SlideShare a Scribd company logo
1 of 56
Download to read offline
1
AN-NAJAH NATIONAL UNIVERSITY
FACULTY OF ENGINEERING
CIVIL ENGINEERING DEPARTMENT
*Prepared By: *Submitted To:
-Basel Salameh -Dr. Monther Dwakit
-Loay Qabaha -Dr. Ibrahim Irman
-Mohamad Hindi -Eng. Hanan Jafar
-Tariq Thawabi
62116112
Design of concrete structure 2 project
2
3
*Introduction:
What is design ?
Selecting proper dimensions of reinforced concrete elements and material
used taking to account economic considerations .
The Design objectives is the designed structure should sustain all loads and
deform within limits for construction use, and should be durable. All the
above are design objectives that can be fulfilled by understanding the
strength and deformation characteristics of the materials used in the design
(concrete and steel).
Every structure has got its form, function and aesthetics. Normally, we
consider that the architects will take care of them and the structural
engineers will be solely responsible for the strength and safety of the
structure. However, the roles of architects and structural engineers are very
much interactive and a unified approach of both will only result in an
Integrated" structure.
In this project, we will design the project in two way systems, let’s to define
what the two way system?
Concrete is used mainly in slabs also in columns & beams. Slabs may be
designed with respect to loads applied over it as a solid slab either one way
or two way, ribbed slab also as one or two way, flat plate, flat slab & waffle
slab…, beams could be hidden or dropped. The main purpose is to distribute
loads and transport it to earth without causing the structure failure.
When the ratio (L/ S) is less than 2.0, it is called two-way slab, shown in.
Bending will take place in the two directions in a dish-like form. Accordingly,
main reinforcement is required in the two directions.
4
Two-way Edge-supported Solid Slabs :
In this system, shown in Figure , beams provide moment interaction
with the columns especially when moment resisting frames are used to
resist lateral loads.
The slab overall thickness is greater because beams project downward,
thus the system becomes inflexible in terms of mechanical layout. The
system can be used economically for spans up to 7.0 meters.
Two-way Edge-supported Ribbed Slabs :
This system, shown in Figure 2.e, can be economically used for spans up to
7.0 meters. It is similar to the waffle slab but the voids between ribs are filled
with hollow blocks. Hidden or drop beams can be used with this system
depending on their spans.
5
Waffle Slabs :
The waffle slab is capable of providing the largest spans of the conventional
concrete floor systems and can be economically used for spans up to 12.0
meters. This is attributed to the considerable reduction in dead load as
compared to other floor systems. Waffle slab construction consists of
orthogonal sets of ribs with solid parts at the columns, as shown in Figure.
The ribs are formed with fiberglass or metal dome forms. The ribs are usually
0..0to 0.90 meter on center. Shear is transferred to the columns by using
beams or shear heads.
*Problem Definition:
Given Data:
 Concrete for Beams , Columns & Slabs , 𝒇́ 𝒄 = 𝟐𝟖 𝑴𝑷𝒂 , &
 ˠ= 25 KN/m3
 Steel for Reinforcing Bars and Shear Reinforcement , Fy= 420MPa
 Floor Height = 4.7 m& number of Floors is 3.
 Superimposed dead load is the gravity load of non-structural parts of
the building .Superimposed dead load= 3.5KN/m2
6
 Live loads are those loads produced by the use and occupancy of
the building or other structure and do not include construction or
environmental load such as wind load, snow load, rain load,
earthquake load, flood load, or dead load. Live loads on a roof are
those produced (1) during maintenance by workers, equipment,
and materials; and (2) during the life of the structure by movable
objects such as planters and by people .Live load= 6 KN/m2.
Requirements:
Design the slab as: with full Design Detailing.
1. Two way solid slab
2. Two way ribbed slab
3. Two way voided slab
L2=frame width =10.5 m
Column strip =4 m
7
Direct Design Method
The direct design method consists of certain steps for distributing moments
to slab and beam sections to satisfy safety requirements and most
serviceability requirements simultaneously. Three basic steps are involved :
a. Determination of the total factored static moment.
b. Distribution of the total factored static moment to negative and positive
Sections.
c. Distribution of negative and positive factored moments to the column
and middle strips and to the beams if any.
Limitations
The direct design method was developed from theoretical procedures for
determination of moments in slabs, requirements for simple design ,
construction procedures, and performance of existing slabs. Therefore, the
slab system, to be designed using the direct design method, should conform
to the following limitations as given by ACI Code 13.6.1 :
1. There must be three or more spans in each direction .
2. Slab panels must be rectangular with a ratio of longer to shorter span ,
center-to-center of supports, not greater than 2.0 .
3. Successive span lengths, center-to-center of supports, in each
direction must not differ by more than one-third of the longer span .
4. Columns must not be offset more than 10 % of the span in the
direction of offset from either axis between centerlines of successive
columns .
5. Loads must be due to gravity only and uniformly distributed
Over the entire panel. The live load must not exceed 2 times the dead
load.
8
*Two Way Ribbed Slab System:
* Slab thickness and modification for the ribbed slab:
Assume αfm> 2:
H min. = (Ln*(0.8+fy/1400))/ (36+9β)
= (10*(0.8+420/1400))/ (36+9*1.33) = 0.23 m =230mm
Frame in south north direction (interior)
4mm8)/12=5.57*103(550*23012 =3bh=(solid)I
4mm813.5*10for the suggested cross section =(ribbed)I
(Calculated from sap frame section definition). I (ribbed) > I (solid) OK .
9
To find the equivalent slab section for the ribbed slab:
13.5*108= (550*h3)/12 ….. h=308.83 mm.
* Loads and shear check:
WD (O.W) = (0.55*0.55*0.4-0.32*0.2*0.4)*25+ (0.4*0.2*0.32)*12= 2.6922 KN
WD= 2.6922/ (0.55*0.55) =8.9 KN/m2
Wu = 1.2(3.5+8.9) +1.6*6= 24.5 KN/m2
Vu= 24.5*0.55*((10.5-0.7/0.5)-0.36) = 61.17 KN
∅VC = 0.75*
𝟏
𝟔
√𝟐𝟖*1.1*150*
𝟑𝟔𝟎
𝟏𝟎𝟎𝟎
= 39.29 KN
Vs= Vu - ∅VC = 21.89 KN
(Av/s) = (21.89*1000)/ (420*360) = 0.14 mm2/mm.
(Av/s) min = max. Of {0.35*(bw/fy), 0.062*(bw/fy)*√𝒇𝒄 } =0.125 mm2/mm
so, use (Av/s) = 0.14 mm2/mm.
S max.= d/2 = 360/2 = 180 mm use 1 Ø 8mm / 180 mm
Now we have to check the assumption that αfm> 2
The suggested beams dimensions are:
B1 (700 *500) for exterior beams I (B1) =7.3*10^9 mm4
B2 (700 *800) for interior beams. I (B2) = 3*10^10 mm4
Columns (700*700) mm
αf= (I beam / (I slab* number of ribs))
11
αf1=0.75 αf2 =1.44 αf3 = 0.7 αf4 = 1.2 αf5 = 1.17
All the values of αfm for all panels are less than 2.
So we have to go to 2< αfm > 0.2 case:-
the least value of αfm = 1.045
H min. = (Ln*(0.8+fy/1400))/ (36+5β*(αfm-0.2))
= ((10.5-0.7)*(0.8+420/1400))/ (36+5*1.33(1.045-0.2) = 0.26 < h=308.83 mm
…. OK
.
* Hand Calculations: analysis and design of frame 3.
A- Static moment (M0) ( for each span ) :-
M( exterior spans) = (24.5*10.5*7.3^2)/8+ (8.4*7.3^2)/8= 1770 KN. m.
M( interior span) = (24.5*10.5*8.3^2)/8+ (8.4*7.3^2)/8= 2288 KN .m
Where ,the factored own weight of beam= 8.4 KN/m .
11
B- Positive and negative moments of total frame:
Refer to (Table 13.6.3.3) to find the moments in frame in end spans.
- 0.7 M (for interior negative moments).
- 0.57M (for all positive moments).
- 0.16M (for exterior negative moments).
For the interior spans:-
0.35M for positive moments
0.65 for the negative moments
C- Moments in column strip including the beam :-
( Table 13.6.4.4 for the positive moments )
L2/L1= 10.5/8=1.31 L2/L1= 10.5/9 = 1.17
αf5*( L2/L1)= 1.53>1 αf5*( L2/L1)= 1.37>1
use interpolation use interpolation
1 ………75 1 ………75
1.31…… X X=66% 1.17…..X X=70%
2 ……… 45 2………45
12
(Table 13.6.4.1 for interior negative moments)
L2/L1= 10.5/8=1.31 L2/L1= 10.5/9 = 1.17
αf5*( L2/L1)= 1.53>1 αf5*( L2/L1)= 1.37>1
use interpolation use interpolation
1 ………75 1 ………75
1.31…… X X=66% 1.17…..X X=70%
2 ……… 45 2………45
(Table 13.6.4.2 for exterior negative moments)
C = (1- 0.63*(0.5/0.7))*((0.7*0.53)/3)= 0.016 m4
Bt = C/(2*Is) = 0.016/(2*(4/0.55)* 13.5*10-4) =0.815< 2.5
