Loop Calibration and
Maintenance
Application Note
Introduction
Process instrumentation
requires periodic calibration
and maintenance to ensure that
it is operating correctly. This
application note contains
information to help guide tech-
nicians through some of the
more common loop calibration
tasks using Fluke tools.
Fluke loop calibrators are
ideal for a wide variety of cali-
bration applications. They
include:
• Fluke 707 Loop Calibrator
• Fluke 705 Loop Calibrator
• Fluke 715 Volt/mA Calibrator
• Fluke 787 ProcessMeter
A summary of the features of
Fluke’s loop calibrators and a
glossary of terms are at the end
of this application note.
Field testing loop
powered isolators
The loop-powered isolator and
the two-wire isolating trans-
mitter are two of the more
prevalent devices in use in
4-20 mA control loops today
(see Figure 1). The testing and
troubleshooting procedures for
each are different and need to
be understood by the techni-
cians performing operational
checks on these units in the
field.
Loop-powered isolators
The main purpose of a loop
isolator is to eliminate ground
loops in control systems while
sending the control signal
current to another part of the
system. Loop-powered
isolators, unlike two-wire
transmitters, draw their operat-
ing power from the “input” side
of the isolator (see Figure 1),
which requires a pickup voltage
from 5.5 V to 13.5 V depending
on the manufacturer.
The output of the loop isola-
tor is an electrically isolated
mirror image of the input side
current. The compliance voltage
associated with the output is
greatly reduced from that of the
input side and ranges around
7.5 V. This produces a total loop
loading capability of 350 Ω.
This limited loop drive capabil-
ity is the primary limitation of
the loop isolator.
Two-wire transmitters
Isolating two-wire transmitters
provide the same isolating
functionality as loop isolators
with the added advantage that
many provide signal condition-
ing for a variety of inputs such
as thermocouple, frequency, dc
current, RTD, strain gauge, and
other process inputs. The
power supplied to a two-wire
transmitter is connected to the
output side of the transmitter.
The two-wire transmitter mod-
ulates the current from the
power supply between 4-20 mA,
proportional to the input.
Typical power supplies for two-
wire transmitters range from
24 V to 48 V. Power supplies of
this size allow a significant loop
load capability on the output.
Figure 1
Field checking a
loop-powered isolator
Fluke loop calibrators have a
unique current simulation fea-
ture that, when connected to
an external power source,
allows you to precisely control
current between 0 mA and 24
mA. When field checking a
loop-powered isolator, the two-
wire loop transmitter supplying
signal current to the isolator for
the loop may be removed and
the calibrator connected in
simulate mode to control loop
current (Figure 2).
Connecting the Fluke
loop calibrator
In this example, we will use
the Fluke 787 Process Meter.
Although the operating controls
vary, this application can also be
performed using the Fluke 707,
715, and 705 loop calibrators.
1. Disconnect the main loop
transmitter and connect the
Fluke 787 to the loop with
the test leads plugged into
the center or “Simulate” ter-
minals of the calibrator (see
Figure 2).
2. Set the 787 rotary switch to
the mA Output mode. Set the
Fluke 787 to the 4-20 mA
output mode. Make connec-
tion for simulate mA. The
787 is now outputting a pre-
cise 4 mA and is providing
operating power to the input
of the loop-powered isolator.
3. Place a Fluke 87, 187 or
equivalent multimeter (1 µA
resolution is ideal; 10 µA is
acceptable), set in the mA
measurement mode, on the
output side of the isolator to
monitor output current (see
Figure 2).
4. Adjust the zero control on
the isolator for a reading of
4.000 mA on the output
meter.
5. Step the input current to
20 mA using the % step
button ▲ (25% or 4 mA
increase) and adjust the
span control on the isolator
to read 20.000 mA on the
output meter connected to
the isolator.
6. Step input current down
to 4 mA using the ▼ button
(25% or 4 mA decrease) and
check for a zero shift, adjust
if necessary.
7. At this point, basic zero
and span adjustments are
complete.
Check linearity
Fluke loop calibrators can eas-
ily check the linearity of your
loop isolator using the % step
buttons ▲ and ▼. Pushing
these buttons when in the out-
put mode increases or
decreases the output current in
25% steps. In the 4-20 mA
current mode these intermedi-
ate steps are at 8 mA (25%), 12
mA (50%), and 16 mA (75%).
To check linearity of the isola-
tor, push the associated % step
buttons up and down and con-
firm that the digital multimeter
(DMM) is reading the same
value as is shown on the loop
calibrator display. A variation
from expected values should be
compared to the linearity limits
stated by the manufacturer of
the loop-powered isolator.
Testing valve positioners
Electronic valve positioners
should receive periodic in-field
calibrations as part of preven-
tive maintenance programs.
Fluke loop calibrators are the
ideal test tools for these
checks. Valve positioners vary
in design and valve type and
should be calibrated using spe-
cific instructions from the
individual manufacturer.
Quick operational checks can
be performed using a field cali-
brator as a signal source while
observing the valve stem posi-
tion, mechanical position
indicators, or flow indicators as
input changes are made. Fluke
loop calibrators provide a con-
venient source for simulating
the controller output to a valve
positioner.
The following example
shows a general method for an
in-field operational check of a
valve fitted with an electronic
valve positioner. These meth-
ods may be adapted to various
types of valves, however, man-
ufacturer’s specific instructions
should always be consulted for
proper and appropriate tech-
niques. In the following
example, valve operation and
movement is checked either by
feel or by observing valve stem
movement.
787 PROCESSMETER
MIN MAX RANGE HOLD H
REL Hz
400100030
Auto
MINMAXAVG
ACmV
%OUTPUT
DC
mA
Mk
kHz
OFF
A mA COM V
30mA
FUSED0.44A
(1A /30 sec)
FUSED
mV
V
V
OUTPUT 0-24mA
SOURCE SIMULATE
+ +
% STEP COARSE FINE
mA
mA
A
mA
OUTPUT
1000V
CAT
Figure 2
2 Fluke Corporation Troubleshooting and Maintenance Using Fluke Loop Calibrators
Step 1: Basic set-up. Setting
the Fluke 707 loop calibra-
tor current output
Place the calibrator in the 4-20
mA output current mode.
Connect the 707 to the input
terminals of the valve posi-
tioner (see Figure 3).
Step 2: Zero adjustment
Set the 707 to an output of 4
mA and allow some time for
valve stem movement to stabi-
lize. Quickly decrease the
current from 4 mA to 3.9 mA
by depressing and turning the
vernier knob in a counter-
clockwise direction. You can
operate the 707 with one hand
while feeling the valve stem
with your free hand to check
for any sign of movement.
Adjust for zero movement
between these two current set-
tings by using the zero
adjustment on the positioner.
Increase and decrease cur-
rent from 4 mA to 4.1 mA using
the vernier knob in the
depressed position. Insure that
the valve stem just begins
movement above the 4.1 mA
setting and fully closed at 4 mA.
Step 3: Span (full open)
position check
Using the 25% button, step the
calibrator output value to
20 mA and allow the valve to
stabilize. Step the input to
20.1 mA using the vernier knob
in the depressed position turn-
ing clockwise while watching
or feeling for movement of the
valve stem. Minimize this move-
ment using the span adjust-
ment on the valve positioner.
Using the vernier knob in
the depressed position, adjust
current up and down between
20.10 mA and 19.9 mA. There
should be no movement of the
valve stem above 20 mA and a
slight movement below 20 mA.
Step 4: Check zero and
span again
Many positioners have interac-
