Luis Alberto Hernรกndez. Int. Journal of Engineering Research and Applications www.ijera.com
ISSN: 2248-9622, Vol. 6, Issue 4, (Part - 2) April 2016, pp.28-34
www.ijera.com 28 | P a g e
Identification of Multiple Harmonic Sources in Electric Power
System with Erroneous Measurements Using Several Indices
Luis Alberto Hernรกndez Armenta*1
, David Romero Romero1
1
Instituto Politรฉcnico Nacional Electrical Engineering Department, Graduate Studies and Research Section,
ESIME Zacatenco, Mexico.
ABSTRACT
This Article shows that the current Total Harmonic Distortion (THD) can be used reliably as index to identify
the location of multiple harmonic sources in a power network. It isproved that the current THD locate the
harmonic sources with aยฑ1%uniformly distributed erroneous measurement. Current THD, Euclidean norm and
the magnitude of the nodal harmonic current are compared as indices to identify harmonic sources in Electric
Power Systems. It is shown that with an erroneous measurement of ยฑ1%, uniformly distributed, it is not
possible to locate multipleharmonic sources using the Euclidean norm and the nodal harmonic current.A 30
nodes system with three harmonic sources is tested with de Heydtโ€™s method, the Euclidean norm and the current
THD.
Keywords: Harmonic, Electric Power System, Current injections method, THD, Euclidean norm, Static Vars
Compensator (SVC).
I. INTRODUCTION
Due to the increase of nonlinear loads and
power electronic controlled devices, different
methods to locate harmonic sources in Power
Systems have been developed [1-19].These methods
can be used to locate harmonic sources, solve
harmonic power flows, and solve problems generated
by the harmonic sources.
Utility companies cannot always locate
harmonic sourcesthatdoes not meet quality standards.
Heydt G.T. in [1] propose a method to locate
harmonic sources in Electric Power System, based on
the current injection method, proposed by Mahmoud
in [20].This method states that the nodes where there
is a harmonic source will have a nodal harmonic
current magnitude different to zero. This asumption
is used as an index to identify harmonic sources [1-
19], i.e., the estimators locate the harmonic sources
using the nodal harmonic current magnitude as index.
Harmonic voltage and current measurements
are necessaryin these methods to locate harmonic
sources. Other articles propose to use other
measurements, like line harmonic current and
harmonic power flows [10, 12, 16].
Heydt [1] and Nguyen [2] methodologies
were not tested with measurement error presence.
The proposed methods to locate harmonic sources are
susceptible to erroneous measurements, this leads to
an unreliable identification of harmonic sources [10-
14]. Because of this problem a different solution has
been proposed, such as weighting measurements [9-
11] or the Euclidean norm [12].
The use of current THD as an index to locate
harmonic sources in Electric Power Systems is
proposed in this paper [25]. The current THD is
compared with the Euclidean norm, as index to
identify harmonic sources. Prior to the calculation of
this index, the nodal harmonic currents and voltages
must be calculated usingHeydtโ€™s method.
IEEE 30 nodes system was tested [26], with three
Static Vars Compensator (SVC), and with erroneous
measurements of ยฑ1% distributed uniformly, like
Kanao et. Al. in [10]. The results in this paper show
that the current THD can be used as a reliable index
to locate harmonic sources in Electric Power
Systems, even with erroneous measurements. When
the current THD is greater than 2.5% (limit
established by IEEE 519-1992 standard [21]), the
harmonic sources were identified consistently. When
the Euclidean norm and the nodal harmonic current
magnitude are used as index for the identification of
harmonic sources, it is not possible locate the
harmonic sources with erroneous measurements.
II. HEYDTโ€™S PROPOSED METHOD
FOR THE IDENTIFICATION OF
HARMONIC SOURCES
Heydtโ€™s proposed method in [1], is based on
the current injection technique [20] to solve the
harmonic power flow method, using the Kirchoffโ€™s
laws, as follows:
๐‘ฐ ๐’‰ = ๐’€ ๐’‰ ๐‘ฝ ๐’‰ (1)
Where:
๐‘ฐ ๐’‰ โˆˆ โ„‚ ๐’
, is a vector that contains the nodal
harmonic currents injected for the harmonic sources.
RESEARCH ARTICLE OPEN ACCESS
Luis Alberto Hernรกndez. Int. Journal of Engineering Research and Applications www.ijera.com
ISSN: 2248-9622, Vol. 6, Issue 4, (Part - 2) April 2016, pp.28-34
www.ijera.com 29 | P a g e
๐’€ ๐’‰ โˆˆ โ„‚ ๐’ร—๐’
,is the ๐’€ ๐’ƒ๐’–๐’” matrix affected by the
harmonics in the net.
๐‘ฝ ๐’‰ โˆˆ โ„‚ ๐’
, is the nodal harmonic voltage vector.
๐’,is the system node number.
๐’‰,is the harmonic number.
Rearranging eq. (1), grouping the known or
measured data, and the unknown data, eq. 2 is
obtained.
๐‘ฐ ๐’ƒ๐’– ๐’‰
๐‘ฝ ๐’ƒ๐’– ๐’‰
= ๐’€ ๐’‰ ๐‘ฝ ๐’‰ =
๐‘ฎ ๐’‰ ๐‘ฏ ๐’‰
๐‘ฑ ๐’‰ ๐‘ฒ ๐’‰
๐‘ฝ ๐’ƒ๐’– ๐’‰
๐‘ฝ ๐’ƒ๐’Œ ๐’‰
(2)
Where:
๐‘ฐ ๐’ƒ๐’Œ ๐’‰
โˆˆ โ„‚ ๐’Ž
, ๐‘ฝ ๐’ƒ๐’Œ ๐’‰
โˆˆ โ„‚ ๐’Ž
are the nodal harmonic
current and voltage measured vectors.
๐‘ฐ ๐’ƒ๐’– ๐’‰
โˆˆ โ„‚ ๐’–
, ๐‘ฝ ๐’ƒ๐’– ๐’‰
โˆˆ โ„‚ ๐’–
,are the nodal harmonic
current and voltage unknown vectors.
๐‘ฎ ๐’‰ โˆˆ โ„‚ ๐’–ร—๐’–
, ๐‘ฏ ๐’‰ โˆˆ โ„‚ ๐’–ร—๐’Ž
, ๐‘ฑ ๐’‰ โˆˆ โ„‚ ๐’Žร—๐’–
, ๐‘ฒ ๐’‰ โˆˆ
โ„‚ ๐’Žร—๐’Ž
,are sub-matrices obtained when the ๐’€ ๐’‰ matrix
is rearranged.
๐’Ž,is the total nodal measurement.
๐’–,is the total unknown data.
Solving with Least Squares sense:
๐‘ฐ ๐’ƒ๐’– ๐’‰
= ๐‘ฎ ๐’‰ ๐‘ฑ ๐’‰
+
๐‘ฐ ๐’ƒ๐’Œ ๐’‰
+ โˆ’๐‘ฎ ๐’‰ ๐‘ฑ ๐’‰
+
๐‘ฒ ๐’‰ + ๐‘ฏ ๐’‰ ๐‘ฝ ๐’ƒ๐’Œ ๐’‰
(3)
The pseudoinverse of ๐‘ฑmust be used to solve (3),
because ๐‘ฑ isnot a square matrix [1, 23-24].
Where:
๐‘ฑ+
๐’‰
โˆˆ โ„‚ ๐’–ร—๐’Ž
,is ๐‘ฑ ๐’‰ pseudoinverse and is defined
as๐‘ฑ ๐’‰
+
= [๐‘ฑ ๐’‰
๐‘ป
๐‘ฑ ๐’‰]โˆ’๐Ÿ
๐‘ฑ ๐’‰
๐‘ป
[1, 23-24].
The process is not iterative, so the result to each
harmonic in the system is obtained directly.
Figure 1, shows the flow chart that resumes the
Heydtโ€™s method proposed to locate harmonic sources.
Unknown nodal harmonic currents are
estimated with this method, so it is necessary to use
(1) to calculate the unknown nodal harmonic
voltages.
Heydtโ€™s method propose the nodal harmonic
current magnitude as index to locate harmonic
sources in Electric Power Systems, i.e., the node
where there isnot a harmonic source connected
should have a harmonic nodal current magnitude
equal or closer to zero. So the node with a harmonic
source will have a harmonic nodal current magnitude
different of zero.
Unfortunately, Heydtโ€™s method fails when
erroneous measurements are present [9-12,
14,25].Then,it is necessary to propose other indexes,
such as the Euclidean norm [12] or current THD [25].
Heydtโ€™s method not only provides the
harmonic source location, it mayidentify the kind of
harmonic sources too. Unfortunately, in the presence
of erroneous measurementsit isnot possible to locate
unknown harmonic sources.
Start
Read system data
Read
measurements
data
h=total
harmonic
number
Yh
is calculated
G, H, J, K are
calculated
J+
is calculated
Ibu is calculated
No
Print results
End
Yes
Ih is calculated
Fig. 1. Heydtโ€™s method flow chart [1].
III. HARMONIC SOURCE LOCATION
USING THE EUCLIDEAN NORM
The Euclidean norm was proposed in [12] as
an index to identify harmonic sources in an Electric
Power System. Prior to calculate the Euclidian norm,
the nodal harmonic current must be known, so it can
be used a harmonic estimation method. In this paper
itโ€™ll be used the Heydtโ€™s method proposed in [1].
Once estimated the nodal harmonic currents,
the nodes with a possible harmonic source are
discriminated. The index to discriminate suspicious
nodes with a harmonic source connected is the
harmonic nodal current [12]. A bus with a nonzero
nodal harmonic current magnitude is suspicious,
where a harmonic source may be connected.
When the suspicious nodes are known, there
are ๐‘ possible combinations of nodes with harmonic
sources connected [12]. ๐‘iscalculated with eq. (4):
๐‘ = ๐ถ1
๐‘š
+ ๐ถ2
๐‘š
+ โ‹ฏ + ๐ถ ๐‘š
๐‘š
= ๐ถ๐‘
๐‘š
๐‘=๐‘š
๐‘=1
(4)
Where:
๐‘, is one of the ๐‘ possible combinations of nodes
with harmonic sources connected.
๐‘š, is the total number of combinations of nodes
with harmonic sources connected.
๐ถ1
๐‘š
is the probability of have one node with
unidentified harmonic source.
๐ถ2
๐‘š
is the probability of have two node with
unidentified harmonic source.
๐ถ ๐‘š
๐‘š
is the probability of have ๐‘š node with
unidentified harmonic source.
Once obtained the ๐‘ possible combinations, the
harmonic nodal voltage is calculated for each
Luis Alberto Hernรกndez. Int. Journal of Engineering Research and Applications www.ijera.com
ISSN: 2248-9622, Vol. 6, Issue 4, (Part - 2) April 2016, pp.28-34
www.ijera.com 30 | P a g e
possible combination. Then, the Euclidean norm of
the difference between the estimated and measured
harmonic nodal voltages is calculated for the ๐‘
combinations. The harmonic sources are located in
the node combination with the least Euclidean norm
value.
๐‘‰โ„Ž โˆ’ ๐‘‰โ„Ž ๐‘
= ๐‘‰โ„Ž
1
โˆ’ ๐‘‰โ„Ž
1 2
+ ๐‘‰โ„Ž
2
โˆ’ ๐‘‰โ„Ž
2 2
+ โ‹ฏ
๐‘š๐‘’๐‘Ž๐‘ 
๐‘–=1
+ ๐‘‰โ„Ž
๐‘š๐‘’๐‘Ž๐‘ 
โˆ’ ๐‘‰โ„Ž
๐‘š๐‘’๐‘Ž๐‘  2 1/2
(5)
Where:
, is the Euclidean norm
, is anestimated value
, is a measured value
๐‘š๐‘’๐‘Ž๐‘ , is the total of measurements
Figure 2 shows the flow chart of the Euclidean
norm method to identify harmonic sources in Electric
Power Systems.
The Euclidean norm method uses the nodal
harmonic voltage as index to locate harmonic
sources, while the method explained before, use the
nodal harmonic current.
With this method it is not possible to know
the kind of harmonic sources in a node, nevertheless,
the nodal harmonic voltage are estimated, so it can be
used (1) to know the kind of harmonic sources
connected in the system.
IV. HARMONIC SOURCES LOCATION
USING CURRENT TOTAL
HARMONIC DISTORTION (THD)
THD is defined as the square root of the
summation of the RMS value of the harmonics,
divided by the RMS value of the fundamental. The
THD is a measure that indicates the nodal harmonic
pollution with respect to the fundamental, for this
reason, THD can be used as index to locate harmonic
sources in an Electric Power System.
NO
Start
Read system data
m = total combinations
i= total measurements
End
Yes
Euclidean
norm is
calculated
Print results
Yes NO
Calculate the c posible
combinations
Least Euclidean
norm is obtained
Fig. 2. Flow chart of the Euclidean norm method
to identify harmonic sources in Electric Power
Systems
In this paper, the current THD is proposed as
an index for the identification of harmonic sources
[25]. Prior to the current THD calculation, it is
necessary use an estimation method to know the
nodal harmonic current, hence Heydtโ€™smethod,
proposed in [1], was used to estimate the nodal
harmonic currents. Once the nodal harmonic currents
are determined, the current THD is calculated in each
Power System bus. The nodes with a current THD
greater than 2.5% (limit allowed by the IEEE 519-
1992 [21]) have a harmonic source connected.
The current THD is defined as:
๐‘‡๐ป๐ท =
1
๐ผ1
๐ผโ„Ž
2
โˆž
โ„Ž=2
Where:
๐ผ1, is the fundamental current.
Figure 3 shows the flow chart of the current
THD method as index to identify harmonic sources in
Electric Power Systems.
No
Start
Read system data
Currentt THD is
calculated
n = node number
THD > 2.5%
End
Yes
There is a harmonic
source at node n
There is not a
harmonic source at
node n
Print results Yes No
Fig. 3. Flow chart ofthe current THD method as
index to identify harmonic sources in Electric Power
Systems.
This method is not iterative; just requires the
previous knowledge of network nodal harmonic
currents. The network nodal harmonic currents can
be calculated using a harmonic estimation method, in
this case the Heydtยดs method.
With this method it is not possible to know the
kind of harmonic sources connected in the system,
so, the current THD only can be used as an index to
locate harmonic sources.
V. TEST SYSTEM
IEEE 30 nodes test system is used in this
paper; it is presented in Figure 4. Three harmonic
sources are connected: nodes 7, 12 and 21. The three
harmonic sources are SVCs.This system isutilized to
test the three methods;Heydtยดs, current THD and the
Euclidean norm.
The test system data were taken from [26],
while SVC data are available in [21] and on Table 1
of this paper. The voltage measurements are
Luis Alberto Hernรกndez. Int. Journal of Engineering Research and Applications www.ijera.com
ISSN: 2248-9622, Vol. 6, Issue 4, (Part - 2) April 2016, pp.28-34
www.ijera.com 31 | P a g e
perturbed with aยฑ1% uniformily distributed error,
like Kanao et. al. in [10].
In Figure 4, the nodes with nodal harmonic
voltage and current measurements are marked with a
black square.
Table 1. Harmonic current percent of the
fundamental injected by the SVC [16]
Harmonic Harmonic current
percent
Lagging
5 7.02 46.92
7 2.5 -29.87
11 1.36 -23.75
13 0.75 71.5
17 0.62 77.12
19 0.32 173.43
23 0.43 178.02
25 0.13 -83.45
29 0.4 -80.45
VI. RESULTS
VI.1. Results Obtained Using The Heydtโ€™s Method