Use interpolation
0 ……. 100
0.815………..X
2.5 …………..75 X= 91.85 %
13
0 ……. 100
0.815………..X
2.5 …………..45
X= 82.07%
1 ……. 91.85
1.31………..X
2…………..82.07
X= 88.82%
D- Moments in beam :
αf5*( L2/L1)= 1.53>1 αf5*( L2/L1)= 1.37>1
M ( beam)= 0.85M ( C.S) M ( beam)= 0.85 M ( C.S)
E- Moments in the slab of C.S = 0.15 M ( C.s) .
********
14
* Model ON SAP:
A- Slab modification:
In two way slab system
f11=f22=f12=V13=V23 = (Actual area/ Sap section area)
= (0.55*0.08+0.32*0.15)/ (0.3088*0.55) =0.54
M11=M22=M33= 0.25
Mass modifier = weight modifier = (8.9/(0.3088*25))= 1.15
B- Model Checks:
* Compatibility and Period is ok.
15
* Equilibrium check.
Area of floor = 25* 38 = 950 m2
Live load = 950*6 = 5700 KN
Superimposed dead load = 950*3.5 = 3325 KN
16
* Stress/Strain relationships (Moment Check):
M0 (interior span) = 2288 KN .m
From SAP: (1372+1385)/2 + 954 = 2332.5 KN .m
% of error = (2332.5-2288)/2288 = 1.94 % < 5% …. OK
Now all of the values of the moments calculated by the direct design method and
by the software (SAP) will be attached by an Excel sheet
Note: we have just five different values in the frame due to symmetry.
Note: the average width of column strip= (8+9)/4 = 4.25 m on both sides.
The width of middle strip = 10.5-4.25 = 6.25 m
17
18
Notes:-
1- All the red cells represent that the area of steel is less than the minimum area of
steel in slab which is equal to bw*d*Ro min = 150*360*0.0033 = 180 mm2 , so this
values should be replaced by 180 mm2 .
2- The blue cells represent that the moment by draw section cut in SAP at the
exterior support in the column strip in more than the moment in the frame , so the
moment in the middle strip is negative and this region should be reinforced by the
minimum area of steel =180 mm2 .
3. The concrete zone (a) must be less than Hf= 80 mm, (As< 2493 mm2), to be able to
apply the steel percentage equation directly.
19
4- The shrinkage steel in the slab:
As = 0.0018*1000*80 = 144 mm2
S max. = 5*h = 5* 80 = 400 mm
S= 1000/ (144/50) = 349 mm
so, use 1 Ø 8mm/ 350 mm in both directions.
Design of beam in frame 3 for shear and torsion:
No torsion in this beam because there is no different in span lengths and moment
values.
Vu (from SAP) = 606 KN at the interior edge of the exterior span
By hand calculation:
Wu = (8.5/2) * 24.5 = 104 KN/m ( at the top of the triangle )
W ( o.w) = 1.2*25*0.7*0.7 = 14.7 KN/m
Vu = ( M1+M2)/2 + W( o.w)*(L/2)+ 0.5*Wu*0.5*L
= (213.8+695)/2 + (14.7*8*0.5)+ ( 0.5*0.5*8*104) = 721.2 KN
21
Design of beam for shear by SAP:
Av/s = 1.127 mm^2/mm
use Ø12 S = 226/1.127 = 200 mm use 1 Ø 12 / 200 mm
Design of columns: - we will use SAP to design the columns and then check one
column by hand calculation.
The framing type is sway ordinary.
A sample of steel percentage in the columns (frame 3).
21
We will check the column with 2.34% steel percentage
to check if the column is braced or not, we did a second order analysis by sap and was
not there a change in the moment values, so we can assume the column is braced
Assume K=1 to be conservative:
KLu/r = 1*4700/ (0.3*700) = 22.38 so the column is short also.
Pu = 8065 KN Mu = 44 KN.m
gama=( 700 – 2*60)/ 700 = 0.83
Mu/bh^2=( (44*10^6)/ (700)^3)/7 = 0.02 Ksi
Pu/bh =( (8065*10^3)/ (700)^2)/7 = 2.35 Ksi
at gama = 0.75 Ro = 2% at gama = 0.9 Ro = 1.9 %
by interpolation Ro = 1.95 % As = 0.0195*700*700 = 9555 mm^2
Ro ( SAP) = 2.34% As= 0.0234*700*700 = 11466 mm^2 ( 14@32
22
Note : there is a high difference between the hand and SAP calculations in column
steel , because the SAP designed for this moment and a minimum moment in the other
direction not only in one direction (Mu2=0 ,take Mu2 min. = 292.298 KN.m .
Ties spacing: S < 16*32 = 512 mm
S < 48*10 = 480 mm
S < 700 mm
So, use 1 Ø10 / 450 mm.
23
*Details for the two way ribbed system: -
1- Cross section in beam in the middle of interior span of frame 3.
2 - Cross section in the middle strip in the middle of interior span of frame 3.
3- Cross section in the column strip slab in the middle of interior span of frame 3.
4- Cross section in column that was checked above.
24
25
**********************************
26
*Two Way Voided Slab System:
* Slab thickness and modification for the ribbed slab:
Assume αfm> 2:
H min. = (Ln*(0.8+fy/1400))/ (36+9β)
= (9.7*(0.8+420/1400))/ (36+9*1.35) = 0.221 m =221mm
Frame in south north direction (interior) (Frame 3) .
4mm8)/12=6.02*10312 =(670*2213= bh(solid)I
4mm8for the suggested cross section = 40.15*10(voided)I
(Calculated from sap frame section definition). I (voided) > I (solid) OK .
27
To find the equivalent slab section for the ribbed slab:
40.15*108= (670*h3)/12 ….. h=415 mm.
* Loads and shear check:
Wd (O.W) = (0.67^2*0.46- 0.52^2*0.32)*25= 3 KN
Wd= 3/(0.67*0.67)=6.7 KN/m2
Wu = 1.2(3.5+6.7)+1.6*6= 21.84 KN/m2
Vu= 21.84*0.67*((10.5-0.8/0.5)-0.4) = 78 KN
∅VC = 0.75*
𝟏
𝟔
√𝟐𝟖*1.1*150*
𝟒𝟎𝟎
𝟏𝟎𝟎𝟎
= 45.6 KN
Vs= Vu - ∅VC = 32.4 KN
(Av/s) = (32.4*1000)/ (420*400) = 0.19 mm2/mm.
(Av/s) min = max. Of {0.35*(bw/fy), 0.062*(bw/fy)*√𝒇𝒄 } =0.125 mm2/mm
so, use (Av/s) = 0.19 mm2/mm.
S max.= d/2 = 400/2 = 200 mm use 1 Ø 8mm / 200 mm
Now we have to check the assumption that αfm> 2
The suggested beams dimensions are:
B1 (400 *800) for exterior and interior beams I (B) =1.7*10^10 mm4
Columns (800*800) mm
αf= (I beam / (I slab* number of ribs))
28
αf1=0.71 αf2 =0.335 αf3 = 0.672 αf4 = 0.237 αf5 = 0.272
All the values of αfm for all panels are less than 2.
So we have to go to αfm< 0.2 case:-
the least value of αfm = 0.294
h min. = Ln/30 = 9.7/30 = 0.32 m < h=415 mm …. OK
* Hand Calculations: analysis and design of frame 3.
A- Static moment (M0) ( for each span ) :-
M( exterior spans) = (21.84*10.5*7.2^2)/8+ (8.4*7.3^2)/8= 1834.5 KN. m.
M( interior span) = (21.84*10.5*8.2^2)/8+ (8.4*7.3^2)/8= 2322 KN .m
Where :- the factored own weight of beam= 8.4 KN/m .
B- Positive and negative moments of total frame:
Refer to (Table 13.6.3.3) to find the moments in frame in end spans.
- 0.7 M (for interior negative moments).
- 0.57M (for all positive moments).
- 0.16M (for exterior negative moments).
29
For the interior spans:-
0.35M for positive moments
0.65 for the negative moments
C- Moments in column strip including the beam :-
( Table 13.6..4.4 for the positive moments )
L2/L1= 10.5/8=1.31 L2/L1= 10.5/9 = 1.17
αf5*( L2/L1< 1 αf5*( L2/L1)< 1
use interpolation use interpolation
X=0.6 X=0.66
(Table 13.6.4.1 for interior negative moments)
L2/L1= 10.5/8=1.31 L2/L1= 10.5/9 = 1.17
αf5*( L2/L1) < 1 αf5*( L2/L1) < 1
use interpolation ( X= 0.66) use interpolation (X=0.75)
( Table 13.6.4.2 for exterior negative moments )
C = (1- 0.63*(0.4/0.8))*((0.8*0.43)/3)= 0.01169 m4
Bt = C/(2*Is) = 0.01169/(2*((1/12)*4*0.415) =0.245< 2.5
Use interpolation
X= 0.972
D- Moments in beam :
αf5*( L2/L1) < 1 αf5*( L2/L1) <1
M ( beam)= 0.285M ( C.S) M ( beam)= 0.285 M ( C.S)
E- Moments in the slab of C.S = 0.15 M ( C.s) .
********
31
* Model ON SAP:
A- Slab modification:
In two way slab system
f11=f22=f12=V13=V23 = (Actual area/ Sap section area)
= (2*0.67*0.07+0.32*0.15)/ (0.415*0.67) =0.51
M11=M22=M33= 0.25
Mass modifier = weight modifier = (6.7/(0.415*25))= 0.645
31
B- Model Checks:
* Compatibility and Period is ok.
32
* Equilibrium check.
Area of floor = 25* 38 = 950 m2
Live load = 950*6 = 5700 KN
Superimposed dead load = 950*3.5 = 3325 KN
* Stress/Strain relationships (Moment Check):
M0 (interior span) = 2322 KN .m
From SAP: (8931+8011)/2 + 793= 2192 KN .m
% of error = (2322-2192)/2322 = 5.5 % < 10% …. OK
33
Now all of the values of the moments calculated by the direct design method and
by the software (SAP) will be attached by an Excel sheet
Note: we have just five different values in the frame due to symmetry.
Note: the average width of column strip= (8+9)/4 = 4.25 m on both sides.
The width of middle strip = 10.5-4.25 = 6.25 m
34
Notes:-
1- All the red cells represent that the area of steel is less than the minimum area of
steel in slab which is equal to bw*d*Ro min = 150*400*0.0033 = 198 mm2 , so this
values should be replaced by 198 mm2 .
2- The blue cells represent that the moment by draw section cut in SAP at the exterior
support in the column strip in more than the moment in the frame , so the moment in
the middle strip is negative and this region should be reinforced by the minimum area
of steel =198 mm2 .
3. The concrete zone (a) must be less than Hf= 70 mm, (As< 2657 mm2), to be able to
