QUESTION 1
Arrange the block in form to enable reduction to be readily made so that the relationship between
disturbance 𝐷 𝑠 and output 𝜃0 can be obtained.
Diagram
Solution
1. Setting the 𝜃𝑖(𝑠) to zero, thus producing the following arrangement
MARCH 3, 2015
LECTURER: DR. MICHEAL LUBWAMA
− −
+
++ +
nuwemchris@gmail.com
2. Combining the blocks that are in cascade arrangement
3. Combining the blocks that are in parallel hence eliminating one summing point it
produces a new arrangement as follows
+
+
+
−
+
−
+
+
nuwemchris@gmail.com
4. Now combining the blocks that are in cascade, results to the following arrangement
5. Finally eliminating the feedback loop results to:
𝐺3
1 − ( 𝐺3)(−𝐺2(𝐺1 𝐻1 + 𝐻2))
=
𝐺3
1 + 𝐺3 𝐺2(𝐺1 𝐻1 + 𝐻2)
Thus:
+
+
+
+
nuwemchris@gmail.com
∴ 𝑇. 𝐹 =
𝜃0
𝐷(𝑠)
=
𝐺3
1 + 𝐺3 𝐺2(𝐺1 𝐻1
+ 𝐻2)
nuwemchris@gmail.com
QUESTION 2
Arrange the block in form to enable reduction to be readily made so that the relationship between
disturbance 𝐷 𝑠 and output 𝜃0 can be obtained.
Diagram
Solution
1. Setting the 𝜃𝑖(𝑠) to zero, thus producing the following arrangement
− −
−
−
+
+
−
++ +
nuwemchris@gmail.com
2. Combining the blocks that are in cascade arrangement
3. Combining the blocks that are in parallel hence eliminating one summing point it
produces a new arrangement as follows
4. Now combining the blocks that are in cascade, results to the following arrangement
+
−
−
+
−
+
+
−
nuwemchris@gmail.com
5. Finally eliminating the feedback loop results to:
𝐺3
1 + ( 𝐺3)(−𝐺2(𝐺1 𝐻1 + 𝐻2))
=
𝐺3
1 − 𝐺3 𝐺2(𝐺1 𝐻1 + 𝐻2)
Thus:
∴ 𝑇. 𝐹 =
𝜃0
𝐷(𝑠)
=
𝐺3
1 − 𝐺3 𝐺2(𝐺1 𝐻1
+ 𝐻2)
nuwemchris@gmail.com
ON-OFF FEEDBACK CONTROL
With on-off control, the controller is essentially a switch which is activated by the error signal and
supplies just an on-off correcting signal. The controller output has just two possible values, equivalent to
on and off. For this reason the controller is sometimes termed a two-step controller. An example of such a
controller is the bimetallic thermostat used with a simple temperature control system, if the actual
temperature is above the required temperature,the bimetallic strip is in an off position and the heater is
switched off; if the actual temperature is below the required temperature, the bimetallic strip moves into
the on position and the heater is switched on. The controller output is thus just on or off and so the
correcting signal on or off. Because the control action is discontinuous and there are time lags in the
system, oscillations, i.e. cycling, of the controlled variable occur about the required condition. Thus, with
temperature control using the bimetallic thermostat, when the room temperature drops below the required
level there is a significant time before the heater begins to have an effect on the room temperature and, in
the meantime, the temperature has fallen even more. When the temperature rises to the required
temperature,since time elapses before the control system reacts and switches the heater off and it cools,
the room temperature goes beyond the required value. The result is that the room temperature oscillates
above and below the required temperature.
On-off control is simple and inexpensive and is often used where cycling can be reduced to an acceptable
level.
PROPORTIONAL CONTROL
With the on-off method of control, the controller output is either an on or an off signal and so the output
is not related to the size of the error. With proportional control the size of the controller output is
proportional to the size of the error, i.e. the controller input.
We can write this as:
Controller output = controller input
where controller input is a constant called the gain. This means the correction element of the control
system will have an input of a signal which is proportional to the size of the correction required. The float
method of controlling the level of water in a cistern is an example of the use of a proportional controller
where the controller output is proportional to the integral of the error with respect to time
nuwemchris@gmail.com
MODULATING FEEDBACK CONTROLL
In this strategy, rather than switch the inlet valve open and shut, a more subtle approach is to inch
the valve by an amount which depends on the difference between the actual level and the desired
level.
Modulating Control implies a more elaborate level measurement and valve actuator. In the first
place it requires a signal related to the actual level (ie a level transmitter). Secondly, the value
actuator must be able to open and close the inlet valve gradually (modulate the value opening).
Furthermore the valve itself must have a smooth characteristic so that its resistance to flow is
infinitely variable.
DERIVATIVE CONTROL
With derivative control the change in controller output from the set point value is proportional to
the rate of change with time of the error signal, i.e. controller output rate of change of error
It is usual to express these controller outputs as a percentage of the full range of output and the
error as a percentage of full range. KD is the constant of proportionality and is commonly referred
to as the derivative time since it has units of time. Figure illustrates the type of response that occurs
when there is a steadily increasing error signal. Because the rate of change of the error with time is
constant, the derivative controller gives a constant controller output signal to the correction
element. With derivative control, as soon as the error signal begins to change there can be quite a
large controller output since it is proportional to the rate of change of the error signal and not its
value. Thus with this form of control there can be rapid corrective responses to error signals that
occur.
Derivative controllers give responses to changing error signals but do not, however, respond to
constant error signals, since with a constant error the rate of change of error with time is zero.
nuwemchris@gmail.com
Digital Control:
Digital systems
The term direct digital control is used to describe the use of digital computers in the control system
to calculate the control signal that is applied to the actuators to control the plant. Such a system is
of the form shown in Figure . At each sample instant the computer samples, via the analogue-to-
digital converter (ADC),the plant output to produce the sampled output value. This, together with
the discrete input value is then processed by the computer according to the required control law to
give the required correction signal which is then sent via the digital-to- analogue converter (DAC)
to provide the correcting action to the plant to give the required control. Direct digital control laws
are computer programs that take the set value and feedback signals and operate on them to give the
output signal to the actuator. The program might thus be designed to implement PID control.
Source;
INSTRUMENTATION AND CONTROL SYSTEMS. W. BOLTON

