SlideShare a Scribd company logo
1 of 8
Download to read offline
BURNER MANAGEMENT SYSTEM(BMS)
The BMS shall be designed to perform the following functions:-
1. Prevent firing unless a satisfactory furnace purge has first
been completed.
2. Prohibit start-up of the equipment unless certain permissive
interlocks have first been completed.
3. Monitor and control the correct component sequencing
(manual or automatic) during start-up and shut-down of the
equipment.
4. Conditionally allow the continued operation of the equipment
only while certain safety interlocks remaining satisfied.
5. Provide component condition feedback to the operator and, if
so equipped, to the plant control systems and/or data loggers.
6. Provide automatic supervision when the equipment is in
service and provide means to make a Master Fuel Trip (MFT)
should certain unacceptable firing conditions occur.
7. Execute a MFT upon certain adverse unit operating
conditions.
8. Because the flue gas path is to be treated the same as a fuel
line, the BMS must monitor the status of the valves and
associated equipment and include them in the permissives and
safety logic.
Operation:-
Per NFPA 8501, section 2-1.3(b):- a common cause of furnace
explosions is “Fuel leakage into an idle furnace and the ignition of
the accumulation by a spark or other source of ignition”.
Proper attention to the design of the interlocks and trip system to
provide a safe light up of the boiler furnace is required.
Philosophy used at Vindhyachal St-2, 3 : -energize to open & De-
energize to close.
Basic components of a BMS/FSSS system:-
a) Control & supervision of :-
1) Furnace purge.
2) SAD modulation
3) Light oil ON-OFF.
4) Heavy oil ON-OFF.
5) Tube mill & Raw coal feeder.
b) Flame scanner intelligence & checking.
c) Overall boiler flame failure protection.
d) Boiler trip protection.
Furnace Purge:-
Before any fuel firing is permitted, either initially or after a
boiler trip, a satisfactory furnace purge cycle must be completed.
As indicated in NFPA 8501, section 6-2.4.1(i):- the purge shall be
“...sufficient for at least eight air changes” of the furnace.
Purge Permissives:-
1. All LONV’s & HONV’s closed .
2. LOTV & HOTV closed.
3. All Mills OFF & PA Fans OFF.
4. All scanners show no flame.
5. “No bolier trip condition” exists.
6. All mill outlet gates are closed.
7. Air flow between 30% & 40% of MCR.
8. All Aux air dampers in modulating position.
Purge air flow (NFPA 8501, section 6-2.4.1(h): The total furnace
airflow shall not be reduced below the purge rate airflow (70% of
the maximum continuous airflow capacity). Reducing airflow below
these limits will lead to a MFT, and a new furnace purge will be
required.
Note:-Non-availability of any above during execution of purge
cycle of 9mins. will reset the purge counter & purging has to
restarted.
Selection of Fuel Oil type & permissives:
1. All of the above mentioned.
2. Oil gun is in place in the burner.
3. Oil pressure & temperature is normal
4. Fuel oil atomizing interlocks are satisfied
5. Fuel oil atomizing medium is provided to the burner
6. Oil control valve is in light-off position.
Other Conditions:
1. No MFT condition after purge
2. All flame scanners report no flame
3. All air dampers are in light-off position.
Start permissive for Oil system(LOTV/HOTV)
1. HORV open
2. All HONV closed & Supply hdr Pr. Adeq. & Temp. adeq. &
No MFT.
Trip conditions for LOTV/HOTV
1. MFT
2. Any LONV/HONV not closed & LO/ HO hdr pr V.Low (2/3
logic)
3. Atom.air /Steam pr. V.Low(2/3 logic) & no LO/HO elev. in
start or stop.
4. HO hdr temp. V.Low & any HONV not closed for >2sec
5. HORV not open(for HO only)
6. Loss of unit critical power(+24VDC)
Failure to meet any of these conditions shall prevent the burner
light-off operation.
Shutdown:-
Per NFPA 8501, section 6-2.4.5:- The normal shutdown cycle
for the boiler shall accomplish the following in the order listed:
(a) Shut off fuel supply to the main burner.
(b) Interrupt spark and shut off fuel supply to igniter, if in
operation.
(c) For oil:
1. Where used, open the recirculating valve.
2. Shut off atomizing medium, if desired.
(d) For gas, vent piping between safety shutoff valves to
atmosphere.
(e) Perform a post purge of the boiler furnace enclosure.
(f) Shut down fan, if desired.”
Normal Boiler Shutdown
A normal shutdown is initiated by operating BOILER
SHUTDOWN switch. This will initiate the shut down sequence
listed above.
Boiler Master Fuel Trip
Any of the following conditions shall cause a boiler trip to
occur. This results in the shutdown of all fuel and requires another
furnace purge cycle before any attempt at re-lighting.
1. Loss of unit 220VDC power for >2sec.
2. Loss of unit critical power(+24VDC)
