SMART HEAT PUMPS
Intelligent and highly efficient
Quality with systems
Air/water system
for heating and cooling
WKF series
1-2017
Max. 55°C
Inlet temperature
ErP Ready
Energie
Effizienz
Klasse
A++
REMKO – THE SYSTEM PROVIDER
2
AIR-CONDITIONING
Room air conditioners
Local air-conditioners
Comfort air-conditioners
Chilled water systems
Chillers
Dehumidifiers
Mobile dehumidifiers
Swimming pool dehumidifier
HEATING
Hot air heating systems
Mobile hot air heating systems
Stationary hot air heating systems
NEW ENERGIES
Heat pump systems
Heat pumps
Heat pump packages
Quality with systems
3
Product overview
Page Series
4 - 19 Heat pumps
4 - 11 Function WKF
12 - 13 The intelligent control Smart-Control
14 - 15 Technical data WKF-compact
16 - 17 Technical data WKF
18 - 19 Technical data WKF Duo
20 - 21 Indoor units for heating and cooling
20 - 21 Wall and ceiling chests KWK-4R
22 - 47 Heat pump packages
22 - 41 Heat pump packages WKF
42 - 43 Solar collectors RSK
44 - 47 Heat pump solar packages WKF
48 - 49 Tank systems
50 - 55 Accessories
Inspected heat pumps with
EHPA quality seal of approval
REMKO's ArtStyle heat pumps
are listed by the European Heat
Pump Association (EHPA – former-
ly D-A-CH) in its seal of approval
list! REMKO's heat pumps thus
fulfil high international standards
and guarantee performance num-
bers you can count on!
ErP-ready
Starting in September 2015, the
energy efficiency label will be used to
indicate the economic efficiency of
all heating systems. REMKO already
uses the label for all heat pumps.
ErP Ready
Energie
Effizienz
Klasse
A++ SG-ready
The Multitalent
REMKO Smart-Control is designed for
use in the intelligent Smart-Grid power
mains.
4
Electrical drive
energy
*
* Heating
25%
75%free solar energy
from the air
Use energy from the air all year round
INDEPENDENT FROM OIL AND GAS
In contrast to other heating systems,
the acquisition costs for a heat pump in
new or old buildings pays off relatively
quickly.
■	 Considerably lower consumption
and operating costs
■	 Hardly any maintenance costs
■	 No costs for chimney and
chimney sweep
■	 No costs for a tank
■	 No costs for a tank room
■	 Simple installation
The advantages of a heat pump
are clear
Government subsidies
Information about government
subsidies can be found under:
www.bafa.de
www.kfw.de
www.foerderdata.de
New dimensions in terms
of independence
The solar energy stored in the
air is an inexhaustible source
of emission-free power. Heat
pumps draw the majority of the
energy from the surrounding air.
This works even in winter with
outside temperatures below
zero. Only the drive energy
has to be provided by electrical
power.
75%* of the heat
comes from the air,
free of charge
* The ratio can vary depending on outdoor temperature and operating conditions.
	 Precise data for the COP value can be found in the technical data.
5
Highly efficient and energy-saving
1/3
Minimal temperature fluctuations
mean energy savings
Time
Temperature
The inverter requires only one-third of the time
of conventional systems to start up
Conventional
Inverter
The REMKO inverter technology
saves money.
The REMKO Smart-WP represents a
decision for a state-of-the-art solu-
tion. Modern inverter technology
makes this possible.
This pioneering technology au-
tomatically adapts the condenser
speed variably to the precise cooling
or heating requirement. This exact
and gentle regulation enables a
particularly energy saving, efficient
operation with a high seasonal
performance factor in comparison to
non-inverter systems.
In summary:
In the event of increased demand,
the heat pump works more inten-
sively, in the event of reduced de-
mand the heat pump switches over
to energy-saving mode.
This saves money.
MODERN INVERTER TECHNOLOGY
6
Heat pump technology
The technology of the heat pump is similar
to that of a refrigerator - only the principle
is reversed. The heat extracted from the air
is brought up to a higher temperature level
in a refrigerant circuit and is then trans-
ferred to the indoor module.
Function of outdoor unit
The outdoor unit extracts heat from the air.
This heat is brought up to a higher tem-
perature level in a refrigerant circuit and
is then transferred to the heating water in
the indoor unit. The condenser speed and
fans speed adapt to the precise cooling or
heating requirement.
Function of indoor unit
The indoor unit transfers the heat con-
tained in the refrigerant to the floor
heating elements or heaters installed in the
building. In order to cool, the function of
the heat pump is simply reversed.
FUNCTION
Evaporation
Liquefying
Condensing
Decompression
Functional diagram
for heating
Outdoor unit for heat pump
Outdoor area
Indoor heat pump unit
Indoor area
REMKO Smart-WP
7
Heat pumps in new buildings.
Independent from oil and gas.
Heat pumps for modernisation
of existing buildings. Combi-
nation with existing heating
appliances.
Heat pumps in industry. The
factory floor is heated and
cooled through concrete core
activation.
Heat pumps for the workshop
office. The ideal space-saving
solution.
WKF-compact series
With additional integrated 300-litre domestic water tank.
All in one unit.
VERSATILE
WKF series
It couldn't be simpler. Everything is com-
pletely installed in a single enclosure.
Highly efficient, regulated heating circuit
pump, heat exchanger, various fittings, and
the Smart-Control control system.
8
Effective domestic water preparation
An integrated 300-litre domestic water tank with
a large-dimension heat exchanger is build into the
unit in the case of the WKF-compact series.
For the WKF series, external storage systems are
available.
Combination with floor heating, modern
heaters, and wall-mounted heating
systems
Heat pumps are able to achieve their highest
levels of efficiency when combined with floor
heating.
With conventional modern radiators, the operat-
ing costs are lower than for oil or gas heating
appliances.
This means that cosy heating is guaranteed even
at lower outside temperatures.
Solar station
Circulation
Chilledwater
Outdoorprobe
Inverted rectifier,
photovoltaic system
Hot water
Outdoor unit
REMKO Smart-WP indoor unit
Combination with tanks systems
The interface and collection point for vari-
ous energy systems
Tanks are available in various designs and capaci-
ties. With connection options for heat pump, solar
system, solid material boiler, and domestic water
preparation, the storage system is the interface
and collection point.
Average temperatures in Germany
50
40
30
20
10
0
10 5 0 -5 -10 -15
Outdoor temperature °C
Annualheatingperformance%
Smart HEAT PUMPS
HEAT PUMPS THAT ADAPT TO THE SYSTEM
20 15
29%
7%
1% 1%
39%
18%
5%
9
Floor heating
Pleasant climate in the summer
In hot weather, the heat pump can be used for
cooling. In order to do so, the function of the
heat pump is simply reversed. You will find air-
conditioning units in the
range of accessories. The
air-conditioning units
work on the convection
principle. The technical
principle of the air-
conditioners is simple:
Air flows past the
interior heat exchanger
and is either heated
or cooled.
Wall and ceiling chests
REMKO KWK series
Air-conditioner
Heater
Solarplant
Photovoltaicplant
Combination with heat generators in
bivalent operation
The heat pump can be combined with a heat
generator in order to cover peak loads. This appli-
ance, for example, can be a gas or oil condensing
boiler that can be directly connected to the WKF
indoor unit.
Combination with a REMKO RSK solar
plant for economic domestic water
preparation and heating support
An ideal combination for a maximum of economic
efficiency and environmental protection.
Direct solar energy delivers a high percentage of
hot water preparation in annual average.
Optimised use of photovoltaic current
The REMKO Smart-WP can preferably be oper-
ated using self-generated photovoltaic current.
As a result, not as much expensive current has to
be obtained from the mains. This saves money
and the dependency on current price increases
decreases.
10
The compact class saves space and installation effort
The REMKO Smart-WP is perfectly suited for new buildings in com-
bination with underfloor heating. WKF-compact does not require a
large mounting area due to its compact construction. This construc-
tion saves space in the mounting area. The costs for installation are
reduced by the high percentage of premounted components.
REMKO Smart-WP
WKF-compact SERIES
The heat pump with integrated 300-litre domestic water tank for
high hot water comfort
Housing solution with EPP
Through the consistent use of EPP moulded parts, insulation is
increased and the loss of energy is minimised.
In addition, considerable weight advantages result.
The front consists of a lacquered design front panel.
Profit from these
advantages:
■	 Heating and cooling
■	 Low investment costs
■	 Power-modulated opera-
tion due to modern inverter
mode
■	 Low operating costs due to
high COP value
(see technical data)
■	 Ready for connection of
solar system to drinking
water supply
■	 Mounting-friendly instal-
lation All connections are
located at the top.
■	 Intelligent defrosting logic
circuit
■	 Integrated electronic bypass
valve for guaranteeing the
minimum volume flow rate
■	 High hot water comfort
through integrated, enam-
elled domestic water tank
with a volume of 300 litres
(BEVB 1.19 kWh/day)
■	 Smart-Control intelligent
control system
Use in intelligent Smart-Grid
power mains possible
■	 Technical unit handover/
CheckServ by REMKO Tech-
nical Service possible
■	 Integrated heating circuit pump
for the supply of the heating
system
■	 Night operation to reduce
noise
■	 Visualization of the outdoor
unit parameters
■	 Chimney sweep function
11
Free choice when installing the outdoor units
You save a lot of space when installing the outdoor
modules externally. You can use the basement space for
other purposes such as a party room or sauna.
Outdoor installation is ideal for buildings without
a basement.
WKF
outdoor units
Cosy heat in the winter, a pleasant climate in
the summer
Winters are getting warmer and summers hotter. Tem-
peratures of over +30°C are no longer uncommon in
summer. This means that in addition to heating, cooling
is taking on an ever more important role. One more rea-
son to install a REMKO heat pump. In winter, the heat
pump operates as an efficient heating system, whilst, in
summer, the water-bearing system ensures for comfort-
able air conditioning.
WKF-compact series with integrated 300-litre
domestic water tank, output between 1.1 and
17.7 kW
12
The future is smart
Diagrams and energy balance
sheets (Smart-Count)
Animated building diagram
with installed components
Smart-Com for integration
into a Smart Home system
Remote control via the Internet
(Smart-Web)
REMKO Smart-Control with TFT screen
Ready for 24h operation
The intelligent Multitalent is an efficient overall
system. Connection to all regenerative energies
is possible.
Whether heat pumps, solar energy, or photo-
voltaics, anything can be integrated. Use in a
Smart-Grid or Smart Home system, such as KNX,
is possible.
The controller offers extensive setting
possibilities.
■	 Time programming of night operation to
reduce noise
■	 Graphic representation of the heating curve
■	 Display of the outdoor unit parameters
■	 Activation of the chimney sweep function
■	 Control of four mixed heating circuits
■	 Integrated dew point control
13
Easy operation via softkeys and
rotary knob
■ 	 Integration of photovoltaic
current into the system
■ 	 Night operation mode
to reduce noise
■ 	 Solar connection
■ 	 Integration of the air-condition-
ing function into the system
■ 	 2 mixed heating
circuits
■ 	 Connection of several
heat generators
Intelligent and
highly efficient
Chimney sweep button to activate
the second WE for exhaust gas
measurement
Service wizard for visualisation
of the operating states
Installation wizard for simplifying
commissioning
■ 	 Integration into a
Smart Home system
■ 	 Dynamic hygiene
function
External data memory Operating instructions can be called
using a central information button.
14
Smart-HEAT PUMPS
WKF-compact series
European uality Label
for Heat Pumps
EHPA / D-A-CH
The compact class saves space and installation effort
WKF-compact series does not require a large mounting area
due to its compact construction and integrated components. In
connection with underfloor heating, this unit is perfectly suited
for new buildings. This construction saves space in the mounting
area. The costs for installation are reduced by the high percentage
of premounted components.
Scope of supply
■	 REMKO Smart-Control – the
intelligent control system
■	 indoor unit with integrated
300-litre domestic water
tank (BEVB 1.19 kWh/day)
■	 Outdoor unit with inverter
technology
■	 Highly efficient, controlled
heating circuit pump
■	 Industrial water set, includ-
ing 3-way changeover valve
■	 Dirt filter 1"
■	 2 shut-off valves 1" and
thermometer
■	 Safety group with SIV,
automatic bleeding valve
and pressure gauge
■	 Outdoor sensor/immersion
probe
■	 Electrically controlled
bypass mixer
■	 Prepared (flange) for solar
drinking water heating
Profit from these advantages
■	 Low investment costs
■	 Power-modulated operation
due to modern inverter mode
■	 Low operating costs due to
high COP value
(see technical data)
■	 Ready for connection of
solar system to drinking
water supply
■	 Mounting-friendly installation
All connections are located at
the top.
■	 Heating and cooling
■	 High hot-water comfort due
to integrated, enamelled WKT
300 domestic water tank with a
volume of 300 litres
■	 Extremely low heating losses of
the WKT 300 domestic water
tank BEVB 1.19 kWh/day
■	 Electric booster heating 49 W
■	 Energy efficiency rating A
■	 Smart-Control intelligent
control system
Use in intelligent Smart-Grid
power mains possible
■	 Technical unit handover by
REMKO Technical Service
possible
■	 Integrated heating circuit
pump for the supply of the
heating system
■	 Integrated electronic bypass
valve for guaranteeing the
minimum volume flow rate
■	 Intelligent thawing logic circuit
■	 Monoenergetic operation
possible through REMKO
Smart-Serv or bivalent opera-
tion possible through REMKO
Smart-BVT
■	 Night operation to reduce
noise
■	 Chimney sweep function
ErP Ready
Energy
A++
Efficiency
Rating
15
Technical data and prices
Area of use: heating 5)
2-7 kW 7-12 kW 12-18 kW
Series WKF 70 compact WKF 120 compact WKF 180 compact
Design Single split Single split Single split
System Air / water Air / water Air / water
Operating mode Heating / cooling Heating / cooling Heating / cooling
Testing EHPA EHPA EHPA
Inverter technology Series Series Series
Smart Control Series Series Series
Preparation for domestic water Series Series Series
Domestic water tank WKT 300 (enamelled) integrated Litre 300 300 300
Heat exchanger area, domestic water tank m² 3.5 3.5 3.5
Number of indoor units/outdoor units 1/1 1/1 1/1
Night operation (power control) Series Series Series
Service limits, heating °C -20 to +35 -20 to +35 -20 to +35
Rated heating capacity (min. / max.) kW 6.0 (0.9 - 6.0) 10.0 (2.5 - 12.5) 14.0 (3.1 - 17.7)
Energy efficiency rating for heating 4)
A++ / A++ A++ / A+ A++ / A++
Rated heating capacity / COP for A7/W35 1)
kW / - 5.45 / 4.6 9.86 / 4.4 14.02 / 4.5
Rated heating capacity / COP for A2/W35 1)
kW / - 4.61 / 3.5 6.95 / 3.6 9.32 / 3.5
Rated heating capacity / COP for A-7/W35 1)
kW / - 4.50 / 2.8 6.14 / 2.9 8.20 / 2.9
Max. supply temperature, heating water °C + 55 + 55 + 55
Service limits, cooling °C +15 to +45 +15 to +45 +15 to +45
Rated cooling capacity (min. / max.) kW 5.0 (1.1 - 8.9) 6.0 (3.3 - 11.9) 11.0 (5.5 - 14.0)
Rated cooling capacity / EER for A35/W7 1)
kW / - 4.90 / 2.8 6.79 / 2.3 12.20 / 2.6
Rated cooling capacity / EER for A35/W18 1)
kW / - 6.70 / 3.6 5.30 / 3.7 12.77 / 3.8
Rated cooling capacity / EER for A27/W18 1)
kW / - 6.80 / 3.9 9.46 / 3.6 18.20 / 4.1
Min. supply temperature, cooling water °C + 7 + 7 + 7
Refrigerant 2)
R410A R410A R410A
Basic refrigerant filling volume / CO2
equivalent kg/t 1.2 / 2.5 2.0 / 4.2 2.85 / 5.8
Refrigerant connections Inch 3/8 / 5/8 3/8 / 5/8 3/8 / 5/8
Max. refrigerant line length m 30 50 75
Max. refrigerant line height m 20 30 30
Voltage supply V/Hz 230/1~/50 230/1~/50 400/3~/50
Rated current consumption for A7/W35 kW 1.18 2.22 3.09
Rated current consumption for A7/W35 A 5.19 10.44 5.02
On-site fuse protection (outdoor unit) A slow-acting 20 20 3x16
Rated flow rate of water at ∆t 5 K m³/h 0.95 1.7 2.4
External maximum pressure loss (heating system) kPa 80 80 80
Max. operating pressure, water bar 3.0 3.0 3.0
Hydraulic connection, inlet flow/return line, flat-sealing Inch 1/4" AG 1/4" AG 1/4" AG
Pipeline diameter to be used on site, Cu pipe mm 28 28 35
Sound power level LwA (outdoor unit) rated/max. dB(A) 63.2/66.0 67.9/69.0 68.3/69.8
Sound pressure level LpA rated/max. 3)
dB(A) 38.2 / 41.0 42.9 / 44.0 42.3 / 45.2
Max. sound pressure level LwA (outdoor unit), night operation 3)
dB(A) 38.0 39.9 39.3
Outdoor unit, standard colour Grey-white Grey-white Grey-white
Dimensions indoor unit Height / width / depth mm 1928/800/790 1928/800/790 1928/800/790
Dimensions outdoor unit Height / width / depth mm 640/880/310 1010/940/330 1430/940/330
Weight indoor unit / outdoor unit kg 236/50 238/74 240/100
Series WKF 70 compact WKF 120 compact WKF 180 compact
Ref. no. 254030 255020 255030
Serial colour of outdoor unit: silver
Ref. no. 254040 255025 255035
1)
COP / EER according to EN 14511, 2)
GWP = 2088 3)
Distance 5m, full sphere, A7/W55 4)
Average, composite system W35/55°C including Smart Control 5)
Total heating requirement, intake flow line 35°C, monoenergetic
Accessories
Series WKF 70 compact WKF 120 compact WKF 180 compact
REMKO Smart-Count – Factory-installed heat meter for the separate
counting of the quantity of heat of heating and hot water 259010 259010 259010
REMKO Smart-Com – Additional software for the integration of the heat pump
into a smart home system such as KNX via the Ethernet interface of Smart Con-
trol, including the heat meter installed at the factory (Smart Count)
254090 254090 254090
REMKO Smart-BVT, factory-installed BVT pipe assembly, 3-way switchover
valve for the integration of a second heat generator (max. 22 kW) without
a circulation pump, bivalently alternating operation. Note: No combination
with REMKO Smart-Serv possible. Only in combination with buffer tank.
254050 259012 259013
REMKO SmartServ – Intelligent provision, installed heating rod 9 kW for
monoenergetic operation, including emergency heating functions
Note: No combination with REMKO Smart-BVT possible.
254059 259022 259023
REMKO Smart-Cool – for active cooling. Pipe subassemblies and circulation
pump in the indoor unit with vapour density insulation. Use in case of
cooling function when the inlet temperature is below the dew point.
259085 259085 259085
For additional accessories, see page 50
16
Profit from these
advantages:
■	 Low investment costs
■	Smart-Inverter
power-modulating mode.
This saves money.
■	 Low operating costs due to
high COP value
(see technical data)
■	 Heating and cooling
■	 Mounting-friendly installa-
tion All connections from the
top.
■	 Night operation to reduce
noise
■	 Smart-Control intelligent
control system
Use in intelligent Smart-Grid
power mains possible
■	 Technical unit handover by
REMKO Technical Service
possible
■	 Monoenergetic operation
possible through REMKO
Smart-Serv or bivalent
operation possible through
REMKO Smart-BVT
■	 Chimney sweep function
It couldn't be simpler.
Everything complete in an indoor unit
Everything is installed in a single housing: Highly efficient circula-
tion pump, heat exchanger, various fittings, and the Smart-Con-
trol control system. In connection with existing tank systems, the
WKF Duo series is prefect for new buildings and renovations.
Smart-HEAT PUMPS
WKF series
European uality Label
for Heat Pumps
EHPA / D-A-CH
Scope of supply
■	 REMKO Smart-Control – the
intelligent control system
■	 Indoor unit
■	 Outdoor unit with
inverter technology
■	 Highly efficient, controlled
heating circuit pump
■	 Dirt filter 1"
■	 2 shut-off valves 1" and
thermometer
■	 Safety group with SIV,
automatic bleeding valve
and pressure gauge
■	 Outdoor sensor/immer-
sion probe
■	 Electrically controlled
bypass mixer
ErP Ready
Energy
A++
Efficiency
Rating
17
Technical data
Area of use: heating 5)
2-7 kW 7-12 kW 12-18 kW
Series WKF 70 WKF 120 WKF 180
Design Single split Single split Single split
System Air / water Air / water Air / water
Operating mode Heating / cooling Heating / cooling Heating / cooling
Testing EHPA EHPA EHPA
Inverter technology Series Series Series
Smart Control Series Series Series
Preparation for domestic water Series Series Series
Domestic water tank WKT 300 (enamelled) integrated – – –
Heat exchanger area, domestic water tank m² – – –
Number of indoor units/outdoor units 1/1 1/1 1/1
Night operation (power control) Series Series Series
Service limits, heating °C -20 to +35 -20 to +35 -20 to +35
Rated heating capacity (min. / max.) kW 6.0 (0.9 - 6.0) 10.0 (2.5 - 12.5) 14.0 (3.1 - 17.7)
Energy efficiency rating for heating 4)
A++ / A++ A++ / A+ A++ / A++
Rated heating capacity / COP for A7/W35 1)
kW / - 5.46 / 4.6 9.86 / 4.4 14.02 / 4.5
Rated heating capacity / COP for A2/W35 1)
kW / - 4.61 / 3.5 6.95 / 3.6 9.32 / 3.5
Rated heating capacity / COP for A-7/W35 1)
kW / - 4.50 / 2.8 6.14 / 2.9 8.20 / 2.9
Max. supply temperature, heating water °C + 55 + 55 + 55
Service limits, cooling °C +15 to +45 +15 to +45 +15 to +45
Rated cooling capacity (min. / max.) kW 5.0 (1.1 - 8.9) 6.0 (3.3 - 11.9) 11.0 (5.5 - 14.0)
Rated cooling capacity / EER for A35/W7 1)
kW / - 2)
4.90 / 2.8 6.79 / 2.3 12.20 / 2.6
Rated cooling capacity / EER for A35/W18 1)
kW / - 2)
6.70 / 3.6 5.30 / 3.7 12.77 / 3.8
Rated cooling capacity / EER for A27/W18 1)
kW / -2)
6.80 / 3.9 9.46 / 3.6 18.20 / 4.1
Min. supply temperature, cooling water °C + 7 + 7 + 7
Refrigerant 2)
R410A R410A R410A
Basic refrigerant filling volume / CO2
equivalent kg/t 1.2 / 2.5 2.0 / 4.2 2.85 / 5.8
Refrigerant connections Inch 3/8 / 5/8 3/8 / 5/8 3/8 / 5/8
Max. refrigerant line length m 30 50 75
Max. refrigerant line height m 20 30 30
Voltage supply V/Hz 230/1~/50 230/1~/50 400/3~/50
Rated current consumption for A7/W35 kW 1.18 2.22 3.09
Rated current consumption for A7/W35 A 5.19 10.44 5.02
On-site fuse protection (outdoor unit) A slow-acting 20 20 3x16
Rated flow rate of water at ∆t 5 K m³/h 0.95 1.7 2.4
External maximum pressure loss (heating system) kPa 80 80 80
Max. operating pressure, water bar 3.0 3.0 3.0
Hydraulic connection, inlet flow/return line, flat-sealing Inch 1/4" AG 1/4" AG 1/4" AG
Pipeline diameter to be used on site, Cu pipe mm 28 28 35
Sound power level LwA (outdoor unit) rated/max. dB(A) 63.2/66.0 67.9/69.0 68.3/69.8
Sound pressure level LpA rated/max. 3)
dB(A) 38.2 / 41.0 42.9 / 44.0 42.3/45.2
Max. sound pressure level LwA (outdoor unit), night operation 3)
dB(A) 38.0 39.9 39.3
Outdoor unit, standard colour Grey-white Grey-white Grey-white
Dimensions indoor unit Height / width / depth mm 500/800/500 500/800/500 500/800/500
Dimensions outdoor unit Height / width / depth mm 640/880/310 1010/940/330 1430/940/330
Weight indoor unit / outdoor unit kg 41/47.5 43/74 45/100
Series WKF 70 WKF 120 WKF 180
Ref. no. 254010 255050 255060
Serial colour of outdoor unit: silver
Ref. no. 254020 255055 255065
1)
COP / EER according to EN 14511, 2)
GWP = 2088 3)
Distance 5m, full sphere, A7/W55 4)
Average, composite system W35/55°C including Smart Control 5)
Total heating requirement, intake flow line 35°C, monoenergetic
Accessories
Series WKF 70 WKF 120 WKF 180
REMKO Smart-Count – Factory-installed heat meter for the separate counting
of the quantity of heat of heating and hot water 259010 259010 259010
REMKO Smart-Com – Additional software for the integration of the heat
pump into a smart home system such as KNX via the Ethernet interface of
Smart Control, including the heat meter installed at the factory (Smart Count)
254090 254090 254090
REMKO Smart-BVT– Factory-installed BVT pipe assembly, 3-way switchover
valve for the integration of a second heat generator (max. 22 kW) without a
circulation pump, bivalently alternating operation. Note: No combination with
REMKO Smart-Serv possible. Only in combination with buffer tank.
254053 259015 259016
REMKO Smart-Serv – Intelligent provision, installed heating rod 9 kW for
monoenergetic operation, including emergency heating functions
Note: No combination with REMKO Smart-BVT possible.
254060 259025 259026
REMKO Smart-Cool – for active cooling. Pipe subassemblies and circulation
pump in the indoor unit with vapour density insulation. Use in case of cooling
function when the inlet temperature is below the dew point.
259085 259085 259085
For additional accessories, see page 50
18
Profit from these
advantages
■	 Low investment costs
■	Smart-Inverter
power-modulated mode.
This saves money.
■	 Low operating costs due to
high COP value
(see technical data)
■	 Heating and cooling
■	 Mounting-friendly installa-
tion All connections from the
top.
■	 Intelligent control system
Use of Smart-Control in
intelligent Smart Grid power
mains possible
■	 Technical unit handover by
REMKO Technical Service
possible
■	 Monoenergetic operation
through REMKO Smart-Serv
■	 Night operation to reduce
noise
■	 Chimney sweep function
■	 Bivalently alternating opera-
tion using Smart-BVT exter-
nally
It couldn't be simpler.
Everything complete in an indoor unit
Everything is installed in a single housing: Two highly efficient
circulation pumps, two heat exchangers, various fittings,
and the Smart-Control control system. In connection with exist-
ing tank systems, the WKF Duo is prefect for new buildings and
renovations.
Smart-HEAT PUMPS
WKF Duo Series
European uality Label
for Heat Pumps
EHPA / D-A-CH
Scope of supply
■	 REMKO Smart-Control—the
intelligent control system
■	 Indoor unit
■	 2 outdoor units with inverter
technology
■	 2 highly efficient, controlled
heating circuit pumps
■	 Dirt filter 1 1/2"
■	 2 shut-off valves 1 1/2"
and thermometer
■	 Safety group with SIV,
automatic bleeding valve
and pressure gauge
■	 Outdoor sensor/immer-
sion probe
■	 Electrically controlled
bypass mixer
ErP Ready
Energy
A++
Efficiency
Rating
19
Accessories
Series WKF 120 DUO WKF 180 DUO
REMKO Smart-Count
Factory-installed heat meter for the separate counting of the quantity of
heat of heating and hot water
259010 259010
REMKO Smart-Com
Additional software for the integration of the heat pump into a smart home
system such as KNX via the Ethernet interface of Smart Control, including
the heat meter installed at the factory (Smart Count)
254090 254090
REMKO Smart-Serv
Intelligent provision, installed heating rod 9 kW for monoenergetic opera-
tion, including emergency heating functions
Note: No combination with REMKO Smart-BVT possible.
259029 259027
REMKO Smart-Cool
for active cooling. Pipe subassemblies and circulation pump in the indoor
unit with vapour density insulation. Use in case of cooling function when
the inlet temperature is below the dew point.
259086 259086
For additional accessories, see page 50
Technical data
Area of use: heating 5)
18-25 kW 25-32 kW
Series WKF 120 DUO WKF 180 DUO
Design Duo Split Duo Split
System Air / water Air / water
Operating mode Heating / cooling Heating / cooling
Testing EHPA EHPA
Inverter technology Series Series
Smart Control Series Series
Preparation for domestic water Series Series
Domestic water tank (enamelled) integrated - -
Heat exchanger area, domestic water tank m² - -
Number of indoor units/outdoor units 1/2 1/2
Night operation (power control) Series Series
Service limits, heating °C -20 to +35 -20 to +35
Rated heating capacity (min. / max.) kW 18.0 (2.5 - 25.0) 29.0 (3.1 - 35.4)
Energy efficiency rating for heating 4)
A++ / A+ A++ / A++
Rated heating capacity / COP for A7/W35 1)
kW / - 19.72 / 4.4 28.04 / 4.5
Rated heating capacity / COP for A2/W35 1)
kW / - 13.90 / 3.6 18.64 / 3.5
Rated heating capacity / COP for A-7/W35 1)
kW / - 12.28 / 2.9 16.40 / 2.9
Max. supply temperature, heating water °C + 55 + 55
Service limits, cooling °C +15 to +45 +15 to +45
Rated cooling capacity (min. / max.) kW 13.0 (3.3 - 23.8) 24.0 (5.5 - 28.0)
Rated cooling capacity / EER for A35/W7 1)
kW / - 13.58 / 2.3 24.40 / 2.6
Rated cooling capacity / EER for A35/W18 1)
kW / - 10.60 / 3.7 25.54 / 3.8
Rated cooling capacity / EER for A27/W18 1)
kW / - 18.92 / 3.6 36.40 / 4.1
Min. supply temperature, cooling water °C + 7 + 7
Refrigerant R410A R410A
Basic refrigerant filling volume for each outdoor unit / CO2
equivalent kg/t 2.0 / 4.2 2.85 / 5.8
Refrigerant connections for each outdoor unit Inch 3/8 / 5/8 3/8 / 5/8
Max. refrigerant line length per outdoor unit m 50 75
Max. refrigerant line length per outdoor unit m 30 30
Voltage supply for each outdoor unit V/Hz 230/1~/50 400/3~/50
Rated current consumption for A7/W35 kW 2 x 2,22 2 x 3.09
Rated current consumption for A7/W35 A 2 x 10,44 2 x 5.02
On-site fuse protection (outdoor unit) A slow-acting 2 x 20 6 x 16
Rated flow rate of water at ∆t 5 K m³/h 2 x 1,7 2 x 2.4
External maximum pressure loss (heating system) kPa 80 80
Max. operating pressure, water bar 3.0 3.0
Hydraulic connection, supply/return line Inch 1½" AG 1½" AG
Pipeline diameter to be used on site, Cu pipe mm 42 42
Sound power level LwA (per outdoor unit) rated/max. dB(A) 67.9/69.0 68.3/69.8
Sound power level LpA (per outdoor unit) rated/max. 3)
dB(A) 42.2/44.0 42.4/45.2
Max. sound pressure level LwA (per outdoor unit), night operation 3)
dB(A) 38.9 39.3
Outdoor unit, standard colour Grey-white Grey-white
Dimensions indoor unit Height / width / depth mm 1000/800/500 1000/800/500
Dimensions outdoor unit Height / width / depth mm 1010/940/330 1430/940/330
Weight indoor unit / outdoor unit kg 78 / 2 x 74 82 / 2 x 100
Series WKF 120 DUO WKF 180 DUO
Ref. no. 255063 255070
Serial colour of outdoor unit: silver
Ref. no. 255064 255075
1)
COP / EER according to EN 14511, 2)
GWP = 2088 3)
Distance 5m, full sphere, A7/W55 4)
Average, composite system W35/55°C including Smart Control 5)
Total heating requirement, intake flow line 35°C, monoenergetic
20
REMKO KWK-4R
The wall and ceiling chests are characterised by a discreet design
In combination with the REMKO heat pump, the wall and ceiling
chests are excellently suited for the renovation of heating systems,
as well as for new construction. Despite low inlet temperatures, the
units quickly generate heat. In this way, the system can react to
fluctuations in the outdoor temperatures quickly and dynamically.
The REMKO wall or ceiling chests work efficiently and thus require
only low inlet temperatures during heating operations – the ideal
supplement to low-temperature systems, such as heat pumps. They
are excellently suited as an efficient replacement for heaters in old
buildings or for conversions in order to lower high inlet tempera-
tures to an economical value. In summer, the units can also be used
for cooling. In this way, they supply pleasant, draft-free, and cool
air to the room. They can optionally be used for vertical installa-
tion into the wall or horizontal installation below the ceiling and are
excellently suited for installation into private living areas.
