WaterQuality
Managementforthe
PlasticsIndustry
Introduction:
Water is called the “universal solvent” because it
will dissolve to some degree anything that it comes
in contact with. Maintaining good water quality will
ensure clean heat exchangers, corrosion free piping
and equipment surfaces. This will prolong the plant
equipment’s life and maximize a plant’s productivity.
PART I:
A Brief Discussion About Water:
When a glass of water is first poured it appears to be
colourless and, depending on the water source,
clear and free of suspended solids. However,
appearances can be deceiving. Water contains
various concentrations of dissolved minerals, salts,
metals and gases.
Some of the more prevalent naturally occurring
impurities in water may include:
In addition, water may also carry impurities that you
can see. These may include suspended rust (iron
oxide), air-borne matter (silica based), product fines
(such as PVC dust) and microbiological matter (MB).
Microbiological matter is often undetectable to the
eye and unless sterilized, it will be present in all
water. If allowed to grow, it can form slime & algae
masses in any systems which are very visible and
can foul heat exchangers and any small orifices and
water passages in piping or in molds.
Sources of Water:
Excluding salt water, the fresh water sources today
have these characteristics:
1) Run-off Water: These waters originate from
rainwater run-off into streams and lakes and are
usually very soft in hardness and low pH. Run-off
water doesn’t have the contact time to dissolve
mineral scale, and the lack of hardness tends to
make it more corrosive than other waters. Its purity
leads to high cycles of concentrations in cooling
water systems and efficient use of water and
chemicals.
2) Lake Water (Great Lakes and St Lawrence River):
Lake water is a combination of spring-fed, run-off
rain water and water from river sources and result in
water of moderate hardness and alkalinity levels.
This makes for good cycles of concentrations and
good water and chemical use. Softening is not
normally necessary for cooling tower systems with a
proper chemical program, and when not sending
cooling tower water to areas of high temperature.
3) Well Water: Well water is usually very hard and
alkaline. When used as cooling tower make-up
water the cooling system must run with limited
cycles of concentrations resulting in high water and
chemical use the water is treated by softening or pH
modification through the addition of acid.
Basic Terminology:
In order to get a good understanding of chemical
water treatment, it is necessary to define some basic
terminology for water properties and the effects of
Dissolved
Gases
Impurity Anions Cations
Acidity
Alkalinity
Sulphates
Gases
Hardness
Iron
Copper
Lead
Salt
CO³
--, HCO³
-, OH-
SO4
--,
Cl-
H+
Ca++, Mg++
Fe++, Fe+++
Cu++,
Pb++
Na+
O², CO²
−2−
each on the performance of industrial water
systems:
1) pH: A numerical value between 1 and 14 which
represents the chemical balance between acidity
and alkalinity in water. One represents the most
acidic condition, 7 is a neutral water and 14 the most
alkaline. City water sources normally vary in pH
between 6.8 and 8. Great Lakes and St. Lawrence
River water pH levels are 7.5 – 7.8 which makes the
water slightly corrosive and practically non-scaling
under most temperatures.
2) Temperature: Temperatures in these articles are
expressed in degrees Fahrenheit. Temperature is
one of the most important factors affecting the one
of the most common problems in water systems - the
formation of hardness scale. Scale formation (Lime)
preferentially occurs on hot heat exchanger surfac-
es. Higher temperatures will also increase the rate
of corrosion.
3) Scale / Corrosion Index: Scaling and corrosion
exist in a balance that can be affected by pH,
temperature, alkalinity, total suspended solids and
total hardness. A common method of expressing this
balance is in terms of a Langelier Saturation Index
(LSI), a mathematical relationship that applies the
above factors mathematically to generate positive
and negative numbers between +4 and -4 with
negative numbers referring to corrosive waters and
positive numbers referring to scaling waters. For
example St Lawrence and Great Lakes water have a
slightly positive LSI and can easily be treated
chemically in closed systems. When used in cooling
systems the LSI increases as impurities build up.
Chemical management programs normally keep the
LSI below +3 before any problems of scaling occur.
However, if water temperatures rise above 120˚F the
LSI will increase beyond +3 and scaling will occur.
4) Corrosion: Corrosion is a chemical or elec-
tro-chemical degradation process of metal surfaces.
The purer the water, the more corrosive the water
becomes. (more negative on LSI). For example
deionised water is the most corrosive, followed by
reverse osmosis water, softened water, city water,
and finally cooling tower water. In general, corrosion
will decrease as the pH increases and becomes
more alkaline. Iron for example, will show minimal
corrosion at a pH of 8.3 and above in untreated
waters.
5) Impurity Concentration: In this article, the
concentration of impurities is expressed in terms of
parts per million (ppm). Higher concentrations of
impurities in combination with other factors of
temperature, flow, pH and alkalinity will combine to
cause problems of deposition of suspended solids,
microbiological fouling and scale formation
6) Total Hardness: Total hardness is expressed in
terms of ppm of Ca++ and Mg++. Under positive LSI
conditions (high pH, alkalinity, temperature, total
dissolved solids) these cations will combine with
carbonate and bicarbonate alkalinity to form scale
on the hottest heat transfer surfaces on any water
system.
7) Scale Formation: Scale formation occurs in direct
proportion to temperature and will reduce heat
transfer in areas where it is needed most – molds,
high temperature hydraulic oil exchangers, TCU’s
and barrel heat exchangers. Scale formation can be
prevented by limiting the hardness in cooling water
systems to below 400-500 ppm with controlled
bleed-off (unless softening is available), and chemi-
cally with scale inhibitors and dispersants.
8) Suspended Solids: Airborne dirt and dust can be
drawn into a tower and cause problems of deposi-
tion and fouling, especially in heat exchangers.
−3−
Corrosion products and microbiological growth from
the water system can also combine and settle in
areas of low flow. Tower systems concentrate the
city water impurities through evaporation, and
suspended solids levels must be limited by
controlled bleed-off. Filtration, strainers (alarmed for
pressure-loss) and chemical dispersants are used
for controlling suspended solids.
9) Deposition: Deposition is the natural result of
over-concentrating suspended solids and tends to
occur on hot heat transfer surfaces and in areas of
low flow, especially in areas changing flow. Deposi-
tion will reduce both flow and heat transfer. Cooling
tower systems are especially prone to deposition
due to the continuous additions of air-borne particu-
late by the washing of air with cooling tower water.
Deposition of suspended solids can be controlled by
dispersants, bleed off, and filtration.
Types of Industrial Water Systems:
Many types of water systems exist. We will catego-
rize these types as being either open or closed.
1) Open Loop Systems: Dynamic systems that require
a continuous addition of water to make-up for losses
due to evaporation and bleed-off. The best example
is a cooling tower system. Such a system relies on
evaporation for cooling. With evaporation, all impuri-
ties (anions and cations) remain behind and concen-
trate several times. The amount of solids in the water
can be limited by bleeding off the dirty water. Clean
city water is than required to make-up for losses.
For this reason, open systems are contaminated with
much higher concentration of hardness, alkalinity
and suspended solids. Moreover, due to their
