SlideShare a Scribd company logo
1 of 11
Download to read offline
IOSR Journal of Computer Engineering (IOSR-JCE)
e-ISSN: 2278-0661, p- ISSN: 2278-8727Volume 11, Issue 2 (May. - Jun. 2013), PP 15-25
www.iosrjournals.org
www.iosrjournals.org 15 | Page
Concepts of Reactive Power Control and Voltage Stability
Methods in Power System Network
Okwe Gerald Ibe, Akwukwaegbu Isdore Onyema MNSE
Department of Electrical/Electronic Engineering Federal University of Technology Owerri Imo State
(NIGERIA)
Abstract: The intent of this paper is to present an analysis of reactive power control and voltage stability in
power systems. It identifies a new model used to enhance voltage stability and exposes several key issues that
had remained as research challenges in this area. The steady state voltage and reactive power control in
distribution systems can be properly controlled by coordinating the available voltage and reactive power
control equipment, such as on-load tap-changers, substation shunt capacitors and feeder shunt capacitors. It
began with an overview of reactive power and voltage stability in transmission, distribution and load, and the
importance of providing reactive power locally. The description of selected control features of shunt power
systems such as SVC (Static Var Compensator) – static compensators of reactive power, STATCOM-type
systems (Static Compensator) static reactive power generators and systems that combine both these solutions,
which are referred to as SVC based on STATCOM where not left out. It explains the need to improve the voltage
safety of Power system, as well as the increasing requirements for energy quality and security. It also discusses
the techniques that were adopted in controlling and monitoring of the rate of power flow in the entire power
system topology. This investigates the system to an optimal level in order to reduce losses and ensures
sufficiency of reactive power control during normal and emergency conditions and to prevent voltage collapse.
Keywords: Reactive Power, Voltage stability, Voltage Collapse, Power system security, voltage control
I. Introduction
The control of voltage and reactive power is a major issue in power system operation. This is because
of the topological differences between distribution and transmission systems, different strategies have evolved.
This paper contains contributions of novel reactive power control and voltage stability schemes for distribution
and transmission systems. A particular interest is taken to the development of control schemes to avoid so-called
voltage collapse, which can result in widespread outages. In order to achieve efficient and reliable operation of
power system, the control of voltage and reactive power should satisfy the following objectives [1]:
• Voltages at all terminals of all equipment in the system are within acceptable limits
• System stability is enhanced to maximize utilization of the transmission system
• The reactive power flow is minimized so as to reduce R I 2
and X I 2
losses.
This ensures that the transmission system operates mainly for active power. Thus the power system
supplies power to a vast number of loads and is feeding from many generating units, there is a problem of
maintaining voltages within required limits. As load varies, the reactive power requirements of the transmission
system vary. Since the reactive power cannot be transferred or transported over long distances, voltage control
has to be effected by using special devices located through the system which possess difficulties in keeping
sufficient levels of voltage in the power system network. This has been occurring practically since the first
power systems started. Increasing requirements regarding both the supply reliability and quality of supplied
power force using more modern (faster, more reliable, with a broader range of applications) devices. The proper
selection and coordination of equipment for controlling reactive power and voltage stability are among the
major challenges of power system engineering [1]. These challenges gave birth to some selected devices to
control or compensate reactive power. In order to cover the additional demand for reactive power and maintain
the ability to control voltage stability within the target range, various sources of reactive power, such as SVC
(Static Var Compensator) – static compensators of reactive power, STATCOM-type systems (Static
Compensator) static reactive power generators and systems that combine both these solutions, which are
referred to as SVC based on STATCOM. In recent decades there has been significant progress in terms of
equipment designed to improve the stability of voltage in power systems. This is mainly due to the development
of power supply systems in the world, which requires seeking better ways of adjusting and controlling power
flows and voltage levels.
Almost all power transported or consumed in alternating current (AC) networks, supply or consume
two of powers: real power and reactive power. Real power accomplishes useful work while reactive power
supports the voltage that must be controlled for system reliability. Reactive power is essential to move active
power through the transmission and distribution system to the customer. For AC systems voltage and current
Concepts Of Reactive Power Control And Voltage Stability Methods In Power System Network
www.iosrjournals.org 16 | Page
pulsate at the system frequency. Although AC voltage and current pulsate at same frequency, they peak at
different time power is the algebraic product of voltage and current. Real power is the average of power over
cycle and measured by volt-amperes or watt. The portion of power with zero average value called reactive
power measured in volt-amperes reactive or vars.
1.1 Reactive Power Control in Electrical Systems
During the daily operation, power systems may experience both over-voltage and under-voltage
violations that can be overcomed by voltage/Var control [1].Through controlling the production, adsorption, and
flow of reactive power at all levels in the system, voltage/Var control can maintain the voltage profile within
acceptable limit and reduce the transmission losses. Transmission connected generators are generally required to
support reactive power flow. For example, Transmission system generators are required by the Grid Code
Requirements to supply their rated power between the limits of 0.85 power factor lagging and 0.90 power factor
leading at the designated terminals. The system operator will perform switching actions to maintain a secure and
economical voltage profile while maintaining a reactive power balance equation:
1.1.1 Generator - MVARs + System gain + Shunt capacitors = [MVAR - Demand + Reactive losses +
Shunt reactors] ……………………………… (1)
The „System gain‟ is an important source of reactive power in the above power balance equation, which is
generated by the capacitive nature of the transmission network itself. By making decisive switching actions in
the early morning before the demand increases, the system gain can be maximized early on, helping to secure
the system for the whole day. To balance the equation some pre-fault reactive generator use will be required.
Other sources of reactive power that will also be used include shunt capacitors, shunt reactors, Static VAR
Compensators and voltage control circuits
1.1.2 Reactive power theory
the reactive power is defined in the IEEE Standard Dictionary 100-1996 under the energy “magner” as:
where Vn and In are respectively the voltage and current rms values of the nth
harmonics of the line frequency,
and In is the phase difference between the voltage and the current nth
harmonics. A convention is also adopted
stating that the reactive energy should be positive when the current is leading the voltage (inductive load).In an
electrical system containing purely sinusoidal voltage and current waveforms at a fixed frequency, the
measurement of reactive power is easy and can be accomplished using several methods without errors.
However, in the presence of non-sinusoidal waveforms, the energy contained in the harmonics causes
measurement errors. According to the Fourier theorem any periodic waveform can be written as a sum of sin
and cosine waves. As energy meters deal with periodic signals at the line frequency both current and voltage
inputs of a single phase meter
can be described by:
Where Vn and In are defined as in Equation 2.
Active power
the average active power is defined as:
The implementation of the active power measurement is relatively easy and is done accurately in most energy
meters in the field.
Apparent power
The apparent power is the maximum real power that can be delivered to a load. As Vrms and Irms are the effective
voltage and current delivered to the load,
Apparent power = Vrms • Irms …………..……………………………….. (6)
……………………………………………………(3)
………………………………......… (4)
…………………….. (5)
………………………….. (2)
Concepts Of Reactive Power Control And Voltage Stability Methods In Power System Network
www.iosrjournals.org 17 | Page
The correct implementation of the apparent energy measurement is bound by the accuracy of the rms
measurements.
1.2 Importance of Reactive Power
Voltage control in an electrical power system is important for proper operation for electrical power
equipment to prevent damage such as overheating of generators and motors, to reduce transmission losses and to
maintain the ability of the system to withstand and prevent voltage collapse. In general terms, decreasing
reactive power causing voltage to fall while increasing it causing voltage to rise. A voltage collapse occurs
when the system try to serve much more load than the voltage can support. When reactive power supply
lower voltage, as voltage drops current must increase to maintain power supplied, causing system to consume
more reactive power and the voltage drops further . If the current increases too much, transmission lines go off
line, overloading other lines and potentially causing cascading failures. If the voltage drops too low, some
generators will disconnect automatically to protect themselves. Voltage collapse occurs when an increase in load
or less generation or transmission facilities causes dropping voltage, which causes a further reduction in reactive
power from capacitor and line charging, and still there further voltage reductions. If voltage reduction continues,
these will cause additional elements to trip, leading further reduction in voltage and loss of the load. The result
in these entire progressive and uncontrollable declines in voltage is that the system unable to provide the
reactive power required supplying the reactive power demands.
1.3 Problems of Reactive Power
Though reactive power is needed to run many electrical devices, it can cause harmful effects on your
appliances and other motorized loads, as well as your electrical infrastructure. Since the current flowing through
your electrical system is higher than that necessary to do the required work, excess power dissipates in the form
of heat as the reactive current flows through resistive components like wires, switches and transformers. Keep in
mind that whenever energy is expended, you pay. It makes no difference whether the energy is expended in the
form of heat or useful work. We can determine how much reactive power your electrical devices use by
measuring their power factor, the ratio between real power and true power. A power factor of 1 (i.e. 100%)
ideally means that all electrical power is applied towards real work. Homes typically have overall power factors
in the range of 70% to 85%, depending upon which appliances may be running. Newer homes with the latest in
energy efficient appliances can have an overall power factor in the nineties. The typical residential power meter
only reads real power, i.e. what you would have with a power factor of 100%. While most electric companies do
not charge residences directly for reactive power, it‟s a common misconception to say that reactive power
correction has no economic benefit. To begin with, electric companies correct for power factor around industrial
complexes, or they will request the offending customer to do so at his expense, or they will charge more for
reactive power. Clearly electric companies benefit from power factor correction, since transmission lines
carrying the additional (reactive) current to heavily industrialized areas costs them money.
1.4 The aim of power factor correction
Many people overlook the benefits that power factor correction can offer the typical home in
comparison to the savings and other benefits that businesses with large inductive loads can expect. Most
importantly, you pay for reactive power in the form of energy losses created by the reactive current flowing in
your home. These losses are in the form of heat and cannot be returned to the grid. Hence you pay. The fewer
kilowatts expended in the home, whether from heat dissipation or not, the lower the electric bill. Since power
factor correction reduces the energy losses, you save. As stated earlier, electric companies correct for power
factor around industrial complexes, or they will request the offending customer to do so, or they will charge for
reactive power. They‟re not worried about residential service because the impact on their distribution grid is not
as severe as in heavily industrialized areas. However, it is true that power factor correction assists the electric
company by reducing demand for electricity, thereby allowing them to satisfy service needs elsewhere. But who
cares? Power factor correction lowers your electric bill by reducing the number of kilowatts expended, and
without it your electric bill will be very exorbitant.
In the most cases, PFC is used for economic reasons. Using compensating device, one can save on
electricity bill as well as keep certain grid parameters determined by the energy provider. Power factor
correction gives even more profits, than only savings. Compensating “unnecessary” reactive power the current
carrying capacity of an existing network can be sufficient to send more active power through it, maintaining the
same ratings of the apparatus within the supplying and distribution system. PFC also allows to decrease
transmission losses and limits voltage drops. Generally, reliability of the network gets better. But one should be
aware, that compensating device connected to the mains can also have negative consequences like:
 Transient generation
 Higher order harmonics generation
Concepts Of Reactive Power Control And Voltage Stability Methods In Power System Network
www.iosrjournals.org 18 | Page
 Long lasting voltage rise
 Gain of higher order harmonics
 Voltage drops, outages and Overvoltage of short duration
 Other kind of distortions
2.1 Overview on Different Voltage and Reactive Power Control Methods
Voltage and reactive power control involves proper coordination among the voltage and reactive power
control equipment in the distribution system to obtain an optimum voltage profile and optimum reactive power
flows in the system according to the objective function and operating constraints. Many DNOs operate OLTC
and shunt capacitors locally by using conventional controllers, e.g., voltage controller for the OLTC and either
voltage, reactive power or time controllers for the capacitors; to perform basic voltage and reactive power
control functions, e.g., to maintain the voltages in the distribution system within the acceptable range and to
minimize power losses. Different voltage and reactive power control methods have been proposed. Properly
locating and sizing shunt capacitors will decrease power losses. As an improvement to the capacitor planning
based on the load size, methods to include customer load profiles and characteristics in the capacitor planning
are proposed in [30]-[32]. Proper capacitor planning will also improve the voltage profile in the distribution
system. The capacitor locating and sizing is studied and executed in the planning stage of the distribution
system. In order to enhance the distribution system further, the capacitor should also be switched properly in the
operation stage of the distribution system [31], using different types of available capacitor control. Most
recently, many researchers have addressed the problem of voltage and reactive power control in distribution
systems by focusing on automated distribution systems, such as in [36]-[40]. At the moment, the voltage and
reactive power control based on automated distribution systems can be divided into two categories: off-line
setting control and real time control [39]. The off-line setting control, [39]-[40] for instance, aims to find a
dispatch schedule for the capacitor switching and the OLTC movement based on a one day ahead load forecast.
Meanwhile, the real time control, [36]-[38] for instance, aims to control the capacitor and OLTC based on real
time measurements and experiences.
The application of dispatch schedule based load forecasting is motivated by the fact that although there
is a random fluctuation in the load variation, the major component of the load variations is related to weather
conditions. Furthermore, there is a deterministic load pattern during the day due to social activities [38].
Therefore, the load profile is quite predictable. It can be forecasted one-day-ahead with an average error less
than 2% [41]-[42]. Different objective functions and operating constraints have been proposed in voltage and
reactive power control with automated distribution systems. Nevertheless, all researchers [36]-[40] still consider
loss Minimization and keeping the voltage within the acceptable range as the main objective and constraint in
the voltage and reactive power control. Another objective that is commonly proposed is flattering the voltage
profile [38], [40]. Commonly added operating constraints include the maximum number of OLTC operations