An extremely low-noise three-stage tangential fan provides impec-
cable air distribution and maximises vent output. The copper-alu-
minium register is designed for medium temperatures of up to 80°C.
Due to the large heat exchanger, an effective heating operation is
guaranteed at low inlet temperatures.
Cooling capacity
KWK 100-4R KWK 150-4R KWK 250-4R KWK 400-4R
Intake
°C
Qges kW Qges kW Qges kW Qges kW
Fan setting
1 2 3 1 2 3 1 2 3 1 2 3
7 0.83 0.93 1.18 1.22 1.27 1.59 1.57 1.69 2.21 1.95 2.05 2.73
10 0.53 0.62 0.78 0.78 0.81 1.04 1.10 1.18 1.54 1.22 1.31 1.86
14 0.37 0.42 0.54 0.54 0.57 0.72 0.69 0.75 1.03 0.86 0.95 1.27
18 0.26 0.29 0.38 0.37 0.40 0.45 0.42 0.45 0.54 0.51 0.57 0.68
Heating capacities
KWK 100-4R KWK 150-4R KWK 250-4R KWK 400-4R
Intake
°C
Qges kW Qges kW Qges kW Qges kW
Fan setting
1 2 3 1 2 3 1 2 3 1 2 3
35 0.48 0.53 0.66 0.73 0.76 0.97 0.97 1.06 1.40 1.18 1.25 1.68
40 0.69 0.78 1.02 1.05 1.10 1.40 1.37 1.48 1.97 1.67 1.76 2.37
45 0.91 1.03 1.35 1.36 1.42 1.80 1.75 1.90 2.53 2.14 2.25 3.05
50 1.13 1.27 1.66 1.66 1.74 2.21 2.13 2.31 3.09 2.60 2.74 3.71
Regulation
REMKO KWK wall and ceiling chests can be regulated by a room
temperature controller. The controller is functional and easy to oper-
ate. Two mounting variants are available: for installation into the
chest or for surface mounting onto the wall. The regulation of the
room temperature controller can be implemented by switching the
fan on and off.
WALL AND CEILING CHESTS
■	 The ideal solution for opti-
cally discreet air conditioning
■	 Low-noise appliance opera-
tion
■	 Service-friendly unit struc-
ture
KWK-4R series
for heating and cooling
Precision room tempera-
ture control for surface
installation
■	 For horizontal and vertical
installations
■	 Extensive accessories avail-
able
Accessories (see page 54)
21
Technical data
Wall and ceiling chests KWK 100-4R KWK 150-4R KWK 250-4R KWK 400-4R
Heating capacity 1) 3)
/ 6)
kW 1.35/0.66 1.80/0.97 2.53/1.40 3.05/1.68
Cooling capacity 1) 2)
kW 1.18 1.59 2.21 2.73
Air flow rate per speed setting m³/h 128/147/200 184/194/254 232/254/353 283/300/423
Sound pressure level per speed setting 5)
dB(A) 25.5/28.5/34.5 25.5/32.5/36.5 26.5/27.5/36.5 25.5/26.5/34.5
Voltage supply V/Hz 230/1~/50
Electr. rated power consumption kW 0.04 0.03 0.05 0.05
Electr. nominal current consumption A 0.11 0.07 0.14 0.20
Operating medium Water
Max. operating pressure kPa 600 600 600 600
Medium connectors - cooling register Inch 1/2 1/2 1/2 1/2
Rated flow volume, medium C/H6)
m³/h 0.20/0.15 0.27/0.17 0.38/0.24 0.47/0.29
Rated pressure drop, indoor C/H kPa 1.2/0.6 3.3/1.6 6.7/4.0 5.5/2.9
Medium volume L 0.6 0.9 1.3 1.5
Dimensions - height mm 480 480 480 480
Dimensions - width mm 660 810 960 1100
Dimensions - depth mm 220 220 220 220
Weight kg 14.0 17.0 20.0 23.0
Serial colour white white white white
Wall and ceiling chests KWK 100-4R KWK 150-4R KWK 250-4R KWK 400-4R
Ref. no. 1663100 1663150 1663250 1663400
For additional accessories, see page 54
1)
Rated flow rate, medium; max. air flow rate
2)
Room temperature TK 27°C, FK 19°C; medium inlet 7°C, medium outlet 12°C
3)
Room temperature TK 20 °C, FK 14 °C; medium inlet 45 °C, medium outlet 40 °C
5)
Measured in a 100m3
room with a reverberation period of 0.3 seconds, distance of 1.5 m
6)
Room temperature TK 20 °C, FK 14 °C; medium inlet 35 °C, medium outlet 30 °C
Dimensions
A B C
KWK 100-4R 660 480 220
KWK 150-4R 810 480 220
KWK 250-4R 960 480 220
KWK 400-4R 1100 480 220
B
A C
KWK 100-400-4R
Dimensions
22
Package consisting of:
HEAT PUMP PACKAGES
Type: Stuttgart
Heat pump package – Type Stuttgart
for WKF 70-180 compact unit series
If the heat pump is intended to serve as a sole heat generator,
this heat pump package is the ideal solution. In connection with
underfloor heating, this unit is perfectly suited for new buildings. In
addition to the heating function, a cooling function can be provided
when necessary. In this package, the drinking water preparation
takes place in a 300-litre drinking water tank integrated into the in-
door module. Through the compact design, installation expenses are
extremely low. The highly efficiently controlled heating circuit pump
in the indoor unit can supply the heating circuits directly with water.
Information about government
subsidies can be found under:
www.bafa.de
www.kfw.de
www.foerderdata.de
Condensate drip tray for outdoor unit with oil separator
Package consisting of:
■	 Indoor unit with inte-
grated 300-litre WKT 300
domestic water tank
(BEVB 1.19 kWh/day)
■ 	 Outdoor unit
For scope of supply, see p. 14
■ 	 Condensate drip tray,
including oil separator for
outdoor unit
Cooling
HeatingHot water
Surface cooling /
surface heating
Night operation
ErP Ready
Energy
A++
Efficiency
Rating
22
23
Hydraulic system diagram of Stuttgart (example of monoenergetic operation)
Indoor unit
Outdoorprobe
Outdoor unit
Chilled
water
ZWP
Hot water
Cooling
circuit
Heating
circuit
Mixed
Technical data
Area of use: heating 1)
4-7 kW 8-11 kW 12-18 kW
Heat pump package, Type Stuttgart WKF 70 compact WKF 120 compact WKF 180 compact
Rated heating capacity (min. / max.) kW 6.0 (0.9 - 6.0) 10.0 (2.5 - 12.5) 14.0 (3.1 - 17.7)
Rated cooling capacity (min. / max.) kW 5.0 (1.1 - 8.9) 6.0 (3.3 - 11.9) 11.0 (5.5 - 14.0)
Energy efficiency rating of HZ/WW/Smart Control composite system A++/A A+/A A++/A
External maximum pressure loss kPa 80 80 80
Series WKF 70 compact WKF 120 compact WKF 180 compact
Ref. no. 254100 256015 256020
1)
Total heating requirement, intake flow line 35°C, monoenergetic
Accessories
Series WKF 70 compact WKF 120 compact WKF 180 compact
REMKO Smart-Count
Factory-installed heat meter for the separate counting of the quantity of
heat of heating and hot water
259010 259010 259010
REMKO Smart-Com
Additional software for the integration of the heat pump into a smart
home system such as KNX via the Ethernet interface of Smart Control,
including the heat meter installed at the factory (Smart Count)
254090 254090 254090
REMKO Smart-Serv
Intelligent provision, installed heating rod 9 kW for monoenergetic
operation, including emergency heating functions
254059 259022 259023
REMKO Smart-Cool
for active cooling. Pipe subassemblies and circulation pump in the indoor
unit with vapour density insulation. Use in case of cooling function
when the inlet temperature is below the dew point.
259085 259085 259085
For additional accessories, see page 50
24
Package consisting of:
HEAT PUMP PACKAGES
Type: Mannheim
Heat pump package – Type Mannheim
for WKF 70-180 compact appliance series
This heat pump package is designed for users who would like to
operate the heat pump in combination with a conventional heat
generator (bivalently alternating). The additional KPS 300 buffer
tank is used for the hydraulic decoupling of large volume flow
rates. A cooling function for the summer can also be activated, if
necessary. In this package, the domestic water preparation takes
place in the 300-litre domestic water tank integrated into the
indoor unit. Through the compact design, installation expenses are
extremely low.
The separate pump assemblies HGU/HGM (can be ordered sepa-
rately) for the heating circuits are equipped with a high-efficiency
pump (0-10 V) regulated in a needs-based manner.
Information about government subsidies can be found under:
www.bafa.de
www.kfw.de
www.foerderdata.de
Package consisting of:
■	 Indoor unit with inte-
grated 300-litre WKT
300 domestic water tank
(BEVB 1.19 kWh/day)
■ 	 Outdoor unit
For scope of supply, see p. 14
■ 	 Condensate drip tray,
including oil separator
for outdoor unit
■ 	 Buffer tank for hot water
KWS 300 (300 litres)
■ 	 Immersion probe
Buffer tank for cooling and hot
water KPS 300 (300 l)
Condensate drip tray for outdoor unit with oil separator
HeatingHot water
Cooling BivalentSurface cooling/
surface heating
Night operation
ErP Ready
Energy
A++
Efficiency
Rating
24
25
S 08
Hydraulic system of Mannheim (example for monoenergetic or alternative bivalent operation)
Indoor unit
Outdoorprobe
Outdoor unit
Chilled
water
HGU HGMZWP HGM
KPS 300
Hot water
Heating
circuit
Non-mixed-
Heating
circuit
Mixed
Heating circuit
Mixed
Technical data
Area of use: heating 1)
4-7 kW 8-11 kW 12-18 kW
Heat pump package, Type Mannheim WKF 70 compact WKF 120 compact WKF 180 compact
Rated heating capacity (min. / max.) kW 6.0 (0.9-6.0) 10.0 (2.5 - 12.5) 14.0 (3.1 - 17.7)
Rated cooling capacity (min. / max.) kW 5.0 (1.1 - 8.9) 6.0 (3.3 - 11.9) 11.0 (5.5 - 14.0)
Energy efficiency rating of HZ/WW/Smart Control composite system A++/A A+/A A++/A
External maximum pressure loss kPa 80 80 80
Series WKF 70 compact WKF 120 compact WKF 180 compact
Ref. no. 254110 256030 256035
1)
Total heating requirement, intake flow line 35°C, monoenergetic
Accessories
Series WKF 70 compact WKF 120 compact WKF 180 compact
REMKO Smart-Count – Factory-installed heat meter for the separate
counting of the quantity of heat of heating and hot water 259010 259010 259010
REMKO Smart-Com – Additional software for the integration of the
heat pump into a smart home system such as KNX via the Ethernet
interface of Smart Control, including the heat meter installed at the
factory (Smart Count)
254090 254090 254090
REMKO Smart-Serv – Intelligent provision, installed heating rod 9 kW
for monoenergetic operation, including emergency heating functions 259059 259022 259023
REMKO Smart-BVT– Factory-installed
BVT pipe assembly, 3-way switchover valve for the integration of a sec-
ond heat generator (max. 22 kW) without a circulation pump, bivalently
alternating operation. Note: No combination with REMKO Smart-Serv
possible. Only in combination with buffer tank.
254050 259012 259013
REMKO Smart-Cool – For active cooling. Pipe subassemblies and circula-
tion pump in the indoor unit with vapour density insulation. Use in case
of cooling function when the inlet temperature is below the dew point.
259085 259085 259085
Heating circuit pump set HGU
Speed-controlled heating circuit pump group (0-10 V)/unmixed 259035 259035 259035
Heating circuit pump set HGM
Speed-controlled heating circuit pump group (0-10 V)/mixed 259036 259036 259036
For additional accessories, see page 50
Cooling
circuit
Boiler/wall-mounted heating system
(max. 22 kW)
26
Package consisting of:
Buffer tank for cooling and
heating water KPS 300 (300 l)
HEAT PUMP PACKAGES
Type: Cologne
Heat pump package type Cologne
for WKF 70-180 appliance series
This heat pump package is designed for users who want heating
first and foremost. The additional KPS 300 buffer tank is used for
the hydraulic decoupling of large volume flow rates. A cooling func-
tion for the summer can also be activated, if necessary. Domestic
water preparation takes place separately. With this heat pump pack-
age, both monoenergetic and bivalently alternating systems can be
accommodated. A second heating appliance (oil/gas boiler without
pump) can be connected directly to the indoor module.
The separate pump assemblies HGU/HGM (can be ordered separately)
for the heating circuits are equipped with a high-efficiency pump
(0-10 V) regulated in a needs-based manner.
Information about government subsidies can be found under:
www.bafa.de
www.kfw.de
www.foerderdata.de
Package consisting of:
■ 	 Indoor unit
■ 	 Outdoor unit
For scope of supply, see p. 16
■ 	 Condensate drip tray,
including oil separator for
outdoor unit
■ 	 Buffer tank for cooling
and heating water KPS
300 (300 litres)
Condensate drip tray for outdoor unit with oil separator
Cooling BivalentHeating Surface cooling/
surface heating
Night operation
ErP Ready
Energy
A++
Efficiency
Rating
26
27
Technical data
Area of use: heating 1)
4-7 kW 8-11 kW 12-18 kW
Heat pump package, Type Cologne WKF 70 WKF 120 WKF 180
Rated heating capacity (min. / max.) kW 6.0 (0.9 - 6.0) 10.0 (2.5 - 12.5) 14.0 (3.1 - 17.7)
Rated cooling capacity (min. / max.) kW 5.0 (1.1 - 8.9) 6.0 (3.3 - 11.9) 11.0 (5.5 - 14.0)
Energy efficiency rating of HZ/WW/Smart Control composite system A+/- A+/- A++/-
External maximum pressure loss kPa 80 80 80
Series WKF 70 WKF 120 WKF 180
with KPS 300
Ref. no. 254120 256045 256050
1)
Total heating requirement, intake flow line 35°C, monoenergetic
Accessories
Series WKF 70 WKF 120 WKF 180
REMKO Smart-Count
Factory-installed heat meter 259010 259010 259010
REMKO Smart-Com – Additional software for the integration of the
heat pump into a smart home system such as KNX via the Ethernet
interface of Smart Control, including the heat meter installed at the
factory (Smart Count)
254090 254090 254090
REMKO Smart-BVT– Factory-installed
BVT pipe assembly, 3-way switchover valve for the integration of a
second heat generator (max. 22 kW) without a circulation pump,
bivalently alternating operation. Note: No combination with REMKO
Smart-Serv possible. Only in combination with buffer tank.
254053 259015 259016
REMKO Smart-Serv – Intelligent provision, installed heating rod 9 kW
for monoenergetic operation, including emergency heating functions
Note: No combination with REMKO Smart-BVT possible.
254060 259025 259026
REMKO Smart-Cool – For active cooling. Pipe subassemblies and
circulation pump in the indoor unit with vapour density insulation.
Use in case of cooling function when the inlet temperature is below
the dew point.
259085 259085 259085
Heating circuit pump set HGU
Speed-controlled heating circuit pump group (0-10 V)/unmixed 259035 259035 259035
Heating circuit pump set HGM
Speed-controlled heating circuit pump group (0-10 V)/mixed 259036 259036 259036
For additional accessories, see page 50
S 08
Indoor unit
Outdoor unit
Cooling
circuit
Hydraulic system diagram of Cologne (example for monoenergetic or alternative bivalent operation)
Outdoorprobe
Boiler/wall-mounted heating system
(max. 22 kW)
Heating circuit
Non-mixed
Heating
circuit
Mixed
Heating
circuit
Mixed
HGU HGM HGM
KPS 300
28
HEAT PUMP PACKAGES
Type: Dortmund
Heat pump package type Dortmund
for WKF 70-180 appliance series
This heat pump package is for users who, in addition to the
heating function, also want drinking water treatment from their
heat pump system. A cooling function for the summer can also
be activated, if necessary. In this package, the domestic water
preparation takes place in an enamelled 300-litre domestic water
Package consisting of:
3-way changeover valve, 5/4"
Tank for drinking water heating,
enamelled EWS 300 (300 litres)
tank. The high-efficiency pump in the indoor module can supply the
heating circuits directly with water.
Information about government subsidies can be found under:
www.bafa.de
www.kfw.de
www.foerderdata.de
Package comprising:
■ 	 Indoor unit
■ 	 Outdoor unit
For scope of supply, see p. 16
■ 	 Buffer tank for domestic
hot water,
enamelled EWS 300 E
(300 litres)
■ 	 3-way changeover valve
■ 	 Condensate drip tray,
including oil separator for
outdoor unit
Condensate drip tray for out-
door unit with oil separator
HeatingHot water Cooling Surface cooling/
surface heating
Night operation
ErP Ready
Energy
A++
Efficiency
Rating
28
29
S 08
Hydraulic system diagram of Dortmund (example for monoenergetic operation)
Technical data
Area of use: heating 1)
4-7 kW 8-11 kW 12-18 kW
Heat pump package, Type Dortmund WKF 70 WKF 120 WKF 180
Rated heating capacity (min. / max.) kW 6.0 (0.9 - 6.0) 10.0 (2.5 - 12.5) 14.0 (3.1 - 17.7)
Rated cooling capacity (min. / max.) kW 5.0 (1.1 - 8.9) 6.0 (3.3 - 11.9) 11.0 (5.5 - 14.0)
Energy efficiency rating of HZ/WW/Smart Control composite system A++/A A+/A A++/A
External maximum pressure loss kPa 80 80 80
Series WKF 70 WKF 120 WKF 180
with EWS 300 E
Ref. no. 254130 256060 256065
1)
Total heating requirement, intake flow line 35°C, monoenergetic
Accessories
Series WKF 70 WKF 120 WKF 180
REMKO Smart-Count
Factory-installed heat meter for the separate counting of the quantity
of heat of heating and hot water
259010 259010 259010
REMKO Smart-Com
Additional software for the integration of the heat pump into a smart
home system such as KNX via the Ethernet interface of Smart Control,
including the heat meter installed at the factory (Smart Count)
254090 254090 254090
REMKO SmartServ
Intelligent provision for failures, installed heating rod 9 kW for mono-
energetic operation, including emergency heating function
254060 259025 259026
REMKO Smart-Cool
for active cooling. Pipe subassemblies and circulation pump in the in-
door unit with vapour density insulation. Use in case of cooling function
when the inlet temperature is below the dew point.
259085 259085 259085
For additional accessories, see page 50
Indoor unit
Outdoor unit
Cooling
circuit
Outdoorprobe
Heating
circuit
Mixed Hot water
ZWP
Chilled water
EWS 300 E
30
Heat pump package type Düsseldorf
for WKF 70-180 appliance series
This heat pump package is the ideal solution for users who, in addi-
tion to the heating function, also want domestic water preparation
from their heat pump system. A cooling function for the summer
can also be activated, if necessary. The domestic water preparation
takes place very efficiently with a 500 litre buffer tank and electroni-
cally regulated fresh water station using the hygienic flow method.
Package consisting of:
Buffer tank for domestic water
HPS 500 (500 litres)
Fresh water station EFS 25, com-
plete with pump and flow switch
HEAT PUMP PACKAGES
Type: Düsseldorf
Condensate drip tray for out-
door unit with oil separator
The high-efficiency pump in the indoor unit can supply the heating
circuits directly with water.
Information about government subsidies can be found under:
www.bafa.de / www.kfw.de / www.foerderdata.de
Package comprising:
■ 	 Indoor unit
■ 	 Outdoor unit
For scope of supply, see p. 16
■ 	 Buffer tank for drinking
water HPS 500
(500 litres)
■ 	 Electrically regulated fresh
water station EFS 25
(for connection sets, see
p.52)
■ 	 3-way changeover valve
■ 	 Condensate drip tray,
including oil separator for
outdoor unit
3-way changeover valve, 5/4"
For connection sets, see p.52
HeatingHot water Cooling Surface cooling/
surface heating
Night operation
ErP Ready
Energy
A++
Efficiency
Rating
30
31
S 08
Indoor unit
Outdoor unit
Cooling
circuit
Hydraulic system of Düssedorf (example for monoenergetic operation)
Outdoorprobe
Heating
circuit
Mixed Hot water Chilled water
EFS 25
ZWP
HPS 500
Technical data
Area of use: heating 1)
4-7 kW 8-11 kW 12-18 kW
Heat pump package, Type Düsseldorf WKF 70 WKF 120 WKF 180
Rated heating capacity (min. / max.) kW 6.0 (0.9 - 6.0) 10.0 (2.5 - 12.5) 14.0 (3.1 - 17.7)
Rated cooling capacity (min. / max.) kW 5.0 (1.1 - 8.9) 6.0 (3.3 - 11.9) 11.0 (5.5 - 14.0)
Energy efficiency rating of HZ/WW/Smart Control composite system A++/A A+/A A++/A
External maximum pressure loss kPa 80 80 80
Series WKF 70 WKF 120 WKF 180
Ref. no. 254140 256075 256080
1)
Total heating requirement, intake flow line 35°C, monoenergetic
Accessories
Series WKF 70 WKF 120 WKF 180
REMKO Smart-Count
Factory-installed heat meter for the separate counting of the quantity of
heat of heating and hot water
259010 259010 259010
REMKO Smart-Com
Additional software for the integration of the heat pump into a smart
home system such as KNX via the Ethernet interface of Smart Control,
including the heat meter installed at the factory (Smart Count)
254090 254090 254090
REMKO Smart-Serv
Intelligent provision, installed heating rod 9 kW for monoenergetic
operation, including emergency heating functions
254060 259025 259026
REMKO Smart-Cool
for active cooling. Pipe subassemblies and circulation pump in the in-
door unit with vapour density insulation. Use in case of cooling function
when the inlet temperature is below the dew point.
259085 259085 259085
For additional accessories, see page 50
32
Heat pump package type Frankfurt
for WKF 70-180 appliance series
The energy-saving package is prepared for the integration of solar
thermal systems or combustible solid fuel burner for heating and
domestic water support. With the fin-tube heat exchanger (special
accessory) RWT31, collector surfaces from approx. 8 to 15 m² can
be connected. The domestic water preparation takes place with a
800 litre or 1000 litre buffer tank and electronically regulated fresh
water station using the hygienic flow method.
Package consisting of:
Multifunction buffer tank MPS
800 (800 litres) or MPS 1000
(1000 litres)
Fresh water station EFS 25, com-
plete with pump and flow switch
2 x 3-way changeover valve, 5/4"
HEAT PUMP PACKAGES
Type: Frankfurt
Condensate drip tray for out-
door unit with oil separator
With this heat pump package, both bivalent and single energy
source systems can be accommodated. The separate pump assem-
blies HGM/HGU (can be ordered separately) for the heating circuits
are equipped with a high-efficiency pump (0-10 V) regulated in a
needs-based manner.
Package comprising:
■ 	 Indoor unit
■ 	 Outdoor unit
For scope of supply, see p. 16
■ 	 Multifunctional buffer
tank MPS 800 (800 litres)
or MPS 1000 (1000 litres)
■ 	 Electrically regulated fresh
water station EFS 25
(for connection sets, see
p. 52)
■ 	 2 x 3-way switchover
valve
■ 	 Immersion probe and
collector sensor
■ 	 Condensate drip tray,
including oil separator for
outdoor unit
For connection sets, see p.52
Hot water BivalentPanel heatingHeatingNight operation
ErP Ready
Energy
A++
Efficiency
Rating
Immersion probe and collector probe
32
33
Technical data
Area of use: heating 1)
4-7 kW 8-11 kW 12-18 kW
Heat pump package, Type Frankfurt WKF 70 WKF 120 WKF 180
Rated heating capacity (min. / max.) kW 6.0 (0.9 - 6.0) 10.0 (2.5 - 12.5) 14.0 (3.1 - 17.7)
Rated cooling capacity (min. / max.) kW 5.0 (1.1 - 8.9) 6.0 (3.3 - 11.9) 11.0 (5.5 - 14.0)
Energy efficiency rating of HZ/WW/Smart Control composite system A++/A A+/A A++/A
External maximum pressure loss kPa 80 80 80
Series WKF 70 WKF 120 WKF 180
with MPS 800
Ref. no. 254150 256090 256095
with MPS 1000
Ref. no. 254160 256091 256096
1)
Total heating requirement, intake flow line 35°C, monoenergetic
Accessories
Series WKF 70 WKF 120 WKF 180
REMKO Smart-Count
Factory-installed heat meter for the separate counting of the quantity of
heat of heating and hot water
259010 259010 259010
REMKO Smart-Com – Additional software for the integration of the
heat pump into a smart home system such as KNX via the Ethernet
interface of Smart Control, including the heat meter installed at the
factory (Smart Count)
254090 254090 254090
REMKO Smart-BVT – Factory-installed
BVT pipe assembly, 3-way switchover valve for the integration of a
second heat generator (max. 22 kW), without a circulation pump,
bivalently alternating operation
Note: No combination with REMKO Smart-Serv possible.
Only in combination with buffer tank.
254053 259015 259016
REMKO Smart-Serv – Intelligent provision, installed heating rod 9 kW
for monoenergetic operation, including emergency heating functions
Note: No combination with REMKO Smart-BVT possible.
254060 259025 259026
Heating circuit pump set HGM
Speed-controlled heating circuit pump group (0-10 V)/mixed 259036 259036 259036
For additional accessories, see page 50
M
Indoor unit
Outdoor unit
Hydraulic system of Frankfurt (example for monoenergetic or bivalently alternating operation)
Outdoorprobe
Heating
circuit
Non-mixed
Heating
circuit
Mixed
Heating
circuit
MixedHot water
Chilled
water
EFS 25
RES
ZWP
MPS 800/1000
Boiler/wall-mounted heating system
(max. 22 kW)
HGU HGM HGM
34
Package consisting of:
Buffer tank for cooling and
heating water KPS 300 (300 l)
HEAT PUMP PACKAGES
Type Cologne Duo
Heat pump package - Type Cologne Duo
for WKF 120-180 Duo unit series
This heat pump package is designed for users who want heating
first and foremost. The additional KPS 300 buffer tank is used for
the hydraulic decoupling of large volume flow rates. A cooling func-
tion for the summer can also be activated, if necessary. Domestic
water preparation takes place separately. With this heat pump pack-
age, both monoenergetic and bivalently alternating systems can be
accommodated. The separate pump assemblies HGU/HGM (can
be ordered separately) for the heating circuits are equipped with a
high-efficiency pump (0-10 V) regulated in a needs-based manner.
Information about government subsidies can be found under:
www.bafa.de / www.kfw.de / www.foerderdata.de
Package consisting of:
■	 Indoor unit
■ 	 2 outdoor units
■ 	 2 condensate drip trays,
including oil separator
for outdoor unit
■ 	 Buffer tank for cooling
and heating water KPS
300 (300 litres)
Bivalent
2 condensate drip trays for outdoor unit with oil separator
Surface cooling/
surface heating
Night operation
ErP Ready
Energy
A++
Efficiency
Rating
Heating Cooling
35
Technical data
Area of use: heating 1)
18-25 kW 25-32 kW
Heat pump package – Type Cologne Duo WKF 120 DUO WKF 180 DUO
Rated heating capacity (min. / max.) kW 18.0 (2.5 - 25.0) 29.0 (3.1 - 35.4)
Rated cooling capacity (min. / max.) kW 13.0 (3.3 - 23.8) 24.0 (11.0 - 28.0)
Energy efficiency rating of HZ/Smart Control composite system A+/A A++/A
Series WKF 120 DUO WKF 180 DUO
Ref. no. 256100 256101
1)
Total heating requirement, intake flow line 35°C, monoenergetic
Accessories
Series WKF 120 DUO WKF 180 DUO
REMKO Smart-Count
Factory-installed heat meter for the separate counting of the quantity
of heat of heating and hot water
259010 259010
REMKO Smart-Com
Additional software for the integration of the heat pump into a smart
home system such as KNX via the Ethernet interface of Smart Con-
trol, including the heat meter installed at the factory (Smart Count)
254090 254090
REMKO Smart-Serv
Intelligent provision, installed heating rod 9 kW for monoenergetic
operation, including emergency heating functions
259029 259027
REMKO Smart-Cool
for active cooling. Pipe subassemblies and circulation pump in the
indoor unit with vapour density insulation. Use in case of cooling
function when the inlet temperature is below the dew point.
259086 259086
Heating circuit pump set HGU
Speed-controlled heating circuit pump group (0-10 V)/unmixed 259035 259035
Heating circuit pump set HGM
Speed-controlled heating circuit pump group (0-10 V)/mixed 259036 259036
S 08
optional
Indoor unit
Outdoor unit
Hydraulic diagram for Cologne Duo (example for monoenergetic or alternative bivalent operation)
Outdoorprobe
Heating
circuit
Non-mixed
Heating
circuit
Mixed
Heating
circuit
Mixed
Heating
circuit
Mixed
Heating
circuit
MixedBoiler/wall-mounted unit
Cooling
circuit
KPS 300
HPU HGU HGM HGM HGM HGM
36
Package consisting of:
HEAT PUMP PACKAGES
Type Mannheim Duo
Heat pump package – Type Mannheim Duo
for WKF 120-180 Duo unit series
This heat pump package is designed for users who would like to
operate the heat pump in combination with a conventional heating
appliance (bivalently alternating). The additional KWS 300 com-
bination buffer tank is used for the hydraulic decoupling of large
volume flow rates. A cooling function for the summer can also be
activated, if necessary.
In this package, the drinking water preparation takes place in an
enamelled 300-litre drinking water tank. Through the compact
design, installation expenses are extremely low.
The separate pump assemblies HGU/HGM (can be ordered sepa-
rately) for the heating circuits are equipped with a high-efficiency
pump (0-10 V) regulated in a needs-based manner.
Information about government subsidies can be found under:
www.bafa.de / www.kfw.de / www.foerderdata.de
Package consisting of:
■ 	 Indoor unit
■ 	 Outdoor unit
For scope of supply, see p. 18
■ 	 2x condensate drip trays,
including oil separator
for outdoor unit
■ 	 Combination buffer tank
KWS 300 (see p. 49)
■ 	 3-way switchover valve
Combination buffer tank for
cooling, heating and hot water
KWS 300
HeatingHot water Cooling BivalentSurface cooling/
surface heating
Night operation
ErP Ready
Energy
A++
Efficiency
Rating
2 condensate drip trays for out-
door unit with oil separator
3-way changeover valve, 6/4"
36
37
Hydraulic system diagram of Mannheim (example for monoenergetic or alternative bivalent operation)
Indoor unit
Outdoorprobe
Outdoor unit
Chilled
water
HGU HGMZWPHPU HGM HGM HGM
KWS 300
Hot water
Heating
circuit
Non-mixed
Heating
circuit
Mixed
Heating
circuit
Mixed
Heating
circuit
Mixed
Heating
circuit
Mixed
Cooling
circuit
Boiler/wall-mounted
heating system
(max. 22 kW)
Technical data
Area of use: heating 1)
18-25 kW 25-32 kW
Heat pump package – Type Mannheim Duo WKF 120 DUO WKF 180 DUO
Rated heating capacity (min. / max.) kW 18.0 (2.5 - 25.0) 29.0 (3.1 - 35.4)
Rated cooling capacity (min. / max.) kW 13.0 (3.3 - 23.8) 24.0 (11.0 - 28.0)
Energy efficiency rating of HZ/Smart Control composite system A+/A A++/A
Series WKF 120 DUO WKF 180 DUO
Ref. no. 256102 256103
1)
Total heating requirement, intake flow line 35°C, monoenergetic
Accessories
Series WKF 120 DUO WKF 180 DUO
REMKO Smart-Count
Factory-installed heat meter for the separate counting of the quantity
of heat of heating and hot water
259010 259010
REMKO Smart-Com
Additional software for the integration of the heat pump into a smart
home system such as KNX via the Ethernet interface of Smart Con-
trol, including the heat meter installed at the factory (Smart Count)
254090 254090
REMKO Smart-Serv
Intelligent provision, installed heating rod 9 kW for monoenergetic
operation, including emergency heating functions
259029 259027
REMKO Smart-Cool
for active cooling. Pipe subassemblies and circulation pump in the
indoor unit with vapour density insulation. Use in case of cooling
function when the inlet temperature is below the dew point.
259086 259086
Heating circuit pump set HGU
Speed-controlled heating circuit pump group (0-10 V)/unmixed 259035 259035
Heating circuit pump set HGM
Speed-controlled heating circuit pump group (0-10 V)/mixed 259036 259036
38
Heat pump package – Type Munich Duo
for WKF 120-180 Duo unit series
This heat pump package is the ideal solution for users with a high
heating capacity and high hot-water requirement who, in addition
to the heating function, also want domestic water preparation from
their heat pump system. A cooling function for the summer can also
be activated, if necessary. The domestic water preparation takes
place very efficiently with a 500, 800, or 1000 litre buffer tank and
electronically controlled fresh water station using the hygienic flow
method. With this heat pump package, both alternatively bivalent
Package consisting of:
Buffer tank for fresh
water station
Fresh water station
EFS 25/ EFS 35
Type Munich Duo
2 condensate drip trays for out-
door unit with oil separator
and monoenergetically operated systems can be accommodated.
The buffer tank is used as a hydraulic switch in case of large pres-
sure losses in the heating circuit.
Information about government subsidies can be found under: www.
bafa.de / www.kfw.de / www.foerderdata.de
Package comprising:
■	 Indoor unit
■ 	 2 outdoor units
■ 	 Buffer tank for cooling and
heating water KPS 300 (300
litres)
■ 	 Buffer tank for domestic water
HPS 500, MPS 800, or MPS
1000
■ 	 Electrically regulated fresh
water station EFS 25/EFS 35
■ 	 3-way changeover valve
■ 	 2 condensate drip trays,
including oil separator for
outdoor unit
3-way changeover valve, 6/4"
Heating Active cooling Surface cooling/
surface heating
HEAT PUMP PACKAGES
Buffer tank for cooling
and hot water
Night operation
ErP Ready
Energy
A++
Efficiency
Rating
Hot water
39
Technical data
Area of use: heating 1)
18-25 kW 25-32 kW
