SlideShare a Scribd company logo
1 of 3
Download to read offline
TUAP065
physics/0112030
INSTRUMENTATION, FIELD NETWORK AND PROCESS AUTOMATION
FOR THE CRYOGENIC SYSTEM OF THE LHC TEST STRING
T. Bager, Ch. Balle, E. Blanco, J. Casas, P. Gomes, L. Serio, A. Suraci, N. Vauthier,
LHC Division, CERN 1211 Geneva 23, Switzerland
S. Pelletier, Soteb National Elektro, 60 rue Clement Ader, 01630 St Genis-Pouilly, France
Abstract
CERN is now setting up String 2 [1], a full-size proto-
type of a regular cell of the LHC arc. It is composed of
two quadrupole, six dipole magnets, and a separate
cryogenic distribution line (QRL) for the supply and
recovery of the cryogen. An electrical feed box (DFB),
with up to 38 High Temperature Superconducting (HTS)
leads, powers the magnets.
About 700 sensors and actuators are distributed along
four Profibus DP and two Profibus PA field buses. The
process automation is handled by two controllers, running
126 Closed Control Loops (CCL).
This paper describes the cryogenic control system,
associated instrumentation, and their commissioning.
1 LAYOUT
String 2 consists of two consecutive LHC half-cells,
comprising: two quadrupoles, six 15 m dipoles, their
multipole correctors, and the QRL. The chain of magnets
is terminated, on the upstream end, by the DFB and, on
the downstream end, by the Magnet Return-Box (MRB).
The QRL is terminated by its feed and return boxes
(QLISF and QLISR).
The DFB houses 3 pairs of 13 kA and 16 pairs of
600 A current leads, to feed 11 electrical circuits. The
MRB contains the short circuits and the connection to the
QRL, simulating the jumper of the following cell. A
6 kW/4.5 K refrigerator supplies and recovers the
cryogen. Fifteen power converters supply the magnets’
electrical circuits.
String 2 has a length of about 120m and follows the
tunnel curvature of the LHC machine (Figure 1). Most of
its elements are heavily instrumented for the experimental
program. String 2 is being assembled in two phases.
Phase 1 started to be commissioned in April 2001; it
comprises all elements except the three dipoles of the
second half-cell, which will be added in early 2002.
Figure 1: overview of String 2
2 PROCESS CONTROL
2.1 Structure
The String 2 cryogenic process [2] is handled by two
industrial Programmable Logic Controllers (PLC), from
Siemens (CPU-S7-414-3DP). One of them is dedicated to
the magnets and QRL cryogenics (PLC1), whereas the
other controls the DFB cryogenics (PLC2).
The refrigerator and its coupling to String 2 are
controlled by an ABB based system, not reported here.
An Engineering WorkStation (EWS) can be remotely
connected to the PLCs, through Profibus DP or Ethernet.
It is used to program the PLCs and to directly access
intelligent devices, for configuration, parameterization
and monitoring.
The cryogenic operation and data storage are
performed on an Operating WorkStation (OWS), linked
to the PLCs through Ethernet. It runs the Supervisory
Control And Data Acquisition (SCADA), which is based
on PcVue32 and was developed by BARC, India, and by
the CERN/LHC/IAS group.
Transients on some process variables are recorded by
a fast VME + LabView data acquisition system,
developed by INCAA, Netherlands, and by IAS group.
2.2 Main Program
Every 100 ms, the main program of each PLC checks
if any of the following routines is scheduled for execution
(Table 1): CCL, input acquisition, phase sequencer,
interlocks, alarms and communication. The time-stamp
associated to every call is available to the OWS.
Table 1: instrumentation and routine count per PLC
PLC1 PLC2 total
process inputs 326 290 616
process outputs 39 42 81
total I/O 365 332 697
CCLs 32+7x2=46 4+38x2=80 126
alarms always valid 16 5 21
alarms for specific phases 25 5 30
interlocks 27 6+38x2=82 109
2.3 Inputs, Outputs and CCLs
Every one of the 81 process outputs (actuators) is
handled by a CCL routine, which implements a PID
algorithm. Half of the actuators have a double PID,
whereby one out of two process inputs can be selected on
the OWS. This leads to 126 PIDs.
The process input to a PID can be filtered (first-order
low-pass) or substituted by a constant value. Two
setpoints, and their respective offsets, are selectable for
each PID; an instantaneous modification of the setpoint
value can be limited in slope.
8th International Conference on Accelerator & Large Experimental Physics Control Systems, 2001, San Jose, California
194
A PID can be in one of the following modes, by order
of increasing priority: automatic, forced by process,
manual or interlocked. The PID output is respectively:
calculated, forced by the process conditions, set by the
operator, or driven into a safe position.
CCLs are scheduled for execution with a rate (up to
1Hz) fixed according to the process characteristics. Some
heaters have their average power regulated by a Pulse-
Width Modulation technique (PWM). Their CCLs are
calculated every 10 s and their digital output updated
every 100 ms, leading to a 1% resolution.
The about 500 inputs not used in CCLs are read by the
