UPS: FirstLine P
WHO IS STACO ENERGY
PRODUCTS COMPANY ?
Who are we?
A 75+ year old privately held
manufacturer of voltage control
and power quality products.
Based in Dayton Ohio with 80 employees.
What do we do??
We provide tailored power solutions to targeted
markets.
HOW DO WE DO IT?
– We partner with the best in every market
• Rep’s, Distributors, Integrators, OEM’s
– We focus on specific vertical applications /
markets
• WWT, Education, High Energy Physics, Process
Manufacturing
– We provide world class service and support
• Over 60 Factory trained service tech’s in the US.
– We manufacture the best products on the
market
• We back our products with the best warranties in the
industry
FIRSTLINE P
65kVA / 58.5kW
80kVA / 72kW
100kVA / 90kW
125kVA / 112.5kW
160kVA / 144kw
200kVA / 180kw
250kVA / 225kw
FIRSTLINE P UPS
• True double conversion, “On-Line”
• Hot Swap Unit Capability
• Digital Signal Process Control
• Menu Selectable Monitoring Panel with Graphic display
• Parallel up to 8 Modules
• Dual Bus Configurations
• Delayed Start Up on power source return
• IGBT, PWM Inverter (Insulated Gate Bipolar Transistor)
• Efficiency up to 98%
• 0.99 High Input Power Factor
• Configurable Power Walk-In
• Sinusoidal Output Waveform
MAJOR COMPONENTS
• Rectifier complete with power factor correction
• Fast Battery charger
• Continuous duty rated Static Switch
• Manual Maintenance Bypass
• Input Isolation switch (SWIN)
• Output Isolation switch (SWOUT)
• Maintenance Isolation switch (SWMB)
• Bypass Isolation switch (SWBY)
• Parallel Kit (Standard)
• 4 x 2 and 2 x 2 Voltage Configuration available
AC INPUT
CHARACTERISTICS
Nominal Voltage: 480 VAC, 3 Phase, 4-wire (plus ground) or 208Y/120 VAC,
3 Phase, 4-wire + ground with external line up and match transformer cabinet
(Optional)
Nominal Voltage Range: +15/-10% from nominal voltage during battery recharge.
Voltage Range on battery: +15% / -40%
Frequency Range: 45 - 65 Hz)
Power Factor: > 0.99 at full load, nominal conditions.
Current Harmonic Distortion (THDi): < 3%
Inrush current: Less than nominal input current for less than one cycle.
Input Surge Protection: UPS shall be equipped to withstand surges per ANSI/IEEE
C62.41.
Rectifier Walk-in: Progressive from 0 to 30 seconds (adjustable).
Rectifier Walk-in Delay Timer: Progressive start of rectifier from 0 to 120 seconds
(adjustable).
AC OUTPUT
CHARACTERISTICS
Voltage: 480Y/277 VAC, ± 1% steady state variation phase-to-phase voltage volts AC,
three-phase, 4 wire plus ground (Standard Voltage) or 208Y/120 VAC, 3 Phase, 4-wire +
ground - with external line up and match transformer cabinet (Optional).
Frequency: 60Hz, + 2%, 60Hz, + .05% when free running.
Voltage regulation: ±1% for balanced load, ±3% for 100% unbalanced load.
Voltage Distortion: Maximum 2% total (THD).
Voltage Transient (Step Load) Response: + 5% for 100% step load change.
Voltage Recovery Time: Return to within 1% of nominal value within 20 milliseconds.
Phase Angle Displacement: 120 degrees + 1 degree for balanced load; 120 degrees,
+ 1 degree for 100% unbalanced load.
Non-Linear Load Capability: Output voltage total harmonic distortion shall be less than
2% when connected to a 100% non-linear load with a crest factor not to exceed 3%.
AC OUTPUT
CHARACTERISTICS
(CONTINUED)
Slew Rate: 1 hertz/second maximum.
Power Factor: 0.9 at the rated volt amperes .
Inverter Overload Capability: 110% of rated load for 60 minutes, 150% of rated load
for 1 minute.
Bypass Overload Capability: 110% for 60 minutes, 125% for 10 minutes,150% for 1
minute.
Output Waveform: Sinusoidal
Efficiency: (DC-AC): Minimum - 95% at Full Load, (AC-AC): Minimum – 93% at Full
Load
CABINET CONFIGURATION
A. Control panel with graphic display
B. Door handle
C. Ventilation grilles
D. Communication area
E. Front Cover panel with
ventilation grilles
F. Switch cover panel
G. Door
1. SWIN: Input isolating switch
2. SWOUT: Output isolating switch
3. SWMB: Maintenance isolating switch
4. WBY: Bypass isolating switch
A
B
D
C
E
1
2
3
4
G
G
F
CARD LOCATIONS
A
F G
E
D
B
C
J
N
H
I
K
A. Parallel Card
B. EPO Control
C. Remote Commands and Alarms
D. RS-232-2
E. RS-232-1
F. Slot 2 (Aux)
G. Slot 1 (Main)
H. Remote Alarm Dry Contact Card 1 (Optional)
I. Remote Alarm Dry Contact Card 2 (Optional)
J. Multi I/O Card (Optional)
K. Interface Terminal Connector
L. UGS (Optional)
BOTTOM CABLE ENTRY
(STANDARD)
Power Battery
Cable Entry
External Control
Cable Entry
Power AC Cable
Entry
REAR
FRONT
UPS Bottom View
AIR FLOW (FORCED &
CONVECTION)
The heat dissipation needed for the
correct operation of the UPS is brought
about by the air current made by the
fans located inside the UPS (forced
convection) and by the air around the
side panels (natural convection).
Clearance: FRONT and at least one of the
three side walls free: right, left or back.
CONTROL PANEL DISPLAY
CONTROL PANEL
MENUS
BASIC CONTROL
FUNCTIONS
o Output Voltage – Selects the rated output voltage
o Operating Mode – Selects the operating Mode: On-Line, Stand-By ON, Smart Active
o Auto Off – If bypass line is present and the load is < of the set value than the load will be
supplied from the bypass line. If the bypass line in not preset and the load is < of the set
value than the load will not be supply (configurable 0 to 99%).
o Battery Low Warning – Estimated battery time remaining for low battery warning (configurable).
o Battery Capacity – Sets the Amp Hour Battery installed.
o Audible Alarm – Audible alarm operating mode: Enable/Disable
o Language Select area – English, Italian, German, French, Spanish, Polish or Turkish.
ADVANCED CONTROL
FUNCTIONS
o Input Frequency Tolerance Range – Selects the acceptable range for the input frequency for
switching to the bypass and for the synchronization of the output: +/- 1 to +/- 6 in 1% stages.
o Bypass Voltage Thresholds – Selects the acceptable voltage range for switching to the bypass:
+/- 5 to +/- 25 in 1% stages.
o Bypass Voltage Threshold for ECO – Selects the acceptable voltage range for operation in ECO
Mode: +/- 5 to +/- 25 in 1% stages.
o Switch-On Delay – Waiting time for automatic power-on after the return of power source voltage:
Disable or configurable 1 to 255 in 1 second stages.
o Power Walk-In – Activates the gradual return to power source mode: Activated or Deactivate
o Power walk-In Duration – Sets the duration of the gradual return to power source voltage
(only if Power Walk-In is activated: Minimum 0 seconds to maximum 125 seconds in 1 second stages.
o Inverter Synchronization Speed to Bypass Line – Selects the synchronization speed of the
inverter to the bypass line: 0.1 to 1 Hz/sec (parallel units), 0.1 to 3 Hz/sec (single units).
ALARMS
Normal Operation
Disturbances on Bypass Line
Manual Bypass (SWMB) On
Bypass Line Volt, Failure
Main Line Voltage Failure
Pre-alarm, Low Battery Voltage
Low Battery Charge or Closed
Disconnect
Low Input Voltage
Output Overload
Internal Fault
Temporary Bypass, Wait
Bypass for Output Overload
Bypass Command ON or OFF
Remote Bypass Command Active
Over-temperature or Fan Failure
Input Voltage Sequence not OK
Output Off
System Off Command ON or OFF
Remote System Command ON or
OFF
Auto-shutdown Timer ON
System Off
Battery test ON
Parallel Cable Fault
Fuse Fault
Battery Discharge Fail
High Battery
Temperature
Slave UPS OFF
Fan Fault
Parallel Redundant Lost: High Unit Power
Parallel Redundant Lost: Unit OFF
Break Circuit Fail
Break Circuit Overload
Rectifier Switched Off by Remote Command
UPS Service Required
Battery Service Required
Input Switch Off
Insulation Loss-AC
Insulation Loss-DC
Over-temperature On Bypass Line Transfer
Inverters Off
FIRSTLINE P 65 – 125KVA
UPS MODELS
Model Number Description
Dimensions
H” x W” x D”
Weight.
(lbs.)
480V x 480V
FLU-065-00
65kVA /58.5kW
480V/480Y/277,
50/60Hz
75 x 31.5 x 33.5 1,499
FLU-080-00
80kVA /72kW
480V/480Y/277,
50/60Hz
75 x 31.5 x 33.5 1,499
FLU-100-00
100kVA /90kW,
480V/480Y/277,
50/60Hz
75 x 31.5 x 33.5 1,609
FLU-125-00
125kVA /112.5kW,
480V/480Y/277,
50/60Hz
75 x 31.5 x 33.5 1,742
FIRSTLINE P 160 – 250KVA UPS
MODELS
Model
Number Description
Dimensions
H” x W” x D”
Weight.
(lbs.)
480V x 480V
FLU-160-00
160kVA /144kW,
480V/480Y/277, 50/60Hz
75 x 39.5 x 33.5 1,984
FLU-160-T
160kVA /144kW,
480V/480Y/277, 50/60Hz
w/ Internal Bypass
75 x 55 x 33.5 2,326
FLU-200-00
200kVA /180kW,
480V/480Y/277, 50/60Hz
75 x 39.5 x 33.5 2,205
FLU-200-T
200kVA /180kW,
480V/480Y/277, 50/60Hz
w/ Internal Bypass
75 x 55 x 33.5 2,546
FLU-250-00
250kVA /225kW,
480V/480Y/277, 50/60Hz
75 x 39.5 x 33.5 2,425
FLU-250-T
250kVA /225kW,
480V/480Y/277, 50/60Hz
w/ Internal Bypass
75 x 55 x 33.5 2,767
FIRSTLINE P APPLICATION
NOTES
1. The FLU-160-00, FLU-200-00 & FLU-250-00 units DO NOT
have an internal bypass. If specification requires internal
bypass the -T Model MUST be used.
2. In all cases, if the specification requires an internal and
external bypass you MUST use the -T Model plus the
Line Up & Match
bypass cabinet.
UPS CABINET 65 – 125KVA
UPS CABINET 160 – 250KVA
W/O BYPASS
UPS CABINET 160 – 250KVA
WITH BYPASS
UPS CABINET - INTERNAL
FIRSTLINE P WITH BATTERY
CABINET
The UPS uses a valve-regulated sealed lead acid (VRLA) heavy
duty industrial battery, designed for auxiliary power service in a UPS
application. The primary battery is furnished with impact-resistant
plastic cases and housed in a matching cabinet(s) next to the UPS.
The UPS is capable of utilizing Wet Cell & NiCad batteries.
Protection Against Deep Discharge and Self-Discharge:
The UPS is equipped with a device designed to protect the battery
against deep discharge, depending on discharge conditions, with
isolation of the battery by a circuit breaker. From the monitoring
panel you can adjust the battery shutdown voltage as a function of a
discharge coefficient to avoid excessive discharge at less than the
rated output. A second device helps avoid self-discharge of the
battery into the UPS control circuits during an extended shutdown of
the UPS (over two hours).
Battery Self-Tests:
1. The battery monitoring system performs the following automatic
functions:
• Battery circuit check, programmable 9-99 days.
• Partial discharge test every three months.
STANDARD EXTERNAL
BATTERY MODELS
Model Number Voltage
#
Cabinets
Internal
Strings
Number
Batteries
Dimensions
H” x W” x D”
Weight
(lbs.)
FLU-BAT-200-1-480-B 480 1 1 40 75 x 26.3 x 38 2,307
FLU-BAT-200-2-480-B 480 1 2 80 75 x 26.3 x 38 3,932
FLU-BAT-300-2-480-B 480 1 2 80 75 x 26.3 x 38 3,923
The FLU-BAT-300-2-480-B is ONLY used with the 100kVA and 125kVA.The FLU-BAT-200-480-1-B can be used with a
FLU-BAT-300-2-480-B
FirstLine P Battery Back Up Times
(Minutes) 65kVA 200W/50AH 1 1 26 14 8 2,100
1 2 66 39 26 3,700
2 3 107 66 46 5,800
2 4 149 93 66 7,400
3 5 190 121 86 9,500
3 6 229 149 107 11,100
4 7 266 171 128 13,200
4 8 301 204 149 14,800
80kVA 200W/50AH 1 2 38 30 19 3,700
2 3 84 51 35 5,800
2 4 118 73 51 7,400
3 5 152 95 67 9,500
3 6 185 118 84 11,100
4 7 217 141 101 13,200
4 8 248 163 118 14,800
100kVA 200W/50AH 1 2 38 21 14 3,700
2 3 64 38 25 5,800
2 4 90 55 38 7,400
3 5 118 73 51 9,500
3 6 145 90 64 11,100
4 7 172 109 77 13,200
4 8 198 127 90 14,800
125kVA 200W/50AH 1 2 30 16 10 3,700
2 3 51 30 20 5,800
2 4 73 44 30 7,400
3 5 95 58 40 9,500
3 6 118 73 50 11,100
4 7 141 88 62 13,200
4 8 164 103 73 14,800
FIRSTLINE P BATTERY
BACK UP TIMES (MINUTES)
160kVA 200W/50AH 2 3 35 19 12 5,800
2 4 51 30 19 7,400
3 5 67 40 27 9,500
3 6 84 51 35 11,100
4 7 101 61 43 13,200
4 8 118 73 51 14,800
