Henderson Foot Bridge Monitoring
Introduction
The monitoring of the Henderson Bridge was carried out from 3 to 14 May 2008. It was expected that
there would be a large crowd during the opening of the bridge to the public. During the monitoring
period, a Micro G vibration data logger and a video recording system were placed near the bridge and
secured with a water proof locked IP65 casing. After the monitoring period, it was fund that the system
had malfunction due to possible vandalism on site. Hence the data was extracted and analyzed. It
was found that the data was too corrupted to be able to recover for analysis and reporting.
Another monitoring was carried out, but unfortunately it was not possible to reproduce the large
number of people walking through the bridge as that of the opening day. Hence it was decided to
have 4 people simulating the conditions.
Dr Tan Guan Hong
Date: 12 September 2008
SysEng (S) Pte Ltd
One Stop Shop for Engineering Solutions
Objective: Bridge response with 4 persons
Field tests were carried out to measure the bridge vibration in the Z and X axes for different loading
conditions. The responses of the bridge were measured and analyzed for its behavior under these
conditions.
The test equipment measures accelerations in the XYZ axes while their respective displacements are
calculated by double integrating the acceleration results. The spectrum analysis are carried out on the
X and Z acceleration results for its peak amplitudes below 10 Hz.
Summary of measurement results
Under these test conditions, the results showed that the Z axis is the most sensitive and picked up
under 1 mg at the frequency of 1.6Hz with a calculated displacement of less than 0.7 mm movements.
The test showed very similar results and hence only typical results are shown here.
Bridge Vibration Measurement Conditions
Measurement conditions:
Weather: Normal with a slight wind present
Human Traffic: Visitors are moving around the bridge, with cars moving through the below road.
Schematic test layout
Figure 1: Axis directions
SysEng (S) Pte Ltd
One Stop Shop for Engineering Solutions
Test 1: 4 persons jumping in Z axis (jumping frequency 0.5 Hz to 0.25 Hz)
Results in the Z Axis
Time [sec]
40
35
30
25
20
15
10
5
0
A
c
c
e
le
r
a
tio
n
[g
]
0.0010
0.0008
0.0006
0.0004
0.0002
0.0000
-0.0002
-0.0004
-0.0006
-0.0008
-0.0010
Time [sec]
40
35
30
25
20
15
10
5
0
Displacement
[cm]
0.08
0.07
0.06
0.05
0.04
0.03
0.02
0.01
0
-0.01
-0.02
-0.03
-0.04
-0.05
-0.06
-0.07
-0.08
Frequency [Hz]
80
70
60
50
40
30
20
10
Fourier
Amplitude
0.00020
0.00018
0.00016
0.00014
0.00012
0.00010
0.00008
0.00006
0.00004
0.00002
0.00000
The acceleration peak frequency is 1.613 Hz for the bridge. Those above 10Hz are the impact forces
SysEng (S) Pte Ltd
One Stop Shop for Engineering Solutions
Results in the X Axis:
Time [sec]
40
35
30
25
20
15
10
5
0
Ac
c
e
le
ra
tion
[g]
0.0010
0.0008
0.0006
0.0004
0.0002
0.0000
-0.0002
-0.0004
-0.0006
-0.0008
-0.0010
Time [sec]
40
35
30
25
20
15
10
5
0
Displacement
[cm]
0.08
0.07
0.06
0.05
0.04
0.03
0.02
0.01
0
-0.01
-0.02
-0.03
-0.04
-0.05
-0.06
-0.07
-0.08
Frequency [Hz]
80
70
60
50
40
30
20
10
Fourier
Amplitude
0.00020
0.00018
0.00016
0.00014
0.00012
0.00010
0.00008
0.00006
0.00004
0.00002
0.00000
X axis Minimum Value 1 Hz, Peak Acceleration for below 10Hz is 1.613 Hz
SysEng (S) Pte Ltd
One Stop Shop for Engineering Solutions
Picture was taken with the forth person behind camera.
SysEng (S) Pte Ltd
One Stop Shop for Engineering Solutions
Test 2: 4 persons walking (about 1 to 2 Hz excitation)
Results in the Z axis:
