Pressure switches and thermostats, type CAS
Data sheet
Description
INDUSTRIAL CONTROLS IC.PD.P10.G1.02 - 520B3138
CAS units are pressure-controlled switches.
The position of the contacts depends on the
pressure in the inlet connection and the set
value. In the series, special attention has been
given to meeting demands for
• a high level of enclosure
• low differential
• robust and compact construction
• resistance to shock and vibration.
Contents Page
CAS pressure switches, description.............................................................................................................................1
Approvals.................................................................................................................................................................................2
Ship approvals........................................................................................................................................................................2
Survey........................................................................................................................................................................................2
ISO 9001 quality approval..................................................................................................................................................2
Ordering ...................................................................................................................................................................................3
Terminology............................................................................................................................................................................3
Technical data.........................................................................................................................................................................4
Dimensions and weight......................................................................................................................................................4
Installation...............................................................................................................................................................................5
Function....................................................................................................................................................................................6
Accessories ..............................................................................................................................................................................7
CAS thermostats, description.........................................................................................................................................8
Approvals.................................................................................................................................................................................8
Ship approvals........................................................................................................................................................................8
Technical data and ordering..............................................................................................................................................8
Dimensions and weight......................................................................................................................................................9
Accessories ..............................................................................................................................................................................9
Installation............................................................................................................................................................................ 10
Function................................................................................................................................................................................. 11
Electrical connection ........................................................................................................................................................ 11
Examples ............................................................................................................................................................................... 11
Conversion table................................................................................................................................................................. 12
The CAS series covers most outdoor as well as
indoor application requirements.
CAS pressure controls are suitable for use in alarm
and regulation systems in factories, diesel plant,
compressors, power stations and on board ship.
0 - 3.5 CAS 133
0 - 10 CAS 136
0 - 18 CAS 137
10 - 35 CAS 139
1 - 10 CAS 143
4 - 40 CAS 145
6 - 60 CAS 147
0.2 - 2.5 CAS 155
20 - 80 CAS 178
70 - 120 CAS 180
60 - 150 CAS 181
2 IC.PD.P10.G2.02 - 520B2358
Data sheet Pressure switches and thermostats, type CAS
ISO 9001 quality approval Danfoss A/S is certificated by BSI in accordance
with international standard ISO 9001. This means
that Danfoss fulfils the international standard
in respect of product development, design,
production and sale. BSI exercises continuous
inspection to ensure that Danfoss observes the
requirements of the standard and that Danfoss’
own quality assurance system is maintained at
the required level.
Approvals CE-marked acc. to EN 60947-5-1
CCC, China Compulsory Certificate
Ship approvals AmericanBureauofShipping,USA(excl.CAS139)
Lloyds Register of Shipping, UK
Germanischer Lloyd, Germany
Bureau Veritas, France
Det Norske Veritas, Norway
Registro Italiano Navale, Italy
RMRS, Maritime Register of Shipping,
Russia
Nippon Kaiji Kyokai, Japan
Survey Pressure switches, type CAS
Standard pressure switches
Pressure switches for high pressure and strongly pulsating media
0 30 60 90 120 150 °C
Range Type
°C
0 10 20 30 40 50 60 bar
Range Type
Pe
bar
Differential pressure switches
Thermostats, type CAS
0 → 3.5 0.1 10 10 40
G ¼
060-315066 CAS 133
0 → 10 0.2 22 22 40 060-315166 CAS 136
6 → 18 0.3 27 27 72 060-315266 CAS 137
10 → 35 0.6 53 53 100 060-315366 CAS 139
CAS 133, 135, 139
CAS 143, 145, 147
1 → 10 0.2 → 0.6 120 180 240
G ¼
060-316066 CAS 143
4 → 40 0.8 → 2.4 120 180 240 060-316166 CAS 145
6 → 60 1 → 3 120 180 240 060-316266 CAS 147
CAS 155
0.2 → 2.5 0.1 0 → 8 22 42 2 x G ¼ 060-313066 CAS 155
Data sheet Pressure switches and thermostats, type CAS
IC.PD.P10.G2.02 - 520B2358 3
Ordering Preferred version
Setting
range pe
(bar)
Mechanical
differential
(bar)
Permissible
operating
pressure
(bar)
Max test
pressure
(bar)
Min. burst
pressure
(bar)
Pressure
connection
Code no. Type
Pressure controls for high pressure and strongly pulsating media
Setting
range pe
(bar)
Mechanical
differential
(bar)
Permissible
operating
pressure
(bar)
Max test
pressure
(bar)
Min. burst
pressure
(bar)
Pressure
connection
Code no. Type
Differential pressure switch type CAS
Setting
range pe
(bar)
Mechanical
differential
(bar)
Permissible
operating
pressure for
low pressure
(bar)
Max test
pressure
(bar)
Min. burst
pressure
(bar)
Pressure
connection
Code no. Type
Max. test pressure
The highest pressure the unit may be subjected
to when, for example, testing the system for
leakage. Therefore, this presure must not occur as
a recurring system pressure.
Min. burst pressure
The pressure which the pressure-sensitive
element will withstand without leaking.
Range setting
The pressure range within which the unit will give
a signal (contact changeover).
Differential
The difference between make pressure and break
pressure (see also page 6).
Permissible burst pressure
The highest permanent or recurring pressure the
unit can be loaded with.
When ordering, please state type and code no.
Standard pressure switches
Terminology
4 IC.PD.P10.G2.02 - 520B2358
Data sheet Pressure switches and thermostats, type CAS
Switch
Microswitch with single pole changeover (SPDT)
Contact load
Alternating current:
220 V, 0.1 A, AC-14 and AC-15 (inductive load)
Direct current: 125 V, 12 W DC-13 (inductive load)
Materials in contact with the medium
Ambient temperature
CAS 133-139: -40 to +70°C
CAS 143-155: -25 to +70°C
Temperature of medium
CAS 133-139: -40 to + 100°C
CAS 143-155: -25 to + 100°C
For water and seawater, max. 80 °C
Vibration resistance
Vibration-stable in the range 2-30 Hz
amplitude 1.1 mm and 30-100 Hz, 4 G.
Enclosure
IP 67 acc. to IEC 529 and DIN 40050.
The pressure control housing is enamelled
pressure die cast aluminium (GD-AISi 12).
The cover is fastened by four screws which
are anchored to prevent loss.
The enclosure can be sealed with fuse wire.
Cable entry
Pg 13.5 for cable diametrers from 5 to 14 mm.
Identification
The type designation and code no. of the unit
is stamped in the side of the housing.
CAS
133
136
137
139
Bellows: Stainless steel, material no.
1.4306 (DIN 17440)
Pressure
connection: Brass material no. 2.0401
(DIN 17660)
CAS
143
145
147
155
Diaphragm
connection: Nickel plated brass CuZn
40 Ob3 ISO R 426
(DIN 17569)
Diaphragm: Nitrile-butadien rubber
Weight:
CAS 133-139 approx. 1.0 kg
CAS 143-147 approx. 1.3 kg
CAS 155 approx. 1.5 kg
Technical data
Dimensions
Data sheet Pressure switches and thermostats, type CAS
IC.PD.P10.G2.02 - 520B2358 5
Installation Installation
CAS pressure controls are fitted with a 3 mm steel
mounting plate. The units should not be allowed
to hang from the pressure connection.
Pressure connection
When fitting or removing pressure lines, the
spanner flats on the pressure connection should
be used to apply counter-torque.
Steam plant
To protect the pressure element from excessive
heat, the insertion of a water-filled loop is
recommended. The loop can, for example, be
made of 10 mm copper tube as shown in fig. 1.
Pulsations
If the pressure medium is superimposed with
severe pulsations, which occur in automatic
sprinkler systems (fire protection), fuel systems
for diesel motors (priming lines), and hydraulic
systems (e.g. propeller systems), etc, types case
143, 145, 147 are recommended. The maximum
permissible pulsation level for these types is 120
bar.
Setting
When the pressure control cover is removed, and
the locking screw (3) is lossened, the range can
be set with the spindle (1) while at the same time
the scale (2) is being read.
Water systems
Water in the pressure element is not harmful,
but in case of frost a water-filled pressure
element may burst. To prevent this happening,
the pressure control can be allowed to operate
on an air cushion.
Media resistance
Se table of materials in contact with the medium,
page 4. If seawater is involved, types CAS 143,
145, 147 are recommended.
Electrical connection
CAS pressure controls are fitted with a PG 13.5
screwed cable entry that is suitable for cable
diameters from 5 to 13 mm.
Contact function is shown in fig. 3.
Fig. 1
1 Range spindle
2 Range scale
3 Locking screw
Fig. 2
Fig. 3
6 IC.PD.P10.G2.02 - 520B2358
Data sheet Pressure switches and thermostats, type CAS
a. CAS 155
Contacts 1-4 make and contacts 1-2 break when the
differential pressure rises above the set range value.
The contacts changeover to their initial position
when the differential pressure again falls to the
range value minus the differential (see fig. 4).
Function I. Alarm for rising differential pressure given at
the set range value.
II. Alarm for falling differential pressure given at
the set range value minus the differential.
Scale setting
Mechanical differential