200kVA 200W/50AH 2 3 25 14 8 5,800
2 4 38 21 14 7,400
3 5 51 30 19 9,500
3 6 64 38 25 11,100
4 7 77 46 32 13,200
4 8 90 55 38 14,800
250kVA 200W/50AH 2 4 28 15 9 7,400
3 5 38 21 14 9,500
3 6 48 28 18 11,100
4 7 58 34 23 13,200
4 8 69 41 28 14,800
kVA/Watts/Ah # CABINETS # STRINGS 50% LOAD 75% LOAD 100 % LOAD Weight (lbs.)
EXTERNAL BATTERY
CABINET
BATTERY CABINET -
INTERNAL
STANDARD BATTERY
CHARACTERISTICS
Standard Battery
Valve Regulated Lead Acid (VRLA), Sealed Maintenance Free, CSB HR12200W specifically
designed for high efficient discharge applications. Its characteristics are high energy density,
small footprint and high discharge efficiency. Rated for more than 260 cycles at 100%
discharge, in cycle service, up to 10 years in standby service.
.
6 Cells per unit
12 volts per unit
200 Watt, 50Ah
Battery Voltage: 420 volts DC minimum before cutoff, 540 volts float.
Maximum DC Current: Maximum DC current at cutoff voltage:
80kVA -196 amperes ,100kVA – 236 amperes,125kVA – 296 amperes
FIRSTLINE P 4 X 4 BYPASS
MODELS
Part Number kVA Voltage Description
Dimensions
H” x W” x D”
Wt.
(lbs.)
FLU-P-65-MBPS 65 480-
480Y/277
3 Breaker External Line Up &
Match Maintenance Bypass,
Top Cable Entry & Interlocks
75 x 15.75 x 33.35 250
FLU-P-80-MBPS 80 480-
480Y/277
3 Breaker External Line Up &
Match Maintenance Bypass,
Top Cable Entry & Interlocks
75 x 15.75 x 33.35 250
FLU-P-100-MBPS 100 480-
480Y/277
3 Breaker External Line Up &
Match Maintenance Bypass,
Top Cable Entry & Interlocks
75 x 15.75 x 33.35 250
FLU-P-125-MBPS 125 480-
480Y/277
3 Breaker External Line Up &
Match Maintenance Bypass,
Top Cable Entry & Interlocks
75 x 15.75 x 33.35 250
FLU-P-160-MBPS 160 480-
480Y/277
3 Breaker External Line Up &
Match Maintenance Bypass,
Top Cable Entry & Interlocks
75 x 30 x 33.5 350
FLU-P-200-MBPS 200 480-
480Y/277
3 Breaker External Line Up &
Match Maintenance Bypass,
Top Cable Entry & Interlocks
75 x 30 x 33.5 350
FLU-P-250-MBPS 250 480-
480Y/277
3 Breaker External Line Up &
Match Maintenance Bypass,
Top Cable Entry & Interlocks
75 x 30 x 33.5 350
65 – 125KVA 4 X 4 - 3
BREAKER MBP CABINET
160 – 250KVA 4 X 4 - 3
BREAKER MBP CABINET
4 X 2 & 2 X 2 TRANSFORMER/
BYPASS CABINET
FIRSTLINE P TOP ENTRY
SIDE CAR MODEL
Part Number kVA Voltage Description
Dimensions
H” x W” x D” Wt. (lbs.)
FLU-CEC All 480
Top Cable Entry Side Car, allows
for top or side cable entry. 75 x 15.75 x 33.35 250
TOP ENTRY SIDE CAR
CABINET
FIRSTLINE P 2 X 2
TRANSFORMERLESS PDU
Part Number kVA
Output
Voltage Description
Dimensions
H” x W” x D”
FLU-PDC-P2 All 208V-
208Y/120
Transformerless Line Up &
Match Power Distribution
(PDU) with (2) 42 Pole, 225
Amp Panelboards, with
Mains and type Sq. D
NQ442L2. Accepts 1, 2 & 3
Pole Branch Circuit Breakers
bolt-on or plug-in.
75 x 22 x 33.35
TRANSFORMERLESS 2 X 2
PDU CABINET
SINGLE OR DUAL SOURCE
INPUT – NO BYPASS
Single Input Dual Input
SINGLE OR DUAL SOURCE
INPUT W/BYPASS
Single Input Dual Input
2 X 2 INPUT/OUTPUT
TRANSFORMERS W/BYPASS
208V OUTPUT
TRANSFORMERS W/BYPASS
PARALLELED SYSTEMS
PARALLELING
The UPS has expansion capabilities for up to 8 modules paralleled
for capacity or redundancy as required to support future growth. The
UPS units can be connected in parallel and shall share the current
and load between them.
In a system with several UPS units connected in parallel, there is a
single MASTER unit and the remaining units are SLAVE units. The
UPS units must be the same rating and the MASTER is chosen on
start-up. The MASTER and SLAVE units can exchange roles. If a
unit is being serviced, e.g. due to an inverter fault, it will
automatically be excluded. The load at this point will be shared
between the units that are still active; if the power in output is
excessive for the remaining UPSs, the system logic will switch all
the units, including the UPS that was excluded, onto the by-pass
line.
COMMUNICATION OPTIONS
PowerShield:
Communication Software provides efficient, user-friendly
UPS management using bar chart displays to show major
operational information such as the input voltage, UPS load
% and batteries charge %. The software also provides
detailed information on fault conditions and UPS operating
characteristics. PowerShield3 has been developed with a
client/server architecture that makes it flexible and easy to
use, and provides multi-lingual and on-line support.
Operating systems supported include Windows 2000,
2003Server, XP, Vista, 2008 Server, 7, Linux, Novell
Netware, Mac OS X and most common UNIX operating
systems such as: IBM AIX, HP, SUN Solaris INTEL and
SPARC, SCO Uniware and Open Server, Silcon Graphics
IRIX, Compaq Tru64 UNIX and DEC UNIX, Open BSD
UNIX and FreeBSD UNIX, NCR UMIX, HP Open VMS
VMWare ESX and VSPHERE.
POWERSHIELD
COMMUNICATION OPTIONS
PowerNETGuard:
Supervision software provides centralize UPS management
using network interface (SNMP) communications. It is ideal
for Data Centre managers and medium to large sized
networks. PowerNETGuard uses the RFC1628 standard
Management Information Base (MIB) and ensures
standardized UPS management wherever they are located.
Operating systems supported include Windows (98, ME, NT,
2000, 2003, XP and Vista), Kinux, MacOSX, Solaris 8, 9 and
10 and Silcon Grapics IRIX.
POWERNETGUARD
COMMUNICATION OPTIONS
Netman Plus:
Allows UPS management across a LAN using any of the main
network communication protocols - TCP/IP, HTTP and network
interface (SNMP). NetMan Plus enabled UPS integrate easily
into medium and large sized networks and provide reliable
communications between the UPS and management systems
employed.
NETMAN PLUS (LAN / WAN)
NETMAN PLUS (WAN)
COMMUNICATION OPTIONS
MultiCOM MODBUS/JBUS:
Protocol converter used to monitor the UPS using the MODBUS/JBUS
protocol on RS232 or RS485 serial lines. It can also manage a second
independent RS232 serial line that can be used to connect to other
devices such as the Netman or a PC using PowerShield software.
COMMUNICATION OPTIONS
MultiCOM Serial/USB:
Provide the UPS with an additional RS232 serial interface or
USB port. The USB port allows the UPS to communicate with
Apple Macintosh computers as well as Windows and Linux
operating systems.
COMMUNICATION OPTIONS
Multi I/O:
Protocol converter provides a configurable input and output
signal contacts to allow UPS integration with control
systems. It can be used to connect two devices to a single
UPS serial communication port. It can also communicate
using the MODBUS/JBUS protocol on RS485 lines.
COMMUNICATION OPTIONS
IBM AS/400 Communication Kit:
Provides a single-level memory management feature that makes it
compulsory for the system to be shutdown in a controlled and
orderly manner. Without UPS protection an AS/400 is not protected
from mains failures. A momentary loss of power can cause
hardware damage, data corruption and a lengthy reboot period.
COMMUNICATION OPTIONS
I/O Expansion Card:
Provides addition remote alarm functions as identified below. The card
contains 6 outputs: potential-free contacts for alarms (programmable from
the display panel) (and capable of switching up to 30 V AC or DC at UP 1
Amp) , 2 inputs (programmable from the panel) and 1 12V DC maximum
100mA auxiliary input. 2 additional slots shall be available for a total of 12
additional contacts.
•Disturbances on Bypass Line
•Manual Bypass ON
•Bypass Line Voltage Fail
•Main Line Voltage Fail
•Pre-alarm , Low Battery Voltage
•Low Input Voltage
•Output Overload
•Internal Fault
•Bypass for Output Overload
•Over Temperature or Fan Failure
•Input Voltage Sequence OK
•Output OFF
ENVIRONMENTAL SENSOR
OPTION
Netman Environmental Sensor:
Monitors and record environmental conditions as well as
activities in protected areas and at the premises where the
UPS is installed. Environmental sensors monitor and
record environmental conditions and activities within a
designated building area. The sensors provide extensive
management and control, triggering cooling fans and locks
in response to changes in temperature and humidity.
Remote monitoring and control can be provided via the
internet, SNMP and PowerShield software. NetMan Plus
can support up to 6 separate sensors. The environmental
sensors are easy to install and do not need a separate
external power supply.
REMOTE MONITOR PANEL
OPTION
MultiPanel - Remote Monitoring Panel:
Provides a detailed UPS status overview in real time. It is
compatible with all FirstLine P UPS’s and can display values for
UPS specific input and output supplies, and battery set
measurements. MultiPanel has a high-definition graphical display
and can report in 7 languages: English, Italian, German, French,
Spanish, Russian and Chinese.
3 independent serial ports are provided, one which allows for UPS
monitoring via the MODBUS/JBUS protocol (on either an RS485
or RS232 serial line). The others can be used with devices such as
the Netman Plus or a PC running PowerShield software.
OTHER OPTIONS
Seismic Bracing & Withstand Certification
Site specific Seismic Bracing for Zone A-F with certification and drawings available.
Top or Side Cable Entry
Standard cable entry is from the bottom with availability for top or
side incoming entry.
Harsh Environment Enclosure
The UPS and any accessory cabinet(s) are capability of being
mounted and completely wired internal to, include AC cooling, inside
any NEMA type enclosure (NEMA 12, 3R, 4X) by the manufacturer.
Spare Parts
Available in three levels - Minor, Moderate and Major
Service Agreements
Multi level service and maintenance agreements available.
AN ENGINEERS COMMENT:
“ I recently I had the pleasure to specify and install the Staco FirstLine
P UPS at one of my high-profile customers . Having been in sales &
service of UPS systems since 1977, it is rare that a real "gem" comes
along! When it comes to a UPS--I would consider this as a gem.”
Demps E. Bannerman, PhD., E.E.
SERVICE
o Services Tailored to our customers needs
o Five levels of service
o System startup to full on site support
o Local factory trained Technicians
o Spare parts kits, batteries monitoring and
replacement, site power quality survey,
infrared thermo scan and more.
START UP CHECK LIST:
PURPOSE: Work to cover during startup of all models of First Line Uninterruptible Power
Supplies.
INSTRUCTIONS:
o Check for physical damage to the system cabinets.
o Verify that all shipping covers, inserts, and brackets are removed as specified in the User’s
Handbook.
o Verify that the UPS is installed in a clean, temperature controlled area, and the environment
meets all criteria in the User’s Manual.
o Verify all internal connections and components are in the proper place and secure.
o Survey physical location of the system. (Accessibility, lighting, cleanliness, ventilation
o Survey additional customer equipment being present (TVSS, Generator, Motors, Capacitors,
and Transformers).
o Survey electrical Installation of UPS regarding wire size and circuit protection.
o Dual Source connections: In equipment’s with separate bypass line, an isolation transformer
must be placed at any of both input power supply mains of the UPS (rectifier input or static
bypass), in order to avoid the direct connection of the neutral of both mains through the
internal wiring of the equipment. This is only applicable power supply comes from two
different electrical mains, as for example: - Two different electrical companies. - One
electrical company and a generator set, ...
QUESTIONS?
Toll Free: 866.261.1191 | sales@stacoenergy.com | www.stacoenergy.com