Table 2 presents the estimated harmonic
nodal currents with Heydtโ€™s method.
It is observed on Table 2, that it is not
possible to locate the harmonic sources in the test
system, because all the nodes have a harmonic
current magnitude different to zero. Therefore,
according to the obtained results, all the nodes
without measurement have a harmonic source
connected, which is incorrect, because there are
harmonic sources only in nodes 7, 12 and 21.
1
2
3 4
5
6
8
11
9
13
12
16
17
2019181514 21
22
24
23
25
27
30
26
29
28
7
G
G
C
C
C10
Fig. 4. IEEE 30 nodes system
VI.2. Results Obtained Using The Euclidean
Norm.
It is necessary to know the nodal harmonic
currents in the system previously for this method.
Bus Harmonic information is taken from Table 2. A
node is considered suspiciouswhen it has a nonzero
harmonic current magnitude. It is important to
observe that all the nodes in Table 2 are suspicious,
because they have a nonzero nodal harmonic current
magnitude.
For this case, the Euclidean norm must be
calculated for the 1804 combinations. The unknowns
are greater than using the current THD, which
represents more complexity and computational time.
Once the ๐‘possible nodes combination with
a harmonic source connected is obtained, nodal
harmonic voltages are calculated using equation (1)
for all the possible combinations.
After nodal harmonic voltages are
calculated, the Euclidean norm of the difference
between the estimated and measured nodal harmonic
voltages is obtained. The harmonic sources are
identified on the node combination with the least
Euclidean norm
Table 2. Harmonic currents estimated using Heydtโ€™s
method.
Harmonic Node Current
Magnitude
Current Angle
5
4 0.05244 -29.14526
7 0.51634 37.95395
8 0.01805 151.2976
10 0.05737 150.2769
12 0.47789 42.22538
15 0.08258 -32.69866
19 0.02558 146.069
21 0.5443 25.52365
24 0.07635 147.7675
26 0.02145 -30.89148
7
4 0.0042 0.53649
7 0.18975 -38.10252
8 0.00302 -165.9232
10 0.00465 -169.3179
12 0.18394 -38.87131
15 0.01551 -174.7489
19 0.00662 6.24152
21 0.17658 -43.0926
24 0.01254 5.84101
26 0.0054 -174.1768
11
4 0.00273 6.64711
7 0.0996 -34.00909
8 0.00392 -167.1774
10 0.00068 -40.87262
12 0.0951 -35.24238
15 0.00054 -38.51659
19 0.00034 141.4175
21 0.09759 -35.68853
24 0.00021 -44.86901
26 0.00017 141.272
13
4 0.00023 -120.1048
7 0.05559 61.69102
8 0.00015 -65.02871
10 0.00001 76.4007
12 0.05291 60.06713
15 0.0002 49.66085
19 0.00009 -124.4183
21 0.05408 59.46381
Luis Alberto Hernรกndez. Int. Journal of Engineering Research and Applications www.ijera.com
ISSN: 2248-9622, Vol. 6, Issue 4, (Part - 2) April 2016, pp.28-34
www.ijera.com 32 | P a g e
24 0.00007 -120.6972
26 0.00002 29.05268
17
4 0.00067 -134.5783
7 0.04602 66.97454
8 0.00151 45.22181
10 0.00005 -87.92987
12 0.04413 65.62669
15 0.00001 176.6073
19 0.00002 31.96162
21 0.04502 65.02678
24 0 31.81417
26 0 -110.9143
Harmonic Node Current
Magnitude
Current Angle
19 4 0.00027 -165.0147
7 0.02384 163.7968
8 0.00032 170.9907
10 0.00006 1.68469
12 0.0228 161.8754
15 0.00025 -25.59733
19 0.00004 150.676
21 0.02315 161.42
24 0.00004 -32.72941
26 0.00011 -7.59551
23
4 0.0001 55.44044
7 0.03158 168.1325
8 0.00043 150.9051
10 0.00108 19.71677
12 0.03059 166.4789
15 0.00018 -43.77839
19 0.00014 33.10193
21 0.03059 165.4211
24 0.00007 -67.372
26 0.00005 177.391
25
4 0.00002 6.96216
7 0.0096 -93.30957
8 0.00006 -160.6385
10 0.0009 -52.89224
12 0.00927 -94.73791
15 0.0002 109.3187
19 0.00011 -53.20313
21 0.00951 -94.29516
24 0.0002 98.29692
26 0.00006 104.553
29
4 0.00034 -41.29469
7 0.02975 -90.1825
8 0.00011 -130.7203
10 0.01155 -85.70278
12 0.0443 -91.70417
15 0.03299 95.28408
19 0.00589 -83.82865
21 0.01298 -102.0905
24 0.05353 92.19901
26 0.00853 98.69428
Since the number of possible nodes
combination is too large, 1804, on Table 3 are listed
the least Euclidean norm for up to๐‘š = 5. In Table 3,
the actual node combination of harmonic sources is
presented with bold letters.
Table 3. Least Euclidean norm for up to five nodes
with unidentified harmonic source
Possi
ble
node
combi
nation
Harmonic
5 7 11 13 17
with
harm
onic
sourc
es
8 0.0219 0.0014 0.0008 0 0.000
4
4, 19 0.0296 0.0071 0.0007 0 0.000
1
4, 8,
19
0.0345 0.0059 0.0002 0 0.000
3
7, 12,
21
3.12 0.3484 0.0163 0.0032 0.01
8, 15,
24, 26
0.0417 0.0035 0.0008 0 0.000
1
4, 15,
19,
24, 26
0.0422 0.0073 0.0007 0 0.000
1
Possible node
combination
with harmonic
sources
Harmonic
19 23 25 29
8 0.0001 0 0 0
4, 19 0 0 0 0.0002
4, 8, 19 0.0001 0 0 0.0002
7, 12, 21 0.0058 0.0048 0.0011 0.0196
8, 15, 24, 26 0 0 0 0
4, 15, 19, 24, 26 0 0 0 0.0002
It is noted in Table 3, that it is not possible
to locate the harmonic sources in the test system
using the smallest Euclidean norm. The Euclidean
norm calculated for the node combination where the
actual harmonic sources are connected (7, 12 and 21)
is greater than the other combinations showed in
Table3.
Euclidean norm isnot a reliable index to
locate harmonic sources in Electric Power Systems
with erroneous measurements of ยฑ1% distributed
uniformly.
VI.3. Results Obtained Using the Euclidean
Norm.
Prior to the calculation of the current THD,
it is necessary to know the nodal harmonic currents in
the system. With the Table 2 information, the current
THD in each node is calculated. Table 4 presents the
current THD in each system node.
As mentioned previously, the nodes with a
current THD greater than 2.5% (limit allowed by the
IEEE519-1992 standard [21]) have a harmonic
source connected. In Table 4, nodes 7, 12 and 21
exceed the limit established of current THD, it means
that there are harmonic sources connected in these
nodes.
Tabla 4. Current THD
Node THD Node THD
1 0 16 0
2 0 17 0
3 0 18 0
4 0.165967 19 0.267643
5 0 20 0
6 0 21 4.764308
Luis Alberto Hernรกndez. Int. Journal of Engineering Research and Applications www.ijera.com
ISSN: 2248-9622, Vol. 6, Issue 4, (Part - 2) April 2016, pp.28-34
www.ijera.com 33 | P a g e
7 4.420703 22 0
8 0.062511 23 0
9 0 24 0.867507
10 0.237188 25 0
11 0 26 0.51029
12 3.143242 27 0
13 0 28 0
14 0 29 0
15 1.012626 30 0
Current THD as index to locate harmonic
sources in Electric Power Systems identifies correctly
the three harmonic sources connected on the test
system, even in the presence of ยฑ1%erroneous
measurements, uniformly distributed.
With the current THD, the kind of harmonic
source cannot be identified. This index only can be
used to locate harmonic sources in Electric Power
Systems.
VII. CONCLUSIONS
It is showed that the current THD locate
consistently the harmonic sources in the test system,
even with erroneous measurements.
The current THD method to locate harmonic
source is simple, it is necessary only to calculate the
current THD for each network node, and determine
the buses that exceed the limit proposed in the
IEEE519-1992 standard.
With ยฑ1% uniformly distributed erroneous
measurements,it is not possible to locate the
harmonic sources in the test systemusing Heydtโ€™sor
the Euclidian norm method. Nevertheless, nodal
harmonic currents estimated by Heydtโ€™s method can
be used for other indexes like current THD or
Euclidean norm.
In the Euclidean norm method, when there is
a big number of combinations of nodes with
unidentified harmonic sources, the method becomes
more complex, and may require more computational
time.
REFERENCES
[1]. Heydt G. T. (1989)Identification of
Harmonic Sources by a State Estimation
Technique. Transaction on Power Delivery,
Vol. 4 No.1, pp. 569 โ€“ 576, IEEE.
[2]. Nguyen H. T., Yang J. J., Choi, S. S.
(2010).On Harmonic State Estimation and
the Evaluation of Harmonic Power
Contribution from Sources. Power and
Energy Society Meeting, IEEE.
[3]. DU Z. P., Arrillaga J., Watson N.R., Chen S.
(1999).Identification of Harmonic Sources
of Power Systems Using State Estimation.
Proceedings Generation Transmission and.
Distribution, Vol. 146 No. 1, pp. 7 โ€“ 12 IEE.
[4]. Sakis A. P., Zhang F., Zelingher S.
(1994).Power System Harmonic State
Estimation. Transactions on Power Delivery,
Vol. 9 No. 3, pp. 1701 - 1709 IEEE.
[5]. Lobos T, Kozina T, Koglin H. J.
(1999).Power System Harmonic State
Estimation Using Linear Least Square
Method and SVD. Proceedings Generation
Transmission and. Distribution, Vol. 148
No. 6, pp. 567 โ€“ 572, IEE.
[6]. Zhang Y., Xu Y., Xu Y. (2011). Research on
Power System Harmonic State Estimation.
International Conference on Power System
Technology, IEEE
[7]. Liao H. (2007). Power System Harmonic
State Estimation and Observability Analysis
via Sparsity Maximization. Transactions on
Power Systems, Vol. 22 No. 1, pp. 15 โ€“ 23,
IEEE.
[8]. Hou S., Xu Z., Lv H., Jiang Z., Wang L.
(2006).Research into Harmonic State
Estimation in Power System Based on PMU
and SVD. International Conference on
Power System Technology, IEEE.
[9]. Moghadasian M., Mokhtari H., Baladi A.
(2010).Power System Harmonic State
Estimation Using WLS and SVD; A
practical Approach. 14th
International
Conference on Harmonics and Quality of
Power, IEEE.
[10]. Kanao N., Yamashita M., Yanagida H.,
Muzykami M. (2005).Power System
Harmonic Analysis Using State-Estimation
Method for Japanese Field Data.
Transactions on Power Delivery, Vol.2 No.
2, pp. 970 โ€“ 977, IEEE.
[11]. Kent K. C., Neville R. W., Arrillaga J.
(2005).Error Analysis in Static Harmonic
State Estimation: A Statistical Approach.
Transactions on Power Delivery, Vol. 20
No. 2, pp. 1045 โ€“ 1050, IEEE.
[12]. Kumar A., Das B., Sharma J. (2004)
Determination of location of Multiple
Harmonic Sources in a Power System.
Electric Power Delivery Systems, Vol. 26,
pp. 73 โ€“ 78. ELSEVIER
[13]. Jain S. K., Singh S. N. (2011). Harmonic
Estimation in Emerging Power Systems:
Key Issues and Challenges. Electric Power
System Research, Vol. 81, pp. 1754 โ€“ 1756.
ELSEVIER.
[14]. Hernรกndez L. A. (2012).Harmonic sources
identification using estimation method in
Electric Power Systems. M.S. Thesis, SEPI-
ESIME Zacatenco IPN.
[15]. Arruda F. E., Nagan N., Ribeiro P. F.
(2010). Three-phase Harmonic Distortion
State Estimation Algorithm Based on
Evolutionary Strategies. Electric Power
System Research, Vol. 80 pp. 1024 โ€“ 1032.
ELSEVIER
Luis Alberto Hernรกndez. Int. Journal of Engineering Research and Applications www.ijera.com
ISSN: 2248-9622, Vol. 6, Issue 4, (Part - 2) April 2016, pp.28-34
www.ijera.com 34 | P a g e
[16]. Dag O., Uแธ‰ac E., Usta ร–. (2012). Harmonic
Source Location and meter placement
optimization by impedance network
approach. Elect. Eng., Vol. 94, pp. 1 โ€“ 10.
SPRINGER.
[17]. Rakpenthai C., Uatrongjit S., Watson N. R.,
Premrudeepreechacharn S. (2013). On
Harmonic State Estimation of Power System
with Uncertain Network Parameters.
Transaction on Power Systems, Vol. 28 No
4, pp. 4829 โ€“ 4838. IEEE.
[18]. Gursor E., Niebur D. (2009). Harmonic
Load Identification Using Complex
Independent Component Analysis.
Transactions on Power Delivery, Vol. 24,
No. 1, pp. 285 โ€“ 292. IEEE
[19]. Dโ€™Antona G., Muscas C., Sulis S. (2011).
Localization of Nonlinear Loads in Electric
Systems through Harmonic Source
Estimation. Transactions on instrumentation
and measurements, Vol. 60, No. 10, IEEE
[20]. Mahmoud A. A., Schultz R. D. (1982). A
Method for Analyzing Harmonic
Distribution in A.C. Power Systems.
Transactions on Power Apparatus and
Systems, Vol. PAS-101 No. 6, pp 1815 -
1824 IEEE.
[21]. IEEE STD 519-1992
(1993).IEEERecommended Practices and
Requirements for Harmonic Control in
Electrical Power Systems. IEEE.
[22]. Task Force on Harmonic Modeling and
Simulation (1996).Modeling and Simulation
of the Propagation of Harmonics in Electric
Power Networks. Transactions on Power
Delivery, Vol. 11 No. 1, pp 452 โ€“ 465,
IEEE.
[23]. Moore R. H (1920).On the reciprocal of the
general algebraic matrix. Bulletin of the
American Mathematical Society, Vol. 26,
pp. 394-395.
[24]. Penrose R. (1955).A generalized inverse for
the matrices. Proceedings of the Cambridge
Philosophical Society, Vol. 51, pp. 406-413.
[25]. Hernรกndez A. L. A., Romero R. D. (2015).
Harmonic sources Index to locate harmonic
sources in Electric Power Systems using
State Estimation with Measurement
Error,Computaciรณn y Sistemas, Vol. 29 No.
22.
[26]. Freris L. L., Sasson A. M. (1968).
Investigation of the load flow problem.IEE,
Vol. 115 No. 10, pp. 1459-1470.
AUTHORS
Luis Alberto Hernรกndez Armenta,
Electrical Engineer 2010 and Master
degree 2012 from the Instituto
Politรฉcnico Nacional. Actually,
PH.D. student on the graduate program in Electric
Engineer on the InstitutoPolitรฉcnico Nacional.
Interest areas: Power Quality, Harmonic Analysis in
Electric Power System, Electric Power System
Analysis and State Estimation.
David Romero Romero,
Electrical Engineer 1974 and
Master degree 1976, from the
Instituto Politรฉcnico Nacional.
PhD. Degree 1984 from Purdue
University in Indiana.
Investigator Pofessor from the
graduated program in Electrical
Engineer from the Instituto Politรฉcnico Nacional.
Interest Areas: Electric Power Systems Stochastic
Analysis, Electric Power Systems Analysis and
Intelligent Control.

