SlideShare a Scribd company logo
1 of 24
Unit IV: Protection and Coordination
The objective of Distribution System Protection:
The main objectives of distribution system protection are:
I. To minimize the duration of a fault
II. To minimize the number of consumers affected by the fault
The secondary objectives of distribution system protection are:
I. To eliminate safety hazards as fast as possible
II. To limit service outages to the smallest possible segment of the system
III.To protect the consumers’ apparatus
IV.To protect the system from unnecessary service interruptions and disturbances
V. To disconnect faulted lines, transformers, or other apparatus.
Unit IV: Protection and Coordination
Overhead distribution systems are subject to two types of electrical faults,
• namely, transient (or temporary) faults and permanent faults.
Depending on the nature of the system involved, approximately 75‐90% of the total number of
faults are temporary in nature.
• Usually, transient faults occur when phase conductors electrically contact other phase
conductors or ground momentarily due to trees, birds, or other animals, high winds, lightning,
flashovers, and so on.
• Transient faults are cleared by a service interruption of a sufficient length of time to extinguish
the power arc.
• The fault duration is minimized and unnecessary fuse blowing is prevented by using
instantaneous or high‐speed tripping and automatic reclosing of a relay‐controlled power CB or
the automatic tripping and reclosing of a circuit recloser.
• The breaker speed, relay settings, and recloser characteristics are selected in a manner to
interrupt the fault current before a series fuse (i.e. the nearest source‐side fuse) is blown, which
would cause the transient fault to become permanent.
Permanent faults are those which require repairs by a repair crew in terms of
I. Replacing burned‐down conductors, blown fuses, or any other damaged apparatus
II. Removing tree limbs from line
III. Manually reclosing a circuit breaker or recloser to restore service
• The number of customers affected by a fault is minimized by properly selecting and locating
the protective apparatus on the feeder main, at the tap point of each branch, and at critical
locations on branch circuits.
• Permanent faults are cleared by fuse cutouts installed at sub-main and lateral tap points.
• This practice limits the number of customers affected by a permanent fault and helps locate the
fault point by reducing the area involved.
• In general, the only part of the distribution circuit not protected by fuses is the main feeder and
feeder tie line.
• The substation is protected from faults on feeder and tie lines by CBs and/or reclosers located
inside the substation.
• Most of the faults are permanent on an underground distribution system, thereby requiring a
different protection approach.
• Although the number of faults occurring on an underground system is relatively much less than
that on the overhead systems, they are usually permanent and can affect a larger number of
customers.
• Faults occurring in the underground residential distribution (URD) systems are cleared by the
blowing of the nearest sectionalizing fuse or fuses.
• Faults occurring on the feeder are cleared by tripping and lockout of the feeder breaker
Equipment
A wide variety of equipment is used to protect distribution networks.
The particular type of protection used depends on the system element being protected and the
system voltage level, and, even though there are no specific standards for the overall protection of
distribution networks, some general indication of how these systems work can be made.
The devices most used for distribution system protection are:
I. Overcurrent Relays
II. Reclosers
III. Sectionalizers
IV. Fuses
It is an overcurrent device with a circuit opening ability when directly heated and gets destroyed
by the flowing over current through it in the event of an overload or short-circuit conditions.
Therefore, the purpose of the fuse is to isolate the failure line or segment from the system
The fuse element is generally made of a material having a low melting point, high
conductivity, and least deterioration due to oxidation e.g.., silver, copper, etc.
• It is inserted in series with the circuit to be protected. Under normal operating conditions, the
fuse element is at a temperature below its melting point.
• Therefore, it carries the normal current without overheating.
• However, when a short circuit or overload occurs, the current flowing through the fuse will
increase beyond its rated value.
• This raises the temperature and fuses element melts, disconnecting the circuit protected by it.
• The time required to blow out the fuse depends upon the magnitude of excessive current.
• The greater the current, the smaller the time taken by the fuse to blow out
Fuse
The advantages of the fuse are:
• The cheapest form of protection available
• Requires no maintenance
• Break heavy short-circuit current without noise or smoke
• The minimum time of operation can be made much shorter than that of the CB
Advantages
The disadvantages of the fuse are:
• Considerable time is required in removing or replacing a fuse after the operation
• The TCC of a fuse cannot always be correlated with that of the protected apparatus.
Disadvantages
• It is an overcurrent protective device that automatically trips and reclosed a number of times to
clear temporary faults or isolate permanent faults.
• About 90% of faults on overhead distribution lines are of temporary nature and caused by
lightning or by-passing of objects near or through lines(birds, vines, tree branches, etc) or
touching of conductors.
• These conditions result in arcing faults and the arc in the air faults can be extinguished by de-
energizing the system by simultaneous opening of CBs on both ends of the feeder or one end of
the feeder.