Time [sec]
150
140
130
120
110
100
90
80
70
60
50
40
30
20
10
0
Acceleration
[g]
0.0010
0.0008
0.0006
0.0004
0.0002
0.0000
-0.0002
-0.0004
-0.0006
-0.0008
-0.0010
Time [sec]
150
140
130
120
110
100
90
80
70
60
50
40
30
20
10
0
Displacement
[cm]
0.08
0.07
0.06
0.05
0.04
0.03
0.02
0.01
0
-0.01
-0.02
-0.03
-0.04
-0.05
-0.06
-0.07
-0.08
Frequency [Hz]
80
70
60
50
40
30
20
10
Fourier
Amplitude
0.00020
0.00018
0.00016
0.00014
0.00012
0.00010
0.00008
0.00006
0.00004
0.00002
0.00000
The acceleration peak frequency is 1.613 Hz for the bridge. Those above 10Hz are the impact forces
SysEng (S) Pte Ltd
One Stop Shop for Engineering Solutions
Results in the X axis:
Time [sec]
150
140
130
120
110
100
90
80
70
60
50
40
30
20
10
0
Acceleration
[g]
0.0010
0.0008
0.0006
0.0004
0.0002
0.0000
-0.0002
-0.0004
-0.0006
-0.0008
-0.0010
Time [sec]
150
140
130
120
110
100
90
80
70
60
50
40
30
20
10
0
Displacement
[cm]
0.08
0.07
0.06
0.05
0.04
0.03
0.02
0.01
0
-0.01
-0.02
-0.03
-0.04
-0.05
-0.06
-0.07
-0.08
Frequency [Hz]
80
70
60
50
40
30
20
10
Fourier
Amplitude
0.00020
0.00018
0.00016
0.00014
0.00012
0.00010
0.00008
0.00006
0.00004
0.00002
0.00000
X axis Minimum Value 1 Hz, Peak Acceleration for below 10Hz is 1.613 Hz
SysEng (S) Pte Ltd
One Stop Shop for Engineering Solutions
Forth person behind camera
SysEng (S) Pte Ltd
One Stop Shop for Engineering Solutions
Test 3: Visitors jogging through the bridge (a little wind is present)
Results in the Z axis
Time [sec]
150
140
130
120
110
100
90
80
70
60
50
40
30
20
10
0
Acceleration
[g]
0.0010
0.0008
0.0006
0.0004
0.0002
0.0000
-0.0002
-0.0004
-0.0006
-0.0008
-0.0010
Time [sec]
150
140
130
120
110
100
90
80
70
60
50
40
30
20
10
0
Displacement
[cm]
0.08
0.07
0.06
0.05
0.04
0.03
0.02
0.01
0
-0.01
-0.02
-0.03
-0.04
-0.05
-0.06
-0.07
-0.08
Frequency [Hz]
80
70
60
50
40
30
20
10
Fourier
Amplitude
0.00020
0.00018
0.00016
0.00014
0.00012
0.00010
0.00008
0.00006
0.00004
0.00002
0.00000
Z axis Minimum Value 1 Hz, Peak (below 10Hz): 1.601 Hz
SysEng (S) Pte Ltd
One Stop Shop for Engineering Solutions
Results in the X axis:
Time [sec]
150
140
130
120
110
100
90
80
70
60
50
40
30
20
10
0
Acceleration
[g]
0.0010
0.0008
0.0006
0.0004
0.0002
0.0000
-0.0002
-0.0004
-0.0006
-0.0008
-0.0010
Time [sec]
150
140
130
120
110
100
90
80
70
60
50
40
30
20
10
0
Displacement
[cm]
0.08
0.07
0.06
0.05
0.04
0.03
0.02
0.01
0
-0.01
-0.02
-0.03
-0.04
-0.05
-0.06
-0.07
-0.08
Frequency [Hz]
80
70
60
50
40
30
20
10
Fourier
Amplitude
0.00020
0.00018
0.00016
0.00014
0.00012
0.00010
0.00008
0.00006
0.00004
0.00002
0.00000
SysEng (S) Pte Ltd
One Stop Shop for Engineering Solutions
Test 4: 3 or 4 groups of peoples moving through the bridge
Results in the Z axis:
Time [sec]
150
140
130
120
110
100
90
80
70
60
50
40
30
20
10
0
Acceleration
[g]
0.0010
0.0008
0.0006
0.0004
0.0002
0.0000
-0.0002
-0.0004
-0.0006
-0.0008
-0.0010
Time [sec]
150
140
130
120
110
100
90
80
70
60
50
40
30
20
10
0
Displacement
[cm]
0.08
0.07
0.06
0.05
0.04
0.03
0.02
0.01
0
-0.01
-0.02
-0.03
-0.04
-0.05
-0.06
-0.07
-0.08
Frequency [Hz]
80
70
60
50
40
30
20
10
Fourier
Amplitude
0.00020
0.00018
0.00016
0.00014
0.00012
0.00010
0.00008
0.00006
0.00004
0.00002
0.00000
Z axis Minimum Value 1 Hz, Peak (below 10Hz): 1.619 Hz
SysEng (S) Pte Ltd
One Stop Shop for Engineering Solutions
Results in the X Axis:
Time [sec]
150
140
130
120
110
100
90
80
70
60
50
40
30
20
10
0
Acceleration
[g]
0.0010
0.0008
0.0006
0.0004
0.0002
0.0000
-0.0002
-0.0004
-0.0006
-0.0008
-0.0010
Time [sec]
150
140
130
120
110
100
90
80
70
60
50
40
30
20
10
0
Displacement
[cm]
0.08
0.07
0.06
0.05
0.04
