SlideShare a Scribd company logo
1 of 104
1 
LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) 
MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION 
PT BADAK NGL BONTANG 
MAULANI CANDRA (0910630076) 
JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK 
UNIVERSITAS BRAWIJAYA 
Daftar Isi 
B A B I ................................................................................................................. 6 
PENDAHULUAN................................................................................................. 6 
1.1 Latar Belakang ...................................................................................... 6 
1.2 Tujuan Penulisan ................................................................................... 8 
1.3 Batasan Masalah.................................................................................... 8 
1.4 Metode Penulisan .................................................................................. 8 
1.5 Sistematika Penulisan............................................................................ 9 
B A B II .............................................................................................................. 11 
TINJAUAN PUSTAKA...................................................................................... 11 
2.1 Sistem Distribusi Tenaga Listrik......................................................... 11 
2.1.1 Umum .............................................................................................. 11 
2.1.2 Jaringan Distribusi menurut Susunan Rangkaian............................ 11 
2.1.2.1 Sistem Radial ................................................................................ 12 
2.2 Transformator ...................................................................................... 16 
2.2.1 Pengertian Transformator................................................................ 16 
2.2.2 Jenis-Jenis Transformator ............................................................... 17 
2.2.3 Prinsip Transformator ..................................................................... 22 
2.2.3.1 Hubungan Tegangan..................................................................... 28 
2.2.3.2 Hubungan Arus............................................................................. 28 
2.2.3.3 Hubungan Impedansi .................................................................... 28 
2.2.4 Pemeliharaan Preventif Transformator ........................................... 30 
2.2.5 Transformator Tipe Kering ............................................................. 32 
2.2.6 Transformator Tipe Basah............................................................... 39 
2.2.7 Pengujian Transformator ................................................................. 49
2.3 Reaktor ................................................................................................ 58 
2.3.1 Definisi ............................................................................................ 58 
2.3.2 Tipe dari Reaktor Seri Dry-type air-core ........................................ 59 
2.3.3 Aplikasi dari Reaktor Seri ............................................................... 59 
2.3.4 Posisi Reaktor pada Bus Bar ........................................................... 60 
2.3.5 Pengujian Rutin, Desain, dan Pengujian lain untuk Reaktor Seri ... 64 
B A B III............................................................................................................. 68 
ANALISA DAN PEMBAHASAN ..................................................................... 68 
3.1 Analisa Pengaruh Transformator dan Reaktor Seri pada Ring Bus .... 68 
3.1.1 Analisa Pengaruh Transformator .................................................... 69 
3.1.2 Analisa Pengaruh Reaktor Seri ....................................................... 72 
3.2 Analisa Kondisi Transformator 34.5 kV/13.8 kV/13.8 kV ................. 74 
3.2.1 Insulation Resistance (IR) Test ....................................................... 76 
3.2.2. Time-Resistance Readings (Dielectric Absorbtion) ....................... 78 
3.2.3 Polarization Index (PI) Test ............................................................ 85 
3.2.4 Power Factor (PF) Test .................................................................. 87 
3.2.5 Oil Dielectric Breakdown Voltage Test .......................................... 89 
3.3 Analisa Kondisi Reaktor Seri Dry-type air-core................................. 91 
3.3.1 Insulation Resistance (IR) Test ....................................................... 95 
3.3.2 Time-Resistance Readings (Dielectric Absorbtion) ........................ 96 
3.3.3 Polarization Index (PI) Test ............................................................ 98 
3.3.4 Power Factor (PF) Test ................................................................. 100 
3.4 Analisis .............................................................................................. 100 
3.4 Upaya ................................................................................................ 102 
3.4.1 Transformator 34.5 kV/13.8 kV/13.8 kV ...................................... 102 
3.4.2 Reaktor Seri Dry-type air-core ..................................................... 103 
2 
LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) 
MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION 
PT BADAK NGL BONTANG 
MAULANI CANDRA (0910630076) 
JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK 
UNIVERSITAS BRAWIJAYA
B A B IV .......................................................................................................... 104 
PENUTUP ......................................................................................................... 104 
4.1 Kesimpulan........................................................................................ 104 
4.2 Saran .................................................................................................. 104 
3 
LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) 
MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION 
PT BADAK NGL BONTANG 
MAULANI CANDRA (0910630076) 
JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK 
UNIVERSITAS BRAWIJAYA
4 
LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) 
MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION 
PT BADAK NGL BONTANG 
MAULANI CANDRA (0910630076) 
JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK 
UNIVERSITAS BRAWIJAYA 
DAFTAR GAMBAR 
Gambar 2.1: Jaringan Distribusi Sistem Radial ........................................................... 12 
Gambar 2.2: Jaringan Distribusi Sistem Loop ............................................................. 13 
Gambar 2.3: Jaringan Distribusi Sistem Tertutup/Ring ............................................... 14 
Gambar 2.4: Jaringan Distribusi Sistem Spindel.......................................................... 15 
Gambar 2.5: Jaringan Distribusi Sistem Cluster .......................................................... 16 
Gambar 2.6: Konstruksi inti tiga fasa........................................................................... 19 
Gambar 2.7: Konstruksi Tipe Cangkang dari Transformator Satu-Fasa dan Tiga-Fasa. ` 
................................................................................................................. 21 
Gambar 2.8: Diagram Rangkaian dan Koneksi dari Transformator Sederhana ........... 23 
Gambar 2.9: Diagram Ekivalen Transformator............................................................ 26 
Gambar 2.10: (a) Diagram Ekivalen yang Telah Disederhanakan dan (b) Diagram 
Vektor yang Telah Disederhanakan dari Transformator ................................................ 27 
Gambar 2.11: Representasi Grafis dari Transformator Daya..................................... 27 
Gambar 2.12: Diagram Rangkaian Ekivalen dari persentase dasar. .......................... 30 
Gambar 2.13: Transformator Tipe Kering Berventilasi dengan Penutup Depan untuk 
memperlihatkan perakitan lilitan- inti. ............................................................................. 33 
Gambar 2.14: Transformator Basah Tiga Fasa .......................................................... 39 
Gambar 2.15: TTR testers: (a) hand-crank TTR; (b) handheld electronic TTR; and (c) 
three-phase electronic TTR. (Courtesy of Megger Inc., Valley Forge, PA.) .................. 52 
Gambar 2.16: IR tester (megohmmeter). (Courtesy of Megger Inc., Valley Forge, 
PA.) 56 
Gambar 2.17: (a) Prinsip Rangkaian Pengukuran tegangan recovery dari Waktu tc; 
(b) Siklus Pengukuran RVM dan kuantitas perekaman selama satu siklus; dan (c) 
tegangan recovery V sebagai fungsi waktu tc. ................................................................ 58 
Gambar 2.18: Bus Coupling....................................................................................... 61 
Gambar 2.19: Terpasang seri dengan incoming feeder .............................................. 62
Gambar 2.20: Terpasang seri dengan outgoing feeder............................................... 62 
Gambar 3.1: Diagram Satu Garis Sistem Distribusi 34.4/13.8 kV PT Badak NGL 
Bontang ................................................................................................................... 6 
Gambar 3.2: Simulasi Ring Bus dengan Menggunakan ETAP ................................... 69 
Gambar 3.1: Simulasi Aliran Daya pada Ring Bus jika Semua Transformator In-service 
................................................................................................................. 70 
Gambar 3.2: Simulasi Aliran Daya pada Ring Bus jika Transformator 30-PT-202 Out-service 
................................................................................................................. 71 
Gambar 3.3: Simulasi Aliran Daya pada Ring Bus jika Salah Satu Kaki Transformator 
30-PT-202 Tidak Dioperasikan. ...................................................................................... 72 
Gambar 3.4: Simulasi jika ring bus tidak dipasang Reaktor Seri tiga fasa Dry-type 
Air-core ............................................................................................................. 73 
Gambar 3.5: Simulasi ring bus setelah dipasang Reaktor Seri tiga fasa Dry-type Air-core 
................................................................................................................. 74 
Gambar 3.6: Konstruksi Reaktor seri dry-type air-core 30-PLR-101 dan 30 PLR 102 .. 
5 
LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) 
MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION 
PT BADAK NGL BONTANG 
MAULANI CANDRA (0910630076) 
JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK 
UNIVERSITAS BRAWIJAYA 
92
6 
LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) 
MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION 
PT BADAK NGL BONTANG 
MAULANI CANDRA (0910630076) 
JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK 
UNIVERSITAS BRAWIJAYA 
B A B I 
PENDAHULUAN 
1.1 Latar Belakang 
Dalam upaya menjaga kehandalan sistem pembangkit, PT. Badak NGL 
menggunakan sistem ring bus 34,5 kV yang menghubungkan seluruh generator di 
Module-I dan Module-II. Sehingga jika salah satu atau beberapa generator di Module-I 
maupun Module-II tidak bisa menyuplai daya, pengalihan beban dapat dilakukan dan 
proses produksi masih tetap bisa terlaksana. Reaktor seri 30-PLR-101 dan 30-PLR-102 
menghubungkan Module I dan Module II. Fungsi dari reaktor adalah untuk membatasi 
arus antar module yang berlebihan diakibatkan starting motor cooling water pump dan 
arus hubung singkat yang dapat mengalir dari Module I dan Module II dan sebaliknya. 
Gambar 3.1: Diagram Satu Garis Sistem Distribusi 34.4/13.8 kV PT Badak NGL 
Bontang
Seperti yang dapat kita lihat pada gambar di atas, sistem ring bus terletak di 
posisi paling atas. Tegangan yang dihasilkan oleh setiap generator sebesar 13,8 kV di 
naikkan dengan menggunakan transformator tiga belitan (Three winding Transformer) 
sampai 34,5 kV dan dikirim ke dalam ring bus. Generator di PT. Badak NGL terdiri 
dari 15 generator dengan rincian 12 generator turbin uap, 2 generator turbin gas, 1 
generator turbin diesel. 
Pada gambar dapat dilihat bahwa dalam satu modul terhubung dengan 4 
transformator tiga belitan (Three winding Transformer). Yaitu Module I yang terhubung 
dengan 30-PT-101, 30-PT-102, 30-PT-103, dan 30-PT-104 sedangkan Module II 
terhubung dengan 30-PT-201, 30-PT-202, 30-PT-203, dan 30-PT-204. Antara Module I 
dan Module II dihubungkan dengan reaktor yaitu Three-phase Dry-type Air-core Series 
Reactor. 
Ring bus terhubung langsung dengan transformator dan reaktor seri. Sehingga 
kondisi dari ring bus dapat ditentukan melaui kondisi dari 8 transformator tiga belitan 
(Three winding Transformer) dan 2 Reaktor Seri Tiga Fasa Tipe-Kering Inti-udara 
(Three-phase Dry-type Air-core Series Reactor). Jika salah satu dari peralatan tersebut 
tidak baik (mengalami kerusakan) maka dapat diambil kesimpulan bahwa kondisi dari 
ring bus juga tidak baik dan begitu pula sebaliknya. Untuk melihat kondisi peralatan 
tersebut, kita dapat mengetahui dari hasil pengujian yang dilakukan dalam 
pemeliharaan. Pemeliharaan yang dilakukan di PT Badak NGL yaitu: 
Tulisan ini bertujuan untuk menganalisis keadaan dari ring bus 34,5 kV 
berdasarkan keadaan dari transformator tiga belitan (Three winding Transformer) dan 
reaktor seri tiga fasa tipe-kering inti-udara (Three-phase Dry-type Air-core Series 
Reactor) dari data yang diperoleh dari pengujian yang dilakukan saat preventive 
maintenance. Selain itu, tulisan ini juga bertujuan untuk membrikan rekomendasi 
7 
LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) 
MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION 
PT BADAK NGL BONTANG 
1. Predictive Maintenance (Conditional Maintenance). 
2. Preventive Maintenace (Time Base Maintenance). 
3. Corrective Maintenance. 
MAULANI CANDRA (0910630076) 
JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK 
UNIVERSITAS BRAWIJAYA
mengenai upaya-upaya yang harus dilakukan PT Badak NGL untuk menjaga kondisi 
dari ring bus tetap dalam keadaan baik. 
8 
LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) 
MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION 
PT BADAK NGL BONTANG 
MAULANI CANDRA (0910630076) 
JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK 
UNIVERSITAS BRAWIJAYA 
1.2 Tujuan Penulisan 
Tujuan dari penulisan laporan ini adalah: 
1. Menganalisis pengaruh dari transformator tiga belitan (Three winding 
Transformer) dan reaktor seri tiga fasa tipe-kering inti-udara (Three-phase 
Dry-type Air-core Series Reactor) terhadap ring bus 34,5 kV. 
2. Menganalisis kondisi 8 transformator tiga belitan (Three winding 
Transformer). 
3. Menganalisis kondisi reaktor seri tiga fasa tipe-kering inti-udara (Three-phase 
Dry-type Air-core Series Reactor). 
1.3 Batasan Masalah 
1. Kondisi pemeliharaan transformator dan reaktor yang dianalisis hanya 
dilakukan pada pengujian terakhir. 
2. Analisis transformator hanya dilakukan pada transformator tiga belitan 
berdasarkan pengujian Insulation Resistance (IR) test, Polarization Index 
(PI) test, Power Factor (PF) loss test, dielectric breakdown voltage test . 
Sedangkan analisis berdasarkan pengujian Dissolve Gas Analysis (DGA) 
test tidak dilakukan. 
3. Analisis reaktor hanya berdasarkan pengujian Insulation Resistance (IR) 
test, Polarization Index (PI) test, dan Power Factor (PF) loss test. 
1.4 Metode Penulisan 
Dalam pengerjaan laporan ini dilakukan beberapa metode, antara lain: 
1. Studi literatur 
2. Kunjungan langsung ke lapangan 
3. Wawancara dengan karyawan PT. Badak NGL
9 
LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) 
MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION 
PT BADAK NGL BONTANG 
MAULANI CANDRA (0910630076) 
JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK 
UNIVERSITAS BRAWIJAYA 
1.5 Sistematika Penulisan 
Sistematika penyusunan laporan adalah sebagai berikut, 
BAB 1 PENDAHULUAN 
Berisi latar belakang, tujuan, batasan 
masalah, metode penelitian dan 
sistematika penulisan tugas khusus laporan 
praktik kerja lapangan di PT. Badak NGL 
BAB 2 TINJAUAN PUSTAKA 
Berisi penjelasan tentang sistem distribusi 
tenaga listrik, transformator dan cara 
pengujiannya, dan reaktor dan pengujian 
yang dilakukan. 
BAB 3 ANALISA DAN PEMBAHASAN 
Analisa Pengaruh Transformator dan Reaktor 
Seri pada Ring Bus, Analisa Kondisi 
Transformator 34.5 kV/13.8 kV/13.8 kV, dan 
Analisa Kondisi Reaktor Seri Dry-type air-core, 
dan upaya-upaya yang harus dilakukan 
untuk menjaga kondisi ring bus. 
BAB 4 PENUTUP 
Berisi kesimpulan dan saran yang diberikan 
penulis
10 
LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) 
MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION 
PT BADAK NGL BONTANG 
MAULANI CANDRA (0910630076) 
JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK 
UNIVERSITAS BRAWIJAYA
11 
LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) 
MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION 
PT BADAK NGL BONTANG 
MAULANI CANDRA (0910630076) 
JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK 
UNIVERSITAS BRAWIJAYA 
B A B II 
TINJAUAN PUSTAKA 
2.1 Sistem Distribusi Tenaga Listrik 
2.1.1 Umum 
Penyaluran daya dalam sistem distribusi dapat melalui saluran udara atau 
saluran bawah tanah. Pemilihan saluran udara dan saluran bawah tanah tergantung pada 
beberapa faktor yang berlainan. Yaitu faktor kontinuitas pelayanan, arah perkembangan 
daerah, biaya pemeliharaan tahunan, biaya modal, segi estetis, dan umur manfaat sistem 
tersebut. Gabungan kedua saluran ini sering kali diperlukan. 
Baik buruknya suatu sistem distribusi dinilai dari beberapa faktor, yaitu : 
1. Regulasi tegangan (Jatuh Tegangan) 
2. Kontinuitas pelayanan 
3. Efisiensi 
4. Harga sistem 
Suatu sistem distribusi harus memenuhi beberapa persyaratan sebagai berikut : 
1. Regulasi tegangan tidak terlalu besar 
2. Gangguan terhadap pelayanana tidak boleh terlalu lama 
3. Biaya sistem tidak terlalu mahal 
2.1.2 Jaringan Distribusi menurut Susunan Rangkaian 
Susunan Rangakain Sistem jaringan distribusi ada beberapa macam, yaitu : 
1. Sistem Radial 
2. Sistem Loop 
3. Sistem Tertutup/Ring 
4. Sistem Spindel 
5. Sistem Cluster 
6. Sistem Grid/Network
12 
LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) 
MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION 
PT BADAK NGL BONTANG 
MAULANI CANDRA (0910630076) 
JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK 
UNIVERSITAS BRAWIJAYA 
2.1.2.1 Sistem Radial 
Gambar 2.1: Jaringan Distribusi Sistem Radial 
Sistem radial ini merupakan suatu sistem distribusi tegangan menengah yang paling 
sederhana, murah, banyak digunakan terutama untuk sistem yang kecil, kawasan 
pedesaan. Proteksi yang digunakan tidak rumit dan keandalannya paling rendah. 
Keuntungan / Kerugian : 
1. Mudah mengoperasikannya 
2. Mudah mencari tegangan 
3. Cocok untuk sistem yang sederhana 
4. Tidak dapat dimanipulasi bila terjadi gangguan.
13 
LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) 
MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION 
PT BADAK NGL BONTANG 
MAULANI CANDRA (0910630076) 
JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK 
UNIVERSITAS BRAWIJAYA 
2.1.2.1 Sistem Loop 
Pada sistem loop terbuka, bagian-bagian penyulang tersambung melalui alat 
pemisah (disconnectors), dan kedua ujung penyulang tersambung pada sumber energi. 
Pada suatu tempat tertentu pada penyulang, alat pemisah sengaja dibiarkan dalam 
keadaan terbuka. Pada asasnya, sistem ini terdiri atas dua penyulang yang dipisahkan 
oleh suatu pemisah, yang dapat berupa sekring, alat pemisah, saklar daya. Terlihat pada 
Gambar 2.6 bila terjadi gangguan, bagian saluran dari penyulang yang terganggu dapat 
dilepas dan menyambungnya pada penyulang yang tidak terganggu. Sistem demikian 
biasanya dioperasikan secara manual dan dipakai pada jaringan yang relatif kecil. 
Gambar 2.2: Jaringan Distribusi Sistem Loop 
Keuntungan/Kerugian : 
1. Secara teknis lebih baik dari sistem radial 
2. Biaya sedikit lebih mahal karena harus dibangun dua penyulang pada jalur yang 
sama 
3. Bisa dimanipulasi bila terjadi gangguan
14 
LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) 
MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION 
PT BADAK NGL BONTANG 
MAULANI CANDRA (0910630076) 
JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK 
UNIVERSITAS BRAWIJAYA 
2.1.2.3 Sistem Tertutup/Ring 
Gambar 2.3: Jaringan Distribusi Sistem Tertutup/Ring 
Keuntungan/Kerugian : 
1. Jumlah konsumen yang besar bisa dijangkau 
2. Gangguan salah satu sisi penghantar harus sanggup menampung seluruh beban 
yang terpasang pada sistem, disini erat hubungannya dengan rugi tegangan. 
3. Mudah operasi
15 
LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) 
MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION 
PT BADAK NGL BONTANG 
MAULANI CANDRA (0910630076) 
JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK 
UNIVERSITAS BRAWIJAYA 
2.1.2.4 Sistem Spindel 
Gambar 2.4: Jaringan Distribusi Sistem Spindel 
Sistem Spindle merupakan sistem yang relatif handal karena disediakan satu 
buah express feeder yang merupakan feeder/penyulang tanpa beban dari gardu induk 
sampai gardu hubung / GH refleksi, banyak digunakan pada jaringan SKTM. Sistem ini 
relatif mahal karena biasanya dalam pembangunannya sekaligus untuk mengatasi 
perkembangan beban dimasa yang akan datang. Proteksinya relatif sederhana hampir 
sama dengan sistem open loop. Biasanya ditiap-tiap feeder dalam sistem spindel 
disediakan gardu tengah (middle point) yang berfungsi untuk titik manufer apabila 
terjadi gangguan pada jaringan tersebut.
16 
LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) 
MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION 
PT BADAK NGL BONTANG 
MAULANI CANDRA (0910630076) 
JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK 
UNIVERSITAS BRAWIJAYA 
2.2.2.5 Sistem Cluster 
Gambar 2.5: Jaringan Distribusi Sistem Cluster 
Sistem clutser ini hampir mirip dengan sistem spindel. Dalam sistem cluster 
tersedia satu express feeder yang merupakan feeder atau penyulang tanpa beban yang 
digunakan sebagai titik menufer beban oleh feeder atau penyulang lain dalam sistem 
cluster tersebut. Proteksi yang diperlukan untuk sistem yang relatif sama dengan sistem 
open loop atau sistem spindle. 
2.2 Transformator 
2.2.1 Pengertian Transformator 
Transformator atau lebih dikenal dengan nama “transformer” atau 
“transformator” sejatinya adalah suatu peralatan listrik yang mengubah daya listrik AC 
pada satu level tegangan yang satu ke level tegangan berdasarkan prinsip induksi 
elektromagnetik tanpa merubah frekuensinya. Tranformator biasa digunakan untuk 
mentransformasikan tegangan (menaikkan atau menurunkan tegangan AC). Selain itu, 
transformator juga dapat digunakan untuk sampling tegangan, sampling arus, dan juga 
mentransformasi impedansi. Transformator terdiri dari dua atau lebih kumparan yang 
membungkus inti besi feromagnetik. 
Transformer adalah peralatan yang sangat handal dan dapat menyediakan 
pelayanan dalam jangka panjang bila pemeliharaan dan perbaikan dilakukan secara
teratur. Kerusakan transformer, ketika mereka terjadi, biasanya yang bersifat sangat 
serius, yang mungkin memerlukan perbaikan mahal dan waktu yang lama. Jaminan 
terbaik untuk mengatasinya adalah memastikan bahwa transformator terpasang dengan 
benar dan dipelihara. 
17 
LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) 
MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION 
PT BADAK NGL BONTANG 
MAULANI CANDRA (0910630076) 
JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK 
UNIVERSITAS BRAWIJAYA 
2.2.2 Jenis-Jenis Transformator 
Untuk pertimbangan kebutuhan pemeliharaan, transformator dapat dibagi 
menjadi kategori berikut: 
1. Medium isolasi 
2. Konstruksi 
3. Aplikasi dan penggunaan 
2.2.2.1 Medium Isolasi 
Media transformator isolasi dapat dibagi lagi menjadi dua jenis : 
1. Tipe Kering 
Transformator tipe kering pada umumnya menggunakan pendinginan udara 
dengan isolasi lilitan dengan kelas A, B, C, atau H. Transformator tipe kering dapat 
pendinginan sendiri atau pendinginan udara yang dipaksa. 
Pendinginan Sendiri : Transformator pendinginan sendiri didinginkan dengan 
sirkulasi alami dari udara melalui kotak transformator. Desain kelas pendinginan untuk 
transformator ini Adalah AA. 
Pendinginan udara dipaksa: transformator didinginkan dengan udara yang 
dipaksa dari tipe kering didinginkan dari sirkulasi udara yang dipaksa melalui kotak. 
Transformator dari tipe ini memiliki peralatan penghembus udara dari semacam kipas. 
Transformator ini memiliki rating 133% dari rating transformator tipe kering 
pendinginan sendiri. Kelas desain pendinginan untuk transformator ini adalah FA. 
Transformator tipe kering dapat diperoleh dengan keduanya yaitu pendinginan sendiri 
maupun pendinginan dipaksa. Desain dari transformator adalah AA/FA. Transformator
tipe kering dapat juga didinginkan oleh gas selain udara. Untuk transformator seperti itu 
dibutuhkan tangki yang disegel. 
2. Tipe Basah 
Pada transformator tipe ini, lilitan dan inti direndam secara keseluruhan pada 
cairan yang dimasukkan pada tangki transformator. Tangki dilengkapi dengan sirip 
pendingin untuk sirkulasi dari cairan transformator. Cairan transformator memberikan 
isolasi medium untuk gulungan sebaik mungkin untuk disipasi panas. Dua cairan sudah 
digunakan secara luda untuk transformator: oli mineral dan polychlorinated biphenyls 
(PCB), yang pada umumnya dikenal sebagai askarel. Askarel secara luas digunakan 
pada transformator untuk aplikasi dalam ruangan karena itu adalah cairan isolasi sintesis 
yang tidak mudah terbakar. Askarel adalah nonbiodegradable dan beracun. 
Environmental Protection Agency (EPA) melarang penggunaan dari askarel pada 
transformator dan peralatan elektrik lainnya, dan kemampuannya untu digunakan 
kembali pada aplikasi baru hampir tidak ada. Cairan yang lebih baru telah diperkenalkan 
seperti silikon, Rtemp, Wecosal, dan Alpha 1 untuk pengganti dari askarel. Yang lain 
masih dalam tahap pengembangan. Tanpa menghirauan apa cairan baru yang ada dalam 
pasaran untuk aplikasi transformator, mereka harus tetap dipelihara dan diuji untuk 
menjamin integritas dari transformator. 
18 
LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) 
MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION 
PT BADAK NGL BONTANG 
Metode pendingina yang digunakan untuk transformator yang berisi cairan. 
MAULANI CANDRA (0910630076) 
JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK 
UNIVERSITAS BRAWIJAYA 
a. ONAN : Oil Natural Air Natural 
Transformator pendinginan sendiri menggunakan sirkulasi alami dari 
cairan isolasi. Panas pada tangki transformator dihilangkan dengan konveksi 
arus yang telah diatur pada cairan, yang bersirkulasi melalui tangki dan sirip 
pendingin. 
b. ONAF : Oil Natural Air Forced 
Pada tipe ini oli akan bersirkulasi dengan alami namun saat oli melalui 
radiator oli akan didinginkan dibantu dengan kipas/fan. 
c. OFAF : Oil Forced Air Forced 
Pada tipe ini oli akan didinginkan dengan bantuan pompa agar sirkulasi 
semakin cepat dan juga dibantu kipas/fan pada radiatornya
d. Pendinginan Air: Transformator ini menggunakan air selain udara untuk 
menghasilkan pendinginan. Sistem pendinginan ini meliputi penukar panas dari 
air yang dipopa melalui gulungan pipa yang dipasang didalam atau diluar dari 
tangki transformator. Kelas desain pendinginan untuk transformator ini adalah 
FOW. 
Khusus jenis transformator tenaga tipe basah, kumparan-kumparan dan intinya 
direndam dalam minyak-transformator, terutama transformator-transformator tenaga 
yang berkapasitas besar, karena minyak transformator mempunyai sifat sebagai media 
pemindah panas dan bersifat pula sebagai isolasi ( tegangan tembus tinggi ) sehingga 
berfungsi sebagai media pendingin dan isolasi. 
19 
LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) 
MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION 
PT BADAK NGL BONTANG 
MAULANI CANDRA (0910630076) 
JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK 
UNIVERSITAS BRAWIJAYA 
2.2.2.2 Konstruksi 
Transformator dapat diklasifikasikan dari konstruksi tangki dan konstruksi inti. 
Gambar 2.6: Konstruksi inti tiga fasa 
Konstruksi tangki
Konstruksi beberapa tipe dari tangki transformator digunakan untuk mencegah 
20 
LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) 
MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION 
PT BADAK NGL BONTANG 
MAULANI CANDRA (0910630076) 
JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK 
UNIVERSITAS BRAWIJAYA 
terbukanya cairan ke atmosfir. Tipe adalah: 
Free breathing : tipe ini untuk membuka ke atmosfer (contoh: pembatas udara 
ditas cairan pada tekanan atmosfir). Transformator bernafas sebagai perubahan tekanan 
udara dan temperatur diluar tangki. Beberapa dari transformator dapat dilengkapi 
dengan komponen dehidrasi pada breather. 
Konservator atau tangki ekspansi : transformator ini dilengkapi dengan tangki 
ekspansi diatas tangki transformator. Tangki transformator dilengkapi dengan oli, dan 
transformator bernafas dengan tangki kecil ini, pada umumnya melewati komponen 
dehidrasi. Tujuan dari tangki kecil ini adalah untuk menyegel cairran transformator dari 
atmosfir dan untuk mengurangi oksidasi dan formasi dari sludge. 
Sealed Tank: transformator ini dilengkapi dengan gas inert, seperti nitrogen yang 
berada di bawah tekanan diatas cairan yang berada pada atas tangki transformator. Pada 
umumnya, range tekanan dari tipe transformator ini adalah -8 sampai 8lb/in2. 
Gas-oil sealed: transformator ini memiliki tangki tambahan untuk secara 
menyeluruh menyegel tangki interior, meliputi cairan transformator, dari atmosfer. 
Vaporization: Transformator tipe ini menggunakan cairan isolasi spesial yang 
tidak mudah terbakar, seperti florocarbon (General Electric R-113), yang tidak mudah 
terbakar, dan kondenser spesial yang dirakit las pada atas dari tangki transformator. 
Ujung tabung pendingin yang diacu dan diatas header tabung. Transformator ini 
menggunakan teknik dari cairan yang disemprot pada inti dan gulungan yang dirakit. 
Tujuan dari kondenser adalah untuk mendinginkan uap udara menjadi cari untuk 
sirkulasi belanjut pada cairan. 
Konstruksi Inti 
Berdasarkan konstruksi corenya, tranformator dapat dibedakan menjadi tipe core 
dan shell. 
1. Tipe Core
Pada tipe ini, kumparan transformator mengelilingi inti yang terlaminasi. 
21 
LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) 
MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION 
PT BADAK NGL BONTANG 
Sebagian besar transformator distribusi kecil menggunakan konstruksi ini. 
MAULANI CANDRA (0910630076) 
JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK 
UNIVERSITAS BRAWIJAYA 
2. Tipe Shell 
Pada tipe ini, Inti magnetik mengelilingi kumparan. Satu keuntungan dari 
jenis shell adalah bahwa ia menawarkan jalur terpisah untuk arus urutan nol melalui 
inti, dibandingkan dengan jenis core di mana jalan-urutan nol ada hanya melalui 
tangki transformator dan akhir sambungan. 
2.2.2.3 Aplikasi dan Penggunaan 
Transformator yang digunakan untuk mengkonversikan energi dapat 
diklasifikasikan ke dalam 5 kategori berdasarkan aplikasi dan penngunaanya. 
1. Transformator Distribusi 
Sebuah transformator distribusi memiliki rating 3-500 kVA. Ada berbagai 
jenis transformator distribusi, tergantung pada media pendingin dan isolasi, 
layanan aplikasi, dan metode pemasangan. Hampir semua transformator distribusi 
dengan pendinginan sendiri. 
Gambar 2.7: Konstruksi Tipe Cangkang dari Transformator Satu-Fasa dan Tiga-Fasa. 
2. Transformer Jaringan
Transformator ini memiliki karakteristik serupa dengan transformator distribusi. 
Namun, penerapannya berbeda. Memiliki persyaratan yang khusus untuk layanan 
jaringan, seperti ventilasi, ukuran lemari besi, kemampuan perendaman, dan persyaratan 
hubung singkat. Transformer Jaringan dapat memiliki peringkat kVA lebih dari 500 
kVA dan tegangan primer sampai dengan 23 kV. 
3. Transformator Arc-Furnace 
Transformator Arc-Furnace adalah transformator tujuan khusus yang digunakan 
dalam proses industri. Ini adalah transformator tegangan rendah dan ampere tinggi dan 
khusus bersiap untuk menahan tekanan mekanis yang disebabkan oleh fluktuasi arus 
yang telah ditentukan. Karena gelombang terdistorsi karena busur, ia memiliki tambahan 
isolasi kumparan. 
4. Transformator Penyearah 
Transformer ini digunakan dalam penyearahan AC ke DC dalam proses di 
Industri. Transformer ini sepsial dirancang untuk tahan tehadap tekanan mekanis akibat 
arus yang tinggi. 
5. Transformator Daya 
Transformator ini memiliki rating lebih dari 500 kVA dan terutama 
digunakan dalam mengubah energi dari stasiun pembangkit ke jaringan transmisi, dari 
jalur transmisi untuk gardu distribusi, atau dari jalur layanan utilitas untuk pembangkit 
gardu distribusi. 
22 
LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) 
MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION 
PT BADAK NGL BONTANG 
MAULANI CANDRA (0910630076) 
JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK 
UNIVERSITAS BRAWIJAYA 
2.2.3 Prinsip Transformator 
Transformer ditemukan pada tahun 1886 oleh William Stanley dan merupakan 
peralatan yang sangat berguna. Sebuah transformator dapat dibagi dalam 3 bagian: 
Kumparan Primer, Kumparan Sekunder dan Inti (Core). Kumparan Primer dan 
Sekunder dihubungkan oleh fluk yang diproduksi dalam inti besi.
23 
LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) 
MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION 
PT BADAK NGL BONTANG 
Gambar 2.8: Diagram Rangkaian dan Koneksi dari Transformator Sederhana 
MAULANI CANDRA (0910630076) 
JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK 
UNIVERSITAS BRAWIJAYA 
Sisi Primer: 
Vp adalah tegangan primer 
Np adalah lilitan primer 
Zps adalah impedansi bocor 
Ip adalah arus primer 
Sisi Sekunder: 
Vs adalah tegangan sekunder 
Ns adalah lilitan sekunder 
Zps adalah impedansi bocor 
Is adalah arus sekunder 
Diasumsikan bahwa lilitan primer dicatu dengan menghubungkan dengan 