3. All forced draft fans OFF.
4. All Induced draft fans OFF.
5. Drum water level V.High for >10Sec.
6. Drum water level V.Low for >5Sec.
7. Air flow<30%of MCR.
8. Furnace pressure V.low(2/3 logic).
9. Furnace pressure V.High(2/3 logic).
10. Loss of Reheater protection.
11. Less than fireball & loss of AC in any elevation in service
12. Emergeny PB pressed
13. Loss of all fuel
14. Unit flame failure.
15. Water wall circulation not proper
16. All SRAPH Off.
17. All BFP’s Off for >10Sec.
MFT will initiate:-
1. Cut-off fuel.(Close HOTV/LOTV, mills, feeders, mill outlet
gates, PA general inlet gates, all HONV/LONV & PA fans.)
2. A feed forward signal to furnace draft control for 30sec.
3. Transfer Aux. air control to manual and open all aux. air
dampers.
4. All fuel air dampers are transferred to manual and opened
fully.
5. Illuminate the appropriate indicator lights and alarms.
6. Return the system to the pre-purge state
Boiler restart will be inhibited until all pre-purge requirements are
satisfied.
First-out trip system:-
1. The first cause of boiler trip is indicated and cuase of trip
memory is set, blocking successive trip commands/reasons.
2. This gets reset only after successful 9 min. purge cycle
completion.
Post purge excursion protection:-
1. After expiry of 9 mins. of purge cycle
2. If all above purge permissives(except pt. no. 7) & air flow
>30% MCR.
3. Furnace press. V.Hi, V.low exits.
Then, “Post purge fan trip” command is issued to FD & ID fans.
This is reset after opening opening of any HO/LO valve.
Alarms:-
The following is a list of recommended alarm conditions:
1. Any boiler or burner trip signal
2. High or low water level
3. High furnace pressure
3. Partial Loss of flame (For the typical two scanner system,
one indicates “no flame”)
5. Main fuel shutoff valves closed
6. Loss of control system power
7. Unsuccessful burner shutdown
Suggested color design:
Oil guns sequence:-
Pair mode or elevation mode
A predefined time of 70 secs given for oil at an elevation to prove.
Gap of 15 secs. between commands of two guns in pair.
How BMS is implemented:-
a) Field devices
b) CER / Remote devices
c) Human interface
Field devices- It includes
Mechanical parts: Valves, dampers, power cylinders, pumps,
piping/ impulse lines, instrument air, Positioners, E/P converters,
AFR, ALR etc
Electrical parts: Ignitor(HEA and its excitor), Solenoids, limit
switches and associated cables.
Electronic parts: Flame scanners, Level / temperature/
pressure switches, transmitters and associated cables.
CER / Remote devices: It includes
Relays, wiring, sold state devices, power supply source &
distribution system(110VAC, 220VDC), power isolation
devices(fuses, breakers etc), contactors, control panel, I/O modules,
Programmable modules, PLC, Flame scanner remote electronics
and other instrumentation required to implement BMS
Purge Permissives indicating lights: white
Purge Available indicating light: green
Purge in progress indicating light: Amber
Purge complete indicating light: White
MFT reset indicating light: red
logics/Philosophy, 24VDC power supply if solid state or Digital
control system is used for logic building.
Human interface: It includes
For conventional UCB- Various selection blocks, On/Off
switches, indication lamps, alarm/ annunciation, recorders/
indicators
For modern UCB- CRT/LVS based. Operation/ view of BMS
devices thru mouse or touch screen. Trend/ bar chart/ mimic /
alarm report tells operator about field status.
Subloops of BMS:-
1) Unit control panel
2) MFT panel
3) SADC controls
4) Oil gun controls
5) Mill controls(one of each mill)
6) RCF controls
7) Flame scanner electronics panel
Logic implementation in BMS panel:-
a) Three channels for MFT conditions, with 2/3 logic for final
trip command to all slave devices.
b) Slave commands to fuel cut-off and start permissives are sent
thru two routes( one being hardwired, other one is thru
software)
c) Modern controls build BMS logics on digital systems(PLC or
DCS) and use relays/ contactors for interfacing with field
devices.
d) Most of the parameters used for BMS have 3 sensors in field
for 2/3 voting.
e) These sensor status are multiplied in MFT panel for use in
three channels(3 x 3)
f) Monitoring of protection instruments for discrepancy in their
status( only one out of three reports or none of the status for a
instrument is available)
g) Sequence control for oil gun & mill startup/ shutdown
incorporating all protections & interlocks.
h) Positioning of Secondary air dampers(Fuel & aux. air) during
furnace purge/ shutdown conditions, cut-in of oil / coal and as
per BLI(for aux. air in normal operation to maintain proper
windbox to furnace DP).

