Quality HVAC System Installation Trust But Verify
Quality HVAC System Installation The goal for a Heating, Ventilation and Air Conditioning (HVAC) system is to provide proper air flow, heating, and cooling to each room
Instructor Barbara Collins ERH West Building Performance Consultant Certified NAHB Green Building Verifier Certified RESNET HERS Rater Energy Star Homes Partner  Certified Environments for Living Verifier
Class Objectives Understand HVAC system air leakage testing requirements in the 2009 IECC Recognize the benefits of sealing ducts for savings, system performance and indoor air quality Understand how ducts are tested for leakage Identify resources for local building departments  Identify the best techniques to seal duct systems; what inspectors should see on inspections Understand the IECC requirements for sizing of HVAC equipment
Current Code Requirements Must comply with all aspects of UL181 standards Fittings, joints & seams of duct system shall be made substantially air tight by means of tapes, mastics, gasketing or other means.
Ducts - IECC Insulation (Prescriptive) Ducts outside the building  envelope:  R-8  All other ducts:  R-6  Sealing (Mandatory) Joints and seams shall comply with IRC, Section M1601.4.1 Building framing cavities shall not be used as supply ducts
2009 IECC Duct Tightness Tests All ducts, air handlers, filter boxes and building cavities used as ducts shall be sealed (Section 403.2.2) Duct tightness shall be verified by testing  Only   Exception:  Duct tightness test is not required if the air handler and all ducts are located within conditioned space Mandatory Requirements
SEAL DUCTS,  SAVE ENERGY Sealing ducts is a cost-effective energy efficiency practice that gives a high return on investment
HVAC System Poor design and installation increases energy costs 10 –30%  Sizing Design Installation
Home Energy Use Residential energy use 22% of U.S. total  25% of carbon emissions in U.S. Heating & cooling is 40 – 60 % of home energy use
Why seal ducts Leaks waste energy and money Average system leakage  New construction  20%  Existing homes  30% Duct sealing reduces heating and cooling energy losses and saves money
Other Problems Duct leakage reduces air flow, conditioned air isn’t delivered to rooms which can cause wide temperature swings between rooms IAQ issues with return leaks drawing in air from attics, garages, crawlspaces Pressure differentials can cause excess building air leakage and back drafting
Duct Tightness Tests Post construction tests Option 1 Leakage to outdoors:  ≤8 cfm/per 100 ft 2  of conditioned floor area  OR Option 2 Total leakage:  ≤12 cfm/per 100 ft 2  of conditioned floor area Mandatory Requirements
Duct Tightness Tests Rough-in test Options Option 1 Total leakage  ≤6 cfm/per 100 ft 2  of conditioned floor area OR Option 2 If air handler not installed at time of test total air  leakage ≤4 cfm/per 100 ft 2 Mandatory Requirements
Exceptions:  Duct tightness test is not required if the air handler and all ducts are located within conditioned space Thermal Boundary is also used to define whether testing is required. Insulation installed on underside of roof sheathing, AHU and ducts in attic, can be considered within thermal boundary
Ventilation Outdoor air intakes and exhausts shall have automatic or gravity dampers that close when the ventilation system is not operating Mandatory Requirements
Test Protocol Pressurize the HVAC system, measure CFM of air required to   reach pressure Test at a pressure differential of 0.1 in w.g. (25Pa) across entire system, including manufacturer’s air handler enclosure
Test Equipment
 
 
Testing at rough-in
Testing Post Construction
Testing leakage to outside
 
Testing leakage to outside
Mastic Sealant Non-toxic – Low VOC Green credits Recommended Set time = 20 hours
More on Mastic High strength adhesive compound Usually applied by trowel, brush, caulking gun or hand 3 types- water-based; solvent-based; and two-component curing systems Water-based is the safest and easiest to use It performs as well and in some cases better than the other 2
VOCs in mastics Volatile organic compounds  In water-based mastics, the only volatile compound is water which is inorganic VOCs are infinitesimally small (not recordable) Water-based mastics pose a low health risk compared to solvent-based and two-component mastics Safer for the user, better IAQ, greener
How to apply mastic Step 1 - Clean Duct Surface  Wipe dust oil and grease from the duct surface  Step 2 - Apply the mastic Gaps less than 1/4″, load brush with mastic and coat entire joint with a continuous strip Use brush end to work mastic into joint  Spread mastic at least one inch on each side of the joint.  The mastic should be thick enough to hide the metal surface of the duct.
Mesh for Gaps If gap is larger than 1/4 inch use fiberglass mesh too  If mesh is sticky on one side, cut enough to cover joint, press in place, then completely cover it with mastic.  If mesh does not have a sticky side, apply a thin layer of mastic, press mesh into the mastic, then apply a finish layer of mastic.
 