More Related Content

What's hot

PID controller in control systems
PID controller in control systemsPID controller in control systems
PID controller in control systemskhalaf Gaeid
 
Pid controller mcq answers
Pid controller   mcq answersPid controller   mcq answers
Pid controller mcq answerskhalaf Gaeid
 
Time response of discrete systems 4th lecture
Time response of discrete systems 4th lectureTime response of discrete systems 4th lecture
Time response of discrete systems 4th lecturekhalaf Gaeid
 
Identification and Tuning of Process with Inverse Response
Identification and Tuning of Process with Inverse ResponseIdentification and Tuning of Process with Inverse Response
Identification and Tuning of Process with Inverse Responseomkarharshe
 
15_feedforward_and_ratio_cntrol
15_feedforward_and_ratio_cntrol15_feedforward_and_ratio_cntrol
15_feedforward_and_ratio_cntrolMircea Tomescu
 
Kf units Electrolytic Cell Volt Regression
Kf units Electrolytic Cell Volt RegressionKf units Electrolytic Cell Volt Regression
Kf units Electrolytic Cell Volt RegressionUsama Khan
 
Linear control system Open loop & Close loop Systems
Linear control system Open loop & Close loop SystemsLinear control system Open loop & Close loop Systems
Linear control system Open loop & Close loop SystemsSohaibUllah5
 
Comparative analysis of P/PI/PID controllers for pH neutralization process
Comparative analysis of P/PI/PID controllers for pH neutralization processComparative analysis of P/PI/PID controllers for pH neutralization process
Comparative analysis of P/PI/PID controllers for pH neutralization processChandra Shekhar
 
