An Introduction to On-line
Partial Discharge Surveys
I Q S e r vic e s
PARTIAL DISCHARGE
When high voltage insulating material
breaks down Partial Discharges are
created, measured in units of charge
known as pico-Coulombs or millivolts.
I Q S e r vic e s
WHAT IS PARTIAL
DISCHARGE?
• Electrical discharges occurring inside medium and
high voltage insulation (flaws, cracks, voids,
irregularities).
• These imperfections create voltage stresses and
cause eventual failure of the insulation.
• Insulation failures begin with and are characterized
by small but detectable releases of energy or Partial
Discharge.
I Q S e r vic e s
• For many years partial discharge testing has been
an IEEE/ANSI standard to identify insulation
problems in electrical apparatus before it leaves
the factory floor.
• Many U.S. and International standards have been
developed for partial discharge testing.
• Until recently Partial Discharge testing was
limited to testing at manufacturer’s laboratories.
• Now computers and sophisticated equipment can
isolate and detect Partial Discharge occurrences in
the field.
PARTIAL DISCHARGE
TESTING USED FOR QUALITY
ASSURANCE
I Q S e r vic e s
I Q S e r vic e s
NO OUTAGE EVALUATION
These proven technologies exist today to evaluate medium or
high voltage systems while the system is energized.
1. Oil testing/DGA – limited to oil transformers
2. Infrared testing – visible loose connections only
3. Visual inspections – problems may not be visible
4. Power Quality – cannot detect insulation failures
5. Vibration – limited to motors and transformers
6. Partial Discharge Testing – single best all-around test
I Q S e r vic e s
PARTIAL DISCHARGE
VS. INFRARED
How are Partial Discharge Inspections
different from Infrared Inspections?
• Infrared identifies electrical current problems (loose
connections) that result in heat. The specimen must be
visible to the naked eye for the infrared camera to detect a
problem.
• Partial Discharge identifies voltage problems that result in
insulation breakdown and generation of Partial Discharges.
The specimen does not need to be visible for Partial
Discharges to be detected.
I Q S e r vic e s
I Q S e r vic e s
I Q S e r vic e s
I Q S e r vic e s
I Q S e r vic e s
INSULATION BREAKDOWN
Why should we be concerned with insulation
breakdown and Partial Discharges?
I Q S e r vic e s
• NFPA 70B states that insulation breakdown
is the number one cause of electrical
failures.
• In medium and high voltage equipment,
partial discharges are the first indication of
insulation breakdown.
INSULATION BREAKDOWN
I Q S e r vic e s
Component Percentage of insulation failure
Transformers 84%
Circuit Breakers 21%
Disconnect Switches 15%
Insulated Switchgear Bus 95%
Bus duct 90%
Cable 89%
Cable Joints (splices) 91%
Cable Terminations 87%
Based on IEEE Gold Book Table 36
Total Failures due to Insulation
Breakdown
I Q S e r vic e s
WHAT TYPE OF FACILITES
ARE AFFECTED?
• INDUSTRIAL - Large Manufacturing,
Cogeneration
• COMMERCIAL - Research Parks, High Rises
• INSTITUTIONAL - Campuses, Hospitals
• GOVERNMENTAL - Military Bases, Large
Office Complexes
• UTILITY - Investor Owned, Municipalities
I Q S e r vic e s
WHERE DO PARTIAL
DISCHARGES OCCUR?
• Electrical Systems > 600V (2.4KV, 4.16 KV,
12KV, etc.)
• Types of Equipment Subject to Partial
Discharge
-Cables -Transformers
-Circuit Breakers - Instrument Transformers
-Switchgear (CT’s, PT’s)
-Insulators - Bushings
-Generators - Motors
-Surge Arrestors - Capacitors
I Q S e r vic e s
ADVANTAGES OF PARTIAL
DISCHARGE SURVEYS
• PREDICTIVE - failures can be prevented.
• NO OUTAGE NECESSARY - does not interrupt
operations.
• NON-DESTRUCTIVE - no damage to electrical
system.
• TRENDING - comparison to previous tests
possible
• PRIORITIZE MAINTENANCE ACTIVITIES -
determine which equipment to service first.
• PLANNING - allows time to schedule repairs.
• FINANCIAL CONTROL – repairs can be budgeted.
I Q S e r vic e s
TYPICAL MEDIUM VOLTAGE
POWER CABLE
CONSTRUCTION
I Q S e r vic e s
Source
Switchgear
Ground Level
Underground Cable in Conduit (not visible)
Visible Cable
Terminations
Load
Unit Substation
Visible Cable
Terminations
TYPICAL HIGH VOLTAGE
UNDERGROUND CABLE
SYSTEM
I Q S e r vic e s
3 STAGES OF CABLE
INSULATION FAILURE
I Q S e r vic e s
STAGE 1
Imperfections
and voids