 
AIRTIGHT DUCT SYSTEM   Boots and Cans Seal seams with mastic Thin mastic will crack Make seal permanent  Plug Don’t Paint Thick as a Nickel  = .077 in 1/16 inch = .0625 in
 
 
 
FLEX DUCT TO METAL Flexible Ducts  Seal inner sleeve & outer sleeve Plastic strap holds the inner liner firmly to the duct or fitting.  Mastic seals liner to connection and covers the end of the liner Use draw band to hold  outer sleeve (vapor barrier)  Vapor barrier should be complete.  All holes, rips, and seams must be sealed with mastic or approved tape
 
AIRTIGHT DUCT SYSTEM   Metal Ducts and Plenums, Duct Board Boxes Openings greater than 1/4 inch should be sealed with mastic and mesh Openings less than 1/4 inch should be sealed with mastic  Special attention to collar connections to duct-board and/or sheet metal; seal around the connection with mastic
Ts Ys & Ls Use mesh tape to strengthen the joint where ducts of different shapes meet.  Seal all seams, even manufactured ones.
 
 
Seal Gores
 
Sealant applied, still leaks
FABRICATION & INSTALLATION  GUIDELINES The air handler box should be air-tight
AHUs & Plenums Fill all openings for wiring, plumbing and refrigerant lines.  Seal all seams in the air handler and plenums.  Tape around access panels, so they can be opened for service.
Air Handler Leaks
Mechanical Systems & Equipment
 
 
 
AIRTIGHT HVAC SYSTEM Air handlers on platforms May be located in a closet indoors  Framers must be told not to put plywood top on before walls are sheetrocked (or duct board) to underside of platform floor  All wall surfaces must be sheetrocked next to and in platform Seal all joints
Boots Seal all joints, including manufactured seams.  The transition between the duct and boot may require mesh tape.
 
AIRTIGHT DUCT SYSTEM   All Duct Types  Register boxes should be sealed to the drywall or floor with caulking or mastic
AIRTIGHT DUCT SYSTEM   All Duct Types  Register boxes should be sealed to the drywall or floor with caulking or mastic
 
 
 
 
 
 
SHEET METAL CONNECTIONS Start the inner fitting into the outer fitting  Apply a 2” wide band of mastic to the exposed part of the inner fitting Fully seat the joint and mechanically fasten with sheet metal screws or rivets Apply a 2.5” wide band of mastic to the outside of the joint covering the screws or rivets and joint gap Allow at least 12 hours drying time before starting system Temperature and humidity conditions can vary, longer dry times may be required
 
 
Locating ducts within thermal boundary Within thermal boundary means within  insulated  space and within the  air barrier  boundary. Attics and crawlspaces can be but are usually  not  conditioned space Critical that space is truly indoors and sealed from unconditioned areas Multi-level dwellings more easily accommodate ducts in conditioned space
Ducts in Unconditioned Space Usually ducts are located in attics and crawlspaces Big temperature differences increase conduction losses and loads  Long duct runs in attics lose 15%+ of cooling capacity before end Convection losses by leakage
Benefits of locating ducts in conditioned space Ducts can be smaller May have shorter runs reduce pressure drop and improve efficiency Can reduce HVAC system costs by reducing loads Improve comfort  No Testing in 09 IECC
 
 
 
 
 
 
 
