SlideShare a Scribd company logo
1 of 8
Download to read offline
IOSR Journal of Mechanical and Civil Engineering (IOSR-JMCE)
e-ISSN: 2278-1684,p-ISSN: 2320-334X, Volume 8, Issue 5 (Sep. - Oct. 2013), PP 48-55
www.iosrjournals.org
www.iosrjournals.org 48 | Page
Strengthening of RC Framed Structure Using Energy Dissipation
Devices
Dr. R. B. khadiranaikar*
, Dr. B. G. Naresh kumar*
, Md. Aqeeb hussain**
,
Avinash Gornale**
Abstract: A large numbers of existing buildings in India are severely deficient against earthquake forces and
the number of such buildings is growing very rapidly. This paper presents a way of using energy dissipation
devices for seismic strengthening of a RC framed structure. The objective was to improve the seismic
performance of the building to resist the earthquake. The viscous dampers are used as an energy dissipation
device in the form of single, double, inverted V, V type of dampers with different percentages of damping such
as 10%, 20% and 30% to prevent building from collapse in a major earthquake and also to control the damage
during earthquake. The performance of the buildings is assessed as per the procedure prescribed in ATC-40
and FEMA 356.
Keywords: seismic performance, energy dissipation devices, non-linear static analysis.
I. Introduction
Earthquake is one of the major natural hazards to the life on the earth and has affected countless cities
and villages of almost every continent. The damage caused by earthquakes are mostly to man mad structures.
Hundreds of small earthquakes occur around the world every day and every year earthquakes take the lives of
thousands of people. Therefore, it is necessary to design structures that are earthquake resistant. Earthquake
engineering has gained lots of attention in recent years since it ensures design of safe structures, which can
safely withstand earthquakes of reasonable magnitude. Conventional seismic design attempts to make building
that do not collapse under strong earthquake shaking, but may sustain damage to non-structural elements and to
some structural members in the building. This may cause the building to be non-functional after the earthquake,
which may be problematic in some structures, like Hospitals, which need to remain functional after an
earthquake. Special techniques are required to design buildings such that they remain practically undamaged
even in a severe earthquake. The energy dissipation devices are recognized as a suitable technique to control the
seismic response of the structure and reduce the damage caused by earthquake. EDD can absorb a portion of
earthquake-induced energy in the structure and minimize the energy dissipation demand on the primary
structure members such as beams, column and walls. These devices can substantially reduce the inter-story drift
and, consequently, non-structural damage. These devices can improve the performance of the building to resist
the earthquake.
1.1. Objectives of the study
The main objectives of this study can be listed as follows;
ď‚· To estimates the performance point and collapse load for the considered building for study under seismic
loading.
ď‚· To study the behavior of the building for incremental lateral load.
ď‚· To estimate the increased performance of the building by using viscous dampers as a retrofitting method.
II. Illustrative Examples
The Layout of plan having 5X4 bays of equal length of 5m Figure 1. The buildings considered are
Reinforced concrete frame building of ten storey’s with regular configurations. The storey height is kept
uniform of 3m for building model which is as fallows,
Strengthening of RC Framed Structure Using Energy Dissipation Devices
www.iosrjournals.org 49 | Page
Figure 1.plan of the building
III. Analysis Methods
Analysis methods are broadly classified as linear static, linear dynamic, nonlinear static and nonlinear
dynamic methods. In these the first two methods are suitable when the structural loads are small and no point,
the load will reach to collapse load and are differs in obtaining the level of forces and their distribution along the
height of the structure. Whereas the non- linear static and non-linear dynamic analysis are the improved methods
over linear approach. During earthquake loads the structural loading will reach to collapse load and the material
stresses will be above yield stresses. So in that case material nonlinearity and geometrical nonlinearity should be
incorporated into the analysis to get better results. These methods also provide information on the strength,
deformation and ductility of the structures as well as distribution of demands.
3.1. Equivalent Static Method
Equivalent static method of analysis is a linear static procedure, in which the response of building is
assumed as linearly elastic manner. The analysis is carried out as per IS1893-2002 (Part 1)
3.2. Response Spectrum Method
Linear dynamic analysis of the building models is performed using ETABS. The lateral loads generated
by ETABS correspond to the seismic zone III and 5% damped response spectrum given in IS 1893-2002 (Part
1). The fundamental natural period values are calculated by ETABS, by solving the Eigen value problem of the
model. Thus, the total earthquake load generated and its distribution along the height corresponds to the mass
and stiffness distribution as modelled by ETABS.
3.3 Pushover Analysis
Pushover analysis is one of the methods available to understand the behavior of structures subjected to
earthquake forces. As the name implies, it is the process of pushing horizontally with a prescribed loading
pattern incrementally until the structure reaches a limit state [ATC-40 1996]. The non linear static analysis
(pushover analysis) is promising tool for seismic performance of existing and new structure. Pushover analysis
gives an estimate of seismic capacity of the structural system and its components based on its material
characteristics and detailing of member dimensions.
The pushover analysis is essentially a step-by-step analysis procedure that applies a distribution of
lateral story forces to a structural model develop from the moment curvature properties of the members the
technique can be useful in evaluation structural response behavior and potential collapse mechanism.
The pushover or capacity curve represents the lateral displacements as the function of force applied to
the structure. Location of hinges in various stages can be obtained from pushover curve as shown in Figure-
2.The range AB is elastic range, B to IO is the range of immediate occupancy, IO to LS is the range of life
safety, and LS to CP is the range of collapse prevention [ATC-40]. If all the hinges are within the CP limit then
the structure is said to be safe. However, depending upon the importance of structure the hinges after IO range
may also need to be retrofitted.
Figure 2.Different Stages of Plastic Hinge Formation.
Strengthening of RC Framed Structure Using Energy Dissipation Devices
www.iosrjournals.org 50 | Page
3.4 Performance Point
The maximum structural displacement expected for the demand earthquake ground motion represents
the performance point. Performance point can also be defined as a condition for which the seismic capacity of
the structure is equal to the seismic demand imposed on the structure by the specific ground motion. It can be
obtained by the intersection of capacity spectrum and demand spectrum. To get the capacity spectrum it is
necessary to convert the capacity curve, which is in terms of base shear and roof displacement, to what is called
as capacity spectrum, which is a representation of capacity curve in Acceleration-Displacement Response
Spectra (ADRS) format. The demand spectrum is the design acceleration spectrum given in IS: 1893 (Part 1)-
2002 modified for 5% damping (for the concrete structures), based on desired response reduction factor
(depending on type of lateral load resisting system) and foundation soil type.
Figure 3.Performance Point.
IV. Results And Discussion
4.1 Energy absorption with different dampers
The energy dissipation devices can absorb portion of energy induced during earthquake. The dampers
used are single diagonal, double diagonal, inverted V and V type of viscous damper at different percentage of
damping such viz 10%, 20% and 30%. The viscous dampers reduce the base shear in the building both in X and
Y direction as the percentage of damping increases. By reducing base shear in the building the earthquake can
be resisted.
Figure 4.The variation of base shears with different percentage of damping in single diagonal damper.
Figure 5.The variation of base shears at different percentage of damping with double diagonal dampers.
Figure 6.The variation of base shears at different percentage of damping with inverted V type dampers.
0
500
1000
1500
2000
2500
0 10 20 30
base shear in x-direction
base shear in y- direction
BaseshearinKN
percentage of damping
0
500
1000
1500
2000
2500
0 10 20 30
base shear in x direction
base shear in y direction
percentage og damping
BaseshearinKN
0
500
1000
1500
2000
2500
0% 10% 20% 30%
base shear in x direction
base shear in y direction
percentage of damping
BaseshearinkN
Strengthening of RC Framed Structure Using Energy Dissipation Devices
www.iosrjournals.org 51 | Page
Figure 7.The variation of base shears at different percentage of damping with V type dampers.
In the Figure 4 the base shear of the structure can be reduced with the use of energy dissipation devices as
viscous dampers. By the comparison of this Figure one can find out that the variation of base shear with
different percentage of damping. This is because energy dissipation devices absorb energy during earthquake.
So the variation of base shear with 0%, 10%, 20% and 30% of damping is 2093.23kN, 1536.28kN, 1268.08kN
and 1183.08kN.
Figure 5 shows the variation of base shear and percentage of damping. At different percentage of
damping there is a reduction in base shear both in X and Y direction the reduction in base shear increase the
capacity of the building to resist the earthquake. There is no much difference between reduction of base shear in
single and double diagonal type of viscous dampers.
From Figure 6 the result shows that there is a significant reduction in base shear at different percentage
of damping. The comparison shows that the reduction of base shear in inverted V type of dampers is less
compare to single and double diagonal dampers.
Figure 7 show the reduction of base shear after installing V type of dampers at different percentage of
damping. So by reducing base shear in the building the performance of the building can be increased during
earthquake. The reduction in base shear of inverted V and V type dampers is almost same.
4.2 Hinge status along x-direction with different dampers.
Performance point determined from pushover analysis is the point at which the capacity of the structure
is exactly equal to the demand made on the structure by the seismic load. The performance of the structure is
assessed by the state of the structure at performance point. This can be done by studying the status of the plastic
hinges formed at different locations in the structure when the structure reaches its performance point. It is
therefore important to study the state of hinges in the structure at performance point. The status of hinges at
performance point for different models considered for the analysis i.e. for all models with different percentage
of damping.
Figure 8. The variation of displacement at different
Percentage of damping
Figure 9. The variation of collapse step and hinges
from A-B at different percentage of damping
0
500
1000
1500
2000
2500
0% 10% 20% 30%
base shear in x direction
base shear in y direction
percentage of damping
BaseshearinKN
6 6 6 6
245 245
219 218
0% 10% 20% 30%
percentage of damping
number of steps
hinges from a-b
collapsestepsandhingesfromA-B
0.6314 0.631
0.5917 0.5912
0% 10% 20% 30%
Percentage of damping
single diagonal dampers
displacement(mm)
Strengthening of RC Framed Structure Using Energy Dissipation Devices
www.iosrjournals.org 52 | Page
Figure 10. the variation of displacement at different
percentage of damping
Figure 11. the variation of collapse step and hinges
from A-B at different percentage of damping
Figure 12. the variation of displacement at different
percentage of damping
Figure 13. the variation of collapse step and hinges
from A-B at different percentage of damping
Figure 14. the variation of displacement at different
percentage of damping
Figure 15. the value of collapse step and hinges from A-B
at different percentage of damping
6 6 8 8
245
221 214 214
0% 10% 20% 30%
percentage of damping
number of steps
hinges from A-B
collapsestepsandhingesfromA-B
6 8 10 10
245
216 216 216
0% 10% 20% 30%
percentage of damping
number of steps