More Related Content

What's hot

Furnace safegaurd supervisory system logic-1
Furnace safegaurd supervisory system logic-1Furnace safegaurd supervisory system logic-1
Furnace safegaurd supervisory system logic-1Ashvani Shukla
 
Pulverized coal fired boiler startup procedure
Pulverized coal fired boiler startup procedurePulverized coal fired boiler startup procedure
Pulverized coal fired boiler startup procedureAshvani Shukla
 
Unit shutdown procedure operation
Unit shutdown procedure operationUnit shutdown procedure operation
Unit shutdown procedure operationNitin Patel
 
Starting & Recommended Interlocks for AH,ID,FD,PA Fans & BD Valves for 270 MW...
Starting & Recommended Interlocks for AH,ID,FD,PA Fans & BD Valves for 270 MW...Starting & Recommended Interlocks for AH,ID,FD,PA Fans & BD Valves for 270 MW...
Starting & Recommended Interlocks for AH,ID,FD,PA Fans & BD Valves for 270 MW...Manohar Tatwawadi
 
Boiler recommissioning procedure after capital overhaul
Boiler recommissioning procedure after capital overhaul Boiler recommissioning procedure after capital overhaul
Boiler recommissioning procedure after capital overhaul Manohar Tatwawadi
 
660 mw turbo governing &amp; protection system
660 mw turbo  governing &amp; protection system660 mw turbo  governing &amp; protection system
660 mw turbo governing &amp; protection systemAshvani Shukla
 
Vertical multistage fire pump catalogue-60HZ
Vertical multistage fire pump catalogue-60HZVertical multistage fire pump catalogue-60HZ
Vertical multistage fire pump catalogue-60HZAndy Chen
 
Thermal Power Plant Simulator, Cold, warm and Hot rolling of Steam Turbine
Thermal Power Plant Simulator, Cold, warm and Hot rolling of Steam TurbineThermal Power Plant Simulator, Cold, warm and Hot rolling of Steam Turbine
Thermal Power Plant Simulator, Cold, warm and Hot rolling of Steam TurbineManohar Tatwawadi
 
Power Plant Simulator Day 3 Part 5
Power Plant Simulator Day 3 Part 5Power Plant Simulator Day 3 Part 5
Power Plant Simulator Day 3 Part 5Manohar Tatwawadi
 
Mobile transformer oil purification plant with high vacuum globecore cmm(uvm)...
Mobile transformer oil purification plant with high vacuum globecore cmm(uvm)...Mobile transformer oil purification plant with high vacuum globecore cmm(uvm)...
Mobile transformer oil purification plant with high vacuum globecore cmm(uvm)...GlobeCore
 
Steam Turbine Lube Oil System Protections Using SCADA & PLC
Steam Turbine Lube Oil System Protections Using SCADA & PLCSteam Turbine Lube Oil System Protections Using SCADA & PLC
Steam Turbine Lube Oil System Protections Using SCADA & PLCNilesh Jha
 
AUTOMATIC TURBINE RUNUP SYSTEM
AUTOMATIC TURBINE RUNUP SYSTEMAUTOMATIC TURBINE RUNUP SYSTEM
AUTOMATIC TURBINE RUNUP SYSTEMkumarswamy927
 
POWER PLANT SIMULATOR 210 MW
POWER PLANT SIMULATOR 210 MW POWER PLANT SIMULATOR 210 MW
POWER PLANT SIMULATOR 210 MW Manohar Tatwawadi
 
INTRODUCTION TO GOVERNING
INTRODUCTION TO GOVERNINGINTRODUCTION TO GOVERNING
INTRODUCTION TO GOVERNINGSURAJ KUMAR
 

What's hot (20)

Furnace safegaurd supervisory system logic-1
Furnace safegaurd supervisory system logic-1Furnace safegaurd supervisory system logic-1
Furnace safegaurd supervisory system logic-1
 
Pulverized coal fired boiler startup procedure
Pulverized coal fired boiler startup procedurePulverized coal fired boiler startup procedure
Pulverized coal fired boiler startup procedure
 
Unit shutdown procedure operation
Unit shutdown procedure operationUnit shutdown procedure operation
Unit shutdown procedure operation
 
Starting & Recommended Interlocks for AH,ID,FD,PA Fans & BD Valves for 270 MW...
Starting & Recommended Interlocks for AH,ID,FD,PA Fans & BD Valves for 270 MW...Starting & Recommended Interlocks for AH,ID,FD,PA Fans & BD Valves for 270 MW...
Starting & Recommended Interlocks for AH,ID,FD,PA Fans & BD Valves for 270 MW...
 
boiler turbine emergency
boiler turbine emergencyboiler turbine emergency
boiler turbine emergency
 
BMS
BMSBMS
BMS
 
Boiler recommissioning procedure after capital overhaul
Boiler recommissioning procedure after capital overhaul Boiler recommissioning procedure after capital overhaul
Boiler recommissioning procedure after capital overhaul
 
Fsss
FsssFsss
Fsss
 
660 mw turbo governing &amp; protection system
660 mw turbo  governing &amp; protection system660 mw turbo  governing &amp; protection system
660 mw turbo governing &amp; protection system
 
Vertical multistage fire pump catalogue-60HZ
Vertical multistage fire pump catalogue-60HZVertical multistage fire pump catalogue-60HZ
Vertical multistage fire pump catalogue-60HZ
 
