STANDARD for

                                       PERFORMANCE
                                       RATING OF
                                       WATER -
                                       CHILLING
                                       PACKAGES
                                       USING THE
                                       VAPOR
                                       COMPRESSION
                                       CYCLE

                                            Standard 550/590




  4100 N. FAIRFAX DR., SUITE 200   •   ARLINGTON, VIRGINIA 22203
IMPORTANT

                                               SAFETY DISCLAIMER

        ARI does not set safety standards and does not certify or guarantee the safety of any products, components or
        systems designed, tested, rated, installed or operated in accordance with this standard/guideline. It is strongly
        recommended that products be designed, constructed, assembled, installed and operated in accordance with
        nationally recognized safety standards and code requirements appropriate for products covered by this
        standard/guideline.

        ARI uses its best efforts to develop standards/guidelines employing state-of-the-art and accepted industry practices.
        ARI does not certify or guarantee that any tests conducted under its standards/guidelines will be non-hazardous or
        free from risk.



                                      ARI CERTIFICATION PROGRAM PROVISIONS

                                             Scope of the Certification Program


                                                          60 Hz Power
                                               Included in Certification Program
                         Water-Cooled                                                 Air-Cooled
 All compressor types                                         All compressor types
 Rated up to 2000 tons [7034 kW] at ARI Standard Rating       Rated up to 200 tons [ 703 kW] at ARI Standard Rating
 Conditions                                                   Conditions
 Hermetic & open type, electric motor driven                  Hermetic & open type, electric motor driven
 Voltages up to 5000 volts                                    Voltages up to 600 volts
                                           Excluded from Certification Program
                         Water-Cooled                                                 Air-Cooled
 Condenserless chillers                                       Condenserless chillers
 Evaporatively cooled chillers                                Evaporatively cooled chillers
 Chillers above 2000 tons [7034 kW]                           Chillers above 200 tons [703 kW]
 Chillers with voltages above 5000 volts                      Chillers with voltages above 600 volts
 Chillers powered by other than electric motor drives         Chillers powered by other than electric motor drives
 Chillers with motors not supplied with the unit by           Secondary coolant ratings (other than water)
 The manufacturer                                             Free cooling
 Secondary coolant ratings (other than water)                 Heat recovery & heat pump ratings
 Free cooling
 Heat recovery & heat pump ratings




Price $10.00 (M) $20.00 (NM)                                                Copyright 2003, by Air-Conditioning and Refrigeration Institute
Printed in U.S.A.                                                            Registered United States Patent and Trademark Office
ARI CERTIFICATION PROGRAM PROVISIONS (CONTINUED)

                                Scope of the Certification Program (Continued)


                                                  50 Hz Power
                                         Included in Certification Program
                        Water-Cooled                                             Air-Cooled
Centrifugal & screw chillers with continuous unloading
Rated 200 - 1000 tons [703-3517 kW] at ARI Standard
Rating Conditions
Hermetic & open type, electric motor driven                                     Not applicable
Voltages up to 5000 volts
                                          Excluded from Certification Program
                        Water-Cooled                                             Air-Cooled
Scroll & reciprocating compressor chillers
with step unloading
Condenserless chillers
Evaporatively cooled chillers                                                   Not applicable
Chillers below 200 tons [703 kW]
Chillers above 1000 tons [3517 kW]
Chillers with voltages above 5000 volts
Chillers powered by other than electric motor drives
Chillers with motors not supplied with the unit by
The manufacturer
Secondary coolant ratings (other than water)
Free cooling
Heat recovery & heat pump ratings
Certified Ratings
The Certification Program ratings verified by test are:

         1.       Capacity, tons [kW]
         2.       Energy Efficiency, as applicable:
                    •     Power Input per Capacity, kW/ton [kW/kW]
                    •     Energy Efficiency Ratio (EER), Btu/(W⋅h)
                    •     Coefficient of Performance (COP), watts/watt [W/W]
         3.       Water pressure drop, psi or ft H2O [kPa]
         4.       Integrated Part-Load Value (IPLV) (Section 5.4.1)
         5.       Non-Standard Part-Load Value (NPLV) (Section 5.4.1)


         Items 1- 5 are at Standard Rating Conditions (Section 5.2) and at non-standard Rating Conditions (Section 5.3) for both
                  full and part load (Section 5.4 for part-load performance requirements).

                                                            Note:
                                   This standard supersedes ARI Standard 550/590-98 with addenda.
TABLE OF CONTENTS

SECTION                                                                                                                                    PAGE

Section 1.    Purpose ..............................................................................................................................1

Section 2.    Scope .................................................................................................................................1

Section 3.    Definitions .........................................................................................................................1

Section 4.    Test Requirements .............................................................................................................2

Section 5.    Rating Requirements .........................................................................................................3

Section 6.    Minimum Data Requirements for Published Ratings......................................................12

Section 7.    Marking and Nameplate Data..........................................................................................13

Section 8.    Conformance Conditions ...............................................................................................13


                                                             TABLES

Table 1.      Standard Rating Conditions...............................................................................................4

Table 2.      Heat Reclaim Standard Rating Conditions........................................................................5

Table 3.      Part-Load Conditions for Rating .......................................................................................6


                                                            FIGURES

Figure 1.     Part-Load Efficiency Curve...............................................................................................7

Figure 2.     Air-Cooled Condenser Entering Air Temperature vs. % Load .........................................9

Figure 3.     Allowable Tolerance Curves for Full and Part Load ........................................................9

Figure 4.     IPLV and NPLV Tolerance Curve .................................................................................11


                                                         APPENDICES

Appendix A.   References - Normative...................................................................................................14

Appendix B.   References - Informative .................................................................................................14

Appendix C.   Method of Testing Water Chilling
              Packages Using the Vapor Compression Cycle - Normative..........................................15

Appendix D.   Derivation of Integrated Part-Load Value (IPLV) - Normative......................................24
TABLES FOR APPENDICES

Table D1.    Group 1 Air-Cooled IPLV Data and Calculation ............................................................28

Table D2.    Group 1 Water-Cooled IPLV Data and Calculation........................................................29

Table D3.    Group 1 - 4 IPLV Summary ............................................................................................30


                                      FIGURES FOR APPENDICES

Figure D1.   Ton-Hour Distribution Categories...................................................................................25

Figure D2.   Bin Groupings – Ton-Hours............................................................................................26

Figure D3.   Group 1 Ton-Hour Distribution Categories ....................................................................26

Figure D4.   Group 2 Ton-Hour Distribution Categories ....................................................................26
ARI STANDARD 550/590-2003


      PERFORMANCE RATING OF WATER-CHILLING
   PACKAGES USING THE VAPOR COMPRESSION CYCLE
                  Section 1. Purpose                           3.3 Condenser. A refrigeration system component which
                                                               condenses refrigerant vapor. Desuperheating and sub-
1.1 Purpose. The purpose of this standard is to establish      cooling of the refrigerant may occur as well.
for Water-Chilling Packages using the vapor compression
cycle: definitions; test requirements; rating requirements;          3.3.1    Air-Cooled Condenser. A component which
minimum data requirements for Published Ratings; marking             condenses refrigerant vapor by rejecting heat to air
and nameplate data; and conformance conditions.                      mechanically circulated over its heat transfer surface
                                                                     causing a rise in the air temperature.
      1.1.1   Intent. This standard is intended for the
      guidance of the industry, including manufacturers,             3.3.2    Air-Cooled Heat Reclaim Condenser. A
      engineers, installers, contractors and users.                  component which condenses refrigerant vapor in the
                                                                     process of rejecting the heat of condensation to air
      1.1.2    Review and Amendment. This standard is                causing a rise in the air temperature. This Condenser
      subject to review and amendment as technology                  may be a separate Condenser the same as or a portion
      advances.                                                      of the Air-Cooled Condenser.

                                                                     3.3.3     Evaporatively-Cooled Condenser.           A
                   Section 2. Scope                                  component which condenses refrigerant vapor by
                                                                     rejecting heat to a water and air mixture mechanically
2.1 Scope. This standard applies to factory-made vapor               circulated over its heat transfer surface, causing
compression refrigeration Water-Chilling Packages                    evaporation of the water and an increase in the
including one or more hermetic or open drive compressors.            enthalpy of the air.
These Water-Chilling Packages include:
                                                                     3.3.4    Water-Cooled Condenser. A component
      •    Water-Cooled, Air-Cooled, or Evaporatively-               which utilizes refrigerant-to-water heat transfer
           Cooled Condensers,                                        means, causing the refrigerant to condense and the
      •    Air-Cooled or Water-Cooled Heat Reclaim                   water to be heated.
           Condensers,
      •    Packages supplied without a Condenser.                    3.3.5    Water-Cooled Heat Reclaim Condenser. A
                                                                     component which utilizes refrigerant-to-water heat
                                                                     transfer means, causing the refrigerant to condense
                Section 3. Definitions                               and the water to be heated. This Condenser may be a
                                                                     separate condenser, the same as, or a portion of the
All terms in this document follow the standard industry              Water-Cooled Condenser.
definitions in the current edition of ASHRAE Terminology
of Heating, Ventilation, Air Conditioning and Refrigeration    3.4 Dew Point. Refrigerant vapor saturation temperature
unless otherwise defined in this section.                      at a specified pressure.

3.1 Bubble Point.          Refrigerant liquid saturation       3.5   Energy Efficiency.
temperature at a specified pressure.
                                                                     3.5.1    Coefficient of Performance (COP). A ratio
3.2 Compressor Saturated Discharge Temperature. For                  of the cooling capacity in watts [W] to the Total
single component and azeotrope refrigerants, it is the               Power Input, in watts [W] at any given set of Rating
saturated temperature corresponding to the refrigerant               Conditions, expressed in watts/watt [W/W].
pressure at the compressor discharge. For zeotropic
refrigerants, it is the arithmetic average of the Dew Point          3.5.2    Energy Efficiency Ratio (EER). A ratio of
and Bubble Point temperatures corresponding to refrigerant           the cooling capacity in Btu/h [W] to the Total Power
pressure at the compressor discharge. It is usually taken at         Input in watts [W] at any given set of Rating
or immediately downstream of the compressor discharge                Conditions, expressed in Btu/(W⋅h).
service valve (in either case on the downstream side of the
valve seat), where discharge valves are used.



                                                                                                                         1
ARI STANDARD 550/590-2003

       3.5.3    Heat Reclaim Coefficient of Performance                  3.10.2 Standard Rating. A rating based on tests
       (COPHR). A ratio of the Net Heat Reclaim Capacity                 performed at Standard Rating Conditions.
       (Btu/h) to the Total Power Input to the unit, W
       converted to Btu/h                                         3.11 Rating Conditions. Any set of operating conditions
                                                                  under which a single level of performance results and which
       3.5.4    Power Input per Capacity. A ratio of the          causes only that level of performance to occur.
       Total Power Input to the unit, in kW to the Net
       Refrigerating Capacity at any given set of Rating                 3.1.1   Standard Rating Conditions.     Rating
       Conditions, expressed in kW/ton [kW/kW].                          Conditions used as the basis of comparison for
                                                                         performance characteristics.
3.6 Fouling Factor. The thermal resistance due to
fouling accumulated on the heat transfer surface.                 3.12 "Shall" or "Should". "Shall" or "should" shall be
                                                                  interpreted as follows:
       3.6.1     Fouling Factor Allowance. Provision for
       anticipated fouling during use specified in                       3.12.1 Shall. Where "shall" or "shall not" is used
       h⋅ft2⋅ºF/Btu [m2⋅ºC/W].                                           for a provision specified, that provision is mandatory
                                                                         if compliance with the standard is claimed.
3.7 Net Heat Reclaim Capacity. A quantity defined as
the mass flow rate of the condenser water multiplied by the              3.12.2 Should, "Should" is used to indicate
difference in enthalpy of water entering and leaving the heat            provisions which are not mandatory but which are
reclaim Condenser, Btu/h [kW].                                           desirable as good practice.

3.8 Net Refrigeration Capacity. A quantity defined as             3.13 Total Power Input. Power input of all components of
the mass flow rate of the evaporator water multiplied by the      the unit.
difference in enthalpy of water entering and leaving the
evaporator, Btu/h or tons [kW].                                   3.14 Water-Chilling Package. A factory-made and
                                                                  prefabricated assembly (not necessarily shipped as one
3.9 Part-Load Value (PLV). A single number figure of              package) of one or more compressors, Condensers and
merit expressing part-load efficiency for equipment on the        evaporators, with interconnections and accessories, designed
basis of weighted operation at various partial load capacities    for the purpose of cooling water. It is a machine specifically
for the equipment.                                                designed to make use of a vapor compression refrigeration
                                                                  cycle to remove heat from water and reject the heat to a
       3.9.1    Integrated Part-Load Value (IPLV). A              cooling medium, usually air or water. The refrigerant
       single number part-load efficiency figure of merit         Condenser may or may not be an integral part of the
       calculated per the method described in this standard       package.
       at Standard Rating Conditions.
                                                                         3.14.1 Heat Reclaim Water-Chilling Package. A
       3.9.2    Non-Standard Part-Load Value (NPLV). A                   factory-made package, designed for the purpose of
       single number part-load efficiency figure of merit                chilling water and containing a Condenser for
       calculated per the method described in this standard              reclaiming heat. Where such equipment is provided
       referenced to conditions other than IPLV conditions.              in more than one assembly, the separate assemblies
       (For units that are not designed to operate at Standard           are to be designed to be used together, and the
       Rating Conditions.)                                               requirements of rating outlined in this standard are
                                                                         based upon the use of matched assemblies. It is a
3.10 Published Ratings. A statement of the assigned                      package specifically designed to make use of the
values of those performance characteristics, under stated                refrigerant cycle to remove heat from the refrigerant
Rating Conditions, by which a unit may be chosen to fit its              and to reject the heat to another fluid (air or water)
application. These values apply to all units of like nominal             for heating use. Any excess heat may be rejected to
size and type (identification) produced by the same                      another medium, usually air or water.
manufacturer. The term Published Rating includes the
rating of all performance characteristics shown on the unit
or published in specifications, advertising or other literature               Section 4. Test Requirements
controlled by the manufacturer, at stated Rating Conditions.
                                                                  4.1 Test Requirements. Ratings shall be established at
       3.10.1 Application Rating. A rating based on tests         the Rating Conditions specified in Section 5. Ratings shall
       performed at application Rating Conditions (other          be verified by tests conducted in accordance with the test
       than Standard Rating Conditions).                          method and procedures described in Appendix C.


2
ARI STANDARD 550/590-2003

            Section 5. Rating Requirements                       5.4.1    Determination of Part- Load Performance.
                                                                 For Water-Chilling Packages covered by this
5.1 Standard Ratings. Standard Ratings for all Water-            standard, the IPLV or NPLV shall be calculated as
Chilling Packages shall be established at the Standard           follows:
Rating Conditions specified in 5.2.
                                                                         a.     Determine the part-load energy
5.2 Standard Rating Conditions.              Water-Chilling                     efficiency at 100%, 75%, 50%, and
Packages shall be rated at conditions specified in Table 1.                     25% load points at the conditions
Heat Reclaim Water-Chilling Packages shall be rated at                          specified in Table 3.
conditions specified in Table 2 and properly identified as the
Heat Reclaim Standard Rating. Standard Ratings shall                     b.     Use the following equation to calculate
include a water-side Fouling Factor Allowance of 0.00025                        the IPLV or NPLV.
h⋅ft2⋅ºF/Btu [0.000044 m2⋅ºC/W] for the Condenser and
0.0001 h⋅ft2 ⋅ºF/Btu [0.000018m2⋅ºC/W] for the evaporator.               IPLV
                                                                           or = 0.01A + 0.42B + 0.45C + 0.12D
                                                                         NPLV                                             1a
5.3 Application Rating Conditions. Application Ratings
should include the following range of Rating Conditions or
be within the operating limits of the equipment:
                                                                         For COP and EER:
All Condenser Types:
                                                                         where:       A = COP or EER at 100%
       Leaving chilled water temperature ......40.0 to 48.0ºF                         B = COP or EER at 75%
       [4.4 to 8.9ºC] in increments of 2ºF or less [1ºC or                            C = COP or EER at 50%
       less].                                                                         D = COP or EER at 25%

Water-Cooled Condensers:                                                 For kW/ton:

       Entering condenser water temperature ......65.0 to
       105.0ºF [18.3 to 40.6ºC] in increments of 5ºF or less
                                                                              IPLV             1
       [3°C or less].                                                          or =
                                                                                                                          1b
                                                                              NPLV 0.01 + 0.42 + 0.45 + 0.12
Air-Cooled Condensers:
                                                                                    A      B      C      D
       Entering Condenser air dry-bulb temperature ......55.0
       to 125.0°F [12.8 to 51.7°C] dry-bulb in increments of
       10°F or less [6°C or less].                                       where:       A=    kW/Ton at 100%
                                                                                      B=    kW/Ton at 75%
Evaporatively-Cooled Condensers:                                                      C=    kW/Ton at 50%
                                                                                      D=    kW/Ton at 25%
       Entering Condenser air wet-bulb temperature
       ......50.0 to 80.0°F [10.0 to 26.7°C] wet-bulb in                 5.4.1.1 For a derivation of equations 1a
       increments of 2.5°F or less [1.4°C or less].                      and 1b, and an example of an IPLV or
                                                                         NPLV calculation, see Appendix D. The
5.4 Part-Load Rating. Water-Chilling Packages which                      weighting factors have been based on the
are capable of capacity reduction shall be rated at 100% and             weighted average of the most common
at each step of capacity reduction provided by the                       building types and operations using average
refrigeration system(s) as published by the manufacturer.                weather in 29 U.S. cities, with and without
Part-load ratings points shall be presented in one or more of            airside economizers.
the following three ways:

       a.   IPLV- Based on the conditions defined in Table
            3.
       b.   NPLV- Based on the conditions defined in Table
            3.
       c.   Separate Part-Load Data Point(s) Suitable for
            Calculating IPLV or NPLV. In addition, other
            part-load points may also be presented.


