SlideShare a Scribd company logo
1 of 62
11
NFPA 70ENFPA 70E
Electrical Safety StandardElectrical Safety Standard
- Get prepared, set the record straight, be “up front”
> Most of you will resist, few will appreciate
> Huge change (For you, burden rate, admin)
> Won’t want to hear or see
> Not trying to harass you, make uncomfortable (Hot!)
> Arc Flash, not our only safety concern
> Your safety & our compliance (Thankful & Grateful?)
22
Standards InteractionStandards Interaction
OSHA 29 CFR 1910
SUBPART S
NFPA 70-E
National Electric Code
IEEE Std 1584-2002
NFPA-70
(Institute of Electrical & Electronics Engineers)
33
44
CD_Opening_2.flv
CD_Opening_2.flv
55
Standards InteractionStandards Interaction
From NFPA 70E Handbook, 2004 Edition, p17 (Explanatory Commentary)
“Fire, shock, and electrocution have been considered to be electrical hazards for many
years. Since the publication of NFPA 70E, 1995 edition, arc flash has been considered
to be an electrical hazard. The arc flash hazard currently is defined to consider only the
thermal aspects of an arcing fault. Other hazards include flying parts and pieces and
the pressure wave that is generated in an arcing fault. Other electrical hazards also
might be associated with an arcing fault.”
66
History of Electrical SafetyHistory of Electrical Safety
77
History of Electrical Safety
NECA = National Electrical Contractors Association
IBEW = International Brotherhood of Electrical Workers
88
NFPA 70E LabelsNFPA 70E Labels
99
may7_clip2_edit2.flv
1010
History of Electrical SafetyHistory of Electrical Safety
1111
Regulatory RequirementRegulatory Requirement
• Per OSHA RulePer OSHA Rule andand NFPA 70E :NFPA 70E :
DO NOT WORK ON EQUIPMENT HOTDO NOT WORK ON EQUIPMENT HOT
(Maintenance or Repair)(Maintenance or Repair)
 Equipment must be put in an electricallyEquipment must be put in an electrically
safe work condition prior tosafe work condition prior to
maintenance.maintenance.
1212
It’s The LawIt’s The Law
But. . .But. . .
• We must test live circuits before repairs are done.We must test live circuits before repairs are done.
• Even after Lock Out / Tag Out, we must verify theEven after Lock Out / Tag Out, we must verify the
absence of voltage – “not dead until tested dead”.absence of voltage – “not dead until tested dead”.
• During this process, a worker could be exposed toDuring this process, a worker could be exposed to
electrical hazards.electrical hazards.
• Troubleshooting work requires that the power beTroubleshooting work requires that the power be
left on.left on.
1313
Necessary LoopholeNecessary Loophole
Because of this there are two exceptions toBecause of this there are two exceptions to “THE“THE
RULE”.RULE”.
1.1. Where de-energizing would introduce increased or additionalWhere de-energizing would introduce increased or additional
hazards.hazards.
2.2. Where killing power is “infeasible” due to equipment design orWhere killing power is “infeasible” due to equipment design or
operational limitations (like voltage testing).operational limitations (like voltage testing).
-1910. 333 (a) (1), Subpart S-1910. 333 (a) (1), Subpart S
1414
NFPA 70 E StandardNFPA 70 E Standard
1.1. Safety –Related Work PracticesSafety –Related Work Practices
 Hazard Analyses for shock and flashHazard Analyses for shock and flash
 Approach boundariesApproach boundaries
 Personal Protective EquipmentPersonal Protective Equipment
 TrainingTraining
1.1. Safety-Related Maintenance RequirementsSafety-Related Maintenance Requirements
 Maintaining electrical components, wiring, equipment in a safeMaintaining electrical components, wiring, equipment in a safe
conditioncondition
1.1. Safety Requirements for Special EquipmentSafety Requirements for Special Equipment
 Batteries, Lasers and power electronic equipBatteries, Lasers and power electronic equip
1.1. Installation Safety RequirementsInstallation Safety Requirements
 Truncated version of NECTruncated version of NEC
 Not to be used in lieu of NECNot to be used in lieu of NEC
Major Work
Practice
Requirements
1515
NFPA 70E - RequirementsNFPA 70E - Requirements
 Electrical Safety Program ElementsElectrical Safety Program Elements
 Awareness training for employees who work on orAwareness training for employees who work on or
near exposed energized electrical conductorsnear exposed energized electrical conductors
 Inspection/evaluation of electrical equipmentInspection/evaluation of electrical equipment
 Identify hazards – hazard/risk evaluation prior to workIdentify hazards – hazard/risk evaluation prior to work
on or near live parts operating at 50 volts or more oron or near live parts operating at 50 volts or more or
where an electrical hazard existswhere an electrical hazard exists
 Conduct an Electrical Hazard AnalysisConduct an Electrical Hazard Analysis
(For everyone, de-energized work)
1616
Electrical Safety Program Elements – Con’tElectrical Safety Program Elements – Con’t
 Develop procedures for jobsDevelop procedures for jobs

