This document summarizes the specifications of a 6KVA and 10KVA true online double conversion UPS system. The UPS offers rack/tower convertible design, flexible 1P/1P or 3P/1P configuration, LCD display with parameter settings, and parallel capability of up to 4 units. It provides pure sine wave output with voltage regulation of ±1% and frequency conversion. The system supports matching extended battery packs for backup times of over 30 minutes.
3. Mission critical & industrial applications
Servers, Computer Rooms
Communication System
Processing Control Equipments,
Security Systems, etc.
VFI-BL 6&10KVA
4. Rack/Tower Convertible Design
Flexible System Configuration 3P/1P or 1P/1P
Rotatable LCD Display with Multifunction
Parameter Settings
N+X Parallel Redundancy
True Online Double Conversion with DSP Control
Unity Power Factor & Low Input Current THD
Green Concept Design for Environment
Main Features
VFI-BL 6&10KVA
5. Estimated Remaining Time on the LCD
ECO Mode Settable
Frequency Converter Mode(optional)
Matching Battery Pack
Hot Swappable Battery Design
Battery Voltage Configurable
Automatic Battery Test Settable from LCD
Main Features
VFI-BL 6&10KVA
6. Common/Separate Battery in Parallel Mode
3-level Intelligent Charging Modes
Built-in Powerful Charger can be automatically set
from 1A to 10A
Superior Overload Capability
Emergency Power OFF(EPO) Built-in
Versatile Communication Interfaces Built-in
Communication Software
UPServer Setting Software
Main Features
VFI-BL 6&10KVA
10. 6-button dot matrix LCD with Backlight
Easy Read-out Numerical Values & UPS Status
Various Parameters Can be set from LCD Display
LCD Display with Multifunction Parameter
Setting
VFI-BL 6&10KVA
11. Input, Output, Inverter,
Battery, Bus, temperature
Parallel, Alarm Code, Version
Easy Read-out Numerical Values & UPS Status
VFI-BL 6&10KVA
12. System Setting
Parallel Setting
Battery Setting
Charge Mode Setting
Different Settings from LCD Display
VFI-BL 6&10KVA
13. up to 4 Units can be set in parallel
Parallel Cable Requirement
N + X Parallel Redundancy
* Main wire for linking all the UPS in parallel should be N*10AWG and N*8AWG for 6K and
10K respectively
Model RTII 9106RT/9306RT RTII 9110RT/9310RT
Connecting Wire 10AWG 8AWG
VFI-BL 6&10KVA
18. De-rating Operation Available
Temperature: Normal operation at 0~40 C
& 12% per 5 C (max. 50 C)
Altitude:
Altitude
(m) 1500 2000 2500 3000 3500 4000 4500 5000
Load
coefficient
100% 95% 90% 85% 80% 75% 70% 65%
VFI-BL 6&10KVA
19. Wide Input Voltage Window 120Vac~276Vac *
for 230V and 304Vac~478Vac for 400V system
High Conversion Efficiency up to 93.5%
ECO Mode(Line-interactive) Settable
Green Concept Design for Environment
* 120/208~160/278V at 50%
160/278~176/304V at 80%
176/304~276/478V at 100%
VFI-BL 6&10KVA
20. Enable User to Shutdown Load on time before Bat.
Cut-off
Estimated Remaining Time on LCD Display
Figure
PBatt. Discharge
0V 0.0A
0% 0min
Figure
NBatt. Discharge
0V 0.0A
0% 0min
Bat. + Bat. -
VFI-BL 6&10KVA
21. Optional Frequency Converter Mode Supported
Set by UPSServer Setting Software
Frequency Converter Mode
VFI-BL 6&10KVA
23. UPS + Battery Packs Runtime Table
Model + 1 EBP + 2 EBPs + 3 EBPs + 4 EBPs
6K 5’12” 14’42” 25’54” 38’
10K 3’24” 10’18” 18’30” 27’30”
NOTE: Battery times indicated above are for reference only, which might
vary according to load configuration and battery charge.
Unit: Minute/Second
BP-240-7 for 6K and BP-240-9 for 10K
VFI-BL 6&10KVA
24. Quantity
Voltage
Capacity
Charge Mode
Battery Setting
Setting
Battery set
EOD 1.70
Batt Num 20
Setting
Battery set
Batt-G 1
Batt-C 7
Setting
Battery set
Boost 2.30
Float 2.20
Setting
Battery set
Boost Enable
Battery Number, String, AH and Charge Mode Setting
VFI-BL 6&10KVA
25. Default Voltage: 240Vdc
192Vdc/216Vdc Configurable
System Battery Voltage Configurable
VFI-BL 6&10KVA
26. For 1P/1P
Battery Voltage v.s. Output Power Factor
16pcs 18pcs 20pcs
Battery Capacity
>=18AH
0.7PF 0.8PF 0.9PF
Battery Capacity
<18AH
0.9PF
For 3P/1P
16pcs 18pcs 20pcs
Power Factor 0.7 PF 0.8 PF 0.9 PF
VFI-BL 6&10KVA
27. Automatic Battery Test Settable from LCD
Settable from LCD Display
Periodically Automatic Battery Test Every 30 Days
Battery Test Period can be set at 10 seconds, 10 min.