                                                                                                                     3
4
                                                               Table 1. Standard Rating Conditions

                                            Water-Cooled                                  Evaporatively-Cooled                               Air-Cooled

     Condenser Water

          Entering        85.0 ºF                                29.4 ºC

         Flow Rate        3.0 gpm/ton                  0.054 L/s per kW
                                                                                                                                                                          ARI STANDARD 550/590-2003




    Condenser Fouling Factor Allowance

         Water-Side       0.00025 h · ft2 · ºF/Btu   0.000044 m2 · ºC/ W

          Air-Side                                                         0.0 ft2 · ºF/Btu                  0.0 m2 · ºC/W 0.0 h · ft2 · ºF/Btu           0.0 m2 · ºC/W

    Entering Air

          Dry-Bulb                                                                                                           95.0 ºF                            35.0 ºC

          Wet-Bulb                                                         75.0 ºF                                 23.9 ºC

    Evaporator Water

          Leaving         44.0 ºF                                 6.7 ºC 44.0 ºF                                     6.7 ºC 44.0 ºF                              6.7 ºC

         Flow Rate        2.4 gpm/ton                   0.043 L/s per kW 2.4 gpm/ton                      0.043 L/s per kW 2.4 gpm/ton              0.043 L/s per kW

    Evaporator Fouling Factor Allowance

         Water-Side       0.0001 h · ft2 ºF/Btu      0.000018 m2 · ºC/W 0.0001 h · ft2 ºF/Btu          0.000018 m2 · ºC/W 0.0001 h · ft2 ºF/Btu 0.000018 m2 · ºC/W

    Without Condenser

     Saturated Discharge 105.0 ºF                                40.6 ºC 105.0 ºF                                  40.6 ºC 125.0 ºF                             51.7 ºC

     Liquid Refrigerant   98.0 ºF                                36.7 ºC 98.0 ºF                                   36.7 ºC 105.0 ºF                             40.6 ºC

     Barometric Pressure 29.92 in Hg                           101.3 kPa 29.92 in Hg                             101.3 kPa 29.92 in Hg                       101.3 kPa
Table 2. Heat Reclaim Standard Rating Conditions


    Temperature                              Water-Cooled                          Evaporatively-Cooled                           Air-Cooled


    Condenser Water


    Entering                   75.0 ºF                              23.9 ºC

                               Flow rate same as in standard cooling           Flow rate same as in standard            Flow rate same as in standard
    Flow Rate
                                             ratings                                  cooling ratings                          cooling ratings

    Entering Air


    Dry-Bulb                                                                                                            40.0 ºF                  4.4 ºC


    Wet-Bulb                                                                  38.0 ºF                          3.3 ºC


    Evaporator Water Leaving   44.0 ºF                               6.7ºC    44.0 ºF                          6.7ºC    44.0 ºF                      6.7ºC


    Field Fouling Allowance              0.00025 h · ft2 · ºF/Btu                       0.0 h · ft2 · ºF/Btu                  0.0 h · ft2 · ºF/Btu


    Heat Reclaim Condenser


                               105.0 ºF                             40.6 ºC
    Entering                     or                                   or                                                70.0 ºF                  21.1ºC
                               95.0 ºF                              35.0 ºC


                               120.0 ºF                             48.9 ºC
    Leaving                      or                                   or                                                95.0 ºF                 35.0 ºC
                               105.0 ºF                             40.6 ºC


    Barometric Pressure        29.92 in Hg                     101.3 kPa      29.92 in Hg               101.3 kPa       29.92 in Hg          101.3 kPa
                                                                                                                                                             ARI STANDARD 550/590-2003




5
ARI STANDARD 550/590-2003


                                                   Table 3. Part-Load Conditions for Rating
                                                                  IPLV                                             NPLV
Evaporator (All Types)
                                            2                                                 2                       2
100% load LWT                                44.0 ºF                   6.7 ºC                   Selected LWT            Selected LWT
0% load LWT                                 44.0 ºF                    6.7 ºC                 Same as 100% load       Same as 100% load
                                            3                                                 3                       3
Flow Rate (gpm)                              2.4 gpm/ton               0.043 L/s per kW         Selected gpm/ton        [L/s per kW]
F.F.A.                                      0.0001 h · ft2 · ºF/Btu    0.000018 m2 · ºC/ W    As Specified            As Specified
1
  Water-Cooled Condenser
                                            2                                                 2                       2
100% load EWT                                85.0ºF                    29.4 ºC                    Selected EWT            Selected EWT
                                                                                              4                       4
75% load EWT                                75.0 ºF                    23.9 ºC
                                                                                              4                       4
50% load EWT                                65.0 ºF                    18.3 ºC
                                                                                              4                       4
25% load EWT                                65.0 ºF                    18.3 ºC
0% load EWT                                 65.0 ºF                    18.3 ºC                65.0 ºF                 18.3 ºC
                                            3                                                 3                       3
Flow rate (gpm) [L/s]                        3.0 gpm/ton               0.054 L/s per kW         Selected gpm/ton        L/s per kW
F.F.A.                                      0.00025 h · ft2 · ºF/Btu   0.000044 m2 · ºC/ W    As Specified            As Specified
1
  Air-Cooled Condenser (Use Figure 2)
100% load EDB                               95.0 ºF                    35.0 ºC
75% load EDB                                80.0 ºF                    26.7 ºC
50% load EDB                                65.0 ºF                    18.3 ºC                           No Rating Requirements
25% load EDB                                55.0 ºF                    12.8 ºC
0% load EDB                                 55.0 ºF                    12.8 ºC
F.F.A.                                      0.0 h⋅ft2⋅ºF/Btu           0.0 m2⋅ºC/W
1
  Evaporatively-Cooled Condenser
100% load EWB                               75.0 ºF                    23.9 ºC
                                                                                                         No Rating Requirements
0% load EWB                                 50.0 ºF                    10.0 ºC
F.F.A.                                      0.0 h⋅ft2⋅ºF/Btu           0.0 m2⋅ºC/W
Air-Cooled Without Condenser
100% load SDT                               125.0 ºF                   51.7 ºC                           No Rating Requirements
0% load SDT                                 55.0 ºF                    12.8 ºC
Water and Evaporatively-Cooled
Without Condenser
                                                                                                         No Rating Requirements
100% load SDT                               105.0 ºF                   40.6 ºC
0% load SDT                                 65.0 ºF                    18.3 ºC
1
             If the unit Manufacturer’s recommended minimum temperatures are greater than those specified in Table 3, then those may
             be used in lieu of the specified temperatures.
2
             Corrected for Fouling Factor Allowance by using the calculation method described in C6.3
3
             The flow rates are to be held constant at full load values for all part-load conditions.
4
             For part-load entering condenser water temperatures, the temperature should vary linearly from the selected EWT at 100%
             load to 65.0 ºF at 50% loads, and fixed at 65.0°F for 50% to 0% loads.

SDT      -   saturated discharge temperature
LWT      -   leaving water (liquid) temperature
EWT      -   entering water (liquid) temperature
EDB      -   entering air dry-bulb temperature
EWB      -   entering air wet-bulb temperature
F.F.A.   -   Fouling Factor Allowance




    6
ARI STANDARD 550/590-2003

5.4.1.2 The IPLV or NPLV rating requires                          where CD is a degradation factor to
that the unit efficiency be determined at                         account for cycling of the compressor for
100%, 75%, 50% and 25% at the conditions                          capacities less than the minimum step of
as specified in Table 3. If the unit, due to its                  capacity. CD should be calculated using
capacity control logic can not be operated at                     the following equation:
75%, 50%, or 25% capacity then the unit
shall be operated at other load points and the                        C D = (-0.13 ⋅ LF) + 1.13
75%, 50%, or 25% capacity efficiencies shall
be determined by plotting the efficiency                          where LF is the load factor calculated
versus the % load using straight line                             using the following equation:
segments to connect the actual performance
points (Figure 1). The 75%, 50%, or 25%
                                                                             % FL
load efficiencies shall then be determined                                           ⋅ (Full load unit capacity)
from the curve. Extrapolation of data shall                        LF =       100
not be used. An actual chiller capacity point                                   (Part − load unit capacity)
equal to or less than the required rating point
must be used to plot the data. For example,
if the minimum actual capacity is 33% then                        where % FL is the % of full load at
the curve can be used to determine the 50%                        standard rating points, i.e. 75%, 50%, and
capacity point, but not the 25% capacity                          25%.
point.
                                                                  Part-Load unit capacity is the measured or
                                                                  calculated unit capacity from which
                                                                  Standard Rating points are determined
                                                                  using the method above.

                                                                  5.4.1.3 Sample Calculation.     The
                                                                  following is an example of an IPLV
                                                                  calculation:

                                                                       Part-Load Values Provided
                                                          Step             Capacity      Input      EER
                                                                          (tons)         (kW)
                                                        3 (full)             100.0       92.3       13.00
                                                             2               72.1        57.4       15.07
If a unit cannot be unloaded to the 25%,                     1*              41.3        31.3       15.83
50%, or 75% capacity point, then the unit
shall be run at the minimum step of                          1**             41.8        33.3       15.06
unloading at the condenser entering water or            *     Minimum possible unit capacity at load conditions.
air temperature based on Table 3 for 25%,               **    Performance at minimum step at 25% load conditions
50% or 75% capacity points as required. The
efficiency shall then be determined by using           Using the above data the part-load EER value
the following equation:                                can be calculated.

           Measured Cooling Capacity
EER =                                              2                      Part-Load Values Provided
        C D ⋅ Measured Total Power Input

                                                                     Point     Load%     Capacity      EER
                                                                                          (tons)
                                                                      A         100%       100         13.00
                                                                      B         75%         75         14.85
                                                                      C         50%         50         15.62



                                                                                                               7
ARI STANDARD 550/590-2003

                Because the unit cannot unload to 25%                              5.5.1.2 Evaporator       water-side     and
                capacity,    the    following     additional                       condenser water-side or air-side heat
                calculations are required to determine point                       transfer surfaces shall be considered clean
                “D”, using the minimum capacity data point                         during testing. Tests will be assumed to
                listed above that was determined at the                            reflect Fouling Factors of 0.0 h⋅ft2 °F/Btu
                minimum step of capacity at the conditions                         [0.0 m2°C/W].
                of a 25% capacity.
                                                                                   5.5.1.3 To determine the capacity of the
                        (0.25) x (100)                                             Water-Chilling Package at the rated
                 LF =                    = 0.60                                    fouling conditions, the procedure defined
                            41.8
                                                                                   in C6.3 shall be used to determine an
                                                                                   adjustment for the evaporator and or
                CD = (-0.13 x 0.60) + 1.13 = 1.05
                                                                                   condenser water temperatures.
                           41.8 x 12000                 Btu       5.6     Tolerances.
               EER =                         = 14.35
                        1.05 x 33.3 x 1000             (W ⋅ h )
                                                                          5.6.1    Allowable Tolerances. The allowable test
                Using the A, B, C and D efficiencies the                  tolerance on capacity, tons [kW], EER, COP, Power
                IPLV can then be calculated as follows:                   Input per Capacity kW/ton [kW/kW] and heat
                                                                          balance shall be determined from the following
                  IPLV (EER) = (0.01 x 13.00) + (0.42 x                   equation:
                               14.85) + ( 0.45 x 15.62)
                               + (0.12 x 14.35)                           Tolerance %
                             =15.12 Btu/(W⋅h)
                                                                                                                 E
                                                                            = 10.5 - (0.07 x % FL) + (                  )
5.5 Fouling Factor Allowances. When ratings are                                                           DTFL   x % FL
published, they shall include those with Fouling Factors as
specified in Table 1. Additional ratings, or means of                       DTFL     = Difference between entering and
determining those ratings, at other Fouling Factor Allowances                          leaving chilled water temperature at
may also be published.                                                                 full load, °F [°C]

      5.5.1    Method of Establishing Clean and Fouled                      E        = 1500 for IP, [833.3] for SI units
      Ratings from Laboratory Test Data.
                                                                        See Figure 3 for graphical representation only.
                5.5.1.1 A series of tests shall be run in
                accordance with the method outlined in
                Appendix C to establish the unit’s
                performance.




8
ARI STANDARD 550/590-2003




                        9
ARI STANDARD 550/590-2003

     5.6.2    Full Load. To comply with this standard,
     published or reported Net Refrigeration Capacity         Rated full load performance
     shall be based on data obtained in accordance with
     the provisions of this section, and shall have a Net     Rated capacity = 100 tons
     Refrigeration Capacity and full load efficiency of not   Rated power    = 70 kW
     less than 100 % of its ratings within the allowable      Cooling DTFL = 10ºF
     tolerance.    The allowable tolerance shall be
     determined by the equation specified in 5.6.1.                                                         kW
                                                              Total Power Input per Capacity = 0.70
                                                                                                            ton
     Water pressure drop in the evaporator and Condenser
     shall not exceed 115 % of the rated pressure drop at     Allowable Test Tolerance:
     the specified water flow rate.
                                                                                                    (1500)
     Full Load Example in EER (in IP Units only for           Tolerance = 10.5 - (.07 x 100) +
     clarity):                                                                                    (10 x 100)

     Rated Full Load Performance                                          = 10.5 – 0 7 + 1.5 = 5%

     Rated Capacity = 100 tons                                                             (100 − 5)
     Rated Power     = 92.3 kW                                Min. allowable capacity =              x 100
                                                                                             100
     Evaporator DTFL = 10°F
                                                                          = 95 tons
              100 tons x 12000 Btu/ton ⋅ h         Btu
     EER =                                 = 13.0
                92.3 kW x 1000W/kW                (W ⋅ h)                                         (100 + 5)
                                                              Max. allowable kW / ton =                     x .70
     Allowable Test Tolerance =
                                                                                                    100
                                                                          = .735 kW/ton
                                          1500
     10.5 - (0.07 x 100%) +
                                       10 x 100%              Max. power at min. capacity

     = 10.5 - 7 + 1.5 = 5%                                                = .735 x 95 = 69.825 kW

     Min. Allowable Capacity =                                5.6.3     Part-Load. The tolerance on part-load EER
                                                              shall be the tolerance as determined from 5.6.1.
     (100 tons − 5 tons )      x 100 = 95 tons
              100                                             Part-Load Example in EER (in IP Units only for
                                                              clarity):
     Min. Allowable EER =
                                                              Rated Part-Load Performance
     (100 - 5)   x 13.0
                              Btu
                                       = 12.35
                                                  Btu         Power at 69.5% Rated Capacity          =      59.6 kW
        100                  (W ⋅ h)             (W ⋅ h)      69.5% Rated Capacity                   =      69.5 tons
                                                              Cooling DTFL                           =      10.0°F
     Max. power at min. capacity =
                                                                       69.5 x 12000                  Btu
                                                              EER =                      = 14.0
      95 tons x 12000 Btu/ton ⋅ h                                       59.6 x 1000               (W ⋅ h)
                                         = 92.3 kW
                    Btu
           12.35             x 1000
                   (W ⋅ h)
                                                              Allowable Test Tolerance =

                                                                                           1500
                                                              10.5 − (0.07 ⋅ 69.5%) +
                                                                                        10 x 69.5%
     Full Load Example in kW/ton (in IP Units only for
     clarity):                                                            = 10.5 - 4.87 + 2.16 = 7.8%

10
ARI STANDARD 550/590 2003

Min. Allowable EER =
                                                    Max. allowable Total Power Input per Ton
(100 - 7.8)
            x 14.0 = 12.91 EER
   100                                                                   (100 + 10%)
                                                                     =                 x .70
                                                                           100
Part-Load Example in kW/ton (in IP Units only for                    = 0.77 kW/ton
clarity):
                                                    5.6.4    IPLV and NPLV Tolerances. The allowable
Rated Part-Load Performance                         tolerance on IPLV and NPLV shall be determined by
                                                    the following equation:
50% capacity                =   50 tons                                                  35
50% power                   =   35 kW               Allowable Percent Tolerance = 6.5 +
Total Power Input per Ton   =   0.70 kW/ton                                             DTFL
Full Load DTFL              =   10ºF
                                                    See Figure 4
Allowable Test Performance
                                                    The single number IPLV or NPLV, calculated for the
                                        (1500)      part-load conditions, shall not be less than the rated
 Tolerance      = 10.5 - (.07 x 50) +               IPLV or NPLV, less the allowable tolerance.
                                      10 x 50
                 = 10.5 - 3.5 + 3 = 10%




                                                                                                      11
ARI STANDARD 550/590-2003

     Section 6. Minimum Data Requirements for                  6.2.2   Water-Cooled Condenser Packages.
                 Published Ratings
                                                                       6.2.2.1 Condenser water pressure drop
6.1 Minimum Data Requirements for Published Ratings.                   (inlet to outlet), psi or ft H2O [kPa].
As a minimum, Published Ratings shall include all Standard
Ratings. All claims to ratings within the scope of this                6.2.2.2    Any two of the following:
standard shall include the statement "Rated in accordance
with ARI Standard 550/590." All claims to ratings outside              Entering condenser water temperature, ºF
the scope of the standard shall include the statement                  [ºC]
"Outside the scope of ARI Standard 550/590." Wherever                  Leaving condenser water temperature, ºF
Application Ratings are published or printed, they shall               [ºC]
include a statement of the conditions at which the ratings             Water temperature rise through the
apply.                                                                 condenser, ºF [ºC]

6.2 Published Ratings. Published Ratings shall state all of            6.2.2.3 Condenser water flow rate, gpm
the standard operating conditions and shall include the                [L/s].
following.
                                                                       6.2.2.4 Condenser       Fouling     Factor,
       6.2.1   General.                                                h · ft2 · ºF/Btu [m2 · ºC/ W], as stated in
                                                                       Table 1.
               6.2.1.1 Refrigerant   designation in
               accordance with ANSI/ASHRAE Standard            6.2.3   Air-Cooled Condenser Packages.
               34.
                                                                       6.2.3.1 Entering air dry-bulb temperature,
               6.2.1.2 Model number designations                       ºF [ºC] (as stated in Table 1).
               providing identification of the Water-
               Chilling Packages to which the ratings shall            6.2.3.2 Power input to fan(s), kW [kW].
               apply.
                                                               6.2.4   Evaporatively-Cooled Condenser Packages.
               6.2.1.3 Net Refrigeration Capacity, tons
               [kW].                                                   6.2.4.1 Entering air wet-bulb temperature,
                                                                       ºF [ºC] (as stated in Table 1).
               6.2.1.4 Total Power Input to chiller, bhp or
               kW, as applicable.                                      6.2.4.2 Power input to fan(s) and pump(s),
                                                                       kW [kW].
               6.2.1.5 Energy Efficiency, expressed as
               EER, COP or kW/ton.                                     6.2.4.3 Condenser spray pump power
                                                                       consumption, kW [kW].
               6.2.1.6 Evaporator       Fouling    Factor,
               h · ft2 · ºF/Btu [m2 · ºC/ W], as stated in             6.2.4.4 Statement of Condenser Fouling
               Table 1.                                                Factor Allowance on heat exchanger,
                                                                       h · ft2 · ºF/Btu [m2 · ºC/ W].
               6.2.1.7 Chilled water entering and leaving
               temperatures, ºF [ºC] (as stated in Table 1),   6.2.5   Packages without Condenser (for use with
               or leaving water temperature and                Remote Condensers).
               temperature difference, ºF [ºC].
                                                                       6.2.5.1 Compressor saturated discharge
               6.2.1.8 Evaporator water pressure drop                  temperature, ºF [ºC] (as stated in Table 1).
               (inlet to outlet), psi or ft H2O [kPa].
                                                                       6.2.5.2 Liquid refrigerant temperature
               6.2.1.9 Chilled water flow rate, gpm [L/s].             entering chiller package, ºF [ºC] (as stated
                                                                       in Table 1).
               6.2.1.10 Nominal voltage, V, and
               frequency, Hz, for which ratings are valid.             6.2.5.3 Condenser heat rejection capacity
                                                                       requirements, Btu/h [kW].




