Logistics Risk Management
in the Transformer Industry
by: ShockWatch, Inc.
Logistics Risk Management in the Transformer Industry
1
In 2014 an electrical transformer being shipped from
Israel to Canada was damaged in transit. The $2 million
transformer was returned to Israel for repair then shipped
back to the client, delaying the project. The insurer sued the
railway and the logistics carrier for $911,233 in damages. It
settled for $750,000 on behalf of its client.
In a 2013 case (ABB Inc. v. CSX Transportation), when a
$1.3 million transformer was “allegedly damaged” in transit,
a U.S. appeals court reversed a portion of a lower court
ruling and made the railroad liable for the full damages of
$550,000 rather than the $25,000 liability it expected under
the Carmack Amendment to the Interstate Commerce Act.
CSX has never admitted liability.
These cases are notable, but not the only examples of
accidents that cause delays in transformer delivery and
installation. Simply attaching impact monitors to the
shipments could have improved both of those situations.
These important risk management tools would have shown
the extent, duration, and location of the impacts quickly and
easily, helping prove liability for some rather substantial
repair bills.
Logistics is a Vital Part of Transformer Health
Consider this: the supply chain for transformers stretches
around the globe, involving multiple handoffs, transportation
methods, and carriers. Each handoff entails risk.
The transformer for the substation at Conway, New
Hampshire is a case in point. The 411 ton transformer was
built in Hebei, China, 7,000 miles from its destination.
It traveled by truck and rail from Hebei to the port of
Xingang, where it was loaded onto a ship. It crossed the
Pacific, transited the Panama Canal, entered the Gulf of
Mexico and stopped in Houston. It then entered the Atlantic
and steamed up the East Coast before being offloaded at
Searsport, Maine onto a Schnable rail car. Designed for
tight turns, the Schnable car uses hydraulics to shift the
load left or right to ensure clearances.
From Maine, the transformer went by rail through Quebec,
Canada, and returned to the U.S. through Vermont before
reaching North Conway, New Hampshire. There, it was
transferred to truck for its final journey to the Conway Power
Station.
That convoluted route was necessary to ensure the
infrastructure could support the 411 ton transformer. Still,
it crossed 84 bridges. Some of those hadn’t borne heavy
freight in 26 years. In all, more than 15 service providers
were involved in transporting the transformer and ensuring
the safety of the route.
Logistics Risk Management in the Transformer Industry
Abstract: Transformers often are shipped thousands of miles, involving multiple handoffs,
and more than a dozen logistics teams before they are installed. With an impact threshold
of about 2.5g, damage isn’t always evident. Hidden damage may trigger an event cascade
that causes catastrophic failure long after installation. Impact monitors reduce that potential
by recording the impact and duration of potentially damaging events. Prior to transformer
installation, this data can be compared to the transformer damage boundary to determine the
extent of potential damage. This data enables improvements in risk management practices
that, by properly ascribing liability, can identify where and when damage occurred and
ultimately reduce warranty costs and transformer downtime.
Logistics Risk Management in the Transformer Industry
Impacts and vibrations can:
•	 Loosen nuts and bolts, causing overheating.
•	 When panels are loosened, it also can create excessive
noise and create resonance among components.
•	 Abrade insulation, leading to short circuits and damaged
windings.
•	 Distort or displace windings, loosening their clamping
pressure, which contributes to their collapse during
electrical faults.
•	 Reduce clearances between the housing and
components.
•	 Damage related components, like radiators and
bushings.
•	 Harden metals.
•	 Create microfissures in the transforme .
It’s bad enough when this damage occurs in geographically
accessible locations. When it occurs in remote parts of
the world, shipping the damaged transformer back to the
manufacturer isn’t always a valid option. Instead, a repair
team may need to fly in at great expense.
Where Damage Occurs
An analysis showed that large power transformers
(>100T) get damaged between the 2.5 to 5.0 g (2-20
Hz) band, while small equipment like a laptop gets
damaged between 37 to 50 g (2-250Hz) band.
That means that most damage to transformers occurs at
low acceleration levels during transit. This damage is most
likely from loading, unloading, and rigging operations, and
during transportation. A small portion of damage occurs as
transformers are positioned on their foundations.
What Can Go Wrong?
Such a complex transportation plan and long supply chain
requires meticulous planning. Each transfer increases
the risk. Although the Conway, NH delivery was executed
smoothly, other transformers have broken free and
damaged other goods. One even fell off its transport car.
Several court cases cite “damage” or “alleged damage”
during transport.
A drop of even a few inches can damage transformers.
The heavier they are, the greater the potential for damage.
(Damage is determined by weight, volume and impact
surface, and also by the amplitude, duration, and frequency
of the impact.)
The resulting damage may be visible or, more concerning,
concealed.
If concealed, these transformers may be installed and made
operational, triggering failures during power up or even later
in their life cycle. That damage may never be tracked back
to its source, causing great expense for power utilities or
manufacturers through no fault of their own.
One instruction manual (from manufacturer WEG) for
dry transformers, for example, cautions handlers to lift
the transformer only by specific points. Using others
could severely damage the transformer. Forklifts aren’t
recommended, either, and strains may only be applied to
the base beams or core pressing beams. It points out that
transformers with protective boxes shouldn’t be lifted using
the eyebolts on the outside of the box. Instead, it can be
