3 560 560 3NE3 336 1000 aR 2 630 1.0 2 x 185 3 630 630 3NE3 337-8 900 aR 2 710 1.0 2 x 200 3 680 680 3NE3 338-8 800 aR 2 800 0.95 2 x 200 3 700 665 3NE3 340-8 690 aR 2 900 0.95 2 x 200 3 750 713 3NE4 3NE4 101 1000 gR 0 32 0.85 6 3NH3 120/ 3NH4 230 0/1 32 27 3NE4 102 1000 gR 0 40 0.85 10 0/1 40 34 3NE4 117 1000 gR 0 50 0.85 10 0/1 50 43 3NE4 118 1000 aR 0 63 0.85 16 0/1 63 54 3NE4 120 1000 aR 0 80 0.85 25 0/1 80 68 3NE4 121 1000 aR 0 100 0.85 35 0/1 100 85 3NE4 122 1000 aR 0 125 0.85 50 0/1 125 106 3NE4 124 1000 aR 0 160 0.85 70 0/1 160 136 3NE4 327-0B 800 aR 2 250 0.85 120 3NH3 330 2 240 204 3NE4 330-0B 800 aR 2 315 0.85 240 2 300 255 3NE4 333-0B 800 aR 2 450 0.85 2 x (30 x 5) 3NH3 430 3 425 361 3NE4 334-0B 800 aR 2 500 0.85 2 x (30 x 5) 3 475 404 3NE4 337 800 aR 2 710 0.95 2 x (40 x 5) 3 630 599 3NE8 3NE8 015-1 690 gR 00 25 0.95 4 3NH3 030/ 3NH4 030 00 25 24 3NE8 003-1 690 gR 00 35 0.95 6 00 35 33 3NE8 017-1 690 gR 00 50 0.90 10 00 50 45 3NE8 018-1 690 gR 00 63 0.95 16 00 63 60 3NE8 020-1 690 aR 00 80 0.95 25 00 80 76 3NE8 021-1 690 aR 00 100 0.95 35 3NH3 030/ 3NH4 030 00 100 95 3NE8 022-1 690 aR 00 125 0.95 50 00 125 119 3NE8 024-1 690 aR 00 160 0.95 70 00 160 152 www.dienhathe.xyz www.dienhathe.vn
  • 8. Semiconductor Fuses LV HRC SITOR Fuse Links Application information 2/8 Siemens ET B1 T · 2007 Load rating of fuse links with SITOR 3NP LV HRC fuse switch disconnectors Un = rated voltage BG = size In = rated current WL = varying load factor Ømin Cu = required conductor cross-section Cu Imax = maximum permissible current IWL = maximum permissible current with varying load SITOR fuse links Ø min Cu 3NP LV HRC fuse switch disconnectors Add-on units Busbar devices Order No. Un BG In WL Order No. BG Imax IWL Order No. BG Imax IWL Order No. BG Imax IWL Order No. BG Imax IWL V AC A mm2 A A A A 3NC2 4 3NC2 423-3 500 3 150 0.95 70 3NP54 3 145 125 3NP44 70 3 140 120 3NP44 76 3 140 120 -- -- -- -- 3NC2 425-3 500 3 200 0.95 95 3 180 165 3 175 160 3 175 160 -- -- -- 3NC2 427-3 500 3 250 0.95 120 3 225 205 3 220 200 3 215 195 -- -- -- 3NC2 428-3 500 3 300 0.95 185 3 255 240 3 250 235 3 245 230 -- -- -- 3NC2 431-3 500 3 350 0.95 240 3 330 295 3 320 290 3 315 285 -- -- -- 3NC2 432-3 500 3 400 0.95 240 3 400 380 3 370 370 3 360 360 -- -- -- 3NC8 4 3NC8 423-3 660 3 150 0.85 70 3NP54 3 135 125 3NP44 70 3 120 120 3NP44 76 3 120 120 -- -- -- -- 3NC8 425-3 660 3 200 0.85 95 3 180 165 3 160 160 3 155 155 -- -- -- 3NC8 427-3 660 3 250 0.85 120 3 225 205 3 200 200 3 195 195 -- -- -- 3NC8 431-3 660 3 350 0.85 240 3 300 275 3 270 270 3 260 260 -- -- -- 3NC8 434-3 660 3 500 0.85 2 x 150 3 425 400 3 385 385 3 375 375 -- -- -- 3NC8 444-3 600 3 1000 0.95 2 x (60 x 6) 3NP54 3 800 800 -- -- -- -- 3NP44 76 3 400 400 -- -- -- -- 3NE1 02 3NE1 020-2 690 00 80 1.0 25 3NP50 00 80 80 3NP40 70 00 80 80 3NP40 76 00 80 80 -- -- -- -- 3NE1 021-0 690 00 100 1.0 35 00 100 100 00 100 100 00 100 100 -- -- -- 3NE1 021-2 690 00 100 1.0 35 00 98 101 00 98 98 00 98 98 -- -- -- 3NE1 022-0 690 00 125 1.0 125 00 125 125 00 125 125 00 125 125 -- -- -- 3NE1 022-2 690 00 125 1.0 125 00 125 125 00 120 120 00 120 120 -- -- -- 3NE1 2 3NE1 224-0 690 1 160 1.0 70 3NP52/ 3NP42 1 160 160 3NP53/ 3NP43 2 160 160 3NP42 76 1 160 160 3NP43 76 2 160 160 3NE1 224-2 690 1 160 1.0 70 1 160 160 2 160 160 1 160 160 2 160 160 3NE1 225-0 690 1 200 1.0 95 1 200 200 2 200 200 1 200 200 2 200 200 3NE1 225-2 690 1 200 1.0 95 1 200/ 190 200/ 190 2 200 200 1 190 190 2 200 200 3NE1 227-0 690 1 250 1.0 120 1 250 250 2 250 250 1 250 250 2 250 250 3NE1 227-2 690 1 250 1.0 120 1 250/ 235 250/ 235 2 250 250 1 235 235 2 250 250 3NE1 230-0 690 1 315 1.0 2x 70 3NP53/ 3NP43 2 315 315 -- -- -- -- 3NP4376 2 315 315 -- -- -- -- 3NE1 230-2 690 1 315 1.0 2x 70 3NP53 2 315 315 3NP43 70 2 315 315 2 315 315 -- -- -- 3NE1 3 3NE1 331-0 690 2 350 1.0 2x 95 3NP53/ 3NP43 2 350 350 3NP54/ 3NP44 3 350 350 3NP43 76 2 350 350 3NP44 76 3 350 350 3NE1 331-2 690 2 350 1.0 2x 95 2 350 350 3 350 350 2 350 350 3 350 350 3NE1 332-0 690 2 400 1.0 2x 95 2 400 400 3 400 400 2 400 400 3 400 400 3NE1 333-0 690 2 450 1.0 2x 120 3NP54/ 3NP44 3 450 450 -- -- -- -- 3NP44 76 3 450 450 -- -- -- -- 3NE1 333-2 690 2 450 1.0 2x 120 3NP54 3 450 450 3NP44 70 3 425 425 3 425 425 -- -- -- 3NE1 334-0 690 2 500 1.0 2x 120 3NP54/ 3NP44 3 500 500 -- 3 480 480 -- -- -- 3NE1 334-2 690 2 500 1.0 2x 120 3NP54 3 500 500 3NP44 70 3 465 465 3 450 450 -- -- -- 3NE1 4 3NE1 435-0 690 3 560 1.0 2x 150 3NP54/ 3NP44 3 560 560 -- -- -- -- 3NP44 76 3 510 510 -- -- -- -- 3NE1 435-2 690 3 560 1.0 2x 150 3NP54 3 560 560 3NP44 70 3 540 540 3 500 500 -- -- -- 3NE1 436-0 690 3 630 1.0 2x 185 3 630 630 3 620 620 3 535 535 -- -- -- 3NE1 436-2 690 3 630 1.0 2x 185 3 625 625 3 600 600 3 520 520 -- -- -- 3NE1 437-0 690 3 710 1.0 2x (40x5) 3 710 710 3 690 650 3 600 600 -- -- -- 3NE1 437-1 600 3 710 1.0 2x (40x5) 3 690 690 3 670 630 3 570 570 -- -- -- 3NE1 437-2 690 3 710 1.0 2x (40x5) 3 685 685 -- -- -- -- 3 540 540 -- -- -- 3NE1 438-0 690 3 800 1.0 2x (50x5) 3 800 800 3NP44 70 3 750 700 3 640 630 -- -- -- 3NE1 438-1 600 3 800 1.0 2x (50x5) 3 750 750 3 710 630 3 600 600 -- -- -- 3NE1 438-2 690 3 800 1.0 2x (50x5) 3 770 770 -- -- -- -- 3 580 580 -- -- -- 3NE1 447-2 690 3 670 1.0 2x (40x5) 3 655 655 -- -- -- 3 530 530 -- -- -- 3NE1 448-2 690 3 850 1.0 2x (40x8) 3 820 820 -- -- -- 3 630 630 -- -- -- www.dienhathe.xyz www.dienhathe.vn
  • 9. Semiconductor Fuses LV HRC SITOR Fuse Links Application information 2/9Siemens ET B1 T · 2007 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 Un = rated voltage BG = size In = rated current WL = varying load factor Ømin Cu = required conductor cross-section Cu Imax = maximum permissible current IWL = maximum permissible current with varying load SITOR fuse links Ø min Cu 3NP LV HRC fuse switch disconnectors Add-on units Busbar devices Order No. Un BG In WL Order No. BG Imax IWL Order No. BG Imax IWL Order No. BG Imax IWL Order No. BG Imax IWL V AC A mm2 A A A A 3NE1 8 3NE1 813-0 690 000 16 1.0 1.5 3NP35/ 3NP40 10 000 16 16 3NP50/ 3NP40 70 00 16 16 3NP40 15/ 3NP40 16 000 16 16 3NP40 75/ 3NP40 76 00 16 16 3NE1 814-0 690 000 20 1.0 2.5 000 20 20 00 20 20 000 20 20 00 20 20 3NE1 815-0 690 000 25 1.0 4 000 25 25 00 25 25 000 25 25 00 25 25 3NE1 803-0 690 000 35 1.0 6 000 35 35 00 35 35 000 35 35 00 35 35 3NE1 802-0 690 000 40 1.0 10 000 40 40 00 40 40 000 40 40 00 40 40 3NE1 817-0 690 000 50 1.0 10 000 50 50 00 50 50 000 50 50 00 50 50 3NE1 818-0 690 000 63 1.0 16 000 63 63 00 63 63 000 63 63 00 63 63 3NE1 820-0 690 000 80 1.0 25 000 80 80 00 80 80 000 80 80 00 80 80 3NE3 3NE3 221 1000 1 100 0.95 35 3NP52/ 3NP42 1 95 90 3NP53/ 3NP43 2 100 95 3NP42 76 1 95 90 3NP43 76 2 100 95 3NE3 222 1000 1 125 0.95 50 1 110 110 2 120 114 1 115 109 2 125 119 3NE3 224 1000 1 160 1.0 70 1 140 140 2 150 150 1 150 150 2 160 160 3NE3 225 1000 1 200 1.0 95 1 175 175 2 190 190 1 185 185 2 200 200 3NE3 227 1000 1 250 1.0 120 1 210 210 2 230 230 1 225 225 2 250 250 3NE3 230-0B 1000 1 315 0.95 185 3NP53 2 285 280 3NP43 70 2 270 270 3NP43 76 2 285 285 -- -- -- -- 3NE3 231 1000 1 350 0.95 240 2 310 300 2 290 290 2 310 310 -- -- -- 3NE3 232-0B 1000 1 400 0.90 240 2 330 320 2 310 310 2 330 330 -- -- -- 3NE3 233 1000 1 450 0.90 2x 150 2 360 340 2 330 330 2 360 360 -- -- -- 3NE3 332-0B 1000 2 400 1.0 240 3NP54 3 360 345 3NP44 70 3 345 345 3NP44 76 3 340 340 -- -- -- -- 3NE3 333 1000 2 450 1.0 2x 150 3 400 385 3 385 385 3 370 370 -- -- -- 3NE3 334-0B 1000 2 500 1.0 2x 150 3 450 450 3 430 430 3 410 410 -- -- -- 3NE3 335 1000 2 560 1.0 2x 185 3 510 510 3 490 490 3 450 450 -- -- -- 3NE3 336 1000 2 630 1.0 2x 185 3 580 580 3 560 560 3 500 500 -- -- -- 3NE3 337-8 900 2 710 1.0 2x 200 3 630 630 3 590 590 3 510 510 -- -- -- 3NE3 338-8 800 2 800 0.95 2x 200 3 630 630 3 605 605 3 520 520 -- -- -- 3NE3 340-8 690 2 900 0.95 2x 200 3 630 630 3 630 630 3 530 530 -- -- -- 3NE4 3NE4 101 1000 0 32 0.85 6 3NP52 1 32 27 3NP42 70 1 32 27 3NP42 76 1 32 27 -- -- -- -- 3NE4 102 1000 0 40 0.85 10 1 40 34 1 38 32 1 38 32 -- -- -- 3NE4 117 1000 0 50 0.85 10 1 50 43 1 45 40 1 45 40 -- -- -- 3NE4 118 1000 0 63 0.85 16 1 63 54 1 59 50 1 59 50 -- -- -- 3NE4 120 1000 0 80 0.85 25 1 80 68 1 76 65 1 76 65 -- -- -- 3NE4 121 1000 0 100 0.85 35 1 95 81 1 90 78 1 90 78 -- -- -- 3NE4 122 1000 0 125 0.85 50 1 120 102 1 115 98 1 115 98 -- -- -- 3NE4 124 1000 0 160 0.85 70 1 150 128 1 144 125 1 144 125 -- -- -- 3NE4 327-0B 800 2 250 0.85 120 3NP53/ 3NP54 2/3 210/ 220 205/ 210 3NP44 70 3 205 200 3NP44 76 3 235 210 -- -- -- -- 3NE4 330-0B 800 2 315 0.85 240 2/3 270/ 285 255/ 265 3 260 250 3 280 260 -- -- -- 3NE4 333-0B 800 2 450 0.85 2x (30x5) 2/3 400/ 420 370/ 380 3 375 360 3 390 370 -- -- -- 3NE4 334-0B 800 2 500 0.85 2x (30x5) 3NP54 3 450 400 3NP44 70 3 410 395 3NP44 76 3 415 400 -- -- -- -- 3NE4 337 800 2 710 0.95 2x (40x5) 3 600 570 3 540 540 3 480 480 -- -- -- 3NE8 3NE8 015-1 690 00 25 0.95 4 3NP40 70/ 3NP50 00 25 24 -- -- -- -- 3NP40 75/ 3NP40 76 00 25 24 -- -- -- -- 3NE8 003-1 690 00 35 0.95 6 00 33 31 -- -- -- 00 33 31 -- -- -- 3NE8 017-1 690 00 50 0.90 10 00 45 41 -- -- -- 00 45 41 -- -- -- 3NE8 018-1 690 00 63 0.95 16 00 54 51 -- -- -- 00 53 50 -- -- -- 3NE8 020-1 690 00 80 0.95 25 00 68 65 -- -- -- 00 68 65 -- -- -- 3NE8 021-1 690 00 100 0.95 35 3NP50/ 3NP40 70 00 89 85 -- -- -- -- 3NP40 75/ 3NP40 76 00 85 81 -- -- -- -- 3NE8 022-1 690 00 125 0.95 50 00 106 101 -- -- -- 00 100 95 -- -- -- 3NE8 024-1 690 00 160 0.95 70 00 130 124 -- -- -- 00 125 120 -- -- -- www.dienhathe.xyz www.dienhathe.vn