contact with air, open systems are prone to MB
growth.
2) Closed Loop Systems: No evaporation occurs and
apart from some controlled water losses when
molds are changed no make-up water is required. In
this case, the chemistry of this water is identical to
city water. Therefore, unlike open systems, impuri-
ties in closed systems will not normally concentrate
unless corrosion is active and adding suspended
iron to the system.
Chemical Water Treatment Techniques:
There are a number of water treatment companies
that provide chemicals and services to organizations
with industrial processes and heating. Generally,
most companies have representatives calling
regularly on plants to test their water, calibrate any
plant testing equipment and provide training. Some
companies provide full service contracts to supply
the chemicals, manage and be responsible for the
chemical feed equipment. Additional services
include laboratory analysis, on-site scale and
corrosion studies & equipment inspection.
Chemical Treatment System provides proportional chemical
feed and bleed-off to make-up.
1) Closed Systems – Chilled and Hot Water Heating
Systems: Closed systems do not have the evapora-
tion process that increases the impurity levels that
are found in open cooling water systems. For this
reason, the LSI in closed water systems will remain
below scaling levels, even under higher tempera-
tures. This is the preferred water system for mold
cooling.
−4−
Chemical treatment of a closed system is normally
required only when the system loses water such as
during mold changes. Once the system is treated,
the chemical corrosion inhibitors should remain
unchanged unless the system loses water. Testing is
therefore only required once every two weeks or
after system water losses such as mold changes. If
required, chemicals can be shot fed directly to
the system either directly in the reservoir or in a
chemical pot feeder.
2) Open Cooling Systems – Cooling Towers: Chemi-
cals are best fed continuously in proportion to
make-up and will vary according to the actual load
on the system. A contact meter, on the city water
make-up, controls the chemical feed of scale and
corrosion inhibitors. As the system works harder,
more water is evaporated; more make-up water is
required which feeds more chemicals.
System bleed-off is a way of de-concentrating dirty
tower water. The amount of bleed-off should also
vary in proportion to the load in system. This will
keep the chemical levels constant in the system.
Conductivity is a measurement of the amount of total
dissolved solids in a system. As the load and evapo-
ration increases, the water becomes saturated with
impurities which will increase the water conductivi-
ty. A probe continuously monitors the conductivity of
the water. As water evaporates the conductivity
rises above a pre-set level and a bleed-off solenoid
valve will open to discharge a controlled amount of
cooling tower water to sewer.
The prevention of MB growth in a cooling system is
handled by biocides. These products are to be
shot-fed to a system for maximum impact and fed on
an alternating basis with the second dissimilar
biocide. Hand feeding is commonly done directly in
tower reservoir. However, many plants now use
timer biocide pump systems to avoid plant personnel
from being in direct contact with the chemicals.
Tests for scale and corrosion, chemical levels,
conductivity, MB counts and daily records of
make-up water readings will ensure good control
over a cooling water treatment. Some plants have
their personnel perform daily tests to react instantly
to problems. Other plants take advantage of full-ser-
vice water treatment packages.
Here are a few important formulae used in Cooling
Tower systems:
Where: E = Rate of evaporation
R.R = Recirculation rate
∆T = Temp rise across the tower
F = Sensible heat loss factor (usually 0.85)
Cycles of concentration =
Bleed-off rate =
Rate of Evaporation
(Cycles of concentration – 1)
Concentration of impurities in cooling tower water
Concentration of impurities in city water
E = 0.001 x R.R x ∆T x F
−5−
Berg Fibreglass Cooling Tower
In general, cycles of concentration in a cooling
tower system for Great Lakes and the St-Lawrence
River are kept around 3.5, assuming the suspended
solids do not exceed 50 ppm. This controlled
approach by bleed-off and chemical treatment
will minimize water use and maximize chemical
efficiency.
Conclusion:
Part II:
Water Quality Management for the
Plastics Industry
Introduction:
Types of Water Sources:
1) Medium Hardness Water – Great Lakes/St. Law-
rence River Water: Water from these sources are
moderately hard, approximately 120 – 140 ppm and
have a pH of 7.6 – 7.8. Corrosion inhibitors are
required for iron and copper, and scale inhibitors are
necessary when used in cooling tower water
systems. Treated water from these sources is ideal
for closed water systems (chilled water) mold
cooling applications and can be heated in extruder
barrels or temperature control units without forming
scale deposits.
This water provides very economical make-up water
for cooling tower systems. When properly treated
cycles of concentrations can run up to 3-4 making it
very practical for cooling water cooled chillers, air
compressors and hydraulic heat exchangers. How-
ever, at 3-4 cycles of concentrations scaling will
occur when in contact with hot heat transfer surfac-
es. This is common in hot extruder screw and barrel
heat exchangers and mold temperature control
units. Chilled water (closed system water) is recom-
mended for these applications.
2) Low Hardness Water – Interior Lakes/Run-off
Water: Hardness levels vary from 30 to 80 ppm, and
pH levels of 7.2 to 7.6 are common. Like medium
hardness water low hardness water is also ideal for
closed water systems when treated with corrosion
inhibitors, and scale formation will not occur when
heated.
In tower water systems low hardness make-up
water allows for up to six cycles of concentrations
making for even more economical use and reduced
chemical costs than medium hardness waters. Low
hardness tower water is less susceptible to scale
formation when heated than medium hardness
water, however chilled water (closed system water)
is recommended for hot extruder screw and barrel
heat exchangers and mold temperature control
units.
3) High Hardness Water – Well Water: Well water is
used when low or medium hardness water is
unavailable. The high hardness makes well water
only appropriate for closed water applications under
the guidance of a water treatment specialist. Some
well waters may also contain corrosive contami-
nants such as high levels of chlorides and sulphates,
both of which can make even chemical treatment
difficult.
Well water can be used as tower water make-up but
only with an aggressive chemical or chemical/soft-
ening programmes. Any well water application
requires regular, daily testing and monitoring of
equipment and chemical levels as per your water
treatment company’s recommendations. Any equip-
No matter what type of chilling system a plant is
equipped with, open or closed, understanding the
water in an industrial system and applying appro-
priate chemical water treatment is absolutely
necessary. Your plant’s productivity and the life of
your equipment depend on it.
−6−
ment breakdown or chemical program upset will
cause rapid scaling in all heat transfer equipment.
The result – costly repairs and expensive downtime.
Glycol Systems:
Glycol is commonly used with water in chillers to
provide freeze protection. The percentage of glycol
depends on the coldest temperature that the glycol
reaches during operation. In a chiller this tempera-
ture is normally the saturated suction temperature in
the evaporator, and normally this temperature is
10°F below the chiller set point temperature.
With this fact in mind, since water freezes at 32°F
we only use glycol when the chiller set point is
below 42°F, or if we are cooling a coil that is
