International Journal of Electrical and Computer Engineering (IJECE)
Vol. 7, No. 1, February 2017, pp. 86 – 99
ISSN: 2088-8708 86
Institute of Advanced Engineering and Science
w w w . i a e s j o u r n a l . c o m
Control of an Autonomous Hybrid Microgrid as Energy
Source for a Small Rural Village
Am´erico Joaquim Lampi˜ao*
, Tomonobu Senjyu*
, and Atsushi Yona*
*
Faculty of Engineering, Department of Electrical and Electronics Engineering
*
University of the Ryukyus, 1 Senbaru, Nishihara-cho, Nakagami, Okinawa, 903-0213, Japan
Article Info
Article history:
Received Oct 7, 2016
Revised Dec 11, 2016
Accepted Dec 24, 2016
Keyword:
Microgrid
Utility grid
Photovoltaic system
Battery energy system
Power balance
ABSTRACT
Nowadays, the exhaustion of electricity power in rural areas is becoming an important
issue for many African Nations. Moreover, challenges include the high cost of extend-
ing the power grid to these locations, the economic health of the utilities and lack of
revenue in impoverished villages. Numerous new initiatives are being implemented in
the countries some of them co-financed by international organizations. In this paper,
the hybrid microgrid is carried out as a feasible solution for a small rural village. A
model of hybrid microgrid consisting of combination of photovoltaic (PV) panels and
battery energy storage (BES) and a control system for managing the components of en-
tire system to feed the village as local load is proposed. The control system must avoid
the interruptions of power delivered to the consumers (village) and, therefore, good
quality and reliability of the system is required. The PI controllers are used to regu-
late the voltage and current using three-phase dq transformation, while the parameters
are determined using Ziegler-Nichols tuning method. The effectiveness of the pro-
posed method is verified by simulation results given by Matlab/SimPowerSystems R
environment.
Copyright c 2017 Institute of Advanced Engineering and Science.
All rights reserved.
Corresponding Author:
Am´erico Joaquim Lampi˜ao
Department of Electrical and Electronic Engineering
University of the Ryukyus
1 Senbaru, Nishihara-cho, Okinawa, 903-0213, Japan
Tel: +81-98-895-8686, +258-84-438-3831
Email: americo.lampiao@gmail.com
1. INTRODUCTION
Over 620 million people in Africa still do not have access to the electricity [1]. As known, electricity
is an essential contributor to the well-being of people and a key point of economic betterment for any country in
the world. In 2001, the US National Academy of Engineers (NAE) voted ”electrification” as the most significant
engineering achievement of the past century. According the worldwide calculation of electric consumption at
present, approximately 1.4 billion people more than 20 percent population all over the world does not have
access to electric connection and mostly live in rural areas in Africa [2]. The biggest challenges surrounding
energy in this locations is the high cost to extend the power grid from main to these locations. New initiatives
are being implemented using renewable energy source, but improvements are still required [3]. In this paper, a
model of autonomous hybrid microgrid supplying a small rural village as local load and the respective controller
is proposed to demonstrate their feasibility solution in rural villages. The hybrid source is a combined PV
panels and Battery storage, connected to the load through voltage source inverter (VSI), filter and isolating
transformer. The loads are typically rural such as mills, water pumps for irrigation, and small houses with one
or two compartments. The households mainly use the firewood for cooking, therefore, small power for each
house is expected. The use of PV panels as renewable energy has advantages due the environmental regulation
protection, but the generated power changes according the temperature and solar radiation [4]-[6]. This fact
Journal Homepage: http://iaesjournal.com/online/index.php/IJECE
Institute of Advanced Engineering and Science
w w w . i a e s j o u r n a l . c o m
, DOI: 10.11591/ijece.v7i1.12900
IJECE ISSN: 2088-8708 87
generates stability, reliability and power quality problems at the consumers [7]-[11].
The battery is used to overcome the intermittent and uncertain of the photovoltaic (PV) generation
[13]. The PV system is composed by PV panels and DC/DC boost converter. In order to maximize the efficiency
of the PVs and maintain the voltage at the DC-link, a combination of MPPT (maximum power point tracking)
and DC/DC boost converter is used. The MPPT uses an algorithm to maintain the generated power at maximum
point [11-13].
Depending on the PV generation and load demand, the battery may operate at either charging or
discharging mode. In discharging mode, the battery works as power source and injects power to the inverter
and, therefore makes balance between generation and load power demand. In charge mode, the battery receives
the power from PV system. These achievements are possible by using a DC/DC bidirectional converter. The
VSI is used to interface the DC-side with AC-side and, therefore, to convert DC current to AC with appropriate
natural frequency. The inverter operates in high frequency (around 5-20 kHz), and causes harmonic distortions
in output current [17]-[21], therefore, in this study a filter harmonics will be taken into account. In this paper,
an isolating transformer rated at 100 kVA, to step-up the line voltage from 230 V to 380 V, is used. In addition,
power supply companies demand this for the elimination of possible zero sequence or DC components in the
generated voltages and for increased protection it affords [9]. This fact can be used as an advantage since the
transformer can form part of a filter impedance and may, therefore, reduce the undesired harmonic content of
the output current. Power quality standards for connection of an inverter to the load are still under development,
since previously there have been few similar high power electronic applications. In this study the important
aspect of power quality is harmonic distortion. General requirements for harmonic distortion can be found in
standards IEEE [1547.1-1547.8].
The control solution proposed, provides high quality of current delivered to the consumers and, there-
fore, high power quality. In addition, active and reactive power control is provided. The choice of control
variables are based on standards, regulations and procedures presented in scientific publications. PLL (phase
locked loop) and PI controllers was used to accomplish the power management of the system using dq syn-
chronous reference. The parameters was determined using Ziegler-Nichols tuning method. Over the years,
considerable research has been conducted on current and voltage regulation in microgrids, and various ap-
proaches have been proposed. In this paper a review of the latest journal and conference papers related to
the control in microgrids are carried out to demonstrate the validity of the proposed method, performed using
MATLAB/ SimPowerSystems R
. Simulation results demonstrate the effectiveness of proposed controller and,
therefore, can be used to analyse microgrids connections.
The rest of the section in this paper is organized as follows: In Section II, the proposed model is
presented and the main components including control methodology are described. In Section III the discussion
of the simulation results to show the effectiveness of the proposed system is presented. Finally, conclusions are
drawn in Section IV.
2. RESEARCH METHOD
The methodology adopted in this study, is proposing the schematic configuration of the model to
be implemented and simulated using Matlab/Simulink environment. The components are described and the
simulation results are presented. The conclusion is based on the presented results. Figure 1, shows the proposed
model, and the description are presented below.
2.1. PV System
The PV array used in this paper acts as an input source for charging the battery as well as supplying to
the AC load during normal conditions. The basic equation of a PV panel is presented in [12]. Table 2, shows the
constant values for the standard state of each PV panel as used in the present study. As mentioned in preview
chapters, the PV generates intermittent power due the variation of sun’s radiation and cell temperature. In order
to maximize the power and maintain the voltage in DC-link at required level (400 V), a combined MPPT and
DC/DC boost converter are used. The MPPT aims at using an algorithm to ensure the array to operate at the
maximum power point [6]. There are many different MPPT methods. Perturbation and Observation (P&O)
method is used most widely since it is much simpler and needs fewer measured variables as input. In this study
P&O was used and performed according [4].
Control of an Autonomous Hybrid Microgrid as Energy Source for a Small ... (Am´erico J. Lampi˜ao)
88 ISSN: 2088-8708
B1
B1
B1
B1
B1
B1
R1 L1
PV_array
BESS
CBm
DC
MPPT
Boost converter 3-Phase VSI
RD
Cf
Clink
230 / 380V
DC
Rural Village
Ch = Chopper circuit
DC
AC
DC
DC
Bidirection DC/DC converter
Ch
House1 House3
House2 House4
House5
House6
50Hz, 380V, ±100kVA
Scan:
Voltage
Current
Fig. 1. Proposed system topology.
2.2. Battery Energy Storage System (BESS)
The battery is required to improve the system performance of microgrid and make the balance between
the generated power and load power demand through charge/discharge energy to or from this storage [8]. In
this paper, the battery model is Lithium-Ion taken from the MATLAB/Simulink tools with a nominal voltage
of 310 V. The initial state of charge (SOC) of the model can be set according to the need of the simulation.
The simulation parameters are shown in Table 1. The battery is connected at the DC-link through a DC/DC
bidirectional converter. The objective of this converter is to maintain the voltage on DC-link (400 V) and to
operate the system in order to charge/discharge the battery according the different situations. In charge mode the
PV generates more than required power and, therefore, the extra power must stored in the battery. In discharge
mode, the PV generates less than required power, then the battery injects power to balance the generated
power with load power demand. Figure 2, shows the schematic configuration of bidirectional converter and the
parameters are achieved according [11], and [15].
Table 1. Parameters of the Battery model.
Parameter Value
Nominal Voltage [V] 310
Rated Capacity [Ah] 8.2
Fully Charged Voltage [V] 360.836
Nominal current [A] 7.4157
Initial State-of-Charge [%] 80
2.3. DC-bus dynamics and protection
A chopper circuit is used in DC-link to dissipate excess power during fault condition or over voltage. If
the DC-link voltage exceeds the maximum limit (425 V), the DC-link will be short-circuited through the resistor
rc and the excess of power will be dissipated in this resistor, then the DC-link voltage will be maintained. A
common capacitor Clink is installed in parallel with chopper circuit as shown in Figure 2. In this study, the
value of rc is 300 Ω.
2.4. Inverter characteristics
The role of power electronics converter is very important in renewable energy systems [11]. In this
study, the inverter is set-up in accordance with the circuit shown in Figure 2. An IGBT six pack is modelled and
controlled in order to achieve the required objectives. The space-vector (SV) power width modulation (PWM)
technique is used to produce the switching control signals to be applied at three-phase inverter.
IJECE Vol. 7, No. 1, February 2017: 86 – 99
IJECE ISSN: 2088-8708 89
D1
Qp
Clink
Ip=Ipv
PV_array
PWM
MPPT
IpvVpv
Vdc*
Vpv
Lp
Boost controller
Ih
Ic
Ie
Lb
Ib
Ib
PWM
Vdc*
Battery controller
B1
B1
B1
B1
B1
B1
Vdc Ib
Ib*
AND
Qb2
Qb1
b1 b2
BESS
Q6Q2
Q1 Q5
Q4
Q3
a
b
c
PI1
Ird
Qc
rc
R1 L1 R2 L2
Cf
RD
LCL Filter
Winding Tr.
Chopper
Vdc
PI2
Vdc
PI3
Icf
ON/OFF
O
O
O
O
n
Vcf
<
AND
NOT
SOC
85%
CB
p
I1 I2
Load
(Village)
Fig. 2. Detailed system configuration.
2.5. Harmonics filter and isolating transformer
In this study, a LC filter combined with equivalent impedance of isolating transformer is used to reduce
the harmonics distortions in output inverter. The final configuration is a LCL filter which the components are
determined based on [17]. The primary objective of isolating transformer is to step-up the line voltage from
230 V to 380 V (nominal load voltage). The parameters are presented in Table 3.
2.6. Load characteristics
The main use of electricity is expected to be for lights, mills, bars, water pump for irrigation, and
office in village center. The load varies according the season and time. For example, during the rain season
the use of water pumps are not required for irrigation, and therefore the load power is small. In this study, the
estimated maximum load power is assumed 100 kVA and the line voltage and natural frequency is 380 V and
50 Hz, respectively.
Table 2. PV panel constants.
Parameters Value Parameters Value
Short-circuit current Isc 8.36 A Number of cells per module Ncells 54
Open circuit voltage Voc 33.20 V Number of panels in series Ns 14
Voltage at maximum power point Vmpp 26.3 V Number of panels in parallel Np 80
Current at maximum power point Impp 7.61 A Diode quality factor A 1.5
Temperature coefficient of Isc 0.00502 Series resistance Rs 0.16 Ω
Elementary charge q 1.6×10−19
C Parallel resistance Rp 1010.60 Ω
Boltzmanns constant B 1.38×10−23
Energy gap Eg 1.2 V
3. CONTROL OF THE SYSTEM
The overall control structure consists of a DC-link voltage controller and a line current controller. To
supply a line current with low distortion, the connection to the grid is made by an AC filter [17] which consists
of combination of LC and equivalent impedance of isolating transformer used to boost the line voltage from
Control of an Autonomous Hybrid Microgrid as Energy Source for a Small ... (Am´erico J. Lampi˜ao)
90 ISSN: 2088-8708
230 V to 380 V. The final configuration is LCL filter, as shown in Figure 2. The control is made in dq reference
and PLL is used to regulate the system frequency. In order to achieve good performance of control parameters,
the poles and zeros of transfer function was verified.
3.1. Control of Boost and Bidirectional DC/DC converters
The linearisation of boost and bidirectional DC/DC converters are analysed and presented in [8] and
[15]. From this analysis, the voltage and current transfer functions are given by:
G(v) =
Vout
d
=
− L
(1−D)2 Vins + RVin
RLCs2 + Ls + R(1 − D)2
(1)
G(i) =
Iin
d
=
Vin
(1−D) (2 + RCs)
RLCs2 + Ls + R(1 − D)2
(2)
where Vout is reference output voltage (400 V), Vin is input voltage, Iin is the inductor current, L is inductor, C
is common capacitor in DC-link, D is the duty cycle and R is the equivalent load resistor. The details about this
task is presented in [11]. In this paper, the equation (1) and (2) was used to design the DC/DC boost controller
and DC/DC bidirectional converter. As mentioned in above chapters, Ziegler-Nichols tuning method was used
to achieve the control parameters. Figures 4(b) and -(d), show the tuning block diagrams of voltage and current.
The inductances of boost and bidirectional converters used in this study are 3 mH and 1 mH, respectively.
3.2. DC-link voltage regulator
The purpose of the DC-link voltage controller is to preserve the DC-link voltage at its reference
value (V dc∗
) and to provide the reference power (Pe). To design the DC-link voltage regulator, the following
assumptions are considered.
• The grid voltage amplitude is constant;
• Using rotary axes dq, the grid voltage V g coincides with d-axis;
• The unity power factor is required, then the displacement between the grid voltage and current is zero.
Their q-axis components are also zeros.
For an accurate control model, it was made a linearisation in DC-side. Figure 2, shows the schematic config-
uration. In normal condition the gate of IGBT (Qc) receives the signal zero, meaning that the chopper circuit
is opened and no current is flowing through dump-resistor. Neglecting the chopper circuit, the DC side of the
inverter can be described as follows:



ih = ie + ic
ie = γaia + γbib + γcic
ic = Clink
vdc
dt
Ph = ihvdc
(3)
where ic is current through the DC-link capacitor, Ph is available hybrid active power at specific solar radiation
and SOC, Clink is DC-link capacitor, ih is the hybrid current, Vdc is voltage in DC-link, ie is the current
delivered to the inverter (which is a function of the line currents ia, ib, ic, and the states of the power-poles
γa, γb, γc (1: ’on’, 0:’off’, γi  + upper pole,γi  − lower pole in the 3-phase VSI).
To achieve steady state operation the supplied DC power of the Ph and the AC power for load must
be balanced. The DC voltage controller gives the set point of the AC power. Assuming, in this paper, that there
is no power losses in the inverter, if only active power is to be injected into the grid (load):
Pe ≈ Pg = 3 · Vg · Ig = 3
2 · Vgd · Igd
Qe ≈ 0
(4)
The generated hybrid power and the link capacitor power are expressed by equations (3) and (4), respectively:
Phybrid = Ih · Vdc (5)
IJECE Vol. 7, No. 1, February 2017: 86 – 99
IJECE ISSN: 2088-8708 91
vid
ωL
id,ref
PI4
Id,max
Id,min
Vdc*
ωL
Viq,max
Viq,min vq
iq,ref
Isq,max
Isq,min
Q,ref
vd
∆id
∆iq
id
iq
Vdc
Q
viq∆Q
∆v
SVPWM
dq
abc
abc
dq
abc
dq
vd
vq
id
iq
Dump load
Controller
Vdc(max)
Vid,max
Vid,min
VdcVdc
rd
IGBT
Clink
PLL
ie
φ
Pcc
PI6
PI7PI5
~380V
50Hz
Fig. 3. Control scheme of the grid-side inverter.
Pcapacitor = Clink · Vdc ·
dVdc
dt
(6)
The VSI losses are neglected, then the following relationship is verified:
Pgrid = Phybrid · Pcapacitor (7)
Following equations (3) to (7), the relation between DC-link voltage and the grid current expressed in rotary
axis is obtained:
Vdc =
1
Clink · s
(Ih −
3
2
Vgd
Vdc
· Igd) (8)
where Vg or Vs is the reference phase voltage in output inverter (132.8 V). The DC-link voltage is regulated
imposing a reference in the active current component (Igd). A voltage variation in the DC-link is compensated
by changing the AC line active currents, in such a way that the DC-link is kept at the established value (400 V).
The PIs are used as regulators and their parameters are achieved by using Ziegler-Nichols tuning method. The
DC-link voltage control loop is presented in Figure 4(b).
3.3. VSI and Grid current controller
The output current controller consists of a model based on LCL filter configuration, as shown in Figure
2. According Kirchhoff’s rules, we obtain the equations:
−→vi −
−→
i1 R1 − L1
d
−→
i1
dt
−
−→
ic Rd − −→vcf = 0 (9)
−→vs +
−→
i2 R2 + L2
d
−→
i2
dt
−
−→
ic Rd − −→vcf = 0 (10)
−→
ic =
−→
i1 −
−→
i2 (11)
The equivalent equations of (9), (10) and (11) can be described as:
d
dt
−→
i1 = −
(Rd + R1)
(L1)
−→
i1 +
Rd
L1
−→
i2 +
1
L1
−→vcf +
1
L1
−→vi (12)
d
dt
−→
i2 = −
(Rd + R2)
(L2)
−→
i2 +
Rd
L2
−→
i1 +
1
L2
−→vcf −
1
L2
−→vs (13)
Control of an Autonomous Hybrid Microgrid as Energy Source for a Small ... (Am´erico J. Lampi˜ao)
92 ISSN: 2088-8708
d
dt
−→vcf =
1
Cf
(
−→
i1 −
−→
i2 ) (14)
where,
−→
i1 = [i1a
i1b
i1c
]t
is the output current at filter,
−→
i2 = [i2a
i2b
i2c
]t
is the current injected to the grid;
−→vcf = [vcfa vcfb
vcfc ]t
is the voltage in capacitor Cf .
The control system is made by using voltage and current measurements. In order to reduce the number
of measurement sensors, and therefore, minimizing the cost of project, we consider only two sensors to detect
voltage and current. The basic control principles used in this paper are generally based on the decoupled current
control presented in [17], and [18]. The three-phase voltage on load bus is measured and transformed into a dq
reference frame (vd and vq). The three-phase current flowing between the loads and the inverter is measured
and transformed to id and iq. With the comparisons of the dq components to their respective references, the
resulting errors are sent to the PI controllers to generate the required output voltage of the inverter.
In order to facilitate the equation analysis, many researches make approximations such that the output
current inverter is assumed equal with the output current at the filter (i1≈i2), because the current ic is very small
[20]-[21]. Considering this approximations, the filter is analysed as RL and the parameters are the summation
of filter impedance and equivalent internal impedance of the transformer (Rt = R1 + R2, and Lt = L1 + L2).
In this paper, this assumptions are used to achieve the decoupled equations:
d
dt
−−→
i1dq
=
−Rt
Lt
ω
−ω −Rt
Lt
−−→
i1dq
−
1
L1
−−→vsdq
+
1
L1
−−→vidq
(15)
where, ω is the system frequency in rad/s. From (15) is obtained:
Vid
= (Rt + Lts)I1d
+ Vsd
− ωLtI1q (16)
Viq
= (Rt + Lts)I1q
+ Vsq
+ ωLtI1d
(17)
In equation (16) and (17), considering:
V ”
d = (Rt + Lts)I1d
(18)
V ”
q = (Rt + Lts)I1q
(19)
The equivalent equation become:
Vid
= V ”
d + Vsd
− ωLtI1q (20)
Viq = V ”
q + Vsq + ωLtI1q (21)
The plant is a first order system with transfer function
G(s) =
I1dq
(s)
Vidq
(s)
=
1
Rt + sLt
(22)
The PI transfer function without derivative action is given by:
Ts = Kp +
Ki
s
= Kp(1 +
1
Tis
) (23)
Where Ti =
Kp
Ki
is integral time constant or reset time, Kp and Ki is proportional and integral gains, respec-
tively. The goal of tuning method is to find the proper gains in order to achieve the required reference values.
The block diagrams of control loops are shown in Figure 4(a) and -(c).
4. RESULT AND ANALYSIS
In order to demonstrate the effectiveness of the proposed control strategy, a combined PV and BESS
(hybrid) connected to the load through three-phase VSI was set up and simulated under three different scenarios
using sampling time 20 µs and time domain from 0 to 0.55 s. The temperature is assumed constant 25 o
C and
sudden changes of solar radiation was implemented as input of PV panels. The initial SOC is 80 % in all
scenarios.
a) Case Study 1: This scenario aims to confirm the functionalities of PV and BESS under solar
variations to supply the load rated with power 100 kW. The simulation is carried out in sequence as follows:
IJECE Vol. 7, No. 1, February 2017: 86 – 99
IJECE ISSN: 2088-8708 93
System transfer function
1
idref /
iqref
1
1/Rt
Lt
RtsKp
1+Ti S
Ti
id /
iq
PI-Controller
Vd’ /Vq’ Vd /Vq
Vdcref
1
1
Clink.SKp
1+Ti S
Ti
PI-Controller
System transfer function
Vdcref
1
Gv(s)
Equation (7)
Kp
1+Ti S
Ti
Vdc
PI-Controller PWM + converter
System transfer function
ILref
1
Gi(s)
Equation (8)
Kp
1+Ti S
Ti
IL
PI-Controller PWM + converter
2
3Vgd
Vdc
IhPWM
(a) (b)
(c) (d)
PWM + converter
Fig. 4. Block diagrams of control loops.
Table 3. Grid parameters and control gains
Parameters Value Parameters Value
Filter inductance L1 265 µH Switching frequency fs 20 kHz
Filter resistance R1 40 mΩ Natural frequency f 50 Hz
Filter resistance Rd 100 mΩ Frequency modulation PWM 10 kHz
Filter capacitor Cf 300 µC PI4 = PI5 [Kp, Ki] [2.1, 253]
Transformer inductance L2 185 µH PI6 = PI7 [Kp, Ki] [0.004, 0.21]
Transformer resistance R2 25 mΩ PI1 [Kp, Ki] [0.0006, 0.13]
Dc-link capacitor Clink 470 µC PI2 [Kp, Ki] [0.0002, 0.18]
Peak load power Pload 100 kW PI3 [Kp, Ki] [0.0004, 0.21]
At t=0.0 s, the simulation starts when the solar radiation is maximum (1 kW/m2
), therefore, the PV panels are
generating more than required load power. In this case, the excess power is stored in battery. The maximum
power injected to the inverter is 115.15 kW, means that 100.0 kW is for load and 15.15 kW is total loss in
inverter, filter, transformer and lines. In that period the battery is receiving power and therefore, the SOC rises
gradually (charging mode). At t=0.2 s, the solar radiation drops suddenly until 0.5 kW/m2
and the PV panels
start to generate less than required power. In that moment, the battery detects the problem and starts to inject
the power to the inverter in order to balance the generation with the load demand. Therefore, the battery starts
to discharge and the SOC decreases gradually. At t=0.4 s, the solar radiation suddenly rises until (1 kW/m2
)
and the PV panels starts again to generate more than required power, then the battery changes from discharge
to charge mode. During this process, the DC-link voltage, power injected in inverter, voltage, and load current
are maintained at 400 V, 115.15 kW, 380 V and 300 A, respectively as the graphics shown in Figure 5.
b) Case Study 2: This scenario aims to confirm the functionalities of PV and BESS under load
variation and solar radiation at 0.5 kW/m2
. The simulation is carried out in sequence as follows: At t=0.0 s, the
simulation starts when the load is 70.0 kW solar radiation at 0.5 kW/m2
, therefore, the PV panels are generating
more than required load power. In this case, the excess power is stored in battery. The system is injecting in
inverter 80.0 kW, meaning that an amount of power is to compensate the losses. In that period the battery is
receiving power and therefore, the SOC is increasing gradually. At t=0.2 s, the load increases until 100 kW,
then in that time the load power becomes more than generated power. In order to compensate the generation,
the battery starts to inject the power to make balance. While the battery is injecting power, the battery is being
discharged and therefore, the SOC is gradually decreasing. At t=0.4 s, the load power suddenly drops then the
battery changes from discharge to charge mode in order to store the excess generated power. Figure 6(a), shows
the behaviour of solar radiation, -(b) shows the voltage on DC-link, -(c) shows the battery current, -(d) shows
the SOC, -(e) shows the active power injected in inverter, -(e) and -(f) show the voltage and current in load bus.
c) Case Study 3: This scenario aims to confirm the functionalities of PV and BESS under faults, load
and solar variations. The simulation is carried out in sequence as follows: At t=0.0 s, the simulation starts when
the all load is connected 100.0 kW and the solar radiation is maximum. The PV panels are generating more
than required power. Therefore the excess power is stored in battery. At t=0.1 s, an instantaneous fault occur
on load bus and transients are observed. When the fault is removed, the system becomes stable. At t=0.15 s,
some loads are disconnected from the grid and, therefore, the power injected in inverter reduces until 70 kW. At
t=0.2 s, a similar fault occur in load bus and the transients are observed again. When the fault is removed the
system becomes stable. At t=0.25 s, all load is connected (100 kW) and therefore the injected power increases
Control of an Autonomous Hybrid Microgrid as Energy Source for a Small ... (Am´erico J. Lampi˜ao)
94 ISSN: 2088-8708
too. At t=0.28 s, the solar radiation drops until 0.5 kW/m2
and the battery starts to inject power to compensate
the generated power according the load demand. At t=0.38 s and 0.48 s, instantaneous faults occur on load
bus and transients are verified. When the voltage on DC-link exceeds 425 V, the chopper circuit detects and an
amount of power is suppressed by dump-load resistor in order to rapidly balance the voltage. Figure 7, shows
the graphics under study. This results demonstrate that the system is controllable and the voltage and current
delivered to the consumers have good quality. Figure 7(f), shows the total harmonic distortion (THD=3.94 %).
5. CONCLUSION
This paper has proposed a model of autonomous hybrid microgrid powering through inverter a small
rural village and the design of respective controller to regulate the instantaneous output voltage. The graphs
obtained during the simulations, explain in detail the system’s versatility in different operating condition. The
system proves how a renewable source of energy such as PV panels can work together with battery in microgrid
to power local loads. Battery storage improves the reliability of the system by overcoming the PV generation
in order to balance with the load demand. The battery storage acts as DC load during charge mode, and as DC
source during discharge mode. The system was accurately modelled using Matlab/simulink and the parameters
have been chosen according the standards and methodologies presented in literatures. The simulation results
demonstrate the effectiveness of the proposed model and respective control methodology.
ACKNOWLEDGEMENT
The authors are really expressing their gratitude to the Senjyu’s Lab. members at the Department of
Electrical and Electronic Engineering, for their contributions.
REFERENCES
[1] UN Documents Gathering a body of global agreements, Chapter 7 of the charter of the United Nations
Signed in San Francisco, California on June, 1945. http://www.un-documents.net/k-002988.htm.
[2] A. H. Khan, et al., ”A Noble Design of a DC Micro Grid for Rural Area in Bangladesh, ” International
Journal of Technology Enhancements and Emerging Engineering Research, vol. 3, pp. 19-26, 2015.
[3] C. Marnay, et al., ”Optimal Technology Selection and Operation of Commercial-Building Microgrids, ”
IEEE Transactions on Power Systems, vol. 23, no. 3, pp. 975-982, August 2008.
[4] M. G. Villalva, et al., ”Comprehensive Approach to Modeling and Simulation of Photovoltaic Arrays, ”
IEEE Transactions on Power Electronics, vol. 24, no. 5, pp. 1198-1208, May 2009.
[5] S. Rahman and H. A. Rahman, ”Use of Photovoltaics in Microgrid as Energy Source and Control Method
using MATLAB/Simulink,” International Journal of Electrical and Computer Engineering (IJECE), vol. 6,
no. 2, pp. 851-858, April 2016.
[6] G. Sekar and T. Anita, ”Design and implementation of solar PV for power quality enhancement in Three-
phase four-wire distribution system, ” Journal of Electrical Engineering and Technology (JEET), pp. 75-82,
2015. http://dx.doi.org/10.5370/JEET.2015.10.1.075.
[7] Z. Miao, et al., ”An SOC based battery management system for microgrids, ” IEEE Transactions on Smart
Grid, vol. 5, no. 2, pp. 966-973, 2014.
[8] M. Miyagi, et al., ”Uninterruptible smart house equipped with the phase synchronization control system, ”
International Journal of Electrical Power and Energy Systems, Elsevier, vol. 63, pp. 302-310, 2014.
[9] R. Majumder, et al., ”Control and protection of a microgrid connected to utility through back-to-back
converters, ” Electric Power Systems Research, Elsevier, vol. 81, pp. 1424-1435, 2011.
[10] M. Prodanovic, and T. C. Green, ”Control and filter design of three-phase inverters for high power quality
grid connection, ” IEEE Transactions on Power Electronics, vol. 18, no. 1, pp. 373-2003, January 2003.
[11] R. Erickson, and D. Maksmovic, ”Fundamentals of power electronics, ” Kluwer Academic Publishers,
vol. 2, pp. 5-350, 2000.
[12] H. Bellia, et al., ”A detailed modeling of photovoltaic module using Matlab,” NRIAG Journal of Astron-
omy and Geophysics, vol. 3, pp. 53-61, May 2014.
[13] H. Matayoshi, et al., ”Uninterrupted smart house equipped with a single-phase dq-transformation system,
” Journal of Renewable and Sustainable Energy, vol. 8, 025101 (106) doi:10.1063/1.4942781.
IJECE Vol. 7, No. 1, February 2017: 86 – 99
IJECE ISSN: 2088-8708 95
[14] A. Panda, et al., ”A single phase photovoltaic inverter control for grid connected system,” Sadhana, Indian
Academy of Sciences, vol. 41, no. 1, pp. 15-30, January 2010.
[15] M. Gowda, et al., ”Moddeling of Buck DC-DC converter using Simulink,” International Journal of Inno-
vative Research in Science, Engineering and Technology, vol. 3, pp. 14965-14975, July 2014.
[16] N. Wang, at al., ”Battery energy storage system information modeling based on IEC 61850,” Journal of
Power and Energy Engineering, vol. 2, pp. 233-238, April 2014.
[17] M. Liserre, et al., ”Design and Control of an LCL-Filter-Based Three-Phase Active Rectifier, ” IEEE
Transactions on Industry Applications, vol. 41, no. 5, pp. 1281-1291, 2005.
[18] T. Raju, and P. R. Reddy, ”A Novel Control Algorithm for an Adaptive Hysteresis Band Current Con-
trolled Shunt Active Power Filter, ” International Refereed Journal of Engineering and Science (IRJES),
pp. 10-16, 2014.
[19] S. Bhat, et al., ”Effect of Parasitic Elements on the Performance of Buck-Boost Converter for PV Sys-
tems,” International Journal of Electrical and Computer Engineering (IJECE), vol. 4, no. 6, pp. 831-836,
December 2014.
[20] X. Bao, et al., ”Feedback Linearization Control of Photovoltaic inverter with LCL Filter, ” 2012 IEEE 7th
International Power Electronics and Motion Control Conference - ECCE Asia, pp. 2197-2201, June 2012.
[21] M. G. M. Abdolrasol, and S. Mekhilef, ”Three phase grid connected anti-islanding controller based
on distributed generation interconnection, ” 2010 IEEE International Conference on Power and Energy
(PECon2010), pp. 717-722, 2010.
BIOGRAPHIES OF AUTHORS
Am´erico Joaquim Lampi˜ao received his B.S. degree in electrical engineering from Universidade
Eduardo Mondlane at Mozambique in 2009. Currently, he is pursuing Master degree in electrical
engineering at Graduate School of Engineering and Science at University of the Ryukyus, Japan.
Besides, he is a junior Engineer at the Electricidade de Moc¸ambique (EDM), the national electricity
utility in Mozambique. His researches interests include power electronics, smart grid, microgrids,
voltage stability, power protection and electricity markets. He is affiliated with Order of Engineers
of Mozambique, and with IEEE as student member.
Tomonobu Senjyu received the B.S. and M.S. degrees in electrical engineering from University of
the Ryukyus Japan and the Ph.D. degree in electrical engineering from Nagoya University, Japan.
Since 1988, he has been with the Department of Electrical and Electronic Engineering, Faculty of
Engineering, University of the Ryukyus, where he is currently working as a Professor. His current
research interests include stability of ac machines, advanced control of electrical machines, power
electronics, renewable energy and smart grid.
Atsushi Yona received the B.S., M.S. and the Ph.D. degree from the University of the Ryukyus,
Okinawa, Japan, in 2006, 2008 and 2010, respectively, all in electrical engineering. In 2008, he
joined the University of the Ryukyus, where he is now a Assistant Professor at the Department of
Electrical and Electronic Engineering. His research interests include the renewable energy, fore-
casting techniques and optimal planning. Dr. Yona is a member of the Institution of Electrical
Engineers of Japan.
Control of an Autonomous Hybrid Microgrid as Energy Source for a Small ... (Am´erico J. Lampi˜ao)
96 ISSN: 2088-8708
0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5 0.55
0.5
1
Time [s]
Solarradiation[kW/m2
]
(a) Solar radiation.
0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5 0.55
200
400
Time [s]
Voltage[V]
Vdcref Vdc
(b) Voltage on Dc-link (V dc − link).
0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5 0.55
-100
-50
0
50
100
Time [s]
Current[A]
(c) Battery current (ib).
0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5 0.55
79.98
80
80.02
80.04
Time [s]
SOC[%]
(d) State-of-Charge (SOC).
0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5 0.55
0
50
100
Time [s]
Activepower[kW]
(e) Active power injected into inverter (Pe).
0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5 0.55
-380
0
380
Time [s]
Voltage[V]
(f) Three-phase load voltage (V abc).
0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5 0.55
-300
-150
0
150
300
Time [s]
Current[A]
(g) Load current (Iabc).
Fig. 5. Simulation results (Scenario - 1)
IJECE Vol. 7, No. 1, February 2017: 86 – 99
IJECE ISSN: 2088-8708 97
0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5 0.55
0.5
1
Time [s]
Solarradiation[kW/m2
]
(a) Solar radiation.
0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5 0.55
200
400
Time [s]
Voltage[V]
Vdcref Vdc
(b) Voltage on Dc-link (V dc − link).
0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5 0.55
-100
-50
0
50
100
Time [s]
Batterycurrent[A]
(c) Battery current (ib).
0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5 0.55
79.98
80
80.02
80.04
Time [s]
SOC[%]
(d) State-of-Charge (SOC).
0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5 0.55
50
100
Time [s]
Activepower[kW]
(e) Active power injected into inverter (Pe).
0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5 0.55
-380
0
380
Time [s]
Voltage[V]
(f) Three-phase load voltage (V abc).
0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5 0.55
-300
-150
0
150
300
Time [s]
Current[A]
(g) Load current (Iabc).
Fig. 6. Simulation results (Scenario - 2)
Control of an Autonomous Hybrid Microgrid as Energy Source for a Small ... (Am´erico J. Lampi˜ao)
98 ISSN: 2088-8708
0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5 0.55
0.5
1
Time [s]
Solarradiation[kW/m2
]
(a) Solar radiation.
0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5 0.55
200
400
600
Time [s]
Voltage[V]
Vdcref
Vdc
(b) Voltage on Dc-link (V dc − link).
0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5 0.55
-100
0
100
200
300
Time [s]
Batterycurrent[A]
(c) Battery current (ib).
0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5 0.55
79.98
80
80.02
80.04
80.06
Time [s]
SOC[%]
(d) State-of-Charge (SOC).
0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5 0.55
50
100
150
Time [s]
Activepower[kW]
(e) Active power injected into inverter (Pe).
0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5 0.55
-380
0
380
Time [s]
Voltage[V]
(f) Three-phase load voltage (V abc).
0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5 0.55
-800
-600
-400
-200
0
200
400
600
Time [s]
Current[A]
(g) Load current (Iabc).
IJECE Vol. 7, No. 1, February 2017: 86 – 99
IJECE ISSN: 2088-8708 99
0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5 0.55
0
0.5
1
1.5
Time [s]
Dump-loadcurrent[A]
(a) Overvoltage detection on Dc-link.
0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5 0.55
0
0.5
1
1.5
Time [s]
Dump-loadcurrent[A]
(b) Dump-load current (irc).
0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5 0.55
0
0.5
1
Time [s]
Vd,Vq[pu]
(c) Load voltage in dq reference (V dq).
0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5 0.55
-2
-1
0
1
2
Time [s]
Id,Iq[pu]
(d) Load current in dq reference (Idq).
0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5 0.55
0
50
Time [s]
Frequency[Hz]
(e) Grid frequency f.
0 2 4 6 8 10 12 14 16 18 20
0
0.5
1
1.5
Harmonic order
Mag(%ofFundamental)
Fundamental (50Hz) = 377.2 , THD= 3.94%
(f) Total Harmonic Distortion (THD).
Fig. 7. Simulation results (Scenario - 3)
Control of an Autonomous Hybrid Microgrid as Energy Source for a Small ... (Am´erico J. Lampi˜ao)