acquisition routines and made available in the OWS, for
monitoring and diagnostics.
2.4 Process Phases
A process phase sequencer tests the start/stop
conditions for every operational phase, such as cool-
down, normal operation, magnet powering, quench
recovery and warm-up. Associated to each phase,
automatic actions are programmed for each actuator:
choose each of two PIDs, choose each of two setpoints,
regulate or force to close or to open, with or without
ramp. These automatic actions can be overridden by
manual or interlocked modes.
2.5 Interlocks
About 30 general interlock conditions are available, in
order to force actuators into a safe position, like:
• close valves when liquid level or pressure are high;
• power-off level indicators if no liquid is present;
• stop heaters if a risk of thermal runaway exists.
Moreover, 80 interlocks protect the HTS current leads
against excessive cooling: each valve controlling the
cooling of the current leads is interlocked with two
temperatures at the warm end of the lead.
The interlock thresholds are editable on the OWS and
the associated process values and status bit are displayed.
This status bit is also visible on each actuator’s PID
faceplate. Interlocks override automatic and manual
actions and they cannot be disabled.
For high-power heaters (>1 kW), local hardware
interlocks are activated by the actual temperature of each
heating element, independently from the PLC.
2.6 Alarms
About 20 alarm conditions are always tested, while 30
others are valid only in specific phases of the process. As
for the interlocks, the threshold for each alarm condition
is editable on the OWS and the process value and status
bit are displayed. Two enable bits are available for alarm
activation and for outgoing signal generation.
If any of the enabled alarms lasts more than 1 minute
without being acknowledged, or if the communication
with a PLC is idle for more than 5 minutes, the OWS
automatically warns the operator. A message with the
type of alarm is sent through email or cellular phone.
Additionally, when any of the enabled alarms lasts
more than 1 minute, or if either PLCs stops, a global
hardwired signal is sent to the CERN Technical Control
Room (TCR). The responsible person will then be called
after a given time. This global signal can also be
enabled/disabled/forced by software and hardware.
2.7 Communication
Specific routines exchange information between both
PLCs and receive data from other systems, such as the
refrigerator and the magnet power converter.
On the other hand, critical signals are hardwired:
• status of refrigerator, vacuum and quench detection;
• interlocks to refrigerator and power converters;
• alarm to the TCR.
3 FIELDBUS NETWORKS
Instrumentation is spread along the string over 120 m.
Most of the process inputs and outputs are accessed by
the PLCs through various fieldbus segments (Figure 2).
Figure 2: Layout and fieldbus networks
Intelligent devices are directly connected to
Profibus PA, operating at 31.25 kbit/s. Conventional
devices are connected to analog or digital modules on
remote I/O stations (ET200M®
from Siemens), which
communicate on Profibus DP, running at 1.5 Mbit/s.
3.1 Network PLC1
To cover the instrumentation distributed along the
magnets and the QRL, three DP and two PA segments
have been used.
The sensors that will be used in the LHC machine are
distributed over two DP segments, each of them 150 m
long. If one of these is down, the sensors on the other will
still be enough to run the machine. Each segment
comprises 4 remote I/O stations, housed in crates under
each dipole, as for the LHC machine.
The third DP segment, extending for about 250 m,
gathers instrumentation specific to the experimental
program of String 2. Sixteen I/O stations are accommo-
dated in ten racks behind the QRL, whereas 8 other are
directly hooked on the QRL. Also on this DP segment are
the two PA segments; they include 7 intelligent valves
and 3 pressure sensors, installed at one end of the QRL,
and 2 valves at the other end. The PLC and some I/O
stations are installed in two racks.
3.2 Network PLC2
Most of the DFB instrumentation is grouped on a
single and short DP segment: 8 I/O stations and a PA
segment that handles one intelligent valve positioner.
The 38 valves, on the cooling inlets of the current
leads, are driven by local PLC output modules. All the
I/O stations and the PLC are installed in two racks. This
configuration is representative of the LHC machine,
where the PLC and I/O stations of the DFB will be
clustered in radiation protected areas.
8th International Conference on Accelerator & Large Experimental Physics Control Systems, 2001, San Jose, California
195
4 INSTRUMENTATION
4.1 Temperature
More than 400 resistive temperature sensors, of three
types, are used in String 2 (Table 2). As all of them are
non-linear, the measured resistance is converted into
temperature by an interpolation table. Each Cernox™
and
Carbon have a specific table, whereas all Platinum have
the same one.