hinges from A-B
collapsestepsandhingesfromA-B
6 10 10 10
245
227 227 227
0% 10% 20% 30%
number of steps
hinges from A-B
percentage of damping
collapsestepsandhingesfromA-B
0.6314
0.5504
0.5323 0.5323
0% 10% 20% 30%
double diagonal dampers
percentage of damping
displcement(mm)
0.6314
0.5837 0.5832 0.5832
0% 10% 20% 30%
inverted v type dampers
percentage of damping
displcement(mm)
0.6314
0.5409 0.5409 0.5409
0% 10% 20% 30%
V type dampers
percentage of damping
displcement(mm)
Strengthening of RC Framed Structure Using Energy Dissipation Devices
www.iosrjournals.org 53 | Page
Figure 8 show that the displacement without dampers is 0.6314mm. After installation of energy dissipation
devices the displacement at 10% of damping reduces to 0.6310mm, at 20% of damping it reduces to 0.5917mm
and at 30% of damping it reduces to 0.5912mm.
In the Figure 9 after installation of dampers with different percentage of damping the number of Hinges in the
region A-B is reduced and different percentage of damping building collapse at step 6.
Figure 10 show the variation of displacement with different percentage of damping. At different percentage of
damping there is a significant reduction in displacement. Reduction in displacement increases the capacity of the
building to resist the earthquake. When we use double diagonal type of viscous dampers the displacement is
more compare to single diagonal dampers.
In the Figure 11 the result show that the number of hinges in the region A-B is reduce at different
percentage of damping. The building collapse at step 6 with 0% and 10% of damping, at step 8 with 20% and
30% of damping.
From Figure 12 the result shows that there is a reduction at different percentage of damping. By
comparing the displacement of inverted V, single diagonal and double diagonal type of dampers. The
displacement in double diagonal dampers is more.
Figure 13 show the variation of collapse step and hinges in the region A-B. After installation of
dampers at 10% of damping building collapse at step8 then at 20% and 30% 0f damping building collapse at
step10. The number of hinges forming in the region is 216 at different percentage of damping.
In the Figure 14 the displacement in the building without damper is 0.6314mm. After installation of
dampers the displacement in the building is constant i.e. 0.5409mm at different percentage of damping.
Figure 15 shows that building without dampers collapse at step6. After installing dampers with
different percentage of damping the building collapse at constant step i.e. step 10. The number of hinges
forming in the region without dampers is 245. After installation of dampers in the building the hinges in the
region forming are constant i.e. 227. By reducing hinges in the building earthquake can be resisted.
4.3 fundamental natural periods with different types of viscous dampers
As per IS: 1893 (part 1) 2002 the fundamental natural period of vibration of a building is given by
empirical formulae, which depend on the height of the building, and base dimensions of the structure. It also
states that a free vibration analysis may be performed as per established methods to obtain the natural periods of
the structure. It has been observed in all types of viscous dampers that the value of fundamental natural period is
increasing as the percentage of damping increases.
Figure 16.The variation of fundamental natural period at different percentage of damping
from Figure 16 result show that at 0% of damping the fundamental natural period is 1.7001(sec).Then after
installing single diagonal type of dampers at 10%, 20% and 30% of damping the fundamental natural period is
increases to 0.30% by which building becomes more flexible during earthquake.
In double diagonal type of dampers the fundamental natural period at 10%, 20%, 30% of damping the
fundamental natural period increases to 0.37% by which building becomes more flexible during earthquake.
In inverted V type of dampers the fundamental natural period at different percentage of damping increases to
0.43% by comparing with single diagonal type of bracing the fundamental natural period of inverted v type of
dampers make the building more flexible.
For V type of dampers the fundamental natural period at different percentage of damping increases to 0.48%
which increases the flexibility of the building.
1.694
1.696
1.698
1.7
1.702
1.704
1.706
1.708
1.71
single diagona
double diagonal
inverted v
v
0% 10% 20% 30%
percentage of damping
fundamentalnaturalperiodinsec
Strengthening of RC Framed Structure Using Energy Dissipation Devices
www.iosrjournals.org 54 | Page
4.4 Performance level in X and Y direction
The performance level describes a limiting damage condition which may be considered satisfactory for
a given building and a given ground motion. The limiting condition is described by the physical damage within
the building, the threat to life safety of the buildings occupants created by the damage, and post-earthquake
serviceability of the building. Target performance levels for structural and non structural systems are specified
independently. Structural performance levels are given names and number of designation. While nonstructural
performance levels are given names and letter designation. Building performance levels are a combination of a
structural performance level and nonstructural performance level.
Table 4.10 the values for comparison of results in x direction with different dampers
Dampers displacem
ent
Base shear Performance
level
displaceme
nt
Base shear Performance
level
% of
absorption
Direction X Without dampers With dampers
0% damping 0.093 2093.23 LS-CP - - - -
SD 10% 0.093 2093.23 LS-CP 0.068 1536.279 IO-LS 26.60%
SD 20% 0.093 2093.23 LS-CP 0.056 1268.082 A-B 39.41%
SD 30% 0.093 2093.23 LS-CP 0.052 1183.082 A-B 43.47%
DD 10% 0.093 2093.23 LS-CP 0.068 1538.031 B-IO 26.52%
DD 20% 0.093 2093.23 LS-CP 0.056 1269.528 B-IO 39.35%
DD 30% 0.093 2093.23 LS-CP 0.053 1184.58 A-B 43.40%
IV 10% 0.093 2093.23 LS-CP 0.068 1543.631 IO-LS 26.25%
IV 20% 0.093 2093.23 LS-CP 0.056 1273.713 A-B 39.15%
IV 30% 0.093 2093.23 LS-CP 0.053 1188.894 A-B 43.20%
V 10% 0.093 2093.23 LS-CP 0.068 1544.583 B-IO 26.21%
V 20% 0.093 2093.23 LS-CP 0.056 1274.501 A-B 39.11%
V 30% 0.093 2093.23 LS-CP 0.053 1189.627 A-B 43.16%
From the table 4.10 it is clear that in x-direction for model without damper the performance level is in between
life safety level to collapse prevention level (LS-CP). So loss is acceptable in this region, then after installing
damper at 10% of damping the performance level comes between immediate occupancy level to life safety level
(IO-LS) so after installing dampers it comes to minor repair for single diagonal and inverted V, then at 20% and
30% it comes to elastic region i.e. (A-B) i.e. no damage region. For double diagonal and V type of viscous
dampers at 10% of damping the performance level is in between B-IO so it is in damage control range then at
20% and 30% of damping it comes to A-B region i.e. no damage region.
Table 4.11 the values for comparison of results in Y direction with different dampers
dampers displacement Base shear Performance
level
Base shear Performance
level
% of
absorption
Direction Y Without dampers With dampers
0% 0.095 2053.349 LS-CP - - -
SD 10% 0.095 2053.349 LS-CP 1506.968 IO-LS 26.63%
SD 20% 0.095 2053.349 LS-CP 1243.888 A-B 39.41%
SD 30% 0.095 2053.349 LS-CP 1160.656 A-B 43.47%
DD 10% 0.095 2053.349 LS-CP 1508.689 IO-LS 24.82%
DD 20% 0.095 2053.349 LS-CP 1245.309 A-B 38.06%
DD 30% 0.095 2053.349 LS-CP 1161.982 A-B 42.10%
IV 10% 0.095 2053.349 LS-CP 1514.13 B-IO 26.26%
IV 20% 0.095 2053.349 LS-CP 1249.379 A-B 39.15%
IV 30% 0.095 2053.349 LS-CP 1166.172 A-B 43.20%
V 10% 0.095 2053.349 LS-CP 1515.072 B-IO 26.21%
V 20% 0.095 2053.349 LS-CP 1250.157 A-B 39.11%
V 30% 0.095 2053.349 LS-CP 1166.897 A-B 43.18%
SD-single diagonal, DD-double diagonal, IV-inverted V and V type of dampers
From table 4.11 it is clear that in y-direction for model without damper the performance level is in between life
safety level to collapse prevention level (LS-CP). So loss is acceptable in this region then after installing damper
at 10% of damping the performance level comes between immediate occupancy level to life safety level (IO-LS)
so after installing dampers it comes to minor repair for single diagonal and double diagonal then at 20% and
30% it comes to elastic region i.e. (A-B) i.e. no damage region. For inverted V and V type of viscous dampers at
10% of damping the performance level is in between B-IO so it is in damage control range then at 20% and 30%
of damping it comes to A-B region i.e. no damage region.
Strengthening of RC Framed Structure Using Energy Dissipation Devices
www.iosrjournals.org 55 | Page
V. Conclusions:
The aim of the project is to improve the capacity of the building to resist the earthquake using energy
dissipation devices, particularly viscous dampers of different types such as single diagonal, double diagonal,
inverted V and V type of viscous dampers.
ď‚· The comparison of the results both in X and Y direction of all the type of viscous dampers indicates that
by installing dampers in the structures we can reduce the base shear of the building. So by reducing base
shear in the concrete frame structure, we can increase the capacity of the building to resist the earthquake.
ď‚· By comparing the results of both single diagonal and double diagonal type of viscous dampers the
percentage reduction in base shear of single diagonal is 26.60% and double diagonal is 26.52%. So the
percentage reduction in double diagonal is low but providing double diagonal type of viscous dampers is
better than single diagonal type of viscous dampers, because we don’t know in which direction earthquake
will occur.
ď‚· By installing the viscous dampers of different types at 10, 20, 30% of damping we can increase the
fundamental natural period which makes the structure more flexible during earthquake. And by comparing
fundamental natural period of all the four type of viscous dampers the increase in fundamental natural
period of V type of viscous damper is more.
ď‚· By comparing the results of performance point in x and y direction, we can conclude that after installing
dampers the performance level from region LS-CP comes to region A-B. So, by installing dampers we can
improve the performance level of the building to resist the earthquake.
ď‚· By installing viscous dampers we can reduce the displacement in the building which makes the building
earthquake resistant.
ď‚· Model without dampers collapse at step 6, after installing single diagonal type of dampers building also
collapse at step 6, in double diagonal type of dampers building collapse at step 8 and for both inverted V
and V type of dampers building collapse at step 10.so by installing dampers with different percentage of
damping in the structure we can increase the lateral load coming to the building during earthquake.
References:
[1]. Vijay Chachapara, Sharadkumar Purohit and P. V. Patel. (2011). “Seismic Response Control of the Building using Passive Devices”
Civil Engineering Department, Institute of Technology, Nirma University, Ahmedabad 382 481
[2]. ali sehat tabatabaei. (2003). “Energy Dissipation Systems for Siesmic Resistance” civil engineering university of east London.
[3]. Fahim sadek, Bijan mohraz And Michael a riley. (2000). “Improved Linear Procedures for Analysis of Structures with Passive
Energy Dissipation Devices” National Institute of Standards and Technology, Gaithersburg, MD
[4]. K. Sathish Kumar, C. Antony Jeyasehar and K. Muthumani. (2012). “A Design Methodology for Supplemental damping for
Seismic Performance Enhancement of Frame Structures” asian journal of civil engineering (building and housing) vol. 13, no. 5
(2012) pages 659-678
[5]. IS: 1893 – 2002 (Part 1), “Criteria for Earthquake Resistant Design of Structures”, part 1-General provisions and buildings, fifth
revision, Bureau of Indian Standard, New Delhi, India.
[6]. IS: 456-2000., “Code of Practice for Plain and Reinforced Concrete”, Bureau of Indian Standard, New Delhi, India.
[7]. ATC, 1996, “Seismic Evaluation and Retrofit of Concrete Buildings”, Volume 1,
[8]. ATC-40 Report, Applied Technology Council, Redwood City, California.
[9]. Federal Emergency Federal Agency, FEMA-356. Pre-standard and Commentary
[10]. for Seismic Rehabilitation of Buildings. Washington DC, 2000.
[11]. Durgesh C. Rai. “Supplemental Damping for Seismic Strengthening: a Case Study”. Department of Earthquake Engineering,
University of Roorkee, Roorkee 247 667, India.
[12]. S.K. Ahirwar, S.K. Jain and M. M. Pande. (2008). “Earthquake Loads on Multistory Buildings as per IS: 1893-1984 and IS: 1893-
2002: A Comparative Study” The 14 World Conference on Earthquake Engineering October 12-17, 2008, Beijing, China.