Fig. 4
b. All other CAS pressure controls
Contacts 1-2 make and contacts 1-4 break when
the pressure falls under the set range value. The
contacts changeover to their initial position when
the pressure again rises to the set range value
plus the differential (see fig. 5).
I. Alarm for falling pressure given at the set range
value.
II. Alarm for rising pressure given at the set range
value plus the differential.
Example 1:
An alarm must be given when the lubrication oil
pressure in a motor falls below 0.8 bar. Select CAS
133 (range 0 to 3.5 bar).
The minimum permissible lubricating oils
pressure of 0.8 bar must be set using the range
spindle. The differential is fixed at 0.1 bar, i.e. the
alarm will not cut out before the pressure rises to
0.9 bar.
The switch break function is normally used for
alarm purposes, i.e. the alarm must be connected
to terminals 1 and 4.
Example 2:
When the differential pressure exceeds 1.3 bar a
filter must be cleaned.
The maximum static pressure (LP) for the CAS 155
of 8 bar must not be exceeded.
The pressure control range spindle must be set
at 1.3 bar.
The alarm must be connected to terminals 1 and
2 (alarm for broken circuit).
Scale setting
Mechanical differential
Fig. 5
Data sheet Pressure switches and thermostats, type CAS
IC.PD.P10.G2.02 - 520B2358 7
Accessories
Part Description Qty. Code no.
Connector with nipple
Pipe thread ISO 228/1, G 3/8 connector, nipple and AL washer (10
mm ext. 8 mm int. diam) for solering onto steel or copper tubing, steel
span of jaws 22
5 017-436866
Connector with nipple
G 3/8 connector, nipple and washer (10 mm ext./ 6.5 mm int. diam.)
for welding, steel span of jaws 22
1 017-422966
Reducer
Pipe thread ISO 228/1, G 3/8 x 7/16 - 20 UNF reducer, washer, brass
span of jaws 22
5 017-420566
Adaptor
Pipe thread ISO 228/1, G 3/8 x 1/8 - 27 NPT with copper washer brass
span of jaws 22
1 060-333466
Adaptor
Pipe thread ISO 228/1, G 3/8 A x 1/4 - 18 NPT with copper washer brass
span of jaws 22
1 060-333566
Adaptor
Pipe thread ISO 228/1, G 3/8 x 1/4 - 18 NPT with copper washer brass
span of jaws 22
1 060-333666
Adaptor 7/16 - 20UNF x R 3/8 (ISO 7/1) brass, span of jaws 19 1 060-324066
Nipple
G 1/4 A x G 3/8 A 060-333266
G 1/4 A x ext. M10 x 1 with washer 060-333866
Damping coil
Pipe thread ISO 228/1, damping coil with G 3/8 connector and 1.5 m
copper capillary tube. Standard washers are supplied.
1 060-104766
Armoured damping coil
Pipe thread ISO 228/1, damping coil with G 3/8 connector and 1 m
copper capillary tube. Standard washers are supplied.
1 060-333366
20 → 80 2.0 130 65 75 110 160 2 060L315166 CAS 178
70 → 120 2.0 220 65 75 110 160 2 060L315366 CAS 180
60 → 150 2.0 250 65 75 110 160 2 060L315566 CAS 181
8 IC.PD.P10.G2.02 - 520B2358
Data sheet Pressure switches and thermostats, type CAS
CAS thermostats are temperature-controlled
switches. The position of the contacts depends
on the temperature of the sensor and the set
scale value. In this series, special attention has
been given to meeting demands for a high level
of enclosure, robust and compact construction,
and resistance to shock and vibration.
Description The CAS series covers most outdoor as well as
indoor application requirements.
CAS thermostats are suitable for use in monitoring
and alarm systems in factories, diesel plant,
compressors, power stations and on board ship.
Technical data and ordering
CAS with remote sensor,
armoured capillary tube
Preferred version
When ordering, please state type and code number
Setting
range
°C
Mechanical
differential
adjustable /
fixed
°C
Max. sensor
temperature
°C
Suitable
sensor length
(see also
“Accessories”)
mm
Capillary
tube length
m
Code no. Type
Switch
Microswitch with single pole changeover (SPDT)
Contact load
Alternating current:
220 V, ~0,1 A, AC-14 and AC-15 (inductive load)
Direct current
125 V, 12W DC-13 (inductive load)
Ambient temperature
CAS 178,180 and 181: -25°C → +70°C
Vibration resistance
Vibration-stable in the range 2-30 Hz,
amplitude 1,1 mm and 30-100 Hz, 4 G.
Enclosure
IP 67 acc. to IEC 529 and DIN 40050.
The thermostat housing is enamelled pressure
die cast aluminium (GD-AISI 12). The cover is
fastened by four screws which are anchored to
prevent loss.
The enclosure can be sealed with fuse wire.
Cable entry
Pg 13.5 for cable diameters from 5 to 14 mm.
Identification
The type designation and code no. of the unit is
stamped in the side of the housing.
Approvals CE marked acc. to EN 60947-5-1
CCC, China Compulsory Certificate
Ship approvals American Bureau of Shipping, USA
Bureau Veritas, France
Det Norske Veritas, Norway
Germanischer Lloyd, Germany
Lloyd Register of Shipping, UK
Nippon Kaiji Kyokai, Japan
Registro Italiano Navale, Italy
RMRS, Maritime Register of Shipping, Russia
Data sheet Pressure switches and thermostats, type CAS
IC.PD.P10.G2.02 - 520B2358 9
Accessories: Sensor pockets for
thermostats
Sensor
pocket
A
mm
Thread
B
Code no. Sensor pocket A
mm
Thread
B
Code no.
Note: all sensor pockets are
supplied without gland nut,
gaskets and washes
Brass 65 ½ NPT 060L326566
Brass 75
75
75
75
½ NPT
G ½ A
G ¾ A
G ½ A (ISO 228/1)
060L326466
060L326266
060L326666
060L328166
Steel 18/8 75 G ½ A 060L326766
Brass 110
110
110
110
½ NPT
G ½ A
G ½ A (ISO 228/1)
G ¾ A (ISO 228/1)
060L328066
060L327166
060L340666
060L340366
Steel 18/8 110
110
G ½ A
½ NPT
060L326866
060L327066
Brass 160
160
G ½ A
G ¾ A (ISO 228/1)
060L326366
060L340566
Steel 18/8 160 G ½ A 060L326966
Brass 200
200
200
G ½ A
G ½ A (ISO 228/1)
G ¾ A (ISO 228/1)
060L320666
060L340866
060L340266
Steel 18/8 200
200
G ½ A
G ¾ A
060L323766
060L324866
Brass 250 G ½ A 060L325466
Brass 330 G ½ A 060L325566
Brass 400 G ½ A 060L325666
Other Accessories Description Qty./ unit Code no.
Clamping band For CAS thermostats with remote sensor (L = 392 mm) 10 017-420466
Heat conductive compound
(Tube with 4.5 cm3
)
For CAS with sensor fitted in a sensor pocket.
For filling sensor pocket to improve heat transfer
between pocket and sensor.
Application range for compound: -20 to +150 °C,
momentarily up to 220°C
1 041E0114
Dimensions and weight
CAS with remote sensor and 2 m armoured capillary tube
Weight: approx. 1.4 kg
CAS 178 20 → 80 2.5
CAS 180 70 → 120 2.4
CAS 181 60 → 150 3.7
10 IC.PD.P10.G2.02 - 520B2358
Data sheet Pressure switches and thermostats, type CAS
Location of unit: CAS thermostats are designed to
withstand the shocks that occur, for example, in
ships on compressors and in large machine
installations. CAS thermostats are fitted with a
base of 3 mm steel plate for fixing to bulkheads,
etc.
Resistance to media
Material specifications for sensor pockets.
Sensor pocket brass
The tube is made of Ms 72 to DIN 17660, the
threaded portion of So Ms 58 Pb to DIN 17661.
Sensor pocket, stainless steel 18/8
Material designation 1.4305 to DIN 17440.
Sensor position
As far as possible the sensor should be positioned
so that its longitudinal axis is at right angles to
the direction flow. The active part of the sensor is
Ø13 mm × 47.5 mm.
The medium
The fastest reaction is obtained from a medium
having high specific heat and high thermal
conductivity. It is therefore advantageous to use
a medium that fulfils these conditions (provided
there is a choice). The flow velocity of the
medium is also of significance. (The optimum
flow velocity for liquids is about 0.3 m/s).
For permissible media pressure see fig. 1.
Installation
Brass Stainless steel 18/8
Fig. 1
Permissible media pressure on the sensor
pocket as a function of temperature
Setting
When the thermostat cover is removed, and the
locking screw (3) fig. 2 is loosened, the range can
be set with the spindle (1) while at the same time
the scale (2) is being read.
Fig. 2
1. Range spindle
2. Range scale
3. Locking screw
Relative
scale
setting
in %
Type
Regulation
range
°C
Correction
factor a for
thermostats
Scale correction
The sensor on CAS thermostats contains an
adsorption charge. Therefore function is not
affected whether the sensor is placed warmer or
colder than the remaining part of the
thermostatic element (bellows and capillary
tube).
However, such a charge is to some extent
sensitive to changes in the temperature of
bellows and capillary tube. Under normal
conditions this is of no importance, but if the
thermostat is to be used in extreme ambient
temperatures there will be a scale deviation.
The deviation can be compensated for as follows:
Scale correction = Z × a
Z can be found from fig. 3, while a is the
correction factor from the table below.
(See example, page 11).
Fig. 3
Factor for scale
deviation
Data sheet Pressure switches and thermostats, type CAS
IC.PD.P10.G2.02 - 520B2358 11
Electrical connection
CAS thermostats are fitted with a Pg 13.5 screwed
cable entry suitable for cables from 5 to 14 mm.
Contact function, see fig. 4.
Fig. 4
Function Differentials
The mechanical differential is the differential
determined by the design of the thermostat. The
thermal differential (operating differential) is the
differential the system operates on.
The thermal differential is always greater than the
mechanical differential and depends on three
factors:
1) Medium flow velocity
2) Temperature change rate of the medium
3) Heat transmission to the sensor
Thermostat function
Contacts 1-4 make while contacts 1-2 break when
the temperature rises above the scale setting.
The contacts changeover to their initial position
when the temperature falls to the scale setting
minus the differential. See fig. 5.
Scale setting
Mechanical differential
Fig. 5
I. Alarm for rising temperature
given at range setting value.
II. Alarm for falling temperature
given at range setting value
minus the differential
Example 1
Diesel engine with cooling water temperature of
85°C (normal). An alarm must be triggered if the
cooling water temperature exceeds 95°C. Choose
a CAS thermostat 180 (range +70 to 120°C).
Main spindle setting: 95°C.
The required alarm function is obtained by
connecting to thermostat terminals 1-4.
Example 2
Find the necessary scale correction for a CAS 180.
Set +95°C at +50°C ambient temperature.
The relative scale setting Z can be calculated from
the following formula:
Setting value - min. scale value
max. scale value - min. scale value
x 100 = %
Relative scale setting: 95 - 70 x 100 = 50%
120 - 70
Factor for scale deviation Z fig. 3, Z ≅ 0.7
Correction factor a, see table page 10,
fig. 3 = 2.4.
Scale correction = Z x a = 0.7 x 2.4 = 1.7°C
CAS must be set at 95 + 1.7 = 96.7°C
®DanfossA/S10-05/IC-MC/mr
Data sheet Pressure switches and thermostats, type CAS
12 IC.PD.P10.G2.02-520B2358
Conversion table
Pascal
(= Newton
per square
metre)
N/m2
)
PA
Pascal per
square mm
N/mm2
bar
Kilopound
per square
metre
(mm H2O)
kp/m2
Meter
water
gauge
m H2O
Technical
atmosphere
(kp/cm2
)
at
Physical
atmosphere
atm
Torr
(0°C)
mm Hg
Inches
Hg (0°C)
Poundforce
per square
inch
(lbf/in2
)
psi
1 Pa 1 10-6
10-5
0.1020 1.020 × 10-4
1.020 × 10-5
9.869 × 10-5
7.500 ×10-3
2.953 × 10-4
1.450 × 10-4
1 N/mm2
106
1 10 1.020 × 105
102.0 10.20 9.869 7.5 ×103
295.3 145.0
1 bar 105
0.1 1 10.197 ×103
10.20 1.020 0.9869 750 29.53 14.50
1 kp/m2
9.80665 9.807 × 10-6
9.807 × 10-5
1 10-3
10-4
0.9678 ×10-4
0.07355 2.896 × 10-3
1.422 × 10-3
1 m H2
O 9806.7 9.807 × 103
0.09807 1000 1 0.1 0.09678 73.55 2.896 1.422
1 at 98.066 ×103
0.09807 0.9807 104
10 1 0.9678 735.5 28.96 14.22
1 atm 101.325 ×103
0.1013 1.013 10.333 ×103
10.33 1.033 1 760 29.92 14.70
1 mm Hg 133.32 1.333 × 10-4
1.333 × 10-3
13.60 0.01360 1.360 × 10-3
1.315 × 10-3
1 0.03937 1.934 × 10-2
1 in Hg 3387 3.387 × 10-3
0.03387 345.3 0.3453 0.03453 0.03342 25.4 1 0.4912
1 psi 6895 6.895 × 10-3
0.06895 703.1 0.7031 0.07031 0.96804 51.71 2.036 1