Table 2: temperature sensors
Type Quantity range covered
Platinum 295 300 K … 30 K
Cernox™ 115 300 K … 1.6 K
Carbon 22 100 K … 1.6 K
In general, Platinum thermometers are directly read by
analog input modules as a four-wire resistor, without any
intermediate signal conditioning.
Most of the Cernox™
and Carbon thermometers are
read through linear multi-range signal conditioners
(STMS), which produce 4-20 mA magnitude and two bits
indicating the range. Logarithmic signal conditioners
(LOG) are used for sampling rates faster than a few
seconds and have a single 4-20 mA output. Both STMS
and LOG are in-house developments [3].
In the current leads, galvanic isolation up to 5 kV is
provided by:
• IPAC®
conditioners for 190 Platinum thermometers
• STMS conditioners and fuses for 6 Cernox™
.
4.2 Pressure
On pipes and vessels, absolute pressures up to
100 mbar or to 25 bar are measured by warm transducers,
with integrated electronics; three of them operate on
Profibus PA whereas 16 other have 4-20mA outputs. The
cold mass pressures are measured by 11 passive low-
voltage sensors, immersed in liquid helium; their signal
conditioners have 4-20mA outputs.
4.3 Liquid Level
The eight liquid helium levels inside the vessels and in
the superfluid heat exchanger are measured with
superconducting-wire gauges (Twickenham Scientific
Instruments). To minimize self-heating, the sensors are
read in 3s pulsed-mode. The output is 4-20 mA.
4.4 Flow
Two mass-flow controllers, ten mass-flow meters and
two cryogenic Coriolis mass flow-meters are used to
control flow rates and to assess thermal performances.
They are read via 4-20 mA current-loops.
4.5 Heaters
Electrical heaters are used to warm-up cold gaseous
helium leaving String 2, and to evaporate liquid helium in
phase separators and in the magnet cold masses.
Twenty-one low-power heaters are driven by level
modulated DC voltage. Five higher power heaters, up to
64 kW, are supplied through 220 VAC solid state relays,
via the PWM technique. Most of these are in series with
programmable relays (Sineax), activated according to the
temperature of the respective heating element.
4.6 Valves
Ten pneumatic valves with intelligent positioners
(Sipart®
PS2, from Siemens) are spread on the two
Profibus PA segments. Thirty-four classical analog valves
are driven with 4-20 mA. Five on/off valves are driven by
0-24 V digital outputs.
5 COMMISSIONING
Starting in April 2001, most of the instrumentation
and control was checked while the last components were
being assembled.
Every instrument had its signal chain verified from the
machine to the PLC and to the SCADA. This included
cabling, signal processing, coherence between PLC and
SCADA databases, and synoptic view. Phases, interlocks
and alarms were tested by changing thresholds, while the
actuators were inhibited.
Before the final closure of the vacuum vessel, several
problems were identified. They were repaired whenever
the instrument or cables were still accessible. The origin
of these issues has been traced to:
• sensor name and serial number mismatch;
• installation procedure not followed;
• broken wires, sensors failure.
All instruments required for the cooling loops were
available when cool-down from 300 K to 4.5 K started,
on August 7. The process was gradually set into auto-
matic mode, and the machine could be left unattended.
Apart from the unavoidable time spent for trouble-
shooting the components and instrumentation not
operating as expected, the overall cool-down from 300 K
to 1.9 K took just over 2 weeks, as expected. Once at
nominal temperature (1.9 K), the dipole and quadrupole
circuits were powered to nominal current (11 850 A).
Only then, the control loops were fine-tuned, and cold-
mass thermometers and pressure sensors were verified for
high accuracy.
During cool-down, the analysis of temperature pro-
files showed additional inversions and identification
errors, mainly on the current leads thermometers.
6 CONCLUSION
The installation and commissioning of String 2 cryo-
genic instrumentation and control was very educative, in
view of the methods to be implemented for LHC. The
structure of software and hardware documentation was
enhanced. Software routines were improved. In the future,
sensors installation procedures must be carefully respect-
ed, in terms of materials, positioning, and follow-up
documentation. In this way, precious time can be saved.
We wish to express our acknowledgement to the
operators team, who gave us valuable help during the
commissioning of instruments and programs.
REFERENCES
[1] F. Bordry et al., “The LHC Test String 2: Design Study”, LHC
Project Report, March 1998.
[2] L. Serio, “The Process of the Cryogenic System for String 2:
Functional Analysis”, LHC-XMS-ES-0004, LHC Engeneering
Specification, Feb 2001.
[3] J. Casas et al., “Signal Conditioning for Cryogenic Thermometry
in the LHC”, CEC/IMC99, Montreal, Canada, July 1999.
8th International Conference on Accelerator & Large Experimental Physics Control Systems, 2001, San Jose, California
196