tive zero and span controls.
This step will help insure proper
valve position adjustment.
Repeat Step 2 and Step 3.
Step 5: Linearity check
For valves with linear action,
linearity can be checked by
setting the 707 to 4 mA and
stepping current to 12 mA
(50%) while observing valve
travel. If your valve is of a non-
linear type, refer to the valve
manual for proper operational
checks.
Step 6: Stroking the valve
Checking for smooth valve
operation is easy to accomplish
using the slow ramp function of
the 707.
• Set the calibrator to mA
source mode and select the
slow ramp function ( ) by
depressing the 25% and 0-
100% buttons simultaneously.
• Allow the calibrator to ramp
through several cycles while
watching or feeling for any
abnormal operation of the
valve, such as sticking in
one position momentarily or
erratic movement.
Flow
Positioner
Fluke 707
Figure 3
Troubleshooting and Maintenance Using Fluke Loop Calibrators Fluke Corporation 3
∨
Calibrating voltage input
signal conditioners
Fluke loop calibrators are ideal
for calibrating many 4-20 mA
signal conditioners using their
precision current sourcing and
simulation capabilities. However,
there are many signal condi-
tioners that require a precision
voltage source for proper cali-
bration. Using a simple
precision resistor and standard
connector, Fluke loop calibra-
tors can field calibrate many
standard and non-standard
voltage input signal condition-
ers. This approach works well
for the 705, 707 and 787 loop
calibration tools (this is not
necessary with the 715 loop
calibrator as it has a precision
direct voltage output).
Voltage input signal condi-
tioners come in many varieties.
The most common are 0-10 V,
0-5 V and 1-5 V input levels.
Typical outputs of these devices
are an isolated or non-isolated
0-10 V or 4-20 mA. Resistors
with values of 250 Ω to 500 Ω
are common loop load resistors
and provide voltage input lev-
els as a function of the loop
current (see Figure 4).
Using Fluke loop calibrators
as a voltage source
A precision shunt resistor may
be used to derive voltages for
calibration using the calibra-
tor’s current source mode.
Using this system, Fluke loop
calibrators are capable of gen-
erating voltages for devices
with input spans as low as 10
mV to as high as 24 V. Table 1
gives values of precision resis-
tors to accommodate a variety
of voltage calibrations and the
Fluke calibrator ideal for each
application.
Constructing a precision
load resistor assembly
A simple precision current
shunt can be constructed using
a precision RN60, 1 W resistor,
(see table for the correct value),
a dual banana jack connector
and some test leads with alli-
gator clips (see Figure 5). The
RN60 class resistor is available
from many commercial sources.
Construct the assembly as
shown in Figure 5. This preci-
sion resistor assembly, coupled
with the precision current
sourcing capabilities of Fluke
loop calibrators, generates pre-
cision voltages to cover 1-5 V
or 2-10 V applications. The
1,000 Ω assembly has an
advantage in that it allows a
direct one-to-one display cor-
relation to voltage when
sourcing current from the Fluke
loop calibrator during calibra-
tion (1 mA = 1 V). The following
example will utilize a 250 Ω to
take advantage of the 0-100%
and 25% buttons on the Fluke
707 (25% or 4 mA = 1 V).
4 Fluke Corporation Troubleshooting and Maintenance Using Fluke Loop Calibrators
Figure 4
Resistor Sourced Generated Fluke Loop
Value Application Current Value Voltage Calibrator
10 Ω mV 0-20.000 mA 0-200.00 mV 707, 705, 787
transducer
250 Ω 0-5 V Source 0-20.000 mA 0-5.000 V 705, 707
1000 Ω 0-10 V Source 0-12.000 mA 0-12.000 V 705, 707, 787
Note: Input impedance of the device under test should be ≥ 1 MΩ
Table 1. Values of precision resistors to accommodate a variety of voltage calibrations
Figure 5
Constructing a precision current shunt
Parts required:
1. Resistor: 1000 Ω
Type: RN60 (50 ppm@70 °C) 1 W
2. 36˝ test leads with alligator clips
3. Connector: Dual Banana Plug 2/screw terminals
Fluke Display Input Output
Reading % Input Voltage Current
4.000 0 1.000 V 4.000 mA
8.000 25 2.000 V 8.000 mA
12.000 50 3.000 V 12.000 mA
16.000 75 4.000 V 16.000 mA
20.000 100 5.000 V 20.000 mA
Calibrating the signal
conditioner
The following is a procedure
for calibrating a 1-5 V input, 4-
20 mA output signal
conditioner using the precision
current shunt constructed in
Figure 5.
Step 1: Setting the Fluke 707
to source 4-20 mA
1. With the shunt assembly in
the “source” jacks, power
the 707 on.
2. Check the display. If the dis-
play does not read 4 mA,
turn the 707 off and on
again while holding the
mode button for two sec-
onds. The display should
now read 4.000 mA.
Step 2: Calibrating
1. Place a precision multimeter,
such as the Fluke 87 DMM,
set to dc current mode, in
series with the output of the
signal conditioner as shown
in Figure 6.
2. Connect the test leads from
the precision shunt assembly
to the signal conditioner
input terminals, observing
proper polarity.
3. With the 707 set in the mA
source mode, the display
should read 4.000 mA (1.00
V across the shunt).
4. Adjust the zero control on
the signal conditioner for an
indication of 4.000 mA on
the DMM.
5. Press the 0-100% button on
the 707 until the display
reads 20.000 mA. Then
adjust the span adjustment
on the signal conditioner
until the display on the
DMM reads 20.000 mA.
6. Push the 0-100% button and
the 707 should read 4.000.
Verify the meter connected
to the output signal condi-
tioner reads 4.000 mA.1
7. Calibration is now complete.
Note: Many manufacturers specify
a warm-up time prior to beginning
calibration.
Step 3: Checking linearity
Once zero and span controls
have been properly set, signal
conditioner linearity may be
verified using the following
procedure. This procedure will
check zero, 25%, 50%, 75%
and span settings for signal
conditioner linearity.
1. With the precision resistor
assembly in place, adjust the
source current of the Fluke
loop calibrator to 4 mA (1.0
V) using the 25% button.
The DMM displays 4 mA.
2. Using the 25% button, step
the source current to 25%,
50%, 75% and 100% and
note the corresponding val-
ues. Table 2 shows the
correct values of output for a
linear signal conditioner. (If
values differ from that
shown in Table 2 by more
than the linearity specifica-
tion of the signal
conditioner, contact the sig-
nal conditioner manufacturer
or replace the device.)
Making fine adjustments
Many signal conditioners with
0-20 mA and 4-20 mA outputs
are notorious for zero and span
control interaction. If, when
checking linearity in the cali-
bration section, your output
meter displayed a value higher
or lower than 4 mA, perform
the following steps to affect the
required 4 and 20 mA display
on the output meter.
1. Note the value above or
below 4 mA that was dis-
played on the output meter
when you returned to a
source value of 4.000 mA on
the 707. Adjust the zero con-
trol on the signal conditioner
so the value of the output
meter shows one-half the
difference of the remaining
mA value to 4 mA.
Example: If your display
reading at zero input in step
7 was 3.50 mA adjust the
output (with 4.000 mA
source current) to display a
reading of 3.75 mA, which is
one-half the delta toward
the desired value of 4 mA
(eg. 4.00 - 3.50 = 0.50;
0.05 / 2 + 3.50 = 3.75, or
one-half the difference
between the reading and
the desired value).
Troubleshooting and Maintenance Using Fluke Loop Calibrators Fluke Corporation 5
Figure 6
1
If your output meter displayed a value higher
or lower than 4 mA, consult the “Making fine
adjustments” section on this page.
Table 2. Correct value of output for a linear signal conditioner
6 Fluke Corporation Troubleshooting and Maintenance Using Fluke Loop Calibrators
2. Set the source current of the
707 to 20.000 mA using the
0-100% button. Note the
“output” meter display read-
