International Journal of Research in Engineering and Science (IJRES)
ISSN (Online): 2320-9364, ISSN (Print): 2320-9356
www.ijres.org Volume 5 Issue 8 ǁ August. 2017 ǁ PP. 68-73
www.ijres.org 68 | Page
Harmonic AnalysisofDistribution System Due to Embedded
Generation Injection
*
Achadiyah A.N.1
,Suyono H.2
,Hasanah R. N.3
(Department Of Electrical Engineering, Faculty OfEngineering, Brawijaya University, Malang, Indonesia)
Corresponding author
*
Achadiyah A.N.
ABSTRACT:The increased demand for electricity and the depletion of fossil energy sources are a challenge
to exploit new and renewable energy sources. Relatively cheap renewable energy sources are Wind Power Plant
(WPP) and Photovoltaic System (PV). Currently, many small scale generating plants are being evolved into
conventional systems known as Embedded Generation (EG). EG as a source of electricity in the distribution
system will affect the flow of system power, system reliability, voltage profile and others. Besides, with the
placement of converter technology in WPP and PV system will give contribution of harmonic enhancement to
the system. This paper presents the harmonic analysis of WPP and PV designs that are injected into
conventional distribution system in one bus at Pujon feeder station Malang, Indonesia. The bus is chosen
because in this area the need for electric power in the area is very high and the existing system has a harmonic
value of 11%. Hybrid Active Filter (HAF) is designed to lower the voltage harmonics due to EG injection into
existing systems without affecting harmonics in other buses. To analyze the harmonics in this study there are 4
scenarios offered: Scenario 1 starts with analysis on existing system, scenario 2 existing in WPP 2 MVA
injection, scenario 3, injection1.3 MVA PV, scenario 4 injected EG (WPP and PV). The simulation result using
PSCAD 4.5 shows in scenario 4 to generate harmonic voltage of 18.6% and after added with HAF, the harmonic
value of the voltage becomes 2.434%.
Keywords: Embedded Generation, Harmonic, Photovoltaic System, Wind Power Plant.
I. INTRODUCTION
As 87.8% of electrical power requirement in Indonesia still utilizes fossil fuel, while the renewable
energy usage is only in a level of 12.2%, i.e. water potential power (9.1%), biomass power (2.66%), wind power
(0.002%), and solar power (0.16%) [1]. The renewable energy source utilizes natural resources by using small-
scale power plant which is known as EG. Hakim [2] creates a feasibility study of hybrid power plant with
maximum capacity of WPP for 2 MVA and of PV for 1.3 MVA located in Mount Banyak, Batu City. Jenkins
[3][4] conducted a research about distributed small-scale power plant which is injected to the distribution system
called the Embedded Generation (EG), which in turn helps electric power requirement.
Suyono [5] shows that injection from EG influences the power system reliability. It consists of voltage
profile, power flow, losses on system, e.g. harmonic. Hasan [6] reduces harmonic value inside WPP using
hybrid filter, i.e. serial connected active filter with shunt passive filter. Kalbat [7] analyzes total harmonic in PV
system design and simulated with PSCAD software.This paper analyzes harmonic voltage from EG design with
hybridized from 2 MVA WPP and 1.3 MVA PV. The design was simulated with PSCAD and the EG was
injected into Pujon Feeder Distribution System.Leopold [8] uses hybrid active power filter for filtering the
harmonic current in EG system by connecting active filter in series circuit with passive filter. Sushare [9] uses
passive filter to eliminate load harmonic and active filter for improving the performance of passive filter. Tzung-
Ling [10] designs Hybrid Active Filter Unit (HAFU) to supress harmonic resonance and to decrease hasrmonic
distortion. The design of EG is then simulated by injecting hybrid system with bus in Pujon Feeder Station with
20 kV medium voltage. The design is expected to give solution to the lack of power supply and the high
harmonic in Pujon Feeder Station.
According to the PT. PLN Gardu Induk Sengkaling, the Pujon Feeder Station still has power shortage
and voltage harmonic as high as 11%, exceeding IEEE 519-1992 standard. Generally, the power shortage in
Pujon is caused by the settlement located in hilly region, while the harmonic high value is mostly caused by tour
sites operating many electric motors. Such problems lead this research into designing EG-injected grid system
and adding HAF in order to decrease harmonic value, which in turn would resulting a reliable electrical power.
II. WIND POWER PLANT (WPP)
According to Ana [11], WPP is consisting of one or more wind turbine. The turbine selection will
determine the quality of power produced. Patel [12] says that wind turbine in WPP system are arranged in
parallel to produce electricity. The choice of turbine type is then based on wind speed, tower structure, count of
rotor blades, the shaft, the generator, the fan, and the control system. Controlling the stability of power
Harmonic Analysis of Distribution System Due To Embedded Generation Injection
www.ijres.org 69 | Page
produced, it also requires anemometer, sensors, stall controllers, power electronics, battery, and mechanical
transmission. Power electronic has a purpose to convert the electrical energy as needed. However, the
components inside power electronics tend to rise the harmonic in WPP system.
Fig.1.Working principle of WPP
Once the wind turns the blades of the turbine, the rotation is then transmitted to the generator rotor
located behind the wind turbine. The generator converts this mechanical rotation energy into electricity, which
generated by the alteration of magnetic flux in the stator and produces AC voltage and current. Prior to the
distribution, it is usually first stored in the batteries, hence it needs rectifier for converting from AC into DC.
The work of this rectifier plays a major role in harmonic generation in WPP system.Generally, the electrical
system of the WPP is divided in two, i.e. fixed speed and variable speed. Considering the wind source in Mount
Banyak, Batu as high as 12 m/s and located on hilly location, the design uses fixed speed turbine and 3-blade
horizontal axis. With this conversion from AC to DC, further analysis about voltage harmonic caused by the
conversion is required.
III. PV SYSTEM
Patel [12] says that the PV system main components are PV cell module, solar radiation, and the
module surface temperature. P System possesses an ability to convert photon from solar radiation into DC
power. The amount of voltage and current depends on the intensity of photon hit the PV cell surface. With the
intensity of the solar rays on the earth surface of 1000 watts with 25 °C, the PV is designed to have 1.3 MVA
capacity. The electricity generated by the PV is then charged into battery, and then converted into AC by
inverter to the transformer and injected directly into Pujon Feeder Station distribution grid.
The presence of inverter, however, leads to harmonic voltage increasing in the system. It can be
reduced by filter. The main purpose of the filter is to reduce the amplitude of specific frequencies of a current or
voltage. On the other side, installation of harmonic filters in the power system makes suppression in harmonic
current spreading to the entire grid.
IV. SIMULATION RESULT
4.1 Existing
The existing data used is originated from Sengkaling Relay Station, which has 2 150/20 kV
transformers with 30 MVA and 60 MVA capacities, respectively. The Pujon Feeder Station is a feeder in
Sengkaling Relay Station which is supplied from transformer of 150/20 kV 300 MVA with 300 A nominal load
capacity. The feeder station installs distribution relay as many as 71 units with each capacity ranged from 25
kVA to 250 kVA.
The Pujon Feeder Station currently operates in average load on 67th
bus with voltage harmonic value as
high as 11%. It exceeds the IEEE 519-1992 standard, which is 5% on 20 kV. By using data from Pujon Feeder
Station, simulation provides 10.853% harmonic voltage and 27.5% total harmonic distortion (THD). Visually,
simulated harmonic voltage and THD is shown in Figure 2. The primary side of 67th
bus experienced voltage
drop from 20 kV to 17 kV, as shown in Figure 3.
Harmonic Analysis of Distribution System Due To Embedded Generation Injection