or EOD
VFI-BL 6&10KVA
28. Common Battery Available when UPS in parallel
Only One String Battery for all paralleled UPS
Affordable & Convenient
Common Battery
VFI-BL 6&10KVA
29. 3-level Intelligent Charging Modes
(Boost Charge 2.30V to 2.35V per cell &Float Charge 2.20V to 2.29V per cell)
Charge
Boost Last Charge
Boost Charge
Floating
t1 t2 Time
7H 1H
VFI-BL 6&10KVA
30. Adjustable from 1A to 10A
Charging Current is automatically
adjusted according to the parameter of
the battery capacity set
Built-in Powerful Charger
VFI-BL 6&10KVA
31. 100%~110% lasts for 1 hour
110%~125% lasts for 10 minutes
125%~150% lasts for 1 minute
Superior Overload Capability
VFI-BL 6&10KVA
32. Provide both NC and NO, settable from LCD
Emergency Power Off
EPO Connections
Wire Function Terminal Wire Size Rating Suggested Wire Size
EPO L1
4-0.32mm2 (12-22AWG) 0.82mm2 (18 AWG)
L2
Default: NO
VFI-BL 6&10KVA
33. Built-in USB/RS-232
Parallel Port
1 Communication Slot
Versatile Communication Interfaces
VFI-BL 6&10KVA
34. 1 Communication Slot for SNMP Card or
Dry Contact Card
Versatile Communication Interfaces
VFI-BL 6&10KVA
40. Input
Specifications
Model VFI6000BL VFI10KBL
Capacity (VA/W) 6KVA/5.4KW 10KVA/9KW
Input
Phase 1Phase 2 Wires + Ground or 3 Phase 4 Wires+ Ground
Rated Voltage 380/400/415Vac or 220/230/240VAC
Voltage Range 208~478Vac or 120VAC-276VAC
Frequency Range 45Hz-55Hz / 55Hz-66Hz
Power Factor ≥0.99
Current THDi
≤3%(100% linear load)
≤5%(100% non-linear load)
Bypass Voltage Range
220Vac Max. : 10%, 15%, 20% or 25%, default : 25%
230Vac Max. : 10%, 15% or 20%, default : 20%
240Vac Max. : 10% or 15%, default : 15%
Min. : 20%, 30% or 45%, default : 45%
ECO Range same as the bypass
Generator Input Support
VFI-BL 6&10KVA
41. Output
Specifications
Model VFI6000BL VFI10KBL
Capacity (VA/W) 6KVA/5.4KW 10KVA/9KW
Output
Phase 1Phase 2 Wires + Ground
Rated Voltage 220/230/240VAC
Power Factor 0.9
Voltage Regulation ±1%
Frequency
Utility
Mode
±1%、±2%、±4%、±5%、±10% of the rated frequency(optional)
Battery
Mode
(50±0.1%)Hz
Crest Factor 3:1
THD
≤2% with linear load
≤5% with non linear load
Waveform Pure Sinewave
VFI-BL 6&10KVA
42. Specifications
Battery
Model VFI6000BL VFI10KBL
Capacity (VA/W) 6KVA/5.4KW 10KVA/9KW
Battery
Voltage Standard: 192Vdc; Optional Voltage: 216/240Vdc
Backup Time
Full load≥2min(Standard), Long time unit depends on the capacity of
external batteries
Estimated remaining time displayed on the LCD
Recharge time to 90% 8~10 hours (Standard)
Charging Current
Maximum Current 10A; charge current can be set according to battery
capacity installed.
Battery Socket Anderson like PowerPole Modular Connectors
VFI-BL 6&10KVA
43. Specifications
Physical
Model VFI6000BL VFI10KBL
Capacity (VA/W) 6KVA/5.4KW 10KVA/9KW
Physical
Input Connection Hardwire
Output Connection Hardwire & IEC320-C13-10A x 2
External Battery
Connection
Anderson like PowerPole Modular Connectors
UPS MODULE
Model Name
Input/Output
Phase
Efficiency Dimension(WxHxD)mm Weight (Kg)
VFI6000BL
1P/1P 92.0%
443x131(3U)x580 23
VFI10KBL 443x131(3U)x580 25
VFI6000BL-31
3P/1P 93.5%
443x131(3U)x580 28
VFI10KBL-31 443x131(3U)x580 30
VFI-BL 6&10KVA
44. Specifications
Extended Battery Pack(EBP)
BATTERY BANK
Model BP-240-7 BP-240-9
Bat. Type 7AH 9AH
Max. Quantity 20 20
Other
Unit Dimensions WxHxD (mm) 443x131(3U)x720
Weight (Kg) 58 67
VFI-BL 6&10KVA