More Related Content

What's hot

M a 723 datasheet
M a 723 datasheetM a 723 datasheet
M a 723 datasheetAndy Medina
 
Stahl 6122 Tank Inspection Light - ATEX Zone 1 Zone 2 Hazardous Area Lighting
Stahl 6122 Tank Inspection Light - ATEX Zone 1 Zone 2 Hazardous Area LightingStahl 6122 Tank Inspection Light - ATEX Zone 1 Zone 2 Hazardous Area Lighting
Stahl 6122 Tank Inspection Light - ATEX Zone 1 Zone 2 Hazardous Area LightingThorne & Derrick International
 
Flameproof High Range Pressure Switches FE Series
Flameproof High Range Pressure Switches FE SeriesFlameproof High Range Pressure Switches FE Series
Flameproof High Range Pressure Switches FE SeriesNK Instruments Pvt. Ltd.
 
Catalog đèn báo nút nhấn công tắc IDEC (Nhật Bản) - dòng A6
Catalog đèn báo nút nhấn công tắc IDEC (Nhật Bản) - dòng A6Catalog đèn báo nút nhấn công tắc IDEC (Nhật Bản) - dòng A6
Catalog đèn báo nút nhấn công tắc IDEC (Nhật Bản) - dòng A6CTY TNHH HẠO PHƯƠNG
 
Original Mosfet P-Channel TJ20A10M3 J20A10M3 J20A10M 100V 10A TO-220 New
Original Mosfet P-Channel TJ20A10M3 J20A10M3 J20A10M 100V 10A TO-220 NewOriginal Mosfet P-Channel TJ20A10M3 J20A10M3 J20A10M 100V 10A TO-220 New
Original Mosfet P-Channel TJ20A10M3 J20A10M3 J20A10M 100V 10A TO-220 NewAUTHELECTRONIC
 
Original MOSFET N-CHANNEL K15A60D K15A60U 15A60D 15A60 TO-220 15A 600V New
Original MOSFET N-CHANNEL K15A60D K15A60U 15A60D 15A60 TO-220 15A 600V NewOriginal MOSFET N-CHANNEL K15A60D K15A60U 15A60D 15A60 TO-220 15A 600V New
Original MOSFET N-CHANNEL K15A60D K15A60U 15A60D 15A60 TO-220 15A 600V NewAUTHELECTRONIC
 
Original N-Channel Mosfet TK5A50D 5A50D 500V 5A TO-220F New Toshiba
Original N-Channel Mosfet TK5A50D 5A50D 500V 5A TO-220F New ToshibaOriginal N-Channel Mosfet TK5A50D 5A50D 500V 5A TO-220F New Toshiba
Original N-Channel Mosfet TK5A50D 5A50D 500V 5A TO-220F New ToshibaAUTHELECTRONIC
 
Catalog đèn báo nút nhấn phi 30 (Dòng chống cháy)
Catalog đèn báo nút nhấn phi 30 (Dòng chống cháy)Catalog đèn báo nút nhấn phi 30 (Dòng chống cháy)
Catalog đèn báo nút nhấn phi 30 (Dòng chống cháy)CTY TNHH HẠO PHƯƠNG
 
Original MOSFET N-CHANNEL K10A60D K10A60U 10A60D 10A60 TO-220 10A 600V New
Original MOSFET N-CHANNEL K10A60D K10A60U 10A60D 10A60 TO-220 10A 600V NewOriginal MOSFET N-CHANNEL K10A60D K10A60U 10A60D 10A60 TO-220 10A 600V New
Original MOSFET N-CHANNEL K10A60D K10A60U 10A60D 10A60 TO-220 10A 600V NewAUTHELECTRONIC
 
Pressure-Control-Brochure
Pressure-Control-BrochurePressure-Control-Brochure
Pressure-Control-BrochureMelanie Brule
 
Original N-Channel Mosfet TK4P50D 500V 4A TO-252 New TOSHIBA
Original N-Channel Mosfet TK4P50D 500V 4A TO-252 New TOSHIBAOriginal N-Channel Mosfet TK4P50D 500V 4A TO-252 New TOSHIBA
Original N-Channel Mosfet TK4P50D 500V 4A TO-252 New TOSHIBAAUTHELECTRONIC
 
Original N-Channel Mosfet DN2540 DN2540N5 2540 TO-220 New Supertex
Original N-Channel Mosfet DN2540 DN2540N5 2540 TO-220 New SupertexOriginal N-Channel Mosfet DN2540 DN2540N5 2540 TO-220 New Supertex
Original N-Channel Mosfet DN2540 DN2540N5 2540 TO-220 New SupertexAUTHELECTRONIC
 
Catalogue MCB Fuji- Miniature Circuit Breaker Fuji - Beeteco.com
Catalogue MCB Fuji- Miniature Circuit Breaker Fuji - Beeteco.comCatalogue MCB Fuji- Miniature Circuit Breaker Fuji - Beeteco.com
Catalogue MCB Fuji- Miniature Circuit Breaker Fuji - Beeteco.comBeeteco
 
Original IGBT TK8A60DA K8A60 600V 7.5A TO-220F New Toshiba
Original IGBT TK8A60DA K8A60 600V 7.5A TO-220F New ToshibaOriginal IGBT TK8A60DA K8A60 600V 7.5A TO-220F New Toshiba
Original IGBT TK8A60DA K8A60 600V 7.5A TO-220F New ToshibaAUTHELECTRONIC
 

What's hot (17)

CeraDyna Cooling fans
CeraDyna Cooling fansCeraDyna Cooling fans
CeraDyna Cooling fans
 
Catalog hmi idec
Catalog hmi idecCatalog hmi idec
Catalog hmi idec
 
M a 723 datasheet
M a 723 datasheetM a 723 datasheet
M a 723 datasheet
 
Stahl 6122 Tank Inspection Light - ATEX Zone 1 Zone 2 Hazardous Area Lighting
Stahl 6122 Tank Inspection Light - ATEX Zone 1 Zone 2 Hazardous Area LightingStahl 6122 Tank Inspection Light - ATEX Zone 1 Zone 2 Hazardous Area Lighting
Stahl 6122 Tank Inspection Light - ATEX Zone 1 Zone 2 Hazardous Area Lighting
 
Flameproof High Range Pressure Switches FE Series
Flameproof High Range Pressure Switches FE SeriesFlameproof High Range Pressure Switches FE Series
Flameproof High Range Pressure Switches FE Series
 
Catalog PX5R IDEC - www.haophuong.com
Catalog PX5R IDEC - www.haophuong.comCatalog PX5R IDEC - www.haophuong.com
Catalog PX5R IDEC - www.haophuong.com
 
Catalog đèn báo nút nhấn công tắc IDEC (Nhật Bản) - dòng A6
Catalog đèn báo nút nhấn công tắc IDEC (Nhật Bản) - dòng A6Catalog đèn báo nút nhấn công tắc IDEC (Nhật Bản) - dòng A6
Catalog đèn báo nút nhấn công tắc IDEC (Nhật Bản) - dòng A6
 
Original Mosfet P-Channel TJ20A10M3 J20A10M3 J20A10M 100V 10A TO-220 New
Original Mosfet P-Channel TJ20A10M3 J20A10M3 J20A10M 100V 10A TO-220 NewOriginal Mosfet P-Channel TJ20A10M3 J20A10M3 J20A10M 100V 10A TO-220 New
Original Mosfet P-Channel TJ20A10M3 J20A10M3 J20A10M 100V 10A TO-220 New
 
Original MOSFET N-CHANNEL K15A60D K15A60U 15A60D 15A60 TO-220 15A 600V New
Original MOSFET N-CHANNEL K15A60D K15A60U 15A60D 15A60 TO-220 15A 600V NewOriginal MOSFET N-CHANNEL K15A60D K15A60U 15A60D 15A60 TO-220 15A 600V New
Original MOSFET N-CHANNEL K15A60D K15A60U 15A60D 15A60 TO-220 15A 600V New
 
Original N-Channel Mosfet TK5A50D 5A50D 500V 5A TO-220F New Toshiba
Original N-Channel Mosfet TK5A50D 5A50D 500V 5A TO-220F New ToshibaOriginal N-Channel Mosfet TK5A50D 5A50D 500V 5A TO-220F New Toshiba
Original N-Channel Mosfet TK5A50D 5A50D 500V 5A TO-220F New Toshiba
 