apply the steel percentage equation directly.
4- The shrinkage steel in the slab:
As = 0.0018*1000*70 = 126 mm2
S max. = 5*h = 5* 70 = 350 mm
S= 1000/ (144/50) = 349 mm
so, use 1 Ø 8mm/ 350 mm in both directions.
35
Design of beam in frame 3 for shear and torsion:
No torsion in this beam because there is no different in span lengths and moment
values.
Vu (from SAP) = 411 KN at the interior edge of the exterior span
By hand calculation:
Wu = (8.5/2) * 21.84 = 92.82 KN/m ( at the top of the triangle )
W ( o.w) = 1.2*25*0.8*0.4 = 9.6 KN/m
Vu = ( M1+M2)/2 + W( o.w)*(L/2)+ 0.5*Wu*0.5*L
= (106.5+365.2)/2 + (9.6*8*0.5)+ ( 0.5*0.5*8*92.82) = 459 KN ( OK )
Design of beam for shear by SAP:
36
Av/s = 0.965 mm^2/mm
use Ø12 S = 226/0.965 = 234 mm use 1 Ø 12 / 200 mm
Design of columns: - we will use SAP to design the columns and then check one
column by hand calculation.
The framing type is sway ordinary.
A sample of steel percentage in the columns (frame 3).
We will check the column with 1% steel percentage
to check if the column is braced or not, we did a second order analysis by sap and was
not there a change in the moment values, so we can assume the column is braced
Assume K=1 to be conservative:
KLu/r = 1*4700/ (0.3*800) = 19.5 so the column is short also.
Pu = 2608 KN Mu = 24 KN.m
gama=( 800 – 2*60)/ 800 = 0.85
Mu/bh^2=( (24*10^6)/ (800)^3)/7 = 0.0.006 Ksi
Pu/bh =( (2608*10^3)/ (800)^2)/7 = 0.6 Ksi
at gama = 0.75 Ro = 1% at gama = 0.9 Ro = 1 %
by interpolation Ro = 1% As = 0.01*800*800 = 6400 mm^2 ( 8@32)
37
Ties spacing: S < 16*32 = 512 mm
S < 48*10 = 480 mm
S < 800 mm
So, use 1 Ø10 / 450 mm.
*Details for the two way ribbed system: -
38
39
41
41
*Two Way Solid Slab System:
*. Slab thickness and modification for the ribbed slab:
Assume αfm> 2:
H min. = (Ln*(0.8+fy/1400))/ (36+9β)
Ln=max clear span =10.5-0.8=9.7 m Β=9.77.2
= (9.7*(0.8+420/1400))/ (36+9*1.34) = 0.222 m =222 mm
Try h=250 mm
To compute αf we need to compute αfm for every beam
Iedge beam =9.86*10-3 m4, L-section 800*600*400
Iinterior beam= 11.5*10-3 m4, T-section 600*400
Column 800*800
42
Frame in east west direction:
I exterior = bh312 = (4*0.253)/12=5.27*10-3 m4
I interior = for the suggested cross section = 0.011m4
Frame in north south direction:
I exterior=0.0136 m4
I interior 1=0.012 m4
I interior 2=5.2*10-3
αf= (I beam / (I slab* number of ribs))
αf1=1.89 αf2 =1.05 αf3 = 1.89 αf4 = .96 αf5 = 0.85
Average for panels smallest =0.97<2
All the values of αfm for all panels are less than 2.
So we have to go to 2< αfm > 0.2 case:-
the least value of αfm = 0.97
43
H min. = (Ln*(0.8+fy/1400))/ (36+5β*(αfm-0.2))
= 0.263 try h=300mm …. OK
* Loads and shear check:
Wd= 0.3(25)/(3.5)=11 KN/m2
Wu = 1.2(11)+1.6*6= 22.8 KN/m2
Vu= 22.5* ((10.5-0.8/0.5)-0.26) = 104.6 KN
∅VC = 0.75*
𝟏
𝟔
√𝟐𝟖**1000*
𝟐𝟔𝟎
𝟏𝟎𝟎𝟎
= 172 KN
∅VC> Vu ok
Now we have to check the assumption that αfm> 2
* Hand Calculations: analysis and design of frame 3.
A- Static moment (M0) ( for each span ) :-
M( exterior spans) = (22.8*10.5*8.6^2)/8= 2757.6 KN. m.
M( interior spans) = (22.8*10.5*7.6^2)/8= 1728.4 KN .m
Where :- the factored own weight of beam= 8.4 KN/m .
B- Positive and negative moments of total frame:
Refer to (Table 13.6.3.3) to find the moments in frame in end spans.
- 0.7 M (for interior negative moments).
- 0.57M (for all positive moments).
- 0.16M (for exterior negative moments).
For the interior spans:-
44
0.35M for positive moments
0.65 for the negative moments
Repeat αf for frame interior
I = 11.573*10-3 m
Is =0.023 m4
αf =0.5
C- Moments in column strip including the beam :-
( Table 13.6.4.4 for the positive moments )
L2/L1= 10.5/8=1.31 @L2/L1= 2
αf5*( L2/L1)= 0.85<1 αf5*( L2/L1)
use interpolation @ L2/L1=1 use interpolation
0 ………60 0 ………60
0.85…… X X=72.7% 0.85…..X X=47.2%
1 ……… 75 1………45
@ ( L2/L1)
Goal
Use interpolation
1 ………72.7
1.31…… X X=64.7%
2 ……… 47.2
45
(Table 13.6.4.1 for interior negative moments)
L2/L1= 10.5/8=1.31 L2/L1= 10.5/9 = 1.17
αf5*( L2/L1)= 0.85 αf5*( L2/L1)= 1.37>1
use interpolation use interpolation
0 ………75 0 ………75
0.85…… X X=75% 0.85…..X X=49.5%
1 ……… 75 1………45
@( L2/L1)
Goal
Use interpolation
1 ………75
1.31…… X X=67%
2 ……… 49.2
(Table 13.6.4.2 for exterior negative moments)
C = (1- 0.63*(0.4/0.6))*((0.6*0.43)/3) + (1- 0.63*(0.3/0.4))*((0.4*0.333) = 8.44*10-3
m4
Bt = C/(2*Is) = 8.44*10-3 /(2*0.023) =0.183< 2.5
Use interpolation
X=100%
46
D- Moments in beam:
αf5*(L2/L1) = 0.85<1
M (beam) = 0.85 *0.85 =0.72 M ( C.S)
* Model ON SAP:
A- Slab modification:
In two way slab system
f11=f22=f12=V13=V23 =1
M11=M22=M33= 0.25
Mass modifier = weight modifier = 1
47
B- Model Checks:
* Compatibility and Period is ok.
* Equilibrium check.
Area of floor = 25* 38 = 950 m2
Live load = 950*6 = 5700 KN
Superimposed dead load = 950*3.5 = 3325 KN
48
* Stress/Strain relationships (Moment Check):
M0 (interior span) = 1728.4 KN .m
From SAP: (1132+1132)/2 + 814 = 1946 KN .m
% of error = (1946.5-1728.4)/ 1728.4 = 9 % < 10% …. OK
Now all of the values of the moments calculated by the direct design method
and by the software (SAP) will be attached by an Excel sheet
Note: we have just five different values in the frame due to symmetry.
Note: the average width of column strip= (8+9)/4 = 4.25 m on both sides.
The width of middle strip = 10.5-4.25 = 6.25 m
49
51
51
.Design of beam in frame 3 for shear and torsion:
No torsion in this beam because there is no different in span lengths and
moment values.
Vu (from SAP) = 733 KN at the interior edge of the exterior span
By hand calculation:
Wu = (8.5/2) * 22.8 = 96.9 KN/m ( at the top of the triangle )
W ( o.w) = 1.2*25*0.4*0.6 = 7.2 KN/m
Vu = ( M1+M2)/2 + W( o.w)*(L/2)+ 0.5*Wu*0.5*L
= (293+457)/2 + (7.2*8*0.5)+ ( 0.5*0.5*8*96.9) = 601 KN (OK) .
Design of beam for shear by SAP:
Av/s = 2.242 mm^2/mm
use Ø12 S = 226/2.242 = 101 mm use 1 Ø 12 / 100 mm
52
Design of columns: - we will use SAP to design the columns and then check
one column by hand calculation.
The framing type is sway ordinary.
A sample of steel percentage in the columns (frame 3).
We will check the column with 1% steel percentage
to check if the column is braced or not, we did a second order analysis by
sap and was not there a change in the moment values, so we can assume the
column is braced
Assume K=1 to be conservative:
KLu/r = 1*4700/ (0.3*800) = 19.5 so the column is short also.
Pu = 2224 KN Mu = 50 KN.m
gama=( 800 – 2*60)/ 800 = 0.85
Mu/bh^2=( (50*10^6)/ (800)^3)/7 =0 Ksi
Pu/bh =( (2224*10^3)/ (800)^2)/7 = 0.49 Ksi
by interpolation Ro < 1% As = 0.01*800*800 = 6480 mm^2
( 8@32 ) .
Ties spacing: S < 16*32 = 512 mm
S < 48*10 = 480 mm
S < 800 mm
so, use 1 Ø10 / 450 mm.
53
*Details for the two way solid system: -
1- Cross section in beam in the middle of interior span of frame 3.
2 - Cross section in the middle strip in the middle of interior span of frame 3.
3- Cross section in the column strip slab in the middle of interior span of
frame 3.
4- Cross section in column that was checked above.
54
55
*Conclusion, Recommendation:
There are differences between the hand calculation and SAP program result
but it’s Acceptable which not exceed 10%.
After analyzing each of the previous systems we have concluded that we
would use Low-rise concrete frame as our primary system. Using this we
would have a system of columns, girders, and voided box beams. This would
frame our first floor and second floor deck from there we would probably use
a steel structure to frame the second story and roof. After constructing and
executing our decision matrix we concluded that The Low-Rise Concrete
frame has the most to offer for our particular building. We used a weighted
scale to come to our conclusion. I’m sure that whether it be the owner or the
Architect they will have criteria that will have greater importance over
others. Our Group also has a good deal of previous system and we made
three floor systems to it.
The direct design method do not given accurate value so, We recommend to
use one way solid slab with girder system in order to decrease slab thickness
and to distribute the loads over coloumns and girders and increace beam
section .We recommend to use two way slab ribbed, but we offer ribbed slab
with hollow blocks to give lighter weight and good insulation too finally, We
recommend to use the most effective floor system , and the most
conservative system and low cost .
The end
56