• After a short time called dead time, the CBs can be reclosed as soon as the arc in fault has been
extinguished and the path has regained its dielectric strength.
• In distribution systems, a multishot auto-reclosing feature is generally provided.
Automatic Circuit Recloser
https://www.youtube.com/watch?v=PwkP1V8okjE
The auto-reclosers controlling the primary feeder perform two, three, or four reclosing
cycles(shot) if necessary
• If the temporary fault has vanished during the dead time, the auto-recloser remains closed.
• If the fault persists after the first/second recloser one more enclosing is attempted.
• If the fault persists after the third/final recloser, the auto-recloser is opened and locked.
With auto-reclosing breakers in primary feeders, the circuit continuity during temporary faults is
improved.
Auto–reclosing is generally not adopted for underground cables. The faults on cables are
generally not temporary
Automatic Circuit Recloser
ADVANTAGES
• It can perform the tasks that can be fulfilled by the combination of a CB, overcurrent relay, and
reclosing relay
• It is light in weight and maintenance-free
• When a permanent fault occurs near the end of the lengthy feeder, then this feeder can be
sectionalized using auto-recloser so as to reduce the outages
DISADVANTAGES
• It cannot clear the permanent faults completely
• It is costlier than the CB
• It is not suitable for cables as the breakdown of insulation in cables causes a permanent outage.
Automatic Circuit Recloser
AUTOMATIC LINE SECTIONALIZER
It is the overcurrent protective devices installed only with backup CBs or auto-reclosing CB.
• It is a no-load switching device that is provided with overcurrent relays, earth fault relays, and
counters.
• The counter counts the number of operations of the backup CB/auto-recloser.
• After a predetermined number of backup CB/auto-recloser, if the CB/auto-recloser open has not
cleared the line fault, the CB/autorecloser opens and thereafter the automatic sectionalizer opens
under no current condition
The operating modes of automatic sectionalizers are as follows:
• If the fault on the distribution line is temporary and is cleared while the autorecloser is open, the
connector of the sectionalizer is reset automatically to its normal position after autorecloser is
closed, and the fault current counter in the sectionalizer will prepare for counting of the next
opening of the auto-recloser
• If the autorecloser is set to lockout on the fourth opening operation, the automation sectionalizer
will be set to trip during the open circuit time following the third tripping operation of the auto-
recloser
AUTOMATIC LINE SECTIONALIZER
Application aspects of automation sectionalizer
Several aspects must be considered to finalize the scheme:
• It must be used in series with auto-reclosers
• It must not be located between two auto-reclosers
• With two or three sectionalizes after one auto-recloser, the sequence must be coordinate
• The minimum fault current has to be more than the minimum fault current at the end of the line
section controlled by the sectionalizer
• Under no circumstances the short time circuit current and momentary peak current at the
location of the sectionalizer should be less than the respective ratings of the sectionalizer
ADVANTAGES
(i) Automatic sectionalizer is cheaper and required less maintenance than auto-reclosers
(ii) They may be employed for interrupting or switching loads within their rating
The main drawback is that the failure rate is in general greater than that of fuse
CIRCUIT BREAKER
A circuit breaker is a switch that opens and cuts off the flow of current when the current exceeds a
certain level. CBs are placed at critical points in circuits to protect against damage that could
result from excessive current flow, which is typically caused by component failure
• High voltage CBs are intended for making HV circuits and for breaking load currents and short-
circuit currents.
• The circuit breakers must have adequate MVA breaking capacity, the shortest possible total
break time, and be highly reliable in service and operation.
• HV circuit breakers must be explosion-proof and fireproof, and weigh as their duty will permit.
• The function of C.B is to isolate the faulty part of the power systems network from that of a
healthy part under abnormal conditions.
• These abnormal conditions will be sensed as a trip signal to the CB after receiving a trip signal
from the relay, the fault part will be isolated from the power system.
• A CB can be operated manually by remote control or automatically.
• The automatic operating phenomena can be observed only under fault conditions.
NECESSITY OF COORDINATION
Time-current characteristics (TCC) of overcurrent protective devices in the distribution system are
selected and set such that the protective devices operate in desired pre-set time sequence in the
event of a fault. This is called protection coordination.
• When two protective apparatus installed in series have the same/different characteristics, which
provide a pre-set initially to isolate the fault is defined as the protective device. It is usually the
apparatus, which will be nearer to the fault.
• The apparatus, which furnishes backup protection but operates only when the protecting device
fails to operate to clear the fault, is defined as the protected device. It is usually the apparatus,
which will be far away from the fault.
OBJECTIVES OF CO-ORDINATION
The main objectives of properly co-ordinate protective devices are:
• Minimize the extent of faults in order to reduce the number of customers affected
• Minimize the service interruptions due to temporary faults
• Minimize the duration of service outages to identify the location of the fault
PROCEDURE OF CO-ORDINATION
Salient points of co-ordination procedure
(i) Draw the diagram of the distribution system indicating the location of overcurrent relays, fuses, auto-
reclosers etc.
(ii) Determine the following