ing. Adjust the span control
of the signal conditioner
one-half the delta from
20.000 mA.
Example: If the output dis-
play reads 21 mA. Adjust the
span control to 20.5 mA
(one-half the delta to the
required value of 20 mA).
3. Repeat this “one-half step”
process until the required
output is obtained. There are
signal conditioners that have
non-interactive controls that
do not require this procedure.
Verifying process scaled,
indicators
Scaled process indicators are
used to provide information
about a process either locally
or to a control room located a
distance away. These indicators
typically take a mA measure-
ment in series with the 4-20
mA loop signal or measure a
1 V-5 V drop across a 250 ohm
resistor in series with the 4-20
mA signal (a 4-20 mA signal
through a 250 ohm resistor
produces a 1 V to 5 V drop).
For indicators with a mA
input, the direct mA current
output of a 705, 707, 715 or
787 can be applied directly to
the input of the indicator. For
voltage input indicators, a 715
is ideal with its direct voltage
output. Or use a resistor across
the output of a 705, 707, or
787 as described previously
(“Using Fluke loop calibrators
as a voltage source”).
This example will show how
to use the 707 to verify a mA
input indicator. Make connec-
tions as shown in Figure 7.
1. Power the 707 up; the default
output should be 4 mA. Note
the indication, (digital or ana-
log) which should be
approximately 0%.
2. Depress the 0-100% button
on the 707; it is now in the
span check mode and is out-
putting 20 mA. Note the
indication (approximately
100%).
3. If testing the linearity is nec-
essary, use the 25% button to
step the mA output in 4 mA
steps and record the indica-
tions.
4. To calculate the errors in per-
cent, use the formula:
Nominal - Actual/Span x 100
Nominal is the ideal value,
actual is the recorded meas-
urement and span is 16 (4-20
mA = a 16 mA span).
Example: If the indication
with 0% applied is 1%, cal-
culate error as such: 0-1/16 =
.0625 X 100 = 6.25% error.
Calculate error based on the
recorded indications and
compare to the tolerances for
the indicator. If any of the
calculated errors are too
large, adjustment may be
necessary. Normally, there
are at least two adjustments
for analog indicators: zero
and span. The zero adjust-
ment is typically on the
faceplate of the indicator.
5. With an output of 4.000 mA
from the 707 adjust the zero
indication. Span adjustment
is either a hard adjustment or
accomplished by bending a
linkage on the meter move-
ment. Refer to the manu-
facturer’s procedure for this
adjustment.
6. Apply a 20.000 mA signal to
the indicator and make the
adjustment as specified. Once
the adjustment is completed,
re-verify the indicator and
confirm the adjustments had
the desired effect. If the indi-
cator still fails the test, it will
either need to be readjusted
until a satisfactory result is
attained, or replaced.
Voltage input indicators
The procedure for using the 707
to verify voltage input indicators
is almost identical to the proce-
dure outlined. The primary
difference is the addition of the
precision 250 ohm adapter.
0%
50%
100%
+
–
Indicator
Input
Figure 7
Accessories 707 Loop Calibrator 715 Volt/mA Calibrator 705 Loop Calibrator 787 ProcessMeter
787CAL Calibration Kit •
80T-IR Infrared Probe • •
80TK Thermocouple • •
80T-150U Temperature Probe • •
TL20/22/24/26/28 Lead Sets • • • •
TL70A/TL75/Y8140A Lead Sets • • • •
AC20/AC80 Clips • • • •
TP20 Industrial Test Probes • • • •
80i-400 AC Current Clamp •
i410 AC/DC Current Clamp • 2 1
i1010 AC/DC Current Clamp • 2 1
C10 Holster, C12A Case • •
C25/C28/V90/C100/C800 Cases • •
C510 Leather Case • •
80K-6/80K-40 High Voltage Probe •
83RF/85RF High Frequency Probes •
PV350 Pressure Vacuum Module • •
Fiber Optic Meter FOM • •
120 amps ac minimum 2dc current only
Troubleshooting and Maintenance Using Fluke Loop Calibrators Fluke Corporation 7
Fluke Loop Calibrator Considerations and Selection
Fluke loop calibration tools have a variety of different performance features and capabilities that
differentiate the models. The charts below will help you determine which model best fits your needs:
707 715 705 787
Loop Calibrator Volt/mA Calibrator Loop Calibrator ProcessMeter
• One-handed quick click • Source or simulate • Simultaneous mA and • Two instruments in one:
operation 24 mA loop current % of span display -Professional DMM
• Simultaneous mA and % • Source voltage to • Accuracy and resolution -Loop calibrator
of span display 100 mV or 10 V • Span check • Precise control of
• Push button 25% steps • Measure voltage output • Auto ramping and loop current
• 0.015% accuracy and process signals stepping • Auto ramping & stepping
1 microamp resolution • High level of safety
Function in any current mode (Cat III)
Measure
DMM capabilities •
V dc 28 V 10 V 28 V 1000 V
V ac (true-rms) 1000 V
Ω 40 MΩ
A dc 24 mA 24 mA 24 mA 30 mA, 1 A
A ac 1 A
Frequency Hz/CPM 20 kHz
mA accuracy 0.015% 0.015% 0.020% 0.05%
Span check • •
Source/Simulate
V dc 10 V
Source voltage with
µV resolution •(1-10 Volts)
mA dc/% scale 24 mA 24 mA 24 mA 24 mA
mA source:
• • •auto step, auto ramp
Record
Min Max •
Hold •
Features
24 V loop supply • • •
Drive capability 24 V compliance 24 V compliance 24 V compliance 12 V compliance
Warranty 3 year 3 year 3 year 3 year
IEC 61010 category/ 30 V 30 V 30 V 1000 V, CAT III
max voltage
Glossary of terms
4-20 mA loop A 4-20 mA signal that is representative of a process variable or a control
signal that controls a process variable.
Compliance voltage The voltage a current source develops when attempting to drive a mA
signal through a resistive load.
DMM Digital multimeter.
Electronic valve positioners Devices that can control the flow in a process with input from a mA or
digital control signal.
Ground loop A difference in potential (voltage) between (2) signal grounds.
Linearity The closeness of a calibration curve to a specified straight line. Linearity
is expressed as the maximum deviation of any calibration point from a
specified straight line.
Loop-powered isolator A device that produces an electrically isolated mirror image of the input
side 4-20 mA current.
mA Milliamp; a unit of electric current equal to one thousandth of an ampere.
Precision current shunt A conductor joining two points in a circuit to form a parallel circuit,
through which a precision voltage can be measured or derived.
RTD Resistance temperature device, a temperature measurement sensor that
has predictable changes in resistance with a change in temperature.
Signal conditioner A circuit to modulate a signal so as to make it intelligible to, or compati-
ble with, another device, including such manipulation as pulse shaping,
pulse clipping, compensating, digitizing, and linearizing.
Strain gauge A measuring element for converting force, pressure, tension, etc., into an
electrical signal.
Thermocouple A junction of dissimilar metals that generates a small voltage correlated
to the temperature of the junction.
µA or uA Microamp; a unit of electric current equal to one millionth of an ampere.
Vernier A small, movable, graduated scale running parallel to the fixed graduated
scale and used for measuring a fractional part of one of the divisions of
the fixed scale.
Fluke Corporation
PO Box 9090, Everett, WA USA 98206
Fluke Europe B.V.
PO Box 1186, 5602 BD
Eindhoven, The Netherlands
For more information call:
In the U.S.A. (800) 443-5853 or
Fax (425) 446-5116
In Europe/M-East/Africa (31 40) 2 675 200 or
Fax (31 40) 2 675 222
Canada (800)-36-FLUKE or
Fax (905) 890-6866
Other countries (425) 446-5500 or
Fax (425) 446-5116
Web access: http://www.fluke.com
©2001 Fluke Corporation. All rights reserved.
Trademarks are the property of their respective owners.
Printed in U.S.A. 8/2001 1627722 A-ENG-N Rev A
Printed on recycled paper.
Fluke.Keeping your world
up and running.