12
ARI STANDARD 550/590 2003

     6.2.6    Heat Reclaim Condenser(s).                              b.   Model number designation providing complete
                                                                           identification
              6.2.6.1 Heat Reclaim Capacity, MBtu/h                   c.   Refrigerant designation (in accordance with
              [kW].                                                        ANSI/ASHRAE Standard 34
                                                                      d.   Voltage, phase and frequency
              6.2.6.2 Water pressure drop, psi or ft H2O
              [kPa] or air pressure drop, in H2O [kPa].        Nameplate voltages for 60 Hertz systems shall include one
                                                               or more of the equipment nameplate voltage ratings shown
              6.2.6.3 Entering and leaving heat reclaim        in Table 1 of ARI Standard 110. Nameplate voltages for 50
              Condenser air or water temperatures, ºF [ºC]     Hertz systems shall include one or more of the utilization
              (stated in Table 2).                             voltages shown in Table 1 of IEC Standard Publication
                                                               60038.
              6.2.6.4 Heat reclaim Condenser air flow
              rate, cfm [m3/s] or heat reclaim Condenser               Section 8. Conformance Conditions
              water flow rate, gpm [L/s].
                                                               8.1 Conformance. While conformance with this standard
              6.2.6.5 Fouling Factor, h · ft2 · ºF/Btu [m2     is voluntary, Conformance shall not be claimed or implied
              · ºC/ W], as stated in Table 1 (for water heat   for products or equipment within the standard’s Purpose
              reclaim Condensers only).                        (Section 1) and Scope (Section 2) unless such product
                                                               claims meet all of the requirements of the standard and all of
                                                               the testing and rating requirements are measured and
    Section 7. Marking and Nameplate Data                      reported in complete compliance with the standard. Any
                                                               product that has not met all the requirements of the standard
7.1 Marking and Nameplate Data. As a minimum, the              cannot reference, state, or acknowledge the standard in any
nameplate shall display the following:                         written, oral, or electronic communication.

     a.   Manufacturer's name and location




                                                                                                                         13
ARI STANDARD 550/590-2003

                APPENDIX A. REFERENCES - NORMATIVE
A.1 Listed here are all standards, handbooks and other               A1.4    ARI Standard 110-2002, Air-Conditioning
publications essential to the formation and implementation           and Refrigerating Equipment Nameplate Voltages,
of the standards. All references in this appendix are                2002, Air-Conditioning and Refrigeration Institute,
considered as part of the standard.                                  4100 North Fairfax Drive, Suite 200, Arlington, VA
                                                                     22203, U.S.A.
      A1.1    ANSI/ASHRAE Standard 30-1995, Method
      of Testing Liquid Chilling Packages, 1995,                     A1.5     ASHRAE Terminology of Heating
      American Society of Heating, Refrigeration, and Air-           Ventilation, Air Conditioning and Refrigeration,
      Conditioning Engineers, Inc. ASHRAE, 25 West                   Second Edition, 1991, American Society of Heating,
      43rd Street, 4th Fl., New York, NY, 10036,                     Refrigeration, and Air-Conditioning Engineers, Inc.
      U.S.A./1791 Tullie Circle, N.E., Atlanta, Georgia,             ASHRAE, 1791 Tullie Circle, N.E., Atlanta,
      30329, U.S.A.                                                  Georgia, 30329, U.S.A.

      A1.2     ANSI/ASHRAE Standard 34-2001 with                     A1.6    ASME      Standard   PTC     19.2-1987,
      Addenda, Number Designation and Safety                         Instruments and Apparatus, Part 2, Pressure
      Classification of Refrigerants, 2001, American                 Measurement, 1987, American Society of
      Society of Heating, Refrigeration, and Air-                    Mechanical Engineers. ASME, 345 East 47th Street,
      Conditioning Engineers, Inc., ASHRAE, 25 West                  New York, NY 10017, U.S.A.
      43rd Street, 4th Fl., New York, NY, 10036,
      U.S.A./1791 Tullie Circle, N.E., Atlanta, Georgia,             A1.7     IEC Standard Publication 60038, IEC
      30329, U.S.A.                                                  Standard      Voltages,   1983,      International
                                                                     Electrotechnical Commission, rue de Varembe, P.O.
      A1.3     ANSI/ASHRAE Standard 41.1-86 (RA                      Box 131, 1211 Geneva 20, Switzerland.
      2001), Measurements Guide - Section on
      Temperature Measurements, 2001, American Society               A1.8     ISA Standard RP31.1, Recommended
      of Heating, Refrigeration, and Air-Conditioning                Practice Specification, Installation, and Calibration
      Engineers, Inc. ASHRAE, 25 West 43rd Street, 4th               of Turbine Flowmeters, 1977, Instrument Society of
      Fl., New York, NY, 10036, U.S.A./1791 Tullie                   America, ISA, 67 Alexander Drive, P.O. Box 12277,
      Circle, N.E., Atlanta, Georgia, 30329, U.S.A.                  Research Triangle Park, NC 27709, U.S.A.




              APPENDIX B. REFERENCES - INFORMATIVE
                                                             None.




14
ARI STANDARD 550/590-2003

  APPENDIX C. METHOD OF TESTING WATER-CHILLING
 PACKAGES USING THE VAPOR COMPRESSION CYCLE -
                   NORMATIVE
C1. Purpose. The purpose of this appendix is to prescribe        C5.1.6 for Water-Cooled Heat Reclaim
a method of testing for Water-Chilling Packages using the        Condensers and C5.1.7 for Air-Cooled Heat
vapor compression cycle and to verify capacity and power         Reclaim Condensers.
requirements at a specific set of conditions.
                                                                         C3.1.5.1 For      Water-Cooled
Testing shall occur where instrumentation and load stability             Heat Reclaim Condensers, the heat
is provided.                                                             reclaim capacity shall be
                                                                         determined by obtaining the
Testing shall not be conducted in field installations where              following data:
steady state conditions are difficult to achieve and
provisions for measurement are not made.                                 a.   Fluid flow rate, gpm [L/s]
                                                                         b.   Temperature        difference
C2. Definitions. Definitions for this appendix are                            between entering and leaving
identical with those in Section 3 of this standard.                           water °F, [°C]

C3.   Test Methods.                                                      The heat rejected through the heat
                                                                         reclaim Condenser is equal to the
      C3.1      Test Method.                                             product of the heat reclaim
                                                                         Condenser water flow rate, the
                C3.1.1 The test will measure net cooling                 water temperature difference, and
                capacity (tons of refrigeration) and energy              the specific heat of water as
                requirements, at a specific set of conditions.           defined by equation C7.

                C3.1.2 To confirm that steady-state                      C3.1.5.2 For Air-Cooled Heat
                conditions have been established at the                  Reclaim Condensers, the heat
                specific set of conditions and within the                reclaim capacity shall be
                tolerances set forth in C6.2.1, three sets of            determined by obtaining the
                data shall be taken, at a minimum of five-               following data:
                minute intervals. To minimize the effects of
                transient conditions, test readings should be            a.   Heat Reclaim Condenser air
                taken as simultaneously as possible.                          flow rate, standard cfm [m3/s]
                                                                              (for air)
                C3.1.3 The test shall include a                          b.   Heat reclaim Condenser air
                measurement of the net heat removed from                      temperature         difference
                the water as it passes through the evaporator                 between entering and leaving
                by determination of the following:                            air

                         a.    Water flow rate, gpm [L/s]                The heat rejected through the Air-
                         b.    Temperature        difference             Cooled Heat Reclaim Condenser
                               between entering and leaving              is equal to the product of the heat
                               water °F, [°C]                            reclaim Condenser airflow rate,
                                                                         the air temperature difference, and
                C3.1.4 The heat removed from the chilled                 the specific heat of moist air as
                water is equal to the product of the chilled             defined by equation C8.
                water flow rate, the water temperature
                difference, and the specific heat of the water           C3.1.5.3 The test shall include
                defined by equation C6.                                  the    determination     of   the
                                                                         compressor power requirement.
                C3.1.5 If supplied with the Water-Chilling               This power shall be determined by
                Package, the test shall include simultaneous             measurement of electrical input to
                determination of the heat reclaim Condenser              the motor drive (see C7.1.4). For
                capacity by obtaining the data as defined in             motors supplied by others, the

                                                                                                        15
ARI STANDARD 550/590- 2003

                    determination of compressor shaft                      C3.2.1 Tests conducted in accordance
                    horsepower input shall be outlined                     with this standard may require cleaning (in
                    in the test procedure. For Air-                        accordance        with       manufacturer's
                    Cooled or Evaporatively-Cooled                         instructions) of the heat transfer surfaces.
                    Condensers, the test shall include                     The as tested Fouling Factors shall then be
                    the    determination     of    the                     assumed to be 0.0 h ⋅ ft2 ⋅ °F/Btu [0.0 m2 ⋅
                    Condenser fan and Condenser                            °C/W].
                    spray pump power requirements.
                                                             C4   Instrumentation.
                    C3.1.5.4 Non-Electric Drive.
                    Where turbine or engine drive is              C4.1    Accuracy of instruments selected shall be in
                    employed, compressor shaft                    accordance with ANSI/ASHRAE Standard 30.
                    horsepower input shall be
                    determined from steam, gas, or oil            C4.2    Temperature measurements shall be made in
                    consumption, at measured supply               accordance with ANSI/ASHRAE Standard 41.1.
                    and exhaust conditions and prime
                    mover manufacturer's certified                C4.3      Flowmeters shall be constructed and
                    performance data.                             installed in accordance with the applicable portion of
                                                                  ANSI/ASHRAE Standard 30. Turbine flow meters
            C3.1.6 Test Verification.                             may be also used in accordance with ISA Standard
                                                                  RP31.1.
                    C3.1.6.1 For the case of Water-
                    Cooled Condensers, in addition to             C4.4      Scales for analog meters shall be such that
                    the determination of net heat                 readings will be at least one-third of full scale
                    removed and energy input                      deflection. All instruments, including gauges and
                    required, data shall be taken to              thermometers shall be calibrated over the range of
                    prepare a heat balance (C6.4.1) to            test readings.
                    substantiate the validity of the test.
                                                                  C4.5    Pressure measurements shall be made in
                    C3.1.6.2 For Air-Cooled and                   accordance with ASME Power Test Code PTC 19.2.
                    Evaporatively-              Cooled
                    Condensers, it is impractical to         C5   Measurements.
                    measure heat rejection in a test;
                    therefore, a heat balance cannot be            C5.1    Data to be Recorded During the Test.
                    calculated.       To verify test
                    accuracy, concurrent redundant                         C5.1.1 Test     Data.       Compressor/
                    instrumentation method (C6.4.2)                        Evaporator (All Condenser Types):
                    shall be used to measure water
                    temperatures, flow rates, and                                    a.   Temperature of water entering
                    power inputs.                                                         evaporator, °F [°C]
                                                                                     b.   Temperature of water leaving
                    C3.1.6.3 For heat reclaim units                                       evaporator, °F [°C]
                    with Air-Cooled Condensers or                                    c.   Chilled water flow rates, gpm
                    Water-Cooled Condensers, where                                        [L/s]
                    the capacity is not sufficient to                                d.   Power input to compressor
                    fully condense the refrigerant, the                                   electrical power, kW [kW]
                    concurrent              redundant
                    instrumentation methods (C6.4.2)                                      Steam      consumption     of
                    shall be used.                                                        turbine, lb/h [kg/h]
                    C3.1.6.4 For heat reclaim units                                       Steam supply pressure, psig
                    with Water-Cooled Condensers                                          [kPa]
                    that fully condense the refrigerant,
                    the heat balance methods (C6.4.1)                                     Steam supply temperature, ºF
                    shall be used.                                                        [ºC]
                                                                                          Steam exhaust pressure, psig
     C3.2   Condition of Heat Transfer Surfaces.                                          or in Hg vac [kPa], or


16
ARI STANDARD 550/590-2003

            Gas consumption of turbine          C5.1.5 Without Condenser.
            or engine, therms or ft3/h,
            [m3/s] and calorific value,                  a.   Discharge         temperature
            Btu/ft3, [J/L], or                                leaving compressor, °F [°C]
                                                         b.   Discharge pressure leaving
            Fuel consumption of diesel or                     compressor, psig [kPa]
            gasoline, gal/h [L/s] and                    c.   Liquid refrigerant temperature
            calorific value, Btu/gal [J/L]                    entering the expansion device,
                                                              °F [°C]
       e.   Evaporator water pressure                    d.   Liquid pressure entering the
            drop (inlet to outlet), psi or ft                 expansion device, psig [kPa]
            H2O [kPa]
       f.   Electrical power input to           C5.1.6 Water-Cooled         Heat     Reclaim
            controls     and      auxiliary     Condenser.
            equipment, kW [kW] (if not
            included in d)                               a.   Temperature of heat reclaim
                                                              entering Condenser water, °F
C5.1.2 Water-Cooled Condenser).                               [°C]
                                                         b.   Temperature of heat reclaim
       a.   Temperature of water entering                     leaving Condenser water, °F
            the Condenser, °F [°C]                            [°C]
       b.   Temperature of water leaving                 c.   Heat reclaim Condenser water
            the Condenser, °F [°C]                            flow rate, gpm [L/s]
       c.   Condenser water flow rate,                   d.   Heat reclaim Condenser water
            gpm [L/s]                                         pressure drop (inlet to outlet),
       d.   Condenser water pressure                          psi or ft H2O [kPa]
            drop (inlet to outlet), psi or ft
            H2O [kPa]                           C5.1.7 Air-Cooled         Heat       Reclaim
                                                Condenser.
C5.1.3 Air-Cooled Condenser.
                                                         a.   Dry-bulb temperature of air
       a.   Dry-bulb temperature of air                       entering the heat reclaim
            entering the Condenser, °F                        Condenser, °F [°C]
            [°C]                                         b.   Dry-bulb temperature of air
       b.   Condenser fan motor power                         leaving the heat reclaim
            consumption, kW [kW]                              Condenser, °F [°C]
       c.   Barometric pressure, in Hg                   c.   Heat reclaim Condenser
            [kPa]                                             standard air flow rate, cfm,
                                                              [m3/s]
C5.1.4 Evaporatively-Cooled Condenser.                   d.   Barometric pressure, in Hg
                                                              [kPa]
       a.   Wet-bulb temperature of air
            entering the Condenser, °F          C5.1.8 If chilled water is used to remove
            [°C]                                heat from any other source(s) within the
       b.   Condenser fan motor power           package, the temperature and flow
            consumption, kW [kW]                measurements of chilled water must be
       c.   Condenser spray pump power          made at points so that the measurement
            consumption, kW [kW]                reflects the net package cooling capacity.
       d.   Barometric pressure, in Hg
            [kPa]                               C5.1.9 If Condenser water is used to cool
                                                the compressor motor or for some other
                                                incidental function within the package, the
                                                temperature and flow measurements of
                                                condenser water must be made at points, so
                                                that the measurement reflects the gross
                                                package heat rejection.