sumber tegangan AC, Vp. Hal ini membuat arus primer, yang menghasilkan medan 
magnet bolak-balik pada inti besi yang secara terus menerus pada arah positif dan 
negatif. Tegangan induksi seketika pada lilitan primer dapat dilihat melalui Hukum 
Faraday yaitu:
24 
LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) 
MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION 
PT BADAK NGL BONTANG 
MAULANI CANDRA (0910630076) 
JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK 
UNIVERSITAS BRAWIJAYA 
푒푝 = −푁푝 
푑∅ 
푑푡 
× 10−8푉 
Dimana =max=sin t dan max= fluksi maksimum seketika pada inti. Nilai rms 
dari tegangan dapat diekspresikan sebagai: 
푒푝 = 4,44푓푁푝퐴퐵푚푎푥 × 10−8푉 
Dimana: 
F adalah frekuensi 
Np adalah jumlah lilitan pada lilitan primer 
A adalah luas penampang inti 
Bmax adalah kerapatan fluksi maksimum 
Fluksi bolak-balik yang dihasilkan oleh lilitan primer pada inti menginduksi 
lilitan sekunder dan menghasilkan tegangan bolak-balik pada lilitan sekunder yang dapat 
ditunjukkan oleh persamaan: 
푒푠 = 4,44푓푁푝퐴퐵푚푎푥 × 10−8푉 
Dimana es adalah tegangan sekunder 
Diasumsikan bahwa lilitan sekunder terbuka (kondisi tanpa beban, Is=0) dan 
transformator dicatu dari sisi primer, arus kecil, In, akan mengalir pada lilitan primer. 
Arus ini disebut arus eksitasi dan menghasilkan fluksi bolak-balik meliputi: 
 Fluksi bersama yang melalui inti. 
 Fluksi bocor yang melalui udara. 
Dalam transformer daya komersial, fluks bocor sangat kecil dan sering 
diabaikan. Fluks bolak-balik dalam inti besi menginduksi tegangan di kumparan primer 
dan sekunder. Tegangan induksi dalam sekunder menghasilkan gaya electromotive 
karena induktansi sendiri. Menurut hukum Lenz, back emf sama dengan tegangan yang
diberikan ke kumparan primer di bawah kondisi tanpa beban. Tegangan yang digunakan 
dapat dinyatakan sebagai berikut: 
Tegangan yang digunakan = total tegangan induksi – drop resistansi pada 
25 
LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) 
MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION 
PT BADAK NGL BONTANG 
MAULANI CANDRA (0910630076) 
JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK 
UNIVERSITAS BRAWIJAYA 
kumparan primer 
Karena drop resistansi pada kumparan primer diabaikan, kita dapat menulis 
tegangan yang digunakan = tegangan terinduksi 
Ketika beban diberikan pada kumparan sekunder, arus primer yang 
proporsional akan mengalir bersesuaian dengan arus sekunder. Akibat pemberian beban 
pada transformator, perbandingan tegangan transformator akan menyimpang dari 
perbandingan jumlah lilitan kumparan primer dan sekunder. Kesalahan kecil dapat 
secara umum diabaikan pada transformator daya. Selain drop tegangan di gulungan 
primer dan sekunder, kerugian akibat arus eksitasi dan arus beban harus 
dipertimbangkan. Rugi-rugi transformator dapat dibagi dalam dua jenis: 
Rugi-rugi tembaga (I2R): Ini adalah rugi daya dalam resistansi dari kumparan 
primer dan sekunder karena arus beban dan magnetisasi dari transformer. 
Rugi Inti: Rugi daya ini dala transformer inti dan dikarenakan oleh arus eksitasi. 
Rugi inti dapat dibagi menjadi rugi-rugi arus eddy dan histerisis. Rugi-rugi arus eddy 
dikarenakan arus eddy dan arus sirkulasi kecil dalam inti, sedangkan rugi-rugi histerisis 
dikarenakan oleh ekergi yang dibutuhkan untuk meluruskan luasan dalam material inti 
magnetik. Rugi inti terus berlanjut selama transformer digunakan. 
Transformator daya dua lilitan dapat direpresentasikan sebagai diagram 
rangkaian seperti yang ditunjukkan pada gambar 2.9. Arus eksitasi pada transformator 
direpresentasikan oleh In, diperlihatkan sebagai arus yang mengalir untuk transformator 
daya pada umumnya dari 3%-6%. Untuk mnyederhanakan rangkaian ekivalen, arus 
eksitasi dapat diabaikan. Selanjutnya, diagram rangkaian ekivalen berdasarkan tegangan 
primer dan sekunder. Gambar 2.10 memberlihatkan diagram rangkaian ekivalen dari
transformator berdasarkan sisi sekunder. Beberapa kali diinginkan untuk 
merepresentasikan transformator berdasarkan vektor diagram. Vektor diagram 
diperlihatkan pada gambar 2.10 (b) berdasarkan diagram rangkaian ekivalen pada 
gambar 2.10 (a). 
26 
LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) 
MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION 
PT BADAK NGL BONTANG 
Gambar 2.9: Diagram Ekivalen Transformator 
MAULANI CANDRA (0910630076) 
JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK 
UNIVERSITAS BRAWIJAYA
27 
LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) 
MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION 
PT BADAK NGL BONTANG 
Gambar 2.10: (a) Diagram Ekivalen yang Telah Disederhanakan 
dan (b) Diagram Vektor yang Telah Disederhanakan 
MAULANI CANDRA (0910630076) 
JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK 
UNIVERSITAS BRAWIJAYA 
dari Transformator 
Gambar 2.11: Representasi Grafis dari Transformator Daya 
Penting untuk mengetahui hubungan antara tegangan transformator dan arus 
sebagai energi yang ditransformasikan dari satu level tegangan ke lainnya. Berdasarkan
transformator yang diperlihatkan pada gambar 2.11. Tegangan, arus, dan impedansi 
diekspresikan sevagai berikut: 
28 
LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) 
MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION 
PT BADAK NGL BONTANG 
MAULANI CANDRA (0910630076) 
JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK 
UNIVERSITAS BRAWIJAYA 
2.2.3.1 Hubungan Tegangan 
Berdasarkan Hukum Faraday 
2.2.3.2 Hubungan Arus 
Daya masuk = Daya keluar (transformator ideal) 
2.2.3.3 Hubungan Impedansi 
Zps didefinisikan sebagai impedansi bocor antara lilitan primer dan sekunder 
yang diukur dalam ohm dan pada lilitan primer dan sekunder dihubung singkat. Nilai 
dari Zps diberikan melalui persamaan
Zsp didefinisikan sebagai impedansi bocor antara lilitan sekunder dan primer 
yang diukur dalam ohm pada lilitan sekunder dengan lilitan sekunder dihubung singkat. 
Nilai dari Zsp diberikan melalui persamaan: 
Persamaan tegangan, arus, dan impedansi untuk transformator dapat ditulis ulang 
29 
LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) 
MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION 
PT BADAK NGL BONTANG 
MAULANI CANDRA (0910630076) 
JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK 
UNIVERSITAS BRAWIJAYA 
sebagai: 
atau 
dan 
Dan sebaliknya: 
Pada umumnya, untuk transformator daya impedansi dispesifikasikan sebagai 
persentasi dibandingkan ohm sebenarnya. Persentasi impedansi dari transformator dapat 
diekspresikan sebagai: 
Persentase dari impedansi dapat diperlihatkan secara terpisah dari tegangan 
tegangan terminal dan didasarkan pada rating KVA dari transformator diagram 
rangkaian ekivalent dari persentase dasar diperlihatkan pada gambar 2.12.
30 
LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) 
MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION 
PT BADAK NGL BONTANG 
Gambar 2.12: Diagram Rangkaian Ekivalen dari persentase dasar. 
MAULANI CANDRA (0910630076) 
JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK 
UNIVERSITAS BRAWIJAYA 
2.2.4 Pemeliharaan Preventif Transformator 
Maksud dari bagian ini adalah untuk menjelaskan prosedur praktik dari 
pemeliharaan preventif transformator. Prosedur yang direkomendasikan ditentukan 
dalam bab ini. Banyak tugas yang dilakukan selama pemeliharaan rutin dan perbaikan 
besar dari transformator. Praktek pemeliharaan yang dibahas dalam bagian ini berlaku 
untuk transformator yang belum mencapai kerusakan yang parah. Selain itu, 
rekomendasi dari prosedur pemeliharaan preventif transformator ini ditulis untuk 
kondisi rata-rata dimana transformator diperlukan pemeliharaan selama beroperasi. Hal 
yang lebih lanjut menjelaskan bahwa semua bagian yang terkait dengan pemeliharaan 
yang sesuai dengan pengalaman dalam pemeliharaan transformator. 
Praktek yang direkomendasikan dikemukakan dalam bagian ini dan sama dengan 
rekomendasi dari perusahaan peralatan untuk lebih detailnya diperlukan pembelajaran 
dan konsultasi dengan produsen. Pemeliharaan preventif transformator melibatkan 
pemeriksaan rutin, penyetelan, pengujian, perbaikan kecil, dan petunjuk penanganan 
khusus. Selain itu, Pengoprasian yang bebas dari masalah pada peralatan selama masa 
pakai tergantung pada instalasi yang tepat, operasi, dan pemeliharaan, yang akan 
dibahas dalam Bagian 2.2.7. 
2.2.4.1 Instalasi Transformator dan Perawatan 
Kehandalan operasi dari transformator tergantung pada instalasi yang benar, 
pemuatan, dan pemeliharaan, serta pada desain yang tepat dan konstruksinya.
Sebagaimana dengan semua peralatan listrik, bila mengabaikan salah satu dari 
persyaratan dasar peralatan listrik dapat menyebabkan masalah serius. Tujuan dari 
pemeliharaan transformator dapat digambarkan sebagai berikut: 
31 
LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) 
MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION 
PT BADAK NGL BONTANG 
MAULANI CANDRA (0910630076) 
JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK 
UNIVERSITAS BRAWIJAYA 
2.2.4.2 Perawatan Biasa 
Prinsipnya melakukan perawatan berupa melakukan perbaikan, pengaturan alat, 
dan penggantian komponen yang diperlukan. 
2.2.4.3 Perawatan 
Prinsipnya adalah melakukan pemeliharaan preventif, pemeliharaan prediktif, 
dan pemeliharaan korektif. Pemeliharaan preventif berupa pemeliharaan secara 
terjadwal dan pengujian secara teratur. Pemeliharaan prediktif berupa pemeliharaan 
dengan cara pemantauan alat dan pengujian, sedangkan pemeliharaan korektif berupa 
pemeliharaan dengan memperbaiki dan memulihkan kondisi sebuah transformator ke 
kondisi aslinya ketika kondisi mengalami penurunan. 
Tujuan pemeliharaan pelindung transformator adalah untuk mengontrol dan 
mencegah kerusakan isolasi pada minyak dan belitan transformator. Kandungan mineral 
pada minyak dan isolasi kertas pada belitan transformator dipengaruhi oleh kelembaban, 
oksigen, suhu, dan unsur katalitik lainnya seperti tembaga, besi, stres listrik, dan 
sebagainya. Hasil akhirnya adalah bahwa oksidasi terjadi dalam minyak yang 
menyebabkan sludging dari transformator. Dalam tempat yang disegel masuknya uap air 
melalui kebocoran udara harus dicegah, karena kelembaban akan mengurangi kekuatan 
dielektrik dari a minyak dan sistem isolasi pada belitan. Selain itu, pemanasan yang 
berlebihan dari transformator akan menyebabkan isolasi kertas rusak yang menghasilkan 
kelembaban (yaitu, memecah serat selulosa yang digunakan dalam membebaskan atom 
hidrogen dan oksigen yang bergabung untuk membentuk H2O). Peningkatan 
kelembaban pada isolasi kertas tidak hanya mengurangi kekuatan isolasi, tetapi juga 
mengakibatkan peningkatan suhu dan penurunan kekuatan dielektrik. 
Langkah pertama adalah membangun desain transformator untuk menjaga 
kelembaban dan oksigen diluar transformator, Langkah berikutnya adalah dengan
mengoperasikan transformator pada rating temperaturnya. Selain itu, tingkat kerusakan 
harus dikontrol dengan memonitor dan menguji sistem isolasi transformator secara 
berkala, dan mengambil tindakan korektif untuk mengembalikan transformator ke 
kondisi aslinya. Prinsipnya dapat diringkas sebagai berikut: 
32 
LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) 
MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION 
PT BADAK NGL BONTANG 
1. Pengontrolan suhu dari transformator 
2. Memeriksa dan memelihara transformator dengan peralatan tambahan 
3. Menguji dan memelihara sistem isolasi transformator 
4. Menjaga isolasi bushing transformator 
5. Menjaga lapisan pelindung transformator 
MAULANI CANDRA (0910630076) 
JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK 
UNIVERSITAS BRAWIJAYA 
2.2.5 Transformator Tipe Kering 
2.2.5.1 Pemasangan 
Faktor-faktor yang harus dingat-ingat dalam menemukan transformator tipe 
kering adalah aksesibilitas, ventilasi, dan kondisi udara. Transformator tipe kering 
(Gambar 2.13) biasanya didesain untuk aplikasi dalam ruangan di tempat yang kering. 
Transformator tipe kering akan beroperasi dengan handal di mana kelembaban mungkin 
tinggi, tetapi di bawah kondisi tersebut mungkin perlu mengambil tindakan preventif 
untuk menjaga transformator tetap kering apabila transformator ditutup untuk waktu 
yang cukup lama. Lokasi di mana ada air menetes harus dihindari, Jika tidak 
memungkinkan, maka perlindungan yang sesuai harus disediakan untuk mencegah air 
memasuki tarfo. Harus dilakukan tindakan preventif untuk menjaga terhadap tetesan air, 
seperti yang mungkin terjadi bila jendela yang terbuka. Celah udara yang cukup sangat 
penting untuk pendinginan transformator. Udara yang disaring dapat mengurangi 
perawatan jika lokasi ini terdapat masalah tertentu. Ketika transformator dipasang pada 
ruang terbatas, celah udara yang cukup harus disediakan untuk menahan suhu udara 
dalam batas yang ditentukan ketika diukur. Hal tersebut biasanya akan memerlukan 
minimal 100 ft3 udara/menit/(kW) dari rugi-rugi transformator. Luas celah udara yang 
diperlukan tergantung pada tinggi dari lemari besi. Untuk pendinginan dari 
transformator, luas efektif yang diperlukan harus minimal 1 ft untuk setiap inlet dan
outlet per 100 kVA dari kapasitas rating transformator, setelah dikurangi daerah yang 
ditempati oleh layar, kisi-kisi, atau louver. 
33 
LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) 
MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION 
PT BADAK NGL BONTANG 
Gambar 2.13: Transformator Tipe Kering Berventilasi dengan Penutup Depan untuk 
memperlihatkan perakitan lilitan-inti. 
MAULANI CANDRA (0910630076) 
JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK 
UNIVERSITAS BRAWIJAYA 
2.2.5.2 Pemeriksaan 
Pada transformator yang baru seharusnya dilakukan pemeriksaan untuk 
memastikan bila terjadi kerusakan selama pengiriman. Pemeriksaan harus dilakukan 
sebelum mengeluarkan transformator dari mobil atau truk, dan apabila terdapat indikasi 
kecacatan pada transformator maka kita seharusnya meminta ganti rugi dan 
memberitahu produsen transformator. 
Selanjutnya menghilangkan penutup pada transformator, dan memeriksa koneksi 
yang kendor, keretakan porselin pada isolasi, kotoran dan benda asing, maupun 
kelembapan. Tindakan korektif harus diambil bila diperlukan. Sebelum dipindahkan 
atau apabila transformator disimpan dan belum dipasang pada instalasi, maka proses 
pengecekan ini dilakukan berulang-ulang. 
Setelah melakukan semua prosedur pengecekan, transformator harus diperiksa 
secara menyeluruh. Sebelum dipasang pada instalasi, motor, relay suhu, dan perangkat 
tambahan lainnya harus diperiksa. Semua koneksi penghubung harus diperiksa bila ada 
yang kendur, dan bila ada koneksi yang kendur maka harus dikencangkan sebelung
transformator dioperasikan. Body dan inti dari transformator seharusnya bersifat tetap 
dan diketanahkan. 
34 
LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) 
MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION 
PT BADAK NGL BONTANG 
MAULANI CANDRA (0910630076) 
JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK 
UNIVERSITAS BRAWIJAYA 
2.2.5.3 Pengujian yang Dianjurkan 
Setelah transformator dipasang pada instalasi listrik, tes-tes yang dianjurkan 
berikut yang harusnya dilakukan : 
Tes isolasi resistance (IR), tes ini bertujuan untuk membandingkan nilai isolasi 
yang diinginkan dan menentukan kesesuaian transformator dalam memberikan energy 
dan penerapan tes tegangan tinggi. Tes IR harus dilakukan segera sebelum transformator 
dioperasikan. 
Nilai-nilai tes IR, pada suhu pabrik 20°C sekitar 1000 MOhm, atau sama dengan 
atau lebih besar dari nilai yang ditampilkan dalam Tabel 5.4. Rumus berikut dapat 
digunakan untuk menghitung nilai IR pada transformator satu fasa atau tiga fasa : 
Dimana : 
C = bernilai 30 pada suhupengukuran 20°C 
E= rating tegangan dari belitan yang diuji 
kVA = kapasitas rating daya pada belitan 
Tabel 2.1: Nilai IR dari Tranformator Tipe Kering
Tes Indeks Polaritas (PI) Tas ini merupakan pengembangan tes IR dimana dalam 
tes ini, dua kali dilakukan pengukuran IR, pertama pada 1 menit dan kedua pada 10 
menit. Kemudian dihitung rasio keduanya dari pengujian 10 menit dan 1 menit. Tes ini 
untuk memberikan nilai penyerapan dielektrik. Seharusnya ditentukan tes PI untuk 
belitan-belitan dan belitan-ground. Nilai tes PI dibawah 2 merupakan indikasi dari 
kerusakan isolasi. 
Tes Tegangan Tinggi AC (dielektrik): Tes dielektrik ini memberikan tekanan 
pada isolasi karena tegangan uji dielektrik lebih tinggi dari tegangan operasi normal. 
Sebelumnya tes IR harus berhasil sebelum melakukan tes dielektrik untuk mencegah 
kemungkinan kegagalan transformator akibat kelembaban. Besar tegangan uji tidak 
boleh melebihi 75% dari nilai tes pabrik. Seting nilai tes teganggan tinggi harus dibuat 
ber-variable untuk mencegah kemungkinan terjadinya perubahan tegangan uji. Nilai-nilai 
35 
LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) 
MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION 
PT BADAK NGL BONTANG 
MAULANI CANDRA (0910630076) 
JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK 
UNIVERSITAS BRAWIJAYA 
Tes dielektrik ditunjukkan pada Tabel 2.5.
Tabel 2.2: Nilai Pengujian Dielektrik yang Diterima dan Pemeliharaan Periodik dari 
Tes Rasio Belitan Transformator (TTR) : Tes TTR digunakan untuk menentukan 
rasio belitan transformator. Tes ini mengukur jumlah lilitan dari belitan primer terhadap 
jumlah putaran belitan sekunder. Nilai-nilai yang dapat diterima dari tes TTR harus 
tidak lebih besar dari 0,5% dibandingkan dengan nilai-nilai dihitung. 
Tes Isolasi Faktor Daya (PF) : Tes ini mengukur lossesrugi-rugi daya dalam 
isolasi yang diuji. Tes ini berhubungan masalah korona. Tes ini dapat dilakukan sebagai 
tes tip-up PF untuk transformator tipe kering untuk membedakan penyebab losses 
sebagai akibat antara kelembaban atau karbonisasi. 
36 
LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) 
MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION 
PT BADAK NGL BONTANG 
Transformator Tipe Kering. 
MAULANI CANDRA (0910630076) 
JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK 
UNIVERSITAS BRAWIJAYA 
2.2.5.4 Perawatan 
Seperti peralatan listrik yang lain, transformator juga membutuhkan perawatan 
secara berkala untuk menjamin kehandalannya. Pengecekan harus dilakukan secara 
berkala dan perlu dilakukan tindakan untuk menjamin kehandalan operasi dari 
transformator. Rentang pengecekan transformator tergantung pada kondisi operasinya. 
Untuk keadaan normal, pengecekan dilakukan sekali dalam setahun atau dalam jangka 
waktu yang lama. Namun untuk transformator yang tercemar debu dan unsur kimia, 
pengecekan dilakukan 3 atau 6 bulan. Biasanya, setelah pengecekan pertama, jadwal 
pengecekan yang tetap dapat diatur tergantung kondisi transformator.
Pengecekan terhadap bahan pengotor pada permukaan isolasi harus dilakukan 
begitu juga keadaan berkarat, korosi, dan cat harus diperiksa dan bila perlu diambil 
tindakan perbaikan. Kipas, motor, dan perangkat tambahan lainnya harus diperiksa dan 
diservis. 
Pembersihan: Jika jumlah kotoran pada belitan transformator atau isolasi 
bertambah banyak perlu dilakukan pembersihan, untuk menjaga sirkulasi udara dan 
menjaga isolasi dari kerusakan. Belitan transformator dapat dibersihkan dengan vacuum 
cleaner, blower, atau dengan udara terkompresi. Penggunaan vacuum cleaner dilakukan 
sebagai langkah pertama dalam membersihkan belitan, kemudian dilanjutkan dengan 
penggunaan kompresi udara atau nitrogen. Penggunaan pembersih cair tidak dianjurkan 
karena dapat merusak bahan isolasi. 
Tes untuk pemeliharaan rutin: Berikut ini adalah tes yang dilakukan untuk 
37 
LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) 
MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION 
PT BADAK NGL BONTANG 
MAULANI CANDRA (0910630076) 
JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK 
UNIVERSITAS BRAWIJAYA 
pemeliharaan rutin dari transformator tipe kering : 
 Tes IR pada winding-to-winding dan winding-to-ground. 
 Tes penyerapan dielektrik harus dibuat winding-to-winding dan winding-to-ground 
selama 10 menit. Batas dari nilai PI yang diijinkan harus di atas 2.0. 
 Tes rasio putaran (TTR) harus dilakukan sama seperti tes yang dianjurkan. 
 Tes teganggan lebih AC harus dilakukan pada semua range tegangan windings-to- 
ground. Tes ini untuk pengujian perawatan rutin. Nilai yang direkomendasikan 
dari tes tegangan ditunjukkan pada Tabel 5.4. 
 Tes Isolasi PF dilakukan untuk hubungan winding-to-ground dan winding-to-winding.. 
Nilai yang direkomendasikan kurang dari 3%. 
2.2.5.5 Metode Drying-Out 
Untuk tujuan pengeringan (drying out), tranfo dapat dianggap peralatan yang 
terdiri dari inti dan kumparan. Bila diperlukan pengeringan transformator sebelum 
diopresikan atau setelah lama tidak operasikan sehingga transformator dalam kondisi
kelembaban yang relatif tinggi, sehingga salah satu metode pengeringan transformator 
berikut dapat digunakan. 
38 
LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) 
MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION 
PT BADAK NGL BONTANG 
MAULANI CANDRA (0910630076) 
JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK 
UNIVERSITAS BRAWIJAYA 
• External heat 
• Internal heat 
• External and internal heat 
Pengeringan dengan External heat : External heat dapat diterapkan pada 
transformator dengan metode berikut: 
 Dengan mengarahkan udara panas ke dalam celah udara yang berada di bawah 
case transformator. 
 Dengan menempatkan inti dan kumparan dalam kotak tidak mudah terbakar dan 
terdapat celah lubang diatas dan dibawah untuk masuknya udara panas. 
 Dengan meletakkan lampu pijar di dekat transformator 
Pengeringan dengan Internal heat: Metode ini relatif lambat dan dijadikan 
alternatif jika dua metode yang lain tidak mengatasi. Transformator harus diletakkan 
pada posisi dimana memungkinkan sirkulasi bebas dari udara dapat mengair melalui 
kumparan dari bagian bawah ke bagian atas transformator. Salah satu belitan harus di 
hubung singkatkan, dan diberi tegangan yang cukup pada frekuensi normal pada belitan 
kumparan yang lain untuk pendekatan arus normal. 
Pengeringan dengan External dan Internal heat : metode Ini merupakan 
kombinasi dari kedua metode-metode yang telah dijelaskan sebelumnya dan sejauh ini 
merupakan metode yang tercepat. Inti dari transformator dan belitan kumparan harus 
diletakkan dalam box yang tidak mudah terbakar, External heat diberikan pada 
transformator seperti yang dijelaskan pada metode pertama, dan arus sirkulasi beredar 
melalui kumparan seperti yang dijelaskan dalam metode kedua. Disarankan bahwa suhu 
pemanas tidak melebihi yang disebutkan dalam dua metode sebelumnya. Waktu 
pengeringan tergantung pada kondisi transformator, ukuran, tegangan, jumlah uap air 
yang diserap, dan metode pengeringan yang digunakan.
39 
LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) 
MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION 
PT BADAK NGL BONTANG 
MAULANI CANDRA (0910630076) 
JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK 
UNIVERSITAS BRAWIJAYA 
2.2.6 Transformator Tipe Basah 
2.2.6.1 Pemasangan 
Transformator harus dipasang sesuai dengan rekomendasi dari National Fire 
Protection Association (NFPA) Dokumen 70, NEC Pasal 450. Karena larangan askarel 
dalam penggunaan cairan sebagai isolasi pada transformator seperti silikon, RTemp, dan 
lainnya. Cairan ini baru memiliki titik api tidak kurang dari 300 ° C dan NEC telah 
mengklasifikasikan sebagai cairan ini mudah terbakar. Minyak yang mengisi 
transformator, dan jika transformator sudah terpasang dalam ruangan harus dimasukkan 
dalam lemari besi yang tahan api sesuai dengan NEC Pasal 450. Bila transformator 
terletak di luar ruangan, transformator biasanya dipasang dengan lubang minyak dan 
diisi dengan kerikil atau batu untuk menahan minyak jika terjadi tumpahan. Kerikil dan 
batu dapat digunakan untuk menghambat minyak untuk mencegah kebakaran pada case 
transformator (lihat Gambar 2.14). Jadi ketika kita memasang transformator yang berisi 
cairan isolasi harus memperhatikan peraturan dan NEC . 
Gambar 2.14: Transformator Basah Tiga Fasa
40 
LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) 
MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION 
PT BADAK NGL BONTANG 
MAULANI CANDRA (0910630076) 
JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK 
UNIVERSITAS BRAWIJAYA 
2.2.6.2 Pengecekan 
Pada transformator yang baru seharusnya dilakukan pemeriksaan untuk 
memastikan bila terjadi kerusakan selama pengiriman. Pemeriksaan harus dilakukan 
sebelum mengeluarkan transformator dari mobil atau truk pengiriman, untuk melihat. 
Selanjutnya pengecekan secara internal dilakukan dengan menghilangkan penutup pada 
transformator, dan memeriksa koneksi yang kendor, keretakan porselin pada isolasi, 
kotoran dan benda asing, maupun kelembapan. Jika minyak atau cairan transformator 
sudah dipasang di pabriknya, maka sebaiknya kita memeriksa transformator dari 
kebocoran. Selain itu pemeriksaan tekanan gas positif dilakukan jika transformator 
dilengkapi dengan gas inert. Pengecekan harus mencakup pemeriksaan case 
transformator, bushing, jangkar dan, kabel grounding, saluran air, penutup 
transformator, katup, dan peralatan lainnya yang dikirim bersama transformator. Apabila 
pemeriksaan internal transformator selesai. pastikan terdapat saluran celah udara pada 
tangki transformator sebelum tangki terpasang pada transformator. Perlu perhatian 
penting bahwa harus ada kandungan oksigen paling sedikit 16% sebelum cairan 
dimasukkan pada tangki transformator. Penutup tidak boleh dibuka dalam keadaan 
basah, karena cairan transformator tidak boleh terkontaminasi dengan udara di atmosfer 
ketika kelembaban relatif di atas 65%. 
2.2.6.3 Pengujian yang Dianjurkan 
Sebelum transformator dipasang pada instalasi listrik, tes-tes yang dianjurkan 
berikut yang harusnya dilakukan : 
Tes IR : Tes IR bertujuan untuk menentukan apakah transformator dalam kondisi 
baik dan juga dijadikan acuan untuk tes transformator kedepannya. Nilai-nilai IR yang 
diukur merupakan fungsi temperatur, apakah kumparan direndam dalam cairan 
transformator atau tidak, atau apakah belitan dalam kondisi dingin atau panas. Nilai 
yang diukur harus dikoreksi sampai 20 ° C dengan mengalikannya dengan faktor 
koreksi. Dalam melakukan tes IR menggunakan alat megohmmeter yang biasa disebut 
Megger, dimana nilai IR yang terukur dalam satuan jutaan ohm (atau megohms). 
Megger memiliki rentang tegangan minimum yang ditunjukkan pada Tabel 2.3 (nilai
yang direkomendasikan untuk rating tegangan dari berbagai transformer). Nation 
Electrical Testing Association (NETA) menunjukkan nilai-nilai yang digunakan untuk 
tes yang dianjurkan dan pemeliharaan transformator (Tabel 2.2). 
Nilai tes IR harus dibandingkan dengan nilai tes IR yang dilakukan pabrik. 
Apabila tidak ada data yang dapat dijadikan acuan dari tes sebelumnya, rumus berikut 
dapat digunakan untuk transformator satu fasa, atau transformator tiga fasa dengan satu 
belitan. 
41 
LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) 
MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION 
PT BADAK NGL BONTANG 
MAULANI CANDRA (0910630076) 
JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK 
UNIVERSITAS BRAWIJAYA 
Dimana : 
C = bernilai 30 pada pada suhu pengukuran 20 ° C (C = 0,8 untuk tes kumparan 
dengan kumparan lainnya atau kumparan yang digrounkan) 
E adalah rating tegangan dari belitan yang diuji 
kVA adalah kapasitas rating dari belitan yang diuji 
Jika transformator yang diuji adalah jenis transformator tiga fasa maka : 
E adalah rating tegangan dari salah satu fase kumparan 
kVA adalah kapasitas rating belitan tiga fasa dari transformator yang diuji yang 
diuji 
Tes dielektrik cairan isolasi : Cairan isolasi harus di tes dengan cara diambil 
samplenya sesuai standar dengan ASTM D-923 dan tes ini bertujuan untuk menentukan 
kekuatan dielektrik-nya, keasaman, kelembaban, interfacial tension, warna, dan PF. Tes 
ini dilakukan untuk memastikan bahwa cairan isolasi tidak berada pada level yang 
bervariasi atau untuk memastikan kekuatan dielektrik belum turun karena
terkontaminasi benda asing. Sampel minyak dan Rtemp diambil dari bagian bawah 
tangki, sedangkan sampel untuk askarel dan silikon diambil dari bagian atas tangki. 
Tes TTR : Tes TTR ini bertujuan untuk memastikan bahwa rasio putaran 
transformator dalam keadaan yang handal, dimana tidak ada kumparan transformator 
yang sort circuit. Pada dasarnya tes ini membandingkan jumlah putaran di kumparan 1 
dengan jumlah putaran pada kumparan 2. Tes ini dilakukan pada setian tap pada 
transformator yang dilengkapi dengan tap changers. Tes TTR ini juga dapat digunakan 
untuk memeriksa polaritas transformator. Nilai dari tes TTR ini yang masih dapat 
ditoleransi tidak boleh lebih besar dari 0,5% dibandingkan nilai yang dihitung pada 
(lihat Bagian 2.2.7.1). 
Tes Hi-pot : Tes Hi-pot ( tes ini juga disebut tes tegangan tinggi) dilakukan pada 
semua rentang teganggan tinggi dan rendah kumparan pada transformator ke ground. 
Baik tegangan AC maupun DC dapat digunakan pada tes ini. Namun dalam praktiknya 
baik itu tegangan AC maupun DC tidak melebihi 34 kV, untuk transformator diatas 
34kV, tes tegangan tinggi AC yang dapat digunakan. Tegangan AC yang diberikan pada 
transformator dengan rentang waktu 3 menit, Jika pada tes ini transformator tidak 
mengalami kegagalan dan tidak terjadi kerusakan maka transformator sudah layak 
digunakan (lihat Bagian 5.8.1). 
PF (dissipation factor) test: Tes ini seharusnya dilakukan untuk transformator 
besar. Tes ini memberikan tekanan dari tegangan pada isolasi transformator yang nilai 
42 
LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) 
MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION 
PT BADAK NGL BONTANG 
Tabel 2.3: Nilai IR dari Transformator yang Diisi Cairan 
MAULANI CANDRA (0910630076) 
JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK 
UNIVERSITAS BRAWIJAYA
tekanannya sebanding dengan tekanan yang dihasilkan pada pengoprasian normal, 
karena tes ini merupakan tes dengan teganggan AC. 
Frequency response analysis (FRA): Tes FRA ini digunakan untuk menilai 
keadaan dari komponen mekanik seperti dari kumparan dan inti pada transformator 
dengan daya yang besar. Tujuan tes ini adalah untuk mengamati peerubahan 
karakteristik fisik pada sebuah transformator yang dikarenakan terjadi kesalahan, 
pengiriman, perbaikan dan pengaruh lainya. Sinyal teganggan dengan range frekuensi 
yang lebar diberikan pada terminal transformator yang yang dicerminkan dari respon 
pengukurannya. 
43 
LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) 
MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION 
PT BADAK NGL BONTANG 
MAULANI CANDRA (0910630076) 
JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK 
UNIVERSITAS BRAWIJAYA 
2.2.6.4 Perawatan 
Seperti peralatan listrik lain, transformer membutuhkan perawatan dari waktu ke 
waktu untuk menjamin keberhasilan operasi. Inspeksi harus dilakukan secara berkala 
dan tindakan korektif dilakukan jika diperlukan untuk menjamin layanan yang paling 
memuaskan dari peralatan ini. Frekuensi inspeksi tergantung pada kondisi operasi. 
Untuk lokasi yang bersih dan kering, inspeksi setiap tahun, atau setelah jangka waktu 
lama, mungkin sudah cukup. Namun, untuk lokasi lainnya, seperti mungkin ditemui di 
mana udara yang tercemar dengan asap debu orchemical, inspeksi dengan interval 3 atau 
6 bulan mungkin diperlukan. Biasanya, setelah periode beberapa pemeriksaan pertama, 
jadwal pasti dapat diatur berdasarkan kondisi yang ada. 
Pembersihan: Jika akumulasi berlebihan dari kotoran ditemukan pada gulungan 
transformator atau isolator ketika transformator diperiksa, kotoran harus dihapus untuk 
memungkinkan sirkulasi bebas dari udara dan untuk menjaga terhadap kemungkinan 
kerusakan isolasi. Perhatian khusus harus diberikan untuk membersihkan ujung atas dan 
bawah belitan dan untuk membersihkan saluran ventilasi. 
2.2.6.5 Pemeliharaan 
Tujuan pemeliharaan transformator adalah untuk menjaga terhadap kerusakan 
dengan mendeteksi penyebab potensial dan menghilangkan mereka. Oleh karena itu, 
pemeliharaan transformator berkala akan memastikan bebas masalah operasi selama
bertahun-tahun. Transformator merupakan perangkat yang sangat sederhana, kasar dan 
sering diabaikan dan dilupakan sampai kegagalan transformator terjadi. Namun, 
transformator adalah link yang penting dalam sistem distribusi listrik dan harus 
diberikan perawatan yang tepat dan perhatian. Jadwal pemeliharaan transformator harus 
ditentukan sesuai dengan sifat kritis atau tidak kritis dari transformator dan beban yang 
terhubung. Transformer listrik yang besar jelas lebih penting daripada pencahayaan 
kecil dan transformator distribusi, dengan demikian mereka membutuhkan perhatian 
lebih dan perawatan. Pemeliharaan dari transformator harus mencakup pemeriksaan 
rutin dan perbaikan, pemeliharaan transformator cair dan pengujian, pemeliharaan 
isolasi belitan transformator dan pengujian, dan setiap pemeliharaan khusus lainnya 
yang dianjurkan oleh produsen transformator. Sebuah pemeliharaan dan panduan 
pengujian transformator daya dengan frekuensi yang direkomendasikan diberikan pada 
Tabel 2.7. 
44 
LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) 
MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION 
PT BADAK NGL BONTANG 
Tabel 2.4: Daftar Pengecekan Inspeksi dan Pemeliharaan Transformator 
MAULANI CANDRA (0910630076) 
JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK 
UNIVERSITAS BRAWIJAYA
Pemeriksaan rutin dan perbaikan: inspeksi rutin dan perbaikan transformator 
melibatkan pengamatan visual dari kondisi operasi transformator dan perbaikan yang 
diperlukan. Frekuensi pengamatan ini tergantung pada pentingnya transformator, 
kondisi lingkungan, dan / atau kondisi operasi. Berbagai organisasi seperti NFPA, Neta, 
dan produsen transformator telah menerbitkan panduan untuk interval inspeksi dan apa 
yang harus memeriksa. Berikut ini adalah jadwal untuk melakukan inspeksi rutin. 
Arus beban: Pembebanan transformator menentukan pemanasan transformator. 
Suhu transformator menentukan harapan hidup, dan penting pada unit besar untuk 
memonitor beban pada setiap jam. Untuk pembebanan yang tepat dari transformator, 