exposed to winter outside air. Some glycol products
contain a corrosion inhibitor however glycol should
not be used only for this purpose. Use corrosion
inhibitors from a chemical company to supplement
the glycol to be certain about preventing corrosion.
Glycol is also a heat retardant rather than being
good at transferring heat. Its presence also adds
viscosity to the cooling fluid requiring higher hp
pumps and higher flow rates to do the same as a
pure water system. Therefore it is only to be used for
freeze protection.
There are generally two glycols that are used –
propylene glycol, a food-grade and non-toxic glycol
and ethylene glycol which although is toxic to
humans and requires special handling and spill
containment practices, is much less expensive and
therefore more commonly used.
Glycol at concentrations above 1-2% is toxic to
bacteria. At low concentrations (0.1-1%) glycol is a
nutrient for bacteria, and the by-product of the
bacterial process is very acidic. Therefore, anytime
you drain a glycol system you must do a thorough
system flushing and immediately treat with a corro-
sion inhibitor. In some cases a chemical cleaning is
a necessary part of the flushing to ensure that you
have completely removed all traces of glycol. Please
consult your water treatment company.
Water Quality And System Design:
For most types of plastics the molds require cool
water temperatures to minimize part cycle times and
maximize productivity. Since the required tempera-
tures for these molds cannot be reliably maintained
with cooling towers during warm weather, and since
the mold passages are small and easily fouled most
plastics plants dedicate a chiller to the molds and
plastic processing sections of extruders and use
tower water for the shell and tube heat exchangers
for hydraulic cooling, chiller condensers, air com-
pressors, extruder feed throats and gear boxes. The
exchangers in this equipment are usually shell and
tube that are easily acid washed if cleaning is
necessary. The spaces between the tubes are more
forgiving to fouling than the small 1/16" spaces found
in plate and frame exchangers and in small mold
passages.
Double Y Strainer for large particle filtration provides protec-
tion to water circulation equipment against plugged strainers
and filters with no downtime.
Smart plant water system design uses mechanical
(chiller) cooling only as needed, and maximizes the
−7−
energy savings found when using water cooled
equipment whenever possible. Tower water (ambi-
ent) cooling costs a fraction of the operating
expense of a chiller, and a fraction of the equipment
capital cost on a $ per ton basis. For this reason
many plants select water-cooled chillers, air
compressors and air dryers to put onto a cooling
tower and dedicate a chiller for only cool water
applications.
There are other cases where tower water is a good
choice for temperature control units, barrel and
screw cooling. The required temperature set points
for these may be between 140 - 180°F and as we
discussed in the previous article the high
concentration of calcium in the tower water will
cause scale formation where tower water directly
contacts the heaters and hot heat exchange
surfaces. Precipitated scale will also migrate
downstream to foul molds and other process
equipment.
Stainless Steel Fine Particle Strainer with Auto-Flush captures
sediment in the clean process water.
If your plant has medium hard make-up plant water,
or if only very clean water can be tolerated in your
molds and processing equipment, and your
exchangers can be adequately cooled with tower
water there are solutions available if you do not have
a spare chiller available.
1) Softening: Softening uses a sodium zeolite resin
that can be regenerated by brine to remove all
calcium hardness from the make-up water. This will
eliminate any hardness scale formation when the
tower water contacts hot heat transfer surfaces,
however the softened water changes its balance
from being scaling water to corrosive water. The
solution is to install a small valved by-pass around
the softener and maintain just enough hardness in
the water (approximately 80-100 ppm) to remove the
corrosiveness and low enough in concentration to
not precipitate when heated. This is a relatively low
cost solution however be cautioned that thorough
monitoring by the plant on a daily basis must be
performed in order to correct any softener upsets,
maintain the salt brine tank and balance the blend
between the hard, by-pass make-up water with the
100% softened make-up water. Failure at any time
can result in totally scaling up your system.
2) Clean Water Tower Systems: Safe, reliable and
worry-free plant operation can be assured by
converting your tower system to a Clean Water
Tower System. Here an efficient plate and frame
exchanger is installed in the tower system with
standard 85°F/95°F water providing the cooling on
one side of the exchanger and a closed loop
process water system operates on the other side.
The process equipment sees a minor increase in
temperature (most exchangers can be sized to a 3 -
5°F difference between the inlet tower water
temperature and the outlet process water tempera-
ture), and the cooling water system becomes a
standard closed loop system that can tolerate high
hardness without scaling.
The difference between this water and tower
water from the same source is that there will be
no make-up to replenish the scaling process, the
hardness level is a fraction of the tower water
hardness, there is no contact with the air so there is
−8−
none of the particulate present to cause fouling or
deposition, and the water treatment is a simple, add
as required process assuming that the system stays
tight (apart from periodic mold changes). A large
system with two separate tanks is shown below.
Tank baffles are not required but were added in this
application to provide extra strength to the two large
tanks.
In small applications less than 150 tons the two tanks
can be brought together with only three pumps
necessary (one process pump, one tower pump and
one standby pump). In other cases, if the tower tank
is large enough, or if it can be modified a heat
exchanger can be added to the tankset and the
baffled tower tank can be converted to two separate
tanks with a full baffle from the bottom to the top of
the tank. Some additional valves and piping changes
then can retain the operation of a standby pump and
use the two tanks to create a Clean Water Tower
Tankset.
3) Other Solutions: Reverse osmosis, deionized water
processes and other forms of water conditioning can
remove hardness and other unwanted contaminants.
There is usually a high cost to buy, install, and
operate this equipment. Some of you may also
encounter the non-chemical devices that claim to
eliminate all chemical treatment, remove existing
Berg Clean Water Tower System ensures safe, reliable, worry-free operation.
−9−
Berg System Manager
with Touch Panel
Double Y-Strainer
Stainless Steel Tanks
1”Drain
Plate Heat Exchanger
Overflow Valve
Fine Particle Strainer
with Auto-Flush
Make Up Valve
Chemical Treatment
System
Berg Cooling Tower Pump Tank System
scale, and run without the need to do daily plant
tests. Many come with testimonials and references
that are hard to trace, and may sound very convinc-
ing. It has been the author’s experience that when
things sound too good to be true they probably are,
and we urge caution and consultation before you
decide to try.
Conclusion:
Prepared by: Mike Sinclair, B. Sc.
Berg Chilling Systems Inc.
Berg Chilling Systems Inc., 51 Nantucket Blvd., Toronto, Ontario, Canada M1P2N5 • 416-755-2221 www.berg-group.com
We hope that this paper provides a basic
understanding of water quality management.
We cannot understate the importance of working
together with a reputable and high quality water
treatment company representative to enable you
to achieve your goal of maximum productivity,
long equipment life and efficient plant equipment
operating expense.