Work permits - procedures for working on or nearWork permits - procedures for working on or near
live partslive parts >> 50 volts or where an electrical hazard50 volts or where an electrical hazard
exists before work is started.exists before work is started.
 Protect employees from shock, burn, blast,Protect employees from shock, burn, blast,
and other hazardsand other hazards
 Use electrically rated toolsUse electrically rated tools
 Perform a job briefing prior to each jobPerform a job briefing prior to each job
 Perform AuditsPerform Audits
Troubleshooting
Exemption
Working it hot (Maintenance & Repair)
1717
NFPA 70E - RequirementsNFPA 70E - Requirements
 Safety Training –Safety Training –
 Classroom or on-the-job or a combination dependingClassroom or on-the-job or a combination depending
on the risk to the employeeon the risk to the employee
 Emergency procedures - for employees working on orEmergency procedures - for employees working on or
near exposed energized electrical conductors ornear exposed energized electrical conductors or
circuit parts:circuit parts:
 Methods of release of victims from contact with exposedMethods of release of victims from contact with exposed
energized conductors or circuit partsenergized conductors or circuit parts
 First Aid, resuscitation, etc.First Aid, resuscitation, etc.
Working it hot (Maintenance & Repair)
1818
NFPA 70E - RequirementsNFPA 70E - Requirements
 Qualified Person – shall be trained and knowledgeable of theQualified Person – shall be trained and knowledgeable of the
construction and operation of equipment or a specific work methodconstruction and operation of equipment or a specific work method
and trained to recognize and avoid the electrical hazards that mightand trained to recognize and avoid the electrical hazards that might
be present with respect to that equipment or work method.be present with respect to that equipment or work method.
Only Qualified Persons are authorizedOnly Qualified Persons are authorized
to work on or near live partsto work on or near live parts
(For everyone, de-energized work)
1919
Creating an NFPA 70ECreating an NFPA 70E
Compliant ProgramCompliant Program
 Develop Electrical Safety ProgramDevelop Electrical Safety Program
 Written electrical safety procedure SafeWritten electrical safety procedure Safe
work practiceswork practices
 Training requirements PPE requirementsTraining requirements PPE requirements
Conduct Shock and Flash Hazard Analyses on allConduct Shock and Flash Hazard Analyses on all
electrical equipment to determine appropriate levels ofelectrical equipment to determine appropriate levels of
protectionprotection
 Train and outfit all affected personnelTrain and outfit all affected personnel
Where do we go from here ?
2020
Start With a Hazard Risk AnalysisStart With a Hazard Risk Analysis
Hazard/Risk Analysis is a decision making process:Hazard/Risk Analysis is a decision making process:
• Evaluate equipment and circuitEvaluate equipment and circuit
information to determine the degree andinformation to determine the degree and
extent of hazardsextent of hazards
• Determine “Determine “ShockShock Approach BoundariesApproach Boundaries””
• DetermineDetermine ““Flash Protection BoundaryFlash Protection Boundary””
• DetermineDetermine “Incident Energy Exposure”“Incident Energy Exposure”
• Determine appropriate PersonalDetermine appropriate Personal
Protective Equipment (PPE)Protective Equipment (PPE)
Must perform Shock and Flash Hazard Analyses when working “on or
near” energized parts (within Limited Approach Boundary).
2121
Shock Hazard AnalysisShock Hazard Analysis
 Protects againstProtects against ContactContact with energized equipmentwith energized equipment
 Use highest voltage level of exposureUse highest voltage level of exposure
 Boundary distance based solely on voltageBoundary distance based solely on voltage
 Boundaries drawn from table in standard – no calcs necessary:Boundaries drawn from table in standard – no calcs necessary:
 LimitedLimited – a safe approach boundary. Only qualified– a safe approach boundary. Only qualified
employees and escorted unqualified employees mayemployees and escorted unqualified employees may
crosscross
 RestrictedRestricted – Only qualified employees may cross.– Only qualified employees may cross.
When working within this boundary, must use specialWhen working within this boundary, must use special
precautionary techniques and PPEprecautionary techniques and PPE
 ProhibitedProhibited – Only qualified employees protected by– Only qualified employees protected by
insulating materialsinsulating materials
2222
FLASH BOUNDARIESFLASH BOUNDARIES
Limited Shock Boundary: Qualified or Unqualified Persons*
* Only if accompanied by Qualified Person
Prohibited Shock Boundary: Qualified Persons Only. PPE as
if direct contact with live part
Restricted Shock Boundary: Qualified Persons Only
Note: shock boundaries dependent on system voltage level
Flash Protection Boundary (FPB)
Must wear appropriate PPE
FPB dependent on fault level and time duration.
Flash Protection Boundary (FPB)
Must wear appropriate PPE
FPB dependent on fault level and time duration.
Equipment
2323
Approach BoundariesApproach Boundaries
Restricted
Approach
Boundary
Condition
Nominal System
Voltage Range,
Phase to Phase
Exposed
Movable
Conductor
Exposed Fixed
Circuit Part
Includes
Inadvertent
Movement
Adder
Prohibited
Approach
Boundary
1 0 to 50 Not Specified Not Specified Not Specified Not Specified
2 51 to 300 10 ft. 0 in. 3 ft. 6 in. Avoid Contact Avoid Contact
3 301 to 750 10 ft. 0 in. 3 ft. 6 in. 1 ft. 0 in. 0 ft. 1 in.
4 751 to 15kV 10 ft. 0 in. 5 ft. 0 in. 2 ft. 2 in. 0 ft. 7 in.
5 15.1kV to 36kV 10 ft. 0 in. 6 ft. 0 in. 2 ft. 7 in. 0 ft. 10 in.
Limited Approach Boundary
1. “Limited” Boundary - Must be Qualified Person
2. “Restricted” Boundary - Must wear Electrical PPE
3. “Prohibited” Boundary - Must wear PPE as if direct contact is being made.
Working with Control Panel door open – in Restricted Approach Boundary
2424
Arc Flash BoundaryArc Flash Boundary
 To protect from thermal burn due to arc flashTo protect from thermal burn due to arc flash
 Electrical systems 600V or less:Electrical systems 600V or less:
 4 feet, or4 feet, or
 The calculated distance based on establishedThe calculated distance based on established
algorithmsalgorithms
 Electrical systems over 600V:Electrical systems over 600V:
 Boundary based on incident energy as calculated orBoundary based on incident energy as calculated or
as given in default tables in Standardas given in default tables in Standard
Work within the Flash Boundary will require electrical PPE to
protect the employee from arc flash injury
(Good rule of thumb is 10 feet)
2525
Flash Hazard AnalysisFlash Hazard Analysis
 Designed to prevent injury from the heat generated in anDesigned to prevent injury from the heat generated in an
arc event – not contactarc event – not contact
 A Flash Hazard Analysis Shall Determine:A Flash Hazard Analysis Shall Determine:
 Flash BoundaryFlash Boundary
 Approach boundary from exposed energized parts within which aApproach boundary from exposed energized parts within which a
person without proper PPE could receive beyond a 2person without proper PPE could receive beyond a 2ndnd
degree burndegree burn
 Incident heat energy of possible arc flash based on:Incident heat energy of possible arc flash based on:
 Available fault currentAvailable fault current
 Fault clearing timeFault clearing time
 Distance from exposed equipmentDistance from exposed equipment
 Directional dissipation of energy (arc-in-the-box scenarios)Directional dissipation of energy (arc-in-the-box scenarios)
 PPE Requirements within the Flash BoundaryPPE Requirements within the Flash Boundary
2626
Arc Flash HazardsArc Flash Hazards
 Electric arcs produce some of the highest temperaturesElectric arcs produce some of the highest temperatures
known to occur on earth – up to 35,000known to occur on earth – up to 35,000
00
degrees Fahrenheit.degrees Fahrenheit.
This is four times the surface temperature of the sun (This is four times the surface temperature of the sun ( 90009000
00
FF))
 All known materials are vaporized at this temperature. WhenAll known materials are vaporized at this temperature. When
materials vaporize they expand in volume (Copper – 67,000materials vaporize they expand in volume (Copper – 67,000
times, Water–1670 times). The air blast can spread moltentimes, Water–1670 times). The air blast can spread molten
metal to great distances with force.metal to great distances with force.
 Rapidly expanding gases, extreme pressure and soundRapidly expanding gases, extreme pressure and sound
waves, molten metal and metal plasma.waves, molten metal and metal plasma.
2727
Arc Flash HazardsArc Flash Hazards
 Pressure: Blast pressure waves have thrownPressure: Blast pressure waves have thrown
workers across rooms and knocked them offworkers across rooms and knocked them off
ladders. Pressure on the chest can be higherladders. Pressure on the chest can be higher
than 2000 lbs/ sq. ft. – blows clothing off body.than 2000 lbs/ sq. ft. – blows clothing off body.
 Clothing can be ignited several feet away.Clothing can be ignited several feet away.
Clothed areas can be burned more severelyClothed areas can be burned more severely
than exposed skin.than exposed skin.
 Hearing loss from sound blast. The sound canHearing loss from sound blast. The sound can
have a magnitude as high as 140 dB at ahave a magnitude as high as 140 dB at a
distance of 2 feet from the arc.distance of 2 feet from the arc.
Sound Pressure ie. Mechanical pressureSound Pressure ie. Mechanical pressure
IHOH Safety & Health Training /IHOH Safety & Health Training /
EducationEducation 2828
2929
Arc Flash CausesArc Flash Causes
 Dust and impuritiesDust and impurities - Dust and impurities on insulating surfaces- Dust and impurities on insulating surfaces
can provide a path for current, allowing it to flashover andcan provide a path for current, allowing it to flashover and
create arc discharge across the surface.create arc discharge across the surface.
 CorrosionCorrosion - Corrosion of equipment creates impurities on- Corrosion of equipment creates impurities on
insulating surfaces. Corrosion also weakens the contactinsulating surfaces. Corrosion also weakens the contact
between conductor terminals, increasing the contact resistancebetween conductor terminals, increasing the contact resistance
through oxidation or other contamination. Heat is generated onthrough oxidation or other contamination. Heat is generated on
the contacts; sparks may be produced; can lead to arcing faultsthe contacts; sparks may be produced; can lead to arcing faults
closest ground source.closest ground source.
 Condensation -Condensation - water vapor can drip causing tracking on thewater vapor can drip causing tracking on the
surface of insulating materials. Can create a flashover tosurface of insulating materials. Can create a flashover to
ground.ground.
 Spark discharge –Spark discharge – Accidental contact; dropping toolsAccidental contact; dropping tools
 Overvoltage across narrow gapsOvervoltage across narrow gaps
 Failure of insulating materialsFailure of insulating materials
 Improper work proceduresImproper work procedures
3030
Arc Flash in Our EquipmentArc Flash in Our Equipment
 Don’t have to beDon’t have to be “working on”“working on” a circuit for an arc flash to occur.a circuit for an arc flash to occur.
Accidental contact is the most common cause of arc flash events.Accidental contact is the most common cause of arc flash events.
 For a low voltage system (480 V), a 3 to 4-inch arc can becomeFor a low voltage system (480 V), a 3 to 4-inch arc can become
“stabilized” and persist for an extended period of time if circuit does“stabilized” and persist for an extended period of time if circuit does
not operate.not operate.
 Energy released is a function of system voltage, fault currentEnergy released is a function of system voltage, fault current
magnitude and fault duration.magnitude and fault duration.
 Arcs in enclosures, such as a Motor Control Center (MCC) or panelArcs in enclosures, such as a Motor Control Center (MCC) or panel
board, magnify blast and energy transmitted as the blast is forced toboard, magnify blast and energy transmitted as the blast is forced to
the open side of the enclosure and toward the worker (Arc-in-the-the open side of the enclosure and toward the worker (Arc-in-the-
Box).Box).
3131
Small arc – burn
to hand
Medium arc – burn to
hand, arm and chest
Severe arc – whole
body burns
Ionization cloud
barely visible
Clearly visible ionized
gas
Exploding plasma of
gases and vaporized
metal
Arc Flash in a PanelboardArc Flash in a Panelboard
3232
10 minute break
Brief video clip of arc flash
in switchgear
Five to Ten Arc Flash Explosions occur in electric equipment every day in the U.S
(Based on statistics compiled by Cap Schell, Inc., a Chicago based research and consulting firm that
specializes in preventing workplace injuries and death)
Bureau of Labor Statistics data for 1994 show 11,153 cases of reported days away from work were due to
electrical burns, electrocution / electrical shock injuries, fires and explosions.
The Census of Fatal Injuries noted 548 employees died from the causes of electrical current exposure, fires
and explosions out of 6,588 work related fatalities nationwide.