Heat pump package – Type Munich Duo WKF 120 DUO WKF 180 DUO
Rated heating capacity (min. / max.) kW 18.0 (2.5 - 25.0) 29.0 (3.1 - 35.4)
Rated cooling capacity (min. / max.) kW 13.0 (3.3 - 23.8) 24.0 (11.0 - 28.0)
Energy efficiency rating of HZ/WW/Smart Control composite system A+/A A++/A
Series WKF 120 DUO WKF 180 DUO
with HPS 500 and EFS 25
Ref. no. 256105 256110
with MPS 800 and EFS 35
Ref. no. 256106 256111
with MPS 1000 and EFS 35
Ref. no. 256107 256112
1)
Total heating requirement, intake flow line 35°C, monoenergetic
Accessories
Series WKF 120 DUO WKF 180 DUO
REMKO Smart-Count – Factory-installed heat meter for the separate
counting of the quantity of heat of heating and hot water 259010 259010
REMKO Smart-Com
Additional software for the integration of the heat pump into a smart
home system such as KNX via the Ethernet interface of Smart Control,
including the heat meter installed at the factory (Smart Count)
254090 254090
REMKO Smart-Serv
Intelligent provision, installed heating rod 9 kW for monoenergetic
operation, including emergency heating functions
259029 259027
REMKO Smart-Cool
for active cooling. Pipe subassemblies and circulation pump in the indoor
unit with vapour density insulation. Use in case of cooling function when
the inlet temperature is below the dew point.
259086 259086
Heating circuit pump set HGU
Speed-controlled heating circuit pump group (0-10 V)/unmixed 259035 259035
Heating circuit pump set HGM
Speed-controlled heating circuit pump group (0-10 V)/mixed 259036 259036
Indoor unit
Outdoor unit
Hydraulic system of Munich Duo (example for monoenergetic or alternative bivalent operation)
Outdoorprobe Heating
circuit
Non-mixed
Heating
circuit
Mixed
Heating
circuit
Mixed
Heating
circuit
Mixed
Heating
circuit
Mixed
EFS 25
RES
ZWP
HPS500, MPS800/1000
Boiler/wall-mounted unit
Cooling
circuit
HGU HGM HGM HGM HGM
Hot
waterCold water
KPS 300
40
Heat pump package – Type Frankfurt Duo / Frankfurt Duo Solar
for WKF 120-180 Duo unit series
The energy-saving package is prepared for the integration of solar
thermal plants or combustible solid fuel burner for heating and
domestic water support. The hot water control and heating function
are supported by the RWT31 fin-tube heat exchanger and four
solar collectors included in the solar package. The domestic water
preparation takes place with a 800 litre or 1000 litre buffer tank and
electronically regulated fresh water station using the hygienic flow
method.
Package consisting of:
Multifunctional buffer tank
MPS 800 or MPS 1000
Fresh water station EFS 25
2 x 3-way changeover valve, 6/4"
Type Frankfurt Duo / Frankfurt Duo Solar
2 condensate drip trays for out-
door unit with oil separator
Solar set RSK 25-10
only available in Solar package
With this heat pump package, both alternatively bivalent and mono-
energetically operated systems can be accommodated. The separate
pump assemblies HGM (can be ordered separately) for the heating
circuits are equipped with a high-efficiency pump (0-10 V) regulated
in a needs-based manner. The solar set included in this package, Type
RSK 25-10, with a collector surface of 10.12 m²
, is ideal for effective
domestic water preparation and heating support.
Package comprising:
■	 Indoor unit
■ 	 2 outdoor units
■ 	 Multifunctional buffer tank
MPS 800 or MPS 1000
■ 	 Electrically regulated fresh
water station EFS 25
■ 	 Two 3-directional switching
valves
■ 	 Immersion probe and collector
sensor
■ 	 2 condensate drip trays,
including oil separator for
outdoor unit
Additional scope of supply for the
Solar package
■ 	 Solar set RSK 25-10
(only available in Solar package)
HEAT PUMP PACKAGES
Hot water BivalentPanel heatingHeating Solar
connection
Night operation
ErP Ready
Energy
A++
Efficiency
Rating
Immersion probe and collector probe
41
Technical data
Area of use: heating 1)
18-25 kW 25-32 kW
Heat pump package - Type Frankfurt Duo / Frankfurt Duo Solar WKF 120 DUO WKF 180 DUO
Rated heating capacity (min. / max.) kW 18.0 (2.5 - 25.0) 29.0 (3.1 - 35.4)
Rated cooling capacity (min. / max.) kW 13.0 (3.3 - 23.8) 24.0 (11.0 - 28.0)
Energy efficiency rating for Frankfurt HZ/WW composite system A+/A A++/A
Energy efficiency rating for Frankfurt Solar HZ/WW/Solar/Smart Control composite system A++/A+ A++/A+
Series WKF 120 DUO WKF 180 DUO
with MPS 800 and EFS 25
Ref. no. 256115 256120
with MPS 800, EFS 25, and solar set RSK 25-10
Ref. no. 256116 256121
with MPS 1000 and EFS 25
Ref. no. 256117 256122
with MPS 1000, EFS 25, and solar set RSK 25-10
Ref. no. 256118 256123
1)
Total heating requirement, intake flow line 35°C, monoenergetic
Accessories
Series WKF 120 DUO WKF 180 DUO
REMKO Smart-Count
Factory-installed heat meter for the separate counting of the quantity of
heat of heating and hot water
259010 259010
REMKO Smart-Com
Additional software for the integration of the heat pump into a smart
home system such as KNX via the Ethernet interface of Smart Control,
including the heat meter installed at the factory (Smart Count)
254090 254090
REMKO Smart-Serv
Intelligent provision, installed heating rod 9 kW for monoenergetic opera-
tion, including emergency heating functions
259029 259027
Heating circuit pump set HGU
Speed-controlled heating circuit pump group (0-10 V)/unmixed 259035 259035
Heating circuit pump set HGM
Speed-controlled heating circuit pump group (0-10 V)/mixed 259036 259036
Hydraulic system of Frankfurt Duo / Frankfurt Duo Solar (example for monoenergetic or alternative bivalent operation)
Indoor unit
Outdoor unit
Outdoorprobe Heating
circuit
Non-mixed
Heating
circuit
Mixed
Heating
circuit
Mixed
Heating
circuit
Mixed
Heating
circuit
Mixed
EFS 25
RES
ZWPSKPHPU
MPS 800/1000
Boiler/
wall-mounted
heating system
Chilled
water
HGU HGM HGM HGM HGM
Hot waterSolar
42
Technical data
Series RSK 25
Domestic water heating/heating support Yes
Rooftop installation Yes
Flat roof installation Yes
Awning/façade installation no
Installation type
vertical, side-by-side
horizontal, stacked (on
request)
Piping meandering
Absorber coating highly selective
Max. number of collectors in series 4
Rated thermal capacity kW 1.9
Efficiency % 79.7
Total collector surface area m² 2.53
Absorber surface area m² 2.35
Aperture surface area m² 2.35
Heat carrier content l 1.7
Permissible operating pressure bar 10
Max. corrugated pipe length m 25
Dimensions - height/width/depth mm 2102/1202/80
Weight kg 44
HEAT PUMP SOLAR PACKAGES
Solar collector RSK 25
Solar collector RSK 25
With the thermal high-performance solar collectors Type RSK
25, you can operate your heating system with even greater
efficiency in combination with the inverter heat pump from
REMKO.
With the refined workmanship and specially developed heat
conducting technology, a maximum amount of solar energy is
utilised.
The RSK 25-5 solar set with two solar collectors utilises solar
energy for hot-water preparation. The RSK 25-10 solar set with
four solar collectors utilises solar energy for hot-water prepara-
tion and heating support.
The REMKO solar sets provide unsurpassed performance in a
perfectly attuned system configuration with the well-known
inverter heat pump.
Cross-section of solar collector RSK 25
Depending on the solar set, the heat pump can be used for air con-
ditioning during the summer, whereas the thermal solar system as-
sumes the hot water preparation. The complete system is controlled
via the REMKO Smart-Control intelligent
control system.
Almost every desire can be fulfilled by the
REMKO heat pump solar packages.
Highly selective
absorber layer
4mm glass
Absorber sheet,
aluminium
Absorber tube
Mineral wool
Bronze-coloured,
anodised aluminium
frame
Assembly system
1
1 2
3
4
5
6
7
2
3
4
5
6
7
KEYMARK DIN-tested
REMKO 011-7S1695 F
42
43
Solar set RSK 25-5
The solar set consisting of two solar collectors type RSK 25 is
an efficient supplement to hot-water preparation.
Solar set RSK 25-10
The solar set consisting of four solar collectors
type RSK 25 is an efficient supplement to hot-water prepara-
tion and heating support.
Solar station
Basic mounting set
Diaphragm expansion vessel
Fin-tube heat exchanger
Glycol, premixed
Immersion probe and collector sensor
Solar set consisting of:
■ 	 2x collectors type REMKO
RSK 25 (5.06 m²)
■ 	 Straight collector connector
■ 	 Solar station with HE pump
■ 	 MAG 18, expansion vessel
■ 	 Wall mount for MAG
■ 	 Connecting tube for MAG
Solar set consisting of:
■	 4x collectors type REMKO
RSK 25 (10.12 m²)
■ 	 Straight collector connector
■ 	 Solar station with HE pump
■ 	 MAG 25,
expansion vessel
■ 	 Wall mount for MAG
■ 	 Connecting tube for MAG
Accessories included in the solar set: (Additional accessories, such as a rooftop anchor, can be found on page 53.)
■ 	 Premixed glycol, 20 l
■ 	 Basic mounting set
■ 	 Expanded mounting set
■ 	 Fin-tube heat exchanger
RWT 31
■ 	 Immersion probe and col-
lector sensor
■ 	 Premixed glycol, 10 l
■ 	 Basic mounting set
■ 	 Fin-tube heat exchang-
er RWT 18
■ 	 Immersion probe and
collector sensor
44
Heat pump package type Stuttgart Solar
for WKF 70-180 appliance series
If the heat pump is intended to serve as a sole heat generator,
this heat pump package is the ideal solution. In addition to the
heating function, a cooling function can be provided when
necessary. In this package, the drinking water preparation takes
place in an enamelled, 300-litre drinking water tank integrated
into the indoor module. In addition, a cooling function can be
provided as necessary while the thermal solar system heats
the domestic water. Through the compact design, installation
expenses are extremely low. The solar set included in this pack-
age, type RSK 25-5, with a collector surface of 5.06 m², is ideal
for effective domestic water preparation.
Package consisting of:
Type: Stuttgart Solar
HEAT PUMP SOLAR PACKAGES
Condensate drip tray for out-
door unit with oil separator
Solar set RSK 25-5
Package comprising:
■	 Indoor unit with inte-
grated 300-litre domestic
water tank
(BEVB 1.19 kWh/day)
■ 	 Outdoor unit
For scope of supply, see p. 14
■ 	 Solar set RSK 25-5
■ 	 Condensate drip tray,
including oil separator for
outdoor unit
Hot water
HeatingNight operation
Solar
connection
Surface cooling/
surface heating
Cooling
ErP Ready
Energy
A++
Efficiency
Rating
44
45
Technical data
Area of use: heating 1)
4-7 kW 8-11 kW 12-18 kW
Heat pump package, Type Stuttgart Solar WKF 70 compact WKF 120 compact WKF 180 compact
Rated heating capacity (min. / max.) kW 6.0 (0.9 - 6.0) 10.0 (2.5 - 12.5) 14.0 (3.1 - 17.7)
Rated cooling capacity (min. / max.) kW 5.0 (1.1 - 8.9) 6.0 (3.3 - 11.9) 11.0 (5.5 - 14.0)
Energy efficiency rating for HZ/WW/Solar/Smart Control composite system A++/A+ A++/A+ A++/A+
External maximum pressure loss kPa 80 80 80
Series WKF 70 compact WKF 120 compact WKF 180 compact
Ref. no. 254170 256230 256235
1)
Total heating requirement, intake flow line 35°C, monoenergetic
Accessories
Series WKF 70 compact WKF 120 compact WKF 180 compact
REMKO Smart-Count
Factory-installed heat meter for the separate counting of the quantity of
heat of heating and hot water
259010 259010 259010
REMKO Smart-Com
Additional software for the integration of the heat pump into a smart home
system such as KNX via the Ethernet interface of Smart Control, including
the heat meter installed at the factory (Smart Count)
254090 254090 254090
REMKO Smart-Serv
Intelligent provision, installed heating rod 9 kW for monoenergetic
operation, including emergency heating functions
259021 259022 259023
REMKO Smart-Cool
for active cooling. Pipe subassemblies and circulation pump in the indoor
unit with vapour density insulation. Use in case of cooling function when
the inlet temperature is below the dew point.
259085 259085 259085
For additional accessories, see page 50
Indoor unit
Outdoor unit
Hydraulic system of Stuttgart Solar (example for monoenergetic operation)
Outdoorprobe
Heating
circuit
MixedCooling circuitSolar Hot water Chilled water
ZWPSKP
46
Package consisting of:
2 x 3-way changeover valve, 5/4"
Solar set RSK 25-10
HEAT PUMP SOLAR PACKAGES
Type Frankfurt Solar
Heat pump package – Type Frankfurt Solar
for WKF 70-180 appliance series
The energy-savings package is prepared for the integration of
the solar-thermal system REMKO RSK 25-10 to the fin-tube
heat exchanger RWT 31. The domestic water preparation takes
place with a 800 litre or 1000 litre multifunction buffer tank
and fresh water station using the hygienic flow method. With
this heat pump package, both bivalent and single energy source
systems can be accommodated.
The solar set included in this package, type RSK 25-10, with a
collector surface of 10.12 m² provides household water and heating
support. The separate pump assemblies HGM (can be ordered sepa-
rately) for the heating circuits are equipped with a high-efficiency
pump (0-10 V) regulated in a needs-based manner.
Information about government subsidies can be found under:
www.bafa.de / www.kfw.de
www.foerderdata.de
Condensate drip tray for outdoor
unit with oil separator
Package comprising:
■	 Indoor unit
■ 	 Outdoor unit
For scope of supply, see p. 16
■ 	 Solar set RSK 25-10
■ 	 Multifunctional buffer
tank MPS 800 (800 litres)
or MPS 1000 (1000 litres)
■ 	 Electrically regulated fresh
water station EFS 25
(for connection sets, see
p. 52)
■ 	 2 x 3-way switchover
valve
■ 	 Condensate drip tray,
including oil separator for
outdoor unit
Multifunction buffer tank MPS
800 (800 litres) or MPS 1000
(1000 litres)
Fresh water station EFS 25, com-
plete with pump and flow switch
For connection sets, see p.52
Hot water Solar
connection
BivalentSurface heatingHeatingNight operation
ErP Ready
Energy
A++
Efficiency
Rating
46
47
Technical data
Area of use: heating 1)
4-7 kW 8-11 kW 12-18 kW
Heat pump package, Type Frankfurt Solar WKF 70 WKF 120 WKF 180
Rated heating capacity (min. / max.) kW 6.0 (0.9 - 6.0) 10.0 (2.5 - 12.5) 14.0 (3.1 - 17.7)
Rated cooling capacity (min. / max.) kW 5.0 (1.1 - 8.9) 6.0 (3.3 - 11.9) 11.0 (5.5 - 14.0)
Energy efficiency rating for HZ/WW/Solar/Smart Control composite system A++/A+ A++/A+ A++/A+
External maximum pressure loss kPa 80 80 80
Series WKF 70 WKF 120 WKF 180
with MPS 800
Ref. no. 254180 256215 256220
with MPS 1000
Ref. no. 254190 256216 256221
1)
Total heating requirement, intake flow line 35°C, monoenergetic
Accessories
Series WKF 70 WKF 120 WKF 180
REMKO Smart-Count
Factory-installed heat meter for the separate counting of the quantity of
heat of heating and hot water
259010 259010 259010
REMKO Smart-Com – Additional software for the integration of the heat
pump into a smart home system such as KNX via the Ethernet interface
of Smart Control, including the heat meter installed at the factory (Smart
Count)
254090 254090 254090
REMKO Smart-BVT, factory-installed
BVT pipe assembly, 3-way switchover valve for the integration of a
second heat generator (max. 22 kW), without a circulation pump,
bivalently alternating operation
Note: No combination with REMKO Smart-Serv possible.
Only in combination with buffer tank.
254050 259015 259016
REMKO Smart-Serv – Intelligent provision, installed heating rod 9 kW
for monoenergetic operation, including emergency heating functions
Note: No combination with REMKO BVT possible.
254060 259025 259026
Heating circuit pump set HGM
Speed-controlled heating circuit pump group (0-10 V)/mixed 259036 259036 259036
For additional accessories, see page 50
ZWP
M
Indoor unit
Outdoor unit
Hydraulic system of Frankfurt Solar (example for monoenergetic or bivalently alternating operation)
Outdoorprobe
Heating
circuit
Non-mixed
Heating
circuit
Mixed
Heating
circuit
MixedHot waterSolar
Chilled
water
EFS 25
ZWPSKP
MPS 800/1000
Boiler/wall-mounted heat-
ing system (max. 22 kW)
HGU HGM HGM
RES
48
Unit type HPS 500 MPS 800 MPS 1000
Storage type Buffer tank Stratified storage
Tank volume Litre 500 800 1000
BEVB kW/24h 2.8 3.4 3.5
Heat retention loss W 116 141 145
Energy efficiency class C - -
Height with insulation mm 1725 1785 2135
Diameter with insulation mm 850 990 990
Diameter without insulation mm 650 790 790
Tilt height without insulation mm 1670 1750 2090
Weight kg 113 157 176
Ref. no. 270300 270380 270400
Unit type KPS 130 KPS 300
Storage type Hot/cold water buffer tank
Tank volume Litre 130 300
BEVB kW/24h 1.2 2.2
Heat retention loss W 50 91
Energy efficiency class B C
Height with insulation mm 742 1690
Diameter mm 680 600
Tilt height without insulation mm 800 1740
Weight kg 39 118
Ref. no. 270240 270250
TANK SYSTEMS
Buffer tanks for heating
water
■	 Universally usable as parallel
buffer (hydraulic switch) or
series-connected buffer
■	 With dummy flange cover
D240 for retrofitting a fin-
tube heat exchanger RWT
31
■	 Electrical immersion heating
element, screw-in 6/4"
■	 Max. operating temperature
95°C
■	 Max. operating pressure 3
bar
Hot/cold water buffer tank
■	 Universally usable as parallel
buffer
(hydraulic switch) or series-
connected buffer
■	 With cleaning flange lid
D180 for retrofitting
■	 Fin-tube heat exchanger
RWT 18, can be retrofitted
■	 Electrical immersion heating
element, screw-in 6/4"
■	 Operating temperature: min.
0°C, max. 95°C
■	 Max. operating pressure 3
bar
■	 Steel sheet inner boiler S235
according to
DIN EN 10 025/10 111
■	 Test pressure 4.5 bar
■	 External anti-rust coating
■	 9 connecting threads (11 for
MPS800/MPS1000) 6/4"
IG with inflow restrictors
■	 4 socket screw threads 1/2"
for sensor/thermometer im-
mersion sleeves
■	 From quality steel S235
according to DIN EN 10
025/10 111
■	 High-efficiency, double-shell
heat insulation, 100 mm,
silver grey
■	 4 connecting threads
AG 5/4"
■	 Powder-coated steel sheet
outer casing in silver-grey
■	 Outer casing reinforced by
beading
■	 High-quality PUR insulation
50 mm (CFC, HCFC and
HFC-free), water vapour
diffusion tight
■	 Sensor conduct for variable
sensor positioning
49
UP TO 45% ENERGY SAV-
INGS DUE TO IMPROVED PU
FOAM INSULATION
Unit type EWS 300 E EWS 500 E KWS 300
Storage type Domestic water tank, enamelled Combination buffer tank
Net domestic water volume Litre 269 426 275
Volume of buffer tank (steam-diffusion-proof) – – 100
Heat exchanger surface m2
3.5 6.2 3.2
BEVB kW/24h 1.23 1.88 1.77
Heat retention loss W 51 78 74
Energy efficiency class B B B
Tap profile XL 3 XL XXL
Height/width/depth mm 1435 1921 1760
Diameter mm 740 750 750
Tilt height mm 1595 2023 1879
Weight kg 173 222 190
Ref. no. 270600 270800 270700
■	 Max. operating pressure
10 bar
■	 Max. operating temperature
95°C
■	 Connection possibilities
for circulation 3/4" AG
■	 Enamelled with double-
coiled smooth-tube heat
exchanger and particularly
large heat exchanger surface
Buffer tank for domestic hot water heating
■	 Inner container with
magnesium protection
anodes
according to DIN 4753
■	 PUR insulation (CFC,
HCFC, and HFC-free)
ACCESSORIES – TANK TECHNOLOGY
Tank systems
Electrical auxiliary heater 6 kW
for KPS/MPS/HPS buffer tank
Electrical auxiliary heater 6/4" for installa-
tion in a buffer tank. Including temperature
regulator and safety temperature limiter.
2, 4 or 6 kW can be optionally connected.
Note: Not suited for domestic water tank.
Ref. no. 260063
Built-in flange heating for EWS 300/500 E
and KWS 300
Consisting of a high-quality tubular heating
element on which an insulated flange plate
is fitted. A protective earthing resistor, ther-
mal sensor and safety temperature limiter.
Max. operating pressure 10 bar.
Heating capacity 6 kW.
Note: Not suited for buffer tanks of the
HPS/MPS/KPS series.
Ref. no. 260160
■	 Cold water supply and hot
water outlet 1" IG
■	 With cleaning flange lid D180
■	 Built-in flange heating
(legionella protection) or fin-
tube heat exchanger RWT
18 can be retrofitted
Fin-tube heat exchanger
For additional indirect heating, e.g. with a
solar thermal system
Unit type RWT 18 RWT 31
Suitable for
buffer tanks
Type EWS 300 E
EWS 500 E
KPS 300
KWS 300
HPS 500
MPS 800
MPS 1000
Heat exchanger
area m² 1.40 3.10
Installation
length in
mm 440 530
Connection G Inch 3/4 1
Contents l 1.50 2.50
Flange Ø 180 / 8-hole 240 / 12-hole
Ref. no. 260200 260210
50
ACCESSORIES – HEAT PUMPS
REMKO Smart-Web
Ethernet interface for the connection of
commercial home router software. For dial-
ling in to Smart-Control. Setting and reading
operating parameters using a smartphone,
tablet PC, laptop, etc.
Ref. no. 248120
REMKO Smart-Control remote control
With the cabled remote control, all functions
of the heat pump and heating circuits can be
set. A room temperature controlled regulation
of the heating circuits (FBH or heaters) can be
realised. In addition, dew point regulation is
possible using the integrated humidity probe.
Ref. no. 248105
REMKO Smart-Com
Additional software for the integration of the
heat pump into a Smart Home system such
as KNX via the Ethernet interface of Smart
Control, including the heat meter installed at
the factory (Smart Count)
Ref. no. 254090
Floor bracket
Robust floor bracket made of reinforced of
rubber with high intrinsic weight and good
damping properties. For heat pump outdoor
unit series WKF. Length 0.6m and/or 1m
WKF 70-180, WKF 120-180 Duo (2x)
BK-600 Plus Ref. no. 260023
BK-1000 Plus Ref. no. 260024
Connecting line between outdoor and
indoor unit
WKF 70-180,
WKF 120-180 Duo
3
8
5
8 " Ø
Ref. no. 260010
Electrical condensation drainage - heating
Electrical condensate drainage heat-
ing, temperature-regulated for the safe
discharge of defrost water with outside
temperatures below the freezing point.
Ref. no. 260045
Condensate drip tray including oil separator
Condensate drip tray made of aluminium for
each outdoor unit, including temperature-
controlled electronic condensate drip tray
heating, leaf guard grating, and oil separator.
According to § 62, Abs.1, WHG (Wasser-
haushaltsgesetz (German Water Resources
Act).
Ref. no. 260135
Dual-direction power meter
Current meter for Smart Heating/Cooling
function, PV integration.
400V/3~/50Hz with S0 interface
Ref. no. 259065
Wall brackets
For mounting to suitable faces and ma-
sonry, including vibration dampers
For device type Type Ref. no.
WKF 70-180 WKM-600 260079
WKF120-180
Duo (2x) WKM-600 260079
Noise
decoupling set 1613900
51
Overflow protection valve
Overflow protection valve 1" for ensur-
ing that the minimum medium flow rate is
maintained.
Ref. no. 260080
BVT set, loose
For the external integration of a 2 WE with
a larger heating capacity. Consisting of:
3-way valve 5/4", overflow valve 1"
For unit type Ref. no.
WKF 70,120,180
WKF 120,180 Duo 260081
Pulse generator, circulation
Pulse generator for the realisation of a
pulse-controlled circulation pump via
REMKO Smart-Control.
Ref. no. 259045
3-way changeover valve
Electrical switching valve / 3-way valve for
domestic water preparation and separate
cooling circuit (four-pipe system).
Ref. no. 260072
Ref. no. 259055
REMKO tank connection set
Pipe subassembly including an electrical
actuator to connect the inlet flow line of an
external hot water tank
Ref. no. 259080
Pipe bushing for WKF series
Robust EPDM seal for watertight sealing of
the refrigerant and electrical lines. Ø 100 mm
Ref. no. 259061
Immersion probe
Immersion probe Pt 1000 for integrating
- Solar reference probe for buffer tank
- Domestic water tank EWS 300
- General buffer probe
Ref. no. 259062
Collector sensor
Immersion probe Pt 1000 for the integra-
tion of solar thermal systems
Ref. no. 260102
Contact probe
Contact probe Pt1000 for the integrating
- A temperature-guided circulation pump
via Smart Control
- A heating circuit with mixer (2 pieces
required)
Ref. no. 259060
Flow sensor for dynamic hygiene function
Flow sensor with frequency output for
recording the cold water volume flow rate in
the domestic water tank. Regulation accord-
ing to DIN 1988-200
Ref. no.
Tap volume ≤ 25l/min 254070
Tap volume ≥ 25l/min 254080
External dew point monitor incl. 1 contact probe
Dew point monitoring is installed for ad-
ditional security to prevent the occurrence of
humidity. The humidity is checked directly on
the corresponding surfaces. It is possible to
connect up to 5 measuring probes.
Ref. no.
Ext. dew point monitor 259070
Additional contact probe 259071
Sludge separator
For the filtration of contamination and corrosion
products from the heating water, glycol-resistant
and insulated
Ref. no.
1 to 2.1 m3
/h 260803
1½ to 5.4 m3
/h 260804
Full heating protection
Corrosion protection and hardness stabilisation
for conventional hot water heating systems
Ref. no.
Without anti-freeze 1 l 260819
With anti-freeze 10 l 260823
With anti-freeze 20 l 260807
With anti-freeze 200 l 260808
With anti-freeze 1000 l 260809
Heating circuit pump set HGU
Consisting of: a speed-controlled (0-10 V)
heating circuit pump without mixer, ball
valves with thermometer
Ref. no. 259035
Heating circuit pump set HGM
Consisting of: a speed-controlled (0-10 V)
heating circuit pump with a mixer, ball valves
with thermometer, 2x Pt 1000 contact probes
Ref. no. 259036
52
FRESH WATER SYSTEMS
Tank connection set
for buffer tanks
For the direct connection of the fresh
water station EFS 25 to the buffer tank.
Note: Not suited for EFS 35/50
For buffer tank Ref. no.
HPS 500 259040
MPS 800 259041
MPS 1000 259042
Return flow layering set RES
for EFS 25 for connection to the buffer tank
RES including tank connection pipes and
3-way switchover valve for temperature-
dependent layering in the buffer tank.
Note: Not suited for EFS 35/50
For buffer tank Ref. no.
MPS 800 259031
MPS 1000 259032
Accessories
Technical data
Fresh water station EFS 25 EFS 35 EFS 50
Transmission power kW 30 1)
79 2)
122
Installation site Tank/wall Wall Wall
Heat pump type WKF 70, 120, 180,
120-180 DUO
180,
120-180 DUO
120 DUO
180 DUO
Min. buffer volume for hot water operation L 500 800 1000
Primary connections IG Inch 3/4 1 1/2 2
Secondary connections AG, flat-sealing Inch 3/4 1 1 ¼
Dimensions - height/width/depth mm 645/348/249 795/602/298 795/602/298
Tap volume at 45°C tap temp. and 50°C tank temp. l/min 17 32 50
Tap volume at 45°C tap temp. and 60 °C tank temp. l/min 28 50 77
Tap volume at 45°C tap temp. and 70 °C tank temp. l/min 36 64 88
Series EFS 25 EFS 35 EFS 50
Ref. no. 260155 260156 260157
1)
Tapping output at 50°C buffer temperature / 12 l/min / 10°C chilled water supply line
2)
Tapping output at 50°C buffer temperature / 32 l/min / 10°C chilled water supply line
Accessories
Other accessories EFS 25 EFS 35 EFS 50
Circulation pump EFS 25
Controllable high-efficiency circulation pump including
pipe subassembly for direct connection to EFS 25.
259052
– –
Circulation pump EFS 35/EFS 50
Speed-controlled high-efficiency circulation pump for
installation directly to the fresh water station
–
259053 259053
Single-layer return valve
for temperature-dependent layer in the buffer
tank
260072 260072 260072
Electronically controlled fresh water stations
EFS series
The fresh water stations of REMKO are used for hygienic domestic water preparation in con-
nection with buffer tanks. The devices are completely equipped with electronic control, speed-
controlled high-efficiency pump, flow switch, and plate heat exchanger. The heat exchanger is
designed for a high flow rate of 25 l/min (EFS25), 35 l/min (EFS35) or 50 l/min (EFS50). The
flow rate can be increased through cascading. The fresh water stations are delivered ready for
mounting in the EPP housing. In the case of the EFS 35/50, the unit is mounted to the wall.
The EFS 25 fresh water station permits mounting directly on the tank or wall.
53
ACCESSORIES –
SOLAR COLLECTORS
3-way changeover valve Solar, 1
Electrical changeover valve/3-way valve
1 for thermal solar plants (included in the
heat pump solar package)
Ref. no. 260800
Collector connector, straight
For the connection of the solar collectors
RSK 25
(included in the REMKO solar set)
Ref. no. 260810
Glycol
Heat transfer medium with corrosion
protection for solar plants (included in the
REMKO solar set)
Ref. no. 260805 10 L
Ref. no. 260806 20 L
Installation coupling for the collector line
For the connection of the corrugated solar
pipe to the RSK 25 solar collectors (included
in the corrugated pipe mounting set)
Ref. no. 260865
Flat roof installation set for solar collectors
RSK 25-5, consisting of: 3x flat roof brack-
ets, 1x safety support
Ref. no. 260842
RSK 25-10, consisting of: 5x flat roof
brackets, 1x safety support
Ref. no. 260843
Insulated, corrugated pipe for solar
collectors for RSK 25-5 and RSK 25-10,
including sensor cable
Design Ref. no.
10 m roll, incl. installation set 260900
15 m roll, incl. installation set 260901
25 m roll, incl. installation set 260902
Corrugated pipe, m
(max. 25 m)
260869
Installation set, separate 260870
Complete rooftop anchor set for solar collectors
For solar package For tile type Ref. no.
RSK 25-5 Frankfurter tile 260850
RSK 25-10 Frankfurter tile 260855
RSK 25-5 Crown tile 260851
RSK 25-10 Crown tile 260856
RSK 25-5 Slate 260852
RSK 25-10 Slate 260857
RSK 25-5 Rafter-independent 260853
RSK 25-10 Rafter-independent 260858 Slate tileCrown tileFrankfurter tile
54
Valve assembly for 2-pipe system, VB
3-way valve assembly for controlling the medium flow rate
during cooling or heating mode.
For unit types Ref. no.
KWK 100-400-4R Wall installation 1661115
KWK 100-400 4R horiz. Ceiling installation 1661117
Condensate pump
For unit type Condensate pump Ref. no.
KWK KP-8 1613125
Feet SF-3
For unit types Ref. no.
KWK 100-400-4R 1662125
Air inlet socket LS-1, with air inlet grid
for the optical disguising of the air inlet area.
For unit types Ref. no.
KWK 100-4R 1662130
KWK 150-4R 1662131
KWK 250-4R 1662132
KWK 400-4R 1662133
ACCESSORIES –
WALL AND CEILING CHESTS
Precision room temperature controller RR-21 for the operation and
control of an indoor unit. Programmable, electronic controller with
various functions such as summer/winter mode changeover, 4 fan
speeds, regulation of the medium flow rate with standard valve
heads. Group control with switch relay possible.
For unit types Ref. no.
KWK 100-400-4R 1611396
Accessories
Room temperature sensor 1611380-1
Inlet temperature probe 1611381-1
Room temperature controller RR-14 indoor unit installation for the opera-
tion and control of an indoor unit. Mechanical controller with basic func-
tions, such as summer/winter programme switching, 3 fan speeds.
For unit types Ref. no.
KWK 100-400-4R 1662101
55
THE NEW ONLINE
HEAT PUMP CONFIGURATOR
The planning of REMKO heat pumps made easy
Test it...
http://wp-konfigurator.remko.de
The heat pump configurator, a simple and free tool for generating an individual heat pump for
your house quickly and easily, is available on www.REMKO.de. In addition to the appropriate heat
pump, the configurator also shows the hydraulic diagram, the accessory parts required for installa-
tion, the bivalence point, and the right Energy Label of the heat pump system. Plan your personal
heat pump system today – with the new heat pump generator of REMKO!
REMKO INTERNATIONAL
...and somewhere near you!
Take advantage of our experience and advice
REMKO dealers
Hotline
Within Germany
+49 (0)5232-606-0
International
+49(0)5232-606-130
REMKO GmbH  Co. KG
Klima- und Wärmetechnik
Im Seelenkamp 12 · 32791 Lage
PO Box 1827 · 32777 Lage
Telephone	+49-5232-606-0
Fax	+49-5232-606-260
E-mail	info@remko.de
URL	www.remko.de
MS/BD/20/11.16  Wereservetherighttotechnicalmodifications.
Informationprovidedwithoutguarantee!