and capacitor switchings [37], [39]-[40], and the minimum distribution system of [37]. Other references, such as
[38], consider minimization of OLTC operations and capacitor switching as the objective function. The
automated control with off-line setting proposed in [39]-[40] fully replaces the local control operation of the
conventional OLTC and capacitor operations with a remotely controlled operation. The main obstacle
application of this method is its dependency on communication links and remote control to all capacitors.
However, many DNOs do not have communication links downstream to the feeder capacitor locations
2.1.1 Distribution System Voltage Control
Distribution system voltage control is sometimes referred to as volt/var control (VVC), which Grainger
and Civanlar (1985) specify as follows: The objective is to minimize the peak power and energy losses while
keeping the voltage within specified limits for a variety of nominal load patterns. This objective is formulated as
an optimization problem that is solved off-line, based on nominal load patterns. The optimization variables are
the locations, sizes and control dead bands of capacitors and tap changer voltage regulators. Tap changers are
normally automatically controlled by a relay controller that measures and regulates the secondary side voltage of
the transformer. The control of transformers operating in parallel in the same substation must be coordinated to
minimize circulating reactive power flows (Lakervi and Holmes, 1989).
2.1.2Transmission System Voltage Control
In practical operation of transmission systems, the voltage needs to be continuously monitored and
controlled to compensate for the daily changes in load, generation and network structure. In fact, the control of
voltage is a major issue in power system operation. Kundur (1994).It identifies the main objectives of voltage
control as: Voltage at the terminals of all equipment in the system should be kept within acceptable limits, to
avoid malfunction of and damage to the equipment. Keeping voltages close to the values for which stabilizing
controls are designed, to enhance system stability and allow maximal utilization of the transmission system.
Concepts Of Reactive Power Control And Voltage Stability Methods In Power System Network
www.iosrjournals.org 19 | Page
Minimize reactive power flows, to reduce active as well as reactive power losses. Whereas distribution systems
as a rule are operated in radial configuration. Consequently, more sophisticated control schemes than those used
in distribution systems are necessary. The control of voltage is often divided into the normal, preventive and
emergency state control. A brief overview of the strategies used in the different operating states follows:-
Primary Control
Primary voltage controllers are used in all power systems to keep the terminal voltages of the
generators close to reference values given by the operator or generated by a secondary controller. An automatic
voltage regulator (AVR) acts on the exciter of a synchronous machine, which supplies the field voltage and
consequently the current in the field winding of the machine and can thereby regulate its terminal voltage. The
response time of the primary controller is short, typically fractions of a second for generators with modern
excitation systems. Furthermore, many generators use a so-called power system stabilizer (PSS) to modulate the
terminal voltage of the machine based on a local frequency measurement to contribute to damping of
electromechanical oscillations. Although the power system stabilizer in most cases is integrated in the AVR, it
only introduces fast oscillations around the mean value given by the AVR as long as the generator remains
synchronized with the rest of the network.
Secondary Control
Secondary voltage control acts on a time-scale of seconds to a minute and within regions of the
network. The aim of secondary voltage control is to keep an appropriate voltage profile in a region of the system
and to minimize circulating reactive power flows and maximize reactive reserves. Normally, the network is
divided in a number of geographic regions. One or a few so-called pilot nodes, which are assumed to be
representative of the voltage situation in the region, are selected for voltage regulation by the secondary
controller. The main actuators are the set point voltages of the primary controllers of the generators within a
region, although the French implementation also uses static compensation devices such as capacitor banks and
reactors. The set point values are calculated by an optimization procedure using a linearized static network
model to make each generator in the region contribute to the control of the pilot node voltage(s).
Tertiary Control
Tertiary voltage control acts system-wide on a time scale of about ten to thirty minutes. The traditional
method of tertiary control is so-called reactive power optimal power flow (OPF) (Carpentier, 1962, Dommel and
Tinney, 1968). The desired operating conditions are specified in the form of a cost function, which is minimized
using nonlinear optimization techniques. Usually, the main goal is to minimize losses and to keep voltages close
to rated values. A secondary goal may be to maximize and distribute reactive reserves. The main control
variables are voltage set points for the generators, or pilot nodes if secondary control is used, and switching
orders to compensation devices such as shunt capacitors and reactors. The power flow equations (Glover and
Sarma, 1994) are specified as equality constraints in the optimization whereas operational limits such as transfer
limits, limits on reactive reserves and voltages are specified as inequality constraints.
2.2 PREVENTIVE AND EMERGENCY STATE VOLTAGE CONTROL
The operation of power systems can be divided into the states normal, alert or emergency (Kundur,
1994). The system normally operates in the normal state, but enters the alert state if the system cannot be
expected to be robust to the contingencies that have been considered in the design of the system. Such situations
may occur for example due to unexpected load increase or outage of some component, such that a single
contingency may force the system into the emergency state. The system enters the emergency state if a severe
enough contingency occurs, so that the system will experience instability or exceeds operational limits unless
emergency control actions are taken. However, the system is still synchronized in the emergency state.
2.3 ELEMENTS OF THE SYSTEM, THAT PRODUCES AND ABSORBS REACTIVE
POWER
Loads- a typical load bus supplied by a power system is composed of a large number of devices. The
composition changes depending on the day, season and weather conditions. The composite characteristics are
normally such that a load bus absorbs reactive power. Both active and reactive powers of the composite loads
vary due to voltage magnitudes. Loads at low-lagging power factors cause excessive voltage drops in the
transmission network. Industrial consumers are charged for reactive power and this convinces them to improve
the load power factor.
Underground cables- they are always loaded below their natural loads, and hence generate reactive power
under all operating conditions
Concepts Of Reactive Power Control And Voltage Stability Methods In Power System Network
www.iosrjournals.org 20 | Page
Overhead lines- depending on the load current either absorb or supply reactive power. At loads below the
natural load, the lines produce net reactive power; on the contrary, at loads above natural load lines absorb
reactive power.
2.4 WAYS OF IMPROVING VOLTAGE STABILITY AND CONTROL
Reactive power compensation is often most effective way to improve both power transfer capability
and voltage stability. The control of voltage levels is accomplished by controlling the production, absorption and
flow of reactive power. The generating units provide the basic means of voltage control, because the automatic
voltage regulators control field excitation to maintain scheduled voltage level at the terminals of the generators.
To control voltage throughout the system we have to use addition devices to compensate reactive power [1].
Reactive compensation can be divided into series and shunt compensation. It can be also divided into active and
passive compensation [2]. But mostly consideration will be focused on shunt capacitor banks, static var
compensator (SVC) and Static Synchronous Compensators (STATCOM), which are the part of group of active
compensators called Flexible AC Transmission Systems (FACTS). The devices used for these purposes may be
classified as follows:
• Shunt capacitors
• Series capacitors
• Shunt reactors
• Synchronous condensers
• SVC
• STATCOM
2.4.1 SHUNT CAPACITORS
Shunt capacitors and reactors and series capacitors provide passive compensation. They are either
permanently connected to the transmission and distribution system or switched. They contribute to voltage
control by modifying the network characteristics. Synchronous condensers, SVC and STATCOM provide active
compensation [2]. The voltages of the buses to which they are connected. Together with the generating units,
they establish voltages at specific points in the system. Voltages at other locations in the system are determined
by active and reactive power flows through various elements, including the passive compensating devices [1].
The primary purposes of transmission system shunt compensation near load areas are voltage control and load
stabilization. Mechanically switched shunt capacitor banks are installed at major substations in load areas for
producing reactive power and keeping voltage within required limits. For voltage stability shunt capacitor banks
are very useful in allowing nearby generators to operate near unity power factor. This maximizes fast acting
reactive reserve. Compared to SVCs, mechanically switched capacitor banks have the advantage of much lower
cost. Switching speeds can be quite fast. Current limiting reactors are used to minimize switching transients.
There are several disadvantages to mechanically switched capacitors. For voltage emergencies the shortcoming of
shunt capacitor banks is that the reactive power output drops with the voltage squared. For transient voltage
instability the switching may not be fast enough to prevent induction motor stalling. Precise and rapid control of
voltage is not possible. Like inductors, capacitor banks are discrete devices, but they are often configured with
several steps to provide a limited amount of variable control. If voltage collapse results in a system, the stab le
parts of the system may experience damaging over voltages immediately following separation. Shunt capacitors
banks are always connected to the bus rather than to the line. They are connected either directly to the high
voltage bus or to the tertiary winding of the main transformer. Shunt capacitor banks are breaker-switched either
automatically by a voltage relays or manually [1]. Figure 2.1 shows example of capacitor bank.
Figure 2.1 Typical capacitor bank
The primary purpose of transmission system shunt compensation near load areas is voltage control and load
stabilization. In other words, shunt capacitors are used to compensate for X I 2
losses in transmission system and
to ensure satisfactory voltage levels during heavy load conditions. Shunt capacitors are used in power system for
power factor correction. The objective of power factor correction is to provide reactive power close to point
Concepts Of Reactive Power Control And Voltage Stability Methods In Power System Network
www.iosrjournals.org 21 | Page
where it is being consumed, rather than supply it from remote sources [1]. Figure 2.2 shows the influence of
shunt compensation on load bus.
Figure 2.2 a) shunt compensation b) phasor diagram without compensationc) phasor diagram with compensation
Switched shunt capacitors are also used for feeder voltage control. They are installed at appropriate location
along the length of the feeder to ensure that voltages at all points remain the allowable minimum or maximum
limits as the loads vary [2]. For voltage stability, shunt capacitor banks are very useful on allowing nearby
generators to operate near unity power factor. This maximizes fast acting reactive reserve [2]. The biggest
disadvantage of shunt capacitors is that the reactive power output drops with the voltage squared. Thus, during
the severe voltage decays these devices are not efficient enough [2]. Compared to static var compensators,
mechanically switched capacitor banks have the advantage of much lower cost. Switching speeds can be quite
fast. Following a transmission line outage, capacitor bank energization should be delayed to allow time for line
reclosing. However, capacitor switching should be before significant amounts of load are restored by
transformer tap changers or distribution voltage regulators [2]. Despite of many advantages of mechanically
switched capacitors, there is couple of disadvantages as well. Firstly, for transient voltage instability, the
switching may not be fast enough to prevent induction motor stalling. If voltage collapse results in system
breakdown, the stable parts of the system may experience damaging over voltages immediately following
separation. Over voltages would be aggravated by energizing of shunt capacitors during the period of voltage
decay [2].
2.4.2 Shunt reactors
Shunt reactors are mainly used to keep the voltage down, by absorbing the reactive power, in the case of
light load and load rejection, and to compensate the capacitive load of the line. Other equipment can be involved
in the provision of reactive power and energy, such as:
• Unified Power Flow Controllers (UPFC) and other advanced FACTS (flexible ac transmission system)
devices;
• Tap staggering of transformers connected in parallel;
• Disconnection of transmission lines;
• Load shedding
2.4.3 Synchronous condensers
Every synchronous machine (motor or generator) has the reactive power capabilities the same as
synchronous generators. Synchronous machines that are designed exclusively to provide reactive support are
called synchronous condensers. Synchronous condensers have all of the response speed and controllability
advantages of generators without the need to construct the rest of the power plant (e.g., fuel-handling equipment
and boilers). Because they are rotating machines with moving parts and auxiliary systems, they require
significantly more maintenance than static compensators. They also consume real power equal to about 3% of the
machine‟s reactive-power rating. Synchronous condensers are used in transmission systems: at the receiving end
of long transmissions, in important substations and in conjunction with HVDC converter stations. Small
synchronous condensers have also been used in high-power industrial networks to increase the short circuit
power. The reactive power output is continuously controllable. The response time with closed-loop voltage
control is from a few seconds and up, depending on different factors. In recent years the synchronous condensers
Concepts Of Reactive Power Control And Voltage Stability Methods In Power System Network
www.iosrjournals.org 22 | Page
have been practically ruled out by the. Thyristor controlled static VAR compensators, because those are much
more cheaper and have regulating characteristics similar to synchronous condensers.
2.4.4 Static VAR compensators
An SVC combines conventional capacitors and inductors with fast switching capability. Switching takes
place in the sub cycle time frame (i.e. in less than 1/50 of a second), providing a continuous range of control. The
range can be designed to span from absorbing to generating reactive power. Advantages include fast, precise
regulation of voltage and unrestricted, largely transient-free, capacitor bank switching. Voltage is regulated
according to a slope (droop) characteristic. Static VAR compensator could be made up from:
TCR (thyristor controlled reactor);
TSC (thyristor switched capacitor) ;
TSR (thyristor switched reactor);
FC (fixed capacitor);
Because SVCs use capacitors they suffer from the same degradation in reactive capability as voltage drops. They
also do not have the short-term overload capability of generators and synchronous condensers. SVC applications
usually require harmonic filters to reduce the amount of harmonics injected into the power system by the thyristor
switching. SVCs provide direct control of voltage (C.W. Taylor, 1994); this is very valuable when there is little
generation in the load area. The remaining capacitive capability of an SVC is a good indication of proximity to
voltage instability. SVCs provide rapid control of temporary over voltages. But on the other hand SVCs have
limited overload capability, because SVC is a Capacitor bank at its boost limit. The critical or collapse voltage
becomes the SVC regulated voltage and instability usually occurs once an SVC reaches its boost limit. SVCs are
expensive; shunt capacitor banks should first be used to allow unity power factor operation of nearby generators.
2.4.4 Static synchronous compensator (STATCOM)
The STATCOM is a solid-state shunt device that generates or absorbs reactive power and is one member
of a family of devices known as flexible AC transmission system (FACTS) devices. The STATCOM is similar to
the SVC in response speed, control capabilities, and the use of power electronics. Rather than using conventional
capacitors and inductors combined with thyristors, the STATCOM uses self-commutated power electronics to
synthesize the reactive power output. Consequently, output capability is generally symmetric, providing as much
capability for production as absorption. The solid-state nature of the STATCOM means that, similar to the SVC,
the controls can be designed to provide very fast and effective voltage control (B. Kirby, 1997). While not having