• Steady state short-circuit current
• Asymmetrical peak short-circuit current
• Normal load current
• Minimum short-circuit current at the above locations
(iii) Co-ordinate protective devices starting from the substation outward or from the end of the distribution
feeder back to the substation
(iv) Draw time current characteristics for the coordination
Generally, time current characteristics(TCC) curves of the protective devices are platted by
collecting the data from the manufacturer.
The values of load current and fault current are obtained from power flow study and fault flow
study
General coordination procedure:
The overcurrent protective devices i.e.., fuse, CB, recloser and line sectionalizer must be co-
ordinate for identifying and isolating the faults.
According to a specific operating sequence, the two overcurrent devices are said to be coordinated
or selected.
For all types of coordination the coordination procedure is the same and as follows:
1. Necessary and required data for coordination of protective devices should be collected
2. For a given distribution network, select the initial location of the protective device
3. Calculate the minimum and maximum value of fault current for various types of faults at
every selected location and at the end of the main feeder or lateral or sub-laterals
4. Choose the necessary protective devices located at the distribution substation in order to
protect the substation transformer properly from any type of faults that occurs in the
distribution system
5. The overcurrent protective devices should be coordinated either from the substation onwards
or the end of the distribution system back to the substation
6. If necessary, reconsider and change the initial location of the protective device
7. Reconsider the selected protective device for current carrying capacity, interrupting capacity
and minimum pickup time
8. Draw the TCC curves showing the coordination of all protective devices used with the
common base voltage
9. Finally, draw the distribution network diagram which shows the minimum and maximum
value of fault current and also the rating of the various protection devices used.
TYPES OF COORDINATION
The different types of co-ordination methods are:
1. Fuse to fuse co-ordination
2. Auto –recloser to fuse co-ordination
3. Circuit breaker to fuse co-ordination
4. Circuit breaker to auto-recloser co-ordination
FUSE TO FUSE CO-ORDINATION
Fuse ‘A’ is called the protective fuse and fuse ‘B’
is called the protecting fuse are drawn single graph
as shown in fig for perfect coordination, fuse ‘B’
must melt and clear the fault before fuse ‘A’ is
damaged.
To ensure this, three things are required
(i)the maximum characteristics of the fuse B is
plotted
(ii)The minimum characteristics of fuse A is
plotted
(iii)75% of the minimum melting curve of A is
plotted to make sure that the fuse is not damaged
and to account for any degradation in the fuse
characteristics
If the damage curve of fuse A and the time clearance curve of fuse B never cross, then it is said to
be perfect protection. If they cross, at some value of current, then it is called the limit of
coordination. For example, suppose the curves cross at 200A. This means that coordination more
than 200A is unlikely.
However, if the maximum available short circuit current of the system at that location is only
150A the fuse would be considered to be fault co-ordinate.
AUTO-RECLOSER TO FUSE CO-ORDINATION
The time-current characteristics of auto-recloser (AR) in the main feeder circuit and fuse B
in the lateral is as shown in fig If the fault ‘F’ beyond the fuse B is temporary, the auto-
recloser ‘AR’ should clear it without blowing of fuse b
The time-current characteristics of the fuse B are in two parts: 1. Minimum melting time
versus fuse B current 2. First operating time versus fuse B current
AUTO-RECLOSER TO FUSE CO-ORDINATION
The above two curves of fuse B is co-ordinate with below two curves of tripping
characteristics of ‘AR’
1. Delayed auto-recloser opening characteristics
2. Instantaneous auto-recloser opening characteristics
3. If fault current is less than ‘M’ the closer operates with delayed opening time
If fault current is less than ‘N’ the auto–recloser operates with instantaneous operating
time.
Beyond current N, fuse B operates
Auto-recloser to fuse co-ordination for the complete auto-reclosing cycle takes into
account the heating of the fuse due to flow of short-circuit current time in the cycle
CIRCUIT BREAKER TO FUSE CO-ORDINATION
The circuit breaker is tripped by over-current phase fault protection. Total fault clearing time is
equal to the relay time plus circuit breaker time.’ When fuse ‘A’ is used as the main protection and
circuit breaker as a backup is shown in fig, the operating time is selected as 150% of the total
operating time of the fuse over current relays for phase to phase fault. Therefore fuse A operates
first and the circuit breaker operates next only if the fuse fails to operate.
If the circuit breaker provides the main protection and the fuse ‘A’ as a back up as shown in fig the
relays should operate instantaneously and the circuit breaker should isolate the fault before
blowing up the fuse. The minimum melting time of the fuse should be about 135% more than the
fault ‘clearing time’ of the circuit–breaker relay combination for phase to phase faults.
CIRCUIT BREAKER TO AUTO-RECLOSER CO-ORDINATION
The circuit breaker provides backup protection.
The auto-recloser has three principal opening characteristics
1. First and second opening operation ‘A’ for instantaneous opening characteristics
2. Third opening operation ‘B’ for delayed opening characteristics
3. Fourth opening operation ‘C’ for extended –delayed opening characteristic
The inverse time characteristics ‘D’ of over current relay and circuit breaker combination should
be above that of the three characteristics of auto-recloser as shown in fig