voids
INSULATION
/ / / /CONDUCTOR / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / /
INSULATION
No problems, minor voids therefore minor partial discharges
Jacket, Shield, Semi-conducting shield
Jacket, Shield, Semi-conducting shield
I Q S e r vic e s
INSULATION
/ / / /CONDUCTOR / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / /
INSULATION
Tracking begins
Jacket, Shield, Semi-conducting shield
Jacket, Shield, Semi-conducting shield
STAGE 2
I Q S e r vic e s
INSULATION
INSULATION
CABLE FAILURE!
Jacket, Shield, Semi-conducting shield
Jacket, Shield, Semi-conducting shield
Blow-up
Phase-to-ground
/ / / /CONDUCTOR / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / /
STAGE 3
I Q S e r vic e s
HOW CAN PARTIAL
DISCHARGES BE DETECTED?
Discharges are detected by special signal processing equipment designed to
eliminate outside interference.
Capacitive Methods - For Unshielded Components
- Dry Type Transformers
- Instrument Transformers
- Switchgear
Inductive Methods - metal enclosed components
- Shielded Cables and Components
- Oil Filled Transformers
- Rotating Apparatus
Acoustic Emission Methods
- Dry & Oil Transformers
- Switchgear
- Unshielded Cables
I Q S e r vic e s
Test Equipment & Sensors
I Q S e r vic e s
Partial Discharge detection of a flaw
in a dry type transformer using
capacitive coupling
flaw
Transformer Coil
Capacitive
sensor
Detector
I Q S e r vic e s
High Voltage Bus
Metallic Switchgear
cover (signal detected
outside)
Partial discharge
site (inside)
Propagation of Transient Earth
Voltages (TEV) in Switchgear
I Q S e r vic e s
Measurements
using
Capacitive PD
sensors
I Q S e r vic e s
Switchgear failure due to internal tracking
I Q S e r vic e s
Tracking on epoxy resin busbar
I Q S e r vic e s
Start of tracking on insulation
I Q S e r vic e s
Failed Switchgear Insulation
I Q S e r vic e s
Detecting PD Using Airborne
Acoustic (Ultrasonic) Sensors
Insulator
Busbar
Sensor
I Q S e r vic e s
Airborne Acoustic Sensor
I Q S e r vic e s
Insulator Failure Prevented
I Q S e r vic e s
Partial Discharge detection of a void in a
shielded cable using inductive coupling.
Insulation
+
Void
Shield (grounded)
Conductor
Detector
Inductive Sensor
I Q S e r vic e s
I Q S e r vic e s
High Frequency Current Transformer Used to Test Cable in
High Voltage Substation
I Q S e r vic e s
Failing Terminations
I Q S e r vic e s
Molded Cable Accessory Failure
I Q S e r vic e s
Splice Void
I Q S e r vic e s
Shield Delamination Causing
Partial Discharge
I Q S e r vic e s
Poor Workmanship Causing
Partial Discharge
I Q S e r vic e s
Testing 15kV cables
On-line testing of cables PD damage to termination
Case Study
I Q S e r vic e s
Identifying & Prioritising Circuits Most at Risk
Using On-Line PD Survey
L IV E L INE P ART IAL D IS C HARG E S URV E Y RE S UL T S
O F 6 2 9 HV F E E D E RS
0
100
200
300
400
500
600
700
800
900
1000
1
2
1
4
2
6
3
8
4
1
0
5
1
2
6
1
4
7
1
6
8
1
9
0
2
1
1
2
3
2
2
5
3
2
7
4
2
9
5
3
1
6
3
3
7
3
5
8
3
7
9
4
0
0
4
2
1
4
4
2
4
6
3
4
8
4
5
0
5
5
2
6
5
4
7
5
6
8
5
8
9
6
1
0
FEEDERS
m
V
D
i
s
c
h
a
rg
e
A C TIO N
C O N C E RN
I Q S e r vic e s
PD Survey - Worst 30 Results
I Q S e r vic e s
PERFORMING A PARTIAL
DISCHARGE SURVEY
• Analyze the single line drawing to develop plan
• Onsite Measurement
– Removal of equipment covers.
– Record field data.
– Obtain signatures of atypical components.
• Offsite Data Analysis
– Correlate measurements to single line drawing.
– Compare atypical results to like insulation from database.
– Analyze signatures.
– Trend Results.
• Report Generation
– Recognize immediate failure possibilities.
– Recommend possible repairs.
– Recommend possible resurvey frequency.
I Q S e r vic e s
SUMMARY
• Electric Insulation will fail.
• Predicting failures is now possible through
Partial Discharge Analysis.
• No outage is required to survey the
equipment.
• Results can be prioritized and trended.
• Partial Discharge Surveys should be
performed annually.
I Q S e r vic e s
We apologize to every electrical professional for taking 252 years
to prevent your failures.
Benjamin Franklin discovered electricity
in 1752. This year we launched an easy
to use, cost effective “no-outage” electrical
inspection technology that detects
medium and high voltage equipment
problems before they fail!

