The Reactive Power, Does It Important For Us
I. INTRODUCTION
A. DEFINITION OF REACTIVE POWER
Almost all power transported or consumed in alternating current (AC) networks. AC
systems supply or consume two kind of power: real power and reactive power .Real
power accomplishes useful work while reactive power supports the voltage that must
be controlled for system reliability.
For AC systems voltage and current pulsate at the system frequency. Although AC
voltage and current pulsate at same frequency, they peak at different time power is the
algebraic product of voltage and current. Real power is the average of power over
cycle and measured by volt-amperes or watt. The portion of power with zero average
value called reactive power measured in volt-amperes reactive or vars.
The total power is called the apparent power (symbolized by the capital letter S) and
measured by volt-amperes or VA. To describe the reactive power , imagine a person
on trampoline , The person real power goes into moving horizontally across
trampoline as it bounces , the effort the person expend to keep standing(represent
reactive power Q ) during bouncing result no net forward motion(represent real power
P) , but it's necessary to walk on trampoline . The motion from trampoline always
perpendicular to the direction the person is walking. So that the direction between P
and Q 90 degree Out of phase.
II. Measuring reactive power
The amount and complexity of household electrical equipment has increased
tremendously over the last few years. Electronic ballast lighting, computer monitors
and air conditioners are welcome additions to our homes but come with additional
burdens. One of these is on the electricity grid, as these appliances generate more
signal harmonics.
This change in the end-consumer profile is a disadvantage for energy distributors
which bill energy based only on active power. With the application of non-linear
loads to power lines the active energy no longer represents the total energy delivered.
As a response to improve billing, the measurement of reactive energy is gaining
interest. For example, Italy’s leading energy distributor has decided to install more
than 20 million household energy meters with active and reactive power
measurements.
This growing interest in measuring reactive energy leads to the question: What
method should an energy meter designer implement to accurately measure the
reactive energy?
Although today’s electronic digital signal processing (DSP) enables reactive energy
measurements to be closer to the theoretical value, there is no consensus in the field of
energy metering on the methods of measurement. This article aims to explain and
compare the three main methods in use, namely the Power Triangle, the Time Delay
and Low-pass Filter.
A. System requirements
Electromechanical meters have set a precedent in reactive energy billing. Although
they are bandwidth limited and cannot take into account harmonics of the line
frequency, they are supported by the international standard for alternating current
static var-hour meters for reactive energy (IEC-1268). The standard defines reactive
energy measurements at the fundamental line frequency, which implies that it is not
mandatory to include harmonics. It also specifies additional testing conditions to
check the robustness of the measurements against the third harmonic, the dc offset in
the current input, and the line frequency variation. The various reactive power
measurement methods presented in this paper are evaluated against these critical tests
of the IEC-1268 (Table 1).
B. Reactive power theory
The reactive power is defined in the IEEE Standard Dictionary 100-1996 under the
energy “magner” as:
(1)
where Vn and In are respectively the voltage and current rms values of the nth
harmonics of the line frequency, and jn is the phase difference between the voltage
and the current nth harmonics. A convention is also adopted stating that the reactive
energy should be positive when the current is leading the voltage (inductive load).
In an electrical system containing purely sinusoidal voltage and current waveforms at
a fixed frequency, the measurement of reactive power is easy and can be
accomplished using several methods without errors. However, in the presence of non-
sinusoidal waveforms, the energy contained in the harmonics causes measurement
errors.
According to the Fourier theorem any periodic waveform can be written as a sum of
sin and cosine waves. As energy meters deal with periodic signals at the line
frequency both current and voltage inputs of a single phase meter can be described by:
(2)
(3)
where Vn, In and jn are defined as in Equation 1.
C. Active power
The average active power is defined as:
(4)
The implementation of the active power measurement is relatively easy and is done
accurately in most energy meters in the field.
D. Apparent power
The apparent power is the maximum real power that can be delivered to a load. As
Vrms and Irms are the effective voltage and current delivered to the load,
Apparent power = Vrms • Irms (5)
The correct implementation of the apparent energy measurement is bound by the
accuracy of the rms measurements.
E. Reactive power calculation
As explained above, different methods can be used to calculate the reactive power.
The theoretical definition of the reactive power is difficult to implement in an
electronic system at a reasonable cost. It requires a dedicated DSP to process the
Hilbert transform necessary to get a constant phase shift of 90° at each frequency.
Several solutions have been developed to overcome this limitation. They can be
categorized in three groups:
1- Method 1: Power triangle
The Power triangle method is based on the assumption that the three energies,
apparent, active and reactive, form a right-angle triangle as shown in Figure 1. The
reactive power can
(6)
then be processed by estimating the active and apparent energies and applying:
Although this method gives excellent results with pure sinusoidal waveforms,
noticeable errors appear in presence of harmonics (Table 1).
2- Method 2: Time delay
A time delay is introduced to shift one of the waveforms by 90° at the fundamental
frequency and multiply the two waveforms:
(7)
where T is the period of the fundamental. In an electronic DSP system, this method
can be implemented by delaying the samples of one input by the number of samples
representing a quarter-cycle of the fundamental frequency (Fline) (Figure 2)
This method presents drawbacks if the line frequency changes and the number of
samples no longer represents a quarter-cycle of the fundamental frequency.
Significant errors are then introduced to the results (Table 1).
3- Method 3: Low-pass filter
A constant 90° phase shift over frequency with an attenuation of 20 dB/decade is
introduced. This solution, which has been implemented by Analog Devices, can be
realized with a single pole low-pass filter on one channel input (Figure 3). If the cut-
off frequency of the low-pass filter is much lower than the fundamental frequency,
this solution provides a 90° phase shift at any frequency higher than the fundamental
frequency. It also attenuates these frequencies by 20 dB/decade (Figure 4).
Similarly to method 2, this solution is susceptible to variations of the line frequency.
However, a dynamic compensation of the gain attenuation with the line frequency can
be achieved by evaluating the line period of the signal (Table 1).
Recent
advances in
technology
have
increased
consumer
demand for
electrical
products
that offer
convenienc
e and
entertainment in the modern home. With these advances have come increased burdens
on utilities that transmit electricity and on consumers that pay for its use. A portion of
this burden is due to reactive power.
If you were to compare the amount of electricity flowing into your home (i.e. apparent
power) with that which performs productive work (i.e. real power) you would see that
there is a difference. Known as reactive power, this additional energy is needed to
energize motor windings and similar type loads in your home. Reactive power is