EXISTING HOMES In existing homes, not unusual to find disconnected duct components, takeoffs loose from ducts or ducts disconnected from register boots
For Sealing Existing Systems Tools & Materials Head lamp, hat with light, or flashlight A work board to span joists in attics  Gallon pail and 2-3 caulk tubes of mastic Caulk Gun, mastic brush, fin and plenum brush Roll of mesh 2-3 pairs of latex gloves  2-3 cloths, can of coil and fin cleaner to wipe joints clean before applying mastic and clean up Utility knife and telescoping mirror Pliers, screw driver and tin snips
Sealing Priorities 1. Disconnected components 2. Connections between the air handling unit and the plenums 3. All seams in the air handling units and plenums, takeoffs, boots, and other connections, especially site-built items.
EXISTING HOMES Leaks connected to the outdoors are more important than leaks inside home’s thermal envelope Holes near the air handler are more important than distant holes with relatively low pressures Supply system leaks waste more energy than return system leaks Furnaces
Remove tie holding duct to connection Roll back insulation and outer cover Seal inner core with mastic and band Roll insulation down and vapor barrier/outer cover Put band and seal with mastic
Wrap Ducts with insulation Insulation may be installed over wet mastic but do not move the ducts too much or mastic seal could be damaged.  All duct support work should be done before applying mastic Wait 2 -4 hours and water based mastic will be dry to the touch
 
 
 
 
 
Oversizing  What do you get when you combine cognitive bias with inaccurate information?
Oversizing  Old Rules of Thumb  One Size Fits All US Department of Energy  Most systems are oversized, increasing installation cost for every house
Oversizing Sizing example   2000 SF House with standard metal windows w/ .75 U-Value and .88 SHGC and 20% duct leakage Calculated Sensible cooling load = 58880 Btu
Equipment Sizing Load calculations determine the proper capacity (size) of equipment Goal is big enough to ensure comfort but no bigger Calculations with ACCA Manual J protocol or other approved methods Mandatory Requirements
 
Oversizing Sizing example   Same 2000 SF house with Low-E windows and tight duct system @ 5% leakage Sensible cooling load = 43877 Btu Average of 1-2” decrease in duct diameter sizes
Oversizing Installation cost is higher Operating cost over life of equipment is higher Can cause comfort problems Improvements in building envelope reduce loads
Right Sizing Costs less to install – saves builder money Costs less to operate - not starting and stopping all the time  Short cycling can cause bigger swings in supply air, less comfort Better humidity control
DESIGN HVAC SYSTEM   Loads and CFM Calculation ACCA Manual J Load Calculation or equivalent required Calculate heat loss and heat gain for each room Total room loads to determine system requirements.
Manual J –Load Calc The local climate – ASHRAE 30 year average Size, shape, and orientation of the house  Insulation levels  Window area, location, and type  Air infiltration rates  Number of occupants  Types and efficiencies of lights and major home appliances (which give off heat) ACCA - Air Conditioning Contractors of America  www.acca.org
“ It’s tough to make predictions, especially about the future.”   -  Yogi Berra
U.S. Dept of Energy 30/30 Vision  2012 IECC 30% More Stringent 2006 IECC  More verification testing
A Quality HVAC System Be properly sized to provide correct air flow, and meet room-by-room calculated heating and cooling loads.  Have sealed ductwork that will provide proper air flow.  Be installed with a return system designed to provide correct return air flow.  Have balanced air flows between supply and return systems to maintain neutral pressure in the home. Be properly charged with refrigerant
Verifying Charge
Ductwork Single most important energy measure for most homes- low hanging fruit Locating inside conditioned space is optimal Seal joints with mastic not duct tape
Equipment Size Oversizing is common and expensive – upfront and during life Sizing properly can reduce cost and help pay for increased cost of other efficiency features
Learn from the mistakes of others. You can't possibly live long enough to make them all yourself   --Sam Levinson
Thank you for participating Any questions  Please complete your evaluation sheets so we can plan future events