More Related Content

What's hot

5.energy audit of pumps
5.energy audit of pumps5.energy audit of pumps
5.energy audit of pumpsPadmadhar PD
 
Eart air tunnel heat exchanger latest ppt
Eart air tunnel heat exchanger latest pptEart air tunnel heat exchanger latest ppt
Eart air tunnel heat exchanger latest pptvikas mahala
 
Compact Thermal Energy Storage
Compact Thermal Energy StorageCompact Thermal Energy Storage
Compact Thermal Energy StorageLeonardo ENERGY
 
Air conditioning systems
Air conditioning systemsAir conditioning systems
Air conditioning systemsMatt Allen
 
All About HVAC System - Created by MG Cooling Solutions
All About HVAC System - Created by MG Cooling SolutionsAll About HVAC System - Created by MG Cooling Solutions
All About HVAC System - Created by MG Cooling SolutionsDr Vijay Gehlot
 
Direct energy conversion (PV Cell, Fuel Cell)
Direct energy conversion (PV Cell, Fuel Cell)Direct energy conversion (PV Cell, Fuel Cell)
Direct energy conversion (PV Cell, Fuel Cell)Ashish Bandewar
 
Design options for hvac distribution systems
Design options for hvac distribution systemsDesign options for hvac distribution systems
Design options for hvac distribution systemsJASON KEMBOI
 
HVAC Energy Efficiency in Commercial Buildings
HVAC Energy Efficiency in Commercial BuildingsHVAC Energy Efficiency in Commercial Buildings
HVAC Energy Efficiency in Commercial BuildingsAlan Richardson
 

What's hot (20)

Energy storage
Energy storageEnergy storage
Energy storage
 
5.energy audit of pumps
5.energy audit of pumps5.energy audit of pumps
5.energy audit of pumps
 
Eart air tunnel heat exchanger latest ppt
Eart air tunnel heat exchanger latest pptEart air tunnel heat exchanger latest ppt
Eart air tunnel heat exchanger latest ppt
 
Compact Thermal Energy Storage
Compact Thermal Energy StorageCompact Thermal Energy Storage
Compact Thermal Energy Storage
 
Hvac duct design
Hvac duct designHvac duct design
Hvac duct design
 
Air conditioning systems
Air conditioning systemsAir conditioning systems
Air conditioning systems
 
Ashrae thermal guidelines svlg 2015 (1)
Ashrae thermal guidelines  svlg 2015 (1)Ashrae thermal guidelines  svlg 2015 (1)
Ashrae thermal guidelines svlg 2015 (1)
 
Eliminating Data Center Hot Spots
Eliminating Data Center Hot SpotsEliminating Data Center Hot Spots
Eliminating Data Center Hot Spots
 
All About HVAC System - Created by MG Cooling Solutions
All About HVAC System - Created by MG Cooling SolutionsAll About HVAC System - Created by MG Cooling Solutions
All About HVAC System - Created by MG Cooling Solutions
 
Solar energy
Solar energySolar energy
Solar energy
 
Direct energy conversion (PV Cell, Fuel Cell)
Direct energy conversion (PV Cell, Fuel Cell)Direct energy conversion (PV Cell, Fuel Cell)
Direct energy conversion (PV Cell, Fuel Cell)
 
VRF system presentation !
VRF system presentation !VRF system presentation !
VRF system presentation !
 