Catalog đèn báo nút nhấn phi 30 (Dòng chống cháy)
Catalog đèn báo nút nhấn phi 30 (Dòng chống cháy)Catalog đèn báo nút nhấn phi 30 (Dòng chống cháy)
Catalog đèn báo nút nhấn phi 30 (Dòng chống cháy)
 
Original MOSFET N-CHANNEL K10A60D K10A60U 10A60D 10A60 TO-220 10A 600V New
Original MOSFET N-CHANNEL K10A60D K10A60U 10A60D 10A60 TO-220 10A 600V NewOriginal MOSFET N-CHANNEL K10A60D K10A60U 10A60D 10A60 TO-220 10A 600V New
Original MOSFET N-CHANNEL K10A60D K10A60U 10A60D 10A60 TO-220 10A 600V New
 
Pressure-Control-Brochure
Pressure-Control-BrochurePressure-Control-Brochure
Pressure-Control-Brochure
 
Original N-Channel Mosfet TK4P50D 500V 4A TO-252 New TOSHIBA
Original N-Channel Mosfet TK4P50D 500V 4A TO-252 New TOSHIBAOriginal N-Channel Mosfet TK4P50D 500V 4A TO-252 New TOSHIBA
Original N-Channel Mosfet TK4P50D 500V 4A TO-252 New TOSHIBA
 
Original N-Channel Mosfet DN2540 DN2540N5 2540 TO-220 New Supertex
Original N-Channel Mosfet DN2540 DN2540N5 2540 TO-220 New SupertexOriginal N-Channel Mosfet DN2540 DN2540N5 2540 TO-220 New Supertex
Original N-Channel Mosfet DN2540 DN2540N5 2540 TO-220 New Supertex
 
Catalogue MCB Fuji- Miniature Circuit Breaker Fuji - Beeteco.com
Catalogue MCB Fuji- Miniature Circuit Breaker Fuji - Beeteco.comCatalogue MCB Fuji- Miniature Circuit Breaker Fuji - Beeteco.com
Catalogue MCB Fuji- Miniature Circuit Breaker Fuji - Beeteco.com
 
Original IGBT TK8A60DA K8A60 600V 7.5A TO-220F New Toshiba
Original IGBT TK8A60DA K8A60 600V 7.5A TO-220F New ToshibaOriginal IGBT TK8A60DA K8A60 600V 7.5A TO-220F New Toshiba
Original IGBT TK8A60DA K8A60 600V 7.5A TO-220F New Toshiba
 

Viewers also liked

Differential Pressure Switch/ Gages
Differential Pressure Switch/ GagesDifferential Pressure Switch/ Gages
Differential Pressure Switch/ GagesDwyer Instruments
 
Tti basic electricity level 1
Tti basic electricity level 1Tti basic electricity level 1
Tti basic electricity level 1liniprasad
 
Electrical components 4
Electrical components 4Electrical components 4
Electrical components 4mar1897
 
Basic electrical comp upload1
Basic electrical comp upload1Basic electrical comp upload1
Basic electrical comp upload1Ganesh Kumar
 
Speed Control of Induction Motor using Variable Frequency Drive
Speed Control of Induction Motor using Variable Frequency DriveSpeed Control of Induction Motor using Variable Frequency Drive
Speed Control of Induction Motor using Variable Frequency DriveSandeep Kaushal
 
ppt on Introduction to basic electrical concept by harshid panchal
ppt on Introduction to basic electrical concept by harshid panchalppt on Introduction to basic electrical concept by harshid panchal
ppt on Introduction to basic electrical concept by harshid panchalharshid panchal
 
speed control of three phase induction motor
speed control of three phase induction motorspeed control of three phase induction motor
speed control of three phase induction motorAshvani Shukla
 
Introduction to Electrical Engineering branch of Engineering
Introduction to Electrical Engineering branch of EngineeringIntroduction to Electrical Engineering branch of Engineering
Introduction to Electrical Engineering branch of EngineeringLearn By Watch
 
Basic electricity
Basic electricityBasic electricity
Basic electricityAdymtz
 
Pressure measurement id Mitesh Kuamr
Pressure measurement id Mitesh KuamrPressure measurement id Mitesh Kuamr
Pressure measurement id Mitesh KuamrMitesh Kumar
 
Electrical Engineering Presentation
Electrical Engineering PresentationElectrical Engineering Presentation
Electrical Engineering Presentationjoe2002
 
Introducing Electricity
Introducing  ElectricityIntroducing  Electricity
Introducing Electricityscotfuture
 
Electricity (ppt)
Electricity (ppt)Electricity (ppt)
Electricity (ppt)Stanley Ang
 

Viewers also liked (20)

JJ Enterprises, Chennai, Contactor Siemens
JJ Enterprises, Chennai, Contactor SiemensJJ Enterprises, Chennai, Contactor Siemens
JJ Enterprises, Chennai, Contactor Siemens
 
Ice asia
Ice asiaIce asia
Ice asia
 
Differential Pressure Switch/ Gages
Differential Pressure Switch/ GagesDifferential Pressure Switch/ Gages
Differential Pressure Switch/ Gages
 
Tti basic electricity level 1
Tti basic electricity level 1Tti basic electricity level 1
Tti basic electricity level 1
 
Electrical components 4
Electrical components 4Electrical components 4
Electrical components 4
 
Basic electrical comp upload1
Basic electrical comp upload1Basic electrical comp upload1
Basic electrical comp upload1
 
Basic of electrical
Basic of electricalBasic of electrical
Basic of electrical
 
Speed Control of Induction Motor using Variable Frequency Drive
Speed Control of Induction Motor using Variable Frequency DriveSpeed Control of Induction Motor using Variable Frequency Drive
Speed Control of Induction Motor using Variable Frequency Drive
 
Thermocouple
ThermocoupleThermocouple
Thermocouple
 
ppt on Introduction to basic electrical concept by harshid panchal
ppt on Introduction to basic electrical concept by harshid panchalppt on Introduction to basic electrical concept by harshid panchal
ppt on Introduction to basic electrical concept by harshid panchal
 
Basic Electrical Theory Bitter
Basic Electrical Theory   BitterBasic Electrical Theory   Bitter
Basic Electrical Theory Bitter
 
speed control of three phase induction motor
speed control of three phase induction motorspeed control of three phase induction motor
speed control of three phase induction motor
 
Introduction to Electrical Engineering branch of Engineering
Introduction to Electrical Engineering branch of EngineeringIntroduction to Electrical Engineering branch of Engineering
Introduction to Electrical Engineering branch of Engineering
 
Basic electricity
Basic electricityBasic electricity
Basic electricity
 
Electrical Engineering
Electrical EngineeringElectrical Engineering
Electrical Engineering
 
Pressure measurement id Mitesh Kuamr
Pressure measurement id Mitesh KuamrPressure measurement id Mitesh Kuamr
Pressure measurement id Mitesh Kuamr
 
Electrical Engineering Presentation
Electrical Engineering PresentationElectrical Engineering Presentation
Electrical Engineering Presentation
 
Introducing Electricity
Introducing  ElectricityIntroducing  Electricity
Introducing Electricity
 
Eee ppt
Eee pptEee ppt
Eee ppt
 
Electricity (ppt)
Electricity (ppt)Electricity (ppt)
Electricity (ppt)
 

Similar to Pressure switches and thermostats, type CAS

HRF3205.pdf
HRF3205.pdfHRF3205.pdf
HRF3205.pdfivan ion
 
Sw low pressure
Sw low pressureSw low pressure
Sw low pressurerenato
 
Lm7805
Lm7805Lm7805
Lm7805tyhfre
 
Data Sheet LM7805
Data Sheet LM7805Data Sheet LM7805
Data Sheet LM7805arwicaksono
 
Original N Channel Mosfet FQD10N60C STD10NM60N 10NM60 10N60 10A 600V TO-252 N...
Original N Channel Mosfet FQD10N60C STD10NM60N 10NM60 10N60 10A 600V TO-252 N...Original N Channel Mosfet FQD10N60C STD10NM60N 10NM60 10N60 10A 600V TO-252 N...
Original N Channel Mosfet FQD10N60C STD10NM60N 10NM60 10N60 10A 600V TO-252 N...AUTHELECTRONIC
 
Original N-Channel Mosfet 2SK2628 K2628 2628 TO-220 New Rochester Electronics
Original N-Channel Mosfet 2SK2628 K2628 2628 TO-220 New Rochester ElectronicsOriginal N-Channel Mosfet 2SK2628 K2628 2628 TO-220 New Rochester Electronics
Original N-Channel Mosfet 2SK2628 K2628 2628 TO-220 New Rochester ElectronicsAUTHELECTRONIC
 
Original N-Channel Mosfet STD12NF06LT4 12NF06 D12NF06 D12NF 60V 12A TO-252 Ne...
Original N-Channel Mosfet STD12NF06LT4 12NF06 D12NF06 D12NF 60V 12A TO-252 Ne...Original N-Channel Mosfet STD12NF06LT4 12NF06 D12NF06 D12NF 60V 12A TO-252 Ne...
Original N-Channel Mosfet STD12NF06LT4 12NF06 D12NF06 D12NF 60V 12A TO-252 Ne...AUTHELECTRONIC
 
จำหน่าย Pressure Switch Norgren - นิวเมติก.com
จำหน่าย Pressure Switch Norgren - นิวเมติก.comจำหน่าย Pressure Switch Norgren - นิวเมติก.com
จำหน่าย Pressure Switch Norgren - นิวเมติก.comDNTMb Inc.
 