More Related Content

What's hot

Advanced motion controls se10a40
Advanced motion controls se10a40Advanced motion controls se10a40
Advanced motion controls se10a40Electromate
 
10 - Ac Power Regulators & Control Power Transformers - Fuji Electric
10 - Ac Power Regulators & Control Power Transformers - Fuji Electric10 - Ac Power Regulators & Control Power Transformers - Fuji Electric
10 - Ac Power Regulators & Control Power Transformers - Fuji ElectricCTY TNHH HẠO PHƯƠNG
 
Advanced motion controls be25a20
Advanced motion controls be25a20Advanced motion controls be25a20
Advanced motion controls be25a20Electromate
 
Advanced motion controls be40a8
Advanced motion controls be40a8Advanced motion controls be40a8
Advanced motion controls be40a8Electromate
 
Current To Pneumatic Converter for Process Control
Current To Pneumatic Converter for Process ControlCurrent To Pneumatic Converter for Process Control
Current To Pneumatic Converter for Process ControlClassic Controls, Inc.
 
Advanced motion controls b25a20
Advanced motion controls b25a20Advanced motion controls b25a20
Advanced motion controls b25a20Electromate
 
Advanced motion controls be40a20
Advanced motion controls be40a20Advanced motion controls be40a20
Advanced motion controls be40a20Electromate
 
Advanced motion controls 25a20
Advanced motion controls 25a20Advanced motion controls 25a20
Advanced motion controls 25a20Electromate
 
Advanced motion controls 30a8
Advanced motion controls 30a8Advanced motion controls 30a8
Advanced motion controls 30a8Electromate
 
Micro Processor Mini Project,Electronic Quiz Table
Micro Processor Mini Project,Electronic Quiz TableMicro Processor Mini Project,Electronic Quiz Table
Micro Processor Mini Project,Electronic Quiz TableSubhashini Sundaram
 
Advanced motion controls be30a8
Advanced motion controls be30a8Advanced motion controls be30a8
Advanced motion controls be30a8Electromate
 
automation of waterpump using 8051 microcontroller
automation of waterpump using 8051 microcontrollerautomation of waterpump using 8051 microcontroller
automation of waterpump using 8051 microcontrollerParth Joshi
 
Cascade pid controllers
Cascade pid controllersCascade pid controllers
Cascade pid controllersahshamseldin
 
Advanced motion controls b40a20
Advanced motion controls b40a20Advanced motion controls b40a20
Advanced motion controls b40a20Electromate
 
Advanced motion controls 50a8
Advanced motion controls 50a8Advanced motion controls 50a8
Advanced motion controls 50a8Electromate
 
Advanced motion controls b40a8
Advanced motion controls b40a8Advanced motion controls b40a8
Advanced motion controls b40a8Electromate
 

What's hot (19)

Advanced motion controls se10a40
Advanced motion controls se10a40Advanced motion controls se10a40
Advanced motion controls se10a40
 
10 - Ac Power Regulators & Control Power Transformers - Fuji Electric
10 - Ac Power Regulators & Control Power Transformers - Fuji Electric10 - Ac Power Regulators & Control Power Transformers - Fuji Electric
10 - Ac Power Regulators & Control Power Transformers - Fuji Electric
 
Advanced motion controls be25a20
Advanced motion controls be25a20Advanced motion controls be25a20
Advanced motion controls be25a20
 
Advanced motion controls be40a8
Advanced motion controls be40a8Advanced motion controls be40a8
Advanced motion controls be40a8
 
Current To Pneumatic Converter for Process Control
Current To Pneumatic Converter for Process ControlCurrent To Pneumatic Converter for Process Control
Current To Pneumatic Converter for Process Control
 
Advanced motion controls b25a20
Advanced motion controls b25a20Advanced motion controls b25a20
Advanced motion controls b25a20
 
Substation commissioning1
Substation commissioning1Substation commissioning1
Substation commissioning1
 
Substation commissioning1
Substation commissioning1Substation commissioning1
Substation commissioning1
 
Advanced motion controls be40a20
Advanced motion controls be40a20Advanced motion controls be40a20
Advanced motion controls be40a20
 
Advanced motion controls 25a20
Advanced motion controls 25a20Advanced motion controls 25a20
Advanced motion controls 25a20
 
I_P Converter final
I_P Converter finalI_P Converter final
I_P Converter final
 
Advanced motion controls 30a8
Advanced motion controls 30a8Advanced motion controls 30a8
Advanced motion controls 30a8
 
Micro Processor Mini Project,Electronic Quiz Table
Micro Processor Mini Project,Electronic Quiz TableMicro Processor Mini Project,Electronic Quiz Table
Micro Processor Mini Project,Electronic Quiz Table
 
Advanced motion controls be30a8
Advanced motion controls be30a8Advanced motion controls be30a8
Advanced motion controls be30a8
 
automation of waterpump using 8051 microcontroller
automation of waterpump using 8051 microcontrollerautomation of waterpump using 8051 microcontroller
automation of waterpump using 8051 microcontroller
 
Cascade pid controllers
Cascade pid controllersCascade pid controllers
Cascade pid controllers
 
Advanced motion controls b40a20
Advanced motion controls b40a20Advanced motion controls b40a20
Advanced motion controls b40a20
 
Advanced motion controls 50a8
Advanced motion controls 50a8Advanced motion controls 50a8
Advanced motion controls 50a8
 
Advanced motion controls b40a8
Advanced motion controls b40a8Advanced motion controls b40a8
Advanced motion controls b40a8
 

Viewers also liked

Alf2007 Workingwith Media
Alf2007 Workingwith MediaAlf2007 Workingwith Media
Alf2007 Workingwith Mediapeddoc07
 
Autoingles on the road.guía
Autoingles on the road.guíaAutoingles on the road.guía
Autoingles on the road.guíalinmimei
 
Energiatakarekossagi Tippfuzet Web
Energiatakarekossagi Tippfuzet WebEnergiatakarekossagi Tippfuzet Web
Energiatakarekossagi Tippfuzet WebCsaba Kocsis
 
מחזורר 15
מחזורר 15מחזורר 15
מחזורר 15ronits
 
áLbum de fotografías
áLbum de fotografíasáLbum de fotografías
áLbum de fotografíaslinmimei
 
Eac1 resuelto mme
Eac1 resuelto mmeEac1 resuelto mme
Eac1 resuelto mmelinmimei
 
Más de chicho y chispa
Más de chicho y chispaMás de chicho y chispa
Más de chicho y chispalinmimei
 
Con mucho carino
Con mucho carinoCon mucho carino
Con mucho carinolinmimei
 
áLbum de fotografías
áLbum de fotografíasáLbum de fotografías
áLbum de fotografíaslinmimei
 
Műanyag zacskók veszélyei
Műanyag zacskók veszélyeiMűanyag zacskók veszélyei
Műanyag zacskók veszélyeiCsaba Kocsis
 
House For Sale Expanded Ranch
House For Sale Expanded RanchHouse For Sale Expanded Ranch
House For Sale Expanded RanchJohn Taylor
 
2201 m01b1 eac2_solucio_1011s2
2201 m01b1 eac2_solucio_1011s22201 m01b1 eac2_solucio_1011s2
2201 m01b1 eac2_solucio_1011s2linmimei
 