the short-term overload capability of generators and synchronous condensers, STATCOM capacity does not
suffer as seriously as SVCs and capacitors do from degraded voltage. STATCOMs are current limited so their
MVAR capability responds linearly to voltage as opposed to the voltage-squared relationship of SVCs and
capacitors. This attribute greatly increases the usefulness of STATCOMs in preventing voltage collapse.
2.4.5 Series capacitors and reactors
Series capacitors compensation is usually applied for long transmission lines and transient stability
improvement. Series compensation reduces net transmission line inductive reactance. The reactive generation I 2
X compensates for the reactive consumption I 2
X of the C transmission line. Series capacitor reactive generation
increases with the current squared, thus generating reactive power when it is most needed. This is a self-
regulating nature of series capacitors. At light loads series capacitors have little effect.
2.5 Power Capacitor Based Compensating Devices
Power factor correction method based on power capacitors is the biggest group of the devices used in
the industry and by the private users, mainly from economic reasons. On the hand, they may be a reason of
unwanted distortions at the spot of operation. That is why they should be carefully selected, in accordance with
actual standards. In terms of rated voltage of capacitors we can distinguish two groups of capacitor banks:
Concepts Of Reactive Power Control And Voltage Stability Methods In Power System Network
www.iosrjournals.org 23 | Page
Figure 2.3. Reactive power capability dependence on real power production for a synchronous generator
Like most electric equipment, generators are limited by their current-carrying capability. Reactive power
production is depended on the field heating limit and absorption on the core end-heating limit of the generator.
Active power output limit is limited by armature heating. Control over the reactive output and the terminal
voltage of the generator is provided by adjusting the DC current in the generator‟s rotating field. Control can be
automatic, continuous, and fast. The inherent characteristics of the generator help maintain system voltage. At
any given field setting, the generator has a specific terminal voltage it is attempting to hold. If the system
voltage declines, the generator will inject reactive power in to the power system, tending to raise system voltage.
If the system voltage rises, the reactive output of the generator will drop, and ultimately reactive power will
flow into the generator, tending to lower system voltage. The voltage regulator will accentuate this behavior by
driving the field current in the appropriate direction to obtain the desired system voltage.
2.6 Reactive Power in Operations
Reactive power affects power system operation in numerous ways:
1 Loads consume reactive power, so this must be provided by some source.
2 The delivery system (transmission lines and transformers) consumes reactive power, so this must be provided
by some source (even if the loads do not consume reactive power). Note however that all transmission lines do
provide some reactive power from their shunt line charging which offsets their consumption of reactive power
in their series line losses.
3 The flow of reactive power from the supplies to the sinks causes additional heating of the lines and voltage
drops in the network.
4 The generation of reactive power can limit the generation of real power. So, one primary dilemma with
reactive power is that a sufficient quantity of it is needed to provide the loads and losses in the network, but
having too much reactive power flowing around in the network causes excess heating and undesirable voltage
drops. The normal answer to this dilemma is to provide reactive power sources exactly at the location where the
reactive power is consumed. And, since strictly speaking it does not take any "fuel" to provide reactive power, it
should be possible to distribute reactive power sources (such as capacitors) all around the network to avoid the
problem of heating the conductors and causing voltage drops. Unfortunately, this is not practical in the extreme
since there are literally millions of lines and loads connected to the grid and so this would require millions of
reactive power sources - all controlled to provide exactly the right amount of reactive power at the right time -
every second of every day. The best we can do in most cases is work with some type of aggregation of load (say
at the feeder leaving a substation) and at terminals of major lines and transformers. This also brings up the issue
of the difference between power factor control (trying to exactly provide the right amount of reactive power
needed to equal that which is consumed) and voltage control (trying to keep voltage levels at exactly the
right level no matter how much reactive power it takes). Reactive power is both the problem and the solution to
network voltage control.
3.1 TECHNICALS CONCEPTS AND NORMS
This paper defines the technical concepts and norms necessary for understanding the voltage instability
(collapse) problem and discusses a number of related issues. Generation and absorption of active and reactive
power by different power system elements where not left out. The lack of supply of reactive power in a system
heavily contributes to the voltage collapse process. The relationship between reactive power and voltage
stability is explained. A number of major incidents of voltage collapse have occurred in different countries in
Concepts Of Reactive Power Control And Voltage Stability Methods In Power System Network
www.iosrjournals.org 24 | Page
the past. The meaning of voltage collapse is described in simple terms and the voltage stability margin is
defined. Contingencies, which are very often the cause of voltage instability, are also discussed.
The voltage collapse: This phenomenon remains a major issue for power system networks. In the words of
Carson Taylor [8], "A power system at a given operating state and subject to a given disturbance undergoes
voltage collapse if post-disturbance equilibrium voltages are below acceptable limits. Voltage collapse may be
total (blackout) or partial. Lack of adequate reactive power resources in a power system is a major contributing
factor to the process of voltage collapse. As loads in a power system increase, voltages across the network tend
to decrease and reactive power losses increase as a result of high current [25]; the reactive loss is proportional to
square of the current. This increased reactive power demand would be supplied by voltage regulating devices
such as generators, static VAR compensators, or capacitors, if possible. However, due to physical limitations,
such devices cannot supply unlimited amounts of reactive power. Often, sustained load growth will result in
some source of reactive power, or perhaps a number of such sources, reaching their physical limits. Once a
reactive power source has reached its maximum limit, it can no longer regulate voltage. Therefore, sustained
load growth results in an accelerated voltage decay, and hence an even greater reactive power requirement. This
may force other voltage regulating devices to their limits, with a subsequent further acceleration in the rate of
decline of voltages. This leads to loss of voltage in a significant part of the system and is described as the
voltage collapse phenomenon. The Institution of Electrical and Electronic Engineers, USA, (IEEE) [6]
defines voltage collapse and voltage instability as:"Voltage collapse is the process by which voltage
instability leads to loss of voltage in a significant part of the system. A system enters a state of voltage
instability when a disturbance, increase in load, or system change causes voltage to drop quickly or drift
downward, and operators and automatic system control fail to halt the decay. The voltage decay may take just a
few seconds but can also be prolonged of the order of 10-20 minutes. If the decay continues unabated, steady
state angular instability or voltage collapse will occur."Voltage collapse: can also be defined the process by
which the sequence of events accompanying voltage instability leads to a low unacceptable voltage profile in a
significant portion of the power system."Similarly, "Voltage stability is the ability of a power system to
maintain steady acceptable voltages at all buses in the system under normal operating conditions and after being
subjected to a disturbance. A system enters a state of voltage instability when a disturbance, increase in load
demand, or change in system condition causes a progressive and uncontrollable drop in voltage. "The main
factor causing instability is the inability of the power system to meet the demand for reactive power. The
heart of the problem is usually the voltage drop that occurs when active power and reactive power flow through
the inductive reactance associated with the transmission network. Voltage Instability is the absence of Voltage
stability, and results in progressive voltage decrease or increase. Power System Security This is the
robustness of the system to imminent disturbance and hence depends on the system operating condition
as well as on the contingent probability of disturbances. Power System Stability may be broadly defined
as the property of a power system that enables it to remain in a state of operating equilibrium after being
subjected to a disturbance.
II. Conclusion
In this paper, several representative techniques of reactive power and voltage/Var control are reviewed.
Their advantages and disadvantages are analyzed. The future challenge is to how to efficiently and accurately
solve the problem taking into consideration the dynamic nature of power systems. In its entirety, it detailed
background information on the on several fundamental properties of reactive power and the consequences of
shortages in reactive power reserves . Open research issues associated with voltage control and reactive power
support have also been discussed. These issues are especially difficult because of the complex interaction
between real and reactive power, from an engineering point of view, and from and economic point of view. It
also explained the fundamentals issues on Reactive power dispatch in electric power system, as a means of
injection of reactive power into the system on the generators for improving voltage stability condition when the
system in heavily loaded situation.
References
[I] Proceedings of Bulk Power System Voltage Phenomena- Voltage Stability and Security. Potosi, MO, September 19-24, 1988.
[2] Proceedings of NSF Workshop on Bulk Power System Voltage Phenomena-Voltage Stability and Security. Deep Creek Lake, MD,
August 4-7, 1991.
[3] Proceedings of Bulk Power System Voltage Phenomena 111- Seminar on Voltage Stability, Security and Control. Davos,
Switzerland, August 22-26, 1994.
[4] Proceedings of the Symposium on Bulk Power System Dynamics and Control IV-Restructuring. Santorini, Greece, August 24-28,
1998.
[5] Proceedings of Bulk Power Systems Dynamics and Control Security and Reliability in a Changing Environment. Onomichi, Japan,
August 26-31, 2001.
[6] C.D. Vournas, P.W. Sauer, and M.A. Pai. Relationships between Voltage and Angel Stability of Power Systems. International
Journal of Electrical Power and Energy Systems, 18:493-500, 1996.
[7] H.P. St. Clair. Practical Concepts in Capability and Performance of Transmission Lines. AIEE Dansactions, 72: 1152-1 157, 1953.
Concepts Of Reactive Power Control And Voltage Stability Methods In Power System Network
www.iosrjournals.org 25 | Page
[8] C.W. Taylor. Power System Voltage Stability. McGraw-Hill, New York, 1994.
[9] P. Kundur. Power System Stability and Control. McGraw Hill, New York, 1994.
[l0] W.R. Lachs. Voltage Collapse in EHV Power Systems. Paper A78057-2, 1978 IEEE PES Winter Meeting, New York, January 28-
February 3, 1978.
[11] Erche, M., Petersson, T. “Reactive Power Sources”. Task Force No 3. CIGRE WG 38-01. April 1987.“Exchange of services
between large electricity generating plants and high voltage electric power systems”. Joint Working Group 39/11. CIGRE, April
1999.
[12] Gil, J.B., San Roman, T.G., Rios, J.J., Martin, P.S. ”Reactive Power Pricing: a Conceptual Framework for Remuneration and
Charging Procedures”. IEEE Transactions on Power Systems, Vol. 15, No.2, May 2000.
[13] Hao, S.H., Papalexopoulos, A. “Reactive Power Pricing and Management “. IEEE Transactions on Power Systems, Vol. 12, No.1,
February 1997.
[14] Kirby, B., Hirst, E. “Ancillary Service Details: Voltage Control”. December 1997.
[15] Larsson, M. (2000) Coordinated Voltage Control in Electric Power Systems. Doctoral dissertation, Department of Industrial
Electrical Engineering and Automation, Lund University.
[16] Miller, T.J. (Editor) "Reactive Power Control in Electric Systems". John Wiley & Sons, New York, 1982."Reactive Power: Basics,
Problems and Solutions”. IEEE Tutorial course. 1987
[17] Taylor, C.W. “Power System Voltage Stability”. McGraw-Hill. ISBN 0-07-063184-0.1994.
[18] Trehan, N. K. “Ancillary Services – Reactive and Voltage Control”. IEEE Winter Meeting 2001. “UCTE-Principles of Network
Operation”. February 1999. Available from www.ucte.org
[19] Xu, W., Zhang, Y., da Silva, L., Kundur, P. ”Competitive Procurement of Dynamic Reactive Power Support Service for
Transmission Access”. IEEE Summer Power Meeting 2000. Whitehead, A. “A New Market in Reactive Power”. Birmingham, UK.
April1998.
[20] IEA, Renewable Energy, Market and Policy Trends in IEA Countries, International Energy Agency, France, 2004.
[21] ESHA, “European Renewable Energy Review 2006”, European Small Hydropower Association, 2007.
http://www.esha.be/fileadmin/ esha_files/documents/publications/articles/ERER2006-Final.pdf, last accessed on 22 Sept, 2007.
[22] S. Rahman, “Green Power: What is and Where We Can Find It?” IEEE Power and Energy Magazine, vol. 1, pp. 30-37, January -
February 2003.
[23] IEA, “Biomass for Power Generation and CHP”, International Energy Agency, 2007. Available at
http://www.iea.org/textbase/techno/essentials3.pdf, last accessed on 22 September 2007.
[24] S. Sheth and M. Shahidehpour, “Tidal Energy in Electric Power Systems”, in Proc. of IEEE Power Engineering Society General
Meeting, 2005.
[25] R. Dettmer, “Wave Energy Gets Seaworthy”, IEE Review, September 2002.
[26] M. Leijon, H. Bernhoff, O. Ågren, J. Isberg, J. Sunberg, M. Berg, K.E. Karlsson and A. Wolfbrandt, “Multiphysics Simulation of
Wave Energy to Electric Energy Conversion by Permanent Magnet Linear Generator”, IEEE Transactions on Energy Conversions,
vol. 20, no.1, March 2005.
[27] Uppsala Universitet, “Wave Power Project – Islandsberg”. Available at http://www.el.angstrom.uu.se/meny/eng/index_E.html, last
accessed on 7 Jan 2008.
[28] M. Thomson, “Automatic voltage control relays and embedded generation. Part I”, Power Engineering Journal, vol. 14, pp. 71 –
76, April 2000.
[29] C.W. Taylor, Power System Voltage Stability, Mc Graw Hill, 1994.
[30] T.S. Abdel Salam, A.Y. Chikhani and R. Hackam, “A New Technique for Loss Varying Load Condition”, IEEE Transactions on
Power Delivery, vol. 9, no. 2, April 1994.
[31] M.Y. Cho and Y.W. Chen, “Fixed/Switched Type Shunt Capacitor Planning of Distribution Systems by Considering Customer
Load Patterns and Simplified Feeder Model”, IEE Proc.-Gener, Transm, Distrib., vol. 144, no. 6, November 1997.
[32] B. Milosevic and M. Begovic, “Capacitor Placement for Conservative Voltage Reduction on Distribution Feeders,” IEEE
Transactions on Power Delivery, vol. 19, no. 3, July 2004.
[33] I. Roytelman and V. Ganesan, “Coordinated Local and Centralized Control in Distribution Management Systems”, IEEE
Transactions on Power Delivery, vol. 15, no. 2, April 2000.
[34] V. Borozan, M.E. Baran and D. Novosel, “Integrated Volt/Var Control in Distribution Systems”, in Proc. of IEEE Power
Engineering Society Winter Meeting, 2001.
[35] A. Augugliaro, L. Dusonchet, S. Favuzza and E.R. Sanseverino, “Voltage Regulation and Power Losses Minimization in Automated
Distribution Networks by an Evolutionary Multiobjective Approach”, IEEE Transactions on Power Systems, vol. 19, no.3, August
2004.
[36] I. Roytelman and V. Ganesan, “Coordinated Local and Centralized Control in Distribution Management Systems”, IEEE
Transactions on Power Delivery, vol. 15, no. 2, April 2000.
[37] V. Borozan, M.E. Baran and D. Novosel, “Integrated Volt/Var Control in Distribution Systems”, in Proc. of IEEE Power
Engineering Society Winter Meeting, 2001.
[38] A. Augugliaro, L. Dusonchet, S. Favuzza and E.R. Sanseverino, “Voltage Regulation and Power Losses Minimization in Automated
Distribution Networks by an Evolutionary Multiobjective Approach”, IEEE Transactions on Power Systems, vol. 19, no.3, August
2004.
[39] Z. Hu, X. Wang, H. Chen and G.A. Taylor, “Volt/VAr Control in Distribution Systems Using a Time-Interval Based Approached”,
IEE Proc.-Gener, Transm, Distrib., vol. 150, no. 5, September 2003.
[40] R.H. Liang and C.K. Cheng, “Dispatch of Main Transformer ULTC and Capacitors in a Distribution System”, IEEE Transaction on
Power Delivery, vol. 16, No. 4, October 2001.
[41] S. Civanlar and J.J. Grainger, “Forecasting Distribution Feeder Loads: Modelling and Application to Volt/VAr Control”, IEEE
Transaction on Power Delivery, vol. 3, no. 1, January 1988.
[42] T. Senjyu, H. Takara, K. Uezato and T. Funabashi, “One-Hour-Ahead Load Forecasting Using Neural Network”, IEEE Transaction
on Power Systems, vol. 17, no.1, February 2002.
[43] J.J. Paserba, D.J. Leonard, N.W. Miller, M.G. Laurby, S.T. Naumann and F.P. Sener, “Coordination of a Distribution Level
Continuously Controlled Compensation with Existing Substation Equipment for Long Term VAR Management”, IEEE Transaction
on Power Delivery, vol. 9, no. 2, April 1994.
[44] S. Repo, H. Laaksonen, et. al. “A Case Study of Voltage Rise Problem due to a Large Amount of Distributed Generation
.