More Related Content

Viewers also liked

Adaptive Relay Scheme Based on Channel State in Dual-Hop System
Adaptive Relay Scheme Based on Channel State in Dual-Hop SystemAdaptive Relay Scheme Based on Channel State in Dual-Hop System
Adaptive Relay Scheme Based on Channel State in Dual-Hop SystemIJERA Editor
ย 
CO2 Capture Using Activated Alumina in Gasoline Passenger Vehicles
CO2 Capture Using Activated Alumina in Gasoline Passenger VehiclesCO2 Capture Using Activated Alumina in Gasoline Passenger Vehicles
CO2 Capture Using Activated Alumina in Gasoline Passenger VehiclesIJERA Editor
ย 
The Effect of Temperature and Rock Permeability on Oil-Water Relative Permeab...
The Effect of Temperature and Rock Permeability on Oil-Water Relative Permeab...The Effect of Temperature and Rock Permeability on Oil-Water Relative Permeab...
The Effect of Temperature and Rock Permeability on Oil-Water Relative Permeab...IJERA Editor
ย 
An Improved Explicit Profile Matching In Mobile Social Networks
An Improved Explicit Profile Matching In Mobile Social NetworksAn Improved Explicit Profile Matching In Mobile Social Networks
An Improved Explicit Profile Matching In Mobile Social NetworksIJERA Editor
ย 
Clock Gating Cells for Low Power Scan Testing By Dft Technique
Clock Gating Cells for Low Power Scan Testing By Dft TechniqueClock Gating Cells for Low Power Scan Testing By Dft Technique
Clock Gating Cells for Low Power Scan Testing By Dft TechniqueIJERA Editor
ย 
Analysis of Changing Land Use Land Cover in Salinity Affected Coastal Region
Analysis of Changing Land Use Land Cover in Salinity Affected Coastal RegionAnalysis of Changing Land Use Land Cover in Salinity Affected Coastal Region
Analysis of Changing Land Use Land Cover in Salinity Affected Coastal RegionIJERA Editor
ย 
Design Optimization of Hydraulic Press Plate using Finite Element Analysis
Design Optimization of Hydraulic Press Plate using Finite Element AnalysisDesign Optimization of Hydraulic Press Plate using Finite Element Analysis
Design Optimization of Hydraulic Press Plate using Finite Element AnalysisIJERA Editor
ย 
Remediation of contaminated soil using soil washing-a review
Remediation of contaminated soil using soil washing-a reviewRemediation of contaminated soil using soil washing-a review
Remediation of contaminated soil using soil washing-a reviewIJERA Editor
ย 
Comparison of the Performances of NH3-H20 and Libr-H2O Vapour Absorption Refr...
Comparison of the Performances of NH3-H20 and Libr-H2O Vapour Absorption Refr...Comparison of the Performances of NH3-H20 and Libr-H2O Vapour Absorption Refr...
Comparison of the Performances of NH3-H20 and Libr-H2O Vapour Absorption Refr...IJERA Editor
ย 
In vitro callus induction of Melothria purpusilla, a traditional medicinal pl...
In vitro callus induction of Melothria purpusilla, a traditional medicinal pl...In vitro callus induction of Melothria purpusilla, a traditional medicinal pl...
In vitro callus induction of Melothria purpusilla, a traditional medicinal pl...IJERA Editor
ย 
Blind Separation of Twin Fetal Heartbeats in an Electrocardiogram using the F...
Blind Separation of Twin Fetal Heartbeats in an Electrocardiogram using the F...Blind Separation of Twin Fetal Heartbeats in an Electrocardiogram using the F...
Blind Separation of Twin Fetal Heartbeats in an Electrocardiogram using the F...IJERA Editor
ย 
โ€œ Sedimentology and geochemistry of recent alluvium of the wadi Beht mean (Fu...
โ€œ Sedimentology and geochemistry of recent alluvium of the wadi Beht mean (Fu...โ€œ Sedimentology and geochemistry of recent alluvium of the wadi Beht mean (Fu...
โ€œ Sedimentology and geochemistry of recent alluvium of the wadi Beht mean (Fu...IJERA Editor
ย 
Removal of Cu(II) Ions from Aqueous Solutions by Adsorption Onto Activated Ca...
Removal of Cu(II) Ions from Aqueous Solutions by Adsorption Onto Activated Ca...Removal of Cu(II) Ions from Aqueous Solutions by Adsorption Onto Activated Ca...
Removal of Cu(II) Ions from Aqueous Solutions by Adsorption Onto Activated Ca...IJERA Editor
ย 
Application of Fuzzy Algebra in Coding Theory
Application of Fuzzy Algebra in Coding TheoryApplication of Fuzzy Algebra in Coding Theory
Application of Fuzzy Algebra in Coding TheoryIJERA Editor
ย 
Integrated Water-Less Management of Night Soil for Depollution of Water Resou...
Integrated Water-Less Management of Night Soil for Depollution of Water Resou...Integrated Water-Less Management of Night Soil for Depollution of Water Resou...
Integrated Water-Less Management of Night Soil for Depollution of Water Resou...IJERA Editor
ย 
Modelling and Analysis of Single Diode Photovoltaic Module using MATLAB/Simulink
Modelling and Analysis of Single Diode Photovoltaic Module using MATLAB/SimulinkModelling and Analysis of Single Diode Photovoltaic Module using MATLAB/Simulink
Modelling and Analysis of Single Diode Photovoltaic Module using MATLAB/SimulinkIJERA Editor
ย 
Modelling and Simulation of DFIG for Wind Energy Generation Using Stator Volt...
Modelling and Simulation of DFIG for Wind Energy Generation Using Stator Volt...Modelling and Simulation of DFIG for Wind Energy Generation Using Stator Volt...
Modelling and Simulation of DFIG for Wind Energy Generation Using Stator Volt...IJERA Editor
ย 
Microtomography of Deciduous Teeth Enamel
Microtomography of Deciduous Teeth EnamelMicrotomography of Deciduous Teeth Enamel
Microtomography of Deciduous Teeth EnamelIJERA Editor
ย 
Transient Stability Analysis of IEEE 9 Bus System in Power World Simulator
Transient Stability Analysis of IEEE 9 Bus System in Power World SimulatorTransient Stability Analysis of IEEE 9 Bus System in Power World Simulator
Transient Stability Analysis of IEEE 9 Bus System in Power World SimulatorIJERA Editor
ย 