More Related Content

What's hot

Assembly programming II
Assembly programming IIAssembly programming II
Assembly programming IIOmar Sanchez
 
Instrumentation & control of typical material handling of FGD Plant
Instrumentation & control of typical material handling of FGD PlantInstrumentation & control of typical material handling of FGD Plant
Instrumentation & control of typical material handling of FGD PlantSANJIB KUMAR PATRA
 
LayerZero Series 70 ePODs: Type-N Static Transfer Switch with Distribution
LayerZero Series 70 ePODs: Type-N Static Transfer Switch with DistributionLayerZero Series 70 ePODs: Type-N Static Transfer Switch with Distribution
LayerZero Series 70 ePODs: Type-N Static Transfer Switch with DistributionLayerZero Power Systems, Inc.
 
SEM88_Presentation
SEM88_PresentationSEM88_Presentation
SEM88_PresentationLuka Penger
 
Fundamentals of plc 1
Fundamentals of plc 1Fundamentals of plc 1
Fundamentals of plc 1Sachin Tupe
 
Beptu induction cooker_ha0101_e
Beptu induction cooker_ha0101_eBeptu induction cooker_ha0101_e
Beptu induction cooker_ha0101_emaihau
 
2.4G Radio Transceiver for IEEE802.15.4 and ZigBee Applications
2.4G Radio Transceiver for IEEE802.15.4 and ZigBee Applications2.4G Radio Transceiver for IEEE802.15.4 and ZigBee Applications
2.4G Radio Transceiver for IEEE802.15.4 and ZigBee ApplicationsPremier Farnell
 
FAR/MARS Avionics CDR
FAR/MARS Avionics CDRFAR/MARS Avionics CDR
FAR/MARS Avionics CDRCade Walton
 
FPGA IMPLIMENTATION OF UART CONTTROLLER
FPGA IMPLIMENTATION OF UART CONTTROLLERFPGA IMPLIMENTATION OF UART CONTTROLLER
FPGA IMPLIMENTATION OF UART CONTTROLLERVarun Kambrath
 
Imx53 uart- GUIDE BOOK
Imx53 uart- GUIDE BOOKImx53 uart- GUIDE BOOK
Imx53 uart- GUIDE BOOKShahrukh Javed
 
Sensor de pressão de pneu
Sensor de pressão de pneuSensor de pressão de pneu
Sensor de pressão de pneuCarlos Vergara
 
Siemens Terminal Box Controller (APOGEE Automation System )
Siemens Terminal Box Controller (APOGEE Automation System )Siemens Terminal Box Controller (APOGEE Automation System )
Siemens Terminal Box Controller (APOGEE Automation System )CONTROLS & SYSTEMS
 
an advance approach to divert trafiic at busy signals using rfid technolgy
an advance approach to divert trafiic at busy signals using rfid technolgyan advance approach to divert trafiic at busy signals using rfid technolgy
an advance approach to divert trafiic at busy signals using rfid technolgyChitrachedu Dada Kalandar
 
Lecture 10 (serial communication)
Lecture 10 (serial communication)Lecture 10 (serial communication)
Lecture 10 (serial communication)cairo university
 
Industrial Temperature Controller System
Industrial Temperature Controller SystemIndustrial Temperature Controller System
Industrial Temperature Controller SystemEdgefxkits & Solutions
 
Arm cortex ( lpc 2148 ) based motor speed control
Arm cortex ( lpc 2148 ) based motor speed control Arm cortex ( lpc 2148 ) based motor speed control
Arm cortex ( lpc 2148 ) based motor speed control Uday Wankar
 
Arm Processor Based Speed Control Of BLDC Motor
Arm Processor Based Speed Control Of BLDC MotorArm Processor Based Speed Control Of BLDC Motor
Arm Processor Based Speed Control Of BLDC MotorUday Wankar
 
Datasheet RTC DS1307 untuk waktu yang tepat pada mikrokontroler
Datasheet RTC DS1307 untuk waktu yang tepat pada mikrokontrolerDatasheet RTC DS1307 untuk waktu yang tepat pada mikrokontroler
Datasheet RTC DS1307 untuk waktu yang tepat pada mikrokontrolerMuhammad Kennedy Ginting
 

What's hot (20)

Assembly programming II
Assembly programming IIAssembly programming II
Assembly programming II
 
Instrumentation & control of typical material handling of FGD Plant
Instrumentation & control of typical material handling of FGD PlantInstrumentation & control of typical material handling of FGD Plant
Instrumentation & control of typical material handling of FGD Plant
 
LayerZero Series 70 ePODs: Type-N Static Transfer Switch with Distribution
LayerZero Series 70 ePODs: Type-N Static Transfer Switch with DistributionLayerZero Series 70 ePODs: Type-N Static Transfer Switch with Distribution
LayerZero Series 70 ePODs: Type-N Static Transfer Switch with Distribution
 
SEM88_Presentation
SEM88_PresentationSEM88_Presentation
SEM88_Presentation
 
Fundamentals of plc 1
Fundamentals of plc 1Fundamentals of plc 1
Fundamentals of plc 1
 
Beptu induction cooker_ha0101_e
Beptu induction cooker_ha0101_eBeptu induction cooker_ha0101_e
Beptu induction cooker_ha0101_e
 
2.4G Radio Transceiver for IEEE802.15.4 and ZigBee Applications
2.4G Radio Transceiver for IEEE802.15.4 and ZigBee Applications2.4G Radio Transceiver for IEEE802.15.4 and ZigBee Applications
2.4G Radio Transceiver for IEEE802.15.4 and ZigBee Applications
 
FAR/MARS Avionics CDR
FAR/MARS Avionics CDRFAR/MARS Avionics CDR
FAR/MARS Avionics CDR
 
FPGA IMPLIMENTATION OF UART CONTTROLLER
FPGA IMPLIMENTATION OF UART CONTTROLLERFPGA IMPLIMENTATION OF UART CONTTROLLER
FPGA IMPLIMENTATION OF UART CONTTROLLER
 
Imx53 uart- GUIDE BOOK
Imx53 uart- GUIDE BOOKImx53 uart- GUIDE BOOK
Imx53 uart- GUIDE BOOK
 
Sensor de pressão de pneu
Sensor de pressão de pneuSensor de pressão de pneu
Sensor de pressão de pneu
 
Siemens Terminal Box Controller (APOGEE Automation System )
Siemens Terminal Box Controller (APOGEE Automation System )Siemens Terminal Box Controller (APOGEE Automation System )
Siemens Terminal Box Controller (APOGEE Automation System )
 
an advance approach to divert trafiic at busy signals using rfid technolgy
an advance approach to divert trafiic at busy signals using rfid technolgyan advance approach to divert trafiic at busy signals using rfid technolgy
an advance approach to divert trafiic at busy signals using rfid technolgy
 