                                                                                          17
ARI STANDARD 550/590- 2003

     C5.2    Auxiliary Data to be Recorded for General     C6.2   Operations and Limits.
     Information.
                                                                  C6.2.1 Start the system and establish the
             C5.2.1 Nameplate data including make,                testing conditions in accordance with the
             model, size and refrigerant, sufficient to           following tolerances and instructions.
             completely identify the water chiller. Unit
             voltage and frequency should be recorded.                    C6.2.1.1 Evaporator             (All
                                                                          Condenser Types)
             C5.2.2 Compressor driver or input rpm for
             open-type compressors.                                       a.   The chilled water flow rate,
                                                                               gpm [L/s], shall not deviate
             C5.2.3 Ambient temperature at test site,                          more than + 5% from that
             °F [°C].                                                          specified.
                                                                          b.   The individual readings of
             C5.2.4 Actual voltage, V, and current,                            water temperature leaving the
             Amps, for each phase of all electric motor                        evaporator shall not vary from
             drives.                                                           the specified values by more
                                                                               than 0.5°F [0.3°C]. Care
             C.5.2.5 Motor, engine or turbine nameplate                        must be taken to insure that
             data.                                                             these water temperatures are
                                                                               the average bulk stream
             C5.2.6 Pressure,      in   H2O      [kPa],                        temperatures.
             temperature, °F [°C] and exhaust pressure,                   c.   The leaving chilled water
             in H2O [kPa] for steam turbine nameplate                          temperature shall be adjusted
             data.                                                             by an increment calculated
                                                                               per C6.3 corresponding to the
             C5.2.7 Fuel gas specification for gas                             specified      field    fouling
             turbine drive, including pressure, in H2O                         allowance required for test.
             [kPa].                                                       d.   Part-load tests for Water-
                                                                               Chilling Packages which have
             C5.2.8 Heat balance for C6.4.                                     continuous             capacity
                                                                               modulation must be taken
             C5.2.9 Date, place, and time of test.                             within + 2% of the full load
                                                                               tons at the specified part load
             C5.2.10 Names of test supervisor and                              capacity.
             witnessing personnel.                                        e.   For water chillers with
                                                                               discrete steps of capacity
C6   Test Procedure.                                                           control, the part-load tests
                                                                               shall be taken as close as
     C6.1    Preparation for Test.                                             practical to the specified part-
                                                                               load capacity as per Table 3.
             C6.1.1 The Water-Chilling Package,
             which has been completely connected in                       C6.2.1.2 Water-Cooled
             accordance with the manufacturer's                           Condenser.
             instructions and is ready for normal
             operation, shall be provided with the                        a.   The water flow rate, gpm
             necessary instrumentation.                                        [L/s], through the Condenser
                                                                               shall not deviate more than +
             C6.1.2 The test shall not be started until                        5% from that specified.
             non-condensables have been removed from                      b.   The individual readings of
             the system.                                                       water temperatures entering
                                                                               the refrigerant Condenser
             C6.1.3 At the manufacturer’s option,                              shall not vary from the
             Condenser and cooler surfaces may be                              specified values by more than
             cleaned as provided in C3.2.1.                                    0.5°F [0.3°C]. Care must be
                                                                               taken to insure that these
                                                                               water temperatures are the


18
ARI STANDARD 550/590-2003

     average     bulk       stream                                the turbine, and Condenser
     temperatures.                                                pressure or vacuum, shall be
c.   The entering condensing                                      maintained at nameplate
     water temperature shall be                                   values.
     adjusted by an increment                              c.     For gas-turbine or gas-engine
     calculated     per       C6.3                                operating machines, gas
     corresponding to the specified                               pressure to turbine or engine,
     Fouling Factor Allowance.                                    and exhaust back-pressure at
                                                                  the turbine or engine shall be
C6.2.1.3 Air-Cooled                                               maintained at nameplate
Condenser,  Including         Heat                                values.
Reclaim.                                                   d.     In all cases, the governor, if
                                                                  provided, shall be adjusted to
a.   The average entering air dry-                                maintain rated compressor
     bulb temperature to the                                      speed.
     Condenser shall not vary from
     the specified values by more     C6.3    Method for Simulating Fouling Factor
     than 1.0°F [0.6°C].              Allowance at Full Load and Part-Load Conditions.
b.   For heat reclaim Air-Cooled
     Condensers the Condenser air             C6.3.1 Obtain the log mean temperature
     flow rate shall not deviate              difference (LMTD) for the evaporator
     from that required for test by           and/or Condenser using the following
     more than + 5%.                          equation at the specified Fouling Factor
                                              Allowance (ffsp).
C6.2.1.4 Evaporatively-Cooled
Condenser.                                                       R
                                              LMTD =
                                                                R                             C1
a.   The entering air wet-bulb                              ln 1 + 
                                                                  S
     temperature shall not vary
     from the values required for
     test by more than 0.5°F                  R = Water temperature range
     [0.3°C].                                   = absolute value (twl - twe), °F[°C]

C6.2.1.5 Chiller          Without             S = Small temperature difference
Condenser.                                      = absolute value (ts - twl), °F [°C]

a.   The saturated discharge                  C6.3.2 Derivation of LMTD:
     temperature shall not vary
     from the values required for                               (t s − t we ) − (t s − t w1 )
                                                LMTD =
     test by more than 0.5°F                                             t − t we 
     [0.3°C].                                                        ln  s          
b.   The      liquid   refrigerant                                       t s − t w1 
     temperature shall not vary
     from the specified values by                           (t w1 − t we )
                                                =
     more than 1.0°F [0.6°C].                          (t − t ) + (t − t ) 
                                                          s    w1      w1  we
                                                    ln                                   
                                                                   t s − t w1            
C6.2.1.6     Miscellaneous.                                                              

a.   For      electrically   driven           The Incremental LMTD (ILMTD) is
     machines,       voltage    and           determined using the following equation:
     frequency at the unit
     terminals shall be maintained                             q
     at the nameplate values within             ILMTD = ff sp ( )                                C2
                                                               A
     tolerances of + 10% on
     voltage and + 1% on
     frequency.
b.   For steam-turbine driven
     machines, steam conditions to
                                                                                                19
ARI STANDARD 550/590- 2003

           C6.3.3 The water temperature needed to
           simulate the additional fouling, TDa, can                         ffsp = 0.00025
           now be calculated:                                                           q
                                                                         ILMTD = ff sp ( )
            TDa = Ssp - Sc                              C3a                             A
                                                                                    2,880,000 
                                                                       = 0.00025
                         R                                                          550 
                                                                                              
            TDa = S sp - z                              C3b
                        e -1                                           = 1.31

           where:                                                                    R
                                                                          TD = Ssp - z
                                                                            a       e -1
                     R
            Z=
                LMTD - ILMTD
                                                                     where:
                  R
            Sc = z
                e −1                                                                  R
                                                                         Z=
           Ssp = Small temperature difference as                               LMTD - ILMTD
                 specified, °F [°C]
           Sc = Small temperature difference as                                  10
                 tested in cleaned condition, °F[°C]                    Z=                  = 1.125
                                                                              10.2 - 1.31
           The water temperature difference, TDa, is                                  10
                                                                         TD = 6.0 - 1.125
           then added to the Condenser entering water                      a              -1
                                                                                   e
           temperature or subtracted from the
                                                                                = 6.0 - 4.8 = 1.2°F
           evaporator leaving water temperature to
           simulate the additional Fouling Factor.
                                                                     The entering Condenser water temperature
                                                                     for testing is then raised 1.2°F to simulate
           C6.3.4 Example-Condenser             Fouling
           Inside Tubes (in I.P Units for clarity):                  the Fouling Factor Allowance of 0.00025 h ⋅
                                                                     ft2 ⋅ °F/Btu. The entering condenser water
           Specified Fouling Factor Allowance,                       temperature will be 85 + 1.2 or 86.2°F.
           ffsp =0.00025 h ⋅ ft2 ⋅°F/Btu
           Condenser load, q = 2,880,000 Btu/h                C6.4   Test Verification:

           Specified Condenser leaving water temp,                   C6.4.1 Heat Balance-Substantiating Test.
           Twl = 95°F
                                                                                C6.4.1.1 Calculation of Heat
           Specified Condenser entering water temp,                             Balance. In most cases, heat
           Twe = 85 °F                                                          losses or heat gain caused by
                                                                                radiation, convection, bearing
           Inside* tube surface area, Ai = 550 ft2                              friction, oil coolers, etc., are
                                                                                relatively small and may or may
           *(Since fouling is inside tubes in this                              not be considered in the overall
           example)                                                             heat balance.

           Saturated condensing temperature,                                    Omitting the effect of the small
                                                                                heat losses and gains mentioned
           ts = 101 °F
                                                                                above, the general heat balance
                                                                                equation is as follows:
                     Ssp = ts - twl = 101 - 95 = 6 °F
                                                                                qev + Winput = qcd + qhrc
                     R = twl - twe = 95 - 85 = 10 °F

                                 R
               LMTD =
                           ln (1 + R/S)
                        10
               =                 = 10.2
                   ln (1 + 10/6)
20
ARI STANDARD 550/590-2003

 where:                                                      manufacturer's certified power
                                                             input/output data shall be used.
 Winput = compressor work input
 as defined in C6.4.1.2 through                              In the case of motor drive:
 C6.4.1.4
                                                             Winput = power measured at
 C6.4.1.2 In       a   hermetic                              motor terminals plus power to
 package, where the motor is                                 auxiliaries as in C.7.1.4.
 cooled by refrigerant, chilled
 water or condenser water, the                               C6.4.1.5 Percent Heat Balance.
 motor cooling load will be                                  Heat balance, in %, is defined as:
 included in the measured
 condenser load, hence                                        (qev + Winput ) - (qcd + q hrc )
                                                                                                 x 100    C4
                                                                        q cd + q hrc
 Winput = electrical power input
 to the compressor motor, Btu/h
 [kW]                                                        For any test of a liquid cooled
                                                             chiller to be acceptable, the heat
 C6.4.1.3 In a package using an                              balance (%) shall be within the
 open-type compressor with prime                             allowable tolerance calculated per
 mover and external gear drive:                              5.6 for the applicable conditions.

 Winput    = qprime mover -qgear                    C6.4.2 Concurrent            Redundant
                                                    Verification Test for Air-Cooled or
 where:                                             Evaporatively- Cooled Condensers.

 Winput       = Power input to the                           C6.4.2.1 Capacity Calculation
                compressor shaft,                            Method. Calculate the capacity of
                Btu/h [kW]                                   the cooler using one set of
 qprime mover = Power delivered by                           instrumentation. Also calculate
                prime mover, Btu/h                           the capacity of the cooler using the
                [kW]                                         redundant set of instrumentation.
 qgear        = Friction loss in the                         For a valid test, these two
                gear box, Btu/h                              calculated values must agree
                [kW]                                         within the tolerance specified in
                                                             Section 5.6. The tested capacity
The value of qprime mover shall be                           of the machine shall be the
determined from the power input                              average of these two values.
to prime mover using certified data
from     the     prime       mover                           C6.4.2.2 Power Calculation
manufacturer.                                                Method. The power measured by
                                                             the two sets of instruments must
The value of qgear shall be                                  be within 2% at all loads. The
determined from certified gear                               tested power of the machine shall
losses provided by the gear                                  be the average of the two
manufacturer.                                                measured powers.

C6.4.1.4 In a package using an                               C6.4.2.3 Efficiency Calculation
open-type compressor with direct                             Method.    Efficiency shall be
drive and the prime mover not                                calculated using the measured
furnished by the manufacturer:                               (averaged) values and must
                                                             comply within the tolerances of
Winput = power input to the                                  5.6.
compressor shaft, Btu/h [kW]
                                       C7   Calculation of Results
For determination of Winput for
turbine or engine operated                  C7.1    Capacity and Power.
machines, the turbine or engine

                                                                                                     21
Ari 550 590
Ari 550 590
Ari 550 590
Ari 550 590
Ari 550 590
Ari 550 590
Ari 550 590
Ari 550 590
Ari 550 590

More Related Content

What's hot

Boiler calculations
Boiler calculationsBoiler calculations
Boiler calculations
Usman Shahdin
 
Basics of HVAC - Part 1 (Heating Ventilation Air Conditioning)
Basics of HVAC - Part 1 (Heating Ventilation Air Conditioning)Basics of HVAC - Part 1 (Heating Ventilation Air Conditioning)
Basics of HVAC - Part 1 (Heating Ventilation Air Conditioning)
MOHAMMED KHAN
 
BMS Automation wiring
BMS Automation wiringBMS Automation wiring
BMS Automation wiring
GAUTAM KOPPALA (JORGE)
 
Heat Load Calculation
Heat Load CalculationHeat Load Calculation
Heat Load Calculation
ijtsrd
 
Hot Water Vapour Absorption Chiller
Hot Water Vapour Absorption ChillerHot Water Vapour Absorption Chiller
Hot Water Vapour Absorption Chiller
NOVATECH Engineering possibilities
 
VARIABLE REFRIGERATE FLOW
VARIABLE REFRIGERATE FLOWVARIABLE REFRIGERATE FLOW
VARIABLE REFRIGERATE FLOW
RIDDHESH VARIK
 
Air Conditioner
Air ConditionerAir Conditioner
Air Conditioner
Ridwanul Hoque
 
Hvac systems presentation_slides
Hvac systems presentation_slidesHvac systems presentation_slides
Hvac systems presentation_slides
guy ygal
 
Ships air conditioning
Ships air conditioningShips air conditioning
Ships air conditioning
Ahmed Mohamed Ashraf
 
Chilled water systems
Chilled water systemsChilled water systems
Chilled water systems
Jason Abston
 
Hvac formulas
Hvac formulasHvac formulas
Cooling load calculations and principles
Cooling load calculations and principlesCooling load calculations and principles
Cooling load calculations and principlesDheiy Myth
 
Heating & Cooling Loads Calculations and HVAC Equipment Sizing
Heating & Cooling Loads Calculations  and HVAC Equipment SizingHeating & Cooling Loads Calculations  and HVAC Equipment Sizing
Heating & Cooling Loads Calculations and HVAC Equipment Sizing
IES VE
 
Air Conditioning System
Air Conditioning SystemAir Conditioning System
Air Conditioning System
Sumit Ranjan
 
Hvac systems
Hvac systemsHvac systems
Hvac systems
Husain Baqer
 
VRF system presentation !
VRF system presentation !VRF system presentation !
VRF system presentation !
Mohamed Sharbudeen Ayub
 
N atural cooling tower
N atural cooling towerN atural cooling tower
N atural cooling tower
Abdullah Mansoor
 
Energy audit of Condenser and CW System
Energy audit of Condenser and CW SystemEnergy audit of Condenser and CW System
Energy audit of Condenser and CW System
Manohar Tatwawadi
 

What's hot (20)

Cooling Load Calculation
Cooling Load CalculationCooling Load Calculation
Cooling Load Calculation
 
Boiler calculations
Boiler calculationsBoiler calculations
Boiler calculations
 
Basics of HVAC - Part 1 (Heating Ventilation Air Conditioning)
Basics of HVAC - Part 1 (Heating Ventilation Air Conditioning)Basics of HVAC - Part 1 (Heating Ventilation Air Conditioning)
Basics of HVAC - Part 1 (Heating Ventilation Air Conditioning)
 
BMS Automation wiring
BMS Automation wiringBMS Automation wiring
BMS Automation wiring
 
Heat Load Calculation
Heat Load CalculationHeat Load Calculation
Heat Load Calculation
 
Hot Water Vapour Absorption Chiller
Hot Water Vapour Absorption ChillerHot Water Vapour Absorption Chiller
Hot Water Vapour Absorption Chiller
 
VARIABLE REFRIGERATE FLOW
VARIABLE REFRIGERATE FLOWVARIABLE REFRIGERATE FLOW
VARIABLE REFRIGERATE FLOW
 
Air Conditioner
Air ConditionerAir Conditioner
Air Conditioner
 
HVAC Sysems & AHU
HVAC Sysems & AHUHVAC Sysems & AHU
HVAC Sysems & AHU
 
Hvac systems presentation_slides
Hvac systems presentation_slidesHvac systems presentation_slides
Hvac systems presentation_slides
 
Ships air conditioning
Ships air conditioningShips air conditioning
Ships air conditioning
 
Chilled water systems
Chilled water systemsChilled water systems
Chilled water systems
 
Hvac formulas
Hvac formulasHvac formulas
Hvac formulas
 
Cooling load calculations and principles
Cooling load calculations and principlesCooling load calculations and principles
Cooling load calculations and principles
 
Heating & Cooling Loads Calculations and HVAC Equipment Sizing
Heating & Cooling Loads Calculations  and HVAC Equipment SizingHeating & Cooling Loads Calculations  and HVAC Equipment Sizing
Heating & Cooling Loads Calculations and HVAC Equipment Sizing
 
Air Conditioning System
Air Conditioning SystemAir Conditioning System
Air Conditioning System
 
Hvac systems
Hvac systemsHvac systems
Hvac systems
 
VRF system presentation !
VRF system presentation !VRF system presentation !
VRF system presentation !
 