returned to the electric grid as the windings de-energize, but is quickly needed again
since motor windings must be re-energized 120 times per second. Reactive power
does no real work, (e.g. turning a fan blade) but provides the magnetizing energy
so that real work can be done.
III. NEEDS OF REACTIVE POWER
Voltage control in an electrical power system is important for proper operation for
electrical power equipment to prevent damage such as overheating of generators and
motors, to reduce transmission losses and to maintain the ability of the system to
withstand and prevent voltage collapse. In general terms, decreasing reactive power
causing voltage to fall while increasing it causing voltage to rise. A voltage collapse
occurs when the system try to serve much more load than the voltage can support.
When reactive power supply lower voltage, as voltage drops current must increase to
maintain power supplied, causing system to consume more reactive power and the
voltage drops further . If the current increase too much, transmission lines go off line,
overloading other lines and potentially causing cascading failures. If the voltage drops
too low, some generators will disconnect automatically to protect themselves. Voltage
collapse occurs when an increase in load or less generation or transmission facilities
causes dropping voltage, which causes a further reduction in reactive power from
capacitor and line charging, and still there further voltage reductions. If voltage
reduction continues, these will cause additional elements to trip, leading further
reduction in voltage and loss of the load. The result in these entire progressive and
uncontrollable declines in voltage is that the system unable to provide the reactive
power required supplying the reactive power demands.
Reactive power needs are determined in the planning process, which is a part of
engineering, part economics and part judgment. The engineering analysis requires
running large, complex mathematical computer models of the electric system. The
economical part required putting costs into models to determine how to achieve an
efficient, reliable system. The judgment arises due to the large number of modeling
choices, expert assumption and approximations that often are necessary.
A. Reactive power blackouts
Insufficient reactive power leading to voltage collapse has been a causal factor in
major blackouts in the worldwide. Voltage collapse occurred in United States in the
blackout of July 2, 1996, and August10, 1996 on the West Coast. Voltage collapse
also factored in blackouts of December 19, 1978, in France; July 23, 1987, in Tokyo;
March 13, 1989, in Québec; August 28, 2003, in London; September 28, 2003, in
Sweden and Denmark; and September 28, 2003, in Italy.
While August 14, 2003, blackout in the United States and Canada was not due to a
voltage collapse as that term has traditionally used by power system engineers, the
task force final report said that" Insufficient reactive power was an issue in the
blackout" and the report also "overestimation of dynamics reactive output of system
generation " as common factor among major outages in the United States. Due to
difficulties modeling dynamic generators output, the amount of dynamic reactive
output from generators has been less than expected, worsening voltage problems and
resultant power outages
V. PROBLEMS OF REACTIVE POWER
Though reactive power is needed to run many electrical devices, it can cause harmful
effects on your appliances and other motorized loads, as well as your electrical
infrastructure. Since the current flowing through your electrical system is higher than
that necessary to do the required work, excess power dissipates in the form of heat as
the reactive current flows through resistive components like wires, switches and
transformers. Keep in mind that whenever energy is expended, you pay. It makes no
difference whether the energy is expended in the form of heat or useful work.
We can determine how much reactive power your electrical devices use by measuring
their power factor, the ratio between real power and true power. A power factor of 1
(i.e. 100%) ideally means that all electrical power is applied towards real work.
Homes typically have overall power factors in the range of 70% to 85%, depending
upon which appliances may be running. Newer homes with the latest in energy
efficient appliances can have an overall power factor in the nineties.
The typical residential power meter only reads real power, i.e. what you would have
with a power factor of 100%. While most electric companies do not charge residences
directly for reactive power, it’s a common misconception to say that reactive power
correction has no economic benefit. To begin with, electric companies correct for
power factor around industrial complexes, or they will request the offending customer
to do so at his expense, or they will charge more for reactive power. Clearly electric
companies benefit from power factor correction, since transmission lines carrying the
additional (reactive) current to heavily industrialized areas costs them money. Many
people overlook the benefits that power factor correction can offer the typical home in
comparison to the savings and other benefits that businesses with large inductive
loads can expect.
.
Most importantly, you pay for reactive power in the form of energy losses created by
the reactive current flowing in your home. These losses are in the form of heat and
cannot be returned to the grid. Hence you pay. The fewer kilowatts expended in the
home, whether from heat dissipation or not, the lower the electric bill. Since power
factor correction reduces the energy losses, you save.
As stated earlier, electric companies correct for power factor around industrial
complexes, or they will request the offending customer to do so, or they will charge
for reactive power. They’re not worried about residential service because the impact
on their distribution grid is not as severe as in heavily industrialized areas. However,
it is true that power factor correction assists the electric company by reducing demand
for electricity, thereby allowing them to satisfy service needs elsewhere. But who
cares? Power factor correction lowers your electric bill by reducing the number of
kilowatts expended, and without it your electric bill will be higher, guaranteed.
We’ve encountered this with other electric companies and have been successful in
getting each of them to issue a retraction. Electric companies do vary greatly and
many show no interest in deviating from their standard marketing strategy by
acknowledging proven energy saving products. Keep in mind that promoting REAL
energy savings to all their customers would devastate their bottom line.
Power factor correction will not raise your electric bill or do harm to your electrical
devices. The technology has been successfully applied throughout industry for years.
When sized properly, power factor correction will enhance the electrical efficiency
and longevity of inductive loads. Power factor correction can have adverse side
effects (e.g. harmonics) on sensitive industrialized equipment if not handled by
knowledgeable, experienced professionals. Power factor correction on residential
dwellings is limited to the capacity of the electrical panel (200 amp max) and does not
over compensate household inductive loads. By increasing the efficiency of electrical
systems, energy demand and its environmental impact is lessened
Conclusion
Efficient completion is a way to achieve efficiency and reduce costs to consumers.
Efficient competition is difficult to achieve. Due to innovation and technological
progress, the optimal industry structure and mode of regulation may not need to
change. As regulated markets move from franchised monopolies toward completion,
Regulation needs to move from direct price regulation to market rules. Competitive
markets required competitive market design.
Put difficulties, efficient market design does not just happen spontaneously. It is the
result of a process that includes full discussion, learning and informed judgment by all
affective and responsible parties.