3333
Flash Hazard AnalysisFlash Hazard Analysis
 Determines the Flash Protection BoundaryDetermines the Flash Protection Boundary
 Determines the required PPEDetermines the required PPE
 2 Methods available:2 Methods available:
1.1. Can use Default Tables in the NFPA 70E StandardCan use Default Tables in the NFPA 70E Standard
 Classifies work tasks in a specific Hazard RiskClassifies work tasks in a specific Hazard Risk
Category (HRC)Category (HRC)
 Specifies required PPE as a function of HRCSpecifies required PPE as a function of HRC
1.1. Can calculate the incident energy to employees if a faultCan calculate the incident energy to employees if a fault
occurred. Can then specify the required PPE based onoccurred. Can then specify the required PPE based on
predicted hazard level.predicted hazard level.
We compared default tables to calculated values:
• Used conservative, but reasonably expected input parameters
• Used 2 different calculation models (took highest values)
• Found calculated values to be less than default tables
3434
Example From Default TableExample From Default Table
• Voltage-rated gloves
• Voltage-rated tools
• Doubled-layered switching hood and hearing protection
• Untreated natural fiber: T-shirt & Long pants
• FR Clothing: Long –sleeve shirt, Pants, Coveralls
• FR Protective Equipment: Hard hat, safety glasses, leather gloves,
leather work shoes
(Note there are footnotes altering above due to fault current levels and
duration. And there are some substitutions permitted.)
Page 55, Table 3-3.9.1/ Page 59,Table 3-3.9.2
600 V Class MCC - Work on energized parts including voltage
testing - What is required?
If You Use the Method #1 Flash Hazard Analysis –
NFPA 70E Default Tables:
Columbia Customer
3535
Example From Default Table, ContinuedExample From Default Table, Continued
3636
Incident Energy & Calories
“Incident Energy-
The amount of energy impressed on a surface, a certain distance from the
source, generated during an electrical arc event. One of the units used
to measure incident energy is calories per centimeter squared ( cal/cm )
The definition of incident energy was added to provide clarity for the user.
Incident energy could be expressed in several different terms, such as
calories per centimeter, joules per square centimeter, or calories per
square inch. However, incident energy must be expressed in the same
terms in which the PPE is thermally rated, which usually is calories per
square centimeter.”
- From NFPA 70E Handbook, 2004 Edition, p. 22 (Text & Explanatory Commentary)
2
(Cigarette lighter produces about 1 cal/cm-sq)
3737
From NFPA 70E Default TablesFrom NFPA 70E Default Tables
Risk
Category
Min. Arc
Rating of
PPE PPE Requirements - NFPA-70E 2004
0 0-2 cal/cm
2
Untreated Cotton; leather gloves; safety glasses
1 2-4 cal/cm
2 FR shirt and pants (or jeans); rubber gloves; safety
glasses; hard hat
2 4-8 cal/cm
2 FR shirt and pants (or jeans); rubber gloves; safety
glasses; hard hat; arc face shield
3 8-25 cal/cm
2 FR shirt and pants; rubber gloves; safety glasses;
hard hat; arc hood; arc jacket
4 25-40 cal/cm
2 FR shirt and pants; rubber gloves; safety glasses;
hard hat; arc hood; multi-layer flash suit
From: NFPA 70E Default Tables
Troubleshooting a 480 V panel is listed in default tables as Hazard Category 2 work.
3838
Work Tasks ImpactedWork Tasks Impacted
Primarily Troubleshooting, Start-Up and Power DownPrimarily Troubleshooting, Start-Up and Power Down
ProceduresProcedures
 Main Disconnect OperationMain Disconnect Operation
 Circuit Breaker OperationCircuit Breaker Operation
 Contactor OperationContactor Operation
 Voltage and Amp ReadingsVoltage and Amp Readings
 Control circuitryControl circuitry
 Power circuitryPower circuitry
 Etc..Etc..
3939
Flash Hazard ThresholdFlash Hazard Threshold
Second Degree
Burn Threshold
1.2 cal/cm2
Note: medical treatment may still be required if bare
skin is exposed to this level of flash - full recovery to be
expected.
Must protect employees from the onset
of 2nd
degree burn
4040
PPE SelectionPPE Selection
From 70E TableFrom 70E Table
For Most Service and Maintenance Work
Limited work on 2300V and 4160V
Synthetic fibers, such as polyester, nylon, acetate, rayon, either alone
or in blends are not permitted – they melt at low temperatures, adhere
to the skin and increase the extent of injury.
Voltage Clothing Gloves Other PPE
Safety Glasses
Hard Hat (if needed)
Safety Glasses
Class E Hard Hat with 8
Cal. ATPV Face Shield
2300-4160
Volts
Safety Glasses
Class E Hard Hat with 8
Cal. ATPV Face Shield
Class 1 Insulated Rubber
Gloves w/ Leather
Protectors
50 - 120 Volts 100% long-sleeve cotton
shirt and pants
Leather Gloves (Class 00 if
possibility of contact)
121 - 600 Volts 100% long-sleeve cotton
or FR shirt and pants
Class 00 or 0 Insulated
Rubber Gloves w/ Leather
Protectors
FR shirt and pants or FR
Coveralls - 9.4 ounce
Indura Ultra Soft (or
equivalent)
For outdoor work, outer layer must be natural fiber or FR
4141
100% Cotton vs. FR Clothing100% Cotton vs. FR Clothing
One Major Exception to the 100% Cotton Rule forOne Major Exception to the 100% Cotton Rule for
480 Volt work:480 Volt work:
When working on (e.g. Voltage testing) the line side terminal ofWhen working on (e.g. Voltage testing) the line side terminal of
a main disconnect at a large industrial customer, weara main disconnect at a large industrial customer, wear
FR clothing as the outer layer instead of 100% cotton.FR clothing as the outer layer instead of 100% cotton.
This is due to the uncertainty of available fault currents and
clearing times with on-site substation transformers and 600
Amp class circuit breakers.
As a result, many Company locations are just
buying FR shirts/pants for all electrical work
4242
100% Cotton vs. FR Clothing100% Cotton vs. FR Clothing
100% cotton will catch on fire & burn, but won’t melt to the burn
making burn worse
FR will not support combustion, that is, it won’t catch on fire and
continue to burn
Tech was seated
cross legged,
brazing slag
‘popped out’
stayed on
pant leg
FR, HRC 2 pants,
(white sheet of paper
Inside pant leg)
4343
Arc Hazards Below 240 VoltsArc Hazards Below 240 Volts
 Rubber gloves and face shield neededRubber gloves and face shield needed
in the 120 - 240 volt range becausein the 120 - 240 volt range because
significant arc hazards may exist suchsignificant arc hazards may exist such
as:as:
 3 Phase, 208 V power circuits supplying equipment3 Phase, 208 V power circuits supplying equipment
in older installations.in older installations.
 Old building infrastructures may not have convertedOld building infrastructures may not have converted
to 480 V systems.to 480 V systems.
Become familiar with the facility electrical distribution
system to fully evaluate the level of hazard.
4444
Electrical PPE RequirementsElectrical PPE Requirements
Electrical PPE (rubber gloves, hard hat / arc face shield,Electrical PPE (rubber gloves, hard hat / arc face shield,
cotton or FR clothing) iscotton or FR clothing) is requiredrequired for troubleshooting,for troubleshooting,
applying LOTO and testing dead. After that,applying LOTO and testing dead. After that,
1.1. The line side terminal of the disconnecting deviceThe line side terminal of the disconnecting device may stillmay still
be energizedbe energized..
2.2. According to this standard, if you areAccording to this standard, if you are “exposed”“exposed” to energizedto energized
parts, electrical PPE is still required.parts, electrical PPE is still required.
 ““Exposed”Exposed” means being within the Limited Approachmeans being within the Limited Approach
Boundary, which is 1 ft, for circuits 120 – 480 V.Boundary, which is 1 ft, for circuits 120 – 480 V.
1.1. You can eliminateYou can eliminate “exposure”“exposure” and remove the PPE if you canand remove the PPE if you can
“Insulate”“Insulate” oror “Isolate”“Isolate” yourself from the energized parts.yourself from the energized parts.
2.2. InsulateInsulate by placing an insulating material over the part.by placing an insulating material over the part.
3.3. IsolateIsolate by placing a rigid barrier over the part to preventby placing a rigid barrier over the part to prevent
contact, or ensure your body and all conductive tools remaincontact, or ensure your body and all conductive tools remain
> 1 ft. away.> 1 ft. away.
PPE requirements based on your distance from “Exposed
Energized Parts”, not the equipment you’re working on
4545
Amperage Testing
4646
Voltage Testing
4747
480 Volt Fused Disconnect Switch
4848
Current-Limiting Fuse
(handout, page 5, question 2)
4949
Current-Limiting Fuse
5050
Current-Limiting FusingCurrent-Limiting Fusing
5151
4160 Volt Starter Cabinet
5252
High Voltage Fuse
5353
Electrical Safety ProcedureElectrical Safety Procedure
Customized for HVAC Service andCustomized for HVAC Service and
Contracting Business:Contracting Business:
 Work ProceduresWork Procedures
 Electrical PPEElectrical PPE
 Protective ClothingProtective Clothing
 TrainingTraining
5454
Electrical Safety ProcedureElectrical Safety Procedure
1.1. Work Procedures:Lockout/Tagout wheneverWork Procedures:Lockout/Tagout whenever
possible – Cardinal Rulepossible – Cardinal Rule
 Approach Boundaries - Based on voltageApproach Boundaries - Based on voltage
 Use of non-conductive tools, materials, equipmentUse of non-conductive tools, materials, equipment
 Insulated tools and equipmentInsulated tools and equipment
 Test Instruments and equipmentTest Instruments and equipment
 Protective Shielding EquipmentProtective Shielding Equipment
 Portable LaddersPortable Ladders
 Safety InterlocksSafety Interlocks
 Use of GFCIsUse of GFCIs
5555
Electrical Safety ProcedureElectrical Safety Procedure
2.2. Electrical PPEElectrical PPE
 Required when working within the LimitedRequired when working within the Limited
Approach BoundaryApproach Boundary
 Flash Hazard Analysis dictates what mustFlash Hazard Analysis dictates what must
be wornbe worn
 Can use NFPA 70E default tables, orCan use NFPA 70E default tables, or
 Can perform customized analysisCan perform customized analysis
 Includes Hand; Head and Face; WholeIncludes Hand; Head and Face; Whole
Body protectionBody protection
5656
Electrical Safety TrainingElectrical Safety Training
Electrical Safety Training Broken DownElectrical Safety Training Broken Down
into 4 Modules:into 4 Modules:
1.1. Awareness LevelAwareness Level
2.2. Basic ElectricityBasic Electricity
3.3. Low Voltage Practices (50-600 V)Low Voltage Practices (50-600 V)
4.4. High Voltage Practices ( > 600 V)High Voltage Practices ( > 600 V)
5757
Electrical Safety PPEElectrical Safety PPE
5858
PPE EnsemblesPPE Ensembles
Hazard Risk
Category 0
Hazard Risk
Category 1
Hazard Risk
Category 2
Hazard Risk
Category 3
Hazard Risk
Category 4
5959
Qualified Person TrainingQualified Person Training
 Basic RequirementsBasic Requirements
1.1. Must have knowledge of construction and operation of equipment and specificMust have knowledge of construction and operation of equipment and specific
work methods to recognize and avoid electrical hazards while performingwork methods to recognize and avoid electrical hazards while performing
work.work.
2.2. Must be familiar with the precautionary techniques, PPE, insulating andMust be familiar with the precautionary techniques, PPE, insulating and
shielding materials, insulated tools and test equipment.shielding materials, insulated tools and test equipment.
 Specific RequirementsSpecific Requirements
1.1. Able to distinguish exposed energized parts from other partsAble to distinguish exposed energized parts from other parts
2.2. Able to determine nominal voltage of exposed live partsAble to determine nominal voltage of exposed live parts
3.3. Approach distances and corresponding voltages in the StandardApproach distances and corresponding voltages in the Standard
4.4. Determine degree of hazard and appropriate PPEDetermine degree of hazard and appropriate PPE
Required by OSHA (via Sec. 5a1) and NFPA 70E
Training can be either classroom, on-the-job, or a combination.
OJT requires direct supervision by a Qualified Person.
Supplemental
Training Needs
6060
Laredo, TX 6/05
2 Contract
Electricians in
arc flash event
3rd
deg burns;
clothing
ignited; victims
survived
6161
Focus On Engineering andFocus On Engineering and
Admin ControlsAdmin Controls
OSHA 1910. 335 “Safeguards for personnel protection”OSHA 1910. 335 “Safeguards for personnel protection”
((a) (2) (ii)a) (2) (ii)
““Protective shields, protective barriers, or insulatingProtective shields, protective barriers, or insulating
materials shall be used to protect each employee frommaterials shall be used to protect each employee from
shock, burns, or electrically related injuries while thatshock, burns, or electrically related injuries while that
employee is working near exposed energized parts whichemployee is working near exposed energized parts which
might be accidentally contacted or where dangerousmight be accidentally contacted or where dangerous
electric heating or arcing might occur. When normallyelectric heating or arcing might occur. When normally
enclosed live parts are exposed for maintenance or repair,enclosed live parts are exposed for maintenance or repair,
they shall be guarded to protect unqualified persons fromthey shall be guarded to protect unqualified persons from
contact with the live part.”contact with the live part.”
6262
Thank You – Questions??