HVAC Install - Trust But Verify

  • 1.
    Quality HVAC SystemInstallation Trust But Verify
  • 2.
    Quality HVAC SystemInstallation The goal for a Heating, Ventilation and Air Conditioning (HVAC) system is to provide proper air flow, heating, and cooling to each room
  • 3.
    Instructor Barbara CollinsERH West Building Performance Consultant Certified NAHB Green Building Verifier Certified RESNET HERS Rater Energy Star Homes Partner Certified Environments for Living Verifier
  • 4.
    Class Objectives UnderstandHVAC system air leakage testing requirements in the 2009 IECC Recognize the benefits of sealing ducts for savings, system performance and indoor air quality Understand how ducts are tested for leakage Identify resources for local building departments Identify the best techniques to seal duct systems; what inspectors should see on inspections Understand the IECC requirements for sizing of HVAC equipment
  • 5.
    Current Code RequirementsMust comply with all aspects of UL181 standards Fittings, joints & seams of duct system shall be made substantially air tight by means of tapes, mastics, gasketing or other means.
  • 6.
    Ducts - IECCInsulation (Prescriptive) Ducts outside the building envelope: R-8 All other ducts: R-6 Sealing (Mandatory) Joints and seams shall comply with IRC, Section M1601.4.1 Building framing cavities shall not be used as supply ducts
  • 7.
    2009 IECC DuctTightness Tests All ducts, air handlers, filter boxes and building cavities used as ducts shall be sealed (Section 403.2.2) Duct tightness shall be verified by testing Only Exception: Duct tightness test is not required if the air handler and all ducts are located within conditioned space Mandatory Requirements
  • 8.
    SEAL DUCTS, SAVE ENERGY Sealing ducts is a cost-effective energy efficiency practice that gives a high return on investment
  • 9.
    HVAC System Poordesign and installation increases energy costs 10 –30% Sizing Design Installation
  • 10.
    Home Energy UseResidential energy use 22% of U.S. total 25% of carbon emissions in U.S. Heating & cooling is 40 – 60 % of home energy use
  • 11.
    Why seal ductsLeaks waste energy and money Average system leakage New construction 20% Existing homes 30% Duct sealing reduces heating and cooling energy losses and saves money
  • 12.
    Other Problems Ductleakage reduces air flow, conditioned air isn’t delivered to rooms which can cause wide temperature swings between rooms IAQ issues with return leaks drawing in air from attics, garages, crawlspaces Pressure differentials can cause excess building air leakage and back drafting
  • 13.
    Duct Tightness TestsPost construction tests Option 1 Leakage to outdoors: ≤8 cfm/per 100 ft 2 of conditioned floor area OR Option 2 Total leakage: ≤12 cfm/per 100 ft 2 of conditioned floor area Mandatory Requirements
  • 14.
    Duct Tightness TestsRough-in test Options Option 1 Total leakage ≤6 cfm/per 100 ft 2 of conditioned floor area OR Option 2 If air handler not installed at time of test total air leakage ≤4 cfm/per 100 ft 2 Mandatory Requirements
  • 15.
    Exceptions: Ducttightness test is not required if the air handler and all ducts are located within conditioned space Thermal Boundary is also used to define whether testing is required. Insulation installed on underside of roof sheathing, AHU and ducts in attic, can be considered within thermal boundary
  • 16.
    Ventilation Outdoor airintakes and exhausts shall have automatic or gravity dampers that close when the ventilation system is not operating Mandatory Requirements
  • 17.
    Test Protocol Pressurizethe HVAC system, measure CFM of air required to reach pressure Test at a pressure differential of 0.1 in w.g. (25Pa) across entire system, including manufacturer’s air handler enclosure
  • 18.
  • 19.
  • 20.
  • 21.
  • 22.
  • 23.
  • 24.
  • 25.
  • 26.
    Mastic Sealant Non-toxic– Low VOC Green credits Recommended Set time = 20 hours
  • 27.
    More on MasticHigh strength adhesive compound Usually applied by trowel, brush, caulking gun or hand 3 types- water-based; solvent-based; and two-component curing systems Water-based is the safest and easiest to use It performs as well and in some cases better than the other 2
  • 28.
    VOCs in masticsVolatile organic compounds In water-based mastics, the only volatile compound is water which is inorganic VOCs are infinitesimally small (not recordable) Water-based mastics pose a low health risk compared to solvent-based and two-component mastics Safer for the user, better IAQ, greener
  • 29.
    How to applymastic Step 1 - Clean Duct Surface Wipe dust oil and grease from the duct surface Step 2 - Apply the mastic Gaps less than 1/4″, load brush with mastic and coat entire joint with a continuous strip Use brush end to work mastic into joint Spread mastic at least one inch on each side of the joint. The mastic should be thick enough to hide the metal surface of the duct.