45 
LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) 
MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION 
PT BADAK NGL BONTANG 
MAULANI CANDRA (0910630076) 
JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK 
UNIVERSITAS BRAWIJAYA
lihat standar ANSI C57.92 untuk transformator terendam cairan dan ANSI C57.96 untuk 
kering tipe transformator. Untuk transformator daya kecil, pembacaan dapat dilakukan 
secara harian atau mingguan. 
Tegangan: Tegangan dari transformator harus dipantau sama seperti 
arus beban. Untuk menjaga rating tegangan sekunder, wajib digunakan tegangan primer 
yang sesuai . Pembacaan tegangan dapat diambil bersama dengan 
arus beban. Pada transformator kurang penting, pembacaan tegangan dapat diambil 
setiap minggu. 
Level Cairan: level cairan penting karena tidak hanya memasok pendinginan 
medium tetapi juga isolasi dari belitan. Kehilangan cairan dapat terjadi karena 
penguapan dari cairan atau karena kebocoran. Pembacaan liquid level dapat diambil 
ketika pembacaan beban yang diambil. Cairan yang hilang dari transformator harus 
diganti segera. 
Suhu: Kemampuan pembebanan dari transformator tergantung pada 
kemampuan suhu. Suhu total transformator adalah jumlah dari 
suhu lingkungan, suhu lilitan isolasi, dan suhu hot-spot. Bila transformator dioperikan di 
atas rating suhunya dapat menyebabkan berkurangnya life time dari transformator itu 
sendiri. 
Peralatan proteksi: Proteksi transformator dasar dibuat oleh NEC. Proteksi ini 
dilengkapi dengan relay dan peralatan proteksi tambahan. Adalah penting bahwa alat 
proteksi diperiksa dan dipelihara secara teratur untuk memastikan bahwa perangkat ini 
akan beroperasi dalam kasus kerusakan atau kegagalan transformator. 
Alarm proteksi: Transformator dilengkapi dengan beberapa tipe alarm seperti 
temperatur lebih, temperatur cairan, dan temperatur tekanan. Itu semua biasanya berupa 
skalar tipe normally open yang dapat dihubungkan ke baik itu alarm atau untuk 
memutus CB. Kontak alarm dan hubungan perkabelannya seharusnya diperiksa setiap 
bulannya. 
46 
LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) 
MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION 
PT BADAK NGL BONTANG 
MAULANI CANDRA (0910630076) 
JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK 
UNIVERSITAS BRAWIJAYA
Hubungan pentanahan: Tangki transformator selalu kokoh diketanahkan untuk 
menghilangkan sengatan listrik per NEC. Sambungan ke tanah tangki transformator 
harus diperiksa apakah longgar, terputus ataupun sudah berkarat. Resistansi pentanahan 
dari sebuah GI tergantung pada jenis dan ukuran dari GI itu sendiri. Resistansi 
pentanahan sangan bervariasi dari 1 ohm untuk GI berukuran besar sampai 25 ohm 
untuk GI berukuran sangat kecil. Frekuensi dari pemeriksaan dan tes seharusnya setiap 
tahun sekali. 
Lightning Arrester: Ketika transformator dipasok dari saluran udara, Lightning 
arrester digunakan untuk melindungi transformator dari petir dan surja lainnya. Arrester 
petir harus diperiksa untuk kelonggaran, bagian yang rusak, kotoran, dan lapisan 
lainnya. Semua kotoran dan lapisan harus dibersihkan, sambungan yang longgar harus 
dikencangkan, dan bagian yang rusak diganti selama cek ini. Pemeriksaan dari arrester 
petir dan sistem grounding harus dilakukan setiap tahun. 
Perangkat pressure-relief: transformator kebanyakan dengan seal dilengkapi 
dengan perangkat pressure-relief untuk mengurangi tekanan yang berlebihan dalam 
tangki akibat busur api internal. Perangkat ini diatur untuk membuka pada tekanan 10- 
15 psi. Pemeriksaan rutin perangkat pressure-relief harus mencakup memeriksa 
kebocoran di sekitar sendi, retak diafragma, dan sejenisnya. Pemeriksaan ini harus 
dilakukan triwulanan. 
Breather: transformer memilik banyak breather baik itu tipe terbuka atau jenis 
dehidrasi. Fungsi agen dehidrasi adalah untuk mencegah kelembaban memasuki tangki 
transformator. Kebanyakan breather tipe dehidrasi mengandung gel silika, yang akan 
berubah dari biru ketika kering ke merah muda pucat saat basah. Pemeriksaan dapat 
dilakukan melalui jendela kaca yang disediakan untuk tujuan tersebut. Breather harus 
diperiksa bulanan dan agen dehidrasi diganti atau direkondisi jika ditemukan rusak atau 
basah. 
47 
LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) 
MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION 
PT BADAK NGL BONTANG 
MAULANI CANDRA (0910630076) 
JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK 
UNIVERSITAS BRAWIJAYA
Peralatan bantu: peralatan Bantu yang dibutuhkan untuk pendinginan, seperti 
kipas, minyak pompa, alat kontrol, dan kabel, harus diperiksa setiap tahun. Peralatan 
tersebut harus dibersihkan dan bagian yang rusak diganti. 
Cairan transformer: Semua cairan transformator mudah mengalami kerusakan, 
dan kontaminan utama adalah udara, kelembaban, dan panas. Kontaminan ini bereaksi 
dengan cairan transformator dan memproduksi asam dan lumpur. Asam, pada 
gilirannya, menyerang isolasi belitan, dan lapisan lumpur cenderung menurunkan 
pendinginan. Kelembaban dalam cairan transformator cenderung menurunkan kekuatan 
dielektrik dari cairan, yang dikombinasikan dengan lumpur, akan menurunkan nilai dari 
isolator flashover dan papan terminal di dalam tangki transformator. Sebagaimana 
dibahas sebelumnya, pemeriksaan rutin dari transformator diperlukan untuk menjaga 
cairan dalam keadaan bebas kontaminan. 
48 
LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) 
MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION 
PT BADAK NGL BONTANG 
MAULANI CANDRA (0910630076) 
JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK 
UNIVERSITAS BRAWIJAYA 
2.6.6 Metode Drying-Out 
Mirip dengan transformator jenis kering, cairan isolasi transformator dapat 
dianggap terdiri dari inti dan susunan koil, kecuali bahwa koil direndam dalam cairan 
isolasi. Langkah-langkah rumit yang diambil untuk mencegah dan mendeteksi 
perembesan dan peningkatan kadar air dalam transformator. Sebelum cairan 
transformator menjadi jenuh dengan air, isolasi kertas gulungan di transformator telah 
menyerap konsentrasi uap air karena afinitas yang besar untuk air. Air di isolasi kertas 
mempercepat degradasi isolasi dan menurunkan integritas listriknya. 
Distribusi uap air dalam transformator selalu dalam keadaan tidak seimbang. 
Melalui rentang yang lebih dingin dari suhu, isolasi padat gulungan transformator akan 
cenderung menyerap kelembaban lebih dari cairan transformator. Namun, ketika 
transformator dibebani, kenaikan suhu belitan akan melepas kelembaban ini. Perubahan 
akibat beban yang bervariasi dan suhu adalah konstan, terlepas dari apakah ada 
kelebihan air atau hanya jumlah yang sangat kecil kelembaban dalam transformator. 
Juga, cairan transformator seperti minyak cenderung menahan lebih banyak air dengan 
peningkatan suhu. Dengan kata lain, akan ada lebih banyak uap air dalam minyak 
transformator ketika pembebanan daripada saat dibongkar. Faktor-faktor lain, seperti
dekomposisi isolasi kertas dan kontaminan, akan cenderung menghasilkan lebih banyak 
uap air dalam cairan transformator. Ketika diperlukan untuk mengeringkan cairan 
transformer, metode berikut dapat digunakan: (1) panas saja, atau (2) panas diikuti 
dengan vakum. 
Panas saja: Metode ini melibatkan pemberian panas saja ke transformator. Salah 
satu bentuk aplikasi metode ini adalah oven pengeringan, yang bisa dilakukan di salah 
satu service shop dari produsen besar. Ketika transformator adalah 
dikeringkan di tempat ini, penting untuk memantau resistensi belitan untuk 
melihat kapan transformator, mencapai suhu oven (100 ° C-120 ° C). Pengukuran PF 
dan IR harus dilakukan pada interval sekitar 6 jam untuk melihat kapan pengeringan 
dicapai, yaitu, ketika sedikitnya empat pembacaan mempunyai nilai yang sama. 
Panas diikuti oleh vakum: Pemanasan transformator dengan cairan dapat 
dilakukan dengan menerapkan hubung singkat ke transformator atau dengan 
mengedarkan minyak panas melalui sistem luar. Seperti pada metode sebelumnya, 
pengukuran PF dan IR harus dilakukan pada interval sekitar 6 jam. Pengeringan berarti 
telah selesai ditunjukkan oleh sedikitnya empat pembacaan yang sama. metode bidang 
pengeringan mungkin melibatkan pemanasan cairan transformator, menghilangkan 
cairan, dan segera menerapkan vakum. Metode lain mungkin melibatkan menghilangkan 
cairan dan pemanasan transformator dengan sirkulasi udara panas. Setelah belitan 
mencapai 90 ° C-100 ° C maka vakum sekitar 0,5 Torr bisa diterapkan. Ketika suhu 
turun di bawah 50 ° C, pengeringan dihentikan. Panjang normal waktu untuk 
menerapkan panas dan vakum mungkin seminggu atau lebih, tergantung pada ukuran 
transformator. Setelah transformator dikeringkan dan vakum ditarik, minyak 
transformator yang telah dibersihkan dapat dimasukkan kembali ke transformator. 
Tindakan preventif untuk mengamati selama proses ini adalah sebagai berikut: 
49 
LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) 
MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION 
PT BADAK NGL BONTANG 
MAULANI CANDRA (0910630076) 
JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK 
UNIVERSITAS BRAWIJAYA 
2.2.7 Pengujian Transformator 
Transformator dapat di tes dengan tegangan AC atau DC. Secara 
keseluruhan, tegangan AC lebih sering digunakan daripada DC karena tegangan AC
dapat mensimulasikan internal stress pada transformator yang serupa saat kondisi 
pengoperasian. 
Berikut merupakan tes yang biasanya dilakukan secara rutin pada 
50 
LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) 
MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION 
PT BADAK NGL BONTANG 
MAULANI CANDRA (0910630076) 
JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK 
UNIVERSITAS BRAWIJAYA 
transformator : 
a. IR test 
b. Tes tegangan tinggi (AC atau DC) 
c. TTR test 
d. Tes polaritas 
e. Tes arus eksitasi 
f. Tes tegangan induksi 
g. Tes cairan insulasi dielektrik 
h. Tes DGA 
i. Polarization recovery voltage test 
j. Transformer core ground test 
k. Frequency response analyzer(FRA)/ sweep FRA (SFRA) 
l. Resistansi belitan DC 
2.2.7.1 Tes Tegangan Tinggi AC 
Tes tegangan tinggi AC di lakukan untuk mengevaluasi kondisi dari belitan 
transformator. Tes ini direkomendasikan pada semua tegangan, terutama di atas 
tegangan 34.5 kV. Untuk perawatan rutin transformator, tegangan yang digunakan saat 
tes harus tidak melebihi 65% dari tegangan tes pabrik. Akan tetapi, tes tegangan tinggi 
untuk perawatan rutin biasanya tidak dilakukan pada transformator karena terdapat 
kemungkinan bahwa tes dapat merusak isolasi belitan. Tes ini biasanya di lakukan untuk 
untuk uji kelayakan atau setelah memperbaiki transformator. Tegangan yang digunakan 
tidak boleh melebihi 75% dari tegangan pabrik. Ketika tes tegangan tinggi digunakan 
untuk perawatan rutin, transformator yang di tes dapat di kenai tegangan rating selama 3 
menit daripada menggunakan 65% tegangan tes pabrik.
51 
LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) 
MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION 
PT BADAK NGL BONTANG 
MAULANI CANDRA (0910630076) 
JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK 
UNIVERSITAS BRAWIJAYA 
2.2.7.2 Pengujian TTR 
Tes ini pada dasarnya digunakan untuk mendeteksi apakah tegangan dihasilkan 
pada belitan sekunder atau tidak. Jika menggunakan TTR tegangan rendah yang dengan 
sumber tenaga tangan, pada belitan tegangan rendah diberi sumber 8 V dan 
transformator referensi di bagian TTR. Belitan di sisi tegangan tinggi dan transformator 
referensi dari TTR di hubungkan melalui sebuah null detecting instrument. Setelah 
tegangan seimbang di 8 V dan alat pendeteksi menunjukkan angka 0, alat penunjuk 
mengindikasikan rasio perbandingan belitan dari transformator tersebut. 
Hasil atau informasi yang ditunjukkan tes TTR ialah sebagai berikut 
 Menunjukan rasio perbandingan jumlah belitan dan masing – masing polaritas 
dari single atau transformator 3 phasa. 
 Memastikan nameplate dari transformator, terutama pada rasio, polaritas, dan 
vektor 
 Menunjukan rasio dan polaritas (tapi tidak rating voltage) dari transformator . 
Tes termasuk penggunaan semua posisi tap pada kondisi no-load dan dengan 
beban, tap changer (LTC) jika transformator dihubungkan dengan control sudut 
fasa. Pada transformator LTC yang dihubungkan dengan pengkontrol sudut fasa, 
tes rasio dan polaritas dilakukan hanya pada posisi netral. Jika di tes pada tap 
berbeban, pembacaan dapat digunakan sebagai referensi untuk pembanding di 
kedepannya, tetapi akan menurun jika dibandingkan dengan nameplate. Tap 
pada LTC dapat di konfirmasikan dengan diberi sumber tegangan rendah 3 fasa 
dan pembacaan tengangan dan sudut fasa untuk setiap fasa. 
 Mengidentifikasi masalah pada belitan transformator, misalnya open-circuit dan 
short-circuit yang berdampak pada sensitivitas dari perbandingan jumlah belitan. 
Standart deviasi telah ditentukan di ANSI/IEEE C5.7.12.00-2006 bagian 9.1 
yang menjelaskan bahwa hasil harus berkisar kurang lebih 0.5% dari nameplate 
dengan tegangan rating yang di aplikasikan pada salah satu belitan. TTR dengan 
error 0.1% diperbolehkan menjadi penentu.
Gambar 2.15: TTR testers: (a) hand-crank TTR; (b) handheld electronic TTR; and (c) three-phase 
 Transformator di isolasi dan di tandai 
 Baca nameplate dari transformator 
 Perhatikan polaritas dan vector (phasornya) 
 Hitung perbandingan belitan untuk setiap posisi tap pada kondisi no-load dan 
52 
LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) 
MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION 
PT BADAK NGL BONTANG 
electronic TTR. (Courtesy of Megger Inc., Valley Forge, PA.) 
Berikut merupakan prosedur dari pelaksanaan tes TTR 
MAULANI CANDRA (0910630076) 
JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK 
UNIVERSITAS BRAWIJAYA 
berbeban 
2.2.7.3 Pengujian Polaritas 
Tes polaritas dapat dilakukan dengan menggunakan tes TTR pada transformator 
daya, distribusi, dan tegangan. Akan tetapi pada transformator arus tes TTR tidak dapat 
dilakukan. Tetapi menggunakan sebuah tes yang dikenal dengan sebutan kick test,
dengan member sumber melalui baterai DC dan menggunakan multimeter. Kick test 
dapat juga digunakan pada transformator daya, distribusi, dan tegangan tetapi tes TTR 
lebih sering digunakan. Rangkaian untuk kick test pada transformator arus dapat terlihat 
pada gambar 5.19. Baterai DC yang digunakan biasanya memiliki tegangan berkisar 
7.5V dan range dari multimeter di set untuk 3 V full-scale. Bagian negative dari sumber 
di hubungkan pada transformator arus di H2 dan bagian positif dibiarkan untuk 
sementara. Bagian positif dari multimeter dihubungkan pada bagian sekunder di X1 dan 
bagian negative di X2. Untuk melakukan tes ini, hubungkan bagian positif dari sumber 
ke H1 dan perhatikan skala pada multimeter. Jika skala pada multimeter menunjuk pada 
skala atas maka transformator tersebut terhubung pada subtractive polarity, jika 
menunjuk skala bawah maka terhubung pada additive polarity. 
53 
LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) 
MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION 
PT BADAK NGL BONTANG 
MAULANI CANDRA (0910630076) 
JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK 
UNIVERSITAS BRAWIJAYA 
2.2.7.4 Pengujian Potensial Induksi 
Tes ini merupakan suatu tes pembuktian dan dilakukan pada tingkat tegangan 
yang lebih tinggi daripada tegangan operasionalnya. Dalam tes ini, isolasi antar belitan 
dan isolasi antar fasa dikenai tegangan 65% dari tegangan tes pabrik dan pada frekuensi 
yang lebih tinggi dari 60 Hz, misalnya 200-300 Hz. Tes ini harus dilakukan tiap 5 tahun 
sekali atau lebih pada transformator yang besar. 
Tes tegangan induksi untuk transformator diberi sumber tegangan 
melalui salah satu belitan dan diberi tegangan 2 kali lipat tegangan normal di belitan 
tersebut selama 7200 gelombang dan durasinya tidak boleh melebihi 60 detik. 
Tabel 2.5: Frequency versus Duration of Test 
Frequency (Hz) Duration (s) 
120 and less 60 
180 40 
240 30 
300 20 
400 18
Ketika tes ini dilakukan pada transformator, frekuensi dari tegangan yang 
diberikan seharusnya cukup tinggi untuk mencegah arus dari transformator yang di uji 
melebihi 30% dari arus ratingnya. Biasanya untuk menguji peralatan yang menggunakan 
frekeuensi 60 Hz digunakan frekuensi sebesar 120 Hz. 
Ketika digunakan frekuensi yang lebih tinggi dari 120 Hz, resiko dari tes ini 
secara abnormal meningkat dengan pesat dan hal tersebut menyebabkan waktu 
pengujian harus di persingkat seperti pada table 5.10. 
Tegangan awal harus bernilai seperempat atau kurang dari tegangan penuh dan 
secara bertahap di tingkatkan dalam waktu tidak lebih dari 15 detik. Setelah diuji selama 
waktu yang tertera pada tabel 5.10, nilai tegangan harus diturunkan secara perlahan 
(tidak boleh lebih dari 5 detik) ke seperempat atau kurang dari nilai penuh, dan setelah 
itu sirkuitnya di open. 
Saat menguji transformator dengan sebuah belitan yang di ketanahkan untuk 
pengoperasian pada suatu ground-netral system, kewaspadaan dan pengawasan harus 
diperketat untuk menghindari tekanan elektro statis yang tinggi di antara belitan lain dan 
ground. 
Jika transformator memiliki salah satu belitan sisi tegangan tinggi di tanahkan 
ketika tes induksi tegangan, pentanahan dari setiap belitan dapat di buat pada suatu titik 
tertentu dari belitan tersebut atau dari belitan transformator step-up yang digunakan 
untuk member tegangan atau hanya sekedar di hubungkan dengan tujuan memberi 
pentanahan. 
Transformator tiga fasa dapat di uji dengan tegangan satu fasa, tegangan untuk 
menguji di induksikan dari tiap line terminal ke ground atau ke line terminal yang lain. 
Bagian netral dari belitan boleh di groundkan saat tes tersebut. 
Ketika tes induksi pada belitan menghasilkan tegangan di antara terminal dari 
belitan yang lain, belitan yang lain dapat di tanahkan, Tes induksi tambahan harus 
dilakukan untuk memberikan tegangan uji di antara terminal yang di ketanahkan. 
54 
LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) 
MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION 
PT BADAK NGL BONTANG 
MAULANI CANDRA (0910630076) 
JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK 
UNIVERSITAS BRAWIJAYA
55 
LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) 
MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION 
PT BADAK NGL BONTANG 
MAULANI CANDRA (0910630076) 
JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK 
UNIVERSITAS BRAWIJAYA 
2.2.7.5 FRA 
Tes FRA dapat di lakukan sebagai respon impuls dari tes SFRA, metode impuls 
memperkirakan respon frekuensi dan respon frekuensi sapu mengukur respon dari 
tingkat frekuensi tertentu. Tes FRA dan SFRA merupakan nondestructive test yang 
digunakan untuk mengetahui deformasi (pergeseran) dari inti dan kumparan. Respon 
frekuensi sapu ialah kemajuan yang besar pada analisis kondisi transformator, tes 
tersebut medapat memberi kita visualisasi dari isi tanki transformator tanpa 
membukanya. Pengertian FRA pada umumnya adalah perbandingan dari output 
sinusoidal yang stabil dari objek yang di tes dengan input sinusoidal yang stabil. SFRA 
adalah teknik yang terbukti untuk menghasilkan pengukuran yang akurat dan presisi. Di 
antara konfigurasi geometris dari belitan dan inti, serta jaringan impedansi yang disusun 
seri dan paralel sebenarnya terdapat suatu hubungan. Jaringan ini dapat di identifikasi 
karena jaringan tersebut memiliki transfer function yang bergantung pada frekuensi. Tes 
FRA dengan metode respon frekuensi sapu menggunakan alat analisis jaringan untuk 
menentukan transfer functionnya. Perubahan pada konfigurasi geometris dapat 
mengubah jaringan impedansi dan berakibat berubahnya transfer functionnya, hal 
tersebut mengakibatkan kegagalan dapat di identifikasi. Masalah mekanis yang biasanya 
terdeteksi pada transformator dengan tes FRA adalah : 
 Pergeseran inti 
 Pergeseran belitan atau deformasi belitan 
 Pentanahan inti yang rusak 
 Kerusakan sebagian pada belitan 
 Tertekuknya hoop 
 Patah atau kendornya penjepit 
 Belitan yang open atau short circuit 
2.2.7.6 DC Resistansi Lilitan 
Tes ini mengukur resistansi DC dari kabel transformator dan belitannya dengan 
menggunakan ohmmeter atau jembatan Kelvin. Resistansi belitan dapat berubah karena 
hubung singkat di antara belitan, belitan longgar, bahkan karena memburuknya
hubungan di tap changer. Salah satu masalah yang berhubungan dengan pengukuran 
resistansi DC pada transformator ialah bagian induktif harus di energisasikan. Bagian 
induktif harus termuati dan di stabilkan agar dapat menghasilkan pembacaan yang 
akurat. Pengukuran harus dilakukan pada setiap posisi tap changer (jika ada) dan 
dibandingkan dengan hasil pengukuran sebelumnya atau hasil tes pabrik. Selisih dari 
hasil pengukuran di lapangan dengan hasil tes pabrik harus kurang dari 2% untuk 
kriteria penerimaan. Jika lebih dari kriteria penerimaan, terdapat kemungkinan terjadi 
hubung singkat pada belitan, sendi yang lemah, atau penghubung tap changer yang 
buruk. Tes ini harus dilakukan ketika tes kelayakan dan ketika tes perawatan lain 
dilakukan. 
56 
LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) 
MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION 
PT BADAK NGL BONTANG 
MAULANI CANDRA (0910630076) 
JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK 
UNIVERSITAS BRAWIJAYA 
2.2.7.7 Pengujian Transformator Core Ground 
Pengukuran IR dilakukan untuk menentukan adanya pentanahan pada inti yang 
tidak disengaja. Pada umumnya, inti yangn berlapis dari transformator daya terisolasi 
dari ground, dan secara sengaja di ketanahkan pada satu titik. Biasanya titik ini dapat di 
akses dari bagian atas transformator, entah itu melewati bushing yang kecil atau di 
belakang tutup manhole. 
2.2.7.8 Polarization Recovery Voltage Test 
Sistem isolasi transformator merupakan gabungan dari dua materi isolasi, yaitu 
cellulose fiber (kertas) dan minyak isolasi. 
Gambar 2.16: IR tester (megohmmeter). (Courtesy of Megger Inc., Valley Forge, PA.) 
Struktur ini menunjukan efek polarisasi pemuatan ruang yang mana sebagian
besar dipengaruhi oleh kelembapan dan umur produk. Hal tersebut menyebabkan 
pengurangan dari time konstan. Time constant yang dihasilkan oleh polarisasi pemuatan 
ruang melebihi 10 ms, dan pada isolasi baru yang kering dapat mencapai 1000 s. 
Gambar 2.17a menunjukan suatu RVM (recovery voltage meter). Saklar S1 di 
tutup selama tc dan sumber tegangan DC U di berikan pada tegangan tertentu ke 
kapasitor (objek yang di tes), saklar S1 kemudian di buka dan saklar S2 ditutup selama 
td (biasanya td = tc/2). Bagian dari kapasitor yang termuati terdisipasi lalu saklar S2 di 
buka dan sisa dari muatan apasitor menghasilkan tegangan di bagian elektroda dari 
kapasitor (gambar 5.23b). 
Terdapat dua parameter yaitu tegangan pembalik pada nilai maksimum (Vmax) 
dan initial slope (tan d). Jika tc dan td meningkat dari nilai mula yang kecil, maka akan 
terjadi perubahan nilai pada Vmax dan tan d pada setiap perubahan tc. 
Gambar 2.17c menunjukan perubahan dari Vmax dengan tc; dapat dilihat bahwa 
kurva Vmax/tc berada pada pincak saat mencapai nilai time constant. Hasil ini 
menunjukan bahwa kurva Vmax/tc juga menunjukan spektrum polarisasi dengan nilai 
maksimum pada time constant isolasi. 
57 
LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) 
MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION 
PT BADAK NGL BONTANG 
MAULANI CANDRA (0910630076) 
JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK 
UNIVERSITAS BRAWIJAYA
Gambar 2.17: (a) Prinsip Rangkaian Pengukuran tegangan recovery dari Waktu tc; (b) Siklus 
Pengukuran RVM dan kuantitas perekaman selama satu siklus; dan (c) tegangan recovery 
58 
LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) 
MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION 
PT BADAK NGL BONTANG 
V sebagai fungsi waktu tc. 
MAULANI CANDRA (0910630076) 
JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK 
UNIVERSITAS BRAWIJAYA 
2.3 Reaktor 
2.3.1 Definisi 
Pada intinya reaktor adalah induktor. Secara fisik ini adalah koil kabel yang 
didalamnya terdapat medan magnet karena aliran arus listrik yang melewati koil 
tersebut. Ketika di energize gaya magnet yang terbentuk menekan aliran listrik yang 
melewatinya sehingga arus dapat disesuaikan dengan kebutuhan dan tidak berlebih 
sehingga arus dapat disesuaikan dengan kebutuhan dan tidak berlebihan sehingga arus 
yang keluar dari reaktor aman untuk peralatan listrik. 
Sebuah loop sederhana pada kabel akan membawa sifat konduktor. Ketika 
semakin banyak loop-nya maka akan membuat nilai induktansi semakin tinggi. 
Kebanyakan bahan seperti besi ditambahkan sebagai pelindung dari belitan. Ini
memiliki efek dari pengonsentrasian fluks magnetis yang akan membuat induktor 
semakin efektif. 
59 
LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) 
MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION 
PT BADAK NGL BONTANG 
MAULANI CANDRA (0910630076) 
JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK 
UNIVERSITAS BRAWIJAYA 
2.3.2 Tipe dari Reaktor Seri Dry-type air-core 
1. Air-core Reactor 
Sebuah reaktor yang tidak memiliki sebuah lapisan magnetis atau perisai 
magnet dan menggunakan aliran udara di sela-selanya sebagai pendingin. 
2. Iron-core Reactor 
Sebuah reaktor yang memiliki perisai besi sebagai pelindung dan 
menggunakan oli sebagai pendingin. 
3. Indoor Reactor 
Reaktor yang diletakkan dalam ruangan tertutup karena konstuksinya 
yang harus dilindungi dari cuaca luar. 
4. Outdoor Reactor 
Reaktor yang mampu bertahan dari cuaca luar 
5. Three-phase Dry-type Air-core Reactor 
Sebuah reaktor yang terdiri dari peralatan fasa tunggal yang ditumpuk 
dan aan secara magnetis terhubung. Tergantung dari aplikasi, nilai impedansinya 
dapat dimodifikasi untuk mengimbangi efek hubungan coupling. 
2.3.3 Aplikasi dari Reaktor Seri 
1. Bus Tie Reactor 
Sebuah reaktor pembatas arus untuk koneksi diantara dua bus berbeda 
atau dua bagian dari bus yang sama untuk membatasi dan melokasikan 
gangguan karena kegagalan dari bus lainnya 
2. Current Limiting Reactor 
Sebuah reaktor yang dikoneksikan seri dengan fasa konduktor untuk 
membatasi arus yang dapat mengalir pada sirkuit saat kondisi hubung singkat 
atau saat kondisi operasi, seperti switching capasitor, starting motor, 
sinkronisasi, penyetabilan bunga api, dan lain-lain. 
3. Duplex Current Limiting Reactor
Sebuah reaktor center-tapped yang digunakan pada dua cabang sirkuit 
yang disuplai dari sirkuit utama dan dimanfaatkan sedemikian rupa untuk 
menjalankan kopling negatif di bawah kondisi normal guna mengurangi 
impedansi sirkuit dan kopling positif pada kondisi gangguan untuk 
meningkatkan impedansi sirkuit. 
60 
LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) 
MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION 
PT BADAK NGL BONTANG 
MAULANI CANDRA (0910630076) 
JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK 
UNIVERSITAS BRAWIJAYA 
4. Feeder Reactor 
Sebuah reaktor pembatas arus yang terkoneksi secara seri dengan sirkuit 
feeder untukmembatasi dan melokasikan gangguan. 
5. High-voltage Power Flow 
Sebuah reaktor transmisi yang terkoneksi secara seri dengan jaringan 
transmisi yang bertujuan untuk mengoptimalisasi aliran daya dengan merubah 
reaktansi kabel. 
6. Insertion Reactor 
Sebuah reaktor yang terkoneksi sesaat ditengah hubungan terbuka dari 
sirkuit yang terganggu untuk kebutuhan sinkronisasi dan atau kebutuhan 
pengalihan tekanan transien. 
7. Load Balancing Reactor 
Sebuah reaktor yang terhubung seri yang berguna untuk memperbaiki 
divisi arus diantara tranformer paralel atau sirkuit yang memiliki nilai 
impedansi tegangan yang tidak sama dibawah kondisi steady-state dan kondisi 
short-circuit. 
8. Motor Starting reactor 
Sebuah reaktor pembatas arus yang berguna untuk membatasi arus 
starting motor. 
2.3.4 Posisi Reaktor pada Bus Bar 
2.3.4.1 Bus Coupling 
Saat terpasang pada coupling reactor akan mengurangi puncak dari hubungan 
pendek di saat pertama kali arus bangkit. 
Keuntungan:
61 
LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) 
MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION 
PT BADAK NGL BONTANG 
- Pembagian beban arus pada transformer lebih baik. 
- Mengurangi gangguan arus hubung singkat. 
- Mengurangi impedansi pada jaringan. 
- Arus short-circuit pada sumber (transformator atau generator) akan berkurang. 
MAULANI CANDRA (0910630076) 
JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK 
UNIVERSITAS BRAWIJAYA 
Kekurangan: 
- Setiap kontribusi arus dari satu incoming-feeder menjadi tidak terbatas 
Gambar 2.18: Bus Coupling 
2.3.4.2 Terpasang seri dengan incoming feeder 
Meski dirancang pada sistem untuk mengatasi arus short-circuit total, sebuah 
CLR dapat diinstal pada incoming-feeder. Pada kasus ini pula, ketika ada arus gangguan 
maka CLR akan mereduksi puncak arus gangguan di awal pembangkitan arus. 
Keuntungan: 
- Disamping sama seperti keuntungan yang terpasang coupling, arus hubung singkat 
pada feeder sumber menjadi terbatas. 
Kerugian: 
- Tingginya rugi-rugi daya dan buruknya regulasi tegangan.
62 
LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) 
MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION 
PT BADAK NGL BONTANG 
Gambar 2.19: Terpasang seri dengan incoming feeder 
MAULANI CANDRA (0910630076) 
JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK 
UNIVERSITAS BRAWIJAYA 
2.3.4.3 Terpasang seri dengan outgoing feeder 
Reaktor terpasang pada outgoing feeder yang akan mereduksi arus hubung singkat 
pada awal puncak pembangkitan arus. 
Keuntungan: 
- Reaktor yang terpasang seperti ini memiliki rugi-rugi daya yang lebih kecil dan 
regulasi tegangan yang lebih baik. 
Kerugian: 
- Biaya instalasi menjadi lebih besar karena banyak reaktor yang akan dipasang. 
Gambar 2.20: Terpasang seri dengan outgoing feeder 
2.3.4.4 Current Limiting Reaktor (CLR) 
Dalam kondisi normal reaktor akan mengalirkan arus seperti penghantar biasa 
tanpa menekan besaran arus yang melewatinya. Dengan kata lain impedansi dari reaktor 
sangat kecil dan tidak mengurangi besar arus. Namun ketika ada arus gangguan yang 
nilainya relatif sangat besar maka CLR akan bekerja mereduksi arus gangguan tersebut
dengan membangkitkan nilai impedansinya dan menjadi tahanan pada sistem yang 
menekan laju arus. 
CLR didesain berdasarkan dua parameter. Yang pertama adalah nilai induktansi 
aktual yang satuannya henri dan yang kedua adalah rating arus dari reaktor itu sendiri. 
Nilai impedansi reaktor dapat dinyatakan dengan fungsi: 
63 
LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) 
MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION 
PT BADAK NGL BONTANG 
MAULANI CANDRA (0910630076) 
JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK 
UNIVERSITAS BRAWIJAYA 
푍푡푟 =  퐿 
푍푡푟 = (2 푓)퐿 
푍푡푟 = (2 × 3.14 × 50)퐿 
푍푡푟 = 314퐿 
Dimana: Z = impedansi (ohm) 
L = induktansi (henri) 
f = frekuensi (hertz) 
Besarnya proteksi oleh CLR tergantung pada rasio T/R yang besarnya ditentukan 
dengan: 
푍푡푟 = 
푅푎푡푒푑 푃푟푖푚푎푟푦 푉표푙푡푎푔푒 
푅푎푡푒푑 푃푟푖푚푎푟푦 퐶푢푟푟푒푛푡 
Unit pengukuran dari reaktor adalah henri. Kemampuan dari reaktor untuk 
menghalangi aliran dari arus AC disebut dengan induktansi. Induktansi dari CLR pada 
umumnya dari 5 sampai 50 milihenri. Nilai dari CLR didasarkan pada total impedansi 
sistem yang diinginkan dari sumber daya. Impedansi sistem membatasi nilai maksimum 
dari arus yang dapat mengalir pada rangkaian primer dan pada umumnya dispesifikan 
sebagai persen impedansi. Nilainya dari 30% sampai 50% dari yang biasa digunakan. 
Impedansi dari reaktor dapat dihitung dengan: 
Presentasi impedansi yang dimiliki CLR dihitung dengan:
64 
LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) 
MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION 
PT BADAK NGL BONTANG 
MAULANI CANDRA (0910630076) 
JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK 
UNIVERSITAS BRAWIJAYA 
%푍 = 
푍푐푙푟 
푍푡푟 
Atau 
%푍 = 
퐿 × 314 × 퐴푚푝푠 
푉표푙푡푠 
× 100 
Ketika terjadi gangguan nilai impedansi meningkat dan menekan arus yang 
melewatinya. Nilai arus gangguan besarnya didapatkan dengan: 
퐹푎푢푙푡 퐶푢푟푟푒푛푡 = 
푉표푙푡푠 
푍푐푙푟 
= 
푅푎푡푒푑 퐶푢푟푟푒푛푡 
%푍 
× 100 
CLR didesain dengan sebuah inti yang akan menangani arus beberapa waktu 
tanpa menyentuh titik jenuh. Drop tegangan yang melewati CLR akan berbanding lurus 
dengan arus yang lewat. Jika reaktor jenuh maka arus lebih akan lewat tanpa ada 
penurunan tegangan dan ini berbahaya bagi sistem disisi keluaran CLR. Pengujian 
2.3.5 Pengujian Rutin, Desain, dan Pengujian lain untuk Reaktor Seri 
Pengujian untuk reaktor seri tipe kering diperlihatkan pada tabel 2.3. 
Tabel 2.6: PengujianRutin, Desain, dan Pengujian 
Pengujian Ketika Dilakukan Klasifikasi Pengujian 
Rutin Desain Lain 
Pengukuran 
Resistansi 
Pengukuran resistansi DC harus 
dilakukan pada semua unit 
X 
Pengukuran 
Impedansi 
Pengukuran impedansi harus 
dilakukan pada semua unit 
X 
Pengukuran Total 
Rugi-rugi 
Total rugi-rugi harus dilakukan pada 
setiap perhitungan 
X 
Pengujian 
Kenaikan 
Temperatur 
Pengujian ini dilakukan dari satu unit 
dari sejumlah unit pada desain yang 
sama 
X 
Pengujian 
tegangangan 
Pengujian tegangangan yang 
diterapkan harus dilakukan pada 
X
Laporan PKL PT Badak NGL
Laporan PKL PT Badak NGL
Laporan PKL PT Badak NGL
Laporan PKL PT Badak NGL
Laporan PKL PT Badak NGL
Laporan PKL PT Badak NGL
Laporan PKL PT Badak NGL
Laporan PKL PT Badak NGL
Laporan PKL PT Badak NGL
Laporan PKL PT Badak NGL
Laporan PKL PT Badak NGL
Laporan PKL PT Badak NGL
Laporan PKL PT Badak NGL
Laporan PKL PT Badak NGL
Laporan PKL PT Badak NGL
Laporan PKL PT Badak NGL
Laporan PKL PT Badak NGL
Laporan PKL PT Badak NGL
Laporan PKL PT Badak NGL
Laporan PKL PT Badak NGL
Laporan PKL PT Badak NGL
Laporan PKL PT Badak NGL
Laporan PKL PT Badak NGL
Laporan PKL PT Badak NGL
Laporan PKL PT Badak NGL
Laporan PKL PT Badak NGL
Laporan PKL PT Badak NGL
Laporan PKL PT Badak NGL
Laporan PKL PT Badak NGL
Laporan PKL PT Badak NGL
Laporan PKL PT Badak NGL
Laporan PKL PT Badak NGL
Laporan PKL PT Badak NGL
Laporan PKL PT Badak NGL
Laporan PKL PT Badak NGL
Laporan PKL PT Badak NGL
Laporan PKL PT Badak NGL
Laporan PKL PT Badak NGL
Laporan PKL PT Badak NGL
Laporan PKL PT Badak NGL

