IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE)
e-ISSN: 2278-1676,p-ISSN: 2320-3331, Volume 11, Issue 1 Ver. IV (Jan. – Feb. 2016), PP 68-75
www.iosrjournals.org
DOI: 10.9790/1676-1101046875 www.iosrjournals.org 68 | Page
Power Transformer Differential Relay Inrush Restraint Setting
Applications
J.O. Aibangbee1
, S.O. Onohaebi 2
1
department Of Electrical &Computer Engineering, Bells University Of Technology, Ota, Nigeria
2
department Of Electrical & Electronic Engineering, University Of Benin, Nigeria
Abstract: This Paper Involves The Study Of Power Transformer Differential Relay Inrush Restraint Settings
Applications. Criteria For The Setting And Testing Of Transformers Differential Relays Was Presented.The
Setting Of The Inrush Restraint On A Per-Phase Basis On The Protected Transformerwas Performed. The
System Was Simulated Using Alternative Transient Program (Atp) Software To Examine The Level Of The
Second Harmonic Presents. The Differential Relay Element Set Point For Inrush Restraint Current Was
Achieved At 15% Of Second Harmonics And 35% Of Fifth Harmonics. These Settings Provide High-Speed
Clearing Of Transformer Faults And Proper Restraint For Inrush Events.It’s Also A Good Margin Of Security
For Energization Of The Transformer Where The Second Harmonic Inrush Current Levels Are Present. These
Settings Were Successful Restraining The Differential Element When Faced With A Fault Recovering
Magnetizing Inrush Event. The Restraint Criterion Was Met On All Phases, As The Transformer Do Not
Tripped During Energization Or Sympathetic Inrush. The Setting Is Sensitive Enough To Recognize
Magnetizing Inrush Current Even With Low Levels Of Second Harmonics; And Selective To Distinguish
Between An Inrush Event And Other Events That May Produce Second Harmonic Current.
Keywords: Power Transformer, Differential Relay, Harmonic Restraint, Energization, Magnetizing Inrush
Current, Relay Setting, Current Transformer, Differential Protection.
I. Introduction
Electric Power Utilities Have Traditionally Used Electromechanical Differential Relay For The
Protection Of Power Transformers In The Past, And Many Such Relays Are Still In Use In Power Systems
Today[1]. The Basic Protection For Power Transformers Is Differentialprotection With Second Harmonic
Restraint Used To Block Thedifferential Element During Inrush Events For The Transformer[2].Differential
Protection Is One Of The Most Reliable And Popular Techniques In Power System Protection. Differential
Protection Is A Fast, Selective Method Of Protection Against Short Circuits In Transformers, And Is The
Standard Protection Used By Transmission Company Of Nigeria (Tcn) To Protect Transformers. Differential
Protection Is A Practical Application Of Kirchhoff’s Current Law. The Sum Of The Currents Entering The
Transformer Should Equal The Sum Of The Currents Leaving The Transformer.If The Net Sum Of The
Currents That Enter And The Currents That Leave A Protection Zone Is Essentially Zero, It Is Concluded That
There Is No Fault In The Protection Zone. However, If The Net Sum Is Not Zero, The Differential Protection
Concludes That A Fault Exists In The Zone And Takes Steps To Isolate The Zone From The Restof The
System. Differential Protection Compares The Measured Currents Entering And Leaving The Transformer To
Create A Differential Current. With The Ideal Transformer Of Figure 1, And Assuming Ideal Current
Transformers, The Differential Current Is Zero When Current Is Flowing Through The Transformer.
Differential Current Greater Than Zero Indicate An Internal Fault Condition. In Practice, The Differential
Current For A Normally Operating Transformer Is Always Greater Than Zero Due To Ct Measurement Error
And The Position Of The Load Tap Changer [3]. Misoperations Can Occur During Energization Of A
Transformer Due To Failure Of The Harmonic Restraint Function. An External Fault Can Also Trigger A
Misoperation During The Voltage Recovering Period, Causing The Differential Relay To Operate Immediately
After A Fault Is Cleared From The System.
Figure 1: Transformer Differential Protection Principle
Power Transformer Differential Relay Inrush Restraint Setting Applications
DOI: 10.9790/1676-1101046875 www.iosrjournals.org 69 | Page
There Are Two Common Situations Where Differential Protectionmay Incorrectly Declare An Internal
Fault Condition. One Conditionis Ct Saturation For A Fault Outside Of The Transformer Zone Ofprotection.
The Error In The Measured Signal Of The Saturatedct Results In A Significant Error In The Differential
Current. Theerroneous Differential Current May Result In Undesired Operationof The Differential Element For
An External Fault Condition. The Second Common Situation Is A Transformer Inrush Event.Some Operating
Situations Instantly Change The Operating Fluxof The Transformer Core, Requiring A Large Supply Of
Current.This Inrush Of Current Typically Occurs In Only One Winding Ofthe Transformer. Therefore Inrush
Currents May Produce Adifferential Current That Results In The Operation Of The Differentialprotection. This
Type Of Event Is Not A Fault Condition, So Thedifferential Protection Should Restrain From Operating For
Thiscondition. This Paper Intends To Discuss The Setting Of Inrush Current Due To Harmonic In Power
Transformers.
II. General Description
Any Event On The Power System That Causes A Significant Increase In The Magnetizing Voltage
Of The Transformer Core Results In Magnetizing Inrush Currents Flowing Into The Transformer. The Three
Most Common Events Areenergization Of Transformer, Magnetizing Inrush Current And Sympathetic Inrush.
These Are Discussed In The Session That Follows.
Energization Of Power Transformer.
This Is The Typical Event Where A Magnetizing Inrush Current Is Of Concern. The Excitation Voltage
On One Winding Is Increased From 0 To Full Voltage. The Transformer Core Typically Saturates, With The
Amount Of Saturation Determined By Transformer Design, System Impedance, The Remnant Flux In The Core,
And The Point On The Voltage Wave When The Transformer Is Energized. The Current Needed To Supply
This Flux May Be As Much As 20 Times The Full Load Rating Of The Transformer, With Typical Value For
Power Transformers For 6 Times The Full Load Rating [3]. Transformer Energization Is A Typical Cause Of
Inrush Currents, But Anytransient In The Transformer Circuit May Generate These Currents. Other Causes
Include Voltagerecovery After The Clearance Of An External Fault Or The Energization Of A Transformer In
Parallelwith A Transformer That Is Already In Service. The Magnitudes And Waveforms Of Inrush
Currentsdepend On A Multitude Of Factors, And Are Almost Impossible To Predict. The Followingsummarizes
The Main Characteristics Of Inrush Currents:
 Generally Contain Dc Offset, Odd Harmonics, And Even Harmonics [4, 5].
 Typically Composed Of Unipolar Or Bipolar Pulses, Separated By Intervals Of Very Low Current Values.
 Peak Values Of Unipolar Inrush Current Pulses Decrease Very Slowly. Time Constant Is Typically Much
Greater Than That Of The Exponentially Decaying Dc Offset Of Fault Currents.
 Second-Harmonic Content Starts With A Low Value And Increases As The Inrush Current Decreases.
Figure 2 Show Equivalent Circuit Of A Transformer. In An Idealtransformer, The Primary And
Secondary Currents Ip And Is Areequal Except For The Small Current Flowing Through The Shuntelement Of
The Magnetizing Branch. The Increase In Flux Causedby An Increase In The Exciting Voltage Draws More
Currentthrough The Magnetizing Branch. When The Transformer Isbeing Energized, This Current Flows
Through Only One Winding.
R , LP P R , LS S IS
Rb
ES
LmRm
Ip
Im
Ie
Ir
VS
Figure 2: Transformer Equivalent Circuits
During Inrush Events Other Than Energization, The Magnetizing Inrush Current May Appear In Both
Windings, With The Inrush Current More Prevalent In One Winding As Show Infigure 3.An External
Magnetizing Force Causes All The Magnetic Moments Of The Steel To Align With The Applied Magnetic
Field. In The Case Of Transformers, The Excitation Voltage Provides This Applied Magnetic Field. The
Alignment Of The Magnetic Moments Causes An Increase In Flux Density Greater Than That Of The External
Magnetic Field. The Steel Is Fully Saturated When All The Magnetic Moments Are Aligned With The Applied
Field. The Magnitude And Characteristic Of The Inrush Current Is Dependent On The Amount Of Saturation Of
The Transformer Core.
Power Transformer Differential Relay Inrush Restraint Setting Applications
DOI: 10.9790/1676-1101046875 www.iosrjournals.org 70 | Page
Figure 3: Magnetization Inrush Current Characteristic In A Power Transformer
Magnetizing Inrush Current
An External Fault May Significantly Reduce The System Voltage, And Therefore Reduce The
Excitation Voltage Of The Transformer. When This Fault Is Cleared, The Excitation Voltage Returns To The
Normal System Voltage Level. The Return Of Voltage May Force A Dc Offset On The Flux Linkages,
Resulting In Magnetizing Inrush Current. This Magnetizing Inrush Current Will Be Less Than That Of
Energization, As There Is No Remnant Flux In The Core[8]. The Current Measured By The Differential Relay
Will Be Fairly Linear Due To The Presence Of Load Current, And May Result In Low Levels Of Second
Harmonic Current.If The Transformer Were Reenergized At The Instant The Voltage Waveform Correspond To
The Residual Magnetic Density Within The Core, There Would Be A Smooth Continuation Of The Previous
Operation With No Transients. However, In Practice, The Instant When Switching Takes Place Cannot Be
Controlled, And A Magnetizing Transient Occurs, Almost Inevitably.
The Transient Generates A Current Known As Inrush Current. The Magnitude Of This Inrush Current
Can Be Several Times The Load Current And Flows Only On One Side Of The Differential Relay, Which
Tends To Operate If Some Form Of Restraint Is Not Provided. Inrush Currents Measured In Separate Phases Of
A Three-Phase Transformer May Differ Considerably Because Of The Following [9]:
 The Angles Of The Energizing Voltages Are Different In Different Phases.
 When The Delta-Connected Winding Is Switched-In, The Line Voltages Are Applied As The Magnetizing
Voltages.
 In The Later Case, The Line Current In A Given Phase Is A Vector Sum Of Two Winding Currents.
 Depending On The Core Type And Other Conditions, Only Some Of The Core Legs May Get Saturated.
Sympathetic Inrush.
Energizing A Transformer On The Power System Can Cause Sympathetic Magnetizing Inrush Currents
To Flow In An Already Energized Parallel Transformer.Energizing The Second Transformer As Shown In
Figure 4(A) Causes Voltage Drop Across The Resistance Of The Sourcefeeding The Transformers. This
Voltage Drop May Cause A Saturation Of The Already Energized Transformer In The Negative Direction. This
Saturation Causes Magnetizing Inrush Current To Supply The Flux. The Magnitude Of The Magnetizing Inrush
Currentis Generally Not As Severe As The Other Cases[5, 6,7].
Figure 4: (A) Sympathetic Inrush Circuit
Figure 4 (B) Shows A Typical Set Of Transformer Inrush Waveforms Captured During The
Energization Of The 60mva, 132kv/33kv Power Transformer, Energized At 132kvdelta/Star Transformer. Ib
And Ic Are Fully Offset, And Ia Shows The Typical Effects Of Interphase Coupling And Highly Non-
Sinusoidal. Magnetizing Inrush Current Under Normal Operating Conditions Is Very Small. However, When A
Transformer Is Energized After It Has Been Taken Out Of Service, The Magnetizing Inrush Current Can Be
Extremely Large As 10 Times Full Load Current For A Short Period (Say 5 Cycles). Closer Examination Of
Power Transformer Differential Relay Inrush Restraint Setting Applications
DOI: 10.9790/1676-1101046875 www.iosrjournals.org 71 | Page
These Waveforms, With Harmonic Analysis, Shows That All Of These Waveforms Have A Strong Second-
Harmonic Component, With A Fourth-Harmonic Component, The Next Most Prevalent Harmonic, In Two Out
Of The Three Phases [11, 12].
Figure 4: (B) Typical Set Of Transformer Inrush Waveforms
Analysis Of Differential Relays Setting
Harmonic Restraint Is The Classical Way To Restrain Relay Tripping. The Techniques Work On The
Principlethat The Magnetizing Inrush Current Contains High Levels Of Second Harmonic Current. The Current
For An Internal Transformer Fault Typically Has Very Low Levels Of Second Harmonic Current. The Simplest
Method Of Harmonic Restraint Uses The Magnitude Of The Second Harmonic In The Differential Current
Compared To The Magnitude Of The Fundamental Frequency Component In The Differential Current. Tripping
Of The Differential Element Is Blocked When This Ratio Exceeds An Adjustable Threshold. The Historical
Setting For Harmonic Restraint Is A Second Harmonic Ratio Of 15%, With An Available Setting Range Of 1%
To 40%. When Set Too High, The Differential Element Trip During Transformer Energizing;And If Set Too
Low, The Inrush Restraint May Block Tripping During Some Internal Fault Events.
Ideally, Setting The Inrush Restraint Function For The Transformer Differential Element Is Exactly
Like Setting Any Other Protection Function. The Key Criteria Are Sensitivity And Selectivity. The Setting Must
