More Related Content Similar to Software-supported testing - SENTRON 3WA air circuit breakers .pdf (20) Software-supported testing - SENTRON 3WA air circuit breakers .pdf1. SENTRON 3WA air circuit breakers
Made for makers. Simply reliable.
Software-supported testing
Unrestricted | © Siemens 2022 | SI EP | 08.12.2022
2. Unrestricted | © Siemens 2022 | SI EP | 08.12.2022
Page 2
Analog
Digital
Protective
F5
Primary Protective Functions
ETU
ACB Function Blocks
L1
L2
L3
Main Contacts
Function direction
1 Transformer
2 Analog-Digital converter
3 Protective functions
4 Tripping solenoid F5
5 Mechanic and main contacts
Software-supported testing – Protective function principle (functional chain)
3WAair circuit breakers
How we do this test today
with the 3WL?
Hand held tester
3WL9111-0AT32-0AA0
List price 2.600,00 €
CT test & simple test function
Function testing unit
3WL9111-0AT44-0AA0
List price 28.700,00 €
Secondary injection test
Secondaryinjection test
3. Unrestricted | © Siemens 2022 | SI EP | 08.12.2022
Page 3
Software-supported testing
for Primary Protective Functions
LT / ST / INST / N or GF
SENTRON powerconfig
version 3.22 or higher
3WA firmware 2.2.0 or higher
Software guided and failsafe
Without assembly work
Connection via USB-C
Software-supported testing
3WAair circuit breakers
Protection settings from the breaker
Extended Breaker Test
• Basic Version for free
• Software license “Standard”
for Test report and more
functions for one year
(7KN2720-0CE00-1YC1)
4. Unrestricted | © Siemens 2022 | SI EP | 08.12.2022
Page 4
Test principle
The principle of software-assisted testing is that the SENTRON
powerconfig configuration software transmits a test signal (current
and/or voltage) to the ETU600 electronic trip unit via the USB-C
interface. The test signal is generated individually according to the
current circuit breaker protection settings and the selected test
function (LT, ST INST, N, GF, etc.).
The ETU600 treats the test signal like an actual current measured
via the current sensors and behaves as specified by the set
protection parameters. The protection function of the ETU600 is not
in test mode, nor is the protection behavior affected. This allows you
to check the real protection and system behavior and also detect
incorrect protection settings.
Software-supported testing
3WAair circuit breakers
5. Unrestricted | © Siemens 2022 | SI EP | 08.12.2022
Page 5
Analog
Digital
Protective
F5
ETU
ACB Function Blocks
L1
L2
L3
Main Contacts
Function direction
Software-supported testing
3WAair circuit breakers
Test = passed
✓ ETU self-monitoring (1 -3)
✓ ETU-Tripping (4)
✓ Tripping-time in tolerance (3)
✓ Main contacts open(4 – 5)
Precondition
current < 100 A
Test signal
The test signal corresponds one-to-one to the actually
measured signal (sample rate) coming from the analog-
to-digital converter. The test signal can be formed for
up to nine measuring inputs. The test signal is
generated individually by the SENTRON powerconfig
configuration software on the basis of the current
protection settings of the 3WA air circuit breaker and
the desired trip.
Test report
6. Unrestricted | © Siemens 2022 | SI EP | 08.12.2022
Page 6
Analog
Digital
Protective
F5
Primary Protective Functions
ETU
ACB Function Blocks
L1
L2
L3
Main Contacts
Function direction
1 Transformer
2 Analog-Digital converter
3 Protective functions
4 Tripping solenoid F5
5 Mechanic and main contacts
The monitoring function constantly checks the
current sensors, the analog-to-digital converter,
and the electronic components of the protection
function. Errors are detected and reported
immediately. The fault-free operation of these
components can therefore always be detected and
ensured.
Software-supported testing
3WAair circuit breakers
The set protection parameters and their
correctness and the mechanical part of the circuit
breaker (see points (4 - 5) are not checked by the
self-monitoring function. This is where software-
assisted testing comes in, which together with self-
monitoring can test the entire functional chain.