More Related Content

What's hot

Reactive Power Compensation in 132kv & 33kv Grid of Narsinghpur Area
Reactive Power Compensation in 132kv & 33kv Grid of Narsinghpur AreaReactive Power Compensation in 132kv & 33kv Grid of Narsinghpur Area
Reactive Power Compensation in 132kv & 33kv Grid of Narsinghpur Areaijceronline
 
Modeling Of Converter “Single Phase to Three Phase by Using Single Phase Sup...
Modeling Of Converter “Single Phase to Three Phase by Using Single Phase  Sup...Modeling Of Converter “Single Phase to Three Phase by Using Single Phase  Sup...
Modeling Of Converter “Single Phase to Three Phase by Using Single Phase Sup...IJMER
 
A Simulink Model for Damping Power System Oscillations Using Fact Devices
A Simulink Model for Damping Power System Oscillations Using Fact DevicesA Simulink Model for Damping Power System Oscillations Using Fact Devices
A Simulink Model for Damping Power System Oscillations Using Fact DevicesIOSR Journals
 
Implementation of Instantaneous Reactive Power Theory for Current Harmonic Re...
Implementation of Instantaneous Reactive Power Theory for Current Harmonic Re...Implementation of Instantaneous Reactive Power Theory for Current Harmonic Re...
Implementation of Instantaneous Reactive Power Theory for Current Harmonic Re...IOSR Journals
 
Power Factor
Power FactorPower Factor
Power FactorTim Cohen
 
Comparative of Conventional and Intelligence Controller based Hybrid Generati...
Comparative of Conventional and Intelligence Controller based Hybrid Generati...Comparative of Conventional and Intelligence Controller based Hybrid Generati...
Comparative of Conventional and Intelligence Controller based Hybrid Generati...IJERD Editor
 
Voltage control of active distribution networks by means of disperse generation
Voltage control of active distribution networks by means of disperse generationVoltage control of active distribution networks by means of disperse generation
Voltage control of active distribution networks by means of disperse generationdavidtrebolle
 
Power Quality Improvement using Passive shunt filters, TCR and TSC combination
Power Quality Improvement using Passive shunt filters, TCR and TSC combinationPower Quality Improvement using Passive shunt filters, TCR and TSC combination
Power Quality Improvement using Passive shunt filters, TCR and TSC combinationIJERA Editor
 
Improvement of the electric power quality using
Improvement of the electric power quality usingImprovement of the electric power quality using
Improvement of the electric power quality usingVikram Rawani
 

What's hot (15)

Reactive Power Compensation in 132kv & 33kv Grid of Narsinghpur Area
Reactive Power Compensation in 132kv & 33kv Grid of Narsinghpur AreaReactive Power Compensation in 132kv & 33kv Grid of Narsinghpur Area
Reactive Power Compensation in 132kv & 33kv Grid of Narsinghpur Area
 
G046033742
G046033742G046033742
G046033742
 
Modeling Of Converter “Single Phase to Three Phase by Using Single Phase Sup...
Modeling Of Converter “Single Phase to Three Phase by Using Single Phase  Sup...Modeling Of Converter “Single Phase to Three Phase by Using Single Phase  Sup...
Modeling Of Converter “Single Phase to Three Phase by Using Single Phase Sup...
 