0.03
0.02
0.01
0
-0.01
-0.02
-0.03
-0.04
-0.05
-0.06
-0.07
-0.08
Frequency [Hz]
80
70
60
50
40
30
20
10
Fourier
Amplitude
0.00020
0.00018
0.00016
0.00014
0.00012
0.00010
0.00008
0.00006
0.00004
0.00002
0.00000
SysEng (S) Pte Ltd
One Stop Shop for Engineering Solutions
Test 5: A group of 3 people crossing and 2 children are playing
Results in the Z axis
Time [sec]
150
140
130
120
110
100
90
80
70
60
50
40
30
20
10
0
Acceleration
[g]
0.0010
0.0008
0.0006
0.0004
0.0002
0.0000
-0.0002
-0.0004
-0.0006
-0.0008
-0.0010
Time [sec]
150
140
130
120
110
100
90
80
70
60
50
40
30
20
10
0
Displacement
[cm]
0.08
0.07
0.06
0.05
0.04
0.03
0.02
0.01
0
-0.01
-0.02
-0.03
-0.04
-0.05
-0.06
-0.07
-0.08
Frequency [Hz]
80
70
60
50
40
30
20
10
Fourier
Amplitude
0.00020
0.00018
0.00016
0.00014
0.00012
0.00010
0.00008
0.00006
0.00004
0.00002
0.00000
Z axis Minimum Value 1 Hz, Peak (below 10Hz): 1.62 Hz
SysEng (S) Pte Ltd
One Stop Shop for Engineering Solutions
Results in the X axis:
Time [sec]
150
140
130
120
110
100
90
80
70
60
50
40
30
20
10
0
Acceleration
[g]
0.0010
0.0008
0.0006
0.0004
0.0002
0.0000
-0.0002
-0.0004
-0.0006
-0.0008
-0.0010
Time [sec]
150
140
130
120
110
100
90
80
70
60
50
40
30
20
10
0
Displacement
[cm]
0.08
0.07
0.06
0.05
0.04
0.03
0.02
0.01
0
-0.01
-0.02
-0.03
-0.04
-0.05
-0.06
-0.07
-0.08
Frequency [Hz]
80
70
60
50
40
30
20
10
Fourier
Amplitude
0.00020
0.00018
0.00016
0.00014
0.00012
0.00010
0.00008
0.00006
0.00004
0.00002
0.00000
X axis Minimum Value 1 Hz,
SysEng (S) Pte Ltd
One Stop Shop for Engineering Solutions
Appendix 1: Monitoring Equipment Specification
For Measurement of the bridge vibration, the system uses motion accelerographs with data upload to
a logging computer. The Motion accelerographs use is certified system from the Canterbury Seismic
Instruments Ltd, utilizing low-noise MEMS accelerometers. Following are the sensor specifications.
SENSOR
Type Triaxial MEM silicon accelerometers
Range ± 3g
Noise level < 0.65 mg RMS noise floor (80Hz
Bandwidth)
Temperature offset error ± 1 % over operating temperature range
Temperature gain error ± 1 % over operating temperature range
Temperature hysteresis ± 0.5 % over operating temperature range
Sampling Zero jitter, zero skew autonomous
sampling
Anti-Alias 8th order elliptic synchronized switched
capacitor anti-alias
filter (fc = 2x measurement bandwidth
(BW))
Extremely high linearity over 0-100 Hz
range
Sampling rate 800Hz
Conversion 16-bit data conversion
SysEng (S) Pte Ltd
One Stop Shop for Engineering Solutions
SAMPLE SIGNAL PROCESSING
Filtering FIR digital anti-alias filter/decimator
Perfect linearity
Measurement Bandwidth 40 or 80Hz
Recorded dynamic range 108dB (80 Hz BW)
108dB (50 Hz BW)
TRIGGERING
Type STA/LTA AND or OR filtered level detection
STA/LTA - Independent thresholds on each channel
- Selectable channel AND or OR triggering
- Thresholds adjustable from 2:1 to 200:1
Level - Independent thresholds on each channel
- Selectable channel AND or OR triggering
- Selectable low pass, high pass and band
pass IIR filters or no filtering
- Level from 1mg to 3000mg in 1mg steps
Pre-event length 10 to 60 seconds in 1-second steps
Post even length 10 to 60 seconds in 1-second step
SysEng (S) Pte Ltd
One Stop Shop for Engineering Solutions
STORAGE
Type Removable FLASH disc
Storage time 55 hours @ 200 samples/s
depends of FLASH disc size
SYSTEM
Processor Type Low power x86 based
OS Multi-tasking real-time Linux based
Supply voltage 10.5 – 24.0V DC
Power consumption 8 W typical 15W max
Temperature range 0 - 70°
C standard
Humidity 0 to 100% (non condensing)