7. Unrestricted | © Siemens 2022 | SI EP | 08.12.2022
Page 7
Software-supported testing – Protective function principle (functional chain)
3WAair circuit breakers
Three levels of testing
Self-monitoring of the ETU
(watchdogs)
Simple Trip-testin the ETU
(Trip command)
Extended Breaker Testof the tripping curve for
LT, ST, INST, N or GF with Test-report
(Testcurrent samples)
8. Unrestricted | © Siemens 2022 | SI EP | 08.12.2022
Page 8
Software-supported testing – step by step
3WAair circuit breakers
SENTRON powerconfig version 3.22 or higher
Put a 3WA from the library to the project
9. Unrestricted | © Siemens 2022 | SI EP | 08.12.2022
Page 9
Software-supported testing – step by step
3WAair circuit breakers
Go to the communication cockpit
Connect the Breaker via USB-C ands select USB
as gateway
10. Unrestricted | © Siemens 2022 | SI EP | 08.12.2022
Page 10
Software-supported testing – step by step
3WAair circuit breakers
You can make a ping to test the connection
11. Unrestricted | © Siemens 2022 | SI EP | 08.12.2022
Page 11
Software-supported testing – step by step
3WAair circuit breakers
Go the Extended Breaker Test cockpit
The Extended Breaker Test is offline
12. Unrestricted | © Siemens 2022 | SI EP | 08.12.2022
Page 12
Software-supported testing – step by step
3WAair circuit breakers
Go online.
Powerconfig will load the current breaker settings.
These setting are the base form the Test.
13. Unrestricted | © Siemens 2022 | SI EP | 08.12.2022
Page 13
Software-supported testing – step by step
3WAair circuit breakers
This message will come if the breaker are different
to the data in the project. Please select yes.
14. Unrestricted | © Siemens 2022 | SI EP | 08.12.2022
Page 14
Software-supported testing – step by step
3WAair circuit breakers
Now its possible to select a Curve-Test
Protection setting of the connected Breaker
The extended Breaker Test is online
15. Unrestricted | © Siemens 2022 | SI EP | 08.12.2022
Page 15
Software-supported testing – step by step
3WAair circuit breakers
A Test current is selected and the Test can begin
16. Unrestricted | © Siemens 2022 | SI EP | 08.12.2022
Page 16
Software-supported testing – step by step
3WAair circuit breakers
You have to confirm that the main contacts are
closed, if no BSS200 is available. If a BSS200 is
available, the status of the main contacts is known
and no query will appear
17. Unrestricted | © Siemens 2022 | SI EP | 08.12.2022
Page 17
Software-supported testing – step by step
3WAair circuit breakers
The Test can now start
ETU-display during the Test
18. Unrestricted | © Siemens 2022 | SI EP | 08.12.2022
Page 18
Software-supported testing – step by step
3WAair circuit breakers
Please confirm the status of the main contacts
after the Test
ETU-display during the Test
19. Unrestricted | © Siemens 2022 | SI EP | 08.12.2022
Page 19
Software-supported testing – step by step
3WAair circuit breakers
Test results are transferred
20. Unrestricted | © Siemens 2022 | SI EP | 08.12.2022
Page 20
Software-supported testing – step by step
3WAair circuit breakers
Test results overview
ETU-display during the Test
21. Unrestricted | © Siemens 2022 | SI EP | 08.12.2022
Page 21
Software-supported testing – step by step
3WAair circuit breakers
You can save the Test results in the project
22. Unrestricted | © Siemens 2022 | SI EP | 08.12.2022
Page 22
Software-supported testing – step by step
3WAair circuit breakers
A detailed Test-Report is available.
You can print this report or save the report as PDF
if the software license Standard is active
23. Unrestricted | © Siemens 2022 | SI EP | 08.12.2022
Page 23
Software-supported testing – step by step
3WAair circuit breakers
Upgrade for Basic to Standard
For the upgrade is the Automation License
Manager needed. Link
SENTRON powerconfig License
7KN2720-0CE00-1YC1
24. Unrestricted | © Siemens 2022 | SI EP | 08.12.2022
Page 24
Software-supported testing – step by step
3WAair circuit breakers
For the upgrade is the Automation License
Manager needed. Link
25. Unrestricted | © Siemens 2022 | SI EP | 08.12.2022
Page 25
Software-supported testing – step by step
3WAair circuit breakers
With the License Standard its possible to select a
specific test current
Test license type Standard
26. Unrestricted | © Siemens 2022 | SI EP | 08.12.2022
Page 26
Software-supported testing – step by step
3WAair circuit breakers
With the License Standard its possible to to
print a detailed Test-Report
Standard
27. Unrestricted | © Siemens 2022 | SI EP | 08.12.2022
Page 27
Software-supported testing – step by step
3WAair circuit breakers
With the License Standard its possible to
print a detailed Test-Report
28. Contact
Published by Siemens AG
Smart Infrastructure
Electrical Products
Seite 28
siemens.com/3wa
Unrestricted | © Siemens 2022 | SI EP | 08.12.2022