A Simulink Model for Damping Power System Oscillations Using Fact Devices
A Simulink Model for Damping Power System Oscillations Using Fact DevicesA Simulink Model for Damping Power System Oscillations Using Fact Devices
A Simulink Model for Damping Power System Oscillations Using Fact Devices
 
Modelling of three phase SVPWM AC-AC converter using unity power factor control
Modelling of three phase SVPWM AC-AC converter using unity power factor controlModelling of three phase SVPWM AC-AC converter using unity power factor control
Modelling of three phase SVPWM AC-AC converter using unity power factor control
 
Implementation of Instantaneous Reactive Power Theory for Current Harmonic Re...
Implementation of Instantaneous Reactive Power Theory for Current Harmonic Re...Implementation of Instantaneous Reactive Power Theory for Current Harmonic Re...
Implementation of Instantaneous Reactive Power Theory for Current Harmonic Re...
 
Power factor
Power factorPower factor
Power factor
 
Power Factor
Power FactorPower Factor
Power Factor
 
Ijetr021124
Ijetr021124Ijetr021124
Ijetr021124
 
Comparative of Conventional and Intelligence Controller based Hybrid Generati...
Comparative of Conventional and Intelligence Controller based Hybrid Generati...Comparative of Conventional and Intelligence Controller based Hybrid Generati...
Comparative of Conventional and Intelligence Controller based Hybrid Generati...
 
I1101047680
I1101047680I1101047680
I1101047680
 
EDS Unit 5.pptx
EDS Unit 5.pptxEDS Unit 5.pptx
EDS Unit 5.pptx
 
Voltage control of active distribution networks by means of disperse generation
Voltage control of active distribution networks by means of disperse generationVoltage control of active distribution networks by means of disperse generation
Voltage control of active distribution networks by means of disperse generation
 
Power Quality Improvement using Passive shunt filters, TCR and TSC combination
Power Quality Improvement using Passive shunt filters, TCR and TSC combinationPower Quality Improvement using Passive shunt filters, TCR and TSC combination
Power Quality Improvement using Passive shunt filters, TCR and TSC combination
 
Improvement of the electric power quality using
Improvement of the electric power quality usingImprovement of the electric power quality using
Improvement of the electric power quality using
 

Viewers also liked

Viewers also liked (7)

SMJERNICE o djelovanju centara za pruanje usluga socijalne skrbi dnevnog zbri...
SMJERNICE o djelovanju centara za pruanje usluga socijalne skrbi dnevnog zbri...SMJERNICE o djelovanju centara za pruanje usluga socijalne skrbi dnevnog zbri...
SMJERNICE o djelovanju centara za pruanje usluga socijalne skrbi dnevnog zbri...
 
Rodrigo d no futuro
Rodrigo d no futuro Rodrigo d no futuro
Rodrigo d no futuro
 
Conference proposal VAASL.org
Conference proposal VAASL.orgConference proposal VAASL.org
Conference proposal VAASL.org
 
Succeed with mathematical games
Succeed with mathematical gamesSucceed with mathematical games
Succeed with mathematical games
 
Praveen
PraveenPraveen
Praveen
 
Squares Review Flashcards
Squares Review FlashcardsSquares Review Flashcards
Squares Review Flashcards
 
Psychology5
Psychology5Psychology5
Psychology5
 

Similar to Yasre

Micro-controller based Automatic Power Factor Correction System Report
Micro-controller based Automatic Power Factor Correction System ReportMicro-controller based Automatic Power Factor Correction System Report
Micro-controller based Automatic Power Factor Correction System ReportTheory to Practical
 
power factor correction using smart relay
power factor correction using smart relaypower factor correction using smart relay
power factor correction using smart relayHatem Seoudy
 
Importance of reactive power in determining the cost of power system in futur...
Importance of reactive power in determining the cost of power system in futur...Importance of reactive power in determining the cost of power system in futur...
Importance of reactive power in determining the cost of power system in futur...Shubham Sachan
 
Project on STATCOM
Project on STATCOMProject on STATCOM
Project on STATCOMSutirtha Das
 
report of Improvement of the Electric Power Quality Using Series Active and S...
report of Improvement of the Electric Power Quality Using Series Active and S...report of Improvement of the Electric Power Quality Using Series Active and S...
report of Improvement of the Electric Power Quality Using Series Active and S...Vikram Rawani
 
HYBRID ACTIVE POWER FILTER FOR EFFECTIVE COMPENSATION WITH CONTROL SCHEME
HYBRID ACTIVE POWER FILTER FOR EFFECTIVE COMPENSATION WITH CONTROL SCHEMEHYBRID ACTIVE POWER FILTER FOR EFFECTIVE COMPENSATION WITH CONTROL SCHEME
HYBRID ACTIVE POWER FILTER FOR EFFECTIVE COMPENSATION WITH CONTROL SCHEMEBlossoms Anjali
 
Power Quality Improvement Using FACT Devices
Power Quality Improvement Using FACT DevicesPower Quality Improvement Using FACT Devices
Power Quality Improvement Using FACT DevicesIJMER
 
Dynamic Power Factor Correction in a Non Linear Environment
Dynamic Power Factor Correction in a Non Linear EnvironmentDynamic Power Factor Correction in a Non Linear Environment
Dynamic Power Factor Correction in a Non Linear Environmentiosrjce
 