More Related Content

Similar to IQ_Partial_Discharge_Presentation.ppt

Overhead & Underground Electric Safety Webinar Presented by Amprobe
Overhead & Underground Electric Safety Webinar Presented by AmprobeOverhead & Underground Electric Safety Webinar Presented by Amprobe
Overhead & Underground Electric Safety Webinar Presented by Amprobe
Transcat
 
Development of underground line fault detector
Development of underground line fault detectorDevelopment of underground line fault detector
Development of underground line fault detector
DODDI NAGASAI
 
Presentation o surge protection devices
Presentation o surge protection devicesPresentation o surge protection devices
Presentation o surge protection devices
RAM PRAKASH PATEL
 
Fluke Electrical Safety Seminar Slides
Fluke Electrical Safety Seminar SlidesFluke Electrical Safety Seminar Slides
Fluke Electrical Safety Seminar Slides
Transcat
 
Kaizenreport
KaizenreportKaizenreport
Kaizenreport
Dhaval Solanki
 
Underground Cable Fault Detection Using Arduino
Underground Cable Fault Detection Using ArduinoUnderground Cable Fault Detection Using Arduino
Underground Cable Fault Detection Using Arduino
IRJET Journal
 
Identifying Casing Shorts With or Without Test Leads - Jim Walton
Identifying Casing Shorts With or Without Test Leads - Jim WaltonIdentifying Casing Shorts With or Without Test Leads - Jim Walton
Identifying Casing Shorts With or Without Test Leads - Jim Walton
nacetwincities
 
A3 predictive maintenance
A3 predictive maintenanceA3 predictive maintenance
A3 predictive maintenance
Amadeo Antonio
 
10 dumb things smart people when testing electricity
10 dumb things smart people when testing electricity10 dumb things smart people when testing electricity
10 dumb things smart people when testing electricity
hcsurfa
 
DATASHEET INVERSORES R6 SAJ TRIFASICOS LV
DATASHEET INVERSORES R6 SAJ TRIFASICOS LVDATASHEET INVERSORES R6 SAJ TRIFASICOS LV
DATASHEET INVERSORES R6 SAJ TRIFASICOS LV
grupopridesolar
 
Lightning and Surge Protection Strategy for Instrumentation
Lightning and Surge Protection Strategy for InstrumentationLightning and Surge Protection Strategy for Instrumentation
Lightning and Surge Protection Strategy for Instrumentation
RekaNext Capital
 
Arc Presentation.pptx
Arc Presentation.pptxArc Presentation.pptx
Arc Presentation.pptx
AlankarSharma14
 
Thyristors, its types
Thyristors, its typesThyristors, its types
Thyristors, its types
Saleem Ahmed
 
Surge and Lightning Protection Oct 2020
Surge and Lightning Protection Oct 2020Surge and Lightning Protection Oct 2020
Surge and Lightning Protection Oct 2020
RekaNext Capital
 
Earthing and disconnecting panel report.pdf
Earthing and disconnecting panel report.pdfEarthing and disconnecting panel report.pdf
Earthing and disconnecting panel report.pdf
MohitKumar989420
 
Isolator and bushing
Isolator and bushingIsolator and bushing
Isolator and bushing
Novia Putri
 
EE6702 Protection and Switchgear notes R2013
EE6702 Protection and Switchgear notes R2013EE6702 Protection and Switchgear notes R2013
EE6702 Protection and Switchgear notes R2013
Velalar College of Engineering and Technology
 
CAMERA CORONA TD100 Technology and Applications.pptx
CAMERA CORONA TD100 Technology and Applications.pptxCAMERA CORONA TD100 Technology and Applications.pptx
CAMERA CORONA TD100 Technology and Applications.pptx
HermelinoMSFilho
 