Viewers also liked (19)

Adaptive Relay Scheme Based on Channel State in Dual-Hop System
Adaptive Relay Scheme Based on Channel State in Dual-Hop SystemAdaptive Relay Scheme Based on Channel State in Dual-Hop System
Adaptive Relay Scheme Based on Channel State in Dual-Hop System
ย 
CO2 Capture Using Activated Alumina in Gasoline Passenger Vehicles
CO2 Capture Using Activated Alumina in Gasoline Passenger VehiclesCO2 Capture Using Activated Alumina in Gasoline Passenger Vehicles
CO2 Capture Using Activated Alumina in Gasoline Passenger Vehicles
ย 
The Effect of Temperature and Rock Permeability on Oil-Water Relative Permeab...
The Effect of Temperature and Rock Permeability on Oil-Water Relative Permeab...The Effect of Temperature and Rock Permeability on Oil-Water Relative Permeab...
The Effect of Temperature and Rock Permeability on Oil-Water Relative Permeab...
ย 
An Improved Explicit Profile Matching In Mobile Social Networks
An Improved Explicit Profile Matching In Mobile Social NetworksAn Improved Explicit Profile Matching In Mobile Social Networks
An Improved Explicit Profile Matching In Mobile Social Networks
ย 
Clock Gating Cells for Low Power Scan Testing By Dft Technique
Clock Gating Cells for Low Power Scan Testing By Dft TechniqueClock Gating Cells for Low Power Scan Testing By Dft Technique
Clock Gating Cells for Low Power Scan Testing By Dft Technique
ย 
Analysis of Changing Land Use Land Cover in Salinity Affected Coastal Region
Analysis of Changing Land Use Land Cover in Salinity Affected Coastal RegionAnalysis of Changing Land Use Land Cover in Salinity Affected Coastal Region
Analysis of Changing Land Use Land Cover in Salinity Affected Coastal Region
ย 
Design Optimization of Hydraulic Press Plate using Finite Element Analysis
Design Optimization of Hydraulic Press Plate using Finite Element AnalysisDesign Optimization of Hydraulic Press Plate using Finite Element Analysis
Design Optimization of Hydraulic Press Plate using Finite Element Analysis
ย 
Remediation of contaminated soil using soil washing-a review
Remediation of contaminated soil using soil washing-a reviewRemediation of contaminated soil using soil washing-a review
Remediation of contaminated soil using soil washing-a review
ย 
Comparison of the Performances of NH3-H20 and Libr-H2O Vapour Absorption Refr...
Comparison of the Performances of NH3-H20 and Libr-H2O Vapour Absorption Refr...Comparison of the Performances of NH3-H20 and Libr-H2O Vapour Absorption Refr...
Comparison of the Performances of NH3-H20 and Libr-H2O Vapour Absorption Refr...
ย 
In vitro callus induction of Melothria purpusilla, a traditional medicinal pl...
In vitro callus induction of Melothria purpusilla, a traditional medicinal pl...In vitro callus induction of Melothria purpusilla, a traditional medicinal pl...
In vitro callus induction of Melothria purpusilla, a traditional medicinal pl...
ย 
Blind Separation of Twin Fetal Heartbeats in an Electrocardiogram using the F...
Blind Separation of Twin Fetal Heartbeats in an Electrocardiogram using the F...Blind Separation of Twin Fetal Heartbeats in an Electrocardiogram using the F...
Blind Separation of Twin Fetal Heartbeats in an Electrocardiogram using the F...
ย 
โ€œ Sedimentology and geochemistry of recent alluvium of the wadi Beht mean (Fu...
โ€œ Sedimentology and geochemistry of recent alluvium of the wadi Beht mean (Fu...โ€œ Sedimentology and geochemistry of recent alluvium of the wadi Beht mean (Fu...
โ€œ Sedimentology and geochemistry of recent alluvium of the wadi Beht mean (Fu...
ย 
Removal of Cu(II) Ions from Aqueous Solutions by Adsorption Onto Activated Ca...
Removal of Cu(II) Ions from Aqueous Solutions by Adsorption Onto Activated Ca...Removal of Cu(II) Ions from Aqueous Solutions by Adsorption Onto Activated Ca...
Removal of Cu(II) Ions from Aqueous Solutions by Adsorption Onto Activated Ca...
ย 
Application of Fuzzy Algebra in Coding Theory
Application of Fuzzy Algebra in Coding TheoryApplication of Fuzzy Algebra in Coding Theory
Application of Fuzzy Algebra in Coding Theory
ย 
Integrated Water-Less Management of Night Soil for Depollution of Water Resou...
Integrated Water-Less Management of Night Soil for Depollution of Water Resou...Integrated Water-Less Management of Night Soil for Depollution of Water Resou...
Integrated Water-Less Management of Night Soil for Depollution of Water Resou...
ย 
Modelling and Analysis of Single Diode Photovoltaic Module using MATLAB/Simulink
Modelling and Analysis of Single Diode Photovoltaic Module using MATLAB/SimulinkModelling and Analysis of Single Diode Photovoltaic Module using MATLAB/Simulink
Modelling and Analysis of Single Diode Photovoltaic Module using MATLAB/Simulink
ย 
Modelling and Simulation of DFIG for Wind Energy Generation Using Stator Volt...
Modelling and Simulation of DFIG for Wind Energy Generation Using Stator Volt...Modelling and Simulation of DFIG for Wind Energy Generation Using Stator Volt...
Modelling and Simulation of DFIG for Wind Energy Generation Using Stator Volt...
ย 
Microtomography of Deciduous Teeth Enamel
Microtomography of Deciduous Teeth EnamelMicrotomography of Deciduous Teeth Enamel
Microtomography of Deciduous Teeth Enamel
ย 
Transient Stability Analysis of IEEE 9 Bus System in Power World Simulator
Transient Stability Analysis of IEEE 9 Bus System in Power World SimulatorTransient Stability Analysis of IEEE 9 Bus System in Power World Simulator
Transient Stability Analysis of IEEE 9 Bus System in Power World Simulator
ย 

Similar to Identification of Multiple Harmonic Sources in Electric Power System with Erroneous Measurements Using Several Indices