More Related Content

What's hot

Arc Flash Safety by Murray State University
Arc Flash Safety by Murray State UniversityArc Flash Safety by Murray State University
Arc Flash Safety by Murray State University
Atlantic Training, LLC.
 
Practical Arc Flash Protection for Electrical Safety Professionals
Practical Arc Flash Protection for Electrical Safety ProfessionalsPractical Arc Flash Protection for Electrical Safety Professionals
Practical Arc Flash Protection for Electrical Safety Professionals
Living Online
 
Arc Flash Energy Protection by EWB Engineering
Arc Flash Energy Protection by EWB EngineeringArc Flash Energy Protection by EWB Engineering
Arc Flash Energy Protection by EWB Engineering
Atlantic Training, LLC.
 
Arc Blast Flash
Arc Blast FlashArc Blast Flash
Arc Blast Flash
jboullemet
 
Introduction to Arc Flash - Revisions to the NFPA 70E, Electrically Safe Wor...
Introduction to Arc Flash - Revisions to the NFPA 70E, Electrically Safe Wor...Introduction to Arc Flash - Revisions to the NFPA 70E, Electrically Safe Wor...
Introduction to Arc Flash - Revisions to the NFPA 70E, Electrically Safe Wor...
Thorne & Derrick International
 
Changes to nfpa 70 e standard for electrical safety
Changes to nfpa 70 e standard for electrical safetyChanges to nfpa 70 e standard for electrical safety
Changes to nfpa 70 e standard for electrical safety
vtsiri
 
Electrical Safety Awareness Training by Albert Einstein College of Medicine
Electrical Safety Awareness Training by Albert Einstein College of MedicineElectrical Safety Awareness Training by Albert Einstein College of Medicine
Electrical Safety Awareness Training by Albert Einstein College of Medicine
Atlantic Training, LLC.
 
Masonry Electrical Safety Training by Rocky Mountain Masonry Institute
Masonry Electrical Safety Training by Rocky Mountain Masonry InstituteMasonry Electrical Safety Training by Rocky Mountain Masonry Institute
Masonry Electrical Safety Training by Rocky Mountain Masonry Institute
Atlantic Training, LLC.
 
Arc Flash Analysis Training by Illinois Institute of Technology
Arc Flash Analysis Training by Illinois Institute of TechnologyArc Flash Analysis Training by Illinois Institute of Technology
Arc Flash Analysis Training by Illinois Institute of Technology
Atlantic Training, LLC.
 

What's hot (20)

Arc Flash Safety by Murray State University
Arc Flash Safety by Murray State UniversityArc Flash Safety by Murray State University
Arc Flash Safety by Murray State University
 
Electrical Safety Training by ISRI
Electrical Safety Training by ISRIElectrical Safety Training by ISRI
Electrical Safety Training by ISRI
 
Practical Arc Flash Protection for Electrical Safety Professionals
Practical Arc Flash Protection for Electrical Safety ProfessionalsPractical Arc Flash Protection for Electrical Safety Professionals
Practical Arc Flash Protection for Electrical Safety Professionals
 
Arc Flash Energy Protection by EWB Engineering
Arc Flash Energy Protection by EWB EngineeringArc Flash Energy Protection by EWB Engineering
Arc Flash Energy Protection by EWB Engineering
 
Arc Flash Safety by BLR
Arc Flash Safety by BLRArc Flash Safety by BLR
Arc Flash Safety by BLR
 
Significant Changes To NFPA 70E by Hoydar Buck, Inc
Significant Changes To NFPA 70E by Hoydar Buck, IncSignificant Changes To NFPA 70E by Hoydar Buck, Inc
Significant Changes To NFPA 70E by Hoydar Buck, Inc
 
Electrical Hazards by Cooper Bussmann
Electrical Hazards by Cooper BussmannElectrical Hazards by Cooper Bussmann
Electrical Hazards by Cooper Bussmann
 
Arc Blast Flash
Arc Blast FlashArc Blast Flash
Arc Blast Flash
 
NFPA 70E Electrical Safety in the Workplace by Hortica
NFPA 70E  Electrical Safety in the Workplace by HorticaNFPA 70E  Electrical Safety in the Workplace by Hortica
NFPA 70E Electrical Safety in the Workplace by Hortica
 
Dl arc flash presentation2013 r3
Dl arc flash presentation2013 r3Dl arc flash presentation2013 r3
Dl arc flash presentation2013 r3
 
Introduction to Arc Flash - Revisions to the NFPA 70E, Electrically Safe Wor...
Introduction to Arc Flash - Revisions to the NFPA 70E, Electrically Safe Wor...Introduction to Arc Flash - Revisions to the NFPA 70E, Electrically Safe Wor...
Introduction to Arc Flash - Revisions to the NFPA 70E, Electrically Safe Wor...
 
Arc Flash Solutions
Arc Flash SolutionsArc Flash Solutions
Arc Flash Solutions
 
Changes to nfpa 70 e standard for electrical safety
Changes to nfpa 70 e standard for electrical safetyChanges to nfpa 70 e standard for electrical safety
Changes to nfpa 70 e standard for electrical safety
 
Electrical Safety In The Workplace by Crawford Engineering Services
Electrical Safety In The Workplace by Crawford Engineering ServicesElectrical Safety In The Workplace by Crawford Engineering Services
Electrical Safety In The Workplace by Crawford Engineering Services
 
Arc Flash Training
Arc Flash TrainingArc Flash Training
Arc Flash Training
 
Electrical Safety Awareness Training by Albert Einstein College of Medicine
Electrical Safety Awareness Training by Albert Einstein College of MedicineElectrical Safety Awareness Training by Albert Einstein College of Medicine
Electrical Safety Awareness Training by Albert Einstein College of Medicine
 
Electrical safety
Electrical safetyElectrical safety
Electrical safety
 
Masonry Electrical Safety Training by Rocky Mountain Masonry Institute
Masonry Electrical Safety Training by Rocky Mountain Masonry InstituteMasonry Electrical Safety Training by Rocky Mountain Masonry Institute
Masonry Electrical Safety Training by Rocky Mountain Masonry Institute
 
Arc flash analysis and electrical hazards
Arc flash analysis and electrical hazardsArc flash analysis and electrical hazards
Arc flash analysis and electrical hazards
 
Arc Flash Analysis Training by Illinois Institute of Technology
Arc Flash Analysis Training by Illinois Institute of TechnologyArc Flash Analysis Training by Illinois Institute of Technology
Arc Flash Analysis Training by Illinois Institute of Technology
 

Viewers also liked

Permitting part3 9.2.2010
Permitting part3 9.2.2010Permitting part3 9.2.2010
Permitting part3 9.2.2010
CCSE Host
 
PAT NFPA 70E Compliance Presentation
PAT NFPA 70E Compliance PresentationPAT NFPA 70E Compliance Presentation
PAT NFPA 70E Compliance Presentation
Merci Flores-Magari
 

Viewers also liked (20)

Electrical hazards & safety training
Electrical hazards & safety trainingElectrical hazards & safety training
Electrical hazards & safety training
 
HVM NFPA 70E White Paper
HVM NFPA 70E White PaperHVM NFPA 70E White Paper
HVM NFPA 70E White Paper
 
Permitting part3 9.2.2010
Permitting part3 9.2.2010Permitting part3 9.2.2010
Permitting part3 9.2.2010
 
Safety in maintenance process, By B C Das
Safety in maintenance process, By B C DasSafety in maintenance process, By B C Das
Safety in maintenance process, By B C Das
 
Safety grounding lightning protection and building
Safety grounding lightning protection and buildingSafety grounding lightning protection and building
Safety grounding lightning protection and building
 
Ee09 801 eed ppt
Ee09 801 eed pptEe09 801 eed ppt
Ee09 801 eed ppt
 
PAT NFPA 70E Compliance Presentation
PAT NFPA 70E Compliance PresentationPAT NFPA 70E Compliance Presentation
PAT NFPA 70E Compliance Presentation
 
Electrical Arc Flash Safety and Risk Management
Electrical Arc Flash Safety and Risk ManagementElectrical Arc Flash Safety and Risk Management
Electrical Arc Flash Safety and Risk Management
 
Electrical Measurment Safety
Electrical Measurment SafetyElectrical Measurment Safety
Electrical Measurment Safety
 
Electrical Hazard & Safety
Electrical Hazard & SafetyElectrical Hazard & Safety
Electrical Hazard & Safety
 