lifted using the leach eyes on the transformer’s top beams
inside the box.
It also cautions against transporting or storing the
transformers if they were subjected to “abnormal vibrations
and occasional collisions.”
2 Logistics Risk Management in the Transformer Industry
When damages occurs
in remote parts of the
world, shipping the
damaged transformer
back to the manufacturer
isn’t always a valid
option.
“
”
Logistics Risk Management in the Transformer Industry
3 Logistics Risk Management in the Transformer Industry
The point of this recommendation is to support pre-
installation analyses that are more efficient and more
accurate. If engineers know the transformer they are
checking experienced an impact that exceeded a certain
threshold – usually about 3Gs – they know to check
carefully for damage that may otherwise be missed.
Likewise, if they can prove the transformer was handled
carefully and experienced no impacts even approaching
the thresholds where damage occurs, they may be able to
streamline the analysis.
By using impact monitors, customers know to check for
visible and hidden damage before these transformers are
installed. And, if damage has occurred, impact recorders
also help attribute liability.
The most advanced impact recorders record the
acceleration of impacts, their direction along x, y, and z
axes, event duration, tilt and roll, vibration, geographic
location, and time of occurrence. They typically record
hundreds of impact events for well-over a year with
accuracy of plus or minus two percent, and report in real-
time or near-real time through wireless networks.
Impact recorders won’t
prevent the damage,
but they can alert you
that transformers have
experienced mechanical
impacts or vibrations...
“
”
When unloading and rigging accidents occur, the impacts
are in the range of 1 to 10gs in the 2-20 Hz band.
Mechanical shocks while on trailers are related to braking
and road conditions. They typically range between 0.5 and
1 g in the 3-350 Hz band, and are unlikely to cause damage.
On trains, transformers experience longitudinal impacts up
to 4 g in the 2-20 Hz band from shunting operations, and
vertical shocks between 0.5 and 1 g in the 2-500Hz band
from rail joints.
Aboard ships, transformers experience rolling, pitching,
and yawing, with low-frequency vibrations typically ranging
between 0.3 and 0.8 g in the 2-30 Hz band. These vibrations
rarely cause damage. However, the pitch and roll of the ship
can reach up to 5-7 degrees and 45 degrees respectively,
which can loosen cargo and send a 100T transformer
crushing into other cargo.
Damage is based on the combination of acceleration (g),
duration (msec), and frequency (Hz). Impact monitors
typically record acceleration and duration to help users
pinpoint the potential for damage, and where and when it
occurred. Frequency may be extrapolated from the duration
of the impact.
Impact Recorders
Impact recorders won’t prevent the damage, but they can
alert you that transformers have experienced mechanical
impacts or vibrations above certain thresholds and,
therefore, may be damaged.
IEEEguideC57.150specifiestworecorderspertransformer,
mounted diagonally opposite each other. The impact
recorders are mounted on opposite ends of the transformer
because transformers are becoming so long in length. If
one end of a transformer is dropped, the recorder on the
opposite end would not record the true acceleration value
because the transformer would attenuate the acceleration
value from one end to the other.
Logistics Risk Management in the Transformer Industry
4 Logistics Risk Management in the Transformer Industry
Because these impact recorders are tamperproof, they
are accepted as evidence by courts of law and are
trusted by insurance companies. Impact monitoring also
can help reduce warranty claims from failures once the
transformers are in operation.
Damage isn’t always evident. Microfractures in internal
components, for example, may not be noticed, but may
cause problems (such as overheating) long after the
transformer has begun operating. Or small, unnoticed
issues may create a cascade that ultimately results
in catastrophic failure. When hidden damage goes
unnoticed, the power utility or manufacturer end up paying
for damage that occurred on the transportation carrier’s
watch. This is damage that should be covered under
the carrier’s insurance. Proper use of impact monitors,
however, helps inspectors uncover hidden damage and
attribute it to the responsible party.
For carriers, impact monitors can help limit their liability
by ascertaining exactly where, during transit, the damage
occurred. With multiple handoffs to carriers in many
countries and widely varying logistics practices and
infrastructure conditions, knowing whether transformers
were damaged on your watch, or before or after you
took possession, can be invaluable in managing risk and
transportation partners.
For example, several carriers have argued they aren’t
liable for damages because they took reasonable care.
However, in Prima (et al) vs. Panalpina, a lower court found
in 2000 Panalpina liable for damages when an electrical
transformer came loose during transit and damaged
other cargo. That court cited Panalpina’s promise to
Westinghouse: “Rest assured your shipment will receive,
door-to-door, our close care & supervision.” An appeals
court overturned the decision, saying Panalpina was a
forwarder, not a carrier. That distinction aside, with impact
monitoring, you can determine whether “reasonable care”
was taken, because you have the impact data.
Using impact monitors also helps engineers better
estimate transformer fragility without resorting to shock
response spectrum analysis or finite element analysis.
Monitors provide real-world, experiential data that can
be accumulated, analyzed, and correlated to specific
conditions, carriers, or transformer designs.
Conclusion
Impact recorders are part of a cohesive risk
management strategy that stretches from
manufacturing to installation. Transformer health
depends on accurate, reliable data – including
data that measures impacts that can cause
damage. Impact monitors provide that data,
thus helping to increase the accuracy of pre-
installation analyses, saving time and money.