More Related Content

What's hot

10 - Ac Power Regulators & Control Power Transformers - Fuji Electric
10 - Ac Power Regulators & Control Power Transformers - Fuji Electric10 - Ac Power Regulators & Control Power Transformers - Fuji Electric
10 - Ac Power Regulators & Control Power Transformers - Fuji ElectricCTY TNHH HẠO PHƯƠNG
 
Off grid solar inverter 10-120 kva (3:3)
Off grid solar inverter 10-120 kva (3:3)Off grid solar inverter 10-120 kva (3:3)
Off grid solar inverter 10-120 kva (3:3)Nasiru Bello
 
Tp series 1-6 k va
Tp series 1-6 k vaTp series 1-6 k va
Tp series 1-6 k vaelsy-ups
 
Stahl G053 Wireless Receiver Repeater EK00 III Data Sheet
Stahl G053 Wireless Receiver Repeater EK00 III Data SheetStahl G053 Wireless Receiver Repeater EK00 III Data Sheet
Stahl G053 Wireless Receiver Repeater EK00 III Data SheetThorne & Derrick International
 
Applied motion products stm datasheet
Applied motion products stm datasheetApplied motion products stm datasheet
Applied motion products stm datasheetElectromate
 
Lsvr lt step voltage regulator
Lsvr lt step voltage regulatorLsvr lt step voltage regulator
Lsvr lt step voltage regulatorJoeChueng
 
Datasheet-emdriveH300
Datasheet-emdriveH300Datasheet-emdriveH300
Datasheet-emdriveH300Martin Pec
 
Advanced motion controls sr60a40
Advanced motion controls sr60a40Advanced motion controls sr60a40
Advanced motion controls sr60a40Electromate
 
Advanced motion controls sr60a40ac
Advanced motion controls sr60a40acAdvanced motion controls sr60a40ac
Advanced motion controls sr60a40acElectromate
 
Datasheet-emdrive150
Datasheet-emdrive150Datasheet-emdrive150
Datasheet-emdrive150Martin Pec
 
Himalayal-AC-Resonant-Test-System
Himalayal-AC-Resonant-Test-SystemHimalayal-AC-Resonant-Test-System
Himalayal-AC-Resonant-Test-SystemFang Sam
 
TMEIC MVG 2 Medium Voltage Drive up to 19,500 KVA at 11 kv
TMEIC MVG 2 Medium Voltage Drive up to 19,500 KVA at 11 kvTMEIC MVG 2 Medium Voltage Drive up to 19,500 KVA at 11 kv
TMEIC MVG 2 Medium Voltage Drive up to 19,500 KVA at 11 kvDavid Batts
 
Advanced motion controls b25a20fac
Advanced motion controls b25a20facAdvanced motion controls b25a20fac
Advanced motion controls b25a20facElectromate
 

What's hot (20)

10 - Ac Power Regulators & Control Power Transformers - Fuji Electric
10 - Ac Power Regulators & Control Power Transformers - Fuji Electric10 - Ac Power Regulators & Control Power Transformers - Fuji Electric
10 - Ac Power Regulators & Control Power Transformers - Fuji Electric
 
Off grid solar inverter 10-120 kva (3:3)
Off grid solar inverter 10-120 kva (3:3)Off grid solar inverter 10-120 kva (3:3)
Off grid solar inverter 10-120 kva (3:3)
 
Tp series 1-6 k va
Tp series 1-6 k vaTp series 1-6 k va
Tp series 1-6 k va
 
Stahl G053 Wireless Receiver Repeater EK00 III Data Sheet
Stahl G053 Wireless Receiver Repeater EK00 III Data SheetStahl G053 Wireless Receiver Repeater EK00 III Data Sheet
Stahl G053 Wireless Receiver Repeater EK00 III Data Sheet
 
Contactores ABB
Contactores ABBContactores ABB
Contactores ABB
 
Applied motion products stm datasheet
Applied motion products stm datasheetApplied motion products stm datasheet
Applied motion products stm datasheet
 
sujesh
sujeshsujesh
sujesh
 
Lsvr lt step voltage regulator
Lsvr lt step voltage regulatorLsvr lt step voltage regulator
Lsvr lt step voltage regulator
 
Smart act 1 English
Smart act 1 EnglishSmart act 1 English
Smart act 1 English
 
Datasheet-emdriveH300
Datasheet-emdriveH300Datasheet-emdriveH300
Datasheet-emdriveH300
 
Advanced motion controls sr60a40
Advanced motion controls sr60a40Advanced motion controls sr60a40
Advanced motion controls sr60a40
 
Advanced motion controls sr60a40ac
Advanced motion controls sr60a40acAdvanced motion controls sr60a40ac
Advanced motion controls sr60a40ac
 
Sqk33.00 autres fiches_en
Sqk33.00 autres fiches_enSqk33.00 autres fiches_en
Sqk33.00 autres fiches_en
 
Datasheet-emdrive150
Datasheet-emdrive150Datasheet-emdrive150
Datasheet-emdrive150
 
Sx460 avr newage_stamford
Sx460 avr newage_stamfordSx460 avr newage_stamford
Sx460 avr newage_stamford
 
Himalayal-AC-Resonant-Test-System
Himalayal-AC-Resonant-Test-SystemHimalayal-AC-Resonant-Test-System
Himalayal-AC-Resonant-Test-System
 
TMEIC MVG 2 Medium Voltage Drive up to 19,500 KVA at 11 kv
TMEIC MVG 2 Medium Voltage Drive up to 19,500 KVA at 11 kvTMEIC MVG 2 Medium Voltage Drive up to 19,500 KVA at 11 kv
TMEIC MVG 2 Medium Voltage Drive up to 19,500 KVA at 11 kv
 
Lm358
Lm358Lm358
Lm358
 
Datasheet lm358
Datasheet lm358Datasheet lm358
Datasheet lm358
 
Advanced motion controls b25a20fac
Advanced motion controls b25a20facAdvanced motion controls b25a20fac
Advanced motion controls b25a20fac
 

Viewers also liked

Product: UPS: UniStar V
Product: UPS: UniStar VProduct: UPS: UniStar V
Product: UPS: UniStar VStaco Energy
 
Revista derecho constitucional (derechos humanos y estados de excepción)
Revista derecho constitucional (derechos humanos y estados de excepción)Revista derecho constitucional (derechos humanos y estados de excepción)
Revista derecho constitucional (derechos humanos y estados de excepción)arlenis camacho
 
Evolucion historica de la criminologia
Evolucion historica de la criminologiaEvolucion historica de la criminologia
Evolucion historica de la criminologiaarlenis camacho
 
Ladies waterproof head scarf
Ladies waterproof head scarfLadies waterproof head scarf
Ladies waterproof head scarfshopkrysi47
 