More Related Content

What's hot

Battery energy storage and power electronics based voltage and frequency cont...
Battery energy storage and power electronics based voltage and frequency cont...Battery energy storage and power electronics based voltage and frequency cont...
Battery energy storage and power electronics based voltage and frequency cont...IAEME Publication
 
GA Based Controller for Autonomous Wind-DG Micro grid
GA Based Controller for Autonomous Wind-DG Micro gridGA Based Controller for Autonomous Wind-DG Micro grid
GA Based Controller for Autonomous Wind-DG Micro gridIOSRJEEE
 
Design of Cost Effective Independent Power System Using Renewables for Rural ...
Design of Cost Effective Independent Power System Using Renewables for Rural ...Design of Cost Effective Independent Power System Using Renewables for Rural ...
Design of Cost Effective Independent Power System Using Renewables for Rural ...IOSR Journals
 
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...IJERD Editor
 
Control for Grid Connected and Intentional Islanding of Distributed Power Gen...
Control for Grid Connected and Intentional Islanding of Distributed Power Gen...Control for Grid Connected and Intentional Islanding of Distributed Power Gen...
Control for Grid Connected and Intentional Islanding of Distributed Power Gen...ijtsrd
 
A SMART RESIDENTIAL PV AND ENERGY STORAGE SYSTEM
A  SMART RESIDENTIAL PV AND ENERGY STORAGE SYSTEMA  SMART RESIDENTIAL PV AND ENERGY STORAGE SYSTEM
A SMART RESIDENTIAL PV AND ENERGY STORAGE SYSTEM Anand Parakkat Parambil
 
Performance analysis of grid-tied photovoltaic system under varying weather c...
Performance analysis of grid-tied photovoltaic system under varying weather c...Performance analysis of grid-tied photovoltaic system under varying weather c...
Performance analysis of grid-tied photovoltaic system under varying weather c...IJECEIAES
 