Harmoni resonance mode analysis
Harmoni resonance mode analysisHarmoni resonance mode analysis
Harmoni resonance mode analysisJose Rubens Macedo Jr
ย 
A Fast Localization of Multiple Harmonic Sources for Rectifier Loads by Utili...
A Fast Localization of Multiple Harmonic Sources for Rectifier Loads by Utili...A Fast Localization of Multiple Harmonic Sources for Rectifier Loads by Utili...
A Fast Localization of Multiple Harmonic Sources for Rectifier Loads by Utili...TELKOMNIKA JOURNAL
ย 
chap3.ppt
chap3.pptchap3.ppt
chap3.pptHusamAljabli
ย 
High Impedance Fault Detection in Power Distribution Networks with Use of Cur...
High Impedance Fault Detection in Power Distribution Networks with Use of Cur...High Impedance Fault Detection in Power Distribution Networks with Use of Cur...
High Impedance Fault Detection in Power Distribution Networks with Use of Cur...ijeei-iaes
ย 
An Approach for Power Flow Analysis of Radial Distribution Networks
An Approach for Power Flow Analysis of Radial Distribution NetworksAn Approach for Power Flow Analysis of Radial Distribution Networks
An Approach for Power Flow Analysis of Radial Distribution Networksresearchinventy
ย 
Performance analysis of cooperative spectrum sensing using double dynamic thr...
Performance analysis of cooperative spectrum sensing using double dynamic thr...Performance analysis of cooperative spectrum sensing using double dynamic thr...
Performance analysis of cooperative spectrum sensing using double dynamic thr...IAESIJAI
ย 
Fdtd calculation model for the transient analyses of grounding systems
Fdtd calculation model for the transient analyses of grounding systemsFdtd calculation model for the transient analyses of grounding systems
Fdtd calculation model for the transient analyses of grounding systemsHimmelstern
ย 
calculation of currents in nanowires
calculation of currents in nanowirescalculation of currents in nanowires
calculation of currents in nanowiresVorname Nachname
ย 
Harmonic Analysis Techniques of Power System-A Review
Harmonic Analysis Techniques of Power System-A ReviewHarmonic Analysis Techniques of Power System-A Review
Harmonic Analysis Techniques of Power System-A ReviewIRJET Journal
ย 
Entropy Based Assessment of Hydrometric Network Using Normal and Log-normal D...
Entropy Based Assessment of Hydrometric Network Using Normal and Log-normal D...Entropy Based Assessment of Hydrometric Network Using Normal and Log-normal D...
Entropy Based Assessment of Hydrometric Network Using Normal and Log-normal D...mathsjournal
ย 
ENTROPY BASED ASSESSMENT OF HYDROMETRIC NETWORK USING NORMAL AND LOG-NORMAL D...
ENTROPY BASED ASSESSMENT OF HYDROMETRIC NETWORK USING NORMAL AND LOG-NORMAL D...ENTROPY BASED ASSESSMENT OF HYDROMETRIC NETWORK USING NORMAL AND LOG-NORMAL D...
ENTROPY BASED ASSESSMENT OF HYDROMETRIC NETWORK USING NORMAL AND LOG-NORMAL D...mathsjournal
ย 
ENTROPY BASED ASSESSMENT OF HYDROMETRIC NETWORK USING NORMAL AND LOG-NORMAL D...
ENTROPY BASED ASSESSMENT OF HYDROMETRIC NETWORK USING NORMAL AND LOG-NORMAL D...ENTROPY BASED ASSESSMENT OF HYDROMETRIC NETWORK USING NORMAL AND LOG-NORMAL D...
ENTROPY BASED ASSESSMENT OF HYDROMETRIC NETWORK USING NORMAL AND LOG-NORMAL D...mathsjournal
ย 
Entropy Based Assesment Of Hydromatric Networks Normal And Log Normal Distrib...
Entropy Based Assesment Of Hydromatric Networks Normal And Log Normal Distrib...Entropy Based Assesment Of Hydromatric Networks Normal And Log Normal Distrib...
Entropy Based Assesment Of Hydromatric Networks Normal And Log Normal Distrib...mathsjournal
ย 
ENTROPY BASED ASSESSMENT OF HYDROMETRIC NETWORK USING NORMAL AND LOG-NORMAL D...
ENTROPY BASED ASSESSMENT OF HYDROMETRIC NETWORK USING NORMAL AND LOG-NORMAL D...ENTROPY BASED ASSESSMENT OF HYDROMETRIC NETWORK USING NORMAL AND LOG-NORMAL D...
ENTROPY BASED ASSESSMENT OF HYDROMETRIC NETWORK USING NORMAL AND LOG-NORMAL D...mathsjournal
ย 
ENTROPY BASED ASSESSMENT OF HYDROMETRIC NETWORK USING NORMAL AND LOG-NORMAL D...
ENTROPY BASED ASSESSMENT OF HYDROMETRIC NETWORK USING NORMAL AND LOG-NORMAL D...ENTROPY BASED ASSESSMENT OF HYDROMETRIC NETWORK USING NORMAL AND LOG-NORMAL D...
ENTROPY BASED ASSESSMENT OF HYDROMETRIC NETWORK USING NORMAL AND LOG-NORMAL D...mathsjournal
ย 
ENTROPY BASED ASSESSMENT OF HYDROMETRIC NETWORK USING NORMAL AND LOG-NORMAL D...
ENTROPY BASED ASSESSMENT OF HYDROMETRIC NETWORK USING NORMAL AND LOG-NORMAL D...ENTROPY BASED ASSESSMENT OF HYDROMETRIC NETWORK USING NORMAL AND LOG-NORMAL D...
ENTROPY BASED ASSESSMENT OF HYDROMETRIC NETWORK USING NORMAL AND LOG-NORMAL D...mathsjournal
ย 
760da4_120dd9cb4b6043f8a4d8ce27ac4d8ae6
760da4_120dd9cb4b6043f8a4d8ce27ac4d8ae6760da4_120dd9cb4b6043f8a4d8ce27ac4d8ae6
760da4_120dd9cb4b6043f8a4d8ce27ac4d8ae6Alexander Barriga, M.S.
ย 
Electrochemical methods: Environmental Analysis
Electrochemical methods: Environmental Analysis Electrochemical methods: Environmental Analysis
Electrochemical methods: Environmental Analysis Almas Tamake
ย 

Similar to Identification of Multiple Harmonic Sources in Electric Power System with Erroneous Measurements Using Several Indices (20)

Harmoni resonance mode analysis
Harmoni resonance mode analysisHarmoni resonance mode analysis
Harmoni resonance mode analysis
ย 
A Fast Localization of Multiple Harmonic Sources for Rectifier Loads by Utili...
A Fast Localization of Multiple Harmonic Sources for Rectifier Loads by Utili...A Fast Localization of Multiple Harmonic Sources for Rectifier Loads by Utili...
A Fast Localization of Multiple Harmonic Sources for Rectifier Loads by Utili...
ย 
Lect. 6 method of quantitative analysis
Lect. 6 method of quantitative analysisLect. 6 method of quantitative analysis
Lect. 6 method of quantitative analysis
ย 
chap3.ppt
chap3.pptchap3.ppt
chap3.ppt
ย 
High Impedance Fault Detection in Power Distribution Networks with Use of Cur...
High Impedance Fault Detection in Power Distribution Networks with Use of Cur...High Impedance Fault Detection in Power Distribution Networks with Use of Cur...
High Impedance Fault Detection in Power Distribution Networks with Use of Cur...
ย 
An Approach for Power Flow Analysis of Radial Distribution Networks
An Approach for Power Flow Analysis of Radial Distribution NetworksAn Approach for Power Flow Analysis of Radial Distribution Networks
An Approach for Power Flow Analysis of Radial Distribution Networks
ย 
Performance analysis of cooperative spectrum sensing using double dynamic thr...
Performance analysis of cooperative spectrum sensing using double dynamic thr...Performance analysis of cooperative spectrum sensing using double dynamic thr...
Performance analysis of cooperative spectrum sensing using double dynamic thr...
ย 
Fdtd calculation model for the transient analyses of grounding systems
Fdtd calculation model for the transient analyses of grounding systemsFdtd calculation model for the transient analyses of grounding systems
Fdtd calculation model for the transient analyses of grounding systems
ย 
calculation of currents in nanowires
calculation of currents in nanowirescalculation of currents in nanowires
calculation of currents in nanowires
ย 
Harmonic Analysis Techniques of Power System-A Review
Harmonic Analysis Techniques of Power System-A ReviewHarmonic Analysis Techniques of Power System-A Review
Harmonic Analysis Techniques of Power System-A Review
ย 
Entropy Based Assessment of Hydrometric Network Using Normal and Log-normal D...
Entropy Based Assessment of Hydrometric Network Using Normal and Log-normal D...Entropy Based Assessment of Hydrometric Network Using Normal and Log-normal D...
Entropy Based Assessment of Hydrometric Network Using Normal and Log-normal D...
ย 
ENTROPY BASED ASSESSMENT OF HYDROMETRIC NETWORK USING NORMAL AND LOG-NORMAL D...
ENTROPY BASED ASSESSMENT OF HYDROMETRIC NETWORK USING NORMAL AND LOG-NORMAL D...ENTROPY BASED ASSESSMENT OF HYDROMETRIC NETWORK USING NORMAL AND LOG-NORMAL D...
ENTROPY BASED ASSESSMENT OF HYDROMETRIC NETWORK USING NORMAL AND LOG-NORMAL D...
ย 
ENTROPY BASED ASSESSMENT OF HYDROMETRIC NETWORK USING NORMAL AND LOG-NORMAL D...
ENTROPY BASED ASSESSMENT OF HYDROMETRIC NETWORK USING NORMAL AND LOG-NORMAL D...ENTROPY BASED ASSESSMENT OF HYDROMETRIC NETWORK USING NORMAL AND LOG-NORMAL D...
ENTROPY BASED ASSESSMENT OF HYDROMETRIC NETWORK USING NORMAL AND LOG-NORMAL D...
ย 
Entropy Based Assesment Of Hydromatric Networks Normal And Log Normal Distrib...
Entropy Based Assesment Of Hydromatric Networks Normal And Log Normal Distrib...Entropy Based Assesment Of Hydromatric Networks Normal And Log Normal Distrib...
Entropy Based Assesment Of Hydromatric Networks Normal And Log Normal Distrib...
ย 
ENTROPY BASED ASSESSMENT OF HYDROMETRIC NETWORK USING NORMAL AND LOG-NORMAL D...
ENTROPY BASED ASSESSMENT OF HYDROMETRIC NETWORK USING NORMAL AND LOG-NORMAL D...ENTROPY BASED ASSESSMENT OF HYDROMETRIC NETWORK USING NORMAL AND LOG-NORMAL D...
ENTROPY BASED ASSESSMENT OF HYDROMETRIC NETWORK USING NORMAL AND LOG-NORMAL D...
ย 
ENTROPY BASED ASSESSMENT OF HYDROMETRIC NETWORK USING NORMAL AND LOG-NORMAL D...
ENTROPY BASED ASSESSMENT OF HYDROMETRIC NETWORK USING NORMAL AND LOG-NORMAL D...ENTROPY BASED ASSESSMENT OF HYDROMETRIC NETWORK USING NORMAL AND LOG-NORMAL D...
ENTROPY BASED ASSESSMENT OF HYDROMETRIC NETWORK USING NORMAL AND LOG-NORMAL D...
ย 
ENTROPY BASED ASSESSMENT OF HYDROMETRIC NETWORK USING NORMAL AND LOG-NORMAL D...
ENTROPY BASED ASSESSMENT OF HYDROMETRIC NETWORK USING NORMAL AND LOG-NORMAL D...ENTROPY BASED ASSESSMENT OF HYDROMETRIC NETWORK USING NORMAL AND LOG-NORMAL D...
ENTROPY BASED ASSESSMENT OF HYDROMETRIC NETWORK USING NORMAL AND LOG-NORMAL D...
ย 
760da4_120dd9cb4b6043f8a4d8ce27ac4d8ae6
760da4_120dd9cb4b6043f8a4d8ce27ac4d8ae6760da4_120dd9cb4b6043f8a4d8ce27ac4d8ae6
760da4_120dd9cb4b6043f8a4d8ce27ac4d8ae6
ย 
ac400907q.pdf
ac400907q.pdfac400907q.pdf
ac400907q.pdf
ย 
Electrochemical methods: Environmental Analysis
Electrochemical methods: Environmental Analysis Electrochemical methods: Environmental Analysis
Electrochemical methods: Environmental Analysis
ย 