Be Sensitive Enough To Recognize Magnetizing Inrush Current Even With Low Levels Of Second Harmonics.
And It Must Be Selective To Distinguish Between An Inrush Event And Other Events That May Produce
Second Harmonic Current. The Standard Process For Setting A Protection Function Is To Perform An Analysis
Of The System. This Analysis Models The Response Of The System For Various Transient Events To Provide
A Basis For Setting Protection Functions.
The Power Transformer Under Analysis Is A 60mva, 132kv/33kv Delta/Star Connected And Energized
At 132kv.The Full Load Current 𝐼𝐹𝐿 =
𝑆 𝑚𝑎𝑥 ∗1000
3∗𝐾𝑉
Where Smax = Transformer Apparent Power In Mva,
Kv = Line Voltage In Kilovolts
Thus For Delta Connected Winding, 𝐼𝐹𝐿 =
60∗1000
3∗132
= 262.44 Amps.
Select Current Transformers (Cts) Of 300:5a Ratio For The Primary Windings.
Ct Secondary Current To The Relay Is 𝐼𝑟𝑒𝑙𝑎𝑦 =
IFl
Ctr
=
262.44∗5
300
= 4.374
For Star Connected Winding, 𝐼𝐹𝐿=
60∗1000
3∗33
= 1049.76 Amps.
Select Current Transformers (Cts) Of 1200:5a Ratio For The Primary Windings.
Ct Secondary Current To The Relay Is 𝐼𝑟𝑒𝑙𝑎𝑦 =
IFl
Ctr
=
1049.76∗5
1200
= 4.374 Amps.
Result Show That Thesum Of The Currents Entering Theprimary Restraint Windings Of The Differential Relay
Equals The Sum Of The Currents Leaving The Secondaryrestraintwinding; Hence The Differential Relay
Operating Current Is Zero. This Concludes That There Is No Fault In The Protection Zone.
Power Transformer Differential Relay Inrush Restraint Setting Applications
DOI: 10.9790/1676-1101046875 www.iosrjournals.org 72 | Page
Differential element Setting
An Instantaneous (High Set) Differential Element Remove The Transformerquickly From Service In
The Event Of Severe Internal Faults And To Eliminate The Effects Of Dc Offsets And Harmonics, The Relay
Trips On The Sensing Of Sequential Positive And Negative Peak Currents Whose Magnitude Exceeds The High
Set Trip Level. This Element Operates Within 15 Milli-Seconds.During Transformer Energization, Significant
2nd Harmonic Current Is Present, Which May Result In False Trips. This Requires The Relay To Suppress Its
Response To The 2nd
Harmonic Component Of Current. The Differential Relay Allows For Adjustment Of The
2nd Harmonic Restraint Element Over The Range Of 0.1 To 0.3 P.U. Of The Transformer’s Rated Current.
Similarly, Over-Excitation Of The Transformer Results In Significant Levels Of 5th Harmonic Current.For
Transformer Protection Applications These Settings Provide High-Speed Clearing Of Transformer Faults And
Proper Restraint For Inrush Events. For A Few Applications, Lowering The Harmonic Restraint Setting, Is
Necessary To Ensure That Transformer Energization Occur Successfully Where Very Low Second Harmonic
Inrush Levels Are Present.
Testing Of Inrush Restraint Methods
To Determine The Most Appropriate Choice For The Inrush Restraint Method And The Inrush
Restraint Mode, A Simple Laboratoryexperimental Procedure Wasperformed Along With Actual Operating
Experience To Develop The Standard Settings For The Inrush Restraint Function. The Schweitzerengineering
Laboratories (Sel-487) Microprocessor-Based Relay Type Was Configured To Some Inrush Restraint Function
And Level Setting Method.
The Procedure Was To Simply Choose Some Settings For The Relay, Connect The Relay To A Three-
Phase Test Set, And Simulates The System Using Alternative Transient Program (Atp) Software To Examine
The Level Of The Second Harmonic Presents. Figure 5(A) Shows Waveform Of Inrush Current And (B) Mal-
Operation Of A Differential Relay Caused By Low Levels Of The Second Harmonic Current During
Energization Of A Transformer.
These Tests Were Repeated Using Different Set Points And Different Restraint Functions Until A
Standard Setting Operating Criteria Was Determined. This Standard Package Of Settings Was Confirmed By
Capturing Transformer In-Rush Records From Various Installations And Comparing The Set Point Levels To
Actual Second Harmonic Levels To Confirm There Is Enough Margins.
Before Beginning The Setting And Testing, We Set The Following Criteria For Acceptable Settings.
 A Minimum Level Setting For Harmonic Restraint At 15%.
 No Operating Time Delay For The Differential Element Is Introduced By The Selected Inrush Restraint
Function Or Inrush Restraint Mode.
 The Differential Element Is Blocked From Operating During This Actual Energization Event.
In Addition, The Inrush Restraint Mode Was Implemented Using The Flexible Configuration Logic Of The
Relay. This Test Procedure Uses Star-Connected Cts That Are Typical On New Installations Using
Microprocessor-Based Differential Relays.
Figure 5: (A) Inrush Current
Figure 5: (B) Second Harmonicsduring Energization Characteristic
Power Transformer Differential Relay Inrush Restraint Setting Applications
DOI: 10.9790/1676-1101046875 www.iosrjournals.org 73 | Page
III. Results And Discussion
The Differential Relay Element Set Point For The Inrush Restraint Current Was 15% Of Second
Harmonics, While The Fifth Harmonics Was Set At 35%.These Setting Provide A Good Margin Of Security For
Energization Of The Transformer Where The Second Harmonic Current May Fall To Low Levels.The Settings
Were Successfully Restraining The Differential Element When Faced With A Fault Recovery Magnetizing
Inrush Event.The Operation Of The Differential Element On Any Phase Operates The Circuit Breakers
Supplying The Transformer. The Restraint Criterion Was Met On All Phases, As The Transformer Do Not
Tripped During Energization Or Sympathetic Inrush. For This Application, The Magnetizing Inrush Currents
During Energization Of The Transformer Were High Enough To Cause Operation Of The Differential Element.
Result Show That The Sum Of The Currents Entering The Primary Restraint Windings Of The Differential
Relay Equals The Sum Of The Currents Leaving The Secondary Restraint Winding; Hence The Differential
Relay Operating Current Is Zero. This Concludes That There Is No Fault In The Protection Zone.
The Results Of The Sel-487 Microprocessor-Based Differential Relay Field Configuration And
Harmonic Restraint Settings Are Tabulated In Table 1and 2, And Detailed Test Procedure Flow Chart Is Shown
In Figure 6.These Results Match The Expected Results For The Different Inrush Restraint Modes.
Table 1: Sel-551 Relay Differential Settings (Field Configuration)
Setting Label Definition Limits
Rid Relay Identifier Sap- 1
Tid Terminal Identifier Line 1
E87w1-A, Enable Winding 1-A In Differential Yes
E87w1-B, Enable Winding 1-B In Differential Yes
E87w1- C. Enable Winding 1-C In Differential Yes
E87w2-A, Enable Winding 2-A In Differential Yes
E87w2-B, Enable Winding 2-B In Differential Yes
E87w2-C. Enable Winding 2-C In Differential Yes
W1ct-A, Winding 1-A, Ct Connection (Delta, Star) Star (Y)
W1ct-B, Winding 1-B, Ct Connection (Delta, Star) Star (Y)
W1ct-C. Winding 1-C, Ct Connection (Delta, Star) Star (Y)
W2ct-A, Winding 2-A, Ct Connection (Delta, Star) Star (Y)
W2ct-B, Winding 2-B, Ct Connection (Delta, Star) Star (Y)
W2ct-C, Winding 2-C, Ct Connection (Delta, Star) Star (Y)
Mva Maximum Transformer Capacity, Three-Phase 60 Mva
Ctr1-A,(Pri) Winding 1-A, Ct Ratio (Ipri/In) 300:5 A
Ctr1-B,( Pri) Winding 1-B, Ct Ratio (Ipri/In) 300:5 A
Ctr1-C,( Pri) Winding 1-C, Ct Ratio (Ipri/In) 300:5 A
Ctr2-A,( Sec) Winding 2-A, Ct Ratio (Isec/In) 1200:5 A
Ctr2-B,( Sec) Winding 2-B, Ct Ratio (Isec/In) 1200:5 A
Ctr2-C,(Sec) Winding 2-C, Ct Ratio (Isec/In) 1200:5 A
Icom Define Internal Winding / Ct Connection Compensation Star (Y)
W1ctvg Winding 1a,B,C (Delta) Vector Group Compensation Dyn 1, (Dab)
Vwdg1 Winding 1a,B,C Line Voltage, Kv 132kv
Vwdg2 Winding 2a,B,C Line Voltage, Kv 33kv
Wdg1(Pri) I Winding 1a,B,C Line Currents (Amps) 262.44
Wdg2(Sec) I Winding 2a,B,C Line Currents (Amps) 1049.76
Nfreq Nominal Frequency Hz 50 Hz,
Phrot Phase Sequence Rotation Abc,
Date-F Month/Day/Year Format Mdy
Table 2: Differential Elements Relay Settings (Harmonic Restraint Results).
Display Descriptions Setting
Wdg1(Pri) Winding 1(A,B&C) Currents( 0.5 - 155 A Secondary) 4.374
Wdg2(Sec) Winding 2(A,B&C) Currents( 0.5 - 155 A Secondary) 4.374
087p Restrained Element Operating Current P.U 0.3
Slp1 Restraint Slope 1 Percentage (5 – 100%) 25
Slp2 Restraint Slope 2 Percentage (Off, 25 – 200%) 50
Irsi Restraint Current Slope 1 Limit ((1-20) Multiple Of Tap) 3
U87p Unrestrained Element Current Pu((1-20) Multiple Of Tap) 10
Pct2 Second- Harmony Blocking Percentage (Off, 5-100%) 15
Pct5 Fifth- Harmony Blocking Percentage (Off, 5-100%) 35
Th5p Fifth- Harmony Alarm Threshold (Off, 0.02 -3.2) Off
Ihbl Independent Harmonic Blocking (Y, N) Nil
Power Transformer Differential Relay Inrush Restraint Setting Applications
DOI: 10.9790/1676-1101046875 www.iosrjournals.org 74 | Page
SET RELAY MODE
SET RELAY LEVEL
PLAY FAULT
DIFFRENTIAL TRIP
RECORD MODE
LEVEL
CHANGE
MODE
REDUCE LEVEL
Figure6: Differential Relay Test Procedures Flow Chart
Advantages Of Microprocessor-Based Differential Relay Protection
 High Stability Against Ct Saturation Provided By Integrated Saturation Detector And Add-On Stabilization
 High Stability Against Inrush Currents Due To Advanced Filter Technology And Optional Cross-Blocking
Function.
 High Stability Against Over-Excitation ( 5th Harmonic Blocking)
 Short Tripping Time - Typically 1.5 Cycles
 High Set Fast Tripping Less Than One (1) Cycle
 Sensitive Earth Differential Protection Against Interturn Faults And Earth Faults Near Winding Neutral
 Integral Ratio And Vector Group Adaptation
 Integral Thermal Overload Protection
 External Start Of Fault Recording
IV. Conclusions
The Settings Of Inrush Restraint For Transformer Differential Protection Used Harmonic Restraint In
A Per-Phase Mode, With A Restraint Level Of 15% Of Second Harmonics And 35% Of Fifth Harmonics. These
Settings Provide High-Speed Clearing Of Transformer Faults And Proper Restraint For Inrush Events. Lowering
The Harmonic Restraint Settingensure That Transformer Energizations Occur Successfully Where Very Low
Second Harmonic Inrush Levels Are Present.The Operation Of The Differential Element On Any Phase
Operates The Circuit Breakers Supplying The Transformer. The Restraint Criterion Was Met On All Phases, As
The Transformer Do Not Tripped During Energization Or Sympathetic Inrush. The Setting Is Sensitive Enough
To Recognize Magnetizing Inrush Current Even With Low Levels Of Second Harmonics; And Selective To
Distinguish Between An Inrush Event And Other Events That May Produce Second Harmonic Current. The
Magnetizing Inrush Currents During Energization Of The Transformer Were High Enough To Cause Operation
Of The Differential Element.The Sum Of The Currents Entering The Primary Restraint Windings Of The
Differential Relay Equals The Sum Of The Currents Leaving The Secondary Restraint Winding; Hence The
Differential Relay Operating Current Is Zero. This Concludes That There Is No Fault In The Protection
Zone.Harmonic Blocking Or Harmonic Restraint Elements Permit Fast Tripping For All Internal Transformer
Faults With Minimal Delay When Energizing A Faulted Transformer; Prevent Transformer Differential Relay
Operation During Transformer Over Excitation, Prevent Differential Element Operation During Transformer
Energization And During Voltage Recovery Following A Power System Fault.
References
[1] Sandro G. A.P.2006. Modeling Relays For Power System Protection Studies, Canada.
[2] Grigsby L. L.2001.“The Electric Power Engineering Handbook”, Crc Press Llc, Boca Raton, Fl, P. 3-29.
[3] bangbee J.O.,2014. “Ph.D. Thesis, Current Transformer Saturation Impacts On Microprocessor-Based Protective Relays
Application In Nigeria Electricity Transmission Network”, University Of Benin, Nigeria
[4] W. K. Sonnemann, C. L. Wagner, And G. D. Rockefeller,1958.“Magnetizing Inrush Phenomena In
[5] Transformer Banks,” Aiee Transactions, Vol. 77, Part Iii, Pp. 884892.
[6] J. Berdy, W. Kaufman, And K. Winick,1976. “A Dissertation On Power Transformer Excitation And Inrush Characteristics,”
Symposium On Transformer Excitation And Inrushcharacteristics And Their Relationship To Transformer Protective Relaying,
Houston, Tx.
[7] Abb Operational Manual Md32-T Type,2007. “Digital Multifunction Transformer Differential Protection Relay”.
[8] Blackburn J. Lewis And Thomas J. Domin, 2007. “Protective Relaying Principles And Applications, Thirdedition”Pp.292-297
[9] Horowitz S. H, And Phadke A. G.,1995. “Power System Relaying, Third Edition”, Research Studies Press Ltd., Somerset, England.
Power Transformer Differential Relay Inrush Restraint Setting Applications
DOI: 10.9790/1676-1101046875 www.iosrjournals.org 75 | Page
[10] Saled M. M.,2001. “A Study On The Inrush Current Phenomena In Transformer Substation”, Conference Record Of The 36th
annual
Meeting Of The Ias,Pp. 1180-1187.
[11] Horowitz S. H, And Phadke A. G.,2008. “Power System Relaying, Third Edition”, Research Studies Press Ltd., Somerset, England,
Pp. 201-206.
[12] Kobet G. L. And Patterson R. W.2000. “Matlab Analysis Of Braytown Transformer Differential Inrush
[13] Misoperation” Georgia Tech Fault And Disturbance Analysis Conference, Atlanta, Ga
[14] Schweitzer Engineering Laboratories (Sel),2007. Digital Differential Relays Operational Manual.
.