More Related Content

What's hot

Tripping and control of impulse generators
Tripping and control of impulse generatorsTripping and control of impulse generators
Tripping and control of impulse generators
Fariza Zahari
 
Power system protection
Power system protectionPower system protection
Power system protection
Anu Priya
 
SWITCHYARD EQUIPMENTS & PROTECTION SYSTEMS
SWITCHYARD EQUIPMENTS & PROTECTION SYSTEMSSWITCHYARD EQUIPMENTS & PROTECTION SYSTEMS
SWITCHYARD EQUIPMENTS & PROTECTION SYSTEMS
Partha Parida
 

What's hot (20)

Switchgear and protection lecture 1
Switchgear and protection lecture 1Switchgear and protection lecture 1
Switchgear and protection lecture 1
 
Tripping and control of impulse generators
Tripping and control of impulse generatorsTripping and control of impulse generators
Tripping and control of impulse generators
 
220 KV Substation Operation & Maintenance
220 KV Substation Operation & Maintenance220 KV Substation Operation & Maintenance
220 KV Substation Operation & Maintenance
 
Unit 03 Protective relays
Unit  03 Protective relaysUnit  03 Protective relays
Unit 03 Protective relays
 
Ppt on protection of power transformers
Ppt on protection of power transformersPpt on protection of power transformers
Ppt on protection of power transformers
 
Relays
RelaysRelays
Relays
 
Vacuum circuit breaker
Vacuum circuit breakerVacuum circuit breaker
Vacuum circuit breaker
 
Power system protection
Power system protectionPower system protection
Power system protection
 
instrument transformer
instrument transformerinstrument transformer
instrument transformer
 
24620708 feeder-protection (1)
24620708 feeder-protection (1)24620708 feeder-protection (1)
24620708 feeder-protection (1)
 
Generator Protection By - Er Rahul Sharma
Generator Protection By - Er Rahul Sharma Generator Protection By - Er Rahul Sharma
Generator Protection By - Er Rahul Sharma
 
Transformer protection
Transformer protectionTransformer protection
Transformer protection
 
relay-distance relay basics
relay-distance relay basicsrelay-distance relay basics
relay-distance relay basics
 
Power System Protection
Power System ProtectionPower System Protection
Power System Protection
 
Capacitive voltage transformer (1)
Capacitive voltage transformer (1)Capacitive voltage transformer (1)
Capacitive voltage transformer (1)
 
Transformer protection
Transformer protectionTransformer protection
Transformer protection
 
SWITCHYARD EQUIPMENTS & PROTECTION SYSTEMS
SWITCHYARD EQUIPMENTS & PROTECTION SYSTEMSSWITCHYARD EQUIPMENTS & PROTECTION SYSTEMS
SWITCHYARD EQUIPMENTS & PROTECTION SYSTEMS
 
Operation and maintenance of transformer
Operation and maintenance of transformerOperation and maintenance of transformer
Operation and maintenance of transformer
 
220kv substation
220kv substation220kv substation
220kv substation
 
Substation protection devices
Substation protection devicesSubstation protection devices
Substation protection devices
 

Similar to Unit IV.pptx

Switchgear and protection engineering Lecture 02.pptx
Switchgear and protection engineering Lecture 02.pptxSwitchgear and protection engineering Lecture 02.pptx
Switchgear and protection engineering Lecture 02.pptx
LoitaFredy
 
Transformer design and protection
Transformer design and protectionTransformer design and protection
Transformer design and protection
ashwin fcc
 
Selective Coordination "The Rest of the Story"
Selective Coordination "The Rest of the Story"Selective Coordination "The Rest of the Story"
Selective Coordination "The Rest of the Story"
michaeljmack
 

Similar to Unit IV.pptx (20)

Switchgear and protection engineering Lecture 02.pptx
Switchgear and protection engineering Lecture 02.pptxSwitchgear and protection engineering Lecture 02.pptx
Switchgear and protection engineering Lecture 02.pptx
 
Er rahul sharma feeder protection
Er rahul sharma feeder protectionEr rahul sharma feeder protection
Er rahul sharma feeder protection
 
errahulsharmafeederprotection-141017104620-conversion-gate02.pdf
errahulsharmafeederprotection-141017104620-conversion-gate02.pdferrahulsharmafeederprotection-141017104620-conversion-gate02.pdf
errahulsharmafeederprotection-141017104620-conversion-gate02.pdf
 
Introduction to switchgear
Introduction to switchgearIntroduction to switchgear
Introduction to switchgear
 
Protective device co ordination with etap
Protective device co ordination with etapProtective device co ordination with etap
Protective device co ordination with etap
 
SGP-4 PROTECTION OF ALTRNTR.pptx
SGP-4 PROTECTION OF ALTRNTR.pptxSGP-4 PROTECTION OF ALTRNTR.pptx
SGP-4 PROTECTION OF ALTRNTR.pptx
 
Circuit breaker
Circuit breakerCircuit breaker
Circuit breaker
 
Fuses_Lec_1.pptx
Fuses_Lec_1.pptxFuses_Lec_1.pptx
Fuses_Lec_1.pptx
 
Circuit breaker
Circuit breakerCircuit breaker
Circuit breaker
 
Unit 05 Protection of feeders and bus-bars
Unit  05 Protection of feeders and bus-bars Unit  05 Protection of feeders and bus-bars
Unit 05 Protection of feeders and bus-bars
 
Module 1 Power System Protection(18EE72).pptx
Module 1 Power System Protection(18EE72).pptxModule 1 Power System Protection(18EE72).pptx
Module 1 Power System Protection(18EE72).pptx
 
lecture1423723756.pdf
lecture1423723756.pdflecture1423723756.pdf
lecture1423723756.pdf
 
Transformer design and protection
Transformer design and protectionTransformer design and protection
Transformer design and protection
 