Performance Based Internal Quality Audit Guide
Performance Based   Internal Quality Audit GuidePerformance Based   Internal Quality Audit Guide
Performance Based Internal Quality Audit Guidesuranto2000
 
Con mucho carino-1
Con mucho carino-1Con mucho carino-1
Con mucho carino-1linmimei
 
Tormenta de hielo_en_suiza
Tormenta de hielo_en_suizaTormenta de hielo_en_suiza
Tormenta de hielo_en_suizalinmimei
 

Viewers also liked (15)

Alf2007 Workingwith Media
Alf2007 Workingwith MediaAlf2007 Workingwith Media
Alf2007 Workingwith Media
 
Autoingles on the road.guía
Autoingles on the road.guíaAutoingles on the road.guía
Autoingles on the road.guía
 
Energiatakarekossagi Tippfuzet Web
Energiatakarekossagi Tippfuzet WebEnergiatakarekossagi Tippfuzet Web
Energiatakarekossagi Tippfuzet Web
 
מחזורר 15
מחזורר 15מחזורר 15
מחזורר 15
 
áLbum de fotografías
áLbum de fotografíasáLbum de fotografías
áLbum de fotografías
 
Eac1 resuelto mme
Eac1 resuelto mmeEac1 resuelto mme
Eac1 resuelto mme
 
Más de chicho y chispa
Más de chicho y chispaMás de chicho y chispa
Más de chicho y chispa
 
Con mucho carino
Con mucho carinoCon mucho carino
Con mucho carino
 
áLbum de fotografías
áLbum de fotografíasáLbum de fotografías
áLbum de fotografías
 
Műanyag zacskók veszélyei
Műanyag zacskók veszélyeiMűanyag zacskók veszélyei
Műanyag zacskók veszélyei
 
House For Sale Expanded Ranch
House For Sale Expanded RanchHouse For Sale Expanded Ranch
House For Sale Expanded Ranch
 
2201 m01b1 eac2_solucio_1011s2
2201 m01b1 eac2_solucio_1011s22201 m01b1 eac2_solucio_1011s2
2201 m01b1 eac2_solucio_1011s2
 
Performance Based Internal Quality Audit Guide
Performance Based   Internal Quality Audit GuidePerformance Based   Internal Quality Audit Guide
Performance Based Internal Quality Audit Guide
 
Con mucho carino-1
Con mucho carino-1Con mucho carino-1
Con mucho carino-1
 
Tormenta de hielo_en_suiza
Tormenta de hielo_en_suizaTormenta de hielo_en_suiza
Tormenta de hielo_en_suiza
 

Similar to Fluke 1627722 w

Instrumentation positioner presentation
Instrumentation positioner presentationInstrumentation positioner presentation
Instrumentation positioner presentationSANGRAM PATNAIK
 
Process control 3 chapter
Process control 3 chapterProcess control 3 chapter
Process control 3 chapterSrinivasa Rao
 
Process control 3 chapter
Process control 3 chapterProcess control 3 chapter
Process control 3 chapterSrinivasa Rao
 
Korg sq 10 owners manual (users)
Korg sq 10 owners manual (users)Korg sq 10 owners manual (users)
Korg sq 10 owners manual (users)anattaembe
 
61F Floatless Level Controller Datasheet
61F Floatless Level Controller Datasheet61F Floatless Level Controller Datasheet
61F Floatless Level Controller Datasheetsteven qi
 
61 f+floatless+level+controller+datasheet
61 f+floatless+level+controller+datasheet61 f+floatless+level+controller+datasheet
61 f+floatless+level+controller+datasheetSudarmono Sudarmono
 
Servo voltage stabilization
Servo voltage stabilizationServo voltage stabilization
Servo voltage stabilizationChirag Panchal
 
Basics of Instrumentation & Control.pptx
Basics of Instrumentation & Control.pptxBasics of Instrumentation & Control.pptx
Basics of Instrumentation & Control.pptxshridharkulkarni58
 
Advanced motion controls 50a20
Advanced motion controls 50a20Advanced motion controls 50a20
Advanced motion controls 50a20Electromate
 
Project Report - Spring 2014
Project Report - Spring 2014Project Report - Spring 2014
Project Report - Spring 2014Garret Stec
 
Grid synchronisation
Grid synchronisationGrid synchronisation
Grid synchronisationmanogna gwen
 

Similar to Fluke 1627722 w (20)

Instrumentation positioner presentation
Instrumentation positioner presentationInstrumentation positioner presentation
Instrumentation positioner presentation
 
Voltage Regulation
Voltage RegulationVoltage Regulation
Voltage Regulation
 
RVR-1(3) automatic step voltage regulator
RVR-1(3) automatic step voltage regulatorRVR-1(3) automatic step voltage regulator
RVR-1(3) automatic step voltage regulator
 
RTCC & AVR
RTCC & AVRRTCC & AVR
RTCC & AVR
 
Process control 3 chapter
Process control 3 chapterProcess control 3 chapter
Process control 3 chapter
 
Calibracion de presion
Calibracion de presionCalibracion de presion
Calibracion de presion
 
Process control 3 chapter
Process control 3 chapterProcess control 3 chapter
Process control 3 chapter
 
Korg sq 10 owners manual (users)
Korg sq 10 owners manual (users)Korg sq 10 owners manual (users)
Korg sq 10 owners manual (users)
 
Zero100E insertion type electromagnetic flow meter catalog
Zero100E insertion type electromagnetic flow meter catalogZero100E insertion type electromagnetic flow meter catalog
Zero100E insertion type electromagnetic flow meter catalog
 
ABB Relay
ABB RelayABB Relay
ABB Relay
 
61F Floatless Level Controller Datasheet
61F Floatless Level Controller Datasheet61F Floatless Level Controller Datasheet
61F Floatless Level Controller Datasheet
 
61 f+floatless+level+controller+datasheet
61 f+floatless+level+controller+datasheet61 f+floatless+level+controller+datasheet
61 f+floatless+level+controller+datasheet
 
Servo voltage stabilization
Servo voltage stabilizationServo voltage stabilization
Servo voltage stabilization
 
Sx460 avr newage_stamford
Sx460 avr newage_stamfordSx460 avr newage_stamford
Sx460 avr newage_stamford
 
Xk 550 rev-j-2
Xk 550 rev-j-2Xk 550 rev-j-2
Xk 550 rev-j-2
 
Basics of Instrumentation & Control.pptx
Basics of Instrumentation & Control.pptxBasics of Instrumentation & Control.pptx
Basics of Instrumentation & Control.pptx
 
Advanced motion controls 50a20
Advanced motion controls 50a20Advanced motion controls 50a20
Advanced motion controls 50a20
 
Project Report - Spring 2014
Project Report - Spring 2014Project Report - Spring 2014
Project Report - Spring 2014
 
Grid synchronisation
Grid synchronisationGrid synchronisation
Grid synchronisation
 
SINGLE PHASE OUTPUT INVERTER
SINGLE PHASE OUTPUT INVERTERSINGLE PHASE OUTPUT INVERTER
SINGLE PHASE OUTPUT INVERTER
 

Recently uploaded

chaitra-1.pptx fake news detection using machine learning
chaitra-1.pptx  fake news detection using machine learningchaitra-1.pptx  fake news detection using machine learning
chaitra-1.pptx fake news detection using machine learningmisbanausheenparvam
 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...Soham Mondal
 
IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024Mark Billinghurst
 
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ
 
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSKurinjimalarL3
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxpurnimasatapathy1234
 
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube ExchangerStudy on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube ExchangerAnamika Sarkar
 
Sachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective IntroductionSachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective IntroductionDr.Costas Sachpazis
 