www.ijres.org 70 | Page
Fig.2.Harmonic voltage graphical representation (existing)
Fig.3.The 67th
bus voltage in graphical representation (existing)
4.2 Existing + WPP 2 MVA
The second scenario is to design 2 MVA WPP and connect it with the existing 20 kV. WPP is then
connected to the existing without both battery and control system. The 2 MVA WPP is designed with output
voltage 690 V and then connected to the step down transformer 0.69/0.38 kV. The WPP system is then injected
directly to the 67th
bus in the secondary side on 0.38 kV. And the simulation results in voltage harmonic less
than 1%, 0.3753 kV voltages and 1.2 MW power. The harmonic value in this scenario is small because of no
control system connected to the system. The graphical representation of the voltage and the harmonic is shown
in Figure 4.
(a) (b)
Fig.4.(a) Graphicalvoltageon bus 67th
, (b) Harmonic on bus 67th
4.3Existing + PV 1.3 MVA
The third scenario is to connect between Pujon existing feeder and PV system. It joins 1.3 MVA PV
system into 67th
bus on Pujon Feeder Station. This bus is selected since it is located in tourist area which has
high power demand and high harmonic. The output of the PV system will be 0.83 kV DC and 1.3 MVA and
then stored in the battery. The battery power drain is then converted into AC 380 V, and converted again into
HarmonikIndividual
100.0
0.0
[3] 10.5832
THDTegangan
100.0
0.0
[1] 27.5086
Harmonic (%)
100.0
0.0
[3] 0.0788124
Harmonic Analysis of Distribution System Due To Embedded Generation Injection
www.ijres.org 71 | Page
0.295/16.53 kV with 0.9 MW power as displayed in Figure 5. This system produces voltage harmonic 8.62%
and total THD of 22.622% as shown in Figure 6.
(a) (b)
Fig.5.(a) Primary Voltage , (b) Secondaryvoltage on bus 67th
(a) (b)
Fig.6 (a) THD Voltage, (b) Harmonic on bus 67th
4.4 Embedded Generation (Existing + WPP + PV)
The fourth scenario is to join WPP and PV design into existing. Prior to existing injection, WPP and
PV are joined together, and the WPP system has the output converted into DC by using rectifier. The output
voltage from WPP is then combined with PV output and DC link 1.76 F. The DC current is then stored in
battery with output voltage of0.453 kV. Just beforeinjection to the existing, the DC is supplied to the inverter
and passive filter to generate AC power of 0.3781 kV. Figure 7 displays the voltage before and after filtering.
Fig.7 Hybrid output voltage of the system
THDVoltage (%)
100.0
0.0
[1] 22.622
Harmonic (%)
100.0
0.0
[3] 8.62858
Harmonic Analysis of Distribution System Due To Embedded Generation Injection
www.ijres.org 72 | Page
The hybrid of WPP and PV is then connected to the 0.38/20 kV step up transformer, and injected to the
67th
bus. As shown by the simulation, the injection of the hybrid system produce 18.6% voltage harmonic and
63.54% THD, and visually can be obtained from Figure 8. Generally, the EG system generates voltage of
0.3115/17 kV with voltage dropping more than 10% and 3.08 MW power. Figure 9(a) shows the graph of
voltage before injection of hybrid system, and Figure 9(b) shows the voltage after.
(a) (b)
Fig.8 (a) THD Voltage, (b) Harmonic on bus 67th
(a) (b)
Fig.9 (a) Voltage before injection, (b) Voltage after injection
The simulation result suggests that the hybrid injection produce distorted voltage, so it requires appropriate filter
to obtain sinusoidal voltage, as shown in Figure 8 and Figure 9. The installation of filter offered is using Hybrid
Active Filter (HAF) from the secondary side of 67th bus.
4.5 Embedded Generation (Existing + WPP + PV)by HAF
The final scenario is to join EG to HAF system. HAF is a combination of active and passive filter.
Akagi [13] stated that active filter works to improve the passive filter performance. HAF is connected to the
primary side of 67th
bus and it’s shown in Figure 10. Once the existing injected by EG, then the entire system is
then connected to the HAF. Simulation result before HAF showed 17.82/0.3374 kV voltage, 18.6% voltage
harmonic, and 63.54% THD. After HAF, simulation produces 17.82/0.3373 kV voltage, 2.43441% voltage
harmonic, and 23.4316% voltage THD. Table 1 shows distinction between the five different simulation.
Fig.10 Design Hybrid Active Filter (HAF)
THD Voltage (%)
100.0
0.0
[1] 63.5429
Voltage Harmonic (%)
100.0
0.0
[3] 18.6078
A
B
C
RLC
RLC
RLC
A
B
C
A
B
C
0.38 [kV]
#2#1
20 [kV]
100 [kVA]
5000[uF]
IdcLinkR
SIGA SIGB
5
SIGC
4
SIGAP
6
SIGBP
2
SIGCP
1 3
VdcLink
0.0001 [ohm]
0.1[uF]
V
V
A
V
A
V
A
Series
Active
Filter
N1 N2
BRK
Harmonic Series Active Filter
0.0009204303211[H]
0.0005692342284[H]252.517293[uF]
0.0005791819032[H]150.1337074[uF]
0.0004059864414[H]142.7955081[uF]
0.000407082963[H]102.3784571[uF]
0.0005877247729[H]53.26251836[uF]
306.0886924[uF]
Harmonic ShuntPassive Filter
Order5,7,9,11,13,15
V
A
V
A
V
A
Power
A
B
P
Iabc
P_in
Power
A
B
P
P_out
Idef
A
C
IM
B
W
S
T
2_PC_440
0.0
0.0
0.0
Harmonic Analysis of Distribution System Due To Embedded Generation Injection
www.ijres.org 73 | Page
Table 1.Embedded Generation (EG) Injection System Scenario
Scenario Existing
bus 67
WPP
2 MVA
PV
1.3 MVA
Harmonic Harmonic (%)
(%) Passive Active
1 √ - - 10.583 4.7 -
2 √ √ - 0.078 - -
3 √ - √ 11.0066 5.9 -
4 √ √ √ 18.6 6.72 2.43
V. CONCLUSION
The results of the analysis and simulation with 4 scenarios can be summarized as follows:
1. The harmonic analysis is performed to find the voltage profile, harmonic voltage and THD voltage.
2. In scenario 1, has a harmonics voltage of 10.583% and after the connect the passive filter down to 4.7%
3. Scenario 3, has a harmonic voltage of 11.0066% and after connected the passive filter drops to 5.9%.
4. Simulation in scenario 4 is generated HAF installation on EG system hence it will decrease harmonic
voltage value from 18.6% to 6.72% if only passive filter function. When the active filter is run as well then
the harmonic voltage becomes 2.43%.
5. The use of HAF generally improves the harmonic value of voltage on the system.
References
[1]. StatistikKetenagalistrikan. 2015. (Jakarta :EnergidanSumberDaya Mineral, 2016).
[2]. Hakim. L, Studikelayakanpembangkittenagahybridsurya-snginterhubunggriddi GunungBanyak Kota
Batu, thesis, Brawijaya University, Indonesia, 2015.
[3]. Jenkins N., Allan R., Cossley P., Kirschen D., and Strbac G., Embedded Generation, The Institution of
Electrical Engineers, London, UK, 2000.
[4]. Jenkins N., Ekanayake J.B., and Strbac G., Distributed Generation,The Institution of Engineering and
Technology, London, UK, 2010.
[5]. Suyono H. andHasanah R.N, Analysis of power losses due to distributed generation increase on
distribution system, Journal Technologi Science and Engineering, 78(6-3), 2016, 23-28.
[6]. HasanK.N.Md, KalleRauma, Alvaro Luna, Ignacio Candela J. and Rodriquez P., Harmonic resonances
damping using hybrid filter for WPP, Member IEEE, 2012, 1312-1319.
[7]. Kalbat A., PSCAD simulation of grid-tied photovoltaic systems and total harmonic distortion analysis, A
tutorial review, Proc. 3th IEEE International Conference on Electric Power and Energy Conversion
Systems,10 (2-4),Yildiz Technical University, Istanbul, Turkey, 2013.
[8]. Leopold Herman, Igor Papic and BostjanBlazic, A proportional-resonant current controller for selective
harmonic compensation in a hybrid active power filter, IEEE Transaction on Power Delivery, 29(5),
2014, 2055-2064.
[9]. Sushree D.S., PravatK.R.andMohanty K.B., Voltage compensation and stability analysis of hybrid series
active filter for harmonic components, Annual IEEE India Conference (INDICON), 2013.
[10]. Tzung-Lin L., Yen-Ching W., Jian-Cheng L., and Josep M.G., Hybrid active filter with variable
conductance for harmonic resonance suppression in industrial power systems, IEEE Transactions on
Industrial Electronics, 62(2), 2015.
[11]. Ana I., A dynamic wind generation model for power systems studies, Member IEEE, Transaction on
Power System, 19(2), 2004, 1387-1401.
[12]. Patel M.R., Wind and solar power system, (U.S. Merchant Marine AcademyKings Point, New York,
U.S.A., 2005)
[13]. Akagi H., Active harmonicfilters :A tutorial review, Proc. vol93, no.12, IEEE,2005.
*Achadiyah A.N. "Harmonic Analysis of distribution System Due to Embedded Generation Injection."
International Journal of Research in Engineering and Science (IJRES) 05.08 (2017): 68-73.