More Related Content

What's hot (19)

Onewayslab
OnewayslabOnewayslab
Onewayslab
 
User guide slab
User guide slabUser guide slab
User guide slab
 
Two way slab
Two way slabTwo way slab
Two way slab
 
Flat slab
Flat slabFlat slab
Flat slab
 
Analysis and design of flat slabs using various codes
Analysis and design of flat slabs using various codesAnalysis and design of flat slabs using various codes
Analysis and design of flat slabs using various codes
 
Design and analysis of RC structures with flat slab
Design and analysis of RC structures with flat slabDesign and analysis of RC structures with flat slab
Design and analysis of RC structures with flat slab
 
Slabs Beam Reinforcement Detailing
Slabs Beam Reinforcement DetailingSlabs Beam Reinforcement Detailing
Slabs Beam Reinforcement Detailing
 
Worked example extract_flat_slabs
Worked example extract_flat_slabsWorked example extract_flat_slabs
Worked example extract_flat_slabs
 
Two-Way Floor Slab
Two-Way Floor SlabTwo-Way Floor Slab
Two-Way Floor Slab
 
Lec 3 design problem of flat plate slab
Lec 3 design problem of flat plate slabLec 3 design problem of flat plate slab
Lec 3 design problem of flat plate slab
 
DESIGN OF FLAT SLABS
DESIGN OF FLAT SLABSDESIGN OF FLAT SLABS
DESIGN OF FLAT SLABS
 
Slab Design-(BNBC & ACI)
Slab Design-(BNBC & ACI)Slab Design-(BNBC & ACI)
Slab Design-(BNBC & ACI)
 
Mathcad 17-slab design
Mathcad   17-slab designMathcad   17-slab design
Mathcad 17-slab design
 
Rc design ii
Rc design iiRc design ii
Rc design ii
 
Reinforcement detailing
Reinforcement  detailingReinforcement  detailing
Reinforcement detailing
 
Concrete beam design
Concrete beam designConcrete beam design
Concrete beam design
 
Isolated footing design
Isolated footing designIsolated footing design
Isolated footing design
 
Flat slabs 1
Flat slabs 1Flat slabs 1
Flat slabs 1
 
Guide to the design and construction of reinforced concrete flat slabs (1)
Guide to the design and construction of reinforced concrete flat slabs (1)Guide to the design and construction of reinforced concrete flat slabs (1)
Guide to the design and construction of reinforced concrete flat slabs (1)
 

Viewers also liked

Environmental impact assessment of charcoal in yabad area -palestine
Environmental impact assessment of charcoal in yabad area -palestine Environmental impact assessment of charcoal in yabad area -palestine
Environmental impact assessment of charcoal in yabad area -palestine Loay Qabaha
 
Project management ,By :Loay Qabaha -An-Najah National University -Nublus_pal...
Project management ,By :Loay Qabaha -An-Najah National University -Nublus_pal...Project management ,By :Loay Qabaha -An-Najah National University -Nublus_pal...
Project management ,By :Loay Qabaha -An-Najah National University -Nublus_pal...Loay Qabaha
 
Spatial_data_Doc7_150913
Spatial_data_Doc7_150913Spatial_data_Doc7_150913
Spatial_data_Doc7_150913Jessica Kauzer
 
LinkMe Brochure late2016
LinkMe Brochure late2016LinkMe Brochure late2016
LinkMe Brochure late2016Juri Di Natale
 
1304 Inbound Marketing Forum - Доклад Марины Тропак
1304 Inbound Marketing Forum - Доклад Марины Тропак 1304 Inbound Marketing Forum - Доклад Марины Тропак
1304 Inbound Marketing Forum - Доклад Марины Тропак Olga Zaimenko
 
Tieg0877sort abc copy
Tieg0877sort abc   copyTieg0877sort abc   copy
Tieg0877sort abc copyGWROY
 
Public Relations Presentation
Public Relations PresentationPublic Relations Presentation
Public Relations PresentationRachel Hill
 
JECRC Syllabus for B.Tech Civil Engineering Branch
JECRC Syllabus for B.Tech Civil Engineering Branch JECRC Syllabus for B.Tech Civil Engineering Branch
JECRC Syllabus for B.Tech Civil Engineering Branch Amit Kumar
 
Ies 2013 general ability solved question paper
Ies 2013 general ability solved question paperIes 2013 general ability solved question paper
Ies 2013 general ability solved question paperThomas Britto
 
Cloud computing - A Cloud Career Path
Cloud computing - A Cloud Career PathCloud computing - A Cloud Career Path
Cloud computing - A Cloud Career PathCognixia
 
Cultural conflicts in organisations
Cultural conflicts in organisationsCultural conflicts in organisations
Cultural conflicts in organisationsGurpreet Kaur
 
Network analysis in basketball
Network analysis in basketballNetwork analysis in basketball
Network analysis in basketballSwaagie
 
Bachelor of civil engineering
Bachelor of civil engineeringBachelor of civil engineering
Bachelor of civil engineeringThomas Britto
 
Civil 3.ce rcc & prestressed_concrete
Civil 3.ce rcc & prestressed_concreteCivil 3.ce rcc & prestressed_concrete
Civil 3.ce rcc & prestressed_concreteThomas Britto
 
LIMIT STATE DESIGN OF RCC
LIMIT STATE DESIGN OF RCCLIMIT STATE DESIGN OF RCC
LIMIT STATE DESIGN OF RCCPavan Kumar
 
Portfolio Civil / Structural Engineer | Designer | Manager
Portfolio Civil / Structural Engineer | Designer | ManagerPortfolio Civil / Structural Engineer | Designer | Manager
Portfolio Civil / Structural Engineer | Designer | ManagerOleg Kilchevskiy
 
Media evaluation analysis part 4
Media evaluation analysis part 4Media evaluation analysis part 4
Media evaluation analysis part 4Alex Dalton
 

Viewers also liked (20)

Environmental impact assessment of charcoal in yabad area -palestine
Environmental impact assessment of charcoal in yabad area -palestine Environmental impact assessment of charcoal in yabad area -palestine
Environmental impact assessment of charcoal in yabad area -palestine
 
Project management ,By :Loay Qabaha -An-Najah National University -Nublus_pal...
Project management ,By :Loay Qabaha -An-Najah National University -Nublus_pal...Project management ,By :Loay Qabaha -An-Najah National University -Nublus_pal...
Project management ,By :Loay Qabaha -An-Najah National University -Nublus_pal...
 
SaintNicholas
SaintNicholasSaintNicholas
SaintNicholas
 
Workshop Funceme 2013
Workshop Funceme 2013Workshop Funceme 2013
Workshop Funceme 2013
 
Spatial_data_Doc7_150913
Spatial_data_Doc7_150913Spatial_data_Doc7_150913
Spatial_data_Doc7_150913
 
LinkMe Brochure late2016
LinkMe Brochure late2016LinkMe Brochure late2016
LinkMe Brochure late2016
 
1304 Inbound Marketing Forum - Доклад Марины Тропак
1304 Inbound Marketing Forum - Доклад Марины Тропак 1304 Inbound Marketing Forum - Доклад Марины Тропак
1304 Inbound Marketing Forum - Доклад Марины Тропак
 
Tieg0877sort abc copy
Tieg0877sort abc   copyTieg0877sort abc   copy
Tieg0877sort abc copy
 
Presentation1
Presentation1Presentation1
Presentation1
 
Public Relations Presentation
Public Relations PresentationPublic Relations Presentation
Public Relations Presentation
 
JECRC Syllabus for B.Tech Civil Engineering Branch
JECRC Syllabus for B.Tech Civil Engineering Branch JECRC Syllabus for B.Tech Civil Engineering Branch
JECRC Syllabus for B.Tech Civil Engineering Branch
 
Ies 2013 general ability solved question paper
Ies 2013 general ability solved question paperIes 2013 general ability solved question paper
Ies 2013 general ability solved question paper
 
Cloud computing - A Cloud Career Path
Cloud computing - A Cloud Career PathCloud computing - A Cloud Career Path
Cloud computing - A Cloud Career Path
 
Cultural conflicts in organisations
Cultural conflicts in organisationsCultural conflicts in organisations
Cultural conflicts in organisations
 
Network analysis in basketball
Network analysis in basketballNetwork analysis in basketball
Network analysis in basketball
 
Bachelor of civil engineering
Bachelor of civil engineeringBachelor of civil engineering
Bachelor of civil engineering
 
Civil 3.ce rcc & prestressed_concrete
Civil 3.ce rcc & prestressed_concreteCivil 3.ce rcc & prestressed_concrete
Civil 3.ce rcc & prestressed_concrete
 