Electric Vehicle as an Energy Storage for Grid Connected Solar Power System
Electric Vehicle as an Energy Storage for Grid Connected Solar Power SystemElectric Vehicle as an Energy Storage for Grid Connected Solar Power System
Electric Vehicle as an Energy Storage for Grid Connected Solar Power SystemIAES-IJPEDS
 
A HYBRID AC/DC SOLAR POWERED STANDALONE SYSTEM WITHOUT INVERTER BASED ON LOAD...
A HYBRID AC/DC SOLAR POWERED STANDALONE SYSTEM WITHOUT INVERTER BASED ON LOAD...A HYBRID AC/DC SOLAR POWERED STANDALONE SYSTEM WITHOUT INVERTER BASED ON LOAD...
A HYBRID AC/DC SOLAR POWERED STANDALONE SYSTEM WITHOUT INVERTER BASED ON LOAD...Iaetsd Iaetsd
 
Integrated arrangement of advanced power electronics through hybrid smart gri...
Integrated arrangement of advanced power electronics through hybrid smart gri...Integrated arrangement of advanced power electronics through hybrid smart gri...
Integrated arrangement of advanced power electronics through hybrid smart gri...TELKOMNIKA JOURNAL
 
Intelligent controller based power quality improvement of microgrid integrati...
Intelligent controller based power quality improvement of microgrid integrati...Intelligent controller based power quality improvement of microgrid integrati...
Intelligent controller based power quality improvement of microgrid integrati...IJECEIAES
 
IRJET- Renewable Energy Hybrid Power System with Improvement of Power Quality...
IRJET- Renewable Energy Hybrid Power System with Improvement of Power Quality...IRJET- Renewable Energy Hybrid Power System with Improvement of Power Quality...
IRJET- Renewable Energy Hybrid Power System with Improvement of Power Quality...IRJET Journal
 

What's hot (15)

Battery energy storage and power electronics based voltage and frequency cont...
Battery energy storage and power electronics based voltage and frequency cont...Battery energy storage and power electronics based voltage and frequency cont...
Battery energy storage and power electronics based voltage and frequency cont...
 
www.ijerd.com
www.ijerd.comwww.ijerd.com
www.ijerd.com
 
GA Based Controller for Autonomous Wind-DG Micro grid
GA Based Controller for Autonomous Wind-DG Micro gridGA Based Controller for Autonomous Wind-DG Micro grid
GA Based Controller for Autonomous Wind-DG Micro grid
 
Modeling and Simulation of Grid Connected PV Generation System Using Matlab/S...
Modeling and Simulation of Grid Connected PV Generation System Using Matlab/S...Modeling and Simulation of Grid Connected PV Generation System Using Matlab/S...
Modeling and Simulation of Grid Connected PV Generation System Using Matlab/S...
 
Design of Cost Effective Independent Power System Using Renewables for Rural ...
Design of Cost Effective Independent Power System Using Renewables for Rural ...Design of Cost Effective Independent Power System Using Renewables for Rural ...
Design of Cost Effective Independent Power System Using Renewables for Rural ...
 
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
 
Control for Grid Connected and Intentional Islanding of Distributed Power Gen...
Control for Grid Connected and Intentional Islanding of Distributed Power Gen...Control for Grid Connected and Intentional Islanding of Distributed Power Gen...
Control for Grid Connected and Intentional Islanding of Distributed Power Gen...
 
A SMART RESIDENTIAL PV AND ENERGY STORAGE SYSTEM
A  SMART RESIDENTIAL PV AND ENERGY STORAGE SYSTEMA  SMART RESIDENTIAL PV AND ENERGY STORAGE SYSTEM
A SMART RESIDENTIAL PV AND ENERGY STORAGE SYSTEM
 
Performance analysis of grid-tied photovoltaic system under varying weather c...
Performance analysis of grid-tied photovoltaic system under varying weather c...Performance analysis of grid-tied photovoltaic system under varying weather c...
Performance analysis of grid-tied photovoltaic system under varying weather c...
 
Electric Vehicle as an Energy Storage for Grid Connected Solar Power System
Electric Vehicle as an Energy Storage for Grid Connected Solar Power SystemElectric Vehicle as an Energy Storage for Grid Connected Solar Power System
Electric Vehicle as an Energy Storage for Grid Connected Solar Power System
 
A HYBRID AC/DC SOLAR POWERED STANDALONE SYSTEM WITHOUT INVERTER BASED ON LOAD...
A HYBRID AC/DC SOLAR POWERED STANDALONE SYSTEM WITHOUT INVERTER BASED ON LOAD...A HYBRID AC/DC SOLAR POWERED STANDALONE SYSTEM WITHOUT INVERTER BASED ON LOAD...
A HYBRID AC/DC SOLAR POWERED STANDALONE SYSTEM WITHOUT INVERTER BASED ON LOAD...
 
Integrated arrangement of advanced power electronics through hybrid smart gri...
Integrated arrangement of advanced power electronics through hybrid smart gri...Integrated arrangement of advanced power electronics through hybrid smart gri...
Integrated arrangement of advanced power electronics through hybrid smart gri...
 
A different visions for uninterruptible load using hybrid solar-grid energy
A different visions for uninterruptible load using hybrid solar-grid energyA different visions for uninterruptible load using hybrid solar-grid energy
A different visions for uninterruptible load using hybrid solar-grid energy
 
Intelligent controller based power quality improvement of microgrid integrati...
Intelligent controller based power quality improvement of microgrid integrati...Intelligent controller based power quality improvement of microgrid integrati...
Intelligent controller based power quality improvement of microgrid integrati...
 
IRJET- Renewable Energy Hybrid Power System with Improvement of Power Quality...
IRJET- Renewable Energy Hybrid Power System with Improvement of Power Quality...IRJET- Renewable Energy Hybrid Power System with Improvement of Power Quality...
IRJET- Renewable Energy Hybrid Power System with Improvement of Power Quality...
 

Similar to Control of an Autonomous Hybrid Microgrid as Energy Source for a Small Rural Village

IRJET- A Review on Solar based Multilevel Inverter with Three Phase Grid Supply
IRJET- A Review on Solar based Multilevel Inverter with Three Phase Grid SupplyIRJET- A Review on Solar based Multilevel Inverter with Three Phase Grid Supply
IRJET- A Review on Solar based Multilevel Inverter with Three Phase Grid SupplyIRJET Journal
 
Implementation of a Voltage Multiplier based on High Step-up Converter using FLC
Implementation of a Voltage Multiplier based on High Step-up Converter using FLCImplementation of a Voltage Multiplier based on High Step-up Converter using FLC
Implementation of a Voltage Multiplier based on High Step-up Converter using FLCIJMTST Journal
 
Frequency control in a microgrid including controllable load
Frequency control in a microgrid including controllable loadFrequency control in a microgrid including controllable load
Frequency control in a microgrid including controllable loadIAEME Publication
 
Proposed PV Transformer-Less Inverter Topology Technique for Leakage Current ...
Proposed PV Transformer-Less Inverter Topology Technique for Leakage Current ...Proposed PV Transformer-Less Inverter Topology Technique for Leakage Current ...
Proposed PV Transformer-Less Inverter Topology Technique for Leakage Current ...IJPEDS-IAES
 
IRJET- Power Quality Improvement in Solar by using Fuzzy Logic Controller
IRJET-  	  Power Quality Improvement in Solar by using Fuzzy Logic ControllerIRJET-  	  Power Quality Improvement in Solar by using Fuzzy Logic Controller
IRJET- Power Quality Improvement in Solar by using Fuzzy Logic ControllerIRJET Journal
 
IRJET- Multi-Level Inverter for Solar On-Grid System Design
IRJET- Multi-Level Inverter for Solar On-Grid System DesignIRJET- Multi-Level Inverter for Solar On-Grid System Design
IRJET- Multi-Level Inverter for Solar On-Grid System DesignIRJET Journal
 
Power Quality Improvement with Multilevel Inverter Based IPQC for Microgrid
Power Quality Improvement with Multilevel Inverter Based IPQC for MicrogridPower Quality Improvement with Multilevel Inverter Based IPQC for Microgrid
Power Quality Improvement with Multilevel Inverter Based IPQC for MicrogridIJMTST Journal
 
IRJET- High-Efficiency Three-Level Stacked-Neutral-Point-Clamped Grid-Tie...
IRJET-  	  High-Efficiency Three-Level Stacked-Neutral-Point-Clamped Grid-Tie...IRJET-  	  High-Efficiency Three-Level Stacked-Neutral-Point-Clamped Grid-Tie...
IRJET- High-Efficiency Three-Level Stacked-Neutral-Point-Clamped Grid-Tie...IRJET Journal
 
FORMULATION AND EXECUTION OF A DC TO DC BOOST CONVERTER WITH NON-CONVENTIONAL...
FORMULATION AND EXECUTION OF A DC TO DC BOOST CONVERTER WITH NON-CONVENTIONAL...FORMULATION AND EXECUTION OF A DC TO DC BOOST CONVERTER WITH NON-CONVENTIONAL...
FORMULATION AND EXECUTION OF A DC TO DC BOOST CONVERTER WITH NON-CONVENTIONAL...IRJET Journal
 
Open-Switch Fault-Tolerant Control of Power Converters in a Grid-Connected Ph...
Open-Switch Fault-Tolerant Control of Power Converters in a Grid-Connected Ph...Open-Switch Fault-Tolerant Control of Power Converters in a Grid-Connected Ph...
Open-Switch Fault-Tolerant Control of Power Converters in a Grid-Connected Ph...IAES-IJPEDS
 
Droop control method for parallel dc converters used in standalone pv wind po...
Droop control method for parallel dc converters used in standalone pv wind po...Droop control method for parallel dc converters used in standalone pv wind po...
Droop control method for parallel dc converters used in standalone pv wind po...eSAT Journals
 
PHYSICAL DESIGN AND MODELING OF 25V DC-DC BOOST CONVERTER FOR STAND ALONE SOL...
PHYSICAL DESIGN AND MODELING OF 25V DC-DC BOOST CONVERTER FOR STAND ALONE SOL...PHYSICAL DESIGN AND MODELING OF 25V DC-DC BOOST CONVERTER FOR STAND ALONE SOL...
PHYSICAL DESIGN AND MODELING OF 25V DC-DC BOOST CONVERTER FOR STAND ALONE SOL...ecij
 
CONTROL STRATEGIES ON GRID-TIED PV INVERTERS
CONTROL STRATEGIES ON GRID-TIED PV INVERTERSCONTROL STRATEGIES ON GRID-TIED PV INVERTERS
CONTROL STRATEGIES ON GRID-TIED PV INVERTERSIRJET Journal
 
Improved Power Quality by using STATCOM Under Various Loading Conditions
Improved Power Quality by using STATCOM Under Various Loading ConditionsImproved Power Quality by using STATCOM Under Various Loading Conditions
Improved Power Quality by using STATCOM Under Various Loading ConditionsIJMTST Journal
 
Analysis of Double Moving Average Power Smoothing Methods for Photovoltaic Sy...
Analysis of Double Moving Average Power Smoothing Methods for Photovoltaic Sy...Analysis of Double Moving Average Power Smoothing Methods for Photovoltaic Sy...
Analysis of Double Moving Average Power Smoothing Methods for Photovoltaic Sy...IRJET Journal
 
Simulation of dcdc converter
Simulation of dcdc converterSimulation of dcdc converter
Simulation of dcdc converterRajesh Pindoriya
 
IRJET - Interleaved High Step-Up DC-DC Converter using Renewable Energy ...
IRJET  -  	  Interleaved High Step-Up DC-DC Converter using Renewable Energy ...IRJET  -  	  Interleaved High Step-Up DC-DC Converter using Renewable Energy ...
IRJET - Interleaved High Step-Up DC-DC Converter using Renewable Energy ...IRJET Journal
 

Similar to Control of an Autonomous Hybrid Microgrid as Energy Source for a Small Rural Village (20)

IRJET- A Review on Solar based Multilevel Inverter with Three Phase Grid Supply
IRJET- A Review on Solar based Multilevel Inverter with Three Phase Grid SupplyIRJET- A Review on Solar based Multilevel Inverter with Three Phase Grid Supply
IRJET- A Review on Solar based Multilevel Inverter with Three Phase Grid Supply
 
Implementation of a Voltage Multiplier based on High Step-up Converter using FLC
Implementation of a Voltage Multiplier based on High Step-up Converter using FLCImplementation of a Voltage Multiplier based on High Step-up Converter using FLC
Implementation of a Voltage Multiplier based on High Step-up Converter using FLC
 
Frequency control in a microgrid including controllable load
Frequency control in a microgrid including controllable loadFrequency control in a microgrid including controllable load
Frequency control in a microgrid including controllable load
 
Proposed PV Transformer-Less Inverter Topology Technique for Leakage Current ...
Proposed PV Transformer-Less Inverter Topology Technique for Leakage Current ...Proposed PV Transformer-Less Inverter Topology Technique for Leakage Current ...
Proposed PV Transformer-Less Inverter Topology Technique for Leakage Current ...
 