  • 10. Semiconductor Fuses LV HRC SITOR Fuse Links Application information 2/10 Siemens ET B1 T · 2007 Load rating of fuse links with SITOR 3KL/3KM LV HRC fuse switch disconnectors Un = rated voltage BG = size In = rated current WL = varying load factor Ømin Cu = required conductor cross-section Cu Imax = maximum permissible current IWL = maximum permissible current with varying load SITOR fuse links Ø min Cu 3KL/3KM switch disconnectors with fuses 3KL add-on devices 3KM busbar devices Order No. Un BG In WL Order No. BG Imax IWL Order No. BG Imax IWL Order No. BG Imax IWL Order No. BG Imax IWL V AC A mm2 A A A A 3NC2 4 3NC2 423-3 500 3 150 0.95 70 3KL61 3 145 138 3KL62 3 150 143 -- -- -- -- -- -- -- -- 3NC2 425-3 500 3 200 0.95 95 3 180 171 3 190 181 -- -- -- -- -- -- 3NC2 427-3 500 3 250 0.95 120 3 225 214 3 240 228 -- -- -- -- -- -- 3NC2 428-3 500 3 300 0.95 185 3 255 242 3 270 257 -- -- -- -- -- -- 3NC2 431-3 500 3 350 0.95 240 3 330 314 3 345 328 -- -- -- -- -- -- 3NC2 432-3 500 3 400 0.95 240 3 400 380 3 400 380 -- -- -- -- -- -- 3NC8 4 3NC8 423-3 660 3 150 0.85 70 3KL61 3 135 115 3KL62 3 140 119 -- -- -- -- -- -- -- -- 3NC8 425-3 660 3 200 0.85 95 3 180 153 3 190 162 -- -- -- -- -- -- 3NC8 427-3 660 3 250 0.85 120 3 225 191 3 240 204 -- -- -- -- -- -- 3NC8 431-3 660 3 350 0.85 240 3 300 255 3 315 268 -- -- -- -- -- -- 3NC8 434-3 660 3 500 0.85 2 x 150 3 425 361 3 450 383 -- -- -- -- -- -- 3NC8 444-3 600 3 1000 0.95 2 x (60 x 6) 3 800 800 3 630 630 -- -- -- -- -- -- 3NE1 0 3NE1 020-2 690 00 80 1.0 25 3KL52 00 80 80 3KL53 00 80 80 3KM52 00 80 80 3KM53 00 80 80 3NE1 021-0 690 00 100 1.0 35 00 100 100 00 100 100 00 100 100 00 100 100 3NE1 021-2 690 00 100 1.0 35 00 100 100 00 100 100 00 100 100 00 100 100 3NE1 022-0 690 00 125 1.0 125 00 125 125 00 125 125 00 125 125 00 125 125 3NE1 022-2 690 00 125 1.0 125 00 125 125 00 125 125 00 125 125 00 125 125 3NE1 2 3NE1 224-0 690 1 160 1.0 70 3KL55 1 160 160 3KL57 2 160 160 3KM55 1 160 160 3KM57 2 160 160 3NE1 224-2 690 1 160 1.0 70 1 160 160 2 160 160 1 160 160 2 160 160 3NE1 225-0 690 1 200 1.0 95 1 200 200 2 200 200 1 200 200 2 200 200 3NE1 225-2 690 1 200 1.0 95 1 200 200 2 200 200 1 200 200 2 200 200 3NE1 227-0 690 1 250 1.0 120 1 250 250 2 250 250 1 250 250 2 250 250 3NE1 227-2 690 1 250 1.0 120 1 245 245 2 250 250 1 245 245 2 250 250 3NE1 230-0 690 1 315 1.0 2x 70 3KL57 2 315 315 -- -- -- -- 3KM57 2 315 315 -- -- -- -- 3NE1 230-2 690 1 315 1.0 2x 70 2 280 280 -- -- -- 2 280 280 -- -- -- 3NE1 3 3NE1 331-0 690 2 350 1.0 2x 95 3KL57 2 330 330 3KL61 3 350 350 3KM57 2 330 330 -- -- -- -- 3NE1 331-2 690 2 350 1.0 2x 95 2 300 300 3 350 350 2 300 300 -- -- -- 3NE1 332-0 690 2 400 1.0 2x 95 2 375 375 3 400 400 2 375 375 -- -- -- 3NE1 333-0 690 2 450 1.0 2x 120 3KL61 3 450 450 3KL62 3 450 450 2 400 400 -- -- -- 3NE1 333-2 690 2 450 1.0 2x 120 3 450 450 3 450 500 2 325 325 -- -- -- 3NE1 334-0 690 2 500 1.0 2x 120 3 500 500 3 500 500 2 400 400 -- -- -- 3NE1 334-2 690 2 500 1.0 2x 120 3 500 500 3 500 500 2 350 350 -- -- -- 3NE1 4 3NE1 435-0 690 3 560 1.0 2x 150 3KL61 3 560 560 3KL62 3 560 560 -- -- -- -- -- -- -- -- 3NE1 435-2 690 3 560 1.0 2x 150 3 560 560 3 560 560 -- -- -- -- -- -- 3NE1 436-0 690 3 630 1.0 2x 185 3 630 630 3 630 630 -- -- -- -- -- -- 3NE1 436-2 690 3 630 1.0 2x 185 3 615 615 3 630 630 -- -- -- -- -- -- 3NE1 437-0 690 3 710 1.0 2x (40x5) 3 630 630 3 710 710 -- -- -- -- -- -- 3NE1 437-1 600 3 710 1.0 2x (40x5) 3 630 630 3 710 710 -- -- -- -- -- -- 3NE1 437-2 690 3 710 1.0 2x (40x5) 3 630 630 3 700 700 -- -- -- -- -- -- 3NE1 438-0 690 3 800 1.0 2x (50x5) 3 630 630 3 800 800 -- -- -- -- -- -- 3NE1 438-1 600 3 800 1.0 2x (50x5) 3 630 630 3 800 800 -- -- -- -- -- -- 3NE1 438-2 690 3 800 1.0 2x (50x5) 3 630 630 3 760 760 -- -- -- -- -- -- 3NE1 447-2 690 3 670 1.0 2x (40x5) 3 630 630 3 670 670 -- -- -- -- -- -- 3NE1 448-2 690 3 850 1.0 2x (40x8) 3 630 630 3 790 790 -- -- -- -- -- -- www.dienhathe.xyz www.dienhathe.vn
  • 11. Semiconductor Fuses LV HRC SITOR Fuse Links Application information 2/11Siemens ET B1 T · 2007 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 Un = rated voltage BG = size In = rated current WL = varying load factor Ømin Cu = required conductor cross-section Cu Imax = maximum permissible current IWL = maximum permissible current with varying load SITOR fuse links Ø min Cu 3KL/3KM switch disconnectors with fuses 3KL... add-on devices 3KM... busbar devices Order No. Un BG In WL Order No. BG Imax IWL Order No. BG Imax IWL Order No. BG Imax IWL Order No. BG Imax IWL V AC A mm2 A A A A 3NE1 8 3NE1 813-0 690 000 16 1.0 1.5 3KL50 00 16 16 3KL52 00 16 16 3KM50 00 16 16 3KM52 00 16 16 3NE1 814-0 690 000 20 1.0 2.5 00 20 20 00 20 20 00 20 20 00 20 20 3NE1 815-0 690 000 25 1.0 4 00 25 25 00 25 25 00 25 25 00 25 25 3NE1 803-0 690 000 35 1.0 6 00 35 35 00 35 35 00 35 35 00 35 35 3NE1 802-0 690 000 40 1.0 10 00 40 40 00 40 40 00 40 40 00 40 40 3NE1 817-0 690 000 50 1.0 10 00 50 50 00 50 50 00 50 50 00 50 50 3NE1 818-0 690 000 63 1.0 16 00 63 63 00 63 63 00 63 63 00 63 63 3NE1 820-0 690 000 80 1.0 25 3KL52 00 80 80 -- -- -- -- 3KM52 00 80 80 -- -- -- -- 3NE3 3NE3 221 1000 1 100 0.95 35 3KL55 1 90 86 3KL57 2 95 90 3KM55 1 90 86 3KM57 2 95 90 3NE3 222 1000 1 125 0.95 50 1 110 105 2 115 109 1 110 105 2 115 109 3NE3 224 1000 1 160 1.0 70 1 140 140 2 150 150 1 140 140 2 150 150 3NE3 225 1000 1 200 1.0 95 1 175 175 2 180 180 1 175 175 2 180 180 3NE3 227 1000 1 250 1.0 120 1 210 210 2 220 220 1 210 210 2 220 220 3NE3 230-0B 1000 1 315 0.95 185 3KL57 2 240 228 -- -- -- -- 3KM57 2 240 228 -- -- -- -- 3NE3 231 1000 1 350 0.95 240 2 265 252 -- -- -- 2 265 252 -- -- -- 3NE3 232-0B 1000 1 400 0.90 240 2 290 261 -- -- -- 2 290 261 -- -- -- 3NE3 233 1000 1 450 0.90 2x 150 2 320 288 -- -- -- 2 320 288 -- -- -- 3NE3 332-0B 1000 2 400 1.0 240 3KL61 3 340 340 3KL62 3 360 360 3KM57 2 290 290 -- -- -- -- 3NE3 333 1000 2 450 1.0 2x 150 3 380 380 3 400 400 2 320 320 -- -- -- 3NE3 334-0B 1000 2 500 1.0 2x 150 3 440 440 3 470 470 2 360 360 -- -- -- 3NE3 335 1000 2 560 1.0 2x 185 3 500 500 3 530 530 2 400 400 -- -- -- 3NE3 336 1000 2 630 1.0 2x 185 3 540 540 3 580 580 2 400 400 -- -- -- 3NE3 337-8 900 2 710 1.0 2x 200 3 600 600 3 640 640 2 400 400 -- -- -- 3NE3 338-8 800 2 800 0.95 2x 200 3 630 630 3 720 680 2 400 400 -- -- -- 3NE3 340-8 690 2 900 0.95 2x 200 3 630 630 3 800 750 2 400 400 -- -- -- 3NE4 3NE4 101 1000 0 32 0.85 6 3KL55 1 32 27 -- -- -- -- 3KM55 1 32 27 -- -- -- -- 3NE4 102 1000 0 40 0.85 10 1 40 34 -- -- -- 1 40 34 -- -- -- 3NE4 117 1000 0 50 0.85 10 1 50 43 -- -- -- 1 50 43 -- -- -- 3NE4 118 1000 0 63 0.85 16 1 63 54 -- -- -- 1 63 54 -- -- -- 3NE4 120 1000 0 80 0.85 25 1 80 68 -- -- -- 1 80 68 -- -- -- 3NE4 121 1000 0 100 0.85 35 1 95 81 -- -- -- 1 95 81 -- -- -- 3NE4 122 1000 0 125 0.85 50 1 120 102 -- -- -- 1 120 102 -- -- -- 3NE4 124 1000 0 160 0.85 70 1 150 128 -- -- -- 1 150 128 -- -- -- 3NE4 327-0B 800 2 250 0.85 120 3KL57 2 175 149 3KL61 3 200 170 3KM57 2 175 149 -- -- -- -- 3NE4 330-0B 800 2 315 0.85 240 2 230 196 3 260 221 2 230 196 -- -- -- 3NE4 333-0B 800 2 450 0.85 2x (30x5) 2 340 289 3 370 315 2 340 289 -- -- -- 3NE4 334-0B 800 2 500 0.85 2x (30x5) 3KL61 3 425 361 3KL62 3 450 375 2 380 323 -- -- -- 3NE4 337 800 2 710 0.95 2x (40x5) 3 600 570 3 630 600 2 400 400 -- -- -- 3NE8 0 3NE8 015-1 690 00 25 0.95 4 3KL50 00 25 24 3KL52 00 25 24 3KM50 00 25 24 3KM52 00 25 24 3NE8 003-1 690 00 35 0.95 6 00 33 31 00 35 33 00 33 31 00 35 33 3NE8 017-1 690 00 50 0.90 10 00 45 41 00 50 45 00 45 41 00 50 45 3NE8 018-1 690 00 63 0.95 16 00 54 51 00 60 57 00 54 51 00 60 57 3NE8 020-1 690 00 80 0.95 25 3KL52 00 68 65 3KL53 00 68 65 3KM52 00 68 65 3KM53 00 68 65 3NE8 021-1 690 00 100 0.95 35 3KL52 00 89 85 3KL53 00 89 85 3KM52 00 89 85 3KM53 00 89 85 3NE8 022-1 690 00 125 0.95 50 00 106 101 00 106 101 00 106 101 00 106 101 3NE8 024-1 690 00 160 0.95 70 00 130 124 00 130 124 00 130 124 00 130 124 www.dienhathe.xyz www.dienhathe.vn
  • 12. Semiconductor Fuses LV HRC SITOR Fuse Links Application information 2/12 Siemens ET B1 T · 2007 Standards The SITOR fuse links comply with the following standards: • IEC 60269-4 • EN 60269-4 If noted in the selection and ordering data and characteristic curves, the SITOR fuse links also comply with the following standards and regulations: • IEC 60269-2-1 DIN VDE 0636-201 (for installation in LV HRC fuse bases according to VDE 0636/201, as well as in fuse switch disconnectors and switch disconnectors with fuses) • u The following SITOR fuse links and LV HRC fuse bases are also u recognized: • CCC The following SITOR fuse links have the Chinese certification CCC: 3NE1 0..-0 3NE1 8..-0 3NE1 2..-0 3NE3 2.. 3NE3 3.. • IEC 60269-4-1 DIN VDE 0636-401 (for screwing onto busbar). SITOR fuse links of size 1 to 3 with gauge 110 mm are also suitable for installation in LV HRC fuse bases according to IEC 60269-2-1 and in fuse switch disconnec- tors and switch disconnectors with fuses. • All SITOR fuse links with rated voltage Un ≤1000 V are CE-marked according to the low-voltage Directive 73/23/EWG. The CE mark- ing confirms conformance of the products with the requirements of the directive. ■More information Environment-friendly recycling In 1995, seven German manufacturers of LV HRC/HV HRC fuse links founded a non-profit association. LV HRC/HV HRC Recycling The objective is to provide a useful recycling option for used fuse links and determine an acceptable disposal concept that meets all the requirements of modern environment protection. Used fuse links are sorted according to product type and are accepted back without packaging for recycling, melted down and the recovered materials are fed back into the material cycle. According to the regulations, statutes and articles of the association, any surplus from the recycling process is donated to a university in order to encourage research in the area of fuse link technology. For further information, please visit our Web site at: http://www.nh-hh-recycling.de Disclaimer The products described here were developed as part of an overall plant or machine to perform safety-related functions. A complete fail- safe system usually contains sensors, evaluation units, signaling de- vices and concepts for failsafe disconnection. It is the responsibility of the manufacturer of a plant or machine to ensure the correct over- all function. Siemens AG, its branches and affiliated companies (hereafter "Siemens"), is not in a position to guarantee the function of an overall plant or machine that was not designed by Siemens. Siemens can accept no liability for recommendations, either explicit or implicit, contained in the following description. Furthermore, no warranty or liability claims above and beyond those provided for in the Siemens General Terms and Conditions can be derived from the description. Caution Fuses must always be fitted by a qualified technician. Series Registration number Reference 3NC1 0.., 3NC1 4.. 3NC2 2.., 3NE1 ... 3NE3 2.., 3NE3 3.. 3NE4 1.., 3NE8 0..-1 3NE8 7..-1 JFHR2 E167357 3NC1 038-., 3NC1 09. 3NC1 49., , 3NC2 29. IZLT2 E220063 3NH3 030, 3NH3 120 3NH3 230, 3NH3 330 3NH3 430 IZLT2 E171267 NH HH www.dienhathe.xyz www.dienhathe.vn
  • 13. Semiconductor Fuses LV HRC SITOR Fuse Links Rated voltage 500 V AC 2/13Siemens ET B1 T · 2007 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 ■Technical specifications 1) Cooling air speed 1 m/s. In the case of natural air cooling, reduction of 5 %. ■Selection and ordering data For dimensional drawings, see pages 2/48 and 2/49. 1) Cladding dimensions and grip lugs according to IEC 60269-2-1; but blade slotted according to IEC 60269-4-1. Type 3NC2 423 3NC2 423-3 3NC2 425 3NC2 425-3 3NC2 427 3NC2 427-3 3NC2 428 3NC2 428-3 3NC2 431 3NC2 431-3 3NC2 432 3NC2 432-3 Operational class (IEC 60269) gR aR Rated voltage Un V AC 500 Rated current In A 1501) 2001) 2501) 3001) 3501) 4001) Melting I2t value I2ts (tvs = 1 ms) A2 s 7000 13600 21000 28000 53000 83000 Breaking I2t value I2tA at Un A2 s 33000 64000 99000 132000 249000 390000 Temperature rise at In (body center) K 26 25 30 40 35 30 Power dissipation at In W 35 40 50 65 60 50 Varying load factor WL 0.85 Weight approx. kg 0.95 Accessories Fuse base, 1-pole 3NH3 430 Fuse puller 3NX1 011 Fuse switch disconnectors 3NP54 Switch disconnector with fuses 3KL61 30-1.B0 Size In Operational class Order No. Weight 1 unit approx. PS*/ P. unit A kg Unit(s) Rated voltage 500 V AC with bolt-on links Mounting dimensions: 110 mm 31) 150 gR 3NC2 423-3 1.063 3 200 gR 3NC2 425-3 1.057 3 250 gR 3NC2 427-3 1.066 3 300 gR 3NC2 428-3 1.078 3 350 aR 3NC2 431-3 1.056 3 400 aR 3NC2 432-3 1.062 3 Special design with 2 oblong slots 3 150 gR 3NC2 423 1.055 3 200 gR 3NC2 425 1.070 3 250 gR 3NC2 427 1.056 3 300 gR 3NC2 428 1.056 3 350 aR 3NC2 431 1.061 3 400 aR 3NC2 432 1.056 1/3 * You can order this quantity or a multiple thereof. www.dienhathe.xyz www.dienhathe.vn