Components of LT Switchgear.pptx
Components of LT Switchgear.pptxComponents of LT Switchgear.pptx
Components of LT Switchgear.pptx
 
Generator and Transformer Protection (PART 2)
Generator and Transformer Protection (PART 2)Generator and Transformer Protection (PART 2)
Generator and Transformer Protection (PART 2)
 
Protection schemes and zones
Protection schemes and zonesProtection schemes and zones
Protection schemes and zones
 
Selective Coordination "The Rest of the Story"
Selective Coordination "The Rest of the Story"Selective Coordination "The Rest of the Story"
Selective Coordination "The Rest of the Story"
 
Vacuum circuit breaker selection of circuit breakers
Vacuum circuit breaker selection of circuit breakersVacuum circuit breaker selection of circuit breakers
Vacuum circuit breaker selection of circuit breakers
 
Busbar Blocking System
Busbar Blocking SystemBusbar Blocking System
Busbar Blocking System
 
transformerdesignandprotection-130408132534-phpapp02.ppt
transformerdesignandprotection-130408132534-phpapp02.ppttransformerdesignandprotection-130408132534-phpapp02.ppt
transformerdesignandprotection-130408132534-phpapp02.ppt
 

Recently uploaded

Hospital management system project report.pdf
Hospital management system project report.pdfHospital management system project report.pdf
Hospital management system project report.pdf
Kamal Acharya
 
Standard vs Custom Battery Packs - Decoding the Power Play
Standard vs Custom Battery Packs - Decoding the Power PlayStandard vs Custom Battery Packs - Decoding the Power Play
Standard vs Custom Battery Packs - Decoding the Power Play
Epec Engineered Technologies
 
Call Girls in South Ex (delhi) call me [🔝9953056974🔝] escort service 24X7
Call Girls in South Ex (delhi) call me [🔝9953056974🔝] escort service 24X7Call Girls in South Ex (delhi) call me [🔝9953056974🔝] escort service 24X7
Call Girls in South Ex (delhi) call me [🔝9953056974🔝] escort service 24X7
9953056974 Low Rate Call Girls In Saket, Delhi NCR
 
DeepFakes presentation : brief idea of DeepFakes
DeepFakes presentation : brief idea of DeepFakesDeepFakes presentation : brief idea of DeepFakes
DeepFakes presentation : brief idea of DeepFakes
MayuraD1
 

Recently uploaded (20)

HOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptx
HOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptxHOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptx
HOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptx
 
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
 
Hospital management system project report.pdf
Hospital management system project report.pdfHospital management system project report.pdf
Hospital management system project report.pdf
 
S1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptx
S1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptxS1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptx
S1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptx
 
Hostel management system project report..pdf
Hostel management system project report..pdfHostel management system project report..pdf
Hostel management system project report..pdf
 
Computer Networks Basics of Network Devices
Computer Networks  Basics of Network DevicesComputer Networks  Basics of Network Devices
Computer Networks Basics of Network Devices
 
PE 459 LECTURE 2- natural gas basic concepts and properties
PE 459 LECTURE 2- natural gas basic concepts and propertiesPE 459 LECTURE 2- natural gas basic concepts and properties
PE 459 LECTURE 2- natural gas basic concepts and properties
 
kiln thermal load.pptx kiln tgermal load
kiln thermal load.pptx kiln tgermal loadkiln thermal load.pptx kiln tgermal load
kiln thermal load.pptx kiln tgermal load
 
Standard vs Custom Battery Packs - Decoding the Power Play
Standard vs Custom Battery Packs - Decoding the Power PlayStandard vs Custom Battery Packs - Decoding the Power Play
Standard vs Custom Battery Packs - Decoding the Power Play
 
Call Girls in South Ex (delhi) call me [🔝9953056974🔝] escort service 24X7
Call Girls in South Ex (delhi) call me [🔝9953056974🔝] escort service 24X7Call Girls in South Ex (delhi) call me [🔝9953056974🔝] escort service 24X7
Call Girls in South Ex (delhi) call me [🔝9953056974🔝] escort service 24X7
 
Thermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - VThermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - V
 
COST-EFFETIVE and Energy Efficient BUILDINGS ptx
COST-EFFETIVE  and Energy Efficient BUILDINGS ptxCOST-EFFETIVE  and Energy Efficient BUILDINGS ptx
COST-EFFETIVE and Energy Efficient BUILDINGS ptx
 
DeepFakes presentation : brief idea of DeepFakes
DeepFakes presentation : brief idea of DeepFakesDeepFakes presentation : brief idea of DeepFakes
DeepFakes presentation : brief idea of DeepFakes
 
Engineering Drawing focus on projection of planes
Engineering Drawing focus on projection of planesEngineering Drawing focus on projection of planes
Engineering Drawing focus on projection of planes
 
Online food ordering system project report.pdf
Online food ordering system project report.pdfOnline food ordering system project report.pdf
Online food ordering system project report.pdf
 
Introduction to Serverless with AWS Lambda
Introduction to Serverless with AWS LambdaIntroduction to Serverless with AWS Lambda
Introduction to Serverless with AWS Lambda
 