Design options for hvac distribution systems
Design options for hvac distribution systemsDesign options for hvac distribution systems
Design options for hvac distribution systems
 
HVAC Energy Efficiency in Commercial Buildings
HVAC Energy Efficiency in Commercial BuildingsHVAC Energy Efficiency in Commercial Buildings
HVAC Energy Efficiency in Commercial Buildings
 
Microhydro in nepal
Microhydro in nepalMicrohydro in nepal
Microhydro in nepal
 
Solar power plant
Solar power plantSolar power plant
Solar power plant
 
Geothermal Energy
Geothermal EnergyGeothermal Energy
Geothermal Energy
 
Euroklimat Company Introduction
Euroklimat Company IntroductionEuroklimat Company Introduction
Euroklimat Company Introduction
 
Wind Farm design and Construction
Wind Farm design and ConstructionWind Farm design and Construction
Wind Farm design and Construction
 
HVAC Fundamentals
HVAC  FundamentalsHVAC  Fundamentals
HVAC Fundamentals
 

Viewers also liked

Signorini catalago 2016
Signorini catalago 2016Signorini catalago 2016
Signorini catalago 2016Dynamic444
 
CANALIZAÇÃO/DUCHES
CANALIZAÇÃO/DUCHESCANALIZAÇÃO/DUCHES
CANALIZAÇÃO/DUCHESDynamic444
 
Piso radiante EMPUR- Guarda
Piso radiante EMPUR- GuardaPiso radiante EMPUR- Guarda
Piso radiante EMPUR- GuardaDynamic444
 
Catalog valdama it-2016
Catalog valdama it-2016Catalog valdama it-2016
Catalog valdama it-2016Dynamic444
 
Signorini catalogo salone 2016 low
Signorini catalogo salone 2016 lowSignorini catalogo salone 2016 low
Signorini catalogo salone 2016 lowDynamic444
 

Viewers also liked (11)

Images (6)
Images (6)Images (6)
Images (6)
 
Signorini catalago 2016
Signorini catalago 2016Signorini catalago 2016
Signorini catalago 2016
 
Images (4)
Images (4)Images (4)
Images (4)
 
Images (8)
Images (8)Images (8)
Images (8)
 
Images (3)
Images (3)Images (3)
Images (3)
 
Images (9)
Images (9)Images (9)
Images (9)
 
CANALIZAÇÃO/DUCHES
CANALIZAÇÃO/DUCHESCANALIZAÇÃO/DUCHES
CANALIZAÇÃO/DUCHES
 
Piso radiante EMPUR- Guarda
Piso radiante EMPUR- GuardaPiso radiante EMPUR- Guarda
Piso radiante EMPUR- Guarda
 
Catalog valdama it-2016
Catalog valdama it-2016Catalog valdama it-2016
Catalog valdama it-2016
 
Images (11)
Images (11)Images (11)
Images (11)
 
Signorini catalogo salone 2016 low
Signorini catalogo salone 2016 lowSignorini catalogo salone 2016 low
Signorini catalogo salone 2016 low
 

Similar to Remko WKF inverter heat pump/ Bomba de calor inverter Remko WKF

Air to Water Low Temperature Heat Pump
Air to Water Low Temperature Heat PumpAir to Water Low Temperature Heat Pump
Air to Water Low Temperature Heat PumpCCSE Host
 
Fuji tu dong hoa catalog frenic-hvac-dienhathe.org
Fuji tu dong hoa catalog frenic-hvac-dienhathe.orgFuji tu dong hoa catalog frenic-hvac-dienhathe.org
Fuji tu dong hoa catalog frenic-hvac-dienhathe.orgDien Ha The
 
General Sales Brochure 2016
General Sales Brochure 2016General Sales Brochure 2016
General Sales Brochure 2016Alan Beresford
 
General Sales Brochure 2016
General Sales Brochure 2016General Sales Brochure 2016
General Sales Brochure 2016Emma Beresford
 
Air Conditioning case study
Air Conditioning case studyAir Conditioning case study
Air Conditioning case studySona Rawat
 
H2i Residential Cooling and Heating System Carried By Unique Indoor Comfort L...
H2i Residential Cooling and Heating System Carried By Unique Indoor Comfort L...H2i Residential Cooling and Heating System Carried By Unique Indoor Comfort L...
H2i Residential Cooling and Heating System Carried By Unique Indoor Comfort L...UniqueIndoorComfortLibertyville
 
Installations Brochure Ecoforest Heat Pumps
Installations Brochure Ecoforest Heat PumpsInstallations Brochure Ecoforest Heat Pumps
Installations Brochure Ecoforest Heat PumpsAdrián Pérez
 
Heat interface units brochure - Docherty Group
Heat interface units brochure  - Docherty GroupHeat interface units brochure  - Docherty Group
Heat interface units brochure - Docherty GroupDocherty Group
 
"Replacement of vapor compression system of domestic refrigerator by an eject...
"Replacement of vapor compression system of domestic refrigerator by an eject..."Replacement of vapor compression system of domestic refrigerator by an eject...
"Replacement of vapor compression system of domestic refrigerator by an eject...IRJET Journal
 
VARIABLE REFRIGERANT FLOW(VRF) ppt
VARIABLE REFRIGERANT FLOW(VRF)  pptVARIABLE REFRIGERANT FLOW(VRF)  ppt
VARIABLE REFRIGERANT FLOW(VRF) pptEzhil Raj s
 
BLUEWAY Air cooled water chiller Brochure
BLUEWAY Air cooled water chiller BrochureBLUEWAY Air cooled water chiller Brochure
BLUEWAY Air cooled water chiller BrochureRoger Luo
 
P-Series Commercial Ductless and Ducted Cooling Systems Catalog Available fro...
P-Series Commercial Ductless and Ducted Cooling Systems Catalog Available fro...P-Series Commercial Ductless and Ducted Cooling Systems Catalog Available fro...
P-Series Commercial Ductless and Ducted Cooling Systems Catalog Available fro...UniqueIndoorComfortLibertyville
 
Dc inverter heat pump blueway
Dc inverter heat pump bluewayDc inverter heat pump blueway
Dc inverter heat pump bluewayRoger Luo
 
Combi Cooler - Energy efficient cooling unit for air handling units
Combi Cooler - Energy efficient cooling unit for air handling unitsCombi Cooler - Energy efficient cooling unit for air handling units
Combi Cooler - Energy efficient cooling unit for air handling unitsBartosz Pijawski
 

Similar to Remko WKF inverter heat pump/ Bomba de calor inverter Remko WKF (20)

Air to Water Low Temperature Heat Pump
Air to Water Low Temperature Heat PumpAir to Water Low Temperature Heat Pump
Air to Water Low Temperature Heat Pump
 
HIU Design Guide
HIU Design GuideHIU Design Guide
HIU Design Guide
 
Fuji tu dong hoa catalog frenic-hvac-dienhathe.org
Fuji tu dong hoa catalog frenic-hvac-dienhathe.orgFuji tu dong hoa catalog frenic-hvac-dienhathe.org
Fuji tu dong hoa catalog frenic-hvac-dienhathe.org
 
General Sales Brochure 2016
General Sales Brochure 2016General Sales Brochure 2016
General Sales Brochure 2016
 
General Sales Brochure 2016
General Sales Brochure 2016General Sales Brochure 2016
General Sales Brochure 2016
 
Module (1.3) types of ac units-hvac-apex
Module (1.3) types of ac units-hvac-apexModule (1.3) types of ac units-hvac-apex
Module (1.3) types of ac units-hvac-apex
 
Air Conditioning case study
Air Conditioning case studyAir Conditioning case study
Air Conditioning case study
 
H2i Residential Cooling and Heating System Carried By Unique Indoor Comfort L...
H2i Residential Cooling and Heating System Carried By Unique Indoor Comfort L...H2i Residential Cooling and Heating System Carried By Unique Indoor Comfort L...
H2i Residential Cooling and Heating System Carried By Unique Indoor Comfort L...
 
Product manual hps
Product manual hpsProduct manual hps
Product manual hps
 
Installations Brochure Ecoforest Heat Pumps
Installations Brochure Ecoforest Heat PumpsInstallations Brochure Ecoforest Heat Pumps
Installations Brochure Ecoforest Heat Pumps
 
Heat interface units brochure - Docherty Group
Heat interface units brochure  - Docherty GroupHeat interface units brochure  - Docherty Group
Heat interface units brochure - Docherty Group
 
Freshbox 602018 03en
Freshbox 602018 03enFreshbox 602018 03en
Freshbox 602018 03en
 
"Replacement of vapor compression system of domestic refrigerator by an eject...
"Replacement of vapor compression system of domestic refrigerator by an eject..."Replacement of vapor compression system of domestic refrigerator by an eject...
"Replacement of vapor compression system of domestic refrigerator by an eject...
 
VARIABLE REFRIGERANT FLOW(VRF) ppt
VARIABLE REFRIGERANT FLOW(VRF)  pptVARIABLE REFRIGERANT FLOW(VRF)  ppt
VARIABLE REFRIGERANT FLOW(VRF) ppt
 
BLUEWAY Air cooled water chiller Brochure
BLUEWAY Air cooled water chiller BrochureBLUEWAY Air cooled water chiller Brochure
BLUEWAY Air cooled water chiller Brochure
 
P-Series Commercial Ductless and Ducted Cooling Systems Catalog Available fro...
P-Series Commercial Ductless and Ducted Cooling Systems Catalog Available fro...P-Series Commercial Ductless and Ducted Cooling Systems Catalog Available fro...
P-Series Commercial Ductless and Ducted Cooling Systems Catalog Available fro...
 
Dc inverter heat pump blueway
Dc inverter heat pump bluewayDc inverter heat pump blueway
Dc inverter heat pump blueway
 
Energy Efficiency in Offices
Energy Efficiency in OfficesEnergy Efficiency in Offices
Energy Efficiency in Offices
 
Combi Cooler - Energy efficient cooling unit for air handling units
Combi Cooler - Energy efficient cooling unit for air handling unitsCombi Cooler - Energy efficient cooling unit for air handling units
Combi Cooler - Energy efficient cooling unit for air handling units
 