Heart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptxHeart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptxPoojaBan
 
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVRajaP95
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130Suhani Kapoor
 
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...ZTE
 
Past, Present and Future of Generative AI
Past, Present and Future of Generative AIPast, Present and Future of Generative AI
Past, Present and Future of Generative AIabhishek36461
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
GDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentationGDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentationGDSCAESB
 
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort serviceGurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort servicejennyeacort
 

Recently uploaded (20)

chaitra-1.pptx fake news detection using machine learning
chaitra-1.pptx  fake news detection using machine learningchaitra-1.pptx  fake news detection using machine learning
chaitra-1.pptx fake news detection using machine learning
 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
 
IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024
 
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
 
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
 
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptx
 
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
 
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube ExchangerStudy on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
 
Sachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective IntroductionSachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
 
Heart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptxHeart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptx
 
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
 
young call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Service
young call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Serviceyoung call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Service
young call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Service
 
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
 
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
 
Past, Present and Future of Generative AI
Past, Present and Future of Generative AIPast, Present and Future of Generative AI
Past, Present and Future of Generative AI
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
 
GDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentationGDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentation
 
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort serviceGurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
 

Fluke 1627722 w

  • 1. Loop Calibration and Maintenance Application Note Introduction Process instrumentation requires periodic calibration and maintenance to ensure that it is operating correctly. This application note contains information to help guide tech- nicians through some of the more common loop calibration tasks using Fluke tools. Fluke loop calibrators are ideal for a wide variety of cali- bration applications. They include: • Fluke 707 Loop Calibrator • Fluke 705 Loop Calibrator • Fluke 715 Volt/mA Calibrator • Fluke 787 ProcessMeter A summary of the features of Fluke’s loop calibrators and a glossary of terms are at the end of this application note. Field testing loop powered isolators The loop-powered isolator and the two-wire isolating trans- mitter are two of the more prevalent devices in use in 4-20 mA control loops today (see Figure 1). The testing and troubleshooting procedures for each are different and need to be understood by the techni- cians performing operational checks on these units in the field. Loop-powered isolators The main purpose of a loop isolator is to eliminate ground loops in control systems while sending the control signal current to another part of the system. Loop-powered isolators, unlike two-wire transmitters, draw their operat- ing power from the “input” side of the isolator (see Figure 1), which requires a pickup voltage from 5.5 V to 13.5 V depending on the manufacturer. The output of the loop isola- tor is an electrically isolated mirror image of the input side current. The compliance voltage associated with the output is greatly reduced from that of the input side and ranges around 7.5 V. This produces a total loop loading capability of 350 Ω. This limited loop drive capabil- ity is the primary limitation of the loop isolator. Two-wire transmitters Isolating two-wire transmitters provide the same isolating functionality as loop isolators with the added advantage that many provide signal condition- ing for a variety of inputs such as thermocouple, frequency, dc current, RTD, strain gauge, and other process inputs. The power supplied to a two-wire transmitter is connected to the output side of the transmitter. The two-wire transmitter mod- ulates the current from the power supply between 4-20 mA, proportional to the input. Typical power supplies for two- wire transmitters range from 24 V to 48 V. Power supplies of this size allow a significant loop load capability on the output. Figure 1
  • 2. Field checking a loop-powered isolator Fluke loop calibrators have a unique current simulation fea- ture that, when connected to an external power source, allows you to precisely control current between 0 mA and 24 mA. When field checking a loop-powered isolator, the two- wire loop transmitter supplying signal current to the isolator for the loop may be removed and the calibrator connected in simulate mode to control loop current (Figure 2). Connecting the Fluke loop calibrator In this example, we will use the Fluke 787 Process Meter. Although the operating controls vary, this application can also be performed using the Fluke 707, 715, and 705 loop calibrators. 1. Disconnect the main loop transmitter and connect the Fluke 787 to the loop with the test leads plugged into the center or “Simulate” ter- minals of the calibrator (see Figure 2). 2. Set the 787 rotary switch to the mA Output mode. Set the Fluke 787 to the 4-20 mA output mode. Make connec- tion for simulate mA. The 787 is now outputting a pre- cise 4 mA and is providing operating power to the input of the loop-powered isolator. 3. Place a Fluke 87, 187 or equivalent multimeter (1 µA resolution is ideal; 10 µA is acceptable), set in the mA measurement mode, on the output side of the isolator to monitor output current (see Figure 2). 4. Adjust the zero control on the isolator for a reading of 4.000 mA on the output meter. 5. Step the input current to 20 mA using the % step button ▲ (25% or 4 mA increase) and adjust the span control on the isolator to read 20.000 mA on the output meter connected to the isolator. 6. Step input current down to 4 mA using the ▼ button (25% or 4 mA decrease) and check for a zero shift, adjust if necessary. 7. At this point, basic zero and span adjustments are complete. Check linearity Fluke loop calibrators can eas- ily check the linearity of your loop isolator using the % step buttons ▲ and ▼. Pushing these buttons when in the out- put mode increases or decreases the output current in 25% steps. In the 4-20 mA current mode these intermedi- ate steps are at 8 mA (25%), 12 mA (50%), and 16 mA (75%). To check linearity of the isola- tor, push the associated % step buttons up and down and con- firm that the digital multimeter (DMM) is reading the same value as is shown on the loop calibrator display. A variation from expected values should be compared to the linearity limits stated by the manufacturer of the loop-powered isolator. Testing valve positioners Electronic valve positioners should receive periodic in-field calibrations as part of preven- tive maintenance programs. Fluke loop calibrators are the ideal test tools for these checks. Valve positioners vary in design and valve type and should be calibrated using spe- cific instructions from the individual manufacturer. Quick operational checks can be performed using a field cali- brator as a signal source while observing the valve stem posi- tion, mechanical position indicators, or flow indicators as input changes are made. Fluke loop calibrators provide a con- venient source for simulating the controller output to a valve positioner. The following example shows a general method for an in-field operational check of a valve fitted with an electronic valve positioner. These meth- ods may be adapted to various types of valves, however, man- ufacturer’s specific instructions should always be consulted for proper and appropriate tech- niques. In the following example, valve operation and movement is checked either by feel or by observing valve stem movement. 787 PROCESSMETER MIN MAX RANGE HOLD H REL Hz 400100030 Auto MINMAXAVG ACmV %OUTPUT DC mA Mk kHz OFF A mA COM V 30mA FUSED0.44A (1A /30 sec) FUSED mV V V OUTPUT 0-24mA SOURCE SIMULATE + + % STEP COARSE FINE mA mA A mA OUTPUT 1000V CAT Figure 2 2 Fluke Corporation Troubleshooting and Maintenance Using Fluke Loop Calibrators