More Related Content

What's hot

Comparative of Conventional and Intelligence Controller based Hybrid Generati...
Comparative of Conventional and Intelligence Controller based Hybrid Generati...Comparative of Conventional and Intelligence Controller based Hybrid Generati...
Comparative of Conventional and Intelligence Controller based Hybrid Generati...IJERD Editor
 
Performance Analysis of DC Micro Grid with PV-Fuel Cell Hybrid Generation
Performance Analysis of DC Micro Grid with PV-Fuel Cell Hybrid GenerationPerformance Analysis of DC Micro Grid with PV-Fuel Cell Hybrid Generation
Performance Analysis of DC Micro Grid with PV-Fuel Cell Hybrid GenerationIJMREMJournal
 
Battery energy storage and power electronics based voltage and frequency cont...
Battery energy storage and power electronics based voltage and frequency cont...Battery energy storage and power electronics based voltage and frequency cont...
Battery energy storage and power electronics based voltage and frequency cont...IAEME Publication
 
Modified One Cycle Controlled Scheme for Single-Phase Grid Connected Pv-Fc Hy...
Modified One Cycle Controlled Scheme for Single-Phase Grid Connected Pv-Fc Hy...Modified One Cycle Controlled Scheme for Single-Phase Grid Connected Pv-Fc Hy...
Modified One Cycle Controlled Scheme for Single-Phase Grid Connected Pv-Fc Hy...IOSR Journals
 
Electric Vehicle as an Energy Storage for Grid Connected Solar Power System
Electric Vehicle as an Energy Storage for Grid Connected Solar Power SystemElectric Vehicle as an Energy Storage for Grid Connected Solar Power System
Electric Vehicle as an Energy Storage for Grid Connected Solar Power SystemIAES-IJPEDS
 
A New Simulation Approach of 3-Φ Transformer-less Grid Connected PV Inverter ...
A New Simulation Approach of 3-Φ Transformer-less Grid Connected PV Inverter ...A New Simulation Approach of 3-Φ Transformer-less Grid Connected PV Inverter ...
A New Simulation Approach of 3-Φ Transformer-less Grid Connected PV Inverter ...IRJET Journal
 
Enhancement of Voltage Stability by using Fuel Cell as Shunt Compensator
Enhancement of Voltage Stability by using Fuel Cell as Shunt CompensatorEnhancement of Voltage Stability by using Fuel Cell as Shunt Compensator
Enhancement of Voltage Stability by using Fuel Cell as Shunt CompensatorIRJET Journal
 
Development and Analysis of Fuzzy Control for MPPT Based Photovoltaic System
Development and Analysis of Fuzzy Control for MPPT Based Photovoltaic SystemDevelopment and Analysis of Fuzzy Control for MPPT Based Photovoltaic System
Development and Analysis of Fuzzy Control for MPPT Based Photovoltaic SystemIJERD Editor
 
Hybrid Green Energy Systems for Uninterrupted Electrification
Hybrid Green Energy Systems for Uninterrupted ElectrificationHybrid Green Energy Systems for Uninterrupted Electrification
Hybrid Green Energy Systems for Uninterrupted ElectrificationDr.NAGARAJAN. S
 
Fuzzy based Modular Cascaded H-Bridge Multilevel PV Inverter with Distributed...
Fuzzy based Modular Cascaded H-Bridge Multilevel PV Inverter with Distributed...Fuzzy based Modular Cascaded H-Bridge Multilevel PV Inverter with Distributed...
Fuzzy based Modular Cascaded H-Bridge Multilevel PV Inverter with Distributed...IJMTST Journal
 
A Wind driven PV- FC Hybrid System and its Power Management Strategies in a Grid
A Wind driven PV- FC Hybrid System and its Power Management Strategies in a GridA Wind driven PV- FC Hybrid System and its Power Management Strategies in a Grid
A Wind driven PV- FC Hybrid System and its Power Management Strategies in a GridIJERA Editor
 
GRC Martin 08 16
GRC Martin 08 16GRC Martin 08 16
GRC Martin 08 16Sean Martin
 
Implementation of two inductor boost converter for an autonomous photovoltaic...
Implementation of two inductor boost converter for an autonomous photovoltaic...Implementation of two inductor boost converter for an autonomous photovoltaic...
Implementation of two inductor boost converter for an autonomous photovoltaic...IAEME Publication
 

What's hot (20)

Comparative of Conventional and Intelligence Controller based Hybrid Generati...
Comparative of Conventional and Intelligence Controller based Hybrid Generati...Comparative of Conventional and Intelligence Controller based Hybrid Generati...
Comparative of Conventional and Intelligence Controller based Hybrid Generati...
 
Performance Analysis of DC Micro Grid with PV-Fuel Cell Hybrid Generation
Performance Analysis of DC Micro Grid with PV-Fuel Cell Hybrid GenerationPerformance Analysis of DC Micro Grid with PV-Fuel Cell Hybrid Generation
Performance Analysis of DC Micro Grid with PV-Fuel Cell Hybrid Generation
 
L01052101108
L01052101108L01052101108
L01052101108
 
Battery energy storage and power electronics based voltage and frequency cont...
Battery energy storage and power electronics based voltage and frequency cont...Battery energy storage and power electronics based voltage and frequency cont...
Battery energy storage and power electronics based voltage and frequency cont...
 
Modified One Cycle Controlled Scheme for Single-Phase Grid Connected Pv-Fc Hy...
Modified One Cycle Controlled Scheme for Single-Phase Grid Connected Pv-Fc Hy...Modified One Cycle Controlled Scheme for Single-Phase Grid Connected Pv-Fc Hy...
Modified One Cycle Controlled Scheme for Single-Phase Grid Connected Pv-Fc Hy...
 
Iu3416131619
Iu3416131619Iu3416131619
Iu3416131619
 
Power Quality Improvement by Solar Photo-voltaic / Wind Energy Integrated Sys...
Power Quality Improvement by Solar Photo-voltaic / Wind Energy Integrated Sys...Power Quality Improvement by Solar Photo-voltaic / Wind Energy Integrated Sys...
Power Quality Improvement by Solar Photo-voltaic / Wind Energy Integrated Sys...
 
Electric Vehicle as an Energy Storage for Grid Connected Solar Power System
Electric Vehicle as an Energy Storage for Grid Connected Solar Power SystemElectric Vehicle as an Energy Storage for Grid Connected Solar Power System
Electric Vehicle as an Energy Storage for Grid Connected Solar Power System
 
A New Simulation Approach of 3-Φ Transformer-less Grid Connected PV Inverter ...
A New Simulation Approach of 3-Φ Transformer-less Grid Connected PV Inverter ...A New Simulation Approach of 3-Φ Transformer-less Grid Connected PV Inverter ...
A New Simulation Approach of 3-Φ Transformer-less Grid Connected PV Inverter ...
 
Enhancement of Voltage Stability by using Fuel Cell as Shunt Compensator
Enhancement of Voltage Stability by using Fuel Cell as Shunt CompensatorEnhancement of Voltage Stability by using Fuel Cell as Shunt Compensator
Enhancement of Voltage Stability by using Fuel Cell as Shunt Compensator
 
Development and Analysis of Fuzzy Control for MPPT Based Photovoltaic System
Development and Analysis of Fuzzy Control for MPPT Based Photovoltaic SystemDevelopment and Analysis of Fuzzy Control for MPPT Based Photovoltaic System
Development and Analysis of Fuzzy Control for MPPT Based Photovoltaic System
 
Hybrid Green Energy Systems for Uninterrupted Electrification
Hybrid Green Energy Systems for Uninterrupted ElectrificationHybrid Green Energy Systems for Uninterrupted Electrification
Hybrid Green Energy Systems for Uninterrupted Electrification
 
Fuzzy based Modular Cascaded H-Bridge Multilevel PV Inverter with Distributed...
Fuzzy based Modular Cascaded H-Bridge Multilevel PV Inverter with Distributed...Fuzzy based Modular Cascaded H-Bridge Multilevel PV Inverter with Distributed...
Fuzzy based Modular Cascaded H-Bridge Multilevel PV Inverter with Distributed...
 