Original N-channel 650 V 0.230 Ohm 12 A MDmesh V Power MOSFET in DPAK DPAK ST...
Original N-channel 650 V 0.230 Ohm 12 A MDmesh V Power MOSFET in DPAK DPAK ST...Original N-channel 650 V 0.230 Ohm 12 A MDmesh V Power MOSFET in DPAK DPAK ST...
Original N-channel 650 V 0.230 Ohm 12 A MDmesh V Power MOSFET in DPAK DPAK ST...AUTHELECTRONIC
 
Original Mosfet N-Channel FQA9N90 9N90C 9N90 900V 8.6A TO-3P New Fairchild
Original Mosfet N-Channel FQA9N90 9N90C 9N90 900V 8.6A TO-3P New FairchildOriginal Mosfet N-Channel FQA9N90 9N90C 9N90 900V 8.6A TO-3P New Fairchild
Original Mosfet N-Channel FQA9N90 9N90C 9N90 900V 8.6A TO-3P New FairchildAUTHELECTRONIC
 
Original N-Channel Mosfet STP65NF06 P65NF06 65A 60V TO-220 New ST
Original N-Channel Mosfet STP65NF06 P65NF06 65A 60V TO-220 New STOriginal N-Channel Mosfet STP65NF06 P65NF06 65A 60V TO-220 New ST
Original N-Channel Mosfet STP65NF06 P65NF06 65A 60V TO-220 New STAUTHELECTRONIC
 
2 cds251103r0517 miniature-circuit-breaker-s200-1np-k-25-ampere
2 cds251103r0517 miniature-circuit-breaker-s200-1np-k-25-ampere2 cds251103r0517 miniature-circuit-breaker-s200-1np-k-25-ampere
2 cds251103r0517 miniature-circuit-breaker-s200-1np-k-25-ampereRabah Zaimeddine
 
Moc3011 optoacop motores 125 v
Moc3011 optoacop motores 125 vMoc3011 optoacop motores 125 v
Moc3011 optoacop motores 125 vPablo Inda-Huerta
 
Tps3305 33
Tps3305 33Tps3305 33
Tps3305 33____
 
Catalogue Timer Idec - Beeteco.com
Catalogue Timer Idec - Beeteco.comCatalogue Timer Idec - Beeteco.com
Catalogue Timer Idec - Beeteco.comBeeteco
 
Original Mosfet SM4024N SM4024NSU 4024 TO-252-3 New
Original Mosfet SM4024N SM4024NSU 4024 TO-252-3 NewOriginal Mosfet SM4024N SM4024NSU 4024 TO-252-3 New
Original Mosfet SM4024N SM4024NSU 4024 TO-252-3 NewAUTHELECTRONIC
 

Similar to Pressure switches and thermostats, type CAS (20)

HRF3205.pdf
HRF3205.pdfHRF3205.pdf
HRF3205.pdf
 
Sw low pressure
Sw low pressureSw low pressure
Sw low pressure
 
08 - Circuit Protector - Fuji Electric
08 - Circuit Protector - Fuji Electric08 - Circuit Protector - Fuji Electric
08 - Circuit Protector - Fuji Electric
 
Utc15 n60
Utc15 n60Utc15 n60
Utc15 n60
 
Lm7805
Lm7805Lm7805
Lm7805
 
Data Sheet LM7805
Data Sheet LM7805Data Sheet LM7805
Data Sheet LM7805
 
Original N Channel Mosfet FQD10N60C STD10NM60N 10NM60 10N60 10A 600V TO-252 N...
Original N Channel Mosfet FQD10N60C STD10NM60N 10NM60 10N60 10A 600V TO-252 N...Original N Channel Mosfet FQD10N60C STD10NM60N 10NM60 10N60 10A 600V TO-252 N...
Original N Channel Mosfet FQD10N60C STD10NM60N 10NM60 10N60 10A 600V TO-252 N...
 
Original N-Channel Mosfet 2SK2628 K2628 2628 TO-220 New Rochester Electronics
Original N-Channel Mosfet 2SK2628 K2628 2628 TO-220 New Rochester ElectronicsOriginal N-Channel Mosfet 2SK2628 K2628 2628 TO-220 New Rochester Electronics
Original N-Channel Mosfet 2SK2628 K2628 2628 TO-220 New Rochester Electronics
 
Original N-Channel Mosfet STD12NF06LT4 12NF06 D12NF06 D12NF 60V 12A TO-252 Ne...
Original N-Channel Mosfet STD12NF06LT4 12NF06 D12NF06 D12NF 60V 12A TO-252 Ne...Original N-Channel Mosfet STD12NF06LT4 12NF06 D12NF06 D12NF 60V 12A TO-252 Ne...
Original N-Channel Mosfet STD12NF06LT4 12NF06 D12NF06 D12NF 60V 12A TO-252 Ne...
 
จำหน่าย Pressure Switch Norgren - นิวเมติก.com
จำหน่าย Pressure Switch Norgren - นิวเมติก.comจำหน่าย Pressure Switch Norgren - นิวเมติก.com
จำหน่าย Pressure Switch Norgren - นิวเมติก.com
 
Original N-channel 650 V 0.230 Ohm 12 A MDmesh V Power MOSFET in DPAK DPAK ST...
Original N-channel 650 V 0.230 Ohm 12 A MDmesh V Power MOSFET in DPAK DPAK ST...Original N-channel 650 V 0.230 Ohm 12 A MDmesh V Power MOSFET in DPAK DPAK ST...
Original N-channel 650 V 0.230 Ohm 12 A MDmesh V Power MOSFET in DPAK DPAK ST...
 
Original Mosfet N-Channel FQA9N90 9N90C 9N90 900V 8.6A TO-3P New Fairchild
Original Mosfet N-Channel FQA9N90 9N90C 9N90 900V 8.6A TO-3P New FairchildOriginal Mosfet N-Channel FQA9N90 9N90C 9N90 900V 8.6A TO-3P New Fairchild
Original Mosfet N-Channel FQA9N90 9N90C 9N90 900V 8.6A TO-3P New Fairchild
 
Original N-Channel Mosfet STP65NF06 P65NF06 65A 60V TO-220 New ST
Original N-Channel Mosfet STP65NF06 P65NF06 65A 60V TO-220 New STOriginal N-Channel Mosfet STP65NF06 P65NF06 65A 60V TO-220 New ST
Original N-Channel Mosfet STP65NF06 P65NF06 65A 60V TO-220 New ST
 
2 cds251103r0517 miniature-circuit-breaker-s200-1np-k-25-ampere
2 cds251103r0517 miniature-circuit-breaker-s200-1np-k-25-ampere2 cds251103r0517 miniature-circuit-breaker-s200-1np-k-25-ampere
2 cds251103r0517 miniature-circuit-breaker-s200-1np-k-25-ampere
 
L293d
L293dL293d
L293d
 
Moc3011 optoacop motores 125 v
Moc3011 optoacop motores 125 vMoc3011 optoacop motores 125 v
Moc3011 optoacop motores 125 v
 
Tps3305 33
Tps3305 33Tps3305 33
Tps3305 33
 
Catalogue Timer Idec - Beeteco.com
Catalogue Timer Idec - Beeteco.comCatalogue Timer Idec - Beeteco.com
Catalogue Timer Idec - Beeteco.com
 
Sistem breaker pro abb
Sistem breaker pro abbSistem breaker pro abb
Sistem breaker pro abb
 
Original Mosfet SM4024N SM4024NSU 4024 TO-252-3 New
Original Mosfet SM4024N SM4024NSU 4024 TO-252-3 NewOriginal Mosfet SM4024N SM4024NSU 4024 TO-252-3 New
Original Mosfet SM4024N SM4024NSU 4024 TO-252-3 New
 

More from Danfoss India

IDC – 2, Reliance Corporate Park, Navi Mumbai - Green Campus certified by IGBC
IDC – 2, Reliance Corporate Park, Navi Mumbai - Green Campus certified by IGBCIDC – 2, Reliance Corporate Park, Navi Mumbai - Green Campus certified by IGBC
IDC – 2, Reliance Corporate Park, Navi Mumbai - Green Campus certified by IGBCDanfoss India
 
RBEI, Coimbatore - CII awarded ‘Excellent Energy Efficient Building’
RBEI, Coimbatore - CII awarded ‘Excellent Energy Efficient Building’RBEI, Coimbatore - CII awarded ‘Excellent Energy Efficient Building’
RBEI, Coimbatore - CII awarded ‘Excellent Energy Efficient Building’Danfoss India
 
Ramanujan IT City, Chennai - 100 % recycled water used for cooling tower
Ramanujan IT City, Chennai - 100 % recycled water used for cooling towerRamanujan IT City, Chennai - 100 % recycled water used for cooling tower
Ramanujan IT City, Chennai - 100 % recycled water used for cooling towerDanfoss India
 
CEPT University, Ahmedabad - Net Zero Energy Building
CEPT University, Ahmedabad - Net Zero Energy BuildingCEPT University, Ahmedabad - Net Zero Energy Building
CEPT University, Ahmedabad - Net Zero Energy BuildingDanfoss India
 
JW Marriott Mumbai Sahar - Gold Rated Green Building
JW Marriott Mumbai Sahar - Gold Rated Green BuildingJW Marriott Mumbai Sahar - Gold Rated Green Building
JW Marriott Mumbai Sahar - Gold Rated Green BuildingDanfoss India
 
Infosys EC-53 (M & C Building), Bangalore – Making Energy Conservation a Habit
Infosys EC-53 (M & C Building), Bangalore – Making Energy Conservation a HabitInfosys EC-53 (M & C Building), Bangalore – Making Energy Conservation a Habit
Infosys EC-53 (M & C Building), Bangalore – Making Energy Conservation a HabitDanfoss India
 
Turbocor oil-free centrifugal compressors - For air-conditioning systems
Turbocor oil-free centrifugal compressors -  For air-conditioning systemsTurbocor oil-free centrifugal compressors -  For air-conditioning systems
Turbocor oil-free centrifugal compressors - For air-conditioning systemsDanfoss India
 
Compressors for Commercial Air Conditioning
Compressors for Commercial Air ConditioningCompressors for Commercial Air Conditioning
Compressors for Commercial Air ConditioningDanfoss India
 
Refrigeration - An Introduction to the Basics
Refrigeration - An Introduction to the BasicsRefrigeration - An Introduction to the Basics
Refrigeration - An Introduction to the BasicsDanfoss India
 
Products and technologies - For all your application needs, today and tomorrow
Products and technologies - For all your application needs, today and tomorrowProducts and technologies - For all your application needs, today and tomorrow
Products and technologies - For all your application needs, today and tomorrowDanfoss India
 
BD compressor with a.c. and d.c. supply
BD compressor with a.c. and d.c. supplyBD compressor with a.c. and d.c. supply
BD compressor with a.c. and d.c. supplyDanfoss India
 
Facts worth knowing about frequency converters
Facts worth knowing about frequency convertersFacts worth knowing about frequency converters
Facts worth knowing about frequency convertersDanfoss India
 
3rd supply chain leaders forum 2014 case from danfoss power solutions
3rd supply chain leaders forum 2014   case from danfoss power solutions3rd supply chain leaders forum 2014   case from danfoss power solutions
3rd supply chain leaders forum 2014 case from danfoss power solutionsDanfoss India
 