Boiler light up & loading
Boiler light up & loadingBoiler light up & loading
Boiler light up & loading
 
Thermal Power Plant Simulator, Cold, warm and Hot rolling of Steam Turbine
Thermal Power Plant Simulator, Cold, warm and Hot rolling of Steam TurbineThermal Power Plant Simulator, Cold, warm and Hot rolling of Steam Turbine
Thermal Power Plant Simulator, Cold, warm and Hot rolling of Steam Turbine
 
Power Plant Simulator Day 3 Part 5
Power Plant Simulator Day 3 Part 5Power Plant Simulator Day 3 Part 5
Power Plant Simulator Day 3 Part 5
 
Mobile transformer oil purification plant with high vacuum globecore cmm(uvm)...
Mobile transformer oil purification plant with high vacuum globecore cmm(uvm)...Mobile transformer oil purification plant with high vacuum globecore cmm(uvm)...
Mobile transformer oil purification plant with high vacuum globecore cmm(uvm)...
 
Steam Turbine Lube Oil System Protections Using SCADA & PLC
Steam Turbine Lube Oil System Protections Using SCADA & PLCSteam Turbine Lube Oil System Protections Using SCADA & PLC
Steam Turbine Lube Oil System Protections Using SCADA & PLC
 
Chap 43
Chap 43Chap 43
Chap 43
 
Power Plant Operations.pdf
Power Plant Operations.pdfPower Plant Operations.pdf
Power Plant Operations.pdf
 
AUTOMATIC TURBINE RUNUP SYSTEM
AUTOMATIC TURBINE RUNUP SYSTEMAUTOMATIC TURBINE RUNUP SYSTEM
AUTOMATIC TURBINE RUNUP SYSTEM
 
POWER PLANT SIMULATOR 210 MW
POWER PLANT SIMULATOR 210 MW POWER PLANT SIMULATOR 210 MW
POWER PLANT SIMULATOR 210 MW
 
INTRODUCTION TO GOVERNING
INTRODUCTION TO GOVERNINGINTRODUCTION TO GOVERNING
INTRODUCTION TO GOVERNING
 

Similar to 94716008 burner-management-system-et-2008

Burner Management System ( FSSS).pptx
Burner Management System ( FSSS).pptxBurner Management System ( FSSS).pptx
Burner Management System ( FSSS).pptxManzoorAlam40
 
fire fighting ppt sop.pptx
fire fighting ppt sop.pptxfire fighting ppt sop.pptx
fire fighting ppt sop.pptxRagaSudha18
 
Globe core oil purification plant SMM 0.6
Globe core oil purification plant SMM 0.6Globe core oil purification plant SMM 0.6
Globe core oil purification plant SMM 0.6GlobeCore
 
UNA DISCUSIÓN TÉCNICA ACERCA DEL SISTEMA DE ADMINISTRACIÓN DE QUEMADOR.pptx
UNA DISCUSIÓN TÉCNICA ACERCA DEL SISTEMA DE ADMINISTRACIÓN DE QUEMADOR.pptxUNA DISCUSIÓN TÉCNICA ACERCA DEL SISTEMA DE ADMINISTRACIÓN DE QUEMADOR.pptx
UNA DISCUSIÓN TÉCNICA ACERCA DEL SISTEMA DE ADMINISTRACIÓN DE QUEMADOR.pptxYudarliRodriguez
 
SIPAT 660 MW Turbo- Governing & Protection System.ppt
SIPAT 660 MW Turbo- Governing & Protection System.pptSIPAT 660 MW Turbo- Governing & Protection System.ppt
SIPAT 660 MW Turbo- Governing & Protection System.pptMarcWorld
 
Operation of hydro power plants
Operation of hydro power plants Operation of hydro power plants
Operation of hydro power plants DINESHPRASAD39
 
Fire Pump System Pressure Control
Fire Pump System Pressure ControlFire Pump System Pressure Control
Fire Pump System Pressure ControlJames S Nasby
 
Boiler operation technical information
Boiler operation   technical informationBoiler operation   technical information
Boiler operation technical informationstephen maloba
 
Dgps control system
Dgps control systemDgps control system
Dgps control systemAryan Raj
 
Maintenance schedule of Substation.
Maintenance schedule of Substation.Maintenance schedule of Substation.
Maintenance schedule of Substation.Sheikh Nazmul Islam
 
Instructions To Use Electronic Controller Logik 25-S in Screw Compressor
Instructions To Use Electronic Controller Logik 25-S in Screw Compressor Instructions To Use Electronic Controller Logik 25-S in Screw Compressor
Instructions To Use Electronic Controller Logik 25-S in Screw Compressor Eaton Compressor & Fabrication
 
E70 CCB2 Brake system for WAG 9 Locomotive.pptx
E70 CCB2 Brake system for WAG 9 Locomotive.pptxE70 CCB2 Brake system for WAG 9 Locomotive.pptx
E70 CCB2 Brake system for WAG 9 Locomotive.pptxSATYANARAYANABODDULA
 