More Related Content

What's hot

5 effective harmonic filter designs for commercial implementation
5 effective harmonic filter designs for commercial implementation5 effective harmonic filter designs for commercial implementation
5 effective harmonic filter designs for commercial implementationPower Matrix Solutions Pvt Ltd
 
Electrical fundamentals terms
Electrical fundamentals termsElectrical fundamentals terms
Electrical fundamentals termsRajneesh Budania
 
Frequency in electrical eng
Frequency in electrical engFrequency in electrical eng
Frequency in electrical engRajneesh Budania
 
Harmonics: Causes and Effects
Harmonics: Causes and EffectsHarmonics: Causes and Effects
Harmonics: Causes and EffectsLeonardo ENERGY
 
Chep 03 Electrical transient
Chep 03  Electrical transientChep 03  Electrical transient
Chep 03 Electrical transientPiyush Tandel
 
Simulation and Design of SRF based Control Algorithm for Three Phase Shunt Ac...
Simulation and Design of SRF based Control Algorithm for Three Phase Shunt Ac...Simulation and Design of SRF based Control Algorithm for Three Phase Shunt Ac...
Simulation and Design of SRF based Control Algorithm for Three Phase Shunt Ac...idescitation
 
P010439497.jeee [zsep02]
P010439497.jeee [zsep02]P010439497.jeee [zsep02]
P010439497.jeee [zsep02]IOSR Journals
 
Analysis of Shunt APF (Active PowerFilter)
Analysis of Shunt APF (Active PowerFilter)Analysis of Shunt APF (Active PowerFilter)
Analysis of Shunt APF (Active PowerFilter)Rajesh Dunna
 
Transformer protection from inrush currents: Discrimination of internal fault...
Transformer protection from inrush currents: Discrimination of internal fault...Transformer protection from inrush currents: Discrimination of internal fault...
Transformer protection from inrush currents: Discrimination of internal fault...Shilpa Shukla
 