IRJET- Power Quality Improvement in Solar by using Fuzzy Logic Controller
IRJET-  	  Power Quality Improvement in Solar by using Fuzzy Logic ControllerIRJET-  	  Power Quality Improvement in Solar by using Fuzzy Logic Controller
IRJET- Power Quality Improvement in Solar by using Fuzzy Logic Controller
 
IRJET- Multi-Level Inverter for Solar On-Grid System Design
IRJET- Multi-Level Inverter for Solar On-Grid System DesignIRJET- Multi-Level Inverter for Solar On-Grid System Design
IRJET- Multi-Level Inverter for Solar On-Grid System Design
 
DC-DC converter based power management for go green applications
DC-DC converter based power management for go green applicationsDC-DC converter based power management for go green applications
DC-DC converter based power management for go green applications
 
Power Quality Improvement with Multilevel Inverter Based IPQC for Microgrid
Power Quality Improvement with Multilevel Inverter Based IPQC for MicrogridPower Quality Improvement with Multilevel Inverter Based IPQC for Microgrid
Power Quality Improvement with Multilevel Inverter Based IPQC for Microgrid
 
IRJET- High-Efficiency Three-Level Stacked-Neutral-Point-Clamped Grid-Tie...
IRJET-  	  High-Efficiency Three-Level Stacked-Neutral-Point-Clamped Grid-Tie...IRJET-  	  High-Efficiency Three-Level Stacked-Neutral-Point-Clamped Grid-Tie...
IRJET- High-Efficiency Three-Level Stacked-Neutral-Point-Clamped Grid-Tie...
 
FORMULATION AND EXECUTION OF A DC TO DC BOOST CONVERTER WITH NON-CONVENTIONAL...
FORMULATION AND EXECUTION OF A DC TO DC BOOST CONVERTER WITH NON-CONVENTIONAL...FORMULATION AND EXECUTION OF A DC TO DC BOOST CONVERTER WITH NON-CONVENTIONAL...
FORMULATION AND EXECUTION OF A DC TO DC BOOST CONVERTER WITH NON-CONVENTIONAL...
 
Open-Switch Fault-Tolerant Control of Power Converters in a Grid-Connected Ph...
Open-Switch Fault-Tolerant Control of Power Converters in a Grid-Connected Ph...Open-Switch Fault-Tolerant Control of Power Converters in a Grid-Connected Ph...
Open-Switch Fault-Tolerant Control of Power Converters in a Grid-Connected Ph...
 
Droop control method for parallel dc converters used in standalone pv wind po...
Droop control method for parallel dc converters used in standalone pv wind po...Droop control method for parallel dc converters used in standalone pv wind po...
Droop control method for parallel dc converters used in standalone pv wind po...
 
PHYSICAL DESIGN AND MODELING OF 25V DC-DC BOOST CONVERTER FOR STAND ALONE SOL...
PHYSICAL DESIGN AND MODELING OF 25V DC-DC BOOST CONVERTER FOR STAND ALONE SOL...PHYSICAL DESIGN AND MODELING OF 25V DC-DC BOOST CONVERTER FOR STAND ALONE SOL...
PHYSICAL DESIGN AND MODELING OF 25V DC-DC BOOST CONVERTER FOR STAND ALONE SOL...
 
CONTROL STRATEGIES ON GRID-TIED PV INVERTERS
CONTROL STRATEGIES ON GRID-TIED PV INVERTERSCONTROL STRATEGIES ON GRID-TIED PV INVERTERS
CONTROL STRATEGIES ON GRID-TIED PV INVERTERS
 
ROLE OF POWER ELECTRONICS IN NON-RENEWABLE AND RENEWABLE ENERGY SYSTEMS
ROLE OF POWER ELECTRONICS IN NON-RENEWABLE AND RENEWABLE ENERGY SYSTEMSROLE OF POWER ELECTRONICS IN NON-RENEWABLE AND RENEWABLE ENERGY SYSTEMS
ROLE OF POWER ELECTRONICS IN NON-RENEWABLE AND RENEWABLE ENERGY SYSTEMS
 
Improved Power Quality by using STATCOM Under Various Loading Conditions
Improved Power Quality by using STATCOM Under Various Loading ConditionsImproved Power Quality by using STATCOM Under Various Loading Conditions
Improved Power Quality by using STATCOM Under Various Loading Conditions
 
Analysis of Double Moving Average Power Smoothing Methods for Photovoltaic Sy...
Analysis of Double Moving Average Power Smoothing Methods for Photovoltaic Sy...Analysis of Double Moving Average Power Smoothing Methods for Photovoltaic Sy...
Analysis of Double Moving Average Power Smoothing Methods for Photovoltaic Sy...
 
Simulation of dcdc converter
Simulation of dcdc converterSimulation of dcdc converter
Simulation of dcdc converter
 
IRJET - Interleaved High Step-Up DC-DC Converter using Renewable Energy ...
IRJET  -  	  Interleaved High Step-Up DC-DC Converter using Renewable Energy ...IRJET  -  	  Interleaved High Step-Up DC-DC Converter using Renewable Energy ...
IRJET - Interleaved High Step-Up DC-DC Converter using Renewable Energy ...
 
Seminar Report on MPPT
Seminar Report on MPPTSeminar Report on MPPT
Seminar Report on MPPT
 

More from IJECEIAES

Cloud service ranking with an integration of k-means algorithm and decision-m...
Cloud service ranking with an integration of k-means algorithm and decision-m...Cloud service ranking with an integration of k-means algorithm and decision-m...
Cloud service ranking with an integration of k-means algorithm and decision-m...IJECEIAES
 
Prediction of the risk of developing heart disease using logistic regression
Prediction of the risk of developing heart disease using logistic regressionPrediction of the risk of developing heart disease using logistic regression
Prediction of the risk of developing heart disease using logistic regressionIJECEIAES
 
Predictive analysis of terrorist activities in Thailand's Southern provinces:...
Predictive analysis of terrorist activities in Thailand's Southern provinces:...Predictive analysis of terrorist activities in Thailand's Southern provinces:...
Predictive analysis of terrorist activities in Thailand's Southern provinces:...IJECEIAES
 
Optimal model of vehicular ad-hoc network assisted by unmanned aerial vehicl...
Optimal model of vehicular ad-hoc network assisted by  unmanned aerial vehicl...Optimal model of vehicular ad-hoc network assisted by  unmanned aerial vehicl...
Optimal model of vehicular ad-hoc network assisted by unmanned aerial vehicl...IJECEIAES
 
Improving cyberbullying detection through multi-level machine learning
Improving cyberbullying detection through multi-level machine learningImproving cyberbullying detection through multi-level machine learning
Improving cyberbullying detection through multi-level machine learningIJECEIAES
 
Comparison of time series temperature prediction with autoregressive integrat...
Comparison of time series temperature prediction with autoregressive integrat...Comparison of time series temperature prediction with autoregressive integrat...
Comparison of time series temperature prediction with autoregressive integrat...IJECEIAES
 
Strengthening data integrity in academic document recording with blockchain a...
Strengthening data integrity in academic document recording with blockchain a...Strengthening data integrity in academic document recording with blockchain a...
Strengthening data integrity in academic document recording with blockchain a...IJECEIAES
 
Design of storage benchmark kit framework for supporting the file storage ret...
Design of storage benchmark kit framework for supporting the file storage ret...Design of storage benchmark kit framework for supporting the file storage ret...
Design of storage benchmark kit framework for supporting the file storage ret...IJECEIAES
 
Detection of diseases in rice leaf using convolutional neural network with tr...
Detection of diseases in rice leaf using convolutional neural network with tr...Detection of diseases in rice leaf using convolutional neural network with tr...
Detection of diseases in rice leaf using convolutional neural network with tr...IJECEIAES
 
A systematic review of in-memory database over multi-tenancy
A systematic review of in-memory database over multi-tenancyA systematic review of in-memory database over multi-tenancy
A systematic review of in-memory database over multi-tenancyIJECEIAES
 
Agriculture crop yield prediction using inertia based cat swarm optimization
Agriculture crop yield prediction using inertia based cat swarm optimizationAgriculture crop yield prediction using inertia based cat swarm optimization
Agriculture crop yield prediction using inertia based cat swarm optimizationIJECEIAES
 
Three layer hybrid learning to improve intrusion detection system performance
Three layer hybrid learning to improve intrusion detection system performanceThree layer hybrid learning to improve intrusion detection system performance
Three layer hybrid learning to improve intrusion detection system performanceIJECEIAES
 
Non-binary codes approach on the performance of short-packet full-duplex tran...
Non-binary codes approach on the performance of short-packet full-duplex tran...Non-binary codes approach on the performance of short-packet full-duplex tran...
Non-binary codes approach on the performance of short-packet full-duplex tran...IJECEIAES
 
Improved design and performance of the global rectenna system for wireless po...
Improved design and performance of the global rectenna system for wireless po...Improved design and performance of the global rectenna system for wireless po...
Improved design and performance of the global rectenna system for wireless po...IJECEIAES
 
Advanced hybrid algorithms for precise multipath channel estimation in next-g...
Advanced hybrid algorithms for precise multipath channel estimation in next-g...Advanced hybrid algorithms for precise multipath channel estimation in next-g...
Advanced hybrid algorithms for precise multipath channel estimation in next-g...IJECEIAES
 
Performance analysis of 2D optical code division multiple access through unde...
Performance analysis of 2D optical code division multiple access through unde...Performance analysis of 2D optical code division multiple access through unde...
Performance analysis of 2D optical code division multiple access through unde...IJECEIAES
 
On performance analysis of non-orthogonal multiple access downlink for cellul...
On performance analysis of non-orthogonal multiple access downlink for cellul...On performance analysis of non-orthogonal multiple access downlink for cellul...
On performance analysis of non-orthogonal multiple access downlink for cellul...IJECEIAES
 
Phase delay through slot-line beam switching microstrip patch array antenna d...
Phase delay through slot-line beam switching microstrip patch array antenna d...Phase delay through slot-line beam switching microstrip patch array antenna d...
Phase delay through slot-line beam switching microstrip patch array antenna d...IJECEIAES
 
A simple feed orthogonal excitation X-band dual circular polarized microstrip...
A simple feed orthogonal excitation X-band dual circular polarized microstrip...A simple feed orthogonal excitation X-band dual circular polarized microstrip...
A simple feed orthogonal excitation X-band dual circular polarized microstrip...IJECEIAES
 
A taxonomy on power optimization techniques for fifthgeneration heterogenous ...
A taxonomy on power optimization techniques for fifthgeneration heterogenous ...A taxonomy on power optimization techniques for fifthgeneration heterogenous ...
A taxonomy on power optimization techniques for fifthgeneration heterogenous ...IJECEIAES
 

More from IJECEIAES (20)

Cloud service ranking with an integration of k-means algorithm and decision-m...
Cloud service ranking with an integration of k-means algorithm and decision-m...Cloud service ranking with an integration of k-means algorithm and decision-m...
Cloud service ranking with an integration of k-means algorithm and decision-m...
 
Prediction of the risk of developing heart disease using logistic regression
Prediction of the risk of developing heart disease using logistic regressionPrediction of the risk of developing heart disease using logistic regression
Prediction of the risk of developing heart disease using logistic regression
 
Predictive analysis of terrorist activities in Thailand's Southern provinces:...
Predictive analysis of terrorist activities in Thailand's Southern provinces:...Predictive analysis of terrorist activities in Thailand's Southern provinces:...
Predictive analysis of terrorist activities in Thailand's Southern provinces:...
 
Optimal model of vehicular ad-hoc network assisted by unmanned aerial vehicl...
Optimal model of vehicular ad-hoc network assisted by  unmanned aerial vehicl...Optimal model of vehicular ad-hoc network assisted by  unmanned aerial vehicl...
Optimal model of vehicular ad-hoc network assisted by unmanned aerial vehicl...
 
Improving cyberbullying detection through multi-level machine learning
Improving cyberbullying detection through multi-level machine learningImproving cyberbullying detection through multi-level machine learning
Improving cyberbullying detection through multi-level machine learning
 
Comparison of time series temperature prediction with autoregressive integrat...
Comparison of time series temperature prediction with autoregressive integrat...Comparison of time series temperature prediction with autoregressive integrat...
Comparison of time series temperature prediction with autoregressive integrat...
 
Strengthening data integrity in academic document recording with blockchain a...
Strengthening data integrity in academic document recording with blockchain a...Strengthening data integrity in academic document recording with blockchain a...
Strengthening data integrity in academic document recording with blockchain a...
 
Design of storage benchmark kit framework for supporting the file storage ret...
Design of storage benchmark kit framework for supporting the file storage ret...Design of storage benchmark kit framework for supporting the file storage ret...
Design of storage benchmark kit framework for supporting the file storage ret...
 
Detection of diseases in rice leaf using convolutional neural network with tr...
Detection of diseases in rice leaf using convolutional neural network with tr...Detection of diseases in rice leaf using convolutional neural network with tr...
Detection of diseases in rice leaf using convolutional neural network with tr...
 