  • 3. Step 1: Basic set-up. Setting the Fluke 707 loop calibra- tor current output Place the calibrator in the 4-20 mA output current mode. Connect the 707 to the input terminals of the valve posi- tioner (see Figure 3). Step 2: Zero adjustment Set the 707 to an output of 4 mA and allow some time for valve stem movement to stabi- lize. Quickly decrease the current from 4 mA to 3.9 mA by depressing and turning the vernier knob in a counter- clockwise direction. You can operate the 707 with one hand while feeling the valve stem with your free hand to check for any sign of movement. Adjust for zero movement between these two current set- tings by using the zero adjustment on the positioner. Increase and decrease cur- rent from 4 mA to 4.1 mA using the vernier knob in the depressed position. Insure that the valve stem just begins movement above the 4.1 mA setting and fully closed at 4 mA. Step 3: Span (full open) position check Using the 25% button, step the calibrator output value to 20 mA and allow the valve to stabilize. Step the input to 20.1 mA using the vernier knob in the depressed position turn- ing clockwise while watching or feeling for movement of the valve stem. Minimize this move- ment using the span adjust- ment on the valve positioner. Using the vernier knob in the depressed position, adjust current up and down between 20.10 mA and 19.9 mA. There should be no movement of the valve stem above 20 mA and a slight movement below 20 mA. Step 4: Check zero and span again Many positioners have interac- tive zero and span controls. This step will help insure proper valve position adjustment. Repeat Step 2 and Step 3. Step 5: Linearity check For valves with linear action, linearity can be checked by setting the 707 to 4 mA and stepping current to 12 mA (50%) while observing valve travel. If your valve is of a non- linear type, refer to the valve manual for proper operational checks. Step 6: Stroking the valve Checking for smooth valve operation is easy to accomplish using the slow ramp function of the 707. • Set the calibrator to mA source mode and select the slow ramp function ( ) by depressing the 25% and 0- 100% buttons simultaneously. • Allow the calibrator to ramp through several cycles while watching or feeling for any abnormal operation of the valve, such as sticking in one position momentarily or erratic movement. Flow Positioner Fluke 707 Figure 3 Troubleshooting and Maintenance Using Fluke Loop Calibrators Fluke Corporation 3 ∨
  • 4. Calibrating voltage input signal conditioners Fluke loop calibrators are ideal for calibrating many 4-20 mA signal conditioners using their precision current sourcing and simulation capabilities. However, there are many signal condi- tioners that require a precision voltage source for proper cali- bration. Using a simple precision resistor and standard connector, Fluke loop calibra- tors can field calibrate many standard and non-standard voltage input signal condition- ers. This approach works well for the 705, 707 and 787 loop calibration tools (this is not necessary with the 715 loop calibrator as it has a precision direct voltage output). Voltage input signal condi- tioners come in many varieties. The most common are 0-10 V, 0-5 V and 1-5 V input levels. Typical outputs of these devices are an isolated or non-isolated 0-10 V or 4-20 mA. Resistors with values of 250 Ω to 500 Ω are common loop load resistors and provide voltage input lev- els as a function of the loop current (see Figure 4). Using Fluke loop calibrators as a voltage source A precision shunt resistor may be used to derive voltages for calibration using the calibra- tor’s current source mode. Using this system, Fluke loop calibrators are capable of gen- erating voltages for devices with input spans as low as 10 mV to as high as 24 V. Table 1 gives values of precision resis- tors to accommodate a variety of voltage calibrations and the Fluke calibrator ideal for each application. Constructing a precision load resistor assembly A simple precision current shunt can be constructed using a precision RN60, 1 W resistor, (see table for the correct value), a dual banana jack connector and some test leads with alli- gator clips (see Figure 5). The RN60 class resistor is available from many commercial sources. Construct the assembly as shown in Figure 5. This preci- sion resistor assembly, coupled with the precision current sourcing capabilities of Fluke loop calibrators, generates pre- cision voltages to cover 1-5 V or 2-10 V applications. The 1,000 Ω assembly has an advantage in that it allows a direct one-to-one display cor- relation to voltage when sourcing current from the Fluke loop calibrator during calibra- tion (1 mA = 1 V). The following example will utilize a 250 Ω to take advantage of the 0-100% and 25% buttons on the Fluke 707 (25% or 4 mA = 1 V). 4 Fluke Corporation Troubleshooting and Maintenance Using Fluke Loop Calibrators Figure 4 Resistor Sourced Generated Fluke Loop Value Application Current Value Voltage Calibrator 10 Ω mV 0-20.000 mA 0-200.00 mV 707, 705, 787 transducer 250 Ω 0-5 V Source 0-20.000 mA 0-5.000 V 705, 707 1000 Ω 0-10 V Source 0-12.000 mA 0-12.000 V 705, 707, 787 Note: Input impedance of the device under test should be ≥ 1 MΩ Table 1. Values of precision resistors to accommodate a variety of voltage calibrations Figure 5 Constructing a precision current shunt Parts required: 1. Resistor: 1000 Ω Type: RN60 (50 ppm@70 °C) 1 W 2. 36˝ test leads with alligator clips 3. Connector: Dual Banana Plug 2/screw terminals
  • 5. Fluke Display Input Output Reading % Input Voltage Current 4.000 0 1.000 V 4.000 mA 8.000 25 2.000 V 8.000 mA 12.000 50 3.000 V 12.000 mA 16.000 75 4.000 V 16.000 mA 20.000 100 5.000 V 20.000 mA Calibrating the signal conditioner The following is a procedure for calibrating a 1-5 V input, 4- 20 mA output signal conditioner using the precision current shunt constructed in Figure 5. Step 1: Setting the Fluke 707 to source 4-20 mA 1. With the shunt assembly in the “source” jacks, power the 707 on. 2. Check the display. If the dis- play does not read 4 mA, turn the 707 off and on again while holding the mode button for two sec- onds. The display should now read 4.000 mA. Step 2: Calibrating 1. Place a precision multimeter, such as the Fluke 87 DMM, set to dc current mode, in series with the output of the signal conditioner as shown in Figure 6. 2. Connect the test leads from the precision shunt assembly to the signal conditioner input terminals, observing proper polarity. 3. With the 707 set in the mA source mode, the display should read 4.000 mA (1.00 V across the shunt). 4. Adjust the zero control on the signal conditioner for an indication of 4.000 mA on the DMM. 5. Press the 0-100% button on the 707 until the display reads 20.000 mA. Then adjust the span adjustment on the signal conditioner until the display on the DMM reads 20.000 mA. 6. Push the 0-100% button and the 707 should read 4.000. Verify the meter connected to the output signal condi- tioner reads 4.000 mA.1 7. Calibration is now complete. Note: Many manufacturers specify a warm-up time prior to beginning calibration. Step 3: Checking linearity Once zero and span controls have been properly set, signal conditioner linearity may be verified using the following procedure. This procedure will check zero, 25%, 50%, 75% and span settings for signal conditioner linearity. 1. With the precision resistor assembly in place, adjust the source current of the Fluke loop calibrator to 4 mA (1.0 V) using the 25% button. The DMM displays 4 mA. 2. Using the 25% button, step the source current to 25%, 50%, 75% and 100% and note the corresponding val- ues. Table 2 shows the correct values of output for a linear signal conditioner. (If values differ from that shown in Table 2 by more than the linearity specifica- tion of the signal conditioner, contact the sig- nal conditioner manufacturer or replace the device.) Making fine adjustments Many signal conditioners with 0-20 mA and 4-20 mA outputs are notorious for zero and span control interaction. If, when checking linearity in the cali- bration section, your output meter displayed a value higher or lower than 4 mA, perform the following steps to affect the required 4 and 20 mA display on the output meter. 1. Note the value above or below 4 mA that was dis- played on the output meter when you returned to a source value of 4.000 mA on the 707. Adjust the zero con- trol on the signal conditioner so the value of the output meter shows one-half the difference of the remaining mA value to 4 mA. Example: If your display reading at zero input in step 7 was 3.50 mA adjust the output (with 4.000 mA source current) to display a reading of 3.75 mA, which is one-half the delta toward the desired value of 4 mA (eg. 4.00 - 3.50 = 0.50; 0.05 / 2 + 3.50 = 3.75, or one-half the difference between the reading and the desired value). Troubleshooting and Maintenance Using Fluke Loop Calibrators Fluke Corporation 5 Figure 6 1 If your output meter displayed a value higher or lower than 4 mA, consult the “Making fine adjustments” section on this page. Table 2. Correct value of output for a linear signal conditioner