7SR210 Overcurrent Relay
7SR210 Overcurrent Relay7SR210 Overcurrent Relay
7SR210 Overcurrent Relay
 
Lecture 10 (serial communication)
Lecture 10 (serial communication)Lecture 10 (serial communication)
Lecture 10 (serial communication)
 
7SR220 Overcurrent Relay
7SR220 Overcurrent Relay7SR220 Overcurrent Relay
7SR220 Overcurrent Relay
 
Industrial Temperature Controller System
Industrial Temperature Controller SystemIndustrial Temperature Controller System
Industrial Temperature Controller System
 
Arm cortex ( lpc 2148 ) based motor speed control
Arm cortex ( lpc 2148 ) based motor speed control Arm cortex ( lpc 2148 ) based motor speed control
Arm cortex ( lpc 2148 ) based motor speed control
 
Arm Processor Based Speed Control Of BLDC Motor
Arm Processor Based Speed Control Of BLDC MotorArm Processor Based Speed Control Of BLDC Motor
Arm Processor Based Speed Control Of BLDC Motor
 
Datasheet RTC DS1307 untuk waktu yang tepat pada mikrokontroler
Datasheet RTC DS1307 untuk waktu yang tepat pada mikrokontrolerDatasheet RTC DS1307 untuk waktu yang tepat pada mikrokontroler
Datasheet RTC DS1307 untuk waktu yang tepat pada mikrokontroler
 

Similar to Pcs

ELECTRONICS PROJECT REPORT OF HOME AUTOMATION CUM BUILDING SECUIRITY
ELECTRONICS PROJECT REPORT OF HOME AUTOMATION CUM BUILDING SECUIRITYELECTRONICS PROJECT REPORT OF HOME AUTOMATION CUM BUILDING SECUIRITY
ELECTRONICS PROJECT REPORT OF HOME AUTOMATION CUM BUILDING SECUIRITYEldhose George
 
D041121722
D041121722D041121722
D041121722IOSR-JEN
 
A 32 channel modular multi input data acquisition system for
A 32 channel modular multi input data acquisition system forA 32 channel modular multi input data acquisition system for
A 32 channel modular multi input data acquisition system forAlexander Decker
 
A 32 channel modular multi input data acquisition system for
A 32 channel modular multi input data acquisition system forA 32 channel modular multi input data acquisition system for
A 32 channel modular multi input data acquisition system forAlexander Decker
 
Parameter controlling of boiler in power plants using fuzzy logic controller
Parameter controlling of boiler in power plants using fuzzy logic controllerParameter controlling of boiler in power plants using fuzzy logic controller
Parameter controlling of boiler in power plants using fuzzy logic controllereSAT Journals
 
The Intellectual Automated Substation
The Intellectual Automated SubstationThe Intellectual Automated Substation
The Intellectual Automated Substationijtsrd
 
Classic control in industry
Classic control in industry Classic control in industry
Classic control in industry Mostafa Ragab
 
1 mrk511232 ben-e_en_product_guide__rec670_1.2_pre-configured
1 mrk511232 ben-e_en_product_guide__rec670_1.2_pre-configured1 mrk511232 ben-e_en_product_guide__rec670_1.2_pre-configured
1 mrk511232 ben-e_en_product_guide__rec670_1.2_pre-configuredJavier Cuzco
 
Q46C2-Two-Electrode-Conductivity-Resistivity-Monitor-1.pdf
Q46C2-Two-Electrode-Conductivity-Resistivity-Monitor-1.pdfQ46C2-Two-Electrode-Conductivity-Resistivity-Monitor-1.pdf
Q46C2-Two-Electrode-Conductivity-Resistivity-Monitor-1.pdfENVIMART
 
Iskra Medium Voltage Automation and Protection (Protection relays)
Iskra Medium Voltage Automation and Protection (Protection relays)Iskra Medium Voltage Automation and Protection (Protection relays)
Iskra Medium Voltage Automation and Protection (Protection relays)Minka Grdesic
 
C041121116
C041121116C041121116
C041121116IOSR-JEN
 
classic control and PLC training report
classic control and PLC training reportclassic control and PLC training report
classic control and PLC training reportahmed abdelnasser
 

Similar to Pcs (20)

Fulltext 1005224
Fulltext 1005224 Fulltext 1005224
Fulltext 1005224
 
ELECTRONICS PROJECT REPORT OF HOME AUTOMATION CUM BUILDING SECUIRITY
ELECTRONICS PROJECT REPORT OF HOME AUTOMATION CUM BUILDING SECUIRITYELECTRONICS PROJECT REPORT OF HOME AUTOMATION CUM BUILDING SECUIRITY
ELECTRONICS PROJECT REPORT OF HOME AUTOMATION CUM BUILDING SECUIRITY
 
D041121722
D041121722D041121722
D041121722
 
A 32 channel modular multi input data acquisition system for
A 32 channel modular multi input data acquisition system forA 32 channel modular multi input data acquisition system for
A 32 channel modular multi input data acquisition system for
 
A 32 channel modular multi input data acquisition system for
A 32 channel modular multi input data acquisition system forA 32 channel modular multi input data acquisition system for
A 32 channel modular multi input data acquisition system for
 