A systematic review of in-memory database over multi-tenancy
A systematic review of in-memory database over multi-tenancyA systematic review of in-memory database over multi-tenancy
A systematic review of in-memory database over multi-tenancy
 
Agriculture crop yield prediction using inertia based cat swarm optimization
Agriculture crop yield prediction using inertia based cat swarm optimizationAgriculture crop yield prediction using inertia based cat swarm optimization
Agriculture crop yield prediction using inertia based cat swarm optimization
 
Three layer hybrid learning to improve intrusion detection system performance
Three layer hybrid learning to improve intrusion detection system performanceThree layer hybrid learning to improve intrusion detection system performance
Three layer hybrid learning to improve intrusion detection system performance
 
Non-binary codes approach on the performance of short-packet full-duplex tran...
Non-binary codes approach on the performance of short-packet full-duplex tran...Non-binary codes approach on the performance of short-packet full-duplex tran...
Non-binary codes approach on the performance of short-packet full-duplex tran...
 
Improved design and performance of the global rectenna system for wireless po...
Improved design and performance of the global rectenna system for wireless po...Improved design and performance of the global rectenna system for wireless po...
Improved design and performance of the global rectenna system for wireless po...
 
Advanced hybrid algorithms for precise multipath channel estimation in next-g...
Advanced hybrid algorithms for precise multipath channel estimation in next-g...Advanced hybrid algorithms for precise multipath channel estimation in next-g...
Advanced hybrid algorithms for precise multipath channel estimation in next-g...
 
Performance analysis of 2D optical code division multiple access through unde...
Performance analysis of 2D optical code division multiple access through unde...Performance analysis of 2D optical code division multiple access through unde...
Performance analysis of 2D optical code division multiple access through unde...
 
On performance analysis of non-orthogonal multiple access downlink for cellul...
On performance analysis of non-orthogonal multiple access downlink for cellul...On performance analysis of non-orthogonal multiple access downlink for cellul...
On performance analysis of non-orthogonal multiple access downlink for cellul...
 
Phase delay through slot-line beam switching microstrip patch array antenna d...
Phase delay through slot-line beam switching microstrip patch array antenna d...Phase delay through slot-line beam switching microstrip patch array antenna d...
Phase delay through slot-line beam switching microstrip patch array antenna d...
 
A simple feed orthogonal excitation X-band dual circular polarized microstrip...
A simple feed orthogonal excitation X-band dual circular polarized microstrip...A simple feed orthogonal excitation X-band dual circular polarized microstrip...
A simple feed orthogonal excitation X-band dual circular polarized microstrip...
 
A taxonomy on power optimization techniques for fifthgeneration heterogenous ...
A taxonomy on power optimization techniques for fifthgeneration heterogenous ...A taxonomy on power optimization techniques for fifthgeneration heterogenous ...
A taxonomy on power optimization techniques for fifthgeneration heterogenous ...
 

Recently uploaded

The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...ranjana rawat
 
Introduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxIntroduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxupamatechverse
 
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSMANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSSIVASHANKAR N
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingrakeshbaidya232001
 
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSHARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSRajkumarAkumalla
 
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxpurnimasatapathy1234
 
Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxupamatechverse
 
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)Suman Mia
 
Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024hassan khalil
 
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
main PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidmain PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidNikhilNagaraju
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escortsranjana rawat
 
SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )Tsuyoshi Horigome
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Dr.Costas Sachpazis
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 

Recently uploaded (20)

The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
 
Introduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxIntroduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptx
 
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSMANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writing
 
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSHARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
 
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptx
 
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINEDJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
 
Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptx
 
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptxExploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
 
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
 
Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024
 
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
 
main PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidmain PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfid
 
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
 
SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 

Control of an Autonomous Hybrid Microgrid as Energy Source for a Small Rural Village