  • 30.
    Mesh for GapsIf gap is larger than 1/4 inch use fiberglass mesh too If mesh is sticky on one side, cut enough to cover joint, press in place, then completely cover it with mastic. If mesh does not have a sticky side, apply a thin layer of mastic, press mesh into the mastic, then apply a finish layer of mastic.
  • 31.
  • 32.
  • 33.
    AIRTIGHT DUCT SYSTEM Boots and Cans Seal seams with mastic Thin mastic will crack Make seal permanent Plug Don’t Paint Thick as a Nickel = .077 in 1/16 inch = .0625 in
  • 34.
  • 35.
  • 36.
  • 37.
    FLEX DUCT TOMETAL Flexible Ducts Seal inner sleeve & outer sleeve Plastic strap holds the inner liner firmly to the duct or fitting. Mastic seals liner to connection and covers the end of the liner Use draw band to hold outer sleeve (vapor barrier) Vapor barrier should be complete. All holes, rips, and seams must be sealed with mastic or approved tape
  • 38.
  • 39.
    AIRTIGHT DUCT SYSTEM Metal Ducts and Plenums, Duct Board Boxes Openings greater than 1/4 inch should be sealed with mastic and mesh Openings less than 1/4 inch should be sealed with mastic Special attention to collar connections to duct-board and/or sheet metal; seal around the connection with mastic
  • 40.
    Ts Ys &Ls Use mesh tape to strengthen the joint where ducts of different shapes meet. Seal all seams, even manufactured ones.
  • 41.
  • 42.
  • 43.
  • 44.
  • 45.
  • 46.
    FABRICATION & INSTALLATION GUIDELINES The air handler box should be air-tight
  • 47.
    AHUs & PlenumsFill all openings for wiring, plumbing and refrigerant lines. Seal all seams in the air handler and plenums. Tape around access panels, so they can be opened for service.
  • 48.
  • 49.
  • 50.
  • 51.
  • 52.
  • 53.
    AIRTIGHT HVAC SYSTEMAir handlers on platforms May be located in a closet indoors Framers must be told not to put plywood top on before walls are sheetrocked (or duct board) to underside of platform floor All wall surfaces must be sheetrocked next to and in platform Seal all joints
  • 54.
    Boots Seal alljoints, including manufactured seams. The transition between the duct and boot may require mesh tape.
  • 55.
  • 56.
    AIRTIGHT DUCT SYSTEM All Duct Types Register boxes should be sealed to the drywall or floor with caulking or mastic
  • 57.
    AIRTIGHT DUCT SYSTEM All Duct Types Register boxes should be sealed to the drywall or floor with caulking or mastic
  • 58.
  • 59.
  • 60.
  • 61.
  • 62.
  • 63.
  • 64.
    SHEET METAL CONNECTIONSStart the inner fitting into the outer fitting Apply a 2” wide band of mastic to the exposed part of the inner fitting Fully seat the joint and mechanically fasten with sheet metal screws or rivets Apply a 2.5” wide band of mastic to the outside of the joint covering the screws or rivets and joint gap Allow at least 12 hours drying time before starting system Temperature and humidity conditions can vary, longer dry times may be required
  • 65.
  • 66.
  • 67.
    Locating ducts withinthermal boundary Within thermal boundary means within insulated space and within the air barrier boundary. Attics and crawlspaces can be but are usually not conditioned space Critical that space is truly indoors and sealed from unconditioned areas Multi-level dwellings more easily accommodate ducts in conditioned space
  • 68.
    Ducts in UnconditionedSpace Usually ducts are located in attics and crawlspaces Big temperature differences increase conduction losses and loads Long duct runs in attics lose 15%+ of cooling capacity before end Convection losses by leakage
  • 69.
    Benefits of locatingducts in conditioned space Ducts can be smaller May have shorter runs reduce pressure drop and improve efficiency Can reduce HVAC system costs by reducing loads Improve comfort No Testing in 09 IECC
  • 70.
  • 71.
  • 72.
  • 73.
  • 74.
  • 75.
  • 76.
  • 77.
    EXISTING HOMES Inexisting homes, not unusual to find disconnected duct components, takeoffs loose from ducts or ducts disconnected from register boots
  • 78.
    For Sealing ExistingSystems Tools & Materials Head lamp, hat with light, or flashlight A work board to span joists in attics Gallon pail and 2-3 caulk tubes of mastic Caulk Gun, mastic brush, fin and plenum brush Roll of mesh 2-3 pairs of latex gloves 2-3 cloths, can of coil and fin cleaner to wipe joints clean before applying mastic and clean up Utility knife and telescoping mirror Pliers, screw driver and tin snips
  • 79.
    Sealing Priorities 1.Disconnected components 2. Connections between the air handling unit and the plenums 3. All seams in the air handling units and plenums, takeoffs, boots, and other connections, especially site-built items.
  • 80.