  • 14. Semiconductor Fuses LV HRC SITOR Fuse Links Rated voltage 500 V AC 2/14 Siemens ET B1 T · 2007 ■Characteristic curves Series 3NC2 4.. Size: 3 Operational class: gR or aR Rated voltage: 500 V AC Rated current: 150 ... 400 A Time/current characteristics diagram Let-through characteristics (current limitation at 50 Hz) Correction factor kA for breaking I2 t value Peak arc voltage 2102 10-3 2 4 6 10-2 64 1038 2 64 1048 2 4 6 10-1 2 4 6 100 2 4 6 101 2 4 6 102 2 4 6 103 2 4 6 104 I2_10809 4 0 0 A3 0 0 A2 0 0 A 3 5 0 A2 5 0 A1 5 0 A vs p [ A ] [s]Virtualpre-arcingtime Prospective short-circuit current p c 103 2 64 1048 10 2 4 6 10 I2_10812 4 3 2 64 1058 2 2 4 6 105 [A] [ A ] 1 5 0 A 2 0 0 A 2 5 0 A 3 0 0 A 3 5 0 A 4 0 0 A Prospective short-circuit current Unlimited peak values: DC component 50 % DC component 0 % Let-throughcurrent 0 100 200 300 400 500 600 1 A w [ V ]Recovery voltage Correctionfactor 0.8 0.6 0.4 0.2 0 200 400 600 800 400 800 1200 s w 1400 1000 600 200 0 I2_10811 [ V ] [V] Recovery voltage PeakarcvoltageÛ www.dienhathe.xyz www.dienhathe.vn
  • 15. Semiconductor Fuses LV HRC SITOR Fuse Links Rated voltage 600 V AC 2/15Siemens ET B1 T · 2007 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 ■Technical specifications 1) Temperature rise and power dissipation for operation in LV HRC fuse base. ■Selection and ordering data For dimensional drawings, see pages 2/48 and 2/49. Type 3NE1 437-1 3NE1 438-1 Operational class (IEC 60269) gR Rated voltage Un V AC 600 Rated current In A 710 800 Melting I2t value I2ts (tvs = 1 ms) A2 s 321000 437000 Breaking I2t value I2tA at Un A2 s 2460000 3350000 Temperature rise at In (body center)1) K 85 95 Power dissipation at In 1) W 65 72 Varying load factor WL 1.0 Certification according to UL 248-13 Weight approx. kg 0.95 Accessories Fuse base, 1-pole 3NH3 430 Fuse puller 3NX1 011 Fuse switch disconnectors 3NP54 Switch disconnector with fuses 3KL62 30 Size In Operational class Order No. Weight 1 unit approx. PS*/ P. unit A kg Unit(s) Rated voltage 600 V AC for mounting in LV HRC fuse bases 3 710 gR 3NE1 437-1 1.120 3 800 gR 3NE1 438-1 1.113 3 * You can order this quantity or a multiple thereof. www.dienhathe.xyz www.dienhathe.vn
  • 16. Semiconductor Fuses LV HRC SITOR Fuse Links Rated voltage 600 V AC 2/16 Siemens ET B1 T · 2007 ■Characteristic curves Series 3NE1 437-1, 3NE1 438-1 Size: 3 Operational class: gR Rated voltage: 600 V AC Rated current: 710 ... 800 A Time/current characteristics diagram Let-through characteristics (current limitation at 50 Hz) Correction factor kA for breaking I2 t value Peak arc voltage p vs 2102 10-3 2 4 6 10-2 64 1038 2 64 1048 2 4 2 4 6 10-1 2 4 6 100 2 4 6 101 2 4 6 102 2 4 6 103 2 4 6 104 I2_10835 6 1058 7 1 0 A 8 0 0 A [ A ] [s]Virtualpre-arcingtime Prospective short-circuit current p c 103 2 64 1048 10 2 4 6 10 I2_10838 5 4 2 64 1058 2 [A] [ A ] 7 1 0 A 8 0 0 A Prospective short-circuit current Unlimited peak values: DC component 50 % DC component 0 % Let-throughcurrent 0 100 200 300 400 500 600 1 700 800 A w [ V ] Correctionfactor Recovery voltage 0.2 0.4 0.6 0.8 200 400 500 600 700 800100 s w 300 1400 1200 1000 800 600 400 200 0 [ V ] [V] 0 Peakarcvoltage Recovery voltage Û www.dienhathe.xyz www.dienhathe.vn
  • 17. Semiconductor Fuses LV HRC SITOR Fuse Links Rated voltage 660 V AC 2/17Siemens ET B1 T · 2007 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 ■Technical specifications 1) Cooling air speed 1 m/s. In the case of natural air cooling, reduction of 5 %. ■Selection and ordering data For dimensional drawings, see pages 2/48 and 2/49. 1) Cladding dimensions and grip lugs according to IEC 60269-2-1; but blade slotted according to IEC 602269-4-1. Type 3NC8 423 3NC8 423-3 3NC8 425 3NC8 425-3 3NC8 427 3NC8 427-3 3NC8 431 3NC8 431-3 3NC8 434 3NC8 434-3 3NC8 444-3 Operational class (IEC 60269) gR aR Rated voltage Un V AC 660 600 Rated current In A 1501) 2001) 250 3501) 5001) 10001) Melting I2t value I2ts (tvs = 1 ms) A2 s 1100 2400 4400 11000 28000 400000 Breaking I2t value I2tA at Un A2 s 17600 38400 70400 176000 448000 2480000 Temperature rise at In (body center) K 33 46 95 65 75 110 Power dissipation at In W 40 55 72 95 130 140 Varying load factor WL 0.85 0.9 Weight approx. kg 0.95 Accessories Fuse base, 1-pole 3NH3 430 – Fuse puller 3NX1 011 Fuse switch disconnectors 3NP54 – Switch disconnector with fuses 3KL61 30-1AB0 – Size In Opera- tional class Order No. Weight 1 unit approx. PS*/ P. unit A kg Unit(s) Rated voltage 660 V AC with bolt-on links Mounting dimensions: 110 mm 31) 150 gR 3NC8 423-3 1.062 3 200 gR 3NC8 425-3 1.063 3 250 gR 3NC8 427-3 1.069 3 350 gR 3NC8 431-3 1.072 3 500 gR 3NC8 434-3 1.069 3 1000 aR 3NC8 444-3 1.085 3 Special design with 2 oblong slots 3 150 gR 3NC8 423 1.044 3 200 gR 3NC8 425 1.060 3 250 gR 3NC8 427 1.074 3 350 gR 3NC8 431 1.065 3 500 gR 3NC8 434 1.095 3 * You can order this quantity or a multiple thereof. www.dienhathe.xyz www.dienhathe.vn
  • 18. Semiconductor Fuses LV HRC SITOR Fuse Links Rated voltage 660 V AC 2/18 Siemens ET B1 T · 2007 ■Characteristic curves Series 3NC8 4.. Size: 3 Operational class: gR or aR Rated voltage: 660 V AC Rated current: 150 ... 1000 A Time/current characteristics diagram Let-through characteristics (current limitation at 50 Hz) Correction factor kA for breaking I2 t value Peak arc voltage p vs 2102 10-3 2 4 6 10-2 64 1038 2 64 1048 2 4 2 4 6 10-1 2 4 6 100 2 4 6 101 2 4 6 102 2 4 6 103 2 4 6 104 I2_10821 6 1058 5 0 0 A 3 5 0 A 2 5 0 A 2 0 0 A 1 0 0 0 A 1 5 0 A [ A ] [s]Virtualpre-arcingtime Prospective short-circuit current 102 2 64 108 10 2 4 6 2 4 6 4 c p [A] [A] 105 103 3 2 64 108 4 2 64 108 5 2 4 1 5 0 A I2_10824 2 0 0 A 2 5 0 A 3 0 0 A 3 5 0 A 4 0 0 A Let-throughcurrent Prospective short-circuit current Unlimited peak values: DC component 50 % DC component 0 % 0 100 200 300 400 500 600 1 700 800 A w 1 0 0 0 A 1 5 0 . . . 5 0 0 A [ V ] Correctionfactor Recovery voltage 0.2 0.4 0.6 0.8 0 200 400 600 800 400 800 1200 s w 1400 1000 600 200 0 I2_10823 1 0 0 0 A 1 5 0 . . . 5 0 0 A [ V ] [V] Recovery voltage PeakarcvoltageÛ www.dienhathe.xyz www.dienhathe.vn
  • 19. Semiconductor Fuses LV HRC SITOR Fuse Links Rated voltage 690 V AC/700 V DC 2/19Siemens ET B1 T · 2007 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 ■Technical specifications ■Selection and ordering data For dimensional drawings, see pages 2/48 and 2/49. Type 3NE8 714-1 3NE8 715-1 3NE8 701-1 3NE8 702-1 3NE8 717-1 3NE8 718-1 Operational class (IEC 60269) gR aR Rated voltage Un V 690 V AC/700 V DC Rated current In A 20 25 32 40 50 63 Melting I2t value I2ts (tvs = 1 ms) A2 s 12 19 40 69 115 215 Breaking I2t value I2tA at Un A2 s 83 140 285 490 815 1550 Temperature rise at In (body center) K 40 45 55 60 70 Power dissipation at In W 7 9 10 12 15 16 Varying load factor WL 0.9 0.95 Certification according to UL 248-13 Weight approx. kg 0.13 Type 3NE8 720-1 3NE8 721-1 3NE8 722-1 3NE8 724-1 3NE8 725-1 3NE8 727-1 3NE8 731-1 Operational class (IEC 60269) aR Rated voltage Un V 690 V AC/700 V DC Rated current In A 80 100 125 160 200 250 315 Melting I2 t value I2 ts (tvs = 1 ms) A2 s 380 695 1250 2350 4200 7750 12000 Breaking I2 t value I2 tA at Un A2 s 2700 4950 9100 17000 30000 55000 85500 Temperature rise at In (body center) K 80 75 80 100 120 125 150 Power dissipation at In W 18 19 23 31 36 42 54 Varying load factor WL 0.9 0.95 0.9 0.85 Certification according to UL 248-13 Weight approx. kg 0.13 Size In Operational class Order No. Weight 1 unit approx. PS*/ P. unit A kg Unit(s) Rated voltage 690 V AC/700 V DC with bolt-on links Mounting dimensions: 80 mm 000 20 gR 3NE8 714-1 0.130 10 25 gR 3NE8 715-1 0.130 10 32 gR 3NE8 701-1 0.131 10 40 gR 3NE8 702-1 0.131 10 50 gR 3NE8 717-1 0.132 10 63 aR 3NE8 718-1 0.132 10 80 aR 3NE8 720-1 0.131 10 100 aR 3NE8 721-1 0.130 10 125 aR 3NE8 722-1 0.131 10 160 aR 3NE8 724-1 0.132 10 200 aR 3NE8 725-1 0.130 10 250 aR 3NE8 727-1 0.133 10 315 aR 3NE8 731-1 0.134 10 * You can order this quantity or a multiple thereof. www.dienhathe.xyz www.dienhathe.vn
  • 20. Semiconductor Fuses LV HRC SITOR Fuse Links Rated voltage 690 V AC/700 V DC 2/20 Siemens ET B1 T · 2007 ■Characteristic curves Series 3NE8 71.-1, 3NE8 70.-1 Size: 000 Operational class: gR or aR Rated voltage: AC 690 V/ 700 V DC Rated current: 20 ... 63 A Time/current characteristics diagram Let-through characteristics (current limitation at 50 Hz) Correction factor kA for breaking I2 t value Peak arc voltage 2101 10-3 2 4 6 10-2 64 1028 2 64 1038 2 4 6 10-1 2 4 6 100 2 4 6 101 2 4 6 102 2 4 6 103 2 4 6 104 I2_10813 5 0 A3 2 A2 0 A 6 3 A4 0 A2 5 A vs p [ A ] [s]Virtualpre-arcingtime Prospective short-circuit current 102 2 64 108 10 2 4 6 2 4 6 3 c p [A] [A] 104 102 3 2 64 108 4 2 64 108 5 2 4 2 0 A I2_10816 2 5 A 3 2 A 4 0 A 5 0 A 6 3 A Let-throughcurrent Prospective short-circuit current Unlimited peak values: DC component 50 % DC component 0 % 0 100 200 300 400 500 600 1 700 800 A w [ V ] Correctionfactor Recovery voltage 0.2 0.4 0.6 0.8 200 400 500 600 700 800100 s w 300 1400 1200 1000 800 600 400 200 0 [ V ] [V] 0 ÛPeakarcvoltage ADA94-5004a-v Recovery voltage www.dienhathe.xyz www.dienhathe.vn
  • 21. Semiconductor Fuses LV HRC SITOR Fuse Links Rated voltage 690 V AC/700 V DC 2/21Siemens ET B1 T · 2007 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 Series 3NE8 72.-1, 3NE8 731-1 Size: 000 Operational class: aR Rated voltage: 690 V AC/ 700 V DC Rated current: 80 ... 315 A Time/current characteristics diagram Let-through characteristics (current limitation at 50 Hz) Correction factor kA for breaking I2 t value Peak arc voltage 2101 10-3 2 4 6 10-2 64 1028 2 64 1038 2 4 2 4 6 10-1 2 4 6 100 2 4 6 101 2 4 6 102 2 4 6 103 2 4 6 104 I2_10817 6 1048 2 5 0 A 2 0 0 A 1 6 0 A 1 2 5 A 1 0 0 A 8 0 A 3 1 5 A vs p [ A ] [s]Virtualpre-arcingtime Prospective short-circuit current 10 2 4 6 2 4 6 4 c[A] 105 103 I2_10820 6 8 0 A 1 0 0 A 1 2 5 A 1 6 0 A 2 0 0 A 2 5 0 A 3 1 5 A 102 2 64 108 3 2 64 108 4 2 64 108 5 2 4 p [A] Let-throughcurrent Prospective short-circuit current Unlimited peak values: DC component 50 % DC component 0 % 0 100 200 300 400 500 600 1 700 800 A w [ V ] Correctionfactor ADA94-5003a-v Recovery voltage 0.2 0.4 0.6 0.8 200 400 500 600 700 800100 s w 300 1400 1200 1000 800 600 400 200 0 [ V ] [V] 0 ÛPeakarcvoltage Recovery voltage www.dienhathe.xyz www.dienhathe.vn
