1. R
Pradeep Sales & Service Pvt. Ltd
10-11,StarIndlEstate,
Nr.SakinakaTel.Exch
Kurla-AndheriRd,Sakinaka,
Andheri(E),Mumbai - 40072
CONTACT US+91 22 28593000
+91 22 28596550
arpit78@hotmail.com
arpit078@yahoo.com
Tap Change Control and Transformer
Monitoring System (TCS-TMC) - Fx 8000A
2. Tap Change Control and Transformer Monitoring System (TCS-TMC) Fx 8000A
Sr.
No.
Features Description
1 Large Backlight LCD 20x4 with 9mm character size for clear vision from far distance
2 Binary Inputs 32 Freely Programmable inputs
3 Binary Outputs 12 fixed outputs
4 mA Inputs 4-20mA inputs – 10 nos.
5 mA Outputs 4-20mA outputs– 5 nos.
6 Ethernet Facility IEC 61850 or Optional IEC103 or Optional IEC 104
7 Modbus Facility RS485 port for communication
8 Parallel Operation Facility Master /Follower/Independent option
9 GSM Facility(optional) Values of basic parameters available through SMS
10 GPS Facility (optional) Location Information with updated Time
11 Disturbance Recording Optional
12 Data Recording Facility
All Parameter Values & events can be recorded & various
reports can besaved in PC
13 Modes Automatic/Manual , Local(device) & Remote(From PC)modes
14
Cooling control & OLTC
Control Facility
Device controls pumps & fans for cooling function & operates in
different modes to Control OLTC function
15 Device Communication
Measured signals can be transmitted from device to M. Box via
FO cable or RJ 45 (Optional) as required
16
Overload Capacity, Aging
Rate
Calculation of transformer life
Sr.
No.
Parameters Specifications
1 Auxiliary Supply 90V - 260V AC/DC, 50 Hz , 15V
2 PT supply 110V AC ±10%, 50Hz, 2.5VA(adjustable)
3 Basic Voltage Adjustment BVA between 50V and 140V AC (adjustable)
4 Sensitivity/Dead Band
Adjustment
DBA around BVA from 0.5% to 9.9% in steps of 0.1%
5 Time Delay Voltage independent, adjustable from 1to 999seconds
6 Blocking from Under Voltage set to 70%-99%
7 Restoration setting Provided at 85% of BVA adjustment
8
Control Output
1 pair of NO potential free contacts, rated at 5A, 230V
AC
9 Line Drop Compensator(LDC) + 25V
10 Operating Temperature -40ºC to 60ºC
11 Panel Cutoutin mm (L x W) 445 x 134
12 Overall dimensionin mm
(L x W x D)
489 x 134 x 272
13 Weight 5.23 kg
14 Mounting Flush
15 Dielectric Strength
2kV AC for 1 minute for first time and further
80%only should be applied