More Related Content

What's hot

Cooling Towers-Open recirculating-summary
Cooling Towers-Open recirculating-summaryCooling Towers-Open recirculating-summary
Cooling Towers-Open recirculating-summaryChandran Udumbasseri
 
New Techniques of wastewater Management
New Techniques  of wastewater ManagementNew Techniques  of wastewater Management
New Techniques of wastewater ManagementPrashant Ojha
 
97377 performance of a new mill supply treatment p
97377 performance of a new mill supply treatment p97377 performance of a new mill supply treatment p
97377 performance of a new mill supply treatment pGustavo Jaime
 
Seminar cooling tower
Seminar cooling towerSeminar cooling tower
Seminar cooling towerRyan Kumpula
 
Power plant chemistry external water treatment
Power plant chemistry external water treatmentPower plant chemistry external water treatment
Power plant chemistry external water treatmentumar farooq
 
Final Journal Report rev5
Final Journal Report rev5Final Journal Report rev5
Final Journal Report rev5Brendan Meehan
 
Ammonia Recovery using membrane distillation
Ammonia Recovery using membrane distillationAmmonia Recovery using membrane distillation
Ammonia Recovery using membrane distillationChristos Charisiadis
 
Electrocoagulation Process Option 4
Electrocoagulation Process Option 4Electrocoagulation Process Option 4
Electrocoagulation Process Option 4Judd Sundine
 
The IWOX®systems
The IWOX®systemsThe IWOX®systems
The IWOX®systemsJoost Edens
 
Gulation settling of natural organic matter from soft tropical water
Gulation settling of natural organic matter from soft tropical waterGulation settling of natural organic matter from soft tropical water
Gulation settling of natural organic matter from soft tropical waterIAEME Publication
 
Temperature Sensitive Material for the Desiccant Dehumidification System
Temperature Sensitive Material for the Desiccant Dehumidification SystemTemperature Sensitive Material for the Desiccant Dehumidification System
Temperature Sensitive Material for the Desiccant Dehumidification SystemKenneth Huang
 
Power plant chemistry by ramesh
Power plant chemistry by rameshPower plant chemistry by ramesh
Power plant chemistry by rameshKomma Ramesh
 

What's hot (20)

Basic water ocr
Basic water ocrBasic water ocr
Basic water ocr
 
Cooling Towers-Open recirculating-summary
Cooling Towers-Open recirculating-summaryCooling Towers-Open recirculating-summary
Cooling Towers-Open recirculating-summary
 
Cooling Water Treatment
Cooling Water TreatmentCooling Water Treatment
Cooling Water Treatment
 
Legionella Paper
Legionella PaperLegionella Paper
Legionella Paper
 
New Techniques of wastewater Management
New Techniques  of wastewater ManagementNew Techniques  of wastewater Management
New Techniques of wastewater Management
 
Boiler water testing
Boiler water testingBoiler water testing
Boiler water testing
 
97377 performance of a new mill supply treatment p
97377 performance of a new mill supply treatment p97377 performance of a new mill supply treatment p
97377 performance of a new mill supply treatment p
 
Seminar cooling tower
Seminar cooling towerSeminar cooling tower
Seminar cooling tower
 
Power plant chemistry external water treatment
Power plant chemistry external water treatmentPower plant chemistry external water treatment
Power plant chemistry external water treatment
 
Final Journal Report rev5
Final Journal Report rev5Final Journal Report rev5
Final Journal Report rev5
 
Ammonia Recovery using membrane distillation
Ammonia Recovery using membrane distillationAmmonia Recovery using membrane distillation
Ammonia Recovery using membrane distillation
 
Feed Water Treatment
Feed Water TreatmentFeed Water Treatment
Feed Water Treatment
 
Electrocoagulation Process Option 4
Electrocoagulation Process Option 4Electrocoagulation Process Option 4
Electrocoagulation Process Option 4
 
Dialysate
DialysateDialysate
Dialysate
 
Presentation of Berezutskyi 1
Presentation of Berezutskyi 1Presentation of Berezutskyi 1
Presentation of Berezutskyi 1
 
The IWOX®systems
The IWOX®systemsThe IWOX®systems
The IWOX®systems
 
Gulation settling of natural organic matter from soft tropical water
Gulation settling of natural organic matter from soft tropical waterGulation settling of natural organic matter from soft tropical water
Gulation settling of natural organic matter from soft tropical water
 
Temperature Sensitive Material for the Desiccant Dehumidification System
Temperature Sensitive Material for the Desiccant Dehumidification SystemTemperature Sensitive Material for the Desiccant Dehumidification System
Temperature Sensitive Material for the Desiccant Dehumidification System
 
Power plant chemistry by ramesh
Power plant chemistry by rameshPower plant chemistry by ramesh
Power plant chemistry by ramesh
 
Water Quality Index
Water Quality IndexWater Quality Index
Water Quality Index
 

Viewers also liked

Speedlancer Design Portfolio - 2015
Speedlancer Design Portfolio - 2015Speedlancer Design Portfolio - 2015
Speedlancer Design Portfolio - 2015speedlancer
 
Flare Gas Recovery Innovations for Wellhead Gas Emissions
Flare Gas Recovery Innovations for Wellhead Gas EmissionsFlare Gas Recovery Innovations for Wellhead Gas Emissions
Flare Gas Recovery Innovations for Wellhead Gas EmissionsBerg Chilling Systems Inc.
 
Schneider electrics building_business_presentation
Schneider electrics building_business_presentationSchneider electrics building_business_presentation
Schneider electrics building_business_presentationbenrodca
 
Water Quality Management | Berg Chilling Systems - Part 2
Water Quality Management | Berg Chilling Systems - Part 2Water Quality Management | Berg Chilling Systems - Part 2
Water Quality Management | Berg Chilling Systems - Part 2Berg Chilling Systems Inc.
 
Berg and gtuit system - Reduce Oil and Gas Flaring | berg chilling systems 2
Berg and gtuit system - Reduce Oil and Gas Flaring | berg chilling systems 2Berg and gtuit system - Reduce Oil and Gas Flaring | berg chilling systems 2
Berg and gtuit system - Reduce Oil and Gas Flaring | berg chilling systems 2Berg Chilling Systems Inc.
 