Performance Improvement of the Radial Distribution System by using Switched C...
Performance Improvement of the Radial Distribution System by using Switched C...Performance Improvement of the Radial Distribution System by using Switched C...
Performance Improvement of the Radial Distribution System by using Switched C...idescitation
 
A seven level cascaded multilevel dstatcom for compensation of reactive power...
A seven level cascaded multilevel dstatcom for compensation of reactive power...A seven level cascaded multilevel dstatcom for compensation of reactive power...
A seven level cascaded multilevel dstatcom for compensation of reactive power...IAEME Publication
 
Demodulation_of_Three-Phase_AC_Power_Transients_in.pdf
Demodulation_of_Three-Phase_AC_Power_Transients_in.pdfDemodulation_of_Three-Phase_AC_Power_Transients_in.pdf
Demodulation_of_Three-Phase_AC_Power_Transients_in.pdfmairiad
 
Concepts of Reactive Power Control and Voltage Stability Methods in Power Sys...
Concepts of Reactive Power Control and Voltage Stability Methods in Power Sys...Concepts of Reactive Power Control and Voltage Stability Methods in Power Sys...
Concepts of Reactive Power Control and Voltage Stability Methods in Power Sys...IOSR Journals
 

Similar to Yasre (20)

Thyristor switched capacitor
Thyristor switched capacitorThyristor switched capacitor
Thyristor switched capacitor
 
Micro-controller based Automatic Power Factor Correction System Report
Micro-controller based Automatic Power Factor Correction System ReportMicro-controller based Automatic Power Factor Correction System Report
Micro-controller based Automatic Power Factor Correction System Report
 
power factor correction using smart relay
power factor correction using smart relaypower factor correction using smart relay
power factor correction using smart relay
 
Importance of reactive power in determining the cost of power system in futur...
Importance of reactive power in determining the cost of power system in futur...Importance of reactive power in determining the cost of power system in futur...
Importance of reactive power in determining the cost of power system in futur...
 
Survey of dc motor
Survey of dc motorSurvey of dc motor
Survey of dc motor
 
Project on STATCOM
Project on STATCOMProject on STATCOM
Project on STATCOM
 
report of Improvement of the Electric Power Quality Using Series Active and S...
report of Improvement of the Electric Power Quality Using Series Active and S...report of Improvement of the Electric Power Quality Using Series Active and S...
report of Improvement of the Electric Power Quality Using Series Active and S...
 
Ijetr012048
Ijetr012048Ijetr012048
Ijetr012048
 
A review on different control techniques using DSTATCOM for distribution syst...
A review on different control techniques using DSTATCOM for distribution syst...A review on different control techniques using DSTATCOM for distribution syst...
A review on different control techniques using DSTATCOM for distribution syst...
 
D011122934
D011122934D011122934
D011122934
 
HYBRID ACTIVE POWER FILTER FOR EFFECTIVE COMPENSATION WITH CONTROL SCHEME
HYBRID ACTIVE POWER FILTER FOR EFFECTIVE COMPENSATION WITH CONTROL SCHEMEHYBRID ACTIVE POWER FILTER FOR EFFECTIVE COMPENSATION WITH CONTROL SCHEME
HYBRID ACTIVE POWER FILTER FOR EFFECTIVE COMPENSATION WITH CONTROL SCHEME
 
I41045662
I41045662I41045662
I41045662
 
Me2420192024
Me2420192024Me2420192024
Me2420192024
 
Power Quality Improvement Using FACT Devices
Power Quality Improvement Using FACT DevicesPower Quality Improvement Using FACT Devices
Power Quality Improvement Using FACT Devices
 
H010615159
H010615159H010615159
H010615159
 
Dynamic Power Factor Correction in a Non Linear Environment
Dynamic Power Factor Correction in a Non Linear EnvironmentDynamic Power Factor Correction in a Non Linear Environment
Dynamic Power Factor Correction in a Non Linear Environment
 
Performance Improvement of the Radial Distribution System by using Switched C...
Performance Improvement of the Radial Distribution System by using Switched C...Performance Improvement of the Radial Distribution System by using Switched C...
Performance Improvement of the Radial Distribution System by using Switched C...
 
A seven level cascaded multilevel dstatcom for compensation of reactive power...
A seven level cascaded multilevel dstatcom for compensation of reactive power...A seven level cascaded multilevel dstatcom for compensation of reactive power...
A seven level cascaded multilevel dstatcom for compensation of reactive power...
 
Demodulation_of_Three-Phase_AC_Power_Transients_in.pdf
Demodulation_of_Three-Phase_AC_Power_Transients_in.pdfDemodulation_of_Three-Phase_AC_Power_Transients_in.pdf
Demodulation_of_Three-Phase_AC_Power_Transients_in.pdf
 
Concepts of Reactive Power Control and Voltage Stability Methods in Power Sys...
Concepts of Reactive Power Control and Voltage Stability Methods in Power Sys...Concepts of Reactive Power Control and Voltage Stability Methods in Power Sys...
Concepts of Reactive Power Control and Voltage Stability Methods in Power Sys...
 