Fuzzy Logic based Maximum Power Point Tracker in Photovoltaic Cell
Fuzzy Logic based Maximum Power Point Tracker in Photovoltaic CellFuzzy Logic based Maximum Power Point Tracker in Photovoltaic Cell
Fuzzy Logic based Maximum Power Point Tracker in Photovoltaic Cell
 
Kw2519001905
Kw2519001905Kw2519001905
Kw2519001905
 
Performance analysis of hybrid photovoltaic/wind energy system using KY boost...
Performance analysis of hybrid photovoltaic/wind energy system using KY boost...Performance analysis of hybrid photovoltaic/wind energy system using KY boost...
Performance analysis of hybrid photovoltaic/wind energy system using KY boost...
 
Comparison study of lead-acid and lithium-ıon batteries for solar photovoltai...
Comparison study of lead-acid and lithium-ıon batteries for solar photovoltai...Comparison study of lead-acid and lithium-ıon batteries for solar photovoltai...
Comparison study of lead-acid and lithium-ıon batteries for solar photovoltai...
 
A Wind driven PV- FC Hybrid System and its Power Management Strategies in a Grid
A Wind driven PV- FC Hybrid System and its Power Management Strategies in a GridA Wind driven PV- FC Hybrid System and its Power Management Strategies in a Grid
A Wind driven PV- FC Hybrid System and its Power Management Strategies in a Grid
 
GRC Martin 08 16
GRC Martin 08 16GRC Martin 08 16
GRC Martin 08 16
 
Implementation of two inductor boost converter for an autonomous photovoltaic...
Implementation of two inductor boost converter for an autonomous photovoltaic...Implementation of two inductor boost converter for an autonomous photovoltaic...
Implementation of two inductor boost converter for an autonomous photovoltaic...
 

Similar to Harmonic AnalysisofDistribution System Due to Embedded Generation Injection

A Grid-Tied Solar Power System with Harmonic Filter to Enhance Power Quality
A Grid-Tied Solar Power System with Harmonic Filter to Enhance Power QualityA Grid-Tied Solar Power System with Harmonic Filter to Enhance Power Quality
A Grid-Tied Solar Power System with Harmonic Filter to Enhance Power QualityIRJET Journal
 
PV Hybrid System with DSTATCOM for Residential Applications
PV Hybrid System with DSTATCOM for Residential ApplicationsPV Hybrid System with DSTATCOM for Residential Applications
PV Hybrid System with DSTATCOM for Residential ApplicationsIDES Editor
 
Comparison of upqc and dvr in wind turbine fed fsig under asymmetric faults
Comparison of upqc and dvr in wind turbine fed fsig under asymmetric faultsComparison of upqc and dvr in wind turbine fed fsig under asymmetric faults
Comparison of upqc and dvr in wind turbine fed fsig under asymmetric faultselelijjournal
 
Advance Technology in Application of Four Leg Inverters to UPQC
Advance Technology in Application of Four Leg Inverters to UPQCAdvance Technology in Application of Four Leg Inverters to UPQC
Advance Technology in Application of Four Leg Inverters to UPQCIJPEDS-IAES
 
Power Quality Improvement Using Custom Power Devices in Squirrel Cage Inducti...
Power Quality Improvement Using Custom Power Devices in Squirrel Cage Inducti...Power Quality Improvement Using Custom Power Devices in Squirrel Cage Inducti...
Power Quality Improvement Using Custom Power Devices in Squirrel Cage Inducti...IJPEDS-IAES
 
IRJET- Impact of UPQC on Protection of Distributed Generation Integrated Dist...
IRJET- Impact of UPQC on Protection of Distributed Generation Integrated Dist...IRJET- Impact of UPQC on Protection of Distributed Generation Integrated Dist...
IRJET- Impact of UPQC on Protection of Distributed Generation Integrated Dist...IRJET Journal
 
A fault-tolerant photovoltaic integrated shunt active power filter with a 27-...
A fault-tolerant photovoltaic integrated shunt active power filter with a 27-...A fault-tolerant photovoltaic integrated shunt active power filter with a 27-...
A fault-tolerant photovoltaic integrated shunt active power filter with a 27-...IJECEIAES
 
International Journal of Engineering Research and Development (IJERD)
International Journal of Engineering Research and Development (IJERD)International Journal of Engineering Research and Development (IJERD)
International Journal of Engineering Research and Development (IJERD)IJERD Editor
 
Power Quality Enhancement in Wind Connected Grid System Interface Based On St...
Power Quality Enhancement in Wind Connected Grid System Interface Based On St...Power Quality Enhancement in Wind Connected Grid System Interface Based On St...
Power Quality Enhancement in Wind Connected Grid System Interface Based On St...IJERA Editor
 
Intelligent controller based power quality improvement of microgrid integrati...
Intelligent controller based power quality improvement of microgrid integrati...Intelligent controller based power quality improvement of microgrid integrati...
Intelligent controller based power quality improvement of microgrid integrati...IJECEIAES
 
Analyzing the Impacts of Solar PV Generation Integration on Radial Distributi...
Analyzing the Impacts of Solar PV Generation Integration on Radial Distributi...Analyzing the Impacts of Solar PV Generation Integration on Radial Distributi...
Analyzing the Impacts of Solar PV Generation Integration on Radial Distributi...IJCSIS Research Publications
 
Enhancement in Power Quality With Grid Interconnection of Renewable Energy So...
Enhancement in Power Quality With Grid Interconnection of Renewable Energy So...Enhancement in Power Quality With Grid Interconnection of Renewable Energy So...
Enhancement in Power Quality With Grid Interconnection of Renewable Energy So...IJERA Editor
 
Development of Load Control Algorithm for PV Microgrid
Development of Load Control Algorithm for PV Microgrid Development of Load Control Algorithm for PV Microgrid
Development of Load Control Algorithm for PV Microgrid IJECEIAES
 
Design_and_Investigation_of_FRT_Schemes_for_Three-Phase_Grid-Tied_PV_System.pdf
Design_and_Investigation_of_FRT_Schemes_for_Three-Phase_Grid-Tied_PV_System.pdfDesign_and_Investigation_of_FRT_Schemes_for_Three-Phase_Grid-Tied_PV_System.pdf
Design_and_Investigation_of_FRT_Schemes_for_Three-Phase_Grid-Tied_PV_System.pdfEngnr Kami Zeb
 

Similar to Harmonic AnalysisofDistribution System Due to Embedded Generation Injection (20)

Lu3620212028
Lu3620212028Lu3620212028
Lu3620212028
 
Af04603185190
Af04603185190Af04603185190
Af04603185190
 
A Grid-Tied Solar Power System with Harmonic Filter to Enhance Power Quality
A Grid-Tied Solar Power System with Harmonic Filter to Enhance Power QualityA Grid-Tied Solar Power System with Harmonic Filter to Enhance Power Quality
A Grid-Tied Solar Power System with Harmonic Filter to Enhance Power Quality
 
PV Hybrid System with DSTATCOM for Residential Applications
PV Hybrid System with DSTATCOM for Residential ApplicationsPV Hybrid System with DSTATCOM for Residential Applications
PV Hybrid System with DSTATCOM for Residential Applications
 
Comparison of upqc and dvr in wind turbine fed fsig under asymmetric faults
Comparison of upqc and dvr in wind turbine fed fsig under asymmetric faultsComparison of upqc and dvr in wind turbine fed fsig under asymmetric faults
Comparison of upqc and dvr in wind turbine fed fsig under asymmetric faults
 
Advance Technology in Application of Four Leg Inverters to UPQC
Advance Technology in Application of Four Leg Inverters to UPQCAdvance Technology in Application of Four Leg Inverters to UPQC
Advance Technology in Application of Four Leg Inverters to UPQC
 
Power Quality Improvement Using Custom Power Devices in Squirrel Cage Inducti...
Power Quality Improvement Using Custom Power Devices in Squirrel Cage Inducti...Power Quality Improvement Using Custom Power Devices in Squirrel Cage Inducti...
Power Quality Improvement Using Custom Power Devices in Squirrel Cage Inducti...
 