N atural cooling tower
N atural cooling towerN atural cooling tower
N atural cooling tower
 
Energy audit of Condenser and CW System
Energy audit of Condenser and CW SystemEnergy audit of Condenser and CW System
Energy audit of Condenser and CW System
 

Similar to Ari 550 590

2 twb0 10 seer monofasica heat pump 1 a 5 tr
2 twb0  10 seer monofasica heat pump   1 a 5 tr2 twb0  10 seer monofasica heat pump   1 a 5 tr
2 twb0 10 seer monofasica heat pump 1 a 5 tr
ssuser776e17
 
720 1500 kva
720 1500 kva720 1500 kva
720 1500 kva
MY SOFTIT
 
Technical guide yc yd pc pd nc nd 090 thru 300 predator r410 a ..
Technical guide  yc  yd  pc  pd  nc  nd 090  thru 300  predator  r410 a  .. Technical guide  yc  yd  pc  pd  nc  nd 090  thru 300  predator  r410 a  ..
Technical guide yc yd pc pd nc nd 090 thru 300 predator r410 a ..
Oscar044
 
Lvped318033 en 2018
Lvped318033 en 2018Lvped318033 en 2018
Lvped318033 en 2018
Fane Pelin
 
Catalogo Air Cooled Scroll Chiller LG.pdf
Catalogo Air Cooled Scroll Chiller LG.pdfCatalogo Air Cooled Scroll Chiller LG.pdf
Catalogo Air Cooled Scroll Chiller LG.pdf
KarenGrau3
 
Certif vitosol 100 f sv1 sh1
Certif vitosol 100 f sv1 sh1Certif vitosol 100 f sv1 sh1
Certif vitosol 100 f sv1 sh1zouloumango
 
65083H
65083H65083H
65083
6508365083
Semicondcutor fuse catalogues
Semicondcutor fuse cataloguesSemicondcutor fuse catalogues
Semicondcutor fuse cataloguesdhanasekarram
 
Configured Water Cooled Screw Chiller Presentation rev 01.ppt
Configured Water Cooled Screw Chiller Presentation rev 01.pptConfigured Water Cooled Screw Chiller Presentation rev 01.ppt
Configured Water Cooled Screw Chiller Presentation rev 01.ppt
AmitVerma364544
 
Legend Power Overview 97 2003 120410 1256 Do
Legend Power   Overview 97 2003 120410 1256 DoLegend Power   Overview 97 2003 120410 1256 Do
Legend Power Overview 97 2003 120410 1256 DoLegend Power
 
dclc-r134a-968 detail.pdf
dclc-r134a-968 detail.pdfdclc-r134a-968 detail.pdf
dclc-r134a-968 detail.pdf
bui thequan
 
Starter Generator - from ePropelled
Starter Generator - from ePropelledStarter Generator - from ePropelled
Starter Generator - from ePropelled
Lakshmi Narsimhan
 
5128A RHapid-Cal Humidity Generator Brochure
5128A RHapid-Cal Humidity Generator Brochure5128A RHapid-Cal Humidity Generator Brochure
5128A RHapid-Cal Humidity Generator Brochure
PT. Siwali Swantika
 
Zhl 10 w-2g+-2_7_8.45
Zhl 10 w-2g+-2_7_8.45Zhl 10 w-2g+-2_7_8.45
Zhl 10 w-2g+-2_7_8.45
Dian Amalia
 
65023
6502365023
High Capacity Chillers 97
High Capacity Chillers 97High Capacity Chillers 97
High Capacity Chillers 97psighi
 
60051
6005160051

Similar to Ari 550 590 (20)

2 twb0 10 seer monofasica heat pump 1 a 5 tr
2 twb0  10 seer monofasica heat pump   1 a 5 tr2 twb0  10 seer monofasica heat pump   1 a 5 tr
2 twb0 10 seer monofasica heat pump 1 a 5 tr
 
720 1500 kva
720 1500 kva720 1500 kva
720 1500 kva
 
Technical guide yc yd pc pd nc nd 090 thru 300 predator r410 a ..
Technical guide  yc  yd  pc  pd  nc  nd 090  thru 300  predator  r410 a  .. Technical guide  yc  yd  pc  pd  nc  nd 090  thru 300  predator  r410 a  ..
Technical guide yc yd pc pd nc nd 090 thru 300 predator r410 a ..
 
Lvped318033 en 2018
Lvped318033 en 2018Lvped318033 en 2018
Lvped318033 en 2018
 
Catalogo Air Cooled Scroll Chiller LG.pdf
Catalogo Air Cooled Scroll Chiller LG.pdfCatalogo Air Cooled Scroll Chiller LG.pdf
Catalogo Air Cooled Scroll Chiller LG.pdf
 
Certif vitosol 100 f sv1 sh1
Certif vitosol 100 f sv1 sh1Certif vitosol 100 f sv1 sh1
Certif vitosol 100 f sv1 sh1
 
BE_YK_EngineeringGuide_G
BE_YK_EngineeringGuide_GBE_YK_EngineeringGuide_G
BE_YK_EngineeringGuide_G
 
65083H
65083H65083H
65083H
 
Super critical boiler
Super critical boilerSuper critical boiler
Super critical boiler
 
65083
6508365083
65083
 
Semicondcutor fuse catalogues
Semicondcutor fuse cataloguesSemicondcutor fuse catalogues
Semicondcutor fuse catalogues
 
Configured Water Cooled Screw Chiller Presentation rev 01.ppt
Configured Water Cooled Screw Chiller Presentation rev 01.pptConfigured Water Cooled Screw Chiller Presentation rev 01.ppt
Configured Water Cooled Screw Chiller Presentation rev 01.ppt
 
Legend Power Overview 97 2003 120410 1256 Do
Legend Power   Overview 97 2003 120410 1256 DoLegend Power   Overview 97 2003 120410 1256 Do
Legend Power Overview 97 2003 120410 1256 Do
 
dclc-r134a-968 detail.pdf
dclc-r134a-968 detail.pdfdclc-r134a-968 detail.pdf
dclc-r134a-968 detail.pdf
 
Starter Generator - from ePropelled
Starter Generator - from ePropelledStarter Generator - from ePropelled
Starter Generator - from ePropelled
 
5128A RHapid-Cal Humidity Generator Brochure
5128A RHapid-Cal Humidity Generator Brochure5128A RHapid-Cal Humidity Generator Brochure
5128A RHapid-Cal Humidity Generator Brochure
 
Zhl 10 w-2g+-2_7_8.45
Zhl 10 w-2g+-2_7_8.45Zhl 10 w-2g+-2_7_8.45
Zhl 10 w-2g+-2_7_8.45
 
65023
6502365023
65023
 
High Capacity Chillers 97
High Capacity Chillers 97High Capacity Chillers 97
High Capacity Chillers 97
 
60051
6005160051
60051
 

Recently uploaded

一比一原版(BU毕业证书)伯恩茅斯大学毕业证成绩单如何办理
一比一原版(BU毕业证书)伯恩茅斯大学毕业证成绩单如何办理一比一原版(BU毕业证书)伯恩茅斯大学毕业证成绩单如何办理
一比一原版(BU毕业证书)伯恩茅斯大学毕业证成绩单如何办理
h7j5io0
 
一比一原版(LSE毕业证书)伦敦政治经济学院毕业证成绩单如何办理
一比一原版(LSE毕业证书)伦敦政治经济学院毕业证成绩单如何办理一比一原版(LSE毕业证书)伦敦政治经济学院毕业证成绩单如何办理
一比一原版(LSE毕业证书)伦敦政治经济学院毕业证成绩单如何办理
jyz59f4j
 
一比一原版(RHUL毕业证书)伦敦大学皇家霍洛威学院毕业证如何办理
一比一原版(RHUL毕业证书)伦敦大学皇家霍洛威学院毕业证如何办理一比一原版(RHUL毕业证书)伦敦大学皇家霍洛威学院毕业证如何办理
一比一原版(RHUL毕业证书)伦敦大学皇家霍洛威学院毕业证如何办理
9a93xvy
 
7 Alternatives to Bullet Points in PowerPoint
7 Alternatives to Bullet Points in PowerPoint7 Alternatives to Bullet Points in PowerPoint
7 Alternatives to Bullet Points in PowerPoint
Alvis Oh
 
Top Israeli Products and Brands - Plan it israel.pdf
Top Israeli Products and Brands - Plan it israel.pdfTop Israeli Products and Brands - Plan it israel.pdf
Top Israeli Products and Brands - Plan it israel.pdf
PlanitIsrael
 
Let's Summon Demons Shirt Let's Summon Demons Shirt
Let's Summon Demons Shirt Let's Summon Demons ShirtLet's Summon Demons Shirt Let's Summon Demons Shirt
Let's Summon Demons Shirt Let's Summon Demons Shirt
TeeFusion
 
Portfolio.pdf
Portfolio.pdfPortfolio.pdf
Portfolio.pdf
garcese
 
一比一原版(UNUK毕业证书)诺丁汉大学毕业证如何办理
一比一原版(UNUK毕业证书)诺丁汉大学毕业证如何办理一比一原版(UNUK毕业证书)诺丁汉大学毕业证如何办理
一比一原版(UNUK毕业证书)诺丁汉大学毕业证如何办理
7sd8fier
 
vernacular architecture in response to climate.pdf
vernacular architecture in response to climate.pdfvernacular architecture in response to climate.pdf
vernacular architecture in response to climate.pdf
PrabhjeetSingh219035
 
原版定做(penn毕业证书)美国宾夕法尼亚大学毕业证文凭学历证书原版一模一样
原版定做(penn毕业证书)美国宾夕法尼亚大学毕业证文凭学历证书原版一模一样原版定做(penn毕业证书)美国宾夕法尼亚大学毕业证文凭学历证书原版一模一样
原版定做(penn毕业证书)美国宾夕法尼亚大学毕业证文凭学历证书原版一模一样
gpffo76j
 
一比一原版(UCB毕业证书)伯明翰大学学院毕业证成绩单如何办理
一比一原版(UCB毕业证书)伯明翰大学学院毕业证成绩单如何办理一比一原版(UCB毕业证书)伯明翰大学学院毕业证成绩单如何办理
一比一原版(UCB毕业证书)伯明翰大学学院毕业证成绩单如何办理
h7j5io0
 
Design Thinking Design thinking Design thinking
Design Thinking Design thinking Design thinkingDesign Thinking Design thinking Design thinking
Design Thinking Design thinking Design thinking
cy0krjxt
 
Design Thinking Design thinking Design thinking
Design Thinking Design thinking Design thinkingDesign Thinking Design thinking Design thinking
Design Thinking Design thinking Design thinking
cy0krjxt
 
一比一原版(MMU毕业证书)曼彻斯特城市大学毕业证成绩单如何办理
一比一原版(MMU毕业证书)曼彻斯特城市大学毕业证成绩单如何办理一比一原版(MMU毕业证书)曼彻斯特城市大学毕业证成绩单如何办理
一比一原版(MMU毕业证书)曼彻斯特城市大学毕业证成绩单如何办理
7sd8fier
 
Transforming Brand Perception and Boosting Profitability
Transforming Brand Perception and Boosting ProfitabilityTransforming Brand Perception and Boosting Profitability
Transforming Brand Perception and Boosting Profitability
aaryangarg12
 
一比一原版(Glasgow毕业证书)格拉斯哥大学毕业证成绩单如何办理
一比一原版(Glasgow毕业证书)格拉斯哥大学毕业证成绩单如何办理一比一原版(Glasgow毕业证书)格拉斯哥大学毕业证成绩单如何办理
一比一原版(Glasgow毕业证书)格拉斯哥大学毕业证成绩单如何办理
n0tivyq
 
Research 20 slides Amelia gavryliuks.pdf
Research 20 slides Amelia gavryliuks.pdfResearch 20 slides Amelia gavryliuks.pdf
Research 20 slides Amelia gavryliuks.pdf
ameli25062005
 
Exploring the Future of Smart Garages.pdf
Exploring the Future of Smart Garages.pdfExploring the Future of Smart Garages.pdf
Exploring the Future of Smart Garages.pdf
fastfixgaragedoor
 
一比一原版(毕业证)长崎大学毕业证成绩单如何办理
一比一原版(毕业证)长崎大学毕业证成绩单如何办理一比一原版(毕业证)长崎大学毕业证成绩单如何办理
一比一原版(毕业证)长崎大学毕业证成绩单如何办理
taqyed
 
Between Filth and Fortune- Urban Cattle Foraging Realities by Devi S Nair, An...
Between Filth and Fortune- Urban Cattle Foraging Realities by Devi S Nair, An...Between Filth and Fortune- Urban Cattle Foraging Realities by Devi S Nair, An...
Between Filth and Fortune- Urban Cattle Foraging Realities by Devi S Nair, An...
Mansi Shah
 

Recently uploaded (20)

一比一原版(BU毕业证书)伯恩茅斯大学毕业证成绩单如何办理
一比一原版(BU毕业证书)伯恩茅斯大学毕业证成绩单如何办理一比一原版(BU毕业证书)伯恩茅斯大学毕业证成绩单如何办理
一比一原版(BU毕业证书)伯恩茅斯大学毕业证成绩单如何办理
 
一比一原版(LSE毕业证书)伦敦政治经济学院毕业证成绩单如何办理
一比一原版(LSE毕业证书)伦敦政治经济学院毕业证成绩单如何办理一比一原版(LSE毕业证书)伦敦政治经济学院毕业证成绩单如何办理
一比一原版(LSE毕业证书)伦敦政治经济学院毕业证成绩单如何办理
 
一比一原版(RHUL毕业证书)伦敦大学皇家霍洛威学院毕业证如何办理
一比一原版(RHUL毕业证书)伦敦大学皇家霍洛威学院毕业证如何办理一比一原版(RHUL毕业证书)伦敦大学皇家霍洛威学院毕业证如何办理
一比一原版(RHUL毕业证书)伦敦大学皇家霍洛威学院毕业证如何办理
 
7 Alternatives to Bullet Points in PowerPoint
7 Alternatives to Bullet Points in PowerPoint7 Alternatives to Bullet Points in PowerPoint
7 Alternatives to Bullet Points in PowerPoint
 
Top Israeli Products and Brands - Plan it israel.pdf
Top Israeli Products and Brands - Plan it israel.pdfTop Israeli Products and Brands - Plan it israel.pdf
Top Israeli Products and Brands - Plan it israel.pdf
 
Let's Summon Demons Shirt Let's Summon Demons Shirt
Let's Summon Demons Shirt Let's Summon Demons ShirtLet's Summon Demons Shirt Let's Summon Demons Shirt
Let's Summon Demons Shirt Let's Summon Demons Shirt
 
Portfolio.pdf
Portfolio.pdfPortfolio.pdf
Portfolio.pdf
 
一比一原版(UNUK毕业证书)诺丁汉大学毕业证如何办理
一比一原版(UNUK毕业证书)诺丁汉大学毕业证如何办理一比一原版(UNUK毕业证书)诺丁汉大学毕业证如何办理
一比一原版(UNUK毕业证书)诺丁汉大学毕业证如何办理
 
vernacular architecture in response to climate.pdf
vernacular architecture in response to climate.pdfvernacular architecture in response to climate.pdf
vernacular architecture in response to climate.pdf
 
原版定做(penn毕业证书)美国宾夕法尼亚大学毕业证文凭学历证书原版一模一样
原版定做(penn毕业证书)美国宾夕法尼亚大学毕业证文凭学历证书原版一模一样原版定做(penn毕业证书)美国宾夕法尼亚大学毕业证文凭学历证书原版一模一样
原版定做(penn毕业证书)美国宾夕法尼亚大学毕业证文凭学历证书原版一模一样
 
一比一原版(UCB毕业证书)伯明翰大学学院毕业证成绩单如何办理
一比一原版(UCB毕业证书)伯明翰大学学院毕业证成绩单如何办理一比一原版(UCB毕业证书)伯明翰大学学院毕业证成绩单如何办理
一比一原版(UCB毕业证书)伯明翰大学学院毕业证成绩单如何办理
 
Design Thinking Design thinking Design thinking
Design Thinking Design thinking Design thinkingDesign Thinking Design thinking Design thinking
Design Thinking Design thinking Design thinking
 
Design Thinking Design thinking Design thinking
Design Thinking Design thinking Design thinkingDesign Thinking Design thinking Design thinking
Design Thinking Design thinking Design thinking
 
一比一原版(MMU毕业证书)曼彻斯特城市大学毕业证成绩单如何办理
一比一原版(MMU毕业证书)曼彻斯特城市大学毕业证成绩单如何办理一比一原版(MMU毕业证书)曼彻斯特城市大学毕业证成绩单如何办理
一比一原版(MMU毕业证书)曼彻斯特城市大学毕业证成绩单如何办理
 
Transforming Brand Perception and Boosting Profitability
Transforming Brand Perception and Boosting ProfitabilityTransforming Brand Perception and Boosting Profitability
Transforming Brand Perception and Boosting Profitability
 
一比一原版(Glasgow毕业证书)格拉斯哥大学毕业证成绩单如何办理
一比一原版(Glasgow毕业证书)格拉斯哥大学毕业证成绩单如何办理一比一原版(Glasgow毕业证书)格拉斯哥大学毕业证成绩单如何办理
一比一原版(Glasgow毕业证书)格拉斯哥大学毕业证成绩单如何办理
 
Research 20 slides Amelia gavryliuks.pdf
Research 20 slides Amelia gavryliuks.pdfResearch 20 slides Amelia gavryliuks.pdf
Research 20 slides Amelia gavryliuks.pdf
 
Exploring the Future of Smart Garages.pdf
Exploring the Future of Smart Garages.pdfExploring the Future of Smart Garages.pdf
Exploring the Future of Smart Garages.pdf
 
一比一原版(毕业证)长崎大学毕业证成绩单如何办理
一比一原版(毕业证)长崎大学毕业证成绩单如何办理一比一原版(毕业证)长崎大学毕业证成绩单如何办理
一比一原版(毕业证)长崎大学毕业证成绩单如何办理
 
Between Filth and Fortune- Urban Cattle Foraging Realities by Devi S Nair, An...
Between Filth and Fortune- Urban Cattle Foraging Realities by Devi S Nair, An...Between Filth and Fortune- Urban Cattle Foraging Realities by Devi S Nair, An...
Between Filth and Fortune- Urban Cattle Foraging Realities by Devi S Nair, An...
 