More Related Content

Similar to Henderson Bridge Report.pdf

20140616 19 depestele-physical_impact_vfinalpresented
20140616 19 depestele-physical_impact_vfinalpresented20140616 19 depestele-physical_impact_vfinalpresented
20140616 19 depestele-physical_impact_vfinalpresented
Jochen Depestele
 
Stress analysis flange coupling
Stress analysis flange couplingStress analysis flange coupling
Stress analysis flange coupling
walid elsibai
 
Vs30 measurements for Seismic Site Classification
Vs30 measurements for Seismic Site ClassificationVs30 measurements for Seismic Site Classification
Vs30 measurements for Seismic Site Classification
Ali Osman Öncel
 

Similar to Henderson Bridge Report.pdf (20)

S1-001.pdf
S1-001.pdfS1-001.pdf
S1-001.pdf
 
Gears presentation
Gears presentation Gears presentation
Gears presentation
 
Gears presentation
Gears presentationGears presentation
Gears presentation
 
result lab
result labresult lab
result lab
 
Gears presentation.ppt
Gears presentation.pptGears presentation.ppt
Gears presentation.ppt
 
Gears presentation.ppt
Gears presentation.pptGears presentation.ppt
Gears presentation.ppt
 
Gears presentation.pptindia is the upcoming leader
Gears presentation.pptindia is the upcoming leaderGears presentation.pptindia is the upcoming leader
Gears presentation.pptindia is the upcoming leader
 
Gears presentation.ppt
Gears presentation.pptGears presentation.ppt
Gears presentation.ppt
 
Stream Discharge
Stream DischargeStream Discharge
Stream Discharge
 
Commissioning of Truebeam LINAC
Commissioning of Truebeam LINACCommissioning of Truebeam LINAC
Commissioning of Truebeam LINAC
 
20140616 19 depestele-physical_impact_vfinalpresented
20140616 19 depestele-physical_impact_vfinalpresented20140616 19 depestele-physical_impact_vfinalpresented
20140616 19 depestele-physical_impact_vfinalpresented
 
2016 aci milwaukee_wi_2016_v3
2016 aci milwaukee_wi_2016_v32016 aci milwaukee_wi_2016_v3
2016 aci milwaukee_wi_2016_v3
 
Vibrational Stand - EN
Vibrational Stand - ENVibrational Stand - EN
Vibrational Stand - EN
 
DHR_Rheology_Theory.pdf
DHR_Rheology_Theory.pdfDHR_Rheology_Theory.pdf
DHR_Rheology_Theory.pdf
 
Stress analysis flange coupling
Stress analysis flange couplingStress analysis flange coupling
Stress analysis flange coupling
 
ConsolidationTest.pdf
ConsolidationTest.pdfConsolidationTest.pdf
ConsolidationTest.pdf
 
Vs30 measurements for Seismic Site Classification
Vs30 measurements for Seismic Site ClassificationVs30 measurements for Seismic Site Classification
Vs30 measurements for Seismic Site Classification
 
Ground Vibration Control Using Signature Hole Method - Thesis BE Mining, Univ...
Ground Vibration Control Using Signature Hole Method - Thesis BE Mining, Univ...Ground Vibration Control Using Signature Hole Method - Thesis BE Mining, Univ...
Ground Vibration Control Using Signature Hole Method - Thesis BE Mining, Univ...
 
MSSISS ATLAS
MSSISS ATLASMSSISS ATLAS
MSSISS ATLAS
 
Peclet Number HDS Sizing Method for Stormwater Treatment
Peclet Number HDS Sizing Method for Stormwater TreatmentPeclet Number HDS Sizing Method for Stormwater Treatment
Peclet Number HDS Sizing Method for Stormwater Treatment
 

More from RekaNext Capital

More from RekaNext Capital (20)

Root cause of Magnetic Humming due to Transformer
Root cause of Magnetic Humming due to TransformerRoot cause of Magnetic Humming due to Transformer
Root cause of Magnetic Humming due to Transformer
 
Design for Product Assembly#4
Design for Product Assembly#4Design for Product Assembly#4
Design for Product Assembly#4
 
Design for Product Assembly#3
Design for Product Assembly#3Design for Product Assembly#3
Design for Product Assembly#3
 
Design for Product Assembly#2
Design for Product Assembly#2Design for Product Assembly#2
Design for Product Assembly#2
 
Assessment of the dynamic characteristics of the Helix Bridge at Marina Bay, ...
Assessment of the dynamic characteristics of the Helix Bridge at Marina Bay, ...Assessment of the dynamic characteristics of the Helix Bridge at Marina Bay, ...
Assessment of the dynamic characteristics of the Helix Bridge at Marina Bay, ...
 
Pre-load results.ppt
Pre-load results.pptPre-load results.ppt
Pre-load results.ppt
 
IDA Mission Critical M2M of SysEng.pdf
IDA Mission Critical M2M of SysEng.pdfIDA Mission Critical M2M of SysEng.pdf
IDA Mission Critical M2M of SysEng.pdf
 
Dr Tan Guan Hong PhD Thesis 1980.pdf
Dr Tan Guan Hong PhD Thesis 1980.pdfDr Tan Guan Hong PhD Thesis 1980.pdf
Dr Tan Guan Hong PhD Thesis 1980.pdf
 
ZigBee Personnel Tracking System
ZigBee Personnel Tracking SystemZigBee Personnel Tracking System
ZigBee Personnel Tracking System
 
AV Latency Measurement
AV Latency MeasurementAV Latency Measurement
AV Latency Measurement
 
Computer Vision for Measurement & FR
Computer Vision for Measurement & FRComputer Vision for Measurement & FR
Computer Vision for Measurement & FR
 
Business Transformation V6
Business Transformation V6Business Transformation V6
Business Transformation V6
 
Business Transformation V5
Business Transformation V5Business Transformation V5
Business Transformation V5
 
Building and Construction Authority GeoSS Seminar 2010
Building and Construction Authority GeoSS Seminar 2010Building and Construction Authority GeoSS Seminar 2010
Building and Construction Authority GeoSS Seminar 2010
 
SysEng Water India 2011 conference presentation
SysEng Water India 2011 conference presentationSysEng Water India 2011 conference presentation
SysEng Water India 2011 conference presentation
 
SysEng Environmental Projects
SysEng Environmental ProjectsSysEng Environmental Projects
SysEng Environmental Projects
 
SysEng Computer Vison Systems
SysEng Computer Vison SystemsSysEng Computer Vison Systems
SysEng Computer Vison Systems
 