More Related Content

What's hot

Onetouch t60-quick-guide-indonesian
Onetouch t60-quick-guide-indonesianOnetouch t60-quick-guide-indonesian
Onetouch t60-quick-guide-indonesianSyariFah Maulidayati
 
Software Requirement Spesification
Software Requirement SpesificationSoftware Requirement Spesification
Software Requirement Spesificationwida dwitiayasa
 
Draft urs tms version 1 0 a
Draft urs   tms version 1 0  aDraft urs   tms version 1 0  a
Draft urs tms version 1 0 ad3styakrisna
 
LaTeX InDesign Crative Cloud
LaTeX InDesign Crative Cloud LaTeX InDesign Crative Cloud
LaTeX InDesign Crative Cloud Hirwanto Iwan
 
Supriyanto s komputasi untuk sains dan teknik menggunakan matlab edisi 4 - ...
Supriyanto s   komputasi untuk sains dan teknik menggunakan matlab edisi 4 - ...Supriyanto s   komputasi untuk sains dan teknik menggunakan matlab edisi 4 - ...
Supriyanto s komputasi untuk sains dan teknik menggunakan matlab edisi 4 - ...Kira R. Yamato
 
Rsni t 03-2005. jembatan
Rsni t 03-2005. jembatanRsni t 03-2005. jembatan
Rsni t 03-2005. jembataniky
 
Psosk 12-supplement file-management_system
Psosk 12-supplement file-management_systemPsosk 12-supplement file-management_system
Psosk 12-supplement file-management_systemHendriyana Jatnika
 
Membuat dokumen la tex edisi 12
Membuat dokumen la tex edisi 12Membuat dokumen la tex edisi 12
Membuat dokumen la tex edisi 12Hirwanto Iwan
 
Ka 06.-praktikum-paket-program-aplikasi
Ka 06.-praktikum-paket-program-aplikasiKa 06.-praktikum-paket-program-aplikasi
Ka 06.-praktikum-paket-program-aplikasiAyu Karisma Alfiana
 
Bagus wahyu dewanto_(i8107036)
Bagus wahyu dewanto_(i8107036)Bagus wahyu dewanto_(i8107036)
Bagus wahyu dewanto_(i8107036)urip setiawan
 
Petunjuk operasional peb53
Petunjuk operasional peb53Petunjuk operasional peb53
Petunjuk operasional peb53lahuddu76
 
Membuat Dokumen Beamer LaTeX
Membuat Dokumen Beamer LaTeXMembuat Dokumen Beamer LaTeX
Membuat Dokumen Beamer LaTeXHirwanto Iwan
 

What's hot (16)

Onetouch t60-quick-guide-indonesian
Onetouch t60-quick-guide-indonesianOnetouch t60-quick-guide-indonesian
Onetouch t60-quick-guide-indonesian
 
Software Requirement Spesification
Software Requirement SpesificationSoftware Requirement Spesification
Software Requirement Spesification
 
Draft urs tms version 1 0 a
Draft urs   tms version 1 0  aDraft urs   tms version 1 0  a
Draft urs tms version 1 0 a
 
LaTeX InDesign Crative Cloud
LaTeX InDesign Crative Cloud LaTeX InDesign Crative Cloud
LaTeX InDesign Crative Cloud
 
Supriyanto s komputasi untuk sains dan teknik menggunakan matlab edisi 4 - ...
Supriyanto s   komputasi untuk sains dan teknik menggunakan matlab edisi 4 - ...Supriyanto s   komputasi untuk sains dan teknik menggunakan matlab edisi 4 - ...
Supriyanto s komputasi untuk sains dan teknik menggunakan matlab edisi 4 - ...
 