Evolucion historica de la criminologia
Evolucion historica de la criminologiaEvolucion historica de la criminologia
Evolucion historica de la criminologiaarlenis camacho
 
Evolución histórica de la Criminología
Evolución histórica de la CriminologíaEvolución histórica de la Criminología
Evolución histórica de la CriminologíaAdelaida Tassoni
 
Product: UPS: FirstLine PL 924
Product: UPS: FirstLine PL 924Product: UPS: FirstLine PL 924
Product: UPS: FirstLine PL 924Staco Energy
 
Historia y evolución del automóvil.
Historia y evolución del automóvil.Historia y evolución del automóvil.
Historia y evolución del automóvil.Jenny Guzmàn
 
Product: Battery Monitoring: FirstLine BMS
Product: Battery Monitoring: FirstLine BMSProduct: Battery Monitoring: FirstLine BMS
Product: Battery Monitoring: FirstLine BMSStaco Energy
 
General: Power Problems
General: Power ProblemsGeneral: Power Problems
General: Power ProblemsStaco Energy
 
Product: UPS: FirstLine XD
Product: UPS: FirstLine XDProduct: UPS: FirstLine XD
Product: UPS: FirstLine XDStaco Energy
 
sqlmap - why (not how) it works?
sqlmap - why (not how) it works?sqlmap - why (not how) it works?
sqlmap - why (not how) it works?Miroslav Stampar
 
Product: UPS: UniStar SCLI924
Product: UPS: UniStar SCLI924Product: UPS: UniStar SCLI924
Product: UPS: UniStar SCLI924Staco Energy
 
Product: UPS: UniStar VP
Product: UPS: UniStar VPProduct: UPS: UniStar VP
Product: UPS: UniStar VPStaco Energy
 
Παρισινή Κομμούνα της Εμμανουέλας Κούκουρα
Παρισινή Κομμούνα της Εμμανουέλας ΚούκουραΠαρισινή Κομμούνα της Εμμανουέλας Κούκουρα
Παρισινή Κομμούνα της Εμμανουέλας ΚούκουραΑντιγόνη Κριπαροπούλου
 
Non-Esoteric XSS Tips & Tricks
Non-Esoteric XSS Tips & TricksNon-Esoteric XSS Tips & Tricks
Non-Esoteric XSS Tips & TricksMiroslav Stampar
 

Viewers also liked (18)

Product: UPS: UniStar V
Product: UPS: UniStar VProduct: UPS: UniStar V
Product: UPS: UniStar V
 
Revista derecho constitucional (derechos humanos y estados de excepción)
Revista derecho constitucional (derechos humanos y estados de excepción)Revista derecho constitucional (derechos humanos y estados de excepción)
Revista derecho constitucional (derechos humanos y estados de excepción)
 
Evolucion historica de la criminologia
Evolucion historica de la criminologiaEvolucion historica de la criminologia
Evolucion historica de la criminologia
 
Ladies waterproof head scarf
Ladies waterproof head scarfLadies waterproof head scarf
Ladies waterproof head scarf
 
Evolucion historica de la criminologia
Evolucion historica de la criminologiaEvolucion historica de la criminologia
Evolucion historica de la criminologia
 
COMANDOS DEL TECLADO
COMANDOS DEL TECLADOCOMANDOS DEL TECLADO
COMANDOS DEL TECLADO
 
Computador
ComputadorComputador
Computador
 
Evolución histórica de la Criminología
Evolución histórica de la CriminologíaEvolución histórica de la Criminología
Evolución histórica de la Criminología
 
Product: UPS: FirstLine PL 924
Product: UPS: FirstLine PL 924Product: UPS: FirstLine PL 924
Product: UPS: FirstLine PL 924
 
Historia y evolución del automóvil.
Historia y evolución del automóvil.Historia y evolución del automóvil.
Historia y evolución del automóvil.
 
Product: Battery Monitoring: FirstLine BMS
Product: Battery Monitoring: FirstLine BMSProduct: Battery Monitoring: FirstLine BMS
Product: Battery Monitoring: FirstLine BMS
 
General: Power Problems
General: Power ProblemsGeneral: Power Problems
General: Power Problems
 
Product: UPS: FirstLine XD
Product: UPS: FirstLine XDProduct: UPS: FirstLine XD
Product: UPS: FirstLine XD
 
sqlmap - why (not how) it works?
sqlmap - why (not how) it works?sqlmap - why (not how) it works?
sqlmap - why (not how) it works?
 
Product: UPS: UniStar SCLI924
Product: UPS: UniStar SCLI924Product: UPS: UniStar SCLI924
Product: UPS: UniStar SCLI924
 
Product: UPS: UniStar VP
Product: UPS: UniStar VPProduct: UPS: UniStar VP
Product: UPS: UniStar VP
 
Παρισινή Κομμούνα της Εμμανουέλας Κούκουρα
Παρισινή Κομμούνα της Εμμανουέλας ΚούκουραΠαρισινή Κομμούνα της Εμμανουέλας Κούκουρα
Παρισινή Κομμούνα της Εμμανουέλας Κούκουρα
 
Non-Esoteric XSS Tips & Tricks
Non-Esoteric XSS Tips & TricksNon-Esoteric XSS Tips & Tricks
Non-Esoteric XSS Tips & Tricks
 

Similar to Product: UPS: FirstLine P

Commercial UPS - Raptor Power Systems
Commercial UPS - Raptor Power SystemsCommercial UPS - Raptor Power Systems
Commercial UPS - Raptor Power SystemsRaptor Power Systems
 
Bộ lưu điện ups gtec chính hãng Italia
Bộ lưu điện ups gtec chính hãng ItaliaBộ lưu điện ups gtec chính hãng Italia
Bộ lưu điện ups gtec chính hãng ItaliaNgoSinh3
 
Advanced motion controls b100a400ac
Advanced motion controls b100a400acAdvanced motion controls b100a400ac
Advanced motion controls b100a400acElectromate
 
Advanced motion controls b060a400ac
Advanced motion controls b060a400acAdvanced motion controls b060a400ac
Advanced motion controls b060a400acElectromate
 
Advanced motion controls 100a25
Advanced motion controls 100a25Advanced motion controls 100a25
Advanced motion controls 100a25Electromate
 
Advanced motion controls b15a8
Advanced motion controls b15a8Advanced motion controls b15a8
Advanced motion controls b15a8Electromate
 
Advanced motion controls b25a20ac
Advanced motion controls b25a20acAdvanced motion controls b25a20ac
Advanced motion controls b25a20acElectromate
 
Advanced motion controls be25a20fac
Advanced motion controls be25a20facAdvanced motion controls be25a20fac
Advanced motion controls be25a20facElectromate
 
Advanced motion controls b40a20i
Advanced motion controls b40a20iAdvanced motion controls b40a20i
Advanced motion controls b40a20iElectromate
 
Sinopak Electric Catalogue
Sinopak Electric CatalogueSinopak Electric Catalogue
Sinopak Electric CatalogueDaniel Wu
 
Sinopak Electric Catalogue
Sinopak Electric CatalogueSinopak Electric Catalogue
Sinopak Electric CatalogueAshley Lin
 
Sinopak Electric Catalogue
Sinopak Electric CatalogueSinopak Electric Catalogue
Sinopak Electric CatalogueAshley Lin
 
Advanced motion controls ab125a200
Advanced motion controls ab125a200Advanced motion controls ab125a200
Advanced motion controls ab125a200Electromate
 
Advanced motion controls be40a20i
Advanced motion controls be40a20iAdvanced motion controls be40a20i
Advanced motion controls be40a20iElectromate
 
Advanced motion controls b25a20i
Advanced motion controls b25a20iAdvanced motion controls b25a20i
Advanced motion controls b25a20iElectromate
 
Advanced motion controls be40a20
Advanced motion controls be40a20Advanced motion controls be40a20
Advanced motion controls be40a20Electromate
 
Advanced motion controls 120a10
Advanced motion controls 120a10Advanced motion controls 120a10
Advanced motion controls 120a10Electromate
 
Advanced motion controls be25a20i
Advanced motion controls be25a20iAdvanced motion controls be25a20i
Advanced motion controls be25a20iElectromate
 
Advanced motion controls b30a8
Advanced motion controls b30a8Advanced motion controls b30a8
Advanced motion controls b30a8Electromate
 
Advanced motion controls ab250a060
Advanced motion controls ab250a060Advanced motion controls ab250a060
Advanced motion controls ab250a060Electromate
 

Similar to Product: UPS: FirstLine P (20)

Commercial UPS - Raptor Power Systems
Commercial UPS - Raptor Power SystemsCommercial UPS - Raptor Power Systems
Commercial UPS - Raptor Power Systems
 
Bộ lưu điện ups gtec chính hãng Italia
Bộ lưu điện ups gtec chính hãng ItaliaBộ lưu điện ups gtec chính hãng Italia
Bộ lưu điện ups gtec chính hãng Italia
 
Advanced motion controls b100a400ac
Advanced motion controls b100a400acAdvanced motion controls b100a400ac
Advanced motion controls b100a400ac
 
Advanced motion controls b060a400ac
Advanced motion controls b060a400acAdvanced motion controls b060a400ac
Advanced motion controls b060a400ac
 
Advanced motion controls 100a25
Advanced motion controls 100a25Advanced motion controls 100a25
Advanced motion controls 100a25
 
Advanced motion controls b15a8
Advanced motion controls b15a8Advanced motion controls b15a8
Advanced motion controls b15a8
 
Advanced motion controls b25a20ac
Advanced motion controls b25a20acAdvanced motion controls b25a20ac
Advanced motion controls b25a20ac
 
Advanced motion controls be25a20fac
Advanced motion controls be25a20facAdvanced motion controls be25a20fac
Advanced motion controls be25a20fac
 
Advanced motion controls b40a20i
Advanced motion controls b40a20iAdvanced motion controls b40a20i
Advanced motion controls b40a20i
 
Sinopak Electric Catalogue
Sinopak Electric CatalogueSinopak Electric Catalogue
Sinopak Electric Catalogue
 
Sinopak Electric Catalogue
Sinopak Electric CatalogueSinopak Electric Catalogue
Sinopak Electric Catalogue
 
Sinopak Electric Catalogue
Sinopak Electric CatalogueSinopak Electric Catalogue
Sinopak Electric Catalogue
 
Advanced motion controls ab125a200
Advanced motion controls ab125a200Advanced motion controls ab125a200
Advanced motion controls ab125a200
 
Advanced motion controls be40a20i
Advanced motion controls be40a20iAdvanced motion controls be40a20i
Advanced motion controls be40a20i
 
Advanced motion controls b25a20i
Advanced motion controls b25a20iAdvanced motion controls b25a20i
Advanced motion controls b25a20i
 
Advanced motion controls be40a20
Advanced motion controls be40a20Advanced motion controls be40a20
Advanced motion controls be40a20
 
Advanced motion controls 120a10
Advanced motion controls 120a10Advanced motion controls 120a10
Advanced motion controls 120a10
 