Recently uploaded

Heart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptxHeart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptxPoojaBan
 
Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...VICTOR MAESTRE RAMIREZ
 
Call Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile serviceCall Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile servicerehmti665
 
CCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdf
CCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdfCCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdf
CCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdfAsst.prof M.Gokilavani
 
What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxWhat are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxwendy cai
 
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVRajaP95
 
GDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentationGDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentationGDSCAESB
 
Oxy acetylene welding presentation note.
Oxy acetylene welding presentation note.Oxy acetylene welding presentation note.
Oxy acetylene welding presentation note.eptoze12
 
Arduino_CSE ece ppt for working and principal of arduino.ppt
Arduino_CSE ece ppt for working and principal of arduino.pptArduino_CSE ece ppt for working and principal of arduino.ppt
Arduino_CSE ece ppt for working and principal of arduino.pptSAURABHKUMAR892774
 
An experimental study in using natural admixture as an alternative for chemic...
An experimental study in using natural admixture as an alternative for chemic...An experimental study in using natural admixture as an alternative for chemic...
An experimental study in using natural admixture as an alternative for chemic...Chandu841456
 
Electronically Controlled suspensions system .pdf
Electronically Controlled suspensions system .pdfElectronically Controlled suspensions system .pdf
Electronically Controlled suspensions system .pdfme23b1001
 
Sachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective IntroductionSachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective IntroductionDr.Costas Sachpazis
 
complete construction, environmental and economics information of biomass com...
complete construction, environmental and economics information of biomass com...complete construction, environmental and economics information of biomass com...
complete construction, environmental and economics information of biomass com...asadnawaz62
 
Introduction-To-Agricultural-Surveillance-Rover.pptx
Introduction-To-Agricultural-Surveillance-Rover.pptxIntroduction-To-Agricultural-Surveillance-Rover.pptx
Introduction-To-Agricultural-Surveillance-Rover.pptxk795866
 
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort serviceGurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort servicejennyeacort
 

Recently uploaded (20)

Heart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptxHeart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptx
 
Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...
 
Call Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile serviceCall Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile service
 
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCRCall Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
 
CCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdf
CCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdfCCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdf
CCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdf
 
Design and analysis of solar grass cutter.pdf
Design and analysis of solar grass cutter.pdfDesign and analysis of solar grass cutter.pdf
Design and analysis of solar grass cutter.pdf
 
What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxWhat are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptx
 
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
 
GDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentationGDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentation
 
Oxy acetylene welding presentation note.
Oxy acetylene welding presentation note.Oxy acetylene welding presentation note.
Oxy acetylene welding presentation note.
 
Arduino_CSE ece ppt for working and principal of arduino.ppt
Arduino_CSE ece ppt for working and principal of arduino.pptArduino_CSE ece ppt for working and principal of arduino.ppt
Arduino_CSE ece ppt for working and principal of arduino.ppt
 
young call girls in Green Park🔝 9953056974 🔝 escort Service
young call girls in Green Park🔝 9953056974 🔝 escort Serviceyoung call girls in Green Park🔝 9953056974 🔝 escort Service
young call girls in Green Park🔝 9953056974 🔝 escort Service
 
An experimental study in using natural admixture as an alternative for chemic...
An experimental study in using natural admixture as an alternative for chemic...An experimental study in using natural admixture as an alternative for chemic...
An experimental study in using natural admixture as an alternative for chemic...
 
Electronically Controlled suspensions system .pdf
Electronically Controlled suspensions system .pdfElectronically Controlled suspensions system .pdf
Electronically Controlled suspensions system .pdf
 
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptxExploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
 
Sachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective IntroductionSachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
 
young call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Service
young call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Serviceyoung call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Service
young call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Service
 
complete construction, environmental and economics information of biomass com...
complete construction, environmental and economics information of biomass com...complete construction, environmental and economics information of biomass com...
complete construction, environmental and economics information of biomass com...
 
Introduction-To-Agricultural-Surveillance-Rover.pptx
Introduction-To-Agricultural-Surveillance-Rover.pptxIntroduction-To-Agricultural-Surveillance-Rover.pptx
Introduction-To-Agricultural-Surveillance-Rover.pptx
 
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort serviceGurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
 