Kp 01 jaringan
Kp 01 jaringanKp 01 jaringan
Kp 01 jaringan
 
Fismat 2
Fismat 2Fismat 2
Fismat 2
 
Panduan BBM
Panduan BBMPanduan BBM
Panduan BBM
 
Rsni t 03-2005. jembatan
Rsni t 03-2005. jembatanRsni t 03-2005. jembatan
Rsni t 03-2005. jembatan
 
Psosk 12-supplement file-management_system
Psosk 12-supplement file-management_systemPsosk 12-supplement file-management_system
Psosk 12-supplement file-management_system
 
Swing excerpt
Swing excerptSwing excerpt
Swing excerpt
 
Membuat dokumen la tex edisi 12
Membuat dokumen la tex edisi 12Membuat dokumen la tex edisi 12
Membuat dokumen la tex edisi 12
 
Ka 06.-praktikum-paket-program-aplikasi
Ka 06.-praktikum-paket-program-aplikasiKa 06.-praktikum-paket-program-aplikasi
Ka 06.-praktikum-paket-program-aplikasi
 
Bagus wahyu dewanto_(i8107036)
Bagus wahyu dewanto_(i8107036)Bagus wahyu dewanto_(i8107036)
Bagus wahyu dewanto_(i8107036)
 
Petunjuk operasional peb53
Petunjuk operasional peb53Petunjuk operasional peb53
Petunjuk operasional peb53
 
Membuat Dokumen Beamer LaTeX
Membuat Dokumen Beamer LaTeXMembuat Dokumen Beamer LaTeX
Membuat Dokumen Beamer LaTeX
 

Viewers also liked

Proposal KKL ELKETRO Okky Prasetiyo pte 2011
Proposal KKL ELKETRO Okky Prasetiyo pte 2011Proposal KKL ELKETRO Okky Prasetiyo pte 2011
Proposal KKL ELKETRO Okky Prasetiyo pte 2011Okky Prasetiyo
 
Makalah transformator
Makalah transformatorMakalah transformator
Makalah transformatorNita ManganDa
 
laporan praktek kerja lapangan
laporan praktek kerja lapanganlaporan praktek kerja lapangan
laporan praktek kerja lapanganRestu Budy
 
Tugas khusus Cut in PT.Badak LNG
Tugas khusus Cut in PT.Badak LNGTugas khusus Cut in PT.Badak LNG
Tugas khusus Cut in PT.Badak LNGDyah Dyfhaza
 
makalah trafo 3 fasa Elektro UnDip
makalah trafo 3 fasa Elektro UnDipmakalah trafo 3 fasa Elektro UnDip
makalah trafo 3 fasa Elektro UnDiprezon arif
 
1.teori dasar listrik
1.teori dasar listrik1.teori dasar listrik
1.teori dasar listrikWicah
 
38617859 pigging-system
38617859 pigging-system38617859 pigging-system
38617859 pigging-systemwidyo saptoto
 
Arus Listrik dan Rangkaian DC ( Anisa Putri Rinjani )
Arus Listrik dan Rangkaian DC ( Anisa Putri Rinjani )Arus Listrik dan Rangkaian DC ( Anisa Putri Rinjani )
Arus Listrik dan Rangkaian DC ( Anisa Putri Rinjani )Anisa Putri Rinjani
 
Proposal kkl ( kuliah kerja lapangan )
Proposal kkl ( kuliah kerja lapangan )Proposal kkl ( kuliah kerja lapangan )
Proposal kkl ( kuliah kerja lapangan )universitas samawa
 
Laporan Prakerin PT PLN (Persero) Area Surabaya Utara
Laporan Prakerin PT PLN (Persero) Area Surabaya UtaraLaporan Prakerin PT PLN (Persero) Area Surabaya Utara
Laporan Prakerin PT PLN (Persero) Area Surabaya Utaraavsai
 
Laporan praktikum fisika dasar (Multimeter dan Hukum Ohm)
Laporan praktikum fisika dasar (Multimeter dan Hukum Ohm)Laporan praktikum fisika dasar (Multimeter dan Hukum Ohm)
Laporan praktikum fisika dasar (Multimeter dan Hukum Ohm)Dandi Ardiansyah Putra
 
Laporan kemajuan kerja projek n s curve
Laporan kemajuan kerja projek n s curveLaporan kemajuan kerja projek n s curve
Laporan kemajuan kerja projek n s curvefaizal060490
 
Safety moment top 20 most dangerous jobs
Safety moment top 20 most dangerous jobsSafety moment top 20 most dangerous jobs
Safety moment top 20 most dangerous jobsBob Davies
 

Viewers also liked (20)

Proposal KKL ELKETRO Okky Prasetiyo pte 2011
Proposal KKL ELKETRO Okky Prasetiyo pte 2011Proposal KKL ELKETRO Okky Prasetiyo pte 2011
Proposal KKL ELKETRO Okky Prasetiyo pte 2011
 
Makalah transformator
Makalah transformatorMakalah transformator
Makalah transformator
 
laporan praktek kerja lapangan
laporan praktek kerja lapanganlaporan praktek kerja lapangan
laporan praktek kerja lapangan
 
Http
HttpHttp
Http
 
Tugas khusus Cut in PT.Badak LNG
Tugas khusus Cut in PT.Badak LNGTugas khusus Cut in PT.Badak LNG
Tugas khusus Cut in PT.Badak LNG
 
makalah trafo 3 fasa Elektro UnDip
makalah trafo 3 fasa Elektro UnDipmakalah trafo 3 fasa Elektro UnDip
makalah trafo 3 fasa Elektro UnDip
 
KKL Batam
KKL BatamKKL Batam
KKL Batam
 
1.teori dasar listrik
1.teori dasar listrik1.teori dasar listrik
1.teori dasar listrik
 
laporan akhir magang
laporan akhir maganglaporan akhir magang
laporan akhir magang
 
38617859 pigging-system
38617859 pigging-system38617859 pigging-system
38617859 pigging-system
 
Kapasitor bank
Kapasitor bankKapasitor bank
Kapasitor bank
 
Arus Listrik dan Rangkaian DC ( Anisa Putri Rinjani )
Arus Listrik dan Rangkaian DC ( Anisa Putri Rinjani )Arus Listrik dan Rangkaian DC ( Anisa Putri Rinjani )
Arus Listrik dan Rangkaian DC ( Anisa Putri Rinjani )
 
Proposal kkl ( kuliah kerja lapangan )
Proposal kkl ( kuliah kerja lapangan )Proposal kkl ( kuliah kerja lapangan )
Proposal kkl ( kuliah kerja lapangan )
 
2 PLN
2 PLN2 PLN
2 PLN
 
Teori dasar listrik
Teori dasar listrikTeori dasar listrik
Teori dasar listrik
 
Laporan Prakerin PT PLN (Persero) Area Surabaya Utara
Laporan Prakerin PT PLN (Persero) Area Surabaya UtaraLaporan Prakerin PT PLN (Persero) Area Surabaya Utara
Laporan Prakerin PT PLN (Persero) Area Surabaya Utara
 
Laporan praktikum fisika dasar (Multimeter dan Hukum Ohm)
Laporan praktikum fisika dasar (Multimeter dan Hukum Ohm)Laporan praktikum fisika dasar (Multimeter dan Hukum Ohm)
Laporan praktikum fisika dasar (Multimeter dan Hukum Ohm)
 
Laporan kemajuan kerja projek n s curve
Laporan kemajuan kerja projek n s curveLaporan kemajuan kerja projek n s curve
Laporan kemajuan kerja projek n s curve
 
Safety moment
Safety momentSafety moment
Safety moment
 
Safety moment top 20 most dangerous jobs
Safety moment top 20 most dangerous jobsSafety moment top 20 most dangerous jobs
Safety moment top 20 most dangerous jobs
 

Similar to Laporan PKL PT Badak NGL

191113081241HZFRIOOY_03.RKS MEP KANTOR JASA RAHARJA SULTENG.pdf
191113081241HZFRIOOY_03.RKS MEP KANTOR JASA RAHARJA SULTENG.pdf191113081241HZFRIOOY_03.RKS MEP KANTOR JASA RAHARJA SULTENG.pdf
191113081241HZFRIOOY_03.RKS MEP KANTOR JASA RAHARJA SULTENG.pdfAbuVulkanikAlJawiy
 
Kirim Final revisi 520 Catu daya.pdf
Kirim Final revisi 520 Catu daya.pdfKirim Final revisi 520 Catu daya.pdf
Kirim Final revisi 520 Catu daya.pdfilmuco
 
Fisika statistik
Fisika statistikFisika statistik
Fisika statistikrian507
 
Step 1-electrical basic electricity
Step 1-electrical basic electricityStep 1-electrical basic electricity
Step 1-electrical basic electricitySlamet Setiyono
 
Fisdasbook i
Fisdasbook iFisdasbook i
Fisdasbook ivivichuzy
 
Fisika dasar IPA
Fisika dasar IPAFisika dasar IPA
Fisika dasar IPAMOSES HADUN
 
02 r1 -__kapasitas_jalan_perkotaan
02 r1 -__kapasitas_jalan_perkotaan02 r1 -__kapasitas_jalan_perkotaan
02 r1 -__kapasitas_jalan_perkotaana_agung_kartika
 
Kp 01 2010 perencanaan jaringan irigasi
Kp 01 2010 perencanaan jaringan irigasiKp 01 2010 perencanaan jaringan irigasi
Kp 01 2010 perencanaan jaringan irigasiArizki_Hidayat
 
Rsni t 02-2005
Rsni t 02-2005Rsni t 02-2005
Rsni t 02-2005iky
 
Modul teknologi sepeda motor (oto225 01)- sistem pengapian oleh beni setya nu...
Modul teknologi sepeda motor (oto225 01)- sistem pengapian oleh beni setya nu...Modul teknologi sepeda motor (oto225 01)- sistem pengapian oleh beni setya nu...
Modul teknologi sepeda motor (oto225 01)- sistem pengapian oleh beni setya nu...Ahmad Faozi
 
Jobsheet Memperbaiki Gangguan-Gangguan Sistem Bahan Bakar Diesel
Jobsheet Memperbaiki Gangguan-Gangguan Sistem Bahan Bakar DieselJobsheet Memperbaiki Gangguan-Gangguan Sistem Bahan Bakar Diesel
Jobsheet Memperbaiki Gangguan-Gangguan Sistem Bahan Bakar DieselCharis Muhammad
 
Materi 2-dasar-sistem-proteksi-tt
Materi 2-dasar-sistem-proteksi-ttMateri 2-dasar-sistem-proteksi-tt
Materi 2-dasar-sistem-proteksi-ttTim Suwardiyanto
 
Isi cover 929050981164c
Isi cover 929050981164cIsi cover 929050981164c
Isi cover 929050981164cYusuf Saputra
 
61607365 pompa-hidram
61607365 pompa-hidram61607365 pompa-hidram
61607365 pompa-hidramRandu Mulia
 
05 r3 -_kapasitas_simpang_2
05 r3 -_kapasitas_simpang_205 r3 -_kapasitas_simpang_2
05 r3 -_kapasitas_simpang_2a_agung_kartika
 

Similar to Laporan PKL PT Badak NGL (20)

191113081241HZFRIOOY_03.RKS MEP KANTOR JASA RAHARJA SULTENG.pdf
191113081241HZFRIOOY_03.RKS MEP KANTOR JASA RAHARJA SULTENG.pdf191113081241HZFRIOOY_03.RKS MEP KANTOR JASA RAHARJA SULTENG.pdf
191113081241HZFRIOOY_03.RKS MEP KANTOR JASA RAHARJA SULTENG.pdf
 
Kirim Final revisi 520 Catu daya.pdf
Kirim Final revisi 520 Catu daya.pdfKirim Final revisi 520 Catu daya.pdf
Kirim Final revisi 520 Catu daya.pdf
 
Fisika statistik
Fisika statistikFisika statistik
Fisika statistik
 
Pendahuluan pbl
Pendahuluan pblPendahuluan pbl
Pendahuluan pbl
 
Step 1-electrical basic electricity
Step 1-electrical basic electricityStep 1-electrical basic electricity
Step 1-electrical basic electricity
 
Fisdasbook i
Fisdasbook iFisdasbook i
Fisdasbook i
 
Fisika dasar IPA
Fisika dasar IPAFisika dasar IPA
Fisika dasar IPA
 
02 r1 -__kapasitas_jalan_perkotaan
02 r1 -__kapasitas_jalan_perkotaan02 r1 -__kapasitas_jalan_perkotaan
02 r1 -__kapasitas_jalan_perkotaan
 
Fisika dasar
Fisika dasarFisika dasar
Fisika dasar
 
Kp 01 2010 perencanaan jaringan irigasi
Kp 01 2010 perencanaan jaringan irigasiKp 01 2010 perencanaan jaringan irigasi
Kp 01 2010 perencanaan jaringan irigasi
 
Laporan kerja praktek
Laporan kerja praktekLaporan kerja praktek
Laporan kerja praktek
 
Fisika Matematika 2
Fisika Matematika 2Fisika Matematika 2
Fisika Matematika 2
 
Rsni t 02-2005
Rsni t 02-2005Rsni t 02-2005
Rsni t 02-2005
 
Fisika dasar1
Fisika dasar1Fisika dasar1
Fisika dasar1
 
Modul teknologi sepeda motor (oto225 01)- sistem pengapian oleh beni setya nu...
Modul teknologi sepeda motor (oto225 01)- sistem pengapian oleh beni setya nu...Modul teknologi sepeda motor (oto225 01)- sistem pengapian oleh beni setya nu...
Modul teknologi sepeda motor (oto225 01)- sistem pengapian oleh beni setya nu...
 
Jobsheet Memperbaiki Gangguan-Gangguan Sistem Bahan Bakar Diesel
Jobsheet Memperbaiki Gangguan-Gangguan Sistem Bahan Bakar DieselJobsheet Memperbaiki Gangguan-Gangguan Sistem Bahan Bakar Diesel
Jobsheet Memperbaiki Gangguan-Gangguan Sistem Bahan Bakar Diesel
 
Materi 2-dasar-sistem-proteksi-tt
Materi 2-dasar-sistem-proteksi-ttMateri 2-dasar-sistem-proteksi-tt
Materi 2-dasar-sistem-proteksi-tt
 
Isi cover 929050981164c
Isi cover 929050981164cIsi cover 929050981164c
Isi cover 929050981164c
 
61607365 pompa-hidram
61607365 pompa-hidram61607365 pompa-hidram
61607365 pompa-hidram
 
05 r3 -_kapasitas_simpang_2
05 r3 -_kapasitas_simpang_205 r3 -_kapasitas_simpang_2
05 r3 -_kapasitas_simpang_2
 

Recently uploaded

2021 - 10 - 03 PAPARAN PENDAHULUAN LEGGER JALAN.pptx
2021 - 10 - 03 PAPARAN PENDAHULUAN LEGGER JALAN.pptx2021 - 10 - 03 PAPARAN PENDAHULUAN LEGGER JALAN.pptx
2021 - 10 - 03 PAPARAN PENDAHULUAN LEGGER JALAN.pptxAnnisaNurHasanah27
 
PPT Manajemen Konstruksi Unsur Unsur Proyek 1.pptx
PPT Manajemen Konstruksi Unsur Unsur Proyek 1.pptxPPT Manajemen Konstruksi Unsur Unsur Proyek 1.pptx
PPT Manajemen Konstruksi Unsur Unsur Proyek 1.pptxHamidNurMukhlis
 
PPT PENILAIAN PERKERASAN JALAN Metode PCI.pptx
PPT PENILAIAN PERKERASAN JALAN Metode PCI.pptxPPT PENILAIAN PERKERASAN JALAN Metode PCI.pptx
PPT PENILAIAN PERKERASAN JALAN Metode PCI.pptxYehezkielAkwila3
 
Transfer Massa dan Panas Teknik Kimia Industri
Transfer Massa dan Panas Teknik Kimia IndustriTransfer Massa dan Panas Teknik Kimia Industri
Transfer Massa dan Panas Teknik Kimia Industririzwahyung
 
Ahli Muda Teknik Bangunan GEdung Jenjang 7 - Samet Kurnianto.pptx
Ahli Muda Teknik Bangunan GEdung Jenjang 7 - Samet Kurnianto.pptxAhli Muda Teknik Bangunan GEdung Jenjang 7 - Samet Kurnianto.pptx
Ahli Muda Teknik Bangunan GEdung Jenjang 7 - Samet Kurnianto.pptxarifyudianto3
 
Materi Safety Talk Persiapan Libur Lebaran
Materi Safety Talk Persiapan Libur LebaranMateri Safety Talk Persiapan Libur Lebaran
Materi Safety Talk Persiapan Libur LebaranSintaMarlina3
 
QCC MANAJEMEN TOOL MAINTENANCE (MAINTENANCE TEAM).pptx
QCC MANAJEMEN TOOL MAINTENANCE (MAINTENANCE TEAM).pptxQCC MANAJEMEN TOOL MAINTENANCE (MAINTENANCE TEAM).pptx
QCC MANAJEMEN TOOL MAINTENANCE (MAINTENANCE TEAM).pptxdjam11
 
Sesi_02_Rangkaian_Hubungan_Seri_Paralel.pptx
Sesi_02_Rangkaian_Hubungan_Seri_Paralel.pptxSesi_02_Rangkaian_Hubungan_Seri_Paralel.pptx
Sesi_02_Rangkaian_Hubungan_Seri_Paralel.pptx185TsabitSujud
 
Kelompok 5 PPt Penerapan Teori Fuzzy.pdf
Kelompok 5 PPt Penerapan Teori Fuzzy.pdfKelompok 5 PPt Penerapan Teori Fuzzy.pdf
Kelompok 5 PPt Penerapan Teori Fuzzy.pdfVardyFahrizal
 

Recently uploaded (9)

2021 - 10 - 03 PAPARAN PENDAHULUAN LEGGER JALAN.pptx
2021 - 10 - 03 PAPARAN PENDAHULUAN LEGGER JALAN.pptx2021 - 10 - 03 PAPARAN PENDAHULUAN LEGGER JALAN.pptx
2021 - 10 - 03 PAPARAN PENDAHULUAN LEGGER JALAN.pptx
 
PPT Manajemen Konstruksi Unsur Unsur Proyek 1.pptx
PPT Manajemen Konstruksi Unsur Unsur Proyek 1.pptxPPT Manajemen Konstruksi Unsur Unsur Proyek 1.pptx
PPT Manajemen Konstruksi Unsur Unsur Proyek 1.pptx
 
PPT PENILAIAN PERKERASAN JALAN Metode PCI.pptx
PPT PENILAIAN PERKERASAN JALAN Metode PCI.pptxPPT PENILAIAN PERKERASAN JALAN Metode PCI.pptx
PPT PENILAIAN PERKERASAN JALAN Metode PCI.pptx
 
Transfer Massa dan Panas Teknik Kimia Industri
Transfer Massa dan Panas Teknik Kimia IndustriTransfer Massa dan Panas Teknik Kimia Industri
Transfer Massa dan Panas Teknik Kimia Industri
 
Ahli Muda Teknik Bangunan GEdung Jenjang 7 - Samet Kurnianto.pptx
Ahli Muda Teknik Bangunan GEdung Jenjang 7 - Samet Kurnianto.pptxAhli Muda Teknik Bangunan GEdung Jenjang 7 - Samet Kurnianto.pptx
Ahli Muda Teknik Bangunan GEdung Jenjang 7 - Samet Kurnianto.pptx
 
Materi Safety Talk Persiapan Libur Lebaran
Materi Safety Talk Persiapan Libur LebaranMateri Safety Talk Persiapan Libur Lebaran
Materi Safety Talk Persiapan Libur Lebaran
 
QCC MANAJEMEN TOOL MAINTENANCE (MAINTENANCE TEAM).pptx
QCC MANAJEMEN TOOL MAINTENANCE (MAINTENANCE TEAM).pptxQCC MANAJEMEN TOOL MAINTENANCE (MAINTENANCE TEAM).pptx
QCC MANAJEMEN TOOL MAINTENANCE (MAINTENANCE TEAM).pptx
 
Sesi_02_Rangkaian_Hubungan_Seri_Paralel.pptx
Sesi_02_Rangkaian_Hubungan_Seri_Paralel.pptxSesi_02_Rangkaian_Hubungan_Seri_Paralel.pptx
Sesi_02_Rangkaian_Hubungan_Seri_Paralel.pptx
 
Kelompok 5 PPt Penerapan Teori Fuzzy.pdf
Kelompok 5 PPt Penerapan Teori Fuzzy.pdfKelompok 5 PPt Penerapan Teori Fuzzy.pdf
Kelompok 5 PPt Penerapan Teori Fuzzy.pdf
 