Advanced motion controls be25a20i
Advanced motion controls be25a20iAdvanced motion controls be25a20i
Advanced motion controls be25a20i
 
Advanced motion controls b30a8
Advanced motion controls b30a8Advanced motion controls b30a8
Advanced motion controls b30a8
 
Advanced motion controls ab250a060
Advanced motion controls ab250a060Advanced motion controls ab250a060
Advanced motion controls ab250a060
 

More from Staco Energy

FirstLine P: 300-500 kVA
FirstLine P: 300-500 kVAFirstLine P: 300-500 kVA
FirstLine P: 300-500 kVAStaco Energy
 
Staco Energy: Corporate Overview
Staco Energy: Corporate OverviewStaco Energy: Corporate Overview
Staco Energy: Corporate OverviewStaco Energy
 
Product: Power Factor & Harmonics: StacoSine: MGE filter presentation
Product: Power Factor & Harmonics: StacoSine: MGE filter presentationProduct: Power Factor & Harmonics: StacoSine: MGE filter presentation
Product: Power Factor & Harmonics: StacoSine: MGE filter presentationStaco Energy
 
Product: Power Factor & Harmonics: StacoSine: Harmonics
Product: Power Factor & Harmonics: StacoSine: HarmonicsProduct: Power Factor & Harmonics: StacoSine: Harmonics
Product: Power Factor & Harmonics: StacoSine: HarmonicsStaco Energy
 
General: Power Quality Presentation
General: Power Quality PresentationGeneral: Power Quality Presentation
General: Power Quality PresentationStaco Energy
 
Product: UPS: Different Types of UPS
Product: UPS: Different Types of UPSProduct: UPS: Different Types of UPS
Product: UPS: Different Types of UPSStaco Energy
 
Product: Power Factor Harmonics
Product: Power Factor HarmonicsProduct: Power Factor Harmonics
Product: Power Factor HarmonicsStaco Energy
 
Product: Power Factor & Harmonics: StacoVAR: Part Numbers
Product: Power Factor & Harmonics: StacoVAR: Part NumbersProduct: Power Factor & Harmonics: StacoVAR: Part Numbers
Product: Power Factor & Harmonics: StacoVAR: Part NumbersStaco Energy
 
Product: Power Factor & Harmonics: StacoVAR: Let's Discuss Power Factor Corre...
Product: Power Factor & Harmonics: StacoVAR: Let's Discuss Power Factor Corre...Product: Power Factor & Harmonics: StacoVAR: Let's Discuss Power Factor Corre...
Product: Power Factor & Harmonics: StacoVAR: Let's Discuss Power Factor Corre...Staco Energy
 
Product: Power Factor & Harmonics: StacoSine: Technical
Product: Power Factor & Harmonics: StacoSine: TechnicalProduct: Power Factor & Harmonics: StacoSine: Technical
Product: Power Factor & Harmonics: StacoSine: TechnicalStaco Energy
 
Company: Intro to Staco
Company: Intro to StacoCompany: Intro to Staco
Company: Intro to StacoStaco Energy
 
Company: Staco Solutions and Applications
Company: Staco Solutions and ApplicationsCompany: Staco Solutions and Applications
Company: Staco Solutions and ApplicationsStaco Energy
 

More from Staco Energy (13)

FirstLine PE
FirstLine PEFirstLine PE
FirstLine PE
 
FirstLine P: 300-500 kVA
FirstLine P: 300-500 kVAFirstLine P: 300-500 kVA
FirstLine P: 300-500 kVA
 
Staco Energy: Corporate Overview
Staco Energy: Corporate OverviewStaco Energy: Corporate Overview
Staco Energy: Corporate Overview
 
Product: Power Factor & Harmonics: StacoSine: MGE filter presentation
Product: Power Factor & Harmonics: StacoSine: MGE filter presentationProduct: Power Factor & Harmonics: StacoSine: MGE filter presentation
Product: Power Factor & Harmonics: StacoSine: MGE filter presentation
 
Product: Power Factor & Harmonics: StacoSine: Harmonics
Product: Power Factor & Harmonics: StacoSine: HarmonicsProduct: Power Factor & Harmonics: StacoSine: Harmonics
Product: Power Factor & Harmonics: StacoSine: Harmonics
 
General: Power Quality Presentation
General: Power Quality PresentationGeneral: Power Quality Presentation
General: Power Quality Presentation
 
Product: UPS: Different Types of UPS
Product: UPS: Different Types of UPSProduct: UPS: Different Types of UPS
Product: UPS: Different Types of UPS
 
Product: Power Factor Harmonics
Product: Power Factor HarmonicsProduct: Power Factor Harmonics
Product: Power Factor Harmonics
 
Product: Power Factor & Harmonics: StacoVAR: Part Numbers
Product: Power Factor & Harmonics: StacoVAR: Part NumbersProduct: Power Factor & Harmonics: StacoVAR: Part Numbers
Product: Power Factor & Harmonics: StacoVAR: Part Numbers
 
Product: Power Factor & Harmonics: StacoVAR: Let's Discuss Power Factor Corre...
Product: Power Factor & Harmonics: StacoVAR: Let's Discuss Power Factor Corre...Product: Power Factor & Harmonics: StacoVAR: Let's Discuss Power Factor Corre...
Product: Power Factor & Harmonics: StacoVAR: Let's Discuss Power Factor Corre...
 
Product: Power Factor & Harmonics: StacoSine: Technical
Product: Power Factor & Harmonics: StacoSine: TechnicalProduct: Power Factor & Harmonics: StacoSine: Technical
Product: Power Factor & Harmonics: StacoSine: Technical
 
Company: Intro to Staco
Company: Intro to StacoCompany: Intro to Staco
Company: Intro to Staco
 
Company: Staco Solutions and Applications
Company: Staco Solutions and ApplicationsCompany: Staco Solutions and Applications
Company: Staco Solutions and Applications
 

Recently uploaded

Banana Powder Manufacturing Plant Project Report 2024 Edition.pptx
Banana Powder Manufacturing Plant Project Report 2024 Edition.pptxBanana Powder Manufacturing Plant Project Report 2024 Edition.pptx
Banana Powder Manufacturing Plant Project Report 2024 Edition.pptxgeorgebrinton95
 
VIP Call Girl Jamshedpur Aashi 8250192130 Independent Escort Service Jamshedpur
VIP Call Girl Jamshedpur Aashi 8250192130 Independent Escort Service JamshedpurVIP Call Girl Jamshedpur Aashi 8250192130 Independent Escort Service Jamshedpur
VIP Call Girl Jamshedpur Aashi 8250192130 Independent Escort Service JamshedpurSuhani Kapoor
 
Catalogue ONG NUOC PPR DE NHAT .pdf
Catalogue ONG NUOC PPR DE NHAT      .pdfCatalogue ONG NUOC PPR DE NHAT      .pdf
Catalogue ONG NUOC PPR DE NHAT .pdfOrient Homes
 
2024 Numerator Consumer Study of Cannabis Usage
2024 Numerator Consumer Study of Cannabis Usage2024 Numerator Consumer Study of Cannabis Usage
2024 Numerator Consumer Study of Cannabis UsageNeil Kimberley
 
Call Girls In Radisson Blu Hotel New Delhi Paschim Vihar ❤️8860477959 Escorts...
Call Girls In Radisson Blu Hotel New Delhi Paschim Vihar ❤️8860477959 Escorts...Call Girls In Radisson Blu Hotel New Delhi Paschim Vihar ❤️8860477959 Escorts...
Call Girls In Radisson Blu Hotel New Delhi Paschim Vihar ❤️8860477959 Escorts...lizamodels9
 
(8264348440) 🔝 Call Girls In Keshav Puram 🔝 Delhi NCR
(8264348440) 🔝 Call Girls In Keshav Puram 🔝 Delhi NCR(8264348440) 🔝 Call Girls In Keshav Puram 🔝 Delhi NCR
(8264348440) 🔝 Call Girls In Keshav Puram 🔝 Delhi NCRsoniya singh
 
VIP Kolkata Call Girl Howrah 👉 8250192130 Available With Room
VIP Kolkata Call Girl Howrah 👉 8250192130  Available With RoomVIP Kolkata Call Girl Howrah 👉 8250192130  Available With Room
VIP Kolkata Call Girl Howrah 👉 8250192130 Available With Roomdivyansh0kumar0
 
Regression analysis: Simple Linear Regression Multiple Linear Regression
Regression analysis:  Simple Linear Regression Multiple Linear RegressionRegression analysis:  Simple Linear Regression Multiple Linear Regression
Regression analysis: Simple Linear Regression Multiple Linear RegressionRavindra Nath Shukla
 
Lean: From Theory to Practice — One City’s (and Library’s) Lean Story… Abridged
Lean: From Theory to Practice — One City’s (and Library’s) Lean Story… AbridgedLean: From Theory to Practice — One City’s (and Library’s) Lean Story… Abridged
Lean: From Theory to Practice — One City’s (and Library’s) Lean Story… AbridgedKaiNexus
 
Call Girls In Sikandarpur Gurgaon ❤️8860477959_Russian 100% Genuine Escorts I...
Call Girls In Sikandarpur Gurgaon ❤️8860477959_Russian 100% Genuine Escorts I...Call Girls In Sikandarpur Gurgaon ❤️8860477959_Russian 100% Genuine Escorts I...
Call Girls In Sikandarpur Gurgaon ❤️8860477959_Russian 100% Genuine Escorts I...lizamodels9
 
Lowrate Call Girls In Laxmi Nagar Delhi ❤️8860477959 Escorts 100% Genuine Ser...
Lowrate Call Girls In Laxmi Nagar Delhi ❤️8860477959 Escorts 100% Genuine Ser...Lowrate Call Girls In Laxmi Nagar Delhi ❤️8860477959 Escorts 100% Genuine Ser...
Lowrate Call Girls In Laxmi Nagar Delhi ❤️8860477959 Escorts 100% Genuine Ser...lizamodels9
 
Marketing Management Business Plan_My Sweet Creations
Marketing Management Business Plan_My Sweet CreationsMarketing Management Business Plan_My Sweet Creations
Marketing Management Business Plan_My Sweet Creationsnakalysalcedo61
 
Eni 2024 1Q Results - 24.04.24 business.
Eni 2024 1Q Results - 24.04.24 business.Eni 2024 1Q Results - 24.04.24 business.
Eni 2024 1Q Results - 24.04.24 business.Eni
 
Intro to BCG's Carbon Emissions Benchmark_vF.pdf
Intro to BCG's Carbon Emissions Benchmark_vF.pdfIntro to BCG's Carbon Emissions Benchmark_vF.pdf
Intro to BCG's Carbon Emissions Benchmark_vF.pdfpollardmorgan
 
rishikeshgirls.in- Rishikesh call girl.pdf
rishikeshgirls.in- Rishikesh call girl.pdfrishikeshgirls.in- Rishikesh call girl.pdf
rishikeshgirls.in- Rishikesh call girl.pdfmuskan1121w
 