Electrical Hazards on Airport
Electrical Hazards on AirportElectrical Hazards on Airport
Electrical Hazards on Airport
 
Risk and hazard
Risk and hazardRisk and hazard
Risk and hazard
 
Inspecting Photovoltaic (PV) Systems for Code Compliance
Inspecting Photovoltaic (PV) Systems for Code ComplianceInspecting Photovoltaic (PV) Systems for Code Compliance
Inspecting Photovoltaic (PV) Systems for Code Compliance
 
Effective Workplace Safety Inspections
Effective Workplace Safety InspectionsEffective Workplace Safety Inspections
Effective Workplace Safety Inspections
 
Electrical Installation Design Project_DUBAI STANDARD_ by Mohnad Ibrahim
Electrical Installation Design Project_DUBAI STANDARD_ by Mohnad IbrahimElectrical Installation Design Project_DUBAI STANDARD_ by Mohnad Ibrahim
Electrical Installation Design Project_DUBAI STANDARD_ by Mohnad Ibrahim
 
Solar PV Codes and Standards
Solar PV Codes and StandardsSolar PV Codes and Standards
Solar PV Codes and Standards
 
National Electrical Code: 2014 Code Changes
National Electrical Code: 2014 Code ChangesNational Electrical Code: 2014 Code Changes
National Electrical Code: 2014 Code Changes
 
Fire Safety
Fire SafetyFire Safety
Fire Safety
 
Introduction on indian codes as applied in electrical design
Introduction on indian codes as applied in electrical designIntroduction on indian codes as applied in electrical design
Introduction on indian codes as applied in electrical design
 
Lab safety good ppt
Lab safety   good pptLab safety   good ppt
Lab safety good ppt
 

Similar to 70 e ppt short 2012

Electrical Safety and NFPA 70E Study Sheet v2.0
Electrical Safety and NFPA 70E Study Sheet v2.0Electrical Safety and NFPA 70E Study Sheet v2.0
Electrical Safety and NFPA 70E Study Sheet v2.0
Richard Gould
 
Understanding Arc Flash presentation engineering
Understanding Arc Flash presentation engineeringUnderstanding Arc Flash presentation engineering
Understanding Arc Flash presentation engineering
Sheeda2
 
Electrical Safety for the Non-Electrical Skilled Worker by EFCOG
Electrical Safety for the Non-Electrical Skilled Worker by EFCOGElectrical Safety for the Non-Electrical Skilled Worker by EFCOG
Electrical Safety for the Non-Electrical Skilled Worker by EFCOG
Atlantic Training, LLC.
 
arcflashsolutions2-160226132648
arcflashsolutions2-160226132648arcflashsolutions2-160226132648
arcflashsolutions2-160226132648
Brian Y. Smith
 
Arc Flash Calculations What Does It All Mean
Arc Flash Calculations What Does It All MeanArc Flash Calculations What Does It All Mean
Arc Flash Calculations What Does It All Mean
B Bhargav Reddy
 
Why Test Series - Arc Flash Evaluations CS-00158
Why Test Series - Arc Flash Evaluations CS-00158Why Test Series - Arc Flash Evaluations CS-00158
Why Test Series - Arc Flash Evaluations CS-00158
Carolyn Dakis
 
Introduction to Arc Flash Training by West Virginia University
Introduction to Arc Flash Training by West Virginia UniversityIntroduction to Arc Flash Training by West Virginia University
Introduction to Arc Flash Training by West Virginia University
Atlantic Training, LLC.
 
MSH_TB_ElectricalHazardAwareness.ppt
MSH_TB_ElectricalHazardAwareness.pptMSH_TB_ElectricalHazardAwareness.ppt
MSH_TB_ElectricalHazardAwareness.ppt
UntungPrawira
 

Similar to 70 e ppt short 2012 (20)

Basic Electrical safety.ppt
Basic Electrical safety.pptBasic Electrical safety.ppt
Basic Electrical safety.ppt
 
Electrical Safety and NFPA 70E Study Sheet v2.0
Electrical Safety and NFPA 70E Study Sheet v2.0Electrical Safety and NFPA 70E Study Sheet v2.0
Electrical Safety and NFPA 70E Study Sheet v2.0
 
Understanding Arc Flash presentation engineering
Understanding Arc Flash presentation engineeringUnderstanding Arc Flash presentation engineering
Understanding Arc Flash presentation engineering
 
Understanding Arc Flash
Understanding Arc FlashUnderstanding Arc Flash
Understanding Arc Flash
 
Electrical Safety for the Non-Electrical Skilled Worker by EFCOG
Electrical Safety for the Non-Electrical Skilled Worker by EFCOGElectrical Safety for the Non-Electrical Skilled Worker by EFCOG
Electrical Safety for the Non-Electrical Skilled Worker by EFCOG
 
Understanding Arc Flash
Understanding Arc FlashUnderstanding Arc Flash
Understanding Arc Flash
 
Arc Flash as it Relates to AC Drives
Arc Flash as it Relates to AC DrivesArc Flash as it Relates to AC Drives
Arc Flash as it Relates to AC Drives
 
arcflashsolutions2-160226132648
arcflashsolutions2-160226132648arcflashsolutions2-160226132648
arcflashsolutions2-160226132648
 
Arc flash analysis, electrical safety and risk assessment
Arc flash analysis, electrical safety and risk assessmentArc flash analysis, electrical safety and risk assessment
Arc flash analysis, electrical safety and risk assessment
 
Arc flash in Industry
Arc flash in Industry Arc flash in Industry
Arc flash in Industry
 
Electrical Safety by Industrial Safety Institute
Electrical Safety by Industrial Safety InstituteElectrical Safety by Industrial Safety Institute
Electrical Safety by Industrial Safety Institute
 
Arc Flash Calculations What Does It All Mean
Arc Flash Calculations What Does It All MeanArc Flash Calculations What Does It All Mean
Arc Flash Calculations What Does It All Mean
 
Skilled worker module_6
Skilled worker module_6Skilled worker module_6
Skilled worker module_6
 
Why Test Series - Arc Flash Evaluations CS-00158
Why Test Series - Arc Flash Evaluations CS-00158Why Test Series - Arc Flash Evaluations CS-00158
Why Test Series - Arc Flash Evaluations CS-00158
 
EDS Services
EDS ServicesEDS Services
EDS Services
 
Introduction to Arc Flash Training by West Virginia University
Introduction to Arc Flash Training by West Virginia UniversityIntroduction to Arc Flash Training by West Virginia University
Introduction to Arc Flash Training by West Virginia University
 
shock_arc_flash
shock_arc_flashshock_arc_flash
shock_arc_flash
 
Unit 106
Unit 106Unit 106
Unit 106
 
MSH_TB_ElectricalHazardAwareness.ppt
MSH_TB_ElectricalHazardAwareness.pptMSH_TB_ElectricalHazardAwareness.ppt
MSH_TB_ElectricalHazardAwareness.ppt
 
MSH_TB_ElectricalHazardAwareness.ppt
MSH_TB_ElectricalHazardAwareness.pptMSH_TB_ElectricalHazardAwareness.ppt
MSH_TB_ElectricalHazardAwareness.ppt
 