Harmonic mitigating transformer
Harmonic mitigating transformerHarmonic mitigating transformer
Harmonic mitigating transformerBiswajit Pratihari
 
Thesis on harmonic distortion ps
Thesis on harmonic distortion psThesis on harmonic distortion ps
Thesis on harmonic distortion pskavithasasidharan
 
Analysis of generated harmonics due to transformer load on power system using
Analysis of generated harmonics due to transformer load on power system usingAnalysis of generated harmonics due to transformer load on power system using
Analysis of generated harmonics due to transformer load on power system usingIAEME Publication
 
Inrush current reduction in three phase power transformer by using prefluxing...
Inrush current reduction in three phase power transformer by using prefluxing...Inrush current reduction in three phase power transformer by using prefluxing...
Inrush current reduction in three phase power transformer by using prefluxing...IAEME Publication
 
Design of shunt active power filter to mitigate harmonic
Design of shunt active power filter to mitigate harmonicDesign of shunt active power filter to mitigate harmonic
Design of shunt active power filter to mitigate harmonicsager alswed
 

What's hot (20)

5 effective harmonic filter designs for commercial implementation
5 effective harmonic filter designs for commercial implementation5 effective harmonic filter designs for commercial implementation
5 effective harmonic filter designs for commercial implementation
 
Electrical fundamentals terms
Electrical fundamentals termsElectrical fundamentals terms
Electrical fundamentals terms
 
Frequency in electrical eng
Frequency in electrical engFrequency in electrical eng
Frequency in electrical eng
 
Harmonics
HarmonicsHarmonics
Harmonics
 
Harmonics
HarmonicsHarmonics
Harmonics
 
Harmonics: Causes and Effects
Harmonics: Causes and EffectsHarmonics: Causes and Effects
Harmonics: Causes and Effects
 
Chep 03 Electrical transient
Chep 03  Electrical transientChep 03  Electrical transient
Chep 03 Electrical transient
 
Simulation and Design of SRF based Control Algorithm for Three Phase Shunt Ac...
Simulation and Design of SRF based Control Algorithm for Three Phase Shunt Ac...Simulation and Design of SRF based Control Algorithm for Three Phase Shunt Ac...
Simulation and Design of SRF based Control Algorithm for Three Phase Shunt Ac...
 
Hormonics impact and_mitigation
Hormonics impact and_mitigationHormonics impact and_mitigation
Hormonics impact and_mitigation
 
P010439497.jeee [zsep02]
P010439497.jeee [zsep02]P010439497.jeee [zsep02]
P010439497.jeee [zsep02]
 
Power quality
Power qualityPower quality
Power quality
 
Analysis of Shunt APF (Active PowerFilter)
Analysis of Shunt APF (Active PowerFilter)Analysis of Shunt APF (Active PowerFilter)
Analysis of Shunt APF (Active PowerFilter)
 
Transformer protection from inrush currents: Discrimination of internal fault...
Transformer protection from inrush currents: Discrimination of internal fault...Transformer protection from inrush currents: Discrimination of internal fault...
Transformer protection from inrush currents: Discrimination of internal fault...
 
Harmonic mitigating transformer
Harmonic mitigating transformerHarmonic mitigating transformer
Harmonic mitigating transformer
 
Thesis on harmonic distortion ps
Thesis on harmonic distortion psThesis on harmonic distortion ps
Thesis on harmonic distortion ps
 
Analysis of generated harmonics due to transformer load on power system using
Analysis of generated harmonics due to transformer load on power system usingAnalysis of generated harmonics due to transformer load on power system using
Analysis of generated harmonics due to transformer load on power system using
 
Inrush current reduction in three phase power transformer by using prefluxing...
Inrush current reduction in three phase power transformer by using prefluxing...Inrush current reduction in three phase power transformer by using prefluxing...
Inrush current reduction in three phase power transformer by using prefluxing...
 
L58037783
L58037783L58037783
L58037783
 
Design of shunt active power filter to mitigate harmonic
Design of shunt active power filter to mitigate harmonicDesign of shunt active power filter to mitigate harmonic
Design of shunt active power filter to mitigate harmonic
 
Harmonics
HarmonicsHarmonics
Harmonics
 

Viewers also liked (20)

I012126670
I012126670I012126670
I012126670
 
кайртаева жадыра театр - предприниматели
кайртаева жадыра   театр - предпринимателикайртаева жадыра   театр - предприниматели
кайртаева жадыра театр - предприниматели
 
N1103048593
N1103048593N1103048593
N1103048593
 
B010330713
B010330713B010330713
B010330713
 
P01813101103
P01813101103P01813101103
P01813101103
 
I012527580
I012527580I012527580
I012527580
 
E012542629
E012542629E012542629
E012542629
 
Q010228189
Q010228189Q010228189
Q010228189
 
F017553034
F017553034F017553034
F017553034
 
M01245104111
M01245104111M01245104111
M01245104111
 
A017660107
A017660107A017660107
A017660107
 
F012113746
F012113746F012113746
F012113746
 
K018217680
K018217680K018217680
K018217680
 
C012421626
C012421626C012421626
C012421626
 
F1802043747
F1802043747F1802043747
F1802043747
 
J018127176.publishing paper of mamatha (1)
J018127176.publishing paper of mamatha (1)J018127176.publishing paper of mamatha (1)
J018127176.publishing paper of mamatha (1)
 
A Generalization of QN-Maps
A Generalization of QN-MapsA Generalization of QN-Maps
A Generalization of QN-Maps
 
L012337275
L012337275L012337275
L012337275
 
A017260110
A017260110A017260110
A017260110
 
N01741100102
N01741100102N01741100102
N01741100102
 

Similar to H1101046875

Voltage Flicker Analysis and its Mitigation by STATCOM for Power Quality Impr...
Voltage Flicker Analysis and its Mitigation by STATCOM for Power Quality Impr...Voltage Flicker Analysis and its Mitigation by STATCOM for Power Quality Impr...
Voltage Flicker Analysis and its Mitigation by STATCOM for Power Quality Impr...IJMTST Journal
 
C0212014018
C0212014018C0212014018
C0212014018theijes
 
Fundamentals of transformer inrush
Fundamentals of transformer inrushFundamentals of transformer inrush
Fundamentals of transformer inrushmichaeljmack
 
Fundamentals of transformer inrush
Fundamentals of transformer inrushFundamentals of transformer inrush
Fundamentals of transformer inrushsaad karboua
 
A Review of Methods Employed to Identify Flicker Producing Sources
A Review of Methods Employed to Identify Flicker Producing SourcesA Review of Methods Employed to Identify Flicker Producing Sources
A Review of Methods Employed to Identify Flicker Producing SourcesTELKOMNIKA JOURNAL
 
Protection of power transformer
Protection of power transformerProtection of power transformer
Protection of power transformerRitesh Verma
 
Minor_project_b.tech_sem7_dec_2017
Minor_project_b.tech_sem7_dec_2017Minor_project_b.tech_sem7_dec_2017
Minor_project_b.tech_sem7_dec_2017Dipen Kantariya
 
pptonprotectionofpowertransformers-161020085118 (1).pdf
pptonprotectionofpowertransformers-161020085118 (1).pdfpptonprotectionofpowertransformers-161020085118 (1).pdf
pptonprotectionofpowertransformers-161020085118 (1).pdfSunny268892
 
Ppt on protection of power transformers
Ppt on protection of power transformersPpt on protection of power transformers
Ppt on protection of power transformerssiddharam kantoli
 
FUNDAMENTALS OF HARMONIC AND APPLIED HARMONICS UNIT 3.pdf
FUNDAMENTALS OF HARMONIC AND APPLIED HARMONICS UNIT 3.pdfFUNDAMENTALS OF HARMONIC AND APPLIED HARMONICS UNIT 3.pdf
FUNDAMENTALS OF HARMONIC AND APPLIED HARMONICS UNIT 3.pdfMURTHYVENKAT2
 
Selection Of Circuit Breaker
Selection Of Circuit BreakerSelection Of Circuit Breaker
Selection Of Circuit BreakerRaviraj solanki
 
Factors to be considered while selecting CT
Factors to be considered while selecting CTFactors to be considered while selecting CT
Factors to be considered while selecting CTParth Patel
 
Power quality & demand side management
Power quality & demand side managementPower quality & demand side management
Power quality & demand side managementMark Anthony Enoy
 

Similar to H1101046875 (20)

EE-524 Project report
EE-524 Project reportEE-524 Project report
EE-524 Project report
 
Voltage Flicker Analysis and its Mitigation by STATCOM for Power Quality Impr...
Voltage Flicker Analysis and its Mitigation by STATCOM for Power Quality Impr...Voltage Flicker Analysis and its Mitigation by STATCOM for Power Quality Impr...
Voltage Flicker Analysis and its Mitigation by STATCOM for Power Quality Impr...
 