    EXISTING HOMES Leaksconnected to the outdoors are more important than leaks inside home’s thermal envelope Holes near the air handler are more important than distant holes with relatively low pressures Supply system leaks waste more energy than return system leaks Furnaces
  • 81.
    Remove tie holdingduct to connection Roll back insulation and outer cover Seal inner core with mastic and band Roll insulation down and vapor barrier/outer cover Put band and seal with mastic
  • 82.
    Wrap Ducts withinsulation Insulation may be installed over wet mastic but do not move the ducts too much or mastic seal could be damaged. All duct support work should be done before applying mastic Wait 2 -4 hours and water based mastic will be dry to the touch
  • 83.
  • 84.
  • 85.
  • 86.
  • 87.
  • 88.
    Oversizing Whatdo you get when you combine cognitive bias with inaccurate information?
  • 89.
    Oversizing OldRules of Thumb One Size Fits All US Department of Energy Most systems are oversized, increasing installation cost for every house
  • 90.
    Oversizing Sizing example 2000 SF House with standard metal windows w/ .75 U-Value and .88 SHGC and 20% duct leakage Calculated Sensible cooling load = 58880 Btu
  • 91.
    Equipment Sizing Loadcalculations determine the proper capacity (size) of equipment Goal is big enough to ensure comfort but no bigger Calculations with ACCA Manual J protocol or other approved methods Mandatory Requirements
  • 92.
  • 93.
    Oversizing Sizing example Same 2000 SF house with Low-E windows and tight duct system @ 5% leakage Sensible cooling load = 43877 Btu Average of 1-2” decrease in duct diameter sizes
  • 94.
    Oversizing Installation costis higher Operating cost over life of equipment is higher Can cause comfort problems Improvements in building envelope reduce loads
  • 95.
    Right Sizing Costsless to install – saves builder money Costs less to operate - not starting and stopping all the time Short cycling can cause bigger swings in supply air, less comfort Better humidity control
  • 96.
    DESIGN HVAC SYSTEM Loads and CFM Calculation ACCA Manual J Load Calculation or equivalent required Calculate heat loss and heat gain for each room Total room loads to determine system requirements.
  • 97.
    Manual J –LoadCalc The local climate – ASHRAE 30 year average Size, shape, and orientation of the house Insulation levels Window area, location, and type Air infiltration rates Number of occupants Types and efficiencies of lights and major home appliances (which give off heat) ACCA - Air Conditioning Contractors of America www.acca.org
  • 98.
    “ It’s toughto make predictions, especially about the future.” - Yogi Berra
  • 99.
    U.S. Dept ofEnergy 30/30 Vision 2012 IECC 30% More Stringent 2006 IECC More verification testing
  • 100.
    A Quality HVACSystem Be properly sized to provide correct air flow, and meet room-by-room calculated heating and cooling loads. Have sealed ductwork that will provide proper air flow. Be installed with a return system designed to provide correct return air flow. Have balanced air flows between supply and return systems to maintain neutral pressure in the home. Be properly charged with refrigerant
  • 101.
  • 102.
    Ductwork Single mostimportant energy measure for most homes- low hanging fruit Locating inside conditioned space is optimal Seal joints with mastic not duct tape
  • 103.
    Equipment Size Oversizingis common and expensive – upfront and during life Sizing properly can reduce cost and help pay for increased cost of other efficiency features
  • 104.
    Learn from themistakes of others. You can't possibly live long enough to make them all yourself --Sam Levinson
  • 105.
    Thank you forparticipating Any questions Please complete your evaluation sheets so we can plan future events

Editor's Notes

  • #7 No Trade offs allowed for duct insulation. Exception: - ducts completely inside the building envelope Building framing cavities shall not be used as supply ducts.
  • #17 Equipment sizing is a direct reference to the IRC. Oversized equipment has a higher initial cost, a higher operating cost, provides less comfort, and the short-cycling reduces the equipment life expectancy. Any one of these is a good reason not to oversize. Heating and cooling system design loads for the purpose of sizing systems and equipment shall be determined in accordance with the procedures described in the ACCA Manual J or an equivalent computation procedure.
  • #92 Equipment sizing is a direct reference to the IRC. Oversized equipment has a higher initial cost, a higher operating cost, provides less comfort, and the short-cycling reduces the equipment life expectancy. Any one of these is a good reason not to oversize. Heating and cooling system design loads for the purpose of sizing systems and equipment shall be determined in accordance with the procedures described in the ACCA Manual J or an equivalent computation procedure.