Katalog fluke-oscilloscope-the-toughest-scopes-ever-built-by-tridinamika
Katalog fluke-oscilloscope-the-toughest-scopes-ever-built-by-tridinamikaKatalog fluke-oscilloscope-the-toughest-scopes-ever-built-by-tridinamika
Katalog fluke-oscilloscope-the-toughest-scopes-ever-built-by-tridinamika
PT. Tridinamika Jaya Instrument
 
MV Switchgear from IEEE
MV Switchgear from IEEEMV Switchgear from IEEE

Similar to IQ_Partial_Discharge_Presentation.ppt (20)

Overhead & Underground Electric Safety Webinar Presented by Amprobe
Overhead & Underground Electric Safety Webinar Presented by AmprobeOverhead & Underground Electric Safety Webinar Presented by Amprobe
Overhead & Underground Electric Safety Webinar Presented by Amprobe
 
Development of underground line fault detector
Development of underground line fault detectorDevelopment of underground line fault detector
Development of underground line fault detector
 
Presentation o surge protection devices
Presentation o surge protection devicesPresentation o surge protection devices
Presentation o surge protection devices
 
Fluke Electrical Safety Seminar Slides
Fluke Electrical Safety Seminar SlidesFluke Electrical Safety Seminar Slides
Fluke Electrical Safety Seminar Slides
 
Kaizenreport
KaizenreportKaizenreport
Kaizenreport
 
Underground Cable Fault Detection Using Arduino
Underground Cable Fault Detection Using ArduinoUnderground Cable Fault Detection Using Arduino
Underground Cable Fault Detection Using Arduino
 
Identifying Casing Shorts With or Without Test Leads - Jim Walton
Identifying Casing Shorts With or Without Test Leads - Jim WaltonIdentifying Casing Shorts With or Without Test Leads - Jim Walton
Identifying Casing Shorts With or Without Test Leads - Jim Walton
 
A3 predictive maintenance
A3 predictive maintenanceA3 predictive maintenance
A3 predictive maintenance
 
10 dumb things smart people when testing electricity
10 dumb things smart people when testing electricity10 dumb things smart people when testing electricity
10 dumb things smart people when testing electricity
 
DATASHEET INVERSORES R6 SAJ TRIFASICOS LV
DATASHEET INVERSORES R6 SAJ TRIFASICOS LVDATASHEET INVERSORES R6 SAJ TRIFASICOS LV
DATASHEET INVERSORES R6 SAJ TRIFASICOS LV
 
Lightning and Surge Protection Strategy for Instrumentation
Lightning and Surge Protection Strategy for InstrumentationLightning and Surge Protection Strategy for Instrumentation
Lightning and Surge Protection Strategy for Instrumentation
 
Arc Presentation.pptx
Arc Presentation.pptxArc Presentation.pptx
Arc Presentation.pptx
 
Thyristors, its types
Thyristors, its typesThyristors, its types
Thyristors, its types
 
Surge and Lightning Protection Oct 2020
Surge and Lightning Protection Oct 2020Surge and Lightning Protection Oct 2020
Surge and Lightning Protection Oct 2020
 
Earthing and disconnecting panel report.pdf
Earthing and disconnecting panel report.pdfEarthing and disconnecting panel report.pdf
Earthing and disconnecting panel report.pdf
 
Isolator and bushing
Isolator and bushingIsolator and bushing
Isolator and bushing
 
EE6702 Protection and Switchgear notes R2013
EE6702 Protection and Switchgear notes R2013EE6702 Protection and Switchgear notes R2013
EE6702 Protection and Switchgear notes R2013
 
CAMERA CORONA TD100 Technology and Applications.pptx
CAMERA CORONA TD100 Technology and Applications.pptxCAMERA CORONA TD100 Technology and Applications.pptx
CAMERA CORONA TD100 Technology and Applications.pptx
 
Katalog fluke-oscilloscope-the-toughest-scopes-ever-built-by-tridinamika
Katalog fluke-oscilloscope-the-toughest-scopes-ever-built-by-tridinamikaKatalog fluke-oscilloscope-the-toughest-scopes-ever-built-by-tridinamika
Katalog fluke-oscilloscope-the-toughest-scopes-ever-built-by-tridinamika
 
MV Switchgear from IEEE
MV Switchgear from IEEEMV Switchgear from IEEE
MV Switchgear from IEEE
 

Recently uploaded

Cosmetic shop management system project report.pdf
Cosmetic shop management system project report.pdfCosmetic shop management system project report.pdf
Cosmetic shop management system project report.pdf
Kamal Acharya
 
Student information management system project report ii.pdf
Student information management system project report ii.pdfStudent information management system project report ii.pdf
Student information management system project report ii.pdf
Kamal Acharya
 