Laporan PKL PT Badak NGL

  • 1. 1 LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION PT BADAK NGL BONTANG MAULANI CANDRA (0910630076) JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK UNIVERSITAS BRAWIJAYA Daftar Isi B A B I ................................................................................................................. 6 PENDAHULUAN................................................................................................. 6 1.1 Latar Belakang ...................................................................................... 6 1.2 Tujuan Penulisan ................................................................................... 8 1.3 Batasan Masalah.................................................................................... 8 1.4 Metode Penulisan .................................................................................. 8 1.5 Sistematika Penulisan............................................................................ 9 B A B II .............................................................................................................. 11 TINJAUAN PUSTAKA...................................................................................... 11 2.1 Sistem Distribusi Tenaga Listrik......................................................... 11 2.1.1 Umum .............................................................................................. 11 2.1.2 Jaringan Distribusi menurut Susunan Rangkaian............................ 11 2.1.2.1 Sistem Radial ................................................................................ 12 2.2 Transformator ...................................................................................... 16 2.2.1 Pengertian Transformator................................................................ 16 2.2.2 Jenis-Jenis Transformator ............................................................... 17 2.2.3 Prinsip Transformator ..................................................................... 22 2.2.3.1 Hubungan Tegangan..................................................................... 28 2.2.3.2 Hubungan Arus............................................................................. 28 2.2.3.3 Hubungan Impedansi .................................................................... 28 2.2.4 Pemeliharaan Preventif Transformator ........................................... 30 2.2.5 Transformator Tipe Kering ............................................................. 32 2.2.6 Transformator Tipe Basah............................................................... 39 2.2.7 Pengujian Transformator ................................................................. 49
  • 2. 2.3 Reaktor ................................................................................................ 58 2.3.1 Definisi ............................................................................................ 58 2.3.2 Tipe dari Reaktor Seri Dry-type air-core ........................................ 59 2.3.3 Aplikasi dari Reaktor Seri ............................................................... 59 2.3.4 Posisi Reaktor pada Bus Bar ........................................................... 60 2.3.5 Pengujian Rutin, Desain, dan Pengujian lain untuk Reaktor Seri ... 64 B A B III............................................................................................................. 68 ANALISA DAN PEMBAHASAN ..................................................................... 68 3.1 Analisa Pengaruh Transformator dan Reaktor Seri pada Ring Bus .... 68 3.1.1 Analisa Pengaruh Transformator .................................................... 69 3.1.2 Analisa Pengaruh Reaktor Seri ....................................................... 72 3.2 Analisa Kondisi Transformator 34.5 kV/13.8 kV/13.8 kV ................. 74 3.2.1 Insulation Resistance (IR) Test ....................................................... 76 3.2.2. Time-Resistance Readings (Dielectric Absorbtion) ....................... 78 3.2.3 Polarization Index (PI) Test ............................................................ 85 3.2.4 Power Factor (PF) Test .................................................................. 87 3.2.5 Oil Dielectric Breakdown Voltage Test .......................................... 89 3.3 Analisa Kondisi Reaktor Seri Dry-type air-core................................. 91 3.3.1 Insulation Resistance (IR) Test ....................................................... 95 3.3.2 Time-Resistance Readings (Dielectric Absorbtion) ........................ 96 3.3.3 Polarization Index (PI) Test ............................................................ 98 3.3.4 Power Factor (PF) Test ................................................................. 100 3.4 Analisis .............................................................................................. 100 3.4 Upaya ................................................................................................ 102 3.4.1 Transformator 34.5 kV/13.8 kV/13.8 kV ...................................... 102 3.4.2 Reaktor Seri Dry-type air-core ..................................................... 103 2 LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION PT BADAK NGL BONTANG MAULANI CANDRA (0910630076) JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK UNIVERSITAS BRAWIJAYA
  • 3. B A B IV .......................................................................................................... 104 PENUTUP ......................................................................................................... 104 4.1 Kesimpulan........................................................................................ 104 4.2 Saran .................................................................................................. 104 3 LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION PT BADAK NGL BONTANG MAULANI CANDRA (0910630076) JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK UNIVERSITAS BRAWIJAYA
  • 4. 4 LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION PT BADAK NGL BONTANG MAULANI CANDRA (0910630076) JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK UNIVERSITAS BRAWIJAYA DAFTAR GAMBAR Gambar 2.1: Jaringan Distribusi Sistem Radial ........................................................... 12 Gambar 2.2: Jaringan Distribusi Sistem Loop ............................................................. 13 Gambar 2.3: Jaringan Distribusi Sistem Tertutup/Ring ............................................... 14 Gambar 2.4: Jaringan Distribusi Sistem Spindel.......................................................... 15 Gambar 2.5: Jaringan Distribusi Sistem Cluster .......................................................... 16 Gambar 2.6: Konstruksi inti tiga fasa........................................................................... 19 Gambar 2.7: Konstruksi Tipe Cangkang dari Transformator Satu-Fasa dan Tiga-Fasa. ` ................................................................................................................. 21 Gambar 2.8: Diagram Rangkaian dan Koneksi dari Transformator Sederhana ........... 23 Gambar 2.9: Diagram Ekivalen Transformator............................................................ 26 Gambar 2.10: (a) Diagram Ekivalen yang Telah Disederhanakan dan (b) Diagram Vektor yang Telah Disederhanakan dari Transformator ................................................ 27 Gambar 2.11: Representasi Grafis dari Transformator Daya..................................... 27 Gambar 2.12: Diagram Rangkaian Ekivalen dari persentase dasar. .......................... 30 Gambar 2.13: Transformator Tipe Kering Berventilasi dengan Penutup Depan untuk memperlihatkan perakitan lilitan- inti. ............................................................................. 33 Gambar 2.14: Transformator Basah Tiga Fasa .......................................................... 39 Gambar 2.15: TTR testers: (a) hand-crank TTR; (b) handheld electronic TTR; and (c) three-phase electronic TTR. (Courtesy of Megger Inc., Valley Forge, PA.) .................. 52 Gambar 2.16: IR tester (megohmmeter). (Courtesy of Megger Inc., Valley Forge, PA.) 56 Gambar 2.17: (a) Prinsip Rangkaian Pengukuran tegangan recovery dari Waktu tc; (b) Siklus Pengukuran RVM dan kuantitas perekaman selama satu siklus; dan (c) tegangan recovery V sebagai fungsi waktu tc. ................................................................ 58 Gambar 2.18: Bus Coupling....................................................................................... 61 Gambar 2.19: Terpasang seri dengan incoming feeder .............................................. 62
  • 5. Gambar 2.20: Terpasang seri dengan outgoing feeder............................................... 62 Gambar 3.1: Diagram Satu Garis Sistem Distribusi 34.4/13.8 kV PT Badak NGL Bontang ................................................................................................................... 6 Gambar 3.2: Simulasi Ring Bus dengan Menggunakan ETAP ................................... 69 Gambar 3.1: Simulasi Aliran Daya pada Ring Bus jika Semua Transformator In-service ................................................................................................................. 70 Gambar 3.2: Simulasi Aliran Daya pada Ring Bus jika Transformator 30-PT-202 Out-service ................................................................................................................. 71 Gambar 3.3: Simulasi Aliran Daya pada Ring Bus jika Salah Satu Kaki Transformator 30-PT-202 Tidak Dioperasikan. ...................................................................................... 72 Gambar 3.4: Simulasi jika ring bus tidak dipasang Reaktor Seri tiga fasa Dry-type Air-core ............................................................................................................. 73 Gambar 3.5: Simulasi ring bus setelah dipasang Reaktor Seri tiga fasa Dry-type Air-core ................................................................................................................. 74 Gambar 3.6: Konstruksi Reaktor seri dry-type air-core 30-PLR-101 dan 30 PLR 102 .. 5 LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION PT BADAK NGL BONTANG MAULANI CANDRA (0910630076) JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK UNIVERSITAS BRAWIJAYA 92
  • 6. 6 LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION PT BADAK NGL BONTANG MAULANI CANDRA (0910630076) JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK UNIVERSITAS BRAWIJAYA B A B I PENDAHULUAN 1.1 Latar Belakang Dalam upaya menjaga kehandalan sistem pembangkit, PT. Badak NGL menggunakan sistem ring bus 34,5 kV yang menghubungkan seluruh generator di Module-I dan Module-II. Sehingga jika salah satu atau beberapa generator di Module-I maupun Module-II tidak bisa menyuplai daya, pengalihan beban dapat dilakukan dan proses produksi masih tetap bisa terlaksana. Reaktor seri 30-PLR-101 dan 30-PLR-102 menghubungkan Module I dan Module II. Fungsi dari reaktor adalah untuk membatasi arus antar module yang berlebihan diakibatkan starting motor cooling water pump dan arus hubung singkat yang dapat mengalir dari Module I dan Module II dan sebaliknya. Gambar 3.1: Diagram Satu Garis Sistem Distribusi 34.4/13.8 kV PT Badak NGL Bontang
  • 7. Seperti yang dapat kita lihat pada gambar di atas, sistem ring bus terletak di posisi paling atas. Tegangan yang dihasilkan oleh setiap generator sebesar 13,8 kV di naikkan dengan menggunakan transformator tiga belitan (Three winding Transformer) sampai 34,5 kV dan dikirim ke dalam ring bus. Generator di PT. Badak NGL terdiri dari 15 generator dengan rincian 12 generator turbin uap, 2 generator turbin gas, 1 generator turbin diesel. Pada gambar dapat dilihat bahwa dalam satu modul terhubung dengan 4 transformator tiga belitan (Three winding Transformer). Yaitu Module I yang terhubung dengan 30-PT-101, 30-PT-102, 30-PT-103, dan 30-PT-104 sedangkan Module II terhubung dengan 30-PT-201, 30-PT-202, 30-PT-203, dan 30-PT-204. Antara Module I dan Module II dihubungkan dengan reaktor yaitu Three-phase Dry-type Air-core Series Reactor. Ring bus terhubung langsung dengan transformator dan reaktor seri. Sehingga kondisi dari ring bus dapat ditentukan melaui kondisi dari 8 transformator tiga belitan (Three winding Transformer) dan 2 Reaktor Seri Tiga Fasa Tipe-Kering Inti-udara (Three-phase Dry-type Air-core Series Reactor). Jika salah satu dari peralatan tersebut tidak baik (mengalami kerusakan) maka dapat diambil kesimpulan bahwa kondisi dari ring bus juga tidak baik dan begitu pula sebaliknya. Untuk melihat kondisi peralatan tersebut, kita dapat mengetahui dari hasil pengujian yang dilakukan dalam pemeliharaan. Pemeliharaan yang dilakukan di PT Badak NGL yaitu: Tulisan ini bertujuan untuk menganalisis keadaan dari ring bus 34,5 kV berdasarkan keadaan dari transformator tiga belitan (Three winding Transformer) dan reaktor seri tiga fasa tipe-kering inti-udara (Three-phase Dry-type Air-core Series Reactor) dari data yang diperoleh dari pengujian yang dilakukan saat preventive maintenance. Selain itu, tulisan ini juga bertujuan untuk membrikan rekomendasi 7 LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION PT BADAK NGL BONTANG 1. Predictive Maintenance (Conditional Maintenance). 2. Preventive Maintenace (Time Base Maintenance). 3. Corrective Maintenance. MAULANI CANDRA (0910630076) JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK UNIVERSITAS BRAWIJAYA
  • 8. mengenai upaya-upaya yang harus dilakukan PT Badak NGL untuk menjaga kondisi dari ring bus tetap dalam keadaan baik. 8 LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION PT BADAK NGL BONTANG MAULANI CANDRA (0910630076) JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK UNIVERSITAS BRAWIJAYA 1.2 Tujuan Penulisan Tujuan dari penulisan laporan ini adalah: 1. Menganalisis pengaruh dari transformator tiga belitan (Three winding Transformer) dan reaktor seri tiga fasa tipe-kering inti-udara (Three-phase Dry-type Air-core Series Reactor) terhadap ring bus 34,5 kV. 2. Menganalisis kondisi 8 transformator tiga belitan (Three winding Transformer). 3. Menganalisis kondisi reaktor seri tiga fasa tipe-kering inti-udara (Three-phase Dry-type Air-core Series Reactor). 1.3 Batasan Masalah 1. Kondisi pemeliharaan transformator dan reaktor yang dianalisis hanya dilakukan pada pengujian terakhir. 2. Analisis transformator hanya dilakukan pada transformator tiga belitan berdasarkan pengujian Insulation Resistance (IR) test, Polarization Index (PI) test, Power Factor (PF) loss test, dielectric breakdown voltage test . Sedangkan analisis berdasarkan pengujian Dissolve Gas Analysis (DGA) test tidak dilakukan. 3. Analisis reaktor hanya berdasarkan pengujian Insulation Resistance (IR) test, Polarization Index (PI) test, dan Power Factor (PF) loss test. 1.4 Metode Penulisan Dalam pengerjaan laporan ini dilakukan beberapa metode, antara lain: 1. Studi literatur 2. Kunjungan langsung ke lapangan 3. Wawancara dengan karyawan PT. Badak NGL
  • 9. 9 LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION PT BADAK NGL BONTANG MAULANI CANDRA (0910630076) JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK UNIVERSITAS BRAWIJAYA 1.5 Sistematika Penulisan Sistematika penyusunan laporan adalah sebagai berikut, BAB 1 PENDAHULUAN Berisi latar belakang, tujuan, batasan masalah, metode penelitian dan sistematika penulisan tugas khusus laporan praktik kerja lapangan di PT. Badak NGL BAB 2 TINJAUAN PUSTAKA Berisi penjelasan tentang sistem distribusi tenaga listrik, transformator dan cara pengujiannya, dan reaktor dan pengujian yang dilakukan. BAB 3 ANALISA DAN PEMBAHASAN Analisa Pengaruh Transformator dan Reaktor Seri pada Ring Bus, Analisa Kondisi Transformator 34.5 kV/13.8 kV/13.8 kV, dan Analisa Kondisi Reaktor Seri Dry-type air-core, dan upaya-upaya yang harus dilakukan untuk menjaga kondisi ring bus. BAB 4 PENUTUP Berisi kesimpulan dan saran yang diberikan penulis
  • 10. 10 LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION PT BADAK NGL BONTANG MAULANI CANDRA (0910630076) JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK UNIVERSITAS BRAWIJAYA
  • 11. 11 LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION PT BADAK NGL BONTANG MAULANI CANDRA (0910630076) JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK UNIVERSITAS BRAWIJAYA B A B II TINJAUAN PUSTAKA 2.1 Sistem Distribusi Tenaga Listrik 2.1.1 Umum Penyaluran daya dalam sistem distribusi dapat melalui saluran udara atau saluran bawah tanah. Pemilihan saluran udara dan saluran bawah tanah tergantung pada beberapa faktor yang berlainan. Yaitu faktor kontinuitas pelayanan, arah perkembangan daerah, biaya pemeliharaan tahunan, biaya modal, segi estetis, dan umur manfaat sistem tersebut. Gabungan kedua saluran ini sering kali diperlukan. Baik buruknya suatu sistem distribusi dinilai dari beberapa faktor, yaitu : 1. Regulasi tegangan (Jatuh Tegangan) 2. Kontinuitas pelayanan 3. Efisiensi 4. Harga sistem Suatu sistem distribusi harus memenuhi beberapa persyaratan sebagai berikut : 1. Regulasi tegangan tidak terlalu besar 2. Gangguan terhadap pelayanana tidak boleh terlalu lama 3. Biaya sistem tidak terlalu mahal 2.1.2 Jaringan Distribusi menurut Susunan Rangkaian Susunan Rangakain Sistem jaringan distribusi ada beberapa macam, yaitu : 1. Sistem Radial 2. Sistem Loop 3. Sistem Tertutup/Ring 4. Sistem Spindel 5. Sistem Cluster 6. Sistem Grid/Network
  • 12. 12 LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION PT BADAK NGL BONTANG MAULANI CANDRA (0910630076) JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK UNIVERSITAS BRAWIJAYA 2.1.2.1 Sistem Radial Gambar 2.1: Jaringan Distribusi Sistem Radial Sistem radial ini merupakan suatu sistem distribusi tegangan menengah yang paling sederhana, murah, banyak digunakan terutama untuk sistem yang kecil, kawasan pedesaan. Proteksi yang digunakan tidak rumit dan keandalannya paling rendah. Keuntungan / Kerugian : 1. Mudah mengoperasikannya 2. Mudah mencari tegangan 3. Cocok untuk sistem yang sederhana 4. Tidak dapat dimanipulasi bila terjadi gangguan.
  • 13. 13 LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION PT BADAK NGL BONTANG MAULANI CANDRA (0910630076) JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK UNIVERSITAS BRAWIJAYA 2.1.2.1 Sistem Loop Pada sistem loop terbuka, bagian-bagian penyulang tersambung melalui alat pemisah (disconnectors), dan kedua ujung penyulang tersambung pada sumber energi. Pada suatu tempat tertentu pada penyulang, alat pemisah sengaja dibiarkan dalam keadaan terbuka. Pada asasnya, sistem ini terdiri atas dua penyulang yang dipisahkan oleh suatu pemisah, yang dapat berupa sekring, alat pemisah, saklar daya. Terlihat pada Gambar 2.6 bila terjadi gangguan, bagian saluran dari penyulang yang terganggu dapat dilepas dan menyambungnya pada penyulang yang tidak terganggu. Sistem demikian biasanya dioperasikan secara manual dan dipakai pada jaringan yang relatif kecil. Gambar 2.2: Jaringan Distribusi Sistem Loop Keuntungan/Kerugian : 1. Secara teknis lebih baik dari sistem radial 2. Biaya sedikit lebih mahal karena harus dibangun dua penyulang pada jalur yang sama 3. Bisa dimanipulasi bila terjadi gangguan
  • 14. 14 LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION PT BADAK NGL BONTANG MAULANI CANDRA (0910630076) JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK UNIVERSITAS BRAWIJAYA 2.1.2.3 Sistem Tertutup/Ring Gambar 2.3: Jaringan Distribusi Sistem Tertutup/Ring Keuntungan/Kerugian : 1. Jumlah konsumen yang besar bisa dijangkau 2. Gangguan salah satu sisi penghantar harus sanggup menampung seluruh beban yang terpasang pada sistem, disini erat hubungannya dengan rugi tegangan. 3. Mudah operasi
  • 15. 15 LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION PT BADAK NGL BONTANG MAULANI CANDRA (0910630076) JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK UNIVERSITAS BRAWIJAYA 2.1.2.4 Sistem Spindel Gambar 2.4: Jaringan Distribusi Sistem Spindel Sistem Spindle merupakan sistem yang relatif handal karena disediakan satu buah express feeder yang merupakan feeder/penyulang tanpa beban dari gardu induk sampai gardu hubung / GH refleksi, banyak digunakan pada jaringan SKTM. Sistem ini relatif mahal karena biasanya dalam pembangunannya sekaligus untuk mengatasi perkembangan beban dimasa yang akan datang. Proteksinya relatif sederhana hampir sama dengan sistem open loop. Biasanya ditiap-tiap feeder dalam sistem spindel disediakan gardu tengah (middle point) yang berfungsi untuk titik manufer apabila terjadi gangguan pada jaringan tersebut.
  • 16. 16 LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION PT BADAK NGL BONTANG MAULANI CANDRA (0910630076) JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK UNIVERSITAS BRAWIJAYA 2.2.2.5 Sistem Cluster Gambar 2.5: Jaringan Distribusi Sistem Cluster Sistem clutser ini hampir mirip dengan sistem spindel. Dalam sistem cluster tersedia satu express feeder yang merupakan feeder atau penyulang tanpa beban yang digunakan sebagai titik menufer beban oleh feeder atau penyulang lain dalam sistem cluster tersebut. Proteksi yang diperlukan untuk sistem yang relatif sama dengan sistem open loop atau sistem spindle. 2.2 Transformator 2.2.1 Pengertian Transformator Transformator atau lebih dikenal dengan nama “transformer” atau “transformator” sejatinya adalah suatu peralatan listrik yang mengubah daya listrik AC pada satu level tegangan yang satu ke level tegangan berdasarkan prinsip induksi elektromagnetik tanpa merubah frekuensinya. Tranformator biasa digunakan untuk mentransformasikan tegangan (menaikkan atau menurunkan tegangan AC). Selain itu, transformator juga dapat digunakan untuk sampling tegangan, sampling arus, dan juga mentransformasi impedansi. Transformator terdiri dari dua atau lebih kumparan yang membungkus inti besi feromagnetik. Transformer adalah peralatan yang sangat handal dan dapat menyediakan pelayanan dalam jangka panjang bila pemeliharaan dan perbaikan dilakukan secara
  • 17. teratur. Kerusakan transformer, ketika mereka terjadi, biasanya yang bersifat sangat serius, yang mungkin memerlukan perbaikan mahal dan waktu yang lama. Jaminan terbaik untuk mengatasinya adalah memastikan bahwa transformator terpasang dengan benar dan dipelihara. 17 LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION PT BADAK NGL BONTANG MAULANI CANDRA (0910630076) JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK UNIVERSITAS BRAWIJAYA 2.2.2 Jenis-Jenis Transformator Untuk pertimbangan kebutuhan pemeliharaan, transformator dapat dibagi menjadi kategori berikut: 1. Medium isolasi 2. Konstruksi 3. Aplikasi dan penggunaan 2.2.2.1 Medium Isolasi Media transformator isolasi dapat dibagi lagi menjadi dua jenis : 1. Tipe Kering Transformator tipe kering pada umumnya menggunakan pendinginan udara dengan isolasi lilitan dengan kelas A, B, C, atau H. Transformator tipe kering dapat pendinginan sendiri atau pendinginan udara yang dipaksa. Pendinginan Sendiri : Transformator pendinginan sendiri didinginkan dengan sirkulasi alami dari udara melalui kotak transformator. Desain kelas pendinginan untuk transformator ini Adalah AA. Pendinginan udara dipaksa: transformator didinginkan dengan udara yang dipaksa dari tipe kering didinginkan dari sirkulasi udara yang dipaksa melalui kotak. Transformator dari tipe ini memiliki peralatan penghembus udara dari semacam kipas. Transformator ini memiliki rating 133% dari rating transformator tipe kering pendinginan sendiri. Kelas desain pendinginan untuk transformator ini adalah FA. Transformator tipe kering dapat diperoleh dengan keduanya yaitu pendinginan sendiri maupun pendinginan dipaksa. Desain dari transformator adalah AA/FA. Transformator
  • 18. tipe kering dapat juga didinginkan oleh gas selain udara. Untuk transformator seperti itu dibutuhkan tangki yang disegel. 2. Tipe Basah Pada transformator tipe ini, lilitan dan inti direndam secara keseluruhan pada cairan yang dimasukkan pada tangki transformator. Tangki dilengkapi dengan sirip pendingin untuk sirkulasi dari cairan transformator. Cairan transformator memberikan isolasi medium untuk gulungan sebaik mungkin untuk disipasi panas. Dua cairan sudah digunakan secara luda untuk transformator: oli mineral dan polychlorinated biphenyls (PCB), yang pada umumnya dikenal sebagai askarel. Askarel secara luas digunakan pada transformator untuk aplikasi dalam ruangan karena itu adalah cairan isolasi sintesis yang tidak mudah terbakar. Askarel adalah nonbiodegradable dan beracun. Environmental Protection Agency (EPA) melarang penggunaan dari askarel pada transformator dan peralatan elektrik lainnya, dan kemampuannya untu digunakan kembali pada aplikasi baru hampir tidak ada. Cairan yang lebih baru telah diperkenalkan seperti silikon, Rtemp, Wecosal, dan Alpha 1 untuk pengganti dari askarel. Yang lain masih dalam tahap pengembangan. Tanpa menghirauan apa cairan baru yang ada dalam pasaran untuk aplikasi transformator, mereka harus tetap dipelihara dan diuji untuk menjamin integritas dari transformator. 18 LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION PT BADAK NGL BONTANG Metode pendingina yang digunakan untuk transformator yang berisi cairan. MAULANI CANDRA (0910630076) JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK UNIVERSITAS BRAWIJAYA a. ONAN : Oil Natural Air Natural Transformator pendinginan sendiri menggunakan sirkulasi alami dari cairan isolasi. Panas pada tangki transformator dihilangkan dengan konveksi arus yang telah diatur pada cairan, yang bersirkulasi melalui tangki dan sirip pendingin. b. ONAF : Oil Natural Air Forced Pada tipe ini oli akan bersirkulasi dengan alami namun saat oli melalui radiator oli akan didinginkan dibantu dengan kipas/fan. c. OFAF : Oil Forced Air Forced Pada tipe ini oli akan didinginkan dengan bantuan pompa agar sirkulasi semakin cepat dan juga dibantu kipas/fan pada radiatornya
  • 19. d. Pendinginan Air: Transformator ini menggunakan air selain udara untuk menghasilkan pendinginan. Sistem pendinginan ini meliputi penukar panas dari air yang dipopa melalui gulungan pipa yang dipasang didalam atau diluar dari tangki transformator. Kelas desain pendinginan untuk transformator ini adalah FOW. Khusus jenis transformator tenaga tipe basah, kumparan-kumparan dan intinya direndam dalam minyak-transformator, terutama transformator-transformator tenaga yang berkapasitas besar, karena minyak transformator mempunyai sifat sebagai media pemindah panas dan bersifat pula sebagai isolasi ( tegangan tembus tinggi ) sehingga berfungsi sebagai media pendingin dan isolasi. 19 LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION PT BADAK NGL BONTANG MAULANI CANDRA (0910630076) JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK UNIVERSITAS BRAWIJAYA 2.2.2.2 Konstruksi Transformator dapat diklasifikasikan dari konstruksi tangki dan konstruksi inti. Gambar 2.6: Konstruksi inti tiga fasa Konstruksi tangki
  • 20. Konstruksi beberapa tipe dari tangki transformator digunakan untuk mencegah 20 LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION PT BADAK NGL BONTANG MAULANI CANDRA (0910630076) JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK UNIVERSITAS BRAWIJAYA terbukanya cairan ke atmosfir. Tipe adalah: Free breathing : tipe ini untuk membuka ke atmosfer (contoh: pembatas udara ditas cairan pada tekanan atmosfir). Transformator bernafas sebagai perubahan tekanan udara dan temperatur diluar tangki. Beberapa dari transformator dapat dilengkapi dengan komponen dehidrasi pada breather. Konservator atau tangki ekspansi : transformator ini dilengkapi dengan tangki ekspansi diatas tangki transformator. Tangki transformator dilengkapi dengan oli, dan transformator bernafas dengan tangki kecil ini, pada umumnya melewati komponen dehidrasi. Tujuan dari tangki kecil ini adalah untuk menyegel cairran transformator dari atmosfir dan untuk mengurangi oksidasi dan formasi dari sludge. Sealed Tank: transformator ini dilengkapi dengan gas inert, seperti nitrogen yang berada di bawah tekanan diatas cairan yang berada pada atas tangki transformator. Pada umumnya, range tekanan dari tipe transformator ini adalah -8 sampai 8lb/in2. Gas-oil sealed: transformator ini memiliki tangki tambahan untuk secara menyeluruh menyegel tangki interior, meliputi cairan transformator, dari atmosfer. Vaporization: Transformator tipe ini menggunakan cairan isolasi spesial yang tidak mudah terbakar, seperti florocarbon (General Electric R-113), yang tidak mudah terbakar, dan kondenser spesial yang dirakit las pada atas dari tangki transformator. Ujung tabung pendingin yang diacu dan diatas header tabung. Transformator ini menggunakan teknik dari cairan yang disemprot pada inti dan gulungan yang dirakit. Tujuan dari kondenser adalah untuk mendinginkan uap udara menjadi cari untuk sirkulasi belanjut pada cairan. Konstruksi Inti Berdasarkan konstruksi corenya, tranformator dapat dibedakan menjadi tipe core dan shell. 1. Tipe Core
  • 21. Pada tipe ini, kumparan transformator mengelilingi inti yang terlaminasi. 21 LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION PT BADAK NGL BONTANG Sebagian besar transformator distribusi kecil menggunakan konstruksi ini. MAULANI CANDRA (0910630076) JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK UNIVERSITAS BRAWIJAYA 2. Tipe Shell Pada tipe ini, Inti magnetik mengelilingi kumparan. Satu keuntungan dari jenis shell adalah bahwa ia menawarkan jalur terpisah untuk arus urutan nol melalui inti, dibandingkan dengan jenis core di mana jalan-urutan nol ada hanya melalui tangki transformator dan akhir sambungan. 2.2.2.3 Aplikasi dan Penggunaan Transformator yang digunakan untuk mengkonversikan energi dapat diklasifikasikan ke dalam 5 kategori berdasarkan aplikasi dan penngunaanya. 1. Transformator Distribusi Sebuah transformator distribusi memiliki rating 3-500 kVA. Ada berbagai jenis transformator distribusi, tergantung pada media pendingin dan isolasi, layanan aplikasi, dan metode pemasangan. Hampir semua transformator distribusi dengan pendinginan sendiri. Gambar 2.7: Konstruksi Tipe Cangkang dari Transformator Satu-Fasa dan Tiga-Fasa. 2. Transformer Jaringan
  • 22. Transformator ini memiliki karakteristik serupa dengan transformator distribusi. Namun, penerapannya berbeda. Memiliki persyaratan yang khusus untuk layanan jaringan, seperti ventilasi, ukuran lemari besi, kemampuan perendaman, dan persyaratan hubung singkat. Transformer Jaringan dapat memiliki peringkat kVA lebih dari 500 kVA dan tegangan primer sampai dengan 23 kV. 3. Transformator Arc-Furnace Transformator Arc-Furnace adalah transformator tujuan khusus yang digunakan dalam proses industri. Ini adalah transformator tegangan rendah dan ampere tinggi dan khusus bersiap untuk menahan tekanan mekanis yang disebabkan oleh fluktuasi arus yang telah ditentukan. Karena gelombang terdistorsi karena busur, ia memiliki tambahan isolasi kumparan. 4. Transformator Penyearah Transformer ini digunakan dalam penyearahan AC ke DC dalam proses di Industri. Transformer ini sepsial dirancang untuk tahan tehadap tekanan mekanis akibat arus yang tinggi. 5. Transformator Daya Transformator ini memiliki rating lebih dari 500 kVA dan terutama digunakan dalam mengubah energi dari stasiun pembangkit ke jaringan transmisi, dari jalur transmisi untuk gardu distribusi, atau dari jalur layanan utilitas untuk pembangkit gardu distribusi. 22 LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION PT BADAK NGL BONTANG MAULANI CANDRA (0910630076) JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK UNIVERSITAS BRAWIJAYA 2.2.3 Prinsip Transformator Transformer ditemukan pada tahun 1886 oleh William Stanley dan merupakan peralatan yang sangat berguna. Sebuah transformator dapat dibagi dalam 3 bagian: Kumparan Primer, Kumparan Sekunder dan Inti (Core). Kumparan Primer dan Sekunder dihubungkan oleh fluk yang diproduksi dalam inti besi.