7.pdf This presentation captures many uses and the significance of the number...
7.pdf This presentation captures many uses and the significance of the number...7.pdf This presentation captures many uses and the significance of the number...
7.pdf This presentation captures many uses and the significance of the number...Paul Menig
 
0183760ssssssssssssssssssssssssssss00101011 (27).pdf
0183760ssssssssssssssssssssssssssss00101011 (27).pdf0183760ssssssssssssssssssssssssssss00101011 (27).pdf
0183760ssssssssssssssssssssssssssss00101011 (27).pdfRenandantas16
 
Cash Payment 9602870969 Escort Service in Udaipur Call Girls
Cash Payment 9602870969 Escort Service in Udaipur Call GirlsCash Payment 9602870969 Escort Service in Udaipur Call Girls
Cash Payment 9602870969 Escort Service in Udaipur Call GirlsApsara Of India
 
Vip Dewas Call Girls #9907093804 Contact Number Escorts Service Dewas
Vip Dewas Call Girls #9907093804 Contact Number Escorts Service DewasVip Dewas Call Girls #9907093804 Contact Number Escorts Service Dewas
Vip Dewas Call Girls #9907093804 Contact Number Escorts Service Dewasmakika9823
 

Recently uploaded (20)

Banana Powder Manufacturing Plant Project Report 2024 Edition.pptx
Banana Powder Manufacturing Plant Project Report 2024 Edition.pptxBanana Powder Manufacturing Plant Project Report 2024 Edition.pptx
Banana Powder Manufacturing Plant Project Report 2024 Edition.pptx
 
VIP Call Girl Jamshedpur Aashi 8250192130 Independent Escort Service Jamshedpur
VIP Call Girl Jamshedpur Aashi 8250192130 Independent Escort Service JamshedpurVIP Call Girl Jamshedpur Aashi 8250192130 Independent Escort Service Jamshedpur
VIP Call Girl Jamshedpur Aashi 8250192130 Independent Escort Service Jamshedpur
 
Catalogue ONG NUOC PPR DE NHAT .pdf
Catalogue ONG NUOC PPR DE NHAT      .pdfCatalogue ONG NUOC PPR DE NHAT      .pdf
Catalogue ONG NUOC PPR DE NHAT .pdf
 
2024 Numerator Consumer Study of Cannabis Usage
2024 Numerator Consumer Study of Cannabis Usage2024 Numerator Consumer Study of Cannabis Usage
2024 Numerator Consumer Study of Cannabis Usage
 
Call Girls In Radisson Blu Hotel New Delhi Paschim Vihar ❤️8860477959 Escorts...
Call Girls In Radisson Blu Hotel New Delhi Paschim Vihar ❤️8860477959 Escorts...Call Girls In Radisson Blu Hotel New Delhi Paschim Vihar ❤️8860477959 Escorts...
Call Girls In Radisson Blu Hotel New Delhi Paschim Vihar ❤️8860477959 Escorts...
 
(8264348440) 🔝 Call Girls In Keshav Puram 🔝 Delhi NCR
(8264348440) 🔝 Call Girls In Keshav Puram 🔝 Delhi NCR(8264348440) 🔝 Call Girls In Keshav Puram 🔝 Delhi NCR
(8264348440) 🔝 Call Girls In Keshav Puram 🔝 Delhi NCR
 
VIP Kolkata Call Girl Howrah 👉 8250192130 Available With Room
VIP Kolkata Call Girl Howrah 👉 8250192130  Available With RoomVIP Kolkata Call Girl Howrah 👉 8250192130  Available With Room
VIP Kolkata Call Girl Howrah 👉 8250192130 Available With Room
 
Regression analysis: Simple Linear Regression Multiple Linear Regression
Regression analysis:  Simple Linear Regression Multiple Linear RegressionRegression analysis:  Simple Linear Regression Multiple Linear Regression
Regression analysis: Simple Linear Regression Multiple Linear Regression
 
Lean: From Theory to Practice — One City’s (and Library’s) Lean Story… Abridged
Lean: From Theory to Practice — One City’s (and Library’s) Lean Story… AbridgedLean: From Theory to Practice — One City’s (and Library’s) Lean Story… Abridged
Lean: From Theory to Practice — One City’s (and Library’s) Lean Story… Abridged
 
Call Girls In Sikandarpur Gurgaon ❤️8860477959_Russian 100% Genuine Escorts I...
Call Girls In Sikandarpur Gurgaon ❤️8860477959_Russian 100% Genuine Escorts I...Call Girls In Sikandarpur Gurgaon ❤️8860477959_Russian 100% Genuine Escorts I...
Call Girls In Sikandarpur Gurgaon ❤️8860477959_Russian 100% Genuine Escorts I...
 
Lowrate Call Girls In Laxmi Nagar Delhi ❤️8860477959 Escorts 100% Genuine Ser...
Lowrate Call Girls In Laxmi Nagar Delhi ❤️8860477959 Escorts 100% Genuine Ser...Lowrate Call Girls In Laxmi Nagar Delhi ❤️8860477959 Escorts 100% Genuine Ser...
Lowrate Call Girls In Laxmi Nagar Delhi ❤️8860477959 Escorts 100% Genuine Ser...
 
KestrelPro Flyer Japan IT Week 2024 (English)
KestrelPro Flyer Japan IT Week 2024 (English)KestrelPro Flyer Japan IT Week 2024 (English)
KestrelPro Flyer Japan IT Week 2024 (English)
 
Marketing Management Business Plan_My Sweet Creations
Marketing Management Business Plan_My Sweet CreationsMarketing Management Business Plan_My Sweet Creations
Marketing Management Business Plan_My Sweet Creations
 
Eni 2024 1Q Results - 24.04.24 business.
Eni 2024 1Q Results - 24.04.24 business.Eni 2024 1Q Results - 24.04.24 business.
Eni 2024 1Q Results - 24.04.24 business.
 
Intro to BCG's Carbon Emissions Benchmark_vF.pdf
Intro to BCG's Carbon Emissions Benchmark_vF.pdfIntro to BCG's Carbon Emissions Benchmark_vF.pdf
Intro to BCG's Carbon Emissions Benchmark_vF.pdf
 
rishikeshgirls.in- Rishikesh call girl.pdf
rishikeshgirls.in- Rishikesh call girl.pdfrishikeshgirls.in- Rishikesh call girl.pdf
rishikeshgirls.in- Rishikesh call girl.pdf
 
7.pdf This presentation captures many uses and the significance of the number...
7.pdf This presentation captures many uses and the significance of the number...7.pdf This presentation captures many uses and the significance of the number...
7.pdf This presentation captures many uses and the significance of the number...
 
0183760ssssssssssssssssssssssssssss00101011 (27).pdf
0183760ssssssssssssssssssssssssssss00101011 (27).pdf0183760ssssssssssssssssssssssssssss00101011 (27).pdf
0183760ssssssssssssssssssssssssssss00101011 (27).pdf
 
Cash Payment 9602870969 Escort Service in Udaipur Call Girls
Cash Payment 9602870969 Escort Service in Udaipur Call GirlsCash Payment 9602870969 Escort Service in Udaipur Call Girls
Cash Payment 9602870969 Escort Service in Udaipur Call Girls
 
Vip Dewas Call Girls #9907093804 Contact Number Escorts Service Dewas
Vip Dewas Call Girls #9907093804 Contact Number Escorts Service DewasVip Dewas Call Girls #9907093804 Contact Number Escorts Service Dewas
Vip Dewas Call Girls #9907093804 Contact Number Escorts Service Dewas
 