Parameter controlling of boiler in power plants using fuzzy logic controller
Parameter controlling of boiler in power plants using fuzzy logic controllerParameter controlling of boiler in power plants using fuzzy logic controller
Parameter controlling of boiler in power plants using fuzzy logic controller
 
The Intellectual Automated Substation
The Intellectual Automated SubstationThe Intellectual Automated Substation
The Intellectual Automated Substation
 
Classic control in industry
Classic control in industry Classic control in industry
Classic control in industry
 
1 mrk511232 ben-e_en_product_guide__rec670_1.2_pre-configured
1 mrk511232 ben-e_en_product_guide__rec670_1.2_pre-configured1 mrk511232 ben-e_en_product_guide__rec670_1.2_pre-configured
1 mrk511232 ben-e_en_product_guide__rec670_1.2_pre-configured
 
UNIT-5-PPT.ppt
UNIT-5-PPT.pptUNIT-5-PPT.ppt
UNIT-5-PPT.ppt
 
D05111923
D05111923D05111923
D05111923
 
Q46C2-Two-Electrode-Conductivity-Resistivity-Monitor-1.pdf
Q46C2-Two-Electrode-Conductivity-Resistivity-Monitor-1.pdfQ46C2-Two-Electrode-Conductivity-Resistivity-Monitor-1.pdf
Q46C2-Two-Electrode-Conductivity-Resistivity-Monitor-1.pdf
 
Iskra Medium Voltage Automation and Protection (Protection relays)
Iskra Medium Voltage Automation and Protection (Protection relays)Iskra Medium Voltage Automation and Protection (Protection relays)
Iskra Medium Voltage Automation and Protection (Protection relays)
 
16928 6274 1
16928 6274 116928 6274 1
16928 6274 1
 
7SR11 Overcurrent Relay
7SR11 Overcurrent Relay7SR11 Overcurrent Relay
7SR11 Overcurrent Relay
 
C041121116
C041121116C041121116
C041121116
 
Scada
ScadaScada
Scada
 
Presentaton on Plc & Scada
Presentaton on Plc & ScadaPresentaton on Plc & Scada
Presentaton on Plc & Scada
 
classic control and PLC training report
classic control and PLC training reportclassic control and PLC training report
classic control and PLC training report
 