  • 22. Semiconductor Fuses LV HRC SITOR Fuse Links Rated voltage 690 V AC, operational class gS 2/22 Siemens ET B1 T · 2007 ■Technical specifications 1) Temperature rise and power dissipation for operation in LV HRC fuse base. Type 3NE1 813-0 3NE1 814-0 3NE1 815-0 3NE1 803-0 3NE1 802-0 3NE1 817-0 3NE1 818-0 3NE1 820-0 Operational class (IEC 60269) gS Rated voltage Un V AC 690 Rated current In A 16 20 25 35 40 50 63 80 Melting I2t value I2ts (tvs = 1 ms) A2 s 18 41 74 166 295 461 903 1843 Breaking I2t value I2tA at Un A2 s 200 430 780 1700 3000 4400 9000 18000 Temperature rise at In (body center)1) K 25 30 35 30 35 40 Power dissipation at In 1) W 3.0 3.5 4.0 5.0 6.0 7.0 8.0 Varying load factor WL 1.0 Certification according to UL 248-13 Weight approx. kg 0.13 Accessories Fuse base, 1-pole 3NH3 030 3-pole 3NH4 030 Fuse puller 3NX1 011 Fuse switch disconnectors 3NP40/3NP50 Switch disconnector with fuses 3KL50 30-1.B00 3KM50 30-1.B00 3KL52 30- 1.B00 3KM52 30- 1.B00 Type 3NE1 021-0 3NE1 022-0 3NE1 224-0 3NE1 225-0 3NE1 227-0 3NE1 230-0 Operational class (IEC 60269) gS Rated voltage Un V AC 690 Rated current In A 100 125 160 200 250 315 Melting I2 t value I2 ts (tvs = 1 ms) A2 s 3100 6000 7400 14500 29500 46100 Breaking I2 t value I2 tA at Un A2 s 33000 63000 60000 100000 200000 310000 Temperature rise at In (body center)1) K 36 40 60 65 75 80 Power dissipation at In 1) W 10 11 24 27 30 38 Varying load factor WL 1.0 Certification according to UL 248-13 Weight approx. kg 0.20 0.55 Accessories Fuse base, 1-pole 3NH3 030 3NH3 230 3NH3 330 3-pole 3NH4 030 3NH4 230 3NH4 330 Fuse puller 3NX1 011 Fuse switch disconnectors 3NP40 3NP50 3NP42 3NP52 3NP53 Switch disconnector with fuses 3KL52 30-1.B00 3KM52 30-1.B00 3KL55 30-1.B00 3KM55 30-1.B00 3KL57 30-1.B00 3KM57 30-1.B00 Type 3NE1 331-0 3NE1 332-0 3NE1 333-0 3NE1 334-0 3NE1 435-0 3NE1 436-0 3NE1 437-0 3NE1 438-0 Operational class (IEC 60269) gS Rated voltage Un V AC 690 Rated current In A 350 400 450 500 560 630 710 800 Melting I2 t value I2 ts (tvs = 1 ms) A2 s 58000 84000 104000 149000 215000 293000 437000 723000 Breaking I2 t value I2 tA at Un A2 s 430000 590000 750000 950000 1700000 2350000 3400000 5000000 Temperature rise at In (body center)1) K 75 85 90 65 70 68 70 Power dissipation at In 1) W 42 45 53 56 50 55 60 59 Varying load factor WL 1.0 Certification according to UL 248-13 Weight approx. kg 0.7 0.95 Accessories Fuse base, 1-pole 3NH3 330 3NH3 430 Fuse puller 3NX1 011 Fuse switch disconnectors 3NP53 3NP54 Switch disconnector with fuses 3KL57 30-1.B00 3KM57 30-1.B00 3KL61 30-1AB0 3KL62 www.dienhathe.xyz www.dienhathe.vn
  • 23. Semiconductor Fuses LV HRC SITOR Fuse Links Rated voltage 690 V AC, operational class gS 2/23Siemens ET B1 T · 2007 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 ■Selection and ordering data For dimensional drawings, see pages 2/48 and 2/49. Size In Operational class Order No. Weight 1 unit approx. PS*/ P. unit A kg Unit(s) Rated voltage 690 V AC for mounting in LV HRC fuse bases 000 16 gS 3NE1 813-0 0.127 3 20 gS 3NE1 814-0 0.128 3 25 gS 3NE1 815-0 0.127 3 35 gS 3NE1 803-0 0.128 3 40 gS 3NE1 802-0 0.127 3 50 gS 3NE1 817-0 0.128 3 63 gS 3NE1 818-0 0.128 3 80 gS 3NE1 820-0 0.129 3 00 100 gS 3NE1 021-0 0.202 3 125 gS 3NE1 022-0 0.202 3 1 160 gS 3NE1 224-0 0.580 3 200 gS 3NE1 225-0 0.582 3 250 gS 3NE1 227-0 0.580 3 315 gS 3NE1 230-0 0.581 3 2 350 gS 3NE1 331-0 0.766 3 400 gS 3NE1 332-0 0.743 3 450 gS 3NE1 333-0 0.760 3 500 gS 3NE1 334-0 0.766 3 3 560 gS 3NE1 435-0 1.111 3 630 gS 3NE1 436-0 1.114 3 710 gS 3NE1 437-0 1.117 3 800 gS 3NE1 438-0 1.124 3 * You can order this quantity or a multiple thereof. www.dienhathe.xyz www.dienhathe.vn
  • 24. Semiconductor Fuses LV HRC SITOR Fuse Links Rated voltage 690 V AC, operational class gS 2/24 Siemens ET B1 T · 2007 ■Characteristic curves Series 3NE1 8..-0 Size: 000 Operational class: gS Rated voltage: 690 V AC Rated current: 16 ... 80 A Time/current characteristics diagram Let-through characteristics (current limitation at 50 Hz) Correction factor kA for breaking I2 t value Peak arc voltage p vs 2101 10-3 2 4 6 10-2 64 1028 2 64 1038 2 4 2 4 6 10-1 2 4 6 100 2 4 6 101 2 4 6 102 2 4 6 103 2 4 6 104 I2_10825 6 1048 4 0 A 3 5 A 2 5 A 2 0 A 1 6 A 5 0 A 6 3 A 8 0 A [ A ] [s]Virtualpre-arcingtime Prospective short-circuit current 102 2 64 108 10 2 4 6 2 4 6 3 c p [A] [A] 104 102 3 2 64 108 4 2 64 108 5 2 4 2 0 A I2_10828 2 5 A 3 2 A 4 0 A 5 0 A 6 3 A 1 6 A 8 0 A Let-throughcurrent Prospective short-circuit current Unlimited peak values: DC component 50 % DC component 0 % 0 100 200 300 400 500 600 1 700 800 A w [ V ] Correctionfactor Recovery voltage 0.2 0.4 0.6 0.8 200 400 500 600 700 800100 s w 300 1400 1200 1000 800 600 400 200 0 [ V ] [V] 0 ÛPeakarcvoltage Recovery voltage www.dienhathe.xyz www.dienhathe.vn
  • 25. Semiconductor Fuses LV HRC SITOR Fuse Links Rated voltage 690 V AC, operational class gS 2/25Siemens ET B1 T · 2007 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 Series 3NE1 02.-0, 3NE1 2..-0 Size: 00, 1 Operational class: gS Rated voltage: 690 V AC Rated current: 100 ... 315 A Time/current characteristics diagram Let-through characteristics (current limitation at 50 Hz) Correction factor kA for breaking I2 t value Peak arc voltage p vs 2102 10-3 2 4 6 10-2 64 1038 2 64 1048 2 4 6 10-1 2 4 6 100 2 4 6 101 2 4 6 102 2 4 6 103 2 4 6 104 I2_10829 2 5 0 A 2 0 0 A 1 6 0 A 1 2 5 A 1 0 0 A 3 1 5 A Virtualpre-arcingtime Prospective short-circuit current p c 103 2 64 1048 10 2 4 6 10 I2_10831 4 3 2 64 1058 2 2 4 6 105 [A] [ A ] 1 0 0 A 2 0 0 A 2 5 0 A 3 1 5 A 1 2 5 / 1 6 0 A Prospective short-circuit current Unlimited peak values: DC component 50 % DC component 0 % Let-throughcurrent 0 100 200 300 400 500 600 1 700 800 A w 3 N E 1 2 . . - 0 3 N E 1 0 2 . - 0 [ V ] Correctionfactor Recovery voltage 0.2 0.4 0.6 0.8 200 400 500 600 700 800100 s w 300 1400 1200 1000 800 600 400 200 0 [ V ] [V] 0 ÛPeakarcvoltage Recovery voltage www.dienhathe.xyz www.dienhathe.vn
  • 26. Semiconductor Fuses LV HRC SITOR Fuse Links Rated voltage 690 V AC, operational class gS 2/26 Siemens ET B1 T · 2007 Series 3NE1 33.-0, 3NE1 43.-0 Size: 2, 3 Operational class: gS Rated voltage: 690 V AC Rated current: 350 ... 800 A Time/current characteristics diagram Let-through characteristics (current limitation at 50 Hz) Correction factor kA for breaking I2t value Peak arc voltage p vs 2102 10-3 2 4 6 10-2 64 1038 2 64 1048 2 4 2 4 6 10-1 2 4 6 100 2 4 6 101 2 4 6 102 2 4 6 103 2 4 6 104 I2_10832 6 1058 5 6 0 A 5 0 0 A 4 5 0 A 4 0 0 A 3 5 0 A 6 3 0 A 7 1 0 A 8 0 0 A [ A ] [s]Virtualpre-arcingtime Prospective short-circuit current p c 103 2 64 1048 10 2 4 6 10 I2_10834 4 3 2 64 1058 2 2 4 6 105 [A] [ A ] 3 5 0 A 4 0 0 A 4 5 0 A 5 0 0 A 5 6 0 A 6 3 0 A 7 1 0 A 8 0 0 A Prospective short-circuit current Unlimited peak values: DC component 50 % DC component 0 % Let-throughcurrent 0 100 200 300 400 500 600 1 700 800 A w [ V ] Correctionfactor Recovery voltage 0.2 0.4 0.6 0.8 200 400 500 600 700 800100 s w 300 1400 1200 1000 800 600 400 200 0 [ V ] [V] 0 ÛPeakarcvoltage Recovery voltage www.dienhathe.xyz www.dienhathe.vn
  • 27. Semiconductor Fuses LV HRC SITOR Fuse Links Rated voltage 690 V AC, operational class gR 2/27Siemens ET B1 T · 2007 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 ■Technical specifications 1) Temperature rise and power dissipation for operation in LV HRC fuse base. Type 3NE1 020-2 3NE1 021-2 3NE1 022-2 3NE1 224-2 3NE1 225-2 3NE1 227-2 3NE1 230-2 Operational class (IEC 60269) gR Rated voltage Un V AC 690 Rated current In A 80 100 125 160 200 250 315 Melting I2t value I2ts (tvs = 1 ms) A2 s 780 1490 3115 2650 5645 11520 22580 Breaking I2t value I2tA at Un A2 s 5800 11000 23000 18600 51800 80900 168000 Temperature rise at In (body center)1) K 45 49 55 70 62 70 75 Power dissipation at In 1) W 10.5 11.5 13.5 30 28 35 42 Varying load factor WL 1.0 Certification according to UL 248-13 Weight approx. kg 0.2 0.55 Accessories Fuse base, 1-pole 3NH3 030 3NH3 230 Fuse puller 3NX1 011 Fuse switch disconnectors 3NP50 3NP52 3NP53 Switch disconnector with fuses 3KL52 3KL55 3KL57 Type 3NE1 331-2 3NE1 333-2 3NE1 334-2 Operational class (IEC 60269) gR Rated voltage Un V AC 690 Rated current In A 350 450 500 Melting I2 t value I2 ts (tvs = 1 ms) A2 s 29500 46100 66400 Breaking I2 t value I2 tA at Un A2s 177000 276500 398000 Temperature rise at In (body center)1) K 82 100 Power dissipation at In 1) W 44 62 65 Varying load factor WL 1.0 Certification according to UL 248-13 Weight approx. kg 0.7 Accessories Fuse base, 1-pole 3NH3 230 3NH3 340 Fuse puller 3NX1 011 3NX1 011 Fuse switch disconnectors 3NP53 3NP54 Switch disconnector with fuses 3KL57 3KL61 Type 3NE1 435-2 3NE1 436-2 3NE1 447-2 3NE1 437-2 3NE1 438-2 3NE1 448-2 Operational class (IEC 60269) gR Rated voltage Un V AC 690 Rated current In A 560 630 670 710 800 850 Melting I2 t value I2 ts (tvs = 1 ms) A2 s 130000 203000 240000 265000 361000 520000 Breaking I2 t value I2 tA at Un A2 s 890000 1390000 1640000 1818000 2475000 3640000 Temperature rise at In (body center)1) K 80 82 90 95 Power dissipation at In 1) W 60 62 65 72 82 76 Varying load factor WL 1.0 Certification according to UL 248-13 Weight approx. kg 1.0 Accessories Fuse base, 1-pole 3NH3 340 Fuse puller 3NX1 011 Fuse switch disconnectors 3NP54 3NP54 Switch disconnector with fuses 3KL61 3KL62 www.dienhathe.xyz www.dienhathe.vn
  • 28. Semiconductor Fuses LV HRC SITOR Fuse Links Rated voltage 690 V AC, operational class gR 2/28 Siemens ET B1 T · 2007 Type 3NE8 015-1 3NE8 003-1 3NE8 017-1 3NE8 018-1 3NE8 020-1 3NE8 021-1 3NE8 022-1 3NE8 024-1 Operational class (IEC 60269) gR aR Rated voltage Un V AC 690 Rated current In A 25 35 50 63 80 100 125 160 Melting I2 t value I2 ts (tvs = 1 ms) A2 s 30 70 120 260 450 850 1400 2800 Breaking I2t value I2tA at Un A2 s 180 400 700 1400 2400 4200 6500 1300 Temperature rise at In (body center) K 35 45 65 70 80 90 110 130 Power dissipation at In W 7 9 14 16 19 22 28 38 Varying load factor WL 0.95 Certification according to UL 248-13 Weight approx. kg 0.20 Accessories Fuse base, 1-pole 3NH3 030 3-pole 3NH4 030 Fuse puller 3NX1 011 Fuse switch disconnectors 3NP40 3NP50 Switch disconnector with fuses 3KL50 30-1.B00 3KM50 30-1.B00 3KL52 30-1.B00 3KM52 30-1.B00 www.dienhathe.xyz www.dienhathe.vn
  • 29. Semiconductor Fuses LV HRC SITOR Fuse Links Rated voltage 690 V AC, operational class gR 2/29Siemens ET B1 T · 2007 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 ■Selection and ordering data For dimensional drawings, see pages 2/48 and 2/49. Size In Operational class Order No. Weight 1 unit approx. PS*/ P. unit A kg Unit(s) Rated voltage 690 V AC for mounting in LV HRC fuse bases 00 80 gR 3NE1 020-2 0.203 3 100 gR 3NE1 021-2 0.203 3 125 gR 3NE1 022-2 0.203 3 1 160 gR 3NE1 224-2 0.613 3 200 gR 3NE1 225-2 0.612 3 250 gR 3NE1 227-2 0.626 3 315 gR 3NE1 230-2 0.615 3 2 350 gR 3NE1 331-2 0.754 3 450 gR 3NE1 333-2 0.768 3 500 gR 3NE1 334-2 0.768 3 3 560 gR 3NE1 435-2 1.149 3 630 gR 3NE1 436-2 1.179 3 670 gR 3NE1 447-2 1.170 3 710 gR 3NE1 437-2 1.153 3 800 gR 3NE1 438-2 1.184 3/1 850 gR 3NE1 448-2 1.207 3 00 25 gR 3NE8 015-1 0.205 3 35 gR 3NE8 003-1 0.204 3 50 gR 3NE8 017-1 0.203 3 63 gR 3NE8 018-1 0.205 3 80 aR 3NE8 020-1 0.203 3 100 aR 3NE8 021-1 0.205 3 125 aR 3NE8 022-1 0.213 3 160 aR 3NE8 024-1 0.207 3 * You can order this quantity or a multiple thereof. www.dienhathe.xyz www.dienhathe.vn