An Energy-Efficient Climate Control Solution for Smart Buildings Based on Pre...
An Energy-Efficient Climate Control Solution for Smart Buildings Based on Pre...An Energy-Efficient Climate Control Solution for Smart Buildings Based on Pre...
An Energy-Efficient Climate Control Solution for Smart Buildings Based on Pre...omar_afify
 
SAP ISU Validation Class : Comparison of n periods
SAP ISU Validation Class : Comparison of n periodsSAP ISU Validation Class : Comparison of n periods
SAP ISU Validation Class : Comparison of n periodsRakesh Dasgupta
 
Modern Control - Lec 06 - PID Tuning
Modern Control - Lec 06 - PID TuningModern Control - Lec 06 - PID Tuning
Modern Control - Lec 06 - PID TuningAmr E. Mohamed
 

What's hot (20)

PID Control
PID ControlPID Control
PID Control
 
PID controller in control systems
PID controller in control systemsPID controller in control systems
PID controller in control systems
 
Pid controller mcq answers
Pid controller   mcq answersPid controller   mcq answers
Pid controller mcq answers
 
Lead-lag controller
Lead-lag controllerLead-lag controller
Lead-lag controller
 
Class 16 floating and proportional control mode
Class 16   floating and proportional control modeClass 16   floating and proportional control mode
Class 16 floating and proportional control mode
 
Time response of discrete systems 4th lecture
Time response of discrete systems 4th lectureTime response of discrete systems 4th lecture
Time response of discrete systems 4th lecture
 
08 pid.controller
08 pid.controller08 pid.controller
08 pid.controller
 
Class 19 pi & pd control modes
Class 19   pi & pd control modesClass 19   pi & pd control modes
Class 19 pi & pd control modes
 
Identification and Tuning of Process with Inverse Response
Identification and Tuning of Process with Inverse ResponseIdentification and Tuning of Process with Inverse Response
Identification and Tuning of Process with Inverse Response
 
15_feedforward_and_ratio_cntrol
15_feedforward_and_ratio_cntrol15_feedforward_and_ratio_cntrol
15_feedforward_and_ratio_cntrol
 
Class 37 inferential control, gain scheduling
Class 37   inferential control, gain schedulingClass 37   inferential control, gain scheduling
Class 37 inferential control, gain scheduling
 
Class 27 pd, pid electronic controllers
Class 27   pd, pid electronic controllersClass 27   pd, pid electronic controllers
Class 27 pd, pid electronic controllers
 
Kf units Electrolytic Cell Volt Regression
Kf units Electrolytic Cell Volt RegressionKf units Electrolytic Cell Volt Regression
Kf units Electrolytic Cell Volt Regression
 
Linear control system Open loop & Close loop Systems
Linear control system Open loop & Close loop SystemsLinear control system Open loop & Close loop Systems
Linear control system Open loop & Close loop Systems
 
Temperature controllers
Temperature controllersTemperature controllers
Temperature controllers
 
Comparative analysis of P/PI/PID controllers for pH neutralization process
Comparative analysis of P/PI/PID controllers for pH neutralization processComparative analysis of P/PI/PID controllers for pH neutralization process
Comparative analysis of P/PI/PID controllers for pH neutralization process
 
An Energy-Efficient Climate Control Solution for Smart Buildings Based on Pre...
An Energy-Efficient Climate Control Solution for Smart Buildings Based on Pre...An Energy-Efficient Climate Control Solution for Smart Buildings Based on Pre...
An Energy-Efficient Climate Control Solution for Smart Buildings Based on Pre...
 