LIMIT STATE DESIGN OF RCC
LIMIT STATE DESIGN OF RCCLIMIT STATE DESIGN OF RCC
LIMIT STATE DESIGN OF RCC
 
Portfolio Civil / Structural Engineer | Designer | Manager
Portfolio Civil / Structural Engineer | Designer | ManagerPortfolio Civil / Structural Engineer | Designer | Manager
Portfolio Civil / Structural Engineer | Designer | Manager
 
Media evaluation analysis part 4
Media evaluation analysis part 4Media evaluation analysis part 4
Media evaluation analysis part 4
 

Similar to Design of concrete structure 2 project-Loay Qabaha &Basel Salame

Reinforced concrete Course assignments, 2019
Reinforced concrete Course assignments, 2019Reinforced concrete Course assignments, 2019
Reinforced concrete Course assignments, 2019JanneHanka
 
IRJET- Comparative Study of Super-Structure Stability Systems for Economic Co...
IRJET- Comparative Study of Super-Structure Stability Systems for Economic Co...IRJET- Comparative Study of Super-Structure Stability Systems for Economic Co...
IRJET- Comparative Study of Super-Structure Stability Systems for Economic Co...IRJET Journal
 
140204-5-PTI EDC-130-Continuous Members-41.pdf
140204-5-PTI EDC-130-Continuous Members-41.pdf140204-5-PTI EDC-130-Continuous Members-41.pdf
140204-5-PTI EDC-130-Continuous Members-41.pdfephrem53
 
Design of Structures Chapter2.pdf
Design of Structures Chapter2.pdfDesign of Structures Chapter2.pdf
Design of Structures Chapter2.pdfUmarSaba1
 
Design of Steel Grillage Foundation for an Auditorium
Design of Steel Grillage Foundation for an AuditoriumDesign of Steel Grillage Foundation for an Auditorium
Design of Steel Grillage Foundation for an AuditoriumIRJET Journal
 
IRJET- Analysis of Four Legged Steel Telecommunication Tower-Equivalent Stati...
IRJET- Analysis of Four Legged Steel Telecommunication Tower-Equivalent Stati...IRJET- Analysis of Four Legged Steel Telecommunication Tower-Equivalent Stati...
IRJET- Analysis of Four Legged Steel Telecommunication Tower-Equivalent Stati...IRJET Journal
 
IRJET - Design and Analysis of Residential Institute Building
IRJET - Design and Analysis of Residential Institute BuildingIRJET - Design and Analysis of Residential Institute Building
IRJET - Design and Analysis of Residential Institute BuildingIRJET Journal
 
Reinforced concrete Course Assignments, 2023
Reinforced concrete Course Assignments, 2023Reinforced concrete Course Assignments, 2023
Reinforced concrete Course Assignments, 2023JanneHanka
 
Design of Structures Chapter2.pptx
Design of Structures Chapter2.pptxDesign of Structures Chapter2.pptx
Design of Structures Chapter2.pptxUmarSaba1
 
Integrated presentation pdf
Integrated presentation pdfIntegrated presentation pdf
Integrated presentation pdfNahom Balcha
 
Fire Resistance of Materials & Structures - Analysing the Steel Structure
Fire Resistance of Materials & Structures - Analysing the Steel StructureFire Resistance of Materials & Structures - Analysing the Steel Structure
Fire Resistance of Materials & Structures - Analysing the Steel StructureArshia Mousavi
 
lacing and battening .pptx
lacing and battening .pptxlacing and battening .pptx
lacing and battening .pptxmayur280524
 
Design of Flat Slab and Bridges
Design of Flat Slab and BridgesDesign of Flat Slab and Bridges
Design of Flat Slab and BridgesAnanthakumar75
 
Cost Optimization of a Tubular Steel Truss Using Limit State Method of Design
Cost Optimization of a Tubular Steel Truss Using Limit State Method of DesignCost Optimization of a Tubular Steel Truss Using Limit State Method of Design
Cost Optimization of a Tubular Steel Truss Using Limit State Method of DesignIJERA Editor
 

Similar to Design of concrete structure 2 project-Loay Qabaha &Basel Salame (20)

Presentation
PresentationPresentation
Presentation
 
Rectangular tank
Rectangular tankRectangular tank
Rectangular tank
 
Reinforced concrete Course assignments, 2019
Reinforced concrete Course assignments, 2019Reinforced concrete Course assignments, 2019
Reinforced concrete Course assignments, 2019
 
IRJET- Comparative Study of Super-Structure Stability Systems for Economic Co...
IRJET- Comparative Study of Super-Structure Stability Systems for Economic Co...IRJET- Comparative Study of Super-Structure Stability Systems for Economic Co...
IRJET- Comparative Study of Super-Structure Stability Systems for Economic Co...
 
140204-5-PTI EDC-130-Continuous Members-41.pdf
140204-5-PTI EDC-130-Continuous Members-41.pdf140204-5-PTI EDC-130-Continuous Members-41.pdf
140204-5-PTI EDC-130-Continuous Members-41.pdf
 
Design of Structures Chapter2.pdf
Design of Structures Chapter2.pdfDesign of Structures Chapter2.pdf
Design of Structures Chapter2.pdf
 
Design of Steel Grillage Foundation for an Auditorium
Design of Steel Grillage Foundation for an AuditoriumDesign of Steel Grillage Foundation for an Auditorium
Design of Steel Grillage Foundation for an Auditorium
 
IRJET- Analysis of Four Legged Steel Telecommunication Tower-Equivalent Stati...
IRJET- Analysis of Four Legged Steel Telecommunication Tower-Equivalent Stati...IRJET- Analysis of Four Legged Steel Telecommunication Tower-Equivalent Stati...
IRJET- Analysis of Four Legged Steel Telecommunication Tower-Equivalent Stati...
 
IRJET - Design and Analysis of Residential Institute Building
IRJET - Design and Analysis of Residential Institute BuildingIRJET - Design and Analysis of Residential Institute Building
IRJET - Design and Analysis of Residential Institute Building
 
Reinforced concrete Course Assignments, 2023
Reinforced concrete Course Assignments, 2023Reinforced concrete Course Assignments, 2023
Reinforced concrete Course Assignments, 2023
 
Design of Structures Chapter2.pptx
Design of Structures Chapter2.pptxDesign of Structures Chapter2.pptx
Design of Structures Chapter2.pptx
 
Integrated presentation pdf
Integrated presentation pdfIntegrated presentation pdf
Integrated presentation pdf
 
Project 2b (1) (2)
Project 2b  (1) (2)Project 2b  (1) (2)
Project 2b (1) (2)
 
Fire Resistance of Materials & Structures - Analysing the Steel Structure
Fire Resistance of Materials & Structures - Analysing the Steel StructureFire Resistance of Materials & Structures - Analysing the Steel Structure
Fire Resistance of Materials & Structures - Analysing the Steel Structure
 
lacing and battening .pptx
lacing and battening .pptxlacing and battening .pptx
lacing and battening .pptx
 
Design of Flat Slab and Bridges
Design of Flat Slab and BridgesDesign of Flat Slab and Bridges
Design of Flat Slab and Bridges
 
Qp
QpQp
Qp
 
MEMS CAPACITIVE ACCELEROMETER
MEMS CAPACITIVE ACCELEROMETERMEMS CAPACITIVE ACCELEROMETER
MEMS CAPACITIVE ACCELEROMETER
 
Design of manual solar tracking system wps
Design of manual solar tracking system wpsDesign of manual solar tracking system wps
Design of manual solar tracking system wps
 
Cost Optimization of a Tubular Steel Truss Using Limit State Method of Design
Cost Optimization of a Tubular Steel Truss Using Limit State Method of DesignCost Optimization of a Tubular Steel Truss Using Limit State Method of Design
Cost Optimization of a Tubular Steel Truss Using Limit State Method of Design
 

Recently uploaded

Biology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptxBiology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptxDeepakSakkari2
 
What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxWhat are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxwendy cai
 
SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )Tsuyoshi Horigome
 
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130Suhani Kapoor
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingrakeshbaidya232001
 
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVRajaP95
 
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Serviceranjana rawat
 
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSHARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSRajkumarAkumalla
 
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)Suman Mia
 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Dr.Costas Sachpazis
 
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSMANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSSIVASHANKAR N
 
Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024hassan khalil
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
Internship report on mechanical engineering
Internship report on mechanical engineeringInternship report on mechanical engineering
Internship report on mechanical engineeringmalavadedarshan25
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130Suhani Kapoor
 
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...ZTE
 
Call Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile serviceCall Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile servicerehmti665
 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxpranjaldaimarysona
 
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxJoão Esperancinha
 

Recently uploaded (20)

Biology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptxBiology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptx
 
What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxWhat are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptx
 
SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )
 
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writing
 
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
 
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
 
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSHARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
 
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
 
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSMANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
 
Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
Internship report on mechanical engineering
Internship report on mechanical engineeringInternship report on mechanical engineering
Internship report on mechanical engineering
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
 
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
 
Call Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile serviceCall Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile service
 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptx
 