More Related Content

Similar to Why Transformers need ShockLog

REPORT -VALLUR THERMAL POWER PLANT
REPORT -VALLUR THERMAL POWER PLANTREPORT -VALLUR THERMAL POWER PLANT
REPORT -VALLUR THERMAL POWER PLANT
RAJPRASAD RS
 
TRANSMISSION PLANNING CRITERIA
TRANSMISSION PLANNING CRITERIATRANSMISSION PLANNING CRITERIA
TRANSMISSION PLANNING CRITERIA
Arun Muraleedharan
 
Edwin Newsletter on transformer failures on 13 October 2015
Edwin Newsletter on transformer failures on 13 October 2015Edwin Newsletter on transformer failures on 13 October 2015
Edwin Newsletter on transformer failures on 13 October 2015
Edwin Low
 
Operating Cranes and Plant near Overhead Electric Lines
Operating Cranes and Plant near Overhead Electric LinesOperating Cranes and Plant near Overhead Electric Lines
Operating Cranes and Plant near Overhead Electric Lines
peterswork1
 
Why transformers fail_final
Why transformers fail_finalWhy transformers fail_final
Why transformers fail_final
Snehangshu Ghosh
 
Earthing and disconnecting panel report.pdf
Earthing and disconnecting panel report.pdfEarthing and disconnecting panel report.pdf
Earthing and disconnecting panel report.pdf
MohitKumar989420
 
Transformer design and protection
Transformer design and protectionTransformer design and protection
Transformer design and protection
ashwin fcc
 
Proboat - Practical Impact Exposure Testing
Proboat - Practical Impact Exposure TestingProboat - Practical Impact Exposure Testing
Proboat - Practical Impact Exposure Testing
Jussi Mannerberg
 

Similar to Why Transformers need ShockLog (20)

REPORT -VALLUR THERMAL POWER PLANT
REPORT -VALLUR THERMAL POWER PLANTREPORT -VALLUR THERMAL POWER PLANT
REPORT -VALLUR THERMAL POWER PLANT
 
TRANSMISSION PLANNING CRITERIA
TRANSMISSION PLANNING CRITERIATRANSMISSION PLANNING CRITERIA
TRANSMISSION PLANNING CRITERIA
 
Unit 05 Protection of feeders and bus-bars
Unit  05 Protection of feeders and bus-bars Unit  05 Protection of feeders and bus-bars
Unit 05 Protection of feeders and bus-bars
 
Edwin Newsletter on transformer failures on 13 October 2015
Edwin Newsletter on transformer failures on 13 October 2015Edwin Newsletter on transformer failures on 13 October 2015
Edwin Newsletter on transformer failures on 13 October 2015
 