  • 30. Semiconductor Fuses LV HRC SITOR Fuse Links Rated voltage 690 V AC, operational class gR 2/30 Siemens ET B1 T · 2007 ■Characteristic curves Series 3NE1 022-2, 3NE1 2..-2, 3NE1 33.-2 Size: 00, 1 Operational class: gR Rated voltage: 690 V AC Rated current: 125 ... 500 A Time/current characteristics diagram Let-through characteristics (current limitation at 50 Hz) Correction factor kA for breaking I2 t value Peak arc voltage 10-3 10-2 2 4 6 10-1 2 4 6 100 2 4 6 101 2 4 6 102 2 4 6 103 2 4 6 6 104 2 4 [s]tVS 2 4 6 p 1052 4 6 1042 4 6 103102 I2_1083980 A 100 A 125 A 160 A 200 A 250 A 315 A 350 A 450 A 500 A VirtualPre-arcingTime Prospective Short-circuit Current 102 103 104 10 5 103 2 4 6 104 105 2 4 6 2 4 6 2 4 6 2 4 6 p I2_10842 C 125 A 160 A 100 A 80 A 500 A 450 A 350 A 315 A 250 A 200 A Prospective Short-Circuit Current PeakLet-ThroughCurrent I2_10840 0 0 100 200 300 400 500 600 700 800 1 80 A - 125 A 160 A - 315 A 350 A - 500 A Recovery voltage Correctionfactor 0.2 0.4 0.6 0.8 I2_10841 2000 400 800 1200 1600 8002000 0 400 600 160...315 A 80...125 A 350...500 A Peakarcvoltage Recovery voltage www.dienhathe.xyz www.dienhathe.vn
  • 31. Semiconductor Fuses LV HRC SITOR Fuse Links Rated voltage 690 V AC, operational class gR 2/31Siemens ET B1 T · 2007 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 Series 3NE1 4..-2 Size: 3 Operational class: gR Rated voltage: 690 V AC Rated current: 560 ... 850 A Time/current characteristics diagram Let-through characteristics (current limitation at 50 Hz) Correction factor kA for breaking I2t value Peak arc voltage 10-3 10-2 2 4 6 10-1 2 4 6 100 2 4 6 101 2 4 6 102 2 4 6 103 2 4 6 6 104 2 4 [s]tVS 2 4 6 p 1052 4 6 1042 4 6 103102 I2_10843 560 A 630 A 670 A 710 A 800 A 850 A VirtualPre-arcingTime Prospective Short-circuit Current 102 103 104 10 5 103 2 4 6 104 105 2 4 6 2 4 6 2 4 6 2 4 6 p I2_10846 C 850 A 800 A 710 A 670 A 630 A 560 A Prospective Short-Circuit Current PeakLet-ThroughCurrent 0 0 100 200 300 400 500 600 700 800 1 I2_10844 Recovery voltage Correctionfactor 0.2 0.4 0.6 0.8 I2_10845 2000 400 800 1200 1600 8002000 0 400 600 Peakarcvoltage Recovery voltage www.dienhathe.xyz www.dienhathe.vn
  • 32. Semiconductor Fuses LV HRC SITOR Fuse Links Rated voltage 690 V AC, operational class gR 2/32 Siemens ET B1 T · 2007 Series 3NE8 0..-1 Size: 00 Operational class: gR or aR Rated voltage: 690 V AC Rated current: 25 ... 160 A Time/current characteristics diagram Let-through characteristics (current limitation at 50 Hz) Correction factor kA for breaking I2 t value Peak arc voltage p vs 2101 10-3 2 4 6 10-2 64 1028 2 64 1038 2 4 2 4 6 10-1 2 4 6 100 2 4 6 101 2 4 6 102 2 4 6 103 2 4 6 104 I2_10847 6 1048 1 0 0 A 8 0 A 6 3 A 5 0 A 3 5 A 2 5 A 1 2 5 A 1 6 0 A [ A ] [s]Virtualpre-arcingtime Prospective short-circuit current 102 2 64 108 10 2 4 6 2 4 6 3 c p [A] [A] 104 102 3 2 64 108 4 2 64 108 5 2 4 2 5 A I2_10850 3 5 A 5 0 A 6 3 A 8 0 A 1 0 0 A 1 2 5 A 1 6 0 A Let-throughcurrent Prospective short-circuit current Unlimited peak values: DC component 50 % DC component 0 % 0 100 200 300 400 500 600 1 700 800 A w [ V ] Correctionfactor Recovery voltage 0.2 0.4 0.6 0.8 0 200 w s 2000 1800 1000 800 400 200 400 600 800 I2_10849 600 1200 1400 1600 [ V ] [V] 0 Peakarcvoltage Recovery voltage Û www.dienhathe.xyz www.dienhathe.vn
  • 33. Semiconductor Fuses LV HRC SITOR Fuse Links Rated voltage 800 V AC 2/33Siemens ET B1 T · 2007 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 ■Technical specifications ■Selection and ordering data For dimensional drawings, see pages 2/48 and 2/49. 1) Cladding dimensions and grip lugs according to IEC 60269-2-1; but blade slotted according to IEC 60269-4-1. Type 3NE4 327-0B 3NE4 330-0B 3NE4 333-0B 3NE4 334-0B 3NE4 337 Operational class (IEC 60269) aR Rated voltage Un V AC 800 Rated current In A 250 315 450 500 710 Melting I2 t value I2 ts (tvs = 1 ms) A2 s 3600 7400 29400 42500 142000 Breaking I2 t value I2 tA at Un A2 s 29700 60700 191000 276000 923000 Temperature rise at In (body center) K 175 170 190 195 170 Power dissipation at In W 105 120 140 155 Varying load factor WL 0.85 0.95 Weight approx. kg 0.7 Accessories Fuse base, 1-pole 3NH3 330 3NH3 430 Fuse puller 3NX1 011 Fuse switch disconnectors 3NP53 3NP54 Switch disconnector with fuses 3KL57 30-1.B00 3KM57 30-1.B00 3KL61 3KL62 Size In Operational class Order No. Weight 1 unit approx. PS*/ P. unit A kg Unit(s) Rated voltage 800 V AC with bolt-on links Mounting dimensions: 110 mm 21) 250 aR 3NE4 327-0B 0.753 3 315 aR 3NE4 330-0B 0.760 3 450 aR 3NE4 333-0B 0.760 3 500 aR 3NE4 334-0B 0.754 3 710 aR 3NE4 337 0.771 3 * You can order this quantity or a multiple thereof. www.dienhathe.xyz www.dienhathe.vn
  • 34. Semiconductor Fuses LV HRC SITOR Fuse Links Rated voltage 800 V AC 2/34 Siemens ET B1 T · 2007 ■Characteristic curves Series 3NE4 3..-0B, 3NE4 337 Size: 2 Operational class: aR Rated voltage: 800 V AC Rated current: 250 ... 710 A Time/current characteristics diagram Let-through characteristics (current limitation at 50 Hz) Correction factor kA for breaking I2 t value Peak arc voltage p vs 2102 10-3 2 4 6 10-2 64 1038 2 64 1048 2 4 2 4 6 10-1 2 4 6 100 2 4 6 101 2 4 6 102 2 4 6 103 2 4 6 104 I2_10851 6 1058 2 5 0 A 3 1 5 A 4 5 0 A 5 0 0 A 7 1 0 A [ A ] [s]Virtualpre-arcingtime Prospective short-circuit current p c 103 2 64 1048 10 2 4 6 10 I2_10854 4 3 2 64 1058 2 2 4 6 105 [A] [ A ] 7 1 0 A 5 0 0 A 4 5 0 A 3 1 5 A 2 5 0 A Prospective short-circuit current Unlimited peak values: DC component 50 % DC component 0 % Let-throughcurrent 0 100 200 300 400 500 600 1 700 800 A w 4 5 0 A 3 1 5 A [ V ] Correctionfactor ADA94-5003a-v Recovery voltage 0.2 0.4 0.6 0.8 0 200 w s 2000 1800 1000 800 400 200 400 600 800 I2_10853 600 1200 1400 1600 1000 [ V ] [V] 0 Peakarcvoltage Recovery voltage Û www.dienhathe.xyz www.dienhathe.vn
  • 35. Semiconductor Fuses LV HRC SITOR Fuse Links Rated voltage 1000 V AC 2/35Siemens ET B1 T · 2007 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 ■Technical specifications Type 3NE4 101 3NE4 102 3NE4 117 3NE4 118 3NE4 120 3NE4 121 3NE4 122 3NE4 124 Operational class (IEC 60269) gR aR Rated voltage Un V AC 1000 Rated current In A 32 40 50 63 80 100 125 160 Melting I2 t value I2 ts (tvs = 1 ms) A2 s 40 75 120 230 450 900 1800 3600 Breaking I2 t value I2 tA at Un A2 s 280 500 800 1500 3000 6000 14000 29000 Temperature rise at In (body center) K 45 50 65 78 82 85 100 120 Power dissipation at In W 12 13 16 20 22 24 30 35 Varying load factor WL 0.9 Certification according to UL 248-13 Weight approx. kg 0.27 Accessories Fuse base, 1-pole 3NH3 120 3-pole 3NH4 230 Fuse puller 3NX1 011 Fuse switch disconnectors 3NP42, 3NP52 Switch disconnector with fuses 3KL55 30-1.B00 3KM55 30-1.B00 Type 3NE3 221 3NE3 222 3NE3 224 3NE3 225 3NE3 227 Operational class (IEC 60269) aR Rated voltage Un V AC 1000 Rated current In A 100 125 160 200 250 Melting I2 t value I2 ts (tvs = 1 ms) A2 s 665 1040 1850 4150 6650 Breaking I2 t value I2 tA at Un A2 s 4800 7200 13000 30000 48000 Temperature rise at In (body center) K 65 70 90 80 90 Power dissipation at In W 28 36 42 50 Varying load factor WL 0.95 1.0 Certification according to UL 248-13 Weight approx. kg 0.55 Accessories Fuse base, 1-pole 3NH3 230 3-pole 3NH4 230 Fuse puller 3NX1 011 Fuse switch disconnectors 3NP42, 3NP52 Switch disconnector with fuses 3KL55 30-1.B00 3KM55 30-1.B00 Type 3NE3 230-0B 3NE3 231 3NE3 232-0B 3NE3 233 Operational class (IEC 60269) aR Rated voltage Un V AC 1000 Rated current In A 315 350 400 450 Melting I2 t value I2 ts (tvs = 1 ms) A2 s 13400 16600 22600 29500 Breaking I2 t value I2 tA at Un A2 s 80000 100000 135000 175000 Temperature rise at In (body center) K 100 120 140 130 Power dissipation at In W 65 75 85 95 Varying load factor WL 0.95 0.9 Certification according to UL 248-13 Weight approx. kg 0.55 Accessories Fuse base, 1-pole 3NH3 330 Fuse puller 3NX1 011 Fuse switch disconnectors 3NP53 Switch disconnector with fuses 3KL57 30-1.B00 3KM57 30-1.B00 www.dienhathe.xyz www.dienhathe.vn
  • 36. Semiconductor Fuses LV HRC SITOR Fuse Links Rated voltage 1000 V AC 2/36 Siemens ET B1 T · 2007 1) Gauge 140 mm, M12 screw connection. Type 3NE3 332-0B 3NE3 333 3NE3 334-0B 3NE3 335 3NE3 336 3NE3 337-8 3NE3 338-8 3NE3 340-8 Operational class (IEC 60269) aR Rated voltage Un V AC 1000 900 800 690 Rated current In A 400 450 500 560 630 710 800 900 Melting I2 t value I2 ts (tvs = 1 ms) A2 s 22600 29500 46100 66400 104000 149000 184000 223000 Breaking I2t value I2tA at Un A2 s 135000 175000 260000 360000 600000 800000 850000 1300000 Temperature rise at In (body center) K 120 125 115 120 110 125 140 160 Power dissipation at In W 85 90 95 100 105 130 165 Varying load factor WL 1.0 0.95 Certification according to UL 248-13 Weight approx. kg 0.7 Accessories Fuse base, 1-pole 3NH3 430 Fuse puller 3NX1 011 Fuse switch disconnectors 3NP54 Switch disconnector with fuses 3KL61 30-1AB0 3KL62 Type 3NE3 421 3NE3 626 3NE3 430 3NE3 432 3NE3 635 3NE3 635-6 3NE3 434 3NE3 636 3NE3 637 3NE3 637-11) Operational class (IEC 60269) aR Rated voltage Un V AC 1000 Rated current In A 100 224 315 400 450 500 630 710 Melting I2 t value I2 ts (tvs = 1 ms) A2 s 1800 7200 29000 48500 65000 116000 170000 260000 Breaking I2 t value I2 tA at Un A2 s 13500 54000 218000 364000 488000 870000 1280000 1950000 Temperature rise at In (body center) K 45 140 120 130 150 120 136 170 Power dissipation at In W 25 85 80 110 95 132 145 Varying load factor WL 1.0 Weight approx. kg 1.15 www.dienhathe.xyz www.dienhathe.vn
  • 37. Semiconductor Fuses LV HRC SITOR Fuse Links Rated voltage 1000 V AC 2/37Siemens ET B1 T · 2007 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 ■Selection and ordering data For dimensional drawings, see pages 2/48 and 2/49. 1) Cladding dimensions and grip lugs according to IEC 60269-2-1; but blade slotted according to IEC 60269-4-1. 2) Rated voltage 900 V AC. 3) Rated voltage 800 V AC. 4) Rated voltage 690 V AC. 5) Design according to 3NE6 4.. and 3NE9 4... Size In Operational class Order No. Weight 1 unit approx. PS*/ P. unit A kg Unit(s) Rated voltage 1000 V AC for mounting in LV HRC fuse bases 0 32 gR 3NE4 101 0.278 3 40 3NE4 102 0.277 3 50 3NE4 117 0.276 3 63 aR 3NE4 118 0.279 3 80 3NE4 120 0.276 3 100 3NE4 121 0.278 3 125 3NE4 122 0.279 3 160 3NE4 124 0.279 3 with bolt-on links Mounting dimensions: 110 mm 11) 100 aR 3NE3 221 0.580 3 125 3NE3 222 0.568 3 160 3NE3 224 0.573 3 200 3NE3 225 0.570 3 250 3NE3 227 0.580 3 315 3NE3 230-0B 0.585 3 350 3NE3 231 0.590 3 400 3NE3 232-0B 0.576 3 450 3NE3 233 0.720 3 21) 400 aR 3NE3 332-0B 0.759 3 450 3NE3 333 0.748 3 500 3NE3 334-0B 0.753 3 560 3NE3 335 0.756 3 630 3NE3 336 0.760 3 7102) 3NE3 337-8 0.762 3 8003) 3NE3 338-8 0.764 3 9004) 3NE3 340-8 0.753 3 Mounting dimensions: 130 mm 3 100 aR 3NE3 421 1.200 3 224 3NE3 626 1.300 3 315 3NE3 430 1.241 3 400 3NE3 432 1.247 3 450 3NE3 635 1.179 3 4505) 3NE3 635-6 1.184 3 500 3NE3 434 1.490 3 630 3NE3 636 1.213 3 710 3NE3 637 1.190 3 Mounting dimensions: 140 mm, M12 screw connection 3 710 aR 3NE3 637-1 1.246 3 * You can order this quantity or a multiple thereof. www.dienhathe.xyz www.dienhathe.vn