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
 
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
 

Design of concrete structure 2 project-Loay Qabaha &Basel Salame

  • 1. 1 AN-NAJAH NATIONAL UNIVERSITY FACULTY OF ENGINEERING CIVIL ENGINEERING DEPARTMENT *Prepared By: *Submitted To: -Basel Salameh -Dr. Monther Dwakit -Loay Qabaha -Dr. Ibrahim Irman -Mohamad Hindi -Eng. Hanan Jafar -Tariq Thawabi 62116112 Design of concrete structure 2 project
  • 2. 2
  • 3. 3 *Introduction: What is design ? Selecting proper dimensions of reinforced concrete elements and material used taking to account economic considerations . The Design objectives is the designed structure should sustain all loads and deform within limits for construction use, and should be durable. All the above are design objectives that can be fulfilled by understanding the strength and deformation characteristics of the materials used in the design (concrete and steel). Every structure has got its form, function and aesthetics. Normally, we consider that the architects will take care of them and the structural engineers will be solely responsible for the strength and safety of the structure. However, the roles of architects and structural engineers are very much interactive and a unified approach of both will only result in an Integrated" structure. In this project, we will design the project in two way systems, let’s to define what the two way system? Concrete is used mainly in slabs also in columns & beams. Slabs may be designed with respect to loads applied over it as a solid slab either one way or two way, ribbed slab also as one or two way, flat plate, flat slab & waffle slab…, beams could be hidden or dropped. The main purpose is to distribute loads and transport it to earth without causing the structure failure. When the ratio (L/ S) is less than 2.0, it is called two-way slab, shown in. Bending will take place in the two directions in a dish-like form. Accordingly, main reinforcement is required in the two directions.
  • 4. 4 Two-way Edge-supported Solid Slabs : In this system, shown in Figure , beams provide moment interaction with the columns especially when moment resisting frames are used to resist lateral loads. The slab overall thickness is greater because beams project downward, thus the system becomes inflexible in terms of mechanical layout. The system can be used economically for spans up to 7.0 meters. Two-way Edge-supported Ribbed Slabs : This system, shown in Figure 2.e, can be economically used for spans up to 7.0 meters. It is similar to the waffle slab but the voids between ribs are filled with hollow blocks. Hidden or drop beams can be used with this system depending on their spans.
  • 5. 5 Waffle Slabs : The waffle slab is capable of providing the largest spans of the conventional concrete floor systems and can be economically used for spans up to 12.0 meters. This is attributed to the considerable reduction in dead load as compared to other floor systems. Waffle slab construction consists of orthogonal sets of ribs with solid parts at the columns, as shown in Figure. The ribs are formed with fiberglass or metal dome forms. The ribs are usually 0..0to 0.90 meter on center. Shear is transferred to the columns by using beams or shear heads. *Problem Definition: Given Data:  Concrete for Beams , Columns & Slabs , 𝒇́ 𝒄 = 𝟐𝟖 𝑴𝑷𝒂 , &  ˠ= 25 KN/m3  Steel for Reinforcing Bars and Shear Reinforcement , Fy= 420MPa  Floor Height = 4.7 m& number of Floors is 3.  Superimposed dead load is the gravity load of non-structural parts of the building .Superimposed dead load= 3.5KN/m2
  • 6. 6  Live loads are those loads produced by the use and occupancy of the building or other structure and do not include construction or environmental load such as wind load, snow load, rain load, earthquake load, flood load, or dead load. Live loads on a roof are those produced (1) during maintenance by workers, equipment, and materials; and (2) during the life of the structure by movable objects such as planters and by people .Live load= 6 KN/m2. Requirements: Design the slab as: with full Design Detailing. 1. Two way solid slab 2. Two way ribbed slab 3. Two way voided slab L2=frame width =10.5 m Column strip =4 m
  • 7. 7 Direct Design Method The direct design method consists of certain steps for distributing moments to slab and beam sections to satisfy safety requirements and most serviceability requirements simultaneously. Three basic steps are involved : a. Determination of the total factored static moment. b. Distribution of the total factored static moment to negative and positive Sections. c. Distribution of negative and positive factored moments to the column and middle strips and to the beams if any. Limitations The direct design method was developed from theoretical procedures for determination of moments in slabs, requirements for simple design , construction procedures, and performance of existing slabs. Therefore, the slab system, to be designed using the direct design method, should conform to the following limitations as given by ACI Code 13.6.1 : 1. There must be three or more spans in each direction . 2. Slab panels must be rectangular with a ratio of longer to shorter span , center-to-center of supports, not greater than 2.0 . 3. Successive span lengths, center-to-center of supports, in each direction must not differ by more than one-third of the longer span . 4. Columns must not be offset more than 10 % of the span in the direction of offset from either axis between centerlines of successive columns . 5. Loads must be due to gravity only and uniformly distributed Over the entire panel. The live load must not exceed 2 times the dead load.
  • 8. 8 *Two Way Ribbed Slab System: * Slab thickness and modification for the ribbed slab: Assume αfm> 2: H min. = (Ln*(0.8+fy/1400))/ (36+9β) = (10*(0.8+420/1400))/ (36+9*1.33) = 0.23 m =230mm Frame in south north direction (interior) 4mm8)/12=5.57*103(550*23012 =3bh=(solid)I 4mm813.5*10for the suggested cross section =(ribbed)I (Calculated from sap frame section definition). I (ribbed) > I (solid) OK .
  • 9. 9 To find the equivalent slab section for the ribbed slab: 13.5*108= (550*h3)/12 ….. h=308.83 mm. * Loads and shear check: WD (O.W) = (0.55*0.55*0.4-0.32*0.2*0.4)*25+ (0.4*0.2*0.32)*12= 2.6922 KN WD= 2.6922/ (0.55*0.55) =8.9 KN/m2 Wu = 1.2(3.5+8.9) +1.6*6= 24.5 KN/m2 Vu= 24.5*0.55*((10.5-0.7/0.5)-0.36) = 61.17 KN ∅VC = 0.75* 𝟏 𝟔 √𝟐𝟖*1.1*150* 𝟑𝟔𝟎 𝟏𝟎𝟎𝟎 = 39.29 KN Vs= Vu - ∅VC = 21.89 KN (Av/s) = (21.89*1000)/ (420*360) = 0.14 mm2/mm. (Av/s) min = max. Of {0.35*(bw/fy), 0.062*(bw/fy)*√𝒇𝒄 } =0.125 mm2/mm so, use (Av/s) = 0.14 mm2/mm. S max.= d/2 = 360/2 = 180 mm use 1 Ø 8mm / 180 mm Now we have to check the assumption that αfm> 2 The suggested beams dimensions are: B1 (700 *500) for exterior beams I (B1) =7.3*10^9 mm4 B2 (700 *800) for interior beams. I (B2) = 3*10^10 mm4 Columns (700*700) mm αf= (I beam / (I slab* number of ribs))
  • 10. 11 αf1=0.75 αf2 =1.44 αf3 = 0.7 αf4 = 1.2 αf5 = 1.17 All the values of αfm for all panels are less than 2. So we have to go to 2< αfm > 0.2 case:- the least value of αfm = 1.045 H min. = (Ln*(0.8+fy/1400))/ (36+5β*(αfm-0.2)) = ((10.5-0.7)*(0.8+420/1400))/ (36+5*1.33(1.045-0.2) = 0.26 < h=308.83 mm …. OK . * Hand Calculations: analysis and design of frame 3. A- Static moment (M0) ( for each span ) :- M( exterior spans) = (24.5*10.5*7.3^2)/8+ (8.4*7.3^2)/8= 1770 KN. m. M( interior span) = (24.5*10.5*8.3^2)/8+ (8.4*7.3^2)/8= 2288 KN .m Where ,the factored own weight of beam= 8.4 KN/m .
  • 11. 11 B- Positive and negative moments of total frame: Refer to (Table 13.6.3.3) to find the moments in frame in end spans. - 0.7 M (for interior negative moments). - 0.57M (for all positive moments). - 0.16M (for exterior negative moments). For the interior spans:- 0.35M for positive moments 0.65 for the negative moments C- Moments in column strip including the beam :- ( Table 13.6.4.4 for the positive moments ) L2/L1= 10.5/8=1.31 L2/L1= 10.5/9 = 1.17 αf5*( L2/L1)= 1.53>1 αf5*( L2/L1)= 1.37>1 use interpolation use interpolation 1 ………75 1 ………75 1.31…… X X=66% 1.17…..X X=70% 2 ……… 45 2………45
  • 12. 12 (Table 13.6.4.1 for interior negative moments) L2/L1= 10.5/8=1.31 L2/L1= 10.5/9 = 1.17 αf5*( L2/L1)= 1.53>1 αf5*( L2/L1)= 1.37>1 use interpolation use interpolation 1 ………75 1 ………75 1.31…… X X=66% 1.17…..X X=70% 2 ……… 45 2………45 (Table 13.6.4.2 for exterior negative moments) C = (1- 0.63*(0.5/0.7))*((0.7*0.53)/3)= 0.016 m4 Bt = C/(2*Is) = 0.016/(2*(4/0.55)* 13.5*10-4) =0.815< 2.5 Use interpolation 0 ……. 100 0.815………..X 2.5 …………..75 X= 91.85 %