Tunnel Monitoring Conference 28 Nov 2003
Tunnel Monitoring Conference 28 Nov 2003 Tunnel Monitoring Conference 28 Nov 2003
Tunnel Monitoring Conference 28 Nov 2003
 
Outdoor High Accuracy People Counting System
Outdoor High Accuracy People Counting SystemOutdoor High Accuracy People Counting System
Outdoor High Accuracy People Counting System
 
Basic AI Limitations
Basic AI LimitationsBasic AI Limitations
Basic AI Limitations
 

Recently uploaded

Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak HamilCara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Kandungan 087776558899
 
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
ssuser89054b
 
Standard vs Custom Battery Packs - Decoding the Power Play
Standard vs Custom Battery Packs - Decoding the Power PlayStandard vs Custom Battery Packs - Decoding the Power Play
Standard vs Custom Battery Packs - Decoding the Power Play
Epec Engineered Technologies
 
scipt v1.pptxcxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx...
scipt v1.pptxcxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx...scipt v1.pptxcxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx...
scipt v1.pptxcxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx...
HenryBriggs2
 
Kuwait City MTP kit ((+919101817206)) Buy Abortion Pills Kuwait
Kuwait City MTP kit ((+919101817206)) Buy Abortion Pills KuwaitKuwait City MTP kit ((+919101817206)) Buy Abortion Pills Kuwait
Kuwait City MTP kit ((+919101817206)) Buy Abortion Pills Kuwait
jaanualu31
 
Digital Communication Essentials: DPCM, DM, and ADM .pptx
Digital Communication Essentials: DPCM, DM, and ADM .pptxDigital Communication Essentials: DPCM, DM, and ADM .pptx
Digital Communication Essentials: DPCM, DM, and ADM .pptx
pritamlangde
 
"Lesotho Leaps Forward: A Chronicle of Transformative Developments"
"Lesotho Leaps Forward: A Chronicle of Transformative Developments""Lesotho Leaps Forward: A Chronicle of Transformative Developments"
"Lesotho Leaps Forward: A Chronicle of Transformative Developments"
mphochane1998
 
Hospital management system project report.pdf
Hospital management system project report.pdfHospital management system project report.pdf
Hospital management system project report.pdf
Kamal Acharya
 

Recently uploaded (20)

NO1 Top No1 Amil Baba In Azad Kashmir, Kashmir Black Magic Specialist Expert ...
NO1 Top No1 Amil Baba In Azad Kashmir, Kashmir Black Magic Specialist Expert ...NO1 Top No1 Amil Baba In Azad Kashmir, Kashmir Black Magic Specialist Expert ...
NO1 Top No1 Amil Baba In Azad Kashmir, Kashmir Black Magic Specialist Expert ...
 
School management system project Report.pdf
School management system project Report.pdfSchool management system project Report.pdf
School management system project Report.pdf
 
Unit 4_Part 1 CSE2001 Exception Handling and Function Template and Class Temp...
Unit 4_Part 1 CSE2001 Exception Handling and Function Template and Class Temp...Unit 4_Part 1 CSE2001 Exception Handling and Function Template and Class Temp...
Unit 4_Part 1 CSE2001 Exception Handling and Function Template and Class Temp...
 
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak HamilCara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
 
Employee leave management system project.
Employee leave management system project.Employee leave management system project.
Employee leave management system project.
 
HAND TOOLS USED AT ELECTRONICS WORK PRESENTED BY KOUSTAV SARKAR
HAND TOOLS USED AT ELECTRONICS WORK PRESENTED BY KOUSTAV SARKARHAND TOOLS USED AT ELECTRONICS WORK PRESENTED BY KOUSTAV SARKAR
HAND TOOLS USED AT ELECTRONICS WORK PRESENTED BY KOUSTAV SARKAR
 
HOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptx
HOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptxHOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptx
HOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptx
 
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
 
Standard vs Custom Battery Packs - Decoding the Power Play
Standard vs Custom Battery Packs - Decoding the Power PlayStandard vs Custom Battery Packs - Decoding the Power Play
Standard vs Custom Battery Packs - Decoding the Power Play
 
scipt v1.pptxcxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx...
scipt v1.pptxcxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx...scipt v1.pptxcxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx...
scipt v1.pptxcxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx...
 
Introduction to Geographic Information Systems
Introduction to Geographic Information SystemsIntroduction to Geographic Information Systems
Introduction to Geographic Information Systems
 
👉 Yavatmal Call Girls Service Just Call 🍑👄6378878445 🍑👄 Top Class Call Girl S...
👉 Yavatmal Call Girls Service Just Call 🍑👄6378878445 🍑👄 Top Class Call Girl S...👉 Yavatmal Call Girls Service Just Call 🍑👄6378878445 🍑👄 Top Class Call Girl S...
👉 Yavatmal Call Girls Service Just Call 🍑👄6378878445 🍑👄 Top Class Call Girl S...
 