SAP ISU Validation Class : Comparison of n periods
SAP ISU Validation Class : Comparison of n periodsSAP ISU Validation Class : Comparison of n periods
SAP ISU Validation Class : Comparison of n periods
 
Class 3 control system components
Class 3   control system componentsClass 3   control system components
Class 3 control system components
 
Modern Control - Lec 06 - PID Tuning
Modern Control - Lec 06 - PID TuningModern Control - Lec 06 - PID Tuning
Modern Control - Lec 06 - PID Tuning
 

Similar to Control systems diagraming

Sistemas de control en tiempo discreto
Sistemas de control en tiempo discretoSistemas de control en tiempo discreto
Sistemas de control en tiempo discretoelian martinez
 
Introduction to control system 2
Introduction to control system 2Introduction to control system 2
Introduction to control system 2turna67
 
Process control handout new1
Process control handout new1Process control handout new1
Process control handout new1Kiya Alemayehu
 
Introduction to control system
Introduction to control systemIntroduction to control system
Introduction to control systemRosh54
 
178633554-Bms-Air-Conditioning-and-Ventilation-Controls-Honeywell
178633554-Bms-Air-Conditioning-and-Ventilation-Controls-Honeywell178633554-Bms-Air-Conditioning-and-Ventilation-Controls-Honeywell
178633554-Bms-Air-Conditioning-and-Ventilation-Controls-HoneywellEUR ING Gorka Akarregi
 
Types of Controllers PID PD I PD
Types of Controllers PID PD I PDTypes of Controllers PID PD I PD
Types of Controllers PID PD I PDAnaseem Hanini
 
Introduction of control engineering
Introduction of control engineeringIntroduction of control engineering
Introduction of control engineeringAshvani Shukla
 
EEP301: Process control trainer
EEP301: Process control trainerEEP301: Process control trainer
EEP301: Process control trainerUmang Gupta
 
Automatic process controls in a Thermal Power Station
Automatic process controls in a Thermal Power StationAutomatic process controls in a Thermal Power Station
Automatic process controls in a Thermal Power StationManohar Tatwawadi
 
Modern Control - Lec 01 - Introduction to Control System
Modern Control - Lec 01 - Introduction to Control SystemModern Control - Lec 01 - Introduction to Control System
Modern Control - Lec 01 - Introduction to Control SystemAmr E. Mohamed
 
Industrial process control
Industrial process controlIndustrial process control
Industrial process controlMohamed A Hakim
 

Similar to Control systems diagraming (20)

On off controller
On off controllerOn off controller
On off controller
 
Sistemas de control en tiempo discreto
Sistemas de control en tiempo discretoSistemas de control en tiempo discreto
Sistemas de control en tiempo discreto
 
Basicontrol
BasicontrolBasicontrol
Basicontrol
 
Time Response
Time ResponseTime Response
Time Response
 
3.CONTROL ACTIONS.pptx
3.CONTROL ACTIONS.pptx3.CONTROL ACTIONS.pptx
3.CONTROL ACTIONS.pptx
 
Introduction to control system 2
Introduction to control system 2Introduction to control system 2
Introduction to control system 2
 
Process control handout new1
Process control handout new1Process control handout new1
Process control handout new1
 
Introduction to control system
Introduction to control systemIntroduction to control system
Introduction to control system
 
178633554-Bms-Air-Conditioning-and-Ventilation-Controls-Honeywell
178633554-Bms-Air-Conditioning-and-Ventilation-Controls-Honeywell178633554-Bms-Air-Conditioning-and-Ventilation-Controls-Honeywell
178633554-Bms-Air-Conditioning-and-Ventilation-Controls-Honeywell
 
Types of Controllers PID PD I PD
Types of Controllers PID PD I PDTypes of Controllers PID PD I PD
Types of Controllers PID PD I PD
 
Introduction of control engineering
Introduction of control engineeringIntroduction of control engineering
Introduction of control engineering
 
EEP301: Process control trainer
EEP301: Process control trainerEEP301: Process control trainer
EEP301: Process control trainer
 
Automatic process controls in a Thermal Power Station
Automatic process controls in a Thermal Power StationAutomatic process controls in a Thermal Power Station
Automatic process controls in a Thermal Power Station
 