Viewers also liked (8)

Speedlancer Design Portfolio - 2015
Speedlancer Design Portfolio - 2015Speedlancer Design Portfolio - 2015
Speedlancer Design Portfolio - 2015
 
Flare Gas Recovery Innovations for Wellhead Gas Emissions
Flare Gas Recovery Innovations for Wellhead Gas EmissionsFlare Gas Recovery Innovations for Wellhead Gas Emissions
Flare Gas Recovery Innovations for Wellhead Gas Emissions
 
RelazioneENG
RelazioneENGRelazioneENG
RelazioneENG
 
Tsx (1)
Tsx (1)Tsx (1)
Tsx (1)
 
Schneider electrics building_business_presentation
Schneider electrics building_business_presentationSchneider electrics building_business_presentation
Schneider electrics building_business_presentation
 
Water Quality Management | Berg Chilling Systems - Part 2
Water Quality Management | Berg Chilling Systems - Part 2Water Quality Management | Berg Chilling Systems - Part 2
Water Quality Management | Berg Chilling Systems - Part 2
 
Berg and gtuit system - Reduce Oil and Gas Flaring | berg chilling systems 2
Berg and gtuit system - Reduce Oil and Gas Flaring | berg chilling systems 2Berg and gtuit system - Reduce Oil and Gas Flaring | berg chilling systems 2
Berg and gtuit system - Reduce Oil and Gas Flaring | berg chilling systems 2
 
Berg Shell Ice Maker
Berg Shell Ice MakerBerg Shell Ice Maker
Berg Shell Ice Maker
 

Similar to Water Quality Management For the Plastics Industry

Cooling water problems and solutions
Cooling water problems and solutionsCooling water problems and solutions
Cooling water problems and solutionsKimia Store
 
Water treatment,Water Treatment & Basic Steam Distribution
Water treatment,Water Treatment&Basic Steam DistributionWater treatment,Water Treatment&Basic Steam Distribution
Water treatment,Water Treatment & Basic Steam DistributionBSMRSTU
 
Water Management in Thermal Power Plants .pdf
Water Management in Thermal Power Plants .pdfWater Management in Thermal Power Plants .pdf
Water Management in Thermal Power Plants .pdfeldoctol
 
Cooling tower water treament research_rev2
Cooling tower water treament research_rev2Cooling tower water treament research_rev2
Cooling tower water treament research_rev2Ryan Barber
 
Water Analysis.pdf
Water Analysis.pdfWater Analysis.pdf
Water Analysis.pdfDr.Timy Jose
 
Fouling effects on boiler
Fouling effects on boilerFouling effects on boiler
Fouling effects on boilerMaharshi Soni
 
Engineering plant facilities 06 mechanics water
Engineering plant facilities 06 mechanics waterEngineering plant facilities 06 mechanics water
Engineering plant facilities 06 mechanics waterLuis Cabrera
 
Desalination plant
Desalination plantDesalination plant
Desalination plantLincy Jancy
 
Water treatment and quality control of dialysate.
Water treatment and quality control of dialysate.Water treatment and quality control of dialysate.
Water treatment and quality control of dialysate.Vishal Golay
 
presentation1kalisindhjhalawar-140821080222-phpapp02.pdf
presentation1kalisindhjhalawar-140821080222-phpapp02.pdfpresentation1kalisindhjhalawar-140821080222-phpapp02.pdf
presentation1kalisindhjhalawar-140821080222-phpapp02.pdfJasaRChoudhary
 
Presentation1 kalisindh jhalawar
Presentation1 kalisindh jhalawarPresentation1 kalisindh jhalawar
Presentation1 kalisindh jhalawarMAHENDRA MEENA
 
The Fundamentals of Water Treatment Technology.pdf
The Fundamentals of Water Treatment Technology.pdfThe Fundamentals of Water Treatment Technology.pdf
The Fundamentals of Water Treatment Technology.pdfssuserb81ee9
 
Introducing nereus for evaporative condensers
Introducing nereus for evaporative condensersIntroducing nereus for evaporative condensers
Introducing nereus for evaporative condensersdamiendasher
 
seawater desalination technology FAQ
seawater desalination technology FAQseawater desalination technology FAQ
seawater desalination technology FAQShiny Zhang
 
Akvo - miscellaneous water systems
Akvo - miscellaneous water systemsAkvo - miscellaneous water systems
Akvo - miscellaneous water systemsMatt Tudge
 
Produced Water | Session X - Steve Jester
Produced Water | Session X - Steve JesterProduced Water | Session X - Steve Jester
Produced Water | Session X - Steve Jesteratlanticcouncil
 
WATER TREATMENT COURSE.pdf
WATER TREATMENT COURSE.pdfWATER TREATMENT COURSE.pdf
WATER TREATMENT COURSE.pdfeldoctol
 
Water Treatment course .pdf
Water Treatment course .pdfWater Treatment course .pdf
Water Treatment course .pdfhepil96495
 

Similar to Water Quality Management For the Plastics Industry (20)

Cooling water problems and solutions
Cooling water problems and solutionsCooling water problems and solutions
Cooling water problems and solutions
 
Water treatment,Water Treatment & Basic Steam Distribution
Water treatment,Water Treatment&Basic Steam DistributionWater treatment,Water Treatment&Basic Steam Distribution
Water treatment,Water Treatment & Basic Steam Distribution
 
Water Management in Thermal Power Plants .pdf
Water Management in Thermal Power Plants .pdfWater Management in Thermal Power Plants .pdf
Water Management in Thermal Power Plants .pdf
 
Waste management system
Waste management systemWaste management system
Waste management system
 
Cooling tower water treament research_rev2
Cooling tower water treament research_rev2Cooling tower water treament research_rev2
Cooling tower water treament research_rev2
 
Feed water treatment
Feed water treatmentFeed water treatment
Feed water treatment
 
Water Analysis.pdf
Water Analysis.pdfWater Analysis.pdf
Water Analysis.pdf
 
Fouling effects on boiler
Fouling effects on boilerFouling effects on boiler
Fouling effects on boiler
 
Engineering plant facilities 06 mechanics water
Engineering plant facilities 06 mechanics waterEngineering plant facilities 06 mechanics water
Engineering plant facilities 06 mechanics water
 
Desalination plant
Desalination plantDesalination plant
Desalination plant
 
Water treatment and quality control of dialysate.
Water treatment and quality control of dialysate.Water treatment and quality control of dialysate.
Water treatment and quality control of dialysate.
 
presentation1kalisindhjhalawar-140821080222-phpapp02.pdf
presentation1kalisindhjhalawar-140821080222-phpapp02.pdfpresentation1kalisindhjhalawar-140821080222-phpapp02.pdf
presentation1kalisindhjhalawar-140821080222-phpapp02.pdf
 
Presentation1 kalisindh jhalawar
Presentation1 kalisindh jhalawarPresentation1 kalisindh jhalawar
Presentation1 kalisindh jhalawar
 
The Fundamentals of Water Treatment Technology.pdf
The Fundamentals of Water Treatment Technology.pdfThe Fundamentals of Water Treatment Technology.pdf
The Fundamentals of Water Treatment Technology.pdf
 
Introducing nereus for evaporative condensers
Introducing nereus for evaporative condensersIntroducing nereus for evaporative condensers
Introducing nereus for evaporative condensers
 
seawater desalination technology FAQ
seawater desalination technology FAQseawater desalination technology FAQ
seawater desalination technology FAQ
 
Akvo - miscellaneous water systems
Akvo - miscellaneous water systemsAkvo - miscellaneous water systems
Akvo - miscellaneous water systems
 
Produced Water | Session X - Steve Jester
Produced Water | Session X - Steve JesterProduced Water | Session X - Steve Jester
Produced Water | Session X - Steve Jester
 
WATER TREATMENT COURSE.pdf
WATER TREATMENT COURSE.pdfWATER TREATMENT COURSE.pdf
WATER TREATMENT COURSE.pdf
 
Water Treatment course .pdf
Water Treatment course .pdfWater Treatment course .pdf
Water Treatment course .pdf
 

Recently uploaded

(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordAsst.prof M.Gokilavani
 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Dr.Costas Sachpazis
 
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...RajaP95
 
Introduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxIntroduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxupamatechverse
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escortsranjana rawat
 
UNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular ConduitsUNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular Conduitsrknatarajan
 
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)Suman Mia
 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations120cr0395
 
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).pptssuser5c9d4b1
 
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...ranjana rawat
 
SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )Tsuyoshi Horigome
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxAsutosh Ranjan
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130Suhani Kapoor
 
UNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its PerformanceUNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its Performancesivaprakash250
 
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSKurinjimalarL3
 

Recently uploaded (20)

(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
 
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...
 