8 fault-analysis-and-electrical
8 fault-analysis-and-electrical8 fault-analysis-and-electrical
8 fault-analysis-and-electrical
 
Training at 132 kv substation
Training at 132 kv substation Training at 132 kv substation
Training at 132 kv substation
 
Operating Cranes and Plant near Overhead Electric Lines
Operating Cranes and Plant near Overhead Electric LinesOperating Cranes and Plant near Overhead Electric Lines
Operating Cranes and Plant near Overhead Electric Lines
 
transformerdesignandprotection-130408132534-phpapp02.ppt
transformerdesignandprotection-130408132534-phpapp02.ppttransformerdesignandprotection-130408132534-phpapp02.ppt
transformerdesignandprotection-130408132534-phpapp02.ppt
 
Study tour to optcl
Study tour to optclStudy tour to optcl
Study tour to optcl
 
Why transformers fail_final
Why transformers fail_finalWhy transformers fail_final
Why transformers fail_final
 
Pq unit ii
Pq unit iiPq unit ii
Pq unit ii
 
Comparing Industrial Level Displacer Transmitter Technologies
Comparing Industrial Level Displacer Transmitter TechnologiesComparing Industrial Level Displacer Transmitter Technologies
Comparing Industrial Level Displacer Transmitter Technologies
 
Earthing and disconnecting panel report.pdf
Earthing and disconnecting panel report.pdfEarthing and disconnecting panel report.pdf
Earthing and disconnecting panel report.pdf
 
protection of feeders in distribution substation
protection of feeders in distribution substationprotection of feeders in distribution substation
protection of feeders in distribution substation
 
Experiments manual
Experiments manual Experiments manual
Experiments manual
 
Reprint3
Reprint3Reprint3
Reprint3
 
Vibration monitoring of Gearboxes.pdf
Vibration monitoring of Gearboxes.pdfVibration monitoring of Gearboxes.pdf
Vibration monitoring of Gearboxes.pdf
 
Water Treatment Plant Protection
Water Treatment Plant ProtectionWater Treatment Plant Protection
Water Treatment Plant Protection
 
Transformer design and protection
Transformer design and protectionTransformer design and protection
Transformer design and protection
 
Proboat - Practical Impact Exposure Testing
Proboat - Practical Impact Exposure TestingProboat - Practical Impact Exposure Testing
Proboat - Practical Impact Exposure Testing
 

Recently uploaded

TrustArc Webinar - Unified Trust Center for Privacy, Security, Compliance, an...
TrustArc Webinar - Unified Trust Center for Privacy, Security, Compliance, an...TrustArc Webinar - Unified Trust Center for Privacy, Security, Compliance, an...
TrustArc Webinar - Unified Trust Center for Privacy, Security, Compliance, an...
TrustArc
 

Recently uploaded (20)

TopCryptoSupers 12thReport OrionX May2024
TopCryptoSupers 12thReport OrionX May2024TopCryptoSupers 12thReport OrionX May2024
TopCryptoSupers 12thReport OrionX May2024
 
JavaScript Usage Statistics 2024 - The Ultimate Guide
JavaScript Usage Statistics 2024 - The Ultimate GuideJavaScript Usage Statistics 2024 - The Ultimate Guide
JavaScript Usage Statistics 2024 - The Ultimate Guide
 
Design and Development of a Provenance Capture Platform for Data Science
Design and Development of a Provenance Capture Platform for Data ScienceDesign and Development of a Provenance Capture Platform for Data Science
Design and Development of a Provenance Capture Platform for Data Science
 
TrustArc Webinar - Unified Trust Center for Privacy, Security, Compliance, an...
TrustArc Webinar - Unified Trust Center for Privacy, Security, Compliance, an...TrustArc Webinar - Unified Trust Center for Privacy, Security, Compliance, an...
TrustArc Webinar - Unified Trust Center for Privacy, Security, Compliance, an...
 