Protective Relay
Protective RelayProtective Relay
Protective Relay
 
C0212014018
C0212014018C0212014018
C0212014018
 
Thyristor switched capacitor
Thyristor switched capacitorThyristor switched capacitor
Thyristor switched capacitor
 
Survey of dc motor
Survey of dc motorSurvey of dc motor
Survey of dc motor
 
Fundamentals of transformer inrush
Fundamentals of transformer inrushFundamentals of transformer inrush
Fundamentals of transformer inrush
 
Fundamentals of transformer inrush
Fundamentals of transformer inrushFundamentals of transformer inrush
Fundamentals of transformer inrush
 
A Review of Methods Employed to Identify Flicker Producing Sources
A Review of Methods Employed to Identify Flicker Producing SourcesA Review of Methods Employed to Identify Flicker Producing Sources
A Review of Methods Employed to Identify Flicker Producing Sources
 
Protection of power transformer
Protection of power transformerProtection of power transformer
Protection of power transformer
 
Minor_project_b.tech_sem7_dec_2017
Minor_project_b.tech_sem7_dec_2017Minor_project_b.tech_sem7_dec_2017
Minor_project_b.tech_sem7_dec_2017
 
pptonprotectionofpowertransformers-161020085118 (1).pdf
pptonprotectionofpowertransformers-161020085118 (1).pdfpptonprotectionofpowertransformers-161020085118 (1).pdf
pptonprotectionofpowertransformers-161020085118 (1).pdf
 
Ppt on protection of power transformers
Ppt on protection of power transformersPpt on protection of power transformers
Ppt on protection of power transformers
 
A010410109
A010410109A010410109
A010410109
 
E044043336
E044043336E044043336
E044043336
 
FUNDAMENTALS OF HARMONIC AND APPLIED HARMONICS UNIT 3.pdf
FUNDAMENTALS OF HARMONIC AND APPLIED HARMONICS UNIT 3.pdfFUNDAMENTALS OF HARMONIC AND APPLIED HARMONICS UNIT 3.pdf
FUNDAMENTALS OF HARMONIC AND APPLIED HARMONICS UNIT 3.pdf
 
Ijirstv3i7002 170302112524
Ijirstv3i7002 170302112524Ijirstv3i7002 170302112524
Ijirstv3i7002 170302112524
 
Selection Of Circuit Breaker
Selection Of Circuit BreakerSelection Of Circuit Breaker
Selection Of Circuit Breaker
 
Factors to be considered while selecting CT
Factors to be considered while selecting CTFactors to be considered while selecting CT
Factors to be considered while selecting CT
 
Power quality & demand side management
Power quality & demand side managementPower quality & demand side management
Power quality & demand side management
 

More from IOSR Journals (20)

A011140104
A011140104A011140104
A011140104
 
M0111397100
M0111397100M0111397100
M0111397100
 
L011138596
L011138596L011138596
L011138596
 
K011138084
K011138084K011138084
K011138084
 
J011137479
J011137479J011137479
J011137479
 
I011136673
I011136673I011136673
I011136673
 
G011134454
G011134454G011134454
G011134454
 
H011135565
H011135565H011135565
H011135565
 
F011134043
F011134043F011134043
F011134043
 
E011133639
E011133639E011133639
E011133639
 
D011132635
D011132635D011132635
D011132635
 
C011131925
C011131925C011131925
C011131925
 
B011130918
B011130918B011130918
B011130918
 
A011130108
A011130108A011130108
A011130108
 
I011125160
I011125160I011125160
I011125160
 
H011124050
H011124050H011124050
H011124050
 
G011123539
G011123539G011123539
G011123539
 
F011123134
F011123134F011123134
F011123134
 
E011122530
E011122530E011122530
E011122530
 
D011121524
D011121524D011121524
D011121524
 

Recently uploaded

Kotlin Multiplatform & Compose Multiplatform - Starter kit for pragmatics
Kotlin Multiplatform & Compose Multiplatform - Starter kit for pragmaticsKotlin Multiplatform & Compose Multiplatform - Starter kit for pragmatics
Kotlin Multiplatform & Compose Multiplatform - Starter kit for pragmaticscarlostorres15106
 
How to Troubleshoot Apps for the Modern Connected Worker
How to Troubleshoot Apps for the Modern Connected WorkerHow to Troubleshoot Apps for the Modern Connected Worker
How to Troubleshoot Apps for the Modern Connected WorkerThousandEyes
 
Pigging Solutions Piggable Sweeping Elbows
Pigging Solutions Piggable Sweeping ElbowsPigging Solutions Piggable Sweeping Elbows
Pigging Solutions Piggable Sweeping ElbowsPigging Solutions
 
How to Remove Document Management Hurdles with X-Docs?
How to Remove Document Management Hurdles with X-Docs?How to Remove Document Management Hurdles with X-Docs?
How to Remove Document Management Hurdles with X-Docs?XfilesPro
 
Swan(sea) Song – personal research during my six years at Swansea ... and bey...
Swan(sea) Song – personal research during my six years at Swansea ... and bey...Swan(sea) Song – personal research during my six years at Swansea ... and bey...
Swan(sea) Song – personal research during my six years at Swansea ... and bey...Alan Dix
 
Azure Monitor & Application Insight to monitor Infrastructure & Application
Azure Monitor & Application Insight to monitor Infrastructure & ApplicationAzure Monitor & Application Insight to monitor Infrastructure & Application
Azure Monitor & Application Insight to monitor Infrastructure & ApplicationAndikSusilo4
 
Slack Application Development 101 Slides
Slack Application Development 101 SlidesSlack Application Development 101 Slides
Slack Application Development 101 Slidespraypatel2
 
Scaling API-first – The story of a global engineering organization
Scaling API-first – The story of a global engineering organizationScaling API-first – The story of a global engineering organization
Scaling API-first – The story of a global engineering organizationRadu Cotescu
 
Handwritten Text Recognition for manuscripts and early printed texts
Handwritten Text Recognition for manuscripts and early printed textsHandwritten Text Recognition for manuscripts and early printed texts
Handwritten Text Recognition for manuscripts and early printed textsMaria Levchenko
 
IAC 2024 - IA Fast Track to Search Focused AI Solutions
IAC 2024 - IA Fast Track to Search Focused AI SolutionsIAC 2024 - IA Fast Track to Search Focused AI Solutions
IAC 2024 - IA Fast Track to Search Focused AI SolutionsEnterprise Knowledge
 
[2024]Digital Global Overview Report 2024 Meltwater.pdf
[2024]Digital Global Overview Report 2024 Meltwater.pdf[2024]Digital Global Overview Report 2024 Meltwater.pdf
[2024]Digital Global Overview Report 2024 Meltwater.pdfhans926745
 
Transcript: #StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024
Transcript: #StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024Transcript: #StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024
Transcript: #StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024BookNet Canada
 
WhatsApp 9892124323 ✓Call Girls In Kalyan ( Mumbai ) secure service
WhatsApp 9892124323 ✓Call Girls In Kalyan ( Mumbai ) secure serviceWhatsApp 9892124323 ✓Call Girls In Kalyan ( Mumbai ) secure service
WhatsApp 9892124323 ✓Call Girls In Kalyan ( Mumbai ) secure servicePooja Nehwal
 
Key Features Of Token Development (1).pptx
Key  Features Of Token  Development (1).pptxKey  Features Of Token  Development (1).pptx
Key Features Of Token Development (1).pptxLBM Solutions
 
Understanding the Laravel MVC Architecture
Understanding the Laravel MVC ArchitectureUnderstanding the Laravel MVC Architecture
Understanding the Laravel MVC ArchitecturePixlogix Infotech
 
SIEMENS: RAPUNZEL – A Tale About Knowledge Graph
SIEMENS: RAPUNZEL – A Tale About Knowledge GraphSIEMENS: RAPUNZEL – A Tale About Knowledge Graph
SIEMENS: RAPUNZEL – A Tale About Knowledge GraphNeo4j
 
A Domino Admins Adventures (Engage 2024)
A Domino Admins Adventures (Engage 2024)A Domino Admins Adventures (Engage 2024)
A Domino Admins Adventures (Engage 2024)Gabriella Davis
 
FULL ENJOY 🔝 8264348440 🔝 Call Girls in Diplomatic Enclave | Delhi
FULL ENJOY 🔝 8264348440 🔝 Call Girls in Diplomatic Enclave | DelhiFULL ENJOY 🔝 8264348440 🔝 Call Girls in Diplomatic Enclave | Delhi
FULL ENJOY 🔝 8264348440 🔝 Call Girls in Diplomatic Enclave | Delhisoniya singh
 
04-2024-HHUG-Sales-and-Marketing-Alignment.pptx
04-2024-HHUG-Sales-and-Marketing-Alignment.pptx04-2024-HHUG-Sales-and-Marketing-Alignment.pptx
04-2024-HHUG-Sales-and-Marketing-Alignment.pptxHampshireHUG
 
SQL Database Design For Developers at php[tek] 2024
SQL Database Design For Developers at php[tek] 2024SQL Database Design For Developers at php[tek] 2024
SQL Database Design For Developers at php[tek] 2024Scott Keck-Warren
 

Recently uploaded (20)

Kotlin Multiplatform & Compose Multiplatform - Starter kit for pragmatics
Kotlin Multiplatform & Compose Multiplatform - Starter kit for pragmaticsKotlin Multiplatform & Compose Multiplatform - Starter kit for pragmatics
Kotlin Multiplatform & Compose Multiplatform - Starter kit for pragmatics
 
How to Troubleshoot Apps for the Modern Connected Worker
How to Troubleshoot Apps for the Modern Connected WorkerHow to Troubleshoot Apps for the Modern Connected Worker
How to Troubleshoot Apps for the Modern Connected Worker
 
Pigging Solutions Piggable Sweeping Elbows
Pigging Solutions Piggable Sweeping ElbowsPigging Solutions Piggable Sweeping Elbows
Pigging Solutions Piggable Sweeping Elbows
 
How to Remove Document Management Hurdles with X-Docs?
How to Remove Document Management Hurdles with X-Docs?How to Remove Document Management Hurdles with X-Docs?
How to Remove Document Management Hurdles with X-Docs?
 
Swan(sea) Song – personal research during my six years at Swansea ... and bey...
Swan(sea) Song – personal research during my six years at Swansea ... and bey...Swan(sea) Song – personal research during my six years at Swansea ... and bey...
Swan(sea) Song – personal research during my six years at Swansea ... and bey...
 