PID controller
PID controllerPID controller
PID controller
 
chap-1(1).pdf
chap-1(1).pdfchap-1(1).pdf
chap-1(1).pdf
 
Modern Control - Lec 01 - Introduction to Control System
Modern Control - Lec 01 - Introduction to Control SystemModern Control - Lec 01 - Introduction to Control System
Modern Control - Lec 01 - Introduction to Control System
 
Industrial process control
Industrial process controlIndustrial process control
Industrial process control
 
Controller modes IPC
Controller modes IPCController modes IPC
Controller modes IPC
 
sssss (1).pptx
sssss (1).pptxsssss (1).pptx
sssss (1).pptx
 
ControlsLab2
ControlsLab2ControlsLab2
ControlsLab2
 

Recently uploaded

College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSHARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSRajkumarAkumalla
 
main PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidmain PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidNikhilNagaraju
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxAsutosh Ranjan
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINEMANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINESIVASHANKAR N
 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Christo Ananth
 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxpranjaldaimarysona
 
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxJoão Esperancinha
 
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSKurinjimalarL3
 
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝soniya singh
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingrakeshbaidya232001
 
GDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentationGDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentationGDSCAESB
 
Introduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxIntroduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxupamatechverse
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130Suhani Kapoor
 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Dr.Costas Sachpazis
 

Recently uploaded (20)

College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
 
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSHARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
 
main PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidmain PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfid
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptx
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
 
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINEMANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptx
 
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
 
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptxExploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
 
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
 
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writing
 
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINEDJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
 
GDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentationGDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentation
 
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
 
Introduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxIntroduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptx
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
 