AI mind or machine power point presentation
AI mind or machine power point presentationAI mind or machine power point presentation
AI mind or machine power point presentation
 
Cyber Insurance - RalphGilot - Embry-Riddle Aeronautical University.pptx
Cyber Insurance - RalphGilot - Embry-Riddle Aeronautical University.pptxCyber Insurance - RalphGilot - Embry-Riddle Aeronautical University.pptx
Cyber Insurance - RalphGilot - Embry-Riddle Aeronautical University.pptx
 
Extensible Python: Robustness through Addition - PyCon 2024
Extensible Python: Robustness through Addition - PyCon 2024Extensible Python: Robustness through Addition - PyCon 2024
Extensible Python: Robustness through Addition - PyCon 2024
 
Vector Search @ sw2con for slideshare.pptx
Vector Search @ sw2con for slideshare.pptxVector Search @ sw2con for slideshare.pptx
Vector Search @ sw2con for slideshare.pptx
 
Using IESVE for Room Loads Analysis - UK & Ireland
Using IESVE for Room Loads Analysis - UK & IrelandUsing IESVE for Room Loads Analysis - UK & Ireland
Using IESVE for Room Loads Analysis - UK & Ireland
 
How to Check CNIC Information Online with Pakdata cf
How to Check CNIC Information Online with Pakdata cfHow to Check CNIC Information Online with Pakdata cf
How to Check CNIC Information Online with Pakdata cf
 
Working together SRE & Platform Engineering
Working together SRE & Platform EngineeringWorking together SRE & Platform Engineering
Working together SRE & Platform Engineering
 
UiPath manufacturing technology benefits and AI overview
UiPath manufacturing technology benefits and AI overviewUiPath manufacturing technology benefits and AI overview
UiPath manufacturing technology benefits and AI overview
 
2024 May Patch Tuesday
2024 May Patch Tuesday2024 May Patch Tuesday
2024 May Patch Tuesday
 
Design Guidelines for Passkeys 2024.pptx
Design Guidelines for Passkeys 2024.pptxDesign Guidelines for Passkeys 2024.pptx
Design Guidelines for Passkeys 2024.pptx
 
WebAssembly is Key to Better LLM Performance
WebAssembly is Key to Better LLM PerformanceWebAssembly is Key to Better LLM Performance
WebAssembly is Key to Better LLM Performance
 
WebRTC and SIP not just audio and video @ OpenSIPS 2024
WebRTC and SIP not just audio and video @ OpenSIPS 2024WebRTC and SIP not just audio and video @ OpenSIPS 2024
WebRTC and SIP not just audio and video @ OpenSIPS 2024
 
(Explainable) Data-Centric AI: what are you explaininhg, and to whom?
(Explainable) Data-Centric AI: what are you explaininhg, and to whom?(Explainable) Data-Centric AI: what are you explaininhg, and to whom?
(Explainable) Data-Centric AI: what are you explaininhg, and to whom?
 
ERP Contender Series: Acumatica vs. Sage Intacct
ERP Contender Series: Acumatica vs. Sage IntacctERP Contender Series: Acumatica vs. Sage Intacct
ERP Contender Series: Acumatica vs. Sage Intacct
 
Syngulon - Selection technology May 2024.pdf
Syngulon - Selection technology May 2024.pdfSyngulon - Selection technology May 2024.pdf
Syngulon - Selection technology May 2024.pdf
 
Top 10 CodeIgniter Development Companies
Top 10 CodeIgniter Development CompaniesTop 10 CodeIgniter Development Companies
Top 10 CodeIgniter Development Companies
 