Ground Improvement Technique: Earth Reinforcement
Ground Improvement Technique: Earth ReinforcementGround Improvement Technique: Earth Reinforcement
Ground Improvement Technique: Earth Reinforcement
 
Kuwait City MTP kit ((+919101817206)) Buy Abortion Pills Kuwait
Kuwait City MTP kit ((+919101817206)) Buy Abortion Pills KuwaitKuwait City MTP kit ((+919101817206)) Buy Abortion Pills Kuwait
Kuwait City MTP kit ((+919101817206)) Buy Abortion Pills Kuwait
 
Digital Communication Essentials: DPCM, DM, and ADM .pptx
Digital Communication Essentials: DPCM, DM, and ADM .pptxDigital Communication Essentials: DPCM, DM, and ADM .pptx
Digital Communication Essentials: DPCM, DM, and ADM .pptx
 
Post office management system project ..pdf
Post office management system project ..pdfPost office management system project ..pdf
Post office management system project ..pdf
 
Path loss model, OKUMURA Model, Hata Model
Path loss model, OKUMURA Model, Hata ModelPath loss model, OKUMURA Model, Hata Model
Path loss model, OKUMURA Model, Hata Model
 
"Lesotho Leaps Forward: A Chronicle of Transformative Developments"
"Lesotho Leaps Forward: A Chronicle of Transformative Developments""Lesotho Leaps Forward: A Chronicle of Transformative Developments"
"Lesotho Leaps Forward: A Chronicle of Transformative Developments"
 
Hostel management system project report..pdf
Hostel management system project report..pdfHostel management system project report..pdf
Hostel management system project report..pdf
 
Hospital management system project report.pdf
Hospital management system project report.pdfHospital management system project report.pdf
Hospital management system project report.pdf
 