Azure Monitor & Application Insight to monitor Infrastructure & Application
Azure Monitor & Application Insight to monitor Infrastructure & ApplicationAzure Monitor & Application Insight to monitor Infrastructure & Application
Azure Monitor & Application Insight to monitor Infrastructure & Application
 
Slack Application Development 101 Slides
Slack Application Development 101 SlidesSlack Application Development 101 Slides
Slack Application Development 101 Slides
 
Scaling API-first – The story of a global engineering organization
Scaling API-first – The story of a global engineering organizationScaling API-first – The story of a global engineering organization
Scaling API-first – The story of a global engineering organization
 
Handwritten Text Recognition for manuscripts and early printed texts
Handwritten Text Recognition for manuscripts and early printed textsHandwritten Text Recognition for manuscripts and early printed texts
Handwritten Text Recognition for manuscripts and early printed texts
 
IAC 2024 - IA Fast Track to Search Focused AI Solutions
IAC 2024 - IA Fast Track to Search Focused AI SolutionsIAC 2024 - IA Fast Track to Search Focused AI Solutions
IAC 2024 - IA Fast Track to Search Focused AI Solutions
 
[2024]Digital Global Overview Report 2024 Meltwater.pdf
[2024]Digital Global Overview Report 2024 Meltwater.pdf[2024]Digital Global Overview Report 2024 Meltwater.pdf
[2024]Digital Global Overview Report 2024 Meltwater.pdf
 
Transcript: #StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024
Transcript: #StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024Transcript: #StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024
Transcript: #StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024
 
WhatsApp 9892124323 ✓Call Girls In Kalyan ( Mumbai ) secure service
WhatsApp 9892124323 ✓Call Girls In Kalyan ( Mumbai ) secure serviceWhatsApp 9892124323 ✓Call Girls In Kalyan ( Mumbai ) secure service
WhatsApp 9892124323 ✓Call Girls In Kalyan ( Mumbai ) secure service
 
Key Features Of Token Development (1).pptx
Key  Features Of Token  Development (1).pptxKey  Features Of Token  Development (1).pptx
Key Features Of Token Development (1).pptx
 
Understanding the Laravel MVC Architecture
Understanding the Laravel MVC ArchitectureUnderstanding the Laravel MVC Architecture
Understanding the Laravel MVC Architecture
 
SIEMENS: RAPUNZEL – A Tale About Knowledge Graph
SIEMENS: RAPUNZEL – A Tale About Knowledge GraphSIEMENS: RAPUNZEL – A Tale About Knowledge Graph
SIEMENS: RAPUNZEL – A Tale About Knowledge Graph
 
A Domino Admins Adventures (Engage 2024)
A Domino Admins Adventures (Engage 2024)A Domino Admins Adventures (Engage 2024)
A Domino Admins Adventures (Engage 2024)
 
FULL ENJOY 🔝 8264348440 🔝 Call Girls in Diplomatic Enclave | Delhi
FULL ENJOY 🔝 8264348440 🔝 Call Girls in Diplomatic Enclave | DelhiFULL ENJOY 🔝 8264348440 🔝 Call Girls in Diplomatic Enclave | Delhi
FULL ENJOY 🔝 8264348440 🔝 Call Girls in Diplomatic Enclave | Delhi
 
04-2024-HHUG-Sales-and-Marketing-Alignment.pptx
04-2024-HHUG-Sales-and-Marketing-Alignment.pptx04-2024-HHUG-Sales-and-Marketing-Alignment.pptx
04-2024-HHUG-Sales-and-Marketing-Alignment.pptx
 
SQL Database Design For Developers at php[tek] 2024
SQL Database Design For Developers at php[tek] 2024SQL Database Design For Developers at php[tek] 2024
SQL Database Design For Developers at php[tek] 2024
 