CME397 Surface Engineering- Professional Elective
CME397 Surface Engineering- Professional ElectiveCME397 Surface Engineering- Professional Elective
CME397 Surface Engineering- Professional Elective
karthi keyan
 
HYDROPOWER - Hydroelectric power generation
HYDROPOWER - Hydroelectric power generationHYDROPOWER - Hydroelectric power generation
HYDROPOWER - Hydroelectric power generation
Robbie Edward Sayers
 
Railway Signalling Principles Edition 3.pdf
Railway Signalling Principles Edition 3.pdfRailway Signalling Principles Edition 3.pdf
Railway Signalling Principles Edition 3.pdf
TeeVichai
 
The role of big data in decision making.
The role of big data in decision making.The role of big data in decision making.
The role of big data in decision making.
ankuprajapati0525
 
AKS UNIVERSITY Satna Final Year Project By OM Hardaha.pdf
AKS UNIVERSITY Satna Final Year Project By OM Hardaha.pdfAKS UNIVERSITY Satna Final Year Project By OM Hardaha.pdf
AKS UNIVERSITY Satna Final Year Project By OM Hardaha.pdf
SamSarthak3
 
WATER CRISIS and its solutions-pptx 1234
WATER CRISIS and its solutions-pptx 1234WATER CRISIS and its solutions-pptx 1234
WATER CRISIS and its solutions-pptx 1234
AafreenAbuthahir2
 
weather web application report.pdf
weather web application report.pdfweather web application report.pdf
weather web application report.pdf
Pratik Pawar
 
ASME IX(9) 2007 Full Version .pdf
ASME IX(9)  2007 Full Version       .pdfASME IX(9)  2007 Full Version       .pdf
ASME IX(9) 2007 Full Version .pdf
AhmedHussein950959
 
addressing modes in computer architecture
addressing modes  in computer architectureaddressing modes  in computer architecture
addressing modes in computer architecture
ShahidSultan24
 
Architectural Portfolio Sean Lockwood
Architectural Portfolio Sean LockwoodArchitectural Portfolio Sean Lockwood
Architectural Portfolio Sean Lockwood
seandesed
 
NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...
NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...
NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...
Amil Baba Dawood bangali
 
一比一原版(SFU毕业证)西蒙菲莎大学毕业证成绩单如何办理
一比一原版(SFU毕业证)西蒙菲莎大学毕业证成绩单如何办理一比一原版(SFU毕业证)西蒙菲莎大学毕业证成绩单如何办理
一比一原版(SFU毕业证)西蒙菲莎大学毕业证成绩单如何办理
bakpo1
 
ethical hacking-mobile hacking methods.ppt
ethical hacking-mobile hacking methods.pptethical hacking-mobile hacking methods.ppt
ethical hacking-mobile hacking methods.ppt
Jayaprasanna4
 
Hybrid optimization of pumped hydro system and solar- Engr. Abdul-Azeez.pdf
Hybrid optimization of pumped hydro system and solar- Engr. Abdul-Azeez.pdfHybrid optimization of pumped hydro system and solar- Engr. Abdul-Azeez.pdf
Hybrid optimization of pumped hydro system and solar- Engr. Abdul-Azeez.pdf
fxintegritypublishin
 
Sachpazis:Terzaghi Bearing Capacity Estimation in simple terms with Calculati...
Sachpazis:Terzaghi Bearing Capacity Estimation in simple terms with Calculati...Sachpazis:Terzaghi Bearing Capacity Estimation in simple terms with Calculati...
Sachpazis:Terzaghi Bearing Capacity Estimation in simple terms with Calculati...
Dr.Costas Sachpazis
 
MCQ Soil mechanics questions (Soil shear strength).pdf
MCQ Soil mechanics questions (Soil shear strength).pdfMCQ Soil mechanics questions (Soil shear strength).pdf
MCQ Soil mechanics questions (Soil shear strength).pdf
Osamah Alsalih
 
Standard Reomte Control Interface - Neometrix
Standard Reomte Control Interface - NeometrixStandard Reomte Control Interface - Neometrix
Standard Reomte Control Interface - Neometrix
Neometrix_Engineering_Pvt_Ltd
 
block diagram and signal flow graph representation
block diagram and signal flow graph representationblock diagram and signal flow graph representation
block diagram and signal flow graph representation
Divya Somashekar
 

Recently uploaded (20)

Cosmetic shop management system project report.pdf
Cosmetic shop management system project report.pdfCosmetic shop management system project report.pdf
Cosmetic shop management system project report.pdf
 
Student information management system project report ii.pdf
Student information management system project report ii.pdfStudent information management system project report ii.pdf
Student information management system project report ii.pdf
 