Ari 550 590

  • 1. 2003 STANDARD for PERFORMANCE RATING OF WATER - CHILLING PACKAGES USING THE VAPOR COMPRESSION CYCLE Standard 550/590 4100 N. FAIRFAX DR., SUITE 200 • ARLINGTON, VIRGINIA 22203
  • 2. IMPORTANT SAFETY DISCLAIMER ARI does not set safety standards and does not certify or guarantee the safety of any products, components or systems designed, tested, rated, installed or operated in accordance with this standard/guideline. It is strongly recommended that products be designed, constructed, assembled, installed and operated in accordance with nationally recognized safety standards and code requirements appropriate for products covered by this standard/guideline. ARI uses its best efforts to develop standards/guidelines employing state-of-the-art and accepted industry practices. ARI does not certify or guarantee that any tests conducted under its standards/guidelines will be non-hazardous or free from risk. ARI CERTIFICATION PROGRAM PROVISIONS Scope of the Certification Program 60 Hz Power Included in Certification Program Water-Cooled Air-Cooled All compressor types All compressor types Rated up to 2000 tons [7034 kW] at ARI Standard Rating Rated up to 200 tons [ 703 kW] at ARI Standard Rating Conditions Conditions Hermetic & open type, electric motor driven Hermetic & open type, electric motor driven Voltages up to 5000 volts Voltages up to 600 volts Excluded from Certification Program Water-Cooled Air-Cooled Condenserless chillers Condenserless chillers Evaporatively cooled chillers Evaporatively cooled chillers Chillers above 2000 tons [7034 kW] Chillers above 200 tons [703 kW] Chillers with voltages above 5000 volts Chillers with voltages above 600 volts Chillers powered by other than electric motor drives Chillers powered by other than electric motor drives Chillers with motors not supplied with the unit by Secondary coolant ratings (other than water) The manufacturer Free cooling Secondary coolant ratings (other than water) Heat recovery & heat pump ratings Free cooling Heat recovery & heat pump ratings Price $10.00 (M) $20.00 (NM) Copyright 2003, by Air-Conditioning and Refrigeration Institute Printed in U.S.A. Registered United States Patent and Trademark Office
  • 3. ARI CERTIFICATION PROGRAM PROVISIONS (CONTINUED) Scope of the Certification Program (Continued) 50 Hz Power Included in Certification Program Water-Cooled Air-Cooled Centrifugal & screw chillers with continuous unloading Rated 200 - 1000 tons [703-3517 kW] at ARI Standard Rating Conditions Hermetic & open type, electric motor driven Not applicable Voltages up to 5000 volts Excluded from Certification Program Water-Cooled Air-Cooled Scroll & reciprocating compressor chillers with step unloading Condenserless chillers Evaporatively cooled chillers Not applicable Chillers below 200 tons [703 kW] Chillers above 1000 tons [3517 kW] Chillers with voltages above 5000 volts Chillers powered by other than electric motor drives Chillers with motors not supplied with the unit by The manufacturer Secondary coolant ratings (other than water) Free cooling Heat recovery & heat pump ratings
  • 4. Certified Ratings The Certification Program ratings verified by test are: 1. Capacity, tons [kW] 2. Energy Efficiency, as applicable: • Power Input per Capacity, kW/ton [kW/kW] • Energy Efficiency Ratio (EER), Btu/(W⋅h) • Coefficient of Performance (COP), watts/watt [W/W] 3. Water pressure drop, psi or ft H2O [kPa] 4. Integrated Part-Load Value (IPLV) (Section 5.4.1) 5. Non-Standard Part-Load Value (NPLV) (Section 5.4.1) Items 1- 5 are at Standard Rating Conditions (Section 5.2) and at non-standard Rating Conditions (Section 5.3) for both full and part load (Section 5.4 for part-load performance requirements). Note: This standard supersedes ARI Standard 550/590-98 with addenda.
  • 5. TABLE OF CONTENTS SECTION PAGE Section 1. Purpose ..............................................................................................................................1 Section 2. Scope .................................................................................................................................1 Section 3. Definitions .........................................................................................................................1 Section 4. Test Requirements .............................................................................................................2 Section 5. Rating Requirements .........................................................................................................3 Section 6. Minimum Data Requirements for Published Ratings......................................................12 Section 7. Marking and Nameplate Data..........................................................................................13 Section 8. Conformance Conditions ...............................................................................................13 TABLES Table 1. Standard Rating Conditions...............................................................................................4 Table 2. Heat Reclaim Standard Rating Conditions........................................................................5 Table 3. Part-Load Conditions for Rating .......................................................................................6 FIGURES Figure 1. Part-Load Efficiency Curve...............................................................................................7 Figure 2. Air-Cooled Condenser Entering Air Temperature vs. % Load .........................................9 Figure 3. Allowable Tolerance Curves for Full and Part Load ........................................................9 Figure 4. IPLV and NPLV Tolerance Curve .................................................................................11 APPENDICES Appendix A. References - Normative...................................................................................................14 Appendix B. References - Informative .................................................................................................14 Appendix C. Method of Testing Water Chilling Packages Using the Vapor Compression Cycle - Normative..........................................15 Appendix D. Derivation of Integrated Part-Load Value (IPLV) - Normative......................................24
  • 6. TABLES FOR APPENDICES Table D1. Group 1 Air-Cooled IPLV Data and Calculation ............................................................28 Table D2. Group 1 Water-Cooled IPLV Data and Calculation........................................................29 Table D3. Group 1 - 4 IPLV Summary ............................................................................................30 FIGURES FOR APPENDICES Figure D1. Ton-Hour Distribution Categories...................................................................................25 Figure D2. Bin Groupings – Ton-Hours............................................................................................26 Figure D3. Group 1 Ton-Hour Distribution Categories ....................................................................26 Figure D4. Group 2 Ton-Hour Distribution Categories ....................................................................26
  • 7. ARI STANDARD 550/590-2003 PERFORMANCE RATING OF WATER-CHILLING PACKAGES USING THE VAPOR COMPRESSION CYCLE Section 1. Purpose 3.3 Condenser. A refrigeration system component which condenses refrigerant vapor. Desuperheating and sub- 1.1 Purpose. The purpose of this standard is to establish cooling of the refrigerant may occur as well. for Water-Chilling Packages using the vapor compression cycle: definitions; test requirements; rating requirements; 3.3.1 Air-Cooled Condenser. A component which minimum data requirements for Published Ratings; marking condenses refrigerant vapor by rejecting heat to air and nameplate data; and conformance conditions. mechanically circulated over its heat transfer surface causing a rise in the air temperature. 1.1.1 Intent. This standard is intended for the guidance of the industry, including manufacturers, 3.3.2 Air-Cooled Heat Reclaim Condenser. A engineers, installers, contractors and users. component which condenses refrigerant vapor in the process of rejecting the heat of condensation to air 1.1.2 Review and Amendment. This standard is causing a rise in the air temperature. This Condenser subject to review and amendment as technology may be a separate Condenser the same as or a portion advances. of the Air-Cooled Condenser. 3.3.3 Evaporatively-Cooled Condenser. A Section 2. Scope component which condenses refrigerant vapor by rejecting heat to a water and air mixture mechanically 2.1 Scope. This standard applies to factory-made vapor circulated over its heat transfer surface, causing compression refrigeration Water-Chilling Packages evaporation of the water and an increase in the including one or more hermetic or open drive compressors. enthalpy of the air. These Water-Chilling Packages include: 3.3.4 Water-Cooled Condenser. A component • Water-Cooled, Air-Cooled, or Evaporatively- which utilizes refrigerant-to-water heat transfer Cooled Condensers, means, causing the refrigerant to condense and the • Air-Cooled or Water-Cooled Heat Reclaim water to be heated. Condensers, • Packages supplied without a Condenser. 3.3.5 Water-Cooled Heat Reclaim Condenser. A component which utilizes refrigerant-to-water heat transfer means, causing the refrigerant to condense Section 3. Definitions and the water to be heated. This Condenser may be a separate condenser, the same as, or a portion of the All terms in this document follow the standard industry Water-Cooled Condenser. definitions in the current edition of ASHRAE Terminology of Heating, Ventilation, Air Conditioning and Refrigeration 3.4 Dew Point. Refrigerant vapor saturation temperature unless otherwise defined in this section. at a specified pressure. 3.1 Bubble Point. Refrigerant liquid saturation 3.5 Energy Efficiency. temperature at a specified pressure. 3.5.1 Coefficient of Performance (COP). A ratio 3.2 Compressor Saturated Discharge Temperature. For of the cooling capacity in watts [W] to the Total single component and azeotrope refrigerants, it is the Power Input, in watts [W] at any given set of Rating saturated temperature corresponding to the refrigerant Conditions, expressed in watts/watt [W/W]. pressure at the compressor discharge. For zeotropic refrigerants, it is the arithmetic average of the Dew Point 3.5.2 Energy Efficiency Ratio (EER). A ratio of and Bubble Point temperatures corresponding to refrigerant the cooling capacity in Btu/h [W] to the Total Power pressure at the compressor discharge. It is usually taken at Input in watts [W] at any given set of Rating or immediately downstream of the compressor discharge Conditions, expressed in Btu/(W⋅h). service valve (in either case on the downstream side of the valve seat), where discharge valves are used. 1
  • 8. ARI STANDARD 550/590-2003 3.5.3 Heat Reclaim Coefficient of Performance 3.10.2 Standard Rating. A rating based on tests (COPHR). A ratio of the Net Heat Reclaim Capacity performed at Standard Rating Conditions. (Btu/h) to the Total Power Input to the unit, W converted to Btu/h 3.11 Rating Conditions. Any set of operating conditions under which a single level of performance results and which 3.5.4 Power Input per Capacity. A ratio of the causes only that level of performance to occur. Total Power Input to the unit, in kW to the Net Refrigerating Capacity at any given set of Rating 3.1.1 Standard Rating Conditions. Rating Conditions, expressed in kW/ton [kW/kW]. Conditions used as the basis of comparison for performance characteristics. 3.6 Fouling Factor. The thermal resistance due to fouling accumulated on the heat transfer surface. 3.12 "Shall" or "Should". "Shall" or "should" shall be interpreted as follows: 3.6.1 Fouling Factor Allowance. Provision for anticipated fouling during use specified in 3.12.1 Shall. Where "shall" or "shall not" is used h⋅ft2⋅ºF/Btu [m2⋅ºC/W]. for a provision specified, that provision is mandatory if compliance with the standard is claimed. 3.7 Net Heat Reclaim Capacity. A quantity defined as the mass flow rate of the condenser water multiplied by the 3.12.2 Should, "Should" is used to indicate difference in enthalpy of water entering and leaving the heat provisions which are not mandatory but which are reclaim Condenser, Btu/h [kW]. desirable as good practice. 3.8 Net Refrigeration Capacity. A quantity defined as 3.13 Total Power Input. Power input of all components of the mass flow rate of the evaporator water multiplied by the the unit. difference in enthalpy of water entering and leaving the evaporator, Btu/h or tons [kW]. 3.14 Water-Chilling Package. A factory-made and prefabricated assembly (not necessarily shipped as one 3.9 Part-Load Value (PLV). A single number figure of package) of one or more compressors, Condensers and merit expressing part-load efficiency for equipment on the evaporators, with interconnections and accessories, designed basis of weighted operation at various partial load capacities for the purpose of cooling water. It is a machine specifically for the equipment. designed to make use of a vapor compression refrigeration cycle to remove heat from water and reject the heat to a 3.9.1 Integrated Part-Load Value (IPLV). A cooling medium, usually air or water. The refrigerant single number part-load efficiency figure of merit Condenser may or may not be an integral part of the calculated per the method described in this standard package. at Standard Rating Conditions. 3.14.1 Heat Reclaim Water-Chilling Package. A 3.9.2 Non-Standard Part-Load Value (NPLV). A factory-made package, designed for the purpose of single number part-load efficiency figure of merit chilling water and containing a Condenser for calculated per the method described in this standard reclaiming heat. Where such equipment is provided referenced to conditions other than IPLV conditions. in more than one assembly, the separate assemblies (For units that are not designed to operate at Standard are to be designed to be used together, and the Rating Conditions.) requirements of rating outlined in this standard are based upon the use of matched assemblies. It is a 3.10 Published Ratings. A statement of the assigned package specifically designed to make use of the values of those performance characteristics, under stated refrigerant cycle to remove heat from the refrigerant Rating Conditions, by which a unit may be chosen to fit its and to reject the heat to another fluid (air or water) application. These values apply to all units of like nominal for heating use. Any excess heat may be rejected to size and type (identification) produced by the same another medium, usually air or water. manufacturer. The term Published Rating includes the rating of all performance characteristics shown on the unit or published in specifications, advertising or other literature Section 4. Test Requirements controlled by the manufacturer, at stated Rating Conditions. 4.1 Test Requirements. Ratings shall be established at 3.10.1 Application Rating. A rating based on tests the Rating Conditions specified in Section 5. Ratings shall performed at application Rating Conditions (other be verified by tests conducted in accordance with the test than Standard Rating Conditions). method and procedures described in Appendix C. 2
  • 9. ARI STANDARD 550/590-2003 Section 5. Rating Requirements 5.4.1 Determination of Part- Load Performance. For Water-Chilling Packages covered by this 5.1 Standard Ratings. Standard Ratings for all Water- standard, the IPLV or NPLV shall be calculated as Chilling Packages shall be established at the Standard follows: Rating Conditions specified in 5.2. a. Determine the part-load energy 5.2 Standard Rating Conditions. Water-Chilling efficiency at 100%, 75%, 50%, and Packages shall be rated at conditions specified in Table 1. 25% load points at the conditions Heat Reclaim Water-Chilling Packages shall be rated at specified in Table 3. conditions specified in Table 2 and properly identified as the Heat Reclaim Standard Rating. Standard Ratings shall b. Use the following equation to calculate include a water-side Fouling Factor Allowance of 0.00025 the IPLV or NPLV. h⋅ft2⋅ºF/Btu [0.000044 m2⋅ºC/W] for the Condenser and 0.0001 h⋅ft2 ⋅ºF/Btu [0.000018m2⋅ºC/W] for the evaporator. IPLV or = 0.01A + 0.42B + 0.45C + 0.12D NPLV 1a 5.3 Application Rating Conditions. Application Ratings should include the following range of Rating Conditions or be within the operating limits of the equipment: For COP and EER: All Condenser Types: where: A = COP or EER at 100% Leaving chilled water temperature ......40.0 to 48.0ºF B = COP or EER at 75% [4.4 to 8.9ºC] in increments of 2ºF or less [1ºC or C = COP or EER at 50% less]. D = COP or EER at 25% Water-Cooled Condensers: For kW/ton: Entering condenser water temperature ......65.0 to 105.0ºF [18.3 to 40.6ºC] in increments of 5ºF or less IPLV 1 [3°C or less]. or = 1b NPLV 0.01 + 0.42 + 0.45 + 0.12 Air-Cooled Condensers: A B C D Entering Condenser air dry-bulb temperature ......55.0 to 125.0°F [12.8 to 51.7°C] dry-bulb in increments of 10°F or less [6°C or less]. where: A= kW/Ton at 100% B= kW/Ton at 75% Evaporatively-Cooled Condensers: C= kW/Ton at 50% D= kW/Ton at 25% Entering Condenser air wet-bulb temperature ......50.0 to 80.0°F [10.0 to 26.7°C] wet-bulb in 5.4.1.1 For a derivation of equations 1a increments of 2.5°F or less [1.4°C or less]. and 1b, and an example of an IPLV or NPLV calculation, see Appendix D. The 5.4 Part-Load Rating. Water-Chilling Packages which weighting factors have been based on the are capable of capacity reduction shall be rated at 100% and weighted average of the most common at each step of capacity reduction provided by the building types and operations using average refrigeration system(s) as published by the manufacturer. weather in 29 U.S. cities, with and without Part-load ratings points shall be presented in one or more of airside economizers. the following three ways: a. IPLV- Based on the conditions defined in Table 3. b. NPLV- Based on the conditions defined in Table 3. c. Separate Part-Load Data Point(s) Suitable for Calculating IPLV or NPLV. In addition, other part-load points may also be presented. 3