I1101047680
I1101047680I1101047680
I1101047680
 
High_reactive_power_DOC.docx
High_reactive_power_DOC.docxHigh_reactive_power_DOC.docx
High_reactive_power_DOC.docx
 
IRJET- Impact of UPQC on Protection of Distributed Generation Integrated Dist...
IRJET- Impact of UPQC on Protection of Distributed Generation Integrated Dist...IRJET- Impact of UPQC on Protection of Distributed Generation Integrated Dist...
IRJET- Impact of UPQC on Protection of Distributed Generation Integrated Dist...
 
Stability analysis of photovoltaic system under grid faults
Stability analysis of photovoltaic system under grid faultsStability analysis of photovoltaic system under grid faults
Stability analysis of photovoltaic system under grid faults
 
A fault-tolerant photovoltaic integrated shunt active power filter with a 27-...
A fault-tolerant photovoltaic integrated shunt active power filter with a 27-...A fault-tolerant photovoltaic integrated shunt active power filter with a 27-...
A fault-tolerant photovoltaic integrated shunt active power filter with a 27-...
 
International Journal of Engineering Research and Development (IJERD)
International Journal of Engineering Research and Development (IJERD)International Journal of Engineering Research and Development (IJERD)
International Journal of Engineering Research and Development (IJERD)
 
Power Quality Enhancement in Wind Connected Grid System Interface Based On St...
Power Quality Enhancement in Wind Connected Grid System Interface Based On St...Power Quality Enhancement in Wind Connected Grid System Interface Based On St...
Power Quality Enhancement in Wind Connected Grid System Interface Based On St...
 
Intelligent controller based power quality improvement of microgrid integrati...
Intelligent controller based power quality improvement of microgrid integrati...Intelligent controller based power quality improvement of microgrid integrati...
Intelligent controller based power quality improvement of microgrid integrati...
 
Analyzing the Impacts of Solar PV Generation Integration on Radial Distributi...
Analyzing the Impacts of Solar PV Generation Integration on Radial Distributi...Analyzing the Impacts of Solar PV Generation Integration on Radial Distributi...
Analyzing the Impacts of Solar PV Generation Integration on Radial Distributi...
 
Enhancement in Power Quality With Grid Interconnection of Renewable Energy So...
Enhancement in Power Quality With Grid Interconnection of Renewable Energy So...Enhancement in Power Quality With Grid Interconnection of Renewable Energy So...
Enhancement in Power Quality With Grid Interconnection of Renewable Energy So...
 
Modeling and Simulation of Grid Connected PV Generation System Using Matlab/S...
Modeling and Simulation of Grid Connected PV Generation System Using Matlab/S...Modeling and Simulation of Grid Connected PV Generation System Using Matlab/S...
Modeling and Simulation of Grid Connected PV Generation System Using Matlab/S...
 
Development of Load Control Algorithm for PV Microgrid
Development of Load Control Algorithm for PV Microgrid Development of Load Control Algorithm for PV Microgrid
Development of Load Control Algorithm for PV Microgrid
 
Design_and_Investigation_of_FRT_Schemes_for_Three-Phase_Grid-Tied_PV_System.pdf
Design_and_Investigation_of_FRT_Schemes_for_Three-Phase_Grid-Tied_PV_System.pdfDesign_and_Investigation_of_FRT_Schemes_for_Three-Phase_Grid-Tied_PV_System.pdf
Design_and_Investigation_of_FRT_Schemes_for_Three-Phase_Grid-Tied_PV_System.pdf
 

More from IJRESJOURNAL

Injection Analysis of Hera And Betano New Power Plants At the Interconnection...
Injection Analysis of Hera And Betano New Power Plants At the Interconnection...Injection Analysis of Hera And Betano New Power Plants At the Interconnection...
Injection Analysis of Hera And Betano New Power Plants At the Interconnection...IJRESJOURNAL
 
Decision Support System Implementation for Candidate Selection of the Head of...
Decision Support System Implementation for Candidate Selection of the Head of...Decision Support System Implementation for Candidate Selection of the Head of...
Decision Support System Implementation for Candidate Selection of the Head of...IJRESJOURNAL
 
Yield Forecasting to Sustain the Agricultural Transportation UnderStochastic ...
Yield Forecasting to Sustain the Agricultural Transportation UnderStochastic ...Yield Forecasting to Sustain the Agricultural Transportation UnderStochastic ...
Yield Forecasting to Sustain the Agricultural Transportation UnderStochastic ...IJRESJOURNAL
 
Injection Analysis of 5 Mwp Photovoltaic Power Plant on 20 Kv Distribution Ne...
Injection Analysis of 5 Mwp Photovoltaic Power Plant on 20 Kv Distribution Ne...Injection Analysis of 5 Mwp Photovoltaic Power Plant on 20 Kv Distribution Ne...
Injection Analysis of 5 Mwp Photovoltaic Power Plant on 20 Kv Distribution Ne...IJRESJOURNAL
 
Developing A Prediction Model for Tensile Elastic Modulus of Steel Fiber – Ce...
Developing A Prediction Model for Tensile Elastic Modulus of Steel Fiber – Ce...Developing A Prediction Model for Tensile Elastic Modulus of Steel Fiber – Ce...
Developing A Prediction Model for Tensile Elastic Modulus of Steel Fiber – Ce...IJRESJOURNAL
 
Effect of Liquid Viscosity on Sloshing in A Rectangular Tank
Effect of Liquid Viscosity on Sloshing in A Rectangular TankEffect of Liquid Viscosity on Sloshing in A Rectangular Tank
Effect of Liquid Viscosity on Sloshing in A Rectangular TankIJRESJOURNAL
 
Design and Implementation Decision Support System using MADM Methode for Bank...
Design and Implementation Decision Support System using MADM Methode for Bank...Design and Implementation Decision Support System using MADM Methode for Bank...
Design and Implementation Decision Support System using MADM Methode for Bank...IJRESJOURNAL
 
Investigations on The Effects of Different Heat Transfer Coefficients in The ...
Investigations on The Effects of Different Heat Transfer Coefficients in The ...Investigations on The Effects of Different Heat Transfer Coefficients in The ...
Investigations on The Effects of Different Heat Transfer Coefficients in The ...IJRESJOURNAL
 
Strategy of Adaptation of Traditional House Architecture Bali Aga
Strategy of Adaptation of Traditional House Architecture Bali AgaStrategy of Adaptation of Traditional House Architecture Bali Aga
Strategy of Adaptation of Traditional House Architecture Bali AgaIJRESJOURNAL
 
Design of Universal Measuring Equipment for Bogie Frame
Design of Universal Measuring Equipment for Bogie FrameDesign of Universal Measuring Equipment for Bogie Frame
Design of Universal Measuring Equipment for Bogie FrameIJRESJOURNAL
 
A Design Of Omni-Directional Mobile Robot Based On Mecanum Wheels
A Design Of Omni-Directional Mobile Robot Based On Mecanum WheelsA Design Of Omni-Directional Mobile Robot Based On Mecanum Wheels
A Design Of Omni-Directional Mobile Robot Based On Mecanum WheelsIJRESJOURNAL
 
An Investigation Into The Prevalence of Code Switching in the Teaching of Nat...
An Investigation Into The Prevalence of Code Switching in the Teaching of Nat...An Investigation Into The Prevalence of Code Switching in the Teaching of Nat...
An Investigation Into The Prevalence of Code Switching in the Teaching of Nat...IJRESJOURNAL
 
The Filling Up of Yogyakarta Governor Position in Social Harmony Perspective
The Filling Up of Yogyakarta Governor Position in Social Harmony PerspectiveThe Filling Up of Yogyakarta Governor Position in Social Harmony Perspective
The Filling Up of Yogyakarta Governor Position in Social Harmony PerspectiveIJRESJOURNAL
 
Quality Function Deployment And Proactive Quality Techniques Applied to Unive...
Quality Function Deployment And Proactive Quality Techniques Applied to Unive...Quality Function Deployment And Proactive Quality Techniques Applied to Unive...
Quality Function Deployment And Proactive Quality Techniques Applied to Unive...IJRESJOURNAL
 
The Analysis And Perspective on Development of Chinese Automotive Heavy-Duty ...
The Analysis And Perspective on Development of Chinese Automotive Heavy-Duty ...The Analysis And Perspective on Development of Chinese Automotive Heavy-Duty ...
The Analysis And Perspective on Development of Chinese Automotive Heavy-Duty ...IJRESJOURNAL
 
Research on the Bottom Software of Electronic Control System in Automobile El...
Research on the Bottom Software of Electronic Control System in Automobile El...Research on the Bottom Software of Electronic Control System in Automobile El...
Research on the Bottom Software of Electronic Control System in Automobile El...IJRESJOURNAL
 