CME397 Surface Engineering- Professional Elective
CME397 Surface Engineering- Professional ElectiveCME397 Surface Engineering- Professional Elective
CME397 Surface Engineering- Professional Elective
 
HYDROPOWER - Hydroelectric power generation
HYDROPOWER - Hydroelectric power generationHYDROPOWER - Hydroelectric power generation
HYDROPOWER - Hydroelectric power generation
 
Railway Signalling Principles Edition 3.pdf
Railway Signalling Principles Edition 3.pdfRailway Signalling Principles Edition 3.pdf
Railway Signalling Principles Edition 3.pdf
 
The role of big data in decision making.
The role of big data in decision making.The role of big data in decision making.
The role of big data in decision making.
 
AKS UNIVERSITY Satna Final Year Project By OM Hardaha.pdf
AKS UNIVERSITY Satna Final Year Project By OM Hardaha.pdfAKS UNIVERSITY Satna Final Year Project By OM Hardaha.pdf
AKS UNIVERSITY Satna Final Year Project By OM Hardaha.pdf
 
WATER CRISIS and its solutions-pptx 1234
WATER CRISIS and its solutions-pptx 1234WATER CRISIS and its solutions-pptx 1234
WATER CRISIS and its solutions-pptx 1234
 
weather web application report.pdf
weather web application report.pdfweather web application report.pdf
weather web application report.pdf
 
ASME IX(9) 2007 Full Version .pdf
ASME IX(9)  2007 Full Version       .pdfASME IX(9)  2007 Full Version       .pdf
ASME IX(9) 2007 Full Version .pdf
 
addressing modes in computer architecture
addressing modes  in computer architectureaddressing modes  in computer architecture
addressing modes in computer architecture
 
Architectural Portfolio Sean Lockwood
Architectural Portfolio Sean LockwoodArchitectural Portfolio Sean Lockwood
Architectural Portfolio Sean Lockwood
 
NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...
NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...
NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...
 
一比一原版(SFU毕业证)西蒙菲莎大学毕业证成绩单如何办理
一比一原版(SFU毕业证)西蒙菲莎大学毕业证成绩单如何办理一比一原版(SFU毕业证)西蒙菲莎大学毕业证成绩单如何办理
一比一原版(SFU毕业证)西蒙菲莎大学毕业证成绩单如何办理
 
ethical hacking-mobile hacking methods.ppt
ethical hacking-mobile hacking methods.pptethical hacking-mobile hacking methods.ppt
ethical hacking-mobile hacking methods.ppt
 
Hybrid optimization of pumped hydro system and solar- Engr. Abdul-Azeez.pdf
Hybrid optimization of pumped hydro system and solar- Engr. Abdul-Azeez.pdfHybrid optimization of pumped hydro system and solar- Engr. Abdul-Azeez.pdf
Hybrid optimization of pumped hydro system and solar- Engr. Abdul-Azeez.pdf
 
Sachpazis:Terzaghi Bearing Capacity Estimation in simple terms with Calculati...
Sachpazis:Terzaghi Bearing Capacity Estimation in simple terms with Calculati...Sachpazis:Terzaghi Bearing Capacity Estimation in simple terms with Calculati...
Sachpazis:Terzaghi Bearing Capacity Estimation in simple terms with Calculati...
 
MCQ Soil mechanics questions (Soil shear strength).pdf
MCQ Soil mechanics questions (Soil shear strength).pdfMCQ Soil mechanics questions (Soil shear strength).pdf
MCQ Soil mechanics questions (Soil shear strength).pdf
 
Standard Reomte Control Interface - Neometrix
Standard Reomte Control Interface - NeometrixStandard Reomte Control Interface - Neometrix
Standard Reomte Control Interface - Neometrix
 
block diagram and signal flow graph representation
block diagram and signal flow graph representationblock diagram and signal flow graph representation
block diagram and signal flow graph representation
 