  • 10. 4 Table 1. Standard Rating Conditions Water-Cooled Evaporatively-Cooled Air-Cooled Condenser Water Entering 85.0 ºF 29.4 ºC Flow Rate 3.0 gpm/ton 0.054 L/s per kW ARI STANDARD 550/590-2003 Condenser Fouling Factor Allowance Water-Side 0.00025 h · ft2 · ºF/Btu 0.000044 m2 · ºC/ W Air-Side 0.0 ft2 · ºF/Btu 0.0 m2 · ºC/W 0.0 h · ft2 · ºF/Btu 0.0 m2 · ºC/W Entering Air Dry-Bulb 95.0 ºF 35.0 ºC Wet-Bulb 75.0 ºF 23.9 ºC Evaporator Water Leaving 44.0 ºF 6.7 ºC 44.0 ºF 6.7 ºC 44.0 ºF 6.7 ºC Flow Rate 2.4 gpm/ton 0.043 L/s per kW 2.4 gpm/ton 0.043 L/s per kW 2.4 gpm/ton 0.043 L/s per kW Evaporator Fouling Factor Allowance Water-Side 0.0001 h · ft2 ºF/Btu 0.000018 m2 · ºC/W 0.0001 h · ft2 ºF/Btu 0.000018 m2 · ºC/W 0.0001 h · ft2 ºF/Btu 0.000018 m2 · ºC/W Without Condenser Saturated Discharge 105.0 ºF 40.6 ºC 105.0 ºF 40.6 ºC 125.0 ºF 51.7 ºC Liquid Refrigerant 98.0 ºF 36.7 ºC 98.0 ºF 36.7 ºC 105.0 ºF 40.6 ºC Barometric Pressure 29.92 in Hg 101.3 kPa 29.92 in Hg 101.3 kPa 29.92 in Hg 101.3 kPa
  • 11. Table 2. Heat Reclaim Standard Rating Conditions Temperature Water-Cooled Evaporatively-Cooled Air-Cooled Condenser Water Entering 75.0 ºF 23.9 ºC Flow rate same as in standard cooling Flow rate same as in standard Flow rate same as in standard Flow Rate ratings cooling ratings cooling ratings Entering Air Dry-Bulb 40.0 ºF 4.4 ºC Wet-Bulb 38.0 ºF 3.3 ºC Evaporator Water Leaving 44.0 ºF 6.7ºC 44.0 ºF 6.7ºC 44.0 ºF 6.7ºC Field Fouling Allowance 0.00025 h · ft2 · ºF/Btu 0.0 h · ft2 · ºF/Btu 0.0 h · ft2 · ºF/Btu Heat Reclaim Condenser 105.0 ºF 40.6 ºC Entering or or 70.0 ºF 21.1ºC 95.0 ºF 35.0 ºC 120.0 ºF 48.9 ºC Leaving or or 95.0 ºF 35.0 ºC 105.0 ºF 40.6 ºC Barometric Pressure 29.92 in Hg 101.3 kPa 29.92 in Hg 101.3 kPa 29.92 in Hg 101.3 kPa ARI STANDARD 550/590-2003 5
  • 12. ARI STANDARD 550/590-2003 Table 3. Part-Load Conditions for Rating IPLV NPLV Evaporator (All Types) 2 2 2 100% load LWT 44.0 ºF 6.7 ºC Selected LWT Selected LWT 0% load LWT 44.0 ºF 6.7 ºC Same as 100% load Same as 100% load 3 3 3 Flow Rate (gpm) 2.4 gpm/ton 0.043 L/s per kW Selected gpm/ton [L/s per kW] F.F.A. 0.0001 h · ft2 · ºF/Btu 0.000018 m2 · ºC/ W As Specified As Specified 1 Water-Cooled Condenser 2 2 2 100% load EWT 85.0ºF 29.4 ºC Selected EWT Selected EWT 4 4 75% load EWT 75.0 ºF 23.9 ºC 4 4 50% load EWT 65.0 ºF 18.3 ºC 4 4 25% load EWT 65.0 ºF 18.3 ºC 0% load EWT 65.0 ºF 18.3 ºC 65.0 ºF 18.3 ºC 3 3 3 Flow rate (gpm) [L/s] 3.0 gpm/ton 0.054 L/s per kW Selected gpm/ton L/s per kW F.F.A. 0.00025 h · ft2 · ºF/Btu 0.000044 m2 · ºC/ W As Specified As Specified 1 Air-Cooled Condenser (Use Figure 2) 100% load EDB 95.0 ºF 35.0 ºC 75% load EDB 80.0 ºF 26.7 ºC 50% load EDB 65.0 ºF 18.3 ºC No Rating Requirements 25% load EDB 55.0 ºF 12.8 ºC 0% load EDB 55.0 ºF 12.8 ºC F.F.A. 0.0 h⋅ft2⋅ºF/Btu 0.0 m2⋅ºC/W 1 Evaporatively-Cooled Condenser 100% load EWB 75.0 ºF 23.9 ºC No Rating Requirements 0% load EWB 50.0 ºF 10.0 ºC F.F.A. 0.0 h⋅ft2⋅ºF/Btu 0.0 m2⋅ºC/W Air-Cooled Without Condenser 100% load SDT 125.0 ºF 51.7 ºC No Rating Requirements 0% load SDT 55.0 ºF 12.8 ºC Water and Evaporatively-Cooled Without Condenser No Rating Requirements 100% load SDT 105.0 ºF 40.6 ºC 0% load SDT 65.0 ºF 18.3 ºC 1 If the unit Manufacturer’s recommended minimum temperatures are greater than those specified in Table 3, then those may be used in lieu of the specified temperatures. 2 Corrected for Fouling Factor Allowance by using the calculation method described in C6.3 3 The flow rates are to be held constant at full load values for all part-load conditions. 4 For part-load entering condenser water temperatures, the temperature should vary linearly from the selected EWT at 100% load to 65.0 ºF at 50% loads, and fixed at 65.0°F for 50% to 0% loads. SDT - saturated discharge temperature LWT - leaving water (liquid) temperature EWT - entering water (liquid) temperature EDB - entering air dry-bulb temperature EWB - entering air wet-bulb temperature F.F.A. - Fouling Factor Allowance 6
  • 13. ARI STANDARD 550/590-2003 5.4.1.2 The IPLV or NPLV rating requires where CD is a degradation factor to that the unit efficiency be determined at account for cycling of the compressor for 100%, 75%, 50% and 25% at the conditions capacities less than the minimum step of as specified in Table 3. If the unit, due to its capacity. CD should be calculated using capacity control logic can not be operated at the following equation: 75%, 50%, or 25% capacity then the unit shall be operated at other load points and the C D = (-0.13 ⋅ LF) + 1.13 75%, 50%, or 25% capacity efficiencies shall be determined by plotting the efficiency where LF is the load factor calculated versus the % load using straight line using the following equation: segments to connect the actual performance points (Figure 1). The 75%, 50%, or 25% % FL load efficiencies shall then be determined ⋅ (Full load unit capacity) from the curve. Extrapolation of data shall LF = 100 not be used. An actual chiller capacity point (Part − load unit capacity) equal to or less than the required rating point must be used to plot the data. For example, if the minimum actual capacity is 33% then where % FL is the % of full load at the curve can be used to determine the 50% standard rating points, i.e. 75%, 50%, and capacity point, but not the 25% capacity 25%. point. Part-Load unit capacity is the measured or calculated unit capacity from which Standard Rating points are determined using the method above. 5.4.1.3 Sample Calculation. The following is an example of an IPLV calculation: Part-Load Values Provided Step Capacity Input EER (tons) (kW) 3 (full) 100.0 92.3 13.00 2 72.1 57.4 15.07 If a unit cannot be unloaded to the 25%, 1* 41.3 31.3 15.83 50%, or 75% capacity point, then the unit shall be run at the minimum step of 1** 41.8 33.3 15.06 unloading at the condenser entering water or * Minimum possible unit capacity at load conditions. air temperature based on Table 3 for 25%, ** Performance at minimum step at 25% load conditions 50% or 75% capacity points as required. The efficiency shall then be determined by using Using the above data the part-load EER value the following equation: can be calculated. Measured Cooling Capacity EER = 2 Part-Load Values Provided C D ⋅ Measured Total Power Input Point Load% Capacity EER (tons) A 100% 100 13.00 B 75% 75 14.85 C 50% 50 15.62 7
  • 14. ARI STANDARD 550/590-2003 Because the unit cannot unload to 25% 5.5.1.2 Evaporator water-side and capacity, the following additional condenser water-side or air-side heat calculations are required to determine point transfer surfaces shall be considered clean “D”, using the minimum capacity data point during testing. Tests will be assumed to listed above that was determined at the reflect Fouling Factors of 0.0 h⋅ft2 °F/Btu minimum step of capacity at the conditions [0.0 m2°C/W]. of a 25% capacity. 5.5.1.3 To determine the capacity of the (0.25) x (100) Water-Chilling Package at the rated LF = = 0.60 fouling conditions, the procedure defined 41.8 in C6.3 shall be used to determine an adjustment for the evaporator and or CD = (-0.13 x 0.60) + 1.13 = 1.05 condenser water temperatures. 41.8 x 12000 Btu 5.6 Tolerances. EER = = 14.35 1.05 x 33.3 x 1000 (W ⋅ h ) 5.6.1 Allowable Tolerances. The allowable test Using the A, B, C and D efficiencies the tolerance on capacity, tons [kW], EER, COP, Power IPLV can then be calculated as follows: Input per Capacity kW/ton [kW/kW] and heat balance shall be determined from the following IPLV (EER) = (0.01 x 13.00) + (0.42 x equation: 14.85) + ( 0.45 x 15.62) + (0.12 x 14.35) Tolerance % =15.12 Btu/(W⋅h) E = 10.5 - (0.07 x % FL) + ( ) 5.5 Fouling Factor Allowances. When ratings are DTFL x % FL published, they shall include those with Fouling Factors as specified in Table 1. Additional ratings, or means of DTFL = Difference between entering and determining those ratings, at other Fouling Factor Allowances leaving chilled water temperature at may also be published. full load, °F [°C] 5.5.1 Method of Establishing Clean and Fouled E = 1500 for IP, [833.3] for SI units Ratings from Laboratory Test Data. See Figure 3 for graphical representation only. 5.5.1.1 A series of tests shall be run in accordance with the method outlined in Appendix C to establish the unit’s performance. 8
  • 16. ARI STANDARD 550/590-2003 5.6.2 Full Load. To comply with this standard, published or reported Net Refrigeration Capacity Rated full load performance shall be based on data obtained in accordance with the provisions of this section, and shall have a Net Rated capacity = 100 tons Refrigeration Capacity and full load efficiency of not Rated power = 70 kW less than 100 % of its ratings within the allowable Cooling DTFL = 10ºF tolerance. The allowable tolerance shall be determined by the equation specified in 5.6.1. kW Total Power Input per Capacity = 0.70 ton Water pressure drop in the evaporator and Condenser shall not exceed 115 % of the rated pressure drop at Allowable Test Tolerance: the specified water flow rate. (1500) Full Load Example in EER (in IP Units only for Tolerance = 10.5 - (.07 x 100) + clarity): (10 x 100) Rated Full Load Performance = 10.5 – 0 7 + 1.5 = 5% Rated Capacity = 100 tons (100 − 5) Rated Power = 92.3 kW Min. allowable capacity = x 100 100 Evaporator DTFL = 10°F = 95 tons 100 tons x 12000 Btu/ton ⋅ h Btu EER = = 13.0 92.3 kW x 1000W/kW (W ⋅ h) (100 + 5) Max. allowable kW / ton = x .70 Allowable Test Tolerance = 100 = .735 kW/ton 1500 10.5 - (0.07 x 100%) + 10 x 100% Max. power at min. capacity = 10.5 - 7 + 1.5 = 5% = .735 x 95 = 69.825 kW Min. Allowable Capacity = 5.6.3 Part-Load. The tolerance on part-load EER shall be the tolerance as determined from 5.6.1. (100 tons − 5 tons ) x 100 = 95 tons 100 Part-Load Example in EER (in IP Units only for clarity): Min. Allowable EER = Rated Part-Load Performance (100 - 5) x 13.0 Btu = 12.35 Btu Power at 69.5% Rated Capacity = 59.6 kW 100 (W ⋅ h) (W ⋅ h) 69.5% Rated Capacity = 69.5 tons Cooling DTFL = 10.0°F Max. power at min. capacity = 69.5 x 12000 Btu EER = = 14.0 95 tons x 12000 Btu/ton ⋅ h 59.6 x 1000 (W ⋅ h) = 92.3 kW Btu 12.35 x 1000 (W ⋅ h) Allowable Test Tolerance = 1500 10.5 − (0.07 ⋅ 69.5%) + 10 x 69.5% Full Load Example in kW/ton (in IP Units only for clarity): = 10.5 - 4.87 + 2.16 = 7.8% 10
  • 17. ARI STANDARD 550/590 2003 Min. Allowable EER = Max. allowable Total Power Input per Ton (100 - 7.8) x 14.0 = 12.91 EER 100 (100 + 10%) = x .70 100 Part-Load Example in kW/ton (in IP Units only for = 0.77 kW/ton clarity): 5.6.4 IPLV and NPLV Tolerances. The allowable Rated Part-Load Performance tolerance on IPLV and NPLV shall be determined by the following equation: 50% capacity = 50 tons 35 50% power = 35 kW Allowable Percent Tolerance = 6.5 + Total Power Input per Ton = 0.70 kW/ton DTFL Full Load DTFL = 10ºF See Figure 4 Allowable Test Performance The single number IPLV or NPLV, calculated for the (1500) part-load conditions, shall not be less than the rated Tolerance = 10.5 - (.07 x 50) + IPLV or NPLV, less the allowable tolerance. 10 x 50 = 10.5 - 3.5 + 3 = 10% 11
  • 18. ARI STANDARD 550/590-2003 Section 6. Minimum Data Requirements for 6.2.2 Water-Cooled Condenser Packages. Published Ratings 6.2.2.1 Condenser water pressure drop 6.1 Minimum Data Requirements for Published Ratings. (inlet to outlet), psi or ft H2O [kPa]. As a minimum, Published Ratings shall include all Standard Ratings. All claims to ratings within the scope of this 6.2.2.2 Any two of the following: standard shall include the statement "Rated in accordance with ARI Standard 550/590." All claims to ratings outside Entering condenser water temperature, ºF the scope of the standard shall include the statement [ºC] "Outside the scope of ARI Standard 550/590." Wherever Leaving condenser water temperature, ºF Application Ratings are published or printed, they shall [ºC] include a statement of the conditions at which the ratings Water temperature rise through the apply. condenser, ºF [ºC] 6.2 Published Ratings. Published Ratings shall state all of 6.2.2.3 Condenser water flow rate, gpm the standard operating conditions and shall include the [L/s]. following. 6.2.2.4 Condenser Fouling Factor, 6.2.1 General. h · ft2 · ºF/Btu [m2 · ºC/ W], as stated in Table 1. 6.2.1.1 Refrigerant designation in accordance with ANSI/ASHRAE Standard 6.2.3 Air-Cooled Condenser Packages. 34. 6.2.3.1 Entering air dry-bulb temperature, 6.2.1.2 Model number designations ºF [ºC] (as stated in Table 1). providing identification of the Water- Chilling Packages to which the ratings shall 6.2.3.2 Power input to fan(s), kW [kW]. apply. 6.2.4 Evaporatively-Cooled Condenser Packages. 6.2.1.3 Net Refrigeration Capacity, tons [kW]. 6.2.4.1 Entering air wet-bulb temperature, ºF [ºC] (as stated in Table 1). 6.2.1.4 Total Power Input to chiller, bhp or kW, as applicable. 6.2.4.2 Power input to fan(s) and pump(s), kW [kW]. 6.2.1.5 Energy Efficiency, expressed as EER, COP or kW/ton. 6.2.4.3 Condenser spray pump power consumption, kW [kW]. 6.2.1.6 Evaporator Fouling Factor, h · ft2 · ºF/Btu [m2 · ºC/ W], as stated in 6.2.4.4 Statement of Condenser Fouling Table 1. Factor Allowance on heat exchanger, h · ft2 · ºF/Btu [m2 · ºC/ W]. 6.2.1.7 Chilled water entering and leaving temperatures, ºF [ºC] (as stated in Table 1), 6.2.5 Packages without Condenser (for use with or leaving water temperature and Remote Condensers). temperature difference, ºF [ºC]. 6.2.5.1 Compressor saturated discharge 6.2.1.8 Evaporator water pressure drop temperature, ºF [ºC] (as stated in Table 1). (inlet to outlet), psi or ft H2O [kPa]. 6.2.5.2 Liquid refrigerant temperature 6.2.1.9 Chilled water flow rate, gpm [L/s]. entering chiller package, ºF [ºC] (as stated in Table 1). 6.2.1.10 Nominal voltage, V, and frequency, Hz, for which ratings are valid. 6.2.5.3 Condenser heat rejection capacity requirements, Btu/h [kW]. 12
  • 19. ARI STANDARD 550/590 2003 6.2.6 Heat Reclaim Condenser(s). b. Model number designation providing complete identification 6.2.6.1 Heat Reclaim Capacity, MBtu/h c. Refrigerant designation (in accordance with [kW]. ANSI/ASHRAE Standard 34 d. Voltage, phase and frequency 6.2.6.2 Water pressure drop, psi or ft H2O [kPa] or air pressure drop, in H2O [kPa]. Nameplate voltages for 60 Hertz systems shall include one or more of the equipment nameplate voltage ratings shown 6.2.6.3 Entering and leaving heat reclaim in Table 1 of ARI Standard 110. Nameplate voltages for 50 Condenser air or water temperatures, ºF [ºC] Hertz systems shall include one or more of the utilization (stated in Table 2). voltages shown in Table 1 of IEC Standard Publication 60038. 6.2.6.4 Heat reclaim Condenser air flow rate, cfm [m3/s] or heat reclaim Condenser Section 8. Conformance Conditions water flow rate, gpm [L/s]. 8.1 Conformance. While conformance with this standard 6.2.6.5 Fouling Factor, h · ft2 · ºF/Btu [m2 is voluntary, Conformance shall not be claimed or implied · ºC/ W], as stated in Table 1 (for water heat for products or equipment within the standard’s Purpose reclaim Condensers only). (Section 1) and Scope (Section 2) unless such product claims meet all of the requirements of the standard and all of the testing and rating requirements are measured and Section 7. Marking and Nameplate Data reported in complete compliance with the standard. Any product that has not met all the requirements of the standard 7.1 Marking and Nameplate Data. As a minimum, the cannot reference, state, or acknowledge the standard in any nameplate shall display the following: written, oral, or electronic communication. a. Manufacturer's name and location 13
  • 20. ARI STANDARD 550/590-2003 APPENDIX A. REFERENCES - NORMATIVE A.1 Listed here are all standards, handbooks and other A1.4 ARI Standard 110-2002, Air-Conditioning publications essential to the formation and implementation and Refrigerating Equipment Nameplate Voltages, of the standards. All references in this appendix are 2002, Air-Conditioning and Refrigeration Institute, considered as part of the standard. 4100 North Fairfax Drive, Suite 200, Arlington, VA 22203, U.S.A. A1.1 ANSI/ASHRAE Standard 30-1995, Method of Testing Liquid Chilling Packages, 1995, A1.5 ASHRAE Terminology of Heating American Society of Heating, Refrigeration, and Air- Ventilation, Air Conditioning and Refrigeration, Conditioning Engineers, Inc. ASHRAE, 25 West Second Edition, 1991, American Society of Heating, 43rd Street, 4th Fl., New York, NY, 10036, Refrigeration, and Air-Conditioning Engineers, Inc. U.S.A./1791 Tullie Circle, N.E., Atlanta, Georgia, ASHRAE, 1791 Tullie Circle, N.E., Atlanta, 30329, U.S.A. Georgia, 30329, U.S.A. A1.2 ANSI/ASHRAE Standard 34-2001 with A1.6 ASME Standard PTC 19.2-1987, Addenda, Number Designation and Safety Instruments and Apparatus, Part 2, Pressure Classification of Refrigerants, 2001, American Measurement, 1987, American Society of Society of Heating, Refrigeration, and Air- Mechanical Engineers. ASME, 345 East 47th Street, Conditioning Engineers, Inc., ASHRAE, 25 West New York, NY 10017, U.S.A. 43rd Street, 4th Fl., New York, NY, 10036, U.S.A./1791 Tullie Circle, N.E., Atlanta, Georgia, A1.7 IEC Standard Publication 60038, IEC 30329, U.S.A. Standard Voltages, 1983, International Electrotechnical Commission, rue de Varembe, P.O. A1.3 ANSI/ASHRAE Standard 41.1-86 (RA Box 131, 1211 Geneva 20, Switzerland. 2001), Measurements Guide - Section on Temperature Measurements, 2001, American Society A1.8 ISA Standard RP31.1, Recommended of Heating, Refrigeration, and Air-Conditioning Practice Specification, Installation, and Calibration Engineers, Inc. ASHRAE, 25 West 43rd Street, 4th of Turbine Flowmeters, 1977, Instrument Society of Fl., New York, NY, 10036, U.S.A./1791 Tullie America, ISA, 67 Alexander Drive, P.O. Box 12277, Circle, N.E., Atlanta, Georgia, 30329, U.S.A. Research Triangle Park, NC 27709, U.S.A. APPENDIX B. REFERENCES - INFORMATIVE None. 14
