11. TM1700 Channels
• Control
Single or 3-phase breaker
control
• Timing M/R
Main & resistor contact
timing
• DCM, ext. accessory
Safe timing with ground on
both sides
• Timing AUX
Auxiliary contact timing
• Analog
Analogue transducers,
motion, pressure...
• Digital
Incremental transducers
11
12. Control Channels
Bounce-free trig/close of circuit
breaker
C, O, C-O, O-C, O-C-O with
adjustable pulse length & delay.
Automatic recording of coil current
15(60)A, coil voltage, coil resistance.
Timing of a/b contacts for single
operation.
Ext. measurement of coil I[A],
possible too (w external current clamp)
12
13. Timing M/R Channels
Main/resistor contact timing
measurements
6 channels per module
Automatic detection of parallel
resistor contacts (PIR)
Measures voltage for DRM and SRM.
Sampling rate up to 40 kHz
13
15. DCM unit
Both sides grounded main contact
timing measurements
6 channels
Can do DCM recordings together
with Timing M/R channels
15
16. Analog Channels
3 channels per module
Sampling rate 40 kHz, resolution: 16
bit
Ranges are adapted to standard
transducer outputs
Voltage measuring input
• Range: 10 V and 400 V
Current measuring input
• Range: 0 – 22 mA
Able to supply transducers
• 10V, 24 V
16
17. Digital Channels
Motion measurement with digital
transducer
6 channels per module
Supports RS422
Ranges up +/- 32000 pulses
Sampling rate: 20 kHz
Transducer supply 5 V and 12 V
17
18. Timing Aux Channels
Timing of auxiliary contacts
6 galvanic separated channels per
module
Senses dry and wet contacts w/o
need of setting
Polarization independent
Voltage sense up to 250 V
Needed if more than one a-contact
and one b-contact shall be recorded
18