Variable speed fire pump controllers
Variable speed fire pump controllersVariable speed fire pump controllers
Variable speed fire pump controllersmichaeljmack
 

Similar to 94716008 burner-management-system-et-2008 (20)

BMS FSSS.pptx
BMS FSSS.pptxBMS FSSS.pptx
BMS FSSS.pptx
 
Burner Management System ( FSSS).pptx
Burner Management System ( FSSS).pptxBurner Management System ( FSSS).pptx
Burner Management System ( FSSS).pptx
 
Steam Boiler Sequence Of Operation
Steam Boiler Sequence Of OperationSteam Boiler Sequence Of Operation
Steam Boiler Sequence Of Operation
 
fire fighting ppt sop.pptx
fire fighting ppt sop.pptxfire fighting ppt sop.pptx
fire fighting ppt sop.pptx
 
Unit protection scheme
Unit protection schemeUnit protection scheme
Unit protection scheme
 
Globe core oil purification plant SMM 0.6
Globe core oil purification plant SMM 0.6Globe core oil purification plant SMM 0.6
Globe core oil purification plant SMM 0.6
 
UNA DISCUSIÓN TÉCNICA ACERCA DEL SISTEMA DE ADMINISTRACIÓN DE QUEMADOR.pptx
UNA DISCUSIÓN TÉCNICA ACERCA DEL SISTEMA DE ADMINISTRACIÓN DE QUEMADOR.pptxUNA DISCUSIÓN TÉCNICA ACERCA DEL SISTEMA DE ADMINISTRACIÓN DE QUEMADOR.pptx
UNA DISCUSIÓN TÉCNICA ACERCA DEL SISTEMA DE ADMINISTRACIÓN DE QUEMADOR.pptx
 
SIPAT 660 MW Turbo- Governing & Protection System.ppt
SIPAT 660 MW Turbo- Governing & Protection System.pptSIPAT 660 MW Turbo- Governing & Protection System.ppt
SIPAT 660 MW Turbo- Governing & Protection System.ppt
 
Operation of hydro power plants
Operation of hydro power plants Operation of hydro power plants
Operation of hydro power plants
 
Pcs
PcsPcs
Pcs
 
xfr oparation & maintenance
xfr oparation & maintenancexfr oparation & maintenance
xfr oparation & maintenance
 
Fire Pump System Pressure Control
Fire Pump System Pressure ControlFire Pump System Pressure Control
Fire Pump System Pressure Control
 
Boiler operation technical information
Boiler operation   technical informationBoiler operation   technical information
Boiler operation technical information
 
Dgps control system
Dgps control systemDgps control system
Dgps control system
 
Maintenance schedule of Substation.
Maintenance schedule of Substation.Maintenance schedule of Substation.
Maintenance schedule of Substation.
 
Instructions To Use Electronic Controller Logik 25-S in Screw Compressor
Instructions To Use Electronic Controller Logik 25-S in Screw Compressor Instructions To Use Electronic Controller Logik 25-S in Screw Compressor
Instructions To Use Electronic Controller Logik 25-S in Screw Compressor
 
E70 CCB2 Brake system for WAG 9 Locomotive.pptx
E70 CCB2 Brake system for WAG 9 Locomotive.pptxE70 CCB2 Brake system for WAG 9 Locomotive.pptx
E70 CCB2 Brake system for WAG 9 Locomotive.pptx
 
Variable speed fire pump controllers
Variable speed fire pump controllersVariable speed fire pump controllers
Variable speed fire pump controllers
 
Automate
AutomateAutomate
Automate
 
Test Rig for 130LPM Pump of LCA- Neometrix
Test Rig for 130LPM Pump of LCA- NeometrixTest Rig for 130LPM Pump of LCA- Neometrix
Test Rig for 130LPM Pump of LCA- Neometrix
 

More from Mowaten Masry

143673805 1-burner-management-system
143673805 1-burner-management-system143673805 1-burner-management-system
143673805 1-burner-management-systemMowaten Masry
 
55419663 burner-management-system
55419663 burner-management-system55419663 burner-management-system
55419663 burner-management-systemMowaten Masry
 
114632948 jeres-j-607-burner-management-systems-for-sru-trains
114632948 jeres-j-607-burner-management-systems-for-sru-trains114632948 jeres-j-607-burner-management-systems-for-sru-trains
114632948 jeres-j-607-burner-management-systems-for-sru-trainsMowaten Masry
 
117697637 burner-mgmt-system
117697637 burner-mgmt-system117697637 burner-mgmt-system
117697637 burner-mgmt-systemMowaten Masry
 
49574055 burner-management-system-safety-integrity-level-selection
49574055 burner-management-system-safety-integrity-level-selection49574055 burner-management-system-safety-integrity-level-selection
49574055 burner-management-system-safety-integrity-level-selectionMowaten Masry
 
Manual reset 8327 direct mount push button (m)
Manual reset 8327 direct mount push button (m)Manual reset 8327 direct mount push button (m)
Manual reset 8327 direct mount push button (m)Mowaten Masry
 