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
 
Introduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxIntroduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptx
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
 
Roadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and RoutesRoadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and Routes
 
UNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular ConduitsUNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular Conduits
 
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
 
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations
 
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
 
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
 
SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptx
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
 
UNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its PerformanceUNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its Performance
 
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
 

Water Quality Management For the Plastics Industry

  • 2. Introduction: Water is called the “universal solvent” because it will dissolve to some degree anything that it comes in contact with. Maintaining good water quality will ensure clean heat exchangers, corrosion free piping and equipment surfaces. This will prolong the plant equipment’s life and maximize a plant’s productivity. PART I: A Brief Discussion About Water: When a glass of water is first poured it appears to be colourless and, depending on the water source, clear and free of suspended solids. However, appearances can be deceiving. Water contains various concentrations of dissolved minerals, salts, metals and gases. Some of the more prevalent naturally occurring impurities in water may include: In addition, water may also carry impurities that you can see. These may include suspended rust (iron oxide), air-borne matter (silica based), product fines (such as PVC dust) and microbiological matter (MB). Microbiological matter is often undetectable to the eye and unless sterilized, it will be present in all water. If allowed to grow, it can form slime & algae masses in any systems which are very visible and can foul heat exchangers and any small orifices and water passages in piping or in molds. Sources of Water: Excluding salt water, the fresh water sources today have these characteristics: 1) Run-off Water: These waters originate from rainwater run-off into streams and lakes and are usually very soft in hardness and low pH. Run-off water doesn’t have the contact time to dissolve mineral scale, and the lack of hardness tends to make it more corrosive than other waters. Its purity leads to high cycles of concentrations in cooling water systems and efficient use of water and chemicals. 2) Lake Water (Great Lakes and St Lawrence River): Lake water is a combination of spring-fed, run-off rain water and water from river sources and result in water of moderate hardness and alkalinity levels. This makes for good cycles of concentrations and good water and chemical use. Softening is not normally necessary for cooling tower systems with a proper chemical program, and when not sending cooling tower water to areas of high temperature. 3) Well Water: Well water is usually very hard and alkaline. When used as cooling tower make-up water the cooling system must run with limited cycles of concentrations resulting in high water and chemical use the water is treated by softening or pH modification through the addition of acid. Basic Terminology: In order to get a good understanding of chemical water treatment, it is necessary to define some basic terminology for water properties and the effects of Dissolved Gases Impurity Anions Cations Acidity Alkalinity Sulphates Gases Hardness Iron Copper Lead Salt CO³ --, HCO³ -, OH- SO4 --, Cl- H+ Ca++, Mg++ Fe++, Fe+++ Cu++, Pb++ Na+ O², CO² −2−
  • 3. each on the performance of industrial water systems: 1) pH: A numerical value between 1 and 14 which represents the chemical balance between acidity and alkalinity in water. One represents the most acidic condition, 7 is a neutral water and 14 the most alkaline. City water sources normally vary in pH between 6.8 and 8. Great Lakes and St. Lawrence River water pH levels are 7.5 – 7.8 which makes the water slightly corrosive and practically non-scaling under most temperatures. 2) Temperature: Temperatures in these articles are expressed in degrees Fahrenheit. Temperature is one of the most important factors affecting the one of the most common problems in water systems - the formation of hardness scale. Scale formation (Lime) preferentially occurs on hot heat exchanger surfac- es. Higher temperatures will also increase the rate of corrosion. 3) Scale / Corrosion Index: Scaling and corrosion exist in a balance that can be affected by pH, temperature, alkalinity, total suspended solids and total hardness. A common method of expressing this balance is in terms of a Langelier Saturation Index (LSI), a mathematical relationship that applies the above factors mathematically to generate positive and negative numbers between +4 and -4 with negative numbers referring to corrosive waters and positive numbers referring to scaling waters. For example St Lawrence and Great Lakes water have a slightly positive LSI and can easily be treated chemically in closed systems. When used in cooling systems the LSI increases as impurities build up. Chemical management programs normally keep the LSI below +3 before any problems of scaling occur. However, if water temperatures rise above 120˚F the LSI will increase beyond +3 and scaling will occur. 4) Corrosion: Corrosion is a chemical or elec- tro-chemical degradation process of metal surfaces. The purer the water, the more corrosive the water becomes. (more negative on LSI). For example deionised water is the most corrosive, followed by reverse osmosis water, softened water, city water, and finally cooling tower water. In general, corrosion will decrease as the pH increases and becomes more alkaline. Iron for example, will show minimal corrosion at a pH of 8.3 and above in untreated waters. 5) Impurity Concentration: In this article, the concentration of impurities is expressed in terms of parts per million (ppm). Higher concentrations of impurities in combination with other factors of temperature, flow, pH and alkalinity will combine to cause problems of deposition of suspended solids, microbiological fouling and scale formation 6) Total Hardness: Total hardness is expressed in terms of ppm of Ca++ and Mg++. Under positive LSI conditions (high pH, alkalinity, temperature, total dissolved solids) these cations will combine with carbonate and bicarbonate alkalinity to form scale on the hottest heat transfer surfaces on any water system. 7) Scale Formation: Scale formation occurs in direct proportion to temperature and will reduce heat transfer in areas where it is needed most – molds, high temperature hydraulic oil exchangers, TCU’s and barrel heat exchangers. Scale formation can be prevented by limiting the hardness in cooling water systems to below 400-500 ppm with controlled bleed-off (unless softening is available), and chemi- cally with scale inhibitors and dispersants. 8) Suspended Solids: Airborne dirt and dust can be drawn into a tower and cause problems of deposi- tion and fouling, especially in heat exchangers. −3−