More Related Content

What's hot

INTERLINE FLOW CONTROLLER
INTERLINE FLOW CONTROLLERINTERLINE FLOW CONTROLLER
INTERLINE FLOW CONTROLLERNitish NIT
 
Reactive power management and voltage control by using statcom
Reactive power management and voltage control by using statcomReactive power management and voltage control by using statcom
Reactive power management and voltage control by using statcomHussain Ali
 
Instantaneous Reactive Power Theory And Its Applications
Instantaneous Reactive Power Theory And Its ApplicationsInstantaneous Reactive Power Theory And Its Applications
Instantaneous Reactive Power Theory And Its Applicationsarunj89
 
Voltage source Converters as a building block of HVDC and FACTS
Voltage source Converters as a building block of HVDC and FACTSVoltage source Converters as a building block of HVDC and FACTS
Voltage source Converters as a building block of HVDC and FACTSKarthik Bharadwaj
 
Power Flow in a Transmission line
Power Flow in a Transmission linePower Flow in a Transmission line
Power Flow in a Transmission lineAyyarao T S L V
 
Series & shunt compensation and FACTs Devices
Series & shunt compensation and FACTs DevicesSeries & shunt compensation and FACTs Devices
Series & shunt compensation and FACTs Deviceskhemraj298
 
Power System Analysis!
Power System Analysis!Power System Analysis!
Power System Analysis!PRABHAHARAN429
 
Gcsc gto thyristor controlled series capacitor
Gcsc   gto thyristor controlled series capacitorGcsc   gto thyristor controlled series capacitor
Gcsc gto thyristor controlled series capacitorLEOPAUL23
 
Unified Power Flow Controller(upfc)1
Unified Power Flow Controller(upfc)1Unified Power Flow Controller(upfc)1
Unified Power Flow Controller(upfc)1JayakalyanReddy
 

What's hot (20)

INTERLINE FLOW CONTROLLER
INTERLINE FLOW CONTROLLERINTERLINE FLOW CONTROLLER
INTERLINE FLOW CONTROLLER
 
Reactive power management and voltage control by using statcom
Reactive power management and voltage control by using statcomReactive power management and voltage control by using statcom
Reactive power management and voltage control by using statcom
 
Power system security and smart grid
Power system security  and  smart gridPower system security  and  smart grid
Power system security and smart grid
 
Dstatcom
DstatcomDstatcom
Dstatcom
 
Balanced faults
Balanced faultsBalanced faults
Balanced faults
 
Load flow study
Load flow studyLoad flow study
Load flow study
 
Tcsc ppt
Tcsc pptTcsc ppt
Tcsc ppt
 
Reactive power compensation
Reactive power compensationReactive power compensation
Reactive power compensation
 
upfc
upfcupfc
upfc
 
Statcom
StatcomStatcom
Statcom
 
Instantaneous Reactive Power Theory And Its Applications
Instantaneous Reactive Power Theory And Its ApplicationsInstantaneous Reactive Power Theory And Its Applications
Instantaneous Reactive Power Theory And Its Applications
 
Voltage source Converters as a building block of HVDC and FACTS
Voltage source Converters as a building block of HVDC and FACTSVoltage source Converters as a building block of HVDC and FACTS
Voltage source Converters as a building block of HVDC and FACTS
 
Power Flow in a Transmission line
Power Flow in a Transmission linePower Flow in a Transmission line
Power Flow in a Transmission line
 
Series & shunt compensation and FACTs Devices
Series & shunt compensation and FACTs DevicesSeries & shunt compensation and FACTs Devices
Series & shunt compensation and FACTs Devices
 
TCSC
TCSCTCSC
TCSC
 
Power System Analysis!
Power System Analysis!Power System Analysis!
Power System Analysis!
 
Lecture 02.pptx
Lecture 02.pptxLecture 02.pptx
Lecture 02.pptx
 
Gcsc gto thyristor controlled series capacitor
Gcsc   gto thyristor controlled series capacitorGcsc   gto thyristor controlled series capacitor
Gcsc gto thyristor controlled series capacitor
 
Unified Power Flow Controller(upfc)1
Unified Power Flow Controller(upfc)1Unified Power Flow Controller(upfc)1
Unified Power Flow Controller(upfc)1
 
Facts controller
Facts controllerFacts controller
Facts controller
 

Viewers also liked

Power system voltage stability
Power system voltage stabilityPower system voltage stability
Power system voltage stabilityAkash Choudhary
 
Reactive power consumption in modern power system
Reactive power consumption in modern power systemReactive power consumption in modern power system
Reactive power consumption in modern power systemRahuldey1991
 
تصنيف الاستقرارية
تصنيف الاستقراريةتصنيف الاستقرارية
تصنيف الاستقراريةmohammedhammed
 
Impacts of distributed generation on electricity market
Impacts of distributed generation on electricity marketImpacts of distributed generation on electricity market
Impacts of distributed generation on electricity marketHarsh Dhiman
 
Advanced power system ii
Advanced power system iiAdvanced power system ii
Advanced power system iiPalak Ariwala
 
Transient enhancement technique
Transient enhancement techniqueTransient enhancement technique
Transient enhancement techniqueVipin Pandey
 
substation automation
substation automationsubstation automation
substation automationMahbub Rashid
 
Classification Of Power System Stability
Classification Of Power System StabilityClassification Of Power System Stability
Classification Of Power System StabilityAravind Shaji
 
Static shunt compensation
Static shunt compensationStatic shunt compensation
Static shunt compensationAyyarao T S L V
 
Flexible AC Transmission (FACTS)
Flexible AC Transmission (FACTS)Flexible AC Transmission (FACTS)
Flexible AC Transmission (FACTS)SHIMI S L
 
Voltage Support and Reactive Power Control in Micro-grid using DG
Voltage Support and Reactive Power Control in Micro-grid using  DGVoltage Support and Reactive Power Control in Micro-grid using  DG
Voltage Support and Reactive Power Control in Micro-grid using DGIJMER
 
Reactive power compensation
Reactive power compensationReactive power compensation
Reactive power compensationcijogeorgep
 
Method of voltage control
Method of voltage controlMethod of voltage control
Method of voltage controlVaibhav Singh
 
Steady State Operation And Enhancement Of Transient Stability In Hydel Power...
Steady State Operation And Enhancement Of Transient Stability  In Hydel Power...Steady State Operation And Enhancement Of Transient Stability  In Hydel Power...
Steady State Operation And Enhancement Of Transient Stability In Hydel Power...IJMER
 
implementation of statcom and reactive power compensation
implementation of statcom and reactive power compensationimplementation of statcom and reactive power compensation
implementation of statcom and reactive power compensationprashant shekhar
 

Viewers also liked (20)

voltage stability
voltage stabilityvoltage stability
voltage stability
 
Power system voltage stability
Power system voltage stabilityPower system voltage stability
Power system voltage stability
 
Reactive power consumption in modern power system
Reactive power consumption in modern power systemReactive power consumption in modern power system
Reactive power consumption in modern power system
 
تصنيف الاستقرارية
تصنيف الاستقراريةتصنيف الاستقرارية
تصنيف الاستقرارية
 
Impacts of distributed generation on electricity market
Impacts of distributed generation on electricity marketImpacts of distributed generation on electricity market
Impacts of distributed generation on electricity market
 
Advanced power system ii
Advanced power system iiAdvanced power system ii
Advanced power system ii
 
132007441829
132007441829132007441829
132007441829
 
Transient enhancement technique
Transient enhancement techniqueTransient enhancement technique
Transient enhancement technique
 
Reactive power management in india
Reactive power  management in indiaReactive power  management in india
Reactive power management in india
 
substation automation
substation automationsubstation automation
substation automation
 
Classification Of Power System Stability
Classification Of Power System StabilityClassification Of Power System Stability
Classification Of Power System Stability
 
Static shunt compensation
Static shunt compensationStatic shunt compensation
Static shunt compensation
 
Flexible AC Transmission (FACTS)
Flexible AC Transmission (FACTS)Flexible AC Transmission (FACTS)
Flexible AC Transmission (FACTS)
 
Voltage Support and Reactive Power Control in Micro-grid using DG
Voltage Support and Reactive Power Control in Micro-grid using  DGVoltage Support and Reactive Power Control in Micro-grid using  DG
Voltage Support and Reactive Power Control in Micro-grid using DG
 
Reactive power compensation
Reactive power compensationReactive power compensation
Reactive power compensation
 
Method of voltage control
Method of voltage controlMethod of voltage control
Method of voltage control
 
Steady State Operation And Enhancement Of Transient Stability In Hydel Power...
Steady State Operation And Enhancement Of Transient Stability  In Hydel Power...Steady State Operation And Enhancement Of Transient Stability  In Hydel Power...
Steady State Operation And Enhancement Of Transient Stability In Hydel Power...
 
implementation of statcom and reactive power compensation
implementation of statcom and reactive power compensationimplementation of statcom and reactive power compensation
implementation of statcom and reactive power compensation
 
PPT ON POWER SYSTEM STABILITY
PPT ON POWER SYSTEM STABILITYPPT ON POWER SYSTEM STABILITY
PPT ON POWER SYSTEM STABILITY
 
Reactive power compensation
Reactive power compensationReactive power compensation
Reactive power compensation
 

Similar to Concepts of Reactive Power Control and Voltage Stability Methods in Power System Network

An Overview of Facts Devices used for Reactive Power Compensation Techniques
An Overview of Facts Devices used for Reactive Power Compensation TechniquesAn Overview of Facts Devices used for Reactive Power Compensation Techniques
An Overview of Facts Devices used for Reactive Power Compensation TechniquesDr. Sudhir Kumar Srivastava
 
Enhancement of Voltage Stability on IEEE 14 Bus Systems Using Static Var Comp...
Enhancement of Voltage Stability on IEEE 14 Bus Systems Using Static Var Comp...Enhancement of Voltage Stability on IEEE 14 Bus Systems Using Static Var Comp...
Enhancement of Voltage Stability on IEEE 14 Bus Systems Using Static Var Comp...paperpublications3
 
International Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentInternational Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentIJERD Editor
 
Voltage collapse mitigation by reactive power
Voltage collapse mitigation by reactive powerVoltage collapse mitigation by reactive power
Voltage collapse mitigation by reactive powereSAT Publishing House
 
Voltage collapse mitigation by reactive power compensation at the load side
Voltage collapse mitigation by reactive power compensation at the load sideVoltage collapse mitigation by reactive power compensation at the load side
Voltage collapse mitigation by reactive power compensation at the load sideeSAT Journals
 
Investigation and Comparison of the Effect of Facts Devices, Capacitors and L...
Investigation and Comparison of the Effect of Facts Devices, Capacitors and L...Investigation and Comparison of the Effect of Facts Devices, Capacitors and L...
Investigation and Comparison of the Effect of Facts Devices, Capacitors and L...IJAPEJOURNAL
 
International Journal of Computational Engineering Research(IJCER)
International Journal of Computational Engineering Research(IJCER)International Journal of Computational Engineering Research(IJCER)
International Journal of Computational Engineering Research(IJCER)ijceronline
 