  • 1. International Journal of Electrical and Computer Engineering (IJECE) Vol. 7, No. 1, February 2017, pp. 86 – 99 ISSN: 2088-8708 86 Institute of Advanced Engineering and Science w w w . i a e s j o u r n a l . c o m Control of an Autonomous Hybrid Microgrid as Energy Source for a Small Rural Village Am´erico Joaquim Lampi˜ao* , Tomonobu Senjyu* , and Atsushi Yona* * Faculty of Engineering, Department of Electrical and Electronics Engineering * University of the Ryukyus, 1 Senbaru, Nishihara-cho, Nakagami, Okinawa, 903-0213, Japan Article Info Article history: Received Oct 7, 2016 Revised Dec 11, 2016 Accepted Dec 24, 2016 Keyword: Microgrid Utility grid Photovoltaic system Battery energy system Power balance ABSTRACT Nowadays, the exhaustion of electricity power in rural areas is becoming an important issue for many African Nations. Moreover, challenges include the high cost of extend- ing the power grid to these locations, the economic health of the utilities and lack of revenue in impoverished villages. Numerous new initiatives are being implemented in the countries some of them co-financed by international organizations. In this paper, the hybrid microgrid is carried out as a feasible solution for a small rural village. A model of hybrid microgrid consisting of combination of photovoltaic (PV) panels and battery energy storage (BES) and a control system for managing the components of en- tire system to feed the village as local load is proposed. The control system must avoid the interruptions of power delivered to the consumers (village) and, therefore, good quality and reliability of the system is required. The PI controllers are used to regu- late the voltage and current using three-phase dq transformation, while the parameters are determined using Ziegler-Nichols tuning method. The effectiveness of the pro- posed method is verified by simulation results given by Matlab/SimPowerSystems R environment. Copyright c 2017 Institute of Advanced Engineering and Science. All rights reserved. Corresponding Author: Am´erico Joaquim Lampi˜ao Department of Electrical and Electronic Engineering University of the Ryukyus 1 Senbaru, Nishihara-cho, Okinawa, 903-0213, Japan Tel: +81-98-895-8686, +258-84-438-3831 Email: americo.lampiao@gmail.com 1. INTRODUCTION Over 620 million people in Africa still do not have access to the electricity [1]. As known, electricity is an essential contributor to the well-being of people and a key point of economic betterment for any country in the world. In 2001, the US National Academy of Engineers (NAE) voted ”electrification” as the most significant engineering achievement of the past century. According the worldwide calculation of electric consumption at present, approximately 1.4 billion people more than 20 percent population all over the world does not have access to electric connection and mostly live in rural areas in Africa [2]. The biggest challenges surrounding energy in this locations is the high cost to extend the power grid from main to these locations. New initiatives are being implemented using renewable energy source, but improvements are still required [3]. In this paper, a model of autonomous hybrid microgrid supplying a small rural village as local load and the respective controller is proposed to demonstrate their feasibility solution in rural villages. The hybrid source is a combined PV panels and Battery storage, connected to the load through voltage source inverter (VSI), filter and isolating transformer. The loads are typically rural such as mills, water pumps for irrigation, and small houses with one or two compartments. The households mainly use the firewood for cooking, therefore, small power for each house is expected. The use of PV panels as renewable energy has advantages due the environmental regulation protection, but the generated power changes according the temperature and solar radiation [4]-[6]. This fact Journal Homepage: http://iaesjournal.com/online/index.php/IJECE Institute of Advanced Engineering and Science w w w . i a e s j o u r n a l . c o m , DOI: 10.11591/ijece.v7i1.12900
  • 2. IJECE ISSN: 2088-8708 87 generates stability, reliability and power quality problems at the consumers [7]-[11]. The battery is used to overcome the intermittent and uncertain of the photovoltaic (PV) generation [13]. The PV system is composed by PV panels and DC/DC boost converter. In order to maximize the efficiency of the PVs and maintain the voltage at the DC-link, a combination of MPPT (maximum power point tracking) and DC/DC boost converter is used. The MPPT uses an algorithm to maintain the generated power at maximum point [11-13]. Depending on the PV generation and load demand, the battery may operate at either charging or discharging mode. In discharging mode, the battery works as power source and injects power to the inverter and, therefore makes balance between generation and load power demand. In charge mode, the battery receives the power from PV system. These achievements are possible by using a DC/DC bidirectional converter. The VSI is used to interface the DC-side with AC-side and, therefore, to convert DC current to AC with appropriate natural frequency. The inverter operates in high frequency (around 5-20 kHz), and causes harmonic distortions in output current [17]-[21], therefore, in this study a filter harmonics will be taken into account. In this paper, an isolating transformer rated at 100 kVA, to step-up the line voltage from 230 V to 380 V, is used. In addition, power supply companies demand this for the elimination of possible zero sequence or DC components in the generated voltages and for increased protection it affords [9]. This fact can be used as an advantage since the transformer can form part of a filter impedance and may, therefore, reduce the undesired harmonic content of the output current. Power quality standards for connection of an inverter to the load are still under development, since previously there have been few similar high power electronic applications. In this study the important aspect of power quality is harmonic distortion. General requirements for harmonic distortion can be found in standards IEEE [1547.1-1547.8]. The control solution proposed, provides high quality of current delivered to the consumers and, there- fore, high power quality. In addition, active and reactive power control is provided. The choice of control variables are based on standards, regulations and procedures presented in scientific publications. PLL (phase locked loop) and PI controllers was used to accomplish the power management of the system using dq syn- chronous reference. The parameters was determined using Ziegler-Nichols tuning method. Over the years, considerable research has been conducted on current and voltage regulation in microgrids, and various ap- proaches have been proposed. In this paper a review of the latest journal and conference papers related to the control in microgrids are carried out to demonstrate the validity of the proposed method, performed using MATLAB/ SimPowerSystems R . Simulation results demonstrate the effectiveness of proposed controller and, therefore, can be used to analyse microgrids connections. The rest of the section in this paper is organized as follows: In Section II, the proposed model is presented and the main components including control methodology are described. In Section III the discussion of the simulation results to show the effectiveness of the proposed system is presented. Finally, conclusions are drawn in Section IV. 2. RESEARCH METHOD The methodology adopted in this study, is proposing the schematic configuration of the model to be implemented and simulated using Matlab/Simulink environment. The components are described and the simulation results are presented. The conclusion is based on the presented results. Figure 1, shows the proposed model, and the description are presented below. 2.1. PV System The PV array used in this paper acts as an input source for charging the battery as well as supplying to the AC load during normal conditions. The basic equation of a PV panel is presented in [12]. Table 2, shows the constant values for the standard state of each PV panel as used in the present study. As mentioned in preview chapters, the PV generates intermittent power due the variation of sun’s radiation and cell temperature. In order to maximize the power and maintain the voltage in DC-link at required level (400 V), a combined MPPT and DC/DC boost converter are used. The MPPT aims at using an algorithm to ensure the array to operate at the maximum power point [6]. There are many different MPPT methods. Perturbation and Observation (P&O) method is used most widely since it is much simpler and needs fewer measured variables as input. In this study P&O was used and performed according [4]. Control of an Autonomous Hybrid Microgrid as Energy Source for a Small ... (Am´erico J. Lampi˜ao)
  • 3. 88 ISSN: 2088-8708 B1 B1 B1 B1 B1 B1 R1 L1 PV_array BESS CBm DC MPPT Boost converter 3-Phase VSI RD Cf Clink 230 / 380V DC Rural Village Ch = Chopper circuit DC AC DC DC Bidirection DC/DC converter Ch House1 House3 House2 House4 House5 House6 50Hz, 380V, ±100kVA Scan: Voltage Current Fig. 1. Proposed system topology. 2.2. Battery Energy Storage System (BESS) The battery is required to improve the system performance of microgrid and make the balance between the generated power and load power demand through charge/discharge energy to or from this storage [8]. In this paper, the battery model is Lithium-Ion taken from the MATLAB/Simulink tools with a nominal voltage of 310 V. The initial state of charge (SOC) of the model can be set according to the need of the simulation. The simulation parameters are shown in Table 1. The battery is connected at the DC-link through a DC/DC bidirectional converter. The objective of this converter is to maintain the voltage on DC-link (400 V) and to operate the system in order to charge/discharge the battery according the different situations. In charge mode the PV generates more than required power and, therefore, the extra power must stored in the battery. In discharge mode, the PV generates less than required power, then the battery injects power to balance the generated power with load power demand. Figure 2, shows the schematic configuration of bidirectional converter and the parameters are achieved according [11], and [15]. Table 1. Parameters of the Battery model. Parameter Value Nominal Voltage [V] 310 Rated Capacity [Ah] 8.2 Fully Charged Voltage [V] 360.836 Nominal current [A] 7.4157 Initial State-of-Charge [%] 80 2.3. DC-bus dynamics and protection A chopper circuit is used in DC-link to dissipate excess power during fault condition or over voltage. If the DC-link voltage exceeds the maximum limit (425 V), the DC-link will be short-circuited through the resistor rc and the excess of power will be dissipated in this resistor, then the DC-link voltage will be maintained. A common capacitor Clink is installed in parallel with chopper circuit as shown in Figure 2. In this study, the value of rc is 300 Ω. 2.4. Inverter characteristics The role of power electronics converter is very important in renewable energy systems [11]. In this study, the inverter is set-up in accordance with the circuit shown in Figure 2. An IGBT six pack is modelled and controlled in order to achieve the required objectives. The space-vector (SV) power width modulation (PWM) technique is used to produce the switching control signals to be applied at three-phase inverter. IJECE Vol. 7, No. 1, February 2017: 86 – 99
  • 4. IJECE ISSN: 2088-8708 89 D1 Qp Clink Ip=Ipv PV_array PWM MPPT IpvVpv Vdc* Vpv Lp Boost controller Ih Ic Ie Lb Ib Ib PWM Vdc* Battery controller B1 B1 B1 B1 B1 B1 Vdc Ib Ib* AND Qb2 Qb1 b1 b2 BESS Q6Q2 Q1 Q5 Q4 Q3 a b c PI1 Ird Qc rc R1 L1 R2 L2 Cf RD LCL Filter Winding Tr. Chopper Vdc PI2 Vdc PI3 Icf ON/OFF O O O O n Vcf < AND NOT SOC 85% CB p I1 I2 Load (Village) Fig. 2. Detailed system configuration. 2.5. Harmonics filter and isolating transformer In this study, a LC filter combined with equivalent impedance of isolating transformer is used to reduce the harmonics distortions in output inverter. The final configuration is a LCL filter which the components are determined based on [17]. The primary objective of isolating transformer is to step-up the line voltage from 230 V to 380 V (nominal load voltage). The parameters are presented in Table 3. 2.6. Load characteristics The main use of electricity is expected to be for lights, mills, bars, water pump for irrigation, and office in village center. The load varies according the season and time. For example, during the rain season the use of water pumps are not required for irrigation, and therefore the load power is small. In this study, the estimated maximum load power is assumed 100 kVA and the line voltage and natural frequency is 380 V and 50 Hz, respectively. Table 2. PV panel constants. Parameters Value Parameters Value Short-circuit current Isc 8.36 A Number of cells per module Ncells 54 Open circuit voltage Voc 33.20 V Number of panels in series Ns 14 Voltage at maximum power point Vmpp 26.3 V Number of panels in parallel Np 80 Current at maximum power point Impp 7.61 A Diode quality factor A 1.5 Temperature coefficient of Isc 0.00502 Series resistance Rs 0.16 Ω Elementary charge q 1.6×10−19 C Parallel resistance Rp 1010.60 Ω Boltzmanns constant B 1.38×10−23 Energy gap Eg 1.2 V 3. CONTROL OF THE SYSTEM The overall control structure consists of a DC-link voltage controller and a line current controller. To supply a line current with low distortion, the connection to the grid is made by an AC filter [17] which consists of combination of LC and equivalent impedance of isolating transformer used to boost the line voltage from Control of an Autonomous Hybrid Microgrid as Energy Source for a Small ... (Am´erico J. Lampi˜ao)
  • 5. 90 ISSN: 2088-8708 230 V to 380 V. The final configuration is LCL filter, as shown in Figure 2. The control is made in dq reference and PLL is used to regulate the system frequency. In order to achieve good performance of control parameters, the poles and zeros of transfer function was verified. 3.1. Control of Boost and Bidirectional DC/DC converters The linearisation of boost and bidirectional DC/DC converters are analysed and presented in [8] and [15]. From this analysis, the voltage and current transfer functions are given by: G(v) = Vout d = − L (1−D)2 Vins + RVin RLCs2 + Ls + R(1 − D)2 (1) G(i) = Iin d = Vin (1−D) (2 + RCs) RLCs2 + Ls + R(1 − D)2 (2) where Vout is reference output voltage (400 V), Vin is input voltage, Iin is the inductor current, L is inductor, C is common capacitor in DC-link, D is the duty cycle and R is the equivalent load resistor. The details about this task is presented in [11]. In this paper, the equation (1) and (2) was used to design the DC/DC boost controller and DC/DC bidirectional converter. As mentioned in above chapters, Ziegler-Nichols tuning method was used to achieve the control parameters. Figures 4(b) and -(d), show the tuning block diagrams of voltage and current. The inductances of boost and bidirectional converters used in this study are 3 mH and 1 mH, respectively. 3.2. DC-link voltage regulator The purpose of the DC-link voltage controller is to preserve the DC-link voltage at its reference value (V dc∗ ) and to provide the reference power (Pe). To design the DC-link voltage regulator, the following assumptions are considered. • The grid voltage amplitude is constant; • Using rotary axes dq, the grid voltage V g coincides with d-axis; • The unity power factor is required, then the displacement between the grid voltage and current is zero. Their q-axis components are also zeros. For an accurate control model, it was made a linearisation in DC-side. Figure 2, shows the schematic config- uration. In normal condition the gate of IGBT (Qc) receives the signal zero, meaning that the chopper circuit is opened and no current is flowing through dump-resistor. Neglecting the chopper circuit, the DC side of the inverter can be described as follows:    ih = ie + ic ie = γaia + γbib + γcic ic = Clink vdc dt Ph = ihvdc (3) where ic is current through the DC-link capacitor, Ph is available hybrid active power at specific solar radiation and SOC, Clink is DC-link capacitor, ih is the hybrid current, Vdc is voltage in DC-link, ie is the current delivered to the inverter (which is a function of the line currents ia, ib, ic, and the states of the power-poles γa, γb, γc (1: ’on’, 0:’off’, γi + upper pole,γi − lower pole in the 3-phase VSI). To achieve steady state operation the supplied DC power of the Ph and the AC power for load must be balanced. The DC voltage controller gives the set point of the AC power. Assuming, in this paper, that there is no power losses in the inverter, if only active power is to be injected into the grid (load): Pe ≈ Pg = 3 · Vg · Ig = 3 2 · Vgd · Igd Qe ≈ 0 (4) The generated hybrid power and the link capacitor power are expressed by equations (3) and (4), respectively: Phybrid = Ih · Vdc (5) IJECE Vol. 7, No. 1, February 2017: 86 – 99
  • 6. IJECE ISSN: 2088-8708 91 vid ωL id,ref PI4 Id,max Id,min Vdc* ωL Viq,max Viq,min vq iq,ref Isq,max Isq,min Q,ref vd ∆id ∆iq id iq Vdc Q viq∆Q ∆v SVPWM dq abc abc dq abc dq vd vq id iq Dump load Controller Vdc(max) Vid,max Vid,min VdcVdc rd IGBT Clink PLL ie φ Pcc PI6 PI7PI5 ~380V 50Hz Fig. 3. Control scheme of the grid-side inverter. Pcapacitor = Clink · Vdc · dVdc dt (6) The VSI losses are neglected, then the following relationship is verified: Pgrid = Phybrid · Pcapacitor (7) Following equations (3) to (7), the relation between DC-link voltage and the grid current expressed in rotary axis is obtained: Vdc = 1 Clink · s (Ih − 3 2 Vgd Vdc · Igd) (8) where Vg or Vs is the reference phase voltage in output inverter (132.8 V). The DC-link voltage is regulated imposing a reference in the active current component (Igd). A voltage variation in the DC-link is compensated by changing the AC line active currents, in such a way that the DC-link is kept at the established value (400 V). The PIs are used as regulators and their parameters are achieved by using Ziegler-Nichols tuning method. The DC-link voltage control loop is presented in Figure 4(b). 3.3. VSI and Grid current controller The output current controller consists of a model based on LCL filter configuration, as shown in Figure 2. According Kirchhoff’s rules, we obtain the equations: −→vi − −→ i1 R1 − L1 d −→ i1 dt − −→ ic Rd − −→vcf = 0 (9) −→vs + −→ i2 R2 + L2 d −→ i2 dt − −→ ic Rd − −→vcf = 0 (10) −→ ic = −→ i1 − −→ i2 (11) The equivalent equations of (9), (10) and (11) can be described as: d dt −→ i1 = − (Rd + R1) (L1) −→ i1 + Rd L1 −→ i2 + 1 L1 −→vcf + 1 L1 −→vi (12) d dt −→ i2 = − (Rd + R2) (L2) −→ i2 + Rd L2 −→ i1 + 1 L2 −→vcf − 1 L2 −→vs (13) Control of an Autonomous Hybrid Microgrid as Energy Source for a Small ... (Am´erico J. Lampi˜ao)