  • 38. Semiconductor Fuses LV HRC SITOR Fuse Links Rated voltage 1000 V AC 2/38 Siemens ET B1 T · 2007 ■Characteristic curves Series 3NE4 1.. Size: 0 Operational class: gR or aR Rated voltage: 1000 V AC Rated current: 32 ... 160 A Time/current characteristics diagram Let-through characteristics (current limitation at 50 Hz) Correction factor kA for breaking I2 t value Peak arc voltage p vs 2101 10-3 2 4 6 10-2 64 1028 2 64 1038 2 4 2 4 6 10-1 2 4 6 100 2 4 6 101 2 4 6 102 2 4 6 103 2 4 6 104 I2_10855 6 1048 1 0 0 A 8 0 A 6 3 A 5 0 A 4 0 A 3 2 A 1 2 5 A 1 6 0 A [s] [ A ] Virtualpre-arcingtime Prospective short-circuit current 102 2 64 108 10 2 4 6 1 0 0 A 2 4 6 3 1 2 5 A c p [A] [A] 104 102 3 2 64 108 4 2 64 108 5 2 4 3 2 A I2_10858 4 0 A 5 0 A 1 6 0 A 6 3 A 8 0 A Let-throughcurrent Prospective short-circuit current Unlimited peak values: DC component 50 % DC component 0 % 0 200 400 600 1 800 1000 A w [ V ] I2_10856 Correctionfactor 0.8 0.6 0.4 0.2 Recovery voltage 0 200 400 600 800 1000 1200 500 1000 1500 2000 2500 0 s w [ V ] [V] I2_10857 Peakarcvoltage Recovery voltage Û www.dienhathe.xyz www.dienhathe.vn
  • 39. Semiconductor Fuses LV HRC SITOR Fuse Links Rated voltage 1000 V AC 2/39Siemens ET B1 T · 2007 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 Series 3NE3 22. Size: 1 Operational class: aR Rated voltage: 1000 V AC Rated current: 100 ... 225 A Time/current characteristics diagram Let-through characteristics (current limitation at 50 Hz) Correction factor kA for breaking I2 t value Peak arc voltage p vs 2101 10-3 2 4 6 10-2 64 1028 2 64 1038 2 4 2 4 6 10-1 2 4 6 100 2 4 6 101 2 4 6 102 2 4 6 103 2 4 6 104 I2_10859 6 1048 1 0 0 A 1 2 5 A 1 6 0 A [s] [ A ] 2 0 0 A 2 5 0 A Virtualpre-arcingtime Prospective short-circuit current 102 2 64 108 10 2 4 6 2 4 6 3 c p [A] [A] 104 102 3 2 64 108 4 2 64 108 5 2 4 I2_10862 2 1 0 0 A 1 2 5 A 1 6 0 A 2 0 0 A 2 5 0 A Let-throughcurrent Prospective short-circuit current Unlimited peak values: DC component 50 % DC component 0 % 0 200 400 600 1 800 1000 A w [ V ] I2_10860 Correctionfactor 0.8 0.6 0.4 0.2 Recovery voltage 0 200 400 600 800 1000 1200 500 1000 1500 2000 2500 0 s w [ V ] [V] I2_10861 ÛPeakarcvoltage Recovery voltage www.dienhathe.xyz www.dienhathe.vn
  • 40. Semiconductor Fuses LV HRC SITOR Fuse Links Rated voltage 1000 V AC 2/40 Siemens ET B1 T · 2007 Series 3NE3 23. Size: 1 Operational class: aR Rated voltage: 1000 V AC Rated current: 315 ... 450 A Time/current characteristics diagram Let-through characteristics (current limitation at 50 Hz) Correction factor kA for breaking I2 t value Peak arc voltage p vs 2102 10-3 2 4 6 10-2 64 1038 2 64 1048 2 4 6 10-1 2 4 6 100 2 4 6 101 2 4 6 102 2 4 6 103 2 4 6 104 I2_10863 4 5 0 A [ A ] 4 0 0 A 3 5 0 A 3 0 0 A [s]Virtualpre-arcingtime Prospective short-circuit current p c 103 2 64 1048 10 2 4 6 10 I2_10864 4 3 2 64 1058 2 2 4 6 105 [A] [ A ] 3 1 5 A 3 5 0 A 4 0 0 A 4 5 0 A Prospective short-circuit current Unlimited peak values: DC component 50 % DC component 0 % Let-throughcurrent 0 200 400 600 1 800 1000 A w [ V ] I2_10860 Correctionfactor 0.8 0.6 0.4 0.2 Recovery voltage 0 200 400 600 800 1000 1200 500 1000 1500 2000 2500 0 s w [ V ] [V] I2_10861 ÛPeakarcvoltage Recovery voltage www.dienhathe.xyz www.dienhathe.vn
  • 41. Semiconductor Fuses LV HRC SITOR Fuse Links Rated voltage 1500 V AC 2/41Siemens ET B1 T · 2007 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 ■Technical specifications ■Selection and ordering data For dimensional drawings, see pages 2/48 and 2/49. 1) M12 screw connection Type 3NE5 424 3NE5 426 3NE5 430 3NE5 431 3NE5 433 3NE5 433-1 Operational class (IEC 60269) aR Rated voltage Un V AC 1500 Rated current In A 160 224 315 350 450 Melting I2 t value I2 ts (tvs = 1 ms) A2 s 7200 18400 41500 57000 116000 Breaking I2 t value I2 tA at Un A2 s 54000 138000 311000 428000 870000 Temperature rise at In (body center) K 75 100 125 150 150 Power dissipation at In W 56 80 115 135 145 Varying load factor WL 1.0 0.95 Weight approx. kg 1.95 Type 3NE5 627 3NE5 633 3NE5 643 Operational class (IEC 60269) aR Rated voltage Un V AC 1500 Rated current In A 250 450 600 Melting I2t value I2ts (tvs = 1 ms) A2 s 11200 78500 260000 Breaking I2 t value I2 tA at Un A2 s 84000 590000 1950000 Temperature rise at In (body center) K 170 160 Power dissipation at In W 130 160 145 Varying load factor WL 1.0 Weight approx. kg 1.6 Size In Operational class Order No. Weight 1 unit approx. PS*/ P. unit A kg Unit(s) Rated voltage 1500 V AC with bolt-on links Mounting dimensions: 210 mm 3 160 aR 3NE5 424 1.900 2 224 3NE5 426 1.968 2 315 3NE5 430 2.000 2 350 3NE5 431 1.959 2 450 3NE5 433 2.100 2 4501) 3NE5 433-1 1.961 2 Mounting dimensions: 170 mm 3 250 3NE5 627 1.562 3 450 3NE5 633 1.585 3 600 3NE5 643 1.587 3 * You can order this quantity or a multiple thereof. www.dienhathe.xyz www.dienhathe.vn
  • 42. Semiconductor Fuses LV HRC SITOR Fuse Links Rated voltage 1500 V AC 2/42 Siemens ET B1 T · 2007 ■Characteristic curves Series 3NE5 4.. Size: 3 Operational class: aR Rated voltage: 1500 V AC Rated current: 160 ... 600 A Time/current characteristics diagram Let-through characteristics (current limitation at 50 Hz) Correction factor kA for breaking I2 t value Peak arc voltage p vs 2102 10-3 2 4 6 10-2 64 1038 2 64 1048 2 4 2 4 6 10-1 2 4 6 100 2 4 6 101 2 4 6 102 2 4 6 103 2 4 6 104 I2_10872 6 1058 1 6 0 A 2 2 4 A 3 1 5 A [s] [ A ] 3 5 0 A 4 5 0 A Virtualpre-arcingtime Prospective short-circuit current p 103 2 64 104 I2_10875 2 64 1058 2 [ A ] 8 1 6 0 A 2 2 4 A 3 1 5 A 3 5 0 A 4 5 0 A 2 4 6 104 3 2 4 10 Prospective short-circuit current Unlimited peak values: DC component 50 % DC component 0 % Let-throughcurrentc[A] 0 500 1 15001000 w A [ V ] Correctionfactor 0.2 0.4 0.6 0.8 I201_10873 Recovery voltage 0 400 800 1200 1600 2000 800 2400 4000 0 s w [ V ] [V] I2_10874 400 1200 2000 2800 3200 3600 1600 Peakarcvoltage Recovery voltage Û www.dienhathe.xyz www.dienhathe.vn
  • 43. Semiconductor Fuses LV HRC SITOR Fuse Links Rated voltage 1500 V AC 2/43Siemens ET B1 T · 2007 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 Series 3NE5 6.. Size: 3 Operational class: aR Rated voltage: 1500 V AC Rated current: 250 ... 600 A Time/current characteristics diagram Let-through characteristics (current limitation at 50 Hz) Correction factor kA for breaking I2 t value Peak arc voltage p vs 2102 10-3 2 4 6 10-2 64 1038 2 64 1048 2 4 2 4 6 10-1 2 4 6 100 2 4 6 101 2 4 6 102 2 4 6 103 2 4 6 104 I2_10876 6 1058 [s] [ A ] 2 5 0 A 4 5 0 A 6 0 0 A Virtualpre-arcingtime Prospective short-circuit current p 103 2 64 104 I2_10877 2 64 1058 2 [ A ] 8 2 5 0 A 4 5 0 A 6 0 0 A c[A] 10 2 4 6 104 3 2 4 Prospective short-circuit current Unlimited peak values: DC component 50 % DC component 0 % Let-throughcurrent 0 500 1 15001000 w A [ V ] Correctionfactor 0.2 0.4 0.6 0.8 I201_10873 Recovery voltage 0 400 800 1200 1600 2000 800 2400 4000 0 s w [ V ] [V] I2_10874 400 1200 2000 2800 3200 3600 1600 Peakarcvoltage Recovery voltage Û www.dienhathe.xyz www.dienhathe.vn
  • 44. Semiconductor Fuses LV HRC SITOR Fuse Links Rated voltage 2000 V AC 2/44 Siemens ET B1 T · 2007 ■Technical specifications 1) M12 screw connection ■Selection and ordering data For dimensional drawings, see pages 2/48 and 2/49. 1) M12 screw connection Type 3NE7 425 3NE7 427 3NE7 431 3NE7 432 3NE7 633 3NE7 633-11) 3NE7 648-11) 3NE7 636 3NE7 636-11) 3NE7 637-11) Operational class (IEC 60269) aR Rated voltage Un V AC 2000 Rated current In A 200 250 350 400 450 525 630 710 Melting I2t value I2ts (tvs = 1 ms) A2 s 18400 29000 74000 116000 128000 149000 260000 415000 Breaking I2t value I2tA at Un A2 s 138000 218000 555000 870000 960000 1120000 1950000 3110000 Temperature rise at In (body center) K 85 110 105 130 165 210 200 230 Power dissipation at In W 75 110 120 150 160 210 220 275 Varying load factor WL 1.0 Weight approx. kg 1.95 Size In Operational class Order No. Weight 1 unit approx. PS*/ P. unit A kg Unit(s) Rated voltage 2000 V AC with bolt-on links Mounting dimensions: 210 mm 3 200 aR 3NE7 425 2.100 2 250 3NE7 427 1.970 2 350 3NE7 431 1.980 2 400 3NE7 432 1.973 2 450 3NE7 633 1.968 2 4501) 3NE7 633-1 1.983 2 5251) 3NE7 648-1 1.975 2 630 3NE7 636 1.997 2 6301) 3NE7 636-1 2.024 2 7101) 3NE7 637-1 1.997 2 * You can order this quantity or a multiple thereof. www.dienhathe.xyz www.dienhathe.vn
  • 45. Semiconductor Fuses LV HRC SITOR Fuse Links Rated voltage 2000 V AC 2/45Siemens ET B1 T · 2007 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 ■Characteristic curves Series 3NE7 4.., 3NE7 6.. Size: 3 Operational class: aR Rated voltage: 2000 V AC Rated current: 200 ... 710 A Time/current characteristics diagram Let-through characteristics (current limitation at 50 Hz) Correction factor kA for breaking I2 t value Peak arc voltage p vs 2102 10-3 2 4 6 10-2 64 1038 2 64 1048 2 4 2 4 6 10-1 2 4 6 100 2 4 6 101 2 4 6 102 2 4 6 103 2 4 6 104 I2_10878 6 1058 [s] [ A ] 2 0 0 A 2 5 0 A 3 5 0 A 4 0 0 A 4 5 0 A 5 2 5 A 6 3 0 A 7 1 0 A Virtualpre-arcingtime Prospective short-circuit current p c 103 2 64 1048 10 2 4 6 2 0 0 A 10 I2_10881 4 3 2 64 1058 2 2 4 6 105 2 5 0 A [A] [ A ] 3 5 0 A 4 0 0 / 4 5 0 A 5 2 5 A 6 3 0 A 7 1 0 A Prospective short-circuit current Unlimited peak values: DC component 50 % DC component 0 % Let-throughcurrent 0 500 1 15001000 w A [ V ] 2000 Correctionfactor 0.2 0.4 0.6 0.8 ADA94-5029b Recovery voltage 0 400 800 1200 1600 2000 2400 800 2400 4000 0 s w [ V ] [V] I2_10880 400 2000 2800 3200 3600 1200 1600 Peakarcvoltage Recovery voltage Û www.dienhathe.xyz www.dienhathe.vn
  • 46. Semiconductor Fuses LV HRC SITOR Fuse Links Rated voltage 2500 V AC 2/46 Siemens ET B1 T · 2007 ■Technical specifications ■Selection and ordering data For dimensional drawings, see pages 2/48 and 2/49. 1) M12 screw connection Type 3NE9 632-1 3NE9 634-1 3NE9 636-1A Operational class (IEC 60269) aR Rated voltage Un V AC 2500 Rated current In A 400 500 630 Melting I2 t value I2 ts (tvs = 1 ms) A2 s 81000 170000 385000 Breaking I2 t value I2 tA at Un A2 s 620000 1270000 2800000 Temperature rise at In (body center) K 160 180 198 Power dissipation at In W 205 235 275 Varying load factor WL 1.0 Weight approx. kg 2.5 Size In Operational class Order No. Weight 1 unit approx. PS*/ P. unit A kg Unit(s) Rated voltage 2500 V AC with bolt-on links Mounting dimensions: 260 mm 3 4001) aR 3NE9 632-1 2.542 1 5001) 3NE9 634-1 2.550 1 6301) 3NE9 636-1A 2.557 1 * You can order this quantity or a multiple thereof. www.dienhathe.xyz www.dienhathe.vn