Risk Based Underwater Inspection (RBUI) For Existing Fixed Platforms In Indon...
Risk Based Underwater Inspection (RBUI) For Existing Fixed Platforms In Indon...Risk Based Underwater Inspection (RBUI) For Existing Fixed Platforms In Indon...
Risk Based Underwater Inspection (RBUI) For Existing Fixed Platforms In Indon...IJRESJOURNAL
 
Dynamic Modeling of Four – Rotorcraft
Dynamic Modeling of Four – RotorcraftDynamic Modeling of Four – Rotorcraft
Dynamic Modeling of Four – RotorcraftIJRESJOURNAL
 
A New Approach on Proportional Fuzzy Likelihood Ratio orderings of Triangular...
A New Approach on Proportional Fuzzy Likelihood Ratio orderings of Triangular...A New Approach on Proportional Fuzzy Likelihood Ratio orderings of Triangular...
A New Approach on Proportional Fuzzy Likelihood Ratio orderings of Triangular...IJRESJOURNAL
 
Implementation of Fan6982 Single Phase Apfc with Analog Controller
Implementation of Fan6982 Single Phase Apfc with Analog ControllerImplementation of Fan6982 Single Phase Apfc with Analog Controller
Implementation of Fan6982 Single Phase Apfc with Analog ControllerIJRESJOURNAL
 

More from IJRESJOURNAL (20)

Injection Analysis of Hera And Betano New Power Plants At the Interconnection...
Injection Analysis of Hera And Betano New Power Plants At the Interconnection...Injection Analysis of Hera And Betano New Power Plants At the Interconnection...
Injection Analysis of Hera And Betano New Power Plants At the Interconnection...
 
Decision Support System Implementation for Candidate Selection of the Head of...
Decision Support System Implementation for Candidate Selection of the Head of...Decision Support System Implementation for Candidate Selection of the Head of...
Decision Support System Implementation for Candidate Selection of the Head of...
 
Yield Forecasting to Sustain the Agricultural Transportation UnderStochastic ...
Yield Forecasting to Sustain the Agricultural Transportation UnderStochastic ...Yield Forecasting to Sustain the Agricultural Transportation UnderStochastic ...
Yield Forecasting to Sustain the Agricultural Transportation UnderStochastic ...
 
Injection Analysis of 5 Mwp Photovoltaic Power Plant on 20 Kv Distribution Ne...
Injection Analysis of 5 Mwp Photovoltaic Power Plant on 20 Kv Distribution Ne...Injection Analysis of 5 Mwp Photovoltaic Power Plant on 20 Kv Distribution Ne...
Injection Analysis of 5 Mwp Photovoltaic Power Plant on 20 Kv Distribution Ne...
 
Developing A Prediction Model for Tensile Elastic Modulus of Steel Fiber – Ce...
Developing A Prediction Model for Tensile Elastic Modulus of Steel Fiber – Ce...Developing A Prediction Model for Tensile Elastic Modulus of Steel Fiber – Ce...
Developing A Prediction Model for Tensile Elastic Modulus of Steel Fiber – Ce...
 
Effect of Liquid Viscosity on Sloshing in A Rectangular Tank
Effect of Liquid Viscosity on Sloshing in A Rectangular TankEffect of Liquid Viscosity on Sloshing in A Rectangular Tank
Effect of Liquid Viscosity on Sloshing in A Rectangular Tank
 
Design and Implementation Decision Support System using MADM Methode for Bank...
Design and Implementation Decision Support System using MADM Methode for Bank...Design and Implementation Decision Support System using MADM Methode for Bank...
Design and Implementation Decision Support System using MADM Methode for Bank...
 
Investigations on The Effects of Different Heat Transfer Coefficients in The ...
Investigations on The Effects of Different Heat Transfer Coefficients in The ...Investigations on The Effects of Different Heat Transfer Coefficients in The ...
Investigations on The Effects of Different Heat Transfer Coefficients in The ...
 
Strategy of Adaptation of Traditional House Architecture Bali Aga
Strategy of Adaptation of Traditional House Architecture Bali AgaStrategy of Adaptation of Traditional House Architecture Bali Aga
Strategy of Adaptation of Traditional House Architecture Bali Aga
 
Design of Universal Measuring Equipment for Bogie Frame
Design of Universal Measuring Equipment for Bogie FrameDesign of Universal Measuring Equipment for Bogie Frame
Design of Universal Measuring Equipment for Bogie Frame
 
A Design Of Omni-Directional Mobile Robot Based On Mecanum Wheels
A Design Of Omni-Directional Mobile Robot Based On Mecanum WheelsA Design Of Omni-Directional Mobile Robot Based On Mecanum Wheels
A Design Of Omni-Directional Mobile Robot Based On Mecanum Wheels
 
An Investigation Into The Prevalence of Code Switching in the Teaching of Nat...
An Investigation Into The Prevalence of Code Switching in the Teaching of Nat...An Investigation Into The Prevalence of Code Switching in the Teaching of Nat...
An Investigation Into The Prevalence of Code Switching in the Teaching of Nat...
 
The Filling Up of Yogyakarta Governor Position in Social Harmony Perspective
The Filling Up of Yogyakarta Governor Position in Social Harmony PerspectiveThe Filling Up of Yogyakarta Governor Position in Social Harmony Perspective
The Filling Up of Yogyakarta Governor Position in Social Harmony Perspective
 
Quality Function Deployment And Proactive Quality Techniques Applied to Unive...
Quality Function Deployment And Proactive Quality Techniques Applied to Unive...Quality Function Deployment And Proactive Quality Techniques Applied to Unive...
Quality Function Deployment And Proactive Quality Techniques Applied to Unive...
 
The Analysis And Perspective on Development of Chinese Automotive Heavy-Duty ...
The Analysis And Perspective on Development of Chinese Automotive Heavy-Duty ...The Analysis And Perspective on Development of Chinese Automotive Heavy-Duty ...
The Analysis And Perspective on Development of Chinese Automotive Heavy-Duty ...
 
Research on the Bottom Software of Electronic Control System in Automobile El...
Research on the Bottom Software of Electronic Control System in Automobile El...Research on the Bottom Software of Electronic Control System in Automobile El...
Research on the Bottom Software of Electronic Control System in Automobile El...
 
Risk Based Underwater Inspection (RBUI) For Existing Fixed Platforms In Indon...
Risk Based Underwater Inspection (RBUI) For Existing Fixed Platforms In Indon...Risk Based Underwater Inspection (RBUI) For Existing Fixed Platforms In Indon...
Risk Based Underwater Inspection (RBUI) For Existing Fixed Platforms In Indon...
 
Dynamic Modeling of Four – Rotorcraft
Dynamic Modeling of Four – RotorcraftDynamic Modeling of Four – Rotorcraft
Dynamic Modeling of Four – Rotorcraft
 
A New Approach on Proportional Fuzzy Likelihood Ratio orderings of Triangular...
A New Approach on Proportional Fuzzy Likelihood Ratio orderings of Triangular...A New Approach on Proportional Fuzzy Likelihood Ratio orderings of Triangular...
A New Approach on Proportional Fuzzy Likelihood Ratio orderings of Triangular...
 