Recently uploaded

VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Bookingdharasingh5698
ย 
Thermal Engineering Unit - I & II . ppt
Thermal Engineering  Unit - I & II . pptThermal Engineering  Unit - I & II . ppt
Thermal Engineering Unit - I & II . pptDineshKumar4165
ย 
22-prompt engineering noted slide shown.pdf
22-prompt engineering noted slide shown.pdf22-prompt engineering noted slide shown.pdf
22-prompt engineering noted slide shown.pdf203318pmpc
ย 
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfKamal Acharya
ย 
Call Girls In Bangalore โ˜Ž 7737669865 ๐Ÿฅต Book Your One night Stand
Call Girls In Bangalore โ˜Ž 7737669865 ๐Ÿฅต Book Your One night StandCall Girls In Bangalore โ˜Ž 7737669865 ๐Ÿฅต Book Your One night Stand
Call Girls In Bangalore โ˜Ž 7737669865 ๐Ÿฅต Book Your One night Standamitlee9823
ย 
Integrated Test Rig For HTFE-25 - Neometrix
Integrated Test Rig For HTFE-25 - NeometrixIntegrated Test Rig For HTFE-25 - Neometrix
Integrated Test Rig For HTFE-25 - NeometrixNeometrix_Engineering_Pvt_Ltd
ย 
Minimum and Maximum Modes of microprocessor 8086
Minimum and Maximum Modes of microprocessor 8086Minimum and Maximum Modes of microprocessor 8086
Minimum and Maximum Modes of microprocessor 8086anil_gaur
ย 
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXssuser89054b
ย 
data_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdfdata_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdfJiananWang21
ย 
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Bookingdharasingh5698
ย 
Employee leave management system project.
Employee leave management system project.Employee leave management system project.
Employee leave management system project.Kamal Acharya
ย 
Block diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.pptBlock diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.pptNANDHAKUMARA10
ย 
Call Girls in Ramesh Nagar Delhi ๐Ÿ’ฏ Call Us ๐Ÿ”9953056974 ๐Ÿ” Escort Service
Call Girls in Ramesh Nagar Delhi ๐Ÿ’ฏ Call Us ๐Ÿ”9953056974 ๐Ÿ” Escort ServiceCall Girls in Ramesh Nagar Delhi ๐Ÿ’ฏ Call Us ๐Ÿ”9953056974 ๐Ÿ” Escort Service
Call Girls in Ramesh Nagar Delhi ๐Ÿ’ฏ Call Us ๐Ÿ”9953056974 ๐Ÿ” Escort Service9953056974 Low Rate Call Girls In Saket, Delhi NCR
ย 
University management System project report..pdf
University management System project report..pdfUniversity management System project report..pdf
University management System project report..pdfKamal Acharya
ย 
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...SUHANI PANDEY
ย 
A Study of Urban Area Plan for Pabna Municipality
A Study of Urban Area Plan for Pabna MunicipalityA Study of Urban Area Plan for Pabna Municipality
A Study of Urban Area Plan for Pabna MunicipalityMorshed Ahmed Rahath
ย 
UNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its PerformanceUNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its Performancesivaprakash250
ย 
Thermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - VThermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - VDineshKumar4165
ย 

Recently uploaded (20)

Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024
ย 
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
ย 
Thermal Engineering Unit - I & II . ppt
Thermal Engineering  Unit - I & II . pptThermal Engineering  Unit - I & II . ppt
Thermal Engineering Unit - I & II . ppt
ย 
22-prompt engineering noted slide shown.pdf
22-prompt engineering noted slide shown.pdf22-prompt engineering noted slide shown.pdf
22-prompt engineering noted slide shown.pdf
ย 
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ย 
Call Girls In Bangalore โ˜Ž 7737669865 ๐Ÿฅต Book Your One night Stand
Call Girls In Bangalore โ˜Ž 7737669865 ๐Ÿฅต Book Your One night StandCall Girls In Bangalore โ˜Ž 7737669865 ๐Ÿฅต Book Your One night Stand
Call Girls In Bangalore โ˜Ž 7737669865 ๐Ÿฅต Book Your One night Stand
ย 
Integrated Test Rig For HTFE-25 - Neometrix
Integrated Test Rig For HTFE-25 - NeometrixIntegrated Test Rig For HTFE-25 - Neometrix
Integrated Test Rig For HTFE-25 - Neometrix
ย 
Minimum and Maximum Modes of microprocessor 8086
Minimum and Maximum Modes of microprocessor 8086Minimum and Maximum Modes of microprocessor 8086
Minimum and Maximum Modes of microprocessor 8086
ย 
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
ย 
data_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdfdata_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdf
ย 
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
ย 
Employee leave management system project.
Employee leave management system project.Employee leave management system project.
Employee leave management system project.
ย 
Block diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.pptBlock diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.ppt
ย 
(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7
(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7
(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7
ย 
Call Girls in Ramesh Nagar Delhi ๐Ÿ’ฏ Call Us ๐Ÿ”9953056974 ๐Ÿ” Escort Service
Call Girls in Ramesh Nagar Delhi ๐Ÿ’ฏ Call Us ๐Ÿ”9953056974 ๐Ÿ” Escort ServiceCall Girls in Ramesh Nagar Delhi ๐Ÿ’ฏ Call Us ๐Ÿ”9953056974 ๐Ÿ” Escort Service
Call Girls in Ramesh Nagar Delhi ๐Ÿ’ฏ Call Us ๐Ÿ”9953056974 ๐Ÿ” Escort Service
ย 
University management System project report..pdf
University management System project report..pdfUniversity management System project report..pdf
University management System project report..pdf
ย 
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
ย 
A Study of Urban Area Plan for Pabna Municipality
A Study of Urban Area Plan for Pabna MunicipalityA Study of Urban Area Plan for Pabna Municipality
A Study of Urban Area Plan for Pabna Municipality
ย 
UNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its PerformanceUNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its Performance
ย 
Thermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - VThermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - V
ย 

Identification of Multiple Harmonic Sources in Electric Power System with Erroneous Measurements Using Several Indices