More Related Content

What's hot

Seismic performance of r c buildings on sloping grounds with different types ...
Seismic performance of r c buildings on sloping grounds with different types ...Seismic performance of r c buildings on sloping grounds with different types ...
Seismic performance of r c buildings on sloping grounds with different types ...eSAT Journals
 
Seismic Analysis of Regular and Irregular Buildings with Vertical Irregularit...
Seismic Analysis of Regular and Irregular Buildings with Vertical Irregularit...Seismic Analysis of Regular and Irregular Buildings with Vertical Irregularit...
Seismic Analysis of Regular and Irregular Buildings with Vertical Irregularit...IRJET Journal
 
IRJET- Seismic Analysis of Building Resting on Sloping Ground with Soil S...
IRJET-  	  Seismic Analysis of Building Resting on Sloping Ground with Soil S...IRJET-  	  Seismic Analysis of Building Resting on Sloping Ground with Soil S...
IRJET- Seismic Analysis of Building Resting on Sloping Ground with Soil S...IRJET Journal
 
IRJET- Effect of Bracing and Unbracing in Steel Stuctures by using ETabs
IRJET-  	  Effect of Bracing and Unbracing in Steel Stuctures by using ETabsIRJET-  	  Effect of Bracing and Unbracing in Steel Stuctures by using ETabs
IRJET- Effect of Bracing and Unbracing in Steel Stuctures by using ETabsIRJET Journal
 
Performance Analysis of the Tall Structure with Diagrid for Seismic Loading
Performance Analysis of the Tall Structure with Diagrid for Seismic LoadingPerformance Analysis of the Tall Structure with Diagrid for Seismic Loading
Performance Analysis of the Tall Structure with Diagrid for Seismic LoadingIRJET Journal
 
Effect of Friction Dampers on RC Structures Subjected to Earthquake
Effect of Friction Dampers on RC Structures Subjected to EarthquakeEffect of Friction Dampers on RC Structures Subjected to Earthquake
Effect of Friction Dampers on RC Structures Subjected to Earthquakeijtsrd
 
PERFORMANCE BASED ANALYSIS OF VERTICALLY IRREGULAR STRUCTURE UNDER VARIOUS SE...
PERFORMANCE BASED ANALYSIS OF VERTICALLY IRREGULAR STRUCTURE UNDER VARIOUS SE...PERFORMANCE BASED ANALYSIS OF VERTICALLY IRREGULAR STRUCTURE UNDER VARIOUS SE...
PERFORMANCE BASED ANALYSIS OF VERTICALLY IRREGULAR STRUCTURE UNDER VARIOUS SE...Ijripublishers Ijri
 
Rc4 lecture 2- eng. samer akil
Rc4  lecture 2- eng. samer akilRc4  lecture 2- eng. samer akil
Rc4 lecture 2- eng. samer akilAminZuraiqi2
 
Study on Seismic Behaviour of RC Frame Vertically Asymmetrical Buildings
Study on Seismic Behaviour of RC Frame Vertically Asymmetrical BuildingsStudy on Seismic Behaviour of RC Frame Vertically Asymmetrical Buildings
Study on Seismic Behaviour of RC Frame Vertically Asymmetrical BuildingsIRJET Journal
 
IRJET- Comparative Analysis of Regular and Irregular Configuration of Mul...
IRJET-  	  Comparative Analysis of Regular and Irregular Configuration of Mul...IRJET-  	  Comparative Analysis of Regular and Irregular Configuration of Mul...
IRJET- Comparative Analysis of Regular and Irregular Configuration of Mul...IRJET Journal
 
Street Light Automatic Intensity Controller
Street Light Automatic Intensity ControllerStreet Light Automatic Intensity Controller
Street Light Automatic Intensity ControllerIRJET Journal
 
IRJET - Seismic Comparison of OMRF & SMRF Structural System on Zone II
IRJET - Seismic Comparison of OMRF & SMRF Structural System on Zone IIIRJET - Seismic Comparison of OMRF & SMRF Structural System on Zone II
IRJET - Seismic Comparison of OMRF & SMRF Structural System on Zone IIIRJET Journal
 
Evaluation of Seismic Behaviour of RCC Building using Coupled Shear wall
Evaluation of Seismic Behaviour of RCC Building using Coupled Shear wallEvaluation of Seismic Behaviour of RCC Building using Coupled Shear wall
Evaluation of Seismic Behaviour of RCC Building using Coupled Shear wallIRJET Journal
 
Seismic Analysis of Multistoreyed RC Building Due to Mass Irregularity by Tim...
Seismic Analysis of Multistoreyed RC Building Due to Mass Irregularity by Tim...Seismic Analysis of Multistoreyed RC Building Due to Mass Irregularity by Tim...
Seismic Analysis of Multistoreyed RC Building Due to Mass Irregularity by Tim...IRJET Journal
 
IRJET- Post Peak Response of Reinforced Concrete Frames with and without in F...
IRJET- Post Peak Response of Reinforced Concrete Frames with and without in F...IRJET- Post Peak Response of Reinforced Concrete Frames with and without in F...
IRJET- Post Peak Response of Reinforced Concrete Frames with and without in F...IRJET Journal
 