Implementation of Fan6982 Single Phase Apfc with Analog Controller
Implementation of Fan6982 Single Phase Apfc with Analog ControllerImplementation of Fan6982 Single Phase Apfc with Analog Controller
Implementation of Fan6982 Single Phase Apfc with Analog Controller
 

Recently uploaded

(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...ranjana rawat
 
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...srsj9000
 
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
Call Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile serviceCall Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile servicerehmti665
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingrakeshbaidya232001
 
main PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidmain PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidNikhilNagaraju
 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Christo Ananth
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSMANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSSIVASHANKAR N
 
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSHARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSRajkumarAkumalla
 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Dr.Costas Sachpazis
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Dr.Costas Sachpazis
 
Introduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxIntroduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxupamatechverse
 
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxJoão Esperancinha
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Serviceranjana rawat
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escortsranjana rawat
 

Recently uploaded (20)

(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
 
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
 
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
 
Call Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile serviceCall Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile service
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writing
 
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCRCall Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
 
main PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidmain PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfid
 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
 
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSMANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
 
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSHARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
 
Introduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxIntroduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptx
 
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
 
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
 
Roadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and RoutesRoadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and Routes
 
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptxExploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
 

Harmonic AnalysisofDistribution System Due to Embedded Generation Injection

  • 1. International Journal of Research in Engineering and Science (IJRES) ISSN (Online): 2320-9364, ISSN (Print): 2320-9356 www.ijres.org Volume 5 Issue 8 ǁ August. 2017 ǁ PP. 68-73 www.ijres.org 68 | Page Harmonic AnalysisofDistribution System Due to Embedded Generation Injection * Achadiyah A.N.1 ,Suyono H.2 ,Hasanah R. N.3 (Department Of Electrical Engineering, Faculty OfEngineering, Brawijaya University, Malang, Indonesia) Corresponding author * Achadiyah A.N. ABSTRACT:The increased demand for electricity and the depletion of fossil energy sources are a challenge to exploit new and renewable energy sources. Relatively cheap renewable energy sources are Wind Power Plant (WPP) and Photovoltaic System (PV). Currently, many small scale generating plants are being evolved into conventional systems known as Embedded Generation (EG). EG as a source of electricity in the distribution system will affect the flow of system power, system reliability, voltage profile and others. Besides, with the placement of converter technology in WPP and PV system will give contribution of harmonic enhancement to the system. This paper presents the harmonic analysis of WPP and PV designs that are injected into conventional distribution system in one bus at Pujon feeder station Malang, Indonesia. The bus is chosen because in this area the need for electric power in the area is very high and the existing system has a harmonic value of 11%. Hybrid Active Filter (HAF) is designed to lower the voltage harmonics due to EG injection into existing systems without affecting harmonics in other buses. To analyze the harmonics in this study there are 4 scenarios offered: Scenario 1 starts with analysis on existing system, scenario 2 existing in WPP 2 MVA injection, scenario 3, injection1.3 MVA PV, scenario 4 injected EG (WPP and PV). The simulation result using PSCAD 4.5 shows in scenario 4 to generate harmonic voltage of 18.6% and after added with HAF, the harmonic value of the voltage becomes 2.434%. Keywords: Embedded Generation, Harmonic, Photovoltaic System, Wind Power Plant. I. INTRODUCTION As 87.8% of electrical power requirement in Indonesia still utilizes fossil fuel, while the renewable energy usage is only in a level of 12.2%, i.e. water potential power (9.1%), biomass power (2.66%), wind power (0.002%), and solar power (0.16%) [1]. The renewable energy source utilizes natural resources by using small- scale power plant which is known as EG. Hakim [2] creates a feasibility study of hybrid power plant with maximum capacity of WPP for 2 MVA and of PV for 1.3 MVA located in Mount Banyak, Batu City. Jenkins [3][4] conducted a research about distributed small-scale power plant which is injected to the distribution system called the Embedded Generation (EG), which in turn helps electric power requirement. Suyono [5] shows that injection from EG influences the power system reliability. It consists of voltage profile, power flow, losses on system, e.g. harmonic. Hasan [6] reduces harmonic value inside WPP using hybrid filter, i.e. serial connected active filter with shunt passive filter. Kalbat [7] analyzes total harmonic in PV system design and simulated with PSCAD software.This paper analyzes harmonic voltage from EG design with hybridized from 2 MVA WPP and 1.3 MVA PV. The design was simulated with PSCAD and the EG was injected into Pujon Feeder Distribution System.Leopold [8] uses hybrid active power filter for filtering the harmonic current in EG system by connecting active filter in series circuit with passive filter. Sushare [9] uses passive filter to eliminate load harmonic and active filter for improving the performance of passive filter. Tzung- Ling [10] designs Hybrid Active Filter Unit (HAFU) to supress harmonic resonance and to decrease hasrmonic distortion. The design of EG is then simulated by injecting hybrid system with bus in Pujon Feeder Station with 20 kV medium voltage. The design is expected to give solution to the lack of power supply and the high harmonic in Pujon Feeder Station. According to the PT. PLN Gardu Induk Sengkaling, the Pujon Feeder Station still has power shortage and voltage harmonic as high as 11%, exceeding IEEE 519-1992 standard. Generally, the power shortage in Pujon is caused by the settlement located in hilly region, while the harmonic high value is mostly caused by tour sites operating many electric motors. Such problems lead this research into designing EG-injected grid system and adding HAF in order to decrease harmonic value, which in turn would resulting a reliable electrical power. II. WIND POWER PLANT (WPP) According to Ana [11], WPP is consisting of one or more wind turbine. The turbine selection will determine the quality of power produced. Patel [12] says that wind turbine in WPP system are arranged in parallel to produce electricity. The choice of turbine type is then based on wind speed, tower structure, count of rotor blades, the shaft, the generator, the fan, and the control system. Controlling the stability of power
  • 2. Harmonic Analysis of Distribution System Due To Embedded Generation Injection www.ijres.org 69 | Page produced, it also requires anemometer, sensors, stall controllers, power electronics, battery, and mechanical transmission. Power electronic has a purpose to convert the electrical energy as needed. However, the components inside power electronics tend to rise the harmonic in WPP system. Fig.1.Working principle of WPP Once the wind turns the blades of the turbine, the rotation is then transmitted to the generator rotor located behind the wind turbine. The generator converts this mechanical rotation energy into electricity, which generated by the alteration of magnetic flux in the stator and produces AC voltage and current. Prior to the distribution, it is usually first stored in the batteries, hence it needs rectifier for converting from AC into DC. The work of this rectifier plays a major role in harmonic generation in WPP system.Generally, the electrical system of the WPP is divided in two, i.e. fixed speed and variable speed. Considering the wind source in Mount Banyak, Batu as high as 12 m/s and located on hilly location, the design uses fixed speed turbine and 3-blade horizontal axis. With this conversion from AC to DC, further analysis about voltage harmonic caused by the conversion is required. III. PV SYSTEM Patel [12] says that the PV system main components are PV cell module, solar radiation, and the module surface temperature. P System possesses an ability to convert photon from solar radiation into DC power. The amount of voltage and current depends on the intensity of photon hit the PV cell surface. With the intensity of the solar rays on the earth surface of 1000 watts with 25 °C, the PV is