I012455457
I012455457I012455457
I012455457
 

Pcs

  • 1. TUAP065 physics/0112030 INSTRUMENTATION, FIELD NETWORK AND PROCESS AUTOMATION FOR THE CRYOGENIC SYSTEM OF THE LHC TEST STRING T. Bager, Ch. Balle, E. Blanco, J. Casas, P. Gomes, L. Serio, A. Suraci, N. Vauthier, LHC Division, CERN 1211 Geneva 23, Switzerland S. Pelletier, Soteb National Elektro, 60 rue Clement Ader, 01630 St Genis-Pouilly, France Abstract CERN is now setting up String 2 [1], a full-size proto- type of a regular cell of the LHC arc. It is composed of two quadrupole, six dipole magnets, and a separate cryogenic distribution line (QRL) for the supply and recovery of the cryogen. An electrical feed box (DFB), with up to 38 High Temperature Superconducting (HTS) leads, powers the magnets. About 700 sensors and actuators are distributed along four Profibus DP and two Profibus PA field buses. The process automation is handled by two controllers, running 126 Closed Control Loops (CCL). This paper describes the cryogenic control system, associated instrumentation, and their commissioning. 1 LAYOUT String 2 consists of two consecutive LHC half-cells, comprising: two quadrupoles, six 15 m dipoles, their multipole correctors, and the QRL. The chain of magnets is terminated, on the upstream end, by the DFB and, on the downstream end, by the Magnet Return-Box (MRB). The QRL is terminated by its feed and return boxes (QLISF and QLISR). The DFB houses 3 pairs of 13 kA and 16 pairs of 600 A current leads, to feed 11 electrical circuits. The MRB contains the short circuits and the connection to the QRL, simulating the jumper of the following cell. A 6 kW/4.5 K refrigerator supplies and recovers the cryogen. Fifteen power converters supply the magnets’ electrical circuits. String 2 has a length of about 120m and follows the tunnel curvature of the LHC machine (Figure 1). Most of its elements are heavily instrumented for the experimental program. String 2 is being assembled in two phases. Phase 1 started to be commissioned in April 2001; it comprises all elements except the three dipoles of the second half-cell, which will be added in early 2002. Figure 1: overview of String 2 2 PROCESS CONTROL 2.1 Structure The String 2 cryogenic process [2] is handled by two industrial Programmable Logic Controllers (PLC), from Siemens (CPU-S7-414-3DP). One of them is dedicated to the magnets and QRL cryogenics (PLC1), whereas the other controls the DFB cryogenics (PLC2). The refrigerator and its coupling to String 2 are controlled by an ABB based system, not reported here. An Engineering WorkStation (EWS) can be remotely connected to the PLCs, through Profibus DP or Ethernet. It is used to program the PLCs and to directly access intelligent devices, for configuration, parameterization and monitoring. The cryogenic operation and data storage are performed on an Operating WorkStation (OWS), linked to the PLCs through Ethernet. It runs the Supervisory Control And Data Acquisition (SCADA), which is based on PcVue32 and was developed by BARC, India, and by the CERN/LHC/IAS group. Transients on some process variables are recorded by a fast VME + LabView data acquisition system, developed by INCAA, Netherlands, and by IAS group. 2.2 Main Program Every 100 ms, the main program of each PLC checks if any of the following routines is scheduled for execution (Table 1): CCL, input acquisition, phase sequencer, interlocks, alarms and communication. The time-stamp associated to every call is available to the OWS. Table 1: instrumentation and routine count per PLC PLC1 PLC2 total process inputs 326 290 616 process outputs 39 42 81 total I/O 365 332 697 CCLs 32+7x2=46 4+38x2=80 126 alarms always valid 16 5 21 alarms for specific phases 25 5 30 interlocks 27 6+38x2=82 109 2.3 Inputs, Outputs and CCLs Every one of the 81 process outputs (actuators) is handled by a CCL routine, which implements a PID algorithm. Half of the actuators have a double PID, whereby one out of two process inputs can be selected on the OWS. This leads to 126 PIDs. The process input to a PID can be filtered (first-order low-pass) or substituted by a constant value. Two setpoints, and their respective offsets, are selectable for each PID; an instantaneous modification of the setpoint value can be limited in slope. 8th International Conference on Accelerator & Large Experimental Physics Control Systems, 2001, San Jose, California 194
  • 2. A PID can be in one of the following modes, by order of increasing priority: automatic, forced by process, manual or interlocked. The PID output is respectively: calculated, forced by the process conditions, set by the operator, or driven into a safe position. CCLs are scheduled for execution with a rate (up to 1Hz) fixed according to the process characteristics. Some heaters have their average power regulated by a Pulse- Width Modulation technique (PWM). Their CCLs are calculated every 10 s and their digital output updated every 100 ms, leading to a 1% resolution. The about 500 inputs not used in CCLs are read by the acquisition routines and made available in the OWS, for monitoring and diagnostics. 2.4 Process Phases A process phase sequencer tests the start/stop conditions for every operational phase, such as cool- down, normal operation, magnet powering, quench recovery and warm-up. Associated to each phase, automatic actions are programmed for each actuator: choose each of two PIDs, choose each of two setpoints, regulate or force to close or to open, with or without ramp. These automatic actions can be overridden by manual or interlocked modes. 2.5 Interlocks About 30 general interlock conditions are available, in order to force actuators into a safe position, like: • close valves when liquid level or pressure are high; • power-off level indicators if no liquid is present; • stop heaters if a risk of thermal runaway exists. Moreover, 80 interlocks protect the HTS current leads against excessive cooling: each valve controlling the cooling of the current leads is interlocked with two temperatures at the warm end of the lead. The interlock thresholds are editable on the OWS and the associated process values and status bit are displayed. This status bit is also visible on each actuator’s PID faceplate. Interlocks override automatic and manual actions and they cannot be disabled. For high-power heaters (>1 kW), local hardware interlocks are activated by the actual temperature of each heating element, independently from the PLC. 2.6 Alarms About 20 alarm conditions are always tested, while 30 others are valid only in specific phases of the process. As for the interlocks, the threshold for each alarm condition is editable on the OWS and the process value and status bit are displayed. Two enable bits are available for alarm activation and for outgoing signal generation. If any of the enabled alarms lasts more than 1 minute without being acknowledged, or if the communication with a PLC is idle for more than 5 minutes, the OWS automatically warns the operator. A message with the type of alarm is sent through email or cellular phone. Additionally, when any of the enabled alarms lasts more than 1 minute, or if either PLCs stops, a global hardwired signal is sent to the CERN Technical Control Room (TCR). The responsible person will then be called after a given time. This global signal can also be enabled/disabled/forced by software and hardware. 