70 e ppt short 2012

  • 1. 11 NFPA 70ENFPA 70E Electrical Safety StandardElectrical Safety Standard - Get prepared, set the record straight, be “up front” > Most of you will resist, few will appreciate > Huge change (For you, burden rate, admin) > Won’t want to hear or see > Not trying to harass you, make uncomfortable (Hot!) > Arc Flash, not our only safety concern > Your safety & our compliance (Thankful & Grateful?)
  • 2. 22 Standards InteractionStandards Interaction OSHA 29 CFR 1910 SUBPART S NFPA 70-E National Electric Code IEEE Std 1584-2002 NFPA-70 (Institute of Electrical & Electronics Engineers)
  • 3. 33
  • 5. 55 Standards InteractionStandards Interaction From NFPA 70E Handbook, 2004 Edition, p17 (Explanatory Commentary) “Fire, shock, and electrocution have been considered to be electrical hazards for many years. Since the publication of NFPA 70E, 1995 edition, arc flash has been considered to be an electrical hazard. The arc flash hazard currently is defined to consider only the thermal aspects of an arcing fault. Other hazards include flying parts and pieces and the pressure wave that is generated in an arcing fault. Other electrical hazards also might be associated with an arcing fault.”
  • 6. 66 History of Electrical SafetyHistory of Electrical Safety
  • 7. 77 History of Electrical Safety NECA = National Electrical Contractors Association IBEW = International Brotherhood of Electrical Workers
  • 10. 1010 History of Electrical SafetyHistory of Electrical Safety
  • 11. 1111 Regulatory RequirementRegulatory Requirement • Per OSHA RulePer OSHA Rule andand NFPA 70E :NFPA 70E : DO NOT WORK ON EQUIPMENT HOTDO NOT WORK ON EQUIPMENT HOT (Maintenance or Repair)(Maintenance or Repair)  Equipment must be put in an electricallyEquipment must be put in an electrically safe work condition prior tosafe work condition prior to maintenance.maintenance.
  • 12. 1212 It’s The LawIt’s The Law But. . .But. . . • We must test live circuits before repairs are done.We must test live circuits before repairs are done. • Even after Lock Out / Tag Out, we must verify theEven after Lock Out / Tag Out, we must verify the absence of voltage – “not dead until tested dead”.absence of voltage – “not dead until tested dead”. • During this process, a worker could be exposed toDuring this process, a worker could be exposed to electrical hazards.electrical hazards. • Troubleshooting work requires that the power beTroubleshooting work requires that the power be left on.left on.
  • 13. 1313 Necessary LoopholeNecessary Loophole Because of this there are two exceptions toBecause of this there are two exceptions to “THE“THE RULE”.RULE”. 1.1. Where de-energizing would introduce increased or additionalWhere de-energizing would introduce increased or additional hazards.hazards. 2.2. Where killing power is “infeasible” due to equipment design orWhere killing power is “infeasible” due to equipment design or operational limitations (like voltage testing).operational limitations (like voltage testing). -1910. 333 (a) (1), Subpart S-1910. 333 (a) (1), Subpart S
  • 14. 1414 NFPA 70 E StandardNFPA 70 E Standard 1.1. Safety –Related Work PracticesSafety –Related Work Practices  Hazard Analyses for shock and flashHazard Analyses for shock and flash  Approach boundariesApproach boundaries  Personal Protective EquipmentPersonal Protective Equipment  TrainingTraining 1.1. Safety-Related Maintenance RequirementsSafety-Related Maintenance Requirements  Maintaining electrical components, wiring, equipment in a safeMaintaining electrical components, wiring, equipment in a safe conditioncondition 1.1. Safety Requirements for Special EquipmentSafety Requirements for Special Equipment  Batteries, Lasers and power electronic equipBatteries, Lasers and power electronic equip 1.1. Installation Safety RequirementsInstallation Safety Requirements  Truncated version of NECTruncated version of NEC  Not to be used in lieu of NECNot to be used in lieu of NEC Major Work Practice Requirements
  • 15. 1515 NFPA 70E - RequirementsNFPA 70E - Requirements  Electrical Safety Program ElementsElectrical Safety Program Elements  Awareness training for employees who work on orAwareness training for employees who work on or near exposed energized electrical conductorsnear exposed energized electrical conductors  Inspection/evaluation of electrical equipmentInspection/evaluation of electrical equipment  Identify hazards – hazard/risk evaluation prior to workIdentify hazards – hazard/risk evaluation prior to work on or near live parts operating at 50 volts or more oron or near live parts operating at 50 volts or more or where an electrical hazard existswhere an electrical hazard exists  Conduct an Electrical Hazard AnalysisConduct an Electrical Hazard Analysis (For everyone, de-energized work)
  • 16. 1616 Electrical Safety Program Elements – Con’tElectrical Safety Program Elements – Con’t  Develop procedures for jobsDevelop procedures for jobs  Work permits - procedures for working on or nearWork permits - procedures for working on or near live partslive parts >> 50 volts or where an electrical hazard50 volts or where an electrical hazard exists before work is started.exists before work is started.  Protect employees from shock, burn, blast,Protect employees from shock, burn, blast, and other hazardsand other hazards  Use electrically rated toolsUse electrically rated tools  Perform a job briefing prior to each jobPerform a job briefing prior to each job  Perform AuditsPerform Audits Troubleshooting Exemption Working it hot (Maintenance & Repair)
  • 17. 1717 NFPA 70E - RequirementsNFPA 70E - Requirements  Safety Training –Safety Training –  Classroom or on-the-job or a combination dependingClassroom or on-the-job or a combination depending on the risk to the employeeon the risk to the employee  Emergency procedures - for employees working on orEmergency procedures - for employees working on or near exposed energized electrical conductors ornear exposed energized electrical conductors or circuit parts:circuit parts:  Methods of release of victims from contact with exposedMethods of release of victims from contact with exposed energized conductors or circuit partsenergized conductors or circuit parts  First Aid, resuscitation, etc.First Aid, resuscitation, etc. Working it hot (Maintenance & Repair)
  • 18. 1818 NFPA 70E - RequirementsNFPA 70E - Requirements  Qualified Person – shall be trained and knowledgeable of theQualified Person – shall be trained and knowledgeable of the construction and operation of equipment or a specific work methodconstruction and operation of equipment or a specific work method and trained to recognize and avoid the electrical hazards that mightand trained to recognize and avoid the electrical hazards that might be present with respect to that equipment or work method.be present with respect to that equipment or work method. Only Qualified Persons are authorizedOnly Qualified Persons are authorized to work on or near live partsto work on or near live parts (For everyone, de-energized work)
  • 19. 1919 Creating an NFPA 70ECreating an NFPA 70E Compliant ProgramCompliant Program  Develop Electrical Safety ProgramDevelop Electrical Safety Program  Written electrical safety procedure SafeWritten electrical safety procedure Safe work practiceswork practices  Training requirements PPE requirementsTraining requirements PPE requirements Conduct Shock and Flash Hazard Analyses on allConduct Shock and Flash Hazard Analyses on all electrical equipment to determine appropriate levels ofelectrical equipment to determine appropriate levels of protectionprotection  Train and outfit all affected personnelTrain and outfit all affected personnel Where do we go from here ?
  • 20. 2020 Start With a Hazard Risk AnalysisStart With a Hazard Risk Analysis Hazard/Risk Analysis is a decision making process:Hazard/Risk Analysis is a decision making process: • Evaluate equipment and circuitEvaluate equipment and circuit information to determine the degree andinformation to determine the degree and extent of hazardsextent of hazards • Determine “Determine “ShockShock Approach BoundariesApproach Boundaries”” • DetermineDetermine ““Flash Protection BoundaryFlash Protection Boundary”” • DetermineDetermine “Incident Energy Exposure”“Incident Energy Exposure” • Determine appropriate PersonalDetermine appropriate Personal Protective Equipment (PPE)Protective Equipment (PPE) Must perform Shock and Flash Hazard Analyses when working “on or near” energized parts (within Limited Approach Boundary).
  • 21. 2121 Shock Hazard AnalysisShock Hazard Analysis  Protects againstProtects against ContactContact with energized equipmentwith energized equipment  Use highest voltage level of exposureUse highest voltage level of exposure  Boundary distance based solely on voltageBoundary distance based solely on voltage  Boundaries drawn from table in standard – no calcs necessary:Boundaries drawn from table in standard – no calcs necessary:  LimitedLimited – a safe approach boundary. Only qualified– a safe approach boundary. Only qualified employees and escorted unqualified employees mayemployees and escorted unqualified employees may crosscross  RestrictedRestricted – Only qualified employees may cross.– Only qualified employees may cross. When working within this boundary, must use specialWhen working within this boundary, must use special precautionary techniques and PPEprecautionary techniques and PPE  ProhibitedProhibited – Only qualified employees protected by– Only qualified employees protected by insulating materialsinsulating materials
  • 22. 2222 FLASH BOUNDARIESFLASH BOUNDARIES Limited Shock Boundary: Qualified or Unqualified Persons* * Only if accompanied by Qualified Person Prohibited Shock Boundary: Qualified Persons Only. PPE as if direct contact with live part Restricted Shock Boundary: Qualified Persons Only Note: shock boundaries dependent on system voltage level Flash Protection Boundary (FPB) Must wear appropriate PPE FPB dependent on fault level and time duration. Flash Protection Boundary (FPB) Must wear appropriate PPE FPB dependent on fault level and time duration. Equipment
  • 23. 2323 Approach BoundariesApproach Boundaries Restricted Approach Boundary Condition Nominal System Voltage Range, Phase to Phase Exposed Movable Conductor Exposed Fixed Circuit Part Includes Inadvertent Movement Adder Prohibited Approach Boundary 1 0 to 50 Not Specified Not Specified Not Specified Not Specified 2 51 to 300 10 ft. 0 in. 3 ft. 6 in. Avoid Contact Avoid Contact 3 301 to 750 10 ft. 0 in. 3 ft. 6 in. 1 ft. 0 in. 0 ft. 1 in. 4 751 to 15kV 10 ft. 0 in. 5 ft. 0 in. 2 ft. 2 in. 0 ft. 7 in. 5 15.1kV to 36kV 10 ft. 0 in. 6 ft. 0 in. 2 ft. 7 in. 0 ft. 10 in. Limited Approach Boundary 1. “Limited” Boundary - Must be Qualified Person 2. “Restricted” Boundary - Must wear Electrical PPE 3. “Prohibited” Boundary - Must wear PPE as if direct contact is being made. Working with Control Panel door open – in Restricted Approach Boundary
  • 24. 2424 Arc Flash BoundaryArc Flash Boundary  To protect from thermal burn due to arc flashTo protect from thermal burn due to arc flash  Electrical systems 600V or less:Electrical systems 600V or less:  4 feet, or4 feet, or  The calculated distance based on establishedThe calculated distance based on established algorithmsalgorithms  Electrical systems over 600V:Electrical systems over 600V:  Boundary based on incident energy as calculated orBoundary based on incident energy as calculated or as given in default tables in Standardas given in default tables in Standard Work within the Flash Boundary will require electrical PPE to protect the employee from arc flash injury (Good rule of thumb is 10 feet)
  • 25. 2525 Flash Hazard AnalysisFlash Hazard Analysis  Designed to prevent injury from the heat generated in anDesigned to prevent injury from the heat generated in an arc event – not contactarc event – not contact  A Flash Hazard Analysis Shall Determine:A Flash Hazard Analysis Shall Determine:  Flash BoundaryFlash Boundary  Approach boundary from exposed energized parts within which aApproach boundary from exposed energized parts within which a person without proper PPE could receive beyond a 2person without proper PPE could receive beyond a 2ndnd degree burndegree burn  Incident heat energy of possible arc flash based on:Incident heat energy of possible arc flash based on:  Available fault currentAvailable fault current  Fault clearing timeFault clearing time  Distance from exposed equipmentDistance from exposed equipment  Directional dissipation of energy (arc-in-the-box scenarios)Directional dissipation of energy (arc-in-the-box scenarios)  PPE Requirements within the Flash BoundaryPPE Requirements within the Flash Boundary
  • 26. 2626 Arc Flash HazardsArc Flash Hazards  Electric arcs produce some of the highest temperaturesElectric arcs produce some of the highest temperatures known to occur on earth – up to 35,000known to occur on earth – up to 35,000 00 degrees Fahrenheit.degrees Fahrenheit. This is four times the surface temperature of the sun (This is four times the surface temperature of the sun ( 90009000 00 FF))  All known materials are vaporized at this temperature. WhenAll known materials are vaporized at this temperature. When materials vaporize they expand in volume (Copper – 67,000materials vaporize they expand in volume (Copper – 67,000 times, Water–1670 times). The air blast can spread moltentimes, Water–1670 times). The air blast can spread molten metal to great distances with force.metal to great distances with force.  Rapidly expanding gases, extreme pressure and soundRapidly expanding gases, extreme pressure and sound waves, molten metal and metal plasma.waves, molten metal and metal plasma.
  • 27. 2727 Arc Flash HazardsArc Flash Hazards  Pressure: Blast pressure waves have thrownPressure: Blast pressure waves have thrown workers across rooms and knocked them offworkers across rooms and knocked them off ladders. Pressure on the chest can be higherladders. Pressure on the chest can be higher than 2000 lbs/ sq. ft. – blows clothing off body.than 2000 lbs/ sq. ft. – blows clothing off body.  Clothing can be ignited several feet away.Clothing can be ignited several feet away. Clothed areas can be burned more severelyClothed areas can be burned more severely than exposed skin.than exposed skin.  Hearing loss from sound blast. The sound canHearing loss from sound blast. The sound can have a magnitude as high as 140 dB at ahave a magnitude as high as 140 dB at a distance of 2 feet from the arc.distance of 2 feet from the arc.
  • 28. Sound Pressure ie. Mechanical pressureSound Pressure ie. Mechanical pressure IHOH Safety & Health Training /IHOH Safety & Health Training / EducationEducation 2828
  • 29. 2929 Arc Flash CausesArc Flash Causes  Dust and impuritiesDust and impurities - Dust and impurities on insulating surfaces- Dust and impurities on insulating surfaces can provide a path for current, allowing it to flashover andcan provide a path for current, allowing it to flashover and create arc discharge across the surface.create arc discharge across the surface.  CorrosionCorrosion - Corrosion of equipment creates impurities on- Corrosion of equipment creates impurities on insulating surfaces. Corrosion also weakens the contactinsulating surfaces. Corrosion also weakens the contact between conductor terminals, increasing the contact resistancebetween conductor terminals, increasing the contact resistance through oxidation or other contamination. Heat is generated onthrough oxidation or other contamination. Heat is generated on the contacts; sparks may be produced; can lead to arcing faultsthe contacts; sparks may be produced; can lead to arcing faults closest ground source.closest ground source.  Condensation -Condensation - water vapor can drip causing tracking on thewater vapor can drip causing tracking on the surface of insulating materials. Can create a flashover tosurface of insulating materials. Can create a flashover to ground.ground.  Spark discharge –Spark discharge – Accidental contact; dropping toolsAccidental contact; dropping tools  Overvoltage across narrow gapsOvervoltage across narrow gaps  Failure of insulating materialsFailure of insulating materials  Improper work proceduresImproper work procedures