Methods of determining_safety_integrity_level
Methods of determining_safety_integrity_levelMethods of determining_safety_integrity_level
Methods of determining_safety_integrity_levelMowaten Masry
 
71364263 voting-logic-sil-calculation
71364263 voting-logic-sil-calculation71364263 voting-logic-sil-calculation
71364263 voting-logic-sil-calculationMowaten Masry
 
96000707 gas-turbine-control
96000707 gas-turbine-control96000707 gas-turbine-control
96000707 gas-turbine-controlMowaten Masry
 
78679939 dvc6000manualinstrucciones
78679939 dvc6000manualinstrucciones78679939 dvc6000manualinstrucciones
78679939 dvc6000manualinstruccionesMowaten Masry
 
Item06 reliability-availability-maintainability-and-safety-programme
Item06 reliability-availability-maintainability-and-safety-programmeItem06 reliability-availability-maintainability-and-safety-programme
Item06 reliability-availability-maintainability-and-safety-programmeMowaten Masry
 
75340982 standards-issued
75340982 standards-issued75340982 standards-issued
75340982 standards-issuedMowaten Masry
 
Safety instrumented systems
Safety instrumented systemsSafety instrumented systems
Safety instrumented systemsMowaten Masry
 
35958867 safety-instrumented-systems
35958867 safety-instrumented-systems35958867 safety-instrumented-systems
35958867 safety-instrumented-systemsMowaten Masry
 

More from Mowaten Masry (19)

143673805 1-burner-management-system
143673805 1-burner-management-system143673805 1-burner-management-system
143673805 1-burner-management-system
 
55419663 burner-management-system
55419663 burner-management-system55419663 burner-management-system
55419663 burner-management-system
 
An9030
An9030An9030
An9030
 
114632948 jeres-j-607-burner-management-systems-for-sru-trains
114632948 jeres-j-607-burner-management-systems-for-sru-trains114632948 jeres-j-607-burner-management-systems-for-sru-trains
114632948 jeres-j-607-burner-management-systems-for-sru-trains
 
117697637 burner-mgmt-system
117697637 burner-mgmt-system117697637 burner-mgmt-system
117697637 burner-mgmt-system
 
49574055 burner-management-system-safety-integrity-level-selection
49574055 burner-management-system-safety-integrity-level-selection49574055 burner-management-system-safety-integrity-level-selection
49574055 burner-management-system-safety-integrity-level-selection
 
Manual reset 8327 direct mount push button (m)
Manual reset 8327 direct mount push button (m)Manual reset 8327 direct mount push button (m)
Manual reset 8327 direct mount push button (m)
 
Methods of determining_safety_integrity_level
Methods of determining_safety_integrity_levelMethods of determining_safety_integrity_level
Methods of determining_safety_integrity_level
 
44636808 bms
44636808 bms44636808 bms
44636808 bms
 
9fcfd50a69d9647585
9fcfd50a69d96475859fcfd50a69d9647585
9fcfd50a69d9647585
 
71364263 voting-logic-sil-calculation
71364263 voting-logic-sil-calculation71364263 voting-logic-sil-calculation
71364263 voting-logic-sil-calculation
 
96000707 gas-turbine-control
96000707 gas-turbine-control96000707 gas-turbine-control
96000707 gas-turbine-control
 
78679939 dvc6000manualinstrucciones
78679939 dvc6000manualinstrucciones78679939 dvc6000manualinstrucciones
78679939 dvc6000manualinstrucciones
 
Item06 reliability-availability-maintainability-and-safety-programme
Item06 reliability-availability-maintainability-and-safety-programmeItem06 reliability-availability-maintainability-and-safety-programme
Item06 reliability-availability-maintainability-and-safety-programme
 
75340982 standards-issued
75340982 standards-issued75340982 standards-issued
75340982 standards-issued
 
Safety instrumented systems
Safety instrumented systemsSafety instrumented systems
Safety instrumented systems
 
35958867 safety-instrumented-systems
35958867 safety-instrumented-systems35958867 safety-instrumented-systems
35958867 safety-instrumented-systems
 
E04
E04E04
E04
 
Ram s
Ram sRam s
Ram s
 

Recently uploaded

High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escortsranjana rawat
 
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxAsutosh Ranjan
 
Introduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxIntroduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxupamatechverse
 
KubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlyKubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlysanyuktamishra911
 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Dr.Costas Sachpazis
 
Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxupamatechverse
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...ranjana rawat
 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxpranjaldaimarysona
 
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur Escorts
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur EscortsRussian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur Escorts
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
result management system report for college project
result management system report for college projectresult management system report for college project
result management system report for college projectTonystark477637
 
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and workingUNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and workingrknatarajan
 
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptx
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptxBSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptx
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptxfenichawla
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...Call Girls in Nagpur High Profile
 
UNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular ConduitsUNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular Conduitsrknatarajan
 