Product: UPS: FirstLine P

  • 2. WHO IS STACO ENERGY PRODUCTS COMPANY ? Who are we? A 75+ year old privately held manufacturer of voltage control and power quality products. Based in Dayton Ohio with 80 employees. What do we do?? We provide tailored power solutions to targeted markets.
  • 3. HOW DO WE DO IT? – We partner with the best in every market • Rep’s, Distributors, Integrators, OEM’s – We focus on specific vertical applications / markets • WWT, Education, High Energy Physics, Process Manufacturing – We provide world class service and support • Over 60 Factory trained service tech’s in the US. – We manufacture the best products on the market • We back our products with the best warranties in the industry
  • 4. FIRSTLINE P 65kVA / 58.5kW 80kVA / 72kW 100kVA / 90kW 125kVA / 112.5kW 160kVA / 144kw 200kVA / 180kw 250kVA / 225kw
  • 5. FIRSTLINE P UPS • True double conversion, “On-Line” • Hot Swap Unit Capability • Digital Signal Process Control • Menu Selectable Monitoring Panel with Graphic display • Parallel up to 8 Modules • Dual Bus Configurations • Delayed Start Up on power source return • IGBT, PWM Inverter (Insulated Gate Bipolar Transistor) • Efficiency up to 98% • 0.99 High Input Power Factor • Configurable Power Walk-In • Sinusoidal Output Waveform
  • 6. MAJOR COMPONENTS • Rectifier complete with power factor correction • Fast Battery charger • Continuous duty rated Static Switch • Manual Maintenance Bypass • Input Isolation switch (SWIN) • Output Isolation switch (SWOUT) • Maintenance Isolation switch (SWMB) • Bypass Isolation switch (SWBY) • Parallel Kit (Standard) • 4 x 2 and 2 x 2 Voltage Configuration available
  • 7. AC INPUT CHARACTERISTICS Nominal Voltage: 480 VAC, 3 Phase, 4-wire (plus ground) or 208Y/120 VAC, 3 Phase, 4-wire + ground with external line up and match transformer cabinet (Optional) Nominal Voltage Range: +15/-10% from nominal voltage during battery recharge. Voltage Range on battery: +15% / -40% Frequency Range: 45 - 65 Hz) Power Factor: > 0.99 at full load, nominal conditions. Current Harmonic Distortion (THDi): < 3% Inrush current: Less than nominal input current for less than one cycle. Input Surge Protection: UPS shall be equipped to withstand surges per ANSI/IEEE C62.41. Rectifier Walk-in: Progressive from 0 to 30 seconds (adjustable). Rectifier Walk-in Delay Timer: Progressive start of rectifier from 0 to 120 seconds (adjustable).
  • 8. AC OUTPUT CHARACTERISTICS Voltage: 480Y/277 VAC, ± 1% steady state variation phase-to-phase voltage volts AC, three-phase, 4 wire plus ground (Standard Voltage) or 208Y/120 VAC, 3 Phase, 4-wire + ground - with external line up and match transformer cabinet (Optional). Frequency: 60Hz, + 2%, 60Hz, + .05% when free running. Voltage regulation: ±1% for balanced load, ±3% for 100% unbalanced load. Voltage Distortion: Maximum 2% total (THD). Voltage Transient (Step Load) Response: + 5% for 100% step load change. Voltage Recovery Time: Return to within 1% of nominal value within 20 milliseconds. Phase Angle Displacement: 120 degrees + 1 degree for balanced load; 120 degrees, + 1 degree for 100% unbalanced load. Non-Linear Load Capability: Output voltage total harmonic distortion shall be less than 2% when connected to a 100% non-linear load with a crest factor not to exceed 3%.
  • 9. AC OUTPUT CHARACTERISTICS (CONTINUED) Slew Rate: 1 hertz/second maximum. Power Factor: 0.9 at the rated volt amperes . Inverter Overload Capability: 110% of rated load for 60 minutes, 150% of rated load for 1 minute. Bypass Overload Capability: 110% for 60 minutes, 125% for 10 minutes,150% for 1 minute. Output Waveform: Sinusoidal Efficiency: (DC-AC): Minimum - 95% at Full Load, (AC-AC): Minimum – 93% at Full Load
  • 10. CABINET CONFIGURATION A. Control panel with graphic display B. Door handle C. Ventilation grilles D. Communication area E. Front Cover panel with ventilation grilles F. Switch cover panel G. Door 1. SWIN: Input isolating switch 2. SWOUT: Output isolating switch 3. SWMB: Maintenance isolating switch 4. WBY: Bypass isolating switch A B D C E 1 2 3 4 G G F
  • 11. CARD LOCATIONS A F G E D B C J N H I K A. Parallel Card B. EPO Control C. Remote Commands and Alarms D. RS-232-2 E. RS-232-1 F. Slot 2 (Aux) G. Slot 1 (Main) H. Remote Alarm Dry Contact Card 1 (Optional) I. Remote Alarm Dry Contact Card 2 (Optional) J. Multi I/O Card (Optional) K. Interface Terminal Connector L. UGS (Optional)
  • 12. BOTTOM CABLE ENTRY (STANDARD) Power Battery Cable Entry External Control Cable Entry Power AC Cable Entry REAR FRONT UPS Bottom View
  • 13. AIR FLOW (FORCED & CONVECTION) The heat dissipation needed for the correct operation of the UPS is brought about by the air current made by the fans located inside the UPS (forced convection) and by the air around the side panels (natural convection). Clearance: FRONT and at least one of the three side walls free: right, left or back.
  • 16. MENUS
  • 17. BASIC CONTROL FUNCTIONS o Output Voltage – Selects the rated output voltage o Operating Mode – Selects the operating Mode: On-Line, Stand-By ON, Smart Active o Auto Off – If bypass line is present and the load is < of the set value than the load will be supplied from the bypass line. If the bypass line in not preset and the load is < of the set value than the load will not be supply (configurable 0 to 99%). o Battery Low Warning – Estimated battery time remaining for low battery warning (configurable). o Battery Capacity – Sets the Amp Hour Battery installed. o Audible Alarm – Audible alarm operating mode: Enable/Disable o Language Select area – English, Italian, German, French, Spanish, Polish or Turkish.
  • 18. ADVANCED CONTROL FUNCTIONS o Input Frequency Tolerance Range – Selects the acceptable range for the input frequency for switching to the bypass and for the synchronization of the output: +/- 1 to +/- 6 in 1% stages. o Bypass Voltage Thresholds – Selects the acceptable voltage range for switching to the bypass: +/- 5 to +/- 25 in 1% stages. o Bypass Voltage Threshold for ECO – Selects the acceptable voltage range for operation in ECO Mode: +/- 5 to +/- 25 in 1% stages. o Switch-On Delay – Waiting time for automatic power-on after the return of power source voltage: Disable or configurable 1 to 255 in 1 second stages. o Power Walk-In – Activates the gradual return to power source mode: Activated or Deactivate o Power walk-In Duration – Sets the duration of the gradual return to power source voltage (only if Power Walk-In is activated: Minimum 0 seconds to maximum 125 seconds in 1 second stages. o Inverter Synchronization Speed to Bypass Line – Selects the synchronization speed of the inverter to the bypass line: 0.1 to 1 Hz/sec (parallel units), 0.1 to 3 Hz/sec (single units).
  • 19. ALARMS Normal Operation Disturbances on Bypass Line Manual Bypass (SWMB) On Bypass Line Volt, Failure Main Line Voltage Failure Pre-alarm, Low Battery Voltage Low Battery Charge or Closed Disconnect Low Input Voltage Output Overload Internal Fault Temporary Bypass, Wait Bypass for Output Overload Bypass Command ON or OFF Remote Bypass Command Active Over-temperature or Fan Failure Input Voltage Sequence not OK Output Off System Off Command ON or OFF Remote System Command ON or OFF Auto-shutdown Timer ON System Off Battery test ON Parallel Cable Fault Fuse Fault Battery Discharge Fail High Battery Temperature Slave UPS OFF Fan Fault Parallel Redundant Lost: High Unit Power Parallel Redundant Lost: Unit OFF Break Circuit Fail Break Circuit Overload Rectifier Switched Off by Remote Command UPS Service Required Battery Service Required Input Switch Off Insulation Loss-AC Insulation Loss-DC Over-temperature On Bypass Line Transfer Inverters Off
  • 20. FIRSTLINE P 65 – 125KVA UPS MODELS Model Number Description Dimensions H” x W” x D” Weight. (lbs.) 480V x 480V FLU-065-00 65kVA /58.5kW 480V/480Y/277, 50/60Hz 75 x 31.5 x 33.5 1,499 FLU-080-00 80kVA /72kW 480V/480Y/277, 50/60Hz 75 x 31.5 x 33.5 1,499 FLU-100-00 100kVA /90kW, 480V/480Y/277, 50/60Hz 75 x 31.5 x 33.5 1,609 FLU-125-00 125kVA /112.5kW, 480V/480Y/277, 50/60Hz 75 x 31.5 x 33.5 1,742
  • 21. FIRSTLINE P 160 – 250KVA UPS MODELS Model Number Description Dimensions H” x W” x D” Weight. (lbs.) 480V x 480V FLU-160-00 160kVA /144kW, 480V/480Y/277, 50/60Hz 75 x 39.5 x 33.5 1,984 FLU-160-T 160kVA /144kW, 480V/480Y/277, 50/60Hz w/ Internal Bypass 75 x 55 x 33.5 2,326 FLU-200-00 200kVA /180kW, 480V/480Y/277, 50/60Hz 75 x 39.5 x 33.5 2,205 FLU-200-T 200kVA /180kW, 480V/480Y/277, 50/60Hz w/ Internal Bypass 75 x 55 x 33.5 2,546 FLU-250-00 250kVA /225kW, 480V/480Y/277, 50/60Hz 75 x 39.5 x 33.5 2,425 FLU-250-T 250kVA /225kW, 480V/480Y/277, 50/60Hz w/ Internal Bypass 75 x 55 x 33.5 2,767
  • 22. FIRSTLINE P APPLICATION NOTES 1. The FLU-160-00, FLU-200-00 & FLU-250-00 units DO NOT have an internal bypass. If specification requires internal bypass the -T Model MUST be used. 2. In all cases, if the specification requires an internal and external bypass you MUST use the -T Model plus the Line Up & Match bypass cabinet.
  • 23. UPS CABINET 65 – 125KVA
  • 24. UPS CABINET 160 – 250KVA W/O BYPASS
  • 25. UPS CABINET 160 – 250KVA WITH BYPASS
  • 26. UPS CABINET - INTERNAL
  • 27. FIRSTLINE P WITH BATTERY CABINET The UPS uses a valve-regulated sealed lead acid (VRLA) heavy duty industrial battery, designed for auxiliary power service in a UPS application. The primary battery is furnished with impact-resistant plastic cases and housed in a matching cabinet(s) next to the UPS. The UPS is capable of utilizing Wet Cell & NiCad batteries. Protection Against Deep Discharge and Self-Discharge: The UPS is equipped with a device designed to protect the battery against deep discharge, depending on discharge conditions, with isolation of the battery by a circuit breaker. From the monitoring panel you can adjust the battery shutdown voltage as a function of a discharge coefficient to avoid excessive discharge at less than the rated output. A second device helps avoid self-discharge of the battery into the UPS control circuits during an extended shutdown of the UPS (over two hours). Battery Self-Tests: 1. The battery monitoring system performs the following automatic functions: • Battery circuit check, programmable 9-99 days. • Partial discharge test every three months.
  • 28. STANDARD EXTERNAL BATTERY MODELS Model Number Voltage # Cabinets Internal Strings Number Batteries Dimensions H” x W” x D” Weight (lbs.) FLU-BAT-200-1-480-B 480 1 1 40 75 x 26.3 x 38 2,307 FLU-BAT-200-2-480-B 480 1 2 80 75 x 26.3 x 38 3,932 FLU-BAT-300-2-480-B 480 1 2 80 75 x 26.3 x 38 3,923 The FLU-BAT-300-2-480-B is ONLY used with the 100kVA and 125kVA.The FLU-BAT-200-480-1-B can be used with a FLU-BAT-300-2-480-B
  • 29. FirstLine P Battery Back Up Times (Minutes) 65kVA 200W/50AH 1 1 26 14 8 2,100 1 2 66 39 26 3,700 2 3 107 66 46 5,800 2 4 149 93 66 7,400 3 5 190 121 86 9,500 3 6 229 149 107 11,100 4 7 266 171 128 13,200 4 8 301 204 149 14,800 80kVA 200W/50AH 1 2 38 30 19 3,700 2 3 84 51 35 5,800 2 4 118 73 51 7,400 3 5 152 95 67 9,500 3 6 185 118 84 11,100 4 7 217 141 101 13,200 4 8 248 163 118 14,800 100kVA 200W/50AH 1 2 38 21 14 3,700 2 3 64 38 25 5,800 2 4 90 55 38 7,400 3 5 118 73 51 9,500 3 6 145 90 64 11,100 4 7 172 109 77 13,200 4 8 198 127 90 14,800 125kVA 200W/50AH 1 2 30 16 10 3,700 2 3 51 30 20 5,800 2 4 73 44 30 7,400 3 5 95 58 40 9,500 3 6 118 73 50 11,100 4 7 141 88 62 13,200 4 8 164 103 73 14,800