  • 21. ARI STANDARD 550/590-2003 APPENDIX C. METHOD OF TESTING WATER-CHILLING PACKAGES USING THE VAPOR COMPRESSION CYCLE - NORMATIVE C1. Purpose. The purpose of this appendix is to prescribe C5.1.6 for Water-Cooled Heat Reclaim a method of testing for Water-Chilling Packages using the Condensers and C5.1.7 for Air-Cooled Heat vapor compression cycle and to verify capacity and power Reclaim Condensers. requirements at a specific set of conditions. C3.1.5.1 For Water-Cooled Testing shall occur where instrumentation and load stability Heat Reclaim Condensers, the heat is provided. reclaim capacity shall be determined by obtaining the Testing shall not be conducted in field installations where following data: steady state conditions are difficult to achieve and provisions for measurement are not made. a. Fluid flow rate, gpm [L/s] b. Temperature difference C2. Definitions. Definitions for this appendix are between entering and leaving identical with those in Section 3 of this standard. water °F, [°C] C3. Test Methods. The heat rejected through the heat reclaim Condenser is equal to the C3.1 Test Method. product of the heat reclaim Condenser water flow rate, the C3.1.1 The test will measure net cooling water temperature difference, and capacity (tons of refrigeration) and energy the specific heat of water as requirements, at a specific set of conditions. defined by equation C7. C3.1.2 To confirm that steady-state C3.1.5.2 For Air-Cooled Heat conditions have been established at the Reclaim Condensers, the heat specific set of conditions and within the reclaim capacity shall be tolerances set forth in C6.2.1, three sets of determined by obtaining the data shall be taken, at a minimum of five- following data: minute intervals. To minimize the effects of transient conditions, test readings should be a. Heat Reclaim Condenser air taken as simultaneously as possible. flow rate, standard cfm [m3/s] (for air) C3.1.3 The test shall include a b. Heat reclaim Condenser air measurement of the net heat removed from temperature difference the water as it passes through the evaporator between entering and leaving by determination of the following: air a. Water flow rate, gpm [L/s] The heat rejected through the Air- b. Temperature difference Cooled Heat Reclaim Condenser between entering and leaving is equal to the product of the heat water °F, [°C] reclaim Condenser airflow rate, the air temperature difference, and C3.1.4 The heat removed from the chilled the specific heat of moist air as water is equal to the product of the chilled defined by equation C8. water flow rate, the water temperature difference, and the specific heat of the water C3.1.5.3 The test shall include defined by equation C6. the determination of the compressor power requirement. C3.1.5 If supplied with the Water-Chilling This power shall be determined by Package, the test shall include simultaneous measurement of electrical input to determination of the heat reclaim Condenser the motor drive (see C7.1.4). For capacity by obtaining the data as defined in motors supplied by others, the 15
  • 22. ARI STANDARD 550/590- 2003 determination of compressor shaft C3.2.1 Tests conducted in accordance horsepower input shall be outlined with this standard may require cleaning (in in the test procedure. For Air- accordance with manufacturer's Cooled or Evaporatively-Cooled instructions) of the heat transfer surfaces. Condensers, the test shall include The as tested Fouling Factors shall then be the determination of the assumed to be 0.0 h ⋅ ft2 ⋅ °F/Btu [0.0 m2 ⋅ Condenser fan and Condenser °C/W]. spray pump power requirements. C4 Instrumentation. C3.1.5.4 Non-Electric Drive. Where turbine or engine drive is C4.1 Accuracy of instruments selected shall be in employed, compressor shaft accordance with ANSI/ASHRAE Standard 30. horsepower input shall be determined from steam, gas, or oil C4.2 Temperature measurements shall be made in consumption, at measured supply accordance with ANSI/ASHRAE Standard 41.1. and exhaust conditions and prime mover manufacturer's certified C4.3 Flowmeters shall be constructed and performance data. installed in accordance with the applicable portion of ANSI/ASHRAE Standard 30. Turbine flow meters C3.1.6 Test Verification. may be also used in accordance with ISA Standard RP31.1. C3.1.6.1 For the case of Water- Cooled Condensers, in addition to C4.4 Scales for analog meters shall be such that the determination of net heat readings will be at least one-third of full scale removed and energy input deflection. All instruments, including gauges and required, data shall be taken to thermometers shall be calibrated over the range of prepare a heat balance (C6.4.1) to test readings. substantiate the validity of the test. C4.5 Pressure measurements shall be made in C3.1.6.2 For Air-Cooled and accordance with ASME Power Test Code PTC 19.2. Evaporatively- Cooled Condensers, it is impractical to C5 Measurements. measure heat rejection in a test; therefore, a heat balance cannot be C5.1 Data to be Recorded During the Test. calculated. To verify test accuracy, concurrent redundant C5.1.1 Test Data. Compressor/ instrumentation method (C6.4.2) Evaporator (All Condenser Types): shall be used to measure water temperatures, flow rates, and a. Temperature of water entering power inputs. evaporator, °F [°C] b. Temperature of water leaving C3.1.6.3 For heat reclaim units evaporator, °F [°C] with Air-Cooled Condensers or c. Chilled water flow rates, gpm Water-Cooled Condensers, where [L/s] the capacity is not sufficient to d. Power input to compressor fully condense the refrigerant, the electrical power, kW [kW] concurrent redundant instrumentation methods (C6.4.2) Steam consumption of shall be used. turbine, lb/h [kg/h] C3.1.6.4 For heat reclaim units Steam supply pressure, psig with Water-Cooled Condensers [kPa] that fully condense the refrigerant, the heat balance methods (C6.4.1) Steam supply temperature, ºF shall be used. [ºC] Steam exhaust pressure, psig C3.2 Condition of Heat Transfer Surfaces. or in Hg vac [kPa], or 16
  • 23. ARI STANDARD 550/590-2003 Gas consumption of turbine C5.1.5 Without Condenser. or engine, therms or ft3/h, [m3/s] and calorific value, a. Discharge temperature Btu/ft3, [J/L], or leaving compressor, °F [°C] b. Discharge pressure leaving Fuel consumption of diesel or compressor, psig [kPa] gasoline, gal/h [L/s] and c. Liquid refrigerant temperature calorific value, Btu/gal [J/L] entering the expansion device, °F [°C] e. Evaporator water pressure d. Liquid pressure entering the drop (inlet to outlet), psi or ft expansion device, psig [kPa] H2O [kPa] f. Electrical power input to C5.1.6 Water-Cooled Heat Reclaim controls and auxiliary Condenser. equipment, kW [kW] (if not included in d) a. Temperature of heat reclaim entering Condenser water, °F C5.1.2 Water-Cooled Condenser). [°C] b. Temperature of heat reclaim a. Temperature of water entering leaving Condenser water, °F the Condenser, °F [°C] [°C] b. Temperature of water leaving c. Heat reclaim Condenser water the Condenser, °F [°C] flow rate, gpm [L/s] c. Condenser water flow rate, d. Heat reclaim Condenser water gpm [L/s] pressure drop (inlet to outlet), d. Condenser water pressure psi or ft H2O [kPa] drop (inlet to outlet), psi or ft H2O [kPa] C5.1.7 Air-Cooled Heat Reclaim Condenser. C5.1.3 Air-Cooled Condenser. a. Dry-bulb temperature of air a. Dry-bulb temperature of air entering the heat reclaim entering the Condenser, °F Condenser, °F [°C] [°C] b. Dry-bulb temperature of air b. Condenser fan motor power leaving the heat reclaim consumption, kW [kW] Condenser, °F [°C] c. Barometric pressure, in Hg c. Heat reclaim Condenser [kPa] standard air flow rate, cfm, [m3/s] C5.1.4 Evaporatively-Cooled Condenser. d. Barometric pressure, in Hg [kPa] a. Wet-bulb temperature of air entering the Condenser, °F C5.1.8 If chilled water is used to remove [°C] heat from any other source(s) within the b. Condenser fan motor power package, the temperature and flow consumption, kW [kW] measurements of chilled water must be c. Condenser spray pump power made at points so that the measurement consumption, kW [kW] reflects the net package cooling capacity. d. Barometric pressure, in Hg [kPa] C5.1.9 If Condenser water is used to cool the compressor motor or for some other incidental function within the package, the temperature and flow measurements of condenser water must be made at points, so that the measurement reflects the gross package heat rejection. 17
  • 24. ARI STANDARD 550/590- 2003 C5.2 Auxiliary Data to be Recorded for General C6.2 Operations and Limits. Information. C6.2.1 Start the system and establish the C5.2.1 Nameplate data including make, testing conditions in accordance with the model, size and refrigerant, sufficient to following tolerances and instructions. completely identify the water chiller. Unit voltage and frequency should be recorded. C6.2.1.1 Evaporator (All Condenser Types) C5.2.2 Compressor driver or input rpm for open-type compressors. a. The chilled water flow rate, gpm [L/s], shall not deviate C5.2.3 Ambient temperature at test site, more than + 5% from that °F [°C]. specified. b. The individual readings of C5.2.4 Actual voltage, V, and current, water temperature leaving the Amps, for each phase of all electric motor evaporator shall not vary from drives. the specified values by more than 0.5°F [0.3°C]. Care C.5.2.5 Motor, engine or turbine nameplate must be taken to insure that data. these water temperatures are the average bulk stream C5.2.6 Pressure, in H2O [kPa], temperatures. temperature, °F [°C] and exhaust pressure, c. The leaving chilled water in H2O [kPa] for steam turbine nameplate temperature shall be adjusted data. by an increment calculated per C6.3 corresponding to the C5.2.7 Fuel gas specification for gas specified field fouling turbine drive, including pressure, in H2O allowance required for test. [kPa]. d. Part-load tests for Water- Chilling Packages which have C5.2.8 Heat balance for C6.4. continuous capacity modulation must be taken C5.2.9 Date, place, and time of test. within + 2% of the full load tons at the specified part load C5.2.10 Names of test supervisor and capacity. witnessing personnel. e. For water chillers with discrete steps of capacity C6 Test Procedure. control, the part-load tests shall be taken as close as C6.1 Preparation for Test. practical to the specified part- load capacity as per Table 3. C6.1.1 The Water-Chilling Package, which has been completely connected in C6.2.1.2 Water-Cooled accordance with the manufacturer's Condenser. instructions and is ready for normal operation, shall be provided with the a. The water flow rate, gpm necessary instrumentation. [L/s], through the Condenser shall not deviate more than + C6.1.2 The test shall not be started until 5% from that specified. non-condensables have been removed from b. The individual readings of the system. water temperatures entering the refrigerant Condenser C6.1.3 At the manufacturer’s option, shall not vary from the Condenser and cooler surfaces may be specified values by more than cleaned as provided in C3.2.1. 0.5°F [0.3°C]. Care must be taken to insure that these water temperatures are the 18
  • 25. ARI STANDARD 550/590-2003 average bulk stream the turbine, and Condenser temperatures. pressure or vacuum, shall be c. The entering condensing maintained at nameplate water temperature shall be values. adjusted by an increment c. For gas-turbine or gas-engine calculated per C6.3 operating machines, gas corresponding to the specified pressure to turbine or engine, Fouling Factor Allowance. and exhaust back-pressure at the turbine or engine shall be C6.2.1.3 Air-Cooled maintained at nameplate Condenser, Including Heat values. Reclaim. d. In all cases, the governor, if provided, shall be adjusted to a. The average entering air dry- maintain rated compressor bulb temperature to the speed. Condenser shall not vary from the specified values by more C6.3 Method for Simulating Fouling Factor than 1.0°F [0.6°C]. Allowance at Full Load and Part-Load Conditions. b. For heat reclaim Air-Cooled Condensers the Condenser air C6.3.1 Obtain the log mean temperature flow rate shall not deviate difference (LMTD) for the evaporator from that required for test by and/or Condenser using the following more than + 5%. equation at the specified Fouling Factor Allowance (ffsp). C6.2.1.4 Evaporatively-Cooled Condenser. R LMTD =  R C1 a. The entering air wet-bulb ln 1 +   S temperature shall not vary from the values required for test by more than 0.5°F R = Water temperature range [0.3°C]. = absolute value (twl - twe), °F[°C] C6.2.1.5 Chiller Without S = Small temperature difference Condenser. = absolute value (ts - twl), °F [°C] a. The saturated discharge C6.3.2 Derivation of LMTD: temperature shall not vary from the values required for (t s − t we ) − (t s − t w1 ) LMTD = test by more than 0.5°F  t − t we  [0.3°C]. ln  s  b. The liquid refrigerant  t s − t w1  temperature shall not vary from the specified values by (t w1 − t we ) = more than 1.0°F [0.6°C].  (t − t ) + (t − t )  s w1 w1 we ln    t s − t w1  C6.2.1.6 Miscellaneous.   a. For electrically driven The Incremental LMTD (ILMTD) is machines, voltage and determined using the following equation: frequency at the unit terminals shall be maintained q at the nameplate values within ILMTD = ff sp ( ) C2 A tolerances of + 10% on voltage and + 1% on frequency. b. For steam-turbine driven machines, steam conditions to 19
  • 26. ARI STANDARD 550/590- 2003 C6.3.3 The water temperature needed to simulate the additional fouling, TDa, can ffsp = 0.00025 now be calculated: q ILMTD = ff sp ( ) TDa = Ssp - Sc C3a A  2,880,000  = 0.00025 R  550    TDa = S sp - z C3b e -1 = 1.31 where: R TD = Ssp - z a e -1 R Z= LMTD - ILMTD where: R Sc = z e −1 R Z= Ssp = Small temperature difference as LMTD - ILMTD specified, °F [°C] Sc = Small temperature difference as 10 tested in cleaned condition, °F[°C] Z= = 1.125 10.2 - 1.31 The water temperature difference, TDa, is 10 TD = 6.0 - 1.125 then added to the Condenser entering water a -1 e temperature or subtracted from the = 6.0 - 4.8 = 1.2°F evaporator leaving water temperature to simulate the additional Fouling Factor. The entering Condenser water temperature for testing is then raised 1.2°F to simulate C6.3.4 Example-Condenser Fouling Inside Tubes (in I.P Units for clarity): the Fouling Factor Allowance of 0.00025 h ⋅ ft2 ⋅ °F/Btu. The entering condenser water Specified Fouling Factor Allowance, temperature will be 85 + 1.2 or 86.2°F. ffsp =0.00025 h ⋅ ft2 ⋅°F/Btu Condenser load, q = 2,880,000 Btu/h C6.4 Test Verification: Specified Condenser leaving water temp, C6.4.1 Heat Balance-Substantiating Test. Twl = 95°F C6.4.1.1 Calculation of Heat Specified Condenser entering water temp, Balance. In most cases, heat Twe = 85 °F losses or heat gain caused by radiation, convection, bearing Inside* tube surface area, Ai = 550 ft2 friction, oil coolers, etc., are relatively small and may or may *(Since fouling is inside tubes in this not be considered in the overall example) heat balance. Saturated condensing temperature, Omitting the effect of the small heat losses and gains mentioned ts = 101 °F above, the general heat balance equation is as follows: Ssp = ts - twl = 101 - 95 = 6 °F qev + Winput = qcd + qhrc R = twl - twe = 95 - 85 = 10 °F R LMTD = ln (1 + R/S) 10 = = 10.2 ln (1 + 10/6) 20
  • 27. ARI STANDARD 550/590-2003 where: manufacturer's certified power input/output data shall be used. Winput = compressor work input as defined in C6.4.1.2 through In the case of motor drive: C6.4.1.4 Winput = power measured at C6.4.1.2 In a hermetic motor terminals plus power to package, where the motor is auxiliaries as in C.7.1.4. cooled by refrigerant, chilled water or condenser water, the C6.4.1.5 Percent Heat Balance. motor cooling load will be Heat balance, in %, is defined as: included in the measured condenser load, hence (qev + Winput ) - (qcd + q hrc ) x 100 C4 q cd + q hrc Winput = electrical power input to the compressor motor, Btu/h [kW] For any test of a liquid cooled chiller to be acceptable, the heat C6.4.1.3 In a package using an balance (%) shall be within the open-type compressor with prime allowable tolerance calculated per mover and external gear drive: 5.6 for the applicable conditions. Winput = qprime mover -qgear C6.4.2 Concurrent Redundant Verification Test for Air-Cooled or where: Evaporatively- Cooled Condensers. Winput = Power input to the C6.4.2.1 Capacity Calculation compressor shaft, Method. Calculate the capacity of Btu/h [kW] the cooler using one set of qprime mover = Power delivered by instrumentation. Also calculate prime mover, Btu/h the capacity of the cooler using the [kW] redundant set of instrumentation. qgear = Friction loss in the For a valid test, these two gear box, Btu/h calculated values must agree [kW] within the tolerance specified in Section 5.6. The tested capacity The value of qprime mover shall be of the machine shall be the determined from the power input average of these two values. to prime mover using certified data from the prime mover C6.4.2.2 Power Calculation manufacturer. Method. The power measured by the two sets of instruments must The value of qgear shall be be within 2% at all loads. The determined from certified gear tested power of the machine shall losses provided by the gear be the average of the two manufacturer. measured powers. C6.4.1.4 In a package using an C6.4.2.3 Efficiency Calculation open-type compressor with direct Method. Efficiency shall be drive and the prime mover not calculated using the measured furnished by the manufacturer: (averaged) values and must comply within the tolerances of Winput = power input to the 5.6. compressor shaft, Btu/h [kW] C7 Calculation of Results For determination of Winput for turbine or engine operated C7.1 Capacity and Power. machines, the turbine or engine 21