Seismic Analysis of regular & Irregular RCC frame structures
Seismic Analysis of regular & Irregular RCC frame structuresSeismic Analysis of regular & Irregular RCC frame structures
Seismic Analysis of regular & Irregular RCC frame structuresDaanish Zama
 
Study of variations in dynamic stability of tall structure corresponding to s...
Study of variations in dynamic stability of tall structure corresponding to s...Study of variations in dynamic stability of tall structure corresponding to s...
Study of variations in dynamic stability of tall structure corresponding to s...ijceronline
 
Seismic Analysis of G 10 Storey Building with Various Locations of Shear Wall...
Seismic Analysis of G 10 Storey Building with Various Locations of Shear Wall...Seismic Analysis of G 10 Storey Building with Various Locations of Shear Wall...
Seismic Analysis of G 10 Storey Building with Various Locations of Shear Wall...ijtsrd
 
SEISMIC MITIGATION OF TWIN TOWER STRUCTURES USING AN ISOLATED CORRIDOR
SEISMIC MITIGATION OF TWIN TOWER STRUCTURES USING AN ISOLATED CORRIDORSEISMIC MITIGATION OF TWIN TOWER STRUCTURES USING AN ISOLATED CORRIDOR
SEISMIC MITIGATION OF TWIN TOWER STRUCTURES USING AN ISOLATED CORRIDORharshilshah546931
 

What's hot (20)

Seismic performance of r c buildings on sloping grounds with different types ...
Seismic performance of r c buildings on sloping grounds with different types ...Seismic performance of r c buildings on sloping grounds with different types ...
Seismic performance of r c buildings on sloping grounds with different types ...
 
Seismic Analysis of Regular and Irregular Buildings with Vertical Irregularit...
Seismic Analysis of Regular and Irregular Buildings with Vertical Irregularit...Seismic Analysis of Regular and Irregular Buildings with Vertical Irregularit...
Seismic Analysis of Regular and Irregular Buildings with Vertical Irregularit...
 
IRJET- Seismic Analysis of Building Resting on Sloping Ground with Soil S...
IRJET-  	  Seismic Analysis of Building Resting on Sloping Ground with Soil S...IRJET-  	  Seismic Analysis of Building Resting on Sloping Ground with Soil S...
IRJET- Seismic Analysis of Building Resting on Sloping Ground with Soil S...
 
IRJET- Effect of Bracing and Unbracing in Steel Stuctures by using ETabs
IRJET-  	  Effect of Bracing and Unbracing in Steel Stuctures by using ETabsIRJET-  	  Effect of Bracing and Unbracing in Steel Stuctures by using ETabs
IRJET- Effect of Bracing and Unbracing in Steel Stuctures by using ETabs
 
Performance Analysis of the Tall Structure with Diagrid for Seismic Loading
Performance Analysis of the Tall Structure with Diagrid for Seismic LoadingPerformance Analysis of the Tall Structure with Diagrid for Seismic Loading
Performance Analysis of the Tall Structure with Diagrid for Seismic Loading
 
Effect of Friction Dampers on RC Structures Subjected to Earthquake
Effect of Friction Dampers on RC Structures Subjected to EarthquakeEffect of Friction Dampers on RC Structures Subjected to Earthquake
Effect of Friction Dampers on RC Structures Subjected to Earthquake
 
PERFORMANCE BASED ANALYSIS OF VERTICALLY IRREGULAR STRUCTURE UNDER VARIOUS SE...
PERFORMANCE BASED ANALYSIS OF VERTICALLY IRREGULAR STRUCTURE UNDER VARIOUS SE...PERFORMANCE BASED ANALYSIS OF VERTICALLY IRREGULAR STRUCTURE UNDER VARIOUS SE...
PERFORMANCE BASED ANALYSIS OF VERTICALLY IRREGULAR STRUCTURE UNDER VARIOUS SE...
 
Rc4 lecture 2- eng. samer akil
Rc4  lecture 2- eng. samer akilRc4  lecture 2- eng. samer akil
Rc4 lecture 2- eng. samer akil
 
Study on Seismic Behaviour of RC Frame Vertically Asymmetrical Buildings
Study on Seismic Behaviour of RC Frame Vertically Asymmetrical BuildingsStudy on Seismic Behaviour of RC Frame Vertically Asymmetrical Buildings
Study on Seismic Behaviour of RC Frame Vertically Asymmetrical Buildings
 
IRJET- Comparative Analysis of Regular and Irregular Configuration of Mul...
IRJET-  	  Comparative Analysis of Regular and Irregular Configuration of Mul...IRJET-  	  Comparative Analysis of Regular and Irregular Configuration of Mul...
IRJET- Comparative Analysis of Regular and Irregular Configuration of Mul...
 
Street Light Automatic Intensity Controller
Street Light Automatic Intensity ControllerStreet Light Automatic Intensity Controller
Street Light Automatic Intensity Controller
 
IRJET - Seismic Comparison of OMRF & SMRF Structural System on Zone II
IRJET - Seismic Comparison of OMRF & SMRF Structural System on Zone IIIRJET - Seismic Comparison of OMRF & SMRF Structural System on Zone II
IRJET - Seismic Comparison of OMRF & SMRF Structural System on Zone II
 
Evaluation of Seismic Behaviour of RCC Building using Coupled Shear wall
Evaluation of Seismic Behaviour of RCC Building using Coupled Shear wallEvaluation of Seismic Behaviour of RCC Building using Coupled Shear wall
Evaluation of Seismic Behaviour of RCC Building using Coupled Shear wall
 
Seismic Analysis of Multistoreyed RC Building Due to Mass Irregularity by Tim...
Seismic Analysis of Multistoreyed RC Building Due to Mass Irregularity by Tim...Seismic Analysis of Multistoreyed RC Building Due to Mass Irregularity by Tim...
Seismic Analysis of Multistoreyed RC Building Due to Mass Irregularity by Tim...
 
IRJET- Post Peak Response of Reinforced Concrete Frames with and without in F...
IRJET- Post Peak Response of Reinforced Concrete Frames with and without in F...IRJET- Post Peak Response of Reinforced Concrete Frames with and without in F...
IRJET- Post Peak Response of Reinforced Concrete Frames with and without in F...
 
Seismic Analysis of regular & Irregular RCC frame structures
Seismic Analysis of regular & Irregular RCC frame structuresSeismic Analysis of regular & Irregular RCC frame structures
Seismic Analysis of regular & Irregular RCC frame structures
 
Study of variations in dynamic stability of tall structure corresponding to s...
Study of variations in dynamic stability of tall structure corresponding to s...Study of variations in dynamic stability of tall structure corresponding to s...
Study of variations in dynamic stability of tall structure corresponding to s...
 
F012475664
F012475664F012475664
F012475664
 
Seismic Analysis of G 10 Storey Building with Various Locations of Shear Wall...
Seismic Analysis of G 10 Storey Building with Various Locations of Shear Wall...Seismic Analysis of G 10 Storey Building with Various Locations of Shear Wall...
Seismic Analysis of G 10 Storey Building with Various Locations of Shear Wall...
 
SEISMIC MITIGATION OF TWIN TOWER STRUCTURES USING AN ISOLATED CORRIDOR
SEISMIC MITIGATION OF TWIN TOWER STRUCTURES USING AN ISOLATED CORRIDORSEISMIC MITIGATION OF TWIN TOWER STRUCTURES USING AN ISOLATED CORRIDOR
SEISMIC MITIGATION OF TWIN TOWER STRUCTURES USING AN ISOLATED CORRIDOR
 

Similar to Strengthening of RC Framed Structure Using Energy Dissipation Devices

IRJET- Seismic Evolution of Soft Storeyed Structures When Exposed to Earth Qu...
IRJET- Seismic Evolution of Soft Storeyed Structures When Exposed to Earth Qu...IRJET- Seismic Evolution of Soft Storeyed Structures When Exposed to Earth Qu...
IRJET- Seismic Evolution of Soft Storeyed Structures When Exposed to Earth Qu...IRJET Journal
 
Performance of Flat Slab Structure Using Pushover Analysis
Performance of Flat Slab Structure Using Pushover AnalysisPerformance of Flat Slab Structure Using Pushover Analysis
Performance of Flat Slab Structure Using Pushover AnalysisIOSR Journals
 
Seismic Response of RC Framed Structures Having Plan and Vertical Irregularit...
Seismic Response of RC Framed Structures Having Plan and Vertical Irregularit...Seismic Response of RC Framed Structures Having Plan and Vertical Irregularit...
Seismic Response of RC Framed Structures Having Plan and Vertical Irregularit...IRJET Journal
 
Analysis and Capacity Based Earthquake Resistance Design of Multy Bay Multy S...
Analysis and Capacity Based Earthquake Resistance Design of Multy Bay Multy S...Analysis and Capacity Based Earthquake Resistance Design of Multy Bay Multy S...
Analysis and Capacity Based Earthquake Resistance Design of Multy Bay Multy S...IJERA Editor
 
Seismic Evolution of Soft Storeyed Buildings when Subjected to Real Time Eart...
Seismic Evolution of Soft Storeyed Buildings when Subjected to Real Time Eart...Seismic Evolution of Soft Storeyed Buildings when Subjected to Real Time Eart...
Seismic Evolution of Soft Storeyed Buildings when Subjected to Real Time Eart...IRJET Journal
 