  • 30. 3030 Arc Flash in Our EquipmentArc Flash in Our Equipment  Don’t have to beDon’t have to be “working on”“working on” a circuit for an arc flash to occur.a circuit for an arc flash to occur. Accidental contact is the most common cause of arc flash events.Accidental contact is the most common cause of arc flash events.  For a low voltage system (480 V), a 3 to 4-inch arc can becomeFor a low voltage system (480 V), a 3 to 4-inch arc can become “stabilized” and persist for an extended period of time if circuit does“stabilized” and persist for an extended period of time if circuit does not operate.not operate.  Energy released is a function of system voltage, fault currentEnergy released is a function of system voltage, fault current magnitude and fault duration.magnitude and fault duration.  Arcs in enclosures, such as a Motor Control Center (MCC) or panelArcs in enclosures, such as a Motor Control Center (MCC) or panel board, magnify blast and energy transmitted as the blast is forced toboard, magnify blast and energy transmitted as the blast is forced to the open side of the enclosure and toward the worker (Arc-in-the-the open side of the enclosure and toward the worker (Arc-in-the- Box).Box).
  • 31. 3131 Small arc – burn to hand Medium arc – burn to hand, arm and chest Severe arc – whole body burns Ionization cloud barely visible Clearly visible ionized gas Exploding plasma of gases and vaporized metal Arc Flash in a PanelboardArc Flash in a Panelboard
  • 32. 3232 10 minute break Brief video clip of arc flash in switchgear Five to Ten Arc Flash Explosions occur in electric equipment every day in the U.S (Based on statistics compiled by Cap Schell, Inc., a Chicago based research and consulting firm that specializes in preventing workplace injuries and death) Bureau of Labor Statistics data for 1994 show 11,153 cases of reported days away from work were due to electrical burns, electrocution / electrical shock injuries, fires and explosions. The Census of Fatal Injuries noted 548 employees died from the causes of electrical current exposure, fires and explosions out of 6,588 work related fatalities nationwide.
  • 33. 3333 Flash Hazard AnalysisFlash Hazard Analysis  Determines the Flash Protection BoundaryDetermines the Flash Protection Boundary  Determines the required PPEDetermines the required PPE  2 Methods available:2 Methods available: 1.1. Can use Default Tables in the NFPA 70E StandardCan use Default Tables in the NFPA 70E Standard  Classifies work tasks in a specific Hazard RiskClassifies work tasks in a specific Hazard Risk Category (HRC)Category (HRC)  Specifies required PPE as a function of HRCSpecifies required PPE as a function of HRC 1.1. Can calculate the incident energy to employees if a faultCan calculate the incident energy to employees if a fault occurred. Can then specify the required PPE based onoccurred. Can then specify the required PPE based on predicted hazard level.predicted hazard level. We compared default tables to calculated values: • Used conservative, but reasonably expected input parameters • Used 2 different calculation models (took highest values) • Found calculated values to be less than default tables
  • 34. 3434 Example From Default TableExample From Default Table • Voltage-rated gloves • Voltage-rated tools • Doubled-layered switching hood and hearing protection • Untreated natural fiber: T-shirt & Long pants • FR Clothing: Long –sleeve shirt, Pants, Coveralls • FR Protective Equipment: Hard hat, safety glasses, leather gloves, leather work shoes (Note there are footnotes altering above due to fault current levels and duration. And there are some substitutions permitted.) Page 55, Table 3-3.9.1/ Page 59,Table 3-3.9.2 600 V Class MCC - Work on energized parts including voltage testing - What is required? If You Use the Method #1 Flash Hazard Analysis – NFPA 70E Default Tables: Columbia Customer
  • 35. 3535 Example From Default Table, ContinuedExample From Default Table, Continued
  • 36. 3636 Incident Energy & Calories “Incident Energy- The amount of energy impressed on a surface, a certain distance from the source, generated during an electrical arc event. One of the units used to measure incident energy is calories per centimeter squared ( cal/cm ) The definition of incident energy was added to provide clarity for the user. Incident energy could be expressed in several different terms, such as calories per centimeter, joules per square centimeter, or calories per square inch. However, incident energy must be expressed in the same terms in which the PPE is thermally rated, which usually is calories per square centimeter.” - From NFPA 70E Handbook, 2004 Edition, p. 22 (Text & Explanatory Commentary) 2 (Cigarette lighter produces about 1 cal/cm-sq)
  • 37. 3737 From NFPA 70E Default TablesFrom NFPA 70E Default Tables Risk Category Min. Arc Rating of PPE PPE Requirements - NFPA-70E 2004 0 0-2 cal/cm 2 Untreated Cotton; leather gloves; safety glasses 1 2-4 cal/cm 2 FR shirt and pants (or jeans); rubber gloves; safety glasses; hard hat 2 4-8 cal/cm 2 FR shirt and pants (or jeans); rubber gloves; safety glasses; hard hat; arc face shield 3 8-25 cal/cm 2 FR shirt and pants; rubber gloves; safety glasses; hard hat; arc hood; arc jacket 4 25-40 cal/cm 2 FR shirt and pants; rubber gloves; safety glasses; hard hat; arc hood; multi-layer flash suit From: NFPA 70E Default Tables Troubleshooting a 480 V panel is listed in default tables as Hazard Category 2 work.
  • 38. 3838 Work Tasks ImpactedWork Tasks Impacted Primarily Troubleshooting, Start-Up and Power DownPrimarily Troubleshooting, Start-Up and Power Down ProceduresProcedures  Main Disconnect OperationMain Disconnect Operation  Circuit Breaker OperationCircuit Breaker Operation  Contactor OperationContactor Operation  Voltage and Amp ReadingsVoltage and Amp Readings  Control circuitryControl circuitry  Power circuitryPower circuitry  Etc..Etc..
  • 39. 3939 Flash Hazard ThresholdFlash Hazard Threshold Second Degree Burn Threshold 1.2 cal/cm2 Note: medical treatment may still be required if bare skin is exposed to this level of flash - full recovery to be expected. Must protect employees from the onset of 2nd degree burn
  • 40. 4040 PPE SelectionPPE Selection From 70E TableFrom 70E Table For Most Service and Maintenance Work Limited work on 2300V and 4160V Synthetic fibers, such as polyester, nylon, acetate, rayon, either alone or in blends are not permitted – they melt at low temperatures, adhere to the skin and increase the extent of injury. Voltage Clothing Gloves Other PPE Safety Glasses Hard Hat (if needed) Safety Glasses Class E Hard Hat with 8 Cal. ATPV Face Shield 2300-4160 Volts Safety Glasses Class E Hard Hat with 8 Cal. ATPV Face Shield Class 1 Insulated Rubber Gloves w/ Leather Protectors 50 - 120 Volts 100% long-sleeve cotton shirt and pants Leather Gloves (Class 00 if possibility of contact) 121 - 600 Volts 100% long-sleeve cotton or FR shirt and pants Class 00 or 0 Insulated Rubber Gloves w/ Leather Protectors FR shirt and pants or FR Coveralls - 9.4 ounce Indura Ultra Soft (or equivalent) For outdoor work, outer layer must be natural fiber or FR
  • 41. 4141 100% Cotton vs. FR Clothing100% Cotton vs. FR Clothing One Major Exception to the 100% Cotton Rule forOne Major Exception to the 100% Cotton Rule for 480 Volt work:480 Volt work: When working on (e.g. Voltage testing) the line side terminal ofWhen working on (e.g. Voltage testing) the line side terminal of a main disconnect at a large industrial customer, weara main disconnect at a large industrial customer, wear FR clothing as the outer layer instead of 100% cotton.FR clothing as the outer layer instead of 100% cotton. This is due to the uncertainty of available fault currents and clearing times with on-site substation transformers and 600 Amp class circuit breakers. As a result, many Company locations are just buying FR shirts/pants for all electrical work
  • 42. 4242 100% Cotton vs. FR Clothing100% Cotton vs. FR Clothing 100% cotton will catch on fire & burn, but won’t melt to the burn making burn worse FR will not support combustion, that is, it won’t catch on fire and continue to burn Tech was seated cross legged, brazing slag ‘popped out’ stayed on pant leg FR, HRC 2 pants, (white sheet of paper Inside pant leg)
  • 43. 4343 Arc Hazards Below 240 VoltsArc Hazards Below 240 Volts  Rubber gloves and face shield neededRubber gloves and face shield needed in the 120 - 240 volt range becausein the 120 - 240 volt range because significant arc hazards may exist suchsignificant arc hazards may exist such as:as:  3 Phase, 208 V power circuits supplying equipment3 Phase, 208 V power circuits supplying equipment in older installations.in older installations.  Old building infrastructures may not have convertedOld building infrastructures may not have converted to 480 V systems.to 480 V systems. Become familiar with the facility electrical distribution system to fully evaluate the level of hazard.
  • 44. 4444 Electrical PPE RequirementsElectrical PPE Requirements Electrical PPE (rubber gloves, hard hat / arc face shield,Electrical PPE (rubber gloves, hard hat / arc face shield, cotton or FR clothing) iscotton or FR clothing) is requiredrequired for troubleshooting,for troubleshooting, applying LOTO and testing dead. After that,applying LOTO and testing dead. After that, 1.1. The line side terminal of the disconnecting deviceThe line side terminal of the disconnecting device may stillmay still be energizedbe energized.. 2.2. According to this standard, if you areAccording to this standard, if you are “exposed”“exposed” to energizedto energized parts, electrical PPE is still required.parts, electrical PPE is still required.  ““Exposed”Exposed” means being within the Limited Approachmeans being within the Limited Approach Boundary, which is 1 ft, for circuits 120 – 480 V.Boundary, which is 1 ft, for circuits 120 – 480 V. 1.1. You can eliminateYou can eliminate “exposure”“exposure” and remove the PPE if you canand remove the PPE if you can “Insulate”“Insulate” oror “Isolate”“Isolate” yourself from the energized parts.yourself from the energized parts. 2.2. InsulateInsulate by placing an insulating material over the part.by placing an insulating material over the part. 3.3. IsolateIsolate by placing a rigid barrier over the part to preventby placing a rigid barrier over the part to prevent contact, or ensure your body and all conductive tools remaincontact, or ensure your body and all conductive tools remain > 1 ft. away.> 1 ft. away. PPE requirements based on your distance from “Exposed Energized Parts”, not the equipment you’re working on
  • 47. 4747 480 Volt Fused Disconnect Switch
  • 53. 5353 Electrical Safety ProcedureElectrical Safety Procedure Customized for HVAC Service andCustomized for HVAC Service and Contracting Business:Contracting Business:  Work ProceduresWork Procedures  Electrical PPEElectrical PPE  Protective ClothingProtective Clothing  TrainingTraining
  • 54. 5454 Electrical Safety ProcedureElectrical Safety Procedure 1.1. Work Procedures:Lockout/Tagout wheneverWork Procedures:Lockout/Tagout whenever possible – Cardinal Rulepossible – Cardinal Rule  Approach Boundaries - Based on voltageApproach Boundaries - Based on voltage  Use of non-conductive tools, materials, equipmentUse of non-conductive tools, materials, equipment  Insulated tools and equipmentInsulated tools and equipment  Test Instruments and equipmentTest Instruments and equipment  Protective Shielding EquipmentProtective Shielding Equipment  Portable LaddersPortable Ladders  Safety InterlocksSafety Interlocks  Use of GFCIsUse of GFCIs
  • 55. 5555 Electrical Safety ProcedureElectrical Safety Procedure 2.2. Electrical PPEElectrical PPE  Required when working within the LimitedRequired when working within the Limited Approach BoundaryApproach Boundary  Flash Hazard Analysis dictates what mustFlash Hazard Analysis dictates what must be wornbe worn  Can use NFPA 70E default tables, orCan use NFPA 70E default tables, or  Can perform customized analysisCan perform customized analysis  Includes Hand; Head and Face; WholeIncludes Hand; Head and Face; Whole Body protectionBody protection
  • 56. 5656 Electrical Safety TrainingElectrical Safety Training Electrical Safety Training Broken DownElectrical Safety Training Broken Down into 4 Modules:into 4 Modules: 1.1. Awareness LevelAwareness Level 2.2. Basic ElectricityBasic Electricity 3.3. Low Voltage Practices (50-600 V)Low Voltage Practices (50-600 V) 4.4. High Voltage Practices ( > 600 V)High Voltage Practices ( > 600 V)
  • 58. 5858 PPE EnsemblesPPE Ensembles Hazard Risk Category 0 Hazard Risk Category 1 Hazard Risk Category 2 Hazard Risk Category 3 Hazard Risk Category 4
  • 59. 5959 Qualified Person TrainingQualified Person Training  Basic RequirementsBasic Requirements 1.1. Must have knowledge of construction and operation of equipment and specificMust have knowledge of construction and operation of equipment and specific work methods to recognize and avoid electrical hazards while performingwork methods to recognize and avoid electrical hazards while performing work.work. 2.2. Must be familiar with the precautionary techniques, PPE, insulating andMust be familiar with the precautionary techniques, PPE, insulating and shielding materials, insulated tools and test equipment.shielding materials, insulated tools and test equipment.  Specific RequirementsSpecific Requirements 1.1. Able to distinguish exposed energized parts from other partsAble to distinguish exposed energized parts from other parts 2.2. Able to determine nominal voltage of exposed live partsAble to determine nominal voltage of exposed live parts 3.3. Approach distances and corresponding voltages in the StandardApproach distances and corresponding voltages in the Standard 4.4. Determine degree of hazard and appropriate PPEDetermine degree of hazard and appropriate PPE Required by OSHA (via Sec. 5a1) and NFPA 70E Training can be either classroom, on-the-job, or a combination. OJT requires direct supervision by a Qualified Person. Supplemental Training Needs
  • 60. 6060 Laredo, TX 6/05 2 Contract Electricians in arc flash event 3rd deg burns; clothing ignited; victims survived
  • 61. 6161 Focus On Engineering andFocus On Engineering and Admin ControlsAdmin Controls OSHA 1910. 335 “Safeguards for personnel protection”OSHA 1910. 335 “Safeguards for personnel protection” ((a) (2) (ii)a) (2) (ii) ““Protective shields, protective barriers, or insulatingProtective shields, protective barriers, or insulating materials shall be used to protect each employee frommaterials shall be used to protect each employee from shock, burns, or electrically related injuries while thatshock, burns, or electrically related injuries while that employee is working near exposed energized parts whichemployee is working near exposed energized parts which might be accidentally contacted or where dangerousmight be accidentally contacted or where dangerous electric heating or arcing might occur. When normallyelectric heating or arcing might occur. When normally enclosed live parts are exposed for maintenance or repair,enclosed live parts are exposed for maintenance or repair, they shall be guarded to protect unqualified persons fromthey shall be guarded to protect unqualified persons from contact with the live part.”contact with the live part.”
  • 62. 6262 Thank You – Questions??