  • 13. 13 0 ……. 100 0.815………..X 2.5 …………..45 X= 82.07% 1 ……. 91.85 1.31………..X 2…………..82.07 X= 88.82% D- Moments in beam : αf5*( L2/L1)= 1.53>1 αf5*( L2/L1)= 1.37>1 M ( beam)= 0.85M ( C.S) M ( beam)= 0.85 M ( C.S) E- Moments in the slab of C.S = 0.15 M ( C.s) . ********
  • 14. 14 * Model ON SAP: A- Slab modification: In two way slab system f11=f22=f12=V13=V23 = (Actual area/ Sap section area) = (0.55*0.08+0.32*0.15)/ (0.3088*0.55) =0.54 M11=M22=M33= 0.25 Mass modifier = weight modifier = (8.9/(0.3088*25))= 1.15 B- Model Checks: * Compatibility and Period is ok.
  • 15. 15 * Equilibrium check. Area of floor = 25* 38 = 950 m2 Live load = 950*6 = 5700 KN Superimposed dead load = 950*3.5 = 3325 KN
  • 16. 16 * Stress/Strain relationships (Moment Check): M0 (interior span) = 2288 KN .m From SAP: (1372+1385)/2 + 954 = 2332.5 KN .m % of error = (2332.5-2288)/2288 = 1.94 % < 5% …. OK Now all of the values of the moments calculated by the direct design method and by the software (SAP) will be attached by an Excel sheet Note: we have just five different values in the frame due to symmetry. Note: the average width of column strip= (8+9)/4 = 4.25 m on both sides. The width of middle strip = 10.5-4.25 = 6.25 m
  • 17. 17
  • 18. 18 Notes:- 1- All the red cells represent that the area of steel is less than the minimum area of steel in slab which is equal to bw*d*Ro min = 150*360*0.0033 = 180 mm2 , so this values should be replaced by 180 mm2 . 2- The blue cells represent that the moment by draw section cut in SAP at the exterior support in the column strip in more than the moment in the frame , so the moment in the middle strip is negative and this region should be reinforced by the minimum area of steel =180 mm2 . 3. The concrete zone (a) must be less than Hf= 80 mm, (As< 2493 mm2), to be able to apply the steel percentage equation directly.
  • 19. 19 4- The shrinkage steel in the slab: As = 0.0018*1000*80 = 144 mm2 S max. = 5*h = 5* 80 = 400 mm S= 1000/ (144/50) = 349 mm so, use 1 Ø 8mm/ 350 mm in both directions. Design of beam in frame 3 for shear and torsion: No torsion in this beam because there is no different in span lengths and moment values. Vu (from SAP) = 606 KN at the interior edge of the exterior span By hand calculation: Wu = (8.5/2) * 24.5 = 104 KN/m ( at the top of the triangle ) W ( o.w) = 1.2*25*0.7*0.7 = 14.7 KN/m Vu = ( M1+M2)/2 + W( o.w)*(L/2)+ 0.5*Wu*0.5*L = (213.8+695)/2 + (14.7*8*0.5)+ ( 0.5*0.5*8*104) = 721.2 KN
  • 20. 21 Design of beam for shear by SAP: Av/s = 1.127 mm^2/mm use Ø12 S = 226/1.127 = 200 mm use 1 Ø 12 / 200 mm Design of columns: - we will use SAP to design the columns and then check one column by hand calculation. The framing type is sway ordinary. A sample of steel percentage in the columns (frame 3).
  • 21. 21 We will check the column with 2.34% steel percentage to check if the column is braced or not, we did a second order analysis by sap and was not there a change in the moment values, so we can assume the column is braced Assume K=1 to be conservative: KLu/r = 1*4700/ (0.3*700) = 22.38 so the column is short also. Pu = 8065 KN Mu = 44 KN.m gama=( 700 – 2*60)/ 700 = 0.83 Mu/bh^2=( (44*10^6)/ (700)^3)/7 = 0.02 Ksi Pu/bh =( (8065*10^3)/ (700)^2)/7 = 2.35 Ksi at gama = 0.75 Ro = 2% at gama = 0.9 Ro = 1.9 % by interpolation Ro = 1.95 % As = 0.0195*700*700 = 9555 mm^2 Ro ( SAP) = 2.34% As= 0.0234*700*700 = 11466 mm^2 ( 14@32
  • 22. 22 Note : there is a high difference between the hand and SAP calculations in column steel , because the SAP designed for this moment and a minimum moment in the other direction not only in one direction (Mu2=0 ,take Mu2 min. = 292.298 KN.m . Ties spacing: S < 16*32 = 512 mm S < 48*10 = 480 mm S < 700 mm So, use 1 Ø10 / 450 mm.
  • 23. 23 *Details for the two way ribbed system: - 1- Cross section in beam in the middle of interior span of frame 3. 2 - Cross section in the middle strip in the middle of interior span of frame 3. 3- Cross section in the column strip slab in the middle of interior span of frame 3. 4- Cross section in column that was checked above.
  • 24. 24
  • 26. 26 *Two Way Voided Slab System: * Slab thickness and modification for the ribbed slab: Assume αfm> 2: H min. = (Ln*(0.8+fy/1400))/ (36+9β) = (9.7*(0.8+420/1400))/ (36+9*1.35) = 0.221 m =221mm Frame in south north direction (interior) (Frame 3) . 4mm8)/12=6.02*10312 =(670*2213= bh(solid)I 4mm8for the suggested cross section = 40.15*10(voided)I (Calculated from sap frame section definition). I (voided) > I (solid) OK .
  • 27. 27 To find the equivalent slab section for the ribbed slab: 40.15*108= (670*h3)/12 ….. h=415 mm. * Loads and shear check: Wd (O.W) = (0.67^2*0.46- 0.52^2*0.32)*25= 3 KN Wd= 3/(0.67*0.67)=6.7 KN/m2 Wu = 1.2(3.5+6.7)+1.6*6= 21.84 KN/m2 Vu= 21.84*0.67*((10.5-0.8/0.5)-0.4) = 78 KN ∅VC = 0.75* 𝟏 𝟔 √𝟐𝟖*1.1*150* 𝟒𝟎𝟎 𝟏𝟎𝟎𝟎 = 45.6 KN Vs= Vu - ∅VC = 32.4 KN (Av/s) = (32.4*1000)/ (420*400) = 0.19 mm2/mm. (Av/s) min = max. Of {0.35*(bw/fy), 0.062*(bw/fy)*√𝒇𝒄 } =0.125 mm2/mm so, use (Av/s) = 0.19 mm2/mm. S max.= d/2 = 400/2 = 200 mm use 1 Ø 8mm / 200 mm Now we have to check the assumption that αfm> 2 The suggested beams dimensions are: B1 (400 *800) for exterior and interior beams I (B) =1.7*10^10 mm4 Columns (800*800) mm αf= (I beam / (I slab* number of ribs))
  • 28. 28 αf1=0.71 αf2 =0.335 αf3 = 0.672 αf4 = 0.237 αf5 = 0.272 All the values of αfm for all panels are less than 2. So we have to go to αfm< 0.2 case:- the least value of αfm = 0.294 h min. = Ln/30 = 9.7/30 = 0.32 m < h=415 mm …. OK * Hand Calculations: analysis and design of frame 3. A- Static moment (M0) ( for each span ) :- M( exterior spans) = (21.84*10.5*7.2^2)/8+ (8.4*7.3^2)/8= 1834.5 KN. m. M( interior span) = (21.84*10.5*8.2^2)/8+ (8.4*7.3^2)/8= 2322 KN .m Where :- the factored own weight of beam= 8.4 KN/m . B- Positive and negative moments of total frame: Refer to (Table 13.6.3.3) to find the moments in frame in end spans. - 0.7 M (for interior negative moments). - 0.57M (for all positive moments). - 0.16M (for exterior negative moments).
  • 29. 29 For the interior spans:- 0.35M for positive moments 0.65 for the negative moments C- Moments in column strip including the beam :- ( Table 13.6..4.4 for the positive moments ) L2/L1= 10.5/8=1.31 L2/L1= 10.5/9 = 1.17 αf5*( L2/L1< 1 αf5*( L2/L1)< 1 use interpolation use interpolation X=0.6 X=0.66 (Table 13.6.4.1 for interior negative moments) L2/L1= 10.5/8=1.31 L2/L1= 10.5/9 = 1.17 αf5*( L2/L1) < 1 αf5*( L2/L1) < 1 use interpolation ( X= 0.66) use interpolation (X=0.75) ( Table 13.6.4.2 for exterior negative moments ) C = (1- 0.63*(0.4/0.8))*((0.8*0.43)/3)= 0.01169 m4 Bt = C/(2*Is) = 0.01169/(2*((1/12)*4*0.415) =0.245< 2.5 Use interpolation X= 0.972 D- Moments in beam : αf5*( L2/L1) < 1 αf5*( L2/L1) <1 M ( beam)= 0.285M ( C.S) M ( beam)= 0.285 M ( C.S) E- Moments in the slab of C.S = 0.15 M ( C.s) . ********
  • 30. 31 * Model ON SAP: A- Slab modification: In two way slab system f11=f22=f12=V13=V23 = (Actual area/ Sap section area) = (2*0.67*0.07+0.32*0.15)/ (0.415*0.67) =0.51 M11=M22=M33= 0.25 Mass modifier = weight modifier = (6.7/(0.415*25))= 0.645
  • 31. 31 B- Model Checks: * Compatibility and Period is ok.
  • 32. 32 * Equilibrium check. Area of floor = 25* 38 = 950 m2 Live load = 950*6 = 5700 KN Superimposed dead load = 950*3.5 = 3325 KN * Stress/Strain relationships (Moment Check): M0 (interior span) = 2322 KN .m From SAP: (8931+8011)/2 + 793= 2192 KN .m % of error = (2322-2192)/2322 = 5.5 % < 10% …. OK
  • 33. 33 Now all of the values of the moments calculated by the direct design method and by the software (SAP) will be attached by an Excel sheet Note: we have just five different values in the frame due to symmetry. Note: the average width of column strip= (8+9)/4 = 4.25 m on both sides. The width of middle strip = 10.5-4.25 = 6.25 m
  • 34. 34 Notes:- 1- All the red cells represent that the area of steel is less than the minimum area of steel in slab which is equal to bw*d*Ro min = 150*400*0.0033 = 198 mm2 , so this values should be replaced by 198 mm2 . 2- The blue cells represent that the moment by draw section cut in SAP at the exterior support in the column strip in more than the moment in the frame , so the moment in the middle strip is negative and this region should be reinforced by the minimum area of steel =198 mm2 . 3. The concrete zone (a) must be less than Hf= 70 mm, (As< 2657 mm2), to be able to apply the steel percentage equation directly. 4- The shrinkage steel in the slab: As = 0.0018*1000*70 = 126 mm2 S max. = 5*h = 5* 70 = 350 mm S= 1000/ (144/50) = 349 mm so, use 1 Ø 8mm/ 350 mm in both directions.