COMPARATIVE ANALYSIS OF MULTISTORY BUILDING WITH AND WITHOUT SHEAR WALL, X BR...
COMPARATIVE ANALYSIS OF MULTISTORY BUILDING WITH AND WITHOUT SHEAR WALL, X BR...COMPARATIVE ANALYSIS OF MULTISTORY BUILDING WITH AND WITHOUT SHEAR WALL, X BR...
COMPARATIVE ANALYSIS OF MULTISTORY BUILDING WITH AND WITHOUT SHEAR WALL, X BR...IRJET Journal
 
Effects of Providing Shear wall and Bracing to Seismic Performance of Concret...
Effects of Providing Shear wall and Bracing to Seismic Performance of Concret...Effects of Providing Shear wall and Bracing to Seismic Performance of Concret...
Effects of Providing Shear wall and Bracing to Seismic Performance of Concret...IRJET Journal
 
Influence of Concrete and Steel Outrigger and Belt Truss in High Rise Moment ...
Influence of Concrete and Steel Outrigger and Belt Truss in High Rise Moment ...Influence of Concrete and Steel Outrigger and Belt Truss in High Rise Moment ...
Influence of Concrete and Steel Outrigger and Belt Truss in High Rise Moment ...IRJET Journal
 
IRJET- Review on Seismic Analyses of RC Frame Structure by using Bracing ...
IRJET-  	  Review on Seismic Analyses of RC Frame Structure by using Bracing ...IRJET-  	  Review on Seismic Analyses of RC Frame Structure by using Bracing ...
IRJET- Review on Seismic Analyses of RC Frame Structure by using Bracing ...IRJET Journal
 
IRJET- Review on Seismic Analyses of RC Frame Structure by using Bracing ...
IRJET-  	  Review on Seismic Analyses of RC Frame Structure by using Bracing ...IRJET-  	  Review on Seismic Analyses of RC Frame Structure by using Bracing ...
IRJET- Review on Seismic Analyses of RC Frame Structure by using Bracing ...IRJET Journal
 
Seismic Performance and Shear Wall Location Assessment of a RC Building- Eva...
Seismic Performance and Shear Wall Location  Assessment of a RC Building- Eva...Seismic Performance and Shear Wall Location  Assessment of a RC Building- Eva...
Seismic Performance and Shear Wall Location Assessment of a RC Building- Eva...IRJET Journal
 
IRJET- Study of Literature on Seismic Response of RC Irregular Structure
IRJET-  	  Study of Literature on Seismic Response of RC Irregular StructureIRJET-  	  Study of Literature on Seismic Response of RC Irregular Structure
IRJET- Study of Literature on Seismic Response of RC Irregular StructureIRJET Journal
 
Inelastic seismic performance of low-rise multi-story structure in hilly area...
Inelastic seismic performance of low-rise multi-story structure in hilly area...Inelastic seismic performance of low-rise multi-story structure in hilly area...
Inelastic seismic performance of low-rise multi-story structure in hilly area...IRJET Journal
 
Study on Torsional Response of Irregualr Buildings Under Seismic Loading
Study on Torsional Response of Irregualr Buildings Under Seismic LoadingStudy on Torsional Response of Irregualr Buildings Under Seismic Loading
Study on Torsional Response of Irregualr Buildings Under Seismic LoadingIRJET Journal
 
Seismic and progressive collapse mitigation of shear energy dissipation beam ...
Seismic and progressive collapse mitigation of shear energy dissipation beam ...Seismic and progressive collapse mitigation of shear energy dissipation beam ...
Seismic and progressive collapse mitigation of shear energy dissipation beam ...IRJET Journal
 
ANALYSIS AND DESIGN OPTIMIZATION OF SHEAR-WALL IN CASE OF HIGH-RISE BUILDING ...
ANALYSIS AND DESIGN OPTIMIZATION OF SHEAR-WALL IN CASE OF HIGH-RISE BUILDING ...ANALYSIS AND DESIGN OPTIMIZATION OF SHEAR-WALL IN CASE OF HIGH-RISE BUILDING ...
ANALYSIS AND DESIGN OPTIMIZATION OF SHEAR-WALL IN CASE OF HIGH-RISE BUILDING ...IRJET Journal
 
Capacity Spectrum Method for RC Building with Cracked and Uncracked Section
Capacity Spectrum Method for RC Building with Cracked and Uncracked SectionCapacity Spectrum Method for RC Building with Cracked and Uncracked Section
Capacity Spectrum Method for RC Building with Cracked and Uncracked SectionIOSR Journals
 
IRJET- Study of Behavior Parameters of the Building with Variations in Story ...
IRJET- Study of Behavior Parameters of the Building with Variations in Story ...IRJET- Study of Behavior Parameters of the Building with Variations in Story ...
IRJET- Study of Behavior Parameters of the Building with Variations in Story ...IRJET Journal
 

Similar to Strengthening of RC Framed Structure Using Energy Dissipation Devices (20)

IRJET- Seismic Evolution of Soft Storeyed Structures When Exposed to Earth Qu...
IRJET- Seismic Evolution of Soft Storeyed Structures When Exposed to Earth Qu...IRJET- Seismic Evolution of Soft Storeyed Structures When Exposed to Earth Qu...
IRJET- Seismic Evolution of Soft Storeyed Structures When Exposed to Earth Qu...
 
Performance of Flat Slab Structure Using Pushover Analysis
Performance of Flat Slab Structure Using Pushover AnalysisPerformance of Flat Slab Structure Using Pushover Analysis
Performance of Flat Slab Structure Using Pushover Analysis
 
Seismic Response of RC Framed Structures Having Plan and Vertical Irregularit...
Seismic Response of RC Framed Structures Having Plan and Vertical Irregularit...Seismic Response of RC Framed Structures Having Plan and Vertical Irregularit...
Seismic Response of RC Framed Structures Having Plan and Vertical Irregularit...
 
Analysis and Capacity Based Earthquake Resistance Design of Multy Bay Multy S...
Analysis and Capacity Based Earthquake Resistance Design of Multy Bay Multy S...Analysis and Capacity Based Earthquake Resistance Design of Multy Bay Multy S...
Analysis and Capacity Based Earthquake Resistance Design of Multy Bay Multy S...
 
Seismic Evolution of Soft Storeyed Buildings when Subjected to Real Time Eart...
Seismic Evolution of Soft Storeyed Buildings when Subjected to Real Time Eart...Seismic Evolution of Soft Storeyed Buildings when Subjected to Real Time Eart...
Seismic Evolution of Soft Storeyed Buildings when Subjected to Real Time Eart...
 
COMPARATIVE ANALYSIS OF MULTISTORY BUILDING WITH AND WITHOUT SHEAR WALL, X BR...
COMPARATIVE ANALYSIS OF MULTISTORY BUILDING WITH AND WITHOUT SHEAR WALL, X BR...COMPARATIVE ANALYSIS OF MULTISTORY BUILDING WITH AND WITHOUT SHEAR WALL, X BR...
COMPARATIVE ANALYSIS OF MULTISTORY BUILDING WITH AND WITHOUT SHEAR WALL, X BR...
 
Effects of Providing Shear wall and Bracing to Seismic Performance of Concret...
Effects of Providing Shear wall and Bracing to Seismic Performance of Concret...Effects of Providing Shear wall and Bracing to Seismic Performance of Concret...
Effects of Providing Shear wall and Bracing to Seismic Performance of Concret...
 
Sap 2000
Sap 2000Sap 2000
Sap 2000
 
Influence of Concrete and Steel Outrigger and Belt Truss in High Rise Moment ...
Influence of Concrete and Steel Outrigger and Belt Truss in High Rise Moment ...Influence of Concrete and Steel Outrigger and Belt Truss in High Rise Moment ...
Influence of Concrete and Steel Outrigger and Belt Truss in High Rise Moment ...
 
IRJET- Review on Seismic Analyses of RC Frame Structure by using Bracing ...
IRJET-  	  Review on Seismic Analyses of RC Frame Structure by using Bracing ...IRJET-  	  Review on Seismic Analyses of RC Frame Structure by using Bracing ...
IRJET- Review on Seismic Analyses of RC Frame Structure by using Bracing ...
 
IRJET- Review on Seismic Analyses of RC Frame Structure by using Bracing ...
IRJET-  	  Review on Seismic Analyses of RC Frame Structure by using Bracing ...IRJET-  	  Review on Seismic Analyses of RC Frame Structure by using Bracing ...
IRJET- Review on Seismic Analyses of RC Frame Structure by using Bracing ...
 
Seismic Performance and Shear Wall Location Assessment of a RC Building- Eva...
Seismic Performance and Shear Wall Location  Assessment of a RC Building- Eva...Seismic Performance and Shear Wall Location  Assessment of a RC Building- Eva...
Seismic Performance and Shear Wall Location Assessment of a RC Building- Eva...
 
IRJET- Study of Literature on Seismic Response of RC Irregular Structure
IRJET-  	  Study of Literature on Seismic Response of RC Irregular StructureIRJET-  	  Study of Literature on Seismic Response of RC Irregular Structure
IRJET- Study of Literature on Seismic Response of RC Irregular Structure
 
Inelastic seismic performance of low-rise multi-story structure in hilly area...
Inelastic seismic performance of low-rise multi-story structure in hilly area...Inelastic seismic performance of low-rise multi-story structure in hilly area...
Inelastic seismic performance of low-rise multi-story structure in hilly area...
 