Editor's Notes

  1. OSHA 29 Code of Federal Regulations (CFR) Part 1910 Subpart S - Regulatory requirement. NFPA 70-2002 National Electrical Code – labeling requirements NFPA 70E-2004, Standard for Electrical Safety in the Workplace. Current version cited by OSHA. Basically describes “how to” on compliance. IEEE (Institute of Electrical and Electronic Engineers) Standard 1584-2002 Guide for Performing Arc Flash Hazard Calculations.
  2. OSHA 29 Code of Federal Regulations (CFR) Part 1910 Subpart S - Regulatory requirement. NFPA 70-2002 National Electrical Code – labeling requirements NFPA 70E-2004, Standard for Electrical Safety in the Workplace. Current version cited by OSHA. Basically describes “how to” on compliance. IEEE (Institute of Electrical and Electronic Engineers) Standard 1584-2002 Guide for Performing Arc Flash Hazard Calculations.
  3. OSHA 29 Code of Federal Regulations (CFR) Part 1910 Subpart S - Regulatory requirement. NFPA 70-2002 National Electrical Code – labeling requirements NFPA 70E-2004, Standard for Electrical Safety in the Workplace. Current version cited by OSHA. Basically describes “how to” on compliance. IEEE (Institute of Electrical and Electronic Engineers) Standard 1584-2002 Guide for Performing Arc Flash Hazard Calculations.
  4. OSHA 29 Code of Federal Regulations (CFR) Part 1910 Subpart S - Regulatory requirement. NFPA 70-2002 National Electrical Code – labeling requirements NFPA 70E-2004, Standard for Electrical Safety in the Workplace. Current version cited by OSHA. Basically describes “how to” on compliance. IEEE (Institute of Electrical and Electronic Engineers) Standard 1584-2002 Guide for Performing Arc Flash Hazard Calculations.
  5. OSHA 29 Code of Federal Regulations (CFR) Part 1910 Subpart S - Regulatory requirement. NFPA 70-2002 National Electrical Code – labeling requirements NFPA 70E-2004, Standard for Electrical Safety in the Workplace. Current version cited by OSHA. Basically describes “how to” on compliance. IEEE (Institute of Electrical and Electronic Engineers) Standard 1584-2002 Guide for Performing Arc Flash Hazard Calculations.