Henderson Bridge Report.pdf

  • 1. SysEng (S) Pte Ltd One Stop Shop for Engineering Solutions Henderson Foot Bridge Monitoring Introduction The monitoring of the Henderson Bridge was carried out from 3 to 14 May 2008. It was expected that there would be a large crowd during the opening of the bridge to the public. During the monitoring period, a Micro G vibration data logger and a video recording system were placed near the bridge and secured with a water proof locked IP65 casing. After the monitoring period, it was fund that the system had malfunction due to possible vandalism on site. Hence the data was extracted and analyzed. It was found that the data was too corrupted to be able to recover for analysis and reporting. Another monitoring was carried out, but unfortunately it was not possible to reproduce the large number of people walking through the bridge as that of the opening day. Hence it was decided to have 4 people simulating the conditions. Dr Tan Guan Hong Date: 12 September 2008
  • 2. SysEng (S) Pte Ltd One Stop Shop for Engineering Solutions Objective: Bridge response with 4 persons Field tests were carried out to measure the bridge vibration in the Z and X axes for different loading conditions. The responses of the bridge were measured and analyzed for its behavior under these conditions. The test equipment measures accelerations in the XYZ axes while their respective displacements are calculated by double integrating the acceleration results. The spectrum analysis are carried out on the X and Z acceleration results for its peak amplitudes below 10 Hz. Summary of measurement results Under these test conditions, the results showed that the Z axis is the most sensitive and picked up under 1 mg at the frequency of 1.6Hz with a calculated displacement of less than 0.7 mm movements. The test showed very similar results and hence only typical results are shown here. Bridge Vibration Measurement Conditions Measurement conditions: Weather: Normal with a slight wind present Human Traffic: Visitors are moving around the bridge, with cars moving through the below road. Schematic test layout Figure 1: Axis directions
  • 3. SysEng (S) Pte Ltd One Stop Shop for Engineering Solutions Test 1: 4 persons jumping in Z axis (jumping frequency 0.5 Hz to 0.25 Hz) Results in the Z Axis Time [sec] 40 35 30 25 20 15 10 5 0 A c c e le r a tio n [g ] 0.0010 0.0008 0.0006 0.0004 0.0002 0.0000 -0.0002 -0.0004 -0.0006 -0.0008 -0.0010 Time [sec] 40 35 30 25 20 15 10 5 0 Displacement [cm] 0.08 0.07 0.06 0.05 0.04 0.03 0.02 0.01 0 -0.01 -0.02 -0.03 -0.04 -0.05 -0.06 -0.07 -0.08 Frequency [Hz] 80 70 60 50 40 30 20 10 Fourier Amplitude 0.00020 0.00018 0.00016 0.00014 0.00012 0.00010 0.00008 0.00006 0.00004 0.00002 0.00000 The acceleration peak frequency is 1.613 Hz for the bridge. Those above 10Hz are the impact forces
  • 4. SysEng (S) Pte Ltd One Stop Shop for Engineering Solutions Results in the X Axis: Time [sec] 40 35 30 25 20 15 10 5 0 Ac c e le ra tion [g] 0.0010 0.0008 0.0006 0.0004 0.0002 0.0000 -0.0002 -0.0004 -0.0006 -0.0008 -0.0010 Time [sec] 40 35 30 25 20 15 10 5 0 Displacement [cm] 0.08 0.07 0.06 0.05 0.04 0.03 0.02 0.01 0 -0.01 -0.02 -0.03 -0.04 -0.05 -0.06 -0.07 -0.08 Frequency [Hz] 80 70 60 50 40 30 20 10 Fourier Amplitude 0.00020 0.00018 0.00016 0.00014 0.00012 0.00010 0.00008 0.00006 0.00004 0.00002 0.00000 X axis Minimum Value 1 Hz, Peak Acceleration for below 10Hz is 1.613 Hz
  • 5. SysEng (S) Pte Ltd One Stop Shop for Engineering Solutions Picture was taken with the forth person behind camera.
  • 6. SysEng (S) Pte Ltd One Stop Shop for Engineering Solutions Test 2: 4 persons walking (about 1 to 2 Hz excitation) Results in the Z axis: Time [sec] 150 140 130 120 110 100 90 80 70 60 50 40 30 20 10 0 Acceleration [g] 0.0010 0.0008 0.0006 0.0004 0.0002 0.0000 -0.0002 -0.0004 -0.0006 -0.0008 -0.0010 Time [sec] 150 140 130 120 110 100 90 80 70 60 50 40 30 20 10 0 Displacement [cm] 0.08 0.07 0.06 0.05 0.04 0.03 0.02 0.01 0 -0.01 -0.02 -0.03 -0.04 -0.05 -0.06 -0.07 -0.08 Frequency [Hz] 80 70 60 50 40 30 20 10 Fourier Amplitude 0.00020 0.00018 0.00016 0.00014 0.00012 0.00010 0.00008 0.00006 0.00004 0.00002 0.00000 The acceleration peak frequency is 1.613 Hz for the bridge. Those above 10Hz are the impact forces
  • 7. SysEng (S) Pte Ltd One Stop Shop for Engineering Solutions Results in the X axis: Time [sec] 150 140 130 120 110 100 90 80 70 60 50 40 30 20 10 0 Acceleration [g] 0.0010 0.0008 0.0006 0.0004 0.0002 0.0000 -0.0002 -0.0004 -0.0006 -0.0008 -0.0010 Time [sec] 150 140 130 120 110 100 90 80 70 60 50 40 30 20 10 0 Displacement [cm] 0.08 0.07 0.06 0.05 0.04 0.03 0.02 0.01 0 -0.01 -0.02 -0.03 -0.04 -0.05 -0.06 -0.07 -0.08 Frequency [Hz] 80 70 60 50 40 30 20 10 Fourier Amplitude 0.00020 0.00018 0.00016 0.00014 0.00012 0.00010 0.00008 0.00006 0.00004 0.00002 0.00000 X axis Minimum Value 1 Hz, Peak Acceleration for below 10Hz is 1.613 Hz
  • 8. SysEng (S) Pte Ltd One Stop Shop for Engineering Solutions Forth person behind camera
  • 9. SysEng (S) Pte Ltd One Stop Shop for Engineering Solutions Test 3: Visitors jogging through the bridge (a little wind is present) Results in the Z axis Time [sec] 150 140 130 120 110 100 90 80 70 60 50 40 30 20 10 0 Acceleration [g] 0.0010 0.0008 0.0006 0.0004 0.0002 0.0000 -0.0002 -0.0004 -0.0006 -0.0008 -0.0010 Time [sec] 150 140 130 120 110 100 90 80 70 60 50 40 30 20 10 0 Displacement [cm] 0.08 0.07 0.06 0.05 0.04 0.03 0.02 0.01 0 -0.01 -0.02 -0.03 -0.04 -0.05 -0.06 -0.07 -0.08 Frequency [Hz] 80 70 60 50 40 30 20 10 Fourier Amplitude 0.00020 0.00018 0.00016 0.00014 0.00012 0.00010 0.00008 0.00006 0.00004 0.00002 0.00000 Z axis Minimum Value 1 Hz, Peak (below 10Hz): 1.601 Hz