Study on Torsional Response of Irregualr Buildings Under Seismic Loading
Study on Torsional Response of Irregualr Buildings Under Seismic LoadingStudy on Torsional Response of Irregualr Buildings Under Seismic Loading
Study on Torsional Response of Irregualr Buildings Under Seismic Loading
 
Seismic and progressive collapse mitigation of shear energy dissipation beam ...
Seismic and progressive collapse mitigation of shear energy dissipation beam ...Seismic and progressive collapse mitigation of shear energy dissipation beam ...
Seismic and progressive collapse mitigation of shear energy dissipation beam ...
 
F012515059
F012515059F012515059
F012515059
 
ANALYSIS AND DESIGN OPTIMIZATION OF SHEAR-WALL IN CASE OF HIGH-RISE BUILDING ...
ANALYSIS AND DESIGN OPTIMIZATION OF SHEAR-WALL IN CASE OF HIGH-RISE BUILDING ...ANALYSIS AND DESIGN OPTIMIZATION OF SHEAR-WALL IN CASE OF HIGH-RISE BUILDING ...
ANALYSIS AND DESIGN OPTIMIZATION OF SHEAR-WALL IN CASE OF HIGH-RISE BUILDING ...
 
Capacity Spectrum Method for RC Building with Cracked and Uncracked Section
Capacity Spectrum Method for RC Building with Cracked and Uncracked SectionCapacity Spectrum Method for RC Building with Cracked and Uncracked Section
Capacity Spectrum Method for RC Building with Cracked and Uncracked Section
 
IRJET- Study of Behavior Parameters of the Building with Variations in Story ...
IRJET- Study of Behavior Parameters of the Building with Variations in Story ...IRJET- Study of Behavior Parameters of the Building with Variations in Story ...
IRJET- Study of Behavior Parameters of the Building with Variations in Story ...
 

More from IOSR Journals (20)

A011140104
A011140104A011140104
A011140104
 
M0111397100
M0111397100M0111397100
M0111397100
 
L011138596
L011138596L011138596
L011138596
 
K011138084
K011138084K011138084
K011138084
 
J011137479
J011137479J011137479
J011137479
 
I011136673
I011136673I011136673
I011136673
 
G011134454
G011134454G011134454
G011134454
 
H011135565
H011135565H011135565
H011135565
 
F011134043
F011134043F011134043
F011134043
 
E011133639
E011133639E011133639
E011133639
 
D011132635
D011132635D011132635
D011132635
 
C011131925
C011131925C011131925
C011131925
 
B011130918
B011130918B011130918
B011130918
 
A011130108
A011130108A011130108
A011130108
 
I011125160
I011125160I011125160
I011125160
 
H011124050
H011124050H011124050
H011124050
 
G011123539
G011123539G011123539
G011123539
 
F011123134
F011123134F011123134
F011123134
 
E011122530
E011122530E011122530
E011122530
 
D011121524
D011121524D011121524
D011121524
 

Recently uploaded

Current Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCLCurrent Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCLDeelipZope
 
Heart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptxHeart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptxPoojaBan
 
INFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETE
INFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETEINFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETE
INFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETEroselinkalist12
 
What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxWhat are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxwendy cai
 
Call Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile serviceCall Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile servicerehmti665
 
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...srsj9000
 
HARMONY IN THE HUMAN BEING - Unit-II UHV-2
HARMONY IN THE HUMAN BEING - Unit-II UHV-2HARMONY IN THE HUMAN BEING - Unit-II UHV-2
HARMONY IN THE HUMAN BEING - Unit-II UHV-2RajaP95
 
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ
 
Churning of Butter, Factors affecting .
Churning of Butter, Factors affecting  .Churning of Butter, Factors affecting  .
Churning of Butter, Factors affecting .Satyam Kumar
 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...Soham Mondal
 
power system scada applications and uses
power system scada applications and usespower system scada applications and uses
power system scada applications and usesDevarapalliHaritha
 
Artificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptxArtificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptxbritheesh05
 
Internship report on mechanical engineering
Internship report on mechanical engineeringInternship report on mechanical engineering
Internship report on mechanical engineeringmalavadedarshan25
 
Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024hassan khalil
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130Suhani Kapoor
 
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube ExchangerStudy on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube ExchangerAnamika Sarkar
 
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxJoĂŁo Esperancinha
 
Biology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptxBiology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptxDeepakSakkari2
 

Recently uploaded (20)

Current Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCLCurrent Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCL
 
Heart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptxHeart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptx
 
INFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETE
INFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETEINFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETE
INFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETE
 
What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxWhat are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptx
 
Call Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile serviceCall Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile service
 
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
 
HARMONY IN THE HUMAN BEING - Unit-II UHV-2
HARMONY IN THE HUMAN BEING - Unit-II UHV-2HARMONY IN THE HUMAN BEING - Unit-II UHV-2
HARMONY IN THE HUMAN BEING - Unit-II UHV-2
 
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
 
Churning of Butter, Factors affecting .
Churning of Butter, Factors affecting  .Churning of Butter, Factors affecting  .
Churning of Butter, Factors affecting .
 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
 
power system scada applications and uses
power system scada applications and usespower system scada applications and uses
power system scada applications and uses
 
Design and analysis of solar grass cutter.pdf
Design and analysis of solar grass cutter.pdfDesign and analysis of solar grass cutter.pdf
Design and analysis of solar grass cutter.pdf
 
Artificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptxArtificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptx
 
Internship report on mechanical engineering
Internship report on mechanical engineeringInternship report on mechanical engineering
Internship report on mechanical engineering
 
Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
 
young call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Service
young call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Serviceyoung call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Service
young call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Service
 
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube ExchangerStudy on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
 
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
 
Biology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptxBiology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptx
 