designed to have 1.3 MVA capacity. The electricity generated by the PV is then charged into battery, and then converted into AC by inverter to the transformer and injected directly into Pujon Feeder Station distribution grid. The presence of inverter, however, leads to harmonic voltage increasing in the system. It can be reduced by filter. The main purpose of the filter is to reduce the amplitude of specific frequencies of a current or voltage. On the other side, installation of harmonic filters in the power system makes suppression in harmonic current spreading to the entire grid. IV. SIMULATION RESULT 4.1 Existing The existing data used is originated from Sengkaling Relay Station, which has 2 150/20 kV transformers with 30 MVA and 60 MVA capacities, respectively. The Pujon Feeder Station is a feeder in Sengkaling Relay Station which is supplied from transformer of 150/20 kV 300 MVA with 300 A nominal load capacity. The feeder station installs distribution relay as many as 71 units with each capacity ranged from 25 kVA to 250 kVA. The Pujon Feeder Station currently operates in average load on 67th bus with voltage harmonic value as high as 11%. It exceeds the IEEE 519-1992 standard, which is 5% on 20 kV. By using data from Pujon Feeder Station, simulation provides 10.853% harmonic voltage and 27.5% total harmonic distortion (THD). Visually, simulated harmonic voltage and THD is shown in Figure 2. The primary side of 67th bus experienced voltage drop from 20 kV to 17 kV, as shown in Figure 3.
  • 3. Harmonic Analysis of Distribution System Due To Embedded Generation Injection www.ijres.org 70 | Page Fig.2.Harmonic voltage graphical representation (existing) Fig.3.The 67th bus voltage in graphical representation (existing) 4.2 Existing + WPP 2 MVA The second scenario is to design 2 MVA WPP and connect it with the existing 20 kV. WPP is then connected to the existing without both battery and control system. The 2 MVA WPP is designed with output voltage 690 V and then connected to the step down transformer 0.69/0.38 kV. The WPP system is then injected directly to the 67th bus in the secondary side on 0.38 kV. And the simulation results in voltage harmonic less than 1%, 0.3753 kV voltages and 1.2 MW power. The harmonic value in this scenario is small because of no control system connected to the system. The graphical representation of the voltage and the harmonic is shown in Figure 4. (a) (b) Fig.4.(a) Graphicalvoltageon bus 67th , (b) Harmonic on bus 67th 4.3Existing + PV 1.3 MVA The third scenario is to connect between Pujon existing feeder and PV system. It joins 1.3 MVA PV system into 67th bus on Pujon Feeder Station. This bus is selected since it is located in tourist area which has high power demand and high harmonic. The output of the PV system will be 0.83 kV DC and 1.3 MVA and then stored in the battery. The battery power drain is then converted into AC 380 V, and converted again into HarmonikIndividual 100.0 0.0 [3] 10.5832 THDTegangan 100.0 0.0 [1] 27.5086 Harmonic (%) 100.0 0.0 [3] 0.0788124
  • 4. Harmonic Analysis of Distribution System Due To Embedded Generation Injection www.ijres.org 71 | Page 0.295/16.53 kV with 0.9 MW power as displayed in Figure 5. This system produces voltage harmonic 8.62% and total THD of 22.622% as shown in Figure 6. (a) (b) Fig.5.(a) Primary Voltage , (b) Secondaryvoltage on bus 67th (a) (b) Fig.6 (a) THD Voltage, (b) Harmonic on bus 67th 4.4 Embedded Generation (Existing + WPP + PV) The fourth scenario is to join WPP and PV design into existing. Prior to existing injection, WPP and PV are joined together, and the WPP system has the output converted into DC by using rectifier. The output voltage from WPP is then combined with PV output and DC link 1.76 F. The DC current is then stored in battery with output voltage of0.453 kV. Just beforeinjection to the existing, the DC is supplied to the inverter and passive filter to generate AC power of 0.3781 kV. Figure 7 displays the voltage before and after filtering. Fig.7 Hybrid output voltage of the system THDVoltage (%) 100.0 0.0 [1] 22.622 Harmonic (%) 100.0 0.0 [3] 8.62858
  • 5. Harmonic Analysis of Distribution System Due To Embedded Generation Injection www.ijres.org 72 | Page The hybrid of WPP and PV is then connected to the 0.38/20 kV step up transformer, and injected to the 67th bus. As shown by the simulation, the injection of the hybrid system produce 18.6% voltage harmonic and 63.54% THD, and visually can be obtained from Figure 8. Generally, the EG system generates voltage of 0.3115/17 kV with voltage dropping more than 10% and 3.08 MW power. Figure 9(a) shows the graph of voltage before injection of hybrid system, and Figure 9(b) shows the voltage after. (a) (b) Fig.8 (a) THD Voltage, (b) Harmonic on bus 67th (a) (b) Fig.9 (a) Voltage before injection, (b) Voltage after injection The simulation result suggests that the hybrid injection produce distorted voltage, so it requires appropriate filter to obtain sinusoidal voltage, as shown in Figure 8 and Figure 9. The installation of filter offered is using Hybrid Active Filter (HAF) from the secondary side of 67th bus. 4.5 Embedded Generation (Existing + WPP + PV)by HAF The final scenario is to join EG to HAF system. HAF is a combination of active and passive filter. Akagi [13] stated that active filter works to improve the passive filter performance. HAF is connected to the primary side of 67th bus and it’s shown in Figure 10. Once the existing injected by EG, then the entire system is then connected to the HAF. Simulation result before HAF showed 17.82/0.3374 kV voltage, 18.6% voltage harmonic, and 63.54% THD. After HAF, simulation produces 17.82/0.3373 kV voltage, 2.43441% voltage harmonic, and 23.4316% voltage THD. Table 1 shows distinction between the five different simulation. Fig.10 Design Hybrid Active Filter (HAF) THD Voltage (%) 100.0 0.0 [1] 63.5429 Voltage Harmonic (%) 100.0 0.0 [3] 18.6078 A B C RLC RLC RLC A B C A B C 0.38 [kV] #2#1 20 [kV] 100 [kVA] 5000[uF] IdcLinkR SIGA SIGB 5 SIGC 4 SIGAP 6 SIGBP 2 SIGCP 1 3 VdcLink 0.0001 [ohm] 0.1[uF] V V A V A V A Series Active Filter N1 N2 BRK Harmonic Series Active Filter 0.0009204303211[H] 0.0005692342284[H]252.517293[uF] 0.0005791819032[H]150.1337074[uF] 0.0004059864414[H]142.7955081[uF] 0.000407082963[H]102.3784571[uF] 0.0005877247729[H]53.26251836[uF] 306.0886924[uF] Harmonic ShuntPassive Filter Order5,7,9,11,13,15 V A V A V A Power A B P Iabc P_in Power A B P P_out Idef A C IM B W S T 2_PC_440 0.0 0.0 0.0
  • 6. Harmonic Analysis of Distribution System Due To Embedded Generation Injection www.ijres.org 73 | Page Table 1.Embedded Generation (EG) Injection System Scenario Scenario Existing bus 67 WPP 2 MVA PV 1.3 MVA Harmonic Harmonic (%) (%) Passive Active 1 √ - - 10.583 4.7 - 2 √ √ - 0.078 - - 3 √ - √ 11.0066 5.9 - 4 √ √ √ 18.6 6.72 2.43 V. CONCLUSION The results of the analysis and simulation with 4 scenarios can be summarized as follows: 1. The harmonic analysis is performed to find the voltage profile, harmonic voltage and THD voltage. 2. In scenario 1, has a harmonics voltage of 10.583% and after the connect the passive filter down to 4.7% 3. Scenario 3, has a harmonic voltage of 11.0066% and after connected the passive filter drops to 5.9%. 4. Simulation in scenario 4 is generated HAF installation on EG system hence it will decrease harmonic voltage value from 18.6% to 6.72% if only passive filter function. When the active filter is run as well then the harmonic voltage becomes 2.43%. 5. The use of HAF generally improves the harmonic value of voltage on the system. References [1]. StatistikKetenagalistrikan. 2015. (Jakarta :EnergidanSumberDaya Mineral, 2016). [2]. Hakim. L, Studikelayakanpembangkittenagahybridsurya-snginterhubunggriddi GunungBanyak Kota Batu, thesis, Brawijaya University, Indonesia, 2015. [3]. Jenkins N., Allan R., Cossley P., Kirschen D., and Strbac G., Embedded Generation, The Institution of Electrical Engineers, London, UK, 2000. [4]. Jenkins N., Ekanayake J.B., and Strbac G., Distributed Generation,The Institution of Engineering and Technology, London, UK, 2010. [5]. Suyono H. andHasanah R.N, Analysis of power losses due to distributed generation increase on distribution system, Journal Technologi Science and Engineering, 78(6-3), 2016, 23-28. [6]. HasanK.N.Md, KalleRauma, Alvaro Luna, Ignacio Candela J. and Rodriquez P., Harmonic resonances damping using hybrid filter for WPP, Member IEEE, 2012, 1312-1319. [7]. Kalbat A., PSCAD simulation of grid-tied photovoltaic systems and total harmonic distortion analysis, A tutorial review, Proc. 3th IEEE International Conference on Electric Power and Energy Conversion Systems,10 (2-4),Yildiz Technical University, Istanbul, Turkey, 2013. [8]. Leopold Herman, Igor Papic and BostjanBlazic, A proportional-resonant current controller for selective harmonic compensation in a hybrid active power filter, IEEE Transaction on Power Delivery, 29(5), 2014, 2055-2064. [9]. Sushree D.S., PravatK.R.andMohanty K.B., Voltage compensation and stability analysis of hybrid series active filter for harmonic components, Annual IEEE India Conference (INDICON), 2013. [10]. Tzung-Lin L., Yen-Ching W., Jian-Cheng L., and Josep M.G., Hybrid active filter with variable conductance for harmonic resonance suppression in industrial power systems, IEEE Transactions on Industrial Electronics, 62(2), 2015. [11]. Ana I., A dynamic wind generation model for power systems studies, Member IEEE, Transaction on Power System, 19(2), 2004, 1387-1401. [12]. Patel M.R., Wind and solar power system, (U.S. Merchant Marine AcademyKings Point, New York, U.S.A., 2005) [13]. Akagi H., Active harmonicfilters :A tutorial review, Proc. vol93, no.12, IEEE,2005. *Achadiyah A.N. "Harmonic Analysis of distribution System Due to Embedded Generation Injection." International Journal of Research in Engineering and Science (IJRES) 05.08 (2017): 68-73.