Control systems diagraming

  • 1. UNIVERSITYMAKERERE COLLEGE OF ENGINEERING, DESIGN, ART AND TECHNOLOGY SCHOOL OF ENGINEERING DEPARTMENT OF MECHANICAL ENGINEERING QUESTION 1 Arrange the block in form to enable reduction to be readily made so that the relationship between disturbance 𝐷 𝑠 and output 𝜃0 can be obtained. Diagram Solution 1. Setting the 𝜃𝑖(𝑠) to zero, thus producing the following arrangement MARCH 3, 2015 LECTURER: DR. MICHEAL LUBWAMA − − + ++ +
  • 2. nuwemchris@gmail.com 2. Combining the blocks that are in cascade arrangement 3. Combining the blocks that are in parallel hence eliminating one summing point it produces a new arrangement as follows + + + − + − + +
  • 3. nuwemchris@gmail.com 4. Now combining the blocks that are in cascade, results to the following arrangement 5. Finally eliminating the feedback loop results to: 𝐺3 1 − ( 𝐺3)(−𝐺2(𝐺1 𝐻1 + 𝐻2)) = 𝐺3 1 + 𝐺3 𝐺2(𝐺1 𝐻1 + 𝐻2) Thus: + + + +
  • 4. nuwemchris@gmail.com ∴ 𝑇. 𝐹 = 𝜃0 𝐷(𝑠) = 𝐺3 1 + 𝐺3 𝐺2(𝐺1 𝐻1 + 𝐻2)
  • 5. nuwemchris@gmail.com QUESTION 2 Arrange the block in form to enable reduction to be readily made so that the relationship between disturbance 𝐷 𝑠 and output 𝜃0 can be obtained. Diagram Solution 1. Setting the 𝜃𝑖(𝑠) to zero, thus producing the following arrangement − − − − + + − ++ +
  • 6. nuwemchris@gmail.com 2. Combining the blocks that are in cascade arrangement 3. Combining the blocks that are in parallel hence eliminating one summing point it produces a new arrangement as follows 4. Now combining the blocks that are in cascade, results to the following arrangement + − − + − + + −
  • 7. nuwemchris@gmail.com 5. Finally eliminating the feedback loop results to: 𝐺3 1 + ( 𝐺3)(−𝐺2(𝐺1 𝐻1 + 𝐻2)) = 𝐺3 1 − 𝐺3 𝐺2(𝐺1 𝐻1 + 𝐻2) Thus: ∴ 𝑇. 𝐹 = 𝜃0 𝐷(𝑠) = 𝐺3 1 − 𝐺3 𝐺2(𝐺1 𝐻1 + 𝐻2)
  • 8. nuwemchris@gmail.com ON-OFF FEEDBACK CONTROL With on-off control, the controller is essentially a switch which is activated by the error signal and supplies just an on-off correcting signal. The controller output has just two possible values, equivalent to on and off. For this reason the controller is sometimes termed a two-step controller. An example of such a controller is the bimetallic thermostat used with a simple temperature control system, if the actual temperature is above the required temperature,the bimetallic strip is in an off position and the heater is switched off; if the actual temperature is below the required temperature, the bimetallic strip moves into the on position and the heater is switched on. The controller output is thus just on or off and so the correcting signal on or off. Because the control action is discontinuous and there are time lags in the system, oscillations, i.e. cycling, of the controlled variable occur about the required condition. Thus, with temperature control using the bimetallic thermostat, when the room temperature drops below the required level there is a significant time before the heater begins to have an effect on the room temperature and, in the meantime, the temperature has fallen even more. When the temperature rises to the required temperature,since time elapses before the control system reacts and switches the heater off and it cools, the room temperature goes beyond the required value. The result is that the room temperature oscillates above and below the required temperature. On-off control is simple and inexpensive and is often used where cycling can be reduced to an acceptable level. PROPORTIONAL CONTROL With the on-off method of control, the controller output is either an on or an off signal and so the output is not related to the size of the error. With proportional control the size of the controller output is proportional to the size of the error, i.e. the controller input. We can write this as: Controller output = controller input where controller input is a constant called the gain. This means the correction element of the control system will have an input of a signal which is proportional to the size of the correction required. The float method of controlling the level of water in a cistern is an example of the use of a proportional controller where the controller output is proportional to the integral of the error with respect to time
  • 9. nuwemchris@gmail.com MODULATING FEEDBACK CONTROLL In this strategy, rather than switch the inlet valve open and shut, a more subtle approach is to inch the valve by an amount which depends on the difference between the actual level and the desired level. Modulating Control implies a more elaborate level measurement and valve actuator. In the first place it requires a signal related to the actual level (ie a level transmitter). Secondly, the value actuator must be able to open and close the inlet valve gradually (modulate the value opening). Furthermore the valve itself must have a smooth characteristic so that its resistance to flow is infinitely variable. DERIVATIVE CONTROL With derivative control the change in controller output from the set point value is proportional to the rate of change with time of the error signal, i.e. controller output rate of change of error It is usual to express these controller outputs as a percentage of the full range of output and the error as a percentage of full range. KD is the constant of proportionality and is commonly referred to as the derivative time since it has units of time. Figure illustrates the type of response that occurs when there is a steadily increasing error signal. Because the rate of change of the error with time is constant, the derivative controller gives a constant controller output signal to the correction element. With derivative control, as soon as the error signal begins to change there can be quite a large controller output since it is proportional to the rate of change of the error signal and not its value. Thus with this form of control there can be rapid corrective responses to error signals that occur. Derivative controllers give responses to changing error signals but do not, however, respond to constant error signals, since with a constant error the rate of change of error with time is zero.
  • 10. nuwemchris@gmail.com Digital Control: Digital systems The term direct digital control is used to describe the use of digital computers in the control system to calculate the control signal that is applied to the actuators to control the plant. Such a system is of the form shown in Figure . At each sample instant the computer samples, via the analogue-to- digital converter (ADC),the plant output to produce the sampled output value. This, together with the discrete input value is then processed by the computer according to the required control law to give the required correction signal which is then sent via the digital-to- analogue converter (DAC) to provide the correcting action to the plant to give the required control. Direct digital control laws are computer programs that take the set value and feedback signals and operate on them to give the output signal to the actuator. The program might thus be designed to implement PID control. Source; INSTRUMENTATION AND CONTROL SYSTEMS. W. BOLTON