Online electricity billing project report..pdf
Online electricity billing project report..pdfOnline electricity billing project report..pdf
Online electricity billing project report..pdf
 
Orlando’s Arnold Palmer Hospital Layout Strategy-1.pptx
Orlando’s Arnold Palmer Hospital Layout Strategy-1.pptxOrlando’s Arnold Palmer Hospital Layout Strategy-1.pptx
Orlando’s Arnold Palmer Hospital Layout Strategy-1.pptx
 
Moment Distribution Method For Btech Civil
Moment Distribution Method For Btech CivilMoment Distribution Method For Btech Civil
Moment Distribution Method For Btech Civil
 
Tamil Call Girls Bhayandar WhatsApp +91-9930687706, Best Service
Tamil Call Girls Bhayandar WhatsApp +91-9930687706, Best ServiceTamil Call Girls Bhayandar WhatsApp +91-9930687706, Best Service
Tamil Call Girls Bhayandar WhatsApp +91-9930687706, Best Service
 

Unit IV.pptx

  • 1. Unit IV: Protection and Coordination The objective of Distribution System Protection: The main objectives of distribution system protection are: I. To minimize the duration of a fault II. To minimize the number of consumers affected by the fault The secondary objectives of distribution system protection are: I. To eliminate safety hazards as fast as possible II. To limit service outages to the smallest possible segment of the system III.To protect the consumers’ apparatus IV.To protect the system from unnecessary service interruptions and disturbances V. To disconnect faulted lines, transformers, or other apparatus.
  • 2. Unit IV: Protection and Coordination Overhead distribution systems are subject to two types of electrical faults, • namely, transient (or temporary) faults and permanent faults. Depending on the nature of the system involved, approximately 75‐90% of the total number of faults are temporary in nature. • Usually, transient faults occur when phase conductors electrically contact other phase conductors or ground momentarily due to trees, birds, or other animals, high winds, lightning, flashovers, and so on. • Transient faults are cleared by a service interruption of a sufficient length of time to extinguish the power arc. • The fault duration is minimized and unnecessary fuse blowing is prevented by using instantaneous or high‐speed tripping and automatic reclosing of a relay‐controlled power CB or the automatic tripping and reclosing of a circuit recloser. • The breaker speed, relay settings, and recloser characteristics are selected in a manner to interrupt the fault current before a series fuse (i.e. the nearest source‐side fuse) is blown, which would cause the transient fault to become permanent.
  • 3. Permanent faults are those which require repairs by a repair crew in terms of I. Replacing burned‐down conductors, blown fuses, or any other damaged apparatus II. Removing tree limbs from line III. Manually reclosing a circuit breaker or recloser to restore service • The number of customers affected by a fault is minimized by properly selecting and locating the protective apparatus on the feeder main, at the tap point of each branch, and at critical locations on branch circuits. • Permanent faults are cleared by fuse cutouts installed at sub-main and lateral tap points. • This practice limits the number of customers affected by a permanent fault and helps locate the fault point by reducing the area involved. • In general, the only part of the distribution circuit not protected by fuses is the main feeder and feeder tie line.
  • 4. • The substation is protected from faults on feeder and tie lines by CBs and/or reclosers located inside the substation. • Most of the faults are permanent on an underground distribution system, thereby requiring a different protection approach. • Although the number of faults occurring on an underground system is relatively much less than that on the overhead systems, they are usually permanent and can affect a larger number of customers. • Faults occurring in the underground residential distribution (URD) systems are cleared by the blowing of the nearest sectionalizing fuse or fuses. • Faults occurring on the feeder are cleared by tripping and lockout of the feeder breaker
  • 5. Equipment A wide variety of equipment is used to protect distribution networks. The particular type of protection used depends on the system element being protected and the system voltage level, and, even though there are no specific standards for the overall protection of distribution networks, some general indication of how these systems work can be made. The devices most used for distribution system protection are: I. Overcurrent Relays II. Reclosers III. Sectionalizers IV. Fuses
  • 6. It is an overcurrent device with a circuit opening ability when directly heated and gets destroyed by the flowing over current through it in the event of an overload or short-circuit conditions. Therefore, the purpose of the fuse is to isolate the failure line or segment from the system The fuse element is generally made of a material having a low melting point, high conductivity, and least deterioration due to oxidation e.g.., silver, copper, etc. • It is inserted in series with the circuit to be protected. Under normal operating conditions, the fuse element is at a temperature below its melting point. • Therefore, it carries the normal current without overheating. • However, when a short circuit or overload occurs, the current flowing through the fuse will increase beyond its rated value. • This raises the temperature and fuses element melts, disconnecting the circuit protected by it. • The time required to blow out the fuse depends upon the magnitude of excessive current. • The greater the current, the smaller the time taken by the fuse to blow out Fuse
  • 7. The advantages of the fuse are: • The cheapest form of protection available • Requires no maintenance • Break heavy short-circuit current without noise or smoke • The minimum time of operation can be made much shorter than that of the CB Advantages The disadvantages of the fuse are: • Considerable time is required in removing or replacing a fuse after the operation • The TCC of a fuse cannot always be correlated with that of the protected apparatus. Disadvantages