  • 4. Corrosion products and microbiological growth from the water system can also combine and settle in areas of low flow. Tower systems concentrate the city water impurities through evaporation, and suspended solids levels must be limited by controlled bleed-off. Filtration, strainers (alarmed for pressure-loss) and chemical dispersants are used for controlling suspended solids. 9) Deposition: Deposition is the natural result of over-concentrating suspended solids and tends to occur on hot heat transfer surfaces and in areas of low flow, especially in areas changing flow. Deposi- tion will reduce both flow and heat transfer. Cooling tower systems are especially prone to deposition due to the continuous additions of air-borne particu- late by the washing of air with cooling tower water. Deposition of suspended solids can be controlled by dispersants, bleed off, and filtration. Types of Industrial Water Systems: Many types of water systems exist. We will catego- rize these types as being either open or closed. 1) Open Loop Systems: Dynamic systems that require a continuous addition of water to make-up for losses due to evaporation and bleed-off. The best example is a cooling tower system. Such a system relies on evaporation for cooling. With evaporation, all impuri- ties (anions and cations) remain behind and concen- trate several times. The amount of solids in the water can be limited by bleeding off the dirty water. Clean city water is than required to make-up for losses. For this reason, open systems are contaminated with much higher concentration of hardness, alkalinity and suspended solids. Moreover, due to their contact with air, open systems are prone to MB growth. 2) Closed Loop Systems: No evaporation occurs and apart from some controlled water losses when molds are changed no make-up water is required. In this case, the chemistry of this water is identical to city water. Therefore, unlike open systems, impuri- ties in closed systems will not normally concentrate unless corrosion is active and adding suspended iron to the system. Chemical Water Treatment Techniques: There are a number of water treatment companies that provide chemicals and services to organizations with industrial processes and heating. Generally, most companies have representatives calling regularly on plants to test their water, calibrate any plant testing equipment and provide training. Some companies provide full service contracts to supply the chemicals, manage and be responsible for the chemical feed equipment. Additional services include laboratory analysis, on-site scale and corrosion studies & equipment inspection. Chemical Treatment System provides proportional chemical feed and bleed-off to make-up. 1) Closed Systems – Chilled and Hot Water Heating Systems: Closed systems do not have the evapora- tion process that increases the impurity levels that are found in open cooling water systems. For this reason, the LSI in closed water systems will remain below scaling levels, even under higher tempera- tures. This is the preferred water system for mold cooling. −4−
  • 5. Chemical treatment of a closed system is normally required only when the system loses water such as during mold changes. Once the system is treated, the chemical corrosion inhibitors should remain unchanged unless the system loses water. Testing is therefore only required once every two weeks or after system water losses such as mold changes. If required, chemicals can be shot fed directly to the system either directly in the reservoir or in a chemical pot feeder. 2) Open Cooling Systems – Cooling Towers: Chemi- cals are best fed continuously in proportion to make-up and will vary according to the actual load on the system. A contact meter, on the city water make-up, controls the chemical feed of scale and corrosion inhibitors. As the system works harder, more water is evaporated; more make-up water is required which feeds more chemicals. System bleed-off is a way of de-concentrating dirty tower water. The amount of bleed-off should also vary in proportion to the load in system. This will keep the chemical levels constant in the system. Conductivity is a measurement of the amount of total dissolved solids in a system. As the load and evapo- ration increases, the water becomes saturated with impurities which will increase the water conductivi- ty. A probe continuously monitors the conductivity of the water. As water evaporates the conductivity rises above a pre-set level and a bleed-off solenoid valve will open to discharge a controlled amount of cooling tower water to sewer. The prevention of MB growth in a cooling system is handled by biocides. These products are to be shot-fed to a system for maximum impact and fed on an alternating basis with the second dissimilar biocide. Hand feeding is commonly done directly in tower reservoir. However, many plants now use timer biocide pump systems to avoid plant personnel from being in direct contact with the chemicals. Tests for scale and corrosion, chemical levels, conductivity, MB counts and daily records of make-up water readings will ensure good control over a cooling water treatment. Some plants have their personnel perform daily tests to react instantly to problems. Other plants take advantage of full-ser- vice water treatment packages. Here are a few important formulae used in Cooling Tower systems: Where: E = Rate of evaporation R.R = Recirculation rate ∆T = Temp rise across the tower F = Sensible heat loss factor (usually 0.85) Cycles of concentration = Bleed-off rate = Rate of Evaporation (Cycles of concentration – 1) Concentration of impurities in cooling tower water Concentration of impurities in city water E = 0.001 x R.R x ∆T x F −5− Berg Fibreglass Cooling Tower
  • 6. In general, cycles of concentration in a cooling tower system for Great Lakes and the St-Lawrence River are kept around 3.5, assuming the suspended solids do not exceed 50 ppm. This controlled approach by bleed-off and chemical treatment will minimize water use and maximize chemical efficiency. Conclusion: Part II: Water Quality Management for the Plastics Industry Introduction: Types of Water Sources: 1) Medium Hardness Water – Great Lakes/St. Law- rence River Water: Water from these sources are moderately hard, approximately 120 – 140 ppm and have a pH of 7.6 – 7.8. Corrosion inhibitors are required for iron and copper, and scale inhibitors are necessary when used in cooling tower water systems. Treated water from these sources is ideal for closed water systems (chilled water) mold cooling applications and can be heated in extruder barrels or temperature control units without forming scale deposits. This water provides very economical make-up water for cooling tower systems. When properly treated cycles of concentrations can run up to 3-4 making it very practical for cooling water cooled chillers, air compressors and hydraulic heat exchangers. How- ever, at 3-4 cycles of concentrations scaling will occur when in contact with hot heat transfer surfac- es. This is common in hot extruder screw and barrel heat exchangers and mold temperature control units. Chilled water (closed system water) is recom- mended for these applications. 2) Low Hardness Water – Interior Lakes/Run-off Water: Hardness levels vary from 30 to 80 ppm, and pH levels of 7.2 to 7.6 are common. Like medium hardness water low hardness water is also ideal for closed water systems when treated with corrosion inhibitors, and scale formation will not occur when heated. In tower water systems low hardness make-up water allows for up to six cycles of concentrations making for even more economical use and reduced chemical costs than medium hardness waters. Low hardness tower water is less susceptible to scale formation when heated than medium hardness water, however chilled water (closed system water) is recommended for hot extruder screw and barrel heat exchangers and mold temperature control units. 3) High Hardness Water – Well Water: Well water is used when low or medium hardness water is unavailable. The high hardness makes well water only appropriate for closed water applications under the guidance of a water treatment specialist. Some well waters may also contain corrosive contami- nants such as high levels of chlorides and sulphates, both of which can make even chemical treatment difficult. Well water can be used as tower water make-up but only with an aggressive chemical or chemical/soft- ening programmes. Any well water application requires regular, daily testing and monitoring of equipment and chemical levels as per your water treatment company’s recommendations. Any equip- No matter what type of chilling system a plant is equipped with, open or closed, understanding the water in an industrial system and applying appro- priate chemical water treatment is absolutely necessary. Your plant’s productivity and the life of your equipment depend on it. −6−