Danfoss burner components
Danfoss burner componentsDanfoss burner components
Danfoss burner componentsDanfoss India
 
Danfoss - Smart Solar Inverter Solutions
Danfoss - Smart Solar Inverter SolutionsDanfoss - Smart Solar Inverter Solutions
Danfoss - Smart Solar Inverter SolutionsDanfoss India
 
Oil management solutions for manifolding scroll compressors - Danfoss
Oil management solutions for manifolding scroll compressors - DanfossOil management solutions for manifolding scroll compressors - Danfoss
Oil management solutions for manifolding scroll compressors - DanfossDanfoss India
 
Danfoss Industrial Refrigerationan - An introduction to the basics
Danfoss Industrial Refrigerationan - An introduction to the basicsDanfoss Industrial Refrigerationan - An introduction to the basics
Danfoss Industrial Refrigerationan - An introduction to the basicsDanfoss India
 
Thermostatic expansion valves
Thermostatic expansion valvesThermostatic expansion valves
Thermostatic expansion valvesDanfoss India
 
Ulx inverter series residential single phase transformer-based
Ulx inverter series residential single phase transformer-basedUlx inverter series residential single phase transformer-based
Ulx inverter series residential single phase transformer-basedDanfoss India
 

More from Danfoss India (20)

IDC – 2, Reliance Corporate Park, Navi Mumbai - Green Campus certified by IGBC
IDC – 2, Reliance Corporate Park, Navi Mumbai - Green Campus certified by IGBCIDC – 2, Reliance Corporate Park, Navi Mumbai - Green Campus certified by IGBC
IDC – 2, Reliance Corporate Park, Navi Mumbai - Green Campus certified by IGBC
 
RBEI, Coimbatore - CII awarded ‘Excellent Energy Efficient Building’
RBEI, Coimbatore - CII awarded ‘Excellent Energy Efficient Building’RBEI, Coimbatore - CII awarded ‘Excellent Energy Efficient Building’
RBEI, Coimbatore - CII awarded ‘Excellent Energy Efficient Building’
 
Ramanujan IT City, Chennai - 100 % recycled water used for cooling tower
Ramanujan IT City, Chennai - 100 % recycled water used for cooling towerRamanujan IT City, Chennai - 100 % recycled water used for cooling tower
Ramanujan IT City, Chennai - 100 % recycled water used for cooling tower
 
CEPT University, Ahmedabad - Net Zero Energy Building
CEPT University, Ahmedabad - Net Zero Energy BuildingCEPT University, Ahmedabad - Net Zero Energy Building
CEPT University, Ahmedabad - Net Zero Energy Building
 
JW Marriott Mumbai Sahar - Gold Rated Green Building
JW Marriott Mumbai Sahar - Gold Rated Green BuildingJW Marriott Mumbai Sahar - Gold Rated Green Building
JW Marriott Mumbai Sahar - Gold Rated Green Building
 
Infosys EC-53 (M & C Building), Bangalore – Making Energy Conservation a Habit
Infosys EC-53 (M & C Building), Bangalore – Making Energy Conservation a HabitInfosys EC-53 (M & C Building), Bangalore – Making Energy Conservation a Habit
Infosys EC-53 (M & C Building), Bangalore – Making Energy Conservation a Habit
 
Turbocor oil-free centrifugal compressors - For air-conditioning systems
Turbocor oil-free centrifugal compressors -  For air-conditioning systemsTurbocor oil-free centrifugal compressors -  For air-conditioning systems
Turbocor oil-free centrifugal compressors - For air-conditioning systems
 
Compressors for Commercial Air Conditioning
Compressors for Commercial Air ConditioningCompressors for Commercial Air Conditioning
Compressors for Commercial Air Conditioning
 
Refrigeration - An Introduction to the Basics
Refrigeration - An Introduction to the BasicsRefrigeration - An Introduction to the Basics
Refrigeration - An Introduction to the Basics
 
Products and technologies - For all your application needs, today and tomorrow
Products and technologies - For all your application needs, today and tomorrowProducts and technologies - For all your application needs, today and tomorrow
Products and technologies - For all your application needs, today and tomorrow
 
Danfoss app-pumps
Danfoss app-pumpsDanfoss app-pumps
Danfoss app-pumps
 
BD compressor with a.c. and d.c. supply
BD compressor with a.c. and d.c. supplyBD compressor with a.c. and d.c. supply
BD compressor with a.c. and d.c. supply
 
Facts worth knowing about frequency converters
Facts worth knowing about frequency convertersFacts worth knowing about frequency converters
Facts worth knowing about frequency converters
 
3rd supply chain leaders forum 2014 case from danfoss power solutions
3rd supply chain leaders forum 2014   case from danfoss power solutions3rd supply chain leaders forum 2014   case from danfoss power solutions
3rd supply chain leaders forum 2014 case from danfoss power solutions
 
Danfoss burner components
Danfoss burner componentsDanfoss burner components
Danfoss burner components
 
Danfoss - Smart Solar Inverter Solutions
Danfoss - Smart Solar Inverter SolutionsDanfoss - Smart Solar Inverter Solutions
Danfoss - Smart Solar Inverter Solutions
 
Oil management solutions for manifolding scroll compressors - Danfoss
Oil management solutions for manifolding scroll compressors - DanfossOil management solutions for manifolding scroll compressors - Danfoss
Oil management solutions for manifolding scroll compressors - Danfoss
 
Danfoss Industrial Refrigerationan - An introduction to the basics
Danfoss Industrial Refrigerationan - An introduction to the basicsDanfoss Industrial Refrigerationan - An introduction to the basics
Danfoss Industrial Refrigerationan - An introduction to the basics
 
Thermostatic expansion valves
Thermostatic expansion valvesThermostatic expansion valves
Thermostatic expansion valves
 
Ulx inverter series residential single phase transformer-based
Ulx inverter series residential single phase transformer-basedUlx inverter series residential single phase transformer-based
Ulx inverter series residential single phase transformer-based
 

Recently uploaded

IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024Mark Billinghurst
 
main PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidmain PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidNikhilNagaraju
 
Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...VICTOR MAESTRE RAMIREZ
 
Risk Assessment For Installation of Drainage Pipes.pdf
Risk Assessment For Installation of Drainage Pipes.pdfRisk Assessment For Installation of Drainage Pipes.pdf
Risk Assessment For Installation of Drainage Pipes.pdfROCENODodongVILLACER
 
Electronically Controlled suspensions system .pdf
Electronically Controlled suspensions system .pdfElectronically Controlled suspensions system .pdf
Electronically Controlled suspensions system .pdfme23b1001
 
Oxy acetylene welding presentation note.
Oxy acetylene welding presentation note.Oxy acetylene welding presentation note.
Oxy acetylene welding presentation note.eptoze12
 
Biology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptxBiology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptxDeepakSakkari2
 
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...srsj9000
 
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ
 
complete construction, environmental and economics information of biomass com...
complete construction, environmental and economics information of biomass com...complete construction, environmental and economics information of biomass com...
complete construction, environmental and economics information of biomass com...asadnawaz62
 
Sachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective IntroductionSachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective IntroductionDr.Costas Sachpazis
 
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube ExchangerStudy on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube ExchangerAnamika Sarkar
 
GDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentationGDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentationGDSCAESB
 
Arduino_CSE ece ppt for working and principal of arduino.ppt
Arduino_CSE ece ppt for working and principal of arduino.pptArduino_CSE ece ppt for working and principal of arduino.ppt
Arduino_CSE ece ppt for working and principal of arduino.pptSAURABHKUMAR892774
 
Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024hassan khalil
 
Application of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptxApplication of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptx959SahilShah
 
Internship report on mechanical engineering
Internship report on mechanical engineeringInternship report on mechanical engineering
Internship report on mechanical engineeringmalavadedarshan25
 

Recently uploaded (20)

IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024
 
main PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidmain PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfid
 
Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...
 
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptxExploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
 
Risk Assessment For Installation of Drainage Pipes.pdf
Risk Assessment For Installation of Drainage Pipes.pdfRisk Assessment For Installation of Drainage Pipes.pdf
Risk Assessment For Installation of Drainage Pipes.pdf
 
Electronically Controlled suspensions system .pdf
Electronically Controlled suspensions system .pdfElectronically Controlled suspensions system .pdf
Electronically Controlled suspensions system .pdf
 
Oxy acetylene welding presentation note.
Oxy acetylene welding presentation note.Oxy acetylene welding presentation note.
Oxy acetylene welding presentation note.
 
Biology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptxBiology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptx
 
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
 
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
 
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
 
complete construction, environmental and economics information of biomass com...
complete construction, environmental and economics information of biomass com...complete construction, environmental and economics information of biomass com...
complete construction, environmental and economics information of biomass com...
 
Sachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective IntroductionSachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
 
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube ExchangerStudy on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
 
GDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentationGDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentation
 
Arduino_CSE ece ppt for working and principal of arduino.ppt
Arduino_CSE ece ppt for working and principal of arduino.pptArduino_CSE ece ppt for working and principal of arduino.ppt
Arduino_CSE ece ppt for working and principal of arduino.ppt
 
Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024
 
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCRCall Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
 
Application of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptxApplication of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptx
 
Internship report on mechanical engineering
Internship report on mechanical engineeringInternship report on mechanical engineering
Internship report on mechanical engineering
 

Pressure switches and thermostats, type CAS

  • 1. Pressure switches and thermostats, type CAS Data sheet Description INDUSTRIAL CONTROLS IC.PD.P10.G1.02 - 520B3138 CAS units are pressure-controlled switches. The position of the contacts depends on the pressure in the inlet connection and the set value. In the series, special attention has been given to meeting demands for • a high level of enclosure • low differential • robust and compact construction • resistance to shock and vibration. Contents Page CAS pressure switches, description.............................................................................................................................1 Approvals.................................................................................................................................................................................2 Ship approvals........................................................................................................................................................................2 Survey........................................................................................................................................................................................2 ISO 9001 quality approval..................................................................................................................................................2 Ordering ...................................................................................................................................................................................3 Terminology............................................................................................................................................................................3 Technical data.........................................................................................................................................................................4 Dimensions and weight......................................................................................................................................................4 Installation...............................................................................................................................................................................5 Function....................................................................................................................................................................................6 Accessories ..............................................................................................................................................................................7 CAS thermostats, description.........................................................................................................................................8 Approvals.................................................................................................................................................................................8 Ship approvals........................................................................................................................................................................8 Technical data and ordering..............................................................................................................................................8 Dimensions and weight......................................................................................................................................................9 Accessories ..............................................................................................................................................................................9 Installation............................................................................................................................................................................ 10 Function................................................................................................................................................................................. 11 Electrical connection ........................................................................................................................................................ 11 Examples ............................................................................................................................................................................... 11 Conversion table................................................................................................................................................................. 12 The CAS series covers most outdoor as well as indoor application requirements. CAS pressure controls are suitable for use in alarm and regulation systems in factories, diesel plant, compressors, power stations and on board ship.
  • 2. 0 - 3.5 CAS 133 0 - 10 CAS 136 0 - 18 CAS 137 10 - 35 CAS 139 1 - 10 CAS 143 4 - 40 CAS 145 6 - 60 CAS 147 0.2 - 2.5 CAS 155 20 - 80 CAS 178 70 - 120 CAS 180 60 - 150 CAS 181 2 IC.PD.P10.G2.02 - 520B2358 Data sheet Pressure switches and thermostats, type CAS ISO 9001 quality approval Danfoss A/S is certificated by BSI in accordance with international standard ISO 9001. This means that Danfoss fulfils the international standard in respect of product development, design, production and sale. BSI exercises continuous inspection to ensure that Danfoss observes the requirements of the standard and that Danfoss’ own quality assurance system is maintained at the required level. Approvals CE-marked acc. to EN 60947-5-1 CCC, China Compulsory Certificate Ship approvals AmericanBureauofShipping,USA(excl.CAS139) Lloyds Register of Shipping, UK Germanischer Lloyd, Germany Bureau Veritas, France Det Norske Veritas, Norway Registro Italiano Navale, Italy RMRS, Maritime Register of Shipping, Russia Nippon Kaiji Kyokai, Japan Survey Pressure switches, type CAS Standard pressure switches Pressure switches for high pressure and strongly pulsating media 0 30 60 90 120 150 °C Range Type °C 0 10 20 30 40 50 60 bar Range Type Pe bar Differential pressure switches Thermostats, type CAS
  • 3. 0 → 3.5 0.1 10 10 40 G ¼ 060-315066 CAS 133 0 → 10 0.2 22 22 40 060-315166 CAS 136 6 → 18 0.3 27 27 72 060-315266 CAS 137 10 → 35 0.6 53 53 100 060-315366 CAS 139 CAS 133, 135, 139 CAS 143, 145, 147 1 → 10 0.2 → 0.6 120 180 240 G ¼ 060-316066 CAS 143 4 → 40 0.8 → 2.4 120 180 240 060-316166 CAS 145 6 → 60 1 → 3 120 180 240 060-316266 CAS 147 CAS 155 0.2 → 2.5 0.1 0 → 8 22 42 2 x G ¼ 060-313066 CAS 155 Data sheet Pressure switches and thermostats, type CAS IC.PD.P10.G2.02 - 520B2358 3 Ordering Preferred version Setting range pe (bar) Mechanical differential (bar) Permissible operating pressure (bar) Max test pressure (bar) Min. burst pressure (bar) Pressure connection Code no. Type Pressure controls for high pressure and strongly pulsating media Setting range pe (bar) Mechanical differential (bar) Permissible operating pressure (bar) Max test pressure (bar) Min. burst pressure (bar) Pressure connection Code no. Type Differential pressure switch type CAS Setting range pe (bar) Mechanical differential (bar) Permissible operating pressure for low pressure (bar) Max test pressure (bar) Min. burst pressure (bar) Pressure connection Code no. Type Max. test pressure The highest pressure the unit may be subjected to when, for example, testing the system for leakage. Therefore, this presure must not occur as a recurring system pressure. Min. burst pressure The pressure which the pressure-sensitive element will withstand without leaking. Range setting The pressure range within which the unit will give a signal (contact changeover). Differential The difference between make pressure and break pressure (see also page 6). Permissible burst pressure The highest permanent or recurring pressure the unit can be loaded with. When ordering, please state type and code no. Standard pressure switches Terminology
  • 4. 4 IC.PD.P10.G2.02 - 520B2358 Data sheet Pressure switches and thermostats, type CAS Switch Microswitch with single pole changeover (SPDT) Contact load Alternating current: 220 V, 0.1 A, AC-14 and AC-15 (inductive load) Direct current: 125 V, 12 W DC-13 (inductive load) Materials in contact with the medium Ambient temperature CAS 133-139: -40 to +70°C CAS 143-155: -25 to +70°C Temperature of medium CAS 133-139: -40 to + 100°C CAS 143-155: -25 to + 100°C For water and seawater, max. 80 °C Vibration resistance Vibration-stable in the range 2-30 Hz amplitude 1.1 mm and 30-100 Hz, 4 G. Enclosure IP 67 acc. to IEC 529 and DIN 40050. The pressure control housing is enamelled pressure die cast aluminium (GD-AISi 12). The cover is fastened by four screws which are anchored to prevent loss. The enclosure can be sealed with fuse wire. Cable entry Pg 13.5 for cable diametrers from 5 to 14 mm. Identification The type designation and code no. of the unit is stamped in the side of the housing. CAS 133 136 137 139 Bellows: Stainless steel, material no. 1.4306 (DIN 17440) Pressure connection: Brass material no. 2.0401 (DIN 17660) CAS 143 145 147 155 Diaphragm connection: Nickel plated brass CuZn 40 Ob3 ISO R 426 (DIN 17569) Diaphragm: Nitrile-butadien rubber Weight: CAS 133-139 approx. 1.0 kg CAS 143-147 approx. 1.3 kg CAS 155 approx. 1.5 kg Technical data Dimensions
  • 5. Data sheet Pressure switches and thermostats, type CAS IC.PD.P10.G2.02 - 520B2358 5 Installation Installation CAS pressure controls are fitted with a 3 mm steel mounting plate. The units should not be allowed to hang from the pressure connection. Pressure connection When fitting or removing pressure lines, the spanner flats on the pressure connection should be used to apply counter-torque. Steam plant To protect the pressure element from excessive heat, the insertion of a water-filled loop is recommended. The loop can, for example, be made of 10 mm copper tube as shown in fig. 1. Pulsations If the pressure medium is superimposed with severe pulsations, which occur in automatic sprinkler systems (fire protection), fuel systems for diesel motors (priming lines), and hydraulic systems (e.g. propeller systems), etc, types case 143, 145, 147 are recommended. The maximum permissible pulsation level for these types is 120 bar. Setting When the pressure control cover is removed, and the locking screw (3) is lossened, the range can be set with the spindle (1) while at the same time the scale (2) is being read. Water systems Water in the pressure element is not harmful, but in case of frost a water-filled pressure element may burst. To prevent this happening, the pressure control can be allowed to operate on an air cushion. Media resistance Se table of materials in contact with the medium, page 4. If seawater is involved, types CAS 143, 145, 147 are recommended. Electrical connection CAS pressure controls are fitted with a PG 13.5 screwed cable entry that is suitable for cable diameters from 5 to 13 mm. Contact function is shown in fig. 3. Fig. 1 1 Range spindle 2 Range scale 3 Locking screw Fig. 2 Fig. 3