H1101046875

  • 1. IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-ISSN: 2278-1676,p-ISSN: 2320-3331, Volume 11, Issue 1 Ver. IV (Jan. – Feb. 2016), PP 68-75 www.iosrjournals.org DOI: 10.9790/1676-1101046875 www.iosrjournals.org 68 | Page Power Transformer Differential Relay Inrush Restraint Setting Applications J.O. Aibangbee1 , S.O. Onohaebi 2 1 department Of Electrical &Computer Engineering, Bells University Of Technology, Ota, Nigeria 2 department Of Electrical & Electronic Engineering, University Of Benin, Nigeria Abstract: This Paper Involves The Study Of Power Transformer Differential Relay Inrush Restraint Settings Applications. Criteria For The Setting And Testing Of Transformers Differential Relays Was Presented.The Setting Of The Inrush Restraint On A Per-Phase Basis On The Protected Transformerwas Performed. The System Was Simulated Using Alternative Transient Program (Atp) Software To Examine The Level Of The Second Harmonic Presents. The Differential Relay Element Set Point For Inrush Restraint Current Was Achieved At 15% Of Second Harmonics And 35% Of Fifth Harmonics. These Settings Provide High-Speed Clearing Of Transformer Faults And Proper Restraint For Inrush Events.It’s Also A Good Margin Of Security For Energization Of The Transformer Where The Second Harmonic Inrush Current Levels Are Present. These Settings Were Successful Restraining The Differential Element When Faced With A Fault Recovering Magnetizing Inrush Event. The Restraint Criterion Was Met On All Phases, As The Transformer Do Not Tripped During Energization Or Sympathetic Inrush. The Setting Is Sensitive Enough To Recognize Magnetizing Inrush Current Even With Low Levels Of Second Harmonics; And Selective To Distinguish Between An Inrush Event And Other Events That May Produce Second Harmonic Current. Keywords: Power Transformer, Differential Relay, Harmonic Restraint, Energization, Magnetizing Inrush Current, Relay Setting, Current Transformer, Differential Protection. I. Introduction Electric Power Utilities Have Traditionally Used Electromechanical Differential Relay For The Protection Of Power Transformers In The Past, And Many Such Relays Are Still In Use In Power Systems Today[1]. The Basic Protection For Power Transformers Is Differentialprotection With Second Harmonic Restraint Used To Block Thedifferential Element During Inrush Events For The Transformer[2].Differential Protection Is One Of The Most Reliable And Popular Techniques In Power System Protection. Differential Protection Is A Fast, Selective Method Of Protection Against Short Circuits In Transformers, And Is The Standard Protection Used By Transmission Company Of Nigeria (Tcn) To Protect Transformers. Differential Protection Is A Practical Application Of Kirchhoff’s Current Law. The Sum Of The Currents Entering The Transformer Should Equal The Sum Of The Currents Leaving The Transformer.If The Net Sum Of The Currents That Enter And The Currents That Leave A Protection Zone Is Essentially Zero, It Is Concluded That There Is No Fault In The Protection Zone. However, If The Net Sum Is Not Zero, The Differential Protection Concludes That A Fault Exists In The Zone And Takes Steps To Isolate The Zone From The Restof The System. Differential Protection Compares The Measured Currents Entering And Leaving The Transformer To Create A Differential Current. With The Ideal Transformer Of Figure 1, And Assuming Ideal Current Transformers, The Differential Current Is Zero When Current Is Flowing Through The Transformer. Differential Current Greater Than Zero Indicate An Internal Fault Condition. In Practice, The Differential Current For A Normally Operating Transformer Is Always Greater Than Zero Due To Ct Measurement Error And The Position Of The Load Tap Changer [3]. Misoperations Can Occur During Energization Of A Transformer Due To Failure Of The Harmonic Restraint Function. An External Fault Can Also Trigger A Misoperation During The Voltage Recovering Period, Causing The Differential Relay To Operate Immediately After A Fault Is Cleared From The System. Figure 1: Transformer Differential Protection Principle
  • 2. Power Transformer Differential Relay Inrush Restraint Setting Applications DOI: 10.9790/1676-1101046875 www.iosrjournals.org 69 | Page There Are Two Common Situations Where Differential Protectionmay Incorrectly Declare An Internal Fault Condition. One Conditionis Ct Saturation For A Fault Outside Of The Transformer Zone Ofprotection. The Error In The Measured Signal Of The Saturatedct Results In A Significant Error In The Differential Current. Theerroneous Differential Current May Result In Undesired Operationof The Differential Element For An External Fault Condition. The Second Common Situation Is A Transformer Inrush Event.Some Operating Situations Instantly Change The Operating Fluxof The Transformer Core, Requiring A Large Supply Of Current.This Inrush Of Current Typically Occurs In Only One Winding Ofthe Transformer. Therefore Inrush Currents May Produce Adifferential Current That Results In The Operation Of The Differentialprotection. This Type Of Event Is Not A Fault Condition, So Thedifferential Protection Should Restrain From Operating For Thiscondition. This Paper Intends To Discuss The Setting Of Inrush Current Due To Harmonic In Power Transformers. II. General Description Any Event On The Power System That Causes A Significant Increase In The Magnetizing Voltage Of The Transformer Core Results In Magnetizing Inrush Currents Flowing Into The Transformer. The Three Most Common Events Areenergization Of Transformer, Magnetizing Inrush Current And Sympathetic Inrush. These Are Discussed In The Session That Follows. Energization Of Power Transformer. This Is The Typical Event Where A Magnetizing Inrush Current Is Of Concern. The Excitation Voltage On One Winding Is Increased From 0 To Full Voltage. The Transformer Core Typically Saturates, With The Amount Of Saturation Determined By Transformer Design, System Impedance, The Remnant Flux In The Core, And The Point On The Voltage Wave When The Transformer Is Energized. The Current Needed To Supply This Flux May Be As Much As 20 Times The Full Load Rating Of The Transformer, With Typical Value For Power Transformers For 6 Times The Full Load Rating [3]. Transformer Energization Is A Typical Cause Of Inrush Currents, But Anytransient In The Transformer Circuit May Generate These Currents. Other Causes Include Voltagerecovery After The Clearance Of An External Fault Or The Energization Of A Transformer In Parallelwith A Transformer That Is Already In Service. The Magnitudes And Waveforms Of Inrush Currentsdepend On A Multitude Of Factors, And Are Almost Impossible To Predict. The Followingsummarizes The Main Characteristics Of Inrush Currents:  Generally Contain Dc Offset, Odd Harmonics, And Even Harmonics [4, 5].  Typically Composed Of Unipolar Or Bipolar Pulses, Separated By Intervals Of Very Low Current Values.  Peak Values Of Unipolar Inrush Current Pulses Decrease Very Slowly. Time Constant Is Typically Much Greater Than That Of The Exponentially Decaying Dc Offset Of Fault Currents.  Second-Harmonic Content Starts With A Low Value And Increases As The Inrush Current Decreases. Figure 2 Show Equivalent Circuit Of A Transformer. In An Idealtransformer, The Primary And Secondary Currents Ip And Is Areequal Except For The Small Current Flowing Through The Shuntelement Of The Magnetizing Branch. The Increase In Flux Causedby An Increase In The Exciting Voltage Draws More Currentthrough The Magnetizing Branch. When The Transformer Isbeing Energized, This Current Flows Through Only One Winding. R , LP P R , LS S IS Rb ES LmRm Ip Im Ie Ir VS Figure 2: Transformer Equivalent Circuits During Inrush Events Other Than Energization, The Magnetizing Inrush Current May Appear In Both Windings, With The Inrush Current More Prevalent In One Winding As Show Infigure 3.An External Magnetizing Force Causes All The Magnetic Moments Of The Steel To Align With The Applied Magnetic Field. In The Case Of Transformers, The Excitation Voltage Provides This Applied Magnetic Field. The Alignment Of The Magnetic Moments Causes An Increase In Flux Density Greater Than That Of The External Magnetic Field. The Steel Is Fully Saturated When All The Magnetic Moments Are Aligned With The Applied Field. The Magnitude And Characteristic Of The Inrush Current Is Dependent On The Amount Of Saturation Of The Transformer Core.
  • 3. Power Transformer Differential Relay Inrush Restraint Setting Applications DOI: 10.9790/1676-1101046875 www.iosrjournals.org 70 | Page Figure 3: Magnetization Inrush Current Characteristic In A Power Transformer Magnetizing Inrush Current An External Fault May Significantly Reduce The System Voltage, And Therefore Reduce The Excitation Voltage Of The Transformer. When This Fault Is Cleared, The Excitation Voltage Returns To The Normal System Voltage Level. The Return Of Voltage May Force A Dc Offset On The Flux Linkages, Resulting In Magnetizing Inrush Current. This Magnetizing Inrush Current Will Be Less Than That Of Energization, As There Is No Remnant Flux In The Core[8]. The Current Measured By The Differential Relay Will Be Fairly Linear Due To The Presence Of Load Current, And May Result In Low Levels Of Second Harmonic Current.If The Transformer Were Reenergized At The Instant The Voltage Waveform Correspond To The Residual Magnetic Density Within The Core, There Would Be A Smooth Continuation Of The Previous Operation With No Transients. However, In Practice, The Instant When Switching Takes Place Cannot Be Controlled, And A Magnetizing Transient Occurs, Almost Inevitably. The Transient Generates A Current Known As Inrush Current. The Magnitude Of This Inrush Current Can Be Several Times The Load Current And Flows Only On One Side Of The Differential Relay, Which Tends To Operate If Some Form Of Restraint Is Not Provided. Inrush Currents Measured In Separate Phases Of A Three-Phase Transformer May Differ Considerably Because Of The Following [9]:  The Angles Of The Energizing Voltages Are Different In Different Phases.  When The Delta-Connected Winding Is Switched-In, The Line Voltages Are Applied As The Magnetizing Voltages.  In The Later Case, The Line Current In A Given Phase Is A Vector Sum Of Two Winding Currents.  Depending On The Core Type And Other Conditions, Only Some Of The Core Legs May Get Saturated. Sympathetic Inrush. Energizing A Transformer On The Power System Can Cause Sympathetic Magnetizing Inrush Currents To Flow In An Already Energized Parallel Transformer.Energizing The Second Transformer As Shown In Figure 4(A) Causes Voltage Drop Across The Resistance Of The Sourcefeeding The Transformers. This Voltage Drop May Cause A Saturation Of The Already Energized Transformer In The Negative Direction. This Saturation Causes Magnetizing Inrush Current To Supply The Flux. The Magnitude Of The Magnetizing Inrush Currentis Generally Not As Severe As The Other Cases[5, 6,7]. Figure 4: (A) Sympathetic Inrush Circuit Figure 4 (B) Shows A Typical Set Of Transformer Inrush Waveforms Captured During The Energization Of The 60mva, 132kv/33kv Power Transformer, Energized At 132kvdelta/Star Transformer. Ib And Ic Are Fully Offset, And Ia Shows The Typical Effects Of Interphase Coupling And Highly Non- Sinusoidal. Magnetizing Inrush Current Under Normal Operating Conditions Is Very Small. However, When A Transformer Is Energized After It Has Been Taken Out Of Service, The Magnetizing Inrush Current Can Be Extremely Large As 10 Times Full Load Current For A Short Period (Say 5 Cycles). Closer Examination Of
  • 4. Power Transformer Differential Relay Inrush Restraint Setting Applications DOI: 10.9790/1676-1101046875 www.iosrjournals.org 71 | Page These Waveforms, With Harmonic Analysis, Shows That All Of These Waveforms Have A Strong Second- Harmonic Component, With A Fourth-Harmonic Component, The Next Most Prevalent Harmonic, In Two Out Of The Three Phases [11, 12]. Figure 4: (B) Typical Set Of Transformer Inrush Waveforms Analysis Of Differential Relays Setting Harmonic Restraint Is The Classical Way To Restrain Relay Tripping. The Techniques Work On The Principlethat The Magnetizing Inrush Current Contains High Levels Of Second Harmonic Current. The Current For An Internal Transformer Fault Typically Has Very Low Levels Of Second Harmonic Current. The Simplest Method Of Harmonic Restraint Uses The Magnitude Of The Second Harmonic In The Differential Current Compared To The Magnitude Of The Fundamental Frequency Component In The Differential Current. Tripping Of The Differential Element Is Blocked When This Ratio Exceeds An Adjustable Threshold. The Historical Setting For Harmonic Restraint Is A Second Harmonic Ratio Of 15%, With An Available Setting Range Of 1% To 40%. When Set Too High, The Differential Element Trip During Transformer Energizing;And If Set Too Low, The Inrush Restraint May Block Tripping During Some Internal Fault Events. Ideally, Setting The Inrush Restraint Function For The Transformer Differential Element Is Exactly Like Setting Any Other Protection Function. The Key Criteria Are Sensitivity And Selectivity. The Setting Must Be Sensitive Enough To Recognize Magnetizing Inrush Current Even With Low Levels Of Second Harmonics. And It Must Be Selective To Distinguish Between An Inrush Event And Other Events That May Produce Second Harmonic Current. The Standard Process For Setting A Protection Function Is To Perform An Analysis Of The System. This Analysis Models The Response Of The System For Various Transient Events To Provide A Basis For Setting Protection Functions. The Power Transformer Under Analysis Is A 60mva, 132kv/33kv Delta/Star Connected And Energized At 132kv.The Full Load Current 𝐼𝐹𝐿 = 𝑆 𝑚𝑎𝑥 ∗1000 3∗𝐾𝑉 Where Smax = Transformer Apparent Power In Mva, Kv = Line Voltage In Kilovolts Thus For Delta Connected Winding, 𝐼𝐹𝐿 = 60∗1000 3∗132 = 262.44 Amps. Select Current Transformers (Cts) Of 300:5a Ratio For The Primary Windings. Ct Secondary Current To The Relay Is 𝐼𝑟𝑒𝑙𝑎𝑦 = IFl Ctr = 262.44∗5 300 = 4.374 For Star Connected Winding, 𝐼𝐹𝐿= 60∗1000 3∗33 = 1049.76 Amps. Select Current Transformers (Cts) Of 1200:5a Ratio For The Primary Windings. Ct Secondary Current To The Relay Is 𝐼𝑟𝑒𝑙𝑎𝑦 = IFl Ctr = 1049.76∗5 1200 = 4.374 Amps. Result Show That Thesum Of The Currents Entering Theprimary Restraint Windings Of The Differential Relay Equals The Sum Of The Currents Leaving The Secondaryrestraintwinding; Hence The Differential Relay Operating Current Is Zero. This Concludes That There Is No Fault In The Protection Zone.