Why Transformers need ShockLog

  • 1. Logistics Risk Management in the Transformer Industry by: ShockWatch, Inc.
  • 2. Logistics Risk Management in the Transformer Industry 1 In 2014 an electrical transformer being shipped from Israel to Canada was damaged in transit. The $2 million transformer was returned to Israel for repair then shipped back to the client, delaying the project. The insurer sued the railway and the logistics carrier for $911,233 in damages. It settled for $750,000 on behalf of its client. In a 2013 case (ABB Inc. v. CSX Transportation), when a $1.3 million transformer was “allegedly damaged” in transit, a U.S. appeals court reversed a portion of a lower court ruling and made the railroad liable for the full damages of $550,000 rather than the $25,000 liability it expected under the Carmack Amendment to the Interstate Commerce Act. CSX has never admitted liability. These cases are notable, but not the only examples of accidents that cause delays in transformer delivery and installation. Simply attaching impact monitors to the shipments could have improved both of those situations. These important risk management tools would have shown the extent, duration, and location of the impacts quickly and easily, helping prove liability for some rather substantial repair bills. Logistics is a Vital Part of Transformer Health Consider this: the supply chain for transformers stretches around the globe, involving multiple handoffs, transportation methods, and carriers. Each handoff entails risk. The transformer for the substation at Conway, New Hampshire is a case in point. The 411 ton transformer was built in Hebei, China, 7,000 miles from its destination. It traveled by truck and rail from Hebei to the port of Xingang, where it was loaded onto a ship. It crossed the Pacific, transited the Panama Canal, entered the Gulf of Mexico and stopped in Houston. It then entered the Atlantic and steamed up the East Coast before being offloaded at Searsport, Maine onto a Schnable rail car. Designed for tight turns, the Schnable car uses hydraulics to shift the load left or right to ensure clearances. From Maine, the transformer went by rail through Quebec, Canada, and returned to the U.S. through Vermont before reaching North Conway, New Hampshire. There, it was transferred to truck for its final journey to the Conway Power Station. That convoluted route was necessary to ensure the infrastructure could support the 411 ton transformer. Still, it crossed 84 bridges. Some of those hadn’t borne heavy freight in 26 years. In all, more than 15 service providers were involved in transporting the transformer and ensuring the safety of the route. Logistics Risk Management in the Transformer Industry Abstract: Transformers often are shipped thousands of miles, involving multiple handoffs, and more than a dozen logistics teams before they are installed. With an impact threshold of about 2.5g, damage isn’t always evident. Hidden damage may trigger an event cascade that causes catastrophic failure long after installation. Impact monitors reduce that potential by recording the impact and duration of potentially damaging events. Prior to transformer installation, this data can be compared to the transformer damage boundary to determine the extent of potential damage. This data enables improvements in risk management practices that, by properly ascribing liability, can identify where and when damage occurred and ultimately reduce warranty costs and transformer downtime.
  • 3. Logistics Risk Management in the Transformer Industry Impacts and vibrations can: • Loosen nuts and bolts, causing overheating. • When panels are loosened, it also can create excessive noise and create resonance among components. • Abrade insulation, leading to short circuits and damaged windings. • Distort or displace windings, loosening their clamping pressure, which contributes to their collapse during electrical faults. • Reduce clearances between the housing and components. • Damage related components, like radiators and bushings. • Harden metals. • Create microfissures in the transforme . It’s bad enough when this damage occurs in geographically accessible locations. When it occurs in remote parts of the world, shipping the damaged transformer back to the manufacturer isn’t always a valid option. Instead, a repair team may need to fly in at great expense. Where Damage Occurs An analysis showed that large power transformers (>100T) get damaged between the 2.5 to 5.0 g (2-20 Hz) band, while small equipment like a laptop gets damaged between 37 to 50 g (2-250Hz) band. That means that most damage to transformers occurs at low acceleration levels during transit. This damage is most likely from loading, unloading, and rigging operations, and during transportation. A small portion of damage occurs as transformers are positioned on their foundations. What Can Go Wrong? Such a complex transportation plan and long supply chain requires meticulous planning. Each transfer increases the risk. Although the Conway, NH delivery was executed smoothly, other transformers have broken free and damaged other goods. One even fell off its transport car. Several court cases cite “damage” or “alleged damage” during transport. A drop of even a few inches can damage transformers. The heavier they are, the greater the potential for damage. (Damage is determined by weight, volume and impact surface, and also by the amplitude, duration, and frequency of the impact.) The resulting damage may be visible or, more concerning, concealed. If concealed, these transformers may be installed and made operational, triggering failures during power up or even later in their life cycle. That damage may never be tracked back to its source, causing great expense for power utilities or manufacturers through no fault of their own. One instruction manual (from manufacturer WEG) for dry transformers, for example, cautions handlers to lift the transformer only by specific points. Using others could severely damage the transformer. Forklifts aren’t recommended, either, and strains may only be applied to the base beams or core pressing beams. It points out that transformers with protective boxes shouldn’t be lifted using the eyebolts on the outside of the box. Instead, it can be lifted using the leach eyes on the transformer’s top beams inside the box. It also cautions against transporting or storing the transformers if they were subjected to “abnormal vibrations and occasional collisions.” 2 Logistics Risk Management in the Transformer Industry When damages occurs in remote parts of the world, shipping the damaged transformer back to the manufacturer isn’t always a valid option. “ ”