  • 7. ment breakdown or chemical program upset will cause rapid scaling in all heat transfer equipment. The result – costly repairs and expensive downtime. Glycol Systems: Glycol is commonly used with water in chillers to provide freeze protection. The percentage of glycol depends on the coldest temperature that the glycol reaches during operation. In a chiller this tempera- ture is normally the saturated suction temperature in the evaporator, and normally this temperature is 10°F below the chiller set point temperature. With this fact in mind, since water freezes at 32°F we only use glycol when the chiller set point is below 42°F, or if we are cooling a coil that is exposed to winter outside air. Some glycol products contain a corrosion inhibitor however glycol should not be used only for this purpose. Use corrosion inhibitors from a chemical company to supplement the glycol to be certain about preventing corrosion. Glycol is also a heat retardant rather than being good at transferring heat. Its presence also adds viscosity to the cooling fluid requiring higher hp pumps and higher flow rates to do the same as a pure water system. Therefore it is only to be used for freeze protection. There are generally two glycols that are used – propylene glycol, a food-grade and non-toxic glycol and ethylene glycol which although is toxic to humans and requires special handling and spill containment practices, is much less expensive and therefore more commonly used. Glycol at concentrations above 1-2% is toxic to bacteria. At low concentrations (0.1-1%) glycol is a nutrient for bacteria, and the by-product of the bacterial process is very acidic. Therefore, anytime you drain a glycol system you must do a thorough system flushing and immediately treat with a corro- sion inhibitor. In some cases a chemical cleaning is a necessary part of the flushing to ensure that you have completely removed all traces of glycol. Please consult your water treatment company. Water Quality And System Design: For most types of plastics the molds require cool water temperatures to minimize part cycle times and maximize productivity. Since the required tempera- tures for these molds cannot be reliably maintained with cooling towers during warm weather, and since the mold passages are small and easily fouled most plastics plants dedicate a chiller to the molds and plastic processing sections of extruders and use tower water for the shell and tube heat exchangers for hydraulic cooling, chiller condensers, air com- pressors, extruder feed throats and gear boxes. The exchangers in this equipment are usually shell and tube that are easily acid washed if cleaning is necessary. The spaces between the tubes are more forgiving to fouling than the small 1/16" spaces found in plate and frame exchangers and in small mold passages. Double Y Strainer for large particle filtration provides protec- tion to water circulation equipment against plugged strainers and filters with no downtime. Smart plant water system design uses mechanical (chiller) cooling only as needed, and maximizes the −7−
  • 8. energy savings found when using water cooled equipment whenever possible. Tower water (ambi- ent) cooling costs a fraction of the operating expense of a chiller, and a fraction of the equipment capital cost on a $ per ton basis. For this reason many plants select water-cooled chillers, air compressors and air dryers to put onto a cooling tower and dedicate a chiller for only cool water applications. There are other cases where tower water is a good choice for temperature control units, barrel and screw cooling. The required temperature set points for these may be between 140 - 180°F and as we discussed in the previous article the high concentration of calcium in the tower water will cause scale formation where tower water directly contacts the heaters and hot heat exchange surfaces. Precipitated scale will also migrate downstream to foul molds and other process equipment. Stainless Steel Fine Particle Strainer with Auto-Flush captures sediment in the clean process water. If your plant has medium hard make-up plant water, or if only very clean water can be tolerated in your molds and processing equipment, and your exchangers can be adequately cooled with tower water there are solutions available if you do not have a spare chiller available. 1) Softening: Softening uses a sodium zeolite resin that can be regenerated by brine to remove all calcium hardness from the make-up water. This will eliminate any hardness scale formation when the tower water contacts hot heat transfer surfaces, however the softened water changes its balance from being scaling water to corrosive water. The solution is to install a small valved by-pass around the softener and maintain just enough hardness in the water (approximately 80-100 ppm) to remove the corrosiveness and low enough in concentration to not precipitate when heated. This is a relatively low cost solution however be cautioned that thorough monitoring by the plant on a daily basis must be performed in order to correct any softener upsets, maintain the salt brine tank and balance the blend between the hard, by-pass make-up water with the 100% softened make-up water. Failure at any time can result in totally scaling up your system. 2) Clean Water Tower Systems: Safe, reliable and worry-free plant operation can be assured by converting your tower system to a Clean Water Tower System. Here an efficient plate and frame exchanger is installed in the tower system with standard 85°F/95°F water providing the cooling on one side of the exchanger and a closed loop process water system operates on the other side. The process equipment sees a minor increase in temperature (most exchangers can be sized to a 3 - 5°F difference between the inlet tower water temperature and the outlet process water tempera- ture), and the cooling water system becomes a standard closed loop system that can tolerate high hardness without scaling. The difference between this water and tower water from the same source is that there will be no make-up to replenish the scaling process, the hardness level is a fraction of the tower water hardness, there is no contact with the air so there is −8−
  • 9. none of the particulate present to cause fouling or deposition, and the water treatment is a simple, add as required process assuming that the system stays tight (apart from periodic mold changes). A large system with two separate tanks is shown below. Tank baffles are not required but were added in this application to provide extra strength to the two large tanks. In small applications less than 150 tons the two tanks can be brought together with only three pumps necessary (one process pump, one tower pump and one standby pump). In other cases, if the tower tank is large enough, or if it can be modified a heat exchanger can be added to the tankset and the baffled tower tank can be converted to two separate tanks with a full baffle from the bottom to the top of the tank. Some additional valves and piping changes then can retain the operation of a standby pump and use the two tanks to create a Clean Water Tower Tankset. 3) Other Solutions: Reverse osmosis, deionized water processes and other forms of water conditioning can remove hardness and other unwanted contaminants. There is usually a high cost to buy, install, and operate this equipment. Some of you may also encounter the non-chemical devices that claim to eliminate all chemical treatment, remove existing Berg Clean Water Tower System ensures safe, reliable, worry-free operation. −9− Berg System Manager with Touch Panel Double Y-Strainer Stainless Steel Tanks 1”Drain Plate Heat Exchanger Overflow Valve Fine Particle Strainer with Auto-Flush Make Up Valve Chemical Treatment System Berg Cooling Tower Pump Tank System
  • 10. scale, and run without the need to do daily plant tests. Many come with testimonials and references that are hard to trace, and may sound very convinc- ing. It has been the author’s experience that when things sound too good to be true they probably are, and we urge caution and consultation before you decide to try. Conclusion: Prepared by: Mike Sinclair, B. Sc. Berg Chilling Systems Inc. Berg Chilling Systems Inc., 51 Nantucket Blvd., Toronto, Ontario, Canada M1P2N5 • 416-755-2221 www.berg-group.com We hope that this paper provides a basic understanding of water quality management. We cannot understate the importance of working together with a reputable and high quality water treatment company representative to enable you to achieve your goal of maximum productivity, long equipment life and efficient plant equipment operating expense.