  • 6. 6 IC.PD.P10.G2.02 - 520B2358 Data sheet Pressure switches and thermostats, type CAS a. CAS 155 Contacts 1-4 make and contacts 1-2 break when the differential pressure rises above the set range value. The contacts changeover to their initial position when the differential pressure again falls to the range value minus the differential (see fig. 4). Function I. Alarm for rising differential pressure given at the set range value. II. Alarm for falling differential pressure given at the set range value minus the differential. Scale setting Mechanical differential Fig. 4 b. All other CAS pressure controls Contacts 1-2 make and contacts 1-4 break when the pressure falls under the set range value. The contacts changeover to their initial position when the pressure again rises to the set range value plus the differential (see fig. 5). I. Alarm for falling pressure given at the set range value. II. Alarm for rising pressure given at the set range value plus the differential. Example 1: An alarm must be given when the lubrication oil pressure in a motor falls below 0.8 bar. Select CAS 133 (range 0 to 3.5 bar). The minimum permissible lubricating oils pressure of 0.8 bar must be set using the range spindle. The differential is fixed at 0.1 bar, i.e. the alarm will not cut out before the pressure rises to 0.9 bar. The switch break function is normally used for alarm purposes, i.e. the alarm must be connected to terminals 1 and 4. Example 2: When the differential pressure exceeds 1.3 bar a filter must be cleaned. The maximum static pressure (LP) for the CAS 155 of 8 bar must not be exceeded. The pressure control range spindle must be set at 1.3 bar. The alarm must be connected to terminals 1 and 2 (alarm for broken circuit). Scale setting Mechanical differential Fig. 5
  • 7. Data sheet Pressure switches and thermostats, type CAS IC.PD.P10.G2.02 - 520B2358 7 Accessories Part Description Qty. Code no. Connector with nipple Pipe thread ISO 228/1, G 3/8 connector, nipple and AL washer (10 mm ext. 8 mm int. diam) for solering onto steel or copper tubing, steel span of jaws 22 5 017-436866 Connector with nipple G 3/8 connector, nipple and washer (10 mm ext./ 6.5 mm int. diam.) for welding, steel span of jaws 22 1 017-422966 Reducer Pipe thread ISO 228/1, G 3/8 x 7/16 - 20 UNF reducer, washer, brass span of jaws 22 5 017-420566 Adaptor Pipe thread ISO 228/1, G 3/8 x 1/8 - 27 NPT with copper washer brass span of jaws 22 1 060-333466 Adaptor Pipe thread ISO 228/1, G 3/8 A x 1/4 - 18 NPT with copper washer brass span of jaws 22 1 060-333566 Adaptor Pipe thread ISO 228/1, G 3/8 x 1/4 - 18 NPT with copper washer brass span of jaws 22 1 060-333666 Adaptor 7/16 - 20UNF x R 3/8 (ISO 7/1) brass, span of jaws 19 1 060-324066 Nipple G 1/4 A x G 3/8 A 060-333266 G 1/4 A x ext. M10 x 1 with washer 060-333866 Damping coil Pipe thread ISO 228/1, damping coil with G 3/8 connector and 1.5 m copper capillary tube. Standard washers are supplied. 1 060-104766 Armoured damping coil Pipe thread ISO 228/1, damping coil with G 3/8 connector and 1 m copper capillary tube. Standard washers are supplied. 1 060-333366
  • 8. 20 → 80 2.0 130 65 75 110 160 2 060L315166 CAS 178 70 → 120 2.0 220 65 75 110 160 2 060L315366 CAS 180 60 → 150 2.0 250 65 75 110 160 2 060L315566 CAS 181 8 IC.PD.P10.G2.02 - 520B2358 Data sheet Pressure switches and thermostats, type CAS CAS thermostats are temperature-controlled switches. The position of the contacts depends on the temperature of the sensor and the set scale value. In this series, special attention has been given to meeting demands for a high level of enclosure, robust and compact construction, and resistance to shock and vibration. Description The CAS series covers most outdoor as well as indoor application requirements. CAS thermostats are suitable for use in monitoring and alarm systems in factories, diesel plant, compressors, power stations and on board ship. Technical data and ordering CAS with remote sensor, armoured capillary tube Preferred version When ordering, please state type and code number Setting range °C Mechanical differential adjustable / fixed °C Max. sensor temperature °C Suitable sensor length (see also “Accessories”) mm Capillary tube length m Code no. Type Switch Microswitch with single pole changeover (SPDT) Contact load Alternating current: 220 V, ~0,1 A, AC-14 and AC-15 (inductive load) Direct current 125 V, 12W DC-13 (inductive load) Ambient temperature CAS 178,180 and 181: -25°C → +70°C Vibration resistance Vibration-stable in the range 2-30 Hz, amplitude 1,1 mm and 30-100 Hz, 4 G. Enclosure IP 67 acc. to IEC 529 and DIN 40050. The thermostat housing is enamelled pressure die cast aluminium (GD-AISI 12). The cover is fastened by four screws which are anchored to prevent loss. The enclosure can be sealed with fuse wire. Cable entry Pg 13.5 for cable diameters from 5 to 14 mm. Identification The type designation and code no. of the unit is stamped in the side of the housing. Approvals CE marked acc. to EN 60947-5-1 CCC, China Compulsory Certificate Ship approvals American Bureau of Shipping, USA Bureau Veritas, France Det Norske Veritas, Norway Germanischer Lloyd, Germany Lloyd Register of Shipping, UK Nippon Kaiji Kyokai, Japan Registro Italiano Navale, Italy RMRS, Maritime Register of Shipping, Russia
  • 9. Data sheet Pressure switches and thermostats, type CAS IC.PD.P10.G2.02 - 520B2358 9 Accessories: Sensor pockets for thermostats Sensor pocket A mm Thread B Code no. Sensor pocket A mm Thread B Code no. Note: all sensor pockets are supplied without gland nut, gaskets and washes Brass 65 ½ NPT 060L326566 Brass 75 75 75 75 ½ NPT G ½ A G ¾ A G ½ A (ISO 228/1) 060L326466 060L326266 060L326666 060L328166 Steel 18/8 75 G ½ A 060L326766 Brass 110 110 110 110 ½ NPT G ½ A G ½ A (ISO 228/1) G ¾ A (ISO 228/1) 060L328066 060L327166 060L340666 060L340366 Steel 18/8 110 110 G ½ A ½ NPT 060L326866 060L327066 Brass 160 160 G ½ A G ¾ A (ISO 228/1) 060L326366 060L340566 Steel 18/8 160 G ½ A 060L326966 Brass 200 200 200 G ½ A G ½ A (ISO 228/1) G ¾ A (ISO 228/1) 060L320666 060L340866 060L340266 Steel 18/8 200 200 G ½ A G ¾ A 060L323766 060L324866 Brass 250 G ½ A 060L325466 Brass 330 G ½ A 060L325566 Brass 400 G ½ A 060L325666 Other Accessories Description Qty./ unit Code no. Clamping band For CAS thermostats with remote sensor (L = 392 mm) 10 017-420466 Heat conductive compound (Tube with 4.5 cm3 ) For CAS with sensor fitted in a sensor pocket. For filling sensor pocket to improve heat transfer between pocket and sensor. Application range for compound: -20 to +150 °C, momentarily up to 220°C 1 041E0114 Dimensions and weight CAS with remote sensor and 2 m armoured capillary tube Weight: approx. 1.4 kg
  • 10. CAS 178 20 → 80 2.5 CAS 180 70 → 120 2.4 CAS 181 60 → 150 3.7 10 IC.PD.P10.G2.02 - 520B2358 Data sheet Pressure switches and thermostats, type CAS Location of unit: CAS thermostats are designed to withstand the shocks that occur, for example, in ships on compressors and in large machine installations. CAS thermostats are fitted with a base of 3 mm steel plate for fixing to bulkheads, etc. Resistance to media Material specifications for sensor pockets. Sensor pocket brass The tube is made of Ms 72 to DIN 17660, the threaded portion of So Ms 58 Pb to DIN 17661. Sensor pocket, stainless steel 18/8 Material designation 1.4305 to DIN 17440. Sensor position As far as possible the sensor should be positioned so that its longitudinal axis is at right angles to the direction flow. The active part of the sensor is Ø13 mm × 47.5 mm. The medium The fastest reaction is obtained from a medium having high specific heat and high thermal conductivity. It is therefore advantageous to use a medium that fulfils these conditions (provided there is a choice). The flow velocity of the medium is also of significance. (The optimum flow velocity for liquids is about 0.3 m/s). For permissible media pressure see fig. 1. Installation Brass Stainless steel 18/8 Fig. 1 Permissible media pressure on the sensor pocket as a function of temperature Setting When the thermostat cover is removed, and the locking screw (3) fig. 2 is loosened, the range can be set with the spindle (1) while at the same time the scale (2) is being read. Fig. 2 1. Range spindle 2. Range scale 3. Locking screw Relative scale setting in % Type Regulation range °C Correction factor a for thermostats Scale correction The sensor on CAS thermostats contains an adsorption charge. Therefore function is not affected whether the sensor is placed warmer or colder than the remaining part of the thermostatic element (bellows and capillary tube). However, such a charge is to some extent sensitive to changes in the temperature of bellows and capillary tube. Under normal conditions this is of no importance, but if the thermostat is to be used in extreme ambient temperatures there will be a scale deviation. The deviation can be compensated for as follows: Scale correction = Z × a Z can be found from fig. 3, while a is the correction factor from the table below. (See example, page 11). Fig. 3 Factor for scale deviation
  • 11. Data sheet Pressure switches and thermostats, type CAS IC.PD.P10.G2.02 - 520B2358 11 Electrical connection CAS thermostats are fitted with a Pg 13.5 screwed cable entry suitable for cables from 5 to 14 mm. Contact function, see fig. 4. Fig. 4 Function Differentials The mechanical differential is the differential determined by the design of the thermostat. The thermal differential (operating differential) is the differential the system operates on. The thermal differential is always greater than the mechanical differential and depends on three factors: 1) Medium flow velocity 2) Temperature change rate of the medium 3) Heat transmission to the sensor Thermostat function Contacts 1-4 make while contacts 1-2 break when the temperature rises above the scale setting. The contacts changeover to their initial position when the temperature falls to the scale setting minus the differential. See fig. 5. Scale setting Mechanical differential Fig. 5 I. Alarm for rising temperature given at range setting value. II. Alarm for falling temperature given at range setting value minus the differential Example 1 Diesel engine with cooling water temperature of 85°C (normal). An alarm must be triggered if the cooling water temperature exceeds 95°C. Choose a CAS thermostat 180 (range +70 to 120°C). Main spindle setting: 95°C. The required alarm function is obtained by connecting to thermostat terminals 1-4. Example 2 Find the necessary scale correction for a CAS 180. Set +95°C at +50°C ambient temperature. The relative scale setting Z can be calculated from the following formula: Setting value - min. scale value max. scale value - min. scale value x 100 = % Relative scale setting: 95 - 70 x 100 = 50% 120 - 70 Factor for scale deviation Z fig. 3, Z ≅ 0.7 Correction factor a, see table page 10, fig. 3 = 2.4. Scale correction = Z x a = 0.7 x 2.4 = 1.7°C CAS must be set at 95 + 1.7 = 96.7°C
  • 12. ®DanfossA/S10-05/IC-MC/mr Data sheet Pressure switches and thermostats, type CAS 12 IC.PD.P10.G2.02-520B2358 Conversion table Pascal (= Newton per square metre) N/m2 ) PA Pascal per square mm N/mm2 bar Kilopound per square metre (mm H2O) kp/m2 Meter water gauge m H2O Technical atmosphere (kp/cm2 ) at Physical atmosphere atm Torr (0°C) mm Hg Inches Hg (0°C) Poundforce per square inch (lbf/in2 ) psi 1 Pa 1 10-6 10-5 0.1020 1.020 × 10-4 1.020 × 10-5 9.869 × 10-5 7.500 ×10-3 2.953 × 10-4 1.450 × 10-4 1 N/mm2 106 1 10 1.020 × 105 102.0 10.20 9.869 7.5 ×103 295.3 145.0 1 bar 105 0.1 1 10.197 ×103 10.20 1.020 0.9869 750 29.53 14.50 1 kp/m2 9.80665 9.807 × 10-6 9.807 × 10-5 1 10-3 10-4 0.9678 ×10-4 0.07355 2.896 × 10-3 1.422 × 10-3 1 m H2 O 9806.7 9.807 × 103 0.09807 1000 1 0.1 0.09678 73.55 2.896 1.422 1 at 98.066 ×103 0.09807 0.9807 104 10 1 0.9678 735.5 28.96 14.22 1 atm 101.325 ×103 0.1013 1.013 10.333 ×103 10.33 1.033 1 760 29.92 14.70 1 mm Hg 133.32 1.333 × 10-4 1.333 × 10-3 13.60 0.01360 1.360 × 10-3 1.315 × 10-3 1 0.03937 1.934 × 10-2 1 in Hg 3387 3.387 × 10-3 0.03387 345.3 0.3453 0.03453 0.03342 25.4 1 0.4912 1 psi 6895 6.895 × 10-3 0.06895 703.1 0.7031 0.07031 0.96804 51.71 2.036 1