  • 4. Logistics Risk Management in the Transformer Industry 3 Logistics Risk Management in the Transformer Industry The point of this recommendation is to support pre- installation analyses that are more efficient and more accurate. If engineers know the transformer they are checking experienced an impact that exceeded a certain threshold – usually about 3Gs – they know to check carefully for damage that may otherwise be missed. Likewise, if they can prove the transformer was handled carefully and experienced no impacts even approaching the thresholds where damage occurs, they may be able to streamline the analysis. By using impact monitors, customers know to check for visible and hidden damage before these transformers are installed. And, if damage has occurred, impact recorders also help attribute liability. The most advanced impact recorders record the acceleration of impacts, their direction along x, y, and z axes, event duration, tilt and roll, vibration, geographic location, and time of occurrence. They typically record hundreds of impact events for well-over a year with accuracy of plus or minus two percent, and report in real- time or near-real time through wireless networks. Impact recorders won’t prevent the damage, but they can alert you that transformers have experienced mechanical impacts or vibrations... “ ” When unloading and rigging accidents occur, the impacts are in the range of 1 to 10gs in the 2-20 Hz band. Mechanical shocks while on trailers are related to braking and road conditions. They typically range between 0.5 and 1 g in the 3-350 Hz band, and are unlikely to cause damage. On trains, transformers experience longitudinal impacts up to 4 g in the 2-20 Hz band from shunting operations, and vertical shocks between 0.5 and 1 g in the 2-500Hz band from rail joints. Aboard ships, transformers experience rolling, pitching, and yawing, with low-frequency vibrations typically ranging between 0.3 and 0.8 g in the 2-30 Hz band. These vibrations rarely cause damage. However, the pitch and roll of the ship can reach up to 5-7 degrees and 45 degrees respectively, which can loosen cargo and send a 100T transformer crushing into other cargo. Damage is based on the combination of acceleration (g), duration (msec), and frequency (Hz). Impact monitors typically record acceleration and duration to help users pinpoint the potential for damage, and where and when it occurred. Frequency may be extrapolated from the duration of the impact. Impact Recorders Impact recorders won’t prevent the damage, but they can alert you that transformers have experienced mechanical impacts or vibrations above certain thresholds and, therefore, may be damaged. IEEEguideC57.150specifiestworecorderspertransformer, mounted diagonally opposite each other. The impact recorders are mounted on opposite ends of the transformer because transformers are becoming so long in length. If one end of a transformer is dropped, the recorder on the opposite end would not record the true acceleration value because the transformer would attenuate the acceleration value from one end to the other.
  • 5. Logistics Risk Management in the Transformer Industry 4 Logistics Risk Management in the Transformer Industry Because these impact recorders are tamperproof, they are accepted as evidence by courts of law and are trusted by insurance companies. Impact monitoring also can help reduce warranty claims from failures once the transformers are in operation. Damage isn’t always evident. Microfractures in internal components, for example, may not be noticed, but may cause problems (such as overheating) long after the transformer has begun operating. Or small, unnoticed issues may create a cascade that ultimately results in catastrophic failure. When hidden damage goes unnoticed, the power utility or manufacturer end up paying for damage that occurred on the transportation carrier’s watch. This is damage that should be covered under the carrier’s insurance. Proper use of impact monitors, however, helps inspectors uncover hidden damage and attribute it to the responsible party. For carriers, impact monitors can help limit their liability by ascertaining exactly where, during transit, the damage occurred. With multiple handoffs to carriers in many countries and widely varying logistics practices and infrastructure conditions, knowing whether transformers were damaged on your watch, or before or after you took possession, can be invaluable in managing risk and transportation partners. For example, several carriers have argued they aren’t liable for damages because they took reasonable care. However, in Prima (et al) vs. Panalpina, a lower court found in 2000 Panalpina liable for damages when an electrical transformer came loose during transit and damaged other cargo. That court cited Panalpina’s promise to Westinghouse: “Rest assured your shipment will receive, door-to-door, our close care & supervision.” An appeals court overturned the decision, saying Panalpina was a forwarder, not a carrier. That distinction aside, with impact monitoring, you can determine whether “reasonable care” was taken, because you have the impact data. Using impact monitors also helps engineers better estimate transformer fragility without resorting to shock response spectrum analysis or finite element analysis. Monitors provide real-world, experiential data that can be accumulated, analyzed, and correlated to specific conditions, carriers, or transformer designs. Conclusion Impact recorders are part of a cohesive risk management strategy that stretches from manufacturing to installation. Transformer health depends on accurate, reliable data – including data that measures impacts that can cause damage. Impact monitors provide that data, thus helping to increase the accuracy of pre- installation analyses, saving time and money.