VRF System
VRV System
Introduction
• Variable Refrigerant Flow (VRF), also known as Variable
Refrigerant Volume (VRV)
• Invented in Japan, by DAIKIN in 1982
• Daikin had patented this technology and registered the term VRV
as an official trademark, so other companies called this technology
as VRF
• Daikin, Bluestar, Samsung, LG, Carrier, Mitsubishi, Midea,
Toshiba, York
SYSTEM
• It is a multi split air conditioning unit working on DX
principle with Single OUTDOOR UNIT(ODU) and Multiple
INDOOR UNITS(IDU)
• Interconnected with Refrigerant piping
• COOLING/HEATING can be controlled by adjusting the
amount of refrigerant flowing to each of the IDUs,
enabling the use of different capacities and configurations
• Individualized comfort control
OUTDOOR UNITS
INDOOR UNITS (Wall mounted, Ductable, Cassette,
Floor Standing)
Refrigerant Piping and Accessories (Refnets & Headers)
Inverter Compressor and EEV
Remote Controller - Wired and Wireless (Centralized
Controller for BMS)
COMPONENTS
TYPES OF VRF
SYSTEMS
Cooling Only
Only Cooling is possible
2 Pipe System
Heat Pump
Cooling and Heating
possible, but one at a time
2 Pipe system with a
reversible solenoid valve
Heat Recovery
Cooling and Heating
possible at same time
3 pipe System with
reversible solenoid valve
and branch selectors
ADVANTAGES
• Energy Saving claimed upto 30 %
• Higher COP compared to other DX systems
• Space Saving
• Lesser Noise
• Precise Temperature Control
• Zoned Comfort
• Reduced Operating Cost
• No seperate Control System required
LIMITATIONS
• Initial Cost is high
• Environmental Concerns (GWP of refrigerants)
• Refrigerant piping
• Limitation of height b/w and IDU and ODU in high rise buildings
• Seperate system for fresh air/ventilation required
CHILLER
VS
VRF SYSTEM
Design
VRF is very simplified refrigerant piping system.
More flexible than a chilled water piping sysetm
Control System
Easy network wiring for VRF
Control System
Easy control system compared to Chiller system.
Operation
Precise Temp Control for VRF
Installation/Operation
Less Space required. Sfaht space requirement is also less.
Commissioning
Less commissioning points required for VRF
Maintanence
Maintanence
THANK
YOU

VRF system - HVAC........................

  • 1.
  • 2.
    Introduction • Variable RefrigerantFlow (VRF), also known as Variable Refrigerant Volume (VRV) • Invented in Japan, by DAIKIN in 1982 • Daikin had patented this technology and registered the term VRV as an official trademark, so other companies called this technology as VRF • Daikin, Bluestar, Samsung, LG, Carrier, Mitsubishi, Midea, Toshiba, York
  • 3.
    SYSTEM • It isa multi split air conditioning unit working on DX principle with Single OUTDOOR UNIT(ODU) and Multiple INDOOR UNITS(IDU) • Interconnected with Refrigerant piping • COOLING/HEATING can be controlled by adjusting the amount of refrigerant flowing to each of the IDUs, enabling the use of different capacities and configurations • Individualized comfort control
  • 4.
    OUTDOOR UNITS INDOOR UNITS(Wall mounted, Ductable, Cassette, Floor Standing) Refrigerant Piping and Accessories (Refnets & Headers) Inverter Compressor and EEV Remote Controller - Wired and Wireless (Centralized Controller for BMS) COMPONENTS
  • 6.
    TYPES OF VRF SYSTEMS CoolingOnly Only Cooling is possible 2 Pipe System Heat Pump Cooling and Heating possible, but one at a time 2 Pipe system with a reversible solenoid valve Heat Recovery Cooling and Heating possible at same time 3 pipe System with reversible solenoid valve and branch selectors
  • 7.
    ADVANTAGES • Energy Savingclaimed upto 30 % • Higher COP compared to other DX systems • Space Saving • Lesser Noise • Precise Temperature Control • Zoned Comfort • Reduced Operating Cost • No seperate Control System required
  • 8.
    LIMITATIONS • Initial Costis high • Environmental Concerns (GWP of refrigerants) • Refrigerant piping • Limitation of height b/w and IDU and ODU in high rise buildings • Seperate system for fresh air/ventilation required
  • 9.
  • 10.
    Design VRF is verysimplified refrigerant piping system. More flexible than a chilled water piping sysetm
  • 11.
  • 12.
    Control System Easy controlsystem compared to Chiller system.
  • 13.
  • 14.
    Installation/Operation Less Space required.Sfaht space requirement is also less.
  • 15.
  • 16.
  • 17.
  • 18.