H9 VOLTAGE AND REACTIVE EMERSON EDUARDO RODRIGUES.pdf
H9 VOLTAGE AND REACTIVE EMERSON EDUARDO RODRIGUES.pdfH9 VOLTAGE AND REACTIVE EMERSON EDUARDO RODRIGUES.pdf
H9 VOLTAGE AND REACTIVE EMERSON EDUARDO RODRIGUES.pdfEMERSON EDUARDO RODRIGUES
 
Reactive power compensation
Reactive power compensationReactive power compensation
Reactive power compensationkhaliq ahmed
 
Power system operation Question and answers
Power system operation Question and answersPower system operation Question and answers
Power system operation Question and answersAdhithyaS5
 
Research Inventy : International Journal of Engineering and Science
Research Inventy : International Journal of Engineering and ScienceResearch Inventy : International Journal of Engineering and Science
Research Inventy : International Journal of Engineering and Scienceinventy
 
International Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentInternational Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentIJERD Editor
 
Power Flow Study and Performance of STATCOM and TCSC in Improvement Voltage S...
Power Flow Study and Performance of STATCOM and TCSC in Improvement Voltage S...Power Flow Study and Performance of STATCOM and TCSC in Improvement Voltage S...
Power Flow Study and Performance of STATCOM and TCSC in Improvement Voltage S...IJAPEJOURNAL
 
International Journal of Engineering and Science Invention (IJESI)
International Journal of Engineering and Science Invention (IJESI)International Journal of Engineering and Science Invention (IJESI)
International Journal of Engineering and Science Invention (IJESI)inventionjournals
 
POWER QUALITY ENHANCEMENT USING UPQC
POWER QUALITY ENHANCEMENT USING UPQCPOWER QUALITY ENHANCEMENT USING UPQC
POWER QUALITY ENHANCEMENT USING UPQCIRJET Journal
 
FACTS DEVICES AND POWER SYSTEM STABILITY ppt
FACTS DEVICES AND POWER SYSTEM STABILITY pptFACTS DEVICES AND POWER SYSTEM STABILITY ppt
FACTS DEVICES AND POWER SYSTEM STABILITY pptMamta Bagoria
 

Similar to Concepts of Reactive Power Control and Voltage Stability Methods in Power System Network (20)

D011122934
D011122934D011122934
D011122934
 
An Overview of Facts Devices used for Reactive Power Compensation Techniques
An Overview of Facts Devices used for Reactive Power Compensation TechniquesAn Overview of Facts Devices used for Reactive Power Compensation Techniques
An Overview of Facts Devices used for Reactive Power Compensation Techniques
 
Enhancement of Voltage Stability on IEEE 14 Bus Systems Using Static Var Comp...
Enhancement of Voltage Stability on IEEE 14 Bus Systems Using Static Var Comp...Enhancement of Voltage Stability on IEEE 14 Bus Systems Using Static Var Comp...
Enhancement of Voltage Stability on IEEE 14 Bus Systems Using Static Var Comp...
 
International Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentInternational Journal of Engineering Research and Development
International Journal of Engineering Research and Development
 
Voltage collapse mitigation by reactive power
Voltage collapse mitigation by reactive powerVoltage collapse mitigation by reactive power
Voltage collapse mitigation by reactive power
 
Voltage collapse mitigation by reactive power compensation at the load side
Voltage collapse mitigation by reactive power compensation at the load sideVoltage collapse mitigation by reactive power compensation at the load side
Voltage collapse mitigation by reactive power compensation at the load side
 
Investigation and Comparison of the Effect of Facts Devices, Capacitors and L...
Investigation and Comparison of the Effect of Facts Devices, Capacitors and L...Investigation and Comparison of the Effect of Facts Devices, Capacitors and L...
Investigation and Comparison of the Effect of Facts Devices, Capacitors and L...
 
International Journal of Computational Engineering Research(IJCER)
International Journal of Computational Engineering Research(IJCER)International Journal of Computational Engineering Research(IJCER)
International Journal of Computational Engineering Research(IJCER)
 
Smart grid presentation
Smart grid  presentationSmart grid  presentation
Smart grid presentation
 
H9 VOLTAGE AND REACTIVE EMERSON EDUARDO RODRIGUES.pdf
H9 VOLTAGE AND REACTIVE EMERSON EDUARDO RODRIGUES.pdfH9 VOLTAGE AND REACTIVE EMERSON EDUARDO RODRIGUES.pdf
H9 VOLTAGE AND REACTIVE EMERSON EDUARDO RODRIGUES.pdf
 
Reactive power compensation
Reactive power compensationReactive power compensation
Reactive power compensation
 
Power system operation Question and answers
Power system operation Question and answersPower system operation Question and answers
Power system operation Question and answers
 
Research Inventy : International Journal of Engineering and Science
Research Inventy : International Journal of Engineering and ScienceResearch Inventy : International Journal of Engineering and Science
Research Inventy : International Journal of Engineering and Science
 
International Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentInternational Journal of Engineering Research and Development
International Journal of Engineering Research and Development
 
Power Flow Study and Performance of STATCOM and TCSC in Improvement Voltage S...
Power Flow Study and Performance of STATCOM and TCSC in Improvement Voltage S...Power Flow Study and Performance of STATCOM and TCSC in Improvement Voltage S...
Power Flow Study and Performance of STATCOM and TCSC in Improvement Voltage S...
 
International Journal of Engineering and Science Invention (IJESI)
International Journal of Engineering and Science Invention (IJESI)International Journal of Engineering and Science Invention (IJESI)
International Journal of Engineering and Science Invention (IJESI)
 
Al4201250256
Al4201250256Al4201250256
Al4201250256
 
POWER QUALITY ENHANCEMENT USING UPQC
POWER QUALITY ENHANCEMENT USING UPQCPOWER QUALITY ENHANCEMENT USING UPQC
POWER QUALITY ENHANCEMENT USING UPQC
 
Thyristor switched capacitor
Thyristor switched capacitorThyristor switched capacitor
Thyristor switched capacitor
 
FACTS DEVICES AND POWER SYSTEM STABILITY ppt
FACTS DEVICES AND POWER SYSTEM STABILITY pptFACTS DEVICES AND POWER SYSTEM STABILITY ppt
FACTS DEVICES AND POWER SYSTEM STABILITY ppt
 

More from IOSR Journals (20)

A011140104
A011140104A011140104
A011140104
 
M0111397100
M0111397100M0111397100
M0111397100
 
L011138596
L011138596L011138596
L011138596
 
K011138084
K011138084K011138084
K011138084
 
J011137479
J011137479J011137479
J011137479
 
I011136673
I011136673I011136673
I011136673
 
G011134454
G011134454G011134454
G011134454
 
H011135565
H011135565H011135565
H011135565
 
F011134043
F011134043F011134043
F011134043
 
E011133639
E011133639E011133639
E011133639
 
D011132635
D011132635D011132635
D011132635
 
C011131925
C011131925C011131925
C011131925
 
B011130918
B011130918B011130918
B011130918
 
A011130108
A011130108A011130108
A011130108
 
I011125160
I011125160I011125160
I011125160
 
H011124050
H011124050H011124050
H011124050
 
G011123539
G011123539G011123539
G011123539
 
F011123134
F011123134F011123134
F011123134
 
E011122530
E011122530E011122530
E011122530
 
D011121524
D011121524D011121524
D011121524
 

Recently uploaded

Call Us ≽ 8377877756 ≼ Call Girls In Shastri Nagar (Delhi)
Call Us ≽ 8377877756 ≼ Call Girls In Shastri Nagar (Delhi)Call Us ≽ 8377877756 ≼ Call Girls In Shastri Nagar (Delhi)
Call Us ≽ 8377877756 ≼ Call Girls In Shastri Nagar (Delhi)dollysharma2066
 
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdfCCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdfAsst.prof M.Gokilavani
 
UNIT III ANALOG ELECTRONICS (BASIC ELECTRONICS)
UNIT III ANALOG ELECTRONICS (BASIC ELECTRONICS)UNIT III ANALOG ELECTRONICS (BASIC ELECTRONICS)
UNIT III ANALOG ELECTRONICS (BASIC ELECTRONICS)Dr SOUNDIRARAJ N
 
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube ExchangerStudy on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube ExchangerAnamika Sarkar
 
Why does (not) Kafka need fsync: Eliminating tail latency spikes caused by fsync
Why does (not) Kafka need fsync: Eliminating tail latency spikes caused by fsyncWhy does (not) Kafka need fsync: Eliminating tail latency spikes caused by fsync
Why does (not) Kafka need fsync: Eliminating tail latency spikes caused by fsyncssuser2ae721
 
Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...VICTOR MAESTRE RAMIREZ
 
8251 universal synchronous asynchronous receiver transmitter
8251 universal synchronous asynchronous receiver transmitter8251 universal synchronous asynchronous receiver transmitter
8251 universal synchronous asynchronous receiver transmitterShivangiSharma879191
 
Application of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptxApplication of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptx959SahilShah
 
Concrete Mix Design - IS 10262-2019 - .pptx
Concrete Mix Design - IS 10262-2019 - .pptxConcrete Mix Design - IS 10262-2019 - .pptx
Concrete Mix Design - IS 10262-2019 - .pptxKartikeyaDwivedi3
 
Call Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile serviceCall Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile servicerehmti665
 
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort serviceGurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort servicejennyeacort
 
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...srsj9000
 
Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024hassan khalil
 
An experimental study in using natural admixture as an alternative for chemic...
An experimental study in using natural admixture as an alternative for chemic...An experimental study in using natural admixture as an alternative for chemic...
An experimental study in using natural admixture as an alternative for chemic...Chandu841456
 
Introduction-To-Agricultural-Surveillance-Rover.pptx
Introduction-To-Agricultural-Surveillance-Rover.pptxIntroduction-To-Agricultural-Surveillance-Rover.pptx
Introduction-To-Agricultural-Surveillance-Rover.pptxk795866
 
What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxWhat are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxwendy cai
 
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdfCCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdfAsst.prof M.Gokilavani
 

Recently uploaded (20)

Call Us ≽ 8377877756 ≼ Call Girls In Shastri Nagar (Delhi)
Call Us ≽ 8377877756 ≼ Call Girls In Shastri Nagar (Delhi)Call Us ≽ 8377877756 ≼ Call Girls In Shastri Nagar (Delhi)
Call Us ≽ 8377877756 ≼ Call Girls In Shastri Nagar (Delhi)
 
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdfCCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
 
UNIT III ANALOG ELECTRONICS (BASIC ELECTRONICS)
UNIT III ANALOG ELECTRONICS (BASIC ELECTRONICS)UNIT III ANALOG ELECTRONICS (BASIC ELECTRONICS)
UNIT III ANALOG ELECTRONICS (BASIC ELECTRONICS)
 
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube ExchangerStudy on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
 
Why does (not) Kafka need fsync: Eliminating tail latency spikes caused by fsync
Why does (not) Kafka need fsync: Eliminating tail latency spikes caused by fsyncWhy does (not) Kafka need fsync: Eliminating tail latency spikes caused by fsync
Why does (not) Kafka need fsync: Eliminating tail latency spikes caused by fsync
 
Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...
 
8251 universal synchronous asynchronous receiver transmitter
8251 universal synchronous asynchronous receiver transmitter8251 universal synchronous asynchronous receiver transmitter
8251 universal synchronous asynchronous receiver transmitter
 
Application of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptxApplication of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptx
 
Concrete Mix Design - IS 10262-2019 - .pptx
Concrete Mix Design - IS 10262-2019 - .pptxConcrete Mix Design - IS 10262-2019 - .pptx
Concrete Mix Design - IS 10262-2019 - .pptx
 
young call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Service
young call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Serviceyoung call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Service
young call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Service
 
Call Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile serviceCall Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile service
 
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort serviceGurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
 
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
 
Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024
 
young call girls in Green Park🔝 9953056974 🔝 escort Service
young call girls in Green Park🔝 9953056974 🔝 escort Serviceyoung call girls in Green Park🔝 9953056974 🔝 escort Service
young call girls in Green Park🔝 9953056974 🔝 escort Service
 
An experimental study in using natural admixture as an alternative for chemic...
An experimental study in using natural admixture as an alternative for chemic...An experimental study in using natural admixture as an alternative for chemic...
An experimental study in using natural admixture as an alternative for chemic...
 