  • 1. Luis Alberto Hernรกndez. Int. Journal of Engineering Research and Applications www.ijera.com ISSN: 2248-9622, Vol. 6, Issue 4, (Part - 2) April 2016, pp.28-34 www.ijera.com 28 | P a g e Identification of Multiple Harmonic Sources in Electric Power System with Erroneous Measurements Using Several Indices Luis Alberto Hernรกndez Armenta*1 , David Romero Romero1 1 Instituto Politรฉcnico Nacional Electrical Engineering Department, Graduate Studies and Research Section, ESIME Zacatenco, Mexico. ABSTRACT This Article shows that the current Total Harmonic Distortion (THD) can be used reliably as index to identify the location of multiple harmonic sources in a power network. It isproved that the current THD locate the harmonic sources with aยฑ1%uniformly distributed erroneous measurement. Current THD, Euclidean norm and the magnitude of the nodal harmonic current are compared as indices to identify harmonic sources in Electric Power Systems. It is shown that with an erroneous measurement of ยฑ1%, uniformly distributed, it is not possible to locate multipleharmonic sources using the Euclidean norm and the nodal harmonic current.A 30 nodes system with three harmonic sources is tested with de Heydtโ€™s method, the Euclidean norm and the current THD. Keywords: Harmonic, Electric Power System, Current injections method, THD, Euclidean norm, Static Vars Compensator (SVC). I. INTRODUCTION Due to the increase of nonlinear loads and power electronic controlled devices, different methods to locate harmonic sources in Power Systems have been developed [1-19].These methods can be used to locate harmonic sources, solve harmonic power flows, and solve problems generated by the harmonic sources. Utility companies cannot always locate harmonic sourcesthatdoes not meet quality standards. Heydt G.T. in [1] propose a method to locate harmonic sources in Electric Power System, based on the current injection method, proposed by Mahmoud in [20].This method states that the nodes where there is a harmonic source will have a nodal harmonic current magnitude different to zero. This asumption is used as an index to identify harmonic sources [1- 19], i.e., the estimators locate the harmonic sources using the nodal harmonic current magnitude as index. Harmonic voltage and current measurements are necessaryin these methods to locate harmonic sources. Other articles propose to use other measurements, like line harmonic current and harmonic power flows [10, 12, 16]. Heydt [1] and Nguyen [2] methodologies were not tested with measurement error presence. The proposed methods to locate harmonic sources are susceptible to erroneous measurements, this leads to an unreliable identification of harmonic sources [10- 14]. Because of this problem a different solution has been proposed, such as weighting measurements [9- 11] or the Euclidean norm [12]. The use of current THD as an index to locate harmonic sources in Electric Power Systems is proposed in this paper [25]. The current THD is compared with the Euclidean norm, as index to identify harmonic sources. Prior to the calculation of this index, the nodal harmonic currents and voltages must be calculated usingHeydtโ€™s method. IEEE 30 nodes system was tested [26], with three Static Vars Compensator (SVC), and with erroneous measurements of ยฑ1% distributed uniformly, like Kanao et. Al. in [10]. The results in this paper show that the current THD can be used as a reliable index to locate harmonic sources in Electric Power Systems, even with erroneous measurements. When the current THD is greater than 2.5% (limit established by IEEE 519-1992 standard [21]), the harmonic sources were identified consistently. When the Euclidean norm and the nodal harmonic current magnitude are used as index for the identification of harmonic sources, it is not possible locate the harmonic sources with erroneous measurements. II. HEYDTโ€™S PROPOSED METHOD FOR THE IDENTIFICATION OF HARMONIC SOURCES Heydtโ€™s proposed method in [1], is based on the current injection technique [20] to solve the harmonic power flow method, using the Kirchoffโ€™s laws, as follows: ๐‘ฐ ๐’‰ = ๐’€ ๐’‰ ๐‘ฝ ๐’‰ (1) Where: ๐‘ฐ ๐’‰ โˆˆ โ„‚ ๐’ , is a vector that contains the nodal harmonic currents injected for the harmonic sources. RESEARCH ARTICLE OPEN ACCESS
  • 2. Luis Alberto Hernรกndez. Int. Journal of Engineering Research and Applications www.ijera.com ISSN: 2248-9622, Vol. 6, Issue 4, (Part - 2) April 2016, pp.28-34 www.ijera.com 29 | P a g e ๐’€ ๐’‰ โˆˆ โ„‚ ๐’ร—๐’ ,is the ๐’€ ๐’ƒ๐’–๐’” matrix affected by the harmonics in the net. ๐‘ฝ ๐’‰ โˆˆ โ„‚ ๐’ , is the nodal harmonic voltage vector. ๐’,is the system node number. ๐’‰,is the harmonic number. Rearranging eq. (1), grouping the known or measured data, and the unknown data, eq. 2 is obtained. ๐‘ฐ ๐’ƒ๐’– ๐’‰ ๐‘ฝ ๐’ƒ๐’– ๐’‰ = ๐’€ ๐’‰ ๐‘ฝ ๐’‰ = ๐‘ฎ ๐’‰ ๐‘ฏ ๐’‰ ๐‘ฑ ๐’‰ ๐‘ฒ ๐’‰ ๐‘ฝ ๐’ƒ๐’– ๐’‰ ๐‘ฝ ๐’ƒ๐’Œ ๐’‰ (2) Where: ๐‘ฐ ๐’ƒ๐’Œ ๐’‰ โˆˆ โ„‚ ๐’Ž , ๐‘ฝ ๐’ƒ๐’Œ ๐’‰ โˆˆ โ„‚ ๐’Ž are the nodal harmonic current and voltage measured vectors. ๐‘ฐ ๐’ƒ๐’– ๐’‰ โˆˆ โ„‚ ๐’– , ๐‘ฝ ๐’ƒ๐’– ๐’‰ โˆˆ โ„‚ ๐’– ,are the nodal harmonic current and voltage unknown vectors. ๐‘ฎ ๐’‰ โˆˆ โ„‚ ๐’–ร—๐’– , ๐‘ฏ ๐’‰ โˆˆ โ„‚ ๐’–ร—๐’Ž , ๐‘ฑ ๐’‰ โˆˆ โ„‚ ๐’Žร—๐’– , ๐‘ฒ ๐’‰ โˆˆ โ„‚ ๐’Žร—๐’Ž ,are sub-matrices obtained when the ๐’€ ๐’‰ matrix is rearranged. ๐’Ž,is the total nodal measurement. ๐’–,is the total unknown data. Solving with Least Squares sense: ๐‘ฐ ๐’ƒ๐’– ๐’‰ = ๐‘ฎ ๐’‰ ๐‘ฑ ๐’‰ + ๐‘ฐ ๐’ƒ๐’Œ ๐’‰ + โˆ’๐‘ฎ ๐’‰ ๐‘ฑ ๐’‰ + ๐‘ฒ ๐’‰ + ๐‘ฏ ๐’‰ ๐‘ฝ ๐’ƒ๐’Œ ๐’‰ (3) The pseudoinverse of ๐‘ฑmust be used to solve (3), because ๐‘ฑ isnot a square matrix [1, 23-24]. Where: ๐‘ฑ+ ๐’‰ โˆˆ โ„‚ ๐’–ร—๐’Ž ,is ๐‘ฑ ๐’‰ pseudoinverse and is defined as๐‘ฑ ๐’‰ + = [๐‘ฑ ๐’‰ ๐‘ป ๐‘ฑ ๐’‰]โˆ’๐Ÿ ๐‘ฑ ๐’‰ ๐‘ป [1, 23-24]. The process is not iterative, so the result to each harmonic in the system is obtained directly. Figure 1, shows the flow chart that resumes the Heydtโ€™s method proposed to locate harmonic sources. Unknown nodal harmonic currents are estimated with this method, so it is necessary to use (1) to calculate the unknown nodal harmonic voltages. Heydtโ€™s method propose the nodal harmonic current magnitude as index to locate harmonic sources in Electric Power Systems, i.e., the node where there isnot a harmonic source connected should have a harmonic nodal current magnitude equal or closer to zero. So the node with a harmonic source will have a harmonic nodal current magnitude different of zero. Unfortunately, Heydtโ€™s method fails when erroneous measurements are present [9-12, 14,25].Then,it is necessary to propose other indexes, such as the Euclidean norm [12] or current THD [25]. Heydtโ€™s method not only provides the harmonic source location, it mayidentify the kind of harmonic sources too. Unfortunately, in the presence of erroneous measurementsit isnot possible to locate unknown harmonic sources. Start Read system data Read measurements data h=total harmonic number Yh is calculated G, H, J, K are calculated J+ is calculated Ibu is calculated No Print results End Yes Ih is calculated Fig. 1. Heydtโ€™s method flow chart [1]. III. HARMONIC SOURCE LOCATION USING THE EUCLIDEAN NORM The Euclidean norm was proposed in [12] as an index to identify harmonic sources in an Electric Power System. Prior to calculate the Euclidian norm, the nodal harmonic current must be known, so it can be used a harmonic estimation method. In this paper itโ€™ll be used the Heydtโ€™s method proposed in [1]. Once estimated the nodal harmonic currents, the nodes with a possible harmonic source are discriminated. The index to discriminate suspicious nodes with a harmonic source connected is the harmonic nodal current [12]. A bus with a nonzero nodal harmonic current magnitude is suspicious, where a harmonic source may be connected. When the suspicious nodes are known, there are ๐‘ possible combinations of nodes with harmonic sources connected [12]. ๐‘iscalculated with eq. (4): ๐‘ = ๐ถ1 ๐‘š + ๐ถ2 ๐‘š + โ‹ฏ + ๐ถ ๐‘š ๐‘š = ๐ถ๐‘ ๐‘š ๐‘=๐‘š ๐‘=1 (4) Where: ๐‘, is one of the ๐‘ possible combinations of nodes with harmonic sources connected. ๐‘š, is the total number of combinations of nodes with harmonic sources connected. ๐ถ1 ๐‘š is the probability of have one node with unidentified harmonic source. ๐ถ2 ๐‘š is the probability of have two node with unidentified harmonic source. ๐ถ ๐‘š ๐‘š is the probability of have ๐‘š node with unidentified harmonic source. Once obtained the ๐‘ possible combinations, the harmonic nodal voltage is calculated for each
  • 3. Luis Alberto Hernรกndez. Int. Journal of Engineering Research and Applications www.ijera.com ISSN: 2248-9622, Vol. 6, Issue 4, (Part - 2) April 2016, pp.28-34 www.ijera.com 30 | P a g e possible combination. Then, the Euclidean norm of the difference between the estimated and measured harmonic nodal voltages is calculated for the ๐‘ combinations. The harmonic sources are located in the node combination with the least Euclidean norm value. ๐‘‰โ„Ž โˆ’ ๐‘‰โ„Ž ๐‘ = ๐‘‰โ„Ž 1 โˆ’ ๐‘‰โ„Ž 1 2 + ๐‘‰โ„Ž 2 โˆ’ ๐‘‰โ„Ž 2 2 + โ‹ฏ ๐‘š๐‘’๐‘Ž๐‘  ๐‘–=1 + ๐‘‰โ„Ž ๐‘š๐‘’๐‘Ž๐‘  โˆ’ ๐‘‰โ„Ž ๐‘š๐‘’๐‘Ž๐‘  2 1/2 (5) Where: , is the Euclidean norm , is anestimated value , is a measured value ๐‘š๐‘’๐‘Ž๐‘ , is the total of measurements Figure 2 shows the flow chart of the Euclidean norm method to identify harmonic sources in Electric Power Systems. The Euclidean norm method uses the nodal harmonic voltage as index to locate harmonic sources, while the method explained before, use the nodal harmonic current. With this method it is not possible to know the kind of harmonic sources in a node, nevertheless, the nodal harmonic voltage are estimated, so it can be used (1) to know the kind of harmonic sources connected in the system. IV. HARMONIC SOURCES LOCATION USING CURRENT TOTAL HARMONIC DISTORTION (THD) THD is defined as the square root of the summation of the RMS value of the harmonics, divided by the RMS value of the fundamental. The THD is a measure that indicates the nodal harmonic pollution with respect to the fundamental, for this reason, THD can be used as index to locate harmonic sources in an Electric Power System. NO Start Read system data m = total combinations i= total measurements End Yes Euclidean norm is calculated Print results Yes NO Calculate the c posible combinations Least Euclidean norm is obtained Fig. 2. Flow chart of the Euclidean norm method to identify harmonic sources in Electric Power Systems In this paper, the current THD is proposed as an index for the identification of harmonic sources [25]. Prior to the current THD calculation, it is necessary use an estimation method to know the nodal harmonic current, hence Heydtโ€™smethod, proposed in [1], was used to estimate the nodal harmonic currents. Once the nodal harmonic currents are determined, the current THD is calculated in each Power System bus. The nodes with a current THD greater than 2.5% (limit allowed by the IEEE 519- 1992 [21]) have a harmonic source connected. The current THD is defined as: ๐‘‡๐ป๐ท = 1 ๐ผ1 ๐ผโ„Ž 2 โˆž โ„Ž=2 Where: ๐ผ1, is the fundamental current. Figure 3 shows the flow chart of the current THD method as index to identify harmonic sources in Electric Power Systems. No Start Read system data Currentt THD is calculated n = node number THD > 2.5% End Yes There is a harmonic source at node n There is not a harmonic source at node n Print results Yes No Fig. 3. Flow chart ofthe current THD method as index to identify harmonic sources in Electric Power Systems. This method is not iterative; just requires the previous knowledge of network nodal harmonic currents. The network nodal harmonic currents can be calculated using a harmonic estimation method, in this case the Heydtยดs method. With this method it is not possible to know the kind of harmonic sources connected in the system, so, the current THD only can be used as an index to locate harmonic sources. V. TEST SYSTEM IEEE 30 nodes test system is used in this paper; it is presented in Figure 4. Three harmonic sources are connected: nodes 7, 12 and 21. The three harmonic sources are SVCs.This system isutilized to test the three methods;Heydtยดs, current THD and the Euclidean norm. The test system data were taken from [26], while SVC data are available in [21] and on Table 1 of this paper. The voltage measurements are