Rpf y un50_00
Rpf y un50_00Rpf y un50_00
Rpf y un50_00
 

Remko WKF inverter heat pump/ Bomba de calor inverter Remko WKF

  • 1. SMART HEAT PUMPS Intelligent and highly efficient Quality with systems Air/water system for heating and cooling WKF series 1-2017 Max. 55°C Inlet temperature ErP Ready Energie Effizienz Klasse A++
  • 2. REMKO – THE SYSTEM PROVIDER 2 AIR-CONDITIONING Room air conditioners Local air-conditioners Comfort air-conditioners Chilled water systems Chillers Dehumidifiers Mobile dehumidifiers Swimming pool dehumidifier HEATING Hot air heating systems Mobile hot air heating systems Stationary hot air heating systems NEW ENERGIES Heat pump systems Heat pumps Heat pump packages Quality with systems
  • 3. 3 Product overview Page Series 4 - 19 Heat pumps 4 - 11 Function WKF 12 - 13 The intelligent control Smart-Control 14 - 15 Technical data WKF-compact 16 - 17 Technical data WKF 18 - 19 Technical data WKF Duo 20 - 21 Indoor units for heating and cooling 20 - 21 Wall and ceiling chests KWK-4R 22 - 47 Heat pump packages 22 - 41 Heat pump packages WKF 42 - 43 Solar collectors RSK 44 - 47 Heat pump solar packages WKF 48 - 49 Tank systems 50 - 55 Accessories Inspected heat pumps with EHPA quality seal of approval REMKO's ArtStyle heat pumps are listed by the European Heat Pump Association (EHPA – former- ly D-A-CH) in its seal of approval list! REMKO's heat pumps thus fulfil high international standards and guarantee performance num- bers you can count on! ErP-ready Starting in September 2015, the energy efficiency label will be used to indicate the economic efficiency of all heating systems. REMKO already uses the label for all heat pumps. ErP Ready Energie Effizienz Klasse A++ SG-ready The Multitalent REMKO Smart-Control is designed for use in the intelligent Smart-Grid power mains.
  • 4. 4 Electrical drive energy * * Heating 25% 75%free solar energy from the air Use energy from the air all year round INDEPENDENT FROM OIL AND GAS In contrast to other heating systems, the acquisition costs for a heat pump in new or old buildings pays off relatively quickly. ■ Considerably lower consumption and operating costs ■ Hardly any maintenance costs ■ No costs for chimney and chimney sweep ■ No costs for a tank ■ No costs for a tank room ■ Simple installation The advantages of a heat pump are clear Government subsidies Information about government subsidies can be found under: www.bafa.de www.kfw.de www.foerderdata.de New dimensions in terms of independence The solar energy stored in the air is an inexhaustible source of emission-free power. Heat pumps draw the majority of the energy from the surrounding air. This works even in winter with outside temperatures below zero. Only the drive energy has to be provided by electrical power. 75%* of the heat comes from the air, free of charge * The ratio can vary depending on outdoor temperature and operating conditions. Precise data for the COP value can be found in the technical data.
  • 5. 5 Highly efficient and energy-saving 1/3 Minimal temperature fluctuations mean energy savings Time Temperature The inverter requires only one-third of the time of conventional systems to start up Conventional Inverter The REMKO inverter technology saves money. The REMKO Smart-WP represents a decision for a state-of-the-art solu- tion. Modern inverter technology makes this possible. This pioneering technology au- tomatically adapts the condenser speed variably to the precise cooling or heating requirement. This exact and gentle regulation enables a particularly energy saving, efficient operation with a high seasonal performance factor in comparison to non-inverter systems. In summary: In the event of increased demand, the heat pump works more inten- sively, in the event of reduced de- mand the heat pump switches over to energy-saving mode. This saves money. MODERN INVERTER TECHNOLOGY
  • 6. 6 Heat pump technology The technology of the heat pump is similar to that of a refrigerator - only the principle is reversed. The heat extracted from the air is brought up to a higher temperature level in a refrigerant circuit and is then trans- ferred to the indoor module. Function of outdoor unit The outdoor unit extracts heat from the air. This heat is brought up to a higher tem- perature level in a refrigerant circuit and is then transferred to the heating water in the indoor unit. The condenser speed and fans speed adapt to the precise cooling or heating requirement. Function of indoor unit The indoor unit transfers the heat con- tained in the refrigerant to the floor heating elements or heaters installed in the building. In order to cool, the function of the heat pump is simply reversed. FUNCTION Evaporation Liquefying Condensing Decompression Functional diagram for heating Outdoor unit for heat pump Outdoor area Indoor heat pump unit Indoor area REMKO Smart-WP
  • 7. 7 Heat pumps in new buildings. Independent from oil and gas. Heat pumps for modernisation of existing buildings. Combi- nation with existing heating appliances. Heat pumps in industry. The factory floor is heated and cooled through concrete core activation. Heat pumps for the workshop office. The ideal space-saving solution. WKF-compact series With additional integrated 300-litre domestic water tank. All in one unit. VERSATILE WKF series It couldn't be simpler. Everything is com- pletely installed in a single enclosure. Highly efficient, regulated heating circuit pump, heat exchanger, various fittings, and the Smart-Control control system.
  • 8. 8 Effective domestic water preparation An integrated 300-litre domestic water tank with a large-dimension heat exchanger is build into the unit in the case of the WKF-compact series. For the WKF series, external storage systems are available. Combination with floor heating, modern heaters, and wall-mounted heating systems Heat pumps are able to achieve their highest levels of efficiency when combined with floor heating. With conventional modern radiators, the operat- ing costs are lower than for oil or gas heating appliances. This means that cosy heating is guaranteed even at lower outside temperatures. Solar station Circulation Chilledwater Outdoorprobe Inverted rectifier, photovoltaic system Hot water Outdoor unit REMKO Smart-WP indoor unit Combination with tanks systems The interface and collection point for vari- ous energy systems Tanks are available in various designs and capaci- ties. With connection options for heat pump, solar system, solid material boiler, and domestic water preparation, the storage system is the interface and collection point. Average temperatures in Germany 50 40 30 20 10 0 10 5 0 -5 -10 -15 Outdoor temperature °C Annualheatingperformance% Smart HEAT PUMPS HEAT PUMPS THAT ADAPT TO THE SYSTEM 20 15 29% 7% 1% 1% 39% 18% 5%
  • 9. 9 Floor heating Pleasant climate in the summer In hot weather, the heat pump can be used for cooling. In order to do so, the function of the heat pump is simply reversed. You will find air- conditioning units in the range of accessories. The air-conditioning units work on the convection principle. The technical principle of the air- conditioners is simple: Air flows past the interior heat exchanger and is either heated or cooled. Wall and ceiling chests REMKO KWK series Air-conditioner Heater Solarplant Photovoltaicplant Combination with heat generators in bivalent operation The heat pump can be combined with a heat generator in order to cover peak loads. This appli- ance, for example, can be a gas or oil condensing boiler that can be directly connected to the WKF indoor unit. Combination with a REMKO RSK solar plant for economic domestic water preparation and heating support An ideal combination for a maximum of economic efficiency and environmental protection. Direct solar energy delivers a high percentage of hot water preparation in annual average. Optimised use of photovoltaic current The REMKO Smart-WP can preferably be oper- ated using self-generated photovoltaic current. As a result, not as much expensive current has to be obtained from the mains. This saves money and the dependency on current price increases decreases.
  • 10. 10 The compact class saves space and installation effort The REMKO Smart-WP is perfectly suited for new buildings in com- bination with underfloor heating. WKF-compact does not require a large mounting area due to its compact construction. This construc- tion saves space in the mounting area. The costs for installation are reduced by the high percentage of premounted components. REMKO Smart-WP WKF-compact SERIES The heat pump with integrated 300-litre domestic water tank for high hot water comfort Housing solution with EPP Through the consistent use of EPP moulded parts, insulation is increased and the loss of energy is minimised. In addition, considerable weight advantages result. The front consists of a lacquered design front panel. Profit from these advantages: ■ Heating and cooling ■ Low investment costs ■ Power-modulated opera- tion due to modern inverter mode ■ Low operating costs due to high COP value (see technical data) ■ Ready for connection of solar system to drinking water supply ■ Mounting-friendly instal- lation All connections are located at the top. ■ Intelligent defrosting logic circuit ■ Integrated electronic bypass valve for guaranteeing the minimum volume flow rate ■ High hot water comfort through integrated, enam- elled domestic water tank with a volume of 300 litres (BEVB 1.19 kWh/day) ■ Smart-Control intelligent control system Use in intelligent Smart-Grid power mains possible ■ Technical unit handover/ CheckServ by REMKO Tech- nical Service possible ■ Integrated heating circuit pump for the supply of the heating system ■ Night operation to reduce noise ■ Visualization of the outdoor unit parameters ■ Chimney sweep function
  • 11. 11 Free choice when installing the outdoor units You save a lot of space when installing the outdoor modules externally. You can use the basement space for other purposes such as a party room or sauna. Outdoor installation is ideal for buildings without a basement. WKF outdoor units Cosy heat in the winter, a pleasant climate in the summer Winters are getting warmer and summers hotter. Tem- peratures of over +30°C are no longer uncommon in summer. This means that in addition to heating, cooling is taking on an ever more important role. One more rea- son to install a REMKO heat pump. In winter, the heat pump operates as an efficient heating system, whilst, in summer, the water-bearing system ensures for comfort- able air conditioning. WKF-compact series with integrated 300-litre domestic water tank, output between 1.1 and 17.7 kW
  • 12. 12 The future is smart Diagrams and energy balance sheets (Smart-Count) Animated building diagram with installed components Smart-Com for integration into a Smart Home system Remote control via the Internet (Smart-Web) REMKO Smart-Control with TFT screen Ready for 24h operation The intelligent Multitalent is an efficient overall system. Connection to all regenerative energies is possible. Whether heat pumps, solar energy, or photo- voltaics, anything can be integrated. Use in a Smart-Grid or Smart Home system, such as KNX, is possible. The controller offers extensive setting possibilities. ■ Time programming of night operation to reduce noise ■ Graphic representation of the heating curve ■ Display of the outdoor unit parameters ■ Activation of the chimney sweep function ■ Control of four mixed heating circuits ■ Integrated dew point control
  • 13. 13 Easy operation via softkeys and rotary knob ■ Integration of photovoltaic current into the system ■ Night operation mode to reduce noise ■ Solar connection ■ Integration of the air-condition- ing function into the system ■ 2 mixed heating circuits ■ Connection of several heat generators Intelligent and highly efficient Chimney sweep button to activate the second WE for exhaust gas measurement Service wizard for visualisation of the operating states Installation wizard for simplifying commissioning ■ Integration into a Smart Home system ■ Dynamic hygiene function External data memory Operating instructions can be called using a central information button.
  • 14. 14 Smart-HEAT PUMPS WKF-compact series European uality Label for Heat Pumps EHPA / D-A-CH The compact class saves space and installation effort WKF-compact series does not require a large mounting area due to its compact construction and integrated components. In connection with underfloor heating, this unit is perfectly suited for new buildings. This construction saves space in the mounting area. The costs for installation are reduced by the high percentage of premounted components. Scope of supply ■ REMKO Smart-Control – the intelligent control system ■ indoor unit with integrated 300-litre domestic water tank (BEVB 1.19 kWh/day) ■ Outdoor unit with inverter technology ■ Highly efficient, controlled heating circuit pump ■ Industrial water set, includ- ing 3-way changeover valve ■ Dirt filter 1" ■ 2 shut-off valves 1" and thermometer ■ Safety group with SIV, automatic bleeding valve and pressure gauge ■ Outdoor sensor/immersion probe ■ Electrically controlled bypass mixer ■ Prepared (flange) for solar drinking water heating Profit from these advantages ■ Low investment costs ■ Power-modulated operation due to modern inverter mode ■ Low operating costs due to high COP value (see technical data) ■ Ready for connection of solar system to drinking water supply ■ Mounting-friendly installation All connections are located at the top. ■ Heating and cooling ■ High hot-water comfort due to integrated, enamelled WKT 300 domestic water tank with a volume of 300 litres ■ Extremely low heating losses of the WKT 300 domestic water tank BEVB 1.19 kWh/day ■ Electric booster heating 49 W ■ Energy efficiency rating A ■ Smart-Control intelligent control system Use in intelligent Smart-Grid power mains possible ■ Technical unit handover by REMKO Technical Service possible ■ Integrated heating circuit pump for the supply of the heating system ■ Integrated electronic bypass valve for guaranteeing the minimum volume flow rate ■ Intelligent thawing logic circuit ■ Monoenergetic operation possible through REMKO Smart-Serv or bivalent opera- tion possible through REMKO Smart-BVT ■ Night operation to reduce noise ■ Chimney sweep function ErP Ready Energy A++ Efficiency Rating
  • 15. 15 Technical data and prices Area of use: heating 5) 2-7 kW 7-12 kW 12-18 kW Series WKF 70 compact WKF 120 compact WKF 180 compact Design Single split Single split Single split System Air / water Air / water Air / water Operating mode Heating / cooling Heating / cooling Heating / cooling Testing EHPA EHPA EHPA Inverter technology Series Series Series Smart Control Series Series Series Preparation for domestic water Series Series Series Domestic water tank WKT 300 (enamelled) integrated Litre 300 300 300 Heat exchanger area, domestic water tank m² 3.5 3.5 3.5 Number of indoor units/outdoor units 1/1 1/1 1/1 Night operation (power control) Series Series Series Service limits, heating °C -20 to +35 -20 to +35 -20 to +35 Rated heating capacity (min. / max.) kW 6.0 (0.9 - 6.0) 10.0 (2.5 - 12.5) 14.0 (3.1 - 17.7) Energy efficiency rating for heating 4) A++ / A++ A++ / A+ A++ / A++ Rated heating capacity / COP for A7/W35 1) kW / - 5.45 / 4.6 9.86 / 4.4 14.02 / 4.5 Rated heating capacity / COP for A2/W35 1) kW / - 4.61 / 3.5 6.95 / 3.6 9.32 / 3.5 Rated heating capacity / COP for A-7/W35 1) kW / - 4.50 / 2.8 6.14 / 2.9 8.20 / 2.9 Max. supply temperature, heating water °C + 55 + 55 + 55 Service limits, cooling °C +15 to +45 +15 to +45 +15 to +45 Rated cooling capacity (min. / max.) kW 5.0 (1.1 - 8.9) 6.0 (3.3 - 11.9) 11.0 (5.5 - 14.0) Rated cooling capacity / EER for A35/W7 1) kW / - 4.90 / 2.8 6.79 / 2.3 12.20 / 2.6 Rated cooling capacity / EER for A35/W18 1) kW / - 6.70 / 3.6 5.30 / 3.7 12.77 / 3.8 Rated cooling capacity / EER for A27/W18 1) kW / - 6.80 / 3.9 9.46 / 3.6 18.20 / 4.1 Min. supply temperature, cooling water °C + 7 + 7 + 7 Refrigerant 2) R410A R410A R410A Basic refrigerant filling volume / CO2 equivalent kg/t 1.2 / 2.5 2.0 / 4.2 2.85 / 5.8 Refrigerant connections Inch 3/8 / 5/8 3/8 / 5/8 3/8 / 5/8 Max. refrigerant line length m 30 50 75 Max. refrigerant line height m 20 30 30 Voltage supply V/Hz 230/1~/50 230/1~/50 400/3~/50 Rated current consumption for A7/W35 kW 1.18 2.22 3.09 Rated current consumption for A7/W35 A 5.19 10.44 5.02 On-site fuse protection (outdoor unit) A slow-acting 20 20 3x16 Rated flow rate of water at ∆t 5 K m³/h 0.95 1.7 2.4 External maximum pressure loss (heating system) kPa 80 80 80 Max. operating pressure, water bar 3.0 3.0 3.0 Hydraulic connection, inlet flow/return line, flat-sealing Inch 1/4" AG 1/4" AG 1/4" AG Pipeline diameter to be used on site, Cu pipe mm 28 28 35 Sound power level LwA (outdoor unit) rated/max. dB(A) 63.2/66.0 67.9/69.0 68.3/69.8 Sound pressure level LpA rated/max. 3) dB(A) 38.2 / 41.0 42.9 / 44.0 42.3 / 45.2 Max. sound pressure level LwA (outdoor unit), night operation 3) dB(A) 38.0 39.9 39.3 Outdoor unit, standard colour Grey-white Grey-white Grey-white Dimensions indoor unit Height / width / depth mm 1928/800/790 1928/800/790 1928/800/790 Dimensions outdoor unit Height / width / depth mm 640/880/310 1010/940/330 1430/940/330 Weight indoor unit / outdoor unit kg 236/50 238/74 240/100 Series WKF 70 compact WKF 120 compact WKF 180 compact Ref. no. 254030 255020 255030 Serial colour of outdoor unit: silver Ref. no. 254040 255025 255035 1) COP / EER according to EN 14511, 2) GWP = 2088 3) Distance 5m, full sphere, A7/W55 4) Average, composite system W35/55°C including Smart Control 5) Total heating requirement, intake flow line 35°C, monoenergetic Accessories Series WKF 70 compact WKF 120 compact WKF 180 compact REMKO Smart-Count – Factory-installed heat meter for the separate counting of the quantity of heat of heating and hot water 259010 259010 259010 REMKO Smart-Com – Additional software for the integration of the heat pump into a smart home system such as KNX via the Ethernet interface of Smart Con- trol, including the heat meter installed at the factory (Smart Count) 254090 254090 254090 REMKO Smart-BVT, factory-installed BVT pipe assembly, 3-way switchover valve for the integration of a second heat generator (max. 22 kW) without a circulation pump, bivalently alternating operation. Note: No combination with REMKO Smart-Serv possible. Only in combination with buffer tank. 254050 259012 259013 REMKO SmartServ – Intelligent provision, installed heating rod 9 kW for monoenergetic operation, including emergency heating functions Note: No combination with REMKO Smart-BVT possible. 254059 259022 259023 REMKO Smart-Cool – for active cooling. Pipe subassemblies and circulation pump in the indoor unit with vapour density insulation. Use in case of cooling function when the inlet temperature is below the dew point. 259085 259085 259085 For additional accessories, see page 50
  • 16. 16 Profit from these advantages: ■ Low investment costs ■ Smart-Inverter power-modulating mode. This saves money. ■ Low operating costs due to high COP value (see technical data) ■ Heating and cooling ■ Mounting-friendly installa- tion All connections from the top. ■ Night operation to reduce noise ■ Smart-Control intelligent control system Use in intelligent Smart-Grid power mains possible ■ Technical unit handover by REMKO Technical Service possible ■ Monoenergetic operation possible through REMKO Smart-Serv or bivalent operation possible through REMKO Smart-BVT ■ Chimney sweep function It couldn't be simpler. Everything complete in an indoor unit Everything is installed in a single housing: Highly efficient circula- tion pump, heat exchanger, various fittings, and the Smart-Con- trol control system. In connection with existing tank systems, the WKF Duo series is prefect for new buildings and renovations. Smart-HEAT PUMPS WKF series European uality Label for Heat Pumps EHPA / D-A-CH Scope of supply ■ REMKO Smart-Control – the intelligent control system ■ Indoor unit ■ Outdoor unit with inverter technology ■ Highly efficient, controlled heating circuit pump ■ Dirt filter 1" ■ 2 shut-off valves 1" and thermometer ■ Safety group with SIV, automatic bleeding valve and pressure gauge ■ Outdoor sensor/immer- sion probe ■ Electrically controlled bypass mixer ErP Ready Energy A++ Efficiency Rating
  • 17. 17 Technical data Area of use: heating 5) 2-7 kW 7-12 kW 12-18 kW Series WKF 70 WKF 120 WKF 180 Design Single split Single split Single split System Air / water Air / water Air / water Operating mode Heating / cooling Heating / cooling Heating / cooling Testing EHPA EHPA EHPA Inverter technology Series Series Series Smart Control Series Series Series Preparation for domestic water Series Series Series Domestic water tank WKT 300 (enamelled) integrated – – – Heat exchanger area, domestic water tank m² – – – Number of indoor units/outdoor units 1/1 1/1 1/1 Night operation (power control) Series Series Series Service limits, heating °C -20 to +35 -20 to +35 -20 to +35 Rated heating capacity (min. / max.) kW 6.0 (0.9 - 6.0) 10.0 (2.5 - 12.5) 14.0 (3.1 - 17.7) Energy efficiency rating for heating 4) A++ / A++ A++ / A+ A++ / A++ Rated heating capacity / COP for A7/W35 1) kW / - 5.46 / 4.6 9.86 / 4.4 14.02 / 4.5 Rated heating capacity / COP for A2/W35 1) kW / - 4.61 / 3.5 6.95 / 3.6 9.32 / 3.5 Rated heating capacity / COP for A-7/W35 1) kW / - 4.50 / 2.8 6.14 / 2.9 8.20 / 2.9 Max. supply temperature, heating water °C + 55 + 55 + 55 Service limits, cooling °C +15 to +45 +15 to +45 +15 to +45 Rated cooling capacity (min. / max.) kW 5.0 (1.1 - 8.9) 6.0 (3.3 - 11.9) 11.0 (5.5 - 14.0) Rated cooling capacity / EER for A35/W7 1) kW / - 2) 4.90 / 2.8 6.79 / 2.3 12.20 / 2.6 Rated cooling capacity / EER for A35/W18 1) kW / - 2) 6.70 / 3.6 5.30 / 3.7 12.77 / 3.8 Rated cooling capacity / EER for A27/W18 1) kW / -2) 6.80 / 3.9 9.46 / 3.6 18.20 / 4.1 Min. supply temperature, cooling water °C + 7 + 7 + 7 Refrigerant 2) R410A R410A R410A Basic refrigerant filling volume / CO2 equivalent kg/t 1.2 / 2.5 2.0 / 4.2 2.85 / 5.8 Refrigerant connections Inch 3/8 / 5/8 3/8 / 5/8 3/8 / 5/8 Max. refrigerant line length m 30 50 75 Max. refrigerant line height m 20 30 30 Voltage supply V/Hz 230/1~/50 230/1~/50 400/3~/50 Rated current consumption for A7/W35 kW 1.18 2.22 3.09 Rated current consumption for A7/W35 A 5.19 10.44 5.02 On-site fuse protection (outdoor unit) A slow-acting 20 20 3x16 Rated flow rate of water at ∆t 5 K m³/h 0.95 1.7 2.4 External maximum pressure loss (heating system) kPa 80 80 80 Max. operating pressure, water bar 3.0 3.0 3.0 Hydraulic connection, inlet flow/return line, flat-sealing Inch 1/4" AG 1/4" AG 1/4" AG Pipeline diameter to be used on site, Cu pipe mm 28 28 35 Sound power level LwA (outdoor unit) rated/max. dB(A) 63.2/66.0 67.9/69.0 68.3/69.8 Sound pressure level LpA rated/max. 3) dB(A) 38.2 / 41.0 42.9 / 44.0 42.3/45.2 Max. sound pressure level LwA (outdoor unit), night operation 3) dB(A) 38.0 39.9 39.3 Outdoor unit, standard colour Grey-white Grey-white Grey-white Dimensions indoor unit Height / width / depth mm 500/800/500 500/800/500 500/800/500 Dimensions outdoor unit Height / width / depth mm 640/880/310 1010/940/330 1430/940/330 Weight indoor unit / outdoor unit kg 41/47.5 43/74 45/100 Series WKF 70 WKF 120 WKF 180 Ref. no. 254010 255050 255060 Serial colour of outdoor unit: silver Ref. no. 254020 255055 255065 1) COP / EER according to EN 14511, 2) GWP = 2088 3) Distance 5m, full sphere, A7/W55 4) Average, composite system W35/55°C including Smart Control 5) Total heating requirement, intake flow line 35°C, monoenergetic Accessories Series WKF 70 WKF 120 WKF 180 REMKO Smart-Count – Factory-installed heat meter for the separate counting of the quantity of heat of heating and hot water 259010 259010 259010 REMKO Smart-Com – Additional software for the integration of the heat pump into a smart home system such as KNX via the Ethernet interface of Smart Control, including the heat meter installed at the factory (Smart Count) 254090 254090 254090 REMKO Smart-BVT– Factory-installed BVT pipe assembly, 3-way switchover valve for the integration of a second heat generator (max. 22 kW) without a circulation pump, bivalently alternating operation. Note: No combination with REMKO Smart-Serv possible. Only in combination with buffer tank. 254053 259015 259016 REMKO Smart-Serv – Intelligent provision, installed heating rod 9 kW for monoenergetic operation, including emergency heating functions Note: No combination with REMKO Smart-BVT possible. 254060 259025 259026 REMKO Smart-Cool – for active cooling. Pipe subassemblies and circulation pump in the indoor unit with vapour density insulation. Use in case of cooling function when the inlet temperature is below the dew point. 259085 259085 259085 For additional accessories, see page 50
  • 18. 18 Profit from these advantages ■ Low investment costs ■ Smart-Inverter power-modulated mode. This saves money. ■ Low operating costs due to high COP value (see technical data) ■ Heating and cooling ■ Mounting-friendly installa- tion All connections from the top. ■ Intelligent control system Use of Smart-Control in intelligent Smart Grid power mains possible ■ Technical unit handover by REMKO Technical Service possible ■ Monoenergetic operation through REMKO Smart-Serv ■ Night operation to reduce noise ■ Chimney sweep function ■ Bivalently alternating opera- tion using Smart-BVT exter- nally It couldn't be simpler. Everything complete in an indoor unit Everything is installed in a single housing: Two highly efficient circulation pumps, two heat exchangers, various fittings, and the Smart-Control control system. In connection with exist- ing tank systems, the WKF Duo is prefect for new buildings and renovations. Smart-HEAT PUMPS WKF Duo Series European uality Label for Heat Pumps EHPA / D-A-CH Scope of supply ■ REMKO Smart-Control—the intelligent control system ■ Indoor unit ■ 2 outdoor units with inverter technology ■ 2 highly efficient, controlled heating circuit pumps ■ Dirt filter 1 1/2" ■ 2 shut-off valves 1 1/2" and thermometer ■ Safety group with SIV, automatic bleeding valve and pressure gauge ■ Outdoor sensor/immer- sion probe ■ Electrically controlled bypass mixer ErP Ready Energy A++ Efficiency Rating
  • 19. 19 Accessories Series WKF 120 DUO WKF 180 DUO REMKO Smart-Count Factory-installed heat meter for the separate counting of the quantity of heat of heating and hot water 259010 259010 REMKO Smart-Com Additional software for the integration of the heat pump into a smart home system such as KNX via the Ethernet interface of Smart Control, including the heat meter installed at the factory (Smart Count) 254090 254090 REMKO Smart-Serv Intelligent provision, installed heating rod 9 kW for monoenergetic opera- tion, including emergency heating functions Note: No combination with REMKO Smart-BVT possible. 259029 259027 REMKO Smart-Cool for active cooling. Pipe subassemblies and circulation pump in the indoor unit with vapour density insulation. Use in case of cooling function when the inlet temperature is below the dew point. 259086 259086 For additional accessories, see page 50 Technical data Area of use: heating 5) 18-25 kW 25-32 kW Series WKF 120 DUO WKF 180 DUO Design Duo Split Duo Split System Air / water Air / water Operating mode Heating / cooling Heating / cooling Testing EHPA EHPA Inverter technology Series Series Smart Control Series Series Preparation for domestic water Series Series Domestic water tank (enamelled) integrated - - Heat exchanger area, domestic water tank m² - - Number of indoor units/outdoor units 1/2 1/2 Night operation (power control) Series Series Service limits, heating °C -20 to +35 -20 to +35 Rated heating capacity (min. / max.) kW 18.0 (2.5 - 25.0) 29.0 (3.1 - 35.4) Energy efficiency rating for heating 4) A++ / A+ A++ / A++ Rated heating capacity / COP for A7/W35 1) kW / - 19.72 / 4.4 28.04 / 4.5 Rated heating capacity / COP for A2/W35 1) kW / - 13.90 / 3.6 18.64 / 3.5 Rated heating capacity / COP for A-7/W35 1) kW / - 12.28 / 2.9 16.40 / 2.9 Max. supply temperature, heating water °C + 55 + 55 Service limits, cooling °C +15 to +45 +15 to +45 Rated cooling capacity (min. / max.) kW 13.0 (3.3 - 23.8) 24.0 (5.5 - 28.0) Rated cooling capacity / EER for A35/W7 1) kW / - 13.58 / 2.3 24.40 / 2.6 Rated cooling capacity / EER for A35/W18 1) kW / - 10.60 / 3.7 25.54 / 3.8 Rated cooling capacity / EER for A27/W18 1) kW / - 18.92 / 3.6 36.40 / 4.1 Min. supply temperature, cooling water °C + 7 + 7 Refrigerant R410A R410A Basic refrigerant filling volume for each outdoor unit / CO2 equivalent kg/t 2.0 / 4.2 2.85 / 5.8 Refrigerant connections for each outdoor unit Inch 3/8 / 5/8 3/8 / 5/8 Max. refrigerant line length per outdoor unit m 50 75 Max. refrigerant line length per outdoor unit m 30 30 Voltage supply for each outdoor unit V/Hz 230/1~/50 400/3~/50 Rated current consumption for A7/W35 kW 2 x 2,22 2 x 3.09 Rated current consumption for A7/W35 A 2 x 10,44 2 x 5.02 On-site fuse protection (outdoor unit) A slow-acting 2 x 20 6 x 16 Rated flow rate of water at ∆t 5 K m³/h 2 x 1,7 2 x 2.4 External maximum pressure loss (heating system) kPa 80 80 Max. operating pressure, water bar 3.0 3.0 Hydraulic connection, supply/return line Inch 1½" AG 1½" AG Pipeline diameter to be used on site, Cu pipe mm 42 42 Sound power level LwA (per outdoor unit) rated/max. dB(A) 67.9/69.0 68.3/69.8 Sound power level LpA (per outdoor unit) rated/max. 3) dB(A) 42.2/44.0 42.4/45.2 Max. sound pressure level LwA (per outdoor unit), night operation 3) dB(A) 38.9 39.3 Outdoor unit, standard colour Grey-white Grey-white Dimensions indoor unit Height / width / depth mm 1000/800/500 1000/800/500 Dimensions outdoor unit Height / width / depth mm 1010/940/330 1430/940/330 Weight indoor unit / outdoor unit kg 78 / 2 x 74 82 / 2 x 100 Series WKF 120 DUO WKF 180 DUO Ref. no. 255063 255070 Serial colour of outdoor unit: silver Ref. no. 255064 255075 1) COP / EER according to EN 14511, 2) GWP = 2088 3) Distance 5m, full sphere, A7/W55 4) Average, composite system W35/55°C including Smart Control 5) Total heating requirement, intake flow line 35°C, monoenergetic