  • 8. • It is an overcurrent protective device that automatically trips and reclosed a number of times to clear temporary faults or isolate permanent faults. • About 90% of faults on overhead distribution lines are of temporary nature and caused by lightning or by-passing of objects near or through lines(birds, vines, tree branches, etc) or touching of conductors. • These conditions result in arcing faults and the arc in the air faults can be extinguished by de- energizing the system by simultaneous opening of CBs on both ends of the feeder or one end of the feeder. • After a short time called dead time, the CBs can be reclosed as soon as the arc in fault has been extinguished and the path has regained its dielectric strength. • In distribution systems, a multishot auto-reclosing feature is generally provided. Automatic Circuit Recloser https://www.youtube.com/watch?v=PwkP1V8okjE
  • 9. The auto-reclosers controlling the primary feeder perform two, three, or four reclosing cycles(shot) if necessary • If the temporary fault has vanished during the dead time, the auto-recloser remains closed. • If the fault persists after the first/second recloser one more enclosing is attempted. • If the fault persists after the third/final recloser, the auto-recloser is opened and locked. With auto-reclosing breakers in primary feeders, the circuit continuity during temporary faults is improved. Auto–reclosing is generally not adopted for underground cables. The faults on cables are generally not temporary Automatic Circuit Recloser
  • 10. ADVANTAGES • It can perform the tasks that can be fulfilled by the combination of a CB, overcurrent relay, and reclosing relay • It is light in weight and maintenance-free • When a permanent fault occurs near the end of the lengthy feeder, then this feeder can be sectionalized using auto-recloser so as to reduce the outages DISADVANTAGES • It cannot clear the permanent faults completely • It is costlier than the CB • It is not suitable for cables as the breakdown of insulation in cables causes a permanent outage. Automatic Circuit Recloser
  • 11.
  • 12. AUTOMATIC LINE SECTIONALIZER It is the overcurrent protective devices installed only with backup CBs or auto-reclosing CB. • It is a no-load switching device that is provided with overcurrent relays, earth fault relays, and counters. • The counter counts the number of operations of the backup CB/auto-recloser. • After a predetermined number of backup CB/auto-recloser, if the CB/auto-recloser open has not cleared the line fault, the CB/autorecloser opens and thereafter the automatic sectionalizer opens under no current condition The operating modes of automatic sectionalizers are as follows: • If the fault on the distribution line is temporary and is cleared while the autorecloser is open, the connector of the sectionalizer is reset automatically to its normal position after autorecloser is closed, and the fault current counter in the sectionalizer will prepare for counting of the next opening of the auto-recloser • If the autorecloser is set to lockout on the fourth opening operation, the automation sectionalizer will be set to trip during the open circuit time following the third tripping operation of the auto- recloser
  • 13. AUTOMATIC LINE SECTIONALIZER Application aspects of automation sectionalizer Several aspects must be considered to finalize the scheme: • It must be used in series with auto-reclosers • It must not be located between two auto-reclosers • With two or three sectionalizes after one auto-recloser, the sequence must be coordinate • The minimum fault current has to be more than the minimum fault current at the end of the line section controlled by the sectionalizer • Under no circumstances the short time circuit current and momentary peak current at the location of the sectionalizer should be less than the respective ratings of the sectionalizer ADVANTAGES (i) Automatic sectionalizer is cheaper and required less maintenance than auto-reclosers (ii) They may be employed for interrupting or switching loads within their rating The main drawback is that the failure rate is in general greater than that of fuse
  • 14. CIRCUIT BREAKER A circuit breaker is a switch that opens and cuts off the flow of current when the current exceeds a certain level. CBs are placed at critical points in circuits to protect against damage that could result from excessive current flow, which is typically caused by component failure • High voltage CBs are intended for making HV circuits and for breaking load currents and short- circuit currents. • The circuit breakers must have adequate MVA breaking capacity, the shortest possible total break time, and be highly reliable in service and operation. • HV circuit breakers must be explosion-proof and fireproof, and weigh as their duty will permit. • The function of C.B is to isolate the faulty part of the power systems network from that of a healthy part under abnormal conditions. • These abnormal conditions will be sensed as a trip signal to the CB after receiving a trip signal from the relay, the fault part will be isolated from the power system. • A CB can be operated manually by remote control or automatically. • The automatic operating phenomena can be observed only under fault conditions.
  • 15. NECESSITY OF COORDINATION Time-current characteristics (TCC) of overcurrent protective devices in the distribution system are selected and set such that the protective devices operate in desired pre-set time sequence in the event of a fault. This is called protection coordination. • When two protective apparatus installed in series have the same/different characteristics, which provide a pre-set initially to isolate the fault is defined as the protective device. It is usually the apparatus, which will be nearer to the fault. • The apparatus, which furnishes backup protection but operates only when the protecting device fails to operate to clear the fault, is defined as the protected device. It is usually the apparatus, which will be far away from the fault.