IQ_Partial_Discharge_Presentation.ppt

  • 1. I Q S e r vic e s An Introduction to On-line Partial Discharge Surveys
  • 2. I Q S e r vic e s PARTIAL DISCHARGE When high voltage insulating material breaks down Partial Discharges are created, measured in units of charge known as pico-Coulombs or millivolts.
  • 3. I Q S e r vic e s WHAT IS PARTIAL DISCHARGE? • Electrical discharges occurring inside medium and high voltage insulation (flaws, cracks, voids, irregularities). • These imperfections create voltage stresses and cause eventual failure of the insulation. • Insulation failures begin with and are characterized by small but detectable releases of energy or Partial Discharge.
  • 4. I Q S e r vic e s • For many years partial discharge testing has been an IEEE/ANSI standard to identify insulation problems in electrical apparatus before it leaves the factory floor. • Many U.S. and International standards have been developed for partial discharge testing. • Until recently Partial Discharge testing was limited to testing at manufacturer’s laboratories. • Now computers and sophisticated equipment can isolate and detect Partial Discharge occurrences in the field. PARTIAL DISCHARGE TESTING USED FOR QUALITY ASSURANCE
  • 5. I Q S e r vic e s
  • 6. I Q S e r vic e s NO OUTAGE EVALUATION These proven technologies exist today to evaluate medium or high voltage systems while the system is energized. 1. Oil testing/DGA – limited to oil transformers 2. Infrared testing – visible loose connections only 3. Visual inspections – problems may not be visible 4. Power Quality – cannot detect insulation failures 5. Vibration – limited to motors and transformers 6. Partial Discharge Testing – single best all-around test
  • 7. I Q S e r vic e s PARTIAL DISCHARGE VS. INFRARED How are Partial Discharge Inspections different from Infrared Inspections? • Infrared identifies electrical current problems (loose connections) that result in heat. The specimen must be visible to the naked eye for the infrared camera to detect a problem. • Partial Discharge identifies voltage problems that result in insulation breakdown and generation of Partial Discharges. The specimen does not need to be visible for Partial Discharges to be detected.
  • 8. I Q S e r vic e s
  • 9. I Q S e r vic e s
  • 10. I Q S e r vic e s
  • 11. I Q S e r vic e s
  • 12. I Q S e r vic e s INSULATION BREAKDOWN Why should we be concerned with insulation breakdown and Partial Discharges?
  • 13. I Q S e r vic e s • NFPA 70B states that insulation breakdown is the number one cause of electrical failures. • In medium and high voltage equipment, partial discharges are the first indication of insulation breakdown. INSULATION BREAKDOWN
  • 14. I Q S e r vic e s Component Percentage of insulation failure Transformers 84% Circuit Breakers 21% Disconnect Switches 15% Insulated Switchgear Bus 95% Bus duct 90% Cable 89% Cable Joints (splices) 91% Cable Terminations 87% Based on IEEE Gold Book Table 36 Total Failures due to Insulation Breakdown
  • 15. I Q S e r vic e s WHAT TYPE OF FACILITES ARE AFFECTED? • INDUSTRIAL - Large Manufacturing, Cogeneration • COMMERCIAL - Research Parks, High Rises • INSTITUTIONAL - Campuses, Hospitals • GOVERNMENTAL - Military Bases, Large Office Complexes • UTILITY - Investor Owned, Municipalities
  • 16. I Q S e r vic e s WHERE DO PARTIAL DISCHARGES OCCUR? • Electrical Systems > 600V (2.4KV, 4.16 KV, 12KV, etc.) • Types of Equipment Subject to Partial Discharge -Cables -Transformers -Circuit Breakers - Instrument Transformers -Switchgear (CT’s, PT’s) -Insulators - Bushings -Generators - Motors -Surge Arrestors - Capacitors
  • 17. I Q S e r vic e s ADVANTAGES OF PARTIAL DISCHARGE SURVEYS • PREDICTIVE - failures can be prevented. • NO OUTAGE NECESSARY - does not interrupt operations. • NON-DESTRUCTIVE - no damage to electrical system. • TRENDING - comparison to previous tests possible • PRIORITIZE MAINTENANCE ACTIVITIES - determine which equipment to service first. • PLANNING - allows time to schedule repairs. • FINANCIAL CONTROL – repairs can be budgeted.
  • 18. I Q S e r vic e s TYPICAL MEDIUM VOLTAGE POWER CABLE CONSTRUCTION
  • 19. I Q S e r vic e s Source Switchgear Ground Level Underground Cable in Conduit (not visible) Visible Cable Terminations Load Unit Substation Visible Cable Terminations TYPICAL HIGH VOLTAGE UNDERGROUND CABLE SYSTEM
  • 20. I Q S e r vic e s 3 STAGES OF CABLE INSULATION FAILURE