  • 7. 92 ISSN: 2088-8708 d dt −→vcf = 1 Cf ( −→ i1 − −→ i2 ) (14) where, −→ i1 = [i1a i1b i1c ]t is the output current at filter, −→ i2 = [i2a i2b i2c ]t is the current injected to the grid; −→vcf = [vcfa vcfb vcfc ]t is the voltage in capacitor Cf . The control system is made by using voltage and current measurements. In order to reduce the number of measurement sensors, and therefore, minimizing the cost of project, we consider only two sensors to detect voltage and current. The basic control principles used in this paper are generally based on the decoupled current control presented in [17], and [18]. The three-phase voltage on load bus is measured and transformed into a dq reference frame (vd and vq). The three-phase current flowing between the loads and the inverter is measured and transformed to id and iq. With the comparisons of the dq components to their respective references, the resulting errors are sent to the PI controllers to generate the required output voltage of the inverter. In order to facilitate the equation analysis, many researches make approximations such that the output current inverter is assumed equal with the output current at the filter (i1≈i2), because the current ic is very small [20]-[21]. Considering this approximations, the filter is analysed as RL and the parameters are the summation of filter impedance and equivalent internal impedance of the transformer (Rt = R1 + R2, and Lt = L1 + L2). In this paper, this assumptions are used to achieve the decoupled equations: d dt −−→ i1dq = −Rt Lt ω −ω −Rt Lt −−→ i1dq − 1 L1 −−→vsdq + 1 L1 −−→vidq (15) where, ω is the system frequency in rad/s. From (15) is obtained: Vid = (Rt + Lts)I1d + Vsd − ωLtI1q (16) Viq = (Rt + Lts)I1q + Vsq + ωLtI1d (17) In equation (16) and (17), considering: V ” d = (Rt + Lts)I1d (18) V ” q = (Rt + Lts)I1q (19) The equivalent equation become: Vid = V ” d + Vsd − ωLtI1q (20) Viq = V ” q + Vsq + ωLtI1q (21) The plant is a first order system with transfer function G(s) = I1dq (s) Vidq (s) = 1 Rt + sLt (22) The PI transfer function without derivative action is given by: Ts = Kp + Ki s = Kp(1 + 1 Tis ) (23) Where Ti = Kp Ki is integral time constant or reset time, Kp and Ki is proportional and integral gains, respec- tively. The goal of tuning method is to find the proper gains in order to achieve the required reference values. The block diagrams of control loops are shown in Figure 4(a) and -(c). 4. RESULT AND ANALYSIS In order to demonstrate the effectiveness of the proposed control strategy, a combined PV and BESS (hybrid) connected to the load through three-phase VSI was set up and simulated under three different scenarios using sampling time 20 µs and time domain from 0 to 0.55 s. The temperature is assumed constant 25 o C and sudden changes of solar radiation was implemented as input of PV panels. The initial SOC is 80 % in all scenarios. a) Case Study 1: This scenario aims to confirm the functionalities of PV and BESS under solar variations to supply the load rated with power 100 kW. The simulation is carried out in sequence as follows: IJECE Vol. 7, No. 1, February 2017: 86 – 99
  • 8. IJECE ISSN: 2088-8708 93 System transfer function 1 idref / iqref 1 1/Rt Lt RtsKp 1+Ti S Ti id / iq PI-Controller Vd’ /Vq’ Vd /Vq Vdcref 1 1 Clink.SKp 1+Ti S Ti PI-Controller System transfer function Vdcref 1 Gv(s) Equation (7) Kp 1+Ti S Ti Vdc PI-Controller PWM + converter System transfer function ILref 1 Gi(s) Equation (8) Kp 1+Ti S Ti IL PI-Controller PWM + converter 2 3Vgd Vdc IhPWM (a) (b) (c) (d) PWM + converter Fig. 4. Block diagrams of control loops. Table 3. Grid parameters and control gains Parameters Value Parameters Value Filter inductance L1 265 µH Switching frequency fs 20 kHz Filter resistance R1 40 mΩ Natural frequency f 50 Hz Filter resistance Rd 100 mΩ Frequency modulation PWM 10 kHz Filter capacitor Cf 300 µC PI4 = PI5 [Kp, Ki] [2.1, 253] Transformer inductance L2 185 µH PI6 = PI7 [Kp, Ki] [0.004, 0.21] Transformer resistance R2 25 mΩ PI1 [Kp, Ki] [0.0006, 0.13] Dc-link capacitor Clink 470 µC PI2 [Kp, Ki] [0.0002, 0.18] Peak load power Pload 100 kW PI3 [Kp, Ki] [0.0004, 0.21] At t=0.0 s, the simulation starts when the solar radiation is maximum (1 kW/m2 ), therefore, the PV panels are generating more than required load power. In this case, the excess power is stored in battery. The maximum power injected to the inverter is 115.15 kW, means that 100.0 kW is for load and 15.15 kW is total loss in inverter, filter, transformer and lines. In that period the battery is receiving power and therefore, the SOC rises gradually (charging mode). At t=0.2 s, the solar radiation drops suddenly until 0.5 kW/m2 and the PV panels start to generate less than required power. In that moment, the battery detects the problem and starts to inject the power to the inverter in order to balance the generation with the load demand. Therefore, the battery starts to discharge and the SOC decreases gradually. At t=0.4 s, the solar radiation suddenly rises until (1 kW/m2 ) and the PV panels starts again to generate more than required power, then the battery changes from discharge to charge mode. During this process, the DC-link voltage, power injected in inverter, voltage, and load current are maintained at 400 V, 115.15 kW, 380 V and 300 A, respectively as the graphics shown in Figure 5. b) Case Study 2: This scenario aims to confirm the functionalities of PV and BESS under load variation and solar radiation at 0.5 kW/m2 . The simulation is carried out in sequence as follows: At t=0.0 s, the simulation starts when the load is 70.0 kW solar radiation at 0.5 kW/m2 , therefore, the PV panels are generating more than required load power. In this case, the excess power is stored in battery. The system is injecting in inverter 80.0 kW, meaning that an amount of power is to compensate the losses. In that period the battery is receiving power and therefore, the SOC is increasing gradually. At t=0.2 s, the load increases until 100 kW, then in that time the load power becomes more than generated power. In order to compensate the generation, the battery starts to inject the power to make balance. While the battery is injecting power, the battery is being discharged and therefore, the SOC is gradually decreasing. At t=0.4 s, the load power suddenly drops then the battery changes from discharge to charge mode in order to store the excess generated power. Figure 6(a), shows the behaviour of solar radiation, -(b) shows the voltage on DC-link, -(c) shows the battery current, -(d) shows the SOC, -(e) shows the active power injected in inverter, -(e) and -(f) show the voltage and current in load bus. c) Case Study 3: This scenario aims to confirm the functionalities of PV and BESS under faults, load and solar variations. The simulation is carried out in sequence as follows: At t=0.0 s, the simulation starts when the all load is connected 100.0 kW and the solar radiation is maximum. The PV panels are generating more than required power. Therefore the excess power is stored in battery. At t=0.1 s, an instantaneous fault occur on load bus and transients are observed. When the fault is removed, the system becomes stable. At t=0.15 s, some loads are disconnected from the grid and, therefore, the power injected in inverter reduces until 70 kW. At t=0.2 s, a similar fault occur in load bus and the transients are observed again. When the fault is removed the system becomes stable. At t=0.25 s, all load is connected (100 kW) and therefore the injected power increases Control of an Autonomous Hybrid Microgrid as Energy Source for a Small ... (Am´erico J. Lampi˜ao)
  • 9. 94 ISSN: 2088-8708 too. At t=0.28 s, the solar radiation drops until 0.5 kW/m2 and the battery starts to inject power to compensate the generated power according the load demand. At t=0.38 s and 0.48 s, instantaneous faults occur on load bus and transients are verified. When the voltage on DC-link exceeds 425 V, the chopper circuit detects and an amount of power is suppressed by dump-load resistor in order to rapidly balance the voltage. Figure 7, shows the graphics under study. This results demonstrate that the system is controllable and the voltage and current delivered to the consumers have good quality. Figure 7(f), shows the total harmonic distortion (THD=3.94 %). 5. CONCLUSION This paper has proposed a model of autonomous hybrid microgrid powering through inverter a small rural village and the design of respective controller to regulate the instantaneous output voltage. The graphs obtained during the simulations, explain in detail the system’s versatility in different operating condition. The system proves how a renewable source of energy such as PV panels can work together with battery in microgrid to power local loads. Battery storage improves the reliability of the system by overcoming the PV generation in order to balance with the load demand. The battery storage acts as DC load during charge mode, and as DC source during discharge mode. The system was accurately modelled using Matlab/simulink and the parameters have been chosen according the standards and methodologies presented in literatures. The simulation results demonstrate the effectiveness of the proposed model and respective control methodology. ACKNOWLEDGEMENT The authors are really expressing their gratitude to the Senjyu’s Lab. members at the Department of Electrical and Electronic Engineering, for their contributions. REFERENCES [1] UN Documents Gathering a body of global agreements, Chapter 7 of the charter of the United Nations Signed in San Francisco, California on June, 1945. http://www.un-documents.net/k-002988.htm. [2] A. H. Khan, et al., ”A Noble Design of a DC Micro Grid for Rural Area in Bangladesh, ” International Journal of Technology Enhancements and Emerging Engineering Research, vol. 3, pp. 19-26, 2015. [3] C. Marnay, et al., ”Optimal Technology Selection and Operation of Commercial-Building Microgrids, ” IEEE Transactions on Power Systems, vol. 23, no. 3, pp. 975-982, August 2008. [4] M. G. Villalva, et al., ”Comprehensive Approach to Modeling and Simulation of Photovoltaic Arrays, ” IEEE Transactions on Power Electronics, vol. 24, no. 5, pp. 1198-1208, May 2009. [5] S. Rahman and H. A. Rahman, ”Use of Photovoltaics in Microgrid as Energy Source and Control Method using MATLAB/Simulink,” International Journal of Electrical and Computer Engineering (IJECE), vol. 6, no. 2, pp. 851-858, April 2016. [6] G. Sekar and T. Anita, ”Design and implementation of solar PV for power quality enhancement in Three- phase four-wire distribution system, ” Journal of Electrical Engineering and Technology (JEET), pp. 75-82, 2015. http://dx.doi.org/10.5370/JEET.2015.10.1.075. [7] Z. Miao, et al., ”An SOC based battery management system for microgrids, ” IEEE Transactions on Smart Grid, vol. 5, no. 2, pp. 966-973, 2014. [8] M. Miyagi, et al., ”Uninterruptible smart house equipped with the phase synchronization control system, ” International Journal of Electrical Power and Energy Systems, Elsevier, vol. 63, pp. 302-310, 2014. [9] R. Majumder, et al., ”Control and protection of a microgrid connected to utility through back-to-back converters, ” Electric Power Systems Research, Elsevier, vol. 81, pp. 1424-1435, 2011. [10] M. Prodanovic, and T. C. Green, ”Control and filter design of three-phase inverters for high power quality grid connection, ” IEEE Transactions on Power Electronics, vol. 18, no. 1, pp. 373-2003, January 2003. [11] R. Erickson, and D. Maksmovic, ”Fundamentals of power electronics, ” Kluwer Academic Publishers, vol. 2, pp. 5-350, 2000. [12] H. Bellia, et al., ”A detailed modeling of photovoltaic module using Matlab,” NRIAG Journal of Astron- omy and Geophysics, vol. 3, pp. 53-61, May 2014. [13] H. Matayoshi, et al., ”Uninterrupted smart house equipped with a single-phase dq-transformation system, ” Journal of Renewable and Sustainable Energy, vol. 8, 025101 (106) doi:10.1063/1.4942781. IJECE Vol. 7, No. 1, February 2017: 86 – 99
  • 10. IJECE ISSN: 2088-8708 95 [14] A. Panda, et al., ”A single phase photovoltaic inverter control for grid connected system,” Sadhana, Indian Academy of Sciences, vol. 41, no. 1, pp. 15-30, January 2010. [15] M. Gowda, et al., ”Moddeling of Buck DC-DC converter using Simulink,” International Journal of Inno- vative Research in Science, Engineering and Technology, vol. 3, pp. 14965-14975, July 2014. [16] N. Wang, at al., ”Battery energy storage system information modeling based on IEC 61850,” Journal of Power and Energy Engineering, vol. 2, pp. 233-238, April 2014. [17] M. Liserre, et al., ”Design and Control of an LCL-Filter-Based Three-Phase Active Rectifier, ” IEEE Transactions on Industry Applications, vol. 41, no. 5, pp. 1281-1291, 2005. [18] T. Raju, and P. R. Reddy, ”A Novel Control Algorithm for an Adaptive Hysteresis Band Current Con- trolled Shunt Active Power Filter, ” International Refereed Journal of Engineering and Science (IRJES), pp. 10-16, 2014. [19] S. Bhat, et al., ”Effect of Parasitic Elements on the Performance of Buck-Boost Converter for PV Sys- tems,” International Journal of Electrical and Computer Engineering (IJECE), vol. 4, no. 6, pp. 831-836, December 2014. [20] X. Bao, et al., ”Feedback Linearization Control of Photovoltaic inverter with LCL Filter, ” 2012 IEEE 7th International Power Electronics and Motion Control Conference - ECCE Asia, pp. 2197-2201, June 2012. [21] M. G. M. Abdolrasol, and S. Mekhilef, ”Three phase grid connected anti-islanding controller based on distributed generation interconnection, ” 2010 IEEE International Conference on Power and Energy (PECon2010), pp. 717-722, 2010. BIOGRAPHIES OF AUTHORS Am´erico Joaquim Lampi˜ao received his B.S. degree in electrical engineering from Universidade Eduardo Mondlane at Mozambique in 2009. Currently, he is pursuing Master degree in electrical engineering at Graduate School of Engineering and Science at University of the Ryukyus, Japan. Besides, he is a junior Engineer at the Electricidade de Moc¸ambique (EDM), the national electricity utility in Mozambique. His researches interests include power electronics, smart grid, microgrids, voltage stability, power protection and electricity markets. He is affiliated with Order of Engineers of Mozambique, and with IEEE as student member. Tomonobu Senjyu received the B.S. and M.S. degrees in electrical engineering from University of the Ryukyus Japan and the Ph.D. degree in electrical engineering from Nagoya University, Japan. Since 1988, he has been with the Department of Electrical and Electronic Engineering, Faculty of Engineering, University of the Ryukyus, where he is currently working as a Professor. His current research interests include stability of ac machines, advanced control of electrical machines, power electronics, renewable energy and smart grid. Atsushi Yona received the B.S., M.S. and the Ph.D. degree from the University of the Ryukyus, Okinawa, Japan, in 2006, 2008 and 2010, respectively, all in electrical engineering. In 2008, he joined the University of the Ryukyus, where he is now a Assistant Professor at the Department of Electrical and Electronic Engineering. His research interests include the renewable energy, fore- casting techniques and optimal planning. Dr. Yona is a member of the Institution of Electrical Engineers of Japan. Control of an Autonomous Hybrid Microgrid as Energy Source for a Small ... (Am´erico J. Lampi˜ao)
  • 11. 96 ISSN: 2088-8708 0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5 0.55 0.5 1 Time [s] Solarradiation[kW/m2 ] (a) Solar radiation. 0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5 0.55 200 400 Time [s] Voltage[V] Vdcref Vdc (b) Voltage on Dc-link (V dc − link). 0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5 0.55 -100 -50 0 50 100 Time [s] Current[A] (c) Battery current (ib). 0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5 0.55 79.98 80 80.02 80.04 Time [s] SOC[%] (d) State-of-Charge (SOC). 0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5 0.55 0 50 100 Time [s] Activepower[kW] (e) Active power injected into inverter (Pe). 0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5 0.55 -380 0 380 Time [s] Voltage[V] (f) Three-phase load voltage (V abc). 0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5 0.55 -300 -150 0 150 300 Time [s] Current[A] (g) Load current (Iabc). Fig. 5. Simulation results (Scenario - 1) IJECE Vol. 7, No. 1, February 2017: 86 – 99
  • 12. IJECE ISSN: 2088-8708 97 0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5 0.55 0.5 1 Time [s] Solarradiation[kW/m2 ] (a) Solar radiation. 0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5 0.55 200 400 Time [s] Voltage[V] Vdcref Vdc (b) Voltage on Dc-link (V dc − link). 0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5 0.55 -100 -50 0 50 100 Time [s] Batterycurrent[A] (c) Battery current (ib). 0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5 0.55 79.98 80 80.02 80.04 Time [s] SOC[%] (d) State-of-Charge (SOC). 0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5 0.55 50 100 Time [s] Activepower[kW] (e) Active power injected into inverter (Pe). 0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5 0.55 -380 0 380 Time [s] Voltage[V] (f) Three-phase load voltage (V abc). 0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5 0.55 -300 -150 0 150 300 Time [s] Current[A] (g) Load current (Iabc). Fig. 6. Simulation results (Scenario - 2) Control of an Autonomous Hybrid Microgrid as Energy Source for a Small ... (Am´erico J. Lampi˜ao)
  • 13. 98 ISSN: 2088-8708 0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5 0.55 0.5 1 Time [s] Solarradiation[kW/m2 ] (a) Solar radiation. 0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5 0.55 200 400 600 Time [s] Voltage[V] Vdcref Vdc (b) Voltage on Dc-link (V dc − link). 0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5 0.55 -100 0 100 200 300 Time [s] Batterycurrent[A] (c) Battery current (ib). 0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5 0.55 79.98 80 80.02 80.04 80.06 Time [s] SOC[%] (d) State-of-Charge (SOC). 0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5 0.55 50 100 150 Time [s] Activepower[kW] (e) Active power injected into inverter (Pe). 0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5 0.55 -380 0 380 Time [s] Voltage[V] (f) Three-phase load voltage (V abc). 0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5 0.55 -800 -600 -400 -200 0 200 400 600 Time [s] Current[A] (g) Load current (Iabc). IJECE Vol. 7, No. 1, February 2017: 86 – 99
  • 14. IJECE ISSN: 2088-8708 99 0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5 0.55 0 0.5 1 1.5 Time [s] Dump-loadcurrent[A] (a) Overvoltage detection on Dc-link. 0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5 0.55 0 0.5 1 1.5 Time [s] Dump-loadcurrent[A] (b) Dump-load current (irc). 0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5 0.55 0 0.5 1 Time [s] Vd,Vq[pu] (c) Load voltage in dq reference (V dq). 0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5 0.55 -2 -1 0 1 2 Time [s] Id,Iq[pu] (d) Load current in dq reference (Idq). 0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5 0.55 0 50 Time [s] Frequency[Hz] (e) Grid frequency f. 0 2 4 6 8 10 12 14 16 18 20 0 0.5 1 1.5 Harmonic order Mag(%ofFundamental) Fundamental (50Hz) = 377.2 , THD= 3.94% (f) Total Harmonic Distortion (THD). Fig. 7. Simulation results (Scenario - 3) Control of an Autonomous Hybrid Microgrid as Energy Source for a Small ... (Am´erico J. Lampi˜ao)