  • 47. Semiconductor Fuses LV HRC SITOR Fuse Links Rated voltage 2500 V AC 2/47Siemens ET B1 T · 2007 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 ■Characteristic curves Series 3NE9 63. Size: 3 Operational class: aR Rated voltage: 2500 V AC Rated current: 400 ... 630 A Time/current characteristics diagram Let-through characteristics (current limitation at 50 Hz) Correction factor kA for breaking I2 t value Peak arc voltage p vs 2102 10-3 2 4 6 10-2 64 1038 2 64 1048 2 4 2 4 6 10-1 2 4 6 100 2 4 6 101 2 4 6 102 2 4 6 103 2 4 6 104 I2_10882 6 1058 [s] [ A ] 4 0 0 A 5 0 0 A 6 3 0 A Virtualpre-arcingtime Prospective short-circuit current p c 103 2 64 1048 10 2 4 6 10 I2_10885 4 3 2 64 1058 2 2 4 6 105 [A] [ A ] 4 0 0 A 5 0 0 A 6 3 0 A Prospective short-circuit current Unlimited peak values: DC component 50 % DC component 0 % Let-throughcurrent 0 400 800 1200 1600 2000 2400 1 2800 A w [ V ] Correctionfactor Recovery voltage 0.2 0.4 0.6 0.8 0 500 1000 1500 2000 2500 3000 6000 0 s w [ V ] [V] I2_10884 2000 1000 3000 4000 5000 Peakarcvoltage Recovery voltage Û www.dienhathe.xyz www.dienhathe.vn
  • 48. Semiconductor Fuses LV HRC SITOR Fuse Links Configuration Aids 2/48 Siemens ET B1 T · 2007 ■Dimensional drawings 3NC2 4.., 3NC8 4.. 3NC2 4..-3, 3NC8 4..-3 3NE8 7..-1 3NE1 8..-0 3NE1 02.-0, 3NE1 02.-2, 3NE8 0..-1 3NE1 2..-0, 3NE1 2..-2 3NE1 33.-0, 3NE1 33.-2 3NE1 43.-0, 3NE1 43.-1 3NE1 4..-2 70 60 1814 12 81 10 6 70 108 140 I2 11336 71,5 11,5 18 70 60 12 1814 12 14 81 10 6 70 108 140 71,5 11,5 11,5 I2_11337 8,5 8,5 78 100 54 I2_11343 21 40 6 79,9 50,3 2,3 I2_06713 10 53,3 20 35,8 15 21 40,5 53,8 53 49,4 2,210 I2_06714 6 48 3079 60 35,8 15 10 40,5 52 52 73 66,5 3 I2_06715 25 63,5 6 135 I2_07071 47,5 25 72 60 60 6 10 66,5 3 73 149 70151 I2_06717 10 6 60,4 82,1 68 2,5 73 70 32 73151 I 2 _ 1 2 4 2 7 10 6 6 0 , 4 8 2 , 1 68 2,5 73 7 3 3 2 www.dienhathe.xyz www.dienhathe.vn
  • 49. Semiconductor Fuses LV HRC SITOR Fuse Links Configuration Aids 2/49Siemens ET B1 T · 2007 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 3NE4 3..-0B, 3NE4 337 3NE4 1.. 60 71 48 10 6 60 I2_11338 10,5 14,511,5 12,5 14,511,5 12,5 107,5 141,5 73,5 10,5 10 30 6 15 14 47 65 125 58 I2_06450 3NE3 4.., 3NE3 6.., 3NE3 637-1, 3NE5 4.., 3NE5 433-1, 3NE5 6.., 3NE7 4.., 3NE7 6.., 3NE9 63.-1 Type Dimensions a b c d 3NE3 4.., 3NE3 6.. 160 128 11.5 91.5 3NE3 635-6 see adjacent drawing 3NE3 637-1 170 138 13 91.5 3NE5 4.., 3NE7 4.., 240 208 11.5 171.5 3NE7 6.. 3NE5 433-1, 240 208 13 171.5 3NE7 6..-1 3NE5 6.. 200 168 11.5 131.5 3NE9 63.-1 287 255 13 220 10 6 70 b a c c 70 60 81 14 18 12 14 18 12 d I2_11339 3NE3 22., 3NE3 23., 3NE3 3.. Type Dimensions a b c d e f g 3NE3 22., 3NE3 23. 135 31 12.5 40.5 13.5 52 63.5 3NE3 3.. 149 38 19.5 47.5 15 60 72 3NE3 635-6 I2_06473a 10 f 673 a 10,5 c110 b 12,512,5 10,5 d e f g 10 70 M10 Æ28 70 96 109 10 81,5 I2_11340 www.dienhathe.xyz www.dienhathe.vn
  • 50. Semiconductor Fuses SITOR Fuse Links for Special Applications For rectifiers in electrolysis systems 2/50 Siemens ET B1 T · 2007 ■Technical specifications 1) Maximum tightening torque: - M10 thread (with indicator): 40 Nm - M10 capped thread: 50 Nm, depth of screw entry ≥ 9 mm - M24 × 1.5 thread: 60 Nm. 2) Temperature of water-cooled busbar max. +45 C. 3) Maximum tightening torque: M10 capped thread: 35 Nm, depth of screw entry ≥ 9 mm. 4) Cooling air speed ≥ 2 m/s. 5) Bottom (cooled) connection max. +60 °C, top connection (M10) max. +110 °C. ■Selection and ordering data For dimensional drawings, see page 2/59. Type 3NC5 5311) 3NC5 8411) 3NC5 8401) 3NC5 8381) Operational class (IEC 60269) aR Rated voltage Un V AC 800 1000 Rated current In A 3502) 6302) 6002) 8002) Melting I2t value I2ts (tvs = 1 ms) A2 s 66000 185000 360000 Breaking I2t value I2tA at Un A2 s 260000 888000 1728000 Temperature rise at In (body center) K 200 110 130 Power dissipation at In W 80 145 150 170 Varying load factor WL 0.9 Weight approx. kg 0.67 1.2 1.4 1.2 Type 3NE9 440-6 3NE9 450 3NE6 437 3NE6 444 3NE9 450-7 3NE6 437-7 Operational class (IEC 60269) gR aR Rated voltage Un V AC 600 900 600 900 Rated current In 3) A 850 12504) 7104) 9004) 12505) 7105) Melting I2 t value I2 ts (tvs = 1 ms) A2 s 400000 100000 400000 100000 Breaking I2 t value I2 tA at Un A2 s 2480000 620000 1920000 2480000 620000 Temperature rise at In (body center) K 74 80 105 110 Power dissipation at In W 85 210 150 170 210 150 Varying load factor WL 1.0 0.9 Weight approx. kg 1.0 1.1 1.0 In Un Opera- tional class Order No. Weight 1 unit approx. PS*/ P. unit A V AC kg Unit(s) For rectifiers in electrolysis systems for screwing onto water-cooled busbars 350 800 aR 3NC5 531 0.671 1/3 600 1000 3NC5 840 1.408 3 630 800 3NC5 841 1.185 3 800 1000 3NC5 838 1.196 3 710 900 3NE6 437-7 1.168 3 1250 600 3NE9 450-7 1.245 3 For air-cooled rectifiers in electrolysis systems 710 800 gR 3NE6 437 1.093 3 850 1000 3NE9 440-6 1.082 3 900 1000 aR 3NE6 444 1.175 3 1250 800 3NE9 450 1.114 3 * You can order this quantity or a multiple thereof. www.dienhathe.xyz www.dienhathe.vn
  • 51. Semiconductor Fuses SITOR Fuse Links for Special Applications For rectifiers in electrolysis systems 2/51Siemens ET B1 T · 2007 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 ■Characteristic curves Series 3NC5 531, 3NC5 8.. Operational class: aR Rated voltage: 800 V AC (350 A, 600 A), 1000 V AC (600 A, 800 A) Rated current: 350 ... 800 A Time/current characteristics diagram Correction factor kA for breaking I2t value Let-through characteristics (current limitation at 50 Hz) Peak arc voltage p vs 2102 10-3 2 4 6 10-2 64 1038 2 64 1048 2 4 2 4 6 10-1 2 4 6 100 2 4 6 101 2 4 6 102 2 4 6 103 2 4 6 104 I2_11432 6 1058 [s] [A] 8 0 0 A6 3 0 A 3 5 0 A 6 0 0 A Virtualpre-arcingtime Prospective short-circuit current 0 200 400 600 1 800 1000 A w [V] I2_11434 3 5 0 A 6 3 0 A 6 0 0 A 8 0 0 A Correctionfactor 0.8 0.6 0.4 0.2 Recovery voltage c p [A] [A] I2_11433 103 10 2 4 6 2 4 6 4 105 103 105 2 4104 2 64 82 64 8 3 5 0 A 6 0 0 A 6 3 0 A 8 0 0 A Let-throughcurrent Prospective short-circuit current Unlimited peak values: DC component 50 % DC component 0 % 0 200 400 600 800 1000 1200 400 1200 1600 2000 0 s w [ V ] [V] I2_11435 200 600 800 1000 1400 1800 6 0 0 A 8 0 0 A 3 5 0 A 6 3 0 A Peakarcvoltage Recovery voltage Û www.dienhathe.xyz www.dienhathe.vn
  • 52. Semiconductor Fuses SITOR Fuse Links for Special Applications For rectifiers in electrolysis systems 2/52 Siemens ET B1 T · 2007 Series 3NE6 4.., 3NE9 4.. Operational class: aR, gR Rated voltage: 600 V AC (1250 A), 800 V AC (710 A, 1250 A,), 900 V AC (710 A) Rated current: 710 ... 1250 A Time/current characteristics diagrams p vs 2102 10-3 2 4 6 10-2 64 1038 2 64 1048 2 4 2 4 6 10-1 2 4 6 100 2 4 6 101 2 4 6 102 2 4 6 103 2 4 6 104 I2_11436 6 1058 [s] [A] 8 5 0 A 7 1 0 A Virtualpre-arcingtime Prospective short-circuit current p vs 2102 10-3 2 4 6 10-2 64 1038 2 64 1048 2 4 2 4 6 10-1 2 4 6 100 2 4 6 101 2 4 6 102 2 4 6 103 2 4 6 104 I2_11437 6 1058 [s] [A] 1 2 5 0 A 9 0 0 A Virtualpre-arcingtime Prospective short-circuit current www.dienhathe.xyz www.dienhathe.vn
  • 53. Semiconductor Fuses SITOR Fuse Links for Special Applications For rectifiers in electrolysis systems 2/53Siemens ET B1 T · 2007 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 Series 3NE6 4.., 3NE9 4.. Operational class: aR, gR Rated voltage: 600 V AC (1250 A), 800 V AC (710 A, 1250 A), 900 V AC (710 A) Rated current: 710 ... 1250 A Let-through characteristics (current limitation at 50 Hz) c p [A] [A] I2_11438 103 10 2 4 6 2 4 6 4 105 103 105 2 4104 2 64 82 64 8 7 1 0 A 8 5 0 / 9 0 0 / 1 2 5 0 A Let-throughcurrent Prospective short-circuit current Unlimited peak values: DC component 50 % DC component 0 % Correction factor kA for breaking I2 t value Peak arc voltage 0 200 400 600 1 800 1000 A w [V] I2_11439 9 0 0 A 8 0 0 A 1 2 5 0 A 7 1 0 A Correctionfactor 0.8 0.6 0.4 0.2 Recovery voltage 0 200 400 600 800 1000 1200 400 1200 1600 2000 0 s w [ V ] [V] I2_11440 200 600 800 1000 1400 1800 8 5 0 A 7 1 0 A 9 0 0 A 1 2 5 0 A Peakarcvoltage Recovery voltage Û www.dienhathe.xyz www.dienhathe.vn
  • 54. Semiconductor Fuses SITOR Fuse Links for Special Applications For SITOR thyristor sets 2/54 Siemens ET B1 T · 2007 ■Technical specifications 1) Maximum tightening torque: M10 capped thread: 35 Nm, depth of screw entry ≥ 9 mm. 2) Cooling air speed ≥ 0.5 m/s. In the case of natural air cooling, reduction of 5 %. ■Selection and ordering data For dimensional drawings, see page 2/59. Type 3NE4 117-5 3NE4 121-5 3NE4 146-5 3NE3 525-51) 3NE3 535-51) Operational class (IEC 60269) gR aR Rated voltage Un V AC 1000 800 1000 Rated current In A 50 100 170 2002) 4502) Melting I2t value I2ts (tvs = 1 ms) A2 s 135 900 7370 7150 64500 Breaking I2t value I2tA at Un A2 s 1100 7400 60500 44000 395000 Temperature rise at In (body center) K 95 135 142 75 130 Power dissipation at In W 20 35 43 50 90 Varying load factor WL 0.85 Weight approx. kg 0.28 0.7 Type 3NE4 327-6B1) 3NE4 330-6B1) 3NE4 333-6B1) 3NE4 334-6B1) 3NE4 337-61) Operational class (IEC 60269) aR Rated voltage Un V AC 800 Rated current In A 250 315 450 500 710 Melting I2 t value I2 ts (tvs = 1 ms) A2 s 3600 7400 29400 42500 142000 Breaking I2 t value I2 tA at Un A2 s 29700 60700 191000 276000 923000 Temperature rise at In (body center) K 175 170 190 195 170 Power dissipation at In W 105 120 140 155 Varying load factor WL 0.85 0.95 Weight approx. kg 0.65 In Un Opera- tional class Order No. Weight 1 unit approx. PS*/ P. unit A V AC kg Unit(s) For SITOR 6QG10 thyristor sets 200 1000 aR 3NE3 525-5 0.744 3 450 3NE3 535-5 0.746 3 For SITOR 6QG11 thyristor sets 50 1000 gR 3NE4 117-5 0.303 1/3 100 aR 3NE4 121-5 0.309 1/3 170 800 3NE4 146-5 0.311 1/3 For SITOR 6QG12 thyristor sets 250 800 aR 3NE4 327-6B 0.692 3 315 3NE4 330-6B 0.688 3 450 3NE4 333-6B 0.690 3 500 3NE4 334-6B 0.688 3 710 3NE4 337-6 0.689 3 * You can order this quantity or a multiple thereof. www.dienhathe.xyz www.dienhathe.vn
  • 55. Semiconductor Fuses SITOR Fuse Links for Special Applications For SITOR thyristor sets 2/55Siemens ET B1 T · 2007 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 ■Characteristic curves Series 3NE3 5.5-5, 3NE4 1..-5 Operational class: aR, gR Rated voltage: 800 V AC (170 A), 1000 V AC (50 A, 100 A, 200 A, 450 A) Rated current: 50 ... 450 A Time/current characteristics diagram Correction factor kA for breaking I2t value Let-through characteristics (current limitation at 50 Hz) Peak arc voltage p vs 2101 10-3 2 4 6 10-2 64 1028 2 64 1038 2 4 2 4 6 10-1 2 4 6 100 2 4 6 101 2 4 6 102 2 4 6 103 2 4 6 104 I2_11441 6 1048 [s] [A] 1 7 0 A 5 0 A 1 0 0 A 2 0 0 A 4 5 0 A Virtualpre-arcingtime Prospective short-circuit current 0 200 400 600 1 800 1000 A w [V] I2_11443 5 0 / 1 0 0 A 1 7 0 A 2 0 0 / 4 5 0 A Correctionfactor 0.8 0.6 0.4 0.2 Recovery voltage 102 2 64 108 10 2 4 6 3 c p [A] [A] 102 3 2 64 108 4 2 64 108 5 2 4 I2_11442 10 2 4 6 4 2 4 1 0 0 A 2 0 0 A 1 7 0 A 5 0 A 4 5 0 A Let-throughcurrent Prospective short-circuit current Unlimited peak values: DC component 50 % DC component 0 % 0 200 400 600 800 1000 1200 400 1200 1600 2000 0 s w [ V ] [V] I2_11444 200 600 800 1000 1400 1800 2 0 0 A 1 7 0 A ÛPeakarcvoltage Recovery voltage www.dienhathe.xyz www.dienhathe.vn