  • 20. 20 REMKO KWK-4R The wall and ceiling chests are characterised by a discreet design In combination with the REMKO heat pump, the wall and ceiling chests are excellently suited for the renovation of heating systems, as well as for new construction. Despite low inlet temperatures, the units quickly generate heat. In this way, the system can react to fluctuations in the outdoor temperatures quickly and dynamically. The REMKO wall or ceiling chests work efficiently and thus require only low inlet temperatures during heating operations – the ideal supplement to low-temperature systems, such as heat pumps. They are excellently suited as an efficient replacement for heaters in old buildings or for conversions in order to lower high inlet tempera- tures to an economical value. In summer, the units can also be used for cooling. In this way, they supply pleasant, draft-free, and cool air to the room. They can optionally be used for vertical installa- tion into the wall or horizontal installation below the ceiling and are excellently suited for installation into private living areas. An extremely low-noise three-stage tangential fan provides impec- cable air distribution and maximises vent output. The copper-alu- minium register is designed for medium temperatures of up to 80°C. Due to the large heat exchanger, an effective heating operation is guaranteed at low inlet temperatures. Cooling capacity KWK 100-4R KWK 150-4R KWK 250-4R KWK 400-4R Intake °C Qges kW Qges kW Qges kW Qges kW Fan setting 1 2 3 1 2 3 1 2 3 1 2 3 7 0.83 0.93 1.18 1.22 1.27 1.59 1.57 1.69 2.21 1.95 2.05 2.73 10 0.53 0.62 0.78 0.78 0.81 1.04 1.10 1.18 1.54 1.22 1.31 1.86 14 0.37 0.42 0.54 0.54 0.57 0.72 0.69 0.75 1.03 0.86 0.95 1.27 18 0.26 0.29 0.38 0.37 0.40 0.45 0.42 0.45 0.54 0.51 0.57 0.68 Heating capacities KWK 100-4R KWK 150-4R KWK 250-4R KWK 400-4R Intake °C Qges kW Qges kW Qges kW Qges kW Fan setting 1 2 3 1 2 3 1 2 3 1 2 3 35 0.48 0.53 0.66 0.73 0.76 0.97 0.97 1.06 1.40 1.18 1.25 1.68 40 0.69 0.78 1.02 1.05 1.10 1.40 1.37 1.48 1.97 1.67 1.76 2.37 45 0.91 1.03 1.35 1.36 1.42 1.80 1.75 1.90 2.53 2.14 2.25 3.05 50 1.13 1.27 1.66 1.66 1.74 2.21 2.13 2.31 3.09 2.60 2.74 3.71 Regulation REMKO KWK wall and ceiling chests can be regulated by a room temperature controller. The controller is functional and easy to oper- ate. Two mounting variants are available: for installation into the chest or for surface mounting onto the wall. The regulation of the room temperature controller can be implemented by switching the fan on and off. WALL AND CEILING CHESTS ■ The ideal solution for opti- cally discreet air conditioning ■ Low-noise appliance opera- tion ■ Service-friendly unit struc- ture KWK-4R series for heating and cooling Precision room tempera- ture control for surface installation ■ For horizontal and vertical installations ■ Extensive accessories avail- able Accessories (see page 54)
  • 21. 21 Technical data Wall and ceiling chests KWK 100-4R KWK 150-4R KWK 250-4R KWK 400-4R Heating capacity 1) 3) / 6) kW 1.35/0.66 1.80/0.97 2.53/1.40 3.05/1.68 Cooling capacity 1) 2) kW 1.18 1.59 2.21 2.73 Air flow rate per speed setting m³/h 128/147/200 184/194/254 232/254/353 283/300/423 Sound pressure level per speed setting 5) dB(A) 25.5/28.5/34.5 25.5/32.5/36.5 26.5/27.5/36.5 25.5/26.5/34.5 Voltage supply V/Hz 230/1~/50 Electr. rated power consumption kW 0.04 0.03 0.05 0.05 Electr. nominal current consumption A 0.11 0.07 0.14 0.20 Operating medium Water Max. operating pressure kPa 600 600 600 600 Medium connectors - cooling register Inch 1/2 1/2 1/2 1/2 Rated flow volume, medium C/H6) m³/h 0.20/0.15 0.27/0.17 0.38/0.24 0.47/0.29 Rated pressure drop, indoor C/H kPa 1.2/0.6 3.3/1.6 6.7/4.0 5.5/2.9 Medium volume L 0.6 0.9 1.3 1.5 Dimensions - height mm 480 480 480 480 Dimensions - width mm 660 810 960 1100 Dimensions - depth mm 220 220 220 220 Weight kg 14.0 17.0 20.0 23.0 Serial colour white white white white Wall and ceiling chests KWK 100-4R KWK 150-4R KWK 250-4R KWK 400-4R Ref. no. 1663100 1663150 1663250 1663400 For additional accessories, see page 54 1) Rated flow rate, medium; max. air flow rate 2) Room temperature TK 27°C, FK 19°C; medium inlet 7°C, medium outlet 12°C 3) Room temperature TK 20 °C, FK 14 °C; medium inlet 45 °C, medium outlet 40 °C 5) Measured in a 100m3 room with a reverberation period of 0.3 seconds, distance of 1.5 m 6) Room temperature TK 20 °C, FK 14 °C; medium inlet 35 °C, medium outlet 30 °C Dimensions A B C KWK 100-4R 660 480 220 KWK 150-4R 810 480 220 KWK 250-4R 960 480 220 KWK 400-4R 1100 480 220 B A C KWK 100-400-4R Dimensions
  • 22. 22 Package consisting of: HEAT PUMP PACKAGES Type: Stuttgart Heat pump package – Type Stuttgart for WKF 70-180 compact unit series If the heat pump is intended to serve as a sole heat generator, this heat pump package is the ideal solution. In connection with underfloor heating, this unit is perfectly suited for new buildings. In addition to the heating function, a cooling function can be provided when necessary. In this package, the drinking water preparation takes place in a 300-litre drinking water tank integrated into the in- door module. Through the compact design, installation expenses are extremely low. The highly efficiently controlled heating circuit pump in the indoor unit can supply the heating circuits directly with water. Information about government subsidies can be found under: www.bafa.de www.kfw.de www.foerderdata.de Condensate drip tray for outdoor unit with oil separator Package consisting of: ■ Indoor unit with inte- grated 300-litre WKT 300 domestic water tank (BEVB 1.19 kWh/day) ■ Outdoor unit For scope of supply, see p. 14 ■ Condensate drip tray, including oil separator for outdoor unit Cooling HeatingHot water Surface cooling / surface heating Night operation ErP Ready Energy A++ Efficiency Rating 22
  • 23. 23 Hydraulic system diagram of Stuttgart (example of monoenergetic operation) Indoor unit Outdoorprobe Outdoor unit Chilled water ZWP Hot water Cooling circuit Heating circuit Mixed Technical data Area of use: heating 1) 4-7 kW 8-11 kW 12-18 kW Heat pump package, Type Stuttgart WKF 70 compact WKF 120 compact WKF 180 compact Rated heating capacity (min. / max.) kW 6.0 (0.9 - 6.0) 10.0 (2.5 - 12.5) 14.0 (3.1 - 17.7) Rated cooling capacity (min. / max.) kW 5.0 (1.1 - 8.9) 6.0 (3.3 - 11.9) 11.0 (5.5 - 14.0) Energy efficiency rating of HZ/WW/Smart Control composite system A++/A A+/A A++/A External maximum pressure loss kPa 80 80 80 Series WKF 70 compact WKF 120 compact WKF 180 compact Ref. no. 254100 256015 256020 1) Total heating requirement, intake flow line 35°C, monoenergetic Accessories Series WKF 70 compact WKF 120 compact WKF 180 compact REMKO Smart-Count Factory-installed heat meter for the separate counting of the quantity of heat of heating and hot water 259010 259010 259010 REMKO Smart-Com Additional software for the integration of the heat pump into a smart home system such as KNX via the Ethernet interface of Smart Control, including the heat meter installed at the factory (Smart Count) 254090 254090 254090 REMKO Smart-Serv Intelligent provision, installed heating rod 9 kW for monoenergetic operation, including emergency heating functions 254059 259022 259023 REMKO Smart-Cool for active cooling. Pipe subassemblies and circulation pump in the indoor unit with vapour density insulation. Use in case of cooling function when the inlet temperature is below the dew point. 259085 259085 259085 For additional accessories, see page 50
  • 24. 24 Package consisting of: HEAT PUMP PACKAGES Type: Mannheim Heat pump package – Type Mannheim for WKF 70-180 compact appliance series This heat pump package is designed for users who would like to operate the heat pump in combination with a conventional heat generator (bivalently alternating). The additional KPS 300 buffer tank is used for the hydraulic decoupling of large volume flow rates. A cooling function for the summer can also be activated, if necessary. In this package, the domestic water preparation takes place in the 300-litre domestic water tank integrated into the indoor unit. Through the compact design, installation expenses are extremely low. The separate pump assemblies HGU/HGM (can be ordered sepa- rately) for the heating circuits are equipped with a high-efficiency pump (0-10 V) regulated in a needs-based manner. Information about government subsidies can be found under: www.bafa.de www.kfw.de www.foerderdata.de Package consisting of: ■ Indoor unit with inte- grated 300-litre WKT 300 domestic water tank (BEVB 1.19 kWh/day) ■ Outdoor unit For scope of supply, see p. 14 ■ Condensate drip tray, including oil separator for outdoor unit ■ Buffer tank for hot water KWS 300 (300 litres) ■ Immersion probe Buffer tank for cooling and hot water KPS 300 (300 l) Condensate drip tray for outdoor unit with oil separator HeatingHot water Cooling BivalentSurface cooling/ surface heating Night operation ErP Ready Energy A++ Efficiency Rating 24
  • 25. 25 S 08 Hydraulic system of Mannheim (example for monoenergetic or alternative bivalent operation) Indoor unit Outdoorprobe Outdoor unit Chilled water HGU HGMZWP HGM KPS 300 Hot water Heating circuit Non-mixed- Heating circuit Mixed Heating circuit Mixed Technical data Area of use: heating 1) 4-7 kW 8-11 kW 12-18 kW Heat pump package, Type Mannheim WKF 70 compact WKF 120 compact WKF 180 compact Rated heating capacity (min. / max.) kW 6.0 (0.9-6.0) 10.0 (2.5 - 12.5) 14.0 (3.1 - 17.7) Rated cooling capacity (min. / max.) kW 5.0 (1.1 - 8.9) 6.0 (3.3 - 11.9) 11.0 (5.5 - 14.0) Energy efficiency rating of HZ/WW/Smart Control composite system A++/A A+/A A++/A External maximum pressure loss kPa 80 80 80 Series WKF 70 compact WKF 120 compact WKF 180 compact Ref. no. 254110 256030 256035 1) Total heating requirement, intake flow line 35°C, monoenergetic Accessories Series WKF 70 compact WKF 120 compact WKF 180 compact REMKO Smart-Count – Factory-installed heat meter for the separate counting of the quantity of heat of heating and hot water 259010 259010 259010 REMKO Smart-Com – Additional software for the integration of the heat pump into a smart home system such as KNX via the Ethernet interface of Smart Control, including the heat meter installed at the factory (Smart Count) 254090 254090 254090 REMKO Smart-Serv – Intelligent provision, installed heating rod 9 kW for monoenergetic operation, including emergency heating functions 259059 259022 259023 REMKO Smart-BVT– Factory-installed BVT pipe assembly, 3-way switchover valve for the integration of a sec- ond heat generator (max. 22 kW) without a circulation pump, bivalently alternating operation. Note: No combination with REMKO Smart-Serv possible. Only in combination with buffer tank. 254050 259012 259013 REMKO Smart-Cool – For active cooling. Pipe subassemblies and circula- tion pump in the indoor unit with vapour density insulation. Use in case of cooling function when the inlet temperature is below the dew point. 259085 259085 259085 Heating circuit pump set HGU Speed-controlled heating circuit pump group (0-10 V)/unmixed 259035 259035 259035 Heating circuit pump set HGM Speed-controlled heating circuit pump group (0-10 V)/mixed 259036 259036 259036 For additional accessories, see page 50 Cooling circuit Boiler/wall-mounted heating system (max. 22 kW)
  • 26. 26 Package consisting of: Buffer tank for cooling and heating water KPS 300 (300 l) HEAT PUMP PACKAGES Type: Cologne Heat pump package type Cologne for WKF 70-180 appliance series This heat pump package is designed for users who want heating first and foremost. The additional KPS 300 buffer tank is used for the hydraulic decoupling of large volume flow rates. A cooling func- tion for the summer can also be activated, if necessary. Domestic water preparation takes place separately. With this heat pump pack- age, both monoenergetic and bivalently alternating systems can be accommodated. A second heating appliance (oil/gas boiler without pump) can be connected directly to the indoor module. The separate pump assemblies HGU/HGM (can be ordered separately) for the heating circuits are equipped with a high-efficiency pump (0-10 V) regulated in a needs-based manner. Information about government subsidies can be found under: www.bafa.de www.kfw.de www.foerderdata.de Package consisting of: ■ Indoor unit ■ Outdoor unit For scope of supply, see p. 16 ■ Condensate drip tray, including oil separator for outdoor unit ■ Buffer tank for cooling and heating water KPS 300 (300 litres) Condensate drip tray for outdoor unit with oil separator Cooling BivalentHeating Surface cooling/ surface heating Night operation ErP Ready Energy A++ Efficiency Rating 26
  • 27. 27 Technical data Area of use: heating 1) 4-7 kW 8-11 kW 12-18 kW Heat pump package, Type Cologne WKF 70 WKF 120 WKF 180 Rated heating capacity (min. / max.) kW 6.0 (0.9 - 6.0) 10.0 (2.5 - 12.5) 14.0 (3.1 - 17.7) Rated cooling capacity (min. / max.) kW 5.0 (1.1 - 8.9) 6.0 (3.3 - 11.9) 11.0 (5.5 - 14.0) Energy efficiency rating of HZ/WW/Smart Control composite system A+/- A+/- A++/- External maximum pressure loss kPa 80 80 80 Series WKF 70 WKF 120 WKF 180 with KPS 300 Ref. no. 254120 256045 256050 1) Total heating requirement, intake flow line 35°C, monoenergetic Accessories Series WKF 70 WKF 120 WKF 180 REMKO Smart-Count Factory-installed heat meter 259010 259010 259010 REMKO Smart-Com – Additional software for the integration of the heat pump into a smart home system such as KNX via the Ethernet interface of Smart Control, including the heat meter installed at the factory (Smart Count) 254090 254090 254090 REMKO Smart-BVT– Factory-installed BVT pipe assembly, 3-way switchover valve for the integration of a second heat generator (max. 22 kW) without a circulation pump, bivalently alternating operation. Note: No combination with REMKO Smart-Serv possible. Only in combination with buffer tank. 254053 259015 259016 REMKO Smart-Serv – Intelligent provision, installed heating rod 9 kW for monoenergetic operation, including emergency heating functions Note: No combination with REMKO Smart-BVT possible. 254060 259025 259026 REMKO Smart-Cool – For active cooling. Pipe subassemblies and circulation pump in the indoor unit with vapour density insulation. Use in case of cooling function when the inlet temperature is below the dew point. 259085 259085 259085 Heating circuit pump set HGU Speed-controlled heating circuit pump group (0-10 V)/unmixed 259035 259035 259035 Heating circuit pump set HGM Speed-controlled heating circuit pump group (0-10 V)/mixed 259036 259036 259036 For additional accessories, see page 50 S 08 Indoor unit Outdoor unit Cooling circuit Hydraulic system diagram of Cologne (example for monoenergetic or alternative bivalent operation) Outdoorprobe Boiler/wall-mounted heating system (max. 22 kW) Heating circuit Non-mixed Heating circuit Mixed Heating circuit Mixed HGU HGM HGM KPS 300
  • 28. 28 HEAT PUMP PACKAGES Type: Dortmund Heat pump package type Dortmund for WKF 70-180 appliance series This heat pump package is for users who, in addition to the heating function, also want drinking water treatment from their heat pump system. A cooling function for the summer can also be activated, if necessary. In this package, the domestic water preparation takes place in an enamelled 300-litre domestic water Package consisting of: 3-way changeover valve, 5/4" Tank for drinking water heating, enamelled EWS 300 (300 litres) tank. The high-efficiency pump in the indoor module can supply the heating circuits directly with water. Information about government subsidies can be found under: www.bafa.de www.kfw.de www.foerderdata.de Package comprising: ■ Indoor unit ■ Outdoor unit For scope of supply, see p. 16 ■ Buffer tank for domestic hot water, enamelled EWS 300 E (300 litres) ■ 3-way changeover valve ■ Condensate drip tray, including oil separator for outdoor unit Condensate drip tray for out- door unit with oil separator HeatingHot water Cooling Surface cooling/ surface heating Night operation ErP Ready Energy A++ Efficiency Rating 28
  • 29. 29 S 08 Hydraulic system diagram of Dortmund (example for monoenergetic operation) Technical data Area of use: heating 1) 4-7 kW 8-11 kW 12-18 kW Heat pump package, Type Dortmund WKF 70 WKF 120 WKF 180 Rated heating capacity (min. / max.) kW 6.0 (0.9 - 6.0) 10.0 (2.5 - 12.5) 14.0 (3.1 - 17.7) Rated cooling capacity (min. / max.) kW 5.0 (1.1 - 8.9) 6.0 (3.3 - 11.9) 11.0 (5.5 - 14.0) Energy efficiency rating of HZ/WW/Smart Control composite system A++/A A+/A A++/A External maximum pressure loss kPa 80 80 80 Series WKF 70 WKF 120 WKF 180 with EWS 300 E Ref. no. 254130 256060 256065 1) Total heating requirement, intake flow line 35°C, monoenergetic Accessories Series WKF 70 WKF 120 WKF 180 REMKO Smart-Count Factory-installed heat meter for the separate counting of the quantity of heat of heating and hot water 259010 259010 259010 REMKO Smart-Com Additional software for the integration of the heat pump into a smart home system such as KNX via the Ethernet interface of Smart Control, including the heat meter installed at the factory (Smart Count) 254090 254090 254090 REMKO SmartServ Intelligent provision for failures, installed heating rod 9 kW for mono- energetic operation, including emergency heating function 254060 259025 259026 REMKO Smart-Cool for active cooling. Pipe subassemblies and circulation pump in the in- door unit with vapour density insulation. Use in case of cooling function when the inlet temperature is below the dew point. 259085 259085 259085 For additional accessories, see page 50 Indoor unit Outdoor unit Cooling circuit Outdoorprobe Heating circuit Mixed Hot water ZWP Chilled water EWS 300 E
  • 30. 30 Heat pump package type Düsseldorf for WKF 70-180 appliance series This heat pump package is the ideal solution for users who, in addi- tion to the heating function, also want domestic water preparation from their heat pump system. A cooling function for the summer can also be activated, if necessary. The domestic water preparation takes place very efficiently with a 500 litre buffer tank and electroni- cally regulated fresh water station using the hygienic flow method. Package consisting of: Buffer tank for domestic water HPS 500 (500 litres) Fresh water station EFS 25, com- plete with pump and flow switch HEAT PUMP PACKAGES Type: Düsseldorf Condensate drip tray for out- door unit with oil separator The high-efficiency pump in the indoor unit can supply the heating circuits directly with water. Information about government subsidies can be found under: www.bafa.de / www.kfw.de / www.foerderdata.de Package comprising: ■ Indoor unit ■ Outdoor unit For scope of supply, see p. 16 ■ Buffer tank for drinking water HPS 500 (500 litres) ■ Electrically regulated fresh water station EFS 25 (for connection sets, see p.52) ■ 3-way changeover valve ■ Condensate drip tray, including oil separator for outdoor unit 3-way changeover valve, 5/4" For connection sets, see p.52 HeatingHot water Cooling Surface cooling/ surface heating Night operation ErP Ready Energy A++ Efficiency Rating 30
  • 31. 31 S 08 Indoor unit Outdoor unit Cooling circuit Hydraulic system of Düssedorf (example for monoenergetic operation) Outdoorprobe Heating circuit Mixed Hot water Chilled water EFS 25 ZWP HPS 500 Technical data Area of use: heating 1) 4-7 kW 8-11 kW 12-18 kW Heat pump package, Type Düsseldorf WKF 70 WKF 120 WKF 180 Rated heating capacity (min. / max.) kW 6.0 (0.9 - 6.0) 10.0 (2.5 - 12.5) 14.0 (3.1 - 17.7) Rated cooling capacity (min. / max.) kW 5.0 (1.1 - 8.9) 6.0 (3.3 - 11.9) 11.0 (5.5 - 14.0) Energy efficiency rating of HZ/WW/Smart Control composite system A++/A A+/A A++/A External maximum pressure loss kPa 80 80 80 Series WKF 70 WKF 120 WKF 180 Ref. no. 254140 256075 256080 1) Total heating requirement, intake flow line 35°C, monoenergetic Accessories Series WKF 70 WKF 120 WKF 180 REMKO Smart-Count Factory-installed heat meter for the separate counting of the quantity of heat of heating and hot water 259010 259010 259010 REMKO Smart-Com Additional software for the integration of the heat pump into a smart home system such as KNX via the Ethernet interface of Smart Control, including the heat meter installed at the factory (Smart Count) 254090 254090 254090 REMKO Smart-Serv Intelligent provision, installed heating rod 9 kW for monoenergetic operation, including emergency heating functions 254060 259025 259026 REMKO Smart-Cool for active cooling. Pipe subassemblies and circulation pump in the in- door unit with vapour density insulation. Use in case of cooling function when the inlet temperature is below the dew point. 259085 259085 259085 For additional accessories, see page 50
  • 32. 32 Heat pump package type Frankfurt for WKF 70-180 appliance series The energy-saving package is prepared for the integration of solar thermal systems or combustible solid fuel burner for heating and domestic water support. With the fin-tube heat exchanger (special accessory) RWT31, collector surfaces from approx. 8 to 15 m² can be connected. The domestic water preparation takes place with a 800 litre or 1000 litre buffer tank and electronically regulated fresh water station using the hygienic flow method. Package consisting of: Multifunction buffer tank MPS 800 (800 litres) or MPS 1000 (1000 litres) Fresh water station EFS 25, com- plete with pump and flow switch 2 x 3-way changeover valve, 5/4" HEAT PUMP PACKAGES Type: Frankfurt Condensate drip tray for out- door unit with oil separator With this heat pump package, both bivalent and single energy source systems can be accommodated. The separate pump assem- blies HGM/HGU (can be ordered separately) for the heating circuits are equipped with a high-efficiency pump (0-10 V) regulated in a needs-based manner. Package comprising: ■ Indoor unit ■ Outdoor unit For scope of supply, see p. 16 ■ Multifunctional buffer tank MPS 800 (800 litres) or MPS 1000 (1000 litres) ■ Electrically regulated fresh water station EFS 25 (for connection sets, see p. 52) ■ 2 x 3-way switchover valve ■ Immersion probe and collector sensor ■ Condensate drip tray, including oil separator for outdoor unit For connection sets, see p.52 Hot water BivalentPanel heatingHeatingNight operation ErP Ready Energy A++ Efficiency Rating Immersion probe and collector probe 32
  • 33. 33 Technical data Area of use: heating 1) 4-7 kW 8-11 kW 12-18 kW Heat pump package, Type Frankfurt WKF 70 WKF 120 WKF 180 Rated heating capacity (min. / max.) kW 6.0 (0.9 - 6.0) 10.0 (2.5 - 12.5) 14.0 (3.1 - 17.7) Rated cooling capacity (min. / max.) kW 5.0 (1.1 - 8.9) 6.0 (3.3 - 11.9) 11.0 (5.5 - 14.0) Energy efficiency rating of HZ/WW/Smart Control composite system A++/A A+/A A++/A External maximum pressure loss kPa 80 80 80 Series WKF 70 WKF 120 WKF 180 with MPS 800 Ref. no. 254150 256090 256095 with MPS 1000 Ref. no. 254160 256091 256096 1) Total heating requirement, intake flow line 35°C, monoenergetic Accessories Series WKF 70 WKF 120 WKF 180 REMKO Smart-Count Factory-installed heat meter for the separate counting of the quantity of heat of heating and hot water 259010 259010 259010 REMKO Smart-Com – Additional software for the integration of the heat pump into a smart home system such as KNX via the Ethernet interface of Smart Control, including the heat meter installed at the factory (Smart Count) 254090 254090 254090 REMKO Smart-BVT – Factory-installed BVT pipe assembly, 3-way switchover valve for the integration of a second heat generator (max. 22 kW), without a circulation pump, bivalently alternating operation Note: No combination with REMKO Smart-Serv possible. Only in combination with buffer tank. 254053 259015 259016 REMKO Smart-Serv – Intelligent provision, installed heating rod 9 kW for monoenergetic operation, including emergency heating functions Note: No combination with REMKO Smart-BVT possible. 254060 259025 259026 Heating circuit pump set HGM Speed-controlled heating circuit pump group (0-10 V)/mixed 259036 259036 259036 For additional accessories, see page 50 M Indoor unit Outdoor unit Hydraulic system of Frankfurt (example for monoenergetic or bivalently alternating operation) Outdoorprobe Heating circuit Non-mixed Heating circuit Mixed Heating circuit MixedHot water Chilled water EFS 25 RES ZWP MPS 800/1000 Boiler/wall-mounted heating system (max. 22 kW) HGU HGM HGM
  • 34. 34 Package consisting of: Buffer tank for cooling and heating water KPS 300 (300 l) HEAT PUMP PACKAGES Type Cologne Duo Heat pump package - Type Cologne Duo for WKF 120-180 Duo unit series This heat pump package is designed for users who want heating first and foremost. The additional KPS 300 buffer tank is used for the hydraulic decoupling of large volume flow rates. A cooling func- tion for the summer can also be activated, if necessary. Domestic water preparation takes place separately. With this heat pump pack- age, both monoenergetic and bivalently alternating systems can be accommodated. The separate pump assemblies HGU/HGM (can be ordered separately) for the heating circuits are equipped with a high-efficiency pump (0-10 V) regulated in a needs-based manner. Information about government subsidies can be found under: www.bafa.de / www.kfw.de / www.foerderdata.de Package consisting of: ■ Indoor unit ■ 2 outdoor units ■ 2 condensate drip trays, including oil separator for outdoor unit ■ Buffer tank for cooling and heating water KPS 300 (300 litres) Bivalent 2 condensate drip trays for outdoor unit with oil separator Surface cooling/ surface heating Night operation ErP Ready Energy A++ Efficiency Rating Heating Cooling
  • 35. 35 Technical data Area of use: heating 1) 18-25 kW 25-32 kW Heat pump package – Type Cologne Duo WKF 120 DUO WKF 180 DUO Rated heating capacity (min. / max.) kW 18.0 (2.5 - 25.0) 29.0 (3.1 - 35.4) Rated cooling capacity (min. / max.) kW 13.0 (3.3 - 23.8) 24.0 (11.0 - 28.0) Energy efficiency rating of HZ/Smart Control composite system A+/A A++/A Series WKF 120 DUO WKF 180 DUO Ref. no. 256100 256101 1) Total heating requirement, intake flow line 35°C, monoenergetic Accessories Series WKF 120 DUO WKF 180 DUO REMKO Smart-Count Factory-installed heat meter for the separate counting of the quantity of heat of heating and hot water 259010 259010 REMKO Smart-Com Additional software for the integration of the heat pump into a smart home system such as KNX via the Ethernet interface of Smart Con- trol, including the heat meter installed at the factory (Smart Count) 254090 254090 REMKO Smart-Serv Intelligent provision, installed heating rod 9 kW for monoenergetic operation, including emergency heating functions 259029 259027 REMKO Smart-Cool for active cooling. Pipe subassemblies and circulation pump in the indoor unit with vapour density insulation. Use in case of cooling function when the inlet temperature is below the dew point. 259086 259086 Heating circuit pump set HGU Speed-controlled heating circuit pump group (0-10 V)/unmixed 259035 259035 Heating circuit pump set HGM Speed-controlled heating circuit pump group (0-10 V)/mixed 259036 259036 S 08 optional Indoor unit Outdoor unit Hydraulic diagram for Cologne Duo (example for monoenergetic or alternative bivalent operation) Outdoorprobe Heating circuit Non-mixed Heating circuit Mixed Heating circuit Mixed Heating circuit Mixed Heating circuit MixedBoiler/wall-mounted unit Cooling circuit KPS 300 HPU HGU HGM HGM HGM HGM
  • 36. 36 Package consisting of: HEAT PUMP PACKAGES Type Mannheim Duo Heat pump package – Type Mannheim Duo for WKF 120-180 Duo unit series This heat pump package is designed for users who would like to operate the heat pump in combination with a conventional heating appliance (bivalently alternating). The additional KWS 300 com- bination buffer tank is used for the hydraulic decoupling of large volume flow rates. A cooling function for the summer can also be activated, if necessary. In this package, the drinking water preparation takes place in an enamelled 300-litre drinking water tank. Through the compact design, installation expenses are extremely low. The separate pump assemblies HGU/HGM (can be ordered sepa- rately) for the heating circuits are equipped with a high-efficiency pump (0-10 V) regulated in a needs-based manner. Information about government subsidies can be found under: www.bafa.de / www.kfw.de / www.foerderdata.de Package consisting of: ■ Indoor unit ■ Outdoor unit For scope of supply, see p. 18 ■ 2x condensate drip trays, including oil separator for outdoor unit ■ Combination buffer tank KWS 300 (see p. 49) ■ 3-way switchover valve Combination buffer tank for cooling, heating and hot water KWS 300 HeatingHot water Cooling BivalentSurface cooling/ surface heating Night operation ErP Ready Energy A++ Efficiency Rating 2 condensate drip trays for out- door unit with oil separator 3-way changeover valve, 6/4" 36
  • 37. 37 Hydraulic system diagram of Mannheim (example for monoenergetic or alternative bivalent operation) Indoor unit Outdoorprobe Outdoor unit Chilled water HGU HGMZWPHPU HGM HGM HGM KWS 300 Hot water Heating circuit Non-mixed Heating circuit Mixed Heating circuit Mixed Heating circuit Mixed Heating circuit Mixed Cooling circuit Boiler/wall-mounted heating system (max. 22 kW) Technical data Area of use: heating 1) 18-25 kW 25-32 kW Heat pump package – Type Mannheim Duo WKF 120 DUO WKF 180 DUO Rated heating capacity (min. / max.) kW 18.0 (2.5 - 25.0) 29.0 (3.1 - 35.4) Rated cooling capacity (min. / max.) kW 13.0 (3.3 - 23.8) 24.0 (11.0 - 28.0) Energy efficiency rating of HZ/Smart Control composite system A+/A A++/A Series WKF 120 DUO WKF 180 DUO Ref. no. 256102 256103 1) Total heating requirement, intake flow line 35°C, monoenergetic Accessories Series WKF 120 DUO WKF 180 DUO REMKO Smart-Count Factory-installed heat meter for the separate counting of the quantity of heat of heating and hot water 259010 259010 REMKO Smart-Com Additional software for the integration of the heat pump into a smart home system such as KNX via the Ethernet interface of Smart Con- trol, including the heat meter installed at the factory (Smart Count) 254090 254090 REMKO Smart-Serv Intelligent provision, installed heating rod 9 kW for monoenergetic operation, including emergency heating functions 259029 259027 REMKO Smart-Cool for active cooling. Pipe subassemblies and circulation pump in the indoor unit with vapour density insulation. Use in case of cooling function when the inlet temperature is below the dew point. 259086 259086 Heating circuit pump set HGU Speed-controlled heating circuit pump group (0-10 V)/unmixed 259035 259035 Heating circuit pump set HGM Speed-controlled heating circuit pump group (0-10 V)/mixed 259036 259036
  • 38. 38 Heat pump package – Type Munich Duo for WKF 120-180 Duo unit series This heat pump package is the ideal solution for users with a high heating capacity and high hot-water requirement who, in addition to the heating function, also want domestic water preparation from their heat pump system. A cooling function for the summer can also be activated, if necessary. The domestic water preparation takes place very efficiently with a 500, 800, or 1000 litre buffer tank and electronically controlled fresh water station using the hygienic flow method. With this heat pump package, both alternatively bivalent Package consisting of: Buffer tank for fresh water station Fresh water station EFS 25/ EFS 35 Type Munich Duo 2 condensate drip trays for out- door unit with oil separator and monoenergetically operated systems can be accommodated. The buffer tank is used as a hydraulic switch in case of large pres- sure losses in the heating circuit. Information about government subsidies can be found under: www. bafa.de / www.kfw.de / www.foerderdata.de Package comprising: ■ Indoor unit ■ 2 outdoor units ■ Buffer tank for cooling and heating water KPS 300 (300 litres) ■ Buffer tank for domestic water HPS 500, MPS 800, or MPS 1000 ■ Electrically regulated fresh water station EFS 25/EFS 35 ■ 3-way changeover valve ■ 2 condensate drip trays, including oil separator for outdoor unit 3-way changeover valve, 6/4" Heating Active cooling Surface cooling/ surface heating HEAT PUMP PACKAGES Buffer tank for cooling and hot water Night operation ErP Ready Energy A++ Efficiency Rating Hot water