Introduction-To-Agricultural-Surveillance-Rover.pptx
Introduction-To-Agricultural-Surveillance-Rover.pptxIntroduction-To-Agricultural-Surveillance-Rover.pptx
Introduction-To-Agricultural-Surveillance-Rover.pptx
 
What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxWhat are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptx
 
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptxExploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
 
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdfCCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
 

Concepts of Reactive Power Control and Voltage Stability Methods in Power System Network

  • 1. IOSR Journal of Computer Engineering (IOSR-JCE) e-ISSN: 2278-0661, p- ISSN: 2278-8727Volume 11, Issue 2 (May. - Jun. 2013), PP 15-25 www.iosrjournals.org www.iosrjournals.org 15 | Page Concepts of Reactive Power Control and Voltage Stability Methods in Power System Network Okwe Gerald Ibe, Akwukwaegbu Isdore Onyema MNSE Department of Electrical/Electronic Engineering Federal University of Technology Owerri Imo State (NIGERIA) Abstract: The intent of this paper is to present an analysis of reactive power control and voltage stability in power systems. It identifies a new model used to enhance voltage stability and exposes several key issues that had remained as research challenges in this area. The steady state voltage and reactive power control in distribution systems can be properly controlled by coordinating the available voltage and reactive power control equipment, such as on-load tap-changers, substation shunt capacitors and feeder shunt capacitors. It began with an overview of reactive power and voltage stability in transmission, distribution and load, and the importance of providing reactive power locally. The description of selected control features of shunt power systems such as SVC (Static Var Compensator) – static compensators of reactive power, STATCOM-type systems (Static Compensator) static reactive power generators and systems that combine both these solutions, which are referred to as SVC based on STATCOM where not left out. It explains the need to improve the voltage safety of Power system, as well as the increasing requirements for energy quality and security. It also discusses the techniques that were adopted in controlling and monitoring of the rate of power flow in the entire power system topology. This investigates the system to an optimal level in order to reduce losses and ensures sufficiency of reactive power control during normal and emergency conditions and to prevent voltage collapse. Keywords: Reactive Power, Voltage stability, Voltage Collapse, Power system security, voltage control I. Introduction The control of voltage and reactive power is a major issue in power system operation. This is because of the topological differences between distribution and transmission systems, different strategies have evolved. This paper contains contributions of novel reactive power control and voltage stability schemes for distribution and transmission systems. A particular interest is taken to the development of control schemes to avoid so-called voltage collapse, which can result in widespread outages. In order to achieve efficient and reliable operation of power system, the control of voltage and reactive power should satisfy the following objectives [1]: • Voltages at all terminals of all equipment in the system are within acceptable limits • System stability is enhanced to maximize utilization of the transmission system • The reactive power flow is minimized so as to reduce R I 2 and X I 2 losses. This ensures that the transmission system operates mainly for active power. Thus the power system supplies power to a vast number of loads and is feeding from many generating units, there is a problem of maintaining voltages within required limits. As load varies, the reactive power requirements of the transmission system vary. Since the reactive power cannot be transferred or transported over long distances, voltage control has to be effected by using special devices located through the system which possess difficulties in keeping sufficient levels of voltage in the power system network. This has been occurring practically since the first power systems started. Increasing requirements regarding both the supply reliability and quality of supplied power force using more modern (faster, more reliable, with a broader range of applications) devices. The proper selection and coordination of equipment for controlling reactive power and voltage stability are among the major challenges of power system engineering [1]. These challenges gave birth to some selected devices to control or compensate reactive power. In order to cover the additional demand for reactive power and maintain the ability to control voltage stability within the target range, various sources of reactive power, such as SVC (Static Var Compensator) – static compensators of reactive power, STATCOM-type systems (Static Compensator) static reactive power generators and systems that combine both these solutions, which are referred to as SVC based on STATCOM. In recent decades there has been significant progress in terms of equipment designed to improve the stability of voltage in power systems. This is mainly due to the development of power supply systems in the world, which requires seeking better ways of adjusting and controlling power flows and voltage levels. Almost all power transported or consumed in alternating current (AC) networks, supply or consume two of powers: real power and reactive power. Real power accomplishes useful work while reactive power supports the voltage that must be controlled for system reliability. Reactive power is essential to move active power through the transmission and distribution system to the customer. For AC systems voltage and current
  • 2. Concepts Of Reactive Power Control And Voltage Stability Methods In Power System Network www.iosrjournals.org 16 | Page pulsate at the system frequency. Although AC voltage and current pulsate at same frequency, they peak at different time power is the algebraic product of voltage and current. Real power is the average of power over cycle and measured by volt-amperes or watt. The portion of power with zero average value called reactive power measured in volt-amperes reactive or vars. 1.1 Reactive Power Control in Electrical Systems During the daily operation, power systems may experience both over-voltage and under-voltage violations that can be overcomed by voltage/Var control [1].Through controlling the production, adsorption, and flow of reactive power at all levels in the system, voltage/Var control can maintain the voltage profile within acceptable limit and reduce the transmission losses. Transmission connected generators are generally required to support reactive power flow. For example, Transmission system generators are required by the Grid Code Requirements to supply their rated power between the limits of 0.85 power factor lagging and 0.90 power factor leading at the designated terminals. The system operator will perform switching actions to maintain a secure and economical voltage profile while maintaining a reactive power balance equation: 1.1.1 Generator - MVARs + System gain + Shunt capacitors = [MVAR - Demand + Reactive losses + Shunt reactors] ……………………………… (1) The „System gain‟ is an important source of reactive power in the above power balance equation, which is generated by the capacitive nature of the transmission network itself. By making decisive switching actions in the early morning before the demand increases, the system gain can be maximized early on, helping to secure the system for the whole day. To balance the equation some pre-fault reactive generator use will be required. Other sources of reactive power that will also be used include shunt capacitors, shunt reactors, Static VAR Compensators and voltage control circuits 1.1.2 Reactive power theory the reactive power is defined in the IEEE Standard Dictionary 100-1996 under the energy “magner” as: where Vn and In are respectively the voltage and current rms values of the nth harmonics of the line frequency, and In is the phase difference between the voltage and the current nth harmonics. A convention is also adopted stating that the reactive energy should be positive when the current is leading the voltage (inductive load).In an electrical system containing purely sinusoidal voltage and current waveforms at a fixed frequency, the measurement of reactive power is easy and can be accomplished using several methods without errors. However, in the presence of non-sinusoidal waveforms, the energy contained in the harmonics causes measurement errors. According to the Fourier theorem any periodic waveform can be written as a sum of sin and cosine waves. As energy meters deal with periodic signals at the line frequency both current and voltage inputs of a single phase meter can be described by: Where Vn and In are defined as in Equation 2. Active power the average active power is defined as: The implementation of the active power measurement is relatively easy and is done accurately in most energy meters in the field. Apparent power The apparent power is the maximum real power that can be delivered to a load. As Vrms and Irms are the effective voltage and current delivered to the load, Apparent power = Vrms • Irms …………..……………………………….. (6) ……………………………………………………(3) ………………………………......… (4) …………………….. (5) ………………………….. (2)
  • 3. Concepts Of Reactive Power Control And Voltage Stability Methods In Power System Network www.iosrjournals.org 17 | Page The correct implementation of the apparent energy measurement is bound by the accuracy of the rms measurements. 1.2 Importance of Reactive Power Voltage control in an electrical power system is important for proper operation for electrical power equipment to prevent damage such as overheating of generators and motors, to reduce transmission losses and to maintain the ability of the system to withstand and prevent voltage collapse. In general terms, decreasing reactive power causing voltage to fall while increasing it causing voltage to rise. A voltage collapse occurs when the system try to serve much more load than the voltage can support. When reactive power supply lower voltage, as voltage drops current must increase to maintain power supplied, causing system to consume more reactive power and the voltage drops further . If the current increases too much, transmission lines go off line, overloading other lines and potentially causing cascading failures. If the voltage drops too low, some generators will disconnect automatically to protect themselves. Voltage collapse occurs when an increase in load or less generation or transmission facilities causes dropping voltage, which causes a further reduction in reactive power from capacitor and line charging, and still there further voltage reductions. If voltage reduction continues, these will cause additional elements to trip, leading further reduction in voltage and loss of the load. The result in these entire progressive and uncontrollable declines in voltage is that the system unable to provide the reactive power required supplying the reactive power demands. 1.3 Problems of Reactive Power Though reactive power is needed to run many electrical devices, it can cause harmful effects on your appliances and other motorized loads, as well as your electrical infrastructure. Since the current flowing through your electrical system is higher than that necessary to do the required work, excess power dissipates in the form of heat as the reactive current flows through resistive components like wires, switches and transformers. Keep in mind that whenever energy is expended, you pay. It makes no difference whether the energy is expended in the form of heat or useful work. We can determine how much reactive power your electrical devices use by measuring their power factor, the ratio between real power and true power. A power factor of 1 (i.e. 100%) ideally means that all electrical power is applied towards real work. Homes typically have overall power factors in the range of 70% to 85%, depending upon which appliances may be running. Newer homes with the latest in energy efficient appliances can have an overall power factor in the nineties. The typical residential power meter only reads real power, i.e. what you would have with a power factor of 100%. While most electric companies do not charge residences directly for reactive power, it‟s a common misconception to say that reactive power correction has no economic benefit. To begin with, electric companies correct for power factor around industrial complexes, or they will request the offending customer to do so at his expense, or they will charge more for reactive power. Clearly electric companies benefit from power factor correction, since transmission lines carrying the additional (reactive) current to heavily industrialized areas costs them money. 1.4 The aim of power factor correction Many people overlook the benefits that power factor correction can offer the typical home in comparison to the savings and other benefits that businesses with large inductive loads can expect. Most importantly, you pay for reactive power in the form of energy losses created by the reactive current flowing in your home. These losses are in the form of heat and cannot be returned to the grid. Hence you pay. The fewer kilowatts expended in the home, whether from heat dissipation or not, the lower the electric bill. Since power factor correction reduces the energy losses, you save. As stated earlier, electric companies correct for power factor around industrial complexes, or they will request the offending customer to do so, or they will charge for reactive power. They‟re not worried about residential service because the impact on their distribution grid is not as severe as in heavily industrialized areas. However, it is true that power factor correction assists the electric company by reducing demand for electricity, thereby allowing them to satisfy service needs elsewhere. But who cares? Power factor correction lowers your electric bill by reducing the number of kilowatts expended, and without it your electric bill will be very exorbitant. In the most cases, PFC is used for economic reasons. Using compensating device, one can save on electricity bill as well as keep certain grid parameters determined by the energy provider. Power factor correction gives even more profits, than only savings. Compensating “unnecessary” reactive power the current carrying capacity of an existing network can be sufficient to send more active power through it, maintaining the same ratings of the apparatus within the supplying and distribution system. PFC also allows to decrease transmission losses and limits voltage drops. Generally, reliability of the network gets better. But one should be aware, that compensating device connected to the mains can also have negative consequences like:  Transient generation  Higher order harmonics generation
  • 4. Concepts Of Reactive Power Control And Voltage Stability Methods In Power System Network www.iosrjournals.org 18 | Page  Long lasting voltage rise  Gain of higher order harmonics  Voltage drops, outages and Overvoltage of short duration  Other kind of distortions 2.1 Overview on Different Voltage and Reactive Power Control Methods Voltage and reactive power control involves proper coordination among the voltage and reactive power control equipment in the distribution system to obtain an optimum voltage profile and optimum reactive power flows in the system according to the objective function and operating constraints. Many DNOs operate OLTC and shunt capacitors locally by using conventional controllers, e.g., voltage controller for the OLTC and either voltage, reactive power or time controllers for the capacitors; to perform basic voltage and reactive power control functions, e.g., to maintain the voltages in the distribution system within the acceptable range and to minimize power losses. Different voltage and reactive power control methods have been proposed. Properly locating and sizing shunt capacitors will decrease power losses. As an improvement to the capacitor planning based on the load size, methods to include customer load profiles and characteristics in the capacitor planning are proposed in [30]-[32]. Proper capacitor planning will also improve the voltage profile in the distribution system. The capacitor locating and sizing is studied and executed in the planning stage of the distribution system. In order to enhance the distribution system further, the capacitor should also be switched properly in the operation stage of the distribution system [31], using different types of available capacitor control. Most recently, many researchers have addressed the problem of voltage and reactive power control in distribution systems by focusing on automated distribution systems, such as in [36]-[40]. At the moment, the voltage and reactive power control based on automated distribution systems can be divided into two categories: off-line setting control and real time control [39]. The off-line setting control, [39]-[40] for instance, aims to find a dispatch schedule for the capacitor switching and the OLTC movement based on a one day ahead load forecast. Meanwhile, the real time control, [36]-[38] for instance, aims to control the capacitor and OLTC based on real time measurements and experiences. The application of dispatch schedule based load forecasting is motivated by the fact that although there is a random fluctuation in the load variation, the major component of the load variations is related to weather conditions. Furthermore, there is a deterministic load pattern during the day due to social activities [38]. Therefore, the load profile is quite predictable. It can be forecasted one-day-ahead with an average error less than 2% [41]-[42]. Different objective functions and operating constraints have been proposed in voltage and reactive power control with automated distribution systems. Nevertheless, all researchers [36]-[40] still consider loss Minimization and keeping the voltage within the acceptable range as the main objective and constraint in the voltage and reactive power control. Another objective that is commonly proposed is flattering the voltage profile [38], [40]. Commonly added operating constraints include the maximum number of OLTC operations and capacitor switchings [37], [39]-[40], and the minimum distribution system of [37]. Other references, such as [38], consider minimization of OLTC operations and capacitor switching as the objective function. The automated control with off-line setting proposed in [39]-[40] fully replaces the local control operation of the conventional OLTC and capacitor operations with a remotely controlled operation. The main obstacle application of this method is its dependency on communication links and remote control to all capacitors. However, many DNOs do not have communication links downstream to the feeder capacitor locations 2.1.1 Distribution System Voltage Control Distribution system voltage control is sometimes referred to as volt/var control (VVC), which Grainger and Civanlar (1985) specify as follows: The objective is to minimize the peak power and energy losses while keeping the voltage within specified limits for a variety of nominal load patterns. This objective is formulated as an optimization problem that is solved off-line, based on nominal load patterns. The optimization variables are the locations, sizes and control dead bands of capacitors and tap changer voltage regulators. Tap changers are normally automatically controlled by a relay controller that measures and regulates the secondary side voltage of the transformer. The control of transformers operating in parallel in the same substation must be coordinated to minimize circulating reactive power flows (Lakervi and Holmes, 1989). 2.1.2Transmission System Voltage Control In practical operation of transmission systems, the voltage needs to be continuously monitored and controlled to compensate for the daily changes in load, generation and network structure. In fact, the control of voltage is a major issue in power system operation. Kundur (1994).It identifies the main objectives of voltage control as: Voltage at the terminals of all equipment in the system should be kept within acceptable limits, to avoid malfunction of and damage to the equipment. Keeping voltages close to the values for which stabilizing controls are designed, to enhance system stability and allow maximal utilization of the transmission system.