  • 5. Power Transformer Differential Relay Inrush Restraint Setting Applications DOI: 10.9790/1676-1101046875 www.iosrjournals.org 72 | Page Differential element Setting An Instantaneous (High Set) Differential Element Remove The Transformerquickly From Service In The Event Of Severe Internal Faults And To Eliminate The Effects Of Dc Offsets And Harmonics, The Relay Trips On The Sensing Of Sequential Positive And Negative Peak Currents Whose Magnitude Exceeds The High Set Trip Level. This Element Operates Within 15 Milli-Seconds.During Transformer Energization, Significant 2nd Harmonic Current Is Present, Which May Result In False Trips. This Requires The Relay To Suppress Its Response To The 2nd Harmonic Component Of Current. The Differential Relay Allows For Adjustment Of The 2nd Harmonic Restraint Element Over The Range Of 0.1 To 0.3 P.U. Of The Transformer’s Rated Current. Similarly, Over-Excitation Of The Transformer Results In Significant Levels Of 5th Harmonic Current.For Transformer Protection Applications These Settings Provide High-Speed Clearing Of Transformer Faults And Proper Restraint For Inrush Events. For A Few Applications, Lowering The Harmonic Restraint Setting, Is Necessary To Ensure That Transformer Energization Occur Successfully Where Very Low Second Harmonic Inrush Levels Are Present. Testing Of Inrush Restraint Methods To Determine The Most Appropriate Choice For The Inrush Restraint Method And The Inrush Restraint Mode, A Simple Laboratoryexperimental Procedure Wasperformed Along With Actual Operating Experience To Develop The Standard Settings For The Inrush Restraint Function. The Schweitzerengineering Laboratories (Sel-487) Microprocessor-Based Relay Type Was Configured To Some Inrush Restraint Function And Level Setting Method. The Procedure Was To Simply Choose Some Settings For The Relay, Connect The Relay To A Three- Phase Test Set, And Simulates The System Using Alternative Transient Program (Atp) Software To Examine The Level Of The Second Harmonic Presents. Figure 5(A) Shows Waveform Of Inrush Current And (B) Mal- Operation Of A Differential Relay Caused By Low Levels Of The Second Harmonic Current During Energization Of A Transformer. These Tests Were Repeated Using Different Set Points And Different Restraint Functions Until A Standard Setting Operating Criteria Was Determined. This Standard Package Of Settings Was Confirmed By Capturing Transformer In-Rush Records From Various Installations And Comparing The Set Point Levels To Actual Second Harmonic Levels To Confirm There Is Enough Margins. Before Beginning The Setting And Testing, We Set The Following Criteria For Acceptable Settings.  A Minimum Level Setting For Harmonic Restraint At 15%.  No Operating Time Delay For The Differential Element Is Introduced By The Selected Inrush Restraint Function Or Inrush Restraint Mode.  The Differential Element Is Blocked From Operating During This Actual Energization Event. In Addition, The Inrush Restraint Mode Was Implemented Using The Flexible Configuration Logic Of The Relay. This Test Procedure Uses Star-Connected Cts That Are Typical On New Installations Using Microprocessor-Based Differential Relays. Figure 5: (A) Inrush Current Figure 5: (B) Second Harmonicsduring Energization Characteristic
  • 6. Power Transformer Differential Relay Inrush Restraint Setting Applications DOI: 10.9790/1676-1101046875 www.iosrjournals.org 73 | Page III. Results And Discussion The Differential Relay Element Set Point For The Inrush Restraint Current Was 15% Of Second Harmonics, While The Fifth Harmonics Was Set At 35%.These Setting Provide A Good Margin Of Security For Energization Of The Transformer Where The Second Harmonic Current May Fall To Low Levels.The Settings Were Successfully Restraining The Differential Element When Faced With A Fault Recovery Magnetizing Inrush Event.The Operation Of The Differential Element On Any Phase Operates The Circuit Breakers Supplying The Transformer. The Restraint Criterion Was Met On All Phases, As The Transformer Do Not Tripped During Energization Or Sympathetic Inrush. For This Application, The Magnetizing Inrush Currents During Energization Of The Transformer Were High Enough To Cause Operation Of The Differential Element. Result Show That The Sum Of The Currents Entering The Primary Restraint Windings Of The Differential Relay Equals The Sum Of The Currents Leaving The Secondary Restraint Winding; Hence The Differential Relay Operating Current Is Zero. This Concludes That There Is No Fault In The Protection Zone. The Results Of The Sel-487 Microprocessor-Based Differential Relay Field Configuration And Harmonic Restraint Settings Are Tabulated In Table 1and 2, And Detailed Test Procedure Flow Chart Is Shown In Figure 6.These Results Match The Expected Results For The Different Inrush Restraint Modes. Table 1: Sel-551 Relay Differential Settings (Field Configuration) Setting Label Definition Limits Rid Relay Identifier Sap- 1 Tid Terminal Identifier Line 1 E87w1-A, Enable Winding 1-A In Differential Yes E87w1-B, Enable Winding 1-B In Differential Yes E87w1- C. Enable Winding 1-C In Differential Yes E87w2-A, Enable Winding 2-A In Differential Yes E87w2-B, Enable Winding 2-B In Differential Yes E87w2-C. Enable Winding 2-C In Differential Yes W1ct-A, Winding 1-A, Ct Connection (Delta, Star) Star (Y) W1ct-B, Winding 1-B, Ct Connection (Delta, Star) Star (Y) W1ct-C. Winding 1-C, Ct Connection (Delta, Star) Star (Y) W2ct-A, Winding 2-A, Ct Connection (Delta, Star) Star (Y) W2ct-B, Winding 2-B, Ct Connection (Delta, Star) Star (Y) W2ct-C, Winding 2-C, Ct Connection (Delta, Star) Star (Y) Mva Maximum Transformer Capacity, Three-Phase 60 Mva Ctr1-A,(Pri) Winding 1-A, Ct Ratio (Ipri/In) 300:5 A Ctr1-B,( Pri) Winding 1-B, Ct Ratio (Ipri/In) 300:5 A Ctr1-C,( Pri) Winding 1-C, Ct Ratio (Ipri/In) 300:5 A Ctr2-A,( Sec) Winding 2-A, Ct Ratio (Isec/In) 1200:5 A Ctr2-B,( Sec) Winding 2-B, Ct Ratio (Isec/In) 1200:5 A Ctr2-C,(Sec) Winding 2-C, Ct Ratio (Isec/In) 1200:5 A Icom Define Internal Winding / Ct Connection Compensation Star (Y) W1ctvg Winding 1a,B,C (Delta) Vector Group Compensation Dyn 1, (Dab) Vwdg1 Winding 1a,B,C Line Voltage, Kv 132kv Vwdg2 Winding 2a,B,C Line Voltage, Kv 33kv Wdg1(Pri) I Winding 1a,B,C Line Currents (Amps) 262.44 Wdg2(Sec) I Winding 2a,B,C Line Currents (Amps) 1049.76 Nfreq Nominal Frequency Hz 50 Hz, Phrot Phase Sequence Rotation Abc, Date-F Month/Day/Year Format Mdy Table 2: Differential Elements Relay Settings (Harmonic Restraint Results). Display Descriptions Setting Wdg1(Pri) Winding 1(A,B&C) Currents( 0.5 - 155 A Secondary) 4.374 Wdg2(Sec) Winding 2(A,B&C) Currents( 0.5 - 155 A Secondary) 4.374 087p Restrained Element Operating Current P.U 0.3 Slp1 Restraint Slope 1 Percentage (5 – 100%) 25 Slp2 Restraint Slope 2 Percentage (Off, 25 – 200%) 50 Irsi Restraint Current Slope 1 Limit ((1-20) Multiple Of Tap) 3 U87p Unrestrained Element Current Pu((1-20) Multiple Of Tap) 10 Pct2 Second- Harmony Blocking Percentage (Off, 5-100%) 15 Pct5 Fifth- Harmony Blocking Percentage (Off, 5-100%) 35 Th5p Fifth- Harmony Alarm Threshold (Off, 0.02 -3.2) Off Ihbl Independent Harmonic Blocking (Y, N) Nil
  • 7. Power Transformer Differential Relay Inrush Restraint Setting Applications DOI: 10.9790/1676-1101046875 www.iosrjournals.org 74 | Page SET RELAY MODE SET RELAY LEVEL PLAY FAULT DIFFRENTIAL TRIP RECORD MODE LEVEL CHANGE MODE REDUCE LEVEL Figure6: Differential Relay Test Procedures Flow Chart Advantages Of Microprocessor-Based Differential Relay Protection  High Stability Against Ct Saturation Provided By Integrated Saturation Detector And Add-On Stabilization  High Stability Against Inrush Currents Due To Advanced Filter Technology And Optional Cross-Blocking Function.  High Stability Against Over-Excitation ( 5th Harmonic Blocking)  Short Tripping Time - Typically 1.5 Cycles  High Set Fast Tripping Less Than One (1) Cycle  Sensitive Earth Differential Protection Against Interturn Faults And Earth Faults Near Winding Neutral  Integral Ratio And Vector Group Adaptation  Integral Thermal Overload Protection  External Start Of Fault Recording IV. Conclusions The Settings Of Inrush Restraint For Transformer Differential Protection Used Harmonic Restraint In A Per-Phase Mode, With A Restraint Level Of 15% Of Second Harmonics And 35% Of Fifth Harmonics. These Settings Provide High-Speed Clearing Of Transformer Faults And Proper Restraint For Inrush Events. Lowering The Harmonic Restraint Settingensure That Transformer Energizations Occur Successfully Where Very Low Second Harmonic Inrush Levels Are Present.The Operation Of The Differential Element On Any Phase Operates The Circuit Breakers Supplying The Transformer. The Restraint Criterion Was Met On All Phases, As The Transformer Do Not Tripped During Energization Or Sympathetic Inrush. The Setting Is Sensitive Enough To Recognize Magnetizing Inrush Current Even With Low Levels Of Second Harmonics; And Selective To Distinguish Between An Inrush Event And Other Events That May Produce Second Harmonic Current. The Magnetizing Inrush Currents During Energization Of The Transformer Were High Enough To Cause Operation Of The Differential Element.The Sum Of The Currents Entering The Primary Restraint Windings Of The Differential Relay Equals The Sum Of The Currents Leaving The Secondary Restraint Winding; Hence The Differential Relay Operating Current Is Zero. This Concludes That There Is No Fault In The Protection Zone.Harmonic Blocking Or Harmonic Restraint Elements Permit Fast Tripping For All Internal Transformer Faults With Minimal Delay When Energizing A Faulted Transformer; Prevent Transformer Differential Relay Operation During Transformer Over Excitation, Prevent Differential Element Operation During Transformer Energization And During Voltage Recovery Following A Power System Fault. References [1] Sandro G. A.P.2006. Modeling Relays For Power System Protection Studies, Canada. [2] Grigsby L. L.2001.“The Electric Power Engineering Handbook”, Crc Press Llc, Boca Raton, Fl, P. 3-29. [3] bangbee J.O.,2014. “Ph.D. Thesis, Current Transformer Saturation Impacts On Microprocessor-Based Protective Relays Application In Nigeria Electricity Transmission Network”, University Of Benin, Nigeria [4] W. K. Sonnemann, C. L. Wagner, And G. D. Rockefeller,1958.“Magnetizing Inrush Phenomena In [5] Transformer Banks,” Aiee Transactions, Vol. 77, Part Iii, Pp. 884892. [6] J. Berdy, W. Kaufman, And K. Winick,1976. “A Dissertation On Power Transformer Excitation And Inrush Characteristics,” Symposium On Transformer Excitation And Inrushcharacteristics And Their Relationship To Transformer Protective Relaying, Houston, Tx. [7] Abb Operational Manual Md32-T Type,2007. “Digital Multifunction Transformer Differential Protection Relay”. [8] Blackburn J. Lewis And Thomas J. Domin, 2007. “Protective Relaying Principles And Applications, Thirdedition”Pp.292-297 [9] Horowitz S. H, And Phadke A. G.,1995. “Power System Relaying, Third Edition”, Research Studies Press Ltd., Somerset, England.
  • 8. Power Transformer Differential Relay Inrush Restraint Setting Applications DOI: 10.9790/1676-1101046875 www.iosrjournals.org 75 | Page [10] Saled M. M.,2001. “A Study On The Inrush Current Phenomena In Transformer Substation”, Conference Record Of The 36th annual Meeting Of The Ias,Pp. 1180-1187. [11] Horowitz S. H, And Phadke A. G.,2008. “Power System Relaying, Third Edition”, Research Studies Press Ltd., Somerset, England, Pp. 201-206. [12] Kobet G. L. And Patterson R. W.2000. “Matlab Analysis Of Braytown Transformer Differential Inrush [13] Misoperation” Georgia Tech Fault And Disturbance Analysis Conference, Atlanta, Ga [14] Schweitzer Engineering Laboratories (Sel),2007. Digital Differential Relays Operational Manual. .