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordAsst.prof M.Gokilavani
 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations120cr0395
 
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfKamal Acharya
 

Recently uploaded (20)

High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
 
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
 
Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024
 
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptx
 
Introduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxIntroduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptx
 
KubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlyKubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghly
 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
 
Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptx
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptx
 
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur Escorts
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur EscortsRussian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur Escorts
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur Escorts
 
result management system report for college project
result management system report for college projectresult management system report for college project
result management system report for college project
 
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and workingUNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
 
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptx
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptxBSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptx
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptx
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
 
UNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular ConduitsUNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular Conduits
 
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations
 
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
 

94716008 burner-management-system-et-2008

  • 1. BURNER MANAGEMENT SYSTEM(BMS) The BMS shall be designed to perform the following functions:- 1. Prevent firing unless a satisfactory furnace purge has first been completed. 2. Prohibit start-up of the equipment unless certain permissive interlocks have first been completed. 3. Monitor and control the correct component sequencing (manual or automatic) during start-up and shut-down of the equipment. 4. Conditionally allow the continued operation of the equipment only while certain safety interlocks remaining satisfied. 5. Provide component condition feedback to the operator and, if so equipped, to the plant control systems and/or data loggers. 6. Provide automatic supervision when the equipment is in service and provide means to make a Master Fuel Trip (MFT) should certain unacceptable firing conditions occur. 7. Execute a MFT upon certain adverse unit operating conditions. 8. Because the flue gas path is to be treated the same as a fuel line, the BMS must monitor the status of the valves and associated equipment and include them in the permissives and safety logic. Operation:- Per NFPA 8501, section 2-1.3(b):- a common cause of furnace explosions is “Fuel leakage into an idle furnace and the ignition of the accumulation by a spark or other source of ignition”. Proper attention to the design of the interlocks and trip system to provide a safe light up of the boiler furnace is required. Philosophy used at Vindhyachal St-2, 3 : -energize to open & De- energize to close.
  • 2. Basic components of a BMS/FSSS system:- a) Control & supervision of :- 1) Furnace purge. 2) SAD modulation 3) Light oil ON-OFF. 4) Heavy oil ON-OFF. 5) Tube mill & Raw coal feeder. b) Flame scanner intelligence & checking. c) Overall boiler flame failure protection. d) Boiler trip protection. Furnace Purge:- Before any fuel firing is permitted, either initially or after a boiler trip, a satisfactory furnace purge cycle must be completed. As indicated in NFPA 8501, section 6-2.4.1(i):- the purge shall be “...sufficient for at least eight air changes” of the furnace. Purge Permissives:- 1. All LONV’s & HONV’s closed . 2. LOTV & HOTV closed. 3. All Mills OFF & PA Fans OFF. 4. All scanners show no flame. 5. “No bolier trip condition” exists. 6. All mill outlet gates are closed. 7. Air flow between 30% & 40% of MCR. 8. All Aux air dampers in modulating position. Purge air flow (NFPA 8501, section 6-2.4.1(h): The total furnace airflow shall not be reduced below the purge rate airflow (70% of the maximum continuous airflow capacity). Reducing airflow below these limits will lead to a MFT, and a new furnace purge will be required. Note:-Non-availability of any above during execution of purge cycle of 9mins. will reset the purge counter & purging has to restarted.
  • 3. Selection of Fuel Oil type & permissives: 1. All of the above mentioned. 2. Oil gun is in place in the burner. 3. Oil pressure & temperature is normal 4. Fuel oil atomizing interlocks are satisfied 5. Fuel oil atomizing medium is provided to the burner 6. Oil control valve is in light-off position. Other Conditions: 1. No MFT condition after purge 2. All flame scanners report no flame 3. All air dampers are in light-off position. Start permissive for Oil system(LOTV/HOTV) 1. HORV open 2. All HONV closed & Supply hdr Pr. Adeq. & Temp. adeq. & No MFT. Trip conditions for LOTV/HOTV 1. MFT 2. Any LONV/HONV not closed & LO/ HO hdr pr V.Low (2/3 logic) 3. Atom.air /Steam pr. V.Low(2/3 logic) & no LO/HO elev. in start or stop. 4. HO hdr temp. V.Low & any HONV not closed for >2sec 5. HORV not open(for HO only) 6. Loss of unit critical power(+24VDC) Failure to meet any of these conditions shall prevent the burner light-off operation. Shutdown:- Per NFPA 8501, section 6-2.4.5:- The normal shutdown cycle for the boiler shall accomplish the following in the order listed: (a) Shut off fuel supply to the main burner. (b) Interrupt spark and shut off fuel supply to igniter, if in operation.