  • 23. 23 LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION PT BADAK NGL BONTANG Gambar 2.8: Diagram Rangkaian dan Koneksi dari Transformator Sederhana MAULANI CANDRA (0910630076) JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK UNIVERSITAS BRAWIJAYA Sisi Primer: Vp adalah tegangan primer Np adalah lilitan primer Zps adalah impedansi bocor Ip adalah arus primer Sisi Sekunder: Vs adalah tegangan sekunder Ns adalah lilitan sekunder Zps adalah impedansi bocor Is adalah arus sekunder Diasumsikan bahwa lilitan primer dicatu dengan menghubungkan dengan sumber tegangan AC, Vp. Hal ini membuat arus primer, yang menghasilkan medan magnet bolak-balik pada inti besi yang secara terus menerus pada arah positif dan negatif. Tegangan induksi seketika pada lilitan primer dapat dilihat melalui Hukum Faraday yaitu:
  • 24. 24 LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION PT BADAK NGL BONTANG MAULANI CANDRA (0910630076) JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK UNIVERSITAS BRAWIJAYA 푒푝 = −푁푝 푑∅ 푑푡 × 10−8푉 Dimana =max=sin t dan max= fluksi maksimum seketika pada inti. Nilai rms dari tegangan dapat diekspresikan sebagai: 푒푝 = 4,44푓푁푝퐴퐵푚푎푥 × 10−8푉 Dimana: F adalah frekuensi Np adalah jumlah lilitan pada lilitan primer A adalah luas penampang inti Bmax adalah kerapatan fluksi maksimum Fluksi bolak-balik yang dihasilkan oleh lilitan primer pada inti menginduksi lilitan sekunder dan menghasilkan tegangan bolak-balik pada lilitan sekunder yang dapat ditunjukkan oleh persamaan: 푒푠 = 4,44푓푁푝퐴퐵푚푎푥 × 10−8푉 Dimana es adalah tegangan sekunder Diasumsikan bahwa lilitan sekunder terbuka (kondisi tanpa beban, Is=0) dan transformator dicatu dari sisi primer, arus kecil, In, akan mengalir pada lilitan primer. Arus ini disebut arus eksitasi dan menghasilkan fluksi bolak-balik meliputi:  Fluksi bersama yang melalui inti.  Fluksi bocor yang melalui udara. Dalam transformer daya komersial, fluks bocor sangat kecil dan sering diabaikan. Fluks bolak-balik dalam inti besi menginduksi tegangan di kumparan primer dan sekunder. Tegangan induksi dalam sekunder menghasilkan gaya electromotive karena induktansi sendiri. Menurut hukum Lenz, back emf sama dengan tegangan yang
  • 25. diberikan ke kumparan primer di bawah kondisi tanpa beban. Tegangan yang digunakan dapat dinyatakan sebagai berikut: Tegangan yang digunakan = total tegangan induksi – drop resistansi pada 25 LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION PT BADAK NGL BONTANG MAULANI CANDRA (0910630076) JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK UNIVERSITAS BRAWIJAYA kumparan primer Karena drop resistansi pada kumparan primer diabaikan, kita dapat menulis tegangan yang digunakan = tegangan terinduksi Ketika beban diberikan pada kumparan sekunder, arus primer yang proporsional akan mengalir bersesuaian dengan arus sekunder. Akibat pemberian beban pada transformator, perbandingan tegangan transformator akan menyimpang dari perbandingan jumlah lilitan kumparan primer dan sekunder. Kesalahan kecil dapat secara umum diabaikan pada transformator daya. Selain drop tegangan di gulungan primer dan sekunder, kerugian akibat arus eksitasi dan arus beban harus dipertimbangkan. Rugi-rugi transformator dapat dibagi dalam dua jenis: Rugi-rugi tembaga (I2R): Ini adalah rugi daya dalam resistansi dari kumparan primer dan sekunder karena arus beban dan magnetisasi dari transformer. Rugi Inti: Rugi daya ini dala transformer inti dan dikarenakan oleh arus eksitasi. Rugi inti dapat dibagi menjadi rugi-rugi arus eddy dan histerisis. Rugi-rugi arus eddy dikarenakan arus eddy dan arus sirkulasi kecil dalam inti, sedangkan rugi-rugi histerisis dikarenakan oleh ekergi yang dibutuhkan untuk meluruskan luasan dalam material inti magnetik. Rugi inti terus berlanjut selama transformer digunakan. Transformator daya dua lilitan dapat direpresentasikan sebagai diagram rangkaian seperti yang ditunjukkan pada gambar 2.9. Arus eksitasi pada transformator direpresentasikan oleh In, diperlihatkan sebagai arus yang mengalir untuk transformator daya pada umumnya dari 3%-6%. Untuk mnyederhanakan rangkaian ekivalen, arus eksitasi dapat diabaikan. Selanjutnya, diagram rangkaian ekivalen berdasarkan tegangan primer dan sekunder. Gambar 2.10 memberlihatkan diagram rangkaian ekivalen dari
  • 26. transformator berdasarkan sisi sekunder. Beberapa kali diinginkan untuk merepresentasikan transformator berdasarkan vektor diagram. Vektor diagram diperlihatkan pada gambar 2.10 (b) berdasarkan diagram rangkaian ekivalen pada gambar 2.10 (a). 26 LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION PT BADAK NGL BONTANG Gambar 2.9: Diagram Ekivalen Transformator MAULANI CANDRA (0910630076) JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK UNIVERSITAS BRAWIJAYA
  • 27. 27 LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION PT BADAK NGL BONTANG Gambar 2.10: (a) Diagram Ekivalen yang Telah Disederhanakan dan (b) Diagram Vektor yang Telah Disederhanakan MAULANI CANDRA (0910630076) JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK UNIVERSITAS BRAWIJAYA dari Transformator Gambar 2.11: Representasi Grafis dari Transformator Daya Penting untuk mengetahui hubungan antara tegangan transformator dan arus sebagai energi yang ditransformasikan dari satu level tegangan ke lainnya. Berdasarkan
  • 28. transformator yang diperlihatkan pada gambar 2.11. Tegangan, arus, dan impedansi diekspresikan sevagai berikut: 28 LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION PT BADAK NGL BONTANG MAULANI CANDRA (0910630076) JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK UNIVERSITAS BRAWIJAYA 2.2.3.1 Hubungan Tegangan Berdasarkan Hukum Faraday 2.2.3.2 Hubungan Arus Daya masuk = Daya keluar (transformator ideal) 2.2.3.3 Hubungan Impedansi Zps didefinisikan sebagai impedansi bocor antara lilitan primer dan sekunder yang diukur dalam ohm dan pada lilitan primer dan sekunder dihubung singkat. Nilai dari Zps diberikan melalui persamaan
  • 29. Zsp didefinisikan sebagai impedansi bocor antara lilitan sekunder dan primer yang diukur dalam ohm pada lilitan sekunder dengan lilitan sekunder dihubung singkat. Nilai dari Zsp diberikan melalui persamaan: Persamaan tegangan, arus, dan impedansi untuk transformator dapat ditulis ulang 29 LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION PT BADAK NGL BONTANG MAULANI CANDRA (0910630076) JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK UNIVERSITAS BRAWIJAYA sebagai: atau dan Dan sebaliknya: Pada umumnya, untuk transformator daya impedansi dispesifikasikan sebagai persentasi dibandingkan ohm sebenarnya. Persentasi impedansi dari transformator dapat diekspresikan sebagai: Persentase dari impedansi dapat diperlihatkan secara terpisah dari tegangan tegangan terminal dan didasarkan pada rating KVA dari transformator diagram rangkaian ekivalent dari persentase dasar diperlihatkan pada gambar 2.12.
  • 30. 30 LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION PT BADAK NGL BONTANG Gambar 2.12: Diagram Rangkaian Ekivalen dari persentase dasar. MAULANI CANDRA (0910630076) JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK UNIVERSITAS BRAWIJAYA 2.2.4 Pemeliharaan Preventif Transformator Maksud dari bagian ini adalah untuk menjelaskan prosedur praktik dari pemeliharaan preventif transformator. Prosedur yang direkomendasikan ditentukan dalam bab ini. Banyak tugas yang dilakukan selama pemeliharaan rutin dan perbaikan besar dari transformator. Praktek pemeliharaan yang dibahas dalam bagian ini berlaku untuk transformator yang belum mencapai kerusakan yang parah. Selain itu, rekomendasi dari prosedur pemeliharaan preventif transformator ini ditulis untuk kondisi rata-rata dimana transformator diperlukan pemeliharaan selama beroperasi. Hal yang lebih lanjut menjelaskan bahwa semua bagian yang terkait dengan pemeliharaan yang sesuai dengan pengalaman dalam pemeliharaan transformator. Praktek yang direkomendasikan dikemukakan dalam bagian ini dan sama dengan rekomendasi dari perusahaan peralatan untuk lebih detailnya diperlukan pembelajaran dan konsultasi dengan produsen. Pemeliharaan preventif transformator melibatkan pemeriksaan rutin, penyetelan, pengujian, perbaikan kecil, dan petunjuk penanganan khusus. Selain itu, Pengoprasian yang bebas dari masalah pada peralatan selama masa pakai tergantung pada instalasi yang tepat, operasi, dan pemeliharaan, yang akan dibahas dalam Bagian 2.2.7. 2.2.4.1 Instalasi Transformator dan Perawatan Kehandalan operasi dari transformator tergantung pada instalasi yang benar, pemuatan, dan pemeliharaan, serta pada desain yang tepat dan konstruksinya.
  • 31. Sebagaimana dengan semua peralatan listrik, bila mengabaikan salah satu dari persyaratan dasar peralatan listrik dapat menyebabkan masalah serius. Tujuan dari pemeliharaan transformator dapat digambarkan sebagai berikut: 31 LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION PT BADAK NGL BONTANG MAULANI CANDRA (0910630076) JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK UNIVERSITAS BRAWIJAYA 2.2.4.2 Perawatan Biasa Prinsipnya melakukan perawatan berupa melakukan perbaikan, pengaturan alat, dan penggantian komponen yang diperlukan. 2.2.4.3 Perawatan Prinsipnya adalah melakukan pemeliharaan preventif, pemeliharaan prediktif, dan pemeliharaan korektif. Pemeliharaan preventif berupa pemeliharaan secara terjadwal dan pengujian secara teratur. Pemeliharaan prediktif berupa pemeliharaan dengan cara pemantauan alat dan pengujian, sedangkan pemeliharaan korektif berupa pemeliharaan dengan memperbaiki dan memulihkan kondisi sebuah transformator ke kondisi aslinya ketika kondisi mengalami penurunan. Tujuan pemeliharaan pelindung transformator adalah untuk mengontrol dan mencegah kerusakan isolasi pada minyak dan belitan transformator. Kandungan mineral pada minyak dan isolasi kertas pada belitan transformator dipengaruhi oleh kelembaban, oksigen, suhu, dan unsur katalitik lainnya seperti tembaga, besi, stres listrik, dan sebagainya. Hasil akhirnya adalah bahwa oksidasi terjadi dalam minyak yang menyebabkan sludging dari transformator. Dalam tempat yang disegel masuknya uap air melalui kebocoran udara harus dicegah, karena kelembaban akan mengurangi kekuatan dielektrik dari a minyak dan sistem isolasi pada belitan. Selain itu, pemanasan yang berlebihan dari transformator akan menyebabkan isolasi kertas rusak yang menghasilkan kelembaban (yaitu, memecah serat selulosa yang digunakan dalam membebaskan atom hidrogen dan oksigen yang bergabung untuk membentuk H2O). Peningkatan kelembaban pada isolasi kertas tidak hanya mengurangi kekuatan isolasi, tetapi juga mengakibatkan peningkatan suhu dan penurunan kekuatan dielektrik. Langkah pertama adalah membangun desain transformator untuk menjaga kelembaban dan oksigen diluar transformator, Langkah berikutnya adalah dengan
  • 32. mengoperasikan transformator pada rating temperaturnya. Selain itu, tingkat kerusakan harus dikontrol dengan memonitor dan menguji sistem isolasi transformator secara berkala, dan mengambil tindakan korektif untuk mengembalikan transformator ke kondisi aslinya. Prinsipnya dapat diringkas sebagai berikut: 32 LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION PT BADAK NGL BONTANG 1. Pengontrolan suhu dari transformator 2. Memeriksa dan memelihara transformator dengan peralatan tambahan 3. Menguji dan memelihara sistem isolasi transformator 4. Menjaga isolasi bushing transformator 5. Menjaga lapisan pelindung transformator MAULANI CANDRA (0910630076) JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK UNIVERSITAS BRAWIJAYA 2.2.5 Transformator Tipe Kering 2.2.5.1 Pemasangan Faktor-faktor yang harus dingat-ingat dalam menemukan transformator tipe kering adalah aksesibilitas, ventilasi, dan kondisi udara. Transformator tipe kering (Gambar 2.13) biasanya didesain untuk aplikasi dalam ruangan di tempat yang kering. Transformator tipe kering akan beroperasi dengan handal di mana kelembaban mungkin tinggi, tetapi di bawah kondisi tersebut mungkin perlu mengambil tindakan preventif untuk menjaga transformator tetap kering apabila transformator ditutup untuk waktu yang cukup lama. Lokasi di mana ada air menetes harus dihindari, Jika tidak memungkinkan, maka perlindungan yang sesuai harus disediakan untuk mencegah air memasuki tarfo. Harus dilakukan tindakan preventif untuk menjaga terhadap tetesan air, seperti yang mungkin terjadi bila jendela yang terbuka. Celah udara yang cukup sangat penting untuk pendinginan transformator. Udara yang disaring dapat mengurangi perawatan jika lokasi ini terdapat masalah tertentu. Ketika transformator dipasang pada ruang terbatas, celah udara yang cukup harus disediakan untuk menahan suhu udara dalam batas yang ditentukan ketika diukur. Hal tersebut biasanya akan memerlukan minimal 100 ft3 udara/menit/(kW) dari rugi-rugi transformator. Luas celah udara yang diperlukan tergantung pada tinggi dari lemari besi. Untuk pendinginan dari transformator, luas efektif yang diperlukan harus minimal 1 ft untuk setiap inlet dan
  • 33. outlet per 100 kVA dari kapasitas rating transformator, setelah dikurangi daerah yang ditempati oleh layar, kisi-kisi, atau louver. 33 LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION PT BADAK NGL BONTANG Gambar 2.13: Transformator Tipe Kering Berventilasi dengan Penutup Depan untuk memperlihatkan perakitan lilitan-inti. MAULANI CANDRA (0910630076) JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK UNIVERSITAS BRAWIJAYA 2.2.5.2 Pemeriksaan Pada transformator yang baru seharusnya dilakukan pemeriksaan untuk memastikan bila terjadi kerusakan selama pengiriman. Pemeriksaan harus dilakukan sebelum mengeluarkan transformator dari mobil atau truk, dan apabila terdapat indikasi kecacatan pada transformator maka kita seharusnya meminta ganti rugi dan memberitahu produsen transformator. Selanjutnya menghilangkan penutup pada transformator, dan memeriksa koneksi yang kendor, keretakan porselin pada isolasi, kotoran dan benda asing, maupun kelembapan. Tindakan korektif harus diambil bila diperlukan. Sebelum dipindahkan atau apabila transformator disimpan dan belum dipasang pada instalasi, maka proses pengecekan ini dilakukan berulang-ulang. Setelah melakukan semua prosedur pengecekan, transformator harus diperiksa secara menyeluruh. Sebelum dipasang pada instalasi, motor, relay suhu, dan perangkat tambahan lainnya harus diperiksa. Semua koneksi penghubung harus diperiksa bila ada yang kendur, dan bila ada koneksi yang kendur maka harus dikencangkan sebelung
  • 34. transformator dioperasikan. Body dan inti dari transformator seharusnya bersifat tetap dan diketanahkan. 34 LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION PT BADAK NGL BONTANG MAULANI CANDRA (0910630076) JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK UNIVERSITAS BRAWIJAYA 2.2.5.3 Pengujian yang Dianjurkan Setelah transformator dipasang pada instalasi listrik, tes-tes yang dianjurkan berikut yang harusnya dilakukan : Tes isolasi resistance (IR), tes ini bertujuan untuk membandingkan nilai isolasi yang diinginkan dan menentukan kesesuaian transformator dalam memberikan energy dan penerapan tes tegangan tinggi. Tes IR harus dilakukan segera sebelum transformator dioperasikan. Nilai-nilai tes IR, pada suhu pabrik 20°C sekitar 1000 MOhm, atau sama dengan atau lebih besar dari nilai yang ditampilkan dalam Tabel 5.4. Rumus berikut dapat digunakan untuk menghitung nilai IR pada transformator satu fasa atau tiga fasa : Dimana : C = bernilai 30 pada suhupengukuran 20°C E= rating tegangan dari belitan yang diuji kVA = kapasitas rating daya pada belitan Tabel 2.1: Nilai IR dari Tranformator Tipe Kering
  • 35. Tes Indeks Polaritas (PI) Tas ini merupakan pengembangan tes IR dimana dalam tes ini, dua kali dilakukan pengukuran IR, pertama pada 1 menit dan kedua pada 10 menit. Kemudian dihitung rasio keduanya dari pengujian 10 menit dan 1 menit. Tes ini untuk memberikan nilai penyerapan dielektrik. Seharusnya ditentukan tes PI untuk belitan-belitan dan belitan-ground. Nilai tes PI dibawah 2 merupakan indikasi dari kerusakan isolasi. Tes Tegangan Tinggi AC (dielektrik): Tes dielektrik ini memberikan tekanan pada isolasi karena tegangan uji dielektrik lebih tinggi dari tegangan operasi normal. Sebelumnya tes IR harus berhasil sebelum melakukan tes dielektrik untuk mencegah kemungkinan kegagalan transformator akibat kelembaban. Besar tegangan uji tidak boleh melebihi 75% dari nilai tes pabrik. Seting nilai tes teganggan tinggi harus dibuat ber-variable untuk mencegah kemungkinan terjadinya perubahan tegangan uji. Nilai-nilai 35 LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION PT BADAK NGL BONTANG MAULANI CANDRA (0910630076) JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK UNIVERSITAS BRAWIJAYA Tes dielektrik ditunjukkan pada Tabel 2.5.
  • 36. Tabel 2.2: Nilai Pengujian Dielektrik yang Diterima dan Pemeliharaan Periodik dari Tes Rasio Belitan Transformator (TTR) : Tes TTR digunakan untuk menentukan rasio belitan transformator. Tes ini mengukur jumlah lilitan dari belitan primer terhadap jumlah putaran belitan sekunder. Nilai-nilai yang dapat diterima dari tes TTR harus tidak lebih besar dari 0,5% dibandingkan dengan nilai-nilai dihitung. Tes Isolasi Faktor Daya (PF) : Tes ini mengukur lossesrugi-rugi daya dalam isolasi yang diuji. Tes ini berhubungan masalah korona. Tes ini dapat dilakukan sebagai tes tip-up PF untuk transformator tipe kering untuk membedakan penyebab losses sebagai akibat antara kelembaban atau karbonisasi. 36 LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION PT BADAK NGL BONTANG Transformator Tipe Kering. MAULANI CANDRA (0910630076) JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK UNIVERSITAS BRAWIJAYA 2.2.5.4 Perawatan Seperti peralatan listrik yang lain, transformator juga membutuhkan perawatan secara berkala untuk menjamin kehandalannya. Pengecekan harus dilakukan secara berkala dan perlu dilakukan tindakan untuk menjamin kehandalan operasi dari transformator. Rentang pengecekan transformator tergantung pada kondisi operasinya. Untuk keadaan normal, pengecekan dilakukan sekali dalam setahun atau dalam jangka waktu yang lama. Namun untuk transformator yang tercemar debu dan unsur kimia, pengecekan dilakukan 3 atau 6 bulan. Biasanya, setelah pengecekan pertama, jadwal pengecekan yang tetap dapat diatur tergantung kondisi transformator.
  • 37. Pengecekan terhadap bahan pengotor pada permukaan isolasi harus dilakukan begitu juga keadaan berkarat, korosi, dan cat harus diperiksa dan bila perlu diambil tindakan perbaikan. Kipas, motor, dan perangkat tambahan lainnya harus diperiksa dan diservis. Pembersihan: Jika jumlah kotoran pada belitan transformator atau isolasi bertambah banyak perlu dilakukan pembersihan, untuk menjaga sirkulasi udara dan menjaga isolasi dari kerusakan. Belitan transformator dapat dibersihkan dengan vacuum cleaner, blower, atau dengan udara terkompresi. Penggunaan vacuum cleaner dilakukan sebagai langkah pertama dalam membersihkan belitan, kemudian dilanjutkan dengan penggunaan kompresi udara atau nitrogen. Penggunaan pembersih cair tidak dianjurkan karena dapat merusak bahan isolasi. Tes untuk pemeliharaan rutin: Berikut ini adalah tes yang dilakukan untuk 37 LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION PT BADAK NGL BONTANG MAULANI CANDRA (0910630076) JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK UNIVERSITAS BRAWIJAYA pemeliharaan rutin dari transformator tipe kering :  Tes IR pada winding-to-winding dan winding-to-ground.  Tes penyerapan dielektrik harus dibuat winding-to-winding dan winding-to-ground selama 10 menit. Batas dari nilai PI yang diijinkan harus di atas 2.0.  Tes rasio putaran (TTR) harus dilakukan sama seperti tes yang dianjurkan.  Tes teganggan lebih AC harus dilakukan pada semua range tegangan windings-to- ground. Tes ini untuk pengujian perawatan rutin. Nilai yang direkomendasikan dari tes tegangan ditunjukkan pada Tabel 5.4.  Tes Isolasi PF dilakukan untuk hubungan winding-to-ground dan winding-to-winding.. Nilai yang direkomendasikan kurang dari 3%. 2.2.5.5 Metode Drying-Out Untuk tujuan pengeringan (drying out), tranfo dapat dianggap peralatan yang terdiri dari inti dan kumparan. Bila diperlukan pengeringan transformator sebelum diopresikan atau setelah lama tidak operasikan sehingga transformator dalam kondisi
  • 38. kelembaban yang relatif tinggi, sehingga salah satu metode pengeringan transformator berikut dapat digunakan. 38 LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION PT BADAK NGL BONTANG MAULANI CANDRA (0910630076) JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK UNIVERSITAS BRAWIJAYA • External heat • Internal heat • External and internal heat Pengeringan dengan External heat : External heat dapat diterapkan pada transformator dengan metode berikut:  Dengan mengarahkan udara panas ke dalam celah udara yang berada di bawah case transformator.  Dengan menempatkan inti dan kumparan dalam kotak tidak mudah terbakar dan terdapat celah lubang diatas dan dibawah untuk masuknya udara panas.  Dengan meletakkan lampu pijar di dekat transformator Pengeringan dengan Internal heat: Metode ini relatif lambat dan dijadikan alternatif jika dua metode yang lain tidak mengatasi. Transformator harus diletakkan pada posisi dimana memungkinkan sirkulasi bebas dari udara dapat mengair melalui kumparan dari bagian bawah ke bagian atas transformator. Salah satu belitan harus di hubung singkatkan, dan diberi tegangan yang cukup pada frekuensi normal pada belitan kumparan yang lain untuk pendekatan arus normal. Pengeringan dengan External dan Internal heat : metode Ini merupakan kombinasi dari kedua metode-metode yang telah dijelaskan sebelumnya dan sejauh ini merupakan metode yang tercepat. Inti dari transformator dan belitan kumparan harus diletakkan dalam box yang tidak mudah terbakar, External heat diberikan pada transformator seperti yang dijelaskan pada metode pertama, dan arus sirkulasi beredar melalui kumparan seperti yang dijelaskan dalam metode kedua. Disarankan bahwa suhu pemanas tidak melebihi yang disebutkan dalam dua metode sebelumnya. Waktu pengeringan tergantung pada kondisi transformator, ukuran, tegangan, jumlah uap air yang diserap, dan metode pengeringan yang digunakan.
  • 39. 39 LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION PT BADAK NGL BONTANG MAULANI CANDRA (0910630076) JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK UNIVERSITAS BRAWIJAYA 2.2.6 Transformator Tipe Basah 2.2.6.1 Pemasangan Transformator harus dipasang sesuai dengan rekomendasi dari National Fire Protection Association (NFPA) Dokumen 70, NEC Pasal 450. Karena larangan askarel dalam penggunaan cairan sebagai isolasi pada transformator seperti silikon, RTemp, dan lainnya. Cairan ini baru memiliki titik api tidak kurang dari 300 ° C dan NEC telah mengklasifikasikan sebagai cairan ini mudah terbakar. Minyak yang mengisi transformator, dan jika transformator sudah terpasang dalam ruangan harus dimasukkan dalam lemari besi yang tahan api sesuai dengan NEC Pasal 450. Bila transformator terletak di luar ruangan, transformator biasanya dipasang dengan lubang minyak dan diisi dengan kerikil atau batu untuk menahan minyak jika terjadi tumpahan. Kerikil dan batu dapat digunakan untuk menghambat minyak untuk mencegah kebakaran pada case transformator (lihat Gambar 2.14). Jadi ketika kita memasang transformator yang berisi cairan isolasi harus memperhatikan peraturan dan NEC . Gambar 2.14: Transformator Basah Tiga Fasa
  • 40. 40 LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION PT BADAK NGL BONTANG MAULANI CANDRA (0910630076) JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK UNIVERSITAS BRAWIJAYA 2.2.6.2 Pengecekan Pada transformator yang baru seharusnya dilakukan pemeriksaan untuk memastikan bila terjadi kerusakan selama pengiriman. Pemeriksaan harus dilakukan sebelum mengeluarkan transformator dari mobil atau truk pengiriman, untuk melihat. Selanjutnya pengecekan secara internal dilakukan dengan menghilangkan penutup pada transformator, dan memeriksa koneksi yang kendor, keretakan porselin pada isolasi, kotoran dan benda asing, maupun kelembapan. Jika minyak atau cairan transformator sudah dipasang di pabriknya, maka sebaiknya kita memeriksa transformator dari kebocoran. Selain itu pemeriksaan tekanan gas positif dilakukan jika transformator dilengkapi dengan gas inert. Pengecekan harus mencakup pemeriksaan case transformator, bushing, jangkar dan, kabel grounding, saluran air, penutup transformator, katup, dan peralatan lainnya yang dikirim bersama transformator. Apabila pemeriksaan internal transformator selesai. pastikan terdapat saluran celah udara pada tangki transformator sebelum tangki terpasang pada transformator. Perlu perhatian penting bahwa harus ada kandungan oksigen paling sedikit 16% sebelum cairan dimasukkan pada tangki transformator. Penutup tidak boleh dibuka dalam keadaan basah, karena cairan transformator tidak boleh terkontaminasi dengan udara di atmosfer ketika kelembaban relatif di atas 65%. 2.2.6.3 Pengujian yang Dianjurkan Sebelum transformator dipasang pada instalasi listrik, tes-tes yang dianjurkan berikut yang harusnya dilakukan : Tes IR : Tes IR bertujuan untuk menentukan apakah transformator dalam kondisi baik dan juga dijadikan acuan untuk tes transformator kedepannya. Nilai-nilai IR yang diukur merupakan fungsi temperatur, apakah kumparan direndam dalam cairan transformator atau tidak, atau apakah belitan dalam kondisi dingin atau panas. Nilai yang diukur harus dikoreksi sampai 20 ° C dengan mengalikannya dengan faktor koreksi. Dalam melakukan tes IR menggunakan alat megohmmeter yang biasa disebut Megger, dimana nilai IR yang terukur dalam satuan jutaan ohm (atau megohms). Megger memiliki rentang tegangan minimum yang ditunjukkan pada Tabel 2.3 (nilai
  • 41. yang direkomendasikan untuk rating tegangan dari berbagai transformer). Nation Electrical Testing Association (NETA) menunjukkan nilai-nilai yang digunakan untuk tes yang dianjurkan dan pemeliharaan transformator (Tabel 2.2). Nilai tes IR harus dibandingkan dengan nilai tes IR yang dilakukan pabrik. Apabila tidak ada data yang dapat dijadikan acuan dari tes sebelumnya, rumus berikut dapat digunakan untuk transformator satu fasa, atau transformator tiga fasa dengan satu belitan. 41 LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION PT BADAK NGL BONTANG MAULANI CANDRA (0910630076) JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK UNIVERSITAS BRAWIJAYA Dimana : C = bernilai 30 pada pada suhu pengukuran 20 ° C (C = 0,8 untuk tes kumparan dengan kumparan lainnya atau kumparan yang digrounkan) E adalah rating tegangan dari belitan yang diuji kVA adalah kapasitas rating dari belitan yang diuji Jika transformator yang diuji adalah jenis transformator tiga fasa maka : E adalah rating tegangan dari salah satu fase kumparan kVA adalah kapasitas rating belitan tiga fasa dari transformator yang diuji yang diuji Tes dielektrik cairan isolasi : Cairan isolasi harus di tes dengan cara diambil samplenya sesuai standar dengan ASTM D-923 dan tes ini bertujuan untuk menentukan kekuatan dielektrik-nya, keasaman, kelembaban, interfacial tension, warna, dan PF. Tes ini dilakukan untuk memastikan bahwa cairan isolasi tidak berada pada level yang bervariasi atau untuk memastikan kekuatan dielektrik belum turun karena
  • 42. terkontaminasi benda asing. Sampel minyak dan Rtemp diambil dari bagian bawah tangki, sedangkan sampel untuk askarel dan silikon diambil dari bagian atas tangki. Tes TTR : Tes TTR ini bertujuan untuk memastikan bahwa rasio putaran transformator dalam keadaan yang handal, dimana tidak ada kumparan transformator yang sort circuit. Pada dasarnya tes ini membandingkan jumlah putaran di kumparan 1 dengan jumlah putaran pada kumparan 2. Tes ini dilakukan pada setian tap pada transformator yang dilengkapi dengan tap changers. Tes TTR ini juga dapat digunakan untuk memeriksa polaritas transformator. Nilai dari tes TTR ini yang masih dapat ditoleransi tidak boleh lebih besar dari 0,5% dibandingkan nilai yang dihitung pada (lihat Bagian 2.2.7.1). Tes Hi-pot : Tes Hi-pot ( tes ini juga disebut tes tegangan tinggi) dilakukan pada semua rentang teganggan tinggi dan rendah kumparan pada transformator ke ground. Baik tegangan AC maupun DC dapat digunakan pada tes ini. Namun dalam praktiknya baik itu tegangan AC maupun DC tidak melebihi 34 kV, untuk transformator diatas 34kV, tes tegangan tinggi AC yang dapat digunakan. Tegangan AC yang diberikan pada transformator dengan rentang waktu 3 menit, Jika pada tes ini transformator tidak mengalami kegagalan dan tidak terjadi kerusakan maka transformator sudah layak digunakan (lihat Bagian 5.8.1). PF (dissipation factor) test: Tes ini seharusnya dilakukan untuk transformator besar. Tes ini memberikan tekanan dari tegangan pada isolasi transformator yang nilai 42 LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION PT BADAK NGL BONTANG Tabel 2.3: Nilai IR dari Transformator yang Diisi Cairan MAULANI CANDRA (0910630076) JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK UNIVERSITAS BRAWIJAYA
  • 43. tekanannya sebanding dengan tekanan yang dihasilkan pada pengoprasian normal, karena tes ini merupakan tes dengan teganggan AC. Frequency response analysis (FRA): Tes FRA ini digunakan untuk menilai keadaan dari komponen mekanik seperti dari kumparan dan inti pada transformator dengan daya yang besar. Tujuan tes ini adalah untuk mengamati peerubahan karakteristik fisik pada sebuah transformator yang dikarenakan terjadi kesalahan, pengiriman, perbaikan dan pengaruh lainya. Sinyal teganggan dengan range frekuensi yang lebar diberikan pada terminal transformator yang yang dicerminkan dari respon pengukurannya. 43 LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION PT BADAK NGL BONTANG MAULANI CANDRA (0910630076) JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK UNIVERSITAS BRAWIJAYA 2.2.6.4 Perawatan Seperti peralatan listrik lain, transformer membutuhkan perawatan dari waktu ke waktu untuk menjamin keberhasilan operasi. Inspeksi harus dilakukan secara berkala dan tindakan korektif dilakukan jika diperlukan untuk menjamin layanan yang paling memuaskan dari peralatan ini. Frekuensi inspeksi tergantung pada kondisi operasi. Untuk lokasi yang bersih dan kering, inspeksi setiap tahun, atau setelah jangka waktu lama, mungkin sudah cukup. Namun, untuk lokasi lainnya, seperti mungkin ditemui di mana udara yang tercemar dengan asap debu orchemical, inspeksi dengan interval 3 atau 6 bulan mungkin diperlukan. Biasanya, setelah periode beberapa pemeriksaan pertama, jadwal pasti dapat diatur berdasarkan kondisi yang ada. Pembersihan: Jika akumulasi berlebihan dari kotoran ditemukan pada gulungan transformator atau isolator ketika transformator diperiksa, kotoran harus dihapus untuk memungkinkan sirkulasi bebas dari udara dan untuk menjaga terhadap kemungkinan kerusakan isolasi. Perhatian khusus harus diberikan untuk membersihkan ujung atas dan bawah belitan dan untuk membersihkan saluran ventilasi. 2.2.6.5 Pemeliharaan Tujuan pemeliharaan transformator adalah untuk menjaga terhadap kerusakan dengan mendeteksi penyebab potensial dan menghilangkan mereka. Oleh karena itu, pemeliharaan transformator berkala akan memastikan bebas masalah operasi selama
  • 44. bertahun-tahun. Transformator merupakan perangkat yang sangat sederhana, kasar dan sering diabaikan dan dilupakan sampai kegagalan transformator terjadi. Namun, transformator adalah link yang penting dalam sistem distribusi listrik dan harus diberikan perawatan yang tepat dan perhatian. Jadwal pemeliharaan transformator harus ditentukan sesuai dengan sifat kritis atau tidak kritis dari transformator dan beban yang terhubung. Transformer listrik yang besar jelas lebih penting daripada pencahayaan kecil dan transformator distribusi, dengan demikian mereka membutuhkan perhatian lebih dan perawatan. Pemeliharaan dari transformator harus mencakup pemeriksaan rutin dan perbaikan, pemeliharaan transformator cair dan pengujian, pemeliharaan isolasi belitan transformator dan pengujian, dan setiap pemeliharaan khusus lainnya yang dianjurkan oleh produsen transformator. Sebuah pemeliharaan dan panduan pengujian transformator daya dengan frekuensi yang direkomendasikan diberikan pada Tabel 2.7. 44 LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION PT BADAK NGL BONTANG Tabel 2.4: Daftar Pengecekan Inspeksi dan Pemeliharaan Transformator MAULANI CANDRA (0910630076) JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK UNIVERSITAS BRAWIJAYA
