1. GS EP INS 196 – Input and Output
Standard Functions
2. GS EP INS 196 – Input and Output Standard Functions
This GS revision incorporates the following updates:
All Standard Functions:
Interface sketches updated.
All standard functions edited to make the requirements clearer.
Animation examples updated and added.
“Maintenance inhibit” terminology is now reserved exclusively for executive safety
inputs (DIS, DIS_LM, AIS, and F&G detectors in GS EP INS 198).
PCS and valve typicals now use the term « maintenance mode », related treatment
and animation are unchanged.
GS EP INS 196 – Fiche de suivi - Octobre 2014 2
3. GS EP INS 196 – Input and Output Standard Functions
Safety Related Standard Functions (DIS, DIS_LM, AIS, DO)
Maintenance Inhibit and Startup Inhibit function is relocated from the safety bar
standard function to the safety input standard function (DIS, DIS_LM, AIS).
Consequently, “enable/disable” is no longer used.
New DIS typical (digital input DI split into DI for PCS and DIS for safety). Includes a
DIS-D and DIS-E selector. DI_LM renamed DIS_LM.
Clarification of the definition of input / output card fault (card incapable of
processing the input/output or value is considered invalid).
Simplification of the maintenance function and master inhibit keyswitch text.
Automatic Start up inhibit explanation clarified. Only applied for LL threshold on
AIS.
AIS square root extraction option added
Start up inhibit countdown timer added to process displays to distinguish with
maintenance inhibit.
GS EP INS 196 – Fiche de suivi - Octobre 2014 3
4. GS EP INS 196 – Input and Output Standard Functions
Process Control Related Standard Functions (AI, DI, RAI, DO, HIC)
AI process view representation updated.
Simplification of master inhibit key text.
Clarification of the definition of input / output card fault (card incapable of
processing the input/output or value is considered invalid).
Simplification of the maintenance function and master inhibit keyswitch text.
Maintenance Inhibit function is moved to the safety input typical instead of the
safety bar. Consequently, Input “Enable/disable” is no longer required.
AI square root extraction option added.
RAI now only performs discrepancy alarming, automatic switching removed.
HIC animation added.
DO animation updated.
GS EP INS 196 – Fiche de suivi - Octobre 2014 4