  • 16. OBJECTIVES OF CO-ORDINATION The main objectives of properly co-ordinate protective devices are: • Minimize the extent of faults in order to reduce the number of customers affected • Minimize the service interruptions due to temporary faults • Minimize the duration of service outages to identify the location of the fault PROCEDURE OF CO-ORDINATION Salient points of co-ordination procedure (i) Draw the diagram of the distribution system indicating the location of overcurrent relays, fuses, auto- reclosers etc. (ii) Determine the following • Steady state short-circuit current • Asymmetrical peak short-circuit current • Normal load current • Minimum short-circuit current at the above locations (iii) Co-ordinate protective devices starting from the substation outward or from the end of the distribution feeder back to the substation (iv) Draw time current characteristics for the coordination
  • 17. Generally, time current characteristics(TCC) curves of the protective devices are platted by collecting the data from the manufacturer. The values of load current and fault current are obtained from power flow study and fault flow study General coordination procedure: The overcurrent protective devices i.e.., fuse, CB, recloser and line sectionalizer must be co- ordinate for identifying and isolating the faults. According to a specific operating sequence, the two overcurrent devices are said to be coordinated or selected.
  • 18. For all types of coordination the coordination procedure is the same and as follows: 1. Necessary and required data for coordination of protective devices should be collected 2. For a given distribution network, select the initial location of the protective device 3. Calculate the minimum and maximum value of fault current for various types of faults at every selected location and at the end of the main feeder or lateral or sub-laterals 4. Choose the necessary protective devices located at the distribution substation in order to protect the substation transformer properly from any type of faults that occurs in the distribution system 5. The overcurrent protective devices should be coordinated either from the substation onwards or the end of the distribution system back to the substation 6. If necessary, reconsider and change the initial location of the protective device 7. Reconsider the selected protective device for current carrying capacity, interrupting capacity and minimum pickup time 8. Draw the TCC curves showing the coordination of all protective devices used with the common base voltage 9. Finally, draw the distribution network diagram which shows the minimum and maximum value of fault current and also the rating of the various protection devices used.
  • 19. TYPES OF COORDINATION The different types of co-ordination methods are: 1. Fuse to fuse co-ordination 2. Auto –recloser to fuse co-ordination 3. Circuit breaker to fuse co-ordination 4. Circuit breaker to auto-recloser co-ordination
  • 20. FUSE TO FUSE CO-ORDINATION Fuse ‘A’ is called the protective fuse and fuse ‘B’ is called the protecting fuse are drawn single graph as shown in fig for perfect coordination, fuse ‘B’ must melt and clear the fault before fuse ‘A’ is damaged. To ensure this, three things are required (i)the maximum characteristics of the fuse B is plotted (ii)The minimum characteristics of fuse A is plotted (iii)75% of the minimum melting curve of A is plotted to make sure that the fuse is not damaged and to account for any degradation in the fuse characteristics If the damage curve of fuse A and the time clearance curve of fuse B never cross, then it is said to be perfect protection. If they cross, at some value of current, then it is called the limit of coordination. For example, suppose the curves cross at 200A. This means that coordination more than 200A is unlikely. However, if the maximum available short circuit current of the system at that location is only 150A the fuse would be considered to be fault co-ordinate.
  • 21. AUTO-RECLOSER TO FUSE CO-ORDINATION The time-current characteristics of auto-recloser (AR) in the main feeder circuit and fuse B in the lateral is as shown in fig If the fault ‘F’ beyond the fuse B is temporary, the auto- recloser ‘AR’ should clear it without blowing of fuse b The time-current characteristics of the fuse B are in two parts: 1. Minimum melting time versus fuse B current 2. First operating time versus fuse B current
  • 22. AUTO-RECLOSER TO FUSE CO-ORDINATION The above two curves of fuse B is co-ordinate with below two curves of tripping characteristics of ‘AR’ 1. Delayed auto-recloser opening characteristics 2. Instantaneous auto-recloser opening characteristics 3. If fault current is less than ‘M’ the closer operates with delayed opening time If fault current is less than ‘N’ the auto–recloser operates with instantaneous operating time. Beyond current N, fuse B operates Auto-recloser to fuse co-ordination for the complete auto-reclosing cycle takes into account the heating of the fuse due to flow of short-circuit current time in the cycle
  • 23. CIRCUIT BREAKER TO FUSE CO-ORDINATION The circuit breaker is tripped by over-current phase fault protection. Total fault clearing time is equal to the relay time plus circuit breaker time.’ When fuse ‘A’ is used as the main protection and circuit breaker as a backup is shown in fig, the operating time is selected as 150% of the total operating time of the fuse over current relays for phase to phase fault. Therefore fuse A operates first and the circuit breaker operates next only if the fuse fails to operate. If the circuit breaker provides the main protection and the fuse ‘A’ as a back up as shown in fig the relays should operate instantaneously and the circuit breaker should isolate the fault before blowing up the fuse. The minimum melting time of the fuse should be about 135% more than the fault ‘clearing time’ of the circuit–breaker relay combination for phase to phase faults.
  • 24. CIRCUIT BREAKER TO AUTO-RECLOSER CO-ORDINATION The circuit breaker provides backup protection. The auto-recloser has three principal opening characteristics 1. First and second opening operation ‘A’ for instantaneous opening characteristics 2. Third opening operation ‘B’ for delayed opening characteristics 3. Fourth opening operation ‘C’ for extended –delayed opening characteristic The inverse time characteristics ‘D’ of over current relay and circuit breaker combination should be above that of the three characteristics of auto-recloser as shown in fig