  • 35. 35 Design of beam in frame 3 for shear and torsion: No torsion in this beam because there is no different in span lengths and moment values. Vu (from SAP) = 411 KN at the interior edge of the exterior span By hand calculation: Wu = (8.5/2) * 21.84 = 92.82 KN/m ( at the top of the triangle ) W ( o.w) = 1.2*25*0.8*0.4 = 9.6 KN/m Vu = ( M1+M2)/2 + W( o.w)*(L/2)+ 0.5*Wu*0.5*L = (106.5+365.2)/2 + (9.6*8*0.5)+ ( 0.5*0.5*8*92.82) = 459 KN ( OK ) Design of beam for shear by SAP:
  • 36. 36 Av/s = 0.965 mm^2/mm use Ø12 S = 226/0.965 = 234 mm use 1 Ø 12 / 200 mm Design of columns: - we will use SAP to design the columns and then check one column by hand calculation. The framing type is sway ordinary. A sample of steel percentage in the columns (frame 3). We will check the column with 1% steel percentage to check if the column is braced or not, we did a second order analysis by sap and was not there a change in the moment values, so we can assume the column is braced Assume K=1 to be conservative: KLu/r = 1*4700/ (0.3*800) = 19.5 so the column is short also. Pu = 2608 KN Mu = 24 KN.m gama=( 800 – 2*60)/ 800 = 0.85 Mu/bh^2=( (24*10^6)/ (800)^3)/7 = 0.0.006 Ksi Pu/bh =( (2608*10^3)/ (800)^2)/7 = 0.6 Ksi at gama = 0.75 Ro = 1% at gama = 0.9 Ro = 1 % by interpolation Ro = 1% As = 0.01*800*800 = 6400 mm^2 ( 8@32)
  • 37. 37 Ties spacing: S < 16*32 = 512 mm S < 48*10 = 480 mm S < 800 mm So, use 1 Ø10 / 450 mm. *Details for the two way ribbed system: -
  • 38. 38
  • 39. 39
  • 40. 41
  • 41. 41 *Two Way Solid Slab System: *. Slab thickness and modification for the ribbed slab: Assume αfm> 2: H min. = (Ln*(0.8+fy/1400))/ (36+9β) Ln=max clear span =10.5-0.8=9.7 m Β=9.77.2 = (9.7*(0.8+420/1400))/ (36+9*1.34) = 0.222 m =222 mm Try h=250 mm To compute αf we need to compute αfm for every beam Iedge beam =9.86*10-3 m4, L-section 800*600*400 Iinterior beam= 11.5*10-3 m4, T-section 600*400 Column 800*800
  • 42. 42 Frame in east west direction: I exterior = bh312 = (4*0.253)/12=5.27*10-3 m4 I interior = for the suggested cross section = 0.011m4 Frame in north south direction: I exterior=0.0136 m4 I interior 1=0.012 m4 I interior 2=5.2*10-3 αf= (I beam / (I slab* number of ribs)) αf1=1.89 αf2 =1.05 αf3 = 1.89 αf4 = .96 αf5 = 0.85 Average for panels smallest =0.97<2 All the values of αfm for all panels are less than 2. So we have to go to 2< αfm > 0.2 case:- the least value of αfm = 0.97
  • 43. 43 H min. = (Ln*(0.8+fy/1400))/ (36+5β*(αfm-0.2)) = 0.263 try h=300mm …. OK * Loads and shear check: Wd= 0.3(25)/(3.5)=11 KN/m2 Wu = 1.2(11)+1.6*6= 22.8 KN/m2 Vu= 22.5* ((10.5-0.8/0.5)-0.26) = 104.6 KN ∅VC = 0.75* 𝟏 𝟔 √𝟐𝟖**1000* 𝟐𝟔𝟎 𝟏𝟎𝟎𝟎 = 172 KN ∅VC> Vu ok Now we have to check the assumption that αfm> 2 * Hand Calculations: analysis and design of frame 3. A- Static moment (M0) ( for each span ) :- M( exterior spans) = (22.8*10.5*8.6^2)/8= 2757.6 KN. m. M( interior spans) = (22.8*10.5*7.6^2)/8= 1728.4 KN .m Where :- the factored own weight of beam= 8.4 KN/m . B- Positive and negative moments of total frame: Refer to (Table 13.6.3.3) to find the moments in frame in end spans. - 0.7 M (for interior negative moments). - 0.57M (for all positive moments). - 0.16M (for exterior negative moments). For the interior spans:-
  • 44. 44 0.35M for positive moments 0.65 for the negative moments Repeat αf for frame interior I = 11.573*10-3 m Is =0.023 m4 αf =0.5 C- Moments in column strip including the beam :- ( Table 13.6.4.4 for the positive moments ) L2/L1= 10.5/8=1.31 @L2/L1= 2 αf5*( L2/L1)= 0.85<1 αf5*( L2/L1) use interpolation @ L2/L1=1 use interpolation 0 ………60 0 ………60 0.85…… X X=72.7% 0.85…..X X=47.2% 1 ……… 75 1………45 @ ( L2/L1) Goal Use interpolation 1 ………72.7 1.31…… X X=64.7% 2 ……… 47.2
  • 45. 45 (Table 13.6.4.1 for interior negative moments) L2/L1= 10.5/8=1.31 L2/L1= 10.5/9 = 1.17 αf5*( L2/L1)= 0.85 αf5*( L2/L1)= 1.37>1 use interpolation use interpolation 0 ………75 0 ………75 0.85…… X X=75% 0.85…..X X=49.5% 1 ……… 75 1………45 @( L2/L1) Goal Use interpolation 1 ………75 1.31…… X X=67% 2 ……… 49.2 (Table 13.6.4.2 for exterior negative moments) C = (1- 0.63*(0.4/0.6))*((0.6*0.43)/3) + (1- 0.63*(0.3/0.4))*((0.4*0.333) = 8.44*10-3 m4 Bt = C/(2*Is) = 8.44*10-3 /(2*0.023) =0.183< 2.5 Use interpolation X=100%
  • 46. 46 D- Moments in beam: αf5*(L2/L1) = 0.85<1 M (beam) = 0.85 *0.85 =0.72 M ( C.S) * Model ON SAP: A- Slab modification: In two way slab system f11=f22=f12=V13=V23 =1 M11=M22=M33= 0.25 Mass modifier = weight modifier = 1
  • 47. 47 B- Model Checks: * Compatibility and Period is ok. * Equilibrium check. Area of floor = 25* 38 = 950 m2 Live load = 950*6 = 5700 KN Superimposed dead load = 950*3.5 = 3325 KN
  • 48. 48 * Stress/Strain relationships (Moment Check): M0 (interior span) = 1728.4 KN .m From SAP: (1132+1132)/2 + 814 = 1946 KN .m % of error = (1946.5-1728.4)/ 1728.4 = 9 % < 10% …. OK Now all of the values of the moments calculated by the direct design method and by the software (SAP) will be attached by an Excel sheet Note: we have just five different values in the frame due to symmetry. Note: the average width of column strip= (8+9)/4 = 4.25 m on both sides. The width of middle strip = 10.5-4.25 = 6.25 m
  • 49. 49
  • 50. 51
  • 51. 51 .Design of beam in frame 3 for shear and torsion: No torsion in this beam because there is no different in span lengths and moment values. Vu (from SAP) = 733 KN at the interior edge of the exterior span By hand calculation: Wu = (8.5/2) * 22.8 = 96.9 KN/m ( at the top of the triangle ) W ( o.w) = 1.2*25*0.4*0.6 = 7.2 KN/m Vu = ( M1+M2)/2 + W( o.w)*(L/2)+ 0.5*Wu*0.5*L = (293+457)/2 + (7.2*8*0.5)+ ( 0.5*0.5*8*96.9) = 601 KN (OK) . Design of beam for shear by SAP: Av/s = 2.242 mm^2/mm use Ø12 S = 226/2.242 = 101 mm use 1 Ø 12 / 100 mm
  • 52. 52 Design of columns: - we will use SAP to design the columns and then check one column by hand calculation. The framing type is sway ordinary. A sample of steel percentage in the columns (frame 3). We will check the column with 1% steel percentage to check if the column is braced or not, we did a second order analysis by sap and was not there a change in the moment values, so we can assume the column is braced Assume K=1 to be conservative: KLu/r = 1*4700/ (0.3*800) = 19.5 so the column is short also. Pu = 2224 KN Mu = 50 KN.m gama=( 800 – 2*60)/ 800 = 0.85 Mu/bh^2=( (50*10^6)/ (800)^3)/7 =0 Ksi Pu/bh =( (2224*10^3)/ (800)^2)/7 = 0.49 Ksi by interpolation Ro < 1% As = 0.01*800*800 = 6480 mm^2 ( 8@32 ) . Ties spacing: S < 16*32 = 512 mm S < 48*10 = 480 mm S < 800 mm so, use 1 Ø10 / 450 mm.
  • 53. 53 *Details for the two way solid system: - 1- Cross section in beam in the middle of interior span of frame 3. 2 - Cross section in the middle strip in the middle of interior span of frame 3. 3- Cross section in the column strip slab in the middle of interior span of frame 3. 4- Cross section in column that was checked above.
  • 54. 54
  • 55. 55 *Conclusion, Recommendation: There are differences between the hand calculation and SAP program result but it’s Acceptable which not exceed 10%. After analyzing each of the previous systems we have concluded that we would use Low-rise concrete frame as our primary system. Using this we would have a system of columns, girders, and voided box beams. This would frame our first floor and second floor deck from there we would probably use a steel structure to frame the second story and roof. After constructing and executing our decision matrix we concluded that The Low-Rise Concrete frame has the most to offer for our particular building. We used a weighted scale to come to our conclusion. I’m sure that whether it be the owner or the Architect they will have criteria that will have greater importance over others. Our Group also has a good deal of previous system and we made three floor systems to it. The direct design method do not given accurate value so, We recommend to use one way solid slab with girder system in order to decrease slab thickness and to distribute the loads over coloumns and girders and increace beam section .We recommend to use two way slab ribbed, but we offer ribbed slab with hollow blocks to give lighter weight and good insulation too finally, We recommend to use the most effective floor system , and the most conservative system and low cost . The end
  • 56. 56