  • 10. SysEng (S) Pte Ltd One Stop Shop for Engineering Solutions Results in the X axis: Time [sec] 150 140 130 120 110 100 90 80 70 60 50 40 30 20 10 0 Acceleration [g] 0.0010 0.0008 0.0006 0.0004 0.0002 0.0000 -0.0002 -0.0004 -0.0006 -0.0008 -0.0010 Time [sec] 150 140 130 120 110 100 90 80 70 60 50 40 30 20 10 0 Displacement [cm] 0.08 0.07 0.06 0.05 0.04 0.03 0.02 0.01 0 -0.01 -0.02 -0.03 -0.04 -0.05 -0.06 -0.07 -0.08 Frequency [Hz] 80 70 60 50 40 30 20 10 Fourier Amplitude 0.00020 0.00018 0.00016 0.00014 0.00012 0.00010 0.00008 0.00006 0.00004 0.00002 0.00000
  • 11. SysEng (S) Pte Ltd One Stop Shop for Engineering Solutions Test 4: 3 or 4 groups of peoples moving through the bridge Results in the Z axis: Time [sec] 150 140 130 120 110 100 90 80 70 60 50 40 30 20 10 0 Acceleration [g] 0.0010 0.0008 0.0006 0.0004 0.0002 0.0000 -0.0002 -0.0004 -0.0006 -0.0008 -0.0010 Time [sec] 150 140 130 120 110 100 90 80 70 60 50 40 30 20 10 0 Displacement [cm] 0.08 0.07 0.06 0.05 0.04 0.03 0.02 0.01 0 -0.01 -0.02 -0.03 -0.04 -0.05 -0.06 -0.07 -0.08 Frequency [Hz] 80 70 60 50 40 30 20 10 Fourier Amplitude 0.00020 0.00018 0.00016 0.00014 0.00012 0.00010 0.00008 0.00006 0.00004 0.00002 0.00000 Z axis Minimum Value 1 Hz, Peak (below 10Hz): 1.619 Hz
  • 12. SysEng (S) Pte Ltd One Stop Shop for Engineering Solutions Results in the X Axis: Time [sec] 150 140 130 120 110 100 90 80 70 60 50 40 30 20 10 0 Acceleration [g] 0.0010 0.0008 0.0006 0.0004 0.0002 0.0000 -0.0002 -0.0004 -0.0006 -0.0008 -0.0010 Time [sec] 150 140 130 120 110 100 90 80 70 60 50 40 30 20 10 0 Displacement [cm] 0.08 0.07 0.06 0.05 0.04 0.03 0.02 0.01 0 -0.01 -0.02 -0.03 -0.04 -0.05 -0.06 -0.07 -0.08 Frequency [Hz] 80 70 60 50 40 30 20 10 Fourier Amplitude 0.00020 0.00018 0.00016 0.00014 0.00012 0.00010 0.00008 0.00006 0.00004 0.00002 0.00000
  • 13. SysEng (S) Pte Ltd One Stop Shop for Engineering Solutions Test 5: A group of 3 people crossing and 2 children are playing Results in the Z axis Time [sec] 150 140 130 120 110 100 90 80 70 60 50 40 30 20 10 0 Acceleration [g] 0.0010 0.0008 0.0006 0.0004 0.0002 0.0000 -0.0002 -0.0004 -0.0006 -0.0008 -0.0010 Time [sec] 150 140 130 120 110 100 90 80 70 60 50 40 30 20 10 0 Displacement [cm] 0.08 0.07 0.06 0.05 0.04 0.03 0.02 0.01 0 -0.01 -0.02 -0.03 -0.04 -0.05 -0.06 -0.07 -0.08 Frequency [Hz] 80 70 60 50 40 30 20 10 Fourier Amplitude 0.00020 0.00018 0.00016 0.00014 0.00012 0.00010 0.00008 0.00006 0.00004 0.00002 0.00000 Z axis Minimum Value 1 Hz, Peak (below 10Hz): 1.62 Hz
  • 14. SysEng (S) Pte Ltd One Stop Shop for Engineering Solutions Results in the X axis: Time [sec] 150 140 130 120 110 100 90 80 70 60 50 40 30 20 10 0 Acceleration [g] 0.0010 0.0008 0.0006 0.0004 0.0002 0.0000 -0.0002 -0.0004 -0.0006 -0.0008 -0.0010 Time [sec] 150 140 130 120 110 100 90 80 70 60 50 40 30 20 10 0 Displacement [cm] 0.08 0.07 0.06 0.05 0.04 0.03 0.02 0.01 0 -0.01 -0.02 -0.03 -0.04 -0.05 -0.06 -0.07 -0.08 Frequency [Hz] 80 70 60 50 40 30 20 10 Fourier Amplitude 0.00020 0.00018 0.00016 0.00014 0.00012 0.00010 0.00008 0.00006 0.00004 0.00002 0.00000 X axis Minimum Value 1 Hz,
  • 15. SysEng (S) Pte Ltd One Stop Shop for Engineering Solutions Appendix 1: Monitoring Equipment Specification For Measurement of the bridge vibration, the system uses motion accelerographs with data upload to a logging computer. The Motion accelerographs use is certified system from the Canterbury Seismic Instruments Ltd, utilizing low-noise MEMS accelerometers. Following are the sensor specifications. SENSOR Type Triaxial MEM silicon accelerometers Range ± 3g Noise level < 0.65 mg RMS noise floor (80Hz Bandwidth) Temperature offset error ± 1 % over operating temperature range Temperature gain error ± 1 % over operating temperature range Temperature hysteresis ± 0.5 % over operating temperature range Sampling Zero jitter, zero skew autonomous sampling Anti-Alias 8th order elliptic synchronized switched capacitor anti-alias filter (fc = 2x measurement bandwidth (BW)) Extremely high linearity over 0-100 Hz range Sampling rate 800Hz Conversion 16-bit data conversion
  • 16. SysEng (S) Pte Ltd One Stop Shop for Engineering Solutions SAMPLE SIGNAL PROCESSING Filtering FIR digital anti-alias filter/decimator Perfect linearity Measurement Bandwidth 40 or 80Hz Recorded dynamic range 108dB (80 Hz BW) 108dB (50 Hz BW) TRIGGERING Type STA/LTA AND or OR filtered level detection STA/LTA - Independent thresholds on each channel - Selectable channel AND or OR triggering - Thresholds adjustable from 2:1 to 200:1 Level - Independent thresholds on each channel - Selectable channel AND or OR triggering - Selectable low pass, high pass and band pass IIR filters or no filtering - Level from 1mg to 3000mg in 1mg steps Pre-event length 10 to 60 seconds in 1-second steps Post even length 10 to 60 seconds in 1-second step
  • 17. SysEng (S) Pte Ltd One Stop Shop for Engineering Solutions STORAGE Type Removable FLASH disc Storage time 55 hours @ 200 samples/s depends of FLASH disc size SYSTEM Processor Type Low power x86 based OS Multi-tasking real-time Linux based Supply voltage 10.5 – 24.0V DC Power consumption 8 W typical 15W max Temperature range 0 - 70° C standard Humidity 0 to 100% (non condensing)