  • 21. I Q S e r vic e s STAGE 1 Imperfections and voids voids INSULATION / / / /CONDUCTOR / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / INSULATION No problems, minor voids therefore minor partial discharges Jacket, Shield, Semi-conducting shield Jacket, Shield, Semi-conducting shield
  • 22. I Q S e r vic e s INSULATION / / / /CONDUCTOR / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / INSULATION Tracking begins Jacket, Shield, Semi-conducting shield Jacket, Shield, Semi-conducting shield STAGE 2
  • 23. I Q S e r vic e s INSULATION INSULATION CABLE FAILURE! Jacket, Shield, Semi-conducting shield Jacket, Shield, Semi-conducting shield Blow-up Phase-to-ground / / / /CONDUCTOR / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / STAGE 3
  • 24. I Q S e r vic e s HOW CAN PARTIAL DISCHARGES BE DETECTED? Discharges are detected by special signal processing equipment designed to eliminate outside interference. Capacitive Methods - For Unshielded Components - Dry Type Transformers - Instrument Transformers - Switchgear Inductive Methods - metal enclosed components - Shielded Cables and Components - Oil Filled Transformers - Rotating Apparatus Acoustic Emission Methods - Dry & Oil Transformers - Switchgear - Unshielded Cables
  • 25. I Q S e r vic e s Test Equipment & Sensors
  • 26. I Q S e r vic e s Partial Discharge detection of a flaw in a dry type transformer using capacitive coupling flaw Transformer Coil Capacitive sensor Detector
  • 27. I Q S e r vic e s High Voltage Bus Metallic Switchgear cover (signal detected outside) Partial discharge site (inside) Propagation of Transient Earth Voltages (TEV) in Switchgear
  • 28. I Q S e r vic e s Measurements using Capacitive PD sensors
  • 29. I Q S e r vic e s Switchgear failure due to internal tracking
  • 30. I Q S e r vic e s Tracking on epoxy resin busbar
  • 31. I Q S e r vic e s Start of tracking on insulation
  • 32. I Q S e r vic e s Failed Switchgear Insulation
  • 33. I Q S e r vic e s Detecting PD Using Airborne Acoustic (Ultrasonic) Sensors Insulator Busbar Sensor
  • 34. I Q S e r vic e s Airborne Acoustic Sensor
  • 35. I Q S e r vic e s Insulator Failure Prevented
  • 36. I Q S e r vic e s Partial Discharge detection of a void in a shielded cable using inductive coupling. Insulation + Void Shield (grounded) Conductor Detector Inductive Sensor
  • 37. I Q S e r vic e s
  • 38. I Q S e r vic e s High Frequency Current Transformer Used to Test Cable in High Voltage Substation
  • 39. I Q S e r vic e s Failing Terminations
  • 40. I Q S e r vic e s Molded Cable Accessory Failure
  • 41. I Q S e r vic e s Splice Void
  • 42. I Q S e r vic e s Shield Delamination Causing Partial Discharge
  • 43. I Q S e r vic e s Poor Workmanship Causing Partial Discharge
  • 44. I Q S e r vic e s Testing 15kV cables On-line testing of cables PD damage to termination Case Study
  • 45. I Q S e r vic e s Identifying & Prioritising Circuits Most at Risk Using On-Line PD Survey L IV E L INE P ART IAL D IS C HARG E S URV E Y RE S UL T S O F 6 2 9 HV F E E D E RS 0 100 200 300 400 500 600 700 800 900 1000 1 2 1 4 2 6 3 8 4 1 0 5 1 2 6 1 4 7 1 6 8 1 9 0 2 1 1 2 3 2 2 5 3 2 7 4 2 9 5 3 1 6 3 3 7 3 5 8 3 7 9 4 0 0 4 2 1 4 4 2 4 6 3 4 8 4 5 0 5 5 2 6 5 4 7 5 6 8 5 8 9 6 1 0 FEEDERS m V D i s c h a rg e A C TIO N C O N C E RN
  • 46. I Q S e r vic e s PD Survey - Worst 30 Results
  • 47. I Q S e r vic e s PERFORMING A PARTIAL DISCHARGE SURVEY • Analyze the single line drawing to develop plan • Onsite Measurement – Removal of equipment covers. – Record field data. – Obtain signatures of atypical components. • Offsite Data Analysis – Correlate measurements to single line drawing. – Compare atypical results to like insulation from database. – Analyze signatures. – Trend Results. • Report Generation – Recognize immediate failure possibilities. – Recommend possible repairs. – Recommend possible resurvey frequency.
  • 48. I Q S e r vic e s SUMMARY • Electric Insulation will fail. • Predicting failures is now possible through Partial Discharge Analysis. • No outage is required to survey the equipment. • Results can be prioritized and trended. • Partial Discharge Surveys should be performed annually.
  • 49. I Q S e r vic e s We apologize to every electrical professional for taking 252 years to prevent your failures. Benjamin Franklin discovered electricity in 1752. This year we launched an easy to use, cost effective “no-outage” electrical inspection technology that detects medium and high voltage equipment problems before they fail!