  • 30. FIRSTLINE P BATTERY BACK UP TIMES (MINUTES) 160kVA 200W/50AH 2 3 35 19 12 5,800 2 4 51 30 19 7,400 3 5 67 40 27 9,500 3 6 84 51 35 11,100 4 7 101 61 43 13,200 4 8 118 73 51 14,800 200kVA 200W/50AH 2 3 25 14 8 5,800 2 4 38 21 14 7,400 3 5 51 30 19 9,500 3 6 64 38 25 11,100 4 7 77 46 32 13,200 4 8 90 55 38 14,800 250kVA 200W/50AH 2 4 28 15 9 7,400 3 5 38 21 14 9,500 3 6 48 28 18 11,100 4 7 58 34 23 13,200 4 8 69 41 28 14,800 kVA/Watts/Ah # CABINETS # STRINGS 50% LOAD 75% LOAD 100 % LOAD Weight (lbs.)
  • 33. STANDARD BATTERY CHARACTERISTICS Standard Battery Valve Regulated Lead Acid (VRLA), Sealed Maintenance Free, CSB HR12200W specifically designed for high efficient discharge applications. Its characteristics are high energy density, small footprint and high discharge efficiency. Rated for more than 260 cycles at 100% discharge, in cycle service, up to 10 years in standby service. . 6 Cells per unit 12 volts per unit 200 Watt, 50Ah Battery Voltage: 420 volts DC minimum before cutoff, 540 volts float. Maximum DC Current: Maximum DC current at cutoff voltage: 80kVA -196 amperes ,100kVA – 236 amperes,125kVA – 296 amperes
  • 34. FIRSTLINE P 4 X 4 BYPASS MODELS Part Number kVA Voltage Description Dimensions H” x W” x D” Wt. (lbs.) FLU-P-65-MBPS 65 480- 480Y/277 3 Breaker External Line Up & Match Maintenance Bypass, Top Cable Entry & Interlocks 75 x 15.75 x 33.35 250 FLU-P-80-MBPS 80 480- 480Y/277 3 Breaker External Line Up & Match Maintenance Bypass, Top Cable Entry & Interlocks 75 x 15.75 x 33.35 250 FLU-P-100-MBPS 100 480- 480Y/277 3 Breaker External Line Up & Match Maintenance Bypass, Top Cable Entry & Interlocks 75 x 15.75 x 33.35 250 FLU-P-125-MBPS 125 480- 480Y/277 3 Breaker External Line Up & Match Maintenance Bypass, Top Cable Entry & Interlocks 75 x 15.75 x 33.35 250 FLU-P-160-MBPS 160 480- 480Y/277 3 Breaker External Line Up & Match Maintenance Bypass, Top Cable Entry & Interlocks 75 x 30 x 33.5 350 FLU-P-200-MBPS 200 480- 480Y/277 3 Breaker External Line Up & Match Maintenance Bypass, Top Cable Entry & Interlocks 75 x 30 x 33.5 350 FLU-P-250-MBPS 250 480- 480Y/277 3 Breaker External Line Up & Match Maintenance Bypass, Top Cable Entry & Interlocks 75 x 30 x 33.5 350
  • 35. 65 – 125KVA 4 X 4 - 3 BREAKER MBP CABINET
  • 36. 160 – 250KVA 4 X 4 - 3 BREAKER MBP CABINET
  • 37. 4 X 2 & 2 X 2 TRANSFORMER/ BYPASS CABINET
  • 38. FIRSTLINE P TOP ENTRY SIDE CAR MODEL Part Number kVA Voltage Description Dimensions H” x W” x D” Wt. (lbs.) FLU-CEC All 480 Top Cable Entry Side Car, allows for top or side cable entry. 75 x 15.75 x 33.35 250
  • 39. TOP ENTRY SIDE CAR CABINET
  • 40. FIRSTLINE P 2 X 2 TRANSFORMERLESS PDU Part Number kVA Output Voltage Description Dimensions H” x W” x D” FLU-PDC-P2 All 208V- 208Y/120 Transformerless Line Up & Match Power Distribution (PDU) with (2) 42 Pole, 225 Amp Panelboards, with Mains and type Sq. D NQ442L2. Accepts 1, 2 & 3 Pole Branch Circuit Breakers bolt-on or plug-in. 75 x 22 x 33.35
  • 41. TRANSFORMERLESS 2 X 2 PDU CABINET
  • 42. SINGLE OR DUAL SOURCE INPUT – NO BYPASS Single Input Dual Input
  • 43. SINGLE OR DUAL SOURCE INPUT W/BYPASS Single Input Dual Input
  • 44. 2 X 2 INPUT/OUTPUT TRANSFORMERS W/BYPASS
  • 47. PARALLELING The UPS has expansion capabilities for up to 8 modules paralleled for capacity or redundancy as required to support future growth. The UPS units can be connected in parallel and shall share the current and load between them. In a system with several UPS units connected in parallel, there is a single MASTER unit and the remaining units are SLAVE units. The UPS units must be the same rating and the MASTER is chosen on start-up. The MASTER and SLAVE units can exchange roles. If a unit is being serviced, e.g. due to an inverter fault, it will automatically be excluded. The load at this point will be shared between the units that are still active; if the power in output is excessive for the remaining UPSs, the system logic will switch all the units, including the UPS that was excluded, onto the by-pass line.
  • 48. COMMUNICATION OPTIONS PowerShield: Communication Software provides efficient, user-friendly UPS management using bar chart displays to show major operational information such as the input voltage, UPS load % and batteries charge %. The software also provides detailed information on fault conditions and UPS operating characteristics. PowerShield3 has been developed with a client/server architecture that makes it flexible and easy to use, and provides multi-lingual and on-line support. Operating systems supported include Windows 2000, 2003Server, XP, Vista, 2008 Server, 7, Linux, Novell Netware, Mac OS X and most common UNIX operating systems such as: IBM AIX, HP, SUN Solaris INTEL and SPARC, SCO Uniware and Open Server, Silcon Graphics IRIX, Compaq Tru64 UNIX and DEC UNIX, Open BSD UNIX and FreeBSD UNIX, NCR UMIX, HP Open VMS VMWare ESX and VSPHERE.
  • 50. COMMUNICATION OPTIONS PowerNETGuard: Supervision software provides centralize UPS management using network interface (SNMP) communications. It is ideal for Data Centre managers and medium to large sized networks. PowerNETGuard uses the RFC1628 standard Management Information Base (MIB) and ensures standardized UPS management wherever they are located. Operating systems supported include Windows (98, ME, NT, 2000, 2003, XP and Vista), Kinux, MacOSX, Solaris 8, 9 and 10 and Silcon Grapics IRIX.
  • 52. COMMUNICATION OPTIONS Netman Plus: Allows UPS management across a LAN using any of the main network communication protocols - TCP/IP, HTTP and network interface (SNMP). NetMan Plus enabled UPS integrate easily into medium and large sized networks and provide reliable communications between the UPS and management systems employed.
  • 55. COMMUNICATION OPTIONS MultiCOM MODBUS/JBUS: Protocol converter used to monitor the UPS using the MODBUS/JBUS protocol on RS232 or RS485 serial lines. It can also manage a second independent RS232 serial line that can be used to connect to other devices such as the Netman or a PC using PowerShield software.
  • 56. COMMUNICATION OPTIONS MultiCOM Serial/USB: Provide the UPS with an additional RS232 serial interface or USB port. The USB port allows the UPS to communicate with Apple Macintosh computers as well as Windows and Linux operating systems.
  • 57. COMMUNICATION OPTIONS Multi I/O: Protocol converter provides a configurable input and output signal contacts to allow UPS integration with control systems. It can be used to connect two devices to a single UPS serial communication port. It can also communicate using the MODBUS/JBUS protocol on RS485 lines.
  • 58. COMMUNICATION OPTIONS IBM AS/400 Communication Kit: Provides a single-level memory management feature that makes it compulsory for the system to be shutdown in a controlled and orderly manner. Without UPS protection an AS/400 is not protected from mains failures. A momentary loss of power can cause hardware damage, data corruption and a lengthy reboot period.
  • 59. COMMUNICATION OPTIONS I/O Expansion Card: Provides addition remote alarm functions as identified below. The card contains 6 outputs: potential-free contacts for alarms (programmable from the display panel) (and capable of switching up to 30 V AC or DC at UP 1 Amp) , 2 inputs (programmable from the panel) and 1 12V DC maximum 100mA auxiliary input. 2 additional slots shall be available for a total of 12 additional contacts. •Disturbances on Bypass Line •Manual Bypass ON •Bypass Line Voltage Fail •Main Line Voltage Fail •Pre-alarm , Low Battery Voltage •Low Input Voltage •Output Overload •Internal Fault •Bypass for Output Overload •Over Temperature or Fan Failure •Input Voltage Sequence OK •Output OFF
  • 60. ENVIRONMENTAL SENSOR OPTION Netman Environmental Sensor: Monitors and record environmental conditions as well as activities in protected areas and at the premises where the UPS is installed. Environmental sensors monitor and record environmental conditions and activities within a designated building area. The sensors provide extensive management and control, triggering cooling fans and locks in response to changes in temperature and humidity. Remote monitoring and control can be provided via the internet, SNMP and PowerShield software. NetMan Plus can support up to 6 separate sensors. The environmental sensors are easy to install and do not need a separate external power supply.
  • 61. REMOTE MONITOR PANEL OPTION MultiPanel - Remote Monitoring Panel: Provides a detailed UPS status overview in real time. It is compatible with all FirstLine P UPS’s and can display values for UPS specific input and output supplies, and battery set measurements. MultiPanel has a high-definition graphical display and can report in 7 languages: English, Italian, German, French, Spanish, Russian and Chinese. 3 independent serial ports are provided, one which allows for UPS monitoring via the MODBUS/JBUS protocol (on either an RS485 or RS232 serial line). The others can be used with devices such as the Netman Plus or a PC running PowerShield software.
  • 62. OTHER OPTIONS Seismic Bracing & Withstand Certification Site specific Seismic Bracing for Zone A-F with certification and drawings available. Top or Side Cable Entry Standard cable entry is from the bottom with availability for top or side incoming entry. Harsh Environment Enclosure The UPS and any accessory cabinet(s) are capability of being mounted and completely wired internal to, include AC cooling, inside any NEMA type enclosure (NEMA 12, 3R, 4X) by the manufacturer. Spare Parts Available in three levels - Minor, Moderate and Major Service Agreements Multi level service and maintenance agreements available.
  • 63. AN ENGINEERS COMMENT: “ I recently I had the pleasure to specify and install the Staco FirstLine P UPS at one of my high-profile customers . Having been in sales & service of UPS systems since 1977, it is rare that a real "gem" comes along! When it comes to a UPS--I would consider this as a gem.” Demps E. Bannerman, PhD., E.E.
  • 64. SERVICE o Services Tailored to our customers needs o Five levels of service o System startup to full on site support o Local factory trained Technicians o Spare parts kits, batteries monitoring and replacement, site power quality survey, infrared thermo scan and more.
  • 65. START UP CHECK LIST: PURPOSE: Work to cover during startup of all models of First Line Uninterruptible Power Supplies. INSTRUCTIONS: o Check for physical damage to the system cabinets. o Verify that all shipping covers, inserts, and brackets are removed as specified in the User’s Handbook. o Verify that the UPS is installed in a clean, temperature controlled area, and the environment meets all criteria in the User’s Manual. o Verify all internal connections and components are in the proper place and secure. o Survey physical location of the system. (Accessibility, lighting, cleanliness, ventilation o Survey additional customer equipment being present (TVSS, Generator, Motors, Capacitors, and Transformers). o Survey electrical Installation of UPS regarding wire size and circuit protection. o Dual Source connections: In equipment’s with separate bypass line, an isolation transformer must be placed at any of both input power supply mains of the UPS (rectifier input or static bypass), in order to avoid the direct connection of the neutral of both mains through the internal wiring of the equipment. This is only applicable power supply comes from two different electrical mains, as for example: - Two different electrical companies. - One electrical company and a generator set, ...
  • 66. QUESTIONS? Toll Free: 866.261.1191 | sales@stacoenergy.com | www.stacoenergy.com