  • 45. Pemeriksaan rutin dan perbaikan: inspeksi rutin dan perbaikan transformator melibatkan pengamatan visual dari kondisi operasi transformator dan perbaikan yang diperlukan. Frekuensi pengamatan ini tergantung pada pentingnya transformator, kondisi lingkungan, dan / atau kondisi operasi. Berbagai organisasi seperti NFPA, Neta, dan produsen transformator telah menerbitkan panduan untuk interval inspeksi dan apa yang harus memeriksa. Berikut ini adalah jadwal untuk melakukan inspeksi rutin. Arus beban: Pembebanan transformator menentukan pemanasan transformator. Suhu transformator menentukan harapan hidup, dan penting pada unit besar untuk memonitor beban pada setiap jam. Untuk pembebanan yang tepat dari transformator, 45 LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION PT BADAK NGL BONTANG MAULANI CANDRA (0910630076) JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK UNIVERSITAS BRAWIJAYA
  • 46. lihat standar ANSI C57.92 untuk transformator terendam cairan dan ANSI C57.96 untuk kering tipe transformator. Untuk transformator daya kecil, pembacaan dapat dilakukan secara harian atau mingguan. Tegangan: Tegangan dari transformator harus dipantau sama seperti arus beban. Untuk menjaga rating tegangan sekunder, wajib digunakan tegangan primer yang sesuai . Pembacaan tegangan dapat diambil bersama dengan arus beban. Pada transformator kurang penting, pembacaan tegangan dapat diambil setiap minggu. Level Cairan: level cairan penting karena tidak hanya memasok pendinginan medium tetapi juga isolasi dari belitan. Kehilangan cairan dapat terjadi karena penguapan dari cairan atau karena kebocoran. Pembacaan liquid level dapat diambil ketika pembacaan beban yang diambil. Cairan yang hilang dari transformator harus diganti segera. Suhu: Kemampuan pembebanan dari transformator tergantung pada kemampuan suhu. Suhu total transformator adalah jumlah dari suhu lingkungan, suhu lilitan isolasi, dan suhu hot-spot. Bila transformator dioperikan di atas rating suhunya dapat menyebabkan berkurangnya life time dari transformator itu sendiri. Peralatan proteksi: Proteksi transformator dasar dibuat oleh NEC. Proteksi ini dilengkapi dengan relay dan peralatan proteksi tambahan. Adalah penting bahwa alat proteksi diperiksa dan dipelihara secara teratur untuk memastikan bahwa perangkat ini akan beroperasi dalam kasus kerusakan atau kegagalan transformator. Alarm proteksi: Transformator dilengkapi dengan beberapa tipe alarm seperti temperatur lebih, temperatur cairan, dan temperatur tekanan. Itu semua biasanya berupa skalar tipe normally open yang dapat dihubungkan ke baik itu alarm atau untuk memutus CB. Kontak alarm dan hubungan perkabelannya seharusnya diperiksa setiap bulannya. 46 LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION PT BADAK NGL BONTANG MAULANI CANDRA (0910630076) JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK UNIVERSITAS BRAWIJAYA
  • 47. Hubungan pentanahan: Tangki transformator selalu kokoh diketanahkan untuk menghilangkan sengatan listrik per NEC. Sambungan ke tanah tangki transformator harus diperiksa apakah longgar, terputus ataupun sudah berkarat. Resistansi pentanahan dari sebuah GI tergantung pada jenis dan ukuran dari GI itu sendiri. Resistansi pentanahan sangan bervariasi dari 1 ohm untuk GI berukuran besar sampai 25 ohm untuk GI berukuran sangat kecil. Frekuensi dari pemeriksaan dan tes seharusnya setiap tahun sekali. Lightning Arrester: Ketika transformator dipasok dari saluran udara, Lightning arrester digunakan untuk melindungi transformator dari petir dan surja lainnya. Arrester petir harus diperiksa untuk kelonggaran, bagian yang rusak, kotoran, dan lapisan lainnya. Semua kotoran dan lapisan harus dibersihkan, sambungan yang longgar harus dikencangkan, dan bagian yang rusak diganti selama cek ini. Pemeriksaan dari arrester petir dan sistem grounding harus dilakukan setiap tahun. Perangkat pressure-relief: transformator kebanyakan dengan seal dilengkapi dengan perangkat pressure-relief untuk mengurangi tekanan yang berlebihan dalam tangki akibat busur api internal. Perangkat ini diatur untuk membuka pada tekanan 10- 15 psi. Pemeriksaan rutin perangkat pressure-relief harus mencakup memeriksa kebocoran di sekitar sendi, retak diafragma, dan sejenisnya. Pemeriksaan ini harus dilakukan triwulanan. Breather: transformer memilik banyak breather baik itu tipe terbuka atau jenis dehidrasi. Fungsi agen dehidrasi adalah untuk mencegah kelembaban memasuki tangki transformator. Kebanyakan breather tipe dehidrasi mengandung gel silika, yang akan berubah dari biru ketika kering ke merah muda pucat saat basah. Pemeriksaan dapat dilakukan melalui jendela kaca yang disediakan untuk tujuan tersebut. Breather harus diperiksa bulanan dan agen dehidrasi diganti atau direkondisi jika ditemukan rusak atau basah. 47 LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION PT BADAK NGL BONTANG MAULANI CANDRA (0910630076) JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK UNIVERSITAS BRAWIJAYA
  • 48. Peralatan bantu: peralatan Bantu yang dibutuhkan untuk pendinginan, seperti kipas, minyak pompa, alat kontrol, dan kabel, harus diperiksa setiap tahun. Peralatan tersebut harus dibersihkan dan bagian yang rusak diganti. Cairan transformer: Semua cairan transformator mudah mengalami kerusakan, dan kontaminan utama adalah udara, kelembaban, dan panas. Kontaminan ini bereaksi dengan cairan transformator dan memproduksi asam dan lumpur. Asam, pada gilirannya, menyerang isolasi belitan, dan lapisan lumpur cenderung menurunkan pendinginan. Kelembaban dalam cairan transformator cenderung menurunkan kekuatan dielektrik dari cairan, yang dikombinasikan dengan lumpur, akan menurunkan nilai dari isolator flashover dan papan terminal di dalam tangki transformator. Sebagaimana dibahas sebelumnya, pemeriksaan rutin dari transformator diperlukan untuk menjaga cairan dalam keadaan bebas kontaminan. 48 LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION PT BADAK NGL BONTANG MAULANI CANDRA (0910630076) JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK UNIVERSITAS BRAWIJAYA 2.6.6 Metode Drying-Out Mirip dengan transformator jenis kering, cairan isolasi transformator dapat dianggap terdiri dari inti dan susunan koil, kecuali bahwa koil direndam dalam cairan isolasi. Langkah-langkah rumit yang diambil untuk mencegah dan mendeteksi perembesan dan peningkatan kadar air dalam transformator. Sebelum cairan transformator menjadi jenuh dengan air, isolasi kertas gulungan di transformator telah menyerap konsentrasi uap air karena afinitas yang besar untuk air. Air di isolasi kertas mempercepat degradasi isolasi dan menurunkan integritas listriknya. Distribusi uap air dalam transformator selalu dalam keadaan tidak seimbang. Melalui rentang yang lebih dingin dari suhu, isolasi padat gulungan transformator akan cenderung menyerap kelembaban lebih dari cairan transformator. Namun, ketika transformator dibebani, kenaikan suhu belitan akan melepas kelembaban ini. Perubahan akibat beban yang bervariasi dan suhu adalah konstan, terlepas dari apakah ada kelebihan air atau hanya jumlah yang sangat kecil kelembaban dalam transformator. Juga, cairan transformator seperti minyak cenderung menahan lebih banyak air dengan peningkatan suhu. Dengan kata lain, akan ada lebih banyak uap air dalam minyak transformator ketika pembebanan daripada saat dibongkar. Faktor-faktor lain, seperti
  • 49. dekomposisi isolasi kertas dan kontaminan, akan cenderung menghasilkan lebih banyak uap air dalam cairan transformator. Ketika diperlukan untuk mengeringkan cairan transformer, metode berikut dapat digunakan: (1) panas saja, atau (2) panas diikuti dengan vakum. Panas saja: Metode ini melibatkan pemberian panas saja ke transformator. Salah satu bentuk aplikasi metode ini adalah oven pengeringan, yang bisa dilakukan di salah satu service shop dari produsen besar. Ketika transformator adalah dikeringkan di tempat ini, penting untuk memantau resistensi belitan untuk melihat kapan transformator, mencapai suhu oven (100 ° C-120 ° C). Pengukuran PF dan IR harus dilakukan pada interval sekitar 6 jam untuk melihat kapan pengeringan dicapai, yaitu, ketika sedikitnya empat pembacaan mempunyai nilai yang sama. Panas diikuti oleh vakum: Pemanasan transformator dengan cairan dapat dilakukan dengan menerapkan hubung singkat ke transformator atau dengan mengedarkan minyak panas melalui sistem luar. Seperti pada metode sebelumnya, pengukuran PF dan IR harus dilakukan pada interval sekitar 6 jam. Pengeringan berarti telah selesai ditunjukkan oleh sedikitnya empat pembacaan yang sama. metode bidang pengeringan mungkin melibatkan pemanasan cairan transformator, menghilangkan cairan, dan segera menerapkan vakum. Metode lain mungkin melibatkan menghilangkan cairan dan pemanasan transformator dengan sirkulasi udara panas. Setelah belitan mencapai 90 ° C-100 ° C maka vakum sekitar 0,5 Torr bisa diterapkan. Ketika suhu turun di bawah 50 ° C, pengeringan dihentikan. Panjang normal waktu untuk menerapkan panas dan vakum mungkin seminggu atau lebih, tergantung pada ukuran transformator. Setelah transformator dikeringkan dan vakum ditarik, minyak transformator yang telah dibersihkan dapat dimasukkan kembali ke transformator. Tindakan preventif untuk mengamati selama proses ini adalah sebagai berikut: 49 LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION PT BADAK NGL BONTANG MAULANI CANDRA (0910630076) JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK UNIVERSITAS BRAWIJAYA 2.2.7 Pengujian Transformator Transformator dapat di tes dengan tegangan AC atau DC. Secara keseluruhan, tegangan AC lebih sering digunakan daripada DC karena tegangan AC
  • 50. dapat mensimulasikan internal stress pada transformator yang serupa saat kondisi pengoperasian. Berikut merupakan tes yang biasanya dilakukan secara rutin pada 50 LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION PT BADAK NGL BONTANG MAULANI CANDRA (0910630076) JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK UNIVERSITAS BRAWIJAYA transformator : a. IR test b. Tes tegangan tinggi (AC atau DC) c. TTR test d. Tes polaritas e. Tes arus eksitasi f. Tes tegangan induksi g. Tes cairan insulasi dielektrik h. Tes DGA i. Polarization recovery voltage test j. Transformer core ground test k. Frequency response analyzer(FRA)/ sweep FRA (SFRA) l. Resistansi belitan DC 2.2.7.1 Tes Tegangan Tinggi AC Tes tegangan tinggi AC di lakukan untuk mengevaluasi kondisi dari belitan transformator. Tes ini direkomendasikan pada semua tegangan, terutama di atas tegangan 34.5 kV. Untuk perawatan rutin transformator, tegangan yang digunakan saat tes harus tidak melebihi 65% dari tegangan tes pabrik. Akan tetapi, tes tegangan tinggi untuk perawatan rutin biasanya tidak dilakukan pada transformator karena terdapat kemungkinan bahwa tes dapat merusak isolasi belitan. Tes ini biasanya di lakukan untuk untuk uji kelayakan atau setelah memperbaiki transformator. Tegangan yang digunakan tidak boleh melebihi 75% dari tegangan pabrik. Ketika tes tegangan tinggi digunakan untuk perawatan rutin, transformator yang di tes dapat di kenai tegangan rating selama 3 menit daripada menggunakan 65% tegangan tes pabrik.
  • 51. 51 LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION PT BADAK NGL BONTANG MAULANI CANDRA (0910630076) JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK UNIVERSITAS BRAWIJAYA 2.2.7.2 Pengujian TTR Tes ini pada dasarnya digunakan untuk mendeteksi apakah tegangan dihasilkan pada belitan sekunder atau tidak. Jika menggunakan TTR tegangan rendah yang dengan sumber tenaga tangan, pada belitan tegangan rendah diberi sumber 8 V dan transformator referensi di bagian TTR. Belitan di sisi tegangan tinggi dan transformator referensi dari TTR di hubungkan melalui sebuah null detecting instrument. Setelah tegangan seimbang di 8 V dan alat pendeteksi menunjukkan angka 0, alat penunjuk mengindikasikan rasio perbandingan belitan dari transformator tersebut. Hasil atau informasi yang ditunjukkan tes TTR ialah sebagai berikut  Menunjukan rasio perbandingan jumlah belitan dan masing – masing polaritas dari single atau transformator 3 phasa.  Memastikan nameplate dari transformator, terutama pada rasio, polaritas, dan vektor  Menunjukan rasio dan polaritas (tapi tidak rating voltage) dari transformator . Tes termasuk penggunaan semua posisi tap pada kondisi no-load dan dengan beban, tap changer (LTC) jika transformator dihubungkan dengan control sudut fasa. Pada transformator LTC yang dihubungkan dengan pengkontrol sudut fasa, tes rasio dan polaritas dilakukan hanya pada posisi netral. Jika di tes pada tap berbeban, pembacaan dapat digunakan sebagai referensi untuk pembanding di kedepannya, tetapi akan menurun jika dibandingkan dengan nameplate. Tap pada LTC dapat di konfirmasikan dengan diberi sumber tegangan rendah 3 fasa dan pembacaan tengangan dan sudut fasa untuk setiap fasa.  Mengidentifikasi masalah pada belitan transformator, misalnya open-circuit dan short-circuit yang berdampak pada sensitivitas dari perbandingan jumlah belitan. Standart deviasi telah ditentukan di ANSI/IEEE C5.7.12.00-2006 bagian 9.1 yang menjelaskan bahwa hasil harus berkisar kurang lebih 0.5% dari nameplate dengan tegangan rating yang di aplikasikan pada salah satu belitan. TTR dengan error 0.1% diperbolehkan menjadi penentu.
  • 52. Gambar 2.15: TTR testers: (a) hand-crank TTR; (b) handheld electronic TTR; and (c) three-phase  Transformator di isolasi dan di tandai  Baca nameplate dari transformator  Perhatikan polaritas dan vector (phasornya)  Hitung perbandingan belitan untuk setiap posisi tap pada kondisi no-load dan 52 LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION PT BADAK NGL BONTANG electronic TTR. (Courtesy of Megger Inc., Valley Forge, PA.) Berikut merupakan prosedur dari pelaksanaan tes TTR MAULANI CANDRA (0910630076) JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK UNIVERSITAS BRAWIJAYA berbeban 2.2.7.3 Pengujian Polaritas Tes polaritas dapat dilakukan dengan menggunakan tes TTR pada transformator daya, distribusi, dan tegangan. Akan tetapi pada transformator arus tes TTR tidak dapat dilakukan. Tetapi menggunakan sebuah tes yang dikenal dengan sebutan kick test,
  • 53. dengan member sumber melalui baterai DC dan menggunakan multimeter. Kick test dapat juga digunakan pada transformator daya, distribusi, dan tegangan tetapi tes TTR lebih sering digunakan. Rangkaian untuk kick test pada transformator arus dapat terlihat pada gambar 5.19. Baterai DC yang digunakan biasanya memiliki tegangan berkisar 7.5V dan range dari multimeter di set untuk 3 V full-scale. Bagian negative dari sumber di hubungkan pada transformator arus di H2 dan bagian positif dibiarkan untuk sementara. Bagian positif dari multimeter dihubungkan pada bagian sekunder di X1 dan bagian negative di X2. Untuk melakukan tes ini, hubungkan bagian positif dari sumber ke H1 dan perhatikan skala pada multimeter. Jika skala pada multimeter menunjuk pada skala atas maka transformator tersebut terhubung pada subtractive polarity, jika menunjuk skala bawah maka terhubung pada additive polarity. 53 LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION PT BADAK NGL BONTANG MAULANI CANDRA (0910630076) JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK UNIVERSITAS BRAWIJAYA 2.2.7.4 Pengujian Potensial Induksi Tes ini merupakan suatu tes pembuktian dan dilakukan pada tingkat tegangan yang lebih tinggi daripada tegangan operasionalnya. Dalam tes ini, isolasi antar belitan dan isolasi antar fasa dikenai tegangan 65% dari tegangan tes pabrik dan pada frekuensi yang lebih tinggi dari 60 Hz, misalnya 200-300 Hz. Tes ini harus dilakukan tiap 5 tahun sekali atau lebih pada transformator yang besar. Tes tegangan induksi untuk transformator diberi sumber tegangan melalui salah satu belitan dan diberi tegangan 2 kali lipat tegangan normal di belitan tersebut selama 7200 gelombang dan durasinya tidak boleh melebihi 60 detik. Tabel 2.5: Frequency versus Duration of Test Frequency (Hz) Duration (s) 120 and less 60 180 40 240 30 300 20 400 18
  • 54. Ketika tes ini dilakukan pada transformator, frekuensi dari tegangan yang diberikan seharusnya cukup tinggi untuk mencegah arus dari transformator yang di uji melebihi 30% dari arus ratingnya. Biasanya untuk menguji peralatan yang menggunakan frekeuensi 60 Hz digunakan frekuensi sebesar 120 Hz. Ketika digunakan frekuensi yang lebih tinggi dari 120 Hz, resiko dari tes ini secara abnormal meningkat dengan pesat dan hal tersebut menyebabkan waktu pengujian harus di persingkat seperti pada table 5.10. Tegangan awal harus bernilai seperempat atau kurang dari tegangan penuh dan secara bertahap di tingkatkan dalam waktu tidak lebih dari 15 detik. Setelah diuji selama waktu yang tertera pada tabel 5.10, nilai tegangan harus diturunkan secara perlahan (tidak boleh lebih dari 5 detik) ke seperempat atau kurang dari nilai penuh, dan setelah itu sirkuitnya di open. Saat menguji transformator dengan sebuah belitan yang di ketanahkan untuk pengoperasian pada suatu ground-netral system, kewaspadaan dan pengawasan harus diperketat untuk menghindari tekanan elektro statis yang tinggi di antara belitan lain dan ground. Jika transformator memiliki salah satu belitan sisi tegangan tinggi di tanahkan ketika tes induksi tegangan, pentanahan dari setiap belitan dapat di buat pada suatu titik tertentu dari belitan tersebut atau dari belitan transformator step-up yang digunakan untuk member tegangan atau hanya sekedar di hubungkan dengan tujuan memberi pentanahan. Transformator tiga fasa dapat di uji dengan tegangan satu fasa, tegangan untuk menguji di induksikan dari tiap line terminal ke ground atau ke line terminal yang lain. Bagian netral dari belitan boleh di groundkan saat tes tersebut. Ketika tes induksi pada belitan menghasilkan tegangan di antara terminal dari belitan yang lain, belitan yang lain dapat di tanahkan, Tes induksi tambahan harus dilakukan untuk memberikan tegangan uji di antara terminal yang di ketanahkan. 54 LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION PT BADAK NGL BONTANG MAULANI CANDRA (0910630076) JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK UNIVERSITAS BRAWIJAYA
  • 55. 55 LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION PT BADAK NGL BONTANG MAULANI CANDRA (0910630076) JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK UNIVERSITAS BRAWIJAYA 2.2.7.5 FRA Tes FRA dapat di lakukan sebagai respon impuls dari tes SFRA, metode impuls memperkirakan respon frekuensi dan respon frekuensi sapu mengukur respon dari tingkat frekuensi tertentu. Tes FRA dan SFRA merupakan nondestructive test yang digunakan untuk mengetahui deformasi (pergeseran) dari inti dan kumparan. Respon frekuensi sapu ialah kemajuan yang besar pada analisis kondisi transformator, tes tersebut medapat memberi kita visualisasi dari isi tanki transformator tanpa membukanya. Pengertian FRA pada umumnya adalah perbandingan dari output sinusoidal yang stabil dari objek yang di tes dengan input sinusoidal yang stabil. SFRA adalah teknik yang terbukti untuk menghasilkan pengukuran yang akurat dan presisi. Di antara konfigurasi geometris dari belitan dan inti, serta jaringan impedansi yang disusun seri dan paralel sebenarnya terdapat suatu hubungan. Jaringan ini dapat di identifikasi karena jaringan tersebut memiliki transfer function yang bergantung pada frekuensi. Tes FRA dengan metode respon frekuensi sapu menggunakan alat analisis jaringan untuk menentukan transfer functionnya. Perubahan pada konfigurasi geometris dapat mengubah jaringan impedansi dan berakibat berubahnya transfer functionnya, hal tersebut mengakibatkan kegagalan dapat di identifikasi. Masalah mekanis yang biasanya terdeteksi pada transformator dengan tes FRA adalah :  Pergeseran inti  Pergeseran belitan atau deformasi belitan  Pentanahan inti yang rusak  Kerusakan sebagian pada belitan  Tertekuknya hoop  Patah atau kendornya penjepit  Belitan yang open atau short circuit 2.2.7.6 DC Resistansi Lilitan Tes ini mengukur resistansi DC dari kabel transformator dan belitannya dengan menggunakan ohmmeter atau jembatan Kelvin. Resistansi belitan dapat berubah karena hubung singkat di antara belitan, belitan longgar, bahkan karena memburuknya
  • 56. hubungan di tap changer. Salah satu masalah yang berhubungan dengan pengukuran resistansi DC pada transformator ialah bagian induktif harus di energisasikan. Bagian induktif harus termuati dan di stabilkan agar dapat menghasilkan pembacaan yang akurat. Pengukuran harus dilakukan pada setiap posisi tap changer (jika ada) dan dibandingkan dengan hasil pengukuran sebelumnya atau hasil tes pabrik. Selisih dari hasil pengukuran di lapangan dengan hasil tes pabrik harus kurang dari 2% untuk kriteria penerimaan. Jika lebih dari kriteria penerimaan, terdapat kemungkinan terjadi hubung singkat pada belitan, sendi yang lemah, atau penghubung tap changer yang buruk. Tes ini harus dilakukan ketika tes kelayakan dan ketika tes perawatan lain dilakukan. 56 LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION PT BADAK NGL BONTANG MAULANI CANDRA (0910630076) JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK UNIVERSITAS BRAWIJAYA 2.2.7.7 Pengujian Transformator Core Ground Pengukuran IR dilakukan untuk menentukan adanya pentanahan pada inti yang tidak disengaja. Pada umumnya, inti yangn berlapis dari transformator daya terisolasi dari ground, dan secara sengaja di ketanahkan pada satu titik. Biasanya titik ini dapat di akses dari bagian atas transformator, entah itu melewati bushing yang kecil atau di belakang tutup manhole. 2.2.7.8 Polarization Recovery Voltage Test Sistem isolasi transformator merupakan gabungan dari dua materi isolasi, yaitu cellulose fiber (kertas) dan minyak isolasi. Gambar 2.16: IR tester (megohmmeter). (Courtesy of Megger Inc., Valley Forge, PA.) Struktur ini menunjukan efek polarisasi pemuatan ruang yang mana sebagian
  • 57. besar dipengaruhi oleh kelembapan dan umur produk. Hal tersebut menyebabkan pengurangan dari time konstan. Time constant yang dihasilkan oleh polarisasi pemuatan ruang melebihi 10 ms, dan pada isolasi baru yang kering dapat mencapai 1000 s. Gambar 2.17a menunjukan suatu RVM (recovery voltage meter). Saklar S1 di tutup selama tc dan sumber tegangan DC U di berikan pada tegangan tertentu ke kapasitor (objek yang di tes), saklar S1 kemudian di buka dan saklar S2 ditutup selama td (biasanya td = tc/2). Bagian dari kapasitor yang termuati terdisipasi lalu saklar S2 di buka dan sisa dari muatan apasitor menghasilkan tegangan di bagian elektroda dari kapasitor (gambar 5.23b). Terdapat dua parameter yaitu tegangan pembalik pada nilai maksimum (Vmax) dan initial slope (tan d). Jika tc dan td meningkat dari nilai mula yang kecil, maka akan terjadi perubahan nilai pada Vmax dan tan d pada setiap perubahan tc. Gambar 2.17c menunjukan perubahan dari Vmax dengan tc; dapat dilihat bahwa kurva Vmax/tc berada pada pincak saat mencapai nilai time constant. Hasil ini menunjukan bahwa kurva Vmax/tc juga menunjukan spektrum polarisasi dengan nilai maksimum pada time constant isolasi. 57 LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION PT BADAK NGL BONTANG MAULANI CANDRA (0910630076) JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK UNIVERSITAS BRAWIJAYA
  • 58. Gambar 2.17: (a) Prinsip Rangkaian Pengukuran tegangan recovery dari Waktu tc; (b) Siklus Pengukuran RVM dan kuantitas perekaman selama satu siklus; dan (c) tegangan recovery 58 LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION PT BADAK NGL BONTANG V sebagai fungsi waktu tc. MAULANI CANDRA (0910630076) JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK UNIVERSITAS BRAWIJAYA 2.3 Reaktor 2.3.1 Definisi Pada intinya reaktor adalah induktor. Secara fisik ini adalah koil kabel yang didalamnya terdapat medan magnet karena aliran arus listrik yang melewati koil tersebut. Ketika di energize gaya magnet yang terbentuk menekan aliran listrik yang melewatinya sehingga arus dapat disesuaikan dengan kebutuhan dan tidak berlebih sehingga arus dapat disesuaikan dengan kebutuhan dan tidak berlebihan sehingga arus yang keluar dari reaktor aman untuk peralatan listrik. Sebuah loop sederhana pada kabel akan membawa sifat konduktor. Ketika semakin banyak loop-nya maka akan membuat nilai induktansi semakin tinggi. Kebanyakan bahan seperti besi ditambahkan sebagai pelindung dari belitan. Ini
  • 59. memiliki efek dari pengonsentrasian fluks magnetis yang akan membuat induktor semakin efektif. 59 LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION PT BADAK NGL BONTANG MAULANI CANDRA (0910630076) JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK UNIVERSITAS BRAWIJAYA 2.3.2 Tipe dari Reaktor Seri Dry-type air-core 1. Air-core Reactor Sebuah reaktor yang tidak memiliki sebuah lapisan magnetis atau perisai magnet dan menggunakan aliran udara di sela-selanya sebagai pendingin. 2. Iron-core Reactor Sebuah reaktor yang memiliki perisai besi sebagai pelindung dan menggunakan oli sebagai pendingin. 3. Indoor Reactor Reaktor yang diletakkan dalam ruangan tertutup karena konstuksinya yang harus dilindungi dari cuaca luar. 4. Outdoor Reactor Reaktor yang mampu bertahan dari cuaca luar 5. Three-phase Dry-type Air-core Reactor Sebuah reaktor yang terdiri dari peralatan fasa tunggal yang ditumpuk dan aan secara magnetis terhubung. Tergantung dari aplikasi, nilai impedansinya dapat dimodifikasi untuk mengimbangi efek hubungan coupling. 2.3.3 Aplikasi dari Reaktor Seri 1. Bus Tie Reactor Sebuah reaktor pembatas arus untuk koneksi diantara dua bus berbeda atau dua bagian dari bus yang sama untuk membatasi dan melokasikan gangguan karena kegagalan dari bus lainnya 2. Current Limiting Reactor Sebuah reaktor yang dikoneksikan seri dengan fasa konduktor untuk membatasi arus yang dapat mengalir pada sirkuit saat kondisi hubung singkat atau saat kondisi operasi, seperti switching capasitor, starting motor, sinkronisasi, penyetabilan bunga api, dan lain-lain. 3. Duplex Current Limiting Reactor
  • 60. Sebuah reaktor center-tapped yang digunakan pada dua cabang sirkuit yang disuplai dari sirkuit utama dan dimanfaatkan sedemikian rupa untuk menjalankan kopling negatif di bawah kondisi normal guna mengurangi impedansi sirkuit dan kopling positif pada kondisi gangguan untuk meningkatkan impedansi sirkuit. 60 LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION PT BADAK NGL BONTANG MAULANI CANDRA (0910630076) JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK UNIVERSITAS BRAWIJAYA 4. Feeder Reactor Sebuah reaktor pembatas arus yang terkoneksi secara seri dengan sirkuit feeder untukmembatasi dan melokasikan gangguan. 5. High-voltage Power Flow Sebuah reaktor transmisi yang terkoneksi secara seri dengan jaringan transmisi yang bertujuan untuk mengoptimalisasi aliran daya dengan merubah reaktansi kabel. 6. Insertion Reactor Sebuah reaktor yang terkoneksi sesaat ditengah hubungan terbuka dari sirkuit yang terganggu untuk kebutuhan sinkronisasi dan atau kebutuhan pengalihan tekanan transien. 7. Load Balancing Reactor Sebuah reaktor yang terhubung seri yang berguna untuk memperbaiki divisi arus diantara tranformer paralel atau sirkuit yang memiliki nilai impedansi tegangan yang tidak sama dibawah kondisi steady-state dan kondisi short-circuit. 8. Motor Starting reactor Sebuah reaktor pembatas arus yang berguna untuk membatasi arus starting motor. 2.3.4 Posisi Reaktor pada Bus Bar 2.3.4.1 Bus Coupling Saat terpasang pada coupling reactor akan mengurangi puncak dari hubungan pendek di saat pertama kali arus bangkit. Keuntungan:
  • 61. 61 LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION PT BADAK NGL BONTANG - Pembagian beban arus pada transformer lebih baik. - Mengurangi gangguan arus hubung singkat. - Mengurangi impedansi pada jaringan. - Arus short-circuit pada sumber (transformator atau generator) akan berkurang. MAULANI CANDRA (0910630076) JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK UNIVERSITAS BRAWIJAYA Kekurangan: - Setiap kontribusi arus dari satu incoming-feeder menjadi tidak terbatas Gambar 2.18: Bus Coupling 2.3.4.2 Terpasang seri dengan incoming feeder Meski dirancang pada sistem untuk mengatasi arus short-circuit total, sebuah CLR dapat diinstal pada incoming-feeder. Pada kasus ini pula, ketika ada arus gangguan maka CLR akan mereduksi puncak arus gangguan di awal pembangkitan arus. Keuntungan: - Disamping sama seperti keuntungan yang terpasang coupling, arus hubung singkat pada feeder sumber menjadi terbatas. Kerugian: - Tingginya rugi-rugi daya dan buruknya regulasi tegangan.
  • 62. 62 LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION PT BADAK NGL BONTANG Gambar 2.19: Terpasang seri dengan incoming feeder MAULANI CANDRA (0910630076) JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK UNIVERSITAS BRAWIJAYA 2.3.4.3 Terpasang seri dengan outgoing feeder Reaktor terpasang pada outgoing feeder yang akan mereduksi arus hubung singkat pada awal puncak pembangkitan arus. Keuntungan: - Reaktor yang terpasang seperti ini memiliki rugi-rugi daya yang lebih kecil dan regulasi tegangan yang lebih baik. Kerugian: - Biaya instalasi menjadi lebih besar karena banyak reaktor yang akan dipasang. Gambar 2.20: Terpasang seri dengan outgoing feeder 2.3.4.4 Current Limiting Reaktor (CLR) Dalam kondisi normal reaktor akan mengalirkan arus seperti penghantar biasa tanpa menekan besaran arus yang melewatinya. Dengan kata lain impedansi dari reaktor sangat kecil dan tidak mengurangi besar arus. Namun ketika ada arus gangguan yang nilainya relatif sangat besar maka CLR akan bekerja mereduksi arus gangguan tersebut
  • 63. dengan membangkitkan nilai impedansinya dan menjadi tahanan pada sistem yang menekan laju arus. CLR didesain berdasarkan dua parameter. Yang pertama adalah nilai induktansi aktual yang satuannya henri dan yang kedua adalah rating arus dari reaktor itu sendiri. Nilai impedansi reaktor dapat dinyatakan dengan fungsi: 63 LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION PT BADAK NGL BONTANG MAULANI CANDRA (0910630076) JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK UNIVERSITAS BRAWIJAYA 푍푡푟 =  퐿 푍푡푟 = (2 푓)퐿 푍푡푟 = (2 × 3.14 × 50)퐿 푍푡푟 = 314퐿 Dimana: Z = impedansi (ohm) L = induktansi (henri) f = frekuensi (hertz) Besarnya proteksi oleh CLR tergantung pada rasio T/R yang besarnya ditentukan dengan: 푍푡푟 = 푅푎푡푒푑 푃푟푖푚푎푟푦 푉표푙푡푎푔푒 푅푎푡푒푑 푃푟푖푚푎푟푦 퐶푢푟푟푒푛푡 Unit pengukuran dari reaktor adalah henri. Kemampuan dari reaktor untuk menghalangi aliran dari arus AC disebut dengan induktansi. Induktansi dari CLR pada umumnya dari 5 sampai 50 milihenri. Nilai dari CLR didasarkan pada total impedansi sistem yang diinginkan dari sumber daya. Impedansi sistem membatasi nilai maksimum dari arus yang dapat mengalir pada rangkaian primer dan pada umumnya dispesifikan sebagai persen impedansi. Nilainya dari 30% sampai 50% dari yang biasa digunakan. Impedansi dari reaktor dapat dihitung dengan: Presentasi impedansi yang dimiliki CLR dihitung dengan:
  • 64. 64 LAPORAN KULIAH KERJA NYATA-PRAKTIK (KKN-P) MAINTENANCE DEPARTEMENT – ELECTRICAL SECTION PT BADAK NGL BONTANG MAULANI CANDRA (0910630076) JURUSAN TEKNIK ELEKTRO FAKULTAS TEKNIK UNIVERSITAS BRAWIJAYA %푍 = 푍푐푙푟 푍푡푟 Atau %푍 = 퐿 × 314 × 퐴푚푝푠 푉표푙푡푠 × 100 Ketika terjadi gangguan nilai impedansi meningkat dan menekan arus yang melewatinya. Nilai arus gangguan besarnya didapatkan dengan: 퐹푎푢푙푡 퐶푢푟푟푒푛푡 = 푉표푙푡푠 푍푐푙푟 = 푅푎푡푒푑 퐶푢푟푟푒푛푡 %푍 × 100 CLR didesain dengan sebuah inti yang akan menangani arus beberapa waktu tanpa menyentuh titik jenuh. Drop tegangan yang melewati CLR akan berbanding lurus dengan arus yang lewat. Jika reaktor jenuh maka arus lebih akan lewat tanpa ada penurunan tegangan dan ini berbahaya bagi sistem disisi keluaran CLR. Pengujian 2.3.5 Pengujian Rutin, Desain, dan Pengujian lain untuk Reaktor Seri Pengujian untuk reaktor seri tipe kering diperlihatkan pada tabel 2.3. Tabel 2.6: PengujianRutin, Desain, dan Pengujian Pengujian Ketika Dilakukan Klasifikasi Pengujian Rutin Desain Lain Pengukuran Resistansi Pengukuran resistansi DC harus dilakukan pada semua unit X Pengukuran Impedansi Pengukuran impedansi harus dilakukan pada semua unit X Pengukuran Total Rugi-rugi Total rugi-rugi harus dilakukan pada setiap perhitungan X Pengujian Kenaikan Temperatur Pengujian ini dilakukan dari satu unit dari sejumlah unit pada desain yang sama X Pengujian tegangangan Pengujian tegangangan yang diterapkan harus dilakukan pada X