  • 4. Luis Alberto Hernรกndez. Int. Journal of Engineering Research and Applications www.ijera.com ISSN: 2248-9622, Vol. 6, Issue 4, (Part - 2) April 2016, pp.28-34 www.ijera.com 31 | P a g e perturbed with aยฑ1% uniformily distributed error, like Kanao et. al. in [10]. In Figure 4, the nodes with nodal harmonic voltage and current measurements are marked with a black square. Table 1. Harmonic current percent of the fundamental injected by the SVC [16] Harmonic Harmonic current percent Lagging 5 7.02 46.92 7 2.5 -29.87 11 1.36 -23.75 13 0.75 71.5 17 0.62 77.12 19 0.32 173.43 23 0.43 178.02 25 0.13 -83.45 29 0.4 -80.45 VI. RESULTS VI.1. Results Obtained Using The Heydtโ€™s Method Table 2 presents the estimated harmonic nodal currents with Heydtโ€™s method. It is observed on Table 2, that it is not possible to locate the harmonic sources in the test system, because all the nodes have a harmonic current magnitude different to zero. Therefore, according to the obtained results, all the nodes without measurement have a harmonic source connected, which is incorrect, because there are harmonic sources only in nodes 7, 12 and 21. 1 2 3 4 5 6 8 11 9 13 12 16 17 2019181514 21 22 24 23 25 27 30 26 29 28 7 G G C C C10 Fig. 4. IEEE 30 nodes system VI.2. Results Obtained Using The Euclidean Norm. It is necessary to know the nodal harmonic currents in the system previously for this method. Bus Harmonic information is taken from Table 2. A node is considered suspiciouswhen it has a nonzero harmonic current magnitude. It is important to observe that all the nodes in Table 2 are suspicious, because they have a nonzero nodal harmonic current magnitude. For this case, the Euclidean norm must be calculated for the 1804 combinations. The unknowns are greater than using the current THD, which represents more complexity and computational time. Once the ๐‘possible nodes combination with a harmonic source connected is obtained, nodal harmonic voltages are calculated using equation (1) for all the possible combinations. After nodal harmonic voltages are calculated, the Euclidean norm of the difference between the estimated and measured nodal harmonic voltages is obtained. The harmonic sources are identified on the node combination with the least Euclidean norm Table 2. Harmonic currents estimated using Heydtโ€™s method. Harmonic Node Current Magnitude Current Angle 5 4 0.05244 -29.14526 7 0.51634 37.95395 8 0.01805 151.2976 10 0.05737 150.2769 12 0.47789 42.22538 15 0.08258 -32.69866 19 0.02558 146.069 21 0.5443 25.52365 24 0.07635 147.7675 26 0.02145 -30.89148 7 4 0.0042 0.53649 7 0.18975 -38.10252 8 0.00302 -165.9232 10 0.00465 -169.3179 12 0.18394 -38.87131 15 0.01551 -174.7489 19 0.00662 6.24152 21 0.17658 -43.0926 24 0.01254 5.84101 26 0.0054 -174.1768 11 4 0.00273 6.64711 7 0.0996 -34.00909 8 0.00392 -167.1774 10 0.00068 -40.87262 12 0.0951 -35.24238 15 0.00054 -38.51659 19 0.00034 141.4175 21 0.09759 -35.68853 24 0.00021 -44.86901 26 0.00017 141.272 13 4 0.00023 -120.1048 7 0.05559 61.69102 8 0.00015 -65.02871 10 0.00001 76.4007 12 0.05291 60.06713 15 0.0002 49.66085 19 0.00009 -124.4183 21 0.05408 59.46381
  • 5. Luis Alberto Hernรกndez. Int. Journal of Engineering Research and Applications www.ijera.com ISSN: 2248-9622, Vol. 6, Issue 4, (Part - 2) April 2016, pp.28-34 www.ijera.com 32 | P a g e 24 0.00007 -120.6972 26 0.00002 29.05268 17 4 0.00067 -134.5783 7 0.04602 66.97454 8 0.00151 45.22181 10 0.00005 -87.92987 12 0.04413 65.62669 15 0.00001 176.6073 19 0.00002 31.96162 21 0.04502 65.02678 24 0 31.81417 26 0 -110.9143 Harmonic Node Current Magnitude Current Angle 19 4 0.00027 -165.0147 7 0.02384 163.7968 8 0.00032 170.9907 10 0.00006 1.68469 12 0.0228 161.8754 15 0.00025 -25.59733 19 0.00004 150.676 21 0.02315 161.42 24 0.00004 -32.72941 26 0.00011 -7.59551 23 4 0.0001 55.44044 7 0.03158 168.1325 8 0.00043 150.9051 10 0.00108 19.71677 12 0.03059 166.4789 15 0.00018 -43.77839 19 0.00014 33.10193 21 0.03059 165.4211 24 0.00007 -67.372 26 0.00005 177.391 25 4 0.00002 6.96216 7 0.0096 -93.30957 8 0.00006 -160.6385 10 0.0009 -52.89224 12 0.00927 -94.73791 15 0.0002 109.3187 19 0.00011 -53.20313 21 0.00951 -94.29516 24 0.0002 98.29692 26 0.00006 104.553 29 4 0.00034 -41.29469 7 0.02975 -90.1825 8 0.00011 -130.7203 10 0.01155 -85.70278 12 0.0443 -91.70417 15 0.03299 95.28408 19 0.00589 -83.82865 21 0.01298 -102.0905 24 0.05353 92.19901 26 0.00853 98.69428 Since the number of possible nodes combination is too large, 1804, on Table 3 are listed the least Euclidean norm for up to๐‘š = 5. In Table 3, the actual node combination of harmonic sources is presented with bold letters. Table 3. Least Euclidean norm for up to five nodes with unidentified harmonic source Possi ble node combi nation Harmonic 5 7 11 13 17 with harm onic sourc es 8 0.0219 0.0014 0.0008 0 0.000 4 4, 19 0.0296 0.0071 0.0007 0 0.000 1 4, 8, 19 0.0345 0.0059 0.0002 0 0.000 3 7, 12, 21 3.12 0.3484 0.0163 0.0032 0.01 8, 15, 24, 26 0.0417 0.0035 0.0008 0 0.000 1 4, 15, 19, 24, 26 0.0422 0.0073 0.0007 0 0.000 1 Possible node combination with harmonic sources Harmonic 19 23 25 29 8 0.0001 0 0 0 4, 19 0 0 0 0.0002 4, 8, 19 0.0001 0 0 0.0002 7, 12, 21 0.0058 0.0048 0.0011 0.0196 8, 15, 24, 26 0 0 0 0 4, 15, 19, 24, 26 0 0 0 0.0002 It is noted in Table 3, that it is not possible to locate the harmonic sources in the test system using the smallest Euclidean norm. The Euclidean norm calculated for the node combination where the actual harmonic sources are connected (7, 12 and 21) is greater than the other combinations showed in Table3. Euclidean norm isnot a reliable index to locate harmonic sources in Electric Power Systems with erroneous measurements of ยฑ1% distributed uniformly. VI.3. Results Obtained Using the Euclidean Norm. Prior to the calculation of the current THD, it is necessary to know the nodal harmonic currents in the system. With the Table 2 information, the current THD in each node is calculated. Table 4 presents the current THD in each system node. As mentioned previously, the nodes with a current THD greater than 2.5% (limit allowed by the IEEE519-1992 standard [21]) have a harmonic source connected. In Table 4, nodes 7, 12 and 21 exceed the limit established of current THD, it means that there are harmonic sources connected in these nodes. Tabla 4. Current THD Node THD Node THD 1 0 16 0 2 0 17 0 3 0 18 0 4 0.165967 19 0.267643 5 0 20 0 6 0 21 4.764308
  • 6. Luis Alberto Hernรกndez. Int. Journal of Engineering Research and Applications www.ijera.com ISSN: 2248-9622, Vol. 6, Issue 4, (Part - 2) April 2016, pp.28-34 www.ijera.com 33 | P a g e 7 4.420703 22 0 8 0.062511 23 0 9 0 24 0.867507 10 0.237188 25 0 11 0 26 0.51029 12 3.143242 27 0 13 0 28 0 14 0 29 0 15 1.012626 30 0 Current THD as index to locate harmonic sources in Electric Power Systems identifies correctly the three harmonic sources connected on the test system, even in the presence of ยฑ1%erroneous measurements, uniformly distributed. With the current THD, the kind of harmonic source cannot be identified. This index only can be used to locate harmonic sources in Electric Power Systems. VII. CONCLUSIONS It is showed that the current THD locate consistently the harmonic sources in the test system, even with erroneous measurements. The current THD method to locate harmonic source is simple, it is necessary only to calculate the current THD for each network node, and determine the buses that exceed the limit proposed in the IEEE519-1992 standard. With ยฑ1% uniformly distributed erroneous measurements,it is not possible to locate the harmonic sources in the test systemusing Heydtโ€™sor the Euclidian norm method. Nevertheless, nodal harmonic currents estimated by Heydtโ€™s method can be used for other indexes like current THD or Euclidean norm. In the Euclidean norm method, when there is a big number of combinations of nodes with unidentified harmonic sources, the method becomes more complex, and may require more computational time. REFERENCES [1]. Heydt G. T. (1989)Identification of Harmonic Sources by a State Estimation Technique. Transaction on Power Delivery, Vol. 4 No.1, pp. 569 โ€“ 576, IEEE. [2]. Nguyen H. T., Yang J. J., Choi, S. S. (2010).On Harmonic State Estimation and the Evaluation of Harmonic Power Contribution from Sources. Power and Energy Society Meeting, IEEE. [3]. DU Z. P., Arrillaga J., Watson N.R., Chen S. (1999).Identification of Harmonic Sources of Power Systems Using State Estimation. Proceedings Generation Transmission and. Distribution, Vol. 146 No. 1, pp. 7 โ€“ 12 IEE. [4]. Sakis A. P., Zhang F., Zelingher S. (1994).Power System Harmonic State Estimation. Transactions on Power Delivery, Vol. 9 No. 3, pp. 1701 - 1709 IEEE. [5]. Lobos T, Kozina T, Koglin H. J. (1999).Power System Harmonic State Estimation Using Linear Least Square Method and SVD. Proceedings Generation Transmission and. Distribution, Vol. 148 No. 6, pp. 567 โ€“ 572, IEE. [6]. Zhang Y., Xu Y., Xu Y. (2011). Research on Power System Harmonic State Estimation. International Conference on Power System Technology, IEEE [7]. Liao H. (2007). Power System Harmonic State Estimation and Observability Analysis via Sparsity Maximization. Transactions on Power Systems, Vol. 22 No. 1, pp. 15 โ€“ 23, IEEE. [8]. Hou S., Xu Z., Lv H., Jiang Z., Wang L. (2006).Research into Harmonic State Estimation in Power System Based on PMU and SVD. International Conference on Power System Technology, IEEE. [9]. Moghadasian M., Mokhtari H., Baladi A. (2010).Power System Harmonic State Estimation Using WLS and SVD; A practical Approach. 14th International Conference on Harmonics and Quality of Power, IEEE. [10]. Kanao N., Yamashita M., Yanagida H., Muzykami M. (2005).Power System Harmonic Analysis Using State-Estimation Method for Japanese Field Data. Transactions on Power Delivery, Vol.2 No. 2, pp. 970 โ€“ 977, IEEE. [11]. Kent K. C., Neville R. W., Arrillaga J. (2005).Error Analysis in Static Harmonic State Estimation: A Statistical Approach. Transactions on Power Delivery, Vol. 20 No. 2, pp. 1045 โ€“ 1050, IEEE. [12]. Kumar A., Das B., Sharma J. (2004) Determination of location of Multiple Harmonic Sources in a Power System. Electric Power Delivery Systems, Vol. 26, pp. 73 โ€“ 78. ELSEVIER [13]. Jain S. K., Singh S. N. (2011). Harmonic Estimation in Emerging Power Systems: Key Issues and Challenges. Electric Power System Research, Vol. 81, pp. 1754 โ€“ 1756. ELSEVIER. [14]. Hernรกndez L. A. (2012).Harmonic sources identification using estimation method in Electric Power Systems. M.S. Thesis, SEPI- ESIME Zacatenco IPN. [15]. Arruda F. E., Nagan N., Ribeiro P. F. (2010). Three-phase Harmonic Distortion State Estimation Algorithm Based on Evolutionary Strategies. Electric Power System Research, Vol. 80 pp. 1024 โ€“ 1032. ELSEVIER
  • 7. Luis Alberto Hernรกndez. Int. Journal of Engineering Research and Applications www.ijera.com ISSN: 2248-9622, Vol. 6, Issue 4, (Part - 2) April 2016, pp.28-34 www.ijera.com 34 | P a g e [16]. Dag O., Uแธ‰ac E., Usta ร–. (2012). Harmonic Source Location and meter placement optimization by impedance network approach. Elect. Eng., Vol. 94, pp. 1 โ€“ 10. SPRINGER. [17]. Rakpenthai C., Uatrongjit S., Watson N. R., Premrudeepreechacharn S. (2013). On Harmonic State Estimation of Power System with Uncertain Network Parameters. Transaction on Power Systems, Vol. 28 No 4, pp. 4829 โ€“ 4838. IEEE. [18]. Gursor E., Niebur D. (2009). Harmonic Load Identification Using Complex Independent Component Analysis. Transactions on Power Delivery, Vol. 24, No. 1, pp. 285 โ€“ 292. IEEE [19]. Dโ€™Antona G., Muscas C., Sulis S. (2011). Localization of Nonlinear Loads in Electric Systems through Harmonic Source Estimation. Transactions on instrumentation and measurements, Vol. 60, No. 10, IEEE [20]. Mahmoud A. A., Schultz R. D. (1982). A Method for Analyzing Harmonic Distribution in A.C. Power Systems. Transactions on Power Apparatus and Systems, Vol. PAS-101 No. 6, pp 1815 - 1824 IEEE. [21]. IEEE STD 519-1992 (1993).IEEERecommended Practices and Requirements for Harmonic Control in Electrical Power Systems. IEEE. [22]. Task Force on Harmonic Modeling and Simulation (1996).Modeling and Simulation of the Propagation of Harmonics in Electric Power Networks. Transactions on Power Delivery, Vol. 11 No. 1, pp 452 โ€“ 465, IEEE. [23]. Moore R. H (1920).On the reciprocal of the general algebraic matrix. Bulletin of the American Mathematical Society, Vol. 26, pp. 394-395. [24]. Penrose R. (1955).A generalized inverse for the matrices. Proceedings of the Cambridge Philosophical Society, Vol. 51, pp. 406-413. [25]. Hernรกndez A. L. A., Romero R. D. (2015). Harmonic sources Index to locate harmonic sources in Electric Power Systems using State Estimation with Measurement Error,Computaciรณn y Sistemas, Vol. 29 No. 22. [26]. Freris L. L., Sasson A. M. (1968). Investigation of the load flow problem.IEE, Vol. 115 No. 10, pp. 1459-1470. AUTHORS Luis Alberto Hernรกndez Armenta, Electrical Engineer 2010 and Master degree 2012 from the Instituto Politรฉcnico Nacional. Actually, PH.D. student on the graduate program in Electric Engineer on the InstitutoPolitรฉcnico Nacional. Interest areas: Power Quality, Harmonic Analysis in Electric Power System, Electric Power System Analysis and State Estimation. David Romero Romero, Electrical Engineer 1974 and Master degree 1976, from the Instituto Politรฉcnico Nacional. PhD. Degree 1984 from Purdue University in Indiana. Investigator Pofessor from the graduated program in Electrical Engineer from the Instituto Politรฉcnico Nacional. Interest Areas: Electric Power Systems Stochastic Analysis, Electric Power Systems Analysis and Intelligent Control.