  • 6. 6 Fluke Corporation Troubleshooting and Maintenance Using Fluke Loop Calibrators 2. Set the source current of the 707 to 20.000 mA using the 0-100% button. Note the “output” meter display read- ing. Adjust the span control of the signal conditioner one-half the delta from 20.000 mA. Example: If the output dis- play reads 21 mA. Adjust the span control to 20.5 mA (one-half the delta to the required value of 20 mA). 3. Repeat this “one-half step” process until the required output is obtained. There are signal conditioners that have non-interactive controls that do not require this procedure. Verifying process scaled, indicators Scaled process indicators are used to provide information about a process either locally or to a control room located a distance away. These indicators typically take a mA measure- ment in series with the 4-20 mA loop signal or measure a 1 V-5 V drop across a 250 ohm resistor in series with the 4-20 mA signal (a 4-20 mA signal through a 250 ohm resistor produces a 1 V to 5 V drop). For indicators with a mA input, the direct mA current output of a 705, 707, 715 or 787 can be applied directly to the input of the indicator. For voltage input indicators, a 715 is ideal with its direct voltage output. Or use a resistor across the output of a 705, 707, or 787 as described previously (“Using Fluke loop calibrators as a voltage source”). This example will show how to use the 707 to verify a mA input indicator. Make connec- tions as shown in Figure 7. 1. Power the 707 up; the default output should be 4 mA. Note the indication, (digital or ana- log) which should be approximately 0%. 2. Depress the 0-100% button on the 707; it is now in the span check mode and is out- putting 20 mA. Note the indication (approximately 100%). 3. If testing the linearity is nec- essary, use the 25% button to step the mA output in 4 mA steps and record the indica- tions. 4. To calculate the errors in per- cent, use the formula: Nominal - Actual/Span x 100 Nominal is the ideal value, actual is the recorded meas- urement and span is 16 (4-20 mA = a 16 mA span). Example: If the indication with 0% applied is 1%, cal- culate error as such: 0-1/16 = .0625 X 100 = 6.25% error. Calculate error based on the recorded indications and compare to the tolerances for the indicator. If any of the calculated errors are too large, adjustment may be necessary. Normally, there are at least two adjustments for analog indicators: zero and span. The zero adjust- ment is typically on the faceplate of the indicator. 5. With an output of 4.000 mA from the 707 adjust the zero indication. Span adjustment is either a hard adjustment or accomplished by bending a linkage on the meter move- ment. Refer to the manu- facturer’s procedure for this adjustment. 6. Apply a 20.000 mA signal to the indicator and make the adjustment as specified. Once the adjustment is completed, re-verify the indicator and confirm the adjustments had the desired effect. If the indi- cator still fails the test, it will either need to be readjusted until a satisfactory result is attained, or replaced. Voltage input indicators The procedure for using the 707 to verify voltage input indicators is almost identical to the proce- dure outlined. The primary difference is the addition of the precision 250 ohm adapter. 0% 50% 100% + – Indicator Input Figure 7
  • 7. Accessories 707 Loop Calibrator 715 Volt/mA Calibrator 705 Loop Calibrator 787 ProcessMeter 787CAL Calibration Kit • 80T-IR Infrared Probe • • 80TK Thermocouple • • 80T-150U Temperature Probe • • TL20/22/24/26/28 Lead Sets • • • • TL70A/TL75/Y8140A Lead Sets • • • • AC20/AC80 Clips • • • • TP20 Industrial Test Probes • • • • 80i-400 AC Current Clamp • i410 AC/DC Current Clamp • 2 1 i1010 AC/DC Current Clamp • 2 1 C10 Holster, C12A Case • • C25/C28/V90/C100/C800 Cases • • C510 Leather Case • • 80K-6/80K-40 High Voltage Probe • 83RF/85RF High Frequency Probes • PV350 Pressure Vacuum Module • • Fiber Optic Meter FOM • • 120 amps ac minimum 2dc current only Troubleshooting and Maintenance Using Fluke Loop Calibrators Fluke Corporation 7 Fluke Loop Calibrator Considerations and Selection Fluke loop calibration tools have a variety of different performance features and capabilities that differentiate the models. The charts below will help you determine which model best fits your needs: 707 715 705 787 Loop Calibrator Volt/mA Calibrator Loop Calibrator ProcessMeter • One-handed quick click • Source or simulate • Simultaneous mA and • Two instruments in one: operation 24 mA loop current % of span display -Professional DMM • Simultaneous mA and % • Source voltage to • Accuracy and resolution -Loop calibrator of span display 100 mV or 10 V • Span check • Precise control of • Push button 25% steps • Measure voltage output • Auto ramping and loop current • 0.015% accuracy and process signals stepping • Auto ramping & stepping 1 microamp resolution • High level of safety Function in any current mode (Cat III) Measure DMM capabilities • V dc 28 V 10 V 28 V 1000 V V ac (true-rms) 1000 V Ω 40 MΩ A dc 24 mA 24 mA 24 mA 30 mA, 1 A A ac 1 A Frequency Hz/CPM 20 kHz mA accuracy 0.015% 0.015% 0.020% 0.05% Span check • • Source/Simulate V dc 10 V Source voltage with µV resolution •(1-10 Volts) mA dc/% scale 24 mA 24 mA 24 mA 24 mA mA source: • • •auto step, auto ramp Record Min Max • Hold • Features 24 V loop supply • • • Drive capability 24 V compliance 24 V compliance 24 V compliance 12 V compliance Warranty 3 year 3 year 3 year 3 year IEC 61010 category/ 30 V 30 V 30 V 1000 V, CAT III max voltage
  • 8. Glossary of terms 4-20 mA loop A 4-20 mA signal that is representative of a process variable or a control signal that controls a process variable. Compliance voltage The voltage a current source develops when attempting to drive a mA signal through a resistive load. DMM Digital multimeter. Electronic valve positioners Devices that can control the flow in a process with input from a mA or digital control signal. Ground loop A difference in potential (voltage) between (2) signal grounds. Linearity The closeness of a calibration curve to a specified straight line. Linearity is expressed as the maximum deviation of any calibration point from a specified straight line. Loop-powered isolator A device that produces an electrically isolated mirror image of the input side 4-20 mA current. mA Milliamp; a unit of electric current equal to one thousandth of an ampere. Precision current shunt A conductor joining two points in a circuit to form a parallel circuit, through which a precision voltage can be measured or derived. RTD Resistance temperature device, a temperature measurement sensor that has predictable changes in resistance with a change in temperature. Signal conditioner A circuit to modulate a signal so as to make it intelligible to, or compati- ble with, another device, including such manipulation as pulse shaping, pulse clipping, compensating, digitizing, and linearizing. Strain gauge A measuring element for converting force, pressure, tension, etc., into an electrical signal. Thermocouple A junction of dissimilar metals that generates a small voltage correlated to the temperature of the junction. µA or uA Microamp; a unit of electric current equal to one millionth of an ampere. Vernier A small, movable, graduated scale running parallel to the fixed graduated scale and used for measuring a fractional part of one of the divisions of the fixed scale. Fluke Corporation PO Box 9090, Everett, WA USA 98206 Fluke Europe B.V. PO Box 1186, 5602 BD Eindhoven, The Netherlands For more information call: In the U.S.A. (800) 443-5853 or Fax (425) 446-5116 In Europe/M-East/Africa (31 40) 2 675 200 or Fax (31 40) 2 675 222 Canada (800)-36-FLUKE or Fax (905) 890-6866 Other countries (425) 446-5500 or Fax (425) 446-5116 Web access: http://www.fluke.com ©2001 Fluke Corporation. All rights reserved. Trademarks are the property of their respective owners. Printed in U.S.A. 8/2001 1627722 A-ENG-N Rev A Printed on recycled paper. Fluke.Keeping your world up and running.