  • 39. 39 Technical data Area of use: heating 1) 18-25 kW 25-32 kW Heat pump package – Type Munich Duo WKF 120 DUO WKF 180 DUO Rated heating capacity (min. / max.) kW 18.0 (2.5 - 25.0) 29.0 (3.1 - 35.4) Rated cooling capacity (min. / max.) kW 13.0 (3.3 - 23.8) 24.0 (11.0 - 28.0) Energy efficiency rating of HZ/WW/Smart Control composite system A+/A A++/A Series WKF 120 DUO WKF 180 DUO with HPS 500 and EFS 25 Ref. no. 256105 256110 with MPS 800 and EFS 35 Ref. no. 256106 256111 with MPS 1000 and EFS 35 Ref. no. 256107 256112 1) Total heating requirement, intake flow line 35°C, monoenergetic Accessories Series WKF 120 DUO WKF 180 DUO REMKO Smart-Count – Factory-installed heat meter for the separate counting of the quantity of heat of heating and hot water 259010 259010 REMKO Smart-Com Additional software for the integration of the heat pump into a smart home system such as KNX via the Ethernet interface of Smart Control, including the heat meter installed at the factory (Smart Count) 254090 254090 REMKO Smart-Serv Intelligent provision, installed heating rod 9 kW for monoenergetic operation, including emergency heating functions 259029 259027 REMKO Smart-Cool for active cooling. Pipe subassemblies and circulation pump in the indoor unit with vapour density insulation. Use in case of cooling function when the inlet temperature is below the dew point. 259086 259086 Heating circuit pump set HGU Speed-controlled heating circuit pump group (0-10 V)/unmixed 259035 259035 Heating circuit pump set HGM Speed-controlled heating circuit pump group (0-10 V)/mixed 259036 259036 Indoor unit Outdoor unit Hydraulic system of Munich Duo (example for monoenergetic or alternative bivalent operation) Outdoorprobe Heating circuit Non-mixed Heating circuit Mixed Heating circuit Mixed Heating circuit Mixed Heating circuit Mixed EFS 25 RES ZWP HPS500, MPS800/1000 Boiler/wall-mounted unit Cooling circuit HGU HGM HGM HGM HGM Hot waterCold water KPS 300
  • 40. 40 Heat pump package – Type Frankfurt Duo / Frankfurt Duo Solar for WKF 120-180 Duo unit series The energy-saving package is prepared for the integration of solar thermal plants or combustible solid fuel burner for heating and domestic water support. The hot water control and heating function are supported by the RWT31 fin-tube heat exchanger and four solar collectors included in the solar package. The domestic water preparation takes place with a 800 litre or 1000 litre buffer tank and electronically regulated fresh water station using the hygienic flow method. Package consisting of: Multifunctional buffer tank MPS 800 or MPS 1000 Fresh water station EFS 25 2 x 3-way changeover valve, 6/4" Type Frankfurt Duo / Frankfurt Duo Solar 2 condensate drip trays for out- door unit with oil separator Solar set RSK 25-10 only available in Solar package With this heat pump package, both alternatively bivalent and mono- energetically operated systems can be accommodated. The separate pump assemblies HGM (can be ordered separately) for the heating circuits are equipped with a high-efficiency pump (0-10 V) regulated in a needs-based manner. The solar set included in this package, Type RSK 25-10, with a collector surface of 10.12 m² , is ideal for effective domestic water preparation and heating support. Package comprising: ■ Indoor unit ■ 2 outdoor units ■ Multifunctional buffer tank MPS 800 or MPS 1000 ■ Electrically regulated fresh water station EFS 25 ■ Two 3-directional switching valves ■ Immersion probe and collector sensor ■ 2 condensate drip trays, including oil separator for outdoor unit Additional scope of supply for the Solar package ■ Solar set RSK 25-10 (only available in Solar package) HEAT PUMP PACKAGES Hot water BivalentPanel heatingHeating Solar connection Night operation ErP Ready Energy A++ Efficiency Rating Immersion probe and collector probe
  • 41. 41 Technical data Area of use: heating 1) 18-25 kW 25-32 kW Heat pump package - Type Frankfurt Duo / Frankfurt Duo Solar WKF 120 DUO WKF 180 DUO Rated heating capacity (min. / max.) kW 18.0 (2.5 - 25.0) 29.0 (3.1 - 35.4) Rated cooling capacity (min. / max.) kW 13.0 (3.3 - 23.8) 24.0 (11.0 - 28.0) Energy efficiency rating for Frankfurt HZ/WW composite system A+/A A++/A Energy efficiency rating for Frankfurt Solar HZ/WW/Solar/Smart Control composite system A++/A+ A++/A+ Series WKF 120 DUO WKF 180 DUO with MPS 800 and EFS 25 Ref. no. 256115 256120 with MPS 800, EFS 25, and solar set RSK 25-10 Ref. no. 256116 256121 with MPS 1000 and EFS 25 Ref. no. 256117 256122 with MPS 1000, EFS 25, and solar set RSK 25-10 Ref. no. 256118 256123 1) Total heating requirement, intake flow line 35°C, monoenergetic Accessories Series WKF 120 DUO WKF 180 DUO REMKO Smart-Count Factory-installed heat meter for the separate counting of the quantity of heat of heating and hot water 259010 259010 REMKO Smart-Com Additional software for the integration of the heat pump into a smart home system such as KNX via the Ethernet interface of Smart Control, including the heat meter installed at the factory (Smart Count) 254090 254090 REMKO Smart-Serv Intelligent provision, installed heating rod 9 kW for monoenergetic opera- tion, including emergency heating functions 259029 259027 Heating circuit pump set HGU Speed-controlled heating circuit pump group (0-10 V)/unmixed 259035 259035 Heating circuit pump set HGM Speed-controlled heating circuit pump group (0-10 V)/mixed 259036 259036 Hydraulic system of Frankfurt Duo / Frankfurt Duo Solar (example for monoenergetic or alternative bivalent operation) Indoor unit Outdoor unit Outdoorprobe Heating circuit Non-mixed Heating circuit Mixed Heating circuit Mixed Heating circuit Mixed Heating circuit Mixed EFS 25 RES ZWPSKPHPU MPS 800/1000 Boiler/ wall-mounted heating system Chilled water HGU HGM HGM HGM HGM Hot waterSolar
  • 42. 42 Technical data Series RSK 25 Domestic water heating/heating support Yes Rooftop installation Yes Flat roof installation Yes Awning/façade installation no Installation type vertical, side-by-side horizontal, stacked (on request) Piping meandering Absorber coating highly selective Max. number of collectors in series 4 Rated thermal capacity kW 1.9 Efficiency % 79.7 Total collector surface area m² 2.53 Absorber surface area m² 2.35 Aperture surface area m² 2.35 Heat carrier content l 1.7 Permissible operating pressure bar 10 Max. corrugated pipe length m 25 Dimensions - height/width/depth mm 2102/1202/80 Weight kg 44 HEAT PUMP SOLAR PACKAGES Solar collector RSK 25 Solar collector RSK 25 With the thermal high-performance solar collectors Type RSK 25, you can operate your heating system with even greater efficiency in combination with the inverter heat pump from REMKO. With the refined workmanship and specially developed heat conducting technology, a maximum amount of solar energy is utilised. The RSK 25-5 solar set with two solar collectors utilises solar energy for hot-water preparation. The RSK 25-10 solar set with four solar collectors utilises solar energy for hot-water prepara- tion and heating support. The REMKO solar sets provide unsurpassed performance in a perfectly attuned system configuration with the well-known inverter heat pump. Cross-section of solar collector RSK 25 Depending on the solar set, the heat pump can be used for air con- ditioning during the summer, whereas the thermal solar system as- sumes the hot water preparation. The complete system is controlled via the REMKO Smart-Control intelligent control system. Almost every desire can be fulfilled by the REMKO heat pump solar packages. Highly selective absorber layer 4mm glass Absorber sheet, aluminium Absorber tube Mineral wool Bronze-coloured, anodised aluminium frame Assembly system 1 1 2 3 4 5 6 7 2 3 4 5 6 7 KEYMARK DIN-tested REMKO 011-7S1695 F 42
  • 43. 43 Solar set RSK 25-5 The solar set consisting of two solar collectors type RSK 25 is an efficient supplement to hot-water preparation. Solar set RSK 25-10 The solar set consisting of four solar collectors type RSK 25 is an efficient supplement to hot-water prepara- tion and heating support. Solar station Basic mounting set Diaphragm expansion vessel Fin-tube heat exchanger Glycol, premixed Immersion probe and collector sensor Solar set consisting of: ■ 2x collectors type REMKO RSK 25 (5.06 m²) ■ Straight collector connector ■ Solar station with HE pump ■ MAG 18, expansion vessel ■ Wall mount for MAG ■ Connecting tube for MAG Solar set consisting of: ■ 4x collectors type REMKO RSK 25 (10.12 m²) ■ Straight collector connector ■ Solar station with HE pump ■ MAG 25, expansion vessel ■ Wall mount for MAG ■ Connecting tube for MAG Accessories included in the solar set: (Additional accessories, such as a rooftop anchor, can be found on page 53.) ■ Premixed glycol, 20 l ■ Basic mounting set ■ Expanded mounting set ■ Fin-tube heat exchanger RWT 31 ■ Immersion probe and col- lector sensor ■ Premixed glycol, 10 l ■ Basic mounting set ■ Fin-tube heat exchang- er RWT 18 ■ Immersion probe and collector sensor
  • 44. 44 Heat pump package type Stuttgart Solar for WKF 70-180 appliance series If the heat pump is intended to serve as a sole heat generator, this heat pump package is the ideal solution. In addition to the heating function, a cooling function can be provided when necessary. In this package, the drinking water preparation takes place in an enamelled, 300-litre drinking water tank integrated into the indoor module. In addition, a cooling function can be provided as necessary while the thermal solar system heats the domestic water. Through the compact design, installation expenses are extremely low. The solar set included in this pack- age, type RSK 25-5, with a collector surface of 5.06 m², is ideal for effective domestic water preparation. Package consisting of: Type: Stuttgart Solar HEAT PUMP SOLAR PACKAGES Condensate drip tray for out- door unit with oil separator Solar set RSK 25-5 Package comprising: ■ Indoor unit with inte- grated 300-litre domestic water tank (BEVB 1.19 kWh/day) ■ Outdoor unit For scope of supply, see p. 14 ■ Solar set RSK 25-5 ■ Condensate drip tray, including oil separator for outdoor unit Hot water HeatingNight operation Solar connection Surface cooling/ surface heating Cooling ErP Ready Energy A++ Efficiency Rating 44
  • 45. 45 Technical data Area of use: heating 1) 4-7 kW 8-11 kW 12-18 kW Heat pump package, Type Stuttgart Solar WKF 70 compact WKF 120 compact WKF 180 compact Rated heating capacity (min. / max.) kW 6.0 (0.9 - 6.0) 10.0 (2.5 - 12.5) 14.0 (3.1 - 17.7) Rated cooling capacity (min. / max.) kW 5.0 (1.1 - 8.9) 6.0 (3.3 - 11.9) 11.0 (5.5 - 14.0) Energy efficiency rating for HZ/WW/Solar/Smart Control composite system A++/A+ A++/A+ A++/A+ External maximum pressure loss kPa 80 80 80 Series WKF 70 compact WKF 120 compact WKF 180 compact Ref. no. 254170 256230 256235 1) Total heating requirement, intake flow line 35°C, monoenergetic Accessories Series WKF 70 compact WKF 120 compact WKF 180 compact REMKO Smart-Count Factory-installed heat meter for the separate counting of the quantity of heat of heating and hot water 259010 259010 259010 REMKO Smart-Com Additional software for the integration of the heat pump into a smart home system such as KNX via the Ethernet interface of Smart Control, including the heat meter installed at the factory (Smart Count) 254090 254090 254090 REMKO Smart-Serv Intelligent provision, installed heating rod 9 kW for monoenergetic operation, including emergency heating functions 259021 259022 259023 REMKO Smart-Cool for active cooling. Pipe subassemblies and circulation pump in the indoor unit with vapour density insulation. Use in case of cooling function when the inlet temperature is below the dew point. 259085 259085 259085 For additional accessories, see page 50 Indoor unit Outdoor unit Hydraulic system of Stuttgart Solar (example for monoenergetic operation) Outdoorprobe Heating circuit MixedCooling circuitSolar Hot water Chilled water ZWPSKP
  • 46. 46 Package consisting of: 2 x 3-way changeover valve, 5/4" Solar set RSK 25-10 HEAT PUMP SOLAR PACKAGES Type Frankfurt Solar Heat pump package – Type Frankfurt Solar for WKF 70-180 appliance series The energy-savings package is prepared for the integration of the solar-thermal system REMKO RSK 25-10 to the fin-tube heat exchanger RWT 31. The domestic water preparation takes place with a 800 litre or 1000 litre multifunction buffer tank and fresh water station using the hygienic flow method. With this heat pump package, both bivalent and single energy source systems can be accommodated. The solar set included in this package, type RSK 25-10, with a collector surface of 10.12 m² provides household water and heating support. The separate pump assemblies HGM (can be ordered sepa- rately) for the heating circuits are equipped with a high-efficiency pump (0-10 V) regulated in a needs-based manner. Information about government subsidies can be found under: www.bafa.de / www.kfw.de www.foerderdata.de Condensate drip tray for outdoor unit with oil separator Package comprising: ■ Indoor unit ■ Outdoor unit For scope of supply, see p. 16 ■ Solar set RSK 25-10 ■ Multifunctional buffer tank MPS 800 (800 litres) or MPS 1000 (1000 litres) ■ Electrically regulated fresh water station EFS 25 (for connection sets, see p. 52) ■ 2 x 3-way switchover valve ■ Condensate drip tray, including oil separator for outdoor unit Multifunction buffer tank MPS 800 (800 litres) or MPS 1000 (1000 litres) Fresh water station EFS 25, com- plete with pump and flow switch For connection sets, see p.52 Hot water Solar connection BivalentSurface heatingHeatingNight operation ErP Ready Energy A++ Efficiency Rating 46
  • 47. 47 Technical data Area of use: heating 1) 4-7 kW 8-11 kW 12-18 kW Heat pump package, Type Frankfurt Solar WKF 70 WKF 120 WKF 180 Rated heating capacity (min. / max.) kW 6.0 (0.9 - 6.0) 10.0 (2.5 - 12.5) 14.0 (3.1 - 17.7) Rated cooling capacity (min. / max.) kW 5.0 (1.1 - 8.9) 6.0 (3.3 - 11.9) 11.0 (5.5 - 14.0) Energy efficiency rating for HZ/WW/Solar/Smart Control composite system A++/A+ A++/A+ A++/A+ External maximum pressure loss kPa 80 80 80 Series WKF 70 WKF 120 WKF 180 with MPS 800 Ref. no. 254180 256215 256220 with MPS 1000 Ref. no. 254190 256216 256221 1) Total heating requirement, intake flow line 35°C, monoenergetic Accessories Series WKF 70 WKF 120 WKF 180 REMKO Smart-Count Factory-installed heat meter for the separate counting of the quantity of heat of heating and hot water 259010 259010 259010 REMKO Smart-Com – Additional software for the integration of the heat pump into a smart home system such as KNX via the Ethernet interface of Smart Control, including the heat meter installed at the factory (Smart Count) 254090 254090 254090 REMKO Smart-BVT, factory-installed BVT pipe assembly, 3-way switchover valve for the integration of a second heat generator (max. 22 kW), without a circulation pump, bivalently alternating operation Note: No combination with REMKO Smart-Serv possible. Only in combination with buffer tank. 254050 259015 259016 REMKO Smart-Serv – Intelligent provision, installed heating rod 9 kW for monoenergetic operation, including emergency heating functions Note: No combination with REMKO BVT possible. 254060 259025 259026 Heating circuit pump set HGM Speed-controlled heating circuit pump group (0-10 V)/mixed 259036 259036 259036 For additional accessories, see page 50 ZWP M Indoor unit Outdoor unit Hydraulic system of Frankfurt Solar (example for monoenergetic or bivalently alternating operation) Outdoorprobe Heating circuit Non-mixed Heating circuit Mixed Heating circuit MixedHot waterSolar Chilled water EFS 25 ZWPSKP MPS 800/1000 Boiler/wall-mounted heat- ing system (max. 22 kW) HGU HGM HGM RES
  • 48. 48 Unit type HPS 500 MPS 800 MPS 1000 Storage type Buffer tank Stratified storage Tank volume Litre 500 800 1000 BEVB kW/24h 2.8 3.4 3.5 Heat retention loss W 116 141 145 Energy efficiency class C - - Height with insulation mm 1725 1785 2135 Diameter with insulation mm 850 990 990 Diameter without insulation mm 650 790 790 Tilt height without insulation mm 1670 1750 2090 Weight kg 113 157 176 Ref. no. 270300 270380 270400 Unit type KPS 130 KPS 300 Storage type Hot/cold water buffer tank Tank volume Litre 130 300 BEVB kW/24h 1.2 2.2 Heat retention loss W 50 91 Energy efficiency class B C Height with insulation mm 742 1690 Diameter mm 680 600 Tilt height without insulation mm 800 1740 Weight kg 39 118 Ref. no. 270240 270250 TANK SYSTEMS Buffer tanks for heating water ■ Universally usable as parallel buffer (hydraulic switch) or series-connected buffer ■ With dummy flange cover D240 for retrofitting a fin- tube heat exchanger RWT 31 ■ Electrical immersion heating element, screw-in 6/4" ■ Max. operating temperature 95°C ■ Max. operating pressure 3 bar Hot/cold water buffer tank ■ Universally usable as parallel buffer (hydraulic switch) or series- connected buffer ■ With cleaning flange lid D180 for retrofitting ■ Fin-tube heat exchanger RWT 18, can be retrofitted ■ Electrical immersion heating element, screw-in 6/4" ■ Operating temperature: min. 0°C, max. 95°C ■ Max. operating pressure 3 bar ■ Steel sheet inner boiler S235 according to DIN EN 10 025/10 111 ■ Test pressure 4.5 bar ■ External anti-rust coating ■ 9 connecting threads (11 for MPS800/MPS1000) 6/4" IG with inflow restrictors ■ 4 socket screw threads 1/2" for sensor/thermometer im- mersion sleeves ■ From quality steel S235 according to DIN EN 10 025/10 111 ■ High-efficiency, double-shell heat insulation, 100 mm, silver grey ■ 4 connecting threads AG 5/4" ■ Powder-coated steel sheet outer casing in silver-grey ■ Outer casing reinforced by beading ■ High-quality PUR insulation 50 mm (CFC, HCFC and HFC-free), water vapour diffusion tight ■ Sensor conduct for variable sensor positioning
  • 49. 49 UP TO 45% ENERGY SAV- INGS DUE TO IMPROVED PU FOAM INSULATION Unit type EWS 300 E EWS 500 E KWS 300 Storage type Domestic water tank, enamelled Combination buffer tank Net domestic water volume Litre 269 426 275 Volume of buffer tank (steam-diffusion-proof) – – 100 Heat exchanger surface m2 3.5 6.2 3.2 BEVB kW/24h 1.23 1.88 1.77 Heat retention loss W 51 78 74 Energy efficiency class B B B Tap profile XL 3 XL XXL Height/width/depth mm 1435 1921 1760 Diameter mm 740 750 750 Tilt height mm 1595 2023 1879 Weight kg 173 222 190 Ref. no. 270600 270800 270700 ■ Max. operating pressure 10 bar ■ Max. operating temperature 95°C ■ Connection possibilities for circulation 3/4" AG ■ Enamelled with double- coiled smooth-tube heat exchanger and particularly large heat exchanger surface Buffer tank for domestic hot water heating ■ Inner container with magnesium protection anodes according to DIN 4753 ■ PUR insulation (CFC, HCFC, and HFC-free) ACCESSORIES – TANK TECHNOLOGY Tank systems Electrical auxiliary heater 6 kW for KPS/MPS/HPS buffer tank Electrical auxiliary heater 6/4" for installa- tion in a buffer tank. Including temperature regulator and safety temperature limiter. 2, 4 or 6 kW can be optionally connected. Note: Not suited for domestic water tank. Ref. no. 260063 Built-in flange heating for EWS 300/500 E and KWS 300 Consisting of a high-quality tubular heating element on which an insulated flange plate is fitted. A protective earthing resistor, ther- mal sensor and safety temperature limiter. Max. operating pressure 10 bar. Heating capacity 6 kW. Note: Not suited for buffer tanks of the HPS/MPS/KPS series. Ref. no. 260160 ■ Cold water supply and hot water outlet 1" IG ■ With cleaning flange lid D180 ■ Built-in flange heating (legionella protection) or fin- tube heat exchanger RWT 18 can be retrofitted Fin-tube heat exchanger For additional indirect heating, e.g. with a solar thermal system Unit type RWT 18 RWT 31 Suitable for buffer tanks Type EWS 300 E EWS 500 E KPS 300 KWS 300 HPS 500 MPS 800 MPS 1000 Heat exchanger area m² 1.40 3.10 Installation length in mm 440 530 Connection G Inch 3/4 1 Contents l 1.50 2.50 Flange Ø 180 / 8-hole 240 / 12-hole Ref. no. 260200 260210
  • 50. 50 ACCESSORIES – HEAT PUMPS REMKO Smart-Web Ethernet interface for the connection of commercial home router software. For dial- ling in to Smart-Control. Setting and reading operating parameters using a smartphone, tablet PC, laptop, etc. Ref. no. 248120 REMKO Smart-Control remote control With the cabled remote control, all functions of the heat pump and heating circuits can be set. A room temperature controlled regulation of the heating circuits (FBH or heaters) can be realised. In addition, dew point regulation is possible using the integrated humidity probe. Ref. no. 248105 REMKO Smart-Com Additional software for the integration of the heat pump into a Smart Home system such as KNX via the Ethernet interface of Smart Control, including the heat meter installed at the factory (Smart Count) Ref. no. 254090 Floor bracket Robust floor bracket made of reinforced of rubber with high intrinsic weight and good damping properties. For heat pump outdoor unit series WKF. Length 0.6m and/or 1m WKF 70-180, WKF 120-180 Duo (2x) BK-600 Plus Ref. no. 260023 BK-1000 Plus Ref. no. 260024 Connecting line between outdoor and indoor unit WKF 70-180, WKF 120-180 Duo 3 8 5 8 " Ø Ref. no. 260010 Electrical condensation drainage - heating Electrical condensate drainage heat- ing, temperature-regulated for the safe discharge of defrost water with outside temperatures below the freezing point. Ref. no. 260045 Condensate drip tray including oil separator Condensate drip tray made of aluminium for each outdoor unit, including temperature- controlled electronic condensate drip tray heating, leaf guard grating, and oil separator. According to § 62, Abs.1, WHG (Wasser- haushaltsgesetz (German Water Resources Act). Ref. no. 260135 Dual-direction power meter Current meter for Smart Heating/Cooling function, PV integration. 400V/3~/50Hz with S0 interface Ref. no. 259065 Wall brackets For mounting to suitable faces and ma- sonry, including vibration dampers For device type Type Ref. no. WKF 70-180 WKM-600 260079 WKF120-180 Duo (2x) WKM-600 260079 Noise decoupling set 1613900
  • 51. 51 Overflow protection valve Overflow protection valve 1" for ensur- ing that the minimum medium flow rate is maintained. Ref. no. 260080 BVT set, loose For the external integration of a 2 WE with a larger heating capacity. Consisting of: 3-way valve 5/4", overflow valve 1" For unit type Ref. no. WKF 70,120,180 WKF 120,180 Duo 260081 Pulse generator, circulation Pulse generator for the realisation of a pulse-controlled circulation pump via REMKO Smart-Control. Ref. no. 259045 3-way changeover valve Electrical switching valve / 3-way valve for domestic water preparation and separate cooling circuit (four-pipe system). Ref. no. 260072 Ref. no. 259055 REMKO tank connection set Pipe subassembly including an electrical actuator to connect the inlet flow line of an external hot water tank Ref. no. 259080 Pipe bushing for WKF series Robust EPDM seal for watertight sealing of the refrigerant and electrical lines. Ø 100 mm Ref. no. 259061 Immersion probe Immersion probe Pt 1000 for integrating - Solar reference probe for buffer tank - Domestic water tank EWS 300 - General buffer probe Ref. no. 259062 Collector sensor Immersion probe Pt 1000 for the integra- tion of solar thermal systems Ref. no. 260102 Contact probe Contact probe Pt1000 for the integrating - A temperature-guided circulation pump via Smart Control - A heating circuit with mixer (2 pieces required) Ref. no. 259060 Flow sensor for dynamic hygiene function Flow sensor with frequency output for recording the cold water volume flow rate in the domestic water tank. Regulation accord- ing to DIN 1988-200 Ref. no. Tap volume ≤ 25l/min 254070 Tap volume ≥ 25l/min 254080 External dew point monitor incl. 1 contact probe Dew point monitoring is installed for ad- ditional security to prevent the occurrence of humidity. The humidity is checked directly on the corresponding surfaces. It is possible to connect up to 5 measuring probes. Ref. no. Ext. dew point monitor 259070 Additional contact probe 259071 Sludge separator For the filtration of contamination and corrosion products from the heating water, glycol-resistant and insulated Ref. no. 1 to 2.1 m3 /h 260803 1½ to 5.4 m3 /h 260804 Full heating protection Corrosion protection and hardness stabilisation for conventional hot water heating systems Ref. no. Without anti-freeze 1 l 260819 With anti-freeze 10 l 260823 With anti-freeze 20 l 260807 With anti-freeze 200 l 260808 With anti-freeze 1000 l 260809 Heating circuit pump set HGU Consisting of: a speed-controlled (0-10 V) heating circuit pump without mixer, ball valves with thermometer Ref. no. 259035 Heating circuit pump set HGM Consisting of: a speed-controlled (0-10 V) heating circuit pump with a mixer, ball valves with thermometer, 2x Pt 1000 contact probes Ref. no. 259036
  • 52. 52 FRESH WATER SYSTEMS Tank connection set for buffer tanks For the direct connection of the fresh water station EFS 25 to the buffer tank. Note: Not suited for EFS 35/50 For buffer tank Ref. no. HPS 500 259040 MPS 800 259041 MPS 1000 259042 Return flow layering set RES for EFS 25 for connection to the buffer tank RES including tank connection pipes and 3-way switchover valve for temperature- dependent layering in the buffer tank. Note: Not suited for EFS 35/50 For buffer tank Ref. no. MPS 800 259031 MPS 1000 259032 Accessories Technical data Fresh water station EFS 25 EFS 35 EFS 50 Transmission power kW 30 1) 79 2) 122 Installation site Tank/wall Wall Wall Heat pump type WKF 70, 120, 180, 120-180 DUO 180, 120-180 DUO 120 DUO 180 DUO Min. buffer volume for hot water operation L 500 800 1000 Primary connections IG Inch 3/4 1 1/2 2 Secondary connections AG, flat-sealing Inch 3/4 1 1 ¼ Dimensions - height/width/depth mm 645/348/249 795/602/298 795/602/298 Tap volume at 45°C tap temp. and 50°C tank temp. l/min 17 32 50 Tap volume at 45°C tap temp. and 60 °C tank temp. l/min 28 50 77 Tap volume at 45°C tap temp. and 70 °C tank temp. l/min 36 64 88 Series EFS 25 EFS 35 EFS 50 Ref. no. 260155 260156 260157 1) Tapping output at 50°C buffer temperature / 12 l/min / 10°C chilled water supply line 2) Tapping output at 50°C buffer temperature / 32 l/min / 10°C chilled water supply line Accessories Other accessories EFS 25 EFS 35 EFS 50 Circulation pump EFS 25 Controllable high-efficiency circulation pump including pipe subassembly for direct connection to EFS 25. 259052 – – Circulation pump EFS 35/EFS 50 Speed-controlled high-efficiency circulation pump for installation directly to the fresh water station – 259053 259053 Single-layer return valve for temperature-dependent layer in the buffer tank 260072 260072 260072 Electronically controlled fresh water stations EFS series The fresh water stations of REMKO are used for hygienic domestic water preparation in con- nection with buffer tanks. The devices are completely equipped with electronic control, speed- controlled high-efficiency pump, flow switch, and plate heat exchanger. The heat exchanger is designed for a high flow rate of 25 l/min (EFS25), 35 l/min (EFS35) or 50 l/min (EFS50). The flow rate can be increased through cascading. The fresh water stations are delivered ready for mounting in the EPP housing. In the case of the EFS 35/50, the unit is mounted to the wall. The EFS 25 fresh water station permits mounting directly on the tank or wall.
  • 53. 53 ACCESSORIES – SOLAR COLLECTORS 3-way changeover valve Solar, 1 Electrical changeover valve/3-way valve 1 for thermal solar plants (included in the heat pump solar package) Ref. no. 260800 Collector connector, straight For the connection of the solar collectors RSK 25 (included in the REMKO solar set) Ref. no. 260810 Glycol Heat transfer medium with corrosion protection for solar plants (included in the REMKO solar set) Ref. no. 260805 10 L Ref. no. 260806 20 L Installation coupling for the collector line For the connection of the corrugated solar pipe to the RSK 25 solar collectors (included in the corrugated pipe mounting set) Ref. no. 260865 Flat roof installation set for solar collectors RSK 25-5, consisting of: 3x flat roof brack- ets, 1x safety support Ref. no. 260842 RSK 25-10, consisting of: 5x flat roof brackets, 1x safety support Ref. no. 260843 Insulated, corrugated pipe for solar collectors for RSK 25-5 and RSK 25-10, including sensor cable Design Ref. no. 10 m roll, incl. installation set 260900 15 m roll, incl. installation set 260901 25 m roll, incl. installation set 260902 Corrugated pipe, m (max. 25 m) 260869 Installation set, separate 260870 Complete rooftop anchor set for solar collectors For solar package For tile type Ref. no. RSK 25-5 Frankfurter tile 260850 RSK 25-10 Frankfurter tile 260855 RSK 25-5 Crown tile 260851 RSK 25-10 Crown tile 260856 RSK 25-5 Slate 260852 RSK 25-10 Slate 260857 RSK 25-5 Rafter-independent 260853 RSK 25-10 Rafter-independent 260858 Slate tileCrown tileFrankfurter tile
  • 54. 54 Valve assembly for 2-pipe system, VB 3-way valve assembly for controlling the medium flow rate during cooling or heating mode. For unit types Ref. no. KWK 100-400-4R Wall installation 1661115 KWK 100-400 4R horiz. Ceiling installation 1661117 Condensate pump For unit type Condensate pump Ref. no. KWK KP-8 1613125 Feet SF-3 For unit types Ref. no. KWK 100-400-4R 1662125 Air inlet socket LS-1, with air inlet grid for the optical disguising of the air inlet area. For unit types Ref. no. KWK 100-4R 1662130 KWK 150-4R 1662131 KWK 250-4R 1662132 KWK 400-4R 1662133 ACCESSORIES – WALL AND CEILING CHESTS Precision room temperature controller RR-21 for the operation and control of an indoor unit. Programmable, electronic controller with various functions such as summer/winter mode changeover, 4 fan speeds, regulation of the medium flow rate with standard valve heads. Group control with switch relay possible. For unit types Ref. no. KWK 100-400-4R 1611396 Accessories Room temperature sensor 1611380-1 Inlet temperature probe 1611381-1 Room temperature controller RR-14 indoor unit installation for the opera- tion and control of an indoor unit. Mechanical controller with basic func- tions, such as summer/winter programme switching, 3 fan speeds. For unit types Ref. no. KWK 100-400-4R 1662101
  • 55. 55 THE NEW ONLINE HEAT PUMP CONFIGURATOR The planning of REMKO heat pumps made easy Test it... http://wp-konfigurator.remko.de The heat pump configurator, a simple and free tool for generating an individual heat pump for your house quickly and easily, is available on www.REMKO.de. In addition to the appropriate heat pump, the configurator also shows the hydraulic diagram, the accessory parts required for installa- tion, the bivalence point, and the right Energy Label of the heat pump system. Plan your personal heat pump system today – with the new heat pump generator of REMKO!
  • 56. REMKO INTERNATIONAL ...and somewhere near you! Take advantage of our experience and advice REMKO dealers Hotline Within Germany +49 (0)5232-606-0 International +49(0)5232-606-130 REMKO GmbH Co. KG Klima- und Wärmetechnik Im Seelenkamp 12 · 32791 Lage PO Box 1827 · 32777 Lage Telephone +49-5232-606-0 Fax +49-5232-606-260 E-mail info@remko.de URL www.remko.de MS/BD/20/11.16  Wereservetherighttotechnicalmodifications. Informationprovidedwithoutguarantee!