  • 4. (c) For oil: 1. Where used, open the recirculating valve. 2. Shut off atomizing medium, if desired. (d) For gas, vent piping between safety shutoff valves to atmosphere. (e) Perform a post purge of the boiler furnace enclosure. (f) Shut down fan, if desired.” Normal Boiler Shutdown A normal shutdown is initiated by operating BOILER SHUTDOWN switch. This will initiate the shut down sequence listed above. Boiler Master Fuel Trip Any of the following conditions shall cause a boiler trip to occur. This results in the shutdown of all fuel and requires another furnace purge cycle before any attempt at re-lighting. 1. Loss of unit 220VDC power for >2sec. 2. Loss of unit critical power(+24VDC) 3. All forced draft fans OFF. 4. All Induced draft fans OFF. 5. Drum water level V.High for >10Sec. 6. Drum water level V.Low for >5Sec. 7. Air flow<30%of MCR. 8. Furnace pressure V.low(2/3 logic). 9. Furnace pressure V.High(2/3 logic). 10. Loss of Reheater protection. 11. Less than fireball & loss of AC in any elevation in service 12. Emergeny PB pressed 13. Loss of all fuel 14. Unit flame failure. 15. Water wall circulation not proper 16. All SRAPH Off. 17. All BFP’s Off for >10Sec.
  • 5. MFT will initiate:- 1. Cut-off fuel.(Close HOTV/LOTV, mills, feeders, mill outlet gates, PA general inlet gates, all HONV/LONV & PA fans.) 2. A feed forward signal to furnace draft control for 30sec. 3. Transfer Aux. air control to manual and open all aux. air dampers. 4. All fuel air dampers are transferred to manual and opened fully. 5. Illuminate the appropriate indicator lights and alarms. 6. Return the system to the pre-purge state Boiler restart will be inhibited until all pre-purge requirements are satisfied. First-out trip system:- 1. The first cause of boiler trip is indicated and cuase of trip memory is set, blocking successive trip commands/reasons. 2. This gets reset only after successful 9 min. purge cycle completion. Post purge excursion protection:- 1. After expiry of 9 mins. of purge cycle 2. If all above purge permissives(except pt. no. 7) & air flow >30% MCR. 3. Furnace press. V.Hi, V.low exits. Then, “Post purge fan trip” command is issued to FD & ID fans. This is reset after opening opening of any HO/LO valve. Alarms:- The following is a list of recommended alarm conditions: 1. Any boiler or burner trip signal 2. High or low water level 3. High furnace pressure 3. Partial Loss of flame (For the typical two scanner system, one indicates “no flame”) 5. Main fuel shutoff valves closed
  • 6. 6. Loss of control system power 7. Unsuccessful burner shutdown Suggested color design: Oil guns sequence:- Pair mode or elevation mode A predefined time of 70 secs given for oil at an elevation to prove. Gap of 15 secs. between commands of two guns in pair. How BMS is implemented:- a) Field devices b) CER / Remote devices c) Human interface Field devices- It includes Mechanical parts: Valves, dampers, power cylinders, pumps, piping/ impulse lines, instrument air, Positioners, E/P converters, AFR, ALR etc Electrical parts: Ignitor(HEA and its excitor), Solenoids, limit switches and associated cables. Electronic parts: Flame scanners, Level / temperature/ pressure switches, transmitters and associated cables. CER / Remote devices: It includes Relays, wiring, sold state devices, power supply source & distribution system(110VAC, 220VDC), power isolation devices(fuses, breakers etc), contactors, control panel, I/O modules, Programmable modules, PLC, Flame scanner remote electronics and other instrumentation required to implement BMS Purge Permissives indicating lights: white Purge Available indicating light: green Purge in progress indicating light: Amber Purge complete indicating light: White MFT reset indicating light: red
  • 7. logics/Philosophy, 24VDC power supply if solid state or Digital control system is used for logic building. Human interface: It includes For conventional UCB- Various selection blocks, On/Off switches, indication lamps, alarm/ annunciation, recorders/ indicators For modern UCB- CRT/LVS based. Operation/ view of BMS devices thru mouse or touch screen. Trend/ bar chart/ mimic / alarm report tells operator about field status. Subloops of BMS:- 1) Unit control panel 2) MFT panel 3) SADC controls 4) Oil gun controls 5) Mill controls(one of each mill) 6) RCF controls 7) Flame scanner electronics panel Logic implementation in BMS panel:- a) Three channels for MFT conditions, with 2/3 logic for final trip command to all slave devices. b) Slave commands to fuel cut-off and start permissives are sent thru two routes( one being hardwired, other one is thru software) c) Modern controls build BMS logics on digital systems(PLC or DCS) and use relays/ contactors for interfacing with field devices. d) Most of the parameters used for BMS have 3 sensors in field for 2/3 voting. e) These sensor status are multiplied in MFT panel for use in three channels(3 x 3) f) Monitoring of protection instruments for discrepancy in their status( only one out of three reports or none of the status for a instrument is available)
  • 8. g) Sequence control for oil gun & mill startup/ shutdown incorporating all protections & interlocks. h) Positioning of Secondary air dampers(Fuel & aux. air) during furnace purge/ shutdown conditions, cut-in of oil / coal and as per BLI(for aux. air in normal operation to maintain proper windbox to furnace DP).