  • 56. Semiconductor Fuses SITOR Fuse Links for Special Applications For SITOR thyristor sets 2/56 Siemens ET B1 T · 2007 Series 3NE4 3..-6B, 3NE4 337-6 Operational class: aR Rated voltage: 800 V AC Rated current: 250 ... 710 A Time/current characteristics diagram Correction factor kA for breaking I2 t value Let-through characteristics (current limitation at 50 Hz) Peak arc voltage p vs 2102 10-3 2 4 6 10-2 64 1038 2 64 1048 2 4 2 4 6 10-1 2 4 6 100 2 4 6 101 2 4 6 102 2 4 6 103 2 4 6 104 I2_11445 6 1058 [s] [A] 7 1 0 A 5 0 0 A 4 5 0 A 3 1 5 A 2 5 0 A Virtualpre-arcingtime Prospective short-circuit current 0 100 200 300 400 500 600 1 700 800 A w [ V ] 3 1 5 A 4 5 0 A Correctionfactor Recovery voltage 0.2 0.4 0.6 0.8 c p [A] [A] I2_11446 103 10 2 4 6 2 4 6 4 105 103 105 2 4104 2 64 82 64 8 2 5 0 A 3 1 5 A 4 5 0 A 5 0 0 A 7 1 0 A Let-throughcurrent Prospective short-circuit current Unlimited peak values: DC component 50 % DC component 0 % 0 200 400 600 800 1000 1200 400 1200 1600 2000 0 s w [ V ] [V] I2_11448 200 600 800 1000 1400 1800 Peakarcvoltage Recovery voltage Û www.dienhathe.xyz www.dienhathe.vn
  • 57. Semiconductor Fuses SITOR Fuse Links for Special Applications For railway supply rectifiers 2/57Siemens ET B1 T · 2007 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 ■Technical specifications ■Selection and ordering data For dimensional drawings, see page 2/59. Type 3NC7 327-2 3NC7 331-2 Operational class (IEC 60269) aR Rated voltage Un V AC 680 Rated current In A 250 350 Melting I2t value I2ts (tvs = 1 ms) A2 s 244000 550000 Breaking I2t value I2tA at Un A2 s 635000 1430000 Temperature rise at In (body center) K 45 66 Power dissipation at In W 25 32 Varying load factor WL 0.9 Weight approx. kg 0.7 In Un Opera- tional class Order No. Weight 1 unit approx. PS*/ P. unit A V AC kg Unit(s) For railway supply rectifiers 250 680 aR 3NC7 327-2 0.725 3 350 3NC7 331-2 0.740 3 * You can order this quantity or a multiple thereof. www.dienhathe.xyz www.dienhathe.vn
  • 58. Semiconductor Fuses SITOR Fuse Links for Special Applications For railway supply rectifiers 2/58 Siemens ET B1 T · 2007 ■Characteristic curves Series 3NC7 3..-2 Operational class: aR Rated voltage: 680 V AC Rated current: 250 A, 350 A Time/current characteristics diagram Correction factor kA for breaking I2 t value Let-through characteristics (current limitation at 50 Hz) Peak arc voltage p vs 2102 10-3 2 4 6 10-2 64 1038 2 64 1048 2 4 2 4 6 10-1 2 4 6 100 2 4 6 101 2 4 6 102 2 4 6 103 2 4 6 104 I2_11449 6 1058 [s] [A] 2 5 0 A 3 5 0 A Virtualpre-arcingtime Prospective short-circuit current 0 100 200 300 400 500 600 1 700 800 A w [ V ] Correctionfactor Recovery voltage 0.2 0.4 0.6 0.8 c p [A] [A] I2_11450 103 10 2 4 6 2 4 6 4 105 103 105 2 4104 2 64 82 64 8 2 5 0 A 3 5 0 A Let-throughcurrent Prospective short-circuit current Unlimited peak values: DC component 50 % DC component 0 % 0 200 400 600 800 1000 1200 400 1200 1600 2000 0 s w [ V ] [V] I2_11452 200 600 800 1000 1400 1800 ÛPeakarcvoltage Recovery voltage www.dienhathe.xyz www.dienhathe.vn
  • 59. Semiconductor Fuses SITOR Fuse Links for Special Applications Configuration Aids 2/59Siemens ET B1 T · 2007 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 ■Dimensional drawings 3NC5 531 3NC5 8.. Type Dimensions a b c 3NC5 838, 3NC5 841 98 88.5 25 3NC5 844 119 109.5 20.5 3NE6 4.., 3NE9 4.., 3NE6 4..-7, 3NE9 4..-7 Type Dimensions a b 3NE6 437, 3NE9 440-6, 3NE9 450 89 76 3NE6 444 99 86 50 M10 M10 28 50 SW41 91 9 24,5 0,3 I2_11369 73 M10 40 M24 M10 SW41 b a c 11 I2_11370 10 70 M10 28 70 b a 10 81,5 I2_11371 70 M10 28 70 100 125 83 10 11 10 81,5 75,5 I2_11372 3NE3 5..-5 3NE4 3..-6B, 3NE4 337-6 3NE4 1..-5 3NC7 3..-2 7755 15 60 73 60 M10 20 10,5 82,5 I2_11373 I2_11374 60 M10 20 60 76 77 15 66 47 52 53 3010 54 57 62 26 40 10,4 I2_11375 12,5 57 68 119 57 30 7 79 10,510,5 I2_11376 www.dienhathe.xyz www.dienhathe.vn
  • 60. Semiconductor Fuses SITOR Cylindrical Fuse Links SITOR cylindrical fuse links 2/60 Siemens ET B1 T · 2007 ■Overview Load rating of SITOR cylindrical fuses without strikers in fuse holders/fuse switch disconnectors/fuse disconnectors1)2) Fuse tongs: 3NC1 000 Load rating of SITOR cylindrical fuses with strikers in fuse holders/fuse switch disconnectors/fuse disconnectors1)2) 1) Fuse holders according to IEC 60269-3, UL 512, fuse switch disconnectors (10 x 38, 14 x 51) according to IEC 60947-3, fuse disconnectors (22 x 58) according to IEC 60947-3 2) The values Imax apply for "stand-alone operation". If several devices are butt-mounted and/or subject to unfavorable cooling conditions, these values may be reduced still further. For SITOR fuse links Rated voltage Rated current Required conductor cross- section Cylindrical fuse bases Fuse holders/fuse switch disconnectors/ fuse disconnectors1) 1-pole 2-pole 3-pole 1-pole 2-pole 3-pole In Cu Type Imax Type Imax Type Imax Type Imax Type Imax Type Imax V AC A mm2 A A A A A A Size 10 x 38 3NC1 003 600 3 1 3NC1 038-1 3 3NC1 038-2 / 2 × 3NC1 038-1 3 3NC1 038-3 / 3 × 3NC1 038-1 3 3NC1 091 3 3NC1 092 / 2 × 3NC1 091 3 3NC1 093 / 3 × 3NC1 091 3 3NC1 006 6 1 6 6 6 6 6 6 3NC1 008 8 1 8 8 8 8 8 8 3NC1 010 10 1.5 10 10 10 10 10 10 3NC1 012 12 1.5 12 12 12 12 12 12 3NC1 016 16 2.5 16 16 16 16 16 16 3NC1 020 20 2.5 20 20 20 20 20 20 3NC1 025 25 4 25 24 24 25 25 25 3NC1 032 32 6 32 28 28 30 32 29 Size 14 x 51 3NC1 401 660 1 1 3NC1 451-1 1 – – 3NC1 491 1 3NC1 492 / 2 × 3NC1 491 1 3NC1 493 / 3 × 3NC1 491 1 3NC1 402 2 1 2 2 2 2 3NC1 403 3 1 3 3 3 3 3NC1 404 4 1 4 4 4 4 3NC1 405 690 5 1 5 5 5 5 3NC1 406 6 1 6 6 6 6 3NC1 410 10 1.5 10 10 10 10 3NC1 415 15 1.5 15 15 15 15 3NC1 420 20 2.5 20 20 20 20 3NC1 425 25 4 25 25 24 23 3NC1 430 30 6 30 28 27 25 3NC1 432 32 6 32 31 30 30 3NC1 440 40 10 40 38 37 36 3NC1 450 50 10 50 48 46 44 Size 22 x 58 3NC2 220 690 20 2.5 3NC2 258-1 20 – – 3NC2 291 20 3NC2 292 / 2 × 3NC2 291 20 3NC2 293 / 3 × 3NC2 291 20 3NC2 225 25 4 25 25 25 25 3NC2 232 32 6 32 32 32 32 3NC2 240 40 10 40 40 39 38 3NC2 250 50 10 50 50 48 46 3NC2 263 63 16 63 60 58 56 3NC2 280 80 25 80 74 71 69 3NC2 200 600 100 35 100 95 90 85 For SITOR fuse links Rated voltage Rated current Required conduc- tor cross-section Fuse holders/fuse switch disconnectors/fuse disconnectors1) 1-pole 2-pole 3-pole In Cu Type Imax Type Imax Type Imax V AC A mm2 A A A Size 14 x 51 3NC1 410-5 690 10 1.5 3NC1 491 10 3NC1 492/ 2 × 3NC1 491-5 10 3NC1 493/ 3 × 3NC1 491-5 10 3NC1 415-5 15 1.5 15 15 15 3NC1 420-5 20 2.5 20 20 20 3NC1 425-5 25 4 25 25 25 3NC1 430-5 30 6 30 30 30 3NC1 432-5 32 6 32 32 31 3NC1 440-5 40 10 38 35 34 3NC1 450-5 50 10 48 46 44 Size 22 x 58 3NC2 220-5 690 20 2.5 3NC2 291 20 3NC2 292/ 2 × 3NC2 291-5 20 3NC2 293/ 3 × 3NC2 291-5 20 3NC2 225-5 25 4 25 25 25 3NC2 232-5 32 6 32 31 30 3NC2 240-5 40 10 40 39 37 3NC2 250-5 50 10 45 43 42 3NC2 263-5 63 16 59 55 52 3NC2 280-5 80 25 71 69 68 3NC2 200-5 600 100 35 94 90 85 www.dienhathe.xyz www.dienhathe.vn
  • 61. Semiconductor Fuses SITOR Cylindrical Fuse Links SITOR cylindrical fuse links 2/61Siemens ET B1 T · 2007 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 ■Technical specifications Type 3NC1 003 3NC1 006 3NC1 008 3NC1 010 3NC1 012 3NC1 016 3NC1 020 3NC1 025 3NC1 032 Operational class (IEC 60269) aR Rated voltage Un V 600 V AC/400 V DC Rated current In A 3 6 8 10 12 16 20 25 32 Melting I2t value I2ts (tvs = 1 ms) A2 s 3 4 6 9 15 25 34 60 95 Breaking I2t value I2tA at Un A2 s 8 20 30 60 110 150 200 250 500 Temperature rise at In (body center) K 30 25 40 50 60 80 90 110 Power dissipation at In W 1.2 1.5 2 2.5 3 3.5 4.8 6 7.5 Weight approx. kg 0.01 Type 3NC1 401 3NC1 402 3NC1 403 3NC1 404 3NC1 405 3NC1 406 3NC1 410 Operational class (IEC 60269) aR Rated voltage Un V 660 V AC/700 V DC 690 V AC/700 V DC Rated current In A 1 2 3 4 5 6 10 Melting I2 t value I2 ts (tvs = 1 ms) A2 s – 1.6 – 3.6 Breaking I2 t value I2 tA at Un A2 s 1.2 10 15 25 9 12 20 Temperature rise at In (body center) K 90 30 40 50 20 30 50 Power dissipation at In W 5 3 2.5 3 1.5 1.5 4 Certification according to UL 248-13 Weight approx. kg 0.02 Type 3NC1 415 3NC1 420 3NC1 425 3NC1 430 3NC1 432 3NC1 440 3NC1 450 Operational class (IEC 60269) aR Rated voltage Un V 690 V AC/700 V DC Rated current In A 15 20 25 30 32 40 50 Melting I2 t value I2 ts (tvs = 1 ms) A2 s 10 26 44 58 95 110 220 Breaking I2 t value I2 tA at Un A2 s 75 120 250 300 700 900 1800 Temperature rise at In (body center) K 60 70 80 100 110 Power dissipation at In W 5.5 6 7 9 7.6 8 9 Certification according to UL 248-13 Weight approx. kg 0.02 Type 3NC2 220 3NC2 225 3NC2 232 3NC2 240 3NC2 250 3NC2 263 3NC2 280 3NC2 200 Operational class (IEC 60269) aR Rated voltage Un V 690 V AC/700 V DC 600 V AC/700 V DC Rated current In A 20 25 32 40 50 63 80 100 Melting I2 t value I2 ts (tvs = 1 ms) A2 s 34 50 80 100 185 310 620 1250 Breaking I2 t value I2 tA at Un A2 s 220 300 450 700 1350 2600 5500 8000 Temperature rise at In (body center) K 40 50 65 80 90 100 110 Power dissipation at In W 4.6 5.6 7 8.5 9.5 11 13.5 16 Certification according to UL 248-13 Weight approx. kg 0.06 www.dienhathe.xyz www.dienhathe.vn
  • 62. Semiconductor Fuses SITOR Cylindrical Fuse Links SITOR cylindrical fuse links 2/62 Siemens ET B1 T · 2007 1) UL recognized 1) These devices have been specially developed for the application of SITOR fuse links with regard to heat tolerance with heat dissipation and are there- fore not recommended for standard applications. Type 3NC1 410-5 3NC1 415-5 3NC1 420-5 3NC1 425-5 3NC1 430-5 3NC1 432-5 3NC1 440-5 3NC1 450-5 Operational class (IEC 60269) aR Rated voltage Un V 690 AC/700 DC1) Rated current In A 10 15 20 25 30 32 40 50 Melting I2 t value I2 ts (tvs = 1 ms) A2 s 3.6 9 26 47 58 68 84 200 Breaking I2t value I2tA at Un A2 s 90 100 500 400 500 600 900 2000 Temperature rise at In (body center) K 50 60 70 80 80 80 100 110 Power dissipation at In W 4 5.5 6 7 9 7.6 8 9 Certification according to UL 248-13 Weight approx. kg 0.02 Type 3NC2 220-5 3NC2 225-5 3NC2 232-5 3NC2 240-5 3NC2 250-5 3NC2 263-5 3NC2 280-5 3NC2 200-5 Operational class (IEC 60269) aR Rated voltage Un V 690 AC/700 DC1) 600 AC/700 DC1) Rated current In A 20 25 32 40 50 63 80 100 Melting I2t value I2ts (tvs = 1 ms) A2 s 19 34 54 68 135 280 600 1100 Breaking I2t value I2tA at Un A2 s 240 350 500 800 1500 3000 6000 8500 Temperature rise at In (body center) K 40 50 65 80 90 100 110 110 Power dissipation at In W 5 6 8 9 9.5 11 13.5 16 Certification according to UL 248-13 Weight approx. kg 0.06 Fuse bases Sizes 10 x 38 14 x 51 22 x 58 Rated voltage V AC 600 690 V DC 600 690 Rated current In A 32 50 100 Fuse holders/fuse switch disconnectors/ fuse disconnectors Classifications • According to IEC 60269-3, UL 512 Fuse holders Fuse holders • According to IEC 60947-3 Fuse switch disconnectors Fuse disconnectors Sizes 10 x 38 14 x 51 with and without alarm switches 22 x 58 with and without alarm switches Rated voltage V AC 690 Rated current In A 32 50 100 Max. power dissipation of fuse link1) W 3 (6 mm2) 4.3 (10 mm2) 5 (10 mm2) 6.5 (25 mm2) 9.5 (35 mm2) 11 (50 mm2) Feeder terminals mm2 1.5 ... 25 1.5 ... 35 4 ... 50 Operational class according to IEC 60947-3 22B/32 A/400 V AC 22B/10 A/690 V AC 22B/50 A/400 V AC 22B/20 A/690 V AC 20B/690 V AC Rated conditional short-circuit current • At 400 V kA 50 (32 A gG) 100 (50 A gG) 100 (100 A gG) 80 (80 A gG) Approvals UUS s www.dienhathe.xyz www.dienhathe.vn