  • 5. Concepts Of Reactive Power Control And Voltage Stability Methods In Power System Network www.iosrjournals.org 19 | Page Minimize reactive power flows, to reduce active as well as reactive power losses. Whereas distribution systems as a rule are operated in radial configuration. Consequently, more sophisticated control schemes than those used in distribution systems are necessary. The control of voltage is often divided into the normal, preventive and emergency state control. A brief overview of the strategies used in the different operating states follows:- Primary Control Primary voltage controllers are used in all power systems to keep the terminal voltages of the generators close to reference values given by the operator or generated by a secondary controller. An automatic voltage regulator (AVR) acts on the exciter of a synchronous machine, which supplies the field voltage and consequently the current in the field winding of the machine and can thereby regulate its terminal voltage. The response time of the primary controller is short, typically fractions of a second for generators with modern excitation systems. Furthermore, many generators use a so-called power system stabilizer (PSS) to modulate the terminal voltage of the machine based on a local frequency measurement to contribute to damping of electromechanical oscillations. Although the power system stabilizer in most cases is integrated in the AVR, it only introduces fast oscillations around the mean value given by the AVR as long as the generator remains synchronized with the rest of the network. Secondary Control Secondary voltage control acts on a time-scale of seconds to a minute and within regions of the network. The aim of secondary voltage control is to keep an appropriate voltage profile in a region of the system and to minimize circulating reactive power flows and maximize reactive reserves. Normally, the network is divided in a number of geographic regions. One or a few so-called pilot nodes, which are assumed to be representative of the voltage situation in the region, are selected for voltage regulation by the secondary controller. The main actuators are the set point voltages of the primary controllers of the generators within a region, although the French implementation also uses static compensation devices such as capacitor banks and reactors. The set point values are calculated by an optimization procedure using a linearized static network model to make each generator in the region contribute to the control of the pilot node voltage(s). Tertiary Control Tertiary voltage control acts system-wide on a time scale of about ten to thirty minutes. The traditional method of tertiary control is so-called reactive power optimal power flow (OPF) (Carpentier, 1962, Dommel and Tinney, 1968). The desired operating conditions are specified in the form of a cost function, which is minimized using nonlinear optimization techniques. Usually, the main goal is to minimize losses and to keep voltages close to rated values. A secondary goal may be to maximize and distribute reactive reserves. The main control variables are voltage set points for the generators, or pilot nodes if secondary control is used, and switching orders to compensation devices such as shunt capacitors and reactors. The power flow equations (Glover and Sarma, 1994) are specified as equality constraints in the optimization whereas operational limits such as transfer limits, limits on reactive reserves and voltages are specified as inequality constraints. 2.2 PREVENTIVE AND EMERGENCY STATE VOLTAGE CONTROL The operation of power systems can be divided into the states normal, alert or emergency (Kundur, 1994). The system normally operates in the normal state, but enters the alert state if the system cannot be expected to be robust to the contingencies that have been considered in the design of the system. Such situations may occur for example due to unexpected load increase or outage of some component, such that a single contingency may force the system into the emergency state. The system enters the emergency state if a severe enough contingency occurs, so that the system will experience instability or exceeds operational limits unless emergency control actions are taken. However, the system is still synchronized in the emergency state. 2.3 ELEMENTS OF THE SYSTEM, THAT PRODUCES AND ABSORBS REACTIVE POWER Loads- a typical load bus supplied by a power system is composed of a large number of devices. The composition changes depending on the day, season and weather conditions. The composite characteristics are normally such that a load bus absorbs reactive power. Both active and reactive powers of the composite loads vary due to voltage magnitudes. Loads at low-lagging power factors cause excessive voltage drops in the transmission network. Industrial consumers are charged for reactive power and this convinces them to improve the load power factor. Underground cables- they are always loaded below their natural loads, and hence generate reactive power under all operating conditions
  • 6. Concepts Of Reactive Power Control And Voltage Stability Methods In Power System Network www.iosrjournals.org 20 | Page Overhead lines- depending on the load current either absorb or supply reactive power. At loads below the natural load, the lines produce net reactive power; on the contrary, at loads above natural load lines absorb reactive power. 2.4 WAYS OF IMPROVING VOLTAGE STABILITY AND CONTROL Reactive power compensation is often most effective way to improve both power transfer capability and voltage stability. The control of voltage levels is accomplished by controlling the production, absorption and flow of reactive power. The generating units provide the basic means of voltage control, because the automatic voltage regulators control field excitation to maintain scheduled voltage level at the terminals of the generators. To control voltage throughout the system we have to use addition devices to compensate reactive power [1]. Reactive compensation can be divided into series and shunt compensation. It can be also divided into active and passive compensation [2]. But mostly consideration will be focused on shunt capacitor banks, static var compensator (SVC) and Static Synchronous Compensators (STATCOM), which are the part of group of active compensators called Flexible AC Transmission Systems (FACTS). The devices used for these purposes may be classified as follows: • Shunt capacitors • Series capacitors • Shunt reactors • Synchronous condensers • SVC • STATCOM 2.4.1 SHUNT CAPACITORS Shunt capacitors and reactors and series capacitors provide passive compensation. They are either permanently connected to the transmission and distribution system or switched. They contribute to voltage control by modifying the network characteristics. Synchronous condensers, SVC and STATCOM provide active compensation [2]. The voltages of the buses to which they are connected. Together with the generating units, they establish voltages at specific points in the system. Voltages at other locations in the system are determined by active and reactive power flows through various elements, including the passive compensating devices [1]. The primary purposes of transmission system shunt compensation near load areas are voltage control and load stabilization. Mechanically switched shunt capacitor banks are installed at major substations in load areas for producing reactive power and keeping voltage within required limits. For voltage stability shunt capacitor banks are very useful in allowing nearby generators to operate near unity power factor. This maximizes fast acting reactive reserve. Compared to SVCs, mechanically switched capacitor banks have the advantage of much lower cost. Switching speeds can be quite fast. Current limiting reactors are used to minimize switching transients. There are several disadvantages to mechanically switched capacitors. For voltage emergencies the shortcoming of shunt capacitor banks is that the reactive power output drops with the voltage squared. For transient voltage instability the switching may not be fast enough to prevent induction motor stalling. Precise and rapid control of voltage is not possible. Like inductors, capacitor banks are discrete devices, but they are often configured with several steps to provide a limited amount of variable control. If voltage collapse results in a system, the stab le parts of the system may experience damaging over voltages immediately following separation. Shunt capacitors banks are always connected to the bus rather than to the line. They are connected either directly to the high voltage bus or to the tertiary winding of the main transformer. Shunt capacitor banks are breaker-switched either automatically by a voltage relays or manually [1]. Figure 2.1 shows example of capacitor bank. Figure 2.1 Typical capacitor bank The primary purpose of transmission system shunt compensation near load areas is voltage control and load stabilization. In other words, shunt capacitors are used to compensate for X I 2 losses in transmission system and to ensure satisfactory voltage levels during heavy load conditions. Shunt capacitors are used in power system for power factor correction. The objective of power factor correction is to provide reactive power close to point
  • 7. Concepts Of Reactive Power Control And Voltage Stability Methods In Power System Network www.iosrjournals.org 21 | Page where it is being consumed, rather than supply it from remote sources [1]. Figure 2.2 shows the influence of shunt compensation on load bus. Figure 2.2 a) shunt compensation b) phasor diagram without compensationc) phasor diagram with compensation Switched shunt capacitors are also used for feeder voltage control. They are installed at appropriate location along the length of the feeder to ensure that voltages at all points remain the allowable minimum or maximum limits as the loads vary [2]. For voltage stability, shunt capacitor banks are very useful on allowing nearby generators to operate near unity power factor. This maximizes fast acting reactive reserve [2]. The biggest disadvantage of shunt capacitors is that the reactive power output drops with the voltage squared. Thus, during the severe voltage decays these devices are not efficient enough [2]. Compared to static var compensators, mechanically switched capacitor banks have the advantage of much lower cost. Switching speeds can be quite fast. Following a transmission line outage, capacitor bank energization should be delayed to allow time for line reclosing. However, capacitor switching should be before significant amounts of load are restored by transformer tap changers or distribution voltage regulators [2]. Despite of many advantages of mechanically switched capacitors, there is couple of disadvantages as well. Firstly, for transient voltage instability, the switching may not be fast enough to prevent induction motor stalling. If voltage collapse results in system breakdown, the stable parts of the system may experience damaging over voltages immediately following separation. Over voltages would be aggravated by energizing of shunt capacitors during the period of voltage decay [2]. 2.4.2 Shunt reactors Shunt reactors are mainly used to keep the voltage down, by absorbing the reactive power, in the case of light load and load rejection, and to compensate the capacitive load of the line. Other equipment can be involved in the provision of reactive power and energy, such as: • Unified Power Flow Controllers (UPFC) and other advanced FACTS (flexible ac transmission system) devices; • Tap staggering of transformers connected in parallel; • Disconnection of transmission lines; • Load shedding 2.4.3 Synchronous condensers Every synchronous machine (motor or generator) has the reactive power capabilities the same as synchronous generators. Synchronous machines that are designed exclusively to provide reactive support are called synchronous condensers. Synchronous condensers have all of the response speed and controllability advantages of generators without the need to construct the rest of the power plant (e.g., fuel-handling equipment and boilers). Because they are rotating machines with moving parts and auxiliary systems, they require significantly more maintenance than static compensators. They also consume real power equal to about 3% of the machine‟s reactive-power rating. Synchronous condensers are used in transmission systems: at the receiving end of long transmissions, in important substations and in conjunction with HVDC converter stations. Small synchronous condensers have also been used in high-power industrial networks to increase the short circuit power. The reactive power output is continuously controllable. The response time with closed-loop voltage control is from a few seconds and up, depending on different factors. In recent years the synchronous condensers
  • 8. Concepts Of Reactive Power Control And Voltage Stability Methods In Power System Network www.iosrjournals.org 22 | Page have been practically ruled out by the. Thyristor controlled static VAR compensators, because those are much more cheaper and have regulating characteristics similar to synchronous condensers. 2.4.4 Static VAR compensators An SVC combines conventional capacitors and inductors with fast switching capability. Switching takes place in the sub cycle time frame (i.e. in less than 1/50 of a second), providing a continuous range of control. The range can be designed to span from absorbing to generating reactive power. Advantages include fast, precise regulation of voltage and unrestricted, largely transient-free, capacitor bank switching. Voltage is regulated according to a slope (droop) characteristic. Static VAR compensator could be made up from: TCR (thyristor controlled reactor); TSC (thyristor switched capacitor) ; TSR (thyristor switched reactor); FC (fixed capacitor); Because SVCs use capacitors they suffer from the same degradation in reactive capability as voltage drops. They also do not have the short-term overload capability of generators and synchronous condensers. SVC applications usually require harmonic filters to reduce the amount of harmonics injected into the power system by the thyristor switching. SVCs provide direct control of voltage (C.W. Taylor, 1994); this is very valuable when there is little generation in the load area. The remaining capacitive capability of an SVC is a good indication of proximity to voltage instability. SVCs provide rapid control of temporary over voltages. But on the other hand SVCs have limited overload capability, because SVC is a Capacitor bank at its boost limit. The critical or collapse voltage becomes the SVC regulated voltage and instability usually occurs once an SVC reaches its boost limit. SVCs are expensive; shunt capacitor banks should first be used to allow unity power factor operation of nearby generators. 2.4.4 Static synchronous compensator (STATCOM) The STATCOM is a solid-state shunt device that generates or absorbs reactive power and is one member of a family of devices known as flexible AC transmission system (FACTS) devices. The STATCOM is similar to the SVC in response speed, control capabilities, and the use of power electronics. Rather than using conventional capacitors and inductors combined with thyristors, the STATCOM uses self-commutated power electronics to synthesize the reactive power output. Consequently, output capability is generally symmetric, providing as much capability for production as absorption. The solid-state nature of the STATCOM means that, similar to the SVC, the controls can be designed to provide very fast and effective voltage control (B. Kirby, 1997). While not having the short-term overload capability of generators and synchronous condensers, STATCOM capacity does not suffer as seriously as SVCs and capacitors do from degraded voltage. STATCOMs are current limited so their MVAR capability responds linearly to voltage as opposed to the voltage-squared relationship of SVCs and capacitors. This attribute greatly increases the usefulness of STATCOMs in preventing voltage collapse. 2.4.5 Series capacitors and reactors Series capacitors compensation is usually applied for long transmission lines and transient stability improvement. Series compensation reduces net transmission line inductive reactance. The reactive generation I 2 X compensates for the reactive consumption I 2 X of the C transmission line. Series capacitor reactive generation increases with the current squared, thus generating reactive power when it is most needed. This is a self- regulating nature of series capacitors. At light loads series capacitors have little effect. 2.5 Power Capacitor Based Compensating Devices Power factor correction method based on power capacitors is the biggest group of the devices used in the industry and by the private users, mainly from economic reasons. On the hand, they may be a reason of unwanted distortions at the spot of operation. That is why they should be carefully selected, in accordance with actual standards. In terms of rated voltage of capacitors we can distinguish two groups of capacitor banks:
  • 9. Concepts Of Reactive Power Control And Voltage Stability Methods In Power System Network www.iosrjournals.org 23 | Page Figure 2.3. Reactive power capability dependence on real power production for a synchronous generator Like most electric equipment, generators are limited by their current-carrying capability. Reactive power production is depended on the field heating limit and absorption on the core end-heating limit of the generator. Active power output limit is limited by armature heating. Control over the reactive output and the terminal voltage of the generator is provided by adjusting the DC current in the generator‟s rotating field. Control can be automatic, continuous, and fast. The inherent characteristics of the generator help maintain system voltage. At any given field setting, the generator has a specific terminal voltage it is attempting to hold. If the system voltage declines, the generator will inject reactive power in to the power system, tending to raise system voltage. If the system voltage rises, the reactive output of the generator will drop, and ultimately reactive power will flow into the generator, tending to lower system voltage. The voltage regulator will accentuate this behavior by driving the field current in the appropriate direction to obtain the desired system voltage. 2.6 Reactive Power in Operations Reactive power affects power system operation in numerous ways: 1 Loads consume reactive power, so this must be provided by some source. 2 The delivery system (transmission lines and transformers) consumes reactive power, so this must be provided by some source (even if the loads do not consume reactive power). Note however that all transmission lines do provide some reactive power from their shunt line charging which offsets their consumption of reactive power in their series line losses. 3 The flow of reactive power from the supplies to the sinks causes additional heating of the lines and voltage drops in the network. 4 The generation of reactive power can limit the generation of real power. So, one primary dilemma with reactive power is that a sufficient quantity of it is needed to provide the loads and losses in the network, but having too much reactive power flowing around in the network causes excess heating and undesirable voltage drops. The normal answer to this dilemma is to provide reactive power sources exactly at the location where the reactive power is consumed. And, since strictly speaking it does not take any "fuel" to provide reactive power, it should be possible to distribute reactive power sources (such as capacitors) all around the network to avoid the problem of heating the conductors and causing voltage drops. Unfortunately, this is not practical in the extreme since there are literally millions of lines and loads connected to the grid and so this would require millions of reactive power sources - all controlled to provide exactly the right amount of reactive power at the right time - every second of every day. The best we can do in most cases is work with some type of aggregation of load (say at the feeder leaving a substation) and at terminals of major lines and transformers. This also brings up the issue of the difference between power factor control (trying to exactly provide the right amount of reactive power needed to equal that which is consumed) and voltage control (trying to keep voltage levels at exactly the right level no matter how much reactive power it takes). Reactive power is both the problem and the solution to network voltage control. 3.1 TECHNICALS CONCEPTS AND NORMS This paper defines the technical concepts and norms necessary for understanding the voltage instability (collapse) problem and discusses a number of related issues. Generation and absorption of active and reactive power by different power system elements where not left out. The lack of supply of reactive power in a system heavily contributes to the voltage collapse process. The relationship between reactive power and voltage stability is explained. A number of major incidents of voltage collapse have occurred in different countries in
  • 10. Concepts Of Reactive Power Control And Voltage Stability Methods In Power System Network www.iosrjournals.org 24 | Page the past. The meaning of voltage collapse is described in simple terms and the voltage stability margin is defined. Contingencies, which are very often the cause of voltage instability, are also discussed. The voltage collapse: This phenomenon remains a major issue for power system networks. In the words of Carson Taylor [8], "A power system at a given operating state and subject to a given disturbance undergoes voltage collapse if post-disturbance equilibrium voltages are below acceptable limits. Voltage collapse may be total (blackout) or partial. Lack of adequate reactive power resources in a power system is a major contributing factor to the process of voltage collapse. As loads in a power system increase, voltages across the network tend to decrease and reactive power losses increase as a result of high current [25]; the reactive loss is proportional to square of the current. This increased reactive power demand would be supplied by voltage regulating devices such as generators, static VAR compensators, or capacitors, if possible. However, due to physical limitations, such devices cannot supply unlimited amounts of reactive power. Often, sustained load growth will result in some source of reactive power, or perhaps a number of such sources, reaching their physical limits. Once a reactive power source has reached its maximum limit, it can no longer regulate voltage. Therefore, sustained load growth results in an accelerated voltage decay, and hence an even greater reactive power requirement. This may force other voltage regulating devices to their limits, with a subsequent further acceleration in the rate of decline of voltages. This leads to loss of voltage in a significant part of the system and is described as the voltage collapse phenomenon. The Institution of Electrical and Electronic Engineers, USA, (IEEE) [6] defines voltage collapse and voltage instability as:"Voltage collapse is the process by which voltage instability leads to loss of voltage in a significant part of the system. A system enters a state of voltage instability when a disturbance, increase in load, or system change causes voltage to drop quickly or drift downward, and operators and automatic system control fail to halt the decay. The voltage decay may take just a few seconds but can also be prolonged of the order of 10-20 minutes. If the decay continues unabated, steady state angular instability or voltage collapse will occur."Voltage collapse: can also be defined the process by which the sequence of events accompanying voltage instability leads to a low unacceptable voltage profile in a significant portion of the power system."Similarly, "Voltage stability is the ability of a power system to maintain steady acceptable voltages at all buses in the system under normal operating conditions and after being subjected to a disturbance. A system enters a state of voltage instability when a disturbance, increase in load demand, or change in system condition causes a progressive and uncontrollable drop in voltage. "The main factor causing instability is the inability of the power system to meet the demand for reactive power. The heart of the problem is usually the voltage drop that occurs when active power and reactive power flow through the inductive reactance associated with the transmission network. Voltage Instability is the absence of Voltage stability, and results in progressive voltage decrease or increase. Power System Security This is the robustness of the system to imminent disturbance and hence depends on the system operating condition as well as on the contingent probability of disturbances. Power System Stability may be broadly defined as the property of a power system that enables it to remain in a state of operating equilibrium after being subjected to a disturbance. II. Conclusion In this paper, several representative techniques of reactive power and voltage/Var control are reviewed. Their advantages and disadvantages are analyzed. The future challenge is to how to efficiently and accurately solve the problem taking into consideration the dynamic nature of power systems. In its entirety, it detailed background information on the on several fundamental properties of reactive power and the consequences of shortages in reactive power reserves . Open research issues associated with voltage control and reactive power support have also been discussed. These issues are especially difficult because of the complex interaction between real and reactive power, from an engineering point of view, and from and economic point of view. It also explained the fundamentals issues on Reactive power dispatch in electric power system, as a means of injection of reactive power into the system on the generators for improving voltage stability condition when the system in heavily loaded situation. References [I] Proceedings of Bulk Power System Voltage Phenomena- Voltage Stability and Security. Potosi, MO, September 19-24, 1988. [2] Proceedings of NSF Workshop on Bulk Power System Voltage Phenomena-Voltage Stability and Security. Deep Creek Lake, MD, August 4-7, 1991. [3] Proceedings of Bulk Power System Voltage Phenomena 111- Seminar on Voltage Stability, Security and Control. Davos, Switzerland, August 22-26, 1994. [4] Proceedings of the Symposium on Bulk Power System Dynamics and Control IV-Restructuring. Santorini, Greece, August 24-28, 1998. [5] Proceedings of Bulk Power Systems Dynamics and Control Security and Reliability in a Changing Environment. Onomichi, Japan, August 26-31, 2001. [6] C.D. Vournas, P.W. Sauer, and M.A. Pai. Relationships between Voltage and Angel Stability of Power Systems. International Journal of Electrical Power and Energy Systems, 18:493-500, 1996. [7] H.P. St. Clair. Practical Concepts in Capability and Performance of Transmission Lines. AIEE Dansactions, 72: 1152-1 157, 1953.
  • 11. Concepts Of Reactive Power Control And Voltage Stability Methods In Power System Network www.iosrjournals.org 25 | Page [8] C.W. Taylor. Power System Voltage Stability. McGraw-Hill, New York, 1994. [9] P. Kundur. Power System Stability and Control. McGraw Hill, New York, 1994. [l0] W.R. Lachs. Voltage Collapse in EHV Power Systems. Paper A78057-2, 1978 IEEE PES Winter Meeting, New York, January 28- February 3, 1978. [11] Erche, M., Petersson, T. “Reactive Power Sources”. Task Force No 3. CIGRE WG 38-01. April 1987.“Exchange of services between large electricity generating plants and high voltage electric power systems”. Joint Working Group 39/11. CIGRE, April 1999. [12] Gil, J.B., San Roman, T.G., Rios, J.J., Martin, P.S. ”Reactive Power Pricing: a Conceptual Framework for Remuneration and Charging Procedures”. IEEE Transactions on Power Systems, Vol. 15, No.2, May 2000. [13] Hao, S.H., Papalexopoulos, A. “Reactive Power Pricing and Management “. IEEE Transactions on Power Systems, Vol. 12, No.1, February 1997. [14] Kirby, B., Hirst, E. “Ancillary Service Details: Voltage Control”. December 1997. [15] Larsson, M. (2000) Coordinated Voltage Control in Electric Power Systems. Doctoral dissertation, Department of Industrial Electrical Engineering and Automation, Lund University. [16] Miller, T.J. (Editor) "Reactive Power Control in Electric Systems". John Wiley & Sons, New York, 1982."Reactive Power: Basics, Problems and Solutions”. IEEE Tutorial course. 1987 [17] Taylor, C.W. “Power System Voltage Stability”. McGraw-Hill. ISBN 0-07-063184-0.1994. [18] Trehan, N. K. “Ancillary Services – Reactive and Voltage Control”. IEEE Winter Meeting 2001. “UCTE-Principles of Network Operation”. February 1999. Available from www.ucte.org [19] Xu, W., Zhang, Y., da Silva, L., Kundur, P. ”Competitive Procurement of Dynamic Reactive Power Support Service for Transmission Access”. IEEE Summer Power Meeting 2000. Whitehead, A. “A New Market in Reactive Power”. Birmingham, UK. April1998. [20] IEA, Renewable Energy, Market and Policy Trends in IEA Countries, International Energy Agency, France, 2004. [21] ESHA, “European Renewable Energy Review 2006”, European Small Hydropower Association, 2007. http://www.esha.be/fileadmin/ esha_files/documents/publications/articles/ERER2006-Final.pdf, last accessed on 22 Sept, 2007. [22] S. Rahman, “Green Power: What is and Where We Can Find It?” IEEE Power and Energy Magazine, vol. 1, pp. 30-37, January - February 2003. [23] IEA, “Biomass for Power Generation and CHP”, International Energy Agency, 2007. Available at http://www.iea.org/textbase/techno/essentials3.pdf, last accessed on 22 September 2007. [24] S. Sheth and M. Shahidehpour, “Tidal Energy in Electric Power Systems”, in Proc. of IEEE Power Engineering Society General Meeting, 2005. [25] R. Dettmer, “Wave Energy Gets Seaworthy”, IEE Review, September 2002. [26] M. Leijon, H. Bernhoff, O. Ågren, J. Isberg, J. Sunberg, M. Berg, K.E. Karlsson and A. Wolfbrandt, “Multiphysics Simulation of Wave Energy to Electric Energy Conversion by Permanent Magnet Linear Generator”, IEEE Transactions on Energy Conversions, vol. 20, no.1, March 2005. [27] Uppsala Universitet, “Wave Power Project – Islandsberg”. Available at http://www.el.angstrom.uu.se/meny/eng/index_E.html, last accessed on 7 Jan 2008. [28] M. Thomson, “Automatic voltage control relays and embedded generation. Part I”, Power Engineering Journal, vol. 14, pp. 71 – 76, April 2000. [29] C.W. Taylor, Power System Voltage Stability, Mc Graw Hill, 1994. [30] T.S. Abdel Salam, A.Y. Chikhani and R. Hackam, “A New Technique for Loss Varying Load Condition”, IEEE Transactions on Power Delivery, vol. 9, no. 2, April 1994. [31] M.Y. Cho and Y.W. Chen, “Fixed/Switched Type Shunt Capacitor Planning of Distribution Systems by Considering Customer Load Patterns and Simplified Feeder Model”, IEE Proc.-Gener, Transm, Distrib., vol. 144, no. 6, November 1997. [32] B. Milosevic and M. Begovic, “Capacitor Placement for Conservative Voltage Reduction on Distribution Feeders,” IEEE Transactions on Power Delivery, vol. 19, no. 3, July 2004. [33] I. Roytelman and V. Ganesan, “Coordinated Local and Centralized Control in Distribution Management Systems”, IEEE Transactions on Power Delivery, vol. 15, no. 2, April 2000. [34] V. Borozan, M.E. Baran and D. Novosel, “Integrated Volt/Var Control in Distribution Systems”, in Proc. of IEEE Power Engineering Society Winter Meeting, 2001. [35] A. Augugliaro, L. Dusonchet, S. Favuzza and E.R. Sanseverino, “Voltage Regulation and Power Losses Minimization in Automated Distribution Networks by an Evolutionary Multiobjective Approach”, IEEE Transactions on Power Systems, vol. 19, no.3, August 2004. [36] I. Roytelman and V. Ganesan, “Coordinated Local and Centralized Control in Distribution Management Systems”, IEEE Transactions on Power Delivery, vol. 15, no. 2, April 2000. [37] V. Borozan, M.E. Baran and D. Novosel, “Integrated Volt/Var Control in Distribution Systems”, in Proc. of IEEE Power Engineering Society Winter Meeting, 2001. [38] A. Augugliaro, L. Dusonchet, S. Favuzza and E.R. Sanseverino, “Voltage Regulation and Power Losses Minimization in Automated Distribution Networks by an Evolutionary Multiobjective Approach”, IEEE Transactions on Power Systems, vol. 19, no.3, August 2004. [39] Z. Hu, X. Wang, H. Chen and G.A. Taylor, “Volt/VAr Control in Distribution Systems Using a Time-Interval Based Approached”, IEE Proc.-Gener, Transm, Distrib., vol. 150, no. 5, September 2003. [40] R.H. Liang and C.K. Cheng, “Dispatch of Main Transformer ULTC and Capacitors in a Distribution System”, IEEE Transaction on Power Delivery, vol. 16, No. 4, October 2001. [41] S. Civanlar and J.J. Grainger, “Forecasting Distribution Feeder Loads: Modelling and Application to Volt/VAr Control”, IEEE Transaction on Power Delivery, vol. 3, no. 1, January 1988. [42] T. Senjyu, H. Takara, K. Uezato and T. Funabashi, “One-Hour-Ahead Load Forecasting Using Neural Network”, IEEE Transaction on Power Systems, vol. 17, no.1, February 2002. [43] J.J. Paserba, D.J. Leonard, N.W. Miller, M.G. Laurby, S.T. Naumann and F.P. Sener, “Coordination of a Distribution Level Continuously Controlled Compensation with Existing Substation Equipment for Long Term VAR Management”, IEEE Transaction on Power Delivery, vol. 9, no. 2, April 1994. [44] S. Repo, H. Laaksonen, et. al. “A Case Study of Voltage Rise Problem due to a Large Amount of Distributed Generation .