Strengthening of RC Framed Structure Using Energy Dissipation Devices

  • 1. IOSR Journal of Mechanical and Civil Engineering (IOSR-JMCE) e-ISSN: 2278-1684,p-ISSN: 2320-334X, Volume 8, Issue 5 (Sep. - Oct. 2013), PP 48-55 www.iosrjournals.org www.iosrjournals.org 48 | Page Strengthening of RC Framed Structure Using Energy Dissipation Devices Dr. R. B. khadiranaikar* , Dr. B. G. Naresh kumar* , Md. Aqeeb hussain** , Avinash Gornale** Abstract: A large numbers of existing buildings in India are severely deficient against earthquake forces and the number of such buildings is growing very rapidly. This paper presents a way of using energy dissipation devices for seismic strengthening of a RC framed structure. The objective was to improve the seismic performance of the building to resist the earthquake. The viscous dampers are used as an energy dissipation device in the form of single, double, inverted V, V type of dampers with different percentages of damping such as 10%, 20% and 30% to prevent building from collapse in a major earthquake and also to control the damage during earthquake. The performance of the buildings is assessed as per the procedure prescribed in ATC-40 and FEMA 356. Keywords: seismic performance, energy dissipation devices, non-linear static analysis. I. Introduction Earthquake is one of the major natural hazards to the life on the earth and has affected countless cities and villages of almost every continent. The damage caused by earthquakes are mostly to man mad structures. Hundreds of small earthquakes occur around the world every day and every year earthquakes take the lives of thousands of people. Therefore, it is necessary to design structures that are earthquake resistant. Earthquake engineering has gained lots of attention in recent years since it ensures design of safe structures, which can safely withstand earthquakes of reasonable magnitude. Conventional seismic design attempts to make building that do not collapse under strong earthquake shaking, but may sustain damage to non-structural elements and to some structural members in the building. This may cause the building to be non-functional after the earthquake, which may be problematic in some structures, like Hospitals, which need to remain functional after an earthquake. Special techniques are required to design buildings such that they remain practically undamaged even in a severe earthquake. The energy dissipation devices are recognized as a suitable technique to control the seismic response of the structure and reduce the damage caused by earthquake. EDD can absorb a portion of earthquake-induced energy in the structure and minimize the energy dissipation demand on the primary structure members such as beams, column and walls. These devices can substantially reduce the inter-story drift and, consequently, non-structural damage. These devices can improve the performance of the building to resist the earthquake. 1.1. Objectives of the study The main objectives of this study can be listed as follows; ď‚· To estimates the performance point and collapse load for the considered building for study under seismic loading. ď‚· To study the behavior of the building for incremental lateral load. ď‚· To estimate the increased performance of the building by using viscous dampers as a retrofitting method. II. Illustrative Examples The Layout of plan having 5X4 bays of equal length of 5m Figure 1. The buildings considered are Reinforced concrete frame building of ten storey’s with regular configurations. The storey height is kept uniform of 3m for building model which is as fallows,
  • 2. Strengthening of RC Framed Structure Using Energy Dissipation Devices www.iosrjournals.org 49 | Page Figure 1.plan of the building III. Analysis Methods Analysis methods are broadly classified as linear static, linear dynamic, nonlinear static and nonlinear dynamic methods. In these the first two methods are suitable when the structural loads are small and no point, the load will reach to collapse load and are differs in obtaining the level of forces and their distribution along the height of the structure. Whereas the non- linear static and non-linear dynamic analysis are the improved methods over linear approach. During earthquake loads the structural loading will reach to collapse load and the material stresses will be above yield stresses. So in that case material nonlinearity and geometrical nonlinearity should be incorporated into the analysis to get better results. These methods also provide information on the strength, deformation and ductility of the structures as well as distribution of demands. 3.1. Equivalent Static Method Equivalent static method of analysis is a linear static procedure, in which the response of building is assumed as linearly elastic manner. The analysis is carried out as per IS1893-2002 (Part 1) 3.2. Response Spectrum Method Linear dynamic analysis of the building models is performed using ETABS. The lateral loads generated by ETABS correspond to the seismic zone III and 5% damped response spectrum given in IS 1893-2002 (Part 1). The fundamental natural period values are calculated by ETABS, by solving the Eigen value problem of the model. Thus, the total earthquake load generated and its distribution along the height corresponds to the mass and stiffness distribution as modelled by ETABS. 3.3 Pushover Analysis Pushover analysis is one of the methods available to understand the behavior of structures subjected to earthquake forces. As the name implies, it is the process of pushing horizontally with a prescribed loading pattern incrementally until the structure reaches a limit state [ATC-40 1996]. The non linear static analysis (pushover analysis) is promising tool for seismic performance of existing and new structure. Pushover analysis gives an estimate of seismic capacity of the structural system and its components based on its material characteristics and detailing of member dimensions. The pushover analysis is essentially a step-by-step analysis procedure that applies a distribution of lateral story forces to a structural model develop from the moment curvature properties of the members the technique can be useful in evaluation structural response behavior and potential collapse mechanism. The pushover or capacity curve represents the lateral displacements as the function of force applied to the structure. Location of hinges in various stages can be obtained from pushover curve as shown in Figure- 2.The range AB is elastic range, B to IO is the range of immediate occupancy, IO to LS is the range of life safety, and LS to CP is the range of collapse prevention [ATC-40]. If all the hinges are within the CP limit then the structure is said to be safe. However, depending upon the importance of structure the hinges after IO range may also need to be retrofitted. Figure 2.Different Stages of Plastic Hinge Formation.
  • 3. Strengthening of RC Framed Structure Using Energy Dissipation Devices www.iosrjournals.org 50 | Page 3.4 Performance Point The maximum structural displacement expected for the demand earthquake ground motion represents the performance point. Performance point can also be defined as a condition for which the seismic capacity of the structure is equal to the seismic demand imposed on the structure by the specific ground motion. It can be obtained by the intersection of capacity spectrum and demand spectrum. To get the capacity spectrum it is necessary to convert the capacity curve, which is in terms of base shear and roof displacement, to what is called as capacity spectrum, which is a representation of capacity curve in Acceleration-Displacement Response Spectra (ADRS) format. The demand spectrum is the design acceleration spectrum given in IS: 1893 (Part 1)- 2002 modified for 5% damping (for the concrete structures), based on desired response reduction factor (depending on type of lateral load resisting system) and foundation soil type. Figure 3.Performance Point. IV. Results And Discussion 4.1 Energy absorption with different dampers The energy dissipation devices can absorb portion of energy induced during earthquake. The dampers used are single diagonal, double diagonal, inverted V and V type of viscous damper at different percentage of damping such viz 10%, 20% and 30%. The viscous dampers reduce the base shear in the building both in X and Y direction as the percentage of damping increases. By reducing base shear in the building the earthquake can be resisted. Figure 4.The variation of base shears with different percentage of damping in single diagonal damper. Figure 5.The variation of base shears at different percentage of damping with double diagonal dampers. Figure 6.The variation of base shears at different percentage of damping with inverted V type dampers. 0 500 1000 1500 2000 2500 0 10 20 30 base shear in x-direction base shear in y- direction BaseshearinKN percentage of damping 0 500 1000 1500 2000 2500 0 10 20 30 base shear in x direction base shear in y direction percentage og damping BaseshearinKN 0 500 1000 1500 2000 2500 0% 10% 20% 30% base shear in x direction base shear in y direction percentage of damping BaseshearinkN
  • 4. Strengthening of RC Framed Structure Using Energy Dissipation Devices www.iosrjournals.org 51 | Page Figure 7.The variation of base shears at different percentage of damping with V type dampers. In the Figure 4 the base shear of the structure can be reduced with the use of energy dissipation devices as viscous dampers. By the comparison of this Figure one can find out that the variation of base shear with different percentage of damping. This is because energy dissipation devices absorb energy during earthquake. So the variation of base shear with 0%, 10%, 20% and 30% of damping is 2093.23kN, 1536.28kN, 1268.08kN and 1183.08kN. Figure 5 shows the variation of base shear and percentage of damping. At different percentage of damping there is a reduction in base shear both in X and Y direction the reduction in base shear increase the capacity of the building to resist the earthquake. There is no much difference between reduction of base shear in single and double diagonal type of viscous dampers. From Figure 6 the result shows that there is a significant reduction in base shear at different percentage of damping. The comparison shows that the reduction of base shear in inverted V type of dampers is less compare to single and double diagonal dampers. Figure 7 show the reduction of base shear after installing V type of dampers at different percentage of damping. So by reducing base shear in the building the performance of the building can be increased during earthquake. The reduction in base shear of inverted V and V type dampers is almost same. 4.2 Hinge status along x-direction with different dampers. Performance point determined from pushover analysis is the point at which the capacity of the structure is exactly equal to the demand made on the structure by the seismic load. The performance of the structure is assessed by the state of the structure at performance point. This can be done by studying the status of the plastic hinges formed at different locations in the structure when the structure reaches its performance point. It is therefore important to study the state of hinges in the structure at performance point. The status of hinges at performance point for different models considered for the analysis i.e. for all models with different percentage of damping. Figure 8. The variation of displacement at different Percentage of damping Figure 9. The variation of collapse step and hinges from A-B at different percentage of damping 0 500 1000 1500 2000 2500 0% 10% 20% 30% base shear in x direction base shear in y direction percentage of damping BaseshearinKN 6 6 6 6 245 245 219 218 0% 10% 20% 30% percentage of damping number of steps hinges from a-b collapsestepsandhingesfromA-B 0.6314 0.631 0.5917 0.5912 0% 10% 20% 30% Percentage of damping single diagonal dampers displacement(mm)
  • 5. Strengthening of RC Framed Structure Using Energy Dissipation Devices www.iosrjournals.org 52 | Page Figure 10. the variation of displacement at different percentage of damping Figure 11. the variation of collapse step and hinges from A-B at different percentage of damping Figure 12. the variation of displacement at different percentage of damping Figure 13. the variation of collapse step and hinges from A-B at different percentage of damping Figure 14. the variation of displacement at different percentage of damping Figure 15. the value of collapse step and hinges from A-B at different percentage of damping 6 6 8 8 245 221 214 214 0% 10% 20% 30% percentage of damping number of steps hinges from A-B collapsestepsandhingesfromA-B 6 8 10 10 245 216 216 216 0% 10% 20% 30% percentage of damping number of steps hinges from A-B collapsestepsandhingesfromA-B 6 10 10 10 245 227 227 227 0% 10% 20% 30% number of steps hinges from A-B percentage of damping collapsestepsandhingesfromA-B 0.6314 0.5504 0.5323 0.5323 0% 10% 20% 30% double diagonal dampers percentage of damping displcement(mm) 0.6314 0.5837 0.5832 0.5832 0% 10% 20% 30% inverted v type dampers percentage of damping displcement(mm) 0.6314 0.5409 0.5409 0.5409 0% 10% 20% 30% V type dampers percentage of damping displcement(mm)