2.7 Communication Specific routines exchange information between both PLCs and receive data from other systems, such as the refrigerator and the magnet power converter. On the other hand, critical signals are hardwired: • status of refrigerator, vacuum and quench detection; • interlocks to refrigerator and power converters; • alarm to the TCR. 3 FIELDBUS NETWORKS Instrumentation is spread along the string over 120 m. Most of the process inputs and outputs are accessed by the PLCs through various fieldbus segments (Figure 2). Figure 2: Layout and fieldbus networks Intelligent devices are directly connected to Profibus PA, operating at 31.25 kbit/s. Conventional devices are connected to analog or digital modules on remote I/O stations (ET200M® from Siemens), which communicate on Profibus DP, running at 1.5 Mbit/s. 3.1 Network PLC1 To cover the instrumentation distributed along the magnets and the QRL, three DP and two PA segments have been used. The sensors that will be used in the LHC machine are distributed over two DP segments, each of them 150 m long. If one of these is down, the sensors on the other will still be enough to run the machine. Each segment comprises 4 remote I/O stations, housed in crates under each dipole, as for the LHC machine. The third DP segment, extending for about 250 m, gathers instrumentation specific to the experimental program of String 2. Sixteen I/O stations are accommo- dated in ten racks behind the QRL, whereas 8 other are directly hooked on the QRL. Also on this DP segment are the two PA segments; they include 7 intelligent valves and 3 pressure sensors, installed at one end of the QRL, and 2 valves at the other end. The PLC and some I/O stations are installed in two racks. 3.2 Network PLC2 Most of the DFB instrumentation is grouped on a single and short DP segment: 8 I/O stations and a PA segment that handles one intelligent valve positioner. The 38 valves, on the cooling inlets of the current leads, are driven by local PLC output modules. All the I/O stations and the PLC are installed in two racks. This configuration is representative of the LHC machine, where the PLC and I/O stations of the DFB will be clustered in radiation protected areas. 8th International Conference on Accelerator & Large Experimental Physics Control Systems, 2001, San Jose, California 195
  • 3. 4 INSTRUMENTATION 4.1 Temperature More than 400 resistive temperature sensors, of three types, are used in String 2 (Table 2). As all of them are non-linear, the measured resistance is converted into temperature by an interpolation table. Each Cernox™ and Carbon have a specific table, whereas all Platinum have the same one. Table 2: temperature sensors Type Quantity range covered Platinum 295 300 K … 30 K Cernox™ 115 300 K … 1.6 K Carbon 22 100 K … 1.6 K In general, Platinum thermometers are directly read by analog input modules as a four-wire resistor, without any intermediate signal conditioning. Most of the Cernox™ and Carbon thermometers are read through linear multi-range signal conditioners (STMS), which produce 4-20 mA magnitude and two bits indicating the range. Logarithmic signal conditioners (LOG) are used for sampling rates faster than a few seconds and have a single 4-20 mA output. Both STMS and LOG are in-house developments [3]. In the current leads, galvanic isolation up to 5 kV is provided by: • IPAC® conditioners for 190 Platinum thermometers • STMS conditioners and fuses for 6 Cernox™ . 4.2 Pressure On pipes and vessels, absolute pressures up to 100 mbar or to 25 bar are measured by warm transducers, with integrated electronics; three of them operate on Profibus PA whereas 16 other have 4-20mA outputs. The cold mass pressures are measured by 11 passive low- voltage sensors, immersed in liquid helium; their signal conditioners have 4-20mA outputs. 4.3 Liquid Level The eight liquid helium levels inside the vessels and in the superfluid heat exchanger are measured with superconducting-wire gauges (Twickenham Scientific Instruments). To minimize self-heating, the sensors are read in 3s pulsed-mode. The output is 4-20 mA. 4.4 Flow Two mass-flow controllers, ten mass-flow meters and two cryogenic Coriolis mass flow-meters are used to control flow rates and to assess thermal performances. They are read via 4-20 mA current-loops. 4.5 Heaters Electrical heaters are used to warm-up cold gaseous helium leaving String 2, and to evaporate liquid helium in phase separators and in the magnet cold masses. Twenty-one low-power heaters are driven by level modulated DC voltage. Five higher power heaters, up to 64 kW, are supplied through 220 VAC solid state relays, via the PWM technique. Most of these are in series with programmable relays (Sineax), activated according to the temperature of the respective heating element. 4.6 Valves Ten pneumatic valves with intelligent positioners (Sipart® PS2, from Siemens) are spread on the two Profibus PA segments. Thirty-four classical analog valves are driven with 4-20 mA. Five on/off valves are driven by 0-24 V digital outputs. 5 COMMISSIONING Starting in April 2001, most of the instrumentation and control was checked while the last components were being assembled. Every instrument had its signal chain verified from the machine to the PLC and to the SCADA. This included cabling, signal processing, coherence between PLC and SCADA databases, and synoptic view. Phases, interlocks and alarms were tested by changing thresholds, while the actuators were inhibited. Before the final closure of the vacuum vessel, several problems were identified. They were repaired whenever the instrument or cables were still accessible. The origin of these issues has been traced to: • sensor name and serial number mismatch; • installation procedure not followed; • broken wires, sensors failure. All instruments required for the cooling loops were available when cool-down from 300 K to 4.5 K started, on August 7. The process was gradually set into auto- matic mode, and the machine could be left unattended. Apart from the unavoidable time spent for trouble- shooting the components and instrumentation not operating as expected, the overall cool-down from 300 K to 1.9 K took just over 2 weeks, as expected. Once at nominal temperature (1.9 K), the dipole and quadrupole circuits were powered to nominal current (11 850 A). Only then, the control loops were fine-tuned, and cold- mass thermometers and pressure sensors were verified for high accuracy. During cool-down, the analysis of temperature pro- files showed additional inversions and identification errors, mainly on the current leads thermometers. 6 CONCLUSION The installation and commissioning of String 2 cryo- genic instrumentation and control was very educative, in view of the methods to be implemented for LHC. The structure of software and hardware documentation was enhanced. Software routines were improved. In the future, sensors installation procedures must be carefully respect- ed, in terms of materials, positioning, and follow-up documentation. In this way, precious time can be saved. We wish to express our acknowledgement to the operators team, who gave us valuable help during the commissioning of instruments and programs. REFERENCES [1] F. Bordry et al., “The LHC Test String 2: Design Study”, LHC Project Report, March 1998. [2] L. Serio, “The Process of the Cryogenic System for String 2: Functional Analysis”, LHC-XMS-ES-0004, LHC Engeneering Specification, Feb 2001. [3] J. Casas et al., “Signal Conditioning for Cryogenic Thermometry in the LHC”, CEC/IMC99, Montreal, Canada, July 1999. 8th International Conference on Accelerator & Large Experimental Physics Control Systems, 2001, San Jose, California 196