Yasre

  • 1. The Reactive Power, Does It Important For Us I. INTRODUCTION A. DEFINITION OF REACTIVE POWER Almost all power transported or consumed in alternating current (AC) networks. AC systems supply or consume two kind of power: real power and reactive power .Real power accomplishes useful work while reactive power supports the voltage that must be controlled for system reliability. For AC systems voltage and current pulsate at the system frequency. Although AC voltage and current pulsate at same frequency, they peak at different time power is the algebraic product of voltage and current. Real power is the average of power over cycle and measured by volt-amperes or watt. The portion of power with zero average value called reactive power measured in volt-amperes reactive or vars. The total power is called the apparent power (symbolized by the capital letter S) and measured by volt-amperes or VA. To describe the reactive power , imagine a person on trampoline , The person real power goes into moving horizontally across trampoline as it bounces , the effort the person expend to keep standing(represent reactive power Q ) during bouncing result no net forward motion(represent real power P) , but it's necessary to walk on trampoline . The motion from trampoline always perpendicular to the direction the person is walking. So that the direction between P and Q 90 degree Out of phase. II. Measuring reactive power The amount and complexity of household electrical equipment has increased tremendously over the last few years. Electronic ballast lighting, computer monitors and air conditioners are welcome additions to our homes but come with additional
  • 2. burdens. One of these is on the electricity grid, as these appliances generate more signal harmonics. This change in the end-consumer profile is a disadvantage for energy distributors which bill energy based only on active power. With the application of non-linear loads to power lines the active energy no longer represents the total energy delivered. As a response to improve billing, the measurement of reactive energy is gaining interest. For example, Italy’s leading energy distributor has decided to install more than 20 million household energy meters with active and reactive power measurements. This growing interest in measuring reactive energy leads to the question: What method should an energy meter designer implement to accurately measure the reactive energy? Although today’s electronic digital signal processing (DSP) enables reactive energy measurements to be closer to the theoretical value, there is no consensus in the field of energy metering on the methods of measurement. This article aims to explain and compare the three main methods in use, namely the Power Triangle, the Time Delay and Low-pass Filter. A. System requirements Electromechanical meters have set a precedent in reactive energy billing. Although they are bandwidth limited and cannot take into account harmonics of the line frequency, they are supported by the international standard for alternating current static var-hour meters for reactive energy (IEC-1268). The standard defines reactive energy measurements at the fundamental line frequency, which implies that it is not mandatory to include harmonics. It also specifies additional testing conditions to check the robustness of the measurements against the third harmonic, the dc offset in the current input, and the line frequency variation. The various reactive power measurement methods presented in this paper are evaluated against these critical tests of the IEC-1268 (Table 1). B. Reactive power theory The reactive power is defined in the IEEE Standard Dictionary 100-1996 under the energy “magner” as: (1) where Vn and In are respectively the voltage and current rms values of the nth harmonics of the line frequency, and jn is the phase difference between the voltage and the current nth harmonics. A convention is also adopted stating that the reactive energy should be positive when the current is leading the voltage (inductive load). In an electrical system containing purely sinusoidal voltage and current waveforms at a fixed frequency, the measurement of reactive power is easy and can be accomplished using several methods without errors. However, in the presence of non-
  • 3. sinusoidal waveforms, the energy contained in the harmonics causes measurement errors. According to the Fourier theorem any periodic waveform can be written as a sum of sin and cosine waves. As energy meters deal with periodic signals at the line frequency both current and voltage inputs of a single phase meter can be described by: (2) (3) where Vn, In and jn are defined as in Equation 1. C. Active power The average active power is defined as: (4) The implementation of the active power measurement is relatively easy and is done accurately in most energy meters in the field. D. Apparent power The apparent power is the maximum real power that can be delivered to a load. As Vrms and Irms are the effective voltage and current delivered to the load, Apparent power = Vrms • Irms (5) The correct implementation of the apparent energy measurement is bound by the accuracy of the rms measurements. E. Reactive power calculation As explained above, different methods can be used to calculate the reactive power. The theoretical definition of the reactive power is difficult to implement in an electronic system at a reasonable cost. It requires a dedicated DSP to process the Hilbert transform necessary to get a constant phase shift of 90° at each frequency. Several solutions have been developed to overcome this limitation. They can be categorized in three groups: 1- Method 1: Power triangle The Power triangle method is based on the assumption that the three energies, apparent, active and reactive, form a right-angle triangle as shown in Figure 1. The reactive power can
  • 4. (6) then be processed by estimating the active and apparent energies and applying: Although this method gives excellent results with pure sinusoidal waveforms, noticeable errors appear in presence of harmonics (Table 1). 2- Method 2: Time delay A time delay is introduced to shift one of the waveforms by 90° at the fundamental frequency and multiply the two waveforms: (7) where T is the period of the fundamental. In an electronic DSP system, this method can be implemented by delaying the samples of one input by the number of samples representing a quarter-cycle of the fundamental frequency (Fline) (Figure 2) This method presents drawbacks if the line frequency changes and the number of samples no longer represents a quarter-cycle of the fundamental frequency. Significant errors are then introduced to the results (Table 1). 3- Method 3: Low-pass filter A constant 90° phase shift over frequency with an attenuation of 20 dB/decade is introduced. This solution, which has been implemented by Analog Devices, can be realized with a single pole low-pass filter on one channel input (Figure 3). If the cut- off frequency of the low-pass filter is much lower than the fundamental frequency, this solution provides a 90° phase shift at any frequency higher than the fundamental frequency. It also attenuates these frequencies by 20 dB/decade (Figure 4). Similarly to method 2, this solution is susceptible to variations of the line frequency. However, a dynamic compensation of the gain attenuation with the line frequency can be achieved by evaluating the line period of the signal (Table 1).