  • 6. Strengthening of RC Framed Structure Using Energy Dissipation Devices www.iosrjournals.org 53 | Page Figure 8 show that the displacement without dampers is 0.6314mm. After installation of energy dissipation devices the displacement at 10% of damping reduces to 0.6310mm, at 20% of damping it reduces to 0.5917mm and at 30% of damping it reduces to 0.5912mm. In the Figure 9 after installation of dampers with different percentage of damping the number of Hinges in the region A-B is reduced and different percentage of damping building collapse at step 6. Figure 10 show the variation of displacement with different percentage of damping. At different percentage of damping there is a significant reduction in displacement. Reduction in displacement increases the capacity of the building to resist the earthquake. When we use double diagonal type of viscous dampers the displacement is more compare to single diagonal dampers. In the Figure 11 the result show that the number of hinges in the region A-B is reduce at different percentage of damping. The building collapse at step 6 with 0% and 10% of damping, at step 8 with 20% and 30% of damping. From Figure 12 the result shows that there is a reduction at different percentage of damping. By comparing the displacement of inverted V, single diagonal and double diagonal type of dampers. The displacement in double diagonal dampers is more. Figure 13 show the variation of collapse step and hinges in the region A-B. After installation of dampers at 10% of damping building collapse at step8 then at 20% and 30% 0f damping building collapse at step10. The number of hinges forming in the region is 216 at different percentage of damping. In the Figure 14 the displacement in the building without damper is 0.6314mm. After installation of dampers the displacement in the building is constant i.e. 0.5409mm at different percentage of damping. Figure 15 shows that building without dampers collapse at step6. After installing dampers with different percentage of damping the building collapse at constant step i.e. step 10. The number of hinges forming in the region without dampers is 245. After installation of dampers in the building the hinges in the region forming are constant i.e. 227. By reducing hinges in the building earthquake can be resisted. 4.3 fundamental natural periods with different types of viscous dampers As per IS: 1893 (part 1) 2002 the fundamental natural period of vibration of a building is given by empirical formulae, which depend on the height of the building, and base dimensions of the structure. It also states that a free vibration analysis may be performed as per established methods to obtain the natural periods of the structure. It has been observed in all types of viscous dampers that the value of fundamental natural period is increasing as the percentage of damping increases. Figure 16.The variation of fundamental natural period at different percentage of damping from Figure 16 result show that at 0% of damping the fundamental natural period is 1.7001(sec).Then after installing single diagonal type of dampers at 10%, 20% and 30% of damping the fundamental natural period is increases to 0.30% by which building becomes more flexible during earthquake. In double diagonal type of dampers the fundamental natural period at 10%, 20%, 30% of damping the fundamental natural period increases to 0.37% by which building becomes more flexible during earthquake. In inverted V type of dampers the fundamental natural period at different percentage of damping increases to 0.43% by comparing with single diagonal type of bracing the fundamental natural period of inverted v type of dampers make the building more flexible. For V type of dampers the fundamental natural period at different percentage of damping increases to 0.48% which increases the flexibility of the building. 1.694 1.696 1.698 1.7 1.702 1.704 1.706 1.708 1.71 single diagona double diagonal inverted v v 0% 10% 20% 30% percentage of damping fundamentalnaturalperiodinsec
  • 7. Strengthening of RC Framed Structure Using Energy Dissipation Devices www.iosrjournals.org 54 | Page 4.4 Performance level in X and Y direction The performance level describes a limiting damage condition which may be considered satisfactory for a given building and a given ground motion. The limiting condition is described by the physical damage within the building, the threat to life safety of the buildings occupants created by the damage, and post-earthquake serviceability of the building. Target performance levels for structural and non structural systems are specified independently. Structural performance levels are given names and number of designation. While nonstructural performance levels are given names and letter designation. Building performance levels are a combination of a structural performance level and nonstructural performance level. Table 4.10 the values for comparison of results in x direction with different dampers Dampers displacem ent Base shear Performance level displaceme nt Base shear Performance level % of absorption Direction X Without dampers With dampers 0% damping 0.093 2093.23 LS-CP - - - - SD 10% 0.093 2093.23 LS-CP 0.068 1536.279 IO-LS 26.60% SD 20% 0.093 2093.23 LS-CP 0.056 1268.082 A-B 39.41% SD 30% 0.093 2093.23 LS-CP 0.052 1183.082 A-B 43.47% DD 10% 0.093 2093.23 LS-CP 0.068 1538.031 B-IO 26.52% DD 20% 0.093 2093.23 LS-CP 0.056 1269.528 B-IO 39.35% DD 30% 0.093 2093.23 LS-CP 0.053 1184.58 A-B 43.40% IV 10% 0.093 2093.23 LS-CP 0.068 1543.631 IO-LS 26.25% IV 20% 0.093 2093.23 LS-CP 0.056 1273.713 A-B 39.15% IV 30% 0.093 2093.23 LS-CP 0.053 1188.894 A-B 43.20% V 10% 0.093 2093.23 LS-CP 0.068 1544.583 B-IO 26.21% V 20% 0.093 2093.23 LS-CP 0.056 1274.501 A-B 39.11% V 30% 0.093 2093.23 LS-CP 0.053 1189.627 A-B 43.16% From the table 4.10 it is clear that in x-direction for model without damper the performance level is in between life safety level to collapse prevention level (LS-CP). So loss is acceptable in this region, then after installing damper at 10% of damping the performance level comes between immediate occupancy level to life safety level (IO-LS) so after installing dampers it comes to minor repair for single diagonal and inverted V, then at 20% and 30% it comes to elastic region i.e. (A-B) i.e. no damage region. For double diagonal and V type of viscous dampers at 10% of damping the performance level is in between B-IO so it is in damage control range then at 20% and 30% of damping it comes to A-B region i.e. no damage region. Table 4.11 the values for comparison of results in Y direction with different dampers dampers displacement Base shear Performance level Base shear Performance level % of absorption Direction Y Without dampers With dampers 0% 0.095 2053.349 LS-CP - - - SD 10% 0.095 2053.349 LS-CP 1506.968 IO-LS 26.63% SD 20% 0.095 2053.349 LS-CP 1243.888 A-B 39.41% SD 30% 0.095 2053.349 LS-CP 1160.656 A-B 43.47% DD 10% 0.095 2053.349 LS-CP 1508.689 IO-LS 24.82% DD 20% 0.095 2053.349 LS-CP 1245.309 A-B 38.06% DD 30% 0.095 2053.349 LS-CP 1161.982 A-B 42.10% IV 10% 0.095 2053.349 LS-CP 1514.13 B-IO 26.26% IV 20% 0.095 2053.349 LS-CP 1249.379 A-B 39.15% IV 30% 0.095 2053.349 LS-CP 1166.172 A-B 43.20% V 10% 0.095 2053.349 LS-CP 1515.072 B-IO 26.21% V 20% 0.095 2053.349 LS-CP 1250.157 A-B 39.11% V 30% 0.095 2053.349 LS-CP 1166.897 A-B 43.18% SD-single diagonal, DD-double diagonal, IV-inverted V and V type of dampers From table 4.11 it is clear that in y-direction for model without damper the performance level is in between life safety level to collapse prevention level (LS-CP). So loss is acceptable in this region then after installing damper at 10% of damping the performance level comes between immediate occupancy level to life safety level (IO-LS) so after installing dampers it comes to minor repair for single diagonal and double diagonal then at 20% and 30% it comes to elastic region i.e. (A-B) i.e. no damage region. For inverted V and V type of viscous dampers at 10% of damping the performance level is in between B-IO so it is in damage control range then at 20% and 30% of damping it comes to A-B region i.e. no damage region.
  • 8. Strengthening of RC Framed Structure Using Energy Dissipation Devices www.iosrjournals.org 55 | Page V. Conclusions: The aim of the project is to improve the capacity of the building to resist the earthquake using energy dissipation devices, particularly viscous dampers of different types such as single diagonal, double diagonal, inverted V and V type of viscous dampers. ď‚· The comparison of the results both in X and Y direction of all the type of viscous dampers indicates that by installing dampers in the structures we can reduce the base shear of the building. So by reducing base shear in the concrete frame structure, we can increase the capacity of the building to resist the earthquake. ď‚· By comparing the results of both single diagonal and double diagonal type of viscous dampers the percentage reduction in base shear of single diagonal is 26.60% and double diagonal is 26.52%. So the percentage reduction in double diagonal is low but providing double diagonal type of viscous dampers is better than single diagonal type of viscous dampers, because we don’t know in which direction earthquake will occur. ď‚· By installing the viscous dampers of different types at 10, 20, 30% of damping we can increase the fundamental natural period which makes the structure more flexible during earthquake. And by comparing fundamental natural period of all the four type of viscous dampers the increase in fundamental natural period of V type of viscous damper is more. ď‚· By comparing the results of performance point in x and y direction, we can conclude that after installing dampers the performance level from region LS-CP comes to region A-B. So, by installing dampers we can improve the performance level of the building to resist the earthquake. ď‚· By installing viscous dampers we can reduce the displacement in the building which makes the building earthquake resistant. ď‚· Model without dampers collapse at step 6, after installing single diagonal type of dampers building also collapse at step 6, in double diagonal type of dampers building collapse at step 8 and for both inverted V and V type of dampers building collapse at step 10.so by installing dampers with different percentage of damping in the structure we can increase the lateral load coming to the building during earthquake. References: [1]. Vijay Chachapara, Sharadkumar Purohit and P. V. Patel. (2011). “Seismic Response Control of the Building using Passive Devices” Civil Engineering Department, Institute of Technology, Nirma University, Ahmedabad 382 481 [2]. ali sehat tabatabaei. (2003). “Energy Dissipation Systems for Siesmic Resistance” civil engineering university of east London. [3]. Fahim sadek, Bijan mohraz And Michael a riley. (2000). “Improved Linear Procedures for Analysis of Structures with Passive Energy Dissipation Devices” National Institute of Standards and Technology, Gaithersburg, MD [4]. K. Sathish Kumar, C. Antony Jeyasehar and K. Muthumani. (2012). “A Design Methodology for Supplemental damping for Seismic Performance Enhancement of Frame Structures” asian journal of civil engineering (building and housing) vol. 13, no. 5 (2012) pages 659-678 [5]. IS: 1893 – 2002 (Part 1), “Criteria for Earthquake Resistant Design of Structures”, part 1-General provisions and buildings, fifth revision, Bureau of Indian Standard, New Delhi, India. [6]. IS: 456-2000., “Code of Practice for Plain and Reinforced Concrete”, Bureau of Indian Standard, New Delhi, India. [7]. ATC, 1996, “Seismic Evaluation and Retrofit of Concrete Buildings”, Volume 1, [8]. ATC-40 Report, Applied Technology Council, Redwood City, California. [9]. Federal Emergency Federal Agency, FEMA-356. Pre-standard and Commentary [10]. for Seismic Rehabilitation of Buildings. Washington DC, 2000. [11]. Durgesh C. Rai. “Supplemental Damping for Seismic Strengthening: a Case Study”. Department of Earthquake Engineering, University of Roorkee, Roorkee 247 667, India. [12]. S.K. Ahirwar, S.K. Jain and M. M. Pande. (2008). “Earthquake Loads on Multistory Buildings as per IS: 1893-1984 and IS: 1893- 2002: A Comparative Study” The 14 World Conference on Earthquake Engineering October 12-17, 2008, Beijing, China.