  • 6. entertainment in the modern home. With these advances have come increased burdens on utilities that transmit electricity and on consumers that pay for its use. A portion of this burden is due to reactive power. If you were to compare the amount of electricity flowing into your home (i.e. apparent power) with that which performs productive work (i.e. real power) you would see that there is a difference. Known as reactive power, this additional energy is needed to energize motor windings and similar type loads in your home. Reactive power is returned to the electric grid as the windings de-energize, but is quickly needed again since motor windings must be re-energized 120 times per second. Reactive power does no real work, (e.g. turning a fan blade) but provides the magnetizing energy so that real work can be done. III. NEEDS OF REACTIVE POWER Voltage control in an electrical power system is important for proper operation for electrical power equipment to prevent damage such as overheating of generators and motors, to reduce transmission losses and to maintain the ability of the system to withstand and prevent voltage collapse. In general terms, decreasing reactive power causing voltage to fall while increasing it causing voltage to rise. A voltage collapse occurs when the system try to serve much more load than the voltage can support. When reactive power supply lower voltage, as voltage drops current must increase to maintain power supplied, causing system to consume more reactive power and the voltage drops further . If the current increase too much, transmission lines go off line, overloading other lines and potentially causing cascading failures. If the voltage drops too low, some generators will disconnect automatically to protect themselves. Voltage collapse occurs when an increase in load or less generation or transmission facilities causes dropping voltage, which causes a further reduction in reactive power from capacitor and line charging, and still there further voltage reductions. If voltage reduction continues, these will cause additional elements to trip, leading further reduction in voltage and loss of the load. The result in these entire progressive and uncontrollable declines in voltage is that the system unable to provide the reactive power required supplying the reactive power demands. Reactive power needs are determined in the planning process, which is a part of engineering, part economics and part judgment. The engineering analysis requires running large, complex mathematical computer models of the electric system. The economical part required putting costs into models to determine how to achieve an efficient, reliable system. The judgment arises due to the large number of modeling choices, expert assumption and approximations that often are necessary. A. Reactive power blackouts Insufficient reactive power leading to voltage collapse has been a causal factor in major blackouts in the worldwide. Voltage collapse occurred in United States in the blackout of July 2, 1996, and August10, 1996 on the West Coast. Voltage collapse also factored in blackouts of December 19, 1978, in France; July 23, 1987, in Tokyo;
  • 7. March 13, 1989, in Québec; August 28, 2003, in London; September 28, 2003, in Sweden and Denmark; and September 28, 2003, in Italy. While August 14, 2003, blackout in the United States and Canada was not due to a voltage collapse as that term has traditionally used by power system engineers, the task force final report said that" Insufficient reactive power was an issue in the blackout" and the report also "overestimation of dynamics reactive output of system generation " as common factor among major outages in the United States. Due to difficulties modeling dynamic generators output, the amount of dynamic reactive output from generators has been less than expected, worsening voltage problems and resultant power outages V. PROBLEMS OF REACTIVE POWER Though reactive power is needed to run many electrical devices, it can cause harmful effects on your appliances and other motorized loads, as well as your electrical infrastructure. Since the current flowing through your electrical system is higher than that necessary to do the required work, excess power dissipates in the form of heat as the reactive current flows through resistive components like wires, switches and transformers. Keep in mind that whenever energy is expended, you pay. It makes no difference whether the energy is expended in the form of heat or useful work. We can determine how much reactive power your electrical devices use by measuring their power factor, the ratio between real power and true power. A power factor of 1 (i.e. 100%) ideally means that all electrical power is applied towards real work. Homes typically have overall power factors in the range of 70% to 85%, depending upon which appliances may be running. Newer homes with the latest in energy efficient appliances can have an overall power factor in the nineties. The typical residential power meter only reads real power, i.e. what you would have with a power factor of 100%. While most electric companies do not charge residences directly for reactive power, it’s a common misconception to say that reactive power correction has no economic benefit. To begin with, electric companies correct for power factor around industrial complexes, or they will request the offending customer to do so at his expense, or they will charge more for reactive power. Clearly electric companies benefit from power factor correction, since transmission lines carrying the additional (reactive) current to heavily industrialized areas costs them money. Many people overlook the benefits that power factor correction can offer the typical home in comparison to the savings and other benefits that businesses with large inductive loads can expect. . Most importantly, you pay for reactive power in the form of energy losses created by the reactive current flowing in your home. These losses are in the form of heat and cannot be returned to the grid. Hence you pay. The fewer kilowatts expended in the
  • 8. home, whether from heat dissipation or not, the lower the electric bill. Since power factor correction reduces the energy losses, you save. As stated earlier, electric companies correct for power factor around industrial complexes, or they will request the offending customer to do so, or they will charge for reactive power. They’re not worried about residential service because the impact on their distribution grid is not as severe as in heavily industrialized areas. However, it is true that power factor correction assists the electric company by reducing demand for electricity, thereby allowing them to satisfy service needs elsewhere. But who cares? Power factor correction lowers your electric bill by reducing the number of kilowatts expended, and without it your electric bill will be higher, guaranteed. We’ve encountered this with other electric companies and have been successful in getting each of them to issue a retraction. Electric companies do vary greatly and many show no interest in deviating from their standard marketing strategy by acknowledging proven energy saving products. Keep in mind that promoting REAL energy savings to all their customers would devastate their bottom line. Power factor correction will not raise your electric bill or do harm to your electrical devices. The technology has been successfully applied throughout industry for years. When sized properly, power factor correction will enhance the electrical efficiency and longevity of inductive loads. Power factor correction can have adverse side effects (e.g. harmonics) on sensitive industrialized equipment if not handled by knowledgeable, experienced professionals. Power factor correction on residential dwellings is limited to the capacity of the electrical panel (200 amp max) and does not over compensate household inductive loads. By increasing the efficiency of electrical systems, energy demand and its environmental impact is lessened Conclusion Efficient completion is a way to achieve efficiency and reduce costs to consumers. Efficient competition is difficult to achieve. Due to innovation and technological progress, the optimal industry structure and mode of regulation may not need to change. As regulated markets move from franchised monopolies toward completion, Regulation needs to move from direct price regulation to market rules. Competitive markets required competitive market design. Put difficulties, efficient market design does not just happen spontaneously. It is the